Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:03
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Simulation Timestamp: 2020-06-03 20:04:07
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 31934.17 | 689.42 | 689.42 |
Net Site Energy | 31934.17 | 689.42 | 689.42 |
Total Source Energy | 100038.97 | 2159.72 | 2159.72 |
Net Source Energy | 100038.97 | 2159.72 | 2159.72 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 81.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 5183.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3307.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 654.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1987.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2165.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 851.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1971.99 | 0.00 | 0.00 | 0.00 | 0.00 | 12319.98 |
Humidification | 4.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
Heat Recovery | 66.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 445.35 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 31407.74 | 526.43 | 0.00 | 0.00 | 0.00 | 14602.00 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 81.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2357.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2826.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 3307.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 654.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2165.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 851.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 557.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 1414.22 | 0.00 | 0.00 | 0.00 | 0.00 | 12319.98 | |
Humidification | General | 4.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1.85 |
Heat Recovery | General | 66.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 445.35 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 219.73 | 11.36 | 0.00 | 0.00 | 0.00 | 0.32 |
Other | 372.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 678.05 | 11.36 | 0.00 | 0.00 | 0.00 | 0.32 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 219.73 | 11.36 | 0.00 | 0.00 | 0.00 | 0.32 |
Other | 372.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 678.05 | 11.36 | 0.00 | 0.00 | 0.00 | 0.32 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 31407.741 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 31407.741 | 100.00 |
Total On-Site and Utility Electric Sources | 31407.741 | 100.00 |
Total Electricity End Uses | 31407.741 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 3963.75 | 95.53 |
Air to Air Heat Recovery for Heating | 185.69 | 4.47 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 4149.44 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 14602.00 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 14602.00 | 100.00 |
Total Water End Uses | 14602.00 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.33 |
Time Setpoint Not Met During Occupied Cooling | 186.50 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2235.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:03 |
RunPeriod | RUNPERIOD 1 |
Weather File | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Latitude [deg] | 27.85 |
Longitude [deg] | -82.5 |
Elevation [m] | 8.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.9438 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.9438 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.9438 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.9438 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 03-AUG-15:00 | 20-DEC-07:10 | - | - | - | 30-AUG-15:00 |
Heating | 0.00 | 752355.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 446058.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 283563.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 91242.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 135633.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 56002.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 93657.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1905774.96 | 758051.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 752355.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 261202.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 283563.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5423.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 135633.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 56002.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 44408.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 87.89 | 0.00 | 0.00 | 0.00 |
Cooling | 16416.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10476.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2072.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6295.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6858.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 2697.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 6245.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 15.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 209.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 482.76 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 99468.32 | 570.65 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.90 | 0.00 | 0.00 | 0.00 |
Cooling | 354.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 226.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 58.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.42 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2147.40 | 12.32 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.90 | 0.00 | 0.00 | 0.00 |
Cooling | 354.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 226.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 148.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 58.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 134.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 4.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 10.42 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2147.40 | 12.32 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.53 |
DATACENTER BOT DIRECT AIR | 0.460173 |
DATACENTER MID DIRECT AIR | 4.37 |
DATACENTER TOP DIRECT AIR | 0.438840 |
DATACENTER BASEMENT DIRECT AIR | 21.23 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.63 | 0.337927 | 0.334000 | 1.88 | 0.901139 | 0.500000 | 0.001127 | 0.000418 | 1.88 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.66 | 0.361196 | 0.348000 | 18.33 | 0.963189 | 0.500000 | 0.001055 | 0.007520 | 18.33 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.22 | 0.364098 | 0.355000 | 1.85 | 0.970928 | 0.500000 | 0.001046 | 0.001259 | 1.85 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.837091 | 0.285298 | 0.300000 | 0.251127 | 0.760795 | 0.500000 | 0.001335 | 0.000082 | 0.251127 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.882171 | 0.174462 | 0.300000 | 0.264651 | 0.465231 | 0.500000 | 0.002184 | 0.000085 | 0.264651 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.940005 | 0.254069 | 0.300000 | 0.282002 | 0.677516 | 0.500000 | 0.001500 | 0.000131 | 0.282002 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.13 | 0.136393 | 0.300000 | 0.338518 | 0.363715 | 0.500000 | 0.002793 | 0.000075 | 0.338518 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.48 | 0.319124 | 0.307000 | 2.30 | 0.850997 | 0.500000 | 0.001194 | 0.002668 | 3.60 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 8.89 | 0.173113 | 0.300000 | 2.67 | 0.461636 | 0.500000 | 0.002201 | 0.001852 | 2.67 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 8.52 | 0.280256 | 0.300000 | 2.56 | 0.747350 | 0.500000 | 0.001359 | 0.002675 | 3.61 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 9.26 | 0.166267 | 0.300000 | 2.78 | 0.443378 | 0.500000 | 0.002292 | 0.001703 | 2.78 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.859755 | 0.277777 | 0.300000 | 0.257927 | 0.740740 | 0.500000 | 0.001372 | 0.000364 | 0.491211 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.897037 | 0.171571 | 0.300000 | 0.269111 | 0.457521 | 0.500000 | 0.002221 | 0.000241 | 0.325756 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.951771 | 0.250928 | 0.300000 | 0.285531 | 0.669141 | 0.500000 | 0.001518 | 0.000364 | 0.491168 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.993850 | 0.154857 | 0.300000 | 0.298155 | 0.412953 | 0.500000 | 0.002460 | 0.000221 | 0.298685 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18913.02 | 0.000418 | 329.19 |
CORE_MID VAV BOX REHEAT COIL | 340363.45 | 0.007520 | 6332.58 |
CORE_TOP VAV BOX REHEAT COIL | 56998.75 | 0.001259 | 1160.64 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3707.99 | 0.000082 | 67.44 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3829.21 | 0.000085 | 69.53 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5943.23 | 0.000131 | 112.40 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3405.14 | 0.000075 | 59.27 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 120762.50 | 0.002668 | 2520.45 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 83807.82 | 0.001852 | 1716.60 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 121061.75 | 0.002675 | 2526.69 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 77097.48 | 0.001703 | 1532.07 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 16469.64 | 0.000364 | 343.66 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10921.32 | 0.000241 | 227.88 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 16468.20 | 0.000364 | 343.63 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 10015.89 | 0.000221 | 209.00 |
CAV_BAS_HEATC | 260853.60 | 0.005763 | 4890.37 |
VAV_BOT WITH REHEAT_HEATC | 25908.86 | 0.000572 | 395.18 |
VAV_MID WITH REHEAT_HEATC | 240175.33 | 0.005306 | 3662.54 |
VAV_TOP WITH REHEAT_HEATC | 24953.82 | 0.000551 | 380.53 |
DATACENTER_EXTRAWATERHEATC | 1024880.47 | 0.022643 | 19087.52 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.53 | 5.53 | 5.53 | 5.53 | 5.53 | 5.53 | 1.00 | 1.00 | 5.53 |
VAV_BOT WITH REHEAT | 4.71 | 3.02 | 9.42 | 3.02 | 8.77 | 8.77 | 0.300000 | 0.343956 | 8.77 |
VAV_MID WITH REHEAT | 43.41 | 28.62 | 86.81 | 28.62 | 80.75 | 80.75 | 0.300000 | 0.354456 | 80.75 |
VAV_TOP WITH REHEAT | 4.46 | 2.97 | 8.93 | 3.23 | 8.39 | 8.39 | 0.300000 | 0.385080 | 8.39 |
AIRLOOP DATACENTER BASEMENT | 21.23 | 21.23 | 21.23 | 21.23 | 21.23 | 21.23 | 1.00 | 1.00 | 21.23 |
AIRLOOP DATACENTER BOT | 0.460173 | 0.460173 | 0.460173 | 0.460173 | 0.460173 | 0.460173 | 1.00 | 1.00 | 0.460173 |
AIRLOOP DATACENTER MID | 4.37 | 4.37 | 4.37 | 4.37 | 4.37 | 4.37 | 1.00 | 1.00 | 4.37 |
AIRLOOP DATACENTER TOP | 0.438840 | 0.438840 | 0.438840 | 0.438840 | 0.438840 | 0.438840 | 1.00 | 1.00 | 0.438840 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.53 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.77 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 80.75 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.39 | 2.54 |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.23 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.460173 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.37 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.438840 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 127842.30 | 0.005439 | 5.53 | 0.010602 | 24.99 | 6.67 | 11.42 | 0.008284 |
VAV_BOT WITH REHEAT_COOLC | 247319.70 | 0.010522 | 8.77 | 0.011270 | 27.08 | 6.67 | 11.43 | 0.008284 |
VAV_MID WITH REHEAT_COOLC | 2416254.11 | 0.102793 | 80.75 | 0.011654 | 27.52 | 6.67 | 11.43 | 0.008284 |
VAV_TOP WITH REHEAT_COOLC | 234367.66 | 0.009971 | 8.39 | 0.011222 | 26.98 | 6.67 | 11.43 | 0.008284 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.53 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.005439 | 0.000088 |
CAV_BAS_HEATC_CONTROLLER | 0.005763 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.010522 | 0.000045 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000572 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.102793 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.005306 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009971 | 0.000048 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000551 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022643 | 0.000021 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.77 |
VAV_MID WITH REHEAT FAN | 80.75 |
VAV_TOP WITH REHEAT FAN | 8.39 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.23 | 430226.64 | 309604.58 | 0.010536 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.460173 | 9209.77 | 6667.79 | 0.000226 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.37 | 87574.79 | 63339.89 | 0.002145 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.438840 | 8883.22 | 6392.26 | 0.000218 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.23 | 21.23 | 21.23 | 21.23 | 430226.64 | 430226.64 | 14481.98 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.460173 | 0.460173 | 0.460173 | 0.460173 | 9209.77 | 9209.77 | 669.01 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.37 | 4.37 | 4.37 | 4.37 | 87574.79 | 87574.79 | 6690.08 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.438840 | 0.438840 | 0.438840 | 0.438840 | 8883.22 | 8883.22 | 669.01 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.23 |
DATACENTER BOT SUPPLY FAN | 0.460173 |
DATACENTER MID SUPPLY FAN | 4.37 |
DATACENTER TOP SUPPLY FAN | 0.438840 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.23 | 430226.64 | 0.010536 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.460173 | 9209.77 | 0.000226 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.37 | 87574.79 | 0.002145 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.438840 | 8883.22 | 0.000218 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 14481.98 | |
DATACENTER_EXTRAELECHEATC | 430226.64 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 669.01 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 6690.08 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 669.01 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000080 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.128724 | 30830.46 |
HEATSYS1 PUMP | 0.054495 | 13922.81 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.128724 | 15.45 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.054495 | 6.54 |
COOLSYS1_SUPPLY | 0.128724 | 15.45 |
SINGLE WATER PLANT LOOP | 0.013124 | 1.57 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.128724 | 0.128724 | 540318.53 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 5.96 |
COOLSYS1 PUMP | 0.128724 | 10276.82 |
PLANT CIRC PUMP | 0.013124 | 3347.28 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2466537.47 | 1233268.74 | 0.054495 |
DUMMY BOILER | 540597.10 | 93894.07 | 0.013124 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.128724 | 0.064875 | 1528698.39 | 1536005.17 | 0.076011 |
COOLSYS1 CHILLER2 | 0.128724 | 0.064875 | 1528698.39 | 1536005.17 | 0.076011 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013124 | 139666.47 | 59976.62 | 69833.23 | 7879.72 | 21483.23 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.152022 | 18.24 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.152022 | 38838.05 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 58.49 | 1457961.43 | 11.70 | 182245.18 |
TOWERWATERSYS COOLTOWER 2 | 58.49 | 1457961.43 | 11.70 | 182245.18 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.063162 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 24.20 | 18.90 | 15.70 | 13.60 | 15.50 | 17.10 | 21.20 | 26.90 | 27.60 | 27.90 | 27.40 | 26.20 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Tampa-MacDill AFB FL USA TMY3 WMO#=747880 | 27.85 | -82.52 | -5.00 | 8.00 | 101229 | 1.2032 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 21.85 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.944 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.786 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 7.944 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.367 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 22079.114 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22079.114 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 6225.366 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6225.366 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.9837 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.9401 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 0.8493 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9868 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
47 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
48 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
49 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
50 | 9 | 0.31844121E-15 | 0.33891907E-16 | -0.14717764E-09 | -0.34085343E-17 |
51 | 8 | 0.21517510E-07 | 0.13210865E-12 | 0.37403321E-03 | -0.24466149E-09 |
52 | 7 | -0.12129356E-01 | 0.68855956E-08 | -0.22924263E-01 | 0.13791520E-03 |
53 | 6 | 0.40230169 | 0.24029480E-05 | 0.46949424 | -0.47118258E-02 |
54 | 5 | -5.1608121 | 0.89965799E-04 | -4.4213154 | 0.62814943E-01 |
55 | 4 | 32.871256 | 0.73775273E-03 | 21.362378 | -0.42037561 |
56 | 3 | -110.94624 | 0.16114037E-02 | -55.469893 | 1.5111496 |
57 | 2 | 196.85374 | 0.90819125E-03 | 77.733479 | -2.8963115 |
58 | 1 | -171.06207 | 0.97128343E-04 | -55.213590 | 2.7437919 |
59 | 0 | 57.057407 | 0.55402955E-06 | 15.565444 | |
60 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
61 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
62 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
63 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
64 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
65 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
66 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
67 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
68 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
69 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
70 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
71 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
72 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
73 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
74 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
75 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
76 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
77 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
78 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
79 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
80 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
81 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
82 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
83 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
84 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
85 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
86 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
87 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
88 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
89 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
90 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
91 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
92 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
93 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
94 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
95 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
96 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
97 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
98 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
99 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 | |
100 | 7 | -0.41493644E-09 | 0.26375357E-16 | 0.26213203E-14 | -0.63268016E-17 |
101 | 6 | 0.27465604E-04 | 0.18700671E-07 | 0.31288692E-02 | -0.26247577E-04 |
102 | 5 | -0.19935291E-02 | 0.11146933E-04 | -0.22025565 | 0.19255324E-02 |
103 | 4 | 0.45890804E-01 | 0.50864553E-03 | 4.7717348 | -0.44709298E-01 |
104 | 3 | -0.40280019 | 0.40571884E-02 | -37.694667 | 0.39504237 |
105 | 2 | 1.4296488 | 0.67623010E-02 | 115.84777 | -1.4094303 |
106 | 1 | -2.0629154 | 0.20697549E-02 | -143.53273 | 2.0428830 |
107 | 0 | 1.0055995 | 0.48413807E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.5_SHGC_0.25 | 29 | 1 | VerySmooth | 2.843 | 0.252 | 0.162 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.97990E-002 | 0.16139 | 0.61114 | 0.61114 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10909 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 76775.89965 | 76775.89965 | 5.53195 | 5.53195 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 78129.48675 | 78129.48675 | 5.62856 | 5.62856 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 731178.59561 | 731178.59561 | 52.65964 | 52.65964 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 156000.23925 | 156000.23925 | 6.52301 | 10.77757 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 72536.83692 | 72536.83692 | 5.22399 | 5.22399 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 38341.50446 | 38341.50446 | 1.62407 | 1.62407 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11511.71657 | 11511.71657 | 0.83709 | 0.83709 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 33.90000 | 1.65138E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 1187.60691 | 1187.60691 | 5.04496E-002 | 0.13532 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 12131.72152 | 12131.72152 | 0.88217 | 0.88217 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 30.00267 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 1172.47789 | 1172.47789 | 4.95945E-002 | 8.72074E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 12927.01004 | 12927.01004 | 0.94001 | 0.94001 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 33.70250 | 1.65138E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 3110.86498 | 3110.86498 | 0.13101 | 0.13533 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 15517.88923 | 15517.88923 | 1.12839 | 1.12839 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 32.79400 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 16.17786 | 16.17786 | 6.94007E-004 | 8.72074E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 103846.40066 | 103846.40066 | 7.48363 | 7.48363 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 28.05400 | 1.65138E-002 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 84584.67875 | 84584.67875 | 3.59887 | 3.59887 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 122260.24995 | 122260.24995 | 8.89041 | 8.89041 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 30.45033 | 1.65138E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 56994.87396 | 56994.87396 | 2.42556 | 2.42556 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 117188.83895 | 117188.83895 | 8.52169 | 8.52169 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 33.76833 | 1.65138E-002 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 84793.79247 | 84793.79247 | 3.60781 | 3.60781 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 127294.97529 | 127294.97529 | 9.25653 | 9.25653 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65138E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 49187.68726 | 49187.68726 | 2.09154 | 2.09154 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11823.13572 | 11823.13572 | 0.85976 | 0.85976 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 33.82100 | 1.65138E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 11529.81614 | 11529.81614 | 0.49121 | 0.49121 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 12335.89783 | 12335.89783 | 0.89704 | 0.89704 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 30.67417 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 7645.30747 | 7645.30747 | 0.32576 | 0.32576 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 13088.52872 | 13088.52872 | 0.95177 | 0.95177 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 33.90000 | 1.65138E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 11528.81865 | 11528.81865 | 0.49117 | 0.49117 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 13667.28511 | 13667.28511 | 0.99385 | 0.99385 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 32.66233 | 1.65138E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 7012.48252 | 7012.48252 | 0.29869 | 0.29869 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4.60000 | 5.25715E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8024.31571 | 8024.31571 | 0.46017 | 0.46017 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 26.05267 | 1.65138E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76159.52649 | 76159.52649 | 4.36754 | 4.36754 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 26.05267 | 1.65138E-002 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7652.33026 | 7652.33026 | 0.43884 | 0.43884 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 31.21400 | 1.65138E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 370225.53223 | 370225.53223 | 21.23142 | 21.23142 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 26.25017 | 1.65138E-002 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60000 | 5.25715E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 81175.30 | 5.53195 | 5.53195 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 51362.34 | 1.20008 | 1.20008 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 140691.73 | 8.76924 | 8.76924 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 15097.11 | 1.52282 | 1.52282 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1270269.39 | 80.75371 | 80.75371 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 223076.26 | 22.50136 | 22.50136 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 143220.12 | 8.39018 | 8.39018 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 25093.06 | 3.23089 | 3.23089 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:50:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366708.53 | 21.23142 | 21.23142 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 14481.98 | 0.33837 | 0.33837 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7882.33 | 0.46017 | 0.46017 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 669.01 | 1.56314E-002 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 74802.82 | 4.36754 | 4.36754 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 6690.08 | 0.15631 | 0.15631 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7616.95 | 0.43884 | 0.43884 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 669.01 | 1.56314E-002 | 1.56314E-002 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.53195 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.62856 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33793 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.87994 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90114 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12746E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.17860E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.87994 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18913.01920 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.17860E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 329.18597 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.65964 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36120 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34800 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.32556 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96319 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05483E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.51991E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.32556 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 340363.44909 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.51991E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6332.57852 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.22399 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36410 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35500 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85452 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97093 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04642E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.25932E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85452 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 56998.74803 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25932E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1160.63634 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83709 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28530 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25113 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76080 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33544E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.19235E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25113 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3707.99014 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.19235E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 67.44166 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.88217 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17446 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26465 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46523 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.18386E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.46017E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26465 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3829.20793 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.46017E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 69.53360 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94001 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25407 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28200 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67752 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.49959E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31309E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28200 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5943.23480 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31309E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 112.40299 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12839 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13639 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33852 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36371 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79340E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.52325E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33852 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 3405.14391 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.52325E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 59.26647 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.48363 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31912 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.29747 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.85100 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.19389E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.66810E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.59887 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120762.50104 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.66810E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2520.45155 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.89041 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17311 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.66712 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46164 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.20087E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85163E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.66712 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 83807.81802 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85163E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1716.59564 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.52169 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28026 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.55651 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74735 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35947E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.67471E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.60781 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 121061.75353 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.67471E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2526.69173 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.25653 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16627 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.77696 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44338 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.29150E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.70337E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.77696 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 77097.48167 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.70337E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1532.06742 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85976 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27778 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25793 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74074 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37160E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.63876E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49121 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16469.63588 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.63876E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 343.65627 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89704 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17157 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26911 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45752 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22066E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41293E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32576 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10921.31794 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41293E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 227.87956 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95177 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25093 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28553 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66914 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.51836E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.63845E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.49117 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16468.19911 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.63845E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 343.62635 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99385 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15486 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29816 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41295 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.46033E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.21289E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29869 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10015.89392 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21289E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 209.00091 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46017 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.36754 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.43884 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.23142 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.53195 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.53195 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.53195 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.53195 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.53195 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.53195 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.70811 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.01624 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.41622 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.01624 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.76924 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.76924 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34396 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 43.40595 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.62362 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 86.81190 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.62362 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 80.75371 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 80.75371 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35446 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.46320 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.96524 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 8.92640 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.23089 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.39018 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.39018 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.38508 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.23142 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.23142 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.23142 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.23142 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.23142 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.23142 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46017 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46017 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46017 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46017 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46017 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46017 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.36754 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.36754 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.36754 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.36754 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.36754 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.36754 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.43884 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.43884 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.43884 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.43884 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.43884 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.43884 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.53195 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.76924 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 80.75371 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.39018 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.23142 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46017 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.36754 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.43884 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.53195 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 127842.30363 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 5.43871E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.53195 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.06022E-002 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.99135 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42444 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 260853.59541 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.76324E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 4890.37439 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.53195 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.43871E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 8.75558E-005 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.76324E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.76924 |
306 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53804 |
307 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 247319.69814 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 1.05216E-002 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.76924 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.12698E-002 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.08317 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42611 |
315 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 25908.85924 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.72425E-004 |
318 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 395.18021 |
319 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.76924 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.05216E-002 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.52586E-005 |
322 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.72425E-004 |
323 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 80.75371 |
324 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38036 |
325 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38036 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 2416254.11136 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 0.10279 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 80.75371 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.16542E-002 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 27.51919 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
332 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42706 |
333 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 240175.32800 |
335 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.30638E-003 |
336 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 3662.54418 |
337 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 80.75371 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 0.10279 |
339 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.63252E-006 |
340 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.30638E-003 |
341 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.39018 |
342 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53804 |
343 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 234367.65938 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 9.97054E-003 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.39018 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.12221E-002 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.98349 |
349 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
350 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42599 |
351 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28381E-003 |
352 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 24953.82321 |
353 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.51324E-004 |
354 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 380.53234 |
355 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.39018 |
356 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.97054E-003 |
357 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.77597E-005 |
358 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.51324E-004 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.23142 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.23142 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 430226.63741 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 309604.57558 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.05362E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.23142 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.23142 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.23142 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.23142 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 430226.63741 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 430226.63741 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 14481.98191 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.23142 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.23142 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 430226.63741 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.05362E-002 |
377 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 14481.98191 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 7.97716E-005 |
379 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 430226.63741 |
383 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
384 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1024880.47449 |
385 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.26435E-002 |
386 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19087.52093 |
387 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26435E-002 |
388 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.10299E-005 |
389 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46017 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46017 |
391 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9209.76852 |
392 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6667.78979 |
393 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.25547E-004 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46017 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46017 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46017 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46017 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9209.76852 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9209.76852 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.00757 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
402 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46017 |
403 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46017 |
404 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9209.76852 |
405 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.25547E-004 |
406 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 669.00757 |
407 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.36754 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.36754 |
409 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 87574.78881 |
410 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 63339.89168 |
411 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.14470E-003 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.36754 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.36754 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.36754 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.36754 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 87574.78881 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 87574.78881 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 6690.07569 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
420 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.36754 |
421 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.36754 |
422 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 87574.78881 |
423 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.14470E-003 |
424 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 6690.07569 |
425 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.43884 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.43884 |
427 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 8883.21934 |
428 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6392.25685 |
429 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.17549E-004 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.43884 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.43884 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.43884 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.43884 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8883.21934 |
435 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8883.21934 |
436 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 669.00757 |
437 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
438 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.43884 |
439 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.43884 |
440 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 8883.21934 |
441 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.17549E-004 |
442 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 669.00757 |
443 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.12872 |
444 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 30830.46110 |
445 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.12872 |
446 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 15.44686 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.12872 |
448 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.12872 |
449 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 540318.53080 |
450 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
451 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
452 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
453 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
454 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 5.95777 |
455 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
456 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 5.44951E-002 |
457 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 6.53942 |
458 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 5.44951E-002 |
459 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 13922.80731 |
460 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2466537.47457 |
461 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1233268.73500 |
462 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 5.44951E-002 |
463 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.12872 |
464 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 15.44686 |
465 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.12872 |
466 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 10276.82037 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12872 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.48750E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1528698.39023 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1536005.16500 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.60112E-002 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.12872 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 6.48750E-002 |
474 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1528698.39023 |
475 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1536005.16500 |
476 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 7.60112E-002 |
477 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.31240E-002 |
478 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.57488 |
479 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.31240E-002 |
480 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3347.28133 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.31240E-002 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59976.62134 |
484 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
485 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
486 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21483.23192 |
487 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 540597.09918 |
488 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
489 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31240E-002 |
490 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.15202 |
491 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 18.24269 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.15202 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 38838.04721 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 58.48834 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1457961.42800 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 11.69767 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 182245.17850 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 58.48834 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1457961.42800 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 11.69767 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 182245.17850 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 6.31620E-002 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 6.31620E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17942.92 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 323181.99 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 54084.31 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 3521.40 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 3636.57 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 5642.11 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 3230.49 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 114576.84 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 79520.52 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 114860.76 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 73167.55 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 15626.04 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 10361.92 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 15624.68 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9502.87 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 212037.27 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 21998.32 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 203775.81 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 21171.97 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 824161.48 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 155013.33 | 104675.10 | 50338.23 | 0.68 | 18934.83 | 192.05 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 263325.94 | 173938.00 | 89387.94 | 0.66 | 32254.63 | 327.14 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2466083.70 | 1620521.19 | 845562.51 | 0.66 | 301818.91 | 3061.21 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 251268.75 | 166114.21 | 85154.53 | 0.66 | 30794.40 | 312.33 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.16 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.16 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.5_SHGC_0.25 | N/A | 2.843 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.984 | 0.857 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.940 | 0.824 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.940 | 0.824 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 25 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2173912296 | 0.2468672143 | Fail | Pass | 0.7216948058 | 0.8567271333 | Fail | Fail |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.2529446179 | 0.2545161198 | Pass | Pass | 0.2691563443 | 0.5068350863 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 0.1395726923 | 0.1984592461 | Pass | Pass | 0.1751361573 | 0.3792493077 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 0.1280334134 | 0.1915103310 | Pass | Pass | 0.1680423333 | 0.3726352169 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2195497766 | 0.2264191152 | Pass | Pass | 0.2399101593 | 0.4248698703 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3534083803 | 0.3653620175 | Fail | Fail | 0.2435192381 | 0.4265472229 | Pass | Fail |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3699258824 | 0.4670313631 | Pass | Pass | 0.2523994666 | 0.4410830459 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4175316018 | 0.4757920818 | Pass | Pass | 0.2452837221 | 0.4252867224 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1248031992 | 0.1829870141 | Pass | Pass | 0.1745833951 | 0.3778825577 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2368913293 | 0.3385731182 | Pass | Pass | 0.1775105932 | 0.3798502656 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2859836816 | 0.4893528570 | Pass | Pass | 0.1989049209 | 0.4133380613 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2240955973 | 0.3581063638 | Pass | Pass | 0.1760665060 | 0.3762621499 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1294827208 | 0.1986089442 | Pass | Pass | 0.1679299610 | 0.3712533621 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2265533879 | 0.3224644342 | Pass | Pass | 0.1703368726 | 0.3736954717 | Pass | Fail |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2814659265 | 0.4792247950 | Pass | Pass | 0.2079127672 | 0.4999729285 | Pass | Fail |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2252929703 | 0.3726749035 | Pass | Pass | 0.1696628898 | 0.3699817400 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.1600878102E-002 | 4.4208749663E-002 | Pass | Pass | 0.2774458092 | 0.4977419499 | Fail | Fail |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.7428421218E-002 | 3.1741311428E-002 | Pass | Pass | 0.1891716031 | 0.3896509674 | Fail | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.3601395899E-002 | 6.6358952217E-002 | Pass | Pass | 0.1699288605 | 0.3619351332 | Fail | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.8586418011E-014 | 3.7887773383E-014 | Pass | Pass | 3.6229667585E-003 | 3.1827900732E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.7114113424E-014 | 2.6429826388E-014 | Pass | Pass | 4.4337735871E-003 | 5.5711446502E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.2944609176E-014 | 1.8297697010E-014 | Pass | Pass | 5.8184013076E-003 | 5.7885563998E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.9606640611E-014 | 5.2642745189E-014 | Pass | Pass | 3.1320543002E-005 | 2.3793440732E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 4.60 | 0.00 | 4.60 | Wetbulb [C] | 2.50 | 10.00 |
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 7.90 | 25.10 | Wetbulb [C] | 3.10 | 270.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.857 | 0.984 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.55 | 0.221 | 0.228 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.940 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.940 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.5_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.5_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.5_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.5_SHGC_0.25 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.5_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.5_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.5_SHGC_0.25 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.843 | 0.252 | 0.251 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.843 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.843 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.843 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.843 | 0.252 | 0.251 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.843 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.843 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.843 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.5_SHGC_0.25 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.843 | 0.252 | 0.251 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.843 | 0.252 | 0.251 | ||||||||||||
North Total or Average | 1043.06 | 2.843 | 0.252 | 0.251 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.843 | 0.252 | 0.251 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 7.9438 | 2779.43 | 22079.11 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 210.95 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 7.9438 | 2496.12 | 19828.60 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 189.45 |
CORE_MID_LIGHTS | CORE_MID | 7.9438 | 24961.20 | 198285.97 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 1894.50 |
CORE_TOP_LIGHTS | CORE_TOP | 7.9438 | 2496.12 | 19828.60 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 189.45 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 7.9438 | 313.41 | 2489.68 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.68 | 0.0000 | Y | 18.54 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.65 | 0.0000 | Y | 11.94 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 7.9438 | 313.42 | 2489.73 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.54 | 0.0000 | Y | 18.48 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.63 | 0.0000 | Y | 11.94 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 7.9438 | 3134.13 | 24896.78 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.70 | 0.0000 | Y | 185.55 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 7.9438 | 2019.75 | 16044.43 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.66 | 0.0000 | Y | 119.45 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 7.9438 | 3134.20 | 24897.33 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.55 | 0.0000 | Y | 184.84 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 7.9438 | 2019.75 | 16044.43 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.64 | 0.0000 | Y | 119.39 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 7.9438 | 313.41 | 2489.68 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.70 | 0.0000 | Y | 18.55 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.66 | 0.0000 | Y | 11.94 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 7.9438 | 313.42 | 2489.73 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.55 | 0.0000 | Y | 18.48 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.64 | 0.0000 | Y | 11.94 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 7.9438 | 783.68 | 6225.37 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 59.48 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 7.9438 | 36.20 | 287.59 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 2.75 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 7.9438 | 362.03 | 2875.86 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 27.48 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 7.9438 | 36.20 | 287.59 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 2.75 |
Interior Lighting Total | 7.9438 | 46320.38 | 367958.24 | 1029.77 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9734.40 | AstronomicalClock | - | 41.73 | 41.73 | 76.24 | |
EXTERIOR_LIGHTS_B | 43301.51 | AstronomicalClock | - | 83.73 | 71.13 | 578.13 | |
Exterior Lighting Total | 53035.91 | 654.37 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 3018825.36 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1233268.74 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1536005.17 | 6.28 | 7.08 | 24.16 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1536005.17 | 6.28 | 7.08 | 24.16 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1457961.43 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1457961.43 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 127842.30 | 155013.33 | 104675.10 | 50338.23 | 0.68 | - | 18934.83 | 192.05 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 247319.70 | 263325.94 | 173938.00 | 89387.94 | 0.66 | - | 32254.63 | 327.14 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 2416254.11 | 2466083.70 | 1620521.19 | 845562.51 | 0.66 | - | 301818.91 | 3061.21 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 234367.66 | 251268.75 | 166114.21 | 85154.53 | 0.66 | - | 30794.40 | 312.33 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 430226.64 | 309604.58 | 120622.06 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9209.77 | 6667.79 | 2541.98 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 87574.79 | 63339.89 | 24234.90 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8883.22 | 6392.26 | 2490.96 | 0.72 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18913.02 | 17942.92 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 340363.45 | 323181.99 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 56998.75 | 54084.31 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 3707.99 | 3521.40 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 3829.21 | 3636.57 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 5943.23 | 5642.11 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 3405.14 | 3230.49 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 120762.50 | 114576.84 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 83807.82 | 79520.52 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 121061.75 | 114860.76 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 77097.48 | 73167.55 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 16469.64 | 15626.04 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10921.32 | 10361.92 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16468.20 | 15624.68 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 10015.89 | 9502.87 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 260853.60 | 212037.27 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 25908.86 | 21998.32 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 240175.33 | 203775.81 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 24953.82 | 21171.97 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 430226.64 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9209.77 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 87574.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 8883.22 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 14481.98 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1024880.47 | 824161.48 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 669.01 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 6690.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 669.01 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.53 | 9380.27 | 1695.65 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.77 | 18949.87 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 80.75 | 174504.46 | 2160.95 | 1.00 | 1.08 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.39 | 18130.73 | 2160.95 | 1.00 | 1.12 | General | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.23 | 35201.13 | 1657.97 | 1.00 | 1.13 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 515.44 | 1120.11 | 1.00 | 1.64 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.37 | 4892.12 | 1120.11 | 1.00 | 1.16 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.44 | 491.55 | 1120.11 | 1.00 | 1.67 | General | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.128724 | 30830.46 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.054495 | 13922.81 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.128724 | 10276.82 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013124 | 3347.28 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.152022 | 38838.05 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 76775.90 | 76775.90 | 27.62 | 5.532 | 5.532 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 28.05 | 0.01651 | 1.200 | 0.00 |
CORE_BOTTOM | 78129.49 | 78129.49 | 31.30 | 5.629 | 5.629 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 28.05 | 0.01651 | 1.078 | 0.00 |
CORE_MID | 731178.60 | 731178.60 | 292.93 | 52.660 | 52.660 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.05 | 0.01651 | 10.778 | 0.00 |
CORE_TOP | 72536.84 | 72536.84 | 29.06 | 5.224 | 5.224 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 28.05 | 0.01651 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11511.72 | 11511.72 | 36.73 | 0.837 | 0.837 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00887 | 33.90 | 0.01651 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 12131.72 | 12131.72 | 60.07 | 0.882 | 0.882 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00873 | 30.00 | 0.01651 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12927.01 | 12927.01 | 41.25 | 0.940 | 0.940 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00883 | 33.70 | 0.01651 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 15517.89 | 15517.89 | 76.83 | 1.128 | 1.128 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00868 | 32.79 | 0.01651 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 103846.40 | 103846.40 | 331.34 | 7.484 | 7.484 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00899 | 28.05 | 0.01651 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 122260.25 | 122260.25 | 605.32 | 8.890 | 8.890 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:40:00 | 24.00 | 24.00 | 0.00876 | 30.45 | 0.01651 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 117188.84 | 117188.84 | 373.90 | 8.522 | 8.522 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00892 | 33.77 | 0.01651 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 127294.98 | 127294.98 | 630.25 | 9.257 | 9.257 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00875 | 32.66 | 0.01651 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11823.14 | 11823.14 | 37.72 | 0.860 | 0.860 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00893 | 33.82 | 0.01651 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 12335.90 | 12335.90 | 61.08 | 0.897 | 0.897 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:50:00 | 24.00 | 24.00 | 0.00877 | 30.67 | 0.01651 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13088.53 | 13088.53 | 41.76 | 0.952 | 0.952 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00889 | 33.90 | 0.01651 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 13667.29 | 13667.29 | 67.67 | 0.994 | 0.994 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00874 | 32.66 | 0.01651 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8024.32 | 8024.32 | 221.65 | 0.460 | 0.460 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.05 | 0.01651 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76159.53 | 76159.53 | 2103.69 | 4.368 | 4.368 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 27.00 | 27.00 | 0.00850 | 26.05 | 0.01651 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7652.33 | 7652.33 | 211.37 | 0.439 | 0.439 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 31.21 | 0.01651 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 370225.53 | 370225.53 | 472.42 | 21.231 | 21.231 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 26.25 | 0.01651 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 | |
CORE_MID | 156000.24 | 156000.24 | 62.50 | 6.523 | 10.778 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 10.778 | 0.00 |
CORE_TOP | 38341.50 | 38341.50 | 15.36 | 1.624 | 1.624 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | 4.60 | 0.00526 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 1187.61 | 1187.61 | 3.79 | 0.050 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00672 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 1172.48 | 1172.48 | 5.81 | 0.050 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00685 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 3110.86 | 3110.86 | 9.93 | 0.131 | 0.135 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00715 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16.18 | 16.18 | 0.08 | 0.001 | 0.087 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | 21.00 | 21.00 | 0.00532 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 84584.68 | 84584.68 | 269.88 | 3.599 | 3.599 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 56994.87 | 56994.87 | 282.19 | 2.426 | 2.426 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 84793.79 | 84793.79 | 270.54 | 3.608 | 3.608 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00764 | 4.60 | 0.00526 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 49187.69 | 49187.69 | 243.53 | 2.092 | 2.092 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00754 | 4.60 | 0.00526 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11529.82 | 11529.82 | 36.79 | 0.491 | 0.491 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 7645.31 | 7645.31 | 37.85 | 0.326 | 0.326 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00784 | 4.60 | 0.00526 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 11528.82 | 11528.82 | 36.78 | 0.491 | 0.491 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00782 | 4.60 | 0.00526 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 7012.48 | 7012.48 | 34.72 | 0.299 | 0.299 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00778 | 4.60 | 0.00526 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | 4.60 | 0.00526 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.53 | 5.53 | 1.20 | 1.20 | 5.5319 | 5.5319 | 5.5319 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 8.77 | 8.77 | 1.52 | 1.52 | 8.7692 | 3.0162 | 8.7692 | 0.3440 | 0.3000 |
VAV_MID WITH REHEAT | 80.75 | 80.75 | 22.50 | 22.50 | 80.7537 | 28.6236 | 80.7537 | 0.3545 | 0.3000 |
VAV_TOP WITH REHEAT | 8.39 | 8.39 | 3.23 | 3.23 | 8.3902 | 3.2309 | 8.3902 | 0.3851 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.23 | 21.23 | 0.34 | 0.34 | 21.2314 | 21.2314 | 21.2314 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4602 | 0.4602 | 0.4602 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.37 | 4.37 | 0.16 | 0.16 | 4.3675 | 4.3675 | 4.3675 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.44 | 0.44 | 0.02 | 0.02 | 0.4388 | 0.4388 | 0.4388 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18913.019 | 18913.019 | 1.879939 | 0.00041786 | 329.186 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17942.92 | 18913.02 | 1.879939 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 18989.10 | 18989.10 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 340363.449 | 340363.449 | 18.325555 | 0.00751991 | 6332.579 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 323181.99 | 340363.45 | 18.325555 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 156000.24 | 0.00 | 342029.03 | 342029.03 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 56998.748 | 56998.748 | 1.854515 | 0.00125932 | 1160.636 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 54084.31 | 56998.75 | 1.854515 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00800000 | 51.6744 | 38341.50 | 0.00 | 57259.22 | 57259.22 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 3707.990 | 3707.990 | 0.251127 | 0.00008192 | 67.442 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3521.40 | 3707.99 | 0.251127 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00671502 | 43.4643 | 1187.61 | 0.00 | 3726.35 | 3726.35 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 3829.208 | 3829.208 | 0.264651 | 0.00008460 | 69.534 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3636.57 | 3829.21 | 0.264651 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00685350 | 44.3514 | 1172.48 | 0.00 | 3848.20 | 3848.20 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 5943.235 | 5943.235 | 0.282002 | 0.00013131 | 112.403 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5642.11 | 5943.23 | 0.282002 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00715270 | 46.2662 | 3110.86 | 0.00 | 5971.57 | 5971.57 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 3405.144 | 3405.144 | 0.338518 | 0.00007523 | 59.266 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | 3230.49 | 3405.14 | 0.338518 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00531521 | 34.4795 | 16.18 | 0.00 | 3418.84 | 3418.84 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 120762.501 | 120762.501 | 3.598865 | 0.00266810 | 2520.452 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114576.84 | 120762.50 | 3.598865 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00763980 | 49.3792 | 84584.68 | 0.00 | 121313.86 | 121313.86 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 83807.818 | 83807.818 | 2.667124 | 0.00185163 | 1716.596 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79520.52 | 83807.82 | 2.667124 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00766778 | 49.5577 | 56994.87 | 0.00 | 84190.45 | 84190.45 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 121061.754 | 121061.754 | 3.607810 | 0.00267471 | 2526.692 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114860.76 | 121061.75 | 3.607810 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00764278 | 49.3982 | 84793.79 | 0.00 | 121614.48 | 121614.48 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 77097.482 | 77097.482 | 2.776958 | 0.00170337 | 1532.067 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73167.55 | 77097.48 | 2.776958 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00753837 | 48.7319 | 49187.69 | 0.00 | 77455.51 | 77455.51 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 16469.636 | 16469.636 | 0.491211 | 0.00036388 | 343.656 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15626.04 | 16469.64 | 0.491211 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782475 | 50.5586 | 11529.82 | 0.00 | 16544.83 | 16544.83 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 10921.318 | 10921.318 | 0.325756 | 0.00024129 | 227.880 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10361.92 | 10921.32 | 0.325756 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00783559 | 50.6276 | 7645.31 | 0.00 | 10971.18 | 10971.18 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 16468.199 | 16468.199 | 0.491168 | 0.00036384 | 343.626 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15624.68 | 16468.20 | 0.491168 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00782427 | 50.5555 | 11528.82 | 0.00 | 16543.38 | 16543.38 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 10015.894 | 10015.894 | 0.298685 | 0.00022129 | 209.001 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9502.87 | 10015.89 | 0.298685 | 12.80 | 11.58 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 0.0000 | 21.00 | 0.00778059 | 50.2772 | 7012.48 | 0.00 | 10061.62 | 10061.62 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 127842.304 | -999.000 | 5.531948 | 0.00543871 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 127842.30 | 90042.11 | 5.531948 | 24.99 | 18.44 | 0.01060221 | 11.42 | 11.42 | 0.00828381 | 28.55 | 0.01651377 | 23.71 | 21.6936 | 24.00 | 0.00895556 | 48.1376 | 75736.51 | 0.00 | 141005.57 | 96383.91 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 260853.595 | 260853.595 | 5.531948 | 0.00576324 | 4890.374 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 212037.27 | 240261.73 | 5.531948 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 21.6936 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 223785.51 | 223785.51 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 247319.698 | -999.000 | 8.769245 | 0.01052155 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 247319.70 | 168222.52 | 8.769245 | 27.08 | 19.63 | 0.01126984 | 11.43 | 12.09 | 0.00828381 | 33.90 | 0.01651378 | 25.10 | 28.9425 | 24.00 | 0.00884849 | 47.5699 | 112042.00 | 0.00 | 268205.04 | 177653.98 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 25908.859 | 25908.859 | 2.630773 | 0.00057242 | 395.180 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 21998.32 | 25908.86 | 2.630773 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 96.4751 | 21.00 | 0.00759111 | 49.0656 | 0.00 | 0.00 | 23269.86 | 23269.86 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2416254.111 | -999.000 | 80.753706 | 0.10279303 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2416254.11 | 1593108.99 | 80.753706 | 27.52 | 20.05 | 0.01165415 | 11.43 | 12.09 | 0.00828381 | 33.90 | 0.01651378 | 25.10 | 31.4293 | 24.00 | 0.00889591 | 47.8215 | 981623.31 | 0.00 | 2608787.48 | 1681700.28 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 240175.328 | 240175.328 | 24.226112 | 0.00530638 | 3662.544 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 203775.81 | 240175.33 | 24.226112 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 104.7645 | 21.00 | 0.00780639 | 50.4411 | 431561.27 | 0.00 | 215560.24 | 215560.24 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 234367.659 | -999.000 | 8.390178 | 0.00997054 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 234367.66 | 159916.00 | 8.390178 | 26.98 | 19.56 | 0.01122212 | 11.43 | 12.09 | 0.00828381 | 33.82 | 0.01651377 | 25.08 | 30.2501 | 24.00 | 0.00889026 | 47.7916 | 114856.00 | 0.00 | 254347.17 | 168917.68 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 24953.823 | 24953.823 | 2.517053 | 0.00055132 | 380.532 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:50:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21171.97 | 24953.82 | 2.517053 | 4.60 | 4.60 | 0.00525715 | 12.80 | 11.58 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 100.8338 | 21.00 | 0.00790978 | 51.1001 | 59002.25 | 0.00 | 22396.36 | 22396.36 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 430226.637 | 309604.576 | 21.231423 | 0.01053622 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 459846.28 | 451310.47 | -999.0 | 28.51 | 18.02 | 0.00862793 | 12.80 | 12.09 | 0.00850000 | 33.90 | 0.01651378 | 25.10 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 369601.02 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9209.769 | 6667.790 | 0.460173 | 0.00022555 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9865.75 | 9470.83 | -999.0 | 27.91 | 17.94 | 0.00877222 | 12.80 | 12.09 | 0.00850000 | 26.05 | 0.01651378 | 23.02 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 8024.32 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87574.789 | 63339.892 | 4.367541 | 0.00214470 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 93783.66 | 89836.36 | -999.0 | 27.91 | 17.95 | 0.00878681 | 12.80 | 12.09 | 0.00850000 | 26.05 | 0.01651378 | 23.02 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 76159.53 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8883.219 | 6392.257 | 0.438840 | 0.00021755 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9496.81 | 9103.27 | -999.0 | 28.10 | 18.01 | 0.00878546 | 12.80 | 12.09 | 0.00850000 | 31.41 | 0.01651378 | 24.46 | -999.0000 | 27.00 | 0.00850000 | 38.2570 | 7651.91 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 430226.637 | 430226.637 | 21.231423 | 0.01053622 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 430226.64 | 430226.64 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5937 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9209.769 | 9209.769 | 0.460173 | 0.00022555 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9209.77 | 9209.77 | 0.460173 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3968 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87574.789 | 87574.789 | 4.367541 | 0.00214470 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 87574.79 | 87574.79 | 4.367541 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5790 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8883.219 | 8883.219 | 0.438840 | 0.00021755 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8883.22 | 8883.22 | 0.438840 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5620 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 14481.982 | 14481.982 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14481.98 | 14481.98 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5937 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 922116.09 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5937 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1024880.474 | 1024880.474 | 21.231423 | 0.02264348 | 19087.521 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 824161.48 | 922116.09 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 1.5937 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 0.460173 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.3968 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 6690.076 | 6690.076 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.08 | 6690.08 | 4.367541 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5790 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 0.438840 | 4.60 | 4.60 | 0.00525715 | 40.00 | 21.14 | 0.00800000 | 4.60 | 0.00525715 | 4.60 | 3.5620 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18913.019 | 18913.019 | 1.879939 | 0.00041786 | 329.186 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.7131 | 0.766784 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17942.92 | 18913.02 | 1.0000 | 2.26188047 | 1.879939 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.41781742 | 60.00 | 49.00 | 11.00 | 0.000 | 17942.92 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 18989.10 | 18989.10 | 2.26188047 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 340363.449 | 340363.449 | 18.325555 | 0.00751991 | 6332.579 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 12.8442 | 13.799241 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 323181.99 | 340363.45 | 1.0000 | 22.04870168 | 18.325555 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 7.51914740 | 60.00 | 49.00 | 11.00 | 0.000 | 323181.99 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.60 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 156000.24 | 0.00 | 342029.03 | 342029.03 | 22.04870168 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 28.01 | 17.34 | 0.00800000 | 48572.3 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 56998.748 | 56998.748 | 1.854515 | 0.00125932 | 1160.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 2.1495 | 2.310881 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 54084.31 | 56998.75 | 1.0000 | 2.23129128 | 1.854515 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.25918923 | 60.00 | 49.00 | 11.00 | 0.000 | 54084.31 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.86 | 0.00800000 | 21.00 | 0.00800000 | 51.6744 | 38341.50 | 0.00 | 57259.22 | 57259.22 | 2.23129128 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 37.97 | 20.54 | 0.00800000 | 58721.8 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3707.990 | 3707.990 | 0.251127 | 0.00008192 | 67.442 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.1400 | 0.150332 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3521.40 | 3707.99 | 1.0000 | 0.30214809 | 0.251127 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.08191515 | 60.00 | 49.00 | 11.00 | 0.000 | 3521.40 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.94 | 0.00671502 | 21.00 | 0.00671502 | 43.4643 | 1187.61 | 0.00 | 3726.35 | 3726.35 | 0.30214809 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 24.89 | 16.26 | 0.00800000 | 45392.7 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3829.208 | 3829.208 | 0.264651 | 0.00008460 | 69.534 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.1445 | 0.155246 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 3636.57 | 3829.21 | 1.0000 | 0.31841978 | 0.264651 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.08459304 | 60.00 | 49.00 | 11.00 | 0.000 | 3636.57 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.90 | 0.00685350 | 21.00 | 0.00685350 | 44.3514 | 1172.48 | 0.00 | 3848.20 | 3848.20 | 0.31841978 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 24.65 | 16.17 | 0.00800000 | 45145.1 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5943.235 | 5943.235 | 0.282002 | 0.00013131 | 112.403 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.2242 | 0.240955 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5642.11 | 5943.23 | 1.0000 | 0.33929489 | 0.282002 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.13129512 | 60.00 | 49.00 | 11.00 | 0.000 | 5642.11 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.82 | 0.00715270 | 21.00 | 0.00715270 | 46.2662 | 3110.86 | 0.00 | 5971.57 | 5971.57 | 0.33929489 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 30.06 | 18.03 | 0.00800000 | 50659.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3405.144 | 3405.144 | 0.338518 | 0.00007523 | 59.266 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.1284 | 0.138054 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 22:00:00 | 3230.49 | 3405.14 | 1.0000 | 0.40729412 | 0.338518 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.07522482 | 60.00 | 49.00 | 11.00 | 0.000 | 3230.49 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 21.00 | 0.00531521 | 21.00 | 0.00531521 | 34.4795 | 16.18 | 0.00 | 3418.84 | 3418.84 | 0.40729412 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41453.9 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 120762.501 | 120762.501 | 3.598865 | 0.00266810 | 2520.452 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 4.5536 | 4.896033 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114576.84 | 120762.50 | 1.0000 | 4.33003548 | 3.598865 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.66782772 | 60.00 | 49.00 | 11.00 | 0.000 | 114576.84 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00763980 | 21.00 | 0.00763980 | 49.3792 | 84584.68 | 0.00 | 121313.86 | 121313.86 | 4.33003548 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.28 | 21.23 | 0.00800000 | 61076.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 83807.818 | 83807.818 | 2.667124 | 0.00185163 | 1716.596 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 3.1604 | 3.397792 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 79520.52 | 83807.82 | 1.0000 | 3.20899550 | 2.667124 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.85144245 | 60.00 | 49.00 | 11.00 | 0.000 | 79520.52 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00766778 | 21.00 | 0.00766778 | 49.5577 | 56994.87 | 0.00 | 84190.45 | 84190.45 | 3.20899550 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 38.53 | 20.71 | 0.00800000 | 59295.6 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 121061.754 | 121061.754 | 3.607810 | 0.00267471 | 2526.692 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 4.5649 | 4.908166 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 114860.76 | 121061.75 | 1.0000 | 4.34079701 | 3.607810 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.67443867 | 60.00 | 49.00 | 11.00 | 0.000 | 114860.76 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00764278 | 21.00 | 0.00764278 | 49.3982 | 84793.79 | 0.00 | 121614.48 | 121614.48 | 4.34079701 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.28 | 21.23 | 0.00800000 | 61076.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 77097.482 | 77097.482 | 2.776958 | 0.00170337 | 1532.067 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 2.9079 | 3.125737 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 73167.55 | 77097.48 | 1.0000 | 3.34114341 | 2.776958 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.70320089 | 60.00 | 49.00 | 11.00 | 0.000 | 73167.55 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.91 | 0.00753837 | 21.00 | 0.00753837 | 48.7319 | 49187.69 | 0.00 | 77455.51 | 77455.51 | 3.34114341 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 35.53 | 19.80 | 0.00800000 | 56242.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16469.636 | 16469.636 | 0.491211 | 0.00036388 | 343.656 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.6210 | 0.667723 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15626.04 | 16469.64 | 1.0000 | 0.59100888 | 0.491211 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.36383936 | 60.00 | 49.00 | 11.00 | 0.000 | 15626.04 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782475 | 21.00 | 0.00782475 | 50.5586 | 11529.82 | 0.00 | 16544.83 | 16544.83 | 0.59100888 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61054.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10921.318 | 10921.318 | 0.325756 | 0.00024129 | 227.880 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.4118 | 0.442779 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 10361.92 | 10921.32 | 1.0000 | 0.39193859 | 0.325756 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.24126856 | 60.00 | 49.00 | 11.00 | 0.000 | 10361.92 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00783559 | 21.00 | 0.00783559 | 50.6276 | 7645.31 | 0.00 | 10971.18 | 10971.18 | 0.39193859 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61051.9 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16468.199 | 16468.199 | 0.491168 | 0.00036384 | 343.626 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.6210 | 0.667665 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15624.68 | 16468.20 | 1.0000 | 0.59095696 | 0.491168 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.36380762 | 60.00 | 49.00 | 11.00 | 0.000 | 15624.68 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00782427 | 21.00 | 0.00782427 | 50.5555 | 11528.82 | 0.00 | 16543.38 | 16543.38 | 0.59095696 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.25 | 21.22 | 0.00800000 | 61054.1 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10015.894 | 10015.894 | 0.298685 | 0.00022129 | 209.001 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.3777 | 0.406071 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9502.87 | 10015.89 | 1.0000 | 0.35936808 | 0.298685 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.22126636 | 60.00 | 49.00 | 11.00 | 0.000 | 9502.87 | 4.60 | 0.00525715 | 4.60 | 0.00000000 | 0.0000 | 20.95 | 0.00778059 | 21.00 | 0.00778059 | 50.2772 | 7012.48 | 0.00 | 10061.62 | 10061.62 | 0.35936808 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61057.9 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 127842.304 | -999.000 | 5.531948 | 0.00543871 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.5490 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.531948 | 6.65585686 | 4197.9300 | 999.8980 | 128.71070523 | 12.27 | 6.67 | 5.60 | 3025783.77 | 4.2251 | 4.225097 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 127842.30 | 90042.11 | 1.0000 | 6.65585686 | 5.531948 | 24.99 | 18.44 | 0.01060221 | 52120.4 | 11.42 | 11.42 | 0.00828381 | 32918.2 | 5.43815233 | 6.67 | 10.65 | 5.60 | 9380.272 | 118462.03 | 28.55 | 0.01651377 | 23.71 | 1.20008137 | 21.6936 | 24.00 | 0.00895514 | 24.00 | 0.00895556 | 48.1376 | 75736.51 | 0.00 | 141005.57 | 96383.91 | 6.65585686 | 24.99 | 18.45 | 0.01060221 | 52120.4 | 10.86 | 10.71 | 0.00794303 | 30935.2 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 260853.595 | 260853.595 | 5.531948 | 0.00576324 | 4890.374 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | CAV_BAS FAN | Fan:ConstantVolume | 5.531948 | 6.65585686 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 8.4270 | 10.575700 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 212037.27 | 240261.73 | 1.0000 | 6.65585686 | 5.531948 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 5.76265353 | 60.00 | 49.00 | 11.00 | 0.000 | 212037.27 | 4.60 | 0.00525715 | 4.60 | 1.20008137 | 21.6936 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 51.6744 | 0.00 | 0.00 | 223785.51 | 223785.51 | 6.65585686 | 12.80 | 3.53 | 0.00114047 | 15741.3 | 46.19 | 17.75 | 0.00114047 | 49363.7 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 247319.698 | -999.000 | 8.769245 | 0.01052155 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7901 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.769245 | 10.55086477 | 4197.9300 | 999.8980 | 128.71070523 | 12.27 | 6.67 | 5.60 | 3025783.77 | 8.1737 | 8.173740 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 247319.70 | 168222.52 | 1.0000 | 10.55086477 | 8.769245 | 27.08 | 19.63 | 0.01126984 | 55966.9 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 10.52047838 | 6.67 | 10.65 | 5.60 | 18949.871 | 228369.83 | 33.90 | 0.01651378 | 25.10 | 2.53804000 | 28.9425 | 24.00 | 0.00889710 | 24.00 | 0.00884849 | 47.5699 | 112042.00 | 0.00 | 268205.04 | 177653.98 | 10.55086477 | 27.08 | 19.64 | 0.01126984 | 55966.9 | 10.67 | 10.54 | 0.00786520 | 30546.7 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 25908.859 | 25908.859 | 2.630773 | 0.00057242 | 395.180 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.769245 | 10.55086477 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.8743 | 1.050414 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 21998.32 | 25908.86 | 1.0000 | 3.16525943 | 2.630773 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.57236619 | 60.00 | 49.00 | 11.00 | 0.000 | 21998.32 | 4.60 | 0.00525715 | 4.60 | 2.53804000 | 96.4751 | 6.14 | 0.00000000 | 21.00 | 0.00759111 | 49.0656 | 0.00 | 0.00 | 23269.86 | 23269.86 | 3.16525943 | 12.80 | 8.42 | 0.00507184 | 25667.0 | 20.05 | 11.62 | 0.00507184 | 33018.6 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2416254.111 | -999.000 | 80.753706 | 0.10279303 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5045 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.753706 | 97.16018570 | 4197.9300 | 999.8980 | 128.71070523 | 12.27 | 6.67 | 5.60 | 3025783.77 | 79.8555 | 79.855479 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 2416254.11 | 1593108.99 | 1.0000 | 97.16018570 | 80.753706 | 27.52 | 20.05 | 0.01165415 | 57394.9 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 102.78254960 | 6.67 | 10.65 | 5.60 | 174504.458 | 2241749.65 | 33.90 | 0.01651378 | 25.10 | 25.38036000 | 31.4293 | 24.00 | 0.00897289 | 24.00 | 0.00889591 | 47.8215 | 981623.31 | 0.00 | 2608787.48 | 1681700.28 | 97.16018570 | 27.52 | 20.07 | 0.01165415 | 57394.9 | 10.66 | 10.54 | 0.00786884 | 30544.5 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 240175.328 | 240175.328 | 24.226112 | 0.00530638 | 3662.544 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.753706 | 97.16018570 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 8.0986 | 9.737348 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 203775.81 | 240175.33 | 1.0000 | 29.14805571 | 24.226112 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 5.30583909 | 60.00 | 49.00 | 11.00 | 0.000 | 203775.81 | 4.60 | 0.00525715 | 4.60 | 25.38036000 | 104.7645 | 20.76 | 0.00780639 | 21.00 | 0.00780639 | 50.4411 | 431561.27 | 0.00 | 215560.24 | 215560.24 | 29.14805571 | 12.80 | 8.63 | 0.00525715 | 26134.9 | 20.09 | 11.83 | 0.00525715 | 33530.2 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 234367.659 | -999.000 | 8.390178 | 0.00997054 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.7014 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.390178 | 10.09478416 | 4197.9300 | 999.8980 | 128.71070523 | 12.27 | 6.67 | 5.60 | 3025783.77 | 7.7457 | 7.745684 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 15:50:00 | 234367.66 | 159916.00 | 1.0000 | 10.09478416 | 8.390178 | 26.98 | 19.56 | 0.01122212 | 55742.9 | 11.43 | 12.09 | 0.00828381 | 34322.2 | 9.96952492 | 6.67 | 10.65 | 5.60 | 18130.727 | 216236.93 | 33.82 | 0.01651377 | 25.08 | 2.53804000 | 30.2501 | 24.00 | 0.00891209 | 24.00 | 0.00889026 | 47.7916 | 114856.00 | 0.00 | 254347.17 | 168917.68 | 10.09478416 | 26.98 | 19.57 | 0.01122212 | 55742.9 | 10.67 | 10.54 | 0.00786492 | 30547.0 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 24953.823 | 24953.823 | 2.517053 | 0.00055132 | 380.532 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.390178 | 10.09478416 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 0.8414 | 1.011694 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 09:50:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21171.97 | 24953.82 | 1.0000 | 3.02843525 | 2.517053 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 12.80 | 11.58 | 0.00800000 | 33059.8 | 0.55126799 | 60.00 | 49.00 | 11.00 | 0.000 | 21171.97 | 4.60 | 0.00525715 | 4.60 | 2.53804000 | 100.8338 | 21.00 | 0.00795913 | 21.00 | 0.00790978 | 51.1001 | 59002.25 | 0.00 | 22396.36 | 22396.36 | 3.02843525 | 12.80 | 8.63 | 0.00525715 | 26134.9 | 20.09 | 11.83 | 0.00525715 | 33530.2 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 430226.637 | 309604.576 | 21.231423 | 0.01053622 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8789 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 06:10:00 | 459846.28 | 451310.47 | 0.9356 | -999.0 | -999.0 | 28.51 | 18.02 | 0.00862793 | 50685.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 459846.28 | 33.90 | 0.01651378 | 25.10 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 369601.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9209.769 | 6667.790 | 0.460173 | 0.00022555 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1471 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 9865.75 | 9470.83 | 0.9335 | -999.0 | -999.0 | 27.91 | 17.94 | 0.00877222 | 50443.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9865.75 | 26.05 | 0.01651378 | 23.02 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 8024.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 87574.789 | 63339.892 | 4.367541 | 0.00214470 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1742 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:20:00 | 93783.66 | 89836.36 | 0.9338 | -999.0 | -999.0 | 27.91 | 17.95 | 0.00878681 | 50478.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93783.66 | 26.05 | 0.01651378 | 23.02 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 76159.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8883.219 | 6392.257 | 0.438840 | 0.00021755 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1717 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:30:00 | TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9496.81 | 9103.27 | 0.9354 | -999.0 | -999.0 | 28.10 | 18.01 | 0.00878546 | 50671.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9496.81 | 31.41 | 0.01651378 | 24.46 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2570 | 7651.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 430226.637 | 430226.637 | 21.231423 | 0.01053622 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 430226.64 | 430226.64 | 1.0000 | 25.54494545 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 430226.64 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5937 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9209.769 | 9209.769 | 0.460173 | 0.00022555 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9209.77 | 9209.77 | 1.0000 | 0.55366443 | 0.460173 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9209.77 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.3968 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87574.789 | 87574.789 | 4.367541 | 0.00214470 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 87574.79 | 87574.79 | 1.0000 | 5.25488055 | 4.367541 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87574.79 | 4.60 | 0.00525715 | 4.60 | 0.15631366 | 3.5790 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8883.219 | 8883.219 | 0.438840 | 0.00021755 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2032 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8883.22 | 8883.22 | 1.0000 | 0.52799805 | 0.438840 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8883.22 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.5620 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 14481.982 | 14481.982 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.231423 | 25.54494545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 14481.98 | 14481.98 | 1.0000 | 25.54494545 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14481.98 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5937 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.231423 | 25.54494545 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 922116.09 | 1.0000 | 25.54494545 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5937 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1024880.474 | 1024880.474 | 21.231423 | 0.02264348 | 19087.521 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.231423 | 25.54494545 | 4197.9300 | 999.8980 | 54.48957248 | 71.00 | 82.00 | 11.00 | 2516177.52 | 32.7545 | 41.551385 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 824161.48 | 922116.09 | 1.0000 | 25.54494545 | 21.231423 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 22.64117188 | 60.00 | 49.00 | 11.00 | 0.000 | 824161.48 | 4.60 | 0.00525715 | 4.60 | 0.33837161 | 1.5937 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | 0.00 | 0.00 | 25.54494545 | 16.60 | 4.14 | 0.00008378 | 16892.5 | 16.60 | 4.14 | 0.00008378 | 16892.5 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.460173 | 0.55366443 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 1.0000 | 0.55366443 | 0.460173 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.01 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.3968 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 6690.076 | 6690.076 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.367541 | 5.25488055 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 6690.08 | 6690.08 | 1.0000 | 5.25488055 | 4.367541 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 6690.08 | 4.60 | 0.00525715 | 4.60 | 0.15631366 | 3.5790 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 669.008 | 669.008 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2032 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.438840 | 0.52799805 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 669.01 | 669.01 | 1.0000 | 0.52799805 | 0.438840 | 4.60 | 4.60 | 0.00525715 | 17815.0 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 669.01 | 4.60 | 0.00525715 | 4.60 | 0.01563137 | 3.5620 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2726 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.53 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 8.77 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 25.38 | 80.75 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 8.39 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 4959.17 | 1895.83 | 1846.50 |
CORE_BOTTOM | 4799.83 | 87.67 | 0.00 |
CORE_MID | 3142.83 | 879.83 | 0.00 |
CORE_TOP | 3260.00 | 1482.67 | 19.83 |
PERIMETER_BOT_ZN_3 | 4183.50 | 1017.17 | 23.17 |
PERIMETER_BOT_ZN_2 | 3315.83 | 1705.33 | 67.33 |
PERIMETER_BOT_ZN_1 | 4602.83 | 732.50 | 134.33 |
PERIMETER_BOT_ZN_4 | 4924.33 | 644.00 | 207.50 |
PERIMETER_MID_ZN_3 | 3518.00 | 2110.50 | 251.83 |
PERIMETER_MID_ZN_2 | 2402.00 | 2161.17 | 240.67 |
PERIMETER_MID_ZN_1 | 4288.33 | 1224.17 | 293.17 |
PERIMETER_MID_ZN_4 | 3254.67 | 2084.83 | 203.00 |
PERIMETER_TOP_ZN_3 | 3491.67 | 2453.00 | 478.50 |
PERIMETER_TOP_ZN_2 | 3157.33 | 2545.33 | 402.00 |
PERIMETER_TOP_ZN_1 | 3985.83 | 1636.67 | 393.83 |
PERIMETER_TOP_ZN_4 | 3104.17 | 2441.83 | 330.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5446.83 | 4199.17 | 2235.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 125.33 | 0.00 | 13.17 |
CORE_BOTTOM | 0.00 | 1.83 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.17 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 8.50 | 0.00 | 8.50 |
PERIMETER_BOT_ZN_1 | 0.00 | 55.33 | 0.00 | 55.17 |
PERIMETER_BOT_ZN_4 | 0.00 | 95.33 | 0.00 | 33.83 |
PERIMETER_MID_ZN_3 | 0.00 | 0.33 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 11.00 | 0.00 | 11.00 |
PERIMETER_MID_ZN_1 | 0.00 | 92.17 | 0.00 | 92.00 |
PERIMETER_MID_ZN_4 | 0.00 | 11.00 | 0.00 | 7.17 |
PERIMETER_TOP_ZN_3 | 2.00 | 1.50 | 0.33 | 1.17 |
PERIMETER_TOP_ZN_2 | 1.50 | 15.83 | 0.00 | 15.83 |
PERIMETER_TOP_ZN_1 | 0.50 | 40.17 | 0.00 | 39.17 |
PERIMETER_TOP_ZN_4 | 0.67 | 16.67 | 0.00 | 11.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 1.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 1.83 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 255.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 2.17 | 610.67 | 0.33 | 186.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.003 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.782 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.706 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.673 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.832 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.109 | 0.036 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.085 | 0.035 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.572 | 0.036 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.764 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.104 | 0.086 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.041 | 0.079 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.229 | 0.082 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.793 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.164 | 0.101 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.025 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.254 | 0.101 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 31407.74 | 372728.50 | 22-JAN-10:10 | 1905774.96 | 03-AUG-16:00 |
Electricity:Building | 18521.16 | 249962.80 | 01-JAN-08:50 | 1093898.18 | 12-DEC-08:10 |
Electricity:Zone:BASEMENT | 635.35 | 14476.27 | 01-JAN-06:10 | 31794.69 | 02-JAN-08:10 |
InteriorLights:Electricity | 3307.88 | 15753.54 | 01-JAN-08:50 | 300301.40 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:BASEMENT | 210.95 | 1018.73 | 01-JAN-06:10 | 18337.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3307.88 | 15753.54 | 01-JAN-08:50 | 300301.40 | 25-OCT-07:10 |
Electricity:Zone:CORE_BOTTOM | 510.73 | 6957.75 | 01-JAN-06:10 | 34596.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 189.45 | 914.89 | 01-JAN-06:10 | 16468.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5107.28 | 69577.31 | 01-JAN-06:10 | 345965.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1894.51 | 9148.91 | 01-JAN-06:10 | 164680.46 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 510.73 | 6957.73 | 01-JAN-06:10 | 34596.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 189.45 | 914.89 | 01-JAN-06:10 | 16468.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 58.89 | 842.63 | 01-JAN-08:50 | 4212.42 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.54 | 83.86 | 01-JAN-08:50 | 1936.10 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 37.94 | 543.02 | 01-JAN-07:50 | 2698.74 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.94 | 54.04 | 01-JAN-07:50 | 1231.79 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.82 | 842.65 | 01-JAN-08:00 | 4204.40 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.48 | 83.86 | 01-JAN-08:00 | 1928.05 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 37.93 | 543.02 | 01-JAN-08:50 | 2721.33 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.94 | 54.04 | 01-JAN-08:50 | 1254.39 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 588.96 | 8426.32 | 01-JAN-08:50 | 42162.37 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 185.55 | 838.59 | 01-JAN-08:50 | 19399.19 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 379.42 | 5430.24 | 01-JAN-07:50 | 26999.77 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 119.45 | 540.42 | 01-JAN-07:50 | 12330.31 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 588.26 | 8426.45 | 01-JAN-08:00 | 42085.59 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 184.84 | 838.61 | 01-JAN-08:00 | 19322.06 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 379.37 | 5430.21 | 01-JAN-08:50 | 27218.98 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.40 | 540.42 | 01-JAN-08:50 | 12549.62 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 58.90 | 842.63 | 01-JAN-08:50 | 4216.12 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.56 | 83.86 | 01-JAN-08:50 | 1939.80 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 37.94 | 543.02 | 01-JAN-07:50 | 2699.92 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.94 | 54.04 | 01-JAN-07:50 | 1232.98 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 58.83 | 842.65 | 01-JAN-08:00 | 4208.44 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.48 | 83.86 | 01-JAN-08:00 | 1932.09 | 25-OCT-07:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 37.94 | 543.02 | 01-JAN-08:50 | 2721.82 | 25-OCT-07:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.94 | 54.04 | 01-JAN-08:50 | 1254.89 | 25-OCT-07:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7554.34 | 95195.37 | 01-JAN-06:10 | 384802.81 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 59.48 | 287.24 | 01-JAN-06:10 | 5170.29 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.63 | 1961.87 | 01-JAN-06:10 | 8033.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.75 | 13.27 | 01-JAN-06:10 | 238.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1566.28 | 19618.75 | 01-JAN-06:10 | 80332.68 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 27.48 | 132.69 | 01-JAN-06:10 | 2388.46 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.63 | 1961.87 | 01-JAN-06:10 | 8033.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.75 | 13.27 | 01-JAN-06:10 | 238.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 5150.29 | 66876.05 | 05-JAN-01:40 | 336989.28 | 18-APR-14:50 |
ExteriorEquipment:Electricity | 1987.96 | 13873.41 | 01-JAN-00:10 | 128035.42 | 25-OCT-07:20 |
Transformer:ExteriorEquipment:Electricity | 87.06 | 1613.62 | 01-JAN-00:10 | 5437.44 | 25-OCT-07:20 |
ElectricityPurchased:Facility | 31407.74 | 372728.50 | 22-JAN-10:10 | 1905774.96 | 03-AUG-16:00 |
ElectricityPurchased:Plant | 31407.74 | 372728.50 | 22-JAN-10:10 | 1905774.96 | 03-AUG-16:00 |
Cogeneration:ElectricityPurchased | 31407.74 | 372728.50 | 22-JAN-10:10 | 1905774.96 | 03-AUG-16:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 31407.74 | 372728.50 | 22-JAN-10:10 | 1905774.96 | 03-AUG-16:00 |
ElectricityNet:Plant | 31407.74 | 372728.50 | 22-JAN-10:10 | 1905774.96 | 03-AUG-16:00 |
Cogeneration:ElectricityNet | 31407.74 | 372728.50 | 22-JAN-10:10 | 1905774.96 | 03-AUG-16:00 |
Fans:Electricity | 2165.69 | 41100.24 | 01-JAN-00:10 | 168045.35 | 18-APR-14:50 |
General:Fans:Electricity | 2165.69 | 41100.24 | 01-JAN-00:10 | 168045.35 | 18-APR-14:50 |
ExteriorLights:Electricity | 654.37 | 0.00 | 01-JAN-07:30 | 53035.91 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 654.37 | 0.00 | 01-JAN-07:30 | 53035.91 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 66.16 | 0.00 | 01-JAN-00:10 | 5613.05 | 02-JAN-10:20 |
Cooling:Electricity | 5183.55 | 23831.64 | 05-JAN-01:40 | 456403.65 | 14-AUG-11:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 4.97 | 0.00 | 01-JAN-00:10 | 25734.20 | 13-FEB-22:40 |
Electricity:Plant | 5181.02 | 5988.49 | 05-JAN-02:10 | 448588.16 | 06-OCT-14:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 2357.15 | 0.00 | 01-JAN-00:10 | 298194.05 | 06-OCT-14:00 |
HeatRejection:Electricity | 1971.99 | 2641.21 | 05-JAN-02:10 | 93657.26 | 02-JAN-11:00 |
General:HeatRejection:Electricity | 557.77 | 0.00 | 01-JAN-00:10 | 44408.99 | 02-JAN-11:00 |
Pumps:Electricity | 851.87 | 3347.28 | 05-JAN-02:10 | 57775.26 | 07-AUG-14:40 |
General:Pumps:Electricity | 851.87 | 3347.28 | 05-JAN-02:10 | 57775.26 | 07-AUG-14:40 |
WIRED_LTG_ELECTRICITY | 92.95 | 0.00 | 01-JAN-00:10 | 8438.47 | 25-OCT-07:20 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 526.43 | 5695.87 | 09-JAN-00:50 | 758051.18 | 20-DEC-07:10 |
Gas:Plant | 526.43 | 5695.87 | 09-JAN-00:50 | 758051.18 | 20-DEC-07:10 |
WaterSystems:Gas | 445.35 | 5695.87 | 09-JAN-00:50 | 68572.57 | 20-DEC-13:20 |
Water Heater:WaterSystems:Gas | 445.35 | 5695.87 | 09-JAN-00:50 | 68572.57 | 20-DEC-13:20 |
Heating:Gas | 81.08 | 0.00 | 01-JAN-00:10 | 752355.31 | 20-DEC-07:10 |
Boiler:Heating:Gas | 81.08 | 0.00 | 01-JAN-00:10 | 752355.31 | 20-DEC-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 28771.73 | 112214.30 | 05-JAN-01:40 | 2624048.19 | 07-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 28771.73 | 112214.30 | 05-JAN-01:40 | 2624048.19 | 07-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 28771.73 | 112214.30 | 05-JAN-01:40 | 2624048.19 | 07-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 14602.00 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Water:Plant | 14600.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 14602.00 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
MainsWater:Plant | 14600.15 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 1.85 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-22:40 |
Humidifier:Water | 1.85 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-22:40 |
MainsWater:HVAC | 1.85 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-22:40 |
Humidifier:MainsWater | 1.85 | 0.00 | 01-JAN-00:10 | 0.00 | 13-FEB-22:40 |
HeatRejection:Water | 12319.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
HeatRejection:MainsWater | 12319.98 | 0.00 | 01-JAN-00:10 | 0.00 | 30-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 382.99 | 0.00 | 01-JAN-00:10 | 497907.32 | 06-FEB-07:10 |
PlantLoopHeatingDemand:Plant | 323.62 | 0.00 | 01-JAN-00:10 | 40640.57 | 23-JAN-12:10 |
WaterSystems:PlantLoopHeatingDemand | 323.62 | 0.00 | 01-JAN-00:10 | 40640.57 | 23-JAN-12:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 102217.52 | 173816.06 | 05-JAN-02:10 | 10191625.11 | 07-AUG-14:40 |
EnergyTransfer:Building | 21375.64 | 77604.70 | 05-JAN-02:10 | 1539567.57 | 30-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 758.01 | 0.00 | 01-JAN-00:10 | 80858.24 | 26-DEC-06:10 |
Heating:EnergyTransfer | 26.78 | 0.00 | 01-JAN-00:10 | 165080.39 | 06-FEB-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 12.19 | 0.00 | 01-JAN-00:10 | 60009.42 | 26-APR-04:00 |
Cooling:EnergyTransfer | 21348.86 | 77604.70 | 05-JAN-02:10 | 1539567.57 | 30-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 745.82 | 0.00 | 01-JAN-00:10 | 80858.24 | 26-DEC-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 749.08 | 0.00 | 01-JAN-00:10 | 53471.96 | 26-DEC-10:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 749.08 | 0.00 | 01-JAN-00:10 | 53471.96 | 26-DEC-10:10 |
EnergyTransfer:Zone:CORE_MID | 5623.75 | 0.00 | 01-JAN-00:10 | 441183.21 | 26-APR-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 5623.75 | 0.00 | 01-JAN-00:10 | 441183.21 | 26-APR-05:10 |
EnergyTransfer:Zone:CORE_TOP | 562.11 | 0.00 | 01-JAN-00:10 | 51484.22 | 07-JUL-15:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 0.12 | 0.00 | 01-JAN-00:10 | 26446.35 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 561.99 | 0.00 | 01-JAN-00:10 | 51484.22 | 07-JUL-15:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 104.61 | 0.00 | 01-JAN-00:10 | 10573.65 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 104.61 | 0.00 | 01-JAN-00:10 | 10573.65 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 87.25 | 0.00 | 01-JAN-00:10 | 9772.90 | 03-MAY-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 151.54 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 87.25 | 0.00 | 01-JAN-00:10 | 9772.90 | 03-MAY-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 129.84 | 0.00 | 01-JAN-00:10 | 14147.89 | 06-NOV-13:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 129.84 | 0.00 | 01-JAN-00:10 | 14147.89 | 06-NOV-13:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 126.23 | 0.00 | 01-JAN-00:10 | 14495.17 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 126.23 | 0.00 | 01-JAN-00:10 | 14495.17 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 784.91 | 0.00 | 01-JAN-00:10 | 94294.79 | 21-AUG-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 0.86 | 0.00 | 01-JAN-00:10 | 40705.17 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 784.05 | 0.00 | 01-JAN-00:10 | 94294.79 | 21-AUG-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 736.92 | 0.00 | 01-JAN-00:10 | 99891.42 | 03-MAY-09:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 0.49 | 0.00 | 01-JAN-00:10 | 30032.63 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 736.42 | 0.00 | 01-JAN-00:10 | 99891.42 | 03-MAY-09:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1050.71 | 0.00 | 01-JAN-00:10 | 132775.82 | 06-NOV-13:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 0.08 | 0.00 | 01-JAN-00:10 | 16835.96 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1050.62 | 0.00 | 01-JAN-00:10 | 132775.82 | 06-NOV-13:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 776.27 | 0.00 | 01-JAN-00:10 | 115488.52 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 0.18 | 0.00 | 01-JAN-00:10 | 18817.35 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 776.09 | 0.00 | 01-JAN-00:10 | 115488.52 | 30-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 83.31 | 0.00 | 01-JAN-00:10 | 10881.88 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 1.32 | 0.00 | 01-JAN-00:10 | 10881.88 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 81.99 | 0.00 | 01-JAN-00:10 | 10344.43 | 21-AUG-14:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 75.62 | 0.00 | 01-JAN-00:10 | 10103.46 | 03-MAY-09:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 0.66 | 0.00 | 01-JAN-00:10 | 7380.67 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 74.95 | 0.00 | 01-JAN-00:10 | 10103.46 | 03-MAY-09:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 107.24 | 0.00 | 01-JAN-00:10 | 14389.29 | 06-NOV-14:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 0.55 | 0.00 | 01-JAN-00:10 | 8396.41 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 106.69 | 0.00 | 01-JAN-00:10 | 14389.29 | 06-NOV-14:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 80.11 | 0.00 | 01-JAN-00:10 | 12218.47 | 30-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 0.39 | 0.00 | 01-JAN-00:10 | 5176.07 | 06-FEB-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 79.72 | 0.00 | 01-JAN-00:10 | 12218.47 | 30-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 86.95 | 0.00 | 01-JAN-00:10 | 8562.48 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.78 | 0.00 | 01-JAN-00:10 | 3047.09 | 31-DEC-11:00 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 86.17 | 0.00 | 01-JAN-00:10 | 8562.48 | 02-JAN-06:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 633.17 | 0.00 | 01-JAN-00:10 | 63890.46 | 10-OCT-16:00 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 3.99 | 0.00 | 01-JAN-00:10 | 21679.26 | 20-MAR-04:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 629.17 | 0.00 | 01-JAN-00:10 | 63890.46 | 10-OCT-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 102.09 | 0.00 | 01-JAN-00:10 | 18078.93 | 07-JUL-14:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 4.97 | 0.00 | 01-JAN-00:10 | 11582.68 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 97.12 | 0.00 | 01-JAN-00:10 | 18078.93 | 07-JUL-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.18 | 1026.18 | 05-JAN-08:00 | 7850.75 | 16-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 140.18 | 1026.18 | 05-JAN-08:00 | 7850.75 | 16-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1285.88 | 4940.89 | 22-JAN-08:10 | 73382.74 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1285.88 | 4940.89 | 22-JAN-08:10 | 73382.74 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.46 | 0.35 | 21-JAN-06:50 | 7465.11 | 16-APR-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.07 | 0.00 | 01-JAN-00:10 | 503.68 | 22-JAN-06:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 125.38 | 0.00 | 04-JAN-06:20 | 7465.11 | 16-APR-18:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.95 | 68771.60 | 05-JAN-02:10 | 377639.32 | 18-DEC-23:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.10 | 0.00 | 01-JAN-00:10 | 8619.49 | 21-JAN-23:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7165.85 | 68771.60 | 05-JAN-02:10 | 377639.32 | 18-DEC-23:30 |
EnergyTransfer:Plant | 50547.01 | 0.00 | 01-JAN-00:10 | 6324181.35 | 31-JUL-12:40 |
WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 40640.57 | 23-JAN-12:10 |
WaterUse:WaterSystems:EnergyTransfer | 323.62 | 0.00 | 01-JAN-00:10 | 40640.57 | 23-JAN-12:10 |
EnergyTransfer:HVAC | 30294.87 | 92239.46 | 05-JAN-01:40 | 3074343.93 | 07-AUG-13:00 |
HeatingCoils:EnergyTransfer | 59.37 | 0.00 | 01-JAN-00:10 | 484109.31 | 06-FEB-07:10 |
PlantLoopHeatingDemand:HVAC | 59.37 | 0.00 | 01-JAN-00:10 | 484109.31 | 06-FEB-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 59.37 | 0.00 | 01-JAN-00:10 | 484109.31 | 06-FEB-07:10 |
CoolingCoils:EnergyTransfer | 26086.06 | 92239.46 | 05-JAN-01:40 | 2477023.57 | 07-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 185.69 | 0.00 | 01-JAN-00:10 | 574185.74 | 20-DEC-07:50 |
HeatRecoveryForCooling:EnergyTransfer | 3963.75 | 0.00 | 01-JAN-00:10 | 921254.52 | 07-OCT-08:00 |
LoopToLoop:EnergyTransfer | 17747.19 | 0.00 | 01-JAN-00:10 | 1994863.58 | 31-JUL-12:40 |
Boilers:EnergyTransfer | 57.53 | 0.00 | 01-JAN-00:10 | 627519.68 | 20-DEC-07:10 |
Chillers:EnergyTransfer | 15030.76 | 0.00 | 01-JAN-00:10 | 2001608.37 | 31-JUL-12:40 |
HeatRejection:EnergyTransfer | 17387.91 | 0.00 | 01-JAN-00:10 | 2298882.34 | 31-JUL-12:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 12.189 | -745.825 | 0.000 | 0.000 | 92.669 | 210.953 | 424.397 | 0.000 | 0.000 | 0.000 | 5.616 | 0.000 | 0.000 | 0.000 | 0.000 | -0.003 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -749.078 | 0.000 | 0.000 | 83.458 | 189.451 | 321.278 | 0.000 | 0.000 | 0.000 | 154.890 | 0.000 | 0.000 | 0.000 | 0.000 | -0.000 |
CORE_MID | 0.000 | 0.000 | 0.000 | -5623.742 | 0.000 | 0.000 | 837.798 | 1894.509 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.010 | 0.000 | 0.000 | 0.000 | 0.000 | -321.337 |
CORE_TOP | 0.000 | 0.000 | 0.121 | -561.984 | 0.000 | 0.000 | 84.482 | 189.451 | 321.277 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -33.347 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -104.611 | 0.000 | 0.000 | 10.533 | 18.545 | 40.341 | 28.512 | 0.000 | 0.427 | 33.834 | 0.000 | -25.664 | 0.000 | -1.916 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -87.249 | 0.000 | 0.000 | 6.851 | 11.942 | 25.998 | 42.490 | 0.000 | 0.328 | 15.576 | 0.000 | -14.742 | 0.000 | -1.194 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.000 | -129.837 | 0.000 | 0.000 | 10.497 | 18.477 | 40.342 | 70.698 | 0.000 | 0.414 | 15.040 | 0.000 | -23.640 | 0.000 | -1.991 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -126.230 | 0.000 | 0.000 | 6.780 | 11.937 | 25.997 | 40.285 | 0.000 | 0.268 | 61.382 | 0.000 | -18.969 | 0.000 | -1.450 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 0.858 | -784.027 | 0.000 | 0.000 | 107.227 | 185.550 | 403.414 | 293.230 | 0.000 | 9.017 | 54.794 | 0.000 | -231.492 | 0.000 | -38.571 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 0.494 | -736.405 | 0.000 | 0.000 | 51.268 | 119.448 | 259.975 | 424.501 | 0.000 | 6.275 | 41.852 | 0.000 | -141.401 | 0.000 | -26.006 | -0.002 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 0.085 | -1050.597 | 0.000 | 0.000 | 105.302 | 184.842 | 403.420 | 705.745 | 0.000 | 8.420 | 0.045 | 0.000 | -231.437 | 0.000 | -44.161 | -81.618 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 0.184 | -776.064 | 0.000 | 0.000 | 69.894 | 119.395 | 259.973 | 416.117 | 0.000 | 6.045 | 91.095 | 0.000 | -158.882 | 0.000 | -27.758 | -0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 1.319 | -81.986 | 0.000 | 0.000 | 10.884 | 18.555 | 40.341 | 29.234 | 0.000 | 1.073 | 6.760 | 0.000 | -21.746 | 0.000 | -4.434 | 0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 0.663 | -74.952 | 0.000 | 0.000 | 7.015 | 11.945 | 25.998 | 42.355 | 0.000 | 0.735 | 2.836 | 0.000 | -13.553 | 0.000 | -3.042 | -0.001 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 0.546 | -106.691 | 0.000 | 0.000 | 10.649 | 18.484 | 40.342 | 70.540 | 0.000 | 1.006 | 0.000 | 0.000 | -22.040 | 0.000 | -5.144 | -7.692 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 0.392 | -79.720 | 0.000 | 0.000 | 7.085 | 11.940 | 25.997 | 41.543 | 0.000 | 0.742 | 10.423 | 0.000 | -15.144 | 0.000 | -3.257 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -140.180 | 0.000 | 0.000 | 0.000 | 2.748 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -16.448 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.000 | -1285.877 | 0.000 | 0.000 | 0.000 | 27.477 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -280.406 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.075 | -125.383 | 0.000 | 0.000 | 0.000 | 2.748 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -31.321 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.101 | -7165.865 | 0.000 | 0.000 | 0.000 | 59.480 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -388.573 |
GROUNDFLOOR_PLENUM | 0.780 | -86.171 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.708 | 88.716 | 0.000 | 0.000 | 0.000 | -4.033 | 0.000 |
MIDFLOOR_PLENUM | 3.993 | -629.163 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 12.966 | 680.330 | 0.000 | 0.000 | 0.000 | -68.127 | 0.000 |
TOPFLOOR_PLENUM | 4.972 | -97.116 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.141 | 98.128 | 0.000 | 0.000 | 0.000 | -7.125 | 0.000 |
Total Facility | 9.745 | -812.451 | 17.027 | -20536.305 | 0.000 | 0.000 | 1502.392 | 3307.876 | 15213.288 | 2205.251 | 0.000 | 49.566 | 1361.332 | 0.000 | -918.712 | 0.000 | -238.209 | -1160.750 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 13-FEB-00:07 | 0.00 | 0.00 | 0.00 | -119024.05 | 0.00 | 0.00 | 0.00 | 1103.96 | 13457.54 | 0.00 | 0.00 | 0.00 | 104462.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 26-SEP-03:02 | 0.00 | 0.00 | 0.00 | -93994.42 | 0.00 | 0.00 | 0.00 | 991.43 | 8057.15 | 0.00 | 0.00 | 0.00 | 84945.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 01-MAY-03:02 | 0.00 | 0.00 | 0.00 | -864266.05 | 0.00 | 0.00 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 773780.55 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 31-JUL-03:02 | 0.00 | 0.00 | 0.00 | -87099.92 | 0.00 | 0.00 | 0.00 | 991.43 | 8057.12 | 0.00 | 0.00 | 0.00 | 78051.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 28-JUN-03:01 | 0.00 | 0.00 | 0.00 | -12734.01 | 0.00 | 0.00 | 0.00 | 124.48 | 1011.70 | 0.00 | 0.00 | 14.64 | 11705.34 | 0.00 | -122.15 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:11 | 0.00 | 0.00 | 0.00 | -15872.08 | 0.00 | 0.00 | 23.75 | 54.04 | 488.98 | 11450.41 | 0.00 | 0.00 | 3858.86 | 0.00 | -0.00 | 0.00 | -3.96 | 0.00 |
PERIMETER_BOT_ZN_1 | 01-JAN-13:52 | 0.00 | 0.00 | 0.00 | -18353.77 | 0.00 | 0.00 | 34.76 | 83.86 | 758.78 | 15695.89 | 0.00 | 0.00 | 1810.38 | 0.00 | -0.00 | 0.00 | -29.91 | 0.00 |
PERIMETER_BOT_ZN_4 | 06-AUG-17:12 | 0.00 | 0.00 | 0.00 | -20372.29 | 0.00 | 0.00 | 0.00 | 58.56 | 488.98 | 4893.01 | 0.00 | 0.00 | 14955.52 | 0.00 | -0.00 | 0.00 | -23.79 | 0.00 |
PERIMETER_MID_ZN_3 | 21-AUG-03:02 | 0.00 | 0.00 | 0.00 | -130425.94 | 0.00 | 0.00 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 142.74 | 122689.77 | 0.00 | -3768.38 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 03-SEP-09:32 | 0.00 | 0.00 | 0.00 | -162771.47 | 0.00 | 0.00 | 238.95 | 540.42 | 4889.82 | 95990.55 | 0.00 | 529.47 | 60582.26 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 09-OCT-14:42 | 0.00 | 0.00 | 0.00 | -159340.65 | 0.00 | 0.00 | 375.34 | 838.61 | 7587.84 | 77452.53 | 0.00 | 2174.38 | 70911.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 29-MAY-16:52 | 0.00 | 0.00 | 0.00 | -173766.09 | 0.00 | 0.00 | 229.39 | 540.42 | 4889.79 | 92872.08 | 0.00 | 940.92 | 74293.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 25-JUN-16:22 | 0.00 | 0.00 | 0.00 | -14627.38 | 0.00 | 0.00 | 43.42 | 83.86 | 758.77 | 3498.25 | 0.00 | 135.35 | 10107.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 03-SEP-09:32 | 0.00 | 0.00 | 0.00 | -16502.27 | 0.00 | 0.00 | 23.66 | 54.04 | 488.98 | 9558.73 | 0.00 | 60.41 | 6316.45 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-14:42 | 0.00 | 0.00 | 0.00 | -17845.91 | 0.00 | 0.00 | 36.04 | 83.86 | 758.78 | 7630.59 | 0.00 | 196.92 | 9139.72 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 29-MAY-16:52 | 0.00 | 0.00 | 0.00 | -18792.78 | 0.00 | 0.00 | 21.68 | 54.04 | 488.98 | 9178.27 | 0.00 | 96.51 | 8953.31 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 16-APR-18:10 | 0.00 | 0.00 | 0.00 | -7850.75 | 0.00 | 0.00 | 0.00 | 14.38 | 7794.42 | 0.00 | 0.00 | 0.00 | 41.95 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 16-APR-18:16 | 0.00 | 0.00 | 0.00 | -73382.74 | 0.00 | 0.00 | 0.00 | 143.79 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4705.28 |
DATACENTER_TOP_ZN_6 | 16-APR-18:20 | 0.00 | 0.00 | 0.00 | -7465.11 | 0.00 | 0.00 | 0.00 | 14.38 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -343.69 |
DATACENTER_BASEMENT_ZN_6 | 26-NOV-06:32 | 0.00 | 0.00 | 0.00 | -417263.88 | 0.00 | 0.00 | 0.00 | 287.24 | 284724.39 | 0.00 | 0.00 | 0.00 | 132252.25 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 02-JAN-06:13 | 0.00 | -11381.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11435.66 | 0.00 | -0.00 | 0.00 | -53.99 | 0.00 |
MIDFLOOR_PLENUM | 30-JUN-05:01 | 0.00 | -100527.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100583.51 | 0.00 | -0.00 | 0.00 | -56.10 | 0.00 |
TOPFLOOR_PLENUM | 07-JUL-14:40 | 0.00 | -18078.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.71 | 17961.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 29-AUG-05:02 | 0.00 | -47403.06 | 0.00 | -1894070.23 | 0.00 | 0.00 | 15292.19 | 33955.19 | 623236.89 | 0.00 | 0.00 | 0.00 | 1305216.95 | 0.00 | -34603.56 | 0.00 | -1624.36 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 01-JUN-03:47 | 0.00 | 0.00 | 127589.75 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.96 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -142151.25 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 06-FEB-05:01 | 0.00 | 0.00 | 53259.83 | -0.00 | 0.00 | 0.00 | 0.00 | 1982.86 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -63299.81 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 21-DEC-06:01 | 0.00 | 0.00 | 1515.37 | -0.00 | 0.00 | 0.00 | 91.33 | 148.06 | 651.98 | 0.00 | 0.00 | 0.00 | 656.46 | 0.00 | -2993.09 | 0.00 | -70.10 | 0.00 |
PERIMETER_BOT_ZN_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 93111.81 | -0.00 | 0.00 | 0.00 | 0.00 | 2489.68 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -35115.13 | 0.00 | -4816.37 | -65786.95 |
PERIMETER_MID_ZN_2 | 21-DEC-06:01 | 0.00 | 0.00 | 82102.22 | -0.00 | 0.00 | 0.00 | 957.76 | 1480.58 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28438.13 | 0.00 | -1527.37 | -61094.82 |
PERIMETER_MID_ZN_1 | 06-FEB-06:01 | 0.00 | 0.00 | 99313.15 | -0.00 | 0.00 | 0.00 | 1449.31 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36956.89 | 0.00 | -1226.55 | -74993.67 |
PERIMETER_MID_ZN_4 | 21-DEC-06:01 | 0.00 | 0.00 | 68948.47 | -0.00 | 0.00 | 0.00 | 929.95 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28615.52 | 0.00 | -1575.81 | -47687.39 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:01 | 0.00 | 0.00 | 12555.85 | -0.00 | 0.00 | 0.00 | 0.00 | 124.48 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2762.39 | 0.00 | -516.21 | -10413.43 |
PERIMETER_TOP_ZN_2 | 06-FEB-04:01 | 0.00 | 0.00 | 11847.05 | -0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1897.91 | 0.00 | -359.70 | -10321.63 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 12847.84 | -0.00 | 0.00 | 0.00 | 0.00 | 124.49 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3049.31 | 0.00 | -586.83 | -10347.89 |
PERIMETER_TOP_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 10699.12 | -0.00 | 0.00 | 0.00 | 0.00 | 160.44 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2130.85 | 0.00 | -374.53 | -9006.16 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 05-JAN-04:02 | 0.00 | 0.00 | 520.96 | 0.00 | 0.00 | 0.00 | 0.00 | 14.38 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2483.95 |
DATACENTER_BASEMENT_ZN_6 | 21-JAN-23:43 | 0.00 | 0.00 | 44022.47 | 0.00 | 0.00 | 0.00 | 0.00 | 311.27 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -139241.87 |
GROUNDFLOOR_PLENUM | 22-DEC-04:01 | 11318.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -382.62 | -10935.71 |
MIDFLOOR_PLENUM | 22-MAY-03:02 | 83911.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -83967.70 |
TOPFLOOR_PLENUM | 03-JAN-06:01 | 19724.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -371.56 | -19353.11 |
Total Facility | 06-FEB-06:01 | -569087.51 | 543321.51 | 428503.53 | -543321.51 | 0.00 | 0.00 | 18644.69 | 33955.19 | 386654.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -146116.57 | 0.00 | -7087.66 | -145465.75 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.5319 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.5319 | 0.2169 | 1.0000 | 1.2001 | 0.2169 | ||
VAV_BOT WITH REHEAT | 9.4162 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.7692 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 86.8119 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 80.7537 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 8.9264 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.3902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.2314 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.2314 | 0.0159 | 1.0000 | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4602 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4602 | 0.0340 | 1.0000 | 0.0156 | 0.0340 | ||
AIRLOOP DATACENTER MID | 4.3675 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3675 | 0.0358 | 1.0000 | 0.1563 | 0.0358 | ||
AIRLOOP DATACENTER TOP | 0.4388 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4388 | 0.0356 | 1.0000 | 0.0156 | 0.0356 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.5319 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.5319 | 1.0000 | 1.0000 | 1.2001 | 0.2169 | ||
VAV_BOT WITH REHEAT | 4.7081 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.0162 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 43.4060 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 28.6236 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.4632 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.9652 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.2314 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.2314 | 1.0000 | 1.0000 | 0.3384 | 0.0159 | ||
AIRLOOP DATACENTER BOT | 0.4602 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4602 | 1.0000 | 1.0000 | 0.0156 | 0.0340 | ||
AIRLOOP DATACENTER MID | 4.3675 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3675 | 1.0000 | 1.0000 | 0.1563 | 0.0358 | ||
AIRLOOP DATACENTER TOP | 0.4388 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4388 | 1.0000 | 1.0000 | 0.0156 | 0.0356 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.5319 | 5.5319 | 5.5319 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6286 | 5.6286 | 1.8799 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.6596 | 52.6596 | 18.3256 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2240 | 5.2240 | 1.8545 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8371 | 0.8371 | 0.2511 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8822 | 0.8822 | 0.2647 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9400 | 0.9400 | 0.2820 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1284 | 1.1284 | 0.3385 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4836 | 7.4836 | 2.2975 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.8904 | 8.8904 | 2.6671 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.5217 | 8.5217 | 2.5565 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2565 | 9.2565 | 2.7770 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8598 | 0.8598 | 0.2579 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8970 | 0.8970 | 0.2691 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9518 | 0.9518 | 0.2855 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9939 | 0.9939 | 0.2982 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4602 | 0.4602 | 0.4602 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3675 | 4.3675 | 4.3675 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4388 | 0.4388 | 0.4388 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.2314 | 21.2314 | 21.2314 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.5319 | 5.5319 | 5.5319 | 5.5319 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 9.4162 | 8.7692 | 9.4162 | 3.0162 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 86.8119 | 80.7537 | 86.8119 | 28.6236 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 8.9264 | 8.3902 | 8.9264 | 2.9652 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2314 | 21.2314 | 21.2314 | 21.2314 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4602 | 0.4602 | 0.4602 | 0.4602 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3675 | 4.3675 | 4.3675 | 4.3675 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4388 | 0.4388 | 0.4388 | 0.4388 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.5319 | 5.5319 | 5.5319 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8143 | 2.8143 | 1.8799 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.3298 | 26.3298 | 18.3256 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6120 | 2.6120 | 1.8545 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4185 | 0.4185 | 0.2511 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4411 | 0.4411 | 0.2647 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4700 | 0.4700 | 0.2820 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5642 | 0.5642 | 0.3385 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.7418 | 3.7418 | 2.2975 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.4452 | 4.4452 | 2.6671 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2608 | 4.2608 | 2.5565 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6283 | 4.6283 | 2.7770 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4299 | 0.4299 | 0.2579 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4485 | 0.4485 | 0.2691 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4759 | 0.4759 | 0.2855 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4969 | 0.4969 | 0.2982 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4602 | 0.4602 | 0.4602 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3675 | 4.3675 | 4.3675 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4388 | 0.4388 | 0.4388 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.2314 | 21.2314 | 21.2314 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.5319 | 5.5319 | 5.5319 | 5.5319 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 4.7081 | 3.0162 | 3.0162 | 3.0162 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 43.4060 | 28.6236 | 28.6236 | 28.6236 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.4632 | 2.9652 | 2.9652 | 2.9652 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.2314 | 21.2314 | 21.2314 | 21.2314 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4602 | 0.4602 | 0.4602 | 0.4602 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3675 | 4.3675 | 4.3675 | 4.3675 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4388 | 0.4388 | 0.4388 | 0.4388 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 20:04:07
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 0.33 |
Number of hours cooling loads not met | 186.50 |
Number of hours not met | 186.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 81.08 | 752355.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2357.15 | 298194.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2826.40 | 158209.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3307.88 | 300301.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 654.37 | 53035.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.06 | 5437.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2165.69 | 168045.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 851.87 | 57775.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 557.77 | 44408.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 1414.22 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 4.97 | 25734.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 66.16 | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 445.35 | 68572.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 31407.74 |
Natural Gas | 0.00 | 526.43 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 31934.17 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 71.41 |
Space Heating | 0.00 |
Space Cooling | 111.91 |
Fans (All) | 46.75 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 678.05 |
Subtotal | 678.05 |
Natural Gas [MJ/m2] | |
Space Heating | 1.75 |
Service Water Heating | 9.61 |
Miscellaneous (All) | 11.36 |
Subtotal | 11.36 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.36 |
Space Heating | 0.25 |
Space Cooling | 16.23 |
Fans (All) | 6.78 |
Service Water Heating | 1.39 |
Receptacle Equipment | 47.64 |
Miscellaneous | 17.34 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2724. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.220890E+11 |
February | 0.000 | 0.141585E+11 |
March | 0.000 | 0.125703E+11 |
April | 0.000 | 0.170699E+10 |
May | 0.000 | 0.184973E+10 |
June | 0.000 | 0.724866E+09 |
July | 0.000 | 0.190987E+10 |
August | 0.000 | 0.138336E+10 |
September | 0.000 | 0.191106E+10 |
October | 0.000 | 0.231313E+10 |
November | 0.000 | 0.322217E+10 |
December | 0.000 | 0.172398E+11 |
Annual Sum or Average | 0.810788E+11 | |
Minimum of Months | 0.000 | 0.724866E+09 |
Maximum of Months | 0.000 | 0.220890E+11 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606155E+11 | 118701.03 | 09-JAN-04:01 | 8.83 | 7.21 | 0.566916E+10 | 7499.23 | 12-JAN-10:09 | 18.17 | 17.41 |
February | 0.531340E+11 | 119101.70 | 13-FEB-00:07 | 9.55 | 5.44 | 0.514131E+10 | 7499.10 | 09-FEB-10:00 | 15.00 | 12.67 |
March | 0.607516E+11 | 114999.99 | 20-MAR-01:52 | 12.80 | 8.59 | 0.613425E+10 | 7499.72 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.555890E+11 | 117244.94 | 03-APR-03:00 | 12.60 | 10.64 | 0.544989E+10 | 7499.32 | 12-APR-09:20 | 21.23 | 16.80 |
May | 0.604284E+11 | 103172.39 | 29-MAY-22:20 | 25.60 | 23.72 | 0.590318E+10 | 7498.81 | 05-MAY-09:20 | 27.43 | 22.39 |
June | 0.599460E+11 | 96656.55 | 11-JUN-23:08 | 25.60 | 21.41 | 0.588251E+10 | 7498.81 | 29-JUN-09:20 | 29.63 | 25.44 |
July | 0.623650E+11 | 103483.94 | 04-JUL-23:12 | 28.30 | 24.48 | 0.547497E+10 | 7498.80 | 14-JUL-09:20 | 24.27 | 23.35 |
August | 0.708973E+11 | 101313.90 | 13-AUG-22:50 | 27.62 | 25.21 | 0.613988E+10 | 7498.76 | 17-AUG-09:20 | 26.47 | 23.28 |
September | 0.641406E+11 | 106561.56 | 04-SEP-06:57 | 26.70 | 23.83 | 0.545484E+10 | 7498.78 | 28-SEP-09:20 | 24.97 | 22.80 |
October | 0.675888E+11 | 112653.38 | 28-OCT-03:50 | 11.17 | 5.75 | 0.567419E+10 | 7499.08 | 17-OCT-13:20 | 22.33 | 15.55 |
November | 0.658517E+11 | 116327.77 | 12-NOV-21:32 | 10.57 | 7.29 | 0.561829E+10 | 7503.06 | 10-NOV-10:09 | 22.75 | 18.15 |
December | 0.645073E+11 | 117529.69 | 17-DEC-17:53 | 12.00 | 9.31 | 0.547535E+10 | 7499.57 | 08-DEC-10:00 | 24.00 | 18.76 |
Annual Sum or Average | 0.745815E+12 | 0.680178E+11 | ||||||||
Minimum of Months | 0.531340E+11 | 96656.55 | 8.83 | 5.44 | 0.514131E+10 | 7498.76 | 15.00 | 12.67 | ||
Maximum of Months | 0.708973E+11 | 119101.70 | 28.30 | 25.21 | 0.613988E+10 | 7503.06 | 29.63 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.499521E+11 | 85891.23 | 01-JAN-02:11 | 17.00 | 15.08 | 0.507259E+10 | 6734.82 | 05-JAN-14:09 | 14.17 | 9.62 |
February | 0.480852E+11 | 88771.81 | 28-FEB-04:02 | 18.68 | 18.25 | 0.460419E+10 | 6734.74 | 17-FEB-10:20 | 6.07 | 1.69 |
March | 0.606238E+11 | 85303.23 | 29-MAR-03:02 | 17.55 | 17.34 | 0.549811E+10 | 6735.28 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.650483E+11 | 86015.88 | 01-APR-03:01 | 20.92 | 19.99 | 0.487753E+10 | 6734.89 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.618313E+11 | 93581.22 | 23-MAY-03:02 | 24.90 | 23.43 | 0.528128E+10 | 6734.43 | 22-MAY-09:09 | 26.93 | 23.34 |
June | 0.666720E+11 | 92824.07 | 01-JUN-03:02 | 21.95 | 21.06 | 0.526372E+10 | 6734.43 | 27-JUN-09:09 | 28.58 | 25.38 |
July | 0.712766E+11 | 82077.96 | 12-JUL-05:02 | 23.90 | 23.16 | 0.488804E+10 | 6734.43 | 13-JUL-09:30 | 24.45 | 23.19 |
August | 0.786984E+11 | 82530.71 | 01-AUG-03:01 | 24.15 | 22.81 | 0.549038E+10 | 6734.43 | 07-AUG-09:09 | 27.50 | 25.10 |
September | 0.601875E+11 | 94001.22 | 26-SEP-03:02 | 23.80 | 23.06 | 0.487552E+10 | 6734.42 | 26-SEP-09:09 | 22.80 | 22.01 |
October | 0.650230E+11 | 90233.23 | 19-OCT-03:02 | 20.33 | 18.25 | 0.507282E+10 | 6734.76 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.606846E+11 | 86063.61 | 28-NOV-04:02 | 17.92 | 16.44 | 0.502735E+10 | 6734.74 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.609959E+11 | 83309.02 | 15-DEC-04:01 | 20.17 | 20.17 | 0.489851E+10 | 6734.83 | 26-DEC-14:00 | 13.30 | 6.25 |
Annual Sum or Average | 0.749079E+12 | 0.608500E+11 | ||||||||
Minimum of Months | 0.480852E+11 | 82077.96 | 17.00 | 15.08 | 0.460419E+10 | 6734.42 | 6.07 | 1.69 | ||
Maximum of Months | 0.786984E+11 | 94001.22 | 24.90 | 23.43 | 0.549811E+10 | 6735.28 | 28.58 | 25.38 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.382672E+11 | 72408.38 | 19-JAN-05:02 | 19.00 | 19.00 | 0.503189E+10 | 6777.07 | 10-JAN-10:30 | 8.00 | 3.23 |
February | 0.359757E+11 | 76088.21 | 27-FEB-05:02 | 17.78 | 17.78 | 0.456558E+10 | 6784.58 | 17-FEB-10:00 | 7.20 | 2.43 |
March | 0.440364E+11 | 78414.72 | 30-MAR-05:02 | 20.83 | 19.77 | 0.546065E+10 | 6755.43 | 09-MAR-10:39 | 7.57 | 2.31 |
April | 0.447812E+11 | 80463.53 | 15-APR-04:02 | 21.10 | 20.39 | 0.485491E+10 | 6734.82 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.535128E+11 | 86432.22 | 01-MAY-03:02 | 25.27 | 22.91 | 0.526406E+10 | 6734.46 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.533641E+11 | 80136.27 | 07-JUN-03:01 | 21.10 | 18.25 | 0.524763E+10 | 6734.47 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.528414E+11 | 80788.63 | 06-JUL-03:02 | 26.02 | 24.42 | 0.487211E+10 | 6734.45 | 12-JUL-13:09 | 25.32 | 23.34 |
August | 0.554984E+11 | 78868.74 | 16-AUG-03:01 | 23.68 | 21.91 | 0.547667E+10 | 6734.46 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.503902E+11 | 80189.66 | 08-SEP-03:01 | 22.85 | 22.73 | 0.485187E+10 | 6734.44 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.501936E+11 | 79509.46 | 19-OCT-05:02 | 22.08 | 19.38 | 0.505192E+10 | 6734.79 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.435872E+11 | 77831.66 | 01-NOV-05:02 | 22.62 | 22.36 | 0.499527E+10 | 6734.75 | 13-NOV-10:09 | 16.47 | 13.02 |
December | 0.399272E+11 | 79076.10 | 15-DEC-06:02 | 21.00 | 21.00 | 0.485614E+10 | 6781.95 | 20-DEC-10:00 | 5.00 | 1.06 |
Annual Sum or Average | 0.562375E+12 | 0.605287E+11 | ||||||||
Minimum of Months | 0.359757E+11 | 72408.38 | 17.78 | 17.78 | 0.456558E+10 | 6734.44 | 5.00 | 1.06 | ||
Maximum of Months | 0.554984E+11 | 86432.22 | 26.02 | 24.42 | 0.547667E+10 | 6784.58 | 27.80 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.316966E+11 | 71717.66 | 20-JAN-06:02 | 17.00 | 17.00 | 0.480764E+10 | 6734.50 | 20-JAN-10:20 | 14.67 | 14.08 |
February | 0.319973E+11 | 73407.16 | 03-FEB-06:02 | 18.90 | 18.50 | 0.441208E+10 | 6734.58 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.401738E+11 | 77254.93 | 30-MAR-05:02 | 20.83 | 19.77 | 0.535325E+10 | 6734.63 | 24-MAR-09:09 | 19.03 | 14.06 |
April | 0.447112E+11 | 79545.09 | 22-APR-04:02 | 20.58 | 19.04 | 0.483657E+10 | 6734.82 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.581405E+11 | 86500.65 | 22-MAY-03:03 | 26.10 | 22.50 | 0.526865E+10 | 6734.42 | 22-MAY-09:09 | 26.93 | 23.34 |
June | 0.588767E+11 | 86818.44 | 30-JUN-03:02 | 23.48 | 22.93 | 0.525659E+10 | 6734.43 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.583042E+11 | 87103.72 | 31-JUL-03:02 | 23.98 | 23.18 | 0.488275E+10 | 6734.42 | 03-JUL-13:09 | 31.70 | 25.89 |
August | 0.604029E+11 | 85476.94 | 24-AUG-03:02 | 25.63 | 23.98 | 0.548296E+10 | 6734.42 | 22-AUG-13:09 | 31.28 | 25.58 |
September | 0.531758E+11 | 85788.42 | 05-SEP-03:03 | 22.62 | 22.62 | 0.485459E+10 | 6734.42 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.513653E+11 | 84563.94 | 06-OCT-03:02 | 26.67 | 25.45 | 0.504088E+10 | 6734.75 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.393867E+11 | 77866.96 | 01-NOV-05:02 | 22.62 | 22.36 | 0.492069E+10 | 6734.60 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.337558E+11 | 79291.63 | 16-DEC-06:02 | 20.83 | 19.18 | 0.470955E+10 | 6734.59 | 18-DEC-14:09 | 16.17 | 10.33 |
Annual Sum or Average | 0.561987E+12 | 0.598262E+11 | ||||||||
Minimum of Months | 0.316966E+11 | 71717.66 | 17.00 | 17.00 | 0.441208E+10 | 6734.42 | 14.67 | 10.33 | ||
Maximum of Months | 0.604029E+11 | 87103.72 | 26.67 | 25.45 | 0.548296E+10 | 6734.82 | 31.70 | 25.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.486513E+10 | 10180.01 | 19-JAN-06:01 | 18.83 | 18.83 | 0.614389E+09 | 845.62 | 24-JAN-14:39 | 17.00 | 10.56 |
February | 0.517234E+10 | 10109.32 | 28-FEB-06:01 | 18.38 | 17.90 | 0.566531E+09 | 845.62 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.684328E+10 | 10556.83 | 27-MAR-05:03 | 19.82 | 18.59 | 0.681942E+09 | 845.68 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.880763E+10 | 10729.07 | 24-APR-05:01 | 20.08 | 20.03 | 0.610709E+09 | 845.65 | 18-APR-13:50 | 27.62 | 15.12 |
May | 0.102387E+11 | 12320.77 | 22-MAY-04:41 | 26.10 | 22.50 | 0.664345E+09 | 845.59 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.114711E+11 | 12734.34 | 28-JUN-03:01 | 27.20 | 25.09 | 0.662042E+09 | 845.59 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.120742E+11 | 12499.66 | 05-JUL-03:01 | 25.60 | 23.97 | 0.615316E+09 | 845.59 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.129483E+11 | 12013.39 | 14-AUG-05:04 | 26.10 | 23.76 | 0.690282E+09 | 845.60 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.935479E+10 | 12055.16 | 18-SEP-03:02 | 25.00 | 22.99 | 0.613068E+09 | 845.59 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.946973E+10 | 12006.67 | 07-OCT-05:02 | 26.17 | 26.04 | 0.636230E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.708493E+10 | 10877.42 | 01-NOV-05:01 | 22.62 | 22.36 | 0.626789E+09 | 845.63 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.628240E+10 | 11065.95 | 11-DEC-06:01 | 20.83 | 20.26 | 0.604960E+09 | 845.63 | 26-DEC-14:00 | 13.30 | 6.25 |
Annual Sum or Average | 0.104613E+12 | 0.758660E+10 | ||||||||
Minimum of Months | 0.486513E+10 | 10109.32 | 18.38 | 17.90 | 0.566531E+09 | 845.59 | 13.30 | 6.25 | ||
Maximum of Months | 0.129483E+11 | 12734.34 | 27.20 | 26.04 | 0.690282E+09 | 845.68 | 27.80 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.457224E+10 | 7743.90 | 01-JAN-09:15 | 19.33 | 16.00 | 0.390568E+09 | 544.96 | 11-JAN-10:09 | 14.67 | 12.05 |
February | 0.468673E+10 | 7242.17 | 27-FEB-10:10 | 21.37 | 19.23 | 0.358958E+09 | 544.96 | 09-FEB-10:00 | 15.00 | 12.67 |
March | 0.619115E+10 | 9339.56 | 26-MAR-09:13 | 24.03 | 19.81 | 0.430441E+09 | 545.00 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.757536E+10 | 15383.52 | 23-APR-08:52 | 24.40 | 20.57 | 0.388311E+09 | 544.97 | 03-APR-09:09 | 19.27 | 14.10 |
May | 0.864687E+10 | 15872.85 | 29-MAY-08:11 | 27.07 | 22.69 | 0.426259E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.926779E+10 | 15322.57 | 11-JUN-08:42 | 27.33 | 20.83 | 0.424686E+09 | 544.93 | 13-JUN-13:09 | 32.98 | 21.36 |
July | 0.961930E+10 | 15506.76 | 16-JUL-09:52 | 31.10 | 25.82 | 0.394152E+09 | 544.93 | 17-JUL-13:09 | 33.40 | 24.54 |
August | 0.991209E+10 | 11075.69 | 06-AUG-09:52 | 30.00 | 26.94 | 0.441369E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.764149E+10 | 11998.29 | 10-SEP-09:23 | 33.80 | 27.02 | 0.392044E+09 | 544.93 | 27-SEP-13:09 | 23.30 | 22.57 |
October | 0.786889E+10 | 11173.74 | 15-OCT-08:53 | 23.00 | 19.56 | 0.405926E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.599220E+10 | 10572.41 | 12-NOV-08:30 | 7.75 | 4.23 | 0.398118E+09 | 544.96 | 09-NOV-10:09 | 15.27 | 8.87 |
December | 0.527595E+10 | 5204.17 | 08-DEC-09:40 | 19.00 | 15.12 | 0.374951E+09 | 544.96 | 04-DEC-10:00 | 13.00 | 9.82 |
Annual Sum or Average | 0.872501E+11 | 0.482578E+10 | ||||||||
Minimum of Months | 0.457224E+10 | 5204.17 | 7.75 | 4.23 | 0.358958E+09 | 544.93 | 13.00 | 8.87 | ||
Maximum of Months | 0.991209E+10 | 15872.85 | 33.80 | 27.02 | 0.441369E+09 | 545.00 | 33.40 | 24.54 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.878314E+10 | 18355.76 | 01-JAN-13:52 | 26.00 | 17.86 | 0.629193E+09 | 901.16 | 19-JAN-14:20 | 25.00 | 21.53 |
February | 0.840386E+10 | 16991.09 | 26-FEB-13:23 | 26.35 | 19.08 | 0.572229E+09 | 893.02 | 27-FEB-14:20 | 25.70 | 20.07 |
March | 0.876954E+10 | 12848.76 | 05-MAR-11:54 | 26.60 | 18.35 | 0.679586E+09 | 845.69 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.978557E+10 | 11978.22 | 24-APR-05:01 | 20.08 | 20.03 | 0.609404E+09 | 847.88 | 18-APR-13:50 | 27.62 | 15.12 |
May | 0.105117E+11 | 13542.31 | 08-MAY-05:02 | 23.90 | 21.88 | 0.663791E+09 | 845.61 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.114886E+11 | 13579.29 | 14-JUN-03:01 | 25.00 | 22.65 | 0.661602E+09 | 845.61 | 01-JUN-13:09 | 23.90 | 20.93 |
July | 0.123157E+11 | 13922.90 | 05-JUL-03:01 | 25.60 | 23.97 | 0.614962E+09 | 845.61 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.138522E+11 | 13240.36 | 14-AUG-05:04 | 26.10 | 23.76 | 0.690154E+09 | 845.61 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.108293E+11 | 16672.80 | 10-SEP-12:43 | 35.03 | 27.77 | 0.613193E+09 | 845.61 | 20-SEP-13:39 | 26.60 | 22.71 |
October | 0.130355E+11 | 17105.32 | 01-OCT-13:42 | 27.87 | 18.50 | 0.639673E+09 | 885.03 | 13-OCT-13:39 | 32.73 | 23.23 |
November | 0.113940E+11 | 17118.24 | 11-NOV-11:13 | 26.27 | 21.96 | 0.634469E+09 | 929.03 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.106691E+11 | 17313.92 | 10-DEC-11:13 | 26.33 | 20.63 | 0.614345E+09 | 911.27 | 15-DEC-14:30 | 29.00 | 21.82 |
Annual Sum or Average | 0.129838E+12 | 0.762260E+10 | ||||||||
Minimum of Months | 0.840386E+10 | 11978.22 | 20.08 | 17.86 | 0.572229E+09 | 845.61 | 16.97 | 14.65 | ||
Maximum of Months | 0.138522E+11 | 18355.76 | 35.03 | 27.77 | 0.690154E+09 | 929.03 | 32.73 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625522E+10 | 13885.41 | 19-JAN-06:01 | 18.83 | 18.83 | 0.390389E+09 | 544.94 | 13-JAN-14:00 | 15.00 | 11.60 |
February | 0.687177E+10 | 20124.88 | 26-FEB-17:22 | 23.85 | 19.57 | 0.366035E+09 | 544.96 | 09-FEB-14:00 | 22.20 | 14.68 |
March | 0.930341E+10 | 17246.92 | 30-MAR-03:01 | 20.88 | 19.84 | 0.443171E+09 | 545.00 | 23-MAR-09:09 | 16.78 | 14.62 |
April | 0.122716E+11 | 19747.94 | 23-APR-16:52 | 27.20 | 21.70 | 0.395874E+09 | 544.99 | 18-APR-13:50 | 27.62 | 15.12 |
May | 0.103986E+11 | 19257.55 | 29-MAY-16:22 | 31.70 | 23.59 | 0.426625E+09 | 544.93 | 31-MAY-13:09 | 23.27 | 21.48 |
June | 0.122921E+11 | 19569.89 | 11-JUN-16:32 | 32.93 | 21.66 | 0.426706E+09 | 544.93 | 13-JUN-13:09 | 32.98 | 21.36 |
July | 0.136250E+11 | 20308.07 | 30-JUL-15:42 | 27.38 | 24.30 | 0.397067E+09 | 544.93 | 12-JUL-13:39 | 24.47 | 22.46 |
August | 0.158111E+11 | 20374.06 | 06-AUG-17:12 | 25.67 | 23.79 | 0.445554E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.981763E+10 | 20216.45 | 10-SEP-16:41 | 33.30 | 26.75 | 0.393380E+09 | 544.93 | 07-SEP-13:39 | 26.07 | 23.43 |
October | 0.109799E+11 | 20353.55 | 08-OCT-16:02 | 30.67 | 25.12 | 0.410372E+09 | 544.96 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.928871E+10 | 19596.19 | 05-NOV-15:12 | 27.20 | 19.88 | 0.406302E+09 | 544.97 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.931608E+10 | 17576.38 | 15-DEC-04:01 | 20.17 | 20.17 | 0.395834E+09 | 544.97 | 26-DEC-14:00 | 13.30 | 6.25 |
Annual Sum or Average | 0.126231E+12 | 0.489731E+10 | ||||||||
Minimum of Months | 0.625522E+10 | 13885.41 | 18.83 | 18.83 | 0.366035E+09 | 544.93 | 13.30 | 6.25 | ||
Maximum of Months | 0.158111E+11 | 20374.06 | 33.30 | 26.75 | 0.445554E+09 | 545.00 | 32.98 | 24.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.339545E+10 | 5286.34 | 31-JAN-15:00 | 25.00 | 21.54 | 0.567461E+09 | 845.59 | 02-JAN-14:09 | 26.17 | 18.42 |
February | 0.360096E+10 | 7280.30 | 28-FEB-06:01 | 18.38 | 17.90 | 0.534293E+09 | 845.59 | 03-FEB-14:00 | 13.30 | 11.68 |
March | 0.459020E+10 | 8931.62 | 30-MAR-05:01 | 20.83 | 19.77 | 0.649988E+09 | 845.61 | 20-MAR-13:00 | 17.20 | 11.47 |
April | 0.578631E+10 | 10618.28 | 29-APR-05:02 | 23.20 | 21.68 | 0.603128E+09 | 845.63 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.895357E+10 | 12676.05 | 08-MAY-03:02 | 24.40 | 22.09 | 0.664051E+09 | 845.59 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.949461E+10 | 12795.51 | 29-JUN-03:02 | 25.60 | 24.37 | 0.662144E+09 | 845.59 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.938608E+10 | 12844.35 | 07-JUL-03:02 | 26.02 | 24.08 | 0.615705E+09 | 845.59 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.952587E+10 | 13047.57 | 21-AUG-03:02 | 26.27 | 23.88 | 0.690647E+09 | 845.59 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.781546E+10 | 11662.09 | 11-SEP-03:02 | 25.70 | 23.86 | 0.612085E+09 | 845.59 | 07-SEP-13:39 | 26.07 | 23.43 |
October | 0.724035E+10 | 10892.38 | 24-OCT-05:02 | 24.83 | 24.83 | 0.632271E+09 | 845.64 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.478590E+10 | 10714.25 | 02-NOV-05:02 | 23.38 | 22.55 | 0.606148E+09 | 845.61 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.383007E+10 | 9548.61 | 15-DEC-06:01 | 21.00 | 21.00 | 0.558760E+09 | 845.60 | 01-DEC-14:00 | 24.00 | 16.59 |
Annual Sum or Average | 0.784048E+11 | 0.739668E+10 | ||||||||
Minimum of Months | 0.339545E+10 | 5286.34 | 18.38 | 17.90 | 0.534293E+09 | 845.59 | 13.30 | 10.89 | ||
Maximum of Months | 0.952587E+10 | 13047.57 | 26.27 | 24.83 | 0.690647E+09 | 845.64 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.367279E+10 | 5885.20 | 19-JAN-09:50 | 22.67 | 20.80 | 0.264915E+09 | 521.18 | 19-JAN-11:20 | 25.13 | 21.56 |
February | 0.380709E+10 | 6303.47 | 27-FEB-10:00 | 21.10 | 19.21 | 0.249322E+09 | 521.21 | 09-FEB-11:09 | 16.10 | 12.99 |
March | 0.495194E+10 | 10019.40 | 30-MAR-05:01 | 20.83 | 19.77 | 0.303127E+09 | 521.24 | 23-MAR-08:00 | 16.60 | 14.60 |
April | 0.594759E+10 | 15666.15 | 23-APR-09:43 | 25.82 | 20.98 | 0.282433E+09 | 522.18 | 18-APR-15:30 | 28.00 | 15.83 |
May | 0.812333E+10 | 15956.00 | 29-MAY-08:11 | 27.07 | 22.69 | 0.312792E+09 | 521.19 | 09-MAY-14:20 | 31.33 | 21.91 |
June | 0.831083E+10 | 12311.45 | 29-JUN-03:01 | 25.60 | 24.37 | 0.311841E+09 | 521.20 | 12-JUN-12:09 | 31.70 | 20.33 |
July | 0.824695E+10 | 15381.40 | 16-JUL-10:43 | 30.68 | 26.01 | 0.290701E+09 | 521.20 | 05-JUL-12:09 | 32.20 | 26.45 |
August | 0.818544E+10 | 13375.06 | 27-AUG-08:22 | 28.00 | 23.69 | 0.324156E+09 | 521.19 | 30-AUG-12:09 | 31.18 | 24.69 |
September | 0.691856E+10 | 16275.04 | 03-SEP-09:32 | 29.97 | 24.53 | 0.286214E+09 | 521.20 | 01-SEP-10:20 | 30.17 | 24.71 |
October | 0.672538E+10 | 15536.40 | 09-OCT-09:23 | 28.05 | 22.45 | 0.294539E+09 | 521.20 | 26-OCT-14:09 | 24.17 | 14.42 |
November | 0.487824E+10 | 9289.06 | 02-NOV-05:01 | 23.38 | 22.55 | 0.280067E+09 | 521.19 | 06-NOV-13:20 | 27.57 | 20.86 |
December | 0.387428E+10 | 4521.24 | 10-DEC-09:32 | 22.67 | 19.12 | 0.254807E+09 | 521.17 | 01-DEC-09:00 | 16.00 | 12.60 |
Annual Sum or Average | 0.736424E+11 | 0.345491E+10 | ||||||||
Minimum of Months | 0.367279E+10 | 4521.24 | 20.83 | 19.12 | 0.249322E+09 | 521.17 | 16.00 | 12.60 | ||
Maximum of Months | 0.831083E+10 | 16275.04 | 30.68 | 26.01 | 0.324156E+09 | 522.18 | 32.20 | 26.45 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.763941E+10 | 15638.80 | 01-JAN-11:23 | 23.00 | 17.81 | 0.625441E+09 | 942.41 | 19-JAN-14:39 | 25.00 | 21.53 |
February | 0.711811E+10 | 15572.55 | 26-FEB-13:32 | 26.43 | 19.29 | 0.566967E+09 | 923.17 | 27-FEB-14:39 | 25.90 | 20.25 |
March | 0.671155E+10 | 12158.53 | 30-MAR-05:02 | 20.83 | 19.77 | 0.665882E+09 | 845.64 | 13-MAR-13:09 | 19.68 | 10.41 |
April | 0.684758E+10 | 12074.13 | 29-APR-05:02 | 23.20 | 21.68 | 0.604312E+09 | 845.66 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.920253E+10 | 13419.18 | 08-MAY-03:02 | 24.40 | 22.09 | 0.663497E+09 | 845.61 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.938532E+10 | 13242.90 | 26-JUN-03:01 | 25.50 | 23.65 | 0.661604E+09 | 845.61 | 13-JUN-13:09 | 32.98 | 21.36 |
July | 0.947533E+10 | 14323.13 | 05-JUL-03:02 | 25.60 | 23.97 | 0.615269E+09 | 845.61 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.103406E+11 | 14795.65 | 21-AUG-03:02 | 26.27 | 23.88 | 0.690552E+09 | 845.61 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.943655E+10 | 15262.88 | 10-SEP-12:43 | 35.03 | 27.77 | 0.612763E+09 | 845.61 | 20-SEP-13:39 | 26.60 | 22.71 |
October | 0.110975E+11 | 15930.49 | 09-OCT-14:42 | 29.33 | 22.80 | 0.641879E+09 | 917.44 | 13-OCT-13:50 | 32.87 | 23.23 |
November | 0.948523E+10 | 15560.37 | 05-NOV-15:12 | 27.20 | 19.88 | 0.634775E+09 | 966.20 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.832251E+10 | 15804.07 | 10-DEC-14:51 | 28.00 | 19.99 | 0.606597E+09 | 935.27 | 15-DEC-14:50 | 29.00 | 21.64 |
Annual Sum or Average | 0.105062E+12 | 0.758954E+10 | ||||||||
Minimum of Months | 0.671155E+10 | 12074.13 | 20.83 | 17.81 | 0.566967E+09 | 845.61 | 19.68 | 10.41 | ||
Maximum of Months | 0.110975E+11 | 15930.49 | 35.03 | 27.77 | 0.690552E+09 | 966.20 | 32.98 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403698E+10 | 7524.74 | 31-JAN-16:40 | 23.67 | 21.12 | 0.358408E+09 | 544.93 | 02-JAN-14:30 | 26.50 | 18.51 |
February | 0.425692E+10 | 11828.79 | 27-FEB-05:01 | 17.78 | 17.78 | 0.335802E+09 | 544.93 | 27-FEB-14:09 | 25.60 | 19.99 |
March | 0.522518E+10 | 11588.74 | 07-MAR-06:01 | 21.10 | 20.35 | 0.404659E+09 | 544.93 | 27-MAR-13:09 | 26.78 | 20.94 |
April | 0.641374E+10 | 15958.66 | 23-APR-17:53 | 25.50 | 21.27 | 0.380747E+09 | 544.94 | 12-APR-13:00 | 24.40 | 18.34 |
May | 0.801228E+10 | 17377.27 | 29-MAY-16:52 | 30.60 | 23.79 | 0.424537E+09 | 544.93 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.839720E+10 | 16092.82 | 11-JUN-17:12 | 32.93 | 21.73 | 0.424405E+09 | 544.93 | 13-JUN-13:09 | 32.98 | 21.36 |
July | 0.825191E+10 | 15939.91 | 30-JUL-16:22 | 27.20 | 24.52 | 0.394704E+09 | 544.93 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.867582E+10 | 14803.65 | 07-AUG-03:01 | 26.67 | 24.75 | 0.442943E+09 | 544.93 | 25-AUG-13:09 | 27.80 | 24.45 |
September | 0.728970E+10 | 17206.28 | 03-SEP-16:12 | 31.83 | 24.72 | 0.389346E+09 | 544.93 | 07-SEP-13:39 | 26.07 | 23.43 |
October | 0.719444E+10 | 16667.72 | 08-OCT-16:02 | 30.67 | 25.12 | 0.401302E+09 | 544.94 | 26-OCT-13:20 | 24.13 | 14.28 |
November | 0.533714E+10 | 11300.89 | 03-NOV-05:01 | 22.28 | 21.91 | 0.377870E+09 | 544.94 | 14-NOV-14:00 | 18.80 | 12.78 |
December | 0.451718E+10 | 11817.86 | 15-DEC-06:01 | 21.00 | 21.00 | 0.352657E+09 | 544.94 | 01-DEC-14:00 | 24.00 | 16.59 |
Annual Sum or Average | 0.776085E+11 | 0.468738E+10 | ||||||||
Minimum of Months | 0.403698E+10 | 7524.74 | 17.78 | 17.78 | 0.335802E+09 | 544.93 | 18.80 | 12.78 | ||
Maximum of Months | 0.867582E+10 | 17377.27 | 32.93 | 25.12 | 0.442943E+09 | 544.94 | 32.98 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.295837E+10 | 5542.18 | 31-JAN-15:50 | 25.00 | 21.54 | 0.534066E+09 | 845.59 | 02-JAN-14:39 | 26.67 | 18.56 |
February | 0.340359E+10 | 5934.54 | 22-FEB-14:40 | 25.37 | 20.29 | 0.510072E+09 | 845.59 | 03-FEB-14:00 | 13.30 | 11.68 |
March | 0.458031E+10 | 9179.15 | 30-MAR-05:01 | 20.83 | 19.77 | 0.621824E+09 | 845.59 | 24-MAR-13:39 | 24.77 | 16.15 |
April | 0.607071E+10 | 10663.55 | 29-APR-05:01 | 23.20 | 21.68 | 0.592390E+09 | 845.63 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.970836E+10 | 13967.33 | 08-MAY-03:02 | 24.40 | 22.09 | 0.663406E+09 | 845.59 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.103895E+11 | 14627.92 | 25-JUN-16:22 | 32.50 | 24.75 | 0.661904E+09 | 845.59 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.103104E+11 | 13979.41 | 27-JUL-03:02 | 25.50 | 23.65 | 0.615614E+09 | 845.59 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.103299E+11 | 14566.20 | 20-AUG-13:42 | 33.83 | 25.13 | 0.690109E+09 | 845.59 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.837082E+10 | 14520.68 | 10-SEP-16:41 | 33.30 | 26.75 | 0.610700E+09 | 845.59 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.762103E+10 | 14611.27 | 08-OCT-16:02 | 30.67 | 25.12 | 0.626254E+09 | 845.63 | 17-OCT-13:09 | 22.17 | 15.48 |
November | 0.473106E+10 | 10767.08 | 01-NOV-05:01 | 22.62 | 22.36 | 0.581375E+09 | 845.61 | 21-NOV-14:00 | 22.20 | 15.13 |
December | 0.351488E+10 | 10705.24 | 16-DEC-06:01 | 20.83 | 19.18 | 0.527671E+09 | 845.58 | 08-DEC-14:50 | 26.17 | 19.34 |
Annual Sum or Average | 0.819890E+11 | 0.723539E+10 | ||||||||
Minimum of Months | 0.295837E+10 | 5542.18 | 20.83 | 19.18 | 0.510072E+09 | 845.58 | 13.30 | 10.89 | ||
Maximum of Months | 0.103895E+11 | 14627.92 | 33.83 | 26.75 | 0.690109E+09 | 845.63 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318680E+10 | 5505.49 | 19-JAN-10:10 | 23.28 | 20.98 | 0.346696E+09 | 544.92 | 19-JAN-10:00 | 24.70 | 21.40 |
February | 0.348499E+10 | 5950.77 | 27-FEB-10:30 | 21.90 | 19.27 | 0.332350E+09 | 544.93 | 27-FEB-14:09 | 25.60 | 19.99 |
March | 0.470713E+10 | 7531.05 | 26-MAR-10:05 | 25.78 | 20.20 | 0.408060E+09 | 544.98 | 23-MAR-09:20 | 16.97 | 14.65 |
April | 0.602508E+10 | 15775.55 | 23-APR-09:53 | 26.10 | 21.06 | 0.383917E+09 | 544.97 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.866543E+10 | 16160.34 | 29-MAY-08:11 | 27.07 | 22.69 | 0.425855E+09 | 544.93 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.896444E+10 | 15627.25 | 04-JUN-10:23 | 30.00 | 23.97 | 0.425081E+09 | 544.93 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.891461E+10 | 15800.01 | 16-JUL-10:43 | 30.68 | 26.01 | 0.395107E+09 | 544.93 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.876923E+10 | 15732.62 | 06-AUG-09:52 | 30.00 | 26.94 | 0.442168E+09 | 544.93 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.728642E+10 | 16499.70 | 03-SEP-09:32 | 29.97 | 24.53 | 0.389977E+09 | 544.93 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.692873E+10 | 15783.93 | 09-OCT-10:02 | 29.17 | 22.66 | 0.400109E+09 | 544.94 | 26-OCT-13:30 | 24.10 | 14.32 |
November | 0.461874E+10 | 8182.35 | 02-NOV-05:01 | 23.38 | 22.55 | 0.375268E+09 | 544.93 | 14-NOV-10:39 | 19.20 | 11.72 |
December | 0.340285E+10 | 4442.80 | 10-DEC-09:53 | 24.00 | 19.92 | 0.336944E+09 | 544.92 | 15-DEC-14:09 | 29.00 | 21.99 |
Annual Sum or Average | 0.749544E+11 | 0.466153E+10 | ||||||||
Minimum of Months | 0.318680E+10 | 4442.80 | 21.90 | 19.27 | 0.332350E+09 | 544.92 | 16.97 | 10.89 | ||
Maximum of Months | 0.896444E+10 | 16499.70 | 30.68 | 26.94 | 0.442168E+09 | 544.98 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.660181E+10 | 17300.02 | 01-JAN-14:02 | 25.83 | 17.99 | 0.604038E+09 | 912.88 | 19-JAN-14:50 | 25.00 | 21.53 |
February | 0.658567E+10 | 17138.17 | 26-FEB-14:13 | 26.43 | 19.85 | 0.550690E+09 | 894.96 | 27-FEB-14:39 | 25.90 | 20.25 |
March | 0.647715E+10 | 12613.42 | 05-MAR-15:10 | 27.02 | 18.67 | 0.643746E+09 | 845.63 | 03-MAR-14:00 | 23.30 | 11.80 |
April | 0.711427E+10 | 11869.34 | 29-APR-05:01 | 23.20 | 21.68 | 0.593865E+09 | 845.66 | 10-APR-13:00 | 20.50 | 10.89 |
May | 0.998058E+10 | 15379.81 | 08-MAY-03:02 | 24.40 | 22.09 | 0.662427E+09 | 845.61 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.103113E+11 | 15731.56 | 25-JUN-16:22 | 32.50 | 24.75 | 0.660807E+09 | 845.61 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.104219E+11 | 15252.54 | 20-JUL-03:02 | 26.70 | 24.38 | 0.614830E+09 | 845.61 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.111580E+11 | 16265.70 | 20-AUG-13:42 | 33.83 | 25.13 | 0.689710E+09 | 845.61 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.100109E+11 | 17207.02 | 10-SEP-12:43 | 35.03 | 27.77 | 0.611171E+09 | 845.61 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.114260E+11 | 17841.39 | 09-OCT-14:42 | 29.33 | 22.80 | 0.635450E+09 | 899.40 | 13-OCT-13:00 | 33.00 | 23.23 |
November | 0.901625E+10 | 17262.17 | 11-NOV-11:32 | 26.43 | 22.11 | 0.621121E+09 | 935.54 | 06-NOV-14:09 | 28.30 | 21.02 |
December | 0.759048E+10 | 17204.80 | 10-DEC-13:52 | 27.00 | 20.21 | 0.583298E+09 | 907.68 | 15-DEC-14:50 | 29.00 | 21.64 |
Annual Sum or Average | 0.106694E+12 | 0.747115E+10 | ||||||||
Minimum of Months | 0.647715E+10 | 11869.34 | 23.20 | 17.99 | 0.550690E+09 | 845.61 | 20.50 | 10.89 | ||
Maximum of Months | 0.114260E+11 | 17841.39 | 35.03 | 27.77 | 0.689710E+09 | 935.54 | 33.00 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360767E+10 | 7768.03 | 31-JAN-16:40 | 23.67 | 21.12 | 0.343316E+09 | 544.90 | 19-JAN-14:00 | 25.00 | 21.53 |
February | 0.403983E+10 | 9309.24 | 27-FEB-06:02 | 17.70 | 17.70 | 0.323850E+09 | 544.92 | 22-FEB-14:00 | 25.00 | 20.07 |
March | 0.511358E+10 | 12258.49 | 06-MAR-06:01 | 18.80 | 18.03 | 0.389970E+09 | 544.93 | 27-MAR-13:09 | 26.78 | 20.94 |
April | 0.661238E+10 | 17245.60 | 23-APR-17:53 | 25.50 | 21.27 | 0.372265E+09 | 544.93 | 24-APR-13:09 | 27.28 | 23.57 |
May | 0.857638E+10 | 18793.48 | 29-MAY-16:52 | 30.60 | 23.79 | 0.422130E+09 | 544.93 | 03-MAY-13:09 | 31.88 | 21.90 |
June | 0.904257E+10 | 18399.06 | 25-JUN-16:22 | 32.50 | 24.75 | 0.422655E+09 | 544.93 | 12-JUN-13:09 | 31.78 | 20.54 |
July | 0.892018E+10 | 14431.49 | 20-JUL-03:01 | 26.70 | 24.38 | 0.393297E+09 | 544.93 | 14-JUL-13:09 | 26.93 | 25.44 |
August | 0.925230E+10 | 17126.58 | 06-AUG-17:12 | 25.67 | 23.79 | 0.440978E+09 | 544.93 | 25-AUG-13:20 | 27.90 | 24.41 |
September | 0.771914E+10 | 18661.21 | 03-SEP-16:12 | 31.83 | 24.72 | 0.385819E+09 | 544.93 | 07-SEP-13:00 | 24.40 | 22.88 |
October | 0.747438E+10 | 18047.67 | 08-OCT-16:02 | 30.67 | 25.12 | 0.395290E+09 | 544.94 | 26-OCT-13:20 | 24.13 | 14.28 |
November | 0.521760E+10 | 12113.88 | 03-NOV-05:01 | 22.28 | 21.91 | 0.364873E+09 | 544.93 | 08-NOV-14:00 | 22.70 | 16.44 |
December | 0.414639E+10 | 12769.52 | 16-DEC-06:01 | 20.83 | 19.18 | 0.337760E+09 | 544.92 | 11-DEC-14:39 | 24.67 | 22.83 |
Annual Sum or Average | 0.797224E+11 | 0.459220E+10 | ||||||||
Minimum of Months | 0.360767E+10 | 7768.03 | 17.70 | 17.70 | 0.323850E+09 | 544.90 | 22.70 | 14.28 | ||
Maximum of Months | 0.925230E+10 | 18793.48 | 32.50 | 25.12 | 0.440978E+09 | 544.94 | 31.88 | 25.44 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473477E+10 | 11381.85 | 02-JAN-06:13 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.478201E+10 | 8747.33 | 21-FEB-06:13 | 17.20 | 17.06 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.602176E+10 | 7299.05 | 20-MAR-05:13 | 12.00 | 7.67 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.694025E+10 | 8171.12 | 10-APR-05:13 | 12.20 | 7.43 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.805203E+10 | 10052.68 | 23-MAY-05:01 | 23.90 | 23.41 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.851453E+10 | 8931.03 | 20-JUN-05:01 | 24.90 | 23.36 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.894193E+10 | 11257.62 | 05-JUL-05:01 | 26.10 | 24.88 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.972137E+10 | 9643.59 | 31-AUG-05:01 | 24.13 | 22.97 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.770258E+10 | 9878.22 | 06-SEP-05:01 | 23.82 | 22.53 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.811947E+10 | 10395.68 | 11-OCT-05:01 | 23.20 | 22.16 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.667041E+10 | 8459.89 | 13-NOV-06:05 | 9.80 | 8.12 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.597052E+10 | 7869.88 | 26-DEC-06:13 | 5.90 | 2.18 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.861716E+11 | 0.00 | ||||||||
Minimum of Months | 0.473477E+10 | 7299.05 | 5.90 | 2.18 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.972137E+10 | 11381.85 | 26.10 | 24.88 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.280012E+10 | 6258.11 | 02-JAN-06:13 | 16.00 | 15.39 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.292459E+10 | 4990.40 | 24-FEB-06:13 | 14.60 | 14.60 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.378194E+10 | 5065.77 | 30-MAR-05:10 | 20.83 | 19.77 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.473124E+10 | 5583.99 | 21-APR-05:13 | 18.30 | 17.21 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.690744E+10 | 9424.14 | 08-MAY-05:01 | 23.90 | 21.88 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.705095E+10 | 10053.07 | 30-JUN-05:01 | 24.50 | 23.30 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.710194E+10 | 9235.56 | 07-JUL-05:01 | 25.10 | 23.75 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.737189E+10 | 8767.08 | 23-AUG-05:01 | 26.10 | 23.62 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.630782E+10 | 9776.55 | 01-SEP-05:01 | 24.42 | 23.28 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.624143E+10 | 9844.67 | 07-OCT-05:01 | 26.17 | 26.04 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.426930E+10 | 6852.03 | 07-NOV-06:01 | 20.50 | 19.70 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.342858E+10 | 4981.95 | 18-DEC-06:10 | 3.67 | 0.68 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.629172E+11 | 0.00 | ||||||||
Minimum of Months | 0.280012E+10 | 4981.95 | 3.67 | 0.68 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.737189E+10 | 10053.07 | 26.17 | 26.04 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.262770E+10 | 9243.17 | 19-JAN-15:00 | 25.00 | 21.53 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.357571E+10 | 10975.07 | 24-FEB-14:50 | 25.78 | 20.92 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.491047E+10 | 11552.30 | 06-MAR-14:40 | 26.27 | 21.24 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.770182E+10 | 15862.36 | 28-APR-15:00 | 33.30 | 23.04 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.120969E+11 | 16963.08 | 10-MAY-14:50 | 32.80 | 23.12 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.132200E+11 | 17713.17 | 28-JUN-14:30 | 33.60 | 26.18 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.126665E+11 | 18078.93 | 07-JUL-14:40 | 34.63 | 24.17 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.127722E+11 | 17204.55 | 03-AUG-15:00 | 35.00 | 24.83 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.993599E+10 | 15711.20 | 01-SEP-14:00 | 32.20 | 22.61 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.942351E+10 | 15344.87 | 05-OCT-15:00 | 34.00 | 24.03 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.493179E+10 | 12324.96 | 02-NOV-14:00 | 29.40 | 24.47 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.325531E+10 | 10517.29 | 15-DEC-15:00 | 29.00 | 21.55 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.971179E+11 | 0.00 | ||||||||
Minimum of Months | 0.262770E+10 | 9243.17 | 25.00 | 20.92 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.132200E+11 | 18078.93 | 35.00 | 26.18 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.388723E+10 | 1911.05 | 01-JAN-17:23 | 22.00 | 18.78 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.827977E+10 | 4001.92 | 26-FEB-17:47 | 23.48 | 19.38 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.143134E+11 | 5666.04 | 13-MAR-18:00 | 16.10 | 9.59 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.188363E+11 | 7850.75 | 16-APR-18:05 | 18.43 | 13.26 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.443093E+10 | 1975.66 | 01-MAY-00:05 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.916678E+10 | 3853.30 | 11-JUN-18:12 | 31.67 | 21.41 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.144998E+11 | 5649.09 | 16-JUL-18:50 | 28.98 | 24.52 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.195762E+11 | 7595.51 | 06-AUG-18:05 | 25.00 | 23.59 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.430142E+10 | 2030.98 | 03-SEP-18:00 | 29.90 | 24.07 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.949484E+10 | 3917.58 | 09-OCT-17:20 | 27.33 | 20.84 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.139889E+11 | 5846.34 | 12-NOV-16:53 | 15.00 | 8.72 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.194045E+11 | 7731.85 | 25-DEC-17:10 | 15.45 | 9.34 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.140180E+12 | 0.00 | ||||||||
Minimum of Months | 0.388723E+10 | 1911.05 | 15.00 | 8.72 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.195762E+11 | 7850.75 | 31.67 | 24.52 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273173E+10 | 1719.19 | 31-JAN-17:50 | 22.17 | 20.10 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.708456E+10 | 3608.12 | 27-FEB-17:40 | 23.27 | 19.62 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.129589E+11 | 5361.24 | 06-MAR-17:50 | 24.00 | 20.78 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.177634E+11 | 7338.27 | 16-APR-18:20 | 18.07 | 13.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.401698E+10 | 1784.86 | 29-MAY-18:16 | 29.03 | 23.47 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.865312E+10 | 3612.20 | 11-JUN-18:15 | 31.67 | 21.41 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.138037E+11 | 5328.96 | 07-JUL-16:00 | 34.40 | 24.79 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.186658E+11 | 7147.11 | 30-AUG-18:40 | 31.90 | 23.11 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.379564E+10 | 1890.77 | 03-SEP-18:00 | 29.90 | 24.07 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.874876E+10 | 3634.88 | 09-OCT-17:35 | 26.67 | 20.43 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.127051E+11 | 5480.07 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.176600E+11 | 7214.86 | 15-DEC-17:00 | 28.00 | 21.23 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.128588E+12 | 0.00 | ||||||||
Minimum of Months | 0.273173E+10 | 1719.19 | 18.07 | 13.18 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.186658E+11 | 7338.27 | 34.40 | 24.79 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179292E+10 | 1778.66 | 31-JAN-17:40 | 22.33 | 20.25 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.633539E+10 | 3655.62 | 27-FEB-17:40 | 23.27 | 19.62 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.124333E+11 | 5422.63 | 06-MAR-17:50 | 24.00 | 20.78 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.176097E+11 | 7465.11 | 16-APR-18:20 | 18.07 | 13.18 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.411329E+10 | 2044.70 | 29-MAY-18:00 | 29.40 | 23.46 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.877731E+10 | 3839.36 | 11-JUN-18:22 | 31.40 | 21.45 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.139307E+11 | 5483.57 | 16-JUL-19:00 | 28.90 | 24.50 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.187541E+11 | 7295.60 | 06-AUG-17:35 | 25.33 | 23.69 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.386228E+10 | 2117.73 | 03-SEP-17:45 | 30.10 | 24.21 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.866705E+10 | 3854.68 | 08-OCT-17:35 | 27.67 | 23.80 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.122078E+11 | 5534.49 | 06-NOV-17:00 | 26.60 | 19.71 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.168987E+11 | 7269.42 | 15-DEC-17:00 | 28.00 | 21.23 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.125383E+12 | 0.00 | ||||||||
Minimum of Months | 0.179292E+10 | 1778.66 | 18.07 | 13.18 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.187541E+11 | 7465.11 | 31.40 | 24.50 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239980E+12 | 331360.61 | 05-JAN-01:03 | 5.50 | 3.14 | 0.00 | 0.00 | 01-JAN-00:10 | 17.00 | 16.69 |
February | 0.436152E+12 | 365780.34 | 07-FEB-05:32 | 9.00 | 6.53 | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 | 18.20 |
March | 0.727437E+12 | 412290.20 | 20-MAR-21:42 | 8.80 | 7.66 | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 | 17.16 |
April | 0.941082E+12 | 365012.58 | 28-APR-18:50 | 23.72 | 22.13 | 0.00 | 0.00 | 01-APR-00:10 | 20.72 | 19.79 |
May | 0.239301E+12 | 102980.19 | 01-MAY-00:08 | 22.45 | 19.10 | 0.00 | 0.00 | 01-MAY-00:10 | 22.45 | 19.10 |
June | 0.467731E+12 | 181958.85 | 13-JUN-16:00 | 32.80 | 20.88 | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 | 21.40 |
July | 0.729796E+12 | 274193.44 | 06-JUL-16:00 | 31.70 | 24.74 | 0.00 | 0.00 | 01-JUL-00:10 | 25.07 | 23.10 |
August | 0.976172E+12 | 370988.69 | 06-AUG-15:42 | 25.33 | 21.89 | 0.00 | 0.00 | 01-AUG-00:10 | 25.13 | 23.54 |
September | 0.235349E+12 | 106603.29 | 01-SEP-00:07 | 24.85 | 24.22 | 0.00 | 0.00 | 01-SEP-00:10 | 24.85 | 24.22 |
October | 0.487134E+12 | 183561.99 | 10-OCT-16:00 | 30.00 | 22.38 | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 | 20.64 |
November | 0.708636E+12 | 417263.85 | 26-NOV-06:32 | 9.40 | 8.24 | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 | 21.01 |
December | 0.977081E+12 | 405106.73 | 19-DEC-04:43 | 6.17 | 5.66 | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 | 12.36 |
Annual Sum or Average | 0.716585E+13 | 0.00 | ||||||||
Minimum of Months | 0.235349E+12 | 102980.19 | 5.50 | 3.14 | 0.00 | 0.00 | 14.12 | 12.36 | ||
Maximum of Months | 0.977081E+12 | 417263.85 | 32.80 | 24.74 | 0.00 | 0.00 | 25.13 | 24.22 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.820566E+09 | 122276.73 | 19-JAN-04:47 | 19.00 |
February | 0.876889E+09 | 122555.37 | 03-FEB-04:47 | 19.25 |
March | 0.696499E+09 | 124925.83 | 30-MAR-03:47 | 20.82 |
April | 0.804033E+09 | 127089.04 | 27-APR-03:47 | 21.12 |
May | 0.119443E+10 | 127498.00 | 18-MAY-03:47 | 23.30 |
June | 0.663210E+09 | 127643.59 | 01-JUN-03:47 | 21.75 |
July | 0.132805E+10 | 126741.77 | 01-JUL-03:47 | 24.43 |
August | 0.985477E+09 | 125298.37 | 26-AUG-03:50 | 23.87 |
September | 0.126414E+10 | 127599.26 | 15-SEP-03:48 | 23.90 |
October | 0.134312E+10 | 124360.29 | 15-OCT-14:30 | 30.00 |
November | 0.937829E+09 | 124769.18 | 02-NOV-03:48 | 23.62 |
December | 0.127800E+10 | 122154.26 | 16-DEC-04:50 | 20.83 |
Annual Sum or Average | 0.121922E+11 | |||
Minimum of Months | 0.663210E+09 | 122154.26 | 19.00 | |
Maximum of Months | 0.134312E+10 | 127643.59 | 30.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7703754.74 | 47076.10 | 23-JAN-06:03 | 6.83 |
February | 0.110285E+09 | 53259.87 | 06-FEB-05:01 | 3.03 |
March | 2881456.71 | 47351.44 | 13-MAR-05:01 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.120870E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.03 | |
Maximum of Months | 0.110285E+09 | 53259.87 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 90922.07 | 1515.37 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 90922.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 90922.07 | 1515.37 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32783276.32 | 8870.66 | 10-JAN-06:03 | 3.00 |
February | 26895298.46 | 9311.27 | 06-FEB-05:01 | 3.03 |
March | 3942292.23 | 6998.69 | 13-MAR-05:01 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 22226056.88 | 9106.33 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 85846923.88 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 32783276.32 | 9311.27 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 17549286.51 | 7772.37 | 10-JAN-06:03 | 3.00 |
February | 12343207.56 | 7759.21 | 06-FEB-06:01 | 2.88 |
March | 2905750.54 | 4348.22 | 09-MAR-06:03 | 1.10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 16606620.35 | 8210.18 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 49404864.96 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 17549286.51 | 8210.18 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 375118.22 | 509.14 | 21-JAN-06:03 | 1.00 |
February | 2334536.40 | 9931.28 | 06-FEB-06:01 | 2.88 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 5752412.76 | 9871.42 | 20-DEC-06:01 | 2.83 |
Annual Sum or Average | 8462067.38 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 5752412.76 | 9931.28 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6603257.66 | 6226.89 | 10-JAN-06:03 | 3.00 |
February | 4515923.37 | 6761.21 | 06-FEB-06:01 | 2.88 |
March | 138628.98 | 458.25 | 11-MAR-06:03 | 6.60 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 7191826.60 | 6894.81 | 21-DEC-06:01 | 0.83 |
Annual Sum or Average | 18449636.61 | |||
Minimum of Months | 0.00 | 0.00 | 0.83 | |
Maximum of Months | 7191826.60 | 6894.81 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.513254E+09 | 11635.74 | 23-JAN-05:01 | 7.83 |
February | 0.321351E+09 | 12555.99 | 06-FEB-04:01 | 3.35 |
March | 0.179475E+09 | 10926.65 | 13-MAR-04:02 | 7.05 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 14230708.82 | 10202.20 | 16-NOV-06:01 | 9.40 |
December | 0.290487E+09 | 11430.28 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.131880E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.513254E+09 | 12555.99 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249281E+09 | 10639.84 | 23-JAN-05:01 | 7.83 |
February | 0.140339E+09 | 11847.27 | 06-FEB-04:01 | 3.35 |
March | 0.104911E+09 | 10047.48 | 10-MAR-05:01 | 5.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 3305350.28 | 9249.56 | 16-NOV-06:01 | 9.40 |
December | 0.164862E+09 | 10776.31 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.662698E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.249281E+09 | 11847.27 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.185203E+09 | 11977.08 | 10-JAN-05:01 | 1.33 |
February | 0.129023E+09 | 12848.01 | 06-FEB-04:01 | 3.35 |
March | 0.113753E+09 | 11752.62 | 11-MAR-05:01 | 7.27 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.118414E+09 | 12010.22 | 20-DEC-05:02 | 4.67 |
Annual Sum or Average | 0.546393E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.33 | |
Maximum of Months | 0.185203E+09 | 12848.01 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.168282E+09 | 10130.38 | 10-JAN-05:01 | 1.33 |
February | 93445072.00 | 10699.09 | 06-FEB-05:01 | 3.03 |
March | 51140772.94 | 9301.46 | 13-MAR-05:01 | 6.68 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 67426.61 | 739.56 | 16-NOV-06:01 | 9.40 |
December | 79003756.53 | 10144.79 | 21-DEC-05:01 | 0.17 |
Annual Sum or Average | 0.391939E+09 | |||
Minimum of Months | 0.00 | 0.00 | 0.17 | |
Maximum of Months | 0.168282E+09 | 10699.09 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 62126827.37 | 9912.18 | 09-JAN-04:01 | 8.83 |
February | 57636006.24 | 10288.37 | 21-FEB-04:02 | 17.30 |
March | 74134506.50 | 10473.85 | 20-MAR-03:01 | 12.55 |
April | 90299968.28 | 10308.22 | 10-APR-03:02 | 13.30 |
May | 44598658.79 | 8326.58 | 24-MAY-03:01 | 25.00 |
June | 58198596.96 | 7818.87 | 07-JUN-03:01 | 21.10 |
July | 56602812.91 | 5019.40 | 28-JUL-03:01 | 24.60 |
August | 45792539.84 | 5287.71 | 01-AUG-03:01 | 24.15 |
September | 41747032.08 | 9004.07 | 29-SEP-03:01 | 23.80 |
October | 64089732.78 | 10086.32 | 30-OCT-03:02 | 17.00 |
November | 81327865.07 | 11047.31 | 12-NOV-08:30 | 7.75 |
December | 0.103503E+09 | 11318.17 | 22-DEC-04:01 | 8.83 |
Annual Sum or Average | 0.780058E+09 | |||
Minimum of Months | 41747032.08 | 5019.40 | 7.75 | |
Maximum of Months | 0.103503E+09 | 11318.17 | 25.00 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 43252265.72 | 7183.10 | 09-JAN-06:03 | 6.67 |
February | 64865420.00 | 7155.23 | 08-FEB-06:01 | 12.10 |
March | 46057463.68 | 6591.75 | 13-MAR-05:01 | 6.68 |
April | 26737031.06 | 6273.37 | 10-APR-04:03 | 12.70 |
May | 28867095.58 | 8393.50 | 22-MAY-03:02 | 26.10 |
June | 22023376.26 | 6885.22 | 14-JUN-03:01 | 25.00 |
July | 25423489.91 | 6940.41 | 20-JUL-03:01 | 26.70 |
August | 23466211.73 | 7155.45 | 02-AUG-03:01 | 26.35 |
September | 23937579.08 | 6729.59 | 19-SEP-03:01 | 26.10 |
October | 24392333.05 | 7243.76 | 23-OCT-03:02 | 24.98 |
November | 33968908.20 | 6318.26 | 02-NOV-04:02 | 23.57 |
December | 36320304.95 | 7086.10 | 22-DEC-06:01 | 10.00 |
Annual Sum or Average | 0.399311E+09 | |||
Minimum of Months | 22023376.26 | 6273.37 | 6.67 | |
Maximum of Months | 64865420.00 | 8393.50 | 26.70 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151591E+10 | 19724.08 | 03-JAN-06:01 | 2.83 |
February | 0.865743E+09 | 15667.93 | 10-FEB-06:01 | 11.78 |
March | 0.793435E+09 | 16334.78 | 20-MAR-05:01 | 12.10 |
April | 0.162307E+09 | 15949.04 | 11-APR-05:03 | 10.63 |
May | 39530306.12 | 10467.80 | 01-MAY-03:01 | 25.27 |
June | 31785486.31 | 8812.43 | 07-JUN-04:02 | 21.10 |
July | 25374492.44 | 8366.21 | 17-JUL-03:02 | 24.90 |
August | 27685251.62 | 8564.47 | 31-AUG-03:01 | 25.20 |
September | 31353438.64 | 8691.82 | 01-SEP-03:01 | 23.85 |
October | 85322474.78 | 14405.00 | 28-OCT-05:01 | 10.00 |
November | 0.321849E+09 | 17482.44 | 09-NOV-06:01 | 10.42 |
December | 0.107125E+10 | 16108.13 | 01-DEC-06:01 | 11.00 |
Annual Sum or Average | 0.497154E+10 | |||
Minimum of Months | 25374492.44 | 8366.21 | 2.83 | |
Maximum of Months | 0.151591E+10 | 19724.08 | 25.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 17.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 14.12 | |
Maximum of Months | 0.00 | 0.00 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 74755369.85 | 520.96 | 05-JAN-04:02 | 1.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 18.20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17.62 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 21.63 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 74755369.85 | |||
Minimum of Months | 0.00 | 0.00 | 1.00 | |
Maximum of Months | 74755369.85 | 520.96 | 25.13 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92355463.16 | 44022.81 | 21-JAN-23:43 | 4.17 |
February | 7210824.71 | 30770.17 | 13-FEB-00:21 | 9.25 |
March | 191237.12 | 3187.29 | 20-MAR-21:41 | 8.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 20.72 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 22.45 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.93 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 25.07 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 25.13 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 24.85 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.17 |
November | 1234682.02 | 20578.03 | 26-NOV-06:31 | 9.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 14.12 |
Annual Sum or Average | 0.100992E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.17 | |
Maximum of Months | 92355463.16 | 44022.81 | 25.13 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.176037E+11 | 18337.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.159674E+11 | 18337.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.189649E+11 | 18337.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.169484E+11 | 18337.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.182843E+11 | 18337.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.181926E+11 | 18337.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.170401E+11 | 18337.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.189649E+11 | 18337.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.169484E+11 | 18337.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.176037E+11 | 18337.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.173949E+11 | 18337.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.170401E+11 | 18337.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.210953E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.159674E+11 | 18337.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.189649E+11 | 18337.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158754E+10 | 1850.07 | 31-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.141986E+10 | 1884.95 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166493E+10 | 1803.13 | 27-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.147722E+10 | 1829.00 | 14-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.157501E+10 | 1576.04 | 23-MAY-07:30 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.156070E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.146761E+10 | 1509.46 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.164136E+10 | 1607.52 | 21-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148256E+10 | 1800.13 | 26-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.155459E+10 | 1936.10 | 25-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.156602E+10 | 1893.58 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.154755E+10 | 1926.37 | 12-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.185449E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.141986E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166493E+10 | 1936.10 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101850E+10 | 1173.75 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.912670E+09 | 1190.48 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107078E+10 | 1117.92 | 27-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.952110E+09 | 1154.29 | 14-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101708E+10 | 1015.90 | 30-MAY-15:30 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100856E+10 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.947548E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105885E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.955494E+09 | 1113.90 | 26-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100038E+10 | 1231.79 | 25-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.100610E+10 | 1227.93 | 21-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.994349E+09 | 1231.71 | 12-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119424E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.912670E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107078E+10 | 1231.79 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156557E+10 | 1819.03 | 31-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.140861E+10 | 1865.54 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.165979E+10 | 1792.57 | 27-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.147868E+10 | 1833.15 | 14-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.157968E+10 | 1610.44 | 23-MAY-07:19 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156617E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.147149E+10 | 1549.83 | 14-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.164375E+10 | 1645.96 | 21-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148187E+10 | 1796.95 | 26-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154876E+10 | 1928.05 | 25-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.154595E+10 | 1861.32 | 21-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.152691E+10 | 1915.05 | 12-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184772E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.140861E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.165979E+10 | 1928.05 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101565E+10 | 1202.71 | 31-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.911903E+09 | 1221.28 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107404E+10 | 1188.13 | 13-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.953970E+09 | 1195.93 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101769E+10 | 1092.65 | 24-MAY-07:19 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100811E+10 | 1019.69 | 08-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.947733E+09 | 1053.39 | 14-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105974E+10 | 1142.42 | 23-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.957566E+09 | 1187.73 | 26-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100149E+10 | 1254.39 | 25-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.100125E+10 | 1235.85 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.987633E+09 | 1242.80 | 12-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119368E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.911903E+09 | 1019.69 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107404E+10 | 1254.39 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158908E+10 | 1856.24 | 31-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.142088E+10 | 1890.17 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166587E+10 | 1810.93 | 27-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.147767E+10 | 1835.95 | 14-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.157546E+10 | 1589.99 | 23-MAY-07:30 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.156101E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.146800E+10 | 1509.46 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.164178E+10 | 1620.94 | 21-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148306E+10 | 1807.91 | 26-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.155537E+10 | 1939.92 | 25-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.156753E+10 | 1898.60 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.154925E+10 | 1930.44 | 12-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.185550E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.142088E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166587E+10 | 1939.92 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101875E+10 | 1176.32 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.912919E+09 | 1192.14 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107098E+10 | 1121.31 | 27-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.952280E+09 | 1156.86 | 14-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101719E+10 | 1016.62 | 30-MAY-15:30 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100871E+10 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.947656E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105899E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.955632E+09 | 1117.67 | 26-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100058E+10 | 1233.03 | 25-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.100646E+10 | 1228.73 | 21-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.994683E+09 | 1232.70 | 12-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119448E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.912919E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107098E+10 | 1233.03 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156578E+10 | 1826.48 | 31-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.140896E+10 | 1871.56 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166035E+10 | 1800.81 | 27-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.147917E+10 | 1839.93 | 14-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.158027E+10 | 1623.15 | 23-MAY-07:19 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156669E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.147197E+10 | 1564.02 | 14-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.164421E+10 | 1657.85 | 21-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148229E+10 | 1804.84 | 26-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154932E+10 | 1932.21 | 25-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.154735E+10 | 1867.84 | 21-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.152781E+10 | 1919.63 | 12-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184842E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.140896E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166035E+10 | 1932.21 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101594E+10 | 1203.68 | 31-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.912144E+09 | 1222.10 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107438E+10 | 1191.27 | 13-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.954198E+09 | 1196.91 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101789E+10 | 1094.11 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100829E+10 | 1022.90 | 08-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.947887E+09 | 1055.42 | 14-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105993E+10 | 1144.15 | 23-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.957775E+09 | 1188.78 | 26-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100175E+10 | 1254.96 | 25-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.100150E+10 | 1236.62 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.987846E+09 | 1243.46 | 12-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119395E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.912144E+09 | 1022.90 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107438E+10 | 1254.96 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158912E+10 | 1856.05 | 31-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.142089E+10 | 1890.00 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166587E+10 | 1810.73 | 27-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.147767E+10 | 1835.74 | 14-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.157546E+10 | 1589.59 | 23-MAY-07:30 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.156101E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.146800E+10 | 1509.46 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.164178E+10 | 1620.66 | 21-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148305E+10 | 1807.70 | 26-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.155536E+10 | 1939.80 | 25-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.156756E+10 | 1898.48 | 01-NOV-07:10 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.154926E+10 | 1930.29 | 12-DEC-08:09 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.185550E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.142089E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166587E+10 | 1939.80 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101877E+10 | 1176.51 | 04-JAN-16:00 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.912931E+09 | 1192.05 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107098E+10 | 1121.24 | 27-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.952282E+09 | 1156.76 | 14-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101719E+10 | 1016.52 | 30-MAY-15:30 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100871E+10 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.947653E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105899E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.955632E+09 | 1117.59 | 26-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100058E+10 | 1232.98 | 25-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.100647E+10 | 1228.64 | 21-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.994699E+09 | 1232.62 | 12-DEC-08:09 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.119449E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.912931E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107098E+10 | 1232.98 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.156578E+10 | 1826.30 | 31-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.140896E+10 | 1871.39 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166035E+10 | 1800.61 | 27-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.147916E+10 | 1839.72 | 14-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.158026E+10 | 1622.77 | 23-MAY-07:19 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.156668E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.147196E+10 | 1563.65 | 14-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.164421E+10 | 1657.56 | 21-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148229E+10 | 1804.63 | 26-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.154932E+10 | 1932.09 | 25-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.154735E+10 | 1867.70 | 21-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.152782E+10 | 1919.49 | 12-DEC-08:09 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.184842E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.140896E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166035E+10 | 1932.09 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.101596E+10 | 1203.56 | 31-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.912154E+09 | 1221.99 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107439E+10 | 1191.46 | 13-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.954203E+09 | 1196.78 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101789E+10 | 1093.99 | 24-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100829E+10 | 1023.25 | 08-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.947886E+09 | 1055.19 | 14-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105993E+10 | 1144.12 | 23-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.957772E+09 | 1188.65 | 26-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100175E+10 | 1254.89 | 25-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.100152E+10 | 1236.55 | 01-NOV-07:10 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.987852E+09 | 1243.37 | 12-DEC-08:09 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119396E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.912154E+09 | 1023.25 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107439E+10 | 1254.89 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.496348E+10 | 5170.29 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.450211E+10 | 5170.29 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.534729E+10 | 5170.29 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.477873E+10 | 5170.29 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.515538E+10 | 5170.29 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.512953E+10 | 5170.29 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.480458E+10 | 5170.29 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.534729E+10 | 5170.29 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.477873E+10 | 5170.29 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.496348E+10 | 5170.29 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.490462E+10 | 5170.29 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.480458E+10 | 5170.29 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.594798E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.450211E+10 | 5170.29 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.534729E+10 | 5170.29 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.176037E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.159674E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.169484E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.182843E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.181926E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.170401E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.169484E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.176037E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.173949E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.170401E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.210953E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.159674E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.158754E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1125826.02 | 0.396843E+09 |
February | 0.136985E+10 | 0.141986E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2150180.81 | 0.307840E+09 |
March | 0.163685E+10 | 0.166493E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6763370.85 | 0.320714E+09 |
April | 0.145243E+10 | 0.147722E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14298926.00 | 0.132919E+09 |
May | 0.157338E+10 | 0.157501E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58099664.35 | 20678781.83 |
June | 0.156900E+10 | 0.156070E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54360642.89 | 12595586.05 |
July | 0.145680E+10 | 0.146761E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81414620.24 | 2913584.41 |
August | 0.163685E+10 | 0.164136E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78166572.13 | 12093739.69 |
September | 0.145243E+10 | 0.148256E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65730071.37 | 34419934.61 |
October | 0.150991E+10 | 0.155459E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55127373.62 | 0.113721E+09 |
November | 0.149516E+10 | 0.156602E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5965237.45 | 0.202429E+09 |
December | 0.145680E+10 | 0.154755E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3730609.39 | 0.359242E+09 |
Annual Sum or Average | 0.181194E+11 | 0.185449E+11 | 0.403414E+11 | 0.426933E+09 | 0.191641E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.141986E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1125826.02 | 2913584.41 |
Maximum of Months | 0.163685E+10 | 0.166493E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81414620.24 | 0.396843E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101850E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 867663.58 | 0.259516E+09 |
February | 0.882782E+09 | 0.912670E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1644922.90 | 0.200130E+09 |
March | 0.105485E+10 | 0.107078E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5095631.39 | 0.202286E+09 |
April | 0.936002E+09 | 0.952110E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11038202.24 | 78144089.86 |
May | 0.101394E+10 | 0.101708E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41632048.90 | 11418604.85 |
June | 0.101113E+10 | 0.100856E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40900297.14 | 5374700.41 |
July | 0.938820E+09 | 0.947548E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65703296.29 | 707066.74 |
August | 0.105485E+10 | 0.105885E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65175663.58 | 3405455.08 |
September | 0.936002E+09 | 0.955494E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46872749.20 | 18939156.93 |
October | 0.973041E+09 | 0.100038E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41753635.39 | 66570006.92 |
November | 0.963541E+09 | 0.100610E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4693057.42 | 0.126912E+09 |
December | 0.938820E+09 | 0.994349E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2894922.55 | 0.220907E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119424E+11 | 0.259975E+11 | 0.328272E+09 | 0.119431E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.912670E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 867663.58 | 707066.74 |
Maximum of Months | 0.105485E+10 | 0.107078E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65703296.29 | 0.259516E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.156557E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566816.81 | 0.419715E+09 |
February | 0.136988E+10 | 0.140861E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1507226.40 | 0.320202E+09 |
March | 0.163688E+10 | 0.165979E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5241676.50 | 0.320314E+09 |
April | 0.145246E+10 | 0.147868E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13898822.79 | 0.131706E+09 |
May | 0.157341E+10 | 0.157968E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59643943.93 | 19791574.81 |
June | 0.156904E+10 | 0.156617E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56014552.64 | 11594416.93 |
July | 0.145684E+10 | 0.147149E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84183838.57 | 2567363.95 |
August | 0.163688E+10 | 0.164375E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78839214.38 | 11426688.83 |
September | 0.145246E+10 | 0.148187E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62169454.05 | 36003076.04 |
October | 0.150994E+10 | 0.154876E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45564615.68 | 0.125198E+09 |
November | 0.149520E+10 | 0.154595E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4033250.68 | 0.216724E+09 |
December | 0.145684E+10 | 0.152691E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2637324.95 | 0.376118E+09 |
Annual Sum or Average | 0.181198E+11 | 0.184772E+11 | 0.403420E+11 | 0.414301E+09 | 0.199136E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.140861E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 566816.81 | 2567363.95 |
Maximum of Months | 0.163688E+10 | 0.165979E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84183838.57 | 0.419715E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101565E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 793420.69 | 0.278500E+09 |
February | 0.882782E+09 | 0.911903E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1312954.78 | 0.223719E+09 |
March | 0.105485E+10 | 0.107404E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3835250.76 | 0.240395E+09 |
April | 0.936002E+09 | 0.953970E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7656453.66 | 0.108520E+09 |
May | 0.101394E+10 | 0.101769E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39778767.10 | 19555025.78 |
June | 0.101113E+10 | 0.100811E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34308733.40 | 12543345.79 |
July | 0.938820E+09 | 0.947733E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49692088.41 | 5052668.29 |
August | 0.105485E+10 | 0.105974E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47065098.04 | 15011540.19 |
September | 0.936002E+09 | 0.957566E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43421363.73 | 29462942.03 |
October | 0.973041E+09 | 0.100149E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34722829.38 | 90832993.72 |
November | 0.963541E+09 | 0.100125E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3416384.06 | 0.153512E+09 |
December | 0.938820E+09 | 0.987633E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2081012.19 | 0.273110E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119368E+11 | 0.259973E+11 | 0.268084E+09 | 0.145022E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.911903E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 793420.69 | 5052668.29 |
Maximum of Months | 0.105485E+10 | 0.107404E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49692088.41 | 0.278500E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.158908E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5187498.52 | 0.779880E+09 |
February | 0.136985E+10 | 0.142088E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6355623.94 | 0.597515E+09 |
March | 0.163685E+10 | 0.166587E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17984106.79 | 0.637129E+09 |
April | 0.145243E+10 | 0.147767E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29918316.07 | 0.283824E+09 |
May | 0.157338E+10 | 0.157546E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125065E+09 | 49131935.14 |
June | 0.156900E+10 | 0.156101E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113436E+09 | 36925301.92 |
July | 0.145680E+10 | 0.146800E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158353E+09 | 16076606.63 |
August | 0.163685E+10 | 0.164178E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152095E+09 | 47677300.80 |
September | 0.145243E+10 | 0.148306E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143876E+09 | 73251194.07 |
October | 0.150991E+10 | 0.155537E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121891E+09 | 0.240760E+09 |
November | 0.149516E+10 | 0.156753E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16593751.63 | 0.399678E+09 |
December | 0.145680E+10 | 0.154925E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10956106.92 | 0.695260E+09 |
Annual Sum or Average | 0.181194E+11 | 0.185550E+11 | 0.403414E+11 | 0.901712E+09 | 0.385711E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.142088E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5187498.52 | 16076606.63 |
Maximum of Months | 0.163685E+10 | 0.166587E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158353E+09 | 0.779880E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.101875E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3584464.98 | 0.529955E+09 |
February | 0.649041E+09 | 0.912919E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4516512.86 | 0.409154E+09 |
March | 0.773965E+09 | 0.107098E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11273071.64 | 0.432145E+09 |
April | 0.688021E+09 | 0.952280E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20203471.77 | 0.194489E+09 |
May | 0.744847E+09 | 0.101719E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85398007.46 | 32287016.20 |
June | 0.742030E+09 | 0.100871E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79009228.85 | 23220503.03 |
July | 0.690839E+09 | 0.947656E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111339E+09 | 11243405.30 |
August | 0.773965E+09 | 0.105899E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107369E+09 | 30046718.61 |
September | 0.688021E+09 | 0.955632E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99747969.93 | 45914981.17 |
October | 0.715730E+09 | 0.100058E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85821209.29 | 0.159128E+09 |
November | 0.708685E+09 | 0.100646E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11377682.56 | 0.270127E+09 |
December | 0.690839E+09 | 0.994683E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7815133.68 | 0.462923E+09 |
Annual Sum or Average | 0.858171E+10 | 0.119448E+11 | 0.259975E+11 | 0.627455E+09 | 0.260063E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.912919E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3584464.98 | 11243405.30 |
Maximum of Months | 0.773965E+09 | 0.107098E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111339E+09 | 0.529955E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.156578E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939993.66 | 0.919446E+09 |
February | 0.136988E+10 | 0.140896E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2945258.38 | 0.689163E+09 |
March | 0.163688E+10 | 0.166035E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11148314.30 | 0.681268E+09 |
April | 0.145246E+10 | 0.147917E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28348551.83 | 0.299364E+09 |
May | 0.157341E+10 | 0.158027E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127393E+09 | 49076526.74 |
June | 0.156904E+10 | 0.156669E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116629E+09 | 35269823.24 |
July | 0.145684E+10 | 0.147197E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162919E+09 | 15696087.68 |
August | 0.163688E+10 | 0.164421E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150848E+09 | 49831037.32 |
September | 0.145246E+10 | 0.148229E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131992E+09 | 83736453.82 |
October | 0.150994E+10 | 0.154932E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95137452.93 | 0.297260E+09 |
November | 0.149520E+10 | 0.154735E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8226682.32 | 0.477613E+09 |
December | 0.145684E+10 | 0.152781E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5444255.92 | 0.818398E+09 |
Annual Sum or Average | 0.181198E+11 | 0.184842E+11 | 0.403420E+11 | 0.841973E+09 | 0.441612E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.140896E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 939993.66 | 15696087.68 |
Maximum of Months | 0.163688E+10 | 0.166035E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162919E+09 | 0.919446E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101594E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3153008.85 | 0.549421E+09 |
February | 0.882782E+09 | 0.912144E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4018447.23 | 0.421797E+09 |
March | 0.105485E+10 | 0.107438E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11537762.45 | 0.446752E+09 |
April | 0.936002E+09 | 0.954198E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18054298.33 | 0.214577E+09 |
May | 0.101394E+10 | 0.101789E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87283833.93 | 39071715.61 |
June | 0.101113E+10 | 0.100829E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74956678.04 | 31059598.09 |
July | 0.938820E+09 | 0.947887E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107079E+09 | 17080506.49 |
August | 0.105485E+10 | 0.105993E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102620E+09 | 42014323.84 |
September | 0.936002E+09 | 0.957775E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95638640.14 | 57012356.25 |
October | 0.973041E+09 | 0.100175E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81563335.36 | 0.181785E+09 |
November | 0.963541E+09 | 0.100150E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11667007.01 | 0.281285E+09 |
December | 0.938820E+09 | 0.987846E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6922239.70 | 0.493921E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119395E+11 | 0.259973E+11 | 0.604495E+09 | 0.277578E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.912144E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3153008.85 | 17080506.49 |
Maximum of Months | 0.105485E+10 | 0.107438E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107079E+09 | 0.549421E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.158912E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7853102.77 | 0.872890E+09 |
February | 0.136985E+10 | 0.142089E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8186499.34 | 0.665458E+09 |
March | 0.163685E+10 | 0.166587E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22514772.46 | 0.733324E+09 |
April | 0.145243E+10 | 0.147767E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35231586.82 | 0.337643E+09 |
May | 0.157338E+10 | 0.157546E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149170E+09 | 66355125.42 |
June | 0.156900E+10 | 0.156101E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134486E+09 | 50844824.63 |
July | 0.145680E+10 | 0.146800E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186248E+09 | 24084118.80 |
August | 0.163685E+10 | 0.164178E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181133E+09 | 64109895.72 |
September | 0.145243E+10 | 0.148305E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168902E+09 | 95258558.77 |
October | 0.150991E+10 | 0.155536E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142566E+09 | 0.285510E+09 |
November | 0.149516E+10 | 0.156756E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21612511.85 | 0.452483E+09 |
December | 0.145680E+10 | 0.154926E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15122675.56 | 0.786010E+09 |
Annual Sum or Average | 0.181194E+11 | 0.185550E+11 | 0.403414E+11 | 0.107303E+10 | 0.443397E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.142089E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7853102.77 | 24084118.80 |
Maximum of Months | 0.163685E+10 | 0.166587E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186248E+09 | 0.872890E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101877E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4560980.47 | 0.601693E+09 |
February | 0.882782E+09 | 0.912931E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5051788.52 | 0.461574E+09 |
March | 0.105485E+10 | 0.107098E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12821141.23 | 0.506681E+09 |
April | 0.936002E+09 | 0.952282E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23067959.14 | 0.235921E+09 |
May | 0.101394E+10 | 0.101719E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101281E+09 | 43957491.67 |
June | 0.101113E+10 | 0.100871E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 93150252.83 | 32794885.38 |
July | 0.938820E+09 | 0.947653E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130977E+09 | 16575614.66 |
August | 0.105485E+10 | 0.105899E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127121E+09 | 41408025.16 |
September | 0.936002E+09 | 0.955632E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116255E+09 | 61406255.39 |
October | 0.973041E+09 | 0.100058E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97881255.03 | 0.193027E+09 |
November | 0.963541E+09 | 0.100647E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13461691.50 | 0.313947E+09 |
December | 0.938820E+09 | 0.994699E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9331103.99 | 0.532699E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119449E+11 | 0.259975E+11 | 0.734959E+09 | 0.304168E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.912931E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4560980.47 | 16575614.66 |
Maximum of Months | 0.105485E+10 | 0.107098E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130977E+09 | 0.601693E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.156578E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1141895.67 | 0.105062E+10 |
February | 0.136988E+10 | 0.140896E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3660111.98 | 0.778321E+09 |
March | 0.163688E+10 | 0.166035E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13231892.95 | 0.790244E+09 |
April | 0.145246E+10 | 0.147916E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33601346.78 | 0.356708E+09 |
May | 0.157341E+10 | 0.158026E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152887E+09 | 65766874.47 |
June | 0.156904E+10 | 0.156668E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138706E+09 | 48492881.34 |
July | 0.145684E+10 | 0.147196E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192907E+09 | 23264754.50 |
August | 0.163688E+10 | 0.164421E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180945E+09 | 66532284.10 |
September | 0.145246E+10 | 0.148229E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157952E+09 | 0.107969E+09 |
October | 0.150994E+10 | 0.154932E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114224E+09 | 0.356743E+09 |
November | 0.149520E+10 | 0.154735E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10387596.17 | 0.557028E+09 |
December | 0.145684E+10 | 0.152782E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6737547.64 | 0.941813E+09 |
Annual Sum or Average | 0.181198E+11 | 0.184842E+11 | 0.403420E+11 | 0.100638E+10 | 0.514350E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.140896E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1141895.67 | 23264754.50 |
Maximum of Months | 0.163688E+10 | 0.166035E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192907E+09 | 0.105062E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.101596E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4177993.27 | 0.633728E+09 |
February | 0.882782E+09 | 0.912154E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5022603.64 | 0.482845E+09 |
March | 0.105485E+10 | 0.107439E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14227064.36 | 0.523886E+09 |
April | 0.936002E+09 | 0.954203E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22206814.86 | 0.257660E+09 |
May | 0.101394E+10 | 0.101789E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107837E+09 | 50049816.59 |
June | 0.101113E+10 | 0.100829E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91814191.76 | 40874401.14 |
July | 0.938820E+09 | 0.947886E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131291E+09 | 22674187.13 |
August | 0.105485E+10 | 0.105993E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126235E+09 | 54441093.76 |
September | 0.936002E+09 | 0.957772E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116979E+09 | 72063943.98 |
October | 0.973041E+09 | 0.100175E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98552548.25 | 0.218217E+09 |
November | 0.963541E+09 | 0.100152E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14896552.56 | 0.327395E+09 |
December | 0.938820E+09 | 0.987852E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8933272.55 | 0.573246E+09 |
Annual Sum or Average | 0.116768E+11 | 0.119396E+11 | 0.259973E+11 | 0.742173E+09 | 0.325708E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.912154E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4177993.27 | 22674187.13 |
Maximum of Months | 0.105485E+10 | 0.107439E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131291E+09 | 0.633728E+09 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.496348E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.450211E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.534729E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.477873E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.515538E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.512953E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.480458E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.534729E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.477873E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.496348E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.490462E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.480458E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594798E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.450211E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.534729E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744303.87 | 0.836224E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2182300.12 | 0.647323E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8734134.44 | 0.665863E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20961664.16 | 0.284658E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98888412.61 | 34499753.01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92096191.76 | 26664129.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142382E+09 | 7186517.33 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128844E+09 | 33743281.32 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112906E+09 | 66203590.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88139275.54 | 0.244861E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7532913.40 | 0.429999E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4810162.23 | 0.755466E+09 |
Annual Sum or Average | 0.708222E+09 | 0.403269E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 744303.87 | 7186517.33 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142382E+09 | 0.836224E+09 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2796700.47 | 0.141938E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5470661.03 | 0.109255E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20275284.78 | 0.112364E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38671760.10 | 0.486893E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182204E+09 | 58425289.26 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166405E+09 | 47715775.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251258E+09 | 14028246.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226096E+09 | 65673329.64 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212442E+09 | 0.106905E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164161E+09 | 0.413857E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16095244.06 | 0.722635E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10750189.88 | 0.126096E+10 |
Annual Sum or Average | 0.129662E+10 | 0.681265E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2796700.47 | 14028246.56 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251258E+09 | 0.141938E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509035.28 | 0.143438E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2226975.26 | 0.110319E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10379155.48 | 0.119132E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25276100.56 | 0.552189E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160700E+09 | 77837174.04 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150454E+09 | 59920182.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224174E+09 | 24182708.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213143E+09 | 82059456.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198603E+09 | 0.126847E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134427E+09 | 0.446054E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11858010.48 | 0.740535E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8536920.96 | 0.128664E+10 |
Annual Sum or Average | 0.114129E+10 | 0.712515E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1509035.28 | 24182708.06 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224174E+09 | 0.143438E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 18337.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 18337.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 18337.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 18337.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 18337.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 18337.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 18337.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 18337.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 18337.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 18337.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 18337.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 18337.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 18337.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 18337.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1850.07 | 31-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 | 16-JAN-14:51 | 743.78 | 09-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1884.95 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 02-FEB-13:00 | 1039.19 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1803.13 | 27-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 121.81 | 05-MAR-12:43 | 888.09 | 20-MAR-21:53 |
April | 2010.79 | 03-APR-09:09 | 1829.00 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.43 | 29-APR-17:02 | 539.54 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1576.04 | 23-MAY-07:30 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 248.59 | 21-MAY-13:35 | 111.13 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.30 | 10-JUN-17:02 | 158.84 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1509.46 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 293.07 | 22-JUL-18:50 | 91.35 | 30-JUL-10:55 |
August | 2010.79 | 01-AUG-09:09 | 1607.52 | 21-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 355.62 | 20-AUG-14:00 | 197.89 | 25-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1800.13 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 351.07 | 09-SEP-17:02 | 227.34 | 05-SEP-03:00 |
October | 2010.79 | 02-OCT-09:09 | 1936.10 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.47 | 09-OCT-14:00 | 441.48 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1893.58 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.44 | 05-NOV-13:00 | 628.53 | 12-NOV-08:00 |
December | 2010.79 | 01-DEC-10:09 | 1926.37 | 12-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 71.53 | 10-DEC-15:00 | 971.80 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 91.35 | |||||
Maximum of Months | 2010.79 | 1936.10 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 432.47 | 1039.19 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1173.75 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 16-JAN-15:10 | 488.48 | 22-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1190.48 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 44.69 | 20-FEB-15:00 | 717.21 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1117.92 | 27-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 95.46 | 05-MAR-12:43 | 570.61 | 20-MAR-21:53 |
April | 1295.83 | 03-APR-09:09 | 1154.29 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.08 | 29-APR-17:50 | 336.73 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1015.90 | 30-MAY-15:30 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.83 | 21-MAY-13:32 | 71.00 | 09-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.18 | 10-JUN-17:02 | 91.87 | 06-JUN-22:10 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.23 | 22-JUL-19:10 | 78.08 | 30-JUL-10:55 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 279.76 | 20-AUG-14:00 | 111.52 | 25-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1113.90 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.94 | 09-SEP-22:53 | 144.69 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1231.79 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 329.49 | 09-OCT-13:50 | 284.17 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1227.93 | 21-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.43 | 05-NOV-13:00 | 465.66 | 12-NOV-08:29 |
December | 1295.83 | 01-DEC-10:09 | 1231.71 | 12-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 59.43 | 10-DEC-15:20 | 613.30 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 71.00 | |||||
Maximum of Months | 1295.83 | 1231.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 329.49 | 717.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1819.03 | 31-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 19-JAN-12:10 | 749.93 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1865.54 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 51.79 | 02-FEB-13:00 | 1020.98 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1792.57 | 27-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 76.45 | 26-MAR-13:52 | 888.57 | 20-MAR-21:53 |
April | 2010.83 | 03-APR-09:09 | 1833.15 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 181.09 | 29-APR-17:02 | 535.53 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 1610.44 | 23-MAY-07:19 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 260.51 | 21-MAY-13:35 | 110.43 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 319.13 | 10-JUN-17:02 | 155.48 | 06-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1549.83 | 14-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.93 | 22-JUL-18:52 | 91.52 | 30-JUL-10:55 |
August | 2010.83 | 01-AUG-09:09 | 1645.96 | 21-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 357.59 | 20-AUG-14:00 | 195.80 | 25-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1796.95 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.58 | 09-SEP-17:02 | 234.99 | 05-SEP-03:00 |
October | 2010.83 | 02-OCT-09:09 | 1928.05 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.53 | 09-OCT-13:55 | 451.89 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1861.32 | 21-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.24 | 28-NOV-13:00 | 668.60 | 12-NOV-08:29 |
December | 2010.83 | 01-DEC-10:09 | 1915.05 | 12-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 37.22 | 13-DEC-14:00 | 951.47 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 | 91.52 | |||||
Maximum of Months | 2010.83 | 1928.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 357.59 | 1020.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1202.71 | 31-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 16-JAN-14:30 | 518.33 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1221.28 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 34.20 | 02-FEB-13:00 | 722.51 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 1188.13 | 13-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 77.96 | 05-MAR-12:43 | 647.34 | 20-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 1195.93 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.89 | 29-APR-17:08 | 438.88 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1092.65 | 24-MAY-07:19 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.38 | 21-MAY-13:32 | 95.23 | 09-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1019.69 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.47 | 10-JUN-17:10 | 144.47 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1053.39 | 14-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.20 | 22-JUL-19:10 | 87.07 | 30-JUL-10:55 |
August | 1295.83 | 01-AUG-09:09 | 1142.42 | 23-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 247.09 | 20-AUG-14:00 | 170.22 | 26-AUG-00:10 |
September | 1295.83 | 01-SEP-09:09 | 1187.73 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.42 | 09-SEP-22:53 | 165.41 | 05-SEP-03:00 |
October | 1295.83 | 02-OCT-09:09 | 1254.39 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.16 | 09-OCT-11:50 | 336.80 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1235.85 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.26 | 11-NOV-12:40 | 455.03 | 12-NOV-08:00 |
December | 1295.83 | 01-DEC-10:09 | 1242.80 | 12-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 | 10-DEC-12:00 | 724.60 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1019.69 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 33.37 | 87.07 | |||||
Maximum of Months | 1295.83 | 1254.39 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 309.16 | 724.60 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1856.24 | 31-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.59 | 16-JAN-14:51 | 1473.81 | 21-JAN-05:55 |
February | 2010.79 | 01-FEB-10:09 | 1890.17 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 224.37 | 20-FEB-14:52 | 2028.66 | 05-FEB-07:55 |
March | 2010.79 | 01-MAR-10:09 | 1810.93 | 27-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 332.27 | 05-MAR-12:47 | 1797.57 | 20-MAR-21:53 |
April | 2010.79 | 03-APR-09:09 | 1835.95 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 438.69 | 29-APR-17:02 | 1011.33 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1589.99 | 23-MAY-07:30 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 556.38 | 07-MAY-14:00 | 220.60 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 701.46 | 10-JUN-17:02 | 304.41 | 06-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1509.46 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 659.84 | 22-JUL-19:00 | 199.32 | 31-JUL-02:21 |
August | 2010.79 | 01-AUG-09:09 | 1620.94 | 21-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 788.56 | 20-AUG-13:51 | 461.44 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1807.91 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 791.39 | 09-SEP-17:02 | 462.26 | 05-SEP-02:51 |
October | 2010.79 | 02-OCT-09:09 | 1939.92 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 940.39 | 09-OCT-13:50 | 844.24 | 29-OCT-02:00 |
November | 2010.79 | 01-NOV-09:09 | 1898.60 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.35 | 05-NOV-13:00 | 1253.80 | 12-NOV-06:52 |
December | 2010.79 | 01-DEC-10:09 | 1930.44 | 12-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 216.62 | 10-DEC-15:00 | 1852.67 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 180.59 | 199.32 | |||||
Maximum of Months | 2010.79 | 1939.92 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 940.39 | 2028.66 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1176.32 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 119.03 | 16-JAN-15:10 | 969.11 | 21-JAN-05:55 |
February | 1239.33 | 01-FEB-08:09 | 1192.14 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 178.83 | 20-FEB-14:52 | 1436.61 | 05-FEB-08:00 |
March | 1239.33 | 01-MAR-08:09 | 1121.31 | 27-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 208.50 | 05-MAR-13:10 | 1188.59 | 20-MAR-21:53 |
April | 1239.33 | 03-APR-07:10 | 1156.86 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.69 | 29-APR-17:50 | 670.88 | 01-APR-21:00 |
May | 1239.33 | 01-MAY-07:10 | 1016.62 | 30-MAY-15:30 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 445.47 | 21-MAY-14:00 | 152.86 | 14-MAY-12:10 |
June | 1239.33 | 01-JUN-07:10 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.60 | 10-JUN-17:02 | 188.82 | 07-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 527.00 | 22-JUL-19:00 | 186.04 | 30-JUL-11:00 |
August | 1239.33 | 01-AUG-07:10 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 550.13 | 20-AUG-13:51 | 305.34 | 25-AUG-23:53 |
September | 1239.33 | 01-SEP-07:10 | 1117.67 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 562.00 | 09-SEP-17:02 | 316.06 | 05-SEP-02:51 |
October | 1239.33 | 02-OCT-07:10 | 1233.03 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 701.34 | 09-OCT-14:10 | 567.89 | 29-OCT-02:00 |
November | 1239.33 | 01-NOV-07:10 | 1228.73 | 21-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.69 | 05-NOV-13:00 | 963.08 | 12-NOV-08:30 |
December | 1239.33 | 01-DEC-08:09 | 1232.70 | 12-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 155.09 | 10-DEC-15:00 | 1220.34 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 119.03 | 152.86 | |||||
Maximum of Months | 1239.33 | 1233.03 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 701.34 | 1436.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1826.48 | 31-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | 19-JAN-12:00 | 1592.28 | 26-JAN-03:00 |
February | 2010.83 | 01-FEB-10:09 | 1871.56 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 112.25 | 02-FEB-13:00 | 2123.84 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1800.81 | 27-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 171.86 | 26-MAR-13:52 | 1850.13 | 20-MAR-21:53 |
April | 2010.83 | 03-APR-09:09 | 1839.93 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 420.80 | 29-APR-17:02 | 1063.27 | 01-APR-21:00 |
May | 2010.83 | 01-MAY-09:09 | 1623.15 | 23-MAY-07:19 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 558.06 | 07-MAY-14:00 | 226.32 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 720.67 | 10-JUN-17:02 | 302.01 | 06-JUN-22:10 |
July | 2010.83 | 03-JUL-09:09 | 1564.02 | 14-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 696.74 | 22-JUL-19:00 | 202.56 | 31-JUL-01:53 |
August | 2010.83 | 01-AUG-09:09 | 1657.85 | 21-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 774.40 | 20-AUG-13:51 | 470.58 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1804.84 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 775.06 | 09-SEP-17:02 | 494.55 | 05-SEP-02:51 |
October | 2010.83 | 02-OCT-09:09 | 1932.21 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 750.17 | 09-OCT-13:48 | 955.23 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1867.84 | 21-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.74 | 28-NOV-13:00 | 1410.13 | 12-NOV-10:53 |
December | 2010.83 | 01-DEC-10:09 | 1919.63 | 12-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 | 13-DEC-14:00 | 1923.09 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 25.24 | 202.56 | |||||
Maximum of Months | 2010.83 | 1932.21 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 775.06 | 2123.84 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1203.68 | 31-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 107.39 | 16-JAN-14:30 | 1004.50 | 26-JAN-03:00 |
February | 1295.83 | 01-FEB-10:09 | 1222.10 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 108.08 | 26-FEB-14:00 | 1371.88 | 05-FEB-07:55 |
March | 1295.83 | 01-MAR-10:09 | 1191.27 | 13-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 246.60 | 05-MAR-13:10 | 1239.64 | 20-MAR-21:53 |
April | 1295.83 | 03-APR-09:09 | 1196.91 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 180.72 | 23-APR-14:20 | 725.41 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1094.11 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 435.36 | 21-MAY-14:00 | 159.90 | 09-MAY-02:00 |
June | 1295.83 | 01-JUN-09:09 | 1022.90 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.62 | 10-JUN-17:10 | 226.18 | 06-JUN-22:10 |
July | 1295.83 | 03-JUL-09:09 | 1055.42 | 14-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 426.53 | 22-JUL-19:00 | 176.50 | 31-JUL-01:53 |
August | 1295.83 | 01-AUG-09:09 | 1144.15 | 23-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 575.73 | 20-AUG-13:51 | 341.91 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 1188.78 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 498.58 | 09-SEP-23:00 | 331.84 | 05-SEP-02:51 |
October | 1295.83 | 02-OCT-09:09 | 1254.96 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 707.80 | 09-OCT-12:10 | 615.13 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1236.62 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.74 | 11-NOV-12:40 | 872.37 | 12-NOV-06:52 |
December | 1295.83 | 01-DEC-10:09 | 1243.46 | 12-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 146.31 | 10-DEC-11:00 | 1257.73 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1022.90 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 107.39 | 159.90 | |||||
Maximum of Months | 1295.83 | 1254.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 707.80 | 1371.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1856.05 | 31-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 254.33 | 16-JAN-15:00 | 1789.00 | 21-JAN-05:55 |
February | 2010.79 | 01-FEB-10:09 | 1890.00 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 238.45 | 20-FEB-15:10 | 2294.96 | 05-FEB-08:00 |
March | 2010.79 | 01-MAR-10:09 | 1810.73 | 27-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 417.72 | 05-MAR-12:40 | 2110.32 | 20-MAR-21:53 |
April | 2010.79 | 03-APR-09:09 | 1835.74 | 14-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 502.76 | 29-APR-17:02 | 1173.89 | 01-APR-21:00 |
May | 2010.79 | 01-MAY-09:09 | 1589.59 | 23-MAY-07:30 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 645.31 | 07-MAY-14:00 | 280.16 | 09-MAY-02:00 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 825.23 | 10-JUN-17:02 | 393.83 | 18-JUN-14:00 |
July | 2010.79 | 03-JUL-09:09 | 1509.46 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 738.04 | 22-JUL-18:47 | 268.39 | 31-JUL-01:53 |
August | 2010.79 | 01-AUG-09:09 | 1620.66 | 21-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 943.93 | 20-AUG-13:51 | 555.36 | 25-AUG-23:53 |
September | 2010.79 | 01-SEP-09:09 | 1807.70 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 950.63 | 09-SEP-17:02 | 609.98 | 05-SEP-02:51 |
October | 2010.79 | 02-OCT-09:09 | 1939.80 | 25-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1049.60 | 09-OCT-13:50 | 909.96 | 28-OCT-04:53 |
November | 2010.79 | 01-NOV-09:09 | 1898.48 | 01-NOV-07:10 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.67 | 05-NOV-13:00 | 1479.13 | 12-NOV-06:52 |
December | 2010.79 | 01-DEC-10:09 | 1930.29 | 12-DEC-08:09 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 257.63 | 10-DEC-15:00 | 2050.97 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 238.45 | 268.39 | |||||
Maximum of Months | 2010.79 | 1939.80 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1049.60 | 2294.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1176.51 | 04-JAN-16:00 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 159.19 | 16-JAN-15:00 | 1192.64 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1192.05 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 179.57 | 20-FEB-15:10 | 1539.27 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1121.24 | 27-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 249.46 | 05-MAR-13:10 | 1406.95 | 20-MAR-21:53 |
April | 1295.83 | 03-APR-09:09 | 1156.76 | 14-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.61 | 29-APR-17:50 | 786.16 | 01-APR-21:00 |
May | 1295.83 | 01-MAY-09:09 | 1016.52 | 30-MAY-15:30 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 503.77 | 21-MAY-13:40 | 222.42 | 14-MAY-11:43 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 595.07 | 10-JUN-17:02 | 277.20 | 18-JUN-14:00 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 575.81 | 22-JUL-18:43 | 217.76 | 30-JUL-10:53 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 667.92 | 20-AUG-13:51 | 369.60 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 1117.59 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 694.95 | 09-SEP-23:00 | 413.39 | 05-SEP-02:51 |
October | 1295.83 | 02-OCT-09:09 | 1232.98 | 25-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 779.66 | 09-OCT-14:10 | 616.50 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1228.64 | 21-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 199.14 | 05-NOV-12:50 | 1130.03 | 12-NOV-08:30 |
December | 1295.83 | 01-DEC-10:09 | 1232.62 | 12-DEC-08:09 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 175.78 | 10-DEC-15:20 | 1365.68 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 159.19 | 217.76 | |||||
Maximum of Months | 1295.83 | 1232.98 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 779.66 | 1539.27 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1826.30 | 31-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.90 | 19-JAN-12:00 | 1789.01 | 21-JAN-05:55 |
February | 2010.83 | 01-FEB-10:09 | 1871.39 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.79 | 02-FEB-13:00 | 2291.45 | 05-FEB-08:00 |
March | 2010.83 | 01-MAR-10:09 | 1800.61 | 27-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 204.91 | 26-MAR-13:50 | 2182.80 | 20-MAR-21:53 |
April | 2010.83 | 03-APR-09:09 | 1839.72 | 14-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 483.86 | 29-APR-17:02 | 1239.66 | 01-APR-18:00 |
May | 2010.83 | 01-MAY-09:09 | 1622.77 | 23-MAY-07:19 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 650.43 | 07-MAY-14:00 | 286.56 | 09-MAY-02:00 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 850.42 | 10-JUN-17:02 | 385.00 | 18-JUN-14:00 |
July | 2010.83 | 03-JUL-09:09 | 1563.65 | 14-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 783.52 | 22-JUL-18:43 | 269.26 | 31-JUL-01:53 |
August | 2010.83 | 01-AUG-09:09 | 1657.56 | 21-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 941.06 | 20-AUG-13:51 | 566.07 | 25-AUG-23:53 |
September | 2010.83 | 01-SEP-09:09 | 1804.63 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 933.67 | 09-SEP-23:00 | 645.23 | 05-SEP-02:51 |
October | 2010.83 | 02-OCT-09:09 | 1932.09 | 25-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 907.21 | 09-OCT-13:48 | 1056.87 | 29-OCT-02:00 |
November | 2010.83 | 01-NOV-09:09 | 1867.70 | 21-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.43 | 28-NOV-13:00 | 1732.92 | 12-NOV-11:00 |
December | 2010.83 | 01-DEC-10:09 | 1919.49 | 12-DEC-08:09 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.97 | 13-DEC-14:00 | 2120.90 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 38.90 | 269.26 | |||||
Maximum of Months | 2010.83 | 1932.09 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 941.06 | 2291.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1203.56 | 31-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 138.24 | 16-JAN-13:25 | 1192.63 | 21-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1221.99 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 137.08 | 26-FEB-14:00 | 1525.73 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1191.46 | 13-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 292.42 | 05-MAR-13:10 | 1464.89 | 20-MAR-21:53 |
April | 1295.83 | 03-APR-09:09 | 1196.78 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 211.15 | 23-APR-14:20 | 867.50 | 01-APR-18:00 |
May | 1295.83 | 01-MAY-09:09 | 1093.99 | 24-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 512.87 | 21-MAY-13:40 | 226.69 | 06-MAY-20:00 |
June | 1295.83 | 01-JUN-09:09 | 1023.25 | 08-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 480.72 | 10-JUN-17:10 | 275.49 | 06-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 1055.19 | 14-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 524.06 | 16-JUL-12:50 | 217.34 | 31-JUL-01:53 |
August | 1295.83 | 01-AUG-09:09 | 1144.12 | 23-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 690.70 | 20-AUG-14:00 | 410.81 | 25-AUG-23:53 |
September | 1295.83 | 01-SEP-09:09 | 1188.65 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 656.71 | 09-SEP-23:00 | 424.33 | 05-SEP-02:51 |
October | 1295.83 | 02-OCT-09:09 | 1254.89 | 25-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 834.00 | 09-OCT-12:10 | 685.94 | 29-OCT-02:00 |
November | 1295.83 | 01-NOV-09:09 | 1236.55 | 01-NOV-07:10 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 241.07 | 11-NOV-13:00 | 1034.35 | 12-NOV-06:52 |
December | 1295.83 | 01-DEC-10:09 | 1243.37 | 12-DEC-08:09 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.13 | 10-DEC-11:00 | 1422.79 | 20-DEC-01:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 1023.25 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 137.08 | 217.34 | |||||
Maximum of Months | 1295.83 | 1254.89 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 834.00 | 1525.73 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 5170.29 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 5170.29 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 5170.29 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 5170.29 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 5170.29 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 5170.29 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 5170.29 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 5170.29 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 5170.29 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 5170.29 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 5170.29 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 5170.29 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 5170.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 5170.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 16-JAN-14:51 | 1547.14 | 09-JAN-05:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.01 | 02-FEB-13:00 | 2216.00 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.31 | 26-MAR-13:52 | 1856.36 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.14 | 29-APR-17:02 | 1078.62 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.13 | 21-MAY-13:52 | 168.47 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.46 | 10-JUN-17:02 | 278.27 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 551.64 | 22-JUL-18:52 | 123.36 | 31-JUL-02:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 715.64 | 20-AUG-14:00 | 399.17 | 25-AUG-24:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.37 | 09-SEP-17:02 | 385.74 | 05-SEP-03:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.04 | 09-OCT-14:00 | 912.38 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.61 | 05-NOV-13:00 | 1284.26 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.01 | 10-DEC-15:00 | 2051.71 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.48 | 123.36 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 794.04 | 2216.00 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.04 | 16-JAN-14:51 | 2667.22 | 26-JAN-03:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.72 | 20-FEB-15:00 | 3822.44 | 05-FEB-07:55 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.14 | 05-MAR-12:50 | 3195.09 | 20-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 627.01 | 29-APR-17:02 | 1785.78 | 01-APR-21:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 881.74 | 21-MAY-14:00 | 275.26 | 09-MAY-02:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110.51 | 10-JUN-17:02 | 475.59 | 06-JUN-21:20 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.51 | 22-JUL-19:00 | 220.56 | 31-JUL-03:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1308.76 | 20-AUG-13:51 | 728.71 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.95 | 09-SEP-17:02 | 629.56 | 05-SEP-03:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.75 | 09-OCT-13:52 | 1548.52 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.41 | 05-NOV-13:00 | 2198.53 | 12-NOV-08:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.14 | 10-DEC-15:00 | 3494.58 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.72 | 220.56 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1468.75 | 3822.44 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.80 | 16-JAN-15:00 | 2682.86 | 21-JAN-05:55 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.24 | 02-FEB-13:00 | 3543.40 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.84 | 26-MAR-13:52 | 3399.43 | 20-MAR-21:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 486.78 | 29-APR-17:02 | 1895.98 | 01-APR-18:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 751.75 | 07-MAY-14:00 | 567.09 | 14-MAY-11:53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1053.69 | 10-JUN-17:02 | 511.83 | 18-JUN-14:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 888.58 | 22-JUL-18:50 | 538.24 | 30-JUL-10:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1216.50 | 20-AUG-14:00 | 787.12 | 25-AUG-23:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1371.30 | 09-SEP-23:00 | 859.99 | 05-SEP-03:03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1071.91 | 09-OCT-13:52 | 1459.11 | 29-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.62 | 05-NOV-13:00 | 2308.39 | 12-NOV-06:52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.35 | 10-DEC-15:00 | 3438.83 | 20-DEC-01:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.24 | 511.83 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1371.30 | 3543.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 118701.03 | 09-JAN-04:01 | 0.00 | 8831.65 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 119101.70 | 13-FEB-00:07 | 0.00 | 11039.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 114999.99 | 20-MAR-01:52 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 117244.94 | 03-APR-03:00 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103172.39 | 29-MAY-22:20 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96656.55 | 11-JUN-23:08 | 0.00 | 4415.82 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 103483.94 | 04-JUL-23:12 | 0.00 | 4415.82 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 101313.90 | 13-AUG-22:50 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106561.56 | 04-SEP-06:57 | 3590.45 | 4074.92 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 112653.38 | 28-OCT-03:50 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 116327.77 | 12-NOV-21:32 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 117529.69 | 17-DEC-17:53 | 2692.84 | 3056.19 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 96656.55 | 0.00 | 3056.19 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 119101.70 | 3590.45 | 11039.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 85891.23 | 01-JAN-02:11 | 0.00 | 9914.30 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 88771.81 | 28-FEB-04:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 85303.23 | 29-MAR-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86015.88 | 01-APR-03:01 | 0.00 | 9914.30 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 93581.22 | 23-MAY-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 92824.07 | 01-JUN-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82077.96 | 12-JUL-05:02 | 16122.38 | 18297.83 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 82530.71 | 01-AUG-03:01 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94001.22 | 26-SEP-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 90233.23 | 19-OCT-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86063.61 | 28-NOV-04:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83309.02 | 15-DEC-04:01 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 82077.96 | 0.00 | 9914.30 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94001.22 | 16122.38 | 18297.83 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 72408.38 | 19-JAN-05:02 | 0.00 | 9914.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 76088.21 | 27-FEB-05:02 | 0.00 | 19828.60 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 78414.72 | 30-MAR-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80463.53 | 15-APR-04:02 | 0.00 | 9914.30 | 60428.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86432.22 | 01-MAY-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 80136.27 | 07-JUN-03:01 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80788.63 | 06-JUL-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 78868.74 | 16-AUG-03:01 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80189.66 | 08-SEP-03:01 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79509.46 | 19-OCT-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77831.66 | 01-NOV-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79076.10 | 15-DEC-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 72408.38 | 0.00 | 9914.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86432.22 | 16122.38 | 19828.60 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 71717.66 | 20-JAN-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 73407.16 | 03-FEB-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 77254.93 | 30-MAR-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 79545.09 | 22-APR-04:02 | 0.00 | 9914.30 | 60428.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86500.65 | 22-MAY-03:03 | 0.00 | 5948.58 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86818.44 | 30-JUN-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 87103.72 | 31-JUL-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85476.94 | 24-AUG-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85788.42 | 05-SEP-03:03 | 0.00 | 5948.58 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 84563.94 | 06-OCT-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 77866.96 | 01-NOV-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 79291.63 | 16-DEC-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 71717.66 | 0.00 | 5948.58 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 87103.72 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10180.01 | 19-JAN-06:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.79 |
February | 10109.32 | 28-FEB-06:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.97 |
March | 10556.83 | 27-MAR-05:03 | 809.73 | 918.99 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.08 |
April | 10729.07 | 24-APR-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
May | 12320.77 | 22-MAY-04:41 | 0.00 | 2489.68 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 54.77 | 0.00 |
June | 12734.34 | 28-JUN-03:01 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 | 0.00 |
July | 12499.66 | 05-JUL-03:01 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.04 |
August | 12013.39 | 14-AUG-05:04 | 1012.16 | 1148.74 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 0.00 |
September | 12055.16 | 18-SEP-03:02 | 0.00 | 746.90 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 |
October | 12006.67 | 07-OCT-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 5.92 | 0.00 |
November | 10877.42 | 01-NOV-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
December | 11065.95 | 11-DEC-06:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10109.32 | 0.00 | 746.90 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12734.34 | 2024.33 | 2489.68 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 54.77 | 31.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7743.90 | 01-JAN-09:15 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.20 |
February | 7242.17 | 27-FEB-10:10 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
March | 9339.56 | 26-MAR-09:13 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.96 |
April | 15383.52 | 23-APR-08:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.79 |
May | 15872.85 | 29-MAY-08:11 | 652.28 | 540.42 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.96 |
June | 15322.57 | 11-JUN-08:42 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 9.26 | 0.00 |
July | 15506.76 | 16-JUL-09:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 59.32 | 0.00 |
August | 11075.69 | 06-AUG-09:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 33.46 | 0.00 |
September | 11998.29 | 10-SEP-09:23 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 116.35 | 0.00 |
October | 11173.74 | 15-OCT-08:53 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.71 |
November | 10572.41 | 12-NOV-08:30 | 652.28 | 540.42 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.20 |
December | 5204.17 | 08-DEC-09:40 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5204.17 | 260.91 | 216.17 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15872.85 | 1295.83 | 972.75 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 116.35 | 454.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18355.76 | 01-JAN-13:52 | 607.31 | 503.16 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.91 |
February | 16991.09 | 26-FEB-13:23 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.98 |
March | 12848.76 | 05-MAR-11:54 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 |
April | 11978.22 | 24-APR-05:01 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 |
May | 13542.31 | 08-MAY-05:02 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.70 |
June | 13579.29 | 14-JUN-03:01 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.30 |
July | 13922.90 | 05-JUL-03:01 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
August | 13240.36 | 14-AUG-05:04 | 1012.19 | 1148.76 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 7.63 | 0.00 |
September | 16672.80 | 10-SEP-12:43 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 0.00 |
October | 17105.32 | 01-OCT-13:42 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 0.00 |
November | 17118.24 | 11-NOV-11:13 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.86 |
December | 17313.92 | 10-DEC-11:13 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.92 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11978.22 | 0.00 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18355.76 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 161.64 | 38.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13885.41 | 19-JAN-06:01 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.48 |
February | 20124.88 | 26-FEB-17:22 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.27 |
March | 17246.92 | 30-MAR-03:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 19747.94 | 23-APR-16:52 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.00 |
May | 19257.55 | 29-MAY-16:22 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 65.50 | 0.00 |
June | 19569.89 | 11-JUN-16:32 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 54.03 | 0.00 |
July | 20308.07 | 30-JUL-15:42 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.32 |
August | 20374.06 | 06-AUG-17:12 | 0.00 | 292.81 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.79 |
September | 20216.45 | 10-SEP-16:41 | 652.28 | 540.42 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 | 0.00 |
October | 20353.55 | 08-OCT-16:02 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 123.35 | 0.00 |
November | 19596.19 | 05-NOV-15:12 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1.09 | 0.00 |
December | 17576.38 | 15-DEC-04:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.08 |
Annual Sum or Average | |||||||||||
Minimum of Months | 13885.41 | 0.00 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20374.06 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 123.35 | 67.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5286.34 | 31-JAN-15:00 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 0.00 |
February | 7280.30 | 28-FEB-06:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 |
March | 8931.62 | 30-MAR-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10618.28 | 29-APR-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 |
May | 12676.05 | 08-MAY-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.77 |
June | 12795.51 | 29-JUN-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
July | 12844.35 | 07-JUL-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4.81 | 0.00 |
August | 13047.57 | 21-AUG-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 0.00 |
September | 11662.09 | 11-SEP-03:02 | 0.00 | 622.42 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.22 |
October | 10892.38 | 24-OCT-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 4.46 | 0.00 |
November | 10714.25 | 02-NOV-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.59 |
December | 9548.61 | 15-DEC-06:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.80 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5286.34 | 0.00 | 622.42 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13047.57 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 23.10 | 68.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5885.20 | 19-JAN-09:50 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 |
February | 6303.47 | 27-FEB-10:00 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 |
March | 10019.40 | 30-MAR-05:01 | 1304.55 | 1480.58 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 15666.15 | 23-APR-09:43 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.98 |
May | 15956.00 | 29-MAY-08:11 | 652.28 | 540.42 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.36 |
June | 12311.45 | 29-JUN-03:01 | 0.00 | 802.22 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.03 |
July | 15381.40 | 16-JUL-10:43 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 108.41 | 0.00 |
August | 13375.06 | 27-AUG-08:22 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 46.76 | 0.00 |
September | 16275.04 | 03-SEP-09:32 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 52.95 | 0.00 |
October | 15536.40 | 09-OCT-09:23 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 91.13 | 0.00 |
November | 9289.06 | 02-NOV-05:01 | 1304.55 | 1480.58 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 |
December | 4521.24 | 10-DEC-09:32 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.62 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4521.24 | 0.00 | 216.17 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16275.04 | 1304.55 | 1480.58 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 108.41 | 162.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15638.80 | 01-JAN-11:23 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.60 |
February | 15572.55 | 26-FEB-13:32 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.15 |
March | 12158.53 | 30-MAR-05:02 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12074.13 | 29-APR-05:02 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.97 |
May | 13419.18 | 08-MAY-03:02 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 |
June | 13242.90 | 26-JUN-03:01 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14323.13 | 05-JUL-03:02 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 |
August | 14795.65 | 21-AUG-03:02 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
September | 15262.88 | 10-SEP-12:43 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 353.33 | 0.00 |
October | 15930.49 | 09-OCT-14:42 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 217.44 | 0.00 |
November | 15560.37 | 05-NOV-15:12 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.64 |
December | 15804.07 | 10-DEC-14:51 | 1012.19 | 838.61 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.16 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 12074.13 | 0.00 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15930.49 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 353.33 | 253.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7524.74 | 31-JAN-16:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 |
February | 11828.79 | 27-FEB-05:01 | 0.00 | 1604.44 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 11588.74 | 07-MAR-06:01 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.82 |
April | 15958.66 | 23-APR-17:53 | 0.00 | 234.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 |
May | 17377.27 | 29-MAY-16:52 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 | 0.00 |
June | 16092.82 | 11-JUN-17:12 | 0.00 | 292.81 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 154.17 | 0.00 |
July | 15939.91 | 30-JUL-16:22 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 13.05 | 0.00 |
August | 14803.65 | 07-AUG-03:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 27.51 | 0.00 |
September | 17206.28 | 03-SEP-16:12 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 178.90 | 0.00 |
October | 16667.72 | 08-OCT-16:02 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 277.91 | 0.00 |
November | 11300.89 | 03-NOV-05:01 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11817.86 | 15-DEC-06:01 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.01 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7524.74 | 0.00 | 234.25 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17377.27 | 1304.55 | 1604.44 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 277.91 | 83.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5542.18 | 31-JAN-15:50 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 25.18 | 0.00 |
February | 5934.54 | 22-FEB-14:40 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 11.90 | 0.00 |
March | 9179.15 | 30-MAR-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 10663.55 | 29-APR-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
May | 13967.33 | 08-MAY-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.93 |
June | 14627.92 | 25-JUN-16:22 | 607.30 | 503.15 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 135.35 | 0.00 |
July | 13979.41 | 27-JUL-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 |
August | 14566.20 | 20-AUG-13:42 | 506.08 | 419.29 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 796.61 | 0.00 |
September | 14520.68 | 10-SEP-16:41 | 1012.16 | 838.59 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 240.43 | 0.00 |
October | 14611.27 | 08-OCT-16:02 | 506.08 | 419.29 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 616.39 | 0.00 |
November | 10767.08 | 01-NOV-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.79 |
December | 10705.24 | 16-DEC-06:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.12 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5542.18 | 0.00 | 419.29 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14627.92 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 796.61 | 100.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5505.49 | 19-JAN-10:10 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 |
February | 5950.77 | 27-FEB-10:30 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 |
March | 7531.05 | 26-MAR-10:05 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.36 |
April | 15775.55 | 23-APR-09:53 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.18 |
May | 16160.34 | 29-MAY-08:11 | 652.28 | 540.42 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.44 |
June | 15627.25 | 04-JUN-10:23 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 79.39 | 0.00 |
July | 15800.01 | 16-JUL-10:43 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | 0.00 |
August | 15732.62 | 06-AUG-09:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 78.32 | 0.00 |
September | 16499.70 | 03-SEP-09:32 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 | 0.00 |
October | 15783.93 | 09-OCT-10:02 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 238.57 | 0.00 |
November | 8182.35 | 02-NOV-05:01 | 1304.55 | 1480.58 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
December | 4442.80 | 10-DEC-09:53 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4442.80 | 260.91 | 216.17 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16499.70 | 1304.55 | 1480.58 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 238.57 | 120.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 17300.02 | 01-JAN-14:02 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.74 |
February | 17138.17 | 26-FEB-14:13 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.08 |
March | 12613.42 | 05-MAR-15:10 | 607.31 | 503.16 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 0.00 |
April | 11869.34 | 29-APR-05:01 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.00 |
May | 15379.81 | 08-MAY-03:02 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.62 |
June | 15731.56 | 25-JUN-16:22 | 607.31 | 503.16 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 140.91 | 0.00 |
July | 15252.54 | 20-JUL-03:02 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 17.85 | 0.00 |
August | 16265.70 | 20-AUG-13:42 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 782.20 | 0.00 |
September | 17207.02 | 10-SEP-12:43 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 416.17 | 0.00 |
October | 17841.39 | 09-OCT-14:42 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 196.92 | 0.00 |
November | 17262.17 | 11-NOV-11:32 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.03 |
December | 17204.80 | 10-DEC-13:52 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11869.34 | 0.00 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17841.39 | 2024.37 | 2297.53 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 782.20 | 103.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7768.03 | 31-JAN-16:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 |
February | 9309.24 | 27-FEB-06:02 | 652.28 | 740.29 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12258.49 | 06-MAR-06:01 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.12 |
April | 17245.60 | 23-APR-17:53 | 0.00 | 234.25 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.79 |
May | 18793.48 | 29-MAY-16:52 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 96.51 | 0.00 |
June | 18399.06 | 25-JUN-16:22 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 69.47 | 0.00 |
July | 14431.49 | 20-JUL-03:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
August | 17126.58 | 06-AUG-17:12 | 0.00 | 292.81 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.58 |
September | 18661.21 | 03-SEP-16:12 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 198.12 | 0.00 |
October | 18047.67 | 08-OCT-16:02 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 300.49 | 0.00 |
November | 12113.88 | 03-NOV-05:01 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12769.52 | 16-DEC-06:01 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7768.03 | 0.00 | 234.25 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18793.48 | 1304.55 | 1480.58 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 300.49 | 117.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11381.85 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.99 |
February | 8747.33 | 21-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 |
March | 7299.05 | 20-MAR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.77 |
April | 8171.12 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.96 |
May | 10052.68 | 23-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 |
June | 8931.03 | 20-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 11257.62 | 05-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 0.00 |
August | 9643.59 | 31-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
September | 9878.22 | 06-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.88 |
October | 10395.68 | 11-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.17 |
November | 8459.89 | 13-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.97 |
December | 7869.88 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7299.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11381.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.49 | 274.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6258.11 | 02-JAN-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.66 |
February | 4990.40 | 24-FEB-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5065.77 | 30-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5583.99 | 21-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.52 |
May | 9424.14 | 08-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.56 |
June | 10053.07 | 30-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
July | 9235.56 | 07-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.05 |
August | 8767.08 | 23-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.49 | 0.00 |
September | 9776.55 | 01-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9844.67 | 07-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 0.00 |
November | 6852.03 | 07-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.22 |
December | 4981.95 | 18-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4981.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10053.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.88 | 493.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9243.17 | 19-JAN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.28 |
February | 10975.07 | 24-FEB-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
March | 11552.30 | 06-MAR-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 0.00 |
April | 15862.36 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.87 | 0.00 |
May | 16963.08 | 10-MAY-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.22 | 0.00 |
June | 17713.17 | 28-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.99 | 0.00 |
July | 18078.93 | 07-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.71 | 0.00 |
August | 17204.55 | 03-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.45 | 0.00 |
September | 15711.20 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.38 | 0.00 |
October | 15344.87 | 05-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.95 | 0.00 |
November | 12324.96 | 02-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 | 0.00 |
December | 10517.29 | 15-DEC-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9243.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18078.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.45 | 40.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1911.05 | 01-JAN-17:23 | 0.00 | 39.81 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4001.92 | 26-FEB-17:47 | 0.00 | 39.81 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5666.04 | 13-MAR-18:00 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7850.75 | 16-APR-18:05 | 0.00 | 28.76 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1975.66 | 01-MAY-00:05 | 0.00 | 57.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3853.30 | 11-JUN-18:12 | 0.00 | 57.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5649.09 | 16-JUL-18:50 | 0.00 | 28.76 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7595.51 | 06-AUG-18:05 | 0.00 | 28.76 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2030.98 | 03-SEP-18:00 | 0.00 | 28.76 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3917.58 | 09-OCT-17:20 | 0.00 | 57.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5846.34 | 12-NOV-16:53 | 0.00 | 39.81 | 17537.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7731.85 | 25-DEC-17:10 | 0.00 | 39.81 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1911.05 | 0.00 | 28.76 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7850.75 | 0.00 | 79.62 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1719.19 | 31-JAN-17:50 | 0.00 | 132.69 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3608.12 | 27-FEB-17:40 | 0.00 | 132.69 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5361.24 | 06-MAR-17:50 | 0.00 | 132.69 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7338.27 | 16-APR-18:20 | 0.00 | 71.90 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1784.86 | 29-MAY-18:16 | 0.00 | 71.90 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3612.20 | 11-JUN-18:15 | 0.00 | 57.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5328.96 | 07-JUL-16:00 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7147.11 | 30-AUG-18:40 | 0.00 | 79.62 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1890.77 | 03-SEP-18:00 | 0.00 | 28.76 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3634.88 | 09-OCT-17:35 | 0.00 | 143.79 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5480.07 | 06-NOV-17:00 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7214.86 | 15-DEC-17:00 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1719.19 | 0.00 | 28.76 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7338.27 | 0.00 | 238.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1778.66 | 31-JAN-17:40 | 0.00 | 132.69 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3655.62 | 27-FEB-17:40 | 0.00 | 132.69 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5422.63 | 06-MAR-17:50 | 0.00 | 132.69 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7465.11 | 16-APR-18:20 | 0.00 | 71.90 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2044.70 | 29-MAY-18:00 | 0.00 | 28.76 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3839.36 | 11-JUN-18:22 | 0.00 | 71.90 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5483.57 | 16-JUL-19:00 | 0.00 | 57.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7295.60 | 06-AUG-17:35 | 0.00 | 28.76 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2117.73 | 03-SEP-17:45 | 0.00 | 57.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3854.68 | 08-OCT-17:35 | 0.00 | 28.76 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5534.49 | 06-NOV-17:00 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7269.42 | 15-DEC-17:00 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1778.66 | 0.00 | 28.76 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7465.11 | 0.00 | 238.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 331360.61 | 05-JAN-01:03 | 0.00 | 3112.68 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 365780.34 | 07-FEB-05:32 | 0.00 | 6225.37 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 412290.20 | 20-MAR-21:42 | 0.00 | 5744.77 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365012.58 | 28-APR-18:50 | 0.00 | 1723.43 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 102980.19 | 01-MAY-00:08 | 0.00 | 1245.07 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 181958.85 | 13-JUN-16:00 | 0.00 | 5170.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 274193.44 | 06-JUL-16:00 | 0.00 | 5170.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 370988.69 | 06-AUG-15:42 | 0.00 | 1723.43 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106603.29 | 01-SEP-00:07 | 0.00 | 933.80 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 183561.99 | 10-OCT-16:00 | 0.00 | 5170.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 417263.85 | 26-NOV-06:32 | 0.00 | 2872.38 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 405106.73 | 19-DEC-04:43 | 0.00 | 3112.68 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 102980.19 | 0.00 | 933.80 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 417263.85 | 0.00 | 6225.37 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.177321E+13 | 1368730.20 | 19-JAN-16:40 | 0.641009E+11 | 413486.13 | 10-JAN-07:10 |
February | 0.202698E+13 | 1525221.45 | 27-FEB-16:00 | 0.519893E+11 | 545541.61 | 06-FEB-07:10 |
March | 0.270591E+13 | 1677795.66 | 07-MAR-08:00 | 0.551495E+11 | 478016.48 | 09-MAR-07:10 |
April | 0.308935E+13 | 1883624.23 | 28-APR-15:00 | 0.384373E+11 | 171198.09 | 11-APR-06:10 |
May | 0.221867E+13 | 1409915.41 | 26-MAY-15:09 | 0.384714E+11 | 140743.59 | 30-MAY-00:20 |
June | 0.259402E+13 | 1588245.47 | 28-JUN-15:09 | 0.348027E+11 | 94626.01 | 16-JUN-03:00 |
July | 0.306273E+13 | 1759078.58 | 03-JUL-15:00 | 0.339397E+11 | 94789.54 | 13-JUL-03:49 |
August | 0.355409E+13 | 1905774.96 | 03-AUG-15:00 | 0.361258E+11 | 138629.81 | 06-AUG-16:19 |
September | 0.214412E+13 | 1424178.59 | 05-SEP-07:00 | 0.352640E+11 | 141019.34 | 04-SEP-20:00 |
October | 0.254029E+13 | 1597795.59 | 06-OCT-15:09 | 0.390945E+11 | 170748.69 | 29-OCT-18:19 |
November | 0.267087E+13 | 1698294.96 | 02-NOV-15:09 | 0.416554E+11 | 204736.08 | 15-NOV-07:00 |
December | 0.302749E+13 | 1844516.10 | 14-DEC-16:19 | 0.574003E+11 | 758051.18 | 20-DEC-07:10 |
Annual Sum or Average | 0.314077E+14 | 0.526431E+12 | ||||
Minimum of Months | 0.177321E+13 | 1368730.20 | 0.339397E+11 | 94626.01 | ||
Maximum of Months | 0.355409E+13 | 1905774.96 | 0.641009E+11 | 758051.18 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.277303E+12 | 0.648464E+11 | 0.811612E+12 | 0.168779E+12 | 0.173001E+12 | 0.390486E+11 | 0.00 | 0.160063E+12 | 0.732752E+11 | 0.143491E+10 | 0.385132E+10 | 0.00 | 0.00 |
February | 0.250900E+12 | 0.554042E+11 | 0.102011E+13 | 0.152457E+12 | 0.156017E+12 | 0.447660E+11 | 0.00 | 0.242310E+12 | 0.100872E+12 | 0.779791E+09 | 0.336764E+10 | 0.00 | 0.00 |
March | 0.297315E+12 | 0.565728E+11 | 0.146224E+13 | 0.169058E+12 | 0.176041E+12 | 0.539513E+11 | 0.00 | 0.355693E+12 | 0.130372E+12 | 0.897574E+09 | 0.376177E+10 | 0.00 | 0.00 |
April | 0.265385E+12 | 0.501266E+11 | 0.170426E+13 | 0.163308E+12 | 0.171833E+12 | 0.712969E+11 | 0.00 | 0.502153E+12 | 0.155799E+12 | 0.267448E+09 | 0.492152E+10 | 0.00 | 0.00 |
May | 0.285633E+12 | 0.476310E+11 | 0.820095E+12 | 0.168918E+12 | 0.191125E+12 | 0.842512E+11 | 0.00 | 0.407702E+12 | 0.205760E+12 | 0.00 | 0.755740E+10 | 0.00 | 0.00 |
June | 0.283959E+12 | 0.438259E+11 | 0.110647E+13 | 0.163570E+12 | 0.189075E+12 | 0.884201E+11 | 0.00 | 0.506282E+12 | 0.204861E+12 | 0.00 | 0.755740E+10 | 0.00 | 0.00 |
July | 0.266172E+12 | 0.464854E+11 | 0.143833E+13 | 0.168655E+12 | 0.191630E+12 | 0.941885E+11 | 0.00 | 0.629056E+12 | 0.221042E+12 | 0.00 | 0.717347E+10 | 0.00 | 0.00 |
August | 0.296516E+12 | 0.498585E+11 | 0.177907E+13 | 0.169058E+12 | 0.198161E+12 | 0.991377E+11 | 0.00 | 0.733928E+12 | 0.220493E+12 | 0.00 | 0.786051E+10 | 0.00 | 0.00 |
September | 0.265570E+12 | 0.527996E+11 | 0.784429E+12 | 0.163308E+12 | 0.181217E+12 | 0.837173E+11 | 0.00 | 0.401511E+12 | 0.204398E+12 | 0.00 | 0.717347E+10 | 0.00 | 0.00 |
October | 0.276313E+12 | 0.594050E+11 | 0.112844E+13 | 0.168779E+12 | 0.188956E+12 | 0.808360E+11 | 0.00 | 0.446943E+12 | 0.184504E+12 | 0.204899E+09 | 0.590492E+10 | 0.00 | 0.00 |
November | 0.273951E+12 | 0.615187E+11 | 0.140306E+13 | 0.163415E+12 | 0.173369E+12 | 0.627484E+11 | 0.00 | 0.389049E+12 | 0.140123E+12 | 0.424975E+09 | 0.320636E+10 | 0.00 | 0.00 |
December | 0.268859E+12 | 0.658966E+11 | 0.175516E+13 | 0.168656E+12 | 0.175264E+12 | 0.495098E+11 | 0.00 | 0.408860E+12 | 0.130495E+12 | 0.964260E+09 | 0.382744E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.330788E+13 | 0.654371E+12 | 0.152133E+14 | 0.198796E+13 | 0.216569E+13 | 0.851872E+12 | 0.00 | 0.518355E+13 | 0.197199E+13 | 0.497386E+10 | 0.661632E+11 | ||
Minimum of Months | 0.250900E+12 | 0.438259E+11 | 0.784429E+12 | 0.152457E+12 | 0.156017E+12 | 0.390486E+11 | 0.00 | 0.160063E+12 | 0.732752E+11 | 0.00 | 0.320636E+10 | 0.00 | 0.00 |
Maximum of Months | 0.297315E+12 | 0.658966E+11 | 0.177907E+13 | 0.169058E+12 | 0.198161E+12 | 0.991377E+11 | 0.00 | 0.733928E+12 | 0.221042E+12 | 0.143491E+10 | 0.786051E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.220890E+11 | 0.00 | 0.420119E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.141585E+11 | 0.00 | 0.378308E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.125703E+11 | 0.00 | 0.425792E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.170699E+10 | 0.00 | 0.367303E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.184973E+10 | 0.00 | 0.366217E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.724866E+09 | 0.00 | 0.340778E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.190987E+10 | 0.00 | 0.320298E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.138336E+10 | 0.00 | 0.347425E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.191106E+10 | 0.00 | 0.333529E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.231313E+10 | 0.00 | 0.367814E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.322217E+10 | 0.00 | 0.384332E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.172398E+11 | 0.00 | 0.401605E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.810788E+11 | 0.445352E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.724866E+09 | 0.00 | 0.320298E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.220890E+11 | 0.00 | 0.425792E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 296479.25 | 31-JAN-08:09 | 53035.91 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 128032.24 | 31-JAN-08:20 | 129768.37 | 04-JAN-09:50 | 56861.53 | 31-JAN-16:00 | 0.00 | 01-JAN-00:10 |
February | 298087.52 | 01-FEB-08:09 | 53035.91 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 128033.58 | 01-FEB-08:20 | 130265.53 | 17-FEB-10:50 | 56928.80 | 28-FEB-16:10 | 0.00 | 01-FEB-00:10 |
March | 295024.24 | 27-MAR-07:10 | 53035.91 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 128031.03 | 27-MAR-07:19 | 124707.32 | 27-MAR-05:10 | 56420.86 | 29-MAR-12:09 | 0.00 | 01-MAR-00:10 |
April | 296328.02 | 14-APR-07:10 | 53035.91 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 128032.12 | 14-APR-07:19 | 168045.35 | 18-APR-14:50 | 56844.16 | 24-APR-09:20 | 0.00 | 01-APR-00:10 |
May | 287060.48 | 23-MAY-07:19 | 53035.91 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 128024.42 | 23-MAY-07:30 | 127099.51 | 04-MAY-15:00 | 57373.80 | 26-MAY-14:00 | 0.00 | 01-MAY-00:10 |
June | 284162.65 | 08-JUN-07:10 | 53035.91 | 01-JUN-05:10 | 557421.28 | 01-JUN-07:10 | 128022.02 | 08-JUN-07:19 | 131763.71 | 19-JUN-05:10 | 57167.61 | 01-JUN-12:50 | 0.00 | 01-JUN-00:10 |
July | 285193.16 | 14-JUL-07:10 | 53035.91 | 01-JUL-05:10 | 675712.68 | 03-JUL-07:10 | 128022.87 | 14-JUL-07:19 | 133114.07 | 07-JUL-15:00 | 57629.33 | 31-JUL-12:39 | 0.00 | 01-JUL-00:10 |
August | 288324.93 | 21-AUG-07:10 | 53035.91 | 01-AUG-05:10 | 794004.08 | 01-AUG-07:10 | 128025.47 | 21-AUG-07:19 | 137766.06 | 30-AUG-15:00 | 57775.26 | 07-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 294999.31 | 26-SEP-07:10 | 53035.91 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 128031.01 | 26-SEP-07:19 | 127808.35 | 01-SEP-14:00 | 57269.67 | 05-SEP-15:09 | 0.00 | 01-SEP-00:10 |
October | 300301.40 | 25-OCT-07:10 | 53035.91 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 128035.42 | 25-OCT-07:19 | 134105.23 | 05-OCT-15:30 | 57053.81 | 10-OCT-07:49 | 0.00 | 01-OCT-00:10 |
November | 298129.51 | 21-NOV-16:00 | 53035.91 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 128033.46 | 01-NOV-07:19 | 122893.84 | 15-NOV-17:00 | 57035.71 | 29-NOV-16:10 | 0.00 | 01-NOV-00:10 |
December | 299894.10 | 12-DEC-08:09 | 53035.91 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 128035.08 | 12-DEC-08:20 | 131307.68 | 20-DEC-11:09 | 56812.71 | 13-DEC-09:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 284162.65 | 53035.91 | 439129.89 | 128022.02 | 122893.84 | 56420.86 | 0.00 | |||||||
Maximum of Months | 300301.40 | 53035.91 | 794004.08 | 128035.42 | 168045.35 | 57775.26 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 291580.87 | 19-JAN-16:40 | 93657.26 | 02-JAN-10:00 | 17441.64 | 04-JAN-22:19 | 5613.05 | 02-JAN-10:20 | 0.00 | 0.00 |
February | 327605.71 | 28-FEB-16:10 | 93657.26 | 01-FEB-13:30 | 25734.20 | 13-FEB-22:40 | 5613.05 | 01-FEB-12:09 | 0.00 | 0.00 |
March | 359647.34 | 30-MAR-12:00 | 93657.26 | 06-MAR-09:30 | 19904.90 | 20-MAR-21:10 | 5613.05 | 02-MAR-21:40 | 0.00 | 0.00 |
April | 435529.61 | 28-APR-15:00 | 93657.26 | 01-APR-06:40 | 4120.12 | 10-APR-11:00 | 5613.05 | 01-APR-06:10 | 0.00 | 0.00 |
May | 332633.96 | 26-MAY-15:09 | 93657.26 | 01-MAY-03:20 | 0.00 | 01-MAY-00:10 | 5613.05 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 377420.80 | 28-JUN-14:09 | 93657.26 | 01-JUN-06:30 | 0.00 | 01-JUN-00:10 | 5613.05 | 01-JUN-06:10 | 0.00 | 0.00 |
July | 429278.59 | 03-JUL-15:00 | 93657.26 | 01-JUL-03:20 | 0.00 | 01-JUL-00:10 | 5613.05 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 456403.65 | 14-AUG-10:00 | 93657.26 | 01-AUG-03:30 | 0.00 | 01-AUG-00:10 | 5613.05 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 335716.99 | 18-SEP-13:00 | 93657.26 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 | 5613.05 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 396123.62 | 06-OCT-13:00 | 93657.26 | 02-OCT-09:39 | 3770.14 | 27-OCT-11:00 | 5613.05 | 02-OCT-08:50 | 0.00 | 0.00 |
November | 394104.42 | 01-NOV-13:20 | 93657.26 | 01-NOV-05:40 | 10000.00 | 15-NOV-22:40 | 5613.05 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 416145.20 | 12-DEC-14:39 | 93657.26 | 09-DEC-10:00 | 8695.95 | 30-DEC-17:40 | 5613.05 | 02-DEC-13:30 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||
Minimum of Months | 291580.87 | 93657.26 | 0.00 | 5613.05 | 0.00 | 0.00 | ||||
Maximum of Months | 456403.65 | 93657.26 | 25734.20 | 5613.05 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1368730.20 | 19-JAN-16:40 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 107334.64 | 56608.64 | 0.00 | 291580.87 | 93657.26 |
February | 1525221.45 | 27-FEB-16:00 | 283685.72 | 557421.28 | 0.00 | 91242.13 | 113586.00 | 56704.38 | 0.00 | 323311.63 | 93657.26 |
March | 1677795.66 | 07-MAR-08:00 | 283563.73 | 675712.68 | 0.00 | 128021.52 | 87360.61 | 56282.68 | 0.00 | 347584.13 | 93657.26 |
April | 1883624.23 | 28-APR-15:00 | 283563.73 | 794004.08 | 0.00 | 91242.13 | 124220.97 | 55793.40 | 0.00 | 435529.61 | 93657.26 |
May | 1409915.41 | 26-MAY-15:09 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 106735.94 | 57339.46 | 0.00 | 332633.96 | 93657.26 |
June | 1588245.47 | 28-JUN-15:09 | 283563.73 | 557421.28 | 0.00 | 91242.13 | 126849.11 | 55974.97 | 0.00 | 373923.95 | 93657.26 |
July | 1759078.58 | 03-JUL-15:00 | 283563.73 | 675712.68 | 0.00 | 91242.13 | 123620.31 | 56390.83 | 0.00 | 429278.59 | 93657.26 |
August | 1905774.96 | 03-AUG-15:00 | 283563.73 | 794004.08 | 0.00 | 91242.13 | 135633.55 | 56002.50 | 0.00 | 446058.67 | 93657.26 |
September | 1424178.59 | 05-SEP-07:00 | 283563.73 | 439129.89 | 0.00 | 128021.52 | 96971.93 | 56923.23 | 0.00 | 320297.98 | 93657.26 |
October | 1597795.59 | 06-OCT-15:09 | 283563.73 | 557421.28 | 0.00 | 91242.13 | 128668.79 | 56452.43 | 0.00 | 381176.92 | 93657.26 |
November | 1698294.96 | 02-NOV-15:09 | 283563.73 | 675712.68 | 0.00 | 91242.13 | 120916.87 | 55370.89 | 0.00 | 372218.34 | 93657.26 |
December | 1844516.10 | 14-DEC-16:19 | 285408.29 | 794004.08 | 0.00 | 91242.49 | 112876.12 | 56116.74 | 0.00 | 405598.08 | 93657.26 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1368730.20 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 87360.61 | 55370.89 | 0.00 | 291580.87 | 93657.26 | |
Maximum of Months | 1905774.96 | 285408.29 | 794004.08 | 0.00 | 128021.52 | 135633.55 | 57339.46 | 0.00 | 446058.67 | 93657.26 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 407790.26 | 10-JAN-07:10 | 0.00 | 68176.84 | 19-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 539845.74 | 06-FEB-07:10 | 0.00 | 68120.50 | 01-FEB-12:50 | 0.00 |
March | 0.00 | 0.00 | 472320.61 | 09-MAR-07:10 | 0.00 | 66476.93 | 06-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 165502.22 | 11-APR-06:10 | 0.00 | 63587.46 | 03-APR-11:39 | 0.00 |
May | 0.00 | 0.00 | 135047.72 | 30-MAY-00:20 | 0.00 | 59544.45 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 88930.14 | 16-JUN-03:00 | 0.00 | 54172.03 | 05-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 89093.67 | 13-JUL-03:49 | 0.00 | 51010.95 | 03-JUL-11:39 | 0.00 |
August | 0.00 | 0.00 | 132933.94 | 06-AUG-16:19 | 0.00 | 52591.25 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 135323.47 | 04-SEP-20:00 | 0.00 | 56788.76 | 29-SEP-11:20 | 0.00 |
October | 0.00 | 0.00 | 165052.82 | 29-OCT-18:19 | 0.00 | 61733.08 | 31-OCT-11:20 | 0.00 |
November | 0.00 | 0.00 | 199040.21 | 15-NOV-07:00 | 0.00 | 65457.73 | 30-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 752355.31 | 20-DEC-07:10 | 0.00 | 68572.57 | 20-DEC-13:20 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 88930.14 | 0.00 | 51010.95 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 752355.31 | 0.00 | 68572.57 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 26.92 | 1.67 | 27.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 9.17 | 26.82 | 1.33 | 27.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.55 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.66 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 26.77 | 0.67 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.64 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.89 | 1.00 | 27.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.50 | 26.55 | 1.33 | 27.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.72 | 1.50 | 27.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.87 | 2.17 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 26.67 | 1.83 | 27.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 26.79 | 1.67 | 27.82 |
Annual Sum or Average | 0.00 | 0.00 | 125.33 | 26.75 | 13.17 | 27.60 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.55 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 26.92 | 2.17 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.71 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 25.66 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.71 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.47 | 0.33 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.62 | 3.50 | 27.62 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.41 | 0.50 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.33 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.69 | 2.00 | 27.69 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.54 | 0.67 | 27.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.35 | 0.17 | 27.35 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 8.50 | 27.59 | 8.50 | 27.59 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.69 | 3.50 | 27.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.76 | 6.83 | 26.76 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 26.31 | 3.17 | 26.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.33 | 1.67 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.76 | 6.33 | 27.76 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 | 26.05 | 16.33 | 26.05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 25.65 | 20.83 | 25.65 |
Annual Sum or Average | 0.00 | 0.00 | 55.33 | 26.24 | 55.17 | 26.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 27.76 | 20.83 | 27.76 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.67 | 0.83 | 27.74 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.43 | 2.17 | 27.54 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.34 | 4.67 | 27.79 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.69 | 1.17 | 28.08 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 14.33 | 27.45 | 3.33 | 27.65 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 27.00 | 5.00 | 27.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 26.67 | 3.50 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.78 | 2.33 | 27.96 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.48 | 4.83 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.47 | 2.33 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.32 | 3.67 | 27.56 |
Annual Sum or Average | 0.00 | 0.00 | 95.33 | 27.24 | 33.83 | 27.70 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 16.17 | 27.78 | 5.00 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.65 | 0.67 | 27.65 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.76 | 3.33 | 27.76 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.54 | 1.17 | 27.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.73 | 2.33 | 27.73 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.67 | 27.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.79 | 2.17 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.61 | 0.67 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.00 | 27.69 | 11.00 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.79 | 3.33 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 25.78 | 12.33 | 25.78 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 25.43 | 5.83 | 25.43 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.47 | 2.33 | 27.47 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 18.33 | 25.74 | 18.17 | 25.72 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 25.52 | 29.33 | 25.52 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 25.44 | 24.00 | 25.44 |
Annual Sum or Average | 0.00 | 0.00 | 92.17 | 25.62 | 92.00 | 25.62 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.47 | 29.33 | 27.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.59 | 0.67 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.84 | 1.00 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.85 | 1.17 | 27.83 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.44 | 0.83 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.87 | 1.83 | 27.88 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.56 | 1.50 | 27.58 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.00 | 27.74 | 7.17 | 27.73 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.87 | 1.83 | 27.98 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.00 | 18.87 | 0.33 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.65 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 26.90 | 0.50 | 27.32 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.32 | 0.67 | 27.32 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.00 | 19.05 | 0.33 | 20.30 | 1.50 | 26.94 | 1.17 | 27.32 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.23 | 0.33 | 20.30 | 0.67 | 27.32 | 0.67 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 19.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 17.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.66 | 0.67 | 27.66 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.84 | 3.67 | 27.84 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.76 | 1.17 | 27.76 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.72 | 4.17 | 27.72 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.48 | 1.33 | 27.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.73 | 3.83 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.61 | 1.00 | 27.61 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.50 | 18.83 | 0.00 | 15.83 | 27.72 | 15.83 | 27.72 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.26 | 0.00 | 0.00 | 4.17 | 27.84 | 4.17 | 27.84 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 26.16 | 5.00 | 26.16 |
February | 0.33 | 18.81 | 0.00 | 0.00 | 2.17 | 26.02 | 2.17 | 26.02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.61 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.62 | 4.33 | 27.63 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.26 | 8.00 | 27.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 25.65 | 12.83 | 25.65 |
December | 0.17 | 19.44 | 0.00 | 0.00 | 6.67 | 26.33 | 6.67 | 26.33 |
Annual Sum or Average | 0.50 | 19.02 | 0.00 | 40.17 | 26.42 | 39.17 | 26.40 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.44 | 0.00 | 0.00 | 12.83 | 27.62 | 12.83 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 18.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.67 | 1.00 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.10 | 1.00 | 28.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.94 | 2.00 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.48 | 2.00 | 27.52 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.45 | 1.00 | 27.43 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 28.03 | 2.50 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.75 | 1.83 | 27.79 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.16 | 0.00 | 16.67 | 27.82 | 11.33 | 27.82 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.44 | 0.00 | 0.00 | 3.50 | 28.10 | 2.50 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.00 | 27.59 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 27.59 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.59 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 28.63 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 27.91 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 240.17 | 28.21 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.50 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.60 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 255.00 | 28.19 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 240.17 | 28.63 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.33 | 24.66 | 242.67 | 25.12 | 37.33 | 24.86 |
February | 82.67 | 24.69 | 317.00 | 24.74 | 66.67 | 24.85 |
March | 100.50 | 24.61 | 316.00 | 24.66 | 81.00 | 24.76 |
April | 168.83 | 24.77 | 431.00 | 24.57 | 168.83 | 24.77 |
May | 276.67 | 24.87 | 508.00 | 24.51 | 276.67 | 24.87 |
June | 252.67 | 24.86 | 496.00 | 24.46 | 252.67 | 24.86 |
July | 251.33 | 25.22 | 497.00 | 24.62 | 251.33 | 25.22 |
August | 205.67 | 25.21 | 514.00 | 24.49 | 205.67 | 25.21 |
September | 214.17 | 25.14 | 485.00 | 24.57 | 214.17 | 25.14 |
October | 157.00 | 25.39 | 452.83 | 24.69 | 157.00 | 25.39 |
November | 76.67 | 25.37 | 386.00 | 24.79 | 76.67 | 25.37 |
December | 60.33 | 25.00 | 313.67 | 24.96 | 58.50 | 25.03 |
Annual Sum or Average | 1895.83 | 25.01 | 4959.17 | 24.65 | 1846.50 | 25.04 |
Minimum of Months | 49.33 | 24.61 | 242.67 | 24.46 | 37.33 | 24.76 |
Maximum of Months | 276.67 | 25.39 | 514.00 | 25.12 | 276.67 | 25.39 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.50 | 23.75 | 221.50 | 24.63 | 0.00 | 0.00 |
February | 21.33 | 23.87 | 305.00 | 24.45 | 0.00 | 0.00 |
March | 14.33 | 23.87 | 310.00 | 24.45 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 422.17 | 24.27 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 482.67 | 24.25 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 474.83 | 24.19 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 481.33 | 24.18 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 510.83 | 24.14 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 457.83 | 24.25 | 0.00 | 0.00 |
October | 1.00 | 23.56 | 440.33 | 24.33 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 379.67 | 24.44 | 0.00 | 0.00 |
December | 7.50 | 23.99 | 313.67 | 24.51 | 0.00 | 0.00 |
Annual Sum or Average | 87.67 | 23.82 | 4799.83 | 24.31 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 221.50 | 24.14 | 0.00 | 0.00 |
Maximum of Months | 43.50 | 23.99 | 510.83 | 24.63 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 192.00 | 23.52 | 114.83 | 24.27 | 0.00 | 0.00 |
February | 137.83 | 23.57 | 166.17 | 24.26 | 0.00 | 0.00 |
March | 140.00 | 23.53 | 185.50 | 24.30 | 0.00 | 0.00 |
April | 41.50 | 23.24 | 267.83 | 24.40 | 0.00 | 0.00 |
May | 16.83 | 23.20 | 354.17 | 24.25 | 0.00 | 0.00 |
June | 17.00 | 23.19 | 349.33 | 24.22 | 0.00 | 0.00 |
July | 19.67 | 23.22 | 341.17 | 24.25 | 0.00 | 0.00 |
August | 14.83 | 23.17 | 375.17 | 24.23 | 0.00 | 0.00 |
September | 31.17 | 23.20 | 308.00 | 24.23 | 0.00 | 0.00 |
October | 35.17 | 23.43 | 312.83 | 24.30 | 0.00 | 0.00 |
November | 76.67 | 23.47 | 222.00 | 24.34 | 0.00 | 0.00 |
December | 157.17 | 23.49 | 145.83 | 24.37 | 0.00 | 0.00 |
Annual Sum or Average | 879.83 | 23.47 | 3142.83 | 24.27 | 0.00 | |
Minimum of Months | 14.83 | 23.17 | 114.83 | 24.22 | 0.00 | 0.00 |
Maximum of Months | 192.00 | 23.57 | 375.17 | 24.40 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 359.17 | 22.78 | 80.67 | 24.02 | 2.67 | 21.03 |
February | 249.67 | 22.72 | 136.33 | 23.66 | 15.33 | 20.31 |
March | 228.67 | 23.00 | 169.67 | 24.17 | 1.83 | 20.52 |
April | 74.33 | 23.28 | 263.50 | 24.33 | 0.00 | 0.00 |
May | 8.00 | 23.14 | 405.33 | 24.27 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 419.00 | 24.24 | 0.00 | 0.00 |
July | 0.83 | 23.30 | 426.17 | 24.27 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 422.17 | 24.26 | 0.00 | 0.00 |
September | 6.50 | 23.29 | 349.67 | 24.26 | 0.00 | 0.00 |
October | 53.00 | 23.21 | 327.67 | 24.29 | 0.00 | 0.00 |
November | 199.17 | 23.16 | 165.33 | 24.15 | 0.00 | 0.00 |
December | 303.33 | 22.94 | 94.50 | 24.15 | 0.00 | 0.00 |
Annual Sum or Average | 1482.67 | 22.93 | 3260.00 | 24.22 | 19.83 | 20.43 |
Minimum of Months | 0.00 | 0.00 | 80.67 | 23.66 | 0.00 | 0.00 |
Maximum of Months | 359.17 | 23.30 | 426.17 | 24.33 | 15.33 | 21.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 312.83 | 23.03 | 113.67 | 24.24 | 0.00 | 0.00 |
February | 182.50 | 23.10 | 155.17 | 24.22 | 0.00 | 0.00 |
March | 166.17 | 23.33 | 217.17 | 24.25 | 0.00 | 0.00 |
April | 21.50 | 23.63 | 359.33 | 24.20 | 0.00 | 0.00 |
May | 11.00 | 25.97 | 507.67 | 24.36 | 11.00 | 25.97 |
June | 0.00 | 0.00 | 494.50 | 24.31 | 0.00 | 0.00 |
July | 0.33 | 26.20 | 496.50 | 24.37 | 0.33 | 26.20 |
August | 0.50 | 26.23 | 514.00 | 24.25 | 0.50 | 26.23 |
September | 7.83 | 25.68 | 476.33 | 24.35 | 7.83 | 25.68 |
October | 30.17 | 23.74 | 423.17 | 24.35 | 3.50 | 25.63 |
November | 99.83 | 23.59 | 247.33 | 24.22 | 0.00 | 0.00 |
December | 184.50 | 23.31 | 178.67 | 24.22 | 0.00 | 0.00 |
Annual Sum or Average | 1017.17 | 23.29 | 4183.50 | 24.30 | 23.17 | 25.83 |
Minimum of Months | 0.00 | 0.00 | 113.67 | 24.20 | 0.00 | 0.00 |
Maximum of Months | 312.83 | 26.23 | 514.00 | 24.37 | 11.00 | 26.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 330.67 | 22.70 | 103.17 | 24.40 | 0.67 | 26.26 |
February | 245.50 | 22.74 | 129.17 | 24.27 | 1.67 | 21.32 |
March | 242.00 | 22.73 | 178.67 | 24.31 | 1.17 | 26.31 |
April | 130.50 | 22.92 | 255.17 | 24.14 | 1.67 | 26.36 |
May | 36.00 | 25.22 | 416.00 | 24.41 | 24.17 | 26.29 |
June | 14.50 | 23.93 | 420.83 | 24.24 | 4.17 | 26.21 |
July | 23.00 | 24.13 | 418.83 | 24.26 | 7.67 | 26.41 |
August | 34.67 | 23.01 | 402.50 | 24.10 | 0.83 | 25.87 |
September | 62.00 | 23.99 | 363.50 | 24.41 | 18.50 | 26.36 |
October | 84.17 | 23.18 | 325.00 | 24.33 | 6.00 | 26.23 |
November | 194.67 | 22.94 | 200.67 | 24.27 | 0.67 | 26.26 |
December | 307.67 | 22.72 | 102.33 | 24.19 | 0.17 | 25.86 |
Annual Sum or Average | 1705.33 | 22.92 | 3315.83 | 24.28 | 67.33 | 26.18 |
Minimum of Months | 14.50 | 22.70 | 102.33 | 24.10 | 0.17 | 21.32 |
Maximum of Months | 330.67 | 25.22 | 420.83 | 24.41 | 24.17 | 26.41 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 176.83 | 23.40 | 209.00 | 24.64 | 15.67 | 26.89 |
February | 114.50 | 23.24 | 256.00 | 24.41 | 9.33 | 25.14 |
March | 145.67 | 23.09 | 242.17 | 24.34 | 1.50 | 26.38 |
April | 30.67 | 23.43 | 342.83 | 24.22 | 0.00 | 0.00 |
May | 10.33 | 25.85 | 499.33 | 24.33 | 10.33 | 25.85 |
June | 0.00 | 0.00 | 488.00 | 24.28 | 0.00 | 0.00 |
July | 0.17 | 26.03 | 490.83 | 24.33 | 0.17 | 26.03 |
August | 1.83 | 26.13 | 511.67 | 24.25 | 1.83 | 26.13 |
September | 21.33 | 26.23 | 462.50 | 24.42 | 21.33 | 26.23 |
October | 45.83 | 25.70 | 450.67 | 24.52 | 31.67 | 26.72 |
November | 62.83 | 24.67 | 361.67 | 24.60 | 22.67 | 26.82 |
December | 122.50 | 23.73 | 288.17 | 24.64 | 19.83 | 26.90 |
Annual Sum or Average | 732.50 | 23.75 | 4602.83 | 24.39 | 134.33 | 26.52 |
Minimum of Months | 0.00 | 0.00 | 209.00 | 24.22 | 0.00 | 0.00 |
Maximum of Months | 176.83 | 26.23 | 511.67 | 24.64 | 31.67 | 26.90 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 242.33 | 22.90 | 161.00 | 24.43 | 1.17 | 25.66 |
February | 97.67 | 23.23 | 278.17 | 24.42 | 3.17 | 26.48 |
March | 55.67 | 23.73 | 359.17 | 24.48 | 8.67 | 26.31 |
April | 22.17 | 26.43 | 467.67 | 24.50 | 22.17 | 26.43 |
May | 19.50 | 26.43 | 486.17 | 24.35 | 19.50 | 26.43 |
June | 19.83 | 26.30 | 493.17 | 24.39 | 19.83 | 26.30 |
July | 34.50 | 26.16 | 497.00 | 24.48 | 34.50 | 26.16 |
August | 29.33 | 26.12 | 514.00 | 24.39 | 29.33 | 26.12 |
September | 20.17 | 26.50 | 444.67 | 24.37 | 20.17 | 26.50 |
October | 33.83 | 25.37 | 464.67 | 24.45 | 22.50 | 26.39 |
November | 24.17 | 24.95 | 409.83 | 24.48 | 11.83 | 26.44 |
December | 44.83 | 24.38 | 348.83 | 24.65 | 14.67 | 26.34 |
Annual Sum or Average | 644.00 | 24.10 | 4924.33 | 24.44 | 207.50 | 26.32 |
Minimum of Months | 19.50 | 22.90 | 161.00 | 24.35 | 1.17 | 25.66 |
Maximum of Months | 242.33 | 26.50 | 514.00 | 24.65 | 34.50 | 26.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 413.83 | 22.07 | 63.67 | 23.12 | 19.67 | 21.15 |
February | 327.33 | 22.29 | 91.17 | 23.04 | 20.50 | 19.70 |
March | 318.50 | 22.62 | 113.17 | 23.80 | 8.50 | 20.53 |
April | 148.67 | 23.43 | 247.33 | 24.23 | 12.17 | 25.56 |
May | 31.83 | 25.57 | 507.00 | 24.33 | 31.83 | 25.57 |
June | 13.67 | 25.99 | 492.00 | 24.34 | 13.67 | 25.99 |
July | 38.17 | 25.97 | 487.83 | 24.44 | 38.17 | 25.97 |
August | 24.83 | 25.70 | 506.50 | 24.33 | 24.83 | 25.70 |
September | 37.00 | 25.21 | 443.00 | 24.32 | 36.83 | 25.22 |
October | 102.00 | 23.80 | 376.00 | 24.30 | 31.50 | 25.44 |
November | 269.67 | 22.81 | 119.50 | 24.07 | 0.50 | 23.55 |
December | 385.00 | 22.37 | 70.83 | 23.63 | 13.67 | 21.90 |
Annual Sum or Average | 2110.50 | 22.76 | 3518.00 | 24.24 | 251.83 | 24.40 |
Minimum of Months | 13.67 | 22.07 | 63.67 | 23.04 | 0.50 | 19.70 |
Maximum of Months | 413.83 | 25.99 | 507.00 | 24.44 | 38.17 | 25.99 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 377.00 | 22.05 | 40.00 | 23.59 | 12.17 | 21.63 |
February | 297.17 | 22.18 | 66.50 | 23.34 | 14.83 | 20.43 |
March | 280.17 | 22.31 | 106.17 | 24.24 | 5.33 | 21.44 |
April | 160.17 | 22.98 | 194.50 | 24.46 | 14.67 | 25.89 |
May | 55.83 | 25.29 | 336.17 | 24.53 | 39.50 | 26.25 |
June | 29.17 | 25.24 | 342.00 | 24.45 | 19.67 | 26.36 |
July | 54.17 | 25.34 | 349.00 | 24.58 | 38.17 | 26.36 |
August | 45.50 | 24.54 | 337.67 | 24.44 | 22.83 | 26.14 |
September | 98.67 | 23.93 | 273.33 | 24.53 | 33.00 | 26.06 |
October | 139.50 | 23.31 | 236.17 | 24.51 | 26.00 | 25.99 |
November | 268.50 | 22.53 | 83.17 | 24.43 | 0.67 | 26.60 |
December | 355.33 | 22.13 | 37.33 | 23.43 | 13.83 | 22.17 |
Annual Sum or Average | 2161.17 | 22.67 | 2402.00 | 24.42 | 240.67 | 25.26 |
Minimum of Months | 29.17 | 22.05 | 37.33 | 23.34 | 0.67 | 20.43 |
Maximum of Months | 377.00 | 25.34 | 349.00 | 24.58 | 39.50 | 26.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 219.83 | 23.11 | 196.50 | 24.66 | 21.67 | 26.04 |
February | 162.50 | 22.90 | 215.67 | 24.32 | 13.83 | 23.37 |
March | 210.83 | 22.71 | 188.67 | 24.20 | 5.50 | 21.55 |
April | 111.50 | 23.45 | 280.33 | 24.29 | 11.67 | 25.70 |
May | 30.17 | 25.52 | 492.17 | 24.32 | 30.17 | 25.52 |
June | 14.33 | 25.64 | 483.17 | 24.31 | 13.17 | 25.85 |
July | 31.67 | 25.86 | 482.33 | 24.41 | 31.67 | 25.86 |
August | 23.83 | 25.81 | 501.17 | 24.34 | 23.83 | 25.81 |
September | 49.33 | 25.85 | 451.67 | 24.41 | 49.00 | 25.86 |
October | 77.33 | 25.34 | 437.00 | 24.56 | 50.00 | 26.46 |
November | 107.67 | 23.93 | 315.17 | 24.65 | 21.00 | 26.83 |
December | 185.17 | 23.22 | 244.50 | 24.72 | 21.67 | 26.62 |
Annual Sum or Average | 1224.17 | 23.60 | 4288.33 | 24.42 | 293.17 | 25.86 |
Minimum of Months | 14.33 | 22.71 | 188.67 | 24.20 | 5.50 | 21.55 |
Maximum of Months | 219.83 | 25.86 | 501.17 | 24.72 | 50.00 | 26.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 403.00 | 22.11 | 62.33 | 23.75 | 12.00 | 21.70 |
February | 304.00 | 22.20 | 104.33 | 23.64 | 13.50 | 19.75 |
March | 309.50 | 22.38 | 132.33 | 24.14 | 5.17 | 20.91 |
April | 142.33 | 23.21 | 260.00 | 24.44 | 14.67 | 26.36 |
May | 35.67 | 25.29 | 419.67 | 24.36 | 27.50 | 25.96 |
June | 22.00 | 25.74 | 439.50 | 24.37 | 17.83 | 26.42 |
July | 37.50 | 25.66 | 448.50 | 24.43 | 30.83 | 26.23 |
August | 22.50 | 25.76 | 470.00 | 24.35 | 19.50 | 26.18 |
September | 70.67 | 24.12 | 365.00 | 24.37 | 28.83 | 25.92 |
October | 106.00 | 23.61 | 331.67 | 24.36 | 26.83 | 25.89 |
November | 277.33 | 22.59 | 128.67 | 24.23 | 0.17 | 24.31 |
December | 354.33 | 22.25 | 92.67 | 24.21 | 6.17 | 23.70 |
Annual Sum or Average | 2084.83 | 22.67 | 3254.67 | 24.32 | 203.00 | 25.22 |
Minimum of Months | 22.00 | 22.11 | 62.33 | 23.64 | 0.17 | 19.75 |
Maximum of Months | 403.00 | 25.76 | 470.00 | 24.44 | 30.83 | 26.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 450.67 | 21.53 | 127.83 | 21.34 | 96.33 | 20.47 |
February | 367.50 | 21.78 | 115.17 | 21.77 | 60.83 | 19.78 |
March | 371.17 | 22.18 | 123.50 | 22.90 | 37.33 | 20.27 |
April | 190.17 | 23.02 | 222.00 | 24.23 | 12.17 | 25.53 |
May | 34.83 | 25.52 | 485.17 | 24.34 | 34.83 | 25.52 |
June | 18.67 | 25.74 | 484.83 | 24.35 | 17.00 | 26.00 |
July | 45.67 | 26.05 | 482.67 | 24.46 | 45.67 | 26.05 |
August | 34.67 | 25.67 | 491.50 | 24.35 | 33.50 | 25.76 |
September | 56.17 | 24.84 | 416.00 | 24.34 | 44.33 | 25.27 |
October | 127.83 | 23.41 | 346.67 | 24.32 | 34.50 | 25.45 |
November | 334.83 | 22.32 | 99.50 | 23.82 | 9.33 | 21.76 |
December | 420.83 | 21.82 | 96.83 | 22.30 | 52.67 | 20.87 |
Annual Sum or Average | 2453.00 | 22.35 | 3491.67 | 24.03 | 478.50 | 22.83 |
Minimum of Months | 18.67 | 21.53 | 96.83 | 21.34 | 9.33 | 19.78 |
Maximum of Months | 450.67 | 26.05 | 491.50 | 24.46 | 96.33 | 26.05 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 447.83 | 21.62 | 88.67 | 21.73 | 59.67 | 20.58 |
February | 356.17 | 21.84 | 103.50 | 22.45 | 37.00 | 19.62 |
March | 328.17 | 22.06 | 159.83 | 23.66 | 26.00 | 20.65 |
April | 172.17 | 22.79 | 251.83 | 24.32 | 15.17 | 25.88 |
May | 64.67 | 25.12 | 423.50 | 24.44 | 43.50 | 26.20 |
June | 34.50 | 25.30 | 431.67 | 24.37 | 24.83 | 26.26 |
July | 61.33 | 25.47 | 434.33 | 24.49 | 45.50 | 26.35 |
August | 55.17 | 24.69 | 431.67 | 24.36 | 31.83 | 26.04 |
September | 109.17 | 24.07 | 356.83 | 24.42 | 44.33 | 25.94 |
October | 160.00 | 23.17 | 306.67 | 24.41 | 30.67 | 25.91 |
November | 334.17 | 22.34 | 96.67 | 24.08 | 4.67 | 23.41 |
December | 422.00 | 21.81 | 72.17 | 22.42 | 38.83 | 21.04 |
Annual Sum or Average | 2545.33 | 22.42 | 3157.33 | 24.17 | 402.00 | 23.82 |
Minimum of Months | 34.50 | 21.62 | 72.17 | 21.73 | 4.67 | 19.62 |
Maximum of Months | 447.83 | 25.47 | 434.33 | 24.49 | 59.67 | 26.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 273.00 | 22.42 | 162.83 | 24.01 | 41.83 | 22.60 |
February | 220.00 | 22.28 | 193.83 | 23.85 | 30.17 | 21.29 |
March | 270.83 | 22.29 | 182.33 | 23.73 | 27.17 | 20.76 |
April | 163.33 | 23.04 | 246.83 | 24.28 | 11.83 | 25.65 |
May | 31.50 | 25.45 | 462.33 | 24.34 | 31.50 | 25.45 |
June | 20.00 | 25.26 | 464.67 | 24.33 | 15.50 | 25.89 |
July | 40.50 | 25.71 | 469.83 | 24.43 | 37.67 | 25.89 |
August | 36.50 | 25.67 | 487.17 | 24.35 | 34.17 | 25.84 |
September | 72.00 | 25.41 | 425.67 | 24.43 | 59.83 | 25.87 |
October | 97.67 | 24.74 | 411.83 | 24.53 | 53.17 | 26.39 |
November | 167.17 | 23.16 | 267.50 | 24.58 | 17.50 | 26.47 |
December | 244.17 | 22.57 | 211.00 | 24.35 | 33.50 | 23.82 |
Annual Sum or Average | 1636.67 | 23.06 | 3985.83 | 24.33 | 393.83 | 24.70 |
Minimum of Months | 20.00 | 22.28 | 162.83 | 23.73 | 11.83 | 20.76 |
Maximum of Months | 273.00 | 25.71 | 487.17 | 24.58 | 59.83 | 26.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 428.17 | 21.68 | 92.67 | 22.32 | 51.00 | 20.77 |
February | 336.17 | 21.79 | 104.00 | 22.79 | 33.00 | 19.74 |
March | 339.33 | 21.99 | 131.50 | 23.52 | 23.83 | 20.51 |
April | 187.67 | 22.88 | 228.50 | 24.42 | 16.83 | 26.24 |
May | 66.67 | 24.17 | 400.67 | 24.36 | 29.00 | 25.85 |
June | 40.17 | 24.79 | 421.50 | 24.38 | 21.50 | 26.47 |
July | 47.67 | 25.24 | 426.33 | 24.45 | 34.00 | 26.19 |
August | 43.33 | 24.89 | 444.17 | 24.36 | 27.33 | 26.09 |
September | 102.67 | 23.78 | 345.50 | 24.37 | 34.83 | 25.81 |
October | 145.17 | 23.23 | 306.17 | 24.37 | 30.00 | 25.81 |
November | 322.67 | 22.19 | 105.50 | 24.19 | 2.67 | 24.17 |
December | 382.17 | 21.83 | 97.67 | 23.39 | 26.83 | 21.23 |
Annual Sum or Average | 2441.83 | 22.35 | 3104.17 | 24.19 | 330.83 | 23.79 |
Minimum of Months | 40.17 | 21.68 | 92.67 | 22.32 | 2.67 | 19.74 |
Maximum of Months | 428.17 | 25.24 | 444.17 | 24.45 | 51.00 | 26.47 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.55073 | 38.06427 | 0.49975 | 11.14734 |
February | 454.00000 | 24.51970 | 46.42345 | 0.54784 | 12.11729 |
March | 514.00000 | 24.41699 | 45.21891 | 0.51730 | 11.36247 |
April | 485.00000 | 24.49815 | 56.87018 | 0.61575 | 13.67772 |
May | 508.00000 | 24.50281 | 64.40075 | -0.1760 | 6.84117 |
June | 496.00000 | 24.45260 | 64.22842 | -0.1894 | 6.79841 |
July | 497.00000 | 24.61014 | 63.48277 | -0.1394 | 7.02046 |
August | 514.00000 | 24.48770 | 61.91520 | -0.1705 | 6.90375 |
September | 485.00000 | 24.56297 | 62.12386 | -0.1534 | 6.96366 |
October | 502.00000 | 24.61766 | 56.54700 | 0.66093 | 15.22242 |
November | 489.00000 | 24.61990 | 47.66497 | 0.59617 | 13.34690 |
December | 497.00000 | 24.61068 | 42.66930 | 0.55456 | 12.45550 |
Annual Sum or Average | 5943.00000 | 24.53709 | 54.17950 | 0.26055 | 10.29653 |
Minimum of Months | 454.00000 | 24.41699 | 38.06427 | -0.1894 | 6.79841 |
Maximum of Months | 514.00000 | 24.61990 | 64.40075 | 0.66093 | 15.22242 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.28113 | 37.39129 | 0.43356 | 9.37108 |
February | 454.00000 | 24.31007 | 41.84722 | 0.47823 | 10.19053 |
March | 514.00000 | 24.26312 | 40.91535 | 0.47038 | 9.97429 |
April | 485.00000 | 24.23214 | 46.57085 | 0.51216 | 10.70106 |
May | 508.00000 | 24.21519 | 49.29714 | -0.3425 | 7.81398 |
June | 496.00000 | 24.16437 | 49.19231 | -0.3514 | 7.78239 |
July | 497.00000 | 24.16007 | 49.01206 | -0.3467 | 7.66417 |
August | 514.00000 | 24.13489 | 49.03010 | -0.3420 | 7.54434 |
September | 485.00000 | 24.20719 | 49.22653 | -0.3421 | 7.80162 |
October | 502.00000 | 24.27226 | 46.74004 | 0.52402 | 11.00218 |
November | 489.00000 | 24.33575 | 43.43875 | 0.51435 | 10.88788 |
December | 497.00000 | 24.32417 | 39.87603 | 0.48348 | 10.29183 |
Annual Sum or Average | 5943.00000 | 24.24094 | 45.22758 | 0.13756 | 9.23946 |
Minimum of Months | 454.00000 | 24.13489 | 37.39129 | -0.3514 | 7.54434 |
Maximum of Months | 514.00000 | 24.33575 | 49.29714 | 0.52402 | 11.00218 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.90873 | 38.93162 | 0.32401 | 7.57531 |
February | 454.00000 | 23.92523 | 43.58369 | 0.36425 | 8.19997 |
March | 514.00000 | 23.94846 | 42.60427 | 0.37101 | 8.24610 |
April | 485.00000 | 24.07003 | 47.94351 | 0.44713 | 9.48716 |
May | 508.00000 | 24.06423 | 49.98700 | -0.4103 | 8.90867 |
June | 496.00000 | 24.04536 | 49.92789 | -0.4145 | 8.93774 |
July | 497.00000 | 24.05082 | 49.91161 | -0.4150 | 9.00460 |
August | 514.00000 | 24.06592 | 49.98566 | -0.4058 | 8.79879 |
September | 485.00000 | 23.99448 | 50.21640 | -0.4347 | 9.35242 |
October | 502.00000 | 24.07535 | 47.82170 | 0.45794 | 9.65309 |
November | 489.00000 | 24.01107 | 45.08784 | 0.40982 | 8.80236 |
December | 497.00000 | 23.92284 | 41.88359 | 0.35471 | 8.04070 |
Annual Sum or Average | 5943.00000 | 24.00744 | 46.50240 | 0.05089 | 8.75051 |
Minimum of Months | 454.00000 | 23.90873 | 38.93162 | -0.4347 | 7.57531 |
Maximum of Months | 514.00000 | 24.07535 | 50.21640 | 0.45794 | 9.65309 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.11892 | 41.25905 | 0.12533 | 6.75022 |
February | 454.00000 | 23.28052 | 45.29788 | 0.20526 | 7.76328 |
March | 514.00000 | 23.58805 | 43.81343 | 0.28074 | 7.84194 |
April | 485.00000 | 23.99844 | 48.21077 | 0.43308 | 9.30414 |
May | 508.00000 | 24.14122 | 49.48512 | -0.3683 | 8.23050 |
June | 496.00000 | 24.15974 | 49.24849 | -0.3570 | 7.99762 |
July | 497.00000 | 24.18611 | 49.21985 | -0.3518 | 7.97378 |
August | 514.00000 | 24.15493 | 49.45213 | -0.3594 | 8.08178 |
September | 485.00000 | 24.07355 | 49.85940 | -0.3973 | 8.68480 |
October | 502.00000 | 24.04830 | 47.82194 | 0.45586 | 9.81284 |
November | 489.00000 | 23.67009 | 46.40462 | 0.32316 | 7.74682 |
December | 497.00000 | 23.35340 | 43.80233 | 0.20882 | 7.08777 |
Annual Sum or Average | 5943.00000 | 23.81809 | 46.99243 | 0.01424 | 8.10539 |
Minimum of Months | 454.00000 | 23.11892 | 41.25905 | -0.3973 | 6.75022 |
Maximum of Months | 514.00000 | 24.18611 | 49.85940 | 0.45586 | 9.81284 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.42510 | 39.10481 | 0.20301 | 7.04854 |
February | 454.00000 | 23.66026 | 42.28099 | 0.29529 | 7.93766 |
March | 514.00000 | 23.85822 | 41.22859 | 0.34630 | 8.27594 |
April | 485.00000 | 24.11511 | 46.28988 | 0.47314 | 9.88993 |
May | 508.00000 | 24.34952 | 49.50563 | -0.2671 | 7.16786 |
June | 496.00000 | 24.30118 | 48.48211 | -0.2690 | 6.98592 |
July | 497.00000 | 24.35832 | 48.69832 | -0.2435 | 6.85505 |
August | 514.00000 | 24.24826 | 48.72053 | -0.2740 | 6.96620 |
September | 485.00000 | 24.32668 | 49.90336 | -0.2827 | 7.35957 |
October | 502.00000 | 24.25270 | 47.35740 | 0.52497 | 11.25640 |
November | 489.00000 | 23.99555 | 43.77988 | 0.40658 | 8.86107 |
December | 497.00000 | 23.79990 | 40.96423 | 0.32331 | 7.93596 |
Annual Sum or Average | 5943.00000 | 24.05997 | 45.54161 | 0.10069 | 8.04034 |
Minimum of Months | 454.00000 | 23.42510 | 39.10481 | -0.2827 | 6.85505 |
Maximum of Months | 514.00000 | 24.35832 | 49.90336 | 0.52497 | 11.25640 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.19594 | 38.94945 | 0.18368 | 7.21830 |
February | 454.00000 | 23.34440 | 42.63580 | 0.25709 | 7.73890 |
March | 514.00000 | 23.45744 | 41.66104 | 0.29236 | 8.20623 |
April | 485.00000 | 23.70395 | 47.02125 | 0.41591 | 9.26899 |
May | 508.00000 | 24.20140 | 49.25079 | -0.2640 | 7.84477 |
June | 496.00000 | 24.09863 | 48.61209 | -0.2913 | 7.57889 |
July | 497.00000 | 24.10390 | 48.92170 | -0.2877 | 7.70279 |
August | 514.00000 | 23.92832 | 49.27544 | -0.3475 | 8.23493 |
September | 485.00000 | 24.10027 | 49.81964 | -0.3153 | 8.60751 |
October | 502.00000 | 23.95309 | 47.51579 | 0.48627 | 10.79598 |
November | 489.00000 | 23.62452 | 44.33080 | 0.35301 | 8.47984 |
December | 497.00000 | 23.18417 | 41.90940 | 0.20947 | 7.13247 |
Annual Sum or Average | 5943.00000 | 23.74395 | 45.83934 | 0.05529 | 8.23515 |
Minimum of Months | 454.00000 | 23.18417 | 38.94945 | -0.3475 | 7.13247 |
Maximum of Months | 514.00000 | 24.20140 | 49.81964 | 0.48627 | 10.79598 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.94406 | 37.11751 | 0.37814 | 9.83514 |
February | 454.00000 | 23.98583 | 40.88268 | 0.41949 | 10.22598 |
March | 514.00000 | 23.86937 | 40.76979 | 0.37456 | 9.15328 |
April | 485.00000 | 24.07636 | 46.25530 | 0.47664 | 10.05119 |
May | 508.00000 | 24.31155 | 49.51277 | -0.2765 | 7.23375 |
June | 496.00000 | 24.26487 | 48.55961 | -0.2840 | 7.12807 |
July | 497.00000 | 24.32048 | 48.72497 | -0.2555 | 6.93373 |
August | 514.00000 | 24.24012 | 48.61475 | -0.2638 | 6.89812 |
September | 485.00000 | 24.37498 | 49.42820 | -0.2392 | 7.31060 |
October | 502.00000 | 24.43563 | 46.28049 | 0.61338 | 13.83083 |
November | 489.00000 | 24.37273 | 42.23174 | 0.55391 | 12.47144 |
December | 497.00000 | 24.17237 | 39.41467 | 0.47061 | 11.31060 |
Annual Sum or Average | 5943.00000 | 24.19791 | 44.83787 | 0.16099 | 9.35050 |
Minimum of Months | 454.00000 | 23.86937 | 37.11751 | -0.2840 | 6.89812 |
Maximum of Months | 514.00000 | 24.43563 | 49.51277 | 0.61338 | 13.83083 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.53609 | 37.79882 | 0.29500 | 8.21583 |
February | 454.00000 | 24.00235 | 40.64820 | 0.45402 | 10.55979 |
March | 514.00000 | 24.24624 | 39.40250 | 0.52738 | 11.78922 |
April | 485.00000 | 24.46806 | 44.49626 | 0.67238 | 15.15026 |
May | 508.00000 | 24.29284 | 48.69323 | -0.1912 | 7.00857 |
June | 496.00000 | 24.36701 | 47.55405 | -0.1311 | 6.38183 |
July | 497.00000 | 24.46276 | 47.42919 | -0.0786 | 6.22734 |
August | 514.00000 | 24.37948 | 47.38318 | -0.0653 | 5.96808 |
September | 485.00000 | 24.26752 | 48.87770 | -0.2040 | 7.24214 |
October | 502.00000 | 24.37975 | 45.87583 | 0.63737 | 14.31241 |
November | 489.00000 | 24.36499 | 41.96462 | 0.58325 | 12.85559 |
December | 497.00000 | 24.39071 | 38.50777 | 0.55875 | 12.56160 |
Annual Sum or Average | 5943.00000 | 24.26429 | 44.06991 | 0.25249 | 9.83361 |
Minimum of Months | 454.00000 | 23.53609 | 37.79882 | -0.2040 | 5.96808 |
Maximum of Months | 514.00000 | 24.46806 | 48.87770 | 0.67238 | 15.15026 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.38934 | 42.31214 | -0.0492 | 7.03203 |
February | 454.00000 | 22.74255 | 45.05777 | 0.06633 | 7.72013 |
March | 514.00000 | 23.12736 | 43.90580 | 0.15850 | 7.28598 |
April | 485.00000 | 23.86000 | 48.71505 | 0.39358 | 8.86167 |
May | 508.00000 | 24.32137 | 51.64287 | -0.2841 | 7.38007 |
June | 496.00000 | 24.32234 | 50.21966 | -0.2777 | 7.26816 |
July | 497.00000 | 24.41470 | 51.51452 | -0.2405 | 7.29777 |
August | 514.00000 | 24.31088 | 51.60647 | -0.2791 | 7.38130 |
September | 485.00000 | 24.26112 | 52.90992 | -0.3132 | 7.80652 |
October | 502.00000 | 24.07281 | 50.45563 | 0.47747 | 10.67786 |
November | 489.00000 | 23.32461 | 46.60547 | 0.23065 | 7.17092 |
December | 497.00000 | 22.70984 | 44.96531 | 0.05367 | 6.95949 |
Annual Sum or Average | 5943.00000 | 23.66093 | 48.34110 | -0.0067 | 7.73429 |
Minimum of Months | 454.00000 | 22.38934 | 42.31214 | -0.3132 | 6.95949 |
Maximum of Months | 514.00000 | 24.41470 | 52.90992 | 0.47747 | 10.67786 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 22.26718 | 41.64775 | -0.0438 | 6.84715 |
February | 385.00000 | 22.58124 | 44.32439 | 0.06208 | 7.23599 |
March | 433.00000 | 22.94917 | 42.98691 | 0.15517 | 7.79110 |
April | 410.00000 | 23.69233 | 48.24835 | 0.39495 | 9.50961 |
May | 430.00000 | 24.24595 | 50.84817 | -0.2591 | 8.37933 |
June | 418.00000 | 24.23021 | 49.64309 | -0.2642 | 7.89105 |
July | 422.00000 | 24.34408 | 50.72295 | -0.2222 | 8.12879 |
August | 433.00000 | 24.16429 | 51.08625 | -0.2879 | 8.31731 |
September | 410.00000 | 24.04663 | 52.16914 | -0.3419 | 9.76945 |
October | 427.00000 | 23.83010 | 50.03585 | 0.45414 | 10.95031 |
November | 417.00000 | 23.06715 | 46.02938 | 0.20779 | 7.24992 |
December | 422.00000 | 22.38658 | 44.65205 | 0.00895 | 6.90605 |
Annual Sum or Average | 5034.00000 | 23.48902 | 47.71090 | -0.0123 | 8.25074 |
Minimum of Months | 385.00000 | 22.26718 | 41.64775 | -0.3419 | 6.84715 |
Maximum of Months | 433.00000 | 24.34408 | 52.16914 | 0.45414 | 10.95031 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.75663 | 38.22961 | 0.32914 | 9.67124 |
February | 454.00000 | 23.74973 | 41.82536 | 0.35426 | 9.88664 |
March | 514.00000 | 23.54045 | 42.24738 | 0.28382 | 8.55325 |
April | 485.00000 | 23.95577 | 48.10254 | 0.43118 | 9.53803 |
May | 508.00000 | 24.29147 | 51.57513 | -0.2904 | 7.44397 |
June | 496.00000 | 24.28449 | 50.29863 | -0.2940 | 7.40809 |
July | 497.00000 | 24.37789 | 51.49569 | -0.2529 | 7.34804 |
August | 514.00000 | 24.31666 | 51.30937 | -0.2630 | 7.27317 |
September | 485.00000 | 24.35462 | 51.96536 | -0.2516 | 7.63491 |
October | 502.00000 | 24.43015 | 48.36640 | 0.61036 | 14.07009 |
November | 489.00000 | 24.25372 | 43.18601 | 0.51220 | 11.92781 |
December | 497.00000 | 23.92237 | 41.08637 | 0.39855 | 10.83013 |
Annual Sum or Average | 5943.00000 | 24.10428 | 46.67012 | 0.12783 | 9.28715 |
Minimum of Months | 454.00000 | 23.54045 | 38.22961 | -0.2940 | 7.27317 |
Maximum of Months | 514.00000 | 24.43015 | 51.96536 | 0.61036 | 14.07009 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.46763 | 40.98888 | 0.01243 | 7.02082 |
February | 454.00000 | 22.78525 | 43.97310 | 0.12561 | 7.90979 |
March | 514.00000 | 23.03525 | 43.03867 | 0.18683 | 7.69303 |
April | 485.00000 | 23.83385 | 47.78757 | 0.44541 | 10.29098 |
May | 508.00000 | 24.16063 | 50.98022 | -0.2787 | 7.89303 |
June | 496.00000 | 24.23915 | 49.59003 | -0.2452 | 7.47547 |
July | 497.00000 | 24.30857 | 50.57685 | -0.2208 | 7.50092 |
August | 514.00000 | 24.24304 | 50.57875 | -0.2367 | 7.34031 |
September | 485.00000 | 24.06519 | 51.84745 | -0.3173 | 8.72825 |
October | 502.00000 | 23.95102 | 49.38172 | 0.49674 | 11.39850 |
November | 489.00000 | 23.18253 | 45.83371 | 0.24908 | 7.53922 |
December | 497.00000 | 22.74967 | 43.65152 | 0.10980 | 7.32857 |
Annual Sum or Average | 5943.00000 | 23.59064 | 47.36849 | 0.02567 | 8.17154 |
Minimum of Months | 454.00000 | 22.46763 | 40.98888 | -0.3173 | 7.02082 |
Maximum of Months | 514.00000 | 24.30857 | 51.84745 | 0.49674 | 11.39850 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.76093 | 43.92910 | -0.2127 | 8.81593 |
February | 454.00000 | 22.17826 | 46.51164 | -0.0729 | 9.16309 |
March | 514.00000 | 22.66914 | 44.89180 | 0.04966 | 7.94837 |
April | 485.00000 | 23.63959 | 49.29820 | 0.34992 | 8.66165 |
May | 508.00000 | 24.30607 | 51.68952 | -0.2711 | 7.39450 |
June | 496.00000 | 24.32496 | 50.15783 | -0.2554 | 7.17425 |
July | 497.00000 | 24.42598 | 51.39549 | -0.2164 | 7.29205 |
August | 514.00000 | 24.30370 | 51.71660 | -0.2622 | 7.38593 |
September | 485.00000 | 24.22758 | 53.23552 | -0.3080 | 8.07885 |
October | 502.00000 | 23.93539 | 50.97366 | 0.45413 | 10.82998 |
November | 489.00000 | 22.81493 | 47.87089 | 0.11237 | 7.15681 |
December | 497.00000 | 22.12956 | 46.66386 | -0.0908 | 7.91431 |
Annual Sum or Average | 5943.00000 | 23.40154 | 49.03651 | -0.0611 | 8.14325 |
Minimum of Months | 454.00000 | 21.76093 | 43.92910 | -0.3080 | 7.15681 |
Maximum of Months | 514.00000 | 24.42598 | 53.23552 | 0.45413 | 10.82998 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.86111 | 42.92490 | -0.1539 | 7.85741 |
February | 454.00000 | 22.27162 | 45.65572 | -0.0142 | 8.38035 |
March | 514.00000 | 22.78716 | 43.79738 | 0.11660 | 8.38220 |
April | 485.00000 | 23.63289 | 48.46854 | 0.39422 | 9.69876 |
May | 508.00000 | 24.22541 | 50.74864 | -0.2348 | 8.00550 |
June | 496.00000 | 24.22455 | 49.55751 | -0.2288 | 7.42580 |
July | 497.00000 | 24.32750 | 50.50262 | -0.1926 | 7.75807 |
August | 514.00000 | 24.16745 | 51.02059 | -0.2544 | 7.87646 |
September | 485.00000 | 24.06026 | 52.26078 | -0.3127 | 9.36937 |
October | 502.00000 | 23.78944 | 50.13029 | 0.45794 | 11.35278 |
November | 489.00000 | 22.83632 | 47.01544 | 0.15443 | 7.19578 |
December | 497.00000 | 22.09427 | 45.94789 | -0.0702 | 7.51171 |
Annual Sum or Average | 5943.00000 | 23.36433 | 48.17750 | -0.0291 | 8.39828 |
Minimum of Months | 454.00000 | 21.86111 | 42.92490 | -0.3127 | 7.19578 |
Maximum of Months | 514.00000 | 24.32750 | 52.26078 | 0.45794 | 11.35278 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23191 | 39.83327 | 0.18860 | 9.35451 |
February | 454.00000 | 23.24954 | 43.21164 | 0.22883 | 9.97664 |
March | 514.00000 | 23.14040 | 43.27038 | 0.18717 | 8.80832 |
April | 485.00000 | 23.73624 | 48.71861 | 0.38771 | 9.26435 |
May | 508.00000 | 24.26179 | 51.64951 | -0.2817 | 7.52387 |
June | 496.00000 | 24.27177 | 50.26369 | -0.2761 | 7.36884 |
July | 497.00000 | 24.37637 | 51.40476 | -0.2326 | 7.36347 |
August | 514.00000 | 24.29942 | 51.45102 | -0.2494 | 7.33428 |
September | 485.00000 | 24.30492 | 52.34652 | -0.2513 | 7.98240 |
October | 502.00000 | 24.29873 | 48.91910 | 0.58753 | 13.91436 |
November | 489.00000 | 23.90319 | 44.19917 | 0.42532 | 10.86664 |
December | 497.00000 | 23.42544 | 42.69350 | 0.27207 | 10.20614 |
Annual Sum or Average | 5943.00000 | 23.87845 | 47.35389 | 0.07997 | 9.15283 |
Minimum of Months | 454.00000 | 23.14040 | 39.83327 | -0.2817 | 7.33428 |
Maximum of Months | 514.00000 | 24.37637 | 52.34652 | 0.58753 | 13.91436 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.00560 | 42.36450 | -0.1103 | 7.93978 |
February | 454.00000 | 22.34252 | 45.26213 | 0.01616 | 8.78946 |
March | 514.00000 | 22.66713 | 43.99069 | 0.09952 | 8.09546 |
April | 485.00000 | 23.60310 | 48.42982 | 0.40000 | 9.97064 |
May | 508.00000 | 24.08877 | 51.19885 | -0.2835 | 8.23576 |
June | 496.00000 | 24.18770 | 49.70410 | -0.2402 | 7.66380 |
July | 497.00000 | 24.26216 | 50.65317 | -0.2154 | 7.69428 |
August | 514.00000 | 24.18722 | 50.84176 | -0.2355 | 7.57877 |
September | 485.00000 | 23.97164 | 52.37048 | -0.3304 | 9.36648 |
October | 502.00000 | 23.78992 | 49.98441 | 0.46842 | 11.33953 |
November | 489.00000 | 22.78426 | 46.92513 | 0.15588 | 7.37172 |
December | 497.00000 | 22.31529 | 45.14574 | -0.0000 | 7.75007 |
Annual Sum or Average | 5943.00000 | 23.35764 | 48.08361 | -0.0241 | 8.47540 |
Minimum of Months | 454.00000 | 22.00560 | 42.36450 | -0.3304 | 7.37172 |
Maximum of Months | 514.00000 | 24.26216 | 52.37048 | 0.46842 | 11.33953 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.599957E+11 | 129790.21 | 19-JAN-06:02 | 258.02 | 0.358131E+12 | 0.00 | 0.418126E+12 | 1.79 | 7.69 | 19-JAN-06:02 | 0.00 | 0.00 |
February | 0.808917E+11 | 129036.22 | 03-FEB-06:03 | 312.48 | 0.504930E+12 | 0.00 | 0.585821E+12 | 2.58 | 7.67 | 03-FEB-06:03 | 0.00 | 0.00 |
March | 0.974542E+11 | 135268.05 | 07-MAR-06:02 | 385.72 | 0.598466E+12 | 0.00 | 0.695920E+12 | 2.78 | 7.62 | 07-MAR-06:02 | 0.00 | 0.00 |
April | 0.143163E+12 | 147196.29 | 29-APR-05:02 | 527.01 | 0.915045E+12 | 0.00 | 0.105821E+13 | 4.13 | 7.70 | 24-APR-05:02 | 0.00 | 0.00 |
May | 0.194032E+12 | 212983.03 | 24-MAY-05:03 | 536.84 | 0.126089E+13 | 0.00 | 0.145493E+13 | 4.48 | 7.63 | 13-MAY-05:02 | 0.00 | 0.00 |
June | 0.199589E+12 | 180803.68 | 24-JUN-05:03 | 580.08 | 0.126527E+13 | 0.00 | 0.146486E+13 | 4.75 | 7.65 | 01-JUN-05:02 | 0.00 | 0.00 |
July | 0.212346E+12 | 187967.26 | 25-JUL-05:03 | 634.86 | 0.130855E+13 | 0.00 | 0.152089E+13 | 4.77 | 7.34 | 31-JUL-03:02 | 0.00 | 0.00 |
August | 0.216774E+12 | 199940.43 | 11-AUG-05:03 | 656.73 | 0.135156E+13 | 0.00 | 0.156833E+13 | 4.95 | 7.52 | 17-AUG-05:02 | 0.00 | 0.00 |
September | 0.193276E+12 | 191152.21 | 06-SEP-05:03 | 539.78 | 0.124269E+13 | 0.00 | 0.143596E+13 | 4.55 | 7.65 | 22-SEP-05:02 | 0.00 | 0.00 |
October | 0.175589E+12 | 188566.83 | 21-OCT-05:03 | 548.50 | 0.110894E+13 | 0.00 | 0.128453E+13 | 4.25 | 7.64 | 03-OCT-05:02 | 0.00 | 0.00 |
November | 0.118841E+12 | 163408.85 | 01-NOV-05:03 | 450.71 | 0.726406E+12 | 0.00 | 0.845246E+12 | 3.38 | 7.75 | 08-NOV-06:02 | 0.00 | 0.00 |
December | 0.832516E+11 | 148736.87 | 15-DEC-06:03 | 341.88 | 0.506500E+12 | 0.00 | 0.589751E+12 | 2.39 | 7.65 | 15-DEC-06:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.177520E+13 | 5772.59 | 0.111474E+14 | 0.129226E+14 | 3.74 | |||||||
Minimum of Months | 0.599957E+11 | 129036.22 | 258.02 | 0.358131E+12 | 0.00 | 0.418126E+12 | 1.79 | 7.34 | 0.00 | 0.00 | ||
Maximum of Months | 0.216774E+12 | 212983.03 | 656.73 | 0.135156E+13 | 0.00 | 0.156833E+13 | 4.95 | 7.75 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.510635E+10 | 129790.21 | 19-JAN-06:02 | 12.42 | 0.358659E+11 | 0.00 | 0.409722E+11 | 0.12 | 7.69 | 19-JAN-06:02 | 0.00 | 0.00 |
February | 0.993472E+10 | 129036.22 | 03-FEB-06:03 | 24.28 | 0.699982E+11 | 0.00 | 0.799330E+11 | 0.25 | 7.67 | 03-FEB-06:03 | 0.00 | 0.00 |
March | 0.128030E+11 | 135268.05 | 07-MAR-06:02 | 31.09 | 0.889500E+11 | 0.00 | 0.101753E+12 | 0.29 | 7.62 | 07-MAR-06:02 | 0.00 | 0.00 |
April | 0.198647E+11 | 147196.29 | 29-APR-05:02 | 47.09 | 0.137030E+12 | 0.00 | 0.156894E+12 | 0.45 | 7.70 | 24-APR-05:02 | 0.00 | 0.00 |
May | 0.820483E+11 | 212983.03 | 24-MAY-05:03 | 187.57 | 0.553253E+12 | 0.00 | 0.635302E+12 | 1.70 | 7.63 | 13-MAY-05:02 | 0.00 | 0.00 |
June | 0.837850E+11 | 180803.68 | 24-JUN-05:03 | 188.79 | 0.554450E+12 | 0.00 | 0.638235E+12 | 1.74 | 7.65 | 01-JUN-05:02 | 0.00 | 0.00 |
July | 0.874647E+11 | 187967.26 | 25-JUL-05:03 | 192.45 | 0.570525E+12 | 0.00 | 0.657990E+12 | 1.69 | 7.34 | 31-JUL-03:02 | 0.00 | 0.00 |
August | 0.994608E+11 | 199940.43 | 11-AUG-05:03 | 221.33 | 0.653856E+12 | 0.00 | 0.753316E+12 | 1.96 | 7.52 | 17-AUG-05:02 | 0.00 | 0.00 |
September | 0.824173E+11 | 191152.21 | 06-SEP-05:03 | 187.44 | 0.552638E+12 | 0.00 | 0.635055E+12 | 1.75 | 7.65 | 22-SEP-05:02 | 0.00 | 0.00 |
October | 0.611256E+11 | 188566.83 | 21-OCT-05:03 | 137.73 | 0.407682E+12 | 0.00 | 0.468807E+12 | 1.24 | 7.64 | 03-OCT-05:02 | 0.00 | 0.00 |
November | 0.227204E+11 | 163408.85 | 01-NOV-05:03 | 52.44 | 0.154068E+12 | 0.00 | 0.176789E+12 | 0.49 | 7.75 | 08-NOV-06:02 | 0.00 | 0.00 |
December | 0.152151E+11 | 148736.87 | 15-DEC-06:03 | 35.73 | 0.105069E+12 | 0.00 | 0.120284E+12 | 0.33 | 7.65 | 15-DEC-06:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.581946E+12 | 1318.37 | 0.388339E+13 | 0.446533E+13 | 1.01 | |||||||
Minimum of Months | 0.510635E+10 | 129036.22 | 12.42 | 0.358659E+11 | 0.00 | 0.409722E+11 | 0.12 | 7.34 | 0.00 | 0.00 | ||
Maximum of Months | 0.994608E+11 | 212983.03 | 221.33 | 0.653856E+12 | 0.00 | 0.753316E+12 | 1.96 | 7.75 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.655943E+11 | 744.00 | 49248.27 | 01-JAN-00:05 | 491372.23 | 04-JAN-23:15 | 23.05 | 19.50 | 13.91 |
February | 0.903216E+11 | 672.00 | 49248.27 | 01-FEB-00:10 | 587326.42 | 13-FEB-22:41 | 26.93 | 20.59 | 13.96 |
March | 0.115354E+12 | 744.00 | 49248.27 | 01-MAR-00:10 | 603532.56 | 20-MAR-21:10 | 31.45 | 22.26 | 13.97 |
April | 0.127175E+12 | 720.00 | 49248.27 | 01-APR-00:10 | 670930.68 | 28-APR-17:20 | 38.79 | 26.47 | 13.98 |
May | 0.131907E+12 | 744.00 | 49248.27 | 01-MAY-00:03 | 403034.90 | 01-MAY-00:03 | 32.52 | 28.56 | 13.98 |
June | 0.127652E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 379815.49 | 29-JUN-14:20 | 37.46 | 30.53 | 13.98 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 539194.56 | 21-JUL-16:10 | 42.10 | 32.16 | 13.98 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 688655.57 | 06-AUG-15:21 | 45.81 | 32.93 | 13.98 |
September | 0.127652E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 385300.75 | 01-SEP-00:03 | 31.87 | 27.89 | 13.98 |
October | 0.129572E+12 | 744.00 | 49248.27 | 01-OCT-00:10 | 372038.64 | 07-OCT-17:02 | 33.99 | 27.20 | 13.98 |
November | 0.119770E+12 | 720.00 | 49248.27 | 01-NOV-00:10 | 606169.29 | 12-NOV-05:21 | 32.76 | 23.43 | 13.98 |
December | 0.115413E+12 | 744.00 | 49248.27 | 01-DEC-00:10 | 654274.53 | 13-DEC-17:10 | 34.35 | 22.35 | 13.97 |
Annual Sum or Average | 0.141422E+13 | 8760.00 | 34.31 | 26.19 | 13.97 | ||||
Minimum of Months | 0.655943E+11 | 672.00 | 49248.27 | 372038.64 | 23.05 | 19.50 | 13.91 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 688655.57 | 45.81 | 32.93 | 13.98 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.610572E+10 | 204.36 | 22204.50 | 01-JAN-16:22 | 1262309.06 | 20-JAN-04:01 | 21.98 | 21.36 | 19.46 |
February | 0.829718E+10 | 272.75 | 22204.50 | 01-FEB-12:30 | 1078387.75 | 01-FEB-04:01 | 22.66 | 21.70 | 27.54 |
March | 0.110085E+11 | 329.22 | 22204.50 | 06-MAR-08:15 | 994609.54 | 29-MAR-10:40 | 22.57 | 21.54 | 30.29 |
April | 0.215604E+11 | 479.40 | 22204.50 | 01-APR-03:01 | 1024837.09 | 24-APR-11:00 | 23.51 | 21.90 | 43.73 |
May | 0.427023E+11 | 536.84 | 22204.50 | 01-MAY-01:11 | 1127666.35 | 26-MAY-15:20 | 26.97 | 24.92 | 39.41 |
June | 0.455731E+11 | 580.08 | 22204.50 | 01-JUN-03:01 | 1103080.14 | 08-JUN-05:03 | 27.00 | 24.85 | 44.27 |
July | 0.507479E+11 | 634.86 | 22204.50 | 01-JUL-00:42 | 1160222.19 | 31-JUL-12:40 | 27.89 | 25.75 | 44.42 |
August | 0.518960E+11 | 656.73 | 22204.50 | 01-AUG-00:32 | 1144316.70 | 07-AUG-14:40 | 27.37 | 25.15 | 48.12 |
September | 0.430817E+11 | 539.78 | 22204.50 | 01-SEP-00:03 | 1104315.35 | 05-SEP-08:20 | 27.43 | 25.33 | 39.59 |
October | 0.338356E+11 | 531.70 | 22204.50 | 02-OCT-09:20 | 1428204.07 | 01-OCT-07:42 | 25.62 | 23.77 | 42.19 |
November | 0.141024E+11 | 390.74 | 22204.50 | 01-NOV-01:32 | 1042486.41 | 29-NOV-16:20 | 23.24 | 21.96 | 37.16 |
December | 0.109153E+11 | 285.61 | 22204.50 | 08-DEC-11:00 | 1006242.45 | 12-DEC-14:40 | 22.44 | 21.57 | 26.55 |
Annual Sum or Average | 0.339826E+12 | 5442.07 | 24.90 | 23.33 | 36.92 | ||||
Minimum of Months | 0.610572E+10 | 204.36 | 22204.50 | 994609.54 | 21.98 | 21.36 | 19.46 | ||
Maximum of Months | 0.518960E+11 | 656.73 | 22204.50 | 1428204.07 | 27.89 | 25.75 | 48.12 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.157510E+10 | 19.73 | 22204.50 | 02-JAN-11:00 | 1036789.66 | 18-JAN-15:20 | 21.98 | 21.89 | 1.47 |
February | 0.225293E+10 | 28.20 | 22204.50 | 01-FEB-13:30 | 1021004.01 | 28-FEB-16:20 | 22.66 | 22.51 | 2.53 |
March | 0.400998E+10 | 50.18 | 22204.50 | 06-MAR-09:30 | 994609.54 | 29-MAR-10:40 | 22.57 | 22.34 | 3.70 |
April | 0.706444E+10 | 88.45 | 22204.50 | 01-APR-05:03 | 1024837.09 | 24-APR-11:00 | 23.51 | 23.10 | 6.75 |
May | 0.311507E+11 | 389.69 | 22204.50 | 01-MAY-03:02 | 1127666.35 | 26-MAY-15:20 | 26.97 | 25.29 | 26.92 |
June | 0.316365E+11 | 395.77 | 22204.50 | 01-JUN-03:02 | 1103080.14 | 08-JUN-05:03 | 27.00 | 25.25 | 28.11 |
July | 0.383876E+11 | 480.23 | 22204.50 | 01-JUL-03:13 | 1160222.19 | 31-JUL-12:40 | 27.89 | 25.89 | 31.29 |
August | 0.366909E+11 | 459.00 | 22204.50 | 01-AUG-03:02 | 1144316.70 | 07-AUG-14:40 | 27.37 | 25.40 | 31.33 |
September | 0.336647E+11 | 421.14 | 22204.50 | 01-SEP-03:20 | 1104315.35 | 05-SEP-08:20 | 27.43 | 25.58 | 29.18 |
October | 0.210969E+11 | 263.92 | 22204.50 | 02-OCT-09:40 | 1100674.87 | 06-OCT-14:00 | 25.62 | 24.46 | 18.49 |
November | 0.625064E+10 | 78.23 | 22204.50 | 01-NOV-04:21 | 1042486.41 | 29-NOV-16:20 | 23.24 | 22.87 | 6.11 |
December | 0.416601E+10 | 52.12 | 22204.50 | 09-DEC-11:00 | 1006242.45 | 12-DEC-14:40 | 22.44 | 22.20 | 3.98 |
Annual Sum or Average | 0.217946E+12 | 2726.67 | 24.90 | 23.91 | 15.91 | ||||
Minimum of Months | 0.157510E+10 | 19.73 | 22204.50 | 994609.54 | 21.98 | 21.89 | 1.47 | ||
Maximum of Months | 0.383876E+11 | 480.23 | 22204.50 | 1160222.19 | 27.89 | 25.89 | 31.33 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.150251E+11 | 0.00 | 181.68 | 336305.96 | 10-JAN-07:10 | 0.00 | 73.59 | 74.61 | 0.42 | 0.00 | 0.00 | 0.27 | 10-JAN-07:10 |
February | 0.986923E+10 | 0.00 | 100.48 | 451010.24 | 06-FEB-07:10 | 0.00 | 72.07 | 72.96 | 0.18 | 0.00 | 0.00 | 0.37 | 06-FEB-07:10 |
March | 0.849661E+10 | 0.00 | 85.78 | 493956.66 | 22-MAR-03:50 | 0.00 | 69.12 | 70.34 | 0.08 | 0.00 | 0.00 | 0.40 | 22-MAR-03:50 |
April | 0.132171E+10 | 0.00 | 8.58 | 291360.64 | 12-APR-03:50 | 0.00 | 70.11 | 70.23 | 0.01 | 0.00 | 0.00 | 0.24 | 12-APR-03:50 |
May | 0.146619E+10 | 0.00 | 1.93 | 214420.27 | 30-MAY-00:20 | 0.00 | 70.69 | 70.71 | 0.01 | 0.00 | 0.00 | 0.17 | 30-MAY-00:20 |
June | 0.574553E+09 | 0.00 | 0.76 | 213097.85 | 01-JUN-03:47 | 0.00 | 70.66 | 70.67 | 0.01 | 0.00 | 0.00 | 0.17 | 01-JUN-03:47 |
July | 0.151375E+10 | 0.00 | 1.99 | 213495.33 | 04-JUL-23:10 | 0.00 | 70.65 | 70.67 | 0.02 | 0.00 | 0.00 | 0.17 | 04-JUL-23:10 |
August | 0.109653E+10 | 0.00 | 1.44 | 212471.27 | 13-AUG-22:48 | 0.00 | 70.63 | 70.65 | 0.01 | 0.00 | 0.00 | 0.17 | 13-AUG-22:48 |
September | 0.151530E+10 | 0.00 | 1.99 | 214908.32 | 04-SEP-21:00 | 0.00 | 70.61 | 70.63 | 0.02 | 0.00 | 0.00 | 0.17 | 04-SEP-21:00 |
October | 0.183068E+10 | 0.00 | 11.37 | 309970.28 | 29-OCT-15:35 | 0.00 | 70.34 | 70.51 | 0.02 | 0.00 | 0.00 | 0.25 | 29-OCT-15:35 |
November | 0.236261E+10 | 0.00 | 40.69 | 336615.32 | 26-NOV-13:50 | 0.00 | 69.71 | 70.22 | 0.03 | 0.00 | 0.00 | 0.27 | 26-NOV-13:50 |
December | 0.124561E+11 | 0.00 | 137.61 | 627519.68 | 20-DEC-07:10 | 0.00 | 65.02 | 68.22 | 0.07 | 0.00 | 0.00 | 0.51 | 20-DEC-07:10 |
Annual Sum or Average | 0.575283E+11 | 574.28 | 70.25 | 70.86 | 0.07 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.574553E+09 | 0.00 | 0.76 | 212471.27 | 0.00 | 65.02 | 68.22 | 0.01 | 0.00 | 0.00 | 0.17 | ||
Maximum of Months | 0.150251E+11 | 0.00 | 181.68 | 627519.68 | 0.00 | 73.59 | 74.61 | 0.42 | 0.00 | 0.00 | 0.51 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 23.05 | 23.05 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 26.93 | 26.93 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 31.45 | 31.45 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 38.79 | 38.79 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 32.52 | 32.52 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 37.46 | 37.46 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 42.10 | 42.10 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 45.81 | 45.81 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 31.87 | 31.87 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 33.99 | 33.99 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 32.76 | 32.76 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 34.35 | 34.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 34.31 | 34.31 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 | 23.05 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.81 | 45.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.237464E+11 | 0.00 | 157.51 | 0.182977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136695.33 | 01-JAN-16:51 | 113361.09 | 16-JAN-13:32 | 0.00 | 0.00 | 0.00 |
February | 0.284239E+11 | 0.00 | 200.98 | 0.225019E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136648.76 | 20-FEB-14:00 | 114632.98 | 20-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.378867E+11 | 0.00 | 251.13 | 0.322297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158334.91 | 07-MAR-04:50 | 104921.98 | 06-MAR-01:08 | 0.00 | 0.00 | 0.00 |
April | 0.589657E+11 | 0.00 | 358.00 | 0.513496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166739.81 | 29-APR-03:01 | 109088.87 | 24-APR-02:32 | 0.00 | 0.00 | 0.00 |
May | 0.108467E+12 | 0.00 | 454.64 | 0.850011E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193008.48 | 21-MAY-22:41 | 116493.68 | 30-MAY-00:22 | 0.00 | 0.00 | 0.00 |
June | 0.112501E+12 | 0.00 | 443.00 | 0.855871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193213.74 | 18-JUN-22:11 | 108669.91 | 11-JUN-23:08 | 0.00 | 0.00 | 0.00 |
July | 0.122143E+12 | 0.00 | 444.74 | 0.879344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193199.14 | 02-JUL-18:20 | 114902.33 | 04-JUL-21:08 | 0.00 | 0.00 | 0.00 |
August | 0.132826E+12 | 0.00 | 484.34 | 0.978472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189351.47 | 06-AUG-14:41 | 113031.87 | 13-AUG-19:10 | 0.00 | 0.00 | 0.00 |
September | 0.114807E+12 | 0.00 | 457.35 | 0.853235E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 189087.91 | 17-SEP-13:51 | 118854.38 | 04-SEP-06:57 | 0.00 | 0.00 | 0.00 |
October | 0.996614E+11 | 0.00 | 435.06 | 0.779392E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188809.48 | 15-OCT-14:30 | 116629.62 | 29-OCT-15:38 | 0.00 | 0.00 | 0.00 |
November | 0.554520E+11 | 0.00 | 319.95 | 0.462871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 166268.86 | 11-NOV-16:30 | 110570.19 | 05-NOV-20:22 | 0.00 | 0.00 | 0.00 |
December | 0.363873E+11 | 0.00 | 219.10 | 0.299365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156004.18 | 16-DEC-04:53 | 113860.16 | 11-DEC-00:08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.931269E+12 | 4225.80 | 0.720235E+12 | ||||||||||||
Minimum of Months | 0.237464E+11 | 0.00 | 157.51 | 0.182977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 136648.76 | 104921.98 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.132826E+12 | 0.00 | 484.34 | 0.978472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 193213.74 | 118854.38 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.432714E+11 | 0.00 | 240.44 | 0.306641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 160797.83 | 19-JAN-06:01 | 135078.46 | 19-JAN-06:01 | 0.00 | 0.00 | 0.00 |
February | 0.611315E+11 | 0.00 | 299.84 | 0.422407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152265.92 | 28-FEB-06:01 | 137054.00 | 28-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 0.766018E+11 | 0.00 | 371.21 | 0.579895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 153440.04 | 27-MAR-05:03 | 140861.48 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.125320E+12 | 0.00 | 512.12 | 0.954148E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159762.45 | 01-APR-05:01 | 140696.70 | 24-APR-05:01 | 0.00 | 0.00 | 0.00 |
May | 0.164216E+12 | 0.00 | 504.99 | 0.119816E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 205165.68 | 23-MAY-03:01 | 147585.99 | 30-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.175905E+12 | 0.00 | 546.59 | 0.131756E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 169390.32 | 19-JUN-05:03 | 147360.49 | 26-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.191111E+12 | 0.00 | 588.58 | 0.140186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 183854.36 | 25-JUL-05:02 | 147942.03 | 10-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.207811E+12 | 0.00 | 625.27 | 0.154243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 192242.78 | 15-AUG-05:02 | 154107.52 | 15-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.167251E+12 | 0.00 | 491.85 | 0.112908E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224450.98 | 05-SEP-03:02 | 152144.68 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.151535E+12 | 0.00 | 510.61 | 0.112903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 178807.15 | 14-OCT-05:02 | 147557.05 | 10-OCT-05:03 | 0.00 | 0.00 | 0.00 |
November | 0.942755E+11 | 0.00 | 426.33 | 0.731326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 165459.01 | 01-NOV-05:01 | 142494.31 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 |
December | 0.695551E+11 | 0.00 | 316.88 | 0.517817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 173696.77 | 11-DEC-06:02 | 146508.51 | 11-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152799E+13 | 5434.72 | 0.112304E+13 | ||||||||||||
Minimum of Months | 0.432714E+11 | 0.00 | 240.44 | 0.306641E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 152265.92 | 135078.46 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.207811E+12 | 0.00 | 625.27 | 0.154243E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 224450.98 | 154107.52 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.350125E+12 | 0.00 | 229.37 | 0.240039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1256387.57 | 19-JAN-06:02 | 953965.63 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.491356E+12 | 0.00 | 279.71 | 0.325925E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1390707.20 | 03-FEB-06:02 | 1190589.25 | 28-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 0.589342E+12 | 0.00 | 331.09 | 0.420590E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1626805.92 | 07-MAR-06:01 | 1267221.61 | 30-MAR-05:01 | 0.00 | 0.00 | 0.00 |
April | 0.938170E+12 | 0.00 | 401.11 | 0.662627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1763661.10 | 29-APR-05:02 | 1318478.38 | 24-APR-05:02 | 0.00 | 0.00 | 0.00 |
May | 0.149428E+13 | 0.00 | 470.85 | 0.104160E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2530687.88 | 22-MAY-03:02 | 1423452.81 | 09-MAY-05:02 | 0.00 | 0.00 | 0.00 |
June | 0.151114E+13 | 0.00 | 472.15 | 0.106665E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1876726.25 | 24-JUN-05:02 | 1412282.84 | 24-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.157611E+13 | 0.00 | 477.23 | 0.105551E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2189361.96 | 31-JUL-03:01 | 1364611.97 | 05-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.163962E+13 | 0.00 | 486.49 | 0.110053E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2135296.62 | 26-AUG-05:02 | 1422613.51 | 11-AUG-05:02 | 0.00 | 0.00 | 0.00 |
September | 0.149624E+13 | 0.00 | 457.02 | 0.947253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2672417.15 | 05-SEP-03:02 | 1358683.03 | 06-SEP-05:02 | 0.00 | 0.00 | 0.00 |
October | 0.126766E+13 | 0.00 | 444.58 | 0.883827E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2105685.69 | 21-OCT-05:02 | 1363266.24 | 14-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.731981E+12 | 0.00 | 381.18 | 0.540042E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1760411.15 | 01-NOV-05:02 | 1289058.46 | 03-NOV-05:01 | 0.00 | 0.00 | 0.00 |
December | 0.513040E+12 | 0.00 | 267.64 | 0.351059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1628569.47 | 15-DEC-06:01 | 1267960.21 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125991E+14 | 4698.42 | 0.863565E+13 | ||||||||||||
Minimum of Months | 0.350125E+12 | 0.00 | 229.37 | 0.240039E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1256387.57 | 953965.63 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.163962E+13 | 0.00 | 486.49 | 0.110053E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2672417.15 | 1423452.81 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.344691E+11 | 0.00 | 214.38 | 0.227643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139659.87 | 19-JAN-15:00 | 88400.02 | 19-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 0.494645E+11 | 0.00 | 270.55 | 0.322581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138148.34 | 03-FEB-06:02 | 95997.19 | 27-FEB-06:02 | 0.00 | 0.00 | 0.00 |
March | 0.611557E+11 | 0.00 | 321.48 | 0.431338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 151616.91 | 27-MAR-05:03 | 120788.39 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.992689E+11 | 0.00 | 396.60 | 0.710720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170746.67 | 29-APR-05:01 | 129018.03 | 29-APR-05:01 | 0.00 | 0.00 | 0.00 |
May | 0.163205E+12 | 0.00 | 475.71 | 0.116851E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 267307.50 | 22-MAY-03:02 | 150882.47 | 08-MAY-03:02 | 0.00 | 0.00 | 0.00 |
June | 0.167468E+12 | 0.00 | 476.94 | 0.121730E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 188648.89 | 23-JUN-05:02 | 143153.62 | 23-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.174327E+12 | 0.00 | 486.83 | 0.119971E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 230712.90 | 31-JUL-03:01 | 151485.77 | 20-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.178999E+12 | 0.00 | 491.74 | 0.123334E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 226220.70 | 23-AUG-03:02 | 150307.50 | 23-AUG-03:02 | 0.00 | 0.00 | 0.00 |
September | 0.159714E+12 | 0.00 | 458.09 | 0.103147E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 295297.30 | 05-SEP-03:02 | 143522.33 | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 |
October | 0.134274E+12 | 0.00 | 439.70 | 0.951711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 214539.42 | 21-OCT-05:02 | 143060.51 | 06-OCT-03:02 | 0.00 | 0.00 | 0.00 |
November | 0.726729E+11 | 0.00 | 373.58 | 0.533764E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 172102.87 | 01-NOV-05:01 | 129729.62 | 02-NOV-05:01 | 0.00 | 0.00 | 0.00 |
December | 0.503574E+11 | 0.00 | 261.09 | 0.340240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170642.76 | 16-DEC-06:01 | 123447.92 | 16-DEC-06:01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.134538E+13 | 4666.69 | 0.936832E+12 | ||||||||||||
Minimum of Months | 0.344691E+11 | 0.00 | 214.38 | 0.227643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 138148.34 | 88400.02 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.178999E+12 | 0.00 | 491.74 | 0.123334E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 295297.30 | 151485.77 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.317721E+12 | 0.827699E+11 | 741.26 | 0.315945E+12 | 0.177637E+10 | 0.00 | 1.00 | 03-JAN-04:03 | 0.01 | 22-JAN-00:11 | 433346.41 | 21-JAN-23:40 | 432260.41 | 03-JAN-04:03 | 9732.39 | 03-JAN-04:12 | 92119.77 | 21-JAN-23:40 | 0.00 |
February | 0.500304E+12 | 0.127271E+12 | 671.17 | 0.496868E+12 | 0.343588E+10 | 0.00 | 1.00 | 07-FEB-05:05 | 0.05 | 14-FEB-00:02 | 443852.81 | 13-FEB-22:40 | 443852.81 | 13-FEB-22:40 | 26357.68 | 12-FEB-24:00 | 92299.95 | 13-FEB-22:40 | 0.00 |
March | 0.788383E+12 | 0.203322E+12 | 743.91 | 0.785082E+12 | 0.330102E+10 | 0.00 | 1.00 | 11-MAR-05:02 | 0.03 | 11-MAR-05:17 | 431733.39 | 20-MAR-21:07 | 431733.39 | 20-MAR-21:07 | 9308.04 | 30-MAR-18:50 | 105750.30 | 26-MAR-14:00 | 0.00 |
April | 0.993649E+12 | 0.277932E+12 | 720.00 | 0.989090E+12 | 0.455922E+10 | 0.00 | 1.00 | 14-APR-13:30 | 0.89 | 10-APR-06:20 | 401643.02 | 28-APR-17:40 | 386692.35 | 18-APR-16:50 | 16151.78 | 28-APR-17:50 | 143834.38 | 28-APR-15:00 | 0.00 |
May | 0.331396E+12 | 0.110651E+12 | 744.00 | 0.320737E+12 | 0.106587E+11 | 0.00 | 0.39 | 01-MAY-15:30 | 0.33 | 13-MAY-06:10 | 134361.51 | 01-MAY-16:00 | 132637.55 | 01-MAY-00:10 | 12184.21 | 23-MAY-16:00 | 50854.23 | 01-MAY-15:10 | 0.00 |
June | 0.549214E+12 | 0.184114E+12 | 720.00 | 0.537418E+12 | 0.117959E+11 | 0.00 | 0.62 | 28-JUN-14:10 | 0.54 | 01-JUN-05:10 | 223170.06 | 29-JUN-15:00 | 211113.72 | 14-JUN-14:00 | 15018.51 | 29-JUN-15:00 | 87586.63 | 14-JUN-14:00 | 0.00 |
July | 0.804352E+12 | 0.270208E+12 | 744.00 | 0.791573E+12 | 0.127788E+11 | 0.00 | 0.86 | 21-JUL-16:00 | 0.75 | 01-JUL-00:05 | 310799.32 | 12-JUL-12:30 | 300042.87 | 21-JUL-16:00 | 14086.41 | 12-JUL-12:40 | 126666.71 | 21-JUL-16:00 | 0.00 |
August | 0.103708E+13 | 0.341026E+12 | 744.00 | 0.102571E+13 | 0.113685E+11 | 0.00 | 1.00 | 01-AUG-08:30 | 0.94 | 16-AUG-23:00 | 404516.43 | 07-AUG-14:00 | 392492.93 | 06-AUG-15:42 | 17021.39 | 07-AUG-14:00 | 151171.06 | 30-AUG-16:00 | 0.00 |
September | 0.324823E+12 | 0.106214E+12 | 720.00 | 0.313215E+12 | 0.116081E+11 | 0.00 | 0.39 | 01-SEP-12:10 | 0.33 | 22-SEP-06:10 | 137785.14 | 01-SEP-00:10 | 136083.72 | 01-SEP-00:10 | 11822.99 | 05-SEP-13:00 | 55939.39 | 09-SEP-17:00 | 0.00 |
October | 0.566468E+12 | 0.174287E+12 | 744.00 | 0.557443E+12 | 0.902446E+10 | 0.00 | 0.62 | 06-OCT-11:20 | 0.52 | 17-OCT-06:50 | 224055.24 | 24-OCT-14:20 | 212232.13 | 05-OCT-15:00 | 14012.61 | 24-OCT-20:00 | 86129.96 | 05-OCT-15:00 | 0.00 |
November | 0.769756E+12 | 0.204772E+12 | 719.81 | 0.765562E+12 | 0.419310E+10 | 0.00 | 1.00 | 12-NOV-05:04 | 0.04 | 23-NOV-07:26 | 436929.25 | 26-NOV-05:34 | 430353.01 | 12-NOV-05:27 | 27834.41 | 26-NOV-06:00 | 108077.63 | 02-NOV-13:00 | 0.00 |
December | 0.102752E+13 | 0.256282E+12 | 744.00 | 0.102485E+13 | 0.266627E+10 | 0.00 | 1.00 | 10-DEC-14:36 | 0.63 | 19-DEC-04:42 | 433700.18 | 18-DEC-06:10 | 433700.18 | 18-DEC-06:10 | 9826.39 | 12-DEC-15:00 | 135237.99 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.801066E+13 | 0.233885E+13 | 8756.16 | 0.792349E+13 | 0.871663E+11 | ||||||||||||||
Minimum of Months | 0.317721E+12 | 0.827699E+11 | 671.17 | 0.313215E+12 | 0.177637E+10 | 0.00 | 0.39 | 0.01 | 134361.51 | 132637.55 | 9308.04 | 50854.23 | 0.00 | ||||||
Maximum of Months | 0.103708E+13 | 0.341026E+12 | 744.00 | 0.102571E+13 | 0.127788E+11 | 0.00 | 1.00 | 0.94 | 443852.81 | 443852.81 | 27834.41 | 151171.06 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.506779E+10 | 0.129185E+10 | 744.00 | 0.506765E+10 | 145537.35 | 0.00 | 0.31 | 01-JAN-16:51 | 0.19 | 05-JAN-08:00 | 2333.97 | 01-JAN-17:30 | 2333.97 | 01-JAN-17:30 | 2.91 | 03-JAN-08:55 | 724.96 | 02-JAN-17:00 | 0.00 |
February | 0.916635E+10 | 0.228649E+10 | 672.00 | 0.916625E+10 | 101551.47 | 0.00 | 0.55 | 26-FEB-17:43 | 0.41 | 05-FEB-08:20 | 4346.52 | 26-FEB-17:47 | 4346.52 | 26-FEB-17:47 | 4.97 | 04-FEB-22:00 | 1330.58 | 02-FEB-13:00 | 0.00 |
March | 0.151005E+11 | 0.381039E+10 | 744.00 | 0.151005E+11 | 0.00 | 0.00 | 0.75 | 30-MAR-13:00 | 0.61 | 11-MAR-18:17 | 5947.70 | 13-MAR-18:00 | 5947.70 | 13-MAR-18:00 | 0.00 | 01-MAR-00:10 | 2024.38 | 26-MAR-14:00 | 0.00 |
April | 0.194094E+11 | 0.536870E+10 | 720.00 | 0.194094E+11 | 0.00 | 0.00 | 1.00 | 28-APR-15:10 | 0.83 | 11-APR-07:00 | 8049.79 | 16-APR-18:10 | 8049.79 | 16-APR-18:10 | 0.00 | 01-APR-00:10 | 2946.04 | 28-APR-15:00 | 0.00 |
May | 0.559171E+10 | 0.188226E+10 | 744.00 | 0.559171E+10 | 0.00 | 0.00 | 0.33 | 29-MAY-17:55 | 0.25 | 20-MAY-17:20 | 2396.89 | 01-MAY-00:10 | 2396.89 | 01-MAY-00:10 | 0.00 | 01-MAY-00:03 | 901.87 | 28-MAY-16:00 | 0.00 |
June | 0.101056E+11 | 0.339851E+10 | 720.00 | 0.101056E+11 | 0.00 | 0.00 | 0.57 | 11-JUN-18:02 | 0.47 | 01-JUN-06:00 | 4203.52 | 11-JUN-18:15 | 4203.52 | 11-JUN-18:15 | 0.00 | 01-JUN-00:10 | 1633.46 | 14-JUN-14:00 | 0.00 |
July | 0.152798E+11 | 0.514233E+10 | 744.00 | 0.152798E+11 | 0.00 | 0.00 | 0.81 | 21-JUL-16:00 | 0.69 | 11-JUL-20:10 | 5931.40 | 16-JUL-18:45 | 5931.40 | 16-JUL-18:45 | 0.00 | 01-JUL-00:05 | 2452.19 | 21-JUL-16:00 | 0.00 |
August | 0.201639E+11 | 0.667248E+10 | 744.00 | 0.201639E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-14:50 | 0.88 | 16-AUG-21:10 | 7804.21 | 06-AUG-18:10 | 7804.21 | 06-AUG-18:10 | 0.00 | 01-AUG-00:05 | 3104.81 | 30-AUG-16:00 | 0.00 |
September | 0.542425E+10 | 0.179036E+10 | 720.00 | 0.542425E+10 | 0.00 | 0.00 | 0.34 | 03-SEP-17:55 | 0.25 | 07-SEP-21:12 | 2450.12 | 03-SEP-17:55 | 2450.12 | 03-SEP-17:55 | 0.00 | 01-SEP-00:03 | 952.90 | 09-SEP-17:53 | 0.00 |
October | 0.104641E+11 | 0.320245E+10 | 744.00 | 0.104641E+11 | 0.00 | 0.00 | 0.56 | 05-OCT-17:00 | 0.44 | 28-OCT-07:00 | 4265.37 | 09-OCT-17:15 | 4265.37 | 09-OCT-17:15 | 0.00 | 01-OCT-00:10 | 1612.17 | 05-OCT-15:00 | 0.00 |
November | 0.147453E+11 | 0.385534E+10 | 720.00 | 0.147453E+11 | 0.00 | 0.00 | 0.77 | 06-NOV-17:00 | 0.64 | 16-NOV-08:00 | 6121.19 | 12-NOV-16:53 | 6121.19 | 12-NOV-16:53 | 0.00 | 01-NOV-00:10 | 2044.24 | 02-NOV-13:00 | 0.00 |
December | 0.199990E+11 | 0.487887E+10 | 744.00 | 0.199990E+11 | 0.00 | 0.00 | 0.97 | 15-DEC-17:00 | 0.81 | 21-DEC-08:00 | 7935.39 | 25-DEC-17:03 | 7935.39 | 25-DEC-17:03 | 0.00 | 01-DEC-00:10 | 2683.41 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.150518E+12 | 0.435800E+11 | 8760.00 | 0.150517E+12 | 247088.82 | ||||||||||||||
Minimum of Months | 0.506779E+10 | 0.129185E+10 | 672.00 | 0.506765E+10 | 0.00 | 0.00 | 0.31 | 0.19 | 2333.97 | 2333.97 | 0.00 | 724.96 | 0.00 | ||||||
Maximum of Months | 0.201639E+11 | 0.667248E+10 | 744.00 | 0.201639E+11 | 145537.35 | 0.00 | 1.00 | 0.88 | 8049.79 | 8049.79 | 4.97 | 3104.81 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.388867E+11 | 0.101158E+11 | 744.00 | 0.388853E+11 | 1397216.82 | 0.00 | 0.30 | 19-JAN-17:00 | 0.14 | 22-JAN-08:65 | 21245.80 | 31-JAN-17:50 | 21245.80 | 31-JAN-17:50 | 27.21 | 03-JAN-08:55 | 6683.57 | 02-JAN-17:00 | 0.00 |
February | 0.795545E+11 | 0.200711E+11 | 672.00 | 0.795535E+11 | 1001779.18 | 0.00 | 0.53 | 27-FEB-17:30 | 0.31 | 05-FEB-08:50 | 39424.53 | 27-FEB-17:40 | 39424.53 | 27-FEB-17:40 | 43.26 | 04-FEB-22:00 | 12225.13 | 02-FEB-13:10 | 0.00 |
March | 0.137298E+12 | 0.349057E+11 | 744.00 | 0.137298E+12 | 0.00 | 0.00 | 0.75 | 30-MAR-13:00 | 0.54 | 12-MAR-07:25 | 56293.01 | 06-MAR-17:50 | 56293.01 | 06-MAR-17:50 | 0.00 | 01-MAR-00:10 | 19069.14 | 30-MAR-13:00 | 0.00 |
April | 0.183120E+12 | 0.507598E+11 | 720.00 | 0.183120E+12 | 0.00 | 0.00 | 1.00 | 28-APR-15:00 | 0.80 | 11-APR-07:00 | 75316.06 | 16-APR-18:16 | 75316.06 | 16-APR-18:16 | 0.00 | 01-APR-00:10 | 28079.28 | 28-APR-15:00 | 0.00 |
May | 0.512592E+11 | 0.173181E+11 | 744.00 | 0.512592E+11 | 0.00 | 0.00 | 0.32 | 29-MAY-17:55 | 0.23 | 20-MAY-17:20 | 21881.12 | 29-MAY-18:16 | 21881.12 | 29-MAY-18:16 | 0.00 | 01-MAY-00:03 | 8458.77 | 18-MAY-16:00 | 0.00 |
June | 0.954613E+11 | 0.321330E+11 | 720.00 | 0.954613E+11 | 0.00 | 0.00 | 0.57 | 11-JUN-18:02 | 0.46 | 07-JUN-06:50 | 39463.81 | 11-JUN-18:15 | 39463.81 | 11-JUN-18:15 | 0.00 | 01-JUN-00:10 | 15548.98 | 14-JUN-14:00 | 0.00 |
July | 0.145427E+12 | 0.489452E+11 | 744.00 | 0.145427E+12 | 0.00 | 0.00 | 0.81 | 21-JUL-16:00 | 0.68 | 11-JUL-21:12 | 55982.44 | 07-JUL-16:00 | 55982.44 | 07-JUL-16:00 | 0.00 | 01-JUL-00:05 | 23387.93 | 21-JUL-16:00 | 0.00 |
August | 0.192206E+12 | 0.635876E+11 | 744.00 | 0.192206E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-14:20 | 0.86 | 16-AUG-21:12 | 74022.91 | 30-AUG-18:50 | 74022.91 | 30-AUG-18:50 | 0.00 | 01-AUG-00:05 | 29523.54 | 30-AUG-16:00 | 0.00 |
September | 0.487227E+11 | 0.161687E+11 | 720.00 | 0.487227E+11 | 0.00 | 0.00 | 0.34 | 03-SEP-17:42 | 0.22 | 27-SEP-21:20 | 22900.14 | 03-SEP-17:55 | 22900.14 | 03-SEP-17:55 | 0.00 | 01-SEP-00:03 | 8672.25 | 09-SEP-17:53 | 0.00 |
October | 0.967883E+11 | 0.297658E+11 | 744.00 | 0.967883E+11 | 0.00 | 0.00 | 0.56 | 05-OCT-17:00 | 0.40 | 28-OCT-07:30 | 39681.98 | 09-OCT-17:35 | 39681.98 | 09-OCT-17:35 | 0.00 | 01-OCT-00:10 | 15300.45 | 05-OCT-15:00 | 0.00 |
November | 0.134450E+12 | 0.354103E+11 | 720.00 | 0.134450E+12 | 0.00 | 0.00 | 0.76 | 06-NOV-17:00 | 0.59 | 16-NOV-08:00 | 57436.39 | 06-NOV-17:00 | 57436.39 | 06-NOV-17:00 | 0.00 | 01-NOV-00:10 | 19417.33 | 02-NOV-13:00 | 0.00 |
December | 0.182532E+12 | 0.448752E+11 | 744.00 | 0.182532E+12 | 0.00 | 0.00 | 0.97 | 15-DEC-17:00 | 0.75 | 31-DEC-03:50 | 74128.58 | 15-DEC-17:00 | 74128.58 | 15-DEC-17:00 | 0.00 | 01-DEC-00:10 | 25482.01 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.138571E+13 | 0.404056E+12 | 8760.00 | 0.138570E+13 | 2398996.00 | ||||||||||||||
Minimum of Months | 0.388867E+11 | 0.101158E+11 | 672.00 | 0.388853E+11 | 0.00 | 0.00 | 0.30 | 0.14 | 21245.80 | 21245.80 | 0.00 | 6683.57 | 0.00 | ||||||
Maximum of Months | 0.192206E+12 | 0.635876E+11 | 744.00 | 0.192206E+12 | 1397216.82 | 0.00 | 1.00 | 0.86 | 75316.06 | 75316.06 | 43.26 | 29523.54 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.291948E+10 | 0.783413E+09 | 709.07 | 0.291935E+10 | 132084.66 | 0.00 | 0.30 | 19-JAN-17:00 | 0.00 | 04-JAN-05:45 | 2184.25 | 31-JAN-17:40 | 2184.25 | 31-JAN-17:40 | 2.72 | 03-JAN-11:00 | 669.81 | 02-JAN-17:00 | 0.00 |
February | 0.724074E+10 | 0.185477E+10 | 672.00 | 0.724064E+10 | 102398.56 | 0.00 | 0.53 | 27-FEB-17:30 | 0.12 | 05-FEB-08:50 | 3990.79 | 27-FEB-17:40 | 3990.79 | 27-FEB-17:40 | 3.61 | 04-FEB-22:00 | 1236.79 | 02-FEB-14:00 | 0.00 |
March | 0.132314E+11 | 0.339805E+10 | 744.00 | 0.132314E+11 | 0.00 | 0.00 | 0.74 | 30-MAR-13:00 | 0.41 | 12-MAR-07:50 | 5691.16 | 06-MAR-17:50 | 5691.16 | 06-MAR-17:50 | 0.00 | 01-MAR-00:10 | 1926.25 | 30-MAR-13:00 | 0.00 |
April | 0.181717E+11 | 0.506499E+10 | 720.00 | 0.181717E+11 | 0.00 | 0.00 | 1.00 | 28-APR-15:10 | 0.75 | 02-APR-07:20 | 7656.62 | 16-APR-18:20 | 7656.62 | 16-APR-18:20 | 0.00 | 01-APR-00:10 | 2848.53 | 28-APR-15:00 | 0.00 |
May | 0.522510E+10 | 0.176949E+10 | 744.00 | 0.522510E+10 | 0.00 | 0.00 | 0.35 | 29-MAY-17:55 | 0.22 | 20-MAY-17:20 | 2440.61 | 29-MAY-18:00 | 2440.61 | 29-MAY-18:00 | 0.00 | 01-MAY-00:03 | 920.58 | 28-MAY-16:02 | 0.00 |
June | 0.967238E+10 | 0.326225E+10 | 720.00 | 0.967238E+10 | 0.00 | 0.00 | 0.59 | 11-JUN-18:02 | 0.44 | 07-JUN-07:00 | 4167.60 | 11-JUN-18:26 | 4167.60 | 11-JUN-18:26 | 0.00 | 01-JUN-00:10 | 1595.76 | 14-JUN-14:00 | 0.00 |
July | 0.146723E+11 | 0.494919E+10 | 744.00 | 0.146723E+11 | 0.00 | 0.00 | 0.81 | 21-JUL-16:00 | 0.67 | 11-JUL-21:12 | 5749.81 | 16-JUL-18:53 | 5749.81 | 16-JUL-18:53 | 0.00 | 01-JUL-00:05 | 2382.11 | 21-JUL-16:00 | 0.00 |
August | 0.193134E+11 | 0.640763E+10 | 744.00 | 0.193134E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-14:30 | 0.85 | 16-AUG-21:12 | 7493.51 | 06-AUG-17:35 | 7493.51 | 06-AUG-17:35 | 0.00 | 01-AUG-00:05 | 2994.55 | 30-AUG-16:00 | 0.00 |
September | 0.494269E+10 | 0.164532E+10 | 720.00 | 0.494269E+10 | 0.00 | 0.00 | 0.36 | 10-SEP-17:35 | 0.21 | 07-SEP-21:12 | 2510.89 | 03-SEP-17:45 | 2510.89 | 03-SEP-17:45 | 0.00 | 01-SEP-00:03 | 953.02 | 10-SEP-15:50 | 0.00 |
October | 0.960714E+10 | 0.297304E+10 | 744.00 | 0.960714E+10 | 0.00 | 0.00 | 0.58 | 08-OCT-16:51 | 0.34 | 29-OCT-07:30 | 4182.34 | 08-OCT-17:35 | 4182.34 | 08-OCT-17:35 | 0.00 | 01-OCT-00:10 | 1562.90 | 05-OCT-15:00 | 0.00 |
November | 0.129735E+11 | 0.345060E+10 | 720.00 | 0.129735E+11 | 0.00 | 0.00 | 0.76 | 06-NOV-17:00 | 0.52 | 26-NOV-08:70 | 5798.81 | 06-NOV-17:00 | 5798.81 | 06-NOV-17:00 | 0.00 | 01-NOV-00:10 | 1968.35 | 02-NOV-13:00 | 0.00 |
December | 0.175284E+11 | 0.435757E+10 | 744.00 | 0.175284E+11 | 0.00 | 0.00 | 0.97 | 15-DEC-17:00 | 0.63 | 31-DEC-06:50 | 7468.31 | 15-DEC-17:00 | 7468.31 | 15-DEC-17:00 | 0.00 | 01-DEC-00:10 | 2566.64 | 13-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.135498E+12 | 0.399163E+11 | 8725.07 | 0.135498E+12 | 234483.22 | ||||||||||||||
Minimum of Months | 0.291948E+10 | 0.783413E+09 | 672.00 | 0.291935E+10 | 0.00 | 0.00 | 0.30 | 0.00 | 2184.25 | 2184.25 | 0.00 | 669.81 | 0.00 | ||||||
Maximum of Months | 0.193134E+11 | 0.640763E+10 | 744.00 | 0.193134E+11 | 132084.66 | 0.00 | 1.00 | 0.85 | 7656.62 | 7656.62 | 3.61 | 2994.55 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.08 | 0.00 | 83.08 | 42.81 | 375.75 | 0.00 | 0.00 | 744.00 |
February | 98.01 | 0.00 | 98.01 | 61.55 | 317.56 | 0.00 | 0.00 | 672.00 |
March | 113.70 | 0.00 | 113.70 | 95.30 | 268.03 | 0.00 | 0.00 | 744.00 |
April | 134.19 | 0.54 | 133.64 | 162.71 | 157.92 | 0.00 | 0.00 | 720.00 |
May | 151.98 | 5.53 | 146.44 | 284.75 | 41.65 | 0.00 | 0.00 | 744.00 |
June | 172.82 | 11.93 | 160.89 | 333.51 | 33.60 | 0.00 | 0.00 | 720.00 |
July | 167.72 | 6.37 | 161.36 | 326.89 | 21.19 | 0.00 | 0.00 | 744.00 |
August | 150.21 | 1.17 | 149.04 | 300.67 | 30.84 | 0.00 | 0.00 | 744.00 |
September | 129.76 | 0.01 | 129.75 | 239.75 | 50.39 | 0.00 | 0.00 | 720.00 |
October | 112.76 | 0.00 | 112.76 | 189.78 | 97.96 | 0.00 | 0.00 | 744.00 |
November | 85.60 | 0.00 | 85.60 | 75.51 | 238.58 | 0.00 | 0.00 | 720.00 |
December | 77.23 | 0.00 | 77.23 | 48.00 | 329.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.21 | 2.14 | 121.08 | 180.83 | 162.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 77.23 | 0.00 | 77.23 | 42.81 | 21.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.82 | 11.93 | 161.36 | 333.51 | 375.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.08 | 0.00 | 83.08 | 42.81 | 375.75 | 0.00 | 0.00 | 744.00 |
February | 98.01 | 0.00 | 98.01 | 61.54 | 317.55 | 0.00 | 0.00 | 672.00 |
March | 113.70 | 0.00 | 113.70 | 95.30 | 268.02 | 0.00 | 0.00 | 744.00 |
April | 134.19 | 0.54 | 133.64 | 162.70 | 157.92 | 0.00 | 0.00 | 720.00 |
May | 151.97 | 5.53 | 146.44 | 284.75 | 41.65 | 0.00 | 0.00 | 744.00 |
June | 172.82 | 11.93 | 160.89 | 333.50 | 33.60 | 0.00 | 0.00 | 720.00 |
July | 167.72 | 6.37 | 161.35 | 326.89 | 21.19 | 0.00 | 0.00 | 744.00 |
August | 150.21 | 1.17 | 149.04 | 300.66 | 30.84 | 0.00 | 0.00 | 744.00 |
September | 129.76 | 0.01 | 129.75 | 239.74 | 50.39 | 0.00 | 0.00 | 720.00 |
October | 112.76 | 0.00 | 112.76 | 189.77 | 97.96 | 0.00 | 0.00 | 744.00 |
November | 85.60 | 0.00 | 85.60 | 75.51 | 238.58 | 0.00 | 0.00 | 720.00 |
December | 77.23 | 0.00 | 77.23 | 48.00 | 329.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.21 | 2.14 | 121.07 | 180.82 | 162.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 77.23 | 0.00 | 77.23 | 42.81 | 21.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.82 | 11.93 | 161.35 | 333.50 | 375.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.08 | 0.00 | 83.08 | 42.81 | 375.75 | 0.00 | 0.00 | 744.00 |
February | 98.01 | 0.00 | 98.01 | 61.54 | 317.55 | 0.00 | 0.00 | 672.00 |
March | 113.70 | 0.00 | 113.70 | 95.30 | 268.02 | 0.00 | 0.00 | 744.00 |
April | 134.19 | 0.54 | 133.64 | 162.71 | 157.92 | 0.00 | 0.00 | 720.00 |
May | 151.97 | 5.53 | 146.44 | 284.75 | 41.65 | 0.00 | 0.00 | 744.00 |
June | 172.82 | 11.93 | 160.89 | 333.50 | 33.60 | 0.00 | 0.00 | 720.00 |
July | 167.72 | 6.37 | 161.36 | 326.89 | 21.19 | 0.00 | 0.00 | 744.00 |
August | 150.21 | 1.17 | 149.04 | 300.66 | 30.84 | 0.00 | 0.00 | 744.00 |
September | 129.76 | 0.01 | 129.75 | 239.75 | 50.39 | 0.00 | 0.00 | 720.00 |
October | 112.76 | 0.00 | 112.76 | 189.77 | 97.96 | 0.00 | 0.00 | 744.00 |
November | 85.60 | 0.00 | 85.60 | 75.51 | 238.58 | 0.00 | 0.00 | 720.00 |
December | 77.23 | 0.00 | 77.23 | 48.00 | 329.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.21 | 2.14 | 121.07 | 180.82 | 162.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 77.23 | 0.00 | 77.23 | 42.81 | 21.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.82 | 11.93 | 161.36 | 333.50 | 375.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.08 | 0.00 | 83.08 | 42.81 | 375.75 | 0.00 | 0.00 | 744.00 |
February | 98.01 | 0.00 | 98.01 | 61.54 | 317.55 | 0.00 | 0.00 | 672.00 |
March | 113.70 | 0.00 | 113.70 | 95.30 | 268.02 | 0.00 | 0.00 | 744.00 |
April | 134.19 | 0.54 | 133.64 | 162.70 | 157.92 | 0.00 | 0.00 | 720.00 |
May | 151.97 | 5.53 | 146.44 | 284.75 | 41.65 | 0.00 | 0.00 | 744.00 |
June | 172.82 | 11.93 | 160.89 | 333.50 | 33.60 | 0.00 | 0.00 | 720.00 |
July | 167.72 | 6.37 | 161.35 | 326.89 | 21.19 | 0.00 | 0.00 | 744.00 |
August | 150.21 | 1.17 | 149.04 | 300.66 | 30.84 | 0.00 | 0.00 | 744.00 |
September | 129.76 | 0.01 | 129.75 | 239.74 | 50.39 | 0.00 | 0.00 | 720.00 |
October | 112.76 | 0.00 | 112.76 | 189.77 | 97.96 | 0.00 | 0.00 | 744.00 |
November | 85.60 | 0.00 | 85.60 | 75.51 | 238.58 | 0.00 | 0.00 | 720.00 |
December | 77.23 | 0.00 | 77.23 | 48.00 | 329.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.21 | 2.14 | 121.07 | 180.82 | 162.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 77.23 | 0.00 | 77.23 | 42.81 | 21.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.82 | 11.93 | 161.35 | 333.50 | 375.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 83.07 | 0.00 | 83.07 | 42.81 | 375.73 | 0.00 | 0.00 | 744.00 |
February | 98.01 | 0.00 | 98.01 | 61.54 | 317.54 | 0.00 | 0.00 | 672.00 |
March | 113.70 | 0.00 | 113.70 | 95.29 | 268.01 | 0.00 | 0.00 | 744.00 |
April | 134.18 | 0.54 | 133.64 | 162.70 | 157.92 | 0.00 | 0.00 | 720.00 |
May | 151.97 | 5.53 | 146.43 | 284.74 | 41.65 | 0.00 | 0.00 | 744.00 |
June | 172.81 | 11.93 | 160.88 | 333.49 | 33.60 | 0.00 | 0.00 | 720.00 |
July | 167.71 | 6.37 | 161.35 | 326.88 | 21.19 | 0.00 | 0.00 | 744.00 |
August | 150.20 | 1.17 | 149.03 | 300.65 | 30.84 | 0.00 | 0.00 | 744.00 |
September | 129.75 | 0.01 | 129.74 | 239.74 | 50.39 | 0.00 | 0.00 | 720.00 |
October | 112.75 | 0.00 | 112.75 | 189.77 | 97.96 | 0.00 | 0.00 | 744.00 |
November | 85.60 | 0.00 | 85.60 | 75.50 | 238.57 | 0.00 | 0.00 | 720.00 |
December | 77.23 | 0.00 | 77.23 | 48.00 | 329.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 123.21 | 2.14 | 121.07 | 180.82 | 162.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 77.23 | 0.00 | 77.23 | 42.81 | 21.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 172.81 | 11.93 | 161.35 | 333.49 | 375.73 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 237.57 | 120.97 | 116.60 | 240.53 | 367.24 | 0.00 | 0.00 | 744.00 |
February | 264.53 | 127.70 | 136.83 | 287.65 | 307.10 | 0.00 | 0.00 | 672.00 |
March | 311.21 | 150.10 | 161.11 | 385.86 | 258.61 | 0.00 | 0.00 | 744.00 |
April | 341.51 | 154.46 | 187.05 | 491.43 | 151.26 | 0.00 | 0.00 | 720.00 |
May | 351.98 | 152.62 | 199.36 | 626.95 | 41.88 | 0.00 | 0.00 | 744.00 |
June | 356.96 | 141.55 | 215.41 | 657.43 | 29.90 | 0.00 | 0.00 | 720.00 |
July | 344.17 | 125.94 | 218.23 | 640.22 | 14.96 | 0.00 | 0.00 | 744.00 |
August | 317.15 | 109.04 | 208.11 | 590.16 | 22.72 | 0.00 | 0.00 | 744.00 |
September | 280.95 | 96.60 | 184.35 | 492.61 | 48.64 | 0.00 | 0.00 | 720.00 |
October | 277.62 | 117.16 | 160.47 | 457.13 | 93.90 | 0.00 | 0.00 | 744.00 |
November | 245.78 | 125.38 | 120.40 | 305.33 | 226.96 | 0.00 | 0.00 | 720.00 |
December | 193.52 | 87.65 | 105.86 | 203.37 | 315.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 293.68 | 125.71 | 167.97 | 449.12 | 155.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 193.52 | 87.65 | 105.86 | 203.37 | 14.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 356.96 | 154.46 | 218.23 | 657.43 | 367.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 237.57 | 120.97 | 116.60 | 240.53 | 367.24 | 0.00 | 0.00 | 744.00 |
February | 264.53 | 127.70 | 136.83 | 287.65 | 307.10 | 0.00 | 0.00 | 672.00 |
March | 311.21 | 150.10 | 161.11 | 385.86 | 258.61 | 0.00 | 0.00 | 744.00 |
April | 341.51 | 154.46 | 187.05 | 491.43 | 151.26 | 0.00 | 0.00 | 720.00 |
May | 351.98 | 152.62 | 199.36 | 626.95 | 41.88 | 0.00 | 0.00 | 744.00 |
June | 356.96 | 141.55 | 215.41 | 657.43 | 29.90 | 0.00 | 0.00 | 720.00 |
July | 344.17 | 125.94 | 218.23 | 640.22 | 14.96 | 0.00 | 0.00 | 744.00 |
August | 317.15 | 109.04 | 208.11 | 590.16 | 22.72 | 0.00 | 0.00 | 744.00 |
September | 280.95 | 96.60 | 184.35 | 492.61 | 48.64 | 0.00 | 0.00 | 720.00 |
October | 277.62 | 117.16 | 160.47 | 457.13 | 93.90 | 0.00 | 0.00 | 744.00 |
November | 245.78 | 125.38 | 120.40 | 305.33 | 226.96 | 0.00 | 0.00 | 720.00 |
December | 193.52 | 87.65 | 105.86 | 203.37 | 315.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 293.68 | 125.71 | 167.97 | 449.12 | 155.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 193.52 | 87.65 | 105.86 | 203.37 | 14.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 356.96 | 154.46 | 218.23 | 657.43 | 367.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 237.56 | 120.96 | 116.60 | 240.53 | 367.24 | 0.00 | 0.00 | 744.00 |
February | 264.53 | 127.70 | 136.83 | 287.64 | 307.10 | 0.00 | 0.00 | 672.00 |
March | 311.21 | 150.10 | 161.11 | 385.85 | 258.61 | 0.00 | 0.00 | 744.00 |
April | 341.50 | 154.46 | 187.04 | 491.42 | 151.26 | 0.00 | 0.00 | 720.00 |
May | 351.98 | 152.62 | 199.36 | 626.94 | 41.88 | 0.00 | 0.00 | 744.00 |
June | 356.96 | 141.55 | 215.40 | 657.42 | 29.90 | 0.00 | 0.00 | 720.00 |
July | 344.16 | 125.94 | 218.22 | 640.20 | 14.96 | 0.00 | 0.00 | 744.00 |
August | 317.14 | 109.04 | 208.11 | 590.15 | 22.72 | 0.00 | 0.00 | 744.00 |
September | 280.94 | 96.59 | 184.35 | 492.60 | 48.64 | 0.00 | 0.00 | 720.00 |
October | 277.62 | 117.15 | 160.46 | 457.13 | 93.90 | 0.00 | 0.00 | 744.00 |
November | 245.78 | 125.38 | 120.40 | 305.32 | 226.95 | 0.00 | 0.00 | 720.00 |
December | 193.51 | 87.65 | 105.86 | 203.37 | 315.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 293.67 | 125.71 | 167.97 | 449.11 | 155.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 193.51 | 87.65 | 105.86 | 203.37 | 14.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 356.96 | 154.46 | 218.22 | 657.42 | 367.24 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.34 | 342.61 | 137.74 | 643.13 | 326.01 | 0.00 | 0.00 | 744.00 |
February | 435.55 | 281.94 | 153.62 | 574.55 | 282.46 | 0.00 | 0.00 | 672.00 |
March | 277.96 | 125.40 | 152.56 | 341.35 | 252.97 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 48.20 | 157.79 | 259.54 | 156.22 | 0.00 | 0.00 | 720.00 |
May | 157.40 | 6.63 | 150.77 | 290.22 | 42.28 | 0.00 | 0.00 | 744.00 |
June | 155.52 | 1.42 | 154.10 | 310.10 | 34.14 | 0.00 | 0.00 | 720.00 |
July | 162.79 | 2.95 | 159.84 | 320.10 | 20.37 | 0.00 | 0.00 | 744.00 |
August | 191.50 | 22.93 | 168.57 | 355.84 | 31.67 | 0.00 | 0.00 | 744.00 |
September | 229.79 | 60.52 | 169.27 | 389.47 | 52.04 | 0.00 | 0.00 | 720.00 |
October | 356.57 | 185.72 | 170.85 | 581.90 | 99.47 | 0.00 | 0.00 | 744.00 |
November | 453.91 | 312.55 | 141.35 | 658.87 | 217.68 | 0.00 | 0.00 | 720.00 |
December | 469.37 | 337.12 | 132.25 | 661.90 | 292.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 297.33 | 143.28 | 154.05 | 448.37 | 149.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 155.52 | 1.42 | 132.25 | 259.54 | 20.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 480.34 | 342.61 | 170.85 | 661.90 | 326.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.34 | 342.61 | 137.74 | 643.12 | 326.01 | 0.00 | 0.00 | 744.00 |
February | 435.55 | 281.94 | 153.61 | 574.55 | 282.46 | 0.00 | 0.00 | 672.00 |
March | 277.96 | 125.40 | 152.56 | 341.35 | 252.97 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 48.20 | 157.79 | 259.53 | 156.22 | 0.00 | 0.00 | 720.00 |
May | 157.40 | 6.63 | 150.77 | 290.22 | 42.28 | 0.00 | 0.00 | 744.00 |
June | 155.52 | 1.42 | 154.10 | 310.10 | 34.14 | 0.00 | 0.00 | 720.00 |
July | 162.79 | 2.95 | 159.84 | 320.10 | 20.37 | 0.00 | 0.00 | 744.00 |
August | 191.50 | 22.93 | 168.57 | 355.84 | 31.67 | 0.00 | 0.00 | 744.00 |
September | 229.78 | 60.52 | 169.27 | 389.47 | 52.04 | 0.00 | 0.00 | 720.00 |
October | 356.57 | 185.72 | 170.85 | 581.90 | 99.47 | 0.00 | 0.00 | 744.00 |
November | 453.91 | 312.55 | 141.35 | 658.87 | 217.68 | 0.00 | 0.00 | 720.00 |
December | 469.36 | 337.11 | 132.25 | 661.89 | 292.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 297.33 | 143.28 | 154.04 | 448.37 | 149.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 155.52 | 1.42 | 132.25 | 259.53 | 20.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 480.34 | 342.61 | 170.85 | 661.89 | 326.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.34 | 342.61 | 137.74 | 643.13 | 326.01 | 0.00 | 0.00 | 744.00 |
February | 435.55 | 281.94 | 153.62 | 574.55 | 282.46 | 0.00 | 0.00 | 672.00 |
March | 277.96 | 125.40 | 152.56 | 341.35 | 252.97 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 48.20 | 157.79 | 259.54 | 156.22 | 0.00 | 0.00 | 720.00 |
May | 157.40 | 6.63 | 150.77 | 290.22 | 42.28 | 0.00 | 0.00 | 744.00 |
June | 155.52 | 1.42 | 154.10 | 310.10 | 34.14 | 0.00 | 0.00 | 720.00 |
July | 162.79 | 2.95 | 159.84 | 320.10 | 20.37 | 0.00 | 0.00 | 744.00 |
August | 191.50 | 22.93 | 168.57 | 355.84 | 31.67 | 0.00 | 0.00 | 744.00 |
September | 229.79 | 60.52 | 169.27 | 389.47 | 52.04 | 0.00 | 0.00 | 720.00 |
October | 356.57 | 185.72 | 170.85 | 581.90 | 99.47 | 0.00 | 0.00 | 744.00 |
November | 453.91 | 312.55 | 141.35 | 658.87 | 217.68 | 0.00 | 0.00 | 720.00 |
December | 469.37 | 337.12 | 132.25 | 661.90 | 292.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 297.33 | 143.28 | 154.05 | 448.37 | 149.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 155.52 | 1.42 | 132.25 | 259.54 | 20.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 480.34 | 342.61 | 170.85 | 661.90 | 326.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.34 | 342.61 | 137.74 | 643.12 | 326.01 | 0.00 | 0.00 | 744.00 |
February | 435.55 | 281.94 | 153.61 | 574.55 | 282.46 | 0.00 | 0.00 | 672.00 |
March | 277.96 | 125.40 | 152.56 | 341.35 | 252.97 | 0.00 | 0.00 | 744.00 |
April | 205.99 | 48.20 | 157.79 | 259.53 | 156.22 | 0.00 | 0.00 | 720.00 |
May | 157.40 | 6.63 | 150.77 | 290.22 | 42.28 | 0.00 | 0.00 | 744.00 |
June | 155.52 | 1.42 | 154.10 | 310.10 | 34.14 | 0.00 | 0.00 | 720.00 |
July | 162.79 | 2.95 | 159.84 | 320.10 | 20.37 | 0.00 | 0.00 | 744.00 |
August | 191.50 | 22.93 | 168.57 | 355.84 | 31.67 | 0.00 | 0.00 | 744.00 |
September | 229.78 | 60.52 | 169.27 | 389.47 | 52.04 | 0.00 | 0.00 | 720.00 |
October | 356.57 | 185.72 | 170.85 | 581.90 | 99.47 | 0.00 | 0.00 | 744.00 |
November | 453.91 | 312.55 | 141.35 | 658.87 | 217.68 | 0.00 | 0.00 | 720.00 |
December | 469.36 | 337.11 | 132.25 | 661.89 | 292.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 297.33 | 143.28 | 154.04 | 448.37 | 149.93 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 155.52 | 1.42 | 132.25 | 259.53 | 20.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 480.34 | 342.61 | 170.85 | 661.89 | 326.01 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 480.32 | 342.59 | 137.73 | 643.10 | 326.00 | 0.00 | 0.00 | 744.00 |
February | 435.54 | 281.93 | 153.61 | 574.53 | 282.45 | 0.00 | 0.00 | 672.00 |
March | 277.95 | 125.39 | 152.56 | 341.34 | 252.96 | 0.00 | 0.00 | 744.00 |
April | 205.98 | 48.20 | 157.79 | 259.52 | 156.22 | 0.00 | 0.00 | 720.00 |
May | 157.39 | 6.63 | 150.77 | 290.21 | 42.27 | 0.00 | 0.00 | 744.00 |
June | 155.51 | 1.42 | 154.09 | 310.09 | 34.14 | 0.00 | 0.00 | 720.00 |
July | 162.79 | 2.95 | 159.83 | 320.09 | 20.37 | 0.00 | 0.00 | 744.00 |
August | 191.49 | 22.93 | 168.56 | 355.83 | 31.67 | 0.00 | 0.00 | 744.00 |
September | 229.78 | 60.51 | 169.26 | 389.45 | 52.04 | 0.00 | 0.00 | 720.00 |
October | 356.55 | 185.71 | 170.84 | 581.88 | 99.47 | 0.00 | 0.00 | 744.00 |
November | 453.89 | 312.54 | 141.35 | 658.84 | 217.67 | 0.00 | 0.00 | 720.00 |
December | 469.35 | 337.10 | 132.25 | 661.87 | 292.12 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 297.32 | 143.28 | 154.04 | 448.35 | 149.92 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 155.51 | 1.42 | 132.25 | 259.52 | 20.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 480.32 | 342.59 | 170.84 | 661.87 | 326.00 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.69 | 136.64 | 116.05 | 278.27 | 413.90 | 0.00 | 0.00 | 744.00 |
February | 286.10 | 144.80 | 141.30 | 326.56 | 366.88 | 0.00 | 0.00 | 672.00 |
March | 282.00 | 124.84 | 157.16 | 337.42 | 325.87 | 0.00 | 0.00 | 744.00 |
April | 350.25 | 161.13 | 189.12 | 491.90 | 208.83 | 0.00 | 0.00 | 720.00 |
May | 291.25 | 94.87 | 196.38 | 519.83 | 60.30 | 0.00 | 0.00 | 744.00 |
June | 323.55 | 113.44 | 210.10 | 586.33 | 54.14 | 0.00 | 0.00 | 720.00 |
July | 295.34 | 81.92 | 213.42 | 530.71 | 39.99 | 0.00 | 0.00 | 744.00 |
August | 298.63 | 91.42 | 207.22 | 534.60 | 57.94 | 0.00 | 0.00 | 744.00 |
September | 275.00 | 94.34 | 180.66 | 476.13 | 69.08 | 0.00 | 0.00 | 720.00 |
October | 281.54 | 121.65 | 159.89 | 458.55 | 129.43 | 0.00 | 0.00 | 744.00 |
November | 241.30 | 121.26 | 120.04 | 303.87 | 293.30 | 0.00 | 0.00 | 720.00 |
December | 232.11 | 123.43 | 108.68 | 260.98 | 396.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 283.98 | 117.20 | 166.79 | 425.81 | 200.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 232.11 | 81.92 | 108.68 | 260.98 | 39.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 350.25 | 161.13 | 213.42 | 586.33 | 413.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.69 | 136.64 | 116.05 | 278.27 | 413.90 | 0.00 | 0.00 | 744.00 |
February | 286.10 | 144.80 | 141.30 | 326.56 | 366.88 | 0.00 | 0.00 | 672.00 |
March | 282.00 | 124.84 | 157.16 | 337.42 | 325.87 | 0.00 | 0.00 | 744.00 |
April | 350.25 | 161.13 | 189.12 | 491.90 | 208.83 | 0.00 | 0.00 | 720.00 |
May | 291.25 | 94.87 | 196.38 | 519.83 | 60.30 | 0.00 | 0.00 | 744.00 |
June | 323.55 | 113.44 | 210.10 | 586.33 | 54.14 | 0.00 | 0.00 | 720.00 |
July | 295.34 | 81.92 | 213.42 | 530.71 | 39.99 | 0.00 | 0.00 | 744.00 |
August | 298.63 | 91.42 | 207.22 | 534.60 | 57.94 | 0.00 | 0.00 | 744.00 |
September | 275.00 | 94.34 | 180.66 | 476.13 | 69.08 | 0.00 | 0.00 | 720.00 |
October | 281.54 | 121.65 | 159.89 | 458.55 | 129.43 | 0.00 | 0.00 | 744.00 |
November | 241.30 | 121.26 | 120.04 | 303.87 | 293.30 | 0.00 | 0.00 | 720.00 |
December | 232.11 | 123.43 | 108.68 | 260.98 | 396.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 283.98 | 117.20 | 166.79 | 425.81 | 200.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 232.11 | 81.92 | 108.68 | 260.98 | 39.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 350.25 | 161.13 | 213.42 | 586.33 | 413.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 252.68 | 136.63 | 116.05 | 278.27 | 413.89 | 0.00 | 0.00 | 744.00 |
February | 286.09 | 144.80 | 141.29 | 326.55 | 366.87 | 0.00 | 0.00 | 672.00 |
March | 281.99 | 124.84 | 157.16 | 337.41 | 325.87 | 0.00 | 0.00 | 744.00 |
April | 350.25 | 161.13 | 189.12 | 491.89 | 208.82 | 0.00 | 0.00 | 720.00 |
May | 291.25 | 94.87 | 196.38 | 519.82 | 60.30 | 0.00 | 0.00 | 744.00 |
June | 323.54 | 113.44 | 210.10 | 586.32 | 54.14 | 0.00 | 0.00 | 720.00 |
July | 295.33 | 81.91 | 213.42 | 530.70 | 39.99 | 0.00 | 0.00 | 744.00 |
August | 298.63 | 91.41 | 207.21 | 534.59 | 57.94 | 0.00 | 0.00 | 744.00 |
September | 275.00 | 94.34 | 180.65 | 476.12 | 69.08 | 0.00 | 0.00 | 720.00 |
October | 281.53 | 121.65 | 159.88 | 458.54 | 129.43 | 0.00 | 0.00 | 744.00 |
November | 241.30 | 121.26 | 120.03 | 303.87 | 293.29 | 0.00 | 0.00 | 720.00 |
December | 232.11 | 123.43 | 108.68 | 260.97 | 396.76 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 283.98 | 117.20 | 166.78 | 425.80 | 200.50 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 232.11 | 81.91 | 108.68 | 260.97 | 39.99 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 350.25 | 161.13 | 213.42 | 586.32 | 413.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.39 | 0.00 | 415.39 | 250.30 | 1689.02 | 0.00 | 0.00 | 744.00 |
February | 490.06 | 0.00 | 490.06 | 346.42 | 1410.83 | 0.00 | 0.00 | 672.00 |
March | 568.52 | 0.00 | 568.52 | 514.89 | 1205.12 | 0.00 | 0.00 | 744.00 |
April | 670.94 | 2.72 | 668.22 | 839.61 | 737.06 | 0.00 | 0.00 | 720.00 |
May | 759.88 | 27.67 | 732.21 | 1435.28 | 199.05 | 0.00 | 0.00 | 744.00 |
June | 864.10 | 59.65 | 804.45 | 1679.80 | 171.18 | 0.00 | 0.00 | 720.00 |
July | 838.62 | 31.83 | 806.79 | 1645.31 | 113.19 | 0.00 | 0.00 | 744.00 |
August | 751.06 | 5.86 | 745.20 | 1521.40 | 159.66 | 0.00 | 0.00 | 744.00 |
September | 648.79 | 0.05 | 648.74 | 1213.79 | 227.94 | 0.00 | 0.00 | 720.00 |
October | 563.78 | 0.00 | 563.78 | 972.21 | 448.27 | 0.00 | 0.00 | 744.00 |
November | 428.00 | 0.00 | 428.00 | 415.31 | 1053.77 | 0.00 | 0.00 | 720.00 |
December | 386.16 | 0.00 | 386.16 | 281.00 | 1434.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 616.06 | 10.68 | 605.38 | 929.83 | 734.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 386.16 | 0.00 | 386.16 | 250.30 | 113.19 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 864.10 | 59.65 | 806.79 | 1679.80 | 1689.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 712.69 | 362.90 | 349.79 | 744.36 | 1015.16 | 0.00 | 0.00 | 744.00 |
February | 793.59 | 383.11 | 410.48 | 883.51 | 850.15 | 0.00 | 0.00 | 672.00 |
March | 933.63 | 450.30 | 483.33 | 1163.78 | 734.00 | 0.00 | 0.00 | 744.00 |
April | 1024.51 | 463.38 | 561.13 | 1462.41 | 464.98 | 0.00 | 0.00 | 720.00 |
May | 1055.94 | 457.86 | 598.07 | 1867.48 | 130.02 | 0.00 | 0.00 | 744.00 |
June | 1070.88 | 424.66 | 646.22 | 1956.01 | 110.40 | 0.00 | 0.00 | 720.00 |
July | 1032.49 | 377.82 | 654.67 | 1893.73 | 70.89 | 0.00 | 0.00 | 744.00 |
August | 951.44 | 327.11 | 624.32 | 1746.71 | 101.13 | 0.00 | 0.00 | 744.00 |
September | 842.83 | 289.78 | 553.04 | 1473.87 | 140.96 | 0.00 | 0.00 | 720.00 |
October | 832.85 | 351.46 | 481.39 | 1367.86 | 277.70 | 0.00 | 0.00 | 744.00 |
November | 737.34 | 376.13 | 361.21 | 930.78 | 634.83 | 0.00 | 0.00 | 720.00 |
December | 580.54 | 262.96 | 317.58 | 631.88 | 874.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 881.02 | 377.12 | 503.91 | 1346.08 | 448.38 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 580.54 | 262.96 | 317.58 | 631.88 | 70.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1070.88 | 463.38 | 654.67 | 1956.01 | 1015.16 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2401.76 | 1713.08 | 688.69 | 3185.20 | 1605.85 | 0.00 | 0.00 | 744.00 |
February | 2177.81 | 1409.72 | 768.09 | 2855.64 | 1375.64 | 0.00 | 0.00 | 672.00 |
March | 1389.83 | 627.00 | 762.83 | 1707.74 | 1211.35 | 0.00 | 0.00 | 744.00 |
April | 1029.98 | 241.00 | 788.98 | 1307.51 | 762.69 | 0.00 | 0.00 | 720.00 |
May | 787.01 | 33.15 | 753.86 | 1460.42 | 206.71 | 0.00 | 0.00 | 744.00 |
June | 777.59 | 7.10 | 770.49 | 1561.50 | 176.65 | 0.00 | 0.00 | 720.00 |
July | 813.97 | 14.77 | 799.21 | 1610.64 | 111.45 | 0.00 | 0.00 | 744.00 |
August | 957.50 | 114.64 | 842.86 | 1789.00 | 171.54 | 0.00 | 0.00 | 744.00 |
September | 1148.95 | 302.58 | 846.36 | 1946.93 | 250.89 | 0.00 | 0.00 | 720.00 |
October | 1782.88 | 928.64 | 854.25 | 2893.54 | 495.75 | 0.00 | 0.00 | 744.00 |
November | 2269.58 | 1562.80 | 706.78 | 3275.92 | 1062.99 | 0.00 | 0.00 | 720.00 |
December | 2346.88 | 1685.62 | 661.26 | 3292.85 | 1415.18 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1486.68 | 716.44 | 770.24 | 2237.90 | 733.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 777.59 | 7.10 | 661.26 | 1307.51 | 111.45 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2401.76 | 1713.08 | 854.25 | 3292.85 | 1605.85 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 758.05 | 409.91 | 348.15 | 867.72 | 1103.74 | 0.00 | 0.00 | 744.00 |
February | 858.28 | 434.39 | 423.89 | 1026.19 | 938.64 | 0.00 | 0.00 | 672.00 |
March | 845.98 | 374.51 | 471.47 | 1064.32 | 811.83 | 0.00 | 0.00 | 744.00 |
April | 1050.75 | 483.39 | 567.35 | 1527.15 | 528.95 | 0.00 | 0.00 | 720.00 |
May | 873.75 | 284.61 | 589.14 | 1579.57 | 157.30 | 0.00 | 0.00 | 744.00 |
June | 970.63 | 340.33 | 630.30 | 1788.72 | 140.61 | 0.00 | 0.00 | 720.00 |
July | 886.01 | 245.75 | 640.26 | 1639.07 | 94.82 | 0.00 | 0.00 | 744.00 |
August | 895.89 | 274.24 | 621.65 | 1657.57 | 132.69 | 0.00 | 0.00 | 744.00 |
September | 824.99 | 283.03 | 541.96 | 1449.57 | 170.40 | 0.00 | 0.00 | 720.00 |
October | 844.60 | 364.95 | 479.65 | 1410.61 | 326.43 | 0.00 | 0.00 | 744.00 |
November | 723.89 | 363.79 | 360.11 | 967.55 | 715.57 | 0.00 | 0.00 | 720.00 |
December | 696.34 | 370.30 | 326.04 | 842.22 | 952.01 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 851.94 | 351.59 | 500.35 | 1319.50 | 503.81 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 696.34 | 245.75 | 326.04 | 842.22 | 94.82 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1050.75 | 483.39 | 640.26 | 1788.72 | 1103.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.39 | 0.00 | 415.39 | 276.40 | 1548.18 | 0.00 | 0.00 | 744.00 |
February | 490.06 | 0.00 | 490.06 | 367.12 | 1291.94 | 0.00 | 0.00 | 672.00 |
March | 568.52 | 0.00 | 568.52 | 529.92 | 1127.05 | 0.00 | 0.00 | 744.00 |
April | 670.94 | 2.72 | 668.22 | 837.95 | 711.56 | 0.00 | 0.00 | 720.00 |
May | 759.88 | 27.67 | 732.21 | 1413.31 | 207.37 | 0.00 | 0.00 | 744.00 |
June | 864.10 | 59.65 | 804.45 | 1652.83 | 181.35 | 0.00 | 0.00 | 720.00 |
July | 838.62 | 31.83 | 806.79 | 1615.40 | 122.86 | 0.00 | 0.00 | 744.00 |
August | 751.06 | 5.86 | 745.20 | 1497.50 | 167.88 | 0.00 | 0.00 | 744.00 |
September | 648.79 | 0.05 | 648.74 | 1192.72 | 232.19 | 0.00 | 0.00 | 720.00 |
October | 563.78 | 0.00 | 563.78 | 963.32 | 433.66 | 0.00 | 0.00 | 744.00 |
November | 428.00 | 0.00 | 428.00 | 434.76 | 970.79 | 0.00 | 0.00 | 720.00 |
December | 386.16 | 0.00 | 386.16 | 301.94 | 1317.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 616.06 | 10.68 | 605.38 | 927.01 | 689.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 386.16 | 0.00 | 386.16 | 276.40 | 122.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 864.10 | 59.65 | 806.79 | 1652.83 | 1548.18 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 712.69 | 362.90 | 349.79 | 769.43 | 945.64 | 0.00 | 0.00 | 744.00 |
February | 793.59 | 383.11 | 410.48 | 902.89 | 793.13 | 0.00 | 0.00 | 672.00 |
March | 933.63 | 450.30 | 483.33 | 1170.71 | 700.83 | 0.00 | 0.00 | 744.00 |
April | 1024.51 | 463.38 | 561.13 | 1456.48 | 457.24 | 0.00 | 0.00 | 720.00 |
May | 1055.94 | 457.86 | 598.07 | 1848.91 | 136.84 | 0.00 | 0.00 | 744.00 |
June | 1070.88 | 424.66 | 646.22 | 1935.54 | 118.67 | 0.00 | 0.00 | 720.00 |
July | 1032.49 | 377.82 | 654.67 | 1871.37 | 77.77 | 0.00 | 0.00 | 744.00 |
August | 951.44 | 327.11 | 624.32 | 1727.76 | 107.99 | 0.00 | 0.00 | 744.00 |
September | 842.83 | 289.78 | 553.04 | 1456.45 | 146.89 | 0.00 | 0.00 | 720.00 |
October | 832.85 | 351.46 | 481.39 | 1357.57 | 273.84 | 0.00 | 0.00 | 744.00 |
November | 737.34 | 376.13 | 361.21 | 943.10 | 600.19 | 0.00 | 0.00 | 720.00 |
December | 580.54 | 262.96 | 317.58 | 647.67 | 820.58 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 881.02 | 377.12 | 503.91 | 1343.08 | 429.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 580.54 | 262.96 | 317.58 | 647.67 | 77.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1070.88 | 463.38 | 654.67 | 1935.54 | 945.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2401.76 | 1713.08 | 688.69 | 3216.72 | 1495.64 | 0.00 | 0.00 | 744.00 |
February | 2177.81 | 1409.72 | 768.09 | 2883.77 | 1280.62 | 0.00 | 0.00 | 672.00 |
March | 1389.83 | 627.00 | 762.83 | 1719.66 | 1142.56 | 0.00 | 0.00 | 744.00 |
April | 1029.98 | 241.00 | 788.98 | 1306.66 | 738.79 | 0.00 | 0.00 | 720.00 |
May | 787.01 | 33.15 | 753.86 | 1441.13 | 214.42 | 0.00 | 0.00 | 744.00 |
June | 777.59 | 7.10 | 770.49 | 1538.32 | 186.95 | 0.00 | 0.00 | 720.00 |
July | 813.97 | 14.77 | 799.21 | 1583.28 | 120.32 | 0.00 | 0.00 | 744.00 |
August | 957.50 | 114.64 | 842.86 | 1767.23 | 179.41 | 0.00 | 0.00 | 744.00 |
September | 1148.95 | 302.58 | 846.36 | 1928.38 | 255.02 | 0.00 | 0.00 | 720.00 |
October | 1782.88 | 928.64 | 854.25 | 2882.89 | 483.75 | 0.00 | 0.00 | 744.00 |
November | 2269.58 | 1562.80 | 706.78 | 3291.08 | 1004.16 | 0.00 | 0.00 | 720.00 |
December | 2346.88 | 1685.62 | 661.26 | 3316.63 | 1321.54 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1486.68 | 716.44 | 770.24 | 2236.80 | 698.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 777.59 | 7.10 | 661.26 | 1306.66 | 120.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2401.76 | 1713.08 | 854.25 | 3316.63 | 1495.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 758.05 | 409.91 | 348.15 | 879.56 | 1034.06 | 0.00 | 0.00 | 744.00 |
February | 858.28 | 434.39 | 423.89 | 1035.86 | 878.44 | 0.00 | 0.00 | 672.00 |
March | 845.98 | 374.51 | 471.47 | 1069.28 | 771.01 | 0.00 | 0.00 | 744.00 |
April | 1050.75 | 483.39 | 567.35 | 1524.02 | 513.07 | 0.00 | 0.00 | 720.00 |
May | 873.75 | 284.61 | 589.14 | 1568.82 | 159.38 | 0.00 | 0.00 | 744.00 |
June | 970.63 | 340.33 | 630.30 | 1774.78 | 144.13 | 0.00 | 0.00 | 720.00 |
July | 886.01 | 245.75 | 640.26 | 1624.06 | 97.75 | 0.00 | 0.00 | 744.00 |
August | 895.89 | 274.24 | 621.65 | 1645.07 | 135.40 | 0.00 | 0.00 | 744.00 |
September | 824.99 | 283.03 | 541.96 | 1440.15 | 170.86 | 0.00 | 0.00 | 720.00 |
October | 844.60 | 364.95 | 479.65 | 1405.70 | 317.19 | 0.00 | 0.00 | 744.00 |
November | 723.89 | 363.79 | 360.11 | 975.98 | 673.35 | 0.00 | 0.00 | 720.00 |
December | 696.34 | 370.30 | 326.04 | 851.69 | 892.97 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 851.94 | 351.59 | 500.35 | 1317.32 | 480.22 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 696.34 | 245.75 | 326.04 | 851.69 | 97.75 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1050.75 | 483.39 | 640.26 | 1774.78 | 1034.06 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222519E+09 | 0.00 | 0.222519E+09 | 0.114666E+09 | 0.100640E+10 |
February | 0.237113E+09 | 0.00 | 0.237113E+09 | 0.148891E+09 | 0.768230E+09 |
March | 0.304544E+09 | 0.00 | 0.304544E+09 | 0.255246E+09 | 0.717879E+09 |
April | 0.347816E+09 | 1409276.45 | 0.346407E+09 | 0.421736E+09 | 0.409339E+09 |
May | 0.407054E+09 | 14823637.99 | 0.392230E+09 | 0.762679E+09 | 0.111554E+09 |
June | 0.447949E+09 | 30923982.93 | 0.417025E+09 | 0.864449E+09 | 87096916.33 |
July | 0.449229E+09 | 17050376.57 | 0.432179E+09 | 0.875549E+09 | 56759905.13 |
August | 0.402329E+09 | 3140660.89 | 0.399188E+09 | 0.805304E+09 | 82612354.21 |
September | 0.336331E+09 | 25177.04 | 0.336305E+09 | 0.621425E+09 | 0.130605E+09 |
October | 0.302008E+09 | 0.00 | 0.302008E+09 | 0.508296E+09 | 0.262377E+09 |
November | 0.221876E+09 | 0.00 | 0.221876E+09 | 0.195718E+09 | 0.618394E+09 |
December | 0.206856E+09 | 0.00 | 0.206856E+09 | 0.128562E+09 | 0.881708E+09 |
Annual Sum or Average | 0.388562E+10 | 67373111.88 | 0.381825E+10 | 0.570252E+10 | 0.513295E+10 |
Minimum of Months | 0.206856E+09 | 0.00 | 0.206856E+09 | 0.114666E+09 | 56759905.13 |
Maximum of Months | 0.449229E+09 | 30923982.93 | 0.432179E+09 | 0.875549E+09 | 0.100640E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222516E+09 | 0.00 | 0.222516E+09 | 0.114664E+09 | 0.100640E+10 |
February | 0.237110E+09 | 0.00 | 0.237110E+09 | 0.148889E+09 | 0.768228E+09 |
March | 0.304540E+09 | 0.00 | 0.304540E+09 | 0.255242E+09 | 0.717877E+09 |
April | 0.347812E+09 | 1409245.47 | 0.346403E+09 | 0.421731E+09 | 0.409337E+09 |
May | 0.407048E+09 | 14823312.11 | 0.392225E+09 | 0.762672E+09 | 0.111552E+09 |
June | 0.447943E+09 | 30923303.10 | 0.417020E+09 | 0.864441E+09 | 87095554.86 |
July | 0.449223E+09 | 17050001.74 | 0.432173E+09 | 0.875541E+09 | 56758686.41 |
August | 0.402323E+09 | 3140591.85 | 0.399183E+09 | 0.805296E+09 | 82611042.77 |
September | 0.336326E+09 | 25176.49 | 0.336301E+09 | 0.621419E+09 | 0.130603E+09 |
October | 0.302004E+09 | 0.00 | 0.302004E+09 | 0.508291E+09 | 0.262376E+09 |
November | 0.221873E+09 | 0.00 | 0.221873E+09 | 0.195716E+09 | 0.618392E+09 |
December | 0.206854E+09 | 0.00 | 0.206854E+09 | 0.128561E+09 | 0.881706E+09 |
Annual Sum or Average | 0.388557E+10 | 67371630.76 | 0.381820E+10 | 0.570246E+10 | 0.513293E+10 |
Minimum of Months | 0.206854E+09 | 0.00 | 0.206854E+09 | 0.114664E+09 | 56758686.41 |
Maximum of Months | 0.449223E+09 | 30923303.10 | 0.432173E+09 | 0.875541E+09 | 0.100640E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222517E+09 | 0.00 | 0.222517E+09 | 0.114664E+09 | 0.100640E+10 |
February | 0.237111E+09 | 0.00 | 0.237111E+09 | 0.148889E+09 | 0.768229E+09 |
March | 0.304541E+09 | 0.00 | 0.304541E+09 | 0.255244E+09 | 0.717878E+09 |
April | 0.347813E+09 | 1409255.80 | 0.346404E+09 | 0.421733E+09 | 0.409338E+09 |
May | 0.407050E+09 | 14823420.74 | 0.392226E+09 | 0.762674E+09 | 0.111553E+09 |
June | 0.447945E+09 | 30923529.71 | 0.417021E+09 | 0.864444E+09 | 87096008.68 |
July | 0.449225E+09 | 17050126.69 | 0.432175E+09 | 0.875544E+09 | 56759092.65 |
August | 0.402325E+09 | 3140614.86 | 0.399185E+09 | 0.805299E+09 | 82611479.92 |
September | 0.336327E+09 | 25176.68 | 0.336302E+09 | 0.621421E+09 | 0.130604E+09 |
October | 0.302005E+09 | 0.00 | 0.302005E+09 | 0.508293E+09 | 0.262376E+09 |
November | 0.221874E+09 | 0.00 | 0.221874E+09 | 0.195716E+09 | 0.618392E+09 |
December | 0.206855E+09 | 0.00 | 0.206855E+09 | 0.128561E+09 | 0.881707E+09 |
Annual Sum or Average | 0.388559E+10 | 67372124.47 | 0.381822E+10 | 0.570248E+10 | 0.513294E+10 |
Minimum of Months | 0.206855E+09 | 0.00 | 0.206855E+09 | 0.114664E+09 | 56759092.65 |
Maximum of Months | 0.449225E+09 | 30923529.71 | 0.432175E+09 | 0.875544E+09 | 0.100640E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222516E+09 | 0.00 | 0.222516E+09 | 0.114664E+09 | 0.100640E+10 |
February | 0.237110E+09 | 0.00 | 0.237110E+09 | 0.148889E+09 | 0.768228E+09 |
March | 0.304540E+09 | 0.00 | 0.304540E+09 | 0.255242E+09 | 0.717877E+09 |
April | 0.347812E+09 | 1409245.47 | 0.346403E+09 | 0.421731E+09 | 0.409337E+09 |
May | 0.407048E+09 | 14823312.11 | 0.392225E+09 | 0.762672E+09 | 0.111552E+09 |
June | 0.447943E+09 | 30923303.10 | 0.417020E+09 | 0.864441E+09 | 87095554.86 |
July | 0.449223E+09 | 17050001.74 | 0.432173E+09 | 0.875541E+09 | 56758686.41 |
August | 0.402323E+09 | 3140591.85 | 0.399183E+09 | 0.805296E+09 | 82611042.77 |
September | 0.336326E+09 | 25176.49 | 0.336301E+09 | 0.621419E+09 | 0.130603E+09 |
October | 0.302004E+09 | 0.00 | 0.302004E+09 | 0.508291E+09 | 0.262376E+09 |
November | 0.221873E+09 | 0.00 | 0.221873E+09 | 0.195716E+09 | 0.618392E+09 |
December | 0.206854E+09 | 0.00 | 0.206854E+09 | 0.128561E+09 | 0.881706E+09 |
Annual Sum or Average | 0.388557E+10 | 67371630.76 | 0.381820E+10 | 0.570246E+10 | 0.513293E+10 |
Minimum of Months | 0.206854E+09 | 0.00 | 0.206854E+09 | 0.114664E+09 | 56758686.41 |
Maximum of Months | 0.449223E+09 | 30923303.10 | 0.432173E+09 | 0.875541E+09 | 0.100640E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.222507E+09 | 0.00 | 0.222507E+09 | 0.114659E+09 | 0.100636E+10 |
February | 0.237101E+09 | 0.00 | 0.237101E+09 | 0.148883E+09 | 0.768198E+09 |
March | 0.304529E+09 | 0.00 | 0.304529E+09 | 0.255233E+09 | 0.717849E+09 |
April | 0.347799E+09 | 1409193.84 | 0.346389E+09 | 0.421715E+09 | 0.409321E+09 |
May | 0.407032E+09 | 14822768.97 | 0.392210E+09 | 0.762642E+09 | 0.111548E+09 |
June | 0.447926E+09 | 30922170.06 | 0.417004E+09 | 0.864408E+09 | 87092271.43 |
July | 0.449206E+09 | 17049377.02 | 0.432156E+09 | 0.875507E+09 | 56756601.90 |
August | 0.402308E+09 | 3140476.77 | 0.399168E+09 | 0.805265E+09 | 82607931.74 |
September | 0.336313E+09 | 25175.57 | 0.336288E+09 | 0.621395E+09 | 0.130598E+09 |
October | 0.301992E+09 | 0.00 | 0.301992E+09 | 0.508272E+09 | 0.262365E+09 |
November | 0.221865E+09 | 0.00 | 0.221865E+09 | 0.195708E+09 | 0.618367E+09 |
December | 0.206846E+09 | 0.00 | 0.206846E+09 | 0.128556E+09 | 0.881671E+09 |
Annual Sum or Average | 0.388542E+10 | 67369162.23 | 0.381805E+10 | 0.570224E+10 | 0.513273E+10 |
Minimum of Months | 0.206846E+09 | 0.00 | 0.206846E+09 | 0.114659E+09 | 56756601.90 |
Maximum of Months | 0.449206E+09 | 30922170.06 | 0.432156E+09 | 0.875507E+09 | 0.100636E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.636294E+09 | 0.323996E+09 | 0.312298E+09 | 0.644245E+09 | 0.983622E+09 |
February | 0.639956E+09 | 0.308940E+09 | 0.331016E+09 | 0.695878E+09 | 0.742945E+09 |
March | 0.833554E+09 | 0.402034E+09 | 0.431520E+09 | 0.103349E+10 | 0.692670E+09 |
April | 0.885186E+09 | 0.400364E+09 | 0.484822E+09 | 0.127378E+10 | 0.392061E+09 |
May | 0.942749E+09 | 0.408785E+09 | 0.533965E+09 | 0.167922E+10 | 0.112169E+09 |
June | 0.925248E+09 | 0.366908E+09 | 0.558340E+09 | 0.170407E+10 | 77512440.72 |
July | 0.921819E+09 | 0.337323E+09 | 0.584496E+09 | 0.171476E+10 | 40065270.39 |
August | 0.849450E+09 | 0.292050E+09 | 0.557400E+09 | 0.158068E+10 | 60861020.57 |
September | 0.728211E+09 | 0.250376E+09 | 0.477835E+09 | 0.127683E+10 | 0.126084E+09 |
October | 0.743580E+09 | 0.313789E+09 | 0.429791E+09 | 0.122439E+10 | 0.251495E+09 |
November | 0.637070E+09 | 0.324982E+09 | 0.312088E+09 | 0.791403E+09 | 0.588276E+09 |
December | 0.518311E+09 | 0.234772E+09 | 0.283539E+09 | 0.544707E+09 | 0.846301E+09 |
Annual Sum or Average | 0.926143E+10 | 0.396432E+10 | 0.529711E+10 | 0.141634E+11 | 0.491406E+10 |
Minimum of Months | 0.518311E+09 | 0.234772E+09 | 0.283539E+09 | 0.544707E+09 | 40065270.39 |
Maximum of Months | 0.942749E+09 | 0.408785E+09 | 0.584496E+09 | 0.171476E+10 | 0.983622E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.636294E+09 | 0.323996E+09 | 0.312298E+09 | 0.644245E+09 | 0.983622E+09 |
February | 0.639956E+09 | 0.308940E+09 | 0.331016E+09 | 0.695878E+09 | 0.742945E+09 |
March | 0.833554E+09 | 0.402034E+09 | 0.431520E+09 | 0.103349E+10 | 0.692670E+09 |
April | 0.885186E+09 | 0.400364E+09 | 0.484822E+09 | 0.127378E+10 | 0.392061E+09 |
May | 0.942749E+09 | 0.408785E+09 | 0.533965E+09 | 0.167922E+10 | 0.112169E+09 |
June | 0.925248E+09 | 0.366908E+09 | 0.558340E+09 | 0.170407E+10 | 77512440.72 |
July | 0.921819E+09 | 0.337323E+09 | 0.584496E+09 | 0.171476E+10 | 40065270.39 |
August | 0.849450E+09 | 0.292050E+09 | 0.557400E+09 | 0.158068E+10 | 60861020.57 |
September | 0.728211E+09 | 0.250376E+09 | 0.477835E+09 | 0.127683E+10 | 0.126084E+09 |
October | 0.743580E+09 | 0.313789E+09 | 0.429791E+09 | 0.122439E+10 | 0.251495E+09 |
November | 0.637070E+09 | 0.324982E+09 | 0.312088E+09 | 0.791403E+09 | 0.588276E+09 |
December | 0.518311E+09 | 0.234772E+09 | 0.283539E+09 | 0.544707E+09 | 0.846301E+09 |
Annual Sum or Average | 0.926143E+10 | 0.396432E+10 | 0.529711E+10 | 0.141634E+11 | 0.491406E+10 |
Minimum of Months | 0.518311E+09 | 0.234772E+09 | 0.283539E+09 | 0.544707E+09 | 40065270.39 |
Maximum of Months | 0.942749E+09 | 0.408785E+09 | 0.584496E+09 | 0.171476E+10 | 0.983622E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.636283E+09 | 0.323990E+09 | 0.312292E+09 | 0.644233E+09 | 0.983604E+09 |
February | 0.639944E+09 | 0.308935E+09 | 0.331010E+09 | 0.695865E+09 | 0.742932E+09 |
March | 0.833539E+09 | 0.402026E+09 | 0.431512E+09 | 0.103347E+10 | 0.692657E+09 |
April | 0.885170E+09 | 0.400357E+09 | 0.484813E+09 | 0.127375E+10 | 0.392054E+09 |
May | 0.942732E+09 | 0.408777E+09 | 0.533955E+09 | 0.167919E+10 | 0.112167E+09 |
June | 0.925231E+09 | 0.366902E+09 | 0.558330E+09 | 0.170403E+10 | 77511024.40 |
July | 0.921802E+09 | 0.337317E+09 | 0.584485E+09 | 0.171472E+10 | 40064538.31 |
August | 0.849435E+09 | 0.292045E+09 | 0.557390E+09 | 0.158065E+10 | 60859908.51 |
September | 0.728197E+09 | 0.250371E+09 | 0.477826E+09 | 0.127681E+10 | 0.126082E+09 |
October | 0.743566E+09 | 0.313783E+09 | 0.429783E+09 | 0.122436E+10 | 0.251490E+09 |
November | 0.637058E+09 | 0.324976E+09 | 0.312082E+09 | 0.791389E+09 | 0.588265E+09 |
December | 0.518302E+09 | 0.234768E+09 | 0.283534E+09 | 0.544697E+09 | 0.846285E+09 |
Annual Sum or Average | 0.926126E+10 | 0.396425E+10 | 0.529701E+10 | 0.141632E+11 | 0.491397E+10 |
Minimum of Months | 0.518302E+09 | 0.234768E+09 | 0.283534E+09 | 0.544697E+09 | 40064538.31 |
Maximum of Months | 0.942732E+09 | 0.408777E+09 | 0.584485E+09 | 0.171472E+10 | 0.983604E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128655E+10 | 0.917642E+09 | 0.368912E+09 | 0.172255E+10 | 0.873184E+09 |
February | 0.105369E+10 | 0.682066E+09 | 0.371627E+09 | 0.138996E+10 | 0.683337E+09 |
March | 0.744492E+09 | 0.335866E+09 | 0.408626E+09 | 0.914284E+09 | 0.677557E+09 |
April | 0.533935E+09 | 0.124933E+09 | 0.409002E+09 | 0.672717E+09 | 0.404934E+09 |
May | 0.421582E+09 | 17755816.43 | 0.403826E+09 | 0.777329E+09 | 0.113233E+09 |
June | 0.403099E+09 | 3679077.86 | 0.399420E+09 | 0.803787E+09 | 88485174.95 |
July | 0.436024E+09 | 7909473.51 | 0.428114E+09 | 0.857363E+09 | 54553610.46 |
August | 0.512908E+09 | 61409888.58 | 0.451498E+09 | 0.953093E+09 | 84821195.46 |
September | 0.595605E+09 | 0.156857E+09 | 0.438748E+09 | 0.100950E+10 | 0.134886E+09 |
October | 0.955038E+09 | 0.497441E+09 | 0.457597E+09 | 0.155856E+10 | 0.266424E+09 |
November | 0.117653E+10 | 0.810139E+09 | 0.366391E+09 | 0.170780E+10 | 0.564236E+09 |
December | 0.125715E+10 | 0.902932E+09 | 0.354222E+09 | 0.177282E+10 | 0.782439E+09 |
Annual Sum or Average | 0.937661E+10 | 0.451863E+10 | 0.485798E+10 | 0.141398E+11 | 0.472809E+10 |
Minimum of Months | 0.403099E+09 | 3679077.86 | 0.354222E+09 | 0.672717E+09 | 54553610.46 |
Maximum of Months | 0.128655E+10 | 0.917642E+09 | 0.457597E+09 | 0.177282E+10 | 0.873184E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128654E+10 | 0.917635E+09 | 0.368910E+09 | 0.172254E+10 | 0.873184E+09 |
February | 0.105369E+10 | 0.682061E+09 | 0.371625E+09 | 0.138995E+10 | 0.683336E+09 |
March | 0.744488E+09 | 0.335864E+09 | 0.408624E+09 | 0.914278E+09 | 0.677557E+09 |
April | 0.533932E+09 | 0.124932E+09 | 0.409000E+09 | 0.672714E+09 | 0.404933E+09 |
May | 0.421580E+09 | 17755686.32 | 0.403825E+09 | 0.777327E+09 | 0.113233E+09 |
June | 0.403097E+09 | 3679050.90 | 0.399418E+09 | 0.803784E+09 | 88484699.94 |
July | 0.436022E+09 | 7909415.54 | 0.428112E+09 | 0.857361E+09 | 54553217.06 |
August | 0.512905E+09 | 61409438.57 | 0.451496E+09 | 0.953090E+09 | 84820742.22 |
September | 0.595601E+09 | 0.156855E+09 | 0.438746E+09 | 0.100949E+10 | 0.134885E+09 |
October | 0.955032E+09 | 0.497437E+09 | 0.457595E+09 | 0.155856E+10 | 0.266423E+09 |
November | 0.117652E+10 | 0.810133E+09 | 0.366389E+09 | 0.170778E+10 | 0.564235E+09 |
December | 0.125714E+10 | 0.902925E+09 | 0.354220E+09 | 0.177281E+10 | 0.782438E+09 |
Annual Sum or Average | 0.937656E+10 | 0.451860E+10 | 0.485796E+10 | 0.141397E+11 | 0.472808E+10 |
Minimum of Months | 0.403097E+09 | 3679050.90 | 0.354220E+09 | 0.672714E+09 | 54553217.06 |
Maximum of Months | 0.128654E+10 | 0.917635E+09 | 0.457595E+09 | 0.177281E+10 | 0.873184E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128655E+10 | 0.917642E+09 | 0.368912E+09 | 0.172255E+10 | 0.873184E+09 |
February | 0.105369E+10 | 0.682066E+09 | 0.371627E+09 | 0.138996E+10 | 0.683337E+09 |
March | 0.744492E+09 | 0.335866E+09 | 0.408626E+09 | 0.914284E+09 | 0.677557E+09 |
April | 0.533935E+09 | 0.124933E+09 | 0.409002E+09 | 0.672717E+09 | 0.404934E+09 |
May | 0.421582E+09 | 17755816.43 | 0.403826E+09 | 0.777329E+09 | 0.113233E+09 |
June | 0.403099E+09 | 3679077.86 | 0.399420E+09 | 0.803787E+09 | 88485174.95 |
July | 0.436024E+09 | 7909473.51 | 0.428114E+09 | 0.857363E+09 | 54553610.46 |
August | 0.512908E+09 | 61409888.58 | 0.451498E+09 | 0.953093E+09 | 84821195.46 |
September | 0.595605E+09 | 0.156857E+09 | 0.438748E+09 | 0.100950E+10 | 0.134886E+09 |
October | 0.955038E+09 | 0.497441E+09 | 0.457597E+09 | 0.155856E+10 | 0.266424E+09 |
November | 0.117653E+10 | 0.810139E+09 | 0.366391E+09 | 0.170780E+10 | 0.564236E+09 |
December | 0.125715E+10 | 0.902932E+09 | 0.354222E+09 | 0.177282E+10 | 0.782439E+09 |
Annual Sum or Average | 0.937661E+10 | 0.451863E+10 | 0.485798E+10 | 0.141398E+11 | 0.472809E+10 |
Minimum of Months | 0.403099E+09 | 3679077.86 | 0.354222E+09 | 0.672717E+09 | 54553610.46 |
Maximum of Months | 0.128655E+10 | 0.917642E+09 | 0.457597E+09 | 0.177282E+10 | 0.873184E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128654E+10 | 0.917635E+09 | 0.368910E+09 | 0.172254E+10 | 0.873184E+09 |
February | 0.105369E+10 | 0.682061E+09 | 0.371625E+09 | 0.138995E+10 | 0.683336E+09 |
March | 0.744488E+09 | 0.335864E+09 | 0.408624E+09 | 0.914278E+09 | 0.677557E+09 |
April | 0.533932E+09 | 0.124932E+09 | 0.409000E+09 | 0.672714E+09 | 0.404933E+09 |
May | 0.421580E+09 | 17755686.32 | 0.403825E+09 | 0.777327E+09 | 0.113233E+09 |
June | 0.403097E+09 | 3679050.90 | 0.399418E+09 | 0.803784E+09 | 88484699.94 |
July | 0.436022E+09 | 7909415.54 | 0.428112E+09 | 0.857361E+09 | 54553217.06 |
August | 0.512905E+09 | 61409438.57 | 0.451496E+09 | 0.953090E+09 | 84820742.22 |
September | 0.595601E+09 | 0.156855E+09 | 0.438746E+09 | 0.100949E+10 | 0.134885E+09 |
October | 0.955032E+09 | 0.497437E+09 | 0.457595E+09 | 0.155856E+10 | 0.266423E+09 |
November | 0.117652E+10 | 0.810133E+09 | 0.366389E+09 | 0.170778E+10 | 0.564235E+09 |
December | 0.125714E+10 | 0.902925E+09 | 0.354220E+09 | 0.177281E+10 | 0.782438E+09 |
Annual Sum or Average | 0.937656E+10 | 0.451860E+10 | 0.485796E+10 | 0.141397E+11 | 0.472808E+10 |
Minimum of Months | 0.403097E+09 | 3679050.90 | 0.354220E+09 | 0.672714E+09 | 54553217.06 |
Maximum of Months | 0.128654E+10 | 0.917635E+09 | 0.457595E+09 | 0.177281E+10 | 0.873184E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.128650E+10 | 0.917601E+09 | 0.368896E+09 | 0.172247E+10 | 0.873149E+09 |
February | 0.105365E+10 | 0.682036E+09 | 0.371611E+09 | 0.138990E+10 | 0.683309E+09 |
March | 0.744460E+09 | 0.335852E+09 | 0.408608E+09 | 0.914244E+09 | 0.677530E+09 |
April | 0.533912E+09 | 0.124928E+09 | 0.408984E+09 | 0.672689E+09 | 0.404917E+09 |
May | 0.421564E+09 | 17755035.74 | 0.403809E+09 | 0.777296E+09 | 0.113228E+09 |
June | 0.403082E+09 | 3678916.10 | 0.399403E+09 | 0.803753E+09 | 88481371.11 |
July | 0.436005E+09 | 7909125.74 | 0.428096E+09 | 0.857327E+09 | 54551215.02 |
August | 0.512886E+09 | 61407188.50 | 0.451479E+09 | 0.953053E+09 | 84817550.18 |
September | 0.595579E+09 | 0.156850E+09 | 0.438729E+09 | 0.100946E+10 | 0.134880E+09 |
October | 0.954996E+09 | 0.497419E+09 | 0.457578E+09 | 0.155850E+10 | 0.266413E+09 |
November | 0.117648E+10 | 0.810103E+09 | 0.366375E+09 | 0.170772E+10 | 0.564213E+09 |
December | 0.125710E+10 | 0.902892E+09 | 0.354206E+09 | 0.177274E+10 | 0.782407E+09 |
Annual Sum or Average | 0.937621E+10 | 0.451843E+10 | 0.485778E+10 | 0.141392E+11 | 0.472790E+10 |
Minimum of Months | 0.403082E+09 | 3678916.10 | 0.354206E+09 | 0.672689E+09 | 54551215.02 |
Maximum of Months | 0.128650E+10 | 0.917601E+09 | 0.457578E+09 | 0.177274E+10 | 0.873149E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.676798E+09 | 0.365967E+09 | 0.310831E+09 | 0.745321E+09 | 0.110859E+10 |
February | 0.692124E+09 | 0.350299E+09 | 0.341825E+09 | 0.790004E+09 | 0.887560E+09 |
March | 0.755300E+09 | 0.334368E+09 | 0.420932E+09 | 0.903744E+09 | 0.872817E+09 |
April | 0.907853E+09 | 0.417655E+09 | 0.490199E+09 | 0.127500E+10 | 0.541279E+09 |
May | 0.780088E+09 | 0.254098E+09 | 0.525990E+09 | 0.139231E+10 | 0.161513E+09 |
June | 0.838635E+09 | 0.294048E+09 | 0.544587E+09 | 0.151978E+10 | 0.140325E+09 |
July | 0.791036E+09 | 0.219405E+09 | 0.571632E+09 | 0.142145E+10 | 0.107104E+09 |
August | 0.799861E+09 | 0.244848E+09 | 0.555013E+09 | 0.143188E+10 | 0.155191E+09 |
September | 0.712801E+09 | 0.244541E+09 | 0.468261E+09 | 0.123412E+10 | 0.179056E+09 |
October | 0.754070E+09 | 0.325830E+09 | 0.428240E+09 | 0.122817E+10 | 0.346670E+09 |
November | 0.625449E+09 | 0.314314E+09 | 0.311135E+09 | 0.787644E+09 | 0.760231E+09 |
December | 0.621696E+09 | 0.330606E+09 | 0.291091E+09 | 0.699004E+09 | 0.106270E+10 |
Annual Sum or Average | 0.895571E+10 | 0.369598E+10 | 0.525973E+10 | 0.134284E+11 | 0.632304E+10 |
Minimum of Months | 0.621696E+09 | 0.219405E+09 | 0.291091E+09 | 0.699004E+09 | 0.107104E+09 |
Maximum of Months | 0.907853E+09 | 0.417655E+09 | 0.571632E+09 | 0.151978E+10 | 0.110859E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.676798E+09 | 0.365967E+09 | 0.310831E+09 | 0.745321E+09 | 0.110859E+10 |
February | 0.692124E+09 | 0.350299E+09 | 0.341825E+09 | 0.790004E+09 | 0.887560E+09 |
March | 0.755300E+09 | 0.334368E+09 | 0.420932E+09 | 0.903744E+09 | 0.872817E+09 |
April | 0.907853E+09 | 0.417655E+09 | 0.490199E+09 | 0.127500E+10 | 0.541279E+09 |
May | 0.780088E+09 | 0.254098E+09 | 0.525990E+09 | 0.139231E+10 | 0.161513E+09 |
June | 0.838635E+09 | 0.294048E+09 | 0.544587E+09 | 0.151978E+10 | 0.140325E+09 |
July | 0.791036E+09 | 0.219405E+09 | 0.571632E+09 | 0.142145E+10 | 0.107104E+09 |
August | 0.799861E+09 | 0.244848E+09 | 0.555013E+09 | 0.143188E+10 | 0.155191E+09 |
September | 0.712801E+09 | 0.244541E+09 | 0.468261E+09 | 0.123412E+10 | 0.179056E+09 |
October | 0.754070E+09 | 0.325830E+09 | 0.428240E+09 | 0.122817E+10 | 0.346670E+09 |
November | 0.625449E+09 | 0.314314E+09 | 0.311135E+09 | 0.787644E+09 | 0.760231E+09 |
December | 0.621696E+09 | 0.330606E+09 | 0.291091E+09 | 0.699004E+09 | 0.106270E+10 |
Annual Sum or Average | 0.895571E+10 | 0.369598E+10 | 0.525973E+10 | 0.134284E+11 | 0.632304E+10 |
Minimum of Months | 0.621696E+09 | 0.219405E+09 | 0.291091E+09 | 0.699004E+09 | 0.107104E+09 |
Maximum of Months | 0.907853E+09 | 0.417655E+09 | 0.571632E+09 | 0.151978E+10 | 0.110859E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.676785E+09 | 0.365960E+09 | 0.310825E+09 | 0.745307E+09 | 0.110857E+10 |
February | 0.692112E+09 | 0.350293E+09 | 0.341819E+09 | 0.789990E+09 | 0.887544E+09 |
March | 0.755286E+09 | 0.334362E+09 | 0.420924E+09 | 0.903728E+09 | 0.872801E+09 |
April | 0.907837E+09 | 0.417647E+09 | 0.490190E+09 | 0.127498E+10 | 0.541269E+09 |
May | 0.780074E+09 | 0.254093E+09 | 0.525981E+09 | 0.139228E+10 | 0.161510E+09 |
June | 0.838620E+09 | 0.294043E+09 | 0.544577E+09 | 0.151975E+10 | 0.140323E+09 |
July | 0.791022E+09 | 0.219401E+09 | 0.571621E+09 | 0.142142E+10 | 0.107102E+09 |
August | 0.799846E+09 | 0.244844E+09 | 0.555003E+09 | 0.143185E+10 | 0.155188E+09 |
September | 0.712788E+09 | 0.244536E+09 | 0.468252E+09 | 0.123409E+10 | 0.179053E+09 |
October | 0.754056E+09 | 0.325824E+09 | 0.428232E+09 | 0.122815E+10 | 0.346664E+09 |
November | 0.625438E+09 | 0.314308E+09 | 0.311129E+09 | 0.787629E+09 | 0.760217E+09 |
December | 0.621685E+09 | 0.330600E+09 | 0.291085E+09 | 0.698991E+09 | 0.106268E+10 |
Annual Sum or Average | 0.895555E+10 | 0.369591E+10 | 0.525964E+10 | 0.134282E+11 | 0.632292E+10 |
Minimum of Months | 0.621685E+09 | 0.219401E+09 | 0.291085E+09 | 0.698991E+09 | 0.107102E+09 |
Maximum of Months | 0.907837E+09 | 0.417647E+09 | 0.571621E+09 | 0.151975E+10 | 0.110857E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111259E+10 | 0.00 | 0.111259E+10 | 0.670410E+09 | 0.452388E+10 |
February | 0.118556E+10 | 0.00 | 0.118556E+10 | 0.838058E+09 | 0.341307E+10 |
March | 0.152272E+10 | 0.00 | 0.152272E+10 | 0.137908E+10 | 0.322780E+10 |
April | 0.173908E+10 | 7046427.16 | 0.173203E+10 | 0.217627E+10 | 0.191045E+10 |
May | 0.203527E+10 | 74118662.28 | 0.196115E+10 | 0.384425E+10 | 0.533139E+09 |
June | 0.223975E+10 | 0.154621E+09 | 0.208513E+10 | 0.435403E+10 | 0.443707E+09 |
July | 0.224615E+10 | 85252426.15 | 0.216089E+10 | 0.440680E+10 | 0.303178E+09 |
August | 0.201164E+10 | 15703404.52 | 0.199594E+10 | 0.407492E+10 | 0.427627E+09 |
September | 0.168165E+10 | 125886.02 | 0.168153E+10 | 0.314613E+10 | 0.590828E+09 |
October | 0.151004E+10 | 0.00 | 0.151004E+10 | 0.260396E+10 | 0.120064E+10 |
November | 0.110938E+10 | 0.00 | 0.110938E+10 | 0.107649E+10 | 0.273138E+10 |
December | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.752642E+09 | 0.384348E+10 |
Annual Sum or Average | 0.194281E+11 | 0.336868E+09 | 0.190912E+11 | 0.293230E+11 | 0.231492E+11 |
Minimum of Months | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.670410E+09 | 0.303178E+09 |
Maximum of Months | 0.224615E+10 | 0.154621E+09 | 0.216089E+10 | 0.440680E+10 | 0.452388E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190886E+10 | 0.971978E+09 | 0.936885E+09 | 0.199369E+10 | 0.271901E+10 |
February | 0.191985E+10 | 0.926812E+09 | 0.993037E+09 | 0.213740E+10 | 0.205669E+10 |
March | 0.250064E+10 | 0.120609E+10 | 0.129455E+10 | 0.311707E+10 | 0.196594E+10 |
April | 0.265553E+10 | 0.120108E+10 | 0.145445E+10 | 0.379057E+10 | 0.120523E+10 |
May | 0.282822E+10 | 0.122634E+10 | 0.160188E+10 | 0.500187E+10 | 0.348234E+09 |
June | 0.277572E+10 | 0.110071E+10 | 0.167500E+10 | 0.506999E+10 | 0.286165E+09 |
July | 0.276543E+10 | 0.101196E+10 | 0.175347E+10 | 0.507217E+10 | 0.189869E+09 |
August | 0.254832E+10 | 0.876141E+09 | 0.167218E+10 | 0.467840E+10 | 0.270870E+09 |
September | 0.218461E+10 | 0.751120E+09 | 0.143349E+10 | 0.382026E+10 | 0.365367E+09 |
October | 0.223072E+10 | 0.941357E+09 | 0.128936E+10 | 0.366369E+10 | 0.743781E+09 |
November | 0.191119E+10 | 0.974936E+09 | 0.936254E+09 | 0.241258E+10 | 0.164549E+10 |
December | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.169243E+10 | 0.234350E+10 |
Annual Sum or Average | 0.277840E+11 | 0.118928E+11 | 0.158912E+11 | 0.424501E+11 | 0.141401E+11 |
Minimum of Months | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.169243E+10 | 0.189869E+09 |
Maximum of Months | 0.282822E+10 | 0.122634E+10 | 0.175347E+10 | 0.507217E+10 | 0.271901E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643289E+10 | 0.458830E+10 | 0.184458E+10 | 0.853124E+10 | 0.430112E+10 |
February | 0.526856E+10 | 0.341040E+10 | 0.185815E+10 | 0.690837E+10 | 0.332795E+10 |
March | 0.372252E+10 | 0.167937E+10 | 0.204315E+10 | 0.457402E+10 | 0.324447E+10 |
April | 0.266971E+10 | 0.624679E+09 | 0.204503E+10 | 0.338907E+10 | 0.197688E+10 |
May | 0.210793E+10 | 88780949.09 | 0.201915E+10 | 0.391158E+10 | 0.553662E+09 |
June | 0.201551E+10 | 18395776.14 | 0.199712E+10 | 0.404742E+10 | 0.457868E+09 |
July | 0.218014E+10 | 39548199.17 | 0.214059E+10 | 0.431393E+10 | 0.298497E+09 |
August | 0.256457E+10 | 0.307056E+09 | 0.225752E+10 | 0.479166E+10 | 0.459456E+09 |
September | 0.297807E+10 | 0.784300E+09 | 0.219377E+10 | 0.504644E+10 | 0.650305E+09 |
October | 0.477527E+10 | 0.248726E+10 | 0.228802E+10 | 0.775005E+10 | 0.132781E+10 |
November | 0.588276E+10 | 0.405078E+10 | 0.183198E+10 | 0.849118E+10 | 0.275528E+10 |
December | 0.628589E+10 | 0.451475E+10 | 0.177113E+10 | 0.881957E+10 | 0.379042E+10 |
Annual Sum or Average | 0.468838E+11 | 0.225936E+11 | 0.242902E+11 | 0.705745E+11 | 0.231437E+11 |
Minimum of Months | 0.201551E+10 | 18395776.14 | 0.177113E+10 | 0.338907E+10 | 0.298497E+09 |
Maximum of Months | 0.643289E+10 | 0.458830E+10 | 0.228802E+10 | 0.881957E+10 | 0.430112E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203037E+10 | 0.109789E+10 | 0.932483E+09 | 0.232409E+10 | 0.295626E+10 |
February | 0.207635E+10 | 0.105089E+10 | 0.102546E+10 | 0.248255E+10 | 0.227077E+10 |
March | 0.226588E+10 | 0.100309E+10 | 0.126278E+10 | 0.285068E+10 | 0.217441E+10 |
April | 0.272353E+10 | 0.125295E+10 | 0.147058E+10 | 0.395836E+10 | 0.137104E+10 |
May | 0.234024E+10 | 0.762287E+09 | 0.157795E+10 | 0.423073E+10 | 0.421303E+09 |
June | 0.251588E+10 | 0.882135E+09 | 0.163375E+10 | 0.463637E+10 | 0.364472E+09 |
July | 0.237308E+10 | 0.658207E+09 | 0.171488E+10 | 0.439009E+10 | 0.253958E+09 |
August | 0.239956E+10 | 0.734537E+09 | 0.166502E+10 | 0.443965E+10 | 0.355409E+09 |
September | 0.213838E+10 | 0.733614E+09 | 0.140477E+10 | 0.375728E+10 | 0.441685E+09 |
October | 0.226219E+10 | 0.977479E+09 | 0.128471E+10 | 0.377819E+10 | 0.874310E+09 |
November | 0.187633E+10 | 0.942933E+09 | 0.933395E+09 | 0.250789E+10 | 0.185477E+10 |
December | 0.186507E+10 | 0.991807E+09 | 0.873263E+09 | 0.225580E+10 | 0.254986E+10 |
Annual Sum or Average | 0.268669E+11 | 0.110878E+11 | 0.157790E+11 | 0.416117E+11 | 0.158882E+11 |
Minimum of Months | 0.186507E+10 | 0.658207E+09 | 0.873263E+09 | 0.225580E+10 | 0.253958E+09 |
Maximum of Months | 0.272353E+10 | 0.125295E+10 | 0.171488E+10 | 0.463637E+10 | 0.295626E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111259E+10 | 0.00 | 0.111259E+10 | 0.740319E+09 | 0.414664E+10 |
February | 0.118556E+10 | 0.00 | 0.118556E+10 | 0.888130E+09 | 0.312546E+10 |
March | 0.152272E+10 | 0.00 | 0.152272E+10 | 0.141934E+10 | 0.301869E+10 |
April | 0.173908E+10 | 7046427.16 | 0.173203E+10 | 0.217196E+10 | 0.184436E+10 |
May | 0.203527E+10 | 74118662.28 | 0.196115E+10 | 0.378542E+10 | 0.555407E+09 |
June | 0.223975E+10 | 0.154621E+09 | 0.208513E+10 | 0.428413E+10 | 0.470051E+09 |
July | 0.224615E+10 | 85252426.15 | 0.216089E+10 | 0.432669E+10 | 0.329079E+09 |
August | 0.201164E+10 | 15703404.52 | 0.199594E+10 | 0.401091E+10 | 0.449639E+09 |
September | 0.168165E+10 | 125886.02 | 0.168153E+10 | 0.309153E+10 | 0.601844E+09 |
October | 0.151004E+10 | 0.00 | 0.151004E+10 | 0.258015E+10 | 0.116153E+10 |
November | 0.110938E+10 | 0.00 | 0.110938E+10 | 0.112690E+10 | 0.251629E+10 |
December | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.808706E+09 | 0.352751E+10 |
Annual Sum or Average | 0.194281E+11 | 0.336868E+09 | 0.190912E+11 | 0.292342E+11 | 0.217465E+11 |
Minimum of Months | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.740319E+09 | 0.329079E+09 |
Maximum of Months | 0.224615E+10 | 0.154621E+09 | 0.216089E+10 | 0.432669E+10 | 0.414664E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.190886E+10 | 0.971978E+09 | 0.936885E+09 | 0.206084E+10 | 0.253281E+10 |
February | 0.191985E+10 | 0.926812E+09 | 0.993037E+09 | 0.218427E+10 | 0.191874E+10 |
March | 0.250064E+10 | 0.120609E+10 | 0.129455E+10 | 0.313562E+10 | 0.187709E+10 |
April | 0.265553E+10 | 0.120108E+10 | 0.145445E+10 | 0.377520E+10 | 0.118516E+10 |
May | 0.282822E+10 | 0.122634E+10 | 0.160188E+10 | 0.495212E+10 | 0.366509E+09 |
June | 0.277572E+10 | 0.110071E+10 | 0.167500E+10 | 0.501692E+10 | 0.307591E+09 |
July | 0.276543E+10 | 0.101196E+10 | 0.175347E+10 | 0.501229E+10 | 0.208305E+09 |
August | 0.254832E+10 | 0.876141E+09 | 0.167218E+10 | 0.462764E+10 | 0.289248E+09 |
September | 0.218461E+10 | 0.751120E+09 | 0.143349E+10 | 0.377512E+10 | 0.380731E+09 |
October | 0.223072E+10 | 0.941357E+09 | 0.128936E+10 | 0.363611E+10 | 0.733454E+09 |
November | 0.191119E+10 | 0.974936E+09 | 0.936254E+09 | 0.244451E+10 | 0.155568E+10 |
December | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.173472E+10 | 0.219784E+10 |
Annual Sum or Average | 0.277840E+11 | 0.118928E+11 | 0.158912E+11 | 0.423554E+11 | 0.135532E+11 |
Minimum of Months | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.173472E+10 | 0.208305E+09 |
Maximum of Months | 0.282822E+10 | 0.122634E+10 | 0.175347E+10 | 0.501692E+10 | 0.253281E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.643289E+10 | 0.458830E+10 | 0.184458E+10 | 0.861566E+10 | 0.400591E+10 |
February | 0.526856E+10 | 0.341040E+10 | 0.185815E+10 | 0.697641E+10 | 0.309807E+10 |
March | 0.372252E+10 | 0.167937E+10 | 0.204315E+10 | 0.460595E+10 | 0.306024E+10 |
April | 0.266971E+10 | 0.624679E+09 | 0.204503E+10 | 0.338687E+10 | 0.191493E+10 |
May | 0.210793E+10 | 88780949.09 | 0.201915E+10 | 0.385993E+10 | 0.574294E+09 |
June | 0.201551E+10 | 18395776.14 | 0.199712E+10 | 0.398733E+10 | 0.484568E+09 |
July | 0.218014E+10 | 39548199.17 | 0.214059E+10 | 0.424065E+10 | 0.322269E+09 |
August | 0.256457E+10 | 0.307056E+09 | 0.225752E+10 | 0.473334E+10 | 0.480523E+09 |
September | 0.297807E+10 | 0.784300E+09 | 0.219377E+10 | 0.499836E+10 | 0.661016E+09 |
October | 0.477527E+10 | 0.248726E+10 | 0.228802E+10 | 0.772154E+10 | 0.129567E+10 |
November | 0.588276E+10 | 0.405078E+10 | 0.183198E+10 | 0.853048E+10 | 0.260278E+10 |
December | 0.628589E+10 | 0.451475E+10 | 0.177113E+10 | 0.888326E+10 | 0.353961E+10 |
Annual Sum or Average | 0.468838E+11 | 0.225936E+11 | 0.242902E+11 | 0.705398E+11 | 0.220399E+11 |
Minimum of Months | 0.201551E+10 | 18395776.14 | 0.177113E+10 | 0.338687E+10 | 0.322269E+09 |
Maximum of Months | 0.643289E+10 | 0.458830E+10 | 0.228802E+10 | 0.888326E+10 | 0.400591E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.203037E+10 | 0.109789E+10 | 0.932483E+09 | 0.235581E+10 | 0.276963E+10 |
February | 0.207635E+10 | 0.105089E+10 | 0.102546E+10 | 0.250594E+10 | 0.212512E+10 |
March | 0.226588E+10 | 0.100309E+10 | 0.126278E+10 | 0.286395E+10 | 0.206507E+10 |
April | 0.272353E+10 | 0.125295E+10 | 0.147058E+10 | 0.395027E+10 | 0.132987E+10 |
May | 0.234024E+10 | 0.762287E+09 | 0.157795E+10 | 0.420193E+10 | 0.426872E+09 |
June | 0.251588E+10 | 0.882135E+09 | 0.163375E+10 | 0.460023E+10 | 0.373587E+09 |
July | 0.237308E+10 | 0.658207E+09 | 0.171488E+10 | 0.434988E+10 | 0.261817E+09 |
August | 0.239956E+10 | 0.734537E+09 | 0.166502E+10 | 0.440615E+10 | 0.362662E+09 |
September | 0.213838E+10 | 0.733614E+09 | 0.140477E+10 | 0.373286E+10 | 0.442878E+09 |
October | 0.226219E+10 | 0.977479E+09 | 0.128471E+10 | 0.376504E+10 | 0.849549E+09 |
November | 0.187633E+10 | 0.942933E+09 | 0.933395E+09 | 0.252974E+10 | 0.174533E+10 |
December | 0.186507E+10 | 0.991807E+09 | 0.873263E+09 | 0.228117E+10 | 0.239173E+10 |
Annual Sum or Average | 0.268669E+11 | 0.110878E+11 | 0.157790E+11 | 0.415430E+11 | 0.151441E+11 |
Minimum of Months | 0.186507E+10 | 0.658207E+09 | 0.873263E+09 | 0.228117E+10 | 0.261817E+09 |
Maximum of Months | 0.272353E+10 | 0.125295E+10 | 0.171488E+10 | 0.460023E+10 | 0.276963E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 214.05 | 1878.71 | 415.39 | 0.00 | 415.39 | 0.00 | 0.00 |
February | 307.72 | 1587.76 | 490.06 | 0.00 | 490.06 | 0.00 | 0.00 |
March | 476.48 | 1340.11 | 568.51 | 0.00 | 568.51 | 0.00 | 0.00 |
April | 813.52 | 789.61 | 670.93 | 2.72 | 668.21 | 0.00 | 0.00 |
May | 1423.74 | 208.24 | 759.87 | 27.67 | 732.20 | 0.00 | 0.00 |
June | 1667.51 | 168.01 | 864.08 | 59.65 | 804.43 | 0.00 | 0.00 |
July | 1634.44 | 105.96 | 838.60 | 31.83 | 806.77 | 0.00 | 0.00 |
August | 1503.31 | 154.22 | 751.05 | 5.86 | 745.19 | 0.00 | 0.00 |
September | 1198.72 | 251.93 | 648.77 | 0.05 | 648.73 | 0.00 | 0.00 |
October | 948.87 | 489.80 | 563.77 | 0.00 | 563.77 | 0.00 | 0.00 |
November | 377.54 | 1192.88 | 427.99 | 0.00 | 427.99 | 0.00 | 0.00 |
December | 239.99 | 1645.94 | 386.15 | 0.00 | 386.15 | 0.00 | 0.00 |
Annual Sum or Average | 904.12 | 813.82 | 616.05 | 10.68 | 605.37 | 0.00 | 0.00 |
Minimum of Months | 214.05 | 105.96 | 386.15 | 0.00 | 386.15 | 0.00 | 0.00 |
Maximum of Months | 1667.51 | 1878.71 | 864.08 | 59.65 | 806.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 721.60 | 1101.72 | 712.69 | 362.90 | 349.79 | 0.00 | 0.00 |
February | 862.94 | 921.31 | 793.59 | 383.11 | 410.48 | 0.00 | 0.00 |
March | 1157.58 | 775.83 | 933.63 | 450.30 | 483.33 | 0.00 | 0.00 |
April | 1474.27 | 453.77 | 1024.51 | 463.38 | 561.13 | 0.00 | 0.00 |
May | 1880.84 | 125.64 | 1055.94 | 457.87 | 598.07 | 0.00 | 0.00 |
June | 1972.29 | 89.71 | 1070.88 | 424.66 | 646.22 | 0.00 | 0.00 |
July | 1920.64 | 44.88 | 1032.50 | 377.82 | 654.67 | 0.00 | 0.00 |
August | 1770.47 | 68.17 | 951.44 | 327.11 | 624.32 | 0.00 | 0.00 |
September | 1477.81 | 145.93 | 842.83 | 289.79 | 553.05 | 0.00 | 0.00 |
October | 1371.39 | 281.69 | 832.86 | 351.46 | 481.39 | 0.00 | 0.00 |
November | 915.97 | 680.87 | 737.34 | 376.13 | 361.21 | 0.00 | 0.00 |
December | 610.11 | 947.91 | 580.54 | 262.96 | 317.58 | 0.00 | 0.00 |
Annual Sum or Average | 1347.35 | 467.47 | 881.03 | 377.12 | 503.91 | 0.00 | 0.00 |
Minimum of Months | 610.11 | 44.88 | 580.54 | 262.96 | 317.58 | 0.00 | 0.00 |
Maximum of Months | 1972.29 | 1101.72 | 1070.88 | 463.38 | 654.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3215.59 | 1630.03 | 2401.69 | 1713.02 | 688.67 | 0.00 | 0.00 |
February | 2872.73 | 1412.31 | 2177.75 | 1409.68 | 768.07 | 0.00 | 0.00 |
March | 1706.75 | 1264.84 | 1389.79 | 626.98 | 762.81 | 0.00 | 0.00 |
April | 1297.67 | 781.11 | 1029.96 | 240.99 | 788.96 | 0.00 | 0.00 |
May | 1451.09 | 211.38 | 787.00 | 33.15 | 753.85 | 0.00 | 0.00 |
June | 1550.50 | 170.69 | 777.58 | 7.10 | 770.48 | 0.00 | 0.00 |
July | 1600.50 | 101.84 | 813.95 | 14.77 | 799.19 | 0.00 | 0.00 |
August | 1779.20 | 158.34 | 957.48 | 114.64 | 842.84 | 0.00 | 0.00 |
September | 1947.32 | 260.19 | 1148.92 | 302.57 | 846.34 | 0.00 | 0.00 |
October | 2909.48 | 497.35 | 1782.83 | 928.60 | 854.23 | 0.00 | 0.00 |
November | 3294.32 | 1088.41 | 2269.51 | 1562.75 | 706.77 | 0.00 | 0.00 |
December | 3309.44 | 1460.63 | 2346.81 | 1685.56 | 661.25 | 0.00 | 0.00 |
Annual Sum or Average | 2241.82 | 749.63 | 1486.64 | 716.42 | 770.22 | 0.00 | 0.00 |
Minimum of Months | 1297.67 | 101.84 | 777.58 | 7.10 | 661.25 | 0.00 | 0.00 |
Maximum of Months | 3309.44 | 1630.03 | 2401.69 | 1713.02 | 854.23 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 834.81 | 1241.70 | 758.06 | 409.91 | 348.15 | 0.00 | 0.00 |
February | 979.66 | 1100.64 | 858.28 | 434.40 | 423.89 | 0.00 | 0.00 |
March | 1012.25 | 977.61 | 845.98 | 374.51 | 471.47 | 0.00 | 0.00 |
April | 1475.69 | 626.48 | 1050.75 | 483.39 | 567.36 | 0.00 | 0.00 |
May | 1559.47 | 180.90 | 873.75 | 284.61 | 589.14 | 0.00 | 0.00 |
June | 1758.99 | 162.41 | 970.64 | 340.33 | 630.31 | 0.00 | 0.00 |
July | 1592.11 | 119.96 | 886.01 | 245.75 | 640.26 | 0.00 | 0.00 |
August | 1603.79 | 173.82 | 895.90 | 274.25 | 621.65 | 0.00 | 0.00 |
September | 1428.37 | 207.24 | 825.00 | 283.03 | 541.96 | 0.00 | 0.00 |
October | 1375.63 | 388.29 | 844.61 | 364.95 | 479.66 | 0.00 | 0.00 |
November | 911.62 | 879.89 | 723.89 | 363.79 | 360.11 | 0.00 | 0.00 |
December | 782.93 | 1190.29 | 696.34 | 370.30 | 326.04 | 0.00 | 0.00 |
Annual Sum or Average | 1277.43 | 601.50 | 851.95 | 351.59 | 500.35 | 0.00 | 0.00 |
Minimum of Months | 782.93 | 119.96 | 696.34 | 245.75 | 326.04 | 0.00 | 0.00 |
Maximum of Months | 1758.99 | 1241.70 | 1050.75 | 483.39 | 640.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 250.30 | 1689.02 | 415.39 | 0.00 | 415.39 | 0.00 | 0.00 |
February | 346.42 | 1410.83 | 490.06 | 0.00 | 490.06 | 0.00 | 0.00 |
March | 514.89 | 1205.12 | 568.52 | 0.00 | 568.52 | 0.00 | 0.00 |
April | 839.61 | 737.06 | 670.94 | 2.72 | 668.22 | 0.00 | 0.00 |
May | 1435.28 | 199.05 | 759.88 | 27.67 | 732.21 | 0.00 | 0.00 |
June | 1679.80 | 171.18 | 864.10 | 59.65 | 804.45 | 0.00 | 0.00 |
July | 1645.31 | 113.19 | 838.62 | 31.83 | 806.79 | 0.00 | 0.00 |
August | 1521.40 | 159.66 | 751.06 | 5.86 | 745.20 | 0.00 | 0.00 |
September | 1213.79 | 227.94 | 648.79 | 0.05 | 648.74 | 0.00 | 0.00 |
October | 972.21 | 448.27 | 563.78 | 0.00 | 563.78 | 0.00 | 0.00 |
November | 415.31 | 1053.77 | 428.00 | 0.00 | 428.00 | 0.00 | 0.00 |
December | 281.00 | 1434.99 | 386.16 | 0.00 | 386.16 | 0.00 | 0.00 |
Annual Sum or Average | 929.83 | 734.06 | 616.06 | 10.68 | 605.38 | 0.00 | 0.00 |
Minimum of Months | 250.30 | 113.19 | 386.16 | 0.00 | 386.16 | 0.00 | 0.00 |
Maximum of Months | 1679.80 | 1689.02 | 864.10 | 59.65 | 806.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 744.36 | 1015.16 | 712.69 | 362.90 | 349.79 | 0.00 | 0.00 |
February | 883.51 | 850.15 | 793.59 | 383.11 | 410.48 | 0.00 | 0.00 |
March | 1163.78 | 734.00 | 933.63 | 450.30 | 483.33 | 0.00 | 0.00 |
April | 1462.41 | 464.98 | 1024.51 | 463.38 | 561.13 | 0.00 | 0.00 |
May | 1867.48 | 130.02 | 1055.94 | 457.86 | 598.07 | 0.00 | 0.00 |
June | 1956.01 | 110.40 | 1070.88 | 424.66 | 646.22 | 0.00 | 0.00 |
July | 1893.73 | 70.89 | 1032.49 | 377.82 | 654.67 | 0.00 | 0.00 |
August | 1746.71 | 101.13 | 951.44 | 327.11 | 624.32 | 0.00 | 0.00 |
September | 1473.87 | 140.96 | 842.83 | 289.78 | 553.04 | 0.00 | 0.00 |
October | 1367.86 | 277.70 | 832.85 | 351.46 | 481.39 | 0.00 | 0.00 |
November | 930.78 | 634.83 | 737.34 | 376.13 | 361.21 | 0.00 | 0.00 |
December | 631.88 | 874.96 | 580.54 | 262.96 | 317.58 | 0.00 | 0.00 |
Annual Sum or Average | 1346.08 | 448.38 | 881.02 | 377.12 | 503.91 | 0.00 | 0.00 |
Minimum of Months | 631.88 | 70.89 | 580.54 | 262.96 | 317.58 | 0.00 | 0.00 |
Maximum of Months | 1956.01 | 1015.16 | 1070.88 | 463.38 | 654.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3185.20 | 1605.85 | 2401.76 | 1713.08 | 688.69 | 0.00 | 0.00 |
February | 2855.64 | 1375.64 | 2177.81 | 1409.72 | 768.09 | 0.00 | 0.00 |
March | 1707.74 | 1211.35 | 1389.83 | 627.00 | 762.83 | 0.00 | 0.00 |
April | 1307.51 | 762.69 | 1029.98 | 241.00 | 788.98 | 0.00 | 0.00 |
May | 1460.42 | 206.71 | 787.01 | 33.15 | 753.86 | 0.00 | 0.00 |
June | 1561.50 | 176.65 | 777.59 | 7.10 | 770.49 | 0.00 | 0.00 |
July | 1610.64 | 111.45 | 813.97 | 14.77 | 799.21 | 0.00 | 0.00 |
August | 1789.00 | 171.54 | 957.50 | 114.64 | 842.86 | 0.00 | 0.00 |
September | 1946.93 | 250.89 | 1148.95 | 302.58 | 846.36 | 0.00 | 0.00 |
October | 2893.54 | 495.75 | 1782.88 | 928.64 | 854.25 | 0.00 | 0.00 |
November | 3275.92 | 1062.99 | 2269.58 | 1562.80 | 706.78 | 0.00 | 0.00 |
December | 3292.85 | 1415.18 | 2346.88 | 1685.62 | 661.26 | 0.00 | 0.00 |
Annual Sum or Average | 2237.90 | 733.88 | 1486.68 | 716.44 | 770.24 | 0.00 | 0.00 |
Minimum of Months | 1307.51 | 111.45 | 777.59 | 7.10 | 661.26 | 0.00 | 0.00 |
Maximum of Months | 3292.85 | 1605.85 | 2401.76 | 1713.08 | 854.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 867.72 | 1103.74 | 758.05 | 409.91 | 348.15 | 0.00 | 0.00 |
February | 1026.19 | 938.64 | 858.28 | 434.39 | 423.89 | 0.00 | 0.00 |
March | 1064.32 | 811.83 | 845.98 | 374.51 | 471.47 | 0.00 | 0.00 |
April | 1527.15 | 528.95 | 1050.75 | 483.39 | 567.35 | 0.00 | 0.00 |
May | 1579.57 | 157.30 | 873.75 | 284.61 | 589.14 | 0.00 | 0.00 |
June | 1788.72 | 140.61 | 970.63 | 340.33 | 630.30 | 0.00 | 0.00 |
July | 1639.07 | 94.82 | 886.01 | 245.75 | 640.26 | 0.00 | 0.00 |
August | 1657.57 | 132.69 | 895.89 | 274.24 | 621.65 | 0.00 | 0.00 |
September | 1449.57 | 170.40 | 824.99 | 283.03 | 541.96 | 0.00 | 0.00 |
October | 1410.61 | 326.43 | 844.60 | 364.95 | 479.65 | 0.00 | 0.00 |
November | 967.55 | 715.57 | 723.89 | 363.79 | 360.11 | 0.00 | 0.00 |
December | 842.22 | 952.01 | 696.34 | 370.30 | 326.04 | 0.00 | 0.00 |
Annual Sum or Average | 1319.50 | 503.81 | 851.94 | 351.59 | 500.35 | 0.00 | 0.00 |
Minimum of Months | 842.22 | 94.82 | 696.34 | 245.75 | 326.04 | 0.00 | 0.00 |
Maximum of Months | 1788.72 | 1103.74 | 1050.75 | 483.39 | 640.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 276.40 | 1548.18 | 415.39 | 0.00 | 415.39 | 0.00 | 0.00 |
February | 367.12 | 1291.94 | 490.06 | 0.00 | 490.06 | 0.00 | 0.00 |
March | 529.92 | 1127.05 | 568.52 | 0.00 | 568.52 | 0.00 | 0.00 |
April | 837.95 | 711.56 | 670.94 | 2.72 | 668.22 | 0.00 | 0.00 |
May | 1413.31 | 207.37 | 759.88 | 27.67 | 732.21 | 0.00 | 0.00 |
June | 1652.83 | 181.35 | 864.10 | 59.65 | 804.45 | 0.00 | 0.00 |
July | 1615.40 | 122.86 | 838.62 | 31.83 | 806.79 | 0.00 | 0.00 |
August | 1497.50 | 167.88 | 751.06 | 5.86 | 745.20 | 0.00 | 0.00 |
September | 1192.72 | 232.19 | 648.79 | 0.05 | 648.74 | 0.00 | 0.00 |
October | 963.32 | 433.66 | 563.78 | 0.00 | 563.78 | 0.00 | 0.00 |
November | 434.76 | 970.79 | 428.00 | 0.00 | 428.00 | 0.00 | 0.00 |
December | 301.94 | 1317.02 | 386.16 | 0.00 | 386.16 | 0.00 | 0.00 |
Annual Sum or Average | 927.01 | 689.58 | 616.06 | 10.68 | 605.38 | 0.00 | 0.00 |
Minimum of Months | 276.40 | 122.86 | 386.16 | 0.00 | 386.16 | 0.00 | 0.00 |
Maximum of Months | 1652.83 | 1548.18 | 864.10 | 59.65 | 806.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 769.43 | 945.64 | 712.69 | 362.90 | 349.79 | 0.00 | 0.00 |
February | 902.89 | 793.13 | 793.59 | 383.11 | 410.48 | 0.00 | 0.00 |
March | 1170.71 | 700.83 | 933.63 | 450.30 | 483.33 | 0.00 | 0.00 |
April | 1456.48 | 457.24 | 1024.51 | 463.38 | 561.13 | 0.00 | 0.00 |
May | 1848.91 | 136.84 | 1055.94 | 457.86 | 598.07 | 0.00 | 0.00 |
June | 1935.54 | 118.67 | 1070.88 | 424.66 | 646.22 | 0.00 | 0.00 |
July | 1871.37 | 77.77 | 1032.49 | 377.82 | 654.67 | 0.00 | 0.00 |
August | 1727.76 | 107.99 | 951.44 | 327.11 | 624.32 | 0.00 | 0.00 |
September | 1456.45 | 146.89 | 842.83 | 289.78 | 553.04 | 0.00 | 0.00 |
October | 1357.57 | 273.84 | 832.85 | 351.46 | 481.39 | 0.00 | 0.00 |
November | 943.10 | 600.19 | 737.34 | 376.13 | 361.21 | 0.00 | 0.00 |
December | 647.67 | 820.58 | 580.54 | 262.96 | 317.58 | 0.00 | 0.00 |
Annual Sum or Average | 1343.08 | 429.77 | 881.02 | 377.12 | 503.91 | 0.00 | 0.00 |
Minimum of Months | 647.67 | 77.77 | 580.54 | 262.96 | 317.58 | 0.00 | 0.00 |
Maximum of Months | 1935.54 | 945.64 | 1070.88 | 463.38 | 654.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3216.72 | 1495.64 | 2401.76 | 1713.08 | 688.69 | 0.00 | 0.00 |
February | 2883.77 | 1280.62 | 2177.81 | 1409.72 | 768.09 | 0.00 | 0.00 |
March | 1719.66 | 1142.56 | 1389.83 | 627.00 | 762.83 | 0.00 | 0.00 |
April | 1306.66 | 738.79 | 1029.98 | 241.00 | 788.98 | 0.00 | 0.00 |
May | 1441.13 | 214.42 | 787.01 | 33.15 | 753.86 | 0.00 | 0.00 |
June | 1538.32 | 186.95 | 777.59 | 7.10 | 770.49 | 0.00 | 0.00 |
July | 1583.28 | 120.32 | 813.97 | 14.77 | 799.21 | 0.00 | 0.00 |
August | 1767.23 | 179.41 | 957.50 | 114.64 | 842.86 | 0.00 | 0.00 |
September | 1928.38 | 255.02 | 1148.95 | 302.58 | 846.36 | 0.00 | 0.00 |
October | 2882.89 | 483.75 | 1782.88 | 928.64 | 854.25 | 0.00 | 0.00 |
November | 3291.08 | 1004.16 | 2269.58 | 1562.80 | 706.78 | 0.00 | 0.00 |
December | 3316.63 | 1321.54 | 2346.88 | 1685.62 | 661.26 | 0.00 | 0.00 |
Annual Sum or Average | 2236.80 | 698.88 | 1486.68 | 716.44 | 770.24 | 0.00 | 0.00 |
Minimum of Months | 1306.66 | 120.32 | 777.59 | 7.10 | 661.26 | 0.00 | 0.00 |
Maximum of Months | 3316.63 | 1495.64 | 2401.76 | 1713.08 | 854.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 879.56 | 1034.06 | 758.05 | 409.91 | 348.15 | 0.00 | 0.00 |
February | 1035.86 | 878.44 | 858.28 | 434.39 | 423.89 | 0.00 | 0.00 |
March | 1069.28 | 771.01 | 845.98 | 374.51 | 471.47 | 0.00 | 0.00 |
April | 1524.02 | 513.07 | 1050.75 | 483.39 | 567.35 | 0.00 | 0.00 |
May | 1568.82 | 159.38 | 873.75 | 284.61 | 589.14 | 0.00 | 0.00 |
June | 1774.78 | 144.13 | 970.63 | 340.33 | 630.30 | 0.00 | 0.00 |
July | 1624.06 | 97.75 | 886.01 | 245.75 | 640.26 | 0.00 | 0.00 |
August | 1645.07 | 135.40 | 895.89 | 274.24 | 621.65 | 0.00 | 0.00 |
September | 1440.15 | 170.86 | 824.99 | 283.03 | 541.96 | 0.00 | 0.00 |
October | 1405.70 | 317.19 | 844.60 | 364.95 | 479.65 | 0.00 | 0.00 |
November | 975.98 | 673.35 | 723.89 | 363.79 | 360.11 | 0.00 | 0.00 |
December | 851.69 | 892.97 | 696.34 | 370.30 | 326.04 | 0.00 | 0.00 |
Annual Sum or Average | 1317.32 | 480.22 | 851.94 | 351.59 | 500.35 | 0.00 | 0.00 |
Minimum of Months | 851.69 | 97.75 | 696.34 | 245.75 | 326.04 | 0.00 | 0.00 |
Maximum of Months | 1774.78 | 1034.06 | 1050.75 | 483.39 | 640.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.573316E+09 | 0.503195E+10 | 0.111257E+10 | 0.00 | 0.111257E+10 | 0.00 | 0.00 |
February | 0.744441E+09 | 0.384111E+10 | 0.118555E+10 | 0.00 | 0.118555E+10 | 0.00 | 0.00 |
March | 0.127621E+10 | 0.358936E+10 | 0.152269E+10 | 0.00 | 0.152269E+10 | 0.00 | 0.00 |
April | 0.210865E+10 | 0.204667E+10 | 0.173905E+10 | 7046217.03 | 0.173201E+10 | 0.00 | 0.00 |
May | 0.381334E+10 | 0.557759E+09 | 0.203523E+10 | 74116451.92 | 0.196112E+10 | 0.00 | 0.00 |
June | 0.432218E+10 | 0.435476E+09 | 0.223971E+10 | 0.154616E+09 | 0.208509E+10 | 0.00 | 0.00 |
July | 0.437768E+10 | 0.283793E+09 | 0.224611E+10 | 85249883.76 | 0.216086E+10 | 0.00 | 0.00 |
August | 0.402646E+10 | 0.413054E+09 | 0.201161E+10 | 15702936.22 | 0.199591E+10 | 0.00 | 0.00 |
September | 0.310708E+10 | 0.653014E+09 | 0.168162E+10 | 125882.27 | 0.168150E+10 | 0.00 | 0.00 |
October | 0.254144E+10 | 0.131187E+10 | 0.151001E+10 | 0.00 | 0.151001E+10 | 0.00 | 0.00 |
November | 0.978574E+09 | 0.309194E+10 | 0.110936E+10 | 0.00 | 0.110936E+10 | 0.00 | 0.00 |
December | 0.642800E+09 | 0.440850E+10 | 0.103426E+10 | 0.00 | 0.103426E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.285122E+11 | 0.256645E+11 | 0.194278E+11 | 0.336858E+09 | 0.190909E+11 | 0.00 | 0.00 |
Minimum of Months | 0.573316E+09 | 0.283793E+09 | 0.103426E+10 | 0.00 | 0.103426E+10 | 0.00 | 0.00 |
Maximum of Months | 0.437768E+10 | 0.503195E+10 | 0.224611E+10 | 0.154616E+09 | 0.216086E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.193272E+10 | 0.295085E+10 | 0.190887E+10 | 0.971982E+09 | 0.936889E+09 | 0.00 | 0.00 |
February | 0.208762E+10 | 0.222882E+10 | 0.191986E+10 | 0.926816E+09 | 0.993041E+09 | 0.00 | 0.00 |
March | 0.310045E+10 | 0.207800E+10 | 0.250065E+10 | 0.120609E+10 | 0.129455E+10 | 0.00 | 0.00 |
April | 0.382131E+10 | 0.117618E+10 | 0.265554E+10 | 0.120108E+10 | 0.145446E+10 | 0.00 | 0.00 |
May | 0.503763E+10 | 0.336504E+09 | 0.282823E+10 | 0.122635E+10 | 0.160188E+10 | 0.00 | 0.00 |
June | 0.511216E+10 | 0.232536E+09 | 0.277573E+10 | 0.110072E+10 | 0.167501E+10 | 0.00 | 0.00 |
July | 0.514424E+10 | 0.120195E+09 | 0.276544E+10 | 0.101196E+10 | 0.175348E+10 | 0.00 | 0.00 |
August | 0.474202E+10 | 0.182582E+09 | 0.254834E+10 | 0.876145E+09 | 0.167219E+10 | 0.00 | 0.00 |
September | 0.383048E+10 | 0.378251E+09 | 0.218462E+10 | 0.751123E+09 | 0.143350E+10 | 0.00 | 0.00 |
October | 0.367314E+10 | 0.754479E+09 | 0.223073E+10 | 0.941361E+09 | 0.128936E+10 | 0.00 | 0.00 |
November | 0.237419E+10 | 0.176482E+10 | 0.191120E+10 | 0.974940E+09 | 0.936258E+09 | 0.00 | 0.00 |
December | 0.163411E+10 | 0.253889E+10 | 0.155493E+10 | 0.704312E+09 | 0.850613E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424901E+11 | 0.147421E+11 | 0.277841E+11 | 0.118929E+11 | 0.158912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.163411E+10 | 0.120195E+09 | 0.155493E+10 | 0.704312E+09 | 0.850613E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514424E+10 | 0.295085E+10 | 0.282823E+10 | 0.122635E+10 | 0.175348E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.861265E+10 | 0.436589E+10 | 0.643269E+10 | 0.458815E+10 | 0.184454E+10 | 0.00 | 0.00 |
February | 0.694972E+10 | 0.341665E+10 | 0.526840E+10 | 0.341029E+10 | 0.185811E+10 | 0.00 | 0.00 |
March | 0.457137E+10 | 0.338776E+10 | 0.372242E+10 | 0.167931E+10 | 0.204311E+10 | 0.00 | 0.00 |
April | 0.336355E+10 | 0.202465E+10 | 0.266965E+10 | 0.624659E+09 | 0.204499E+10 | 0.00 | 0.00 |
May | 0.388661E+10 | 0.566160E+09 | 0.210789E+10 | 88778041.24 | 0.201911E+10 | 0.00 | 0.00 |
June | 0.401890E+10 | 0.442421E+09 | 0.201548E+10 | 18395173.62 | 0.199708E+10 | 0.00 | 0.00 |
July | 0.428677E+10 | 0.272765E+09 | 0.218010E+10 | 39546903.84 | 0.214055E+10 | 0.00 | 0.00 |
August | 0.476542E+10 | 0.424101E+09 | 0.256451E+10 | 0.307046E+09 | 0.225747E+10 | 0.00 | 0.00 |
September | 0.504744E+10 | 0.674422E+09 | 0.297799E+10 | 0.784274E+09 | 0.219372E+10 | 0.00 | 0.00 |
October | 0.779274E+10 | 0.133211E+10 | 0.477514E+10 | 0.248717E+10 | 0.228796E+10 | 0.00 | 0.00 |
November | 0.853889E+10 | 0.282116E+10 | 0.588258E+10 | 0.405065E+10 | 0.183194E+10 | 0.00 | 0.00 |
December | 0.886400E+10 | 0.391216E+10 | 0.628570E+10 | 0.451461E+10 | 0.177109E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.706980E+11 | 0.236402E+11 | 0.468825E+11 | 0.225929E+11 | 0.242897E+11 | 0.00 | 0.00 |
Minimum of Months | 0.336355E+10 | 0.272765E+09 | 0.201548E+10 | 18395173.62 | 0.177109E+10 | 0.00 | 0.00 |
Maximum of Months | 0.886400E+10 | 0.436589E+10 | 0.643269E+10 | 0.458815E+10 | 0.228796E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.223595E+10 | 0.332576E+10 | 0.203038E+10 | 0.109789E+10 | 0.932487E+09 | 0.00 | 0.00 |
February | 0.237000E+10 | 0.266266E+10 | 0.207636E+10 | 0.105089E+10 | 0.102547E+10 | 0.00 | 0.00 |
March | 0.271122E+10 | 0.261843E+10 | 0.226589E+10 | 0.100310E+10 | 0.126279E+10 | 0.00 | 0.00 |
April | 0.382498E+10 | 0.162383E+10 | 0.272354E+10 | 0.125296E+10 | 0.147059E+10 | 0.00 | 0.00 |
May | 0.417690E+10 | 0.484536E+09 | 0.234025E+10 | 0.762290E+09 | 0.157796E+10 | 0.00 | 0.00 |
June | 0.455930E+10 | 0.420973E+09 | 0.251589E+10 | 0.882139E+09 | 0.163375E+10 | 0.00 | 0.00 |
July | 0.426431E+10 | 0.321310E+09 | 0.237309E+10 | 0.658210E+09 | 0.171488E+10 | 0.00 | 0.00 |
August | 0.429560E+10 | 0.465570E+09 | 0.239957E+10 | 0.734540E+09 | 0.166503E+10 | 0.00 | 0.00 |
September | 0.370233E+10 | 0.537165E+09 | 0.213839E+10 | 0.733617E+09 | 0.140477E+10 | 0.00 | 0.00 |
October | 0.368449E+10 | 0.104001E+10 | 0.226220E+10 | 0.977483E+09 | 0.128471E+10 | 0.00 | 0.00 |
November | 0.236292E+10 | 0.228068E+10 | 0.187634E+10 | 0.942937E+09 | 0.933399E+09 | 0.00 | 0.00 |
December | 0.209700E+10 | 0.318807E+10 | 0.186508E+10 | 0.991811E+09 | 0.873267E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.402850E+11 | 0.189690E+11 | 0.268670E+11 | 0.110879E+11 | 0.157791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.209700E+10 | 0.321310E+09 | 0.186508E+10 | 0.658210E+09 | 0.873267E+09 | 0.00 | 0.00 |
Maximum of Months | 0.455930E+10 | 0.332576E+10 | 0.272354E+10 | 0.125296E+10 | 0.171488E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.670410E+09 | 0.452388E+10 | 0.111259E+10 | 0.00 | 0.111259E+10 | 0.00 | 0.00 |
February | 0.838058E+09 | 0.341307E+10 | 0.118556E+10 | 0.00 | 0.118556E+10 | 0.00 | 0.00 |
March | 0.137908E+10 | 0.322780E+10 | 0.152272E+10 | 0.00 | 0.152272E+10 | 0.00 | 0.00 |
April | 0.217627E+10 | 0.191045E+10 | 0.173908E+10 | 7046427.16 | 0.173203E+10 | 0.00 | 0.00 |
May | 0.384425E+10 | 0.533139E+09 | 0.203527E+10 | 74118662.28 | 0.196115E+10 | 0.00 | 0.00 |
June | 0.435403E+10 | 0.443707E+09 | 0.223975E+10 | 0.154621E+09 | 0.208513E+10 | 0.00 | 0.00 |
July | 0.440680E+10 | 0.303178E+09 | 0.224615E+10 | 85252426.15 | 0.216089E+10 | 0.00 | 0.00 |
August | 0.407492E+10 | 0.427627E+09 | 0.201164E+10 | 15703404.52 | 0.199594E+10 | 0.00 | 0.00 |
September | 0.314613E+10 | 0.590828E+09 | 0.168165E+10 | 125886.02 | 0.168153E+10 | 0.00 | 0.00 |
October | 0.260396E+10 | 0.120064E+10 | 0.151004E+10 | 0.00 | 0.151004E+10 | 0.00 | 0.00 |
November | 0.107649E+10 | 0.273138E+10 | 0.110938E+10 | 0.00 | 0.110938E+10 | 0.00 | 0.00 |
December | 0.752642E+09 | 0.384348E+10 | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.293230E+11 | 0.231492E+11 | 0.194281E+11 | 0.336868E+09 | 0.190912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.670410E+09 | 0.303178E+09 | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.00 | 0.00 |
Maximum of Months | 0.440680E+10 | 0.452388E+10 | 0.224615E+10 | 0.154621E+09 | 0.216089E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199369E+10 | 0.271901E+10 | 0.190886E+10 | 0.971978E+09 | 0.936885E+09 | 0.00 | 0.00 |
February | 0.213740E+10 | 0.205669E+10 | 0.191985E+10 | 0.926812E+09 | 0.993037E+09 | 0.00 | 0.00 |
March | 0.311707E+10 | 0.196594E+10 | 0.250064E+10 | 0.120609E+10 | 0.129455E+10 | 0.00 | 0.00 |
April | 0.379057E+10 | 0.120523E+10 | 0.265553E+10 | 0.120108E+10 | 0.145445E+10 | 0.00 | 0.00 |
May | 0.500187E+10 | 0.348234E+09 | 0.282822E+10 | 0.122634E+10 | 0.160188E+10 | 0.00 | 0.00 |
June | 0.506999E+10 | 0.286165E+09 | 0.277572E+10 | 0.110071E+10 | 0.167500E+10 | 0.00 | 0.00 |
July | 0.507217E+10 | 0.189869E+09 | 0.276543E+10 | 0.101196E+10 | 0.175347E+10 | 0.00 | 0.00 |
August | 0.467840E+10 | 0.270870E+09 | 0.254832E+10 | 0.876141E+09 | 0.167218E+10 | 0.00 | 0.00 |
September | 0.382026E+10 | 0.365367E+09 | 0.218461E+10 | 0.751120E+09 | 0.143349E+10 | 0.00 | 0.00 |
October | 0.366369E+10 | 0.743781E+09 | 0.223072E+10 | 0.941357E+09 | 0.128936E+10 | 0.00 | 0.00 |
November | 0.241258E+10 | 0.164549E+10 | 0.191119E+10 | 0.974936E+09 | 0.936254E+09 | 0.00 | 0.00 |
December | 0.169243E+10 | 0.234350E+10 | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.424501E+11 | 0.141401E+11 | 0.277840E+11 | 0.118928E+11 | 0.158912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.169243E+10 | 0.189869E+09 | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.00 | 0.00 |
Maximum of Months | 0.507217E+10 | 0.271901E+10 | 0.282822E+10 | 0.122634E+10 | 0.175347E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.853124E+10 | 0.430112E+10 | 0.643289E+10 | 0.458830E+10 | 0.184458E+10 | 0.00 | 0.00 |
February | 0.690837E+10 | 0.332795E+10 | 0.526856E+10 | 0.341040E+10 | 0.185815E+10 | 0.00 | 0.00 |
March | 0.457402E+10 | 0.324447E+10 | 0.372252E+10 | 0.167937E+10 | 0.204315E+10 | 0.00 | 0.00 |
April | 0.338907E+10 | 0.197688E+10 | 0.266971E+10 | 0.624679E+09 | 0.204503E+10 | 0.00 | 0.00 |
May | 0.391158E+10 | 0.553662E+09 | 0.210793E+10 | 88780949.09 | 0.201915E+10 | 0.00 | 0.00 |
June | 0.404742E+10 | 0.457868E+09 | 0.201551E+10 | 18395776.14 | 0.199712E+10 | 0.00 | 0.00 |
July | 0.431393E+10 | 0.298497E+09 | 0.218014E+10 | 39548199.17 | 0.214059E+10 | 0.00 | 0.00 |
August | 0.479166E+10 | 0.459456E+09 | 0.256457E+10 | 0.307056E+09 | 0.225752E+10 | 0.00 | 0.00 |
September | 0.504644E+10 | 0.650305E+09 | 0.297807E+10 | 0.784300E+09 | 0.219377E+10 | 0.00 | 0.00 |
October | 0.775005E+10 | 0.132781E+10 | 0.477527E+10 | 0.248726E+10 | 0.228802E+10 | 0.00 | 0.00 |
November | 0.849118E+10 | 0.275528E+10 | 0.588276E+10 | 0.405078E+10 | 0.183198E+10 | 0.00 | 0.00 |
December | 0.881957E+10 | 0.379042E+10 | 0.628589E+10 | 0.451475E+10 | 0.177113E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.705745E+11 | 0.231437E+11 | 0.468838E+11 | 0.225936E+11 | 0.242902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.338907E+10 | 0.298497E+09 | 0.201551E+10 | 18395776.14 | 0.177113E+10 | 0.00 | 0.00 |
Maximum of Months | 0.881957E+10 | 0.430112E+10 | 0.643289E+10 | 0.458830E+10 | 0.228802E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.232409E+10 | 0.295626E+10 | 0.203037E+10 | 0.109789E+10 | 0.932483E+09 | 0.00 | 0.00 |
February | 0.248255E+10 | 0.227077E+10 | 0.207635E+10 | 0.105089E+10 | 0.102546E+10 | 0.00 | 0.00 |
March | 0.285068E+10 | 0.217441E+10 | 0.226588E+10 | 0.100309E+10 | 0.126278E+10 | 0.00 | 0.00 |
April | 0.395836E+10 | 0.137104E+10 | 0.272353E+10 | 0.125295E+10 | 0.147058E+10 | 0.00 | 0.00 |
May | 0.423073E+10 | 0.421303E+09 | 0.234024E+10 | 0.762287E+09 | 0.157795E+10 | 0.00 | 0.00 |
June | 0.463637E+10 | 0.364472E+09 | 0.251588E+10 | 0.882135E+09 | 0.163375E+10 | 0.00 | 0.00 |
July | 0.439009E+10 | 0.253958E+09 | 0.237308E+10 | 0.658207E+09 | 0.171488E+10 | 0.00 | 0.00 |
August | 0.443965E+10 | 0.355409E+09 | 0.239956E+10 | 0.734537E+09 | 0.166502E+10 | 0.00 | 0.00 |
September | 0.375728E+10 | 0.441685E+09 | 0.213838E+10 | 0.733614E+09 | 0.140477E+10 | 0.00 | 0.00 |
October | 0.377819E+10 | 0.874310E+09 | 0.226219E+10 | 0.977479E+09 | 0.128471E+10 | 0.00 | 0.00 |
November | 0.250789E+10 | 0.185477E+10 | 0.187633E+10 | 0.942933E+09 | 0.933395E+09 | 0.00 | 0.00 |
December | 0.225580E+10 | 0.254986E+10 | 0.186507E+10 | 0.991807E+09 | 0.873263E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.416117E+11 | 0.158882E+11 | 0.268669E+11 | 0.110878E+11 | 0.157790E+11 | 0.00 | 0.00 |
Minimum of Months | 0.225580E+10 | 0.253958E+09 | 0.186507E+10 | 0.658207E+09 | 0.873263E+09 | 0.00 | 0.00 |
Maximum of Months | 0.463637E+10 | 0.295626E+10 | 0.272353E+10 | 0.125295E+10 | 0.171488E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.740319E+09 | 0.414664E+10 | 0.111259E+10 | 0.00 | 0.111259E+10 | 0.00 | 0.00 |
February | 0.888130E+09 | 0.312546E+10 | 0.118556E+10 | 0.00 | 0.118556E+10 | 0.00 | 0.00 |
March | 0.141934E+10 | 0.301869E+10 | 0.152272E+10 | 0.00 | 0.152272E+10 | 0.00 | 0.00 |
April | 0.217196E+10 | 0.184436E+10 | 0.173908E+10 | 7046427.16 | 0.173203E+10 | 0.00 | 0.00 |
May | 0.378542E+10 | 0.555407E+09 | 0.203527E+10 | 74118662.28 | 0.196115E+10 | 0.00 | 0.00 |
June | 0.428413E+10 | 0.470051E+09 | 0.223975E+10 | 0.154621E+09 | 0.208513E+10 | 0.00 | 0.00 |
July | 0.432669E+10 | 0.329079E+09 | 0.224615E+10 | 85252426.15 | 0.216089E+10 | 0.00 | 0.00 |
August | 0.401091E+10 | 0.449639E+09 | 0.201164E+10 | 15703404.52 | 0.199594E+10 | 0.00 | 0.00 |
September | 0.309153E+10 | 0.601844E+09 | 0.168165E+10 | 125886.02 | 0.168153E+10 | 0.00 | 0.00 |
October | 0.258015E+10 | 0.116153E+10 | 0.151004E+10 | 0.00 | 0.151004E+10 | 0.00 | 0.00 |
November | 0.112690E+10 | 0.251629E+10 | 0.110938E+10 | 0.00 | 0.110938E+10 | 0.00 | 0.00 |
December | 0.808706E+09 | 0.352751E+10 | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.292342E+11 | 0.217465E+11 | 0.194281E+11 | 0.336868E+09 | 0.190912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.740319E+09 | 0.329079E+09 | 0.103428E+10 | 0.00 | 0.103428E+10 | 0.00 | 0.00 |
Maximum of Months | 0.432669E+10 | 0.414664E+10 | 0.224615E+10 | 0.154621E+09 | 0.216089E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.206084E+10 | 0.253281E+10 | 0.190886E+10 | 0.971978E+09 | 0.936885E+09 | 0.00 | 0.00 |
February | 0.218427E+10 | 0.191874E+10 | 0.191985E+10 | 0.926812E+09 | 0.993037E+09 | 0.00 | 0.00 |
March | 0.313562E+10 | 0.187709E+10 | 0.250064E+10 | 0.120609E+10 | 0.129455E+10 | 0.00 | 0.00 |
April | 0.377520E+10 | 0.118516E+10 | 0.265553E+10 | 0.120108E+10 | 0.145445E+10 | 0.00 | 0.00 |
May | 0.495212E+10 | 0.366509E+09 | 0.282822E+10 | 0.122634E+10 | 0.160188E+10 | 0.00 | 0.00 |
June | 0.501692E+10 | 0.307591E+09 | 0.277572E+10 | 0.110071E+10 | 0.167500E+10 | 0.00 | 0.00 |
July | 0.501229E+10 | 0.208305E+09 | 0.276543E+10 | 0.101196E+10 | 0.175347E+10 | 0.00 | 0.00 |
August | 0.462764E+10 | 0.289248E+09 | 0.254832E+10 | 0.876141E+09 | 0.167218E+10 | 0.00 | 0.00 |
September | 0.377512E+10 | 0.380731E+09 | 0.218461E+10 | 0.751120E+09 | 0.143349E+10 | 0.00 | 0.00 |
October | 0.363611E+10 | 0.733454E+09 | 0.223072E+10 | 0.941357E+09 | 0.128936E+10 | 0.00 | 0.00 |
November | 0.244451E+10 | 0.155568E+10 | 0.191119E+10 | 0.974936E+09 | 0.936254E+09 | 0.00 | 0.00 |
December | 0.173472E+10 | 0.219784E+10 | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.423554E+11 | 0.135532E+11 | 0.277840E+11 | 0.118928E+11 | 0.158912E+11 | 0.00 | 0.00 |
Minimum of Months | 0.173472E+10 | 0.208305E+09 | 0.155492E+10 | 0.704309E+09 | 0.850609E+09 | 0.00 | 0.00 |
Maximum of Months | 0.501692E+10 | 0.253281E+10 | 0.282822E+10 | 0.122634E+10 | 0.175347E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.861566E+10 | 0.400591E+10 | 0.643289E+10 | 0.458830E+10 | 0.184458E+10 | 0.00 | 0.00 |
February | 0.697641E+10 | 0.309807E+10 | 0.526856E+10 | 0.341040E+10 | 0.185815E+10 | 0.00 | 0.00 |
March | 0.460595E+10 | 0.306024E+10 | 0.372252E+10 | 0.167937E+10 | 0.204315E+10 | 0.00 | 0.00 |
April | 0.338687E+10 | 0.191493E+10 | 0.266971E+10 | 0.624679E+09 | 0.204503E+10 | 0.00 | 0.00 |
May | 0.385993E+10 | 0.574294E+09 | 0.210793E+10 | 88780949.09 | 0.201915E+10 | 0.00 | 0.00 |
June | 0.398733E+10 | 0.484568E+09 | 0.201551E+10 | 18395776.14 | 0.199712E+10 | 0.00 | 0.00 |
July | 0.424065E+10 | 0.322269E+09 | 0.218014E+10 | 39548199.17 | 0.214059E+10 | 0.00 | 0.00 |
August | 0.473334E+10 | 0.480523E+09 | 0.256457E+10 | 0.307056E+09 | 0.225752E+10 | 0.00 | 0.00 |
September | 0.499836E+10 | 0.661016E+09 | 0.297807E+10 | 0.784300E+09 | 0.219377E+10 | 0.00 | 0.00 |
October | 0.772154E+10 | 0.129567E+10 | 0.477527E+10 | 0.248726E+10 | 0.228802E+10 | 0.00 | 0.00 |
November | 0.853048E+10 | 0.260278E+10 | 0.588276E+10 | 0.405078E+10 | 0.183198E+10 | 0.00 | 0.00 |
December | 0.888326E+10 | 0.353961E+10 | 0.628589E+10 | 0.451475E+10 | 0.177113E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.705398E+11 | 0.220399E+11 | 0.468838E+11 | 0.225936E+11 | 0.242902E+11 | 0.00 | 0.00 |
Minimum of Months | 0.338687E+10 | 0.322269E+09 | 0.201551E+10 | 18395776.14 | 0.177113E+10 | 0.00 | 0.00 |
Maximum of Months | 0.888326E+10 | 0.400591E+10 | 0.643289E+10 | 0.458830E+10 | 0.228802E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.235581E+10 | 0.276963E+10 | 0.203037E+10 | 0.109789E+10 | 0.932483E+09 | 0.00 | 0.00 |
February | 0.250594E+10 | 0.212512E+10 | 0.207635E+10 | 0.105089E+10 | 0.102546E+10 | 0.00 | 0.00 |
March | 0.286395E+10 | 0.206507E+10 | 0.226588E+10 | 0.100309E+10 | 0.126278E+10 | 0.00 | 0.00 |
April | 0.395027E+10 | 0.132987E+10 | 0.272353E+10 | 0.125295E+10 | 0.147058E+10 | 0.00 | 0.00 |
May | 0.420193E+10 | 0.426872E+09 | 0.234024E+10 | 0.762287E+09 | 0.157795E+10 | 0.00 | 0.00 |
June | 0.460023E+10 | 0.373587E+09 | 0.251588E+10 | 0.882135E+09 | 0.163375E+10 | 0.00 | 0.00 |
July | 0.434988E+10 | 0.261817E+09 | 0.237308E+10 | 0.658207E+09 | 0.171488E+10 | 0.00 | 0.00 |
August | 0.440615E+10 | 0.362662E+09 | 0.239956E+10 | 0.734537E+09 | 0.166502E+10 | 0.00 | 0.00 |
September | 0.373286E+10 | 0.442878E+09 | 0.213838E+10 | 0.733614E+09 | 0.140477E+10 | 0.00 | 0.00 |
October | 0.376504E+10 | 0.849549E+09 | 0.226219E+10 | 0.977479E+09 | 0.128471E+10 | 0.00 | 0.00 |
November | 0.252974E+10 | 0.174533E+10 | 0.187633E+10 | 0.942933E+09 | 0.933395E+09 | 0.00 | 0.00 |
December | 0.228117E+10 | 0.239173E+10 | 0.186507E+10 | 0.991807E+09 | 0.873263E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.415430E+11 | 0.151441E+11 | 0.268669E+11 | 0.110878E+11 | 0.157790E+11 | 0.00 | 0.00 |
Minimum of Months | 0.228117E+10 | 0.261817E+09 | 0.186507E+10 | 0.658207E+09 | 0.873263E+09 | 0.00 | 0.00 |
Maximum of Months | 0.460023E+10 | 0.276963E+10 | 0.272353E+10 | 0.125295E+10 | 0.171488E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.57 | 11.01 | 8.64 | 3.24 | 3.12 | 48.31 | 209.17 | 0.01 |
February | 15.49 | 12.82 | 10.40 | 2.82 | 4.36 | 58.07 | 218.23 | 0.02 |
March | 17.07 | 13.57 | 10.72 | 3.68 | 7.24 | 76.61 | 186.08 | 0.03 |
April | 21.23 | 17.53 | 15.23 | 2.65 | 11.47 | 90.28 | 216.86 | 0.02 |
May | 26.90 | 22.81 | 21.10 | 3.11 | 19.64 | 106.10 | 173.47 | 0.04 |
June | 27.61 | 23.36 | 21.62 | 2.44 | 19.77 | 115.40 | 187.69 | 0.03 |
July | 27.94 | 24.58 | 23.34 | 2.53 | 20.70 | 123.49 | 154.05 | 0.05 |
August | 27.43 | 23.89 | 22.52 | 3.20 | 20.40 | 118.51 | 145.78 | 0.03 |
September | 26.23 | 23.37 | 22.24 | 3.39 | 19.01 | 101.73 | 135.58 | 0.05 |
October | 24.23 | 20.46 | 18.40 | 4.11 | 16.60 | 78.24 | 178.15 | 0.01 |
November | 18.91 | 15.31 | 12.62 | 2.63 | 7.99 | 49.56 | 205.43 | 0.01 |
December | 15.68 | 12.87 | 10.53 | 3.17 | 6.00 | 45.08 | 191.18 | 0.02 |
Annual Sum or Average | 21.89 | 18.50 | 16.48 | 3.09 | 13.08 | 84.44 | 183.16 | 0.03 |
Minimum of Months | 13.57 | 11.01 | 8.64 | 2.44 | 3.12 | 45.08 | 135.58 | 0.01 |
Maximum of Months | 27.94 | 24.58 | 23.34 | 4.11 | 20.70 | 123.49 | 218.23 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 27.00 | 02-JAN-14:00 | 18.65 | 14.00 | 1.50 | 17.75 | 146.50 | 0.00 |
February | 28.30 | 02-FEB-12:00 | 20.77 | 17.20 | 6.60 | 17.93 | 127.50 | 748.50 |
March | 30.00 | 26-MAR-13:00 | 19.86 | 14.40 | 3.00 | 19.52 | 288.50 | 548.00 |
April | 33.30 | 28-APR-14:00 | 23.04 | 18.80 | 4.10 | 23.15 | 150.50 | 762.50 |
May | 33.90 | 07-MAY-13:00 | 23.75 | 19.40 | 4.10 | 23.15 | 287.50 | 507.50 |
June | 35.00 | 14-JUN-13:00 | 23.93 | 19.40 | 2.10 | 24.16 | 194.50 | 712.50 |
July | 36.10 | 21-JUL-15:00 | 25.95 | 22.20 | 1.50 | 26.65 | 216.00 | 245.00 |
August | 36.30 | 30-AUG-15:00 | 23.72 | 18.50 | 2.40 | 25.33 | 116.00 | 698.50 |
September | 36.40 | 09-SEP-16:00 | 26.63 | 23.40 | 4.40 | 26.48 | 114.00 | 401.50 |
October | 34.00 | 05-OCT-14:00 | 24.03 | 20.00 | 2.60 | 29.55 | 169.50 | 606.00 |
November | 30.00 | 01-NOV-13:00 | 25.01 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 30.00 | 13-DEC-14:00 | 21.82 | 18.00 | 3.10 | 20.92 | 101.50 | 682.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 27.00 | 18.65 | 14.00 | 1.50 | 17.75 | 101.50 | 0.00 | |
Maximum of Months | 36.40 | 26.63 | 23.40 | 6.60 | 29.55 | 288.50 | 762.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 0.00 | 05-JAN-05:00 | -0.0 | -0.0 | 2.10 | -16.0 | 0.00 | 0.00 |
February | -3.4 | 05-FEB-07:10 | -5.2 | -9.4 | 4.68 | -21.3 | 0.00 | 0.00 |
March | 1.10 | 09-MAR-05:00 | -1.8 | -7.3 | 3.60 | -14.4 | 0.00 | 0.00 |
April | 8.30 | 11-APR-05:00 | 6.94 | 5.50 | 0.00 | -6.9 | 0.00 | 0.00 |
May | 21.10 | 07-MAY-00:00 | 19.57 | 18.90 | 0.00 | 11.46 | 0.00 | 0.00 |
June | 20.60 | 07-JUN-01:00 | 17.99 | 16.70 | 3.60 | 10.50 | 0.00 | 0.00 |
July | 22.20 | 11-JUL-19:00 | 21.37 | 21.10 | 2.10 | 20.22 | 0.00 | 0.00 |
August | 20.20 | 25-AUG-23:00 | 20.20 | 20.20 | 5.30 | 11.84 | 0.00 | 0.00 |
September | 19.20 | 07-SEP-17:00 | 19.20 | 19.20 | 2.50 | 16.85 | 35.00 | 7.00 |
October | 10.00 | 28-OCT-04:00 | 5.55 | 0.00 | 3.60 | -0.1 | 0.00 | 0.00 |
November | 7.20 | 12-NOV-07:49 | 4.11 | 0.18 | 4.60 | -9.0 | 36.00 | 517.00 |
December | 0.00 | 21-DEC-04:00 | -0.8 | -2.0 | 2.10 | -16.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -3.4 | -5.2 | -9.4 | 0.00 | -21.3 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 21.37 | 21.10 | 5.30 | 20.22 | 36.00 | 517.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 22.10 | 31-JAN-12:00 | 25.00 | 21.00 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 21.48 | 24-FEB-12:00 | 27.70 | 18.80 | 4.10 | 17.75 | 165.00 | 746.50 |
March | 22.76 | 30-MAR-12:00 | 29.40 | 20.00 | 2.50 | 27.14 | 340.00 | 0.00 |
April | 25.54 | 28-APR-15:00 | 32.20 | 23.30 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 25.83 | 27-MAY-13:00 | 31.70 | 23.90 | 3.10 | 22.13 | 168.50 | 735.50 |
June | 26.52 | 29-JUN-16:00 | 29.40 | 25.60 | 1.50 | 26.32 | 164.00 | 36.00 |
July | 27.16 | 22-JUL-10:00 | 32.20 | 25.60 | 2.10 | 21.96 | 191.00 | 719.50 |
August | 27.24 | 07-AUG-12:00 | 31.00 | 26.00 | 3.10 | 27.95 | 473.00 | 200.00 |
September | 27.78 | 10-SEP-12:00 | 35.00 | 25.50 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.18 | 07-OCT-07:00 | 29.00 | 28.00 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 25.01 | 01-NOV-13:00 | 30.00 | 23.30 | 2.00 | 26.48 | 216.50 | 118.00 |
December | 24.12 | 12-DEC-13:00 | 27.00 | 23.00 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 21.48 | 25.00 | 18.80 | 1.50 | 17.75 | 95.00 | 0.00 | |
Maximum of Months | 28.18 | 35.00 | 28.00 | 5.70 | 27.95 | 473.00 | 746.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 31-JAN-12:00 | 25.00 | 22.10 | 5.70 | 20.92 | 336.50 | 96.00 |
February | 20.20 | 02-FEB-22:00 | 21.50 | 20.56 | 4.80 | 14.65 | 0.00 | 0.00 |
March | 21.10 | 07-MAR-08:00 | 23.30 | 21.69 | 2.00 | 13.91 | 126.00 | 566.50 |
April | 23.30 | 28-APR-15:00 | 32.20 | 25.54 | 3.60 | 22.47 | 156.00 | 575.50 |
May | 24.40 | 26-MAY-08:20 | 27.07 | 25.08 | 3.10 | 23.71 | 252.67 | 47.33 |
June | 25.60 | 29-JUN-14:00 | 27.20 | 26.00 | 5.10 | 24.16 | 335.00 | 238.00 |
July | 25.60 | 02-JUL-05:00 | 26.10 | 25.71 | 2.60 | 19.52 | 30.50 | 8.50 |
August | 26.60 | 09-AUG-18:00 | 26.60 | 26.60 | 1.90 | 19.52 | 26.00 | 23.00 |
September | 25.50 | 10-SEP-12:00 | 35.00 | 27.78 | 2.90 | 24.66 | 239.50 | 662.00 |
October | 28.00 | 07-OCT-07:00 | 29.00 | 28.18 | 2.60 | 21.09 | 95.00 | 500.50 |
November | 23.80 | 01-NOV-10:00 | 26.10 | 24.39 | 2.00 | 22.64 | 228.50 | 113.00 |
December | 23.00 | 12-DEC-13:00 | 27.00 | 24.12 | 2.10 | 19.17 | 160.50 | 599.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.20 | 21.50 | 20.56 | 1.90 | 13.91 | 0.00 | 0.00 | |
Maximum of Months | 28.00 | 35.00 | 28.18 | 5.70 | 24.66 | 336.50 | 662.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 20.46 | 29.60 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 20.78 | 36.65 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 22.23 | 38.94 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 24.49 | 49.11 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 26.95 | 46.95 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 28.93 | 51.71 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 29.89 | 48.43 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 29.58 | 45.50 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 28.08 | 39.22 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 25.80 | 37.51 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 23.35 | 31.26 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 21.40 | 27.18 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 25.18 | 40.17 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 20.46 | 27.18 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 29.89 | 51.71 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.209592E+11 | -.307969E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.125205E+10 | 66.62 | 0.00 | 0.00 |
February | 0.188677E+11 | -.277652E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.112388E+10 | 66.34 | 0.00 | 0.00 |
March | 0.215677E+11 | -.314091E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122474E+10 | 65.57 | 0.00 | 0.00 |
April | 0.170711E+11 | -.267584E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.120838E+10 | 66.47 | 0.00 | 0.00 |
May | 0.165231E+11 | -.265812E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.125624E+10 | 66.71 | 0.00 | 0.00 |
June | 0.149409E+11 | -.247386E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.120856E+10 | 66.42 | 0.00 | 0.00 |
July | 0.125750E+11 | -.227983E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.128233E+10 | 67.71 | 0.00 | 0.00 |
August | 0.150641E+11 | -.252084E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124831E+10 | 66.46 | 0.00 | 0.00 |
September | 0.142311E+11 | -.240467E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122077E+10 | 66.98 | 0.00 | 0.00 |
October | 0.165467E+11 | -.265895E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.126494E+10 | 67.14 | 0.00 | 0.00 |
November | 0.183756E+11 | -.279787E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.122155E+10 | 67.05 | 0.00 | 0.00 |
December | 0.194309E+11 | -.293486E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124920E+10 | 66.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.206153E+12 | -.324020E+12 | 8760.00 | -.147609E+11 | 66.67 | |||||
Minimum of Months | 0.125750E+11 | -.314091E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.128233E+10 | 65.57 | 0.00 | 0.00 |
Maximum of Months | 0.215677E+11 | -.227983E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.112388E+10 | 67.71 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.75 | 0.73 | 01-JAN-07:00 | 6710.44 | 34.60 | 279.17 | 288.33 | 1113.92 | 24.97 | 165.83 | 270.67 |
February | 295.50 | 0.74 | 0.73 | 01-FEB-11:39 | 2772.26 | 26.51 | 165.17 | 272.33 | 954.74 | 21.93 | 104.17 | 257.17 |
March | 296.00 | 0.74 | 0.73 | 02-MAR-12:39 | 1215.62 | 16.82 | 0.00 | 306.33 | 704.54 | 19.73 | 47.17 | 258.17 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:30 | 964.36 | 15.97 | 0.00 | 309.50 | 553.92 | 18.82 | 18.00 | 258.83 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-06:00 | 863.21 | 16.09 | 0.00 | 332.17 | 484.81 | 19.02 | 4.67 | 266.67 |
June | 394.00 | 0.75 | 0.73 | 01-JUN-06:40 | 818.72 | 15.72 | 0.00 | 332.33 | 462.89 | 18.64 | 1.17 | 267.00 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:40 | 909.32 | 16.16 | 0.00 | 345.00 | 497.26 | 19.05 | 9.00 | 279.83 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-06:00 | 1061.43 | 16.55 | 0.00 | 335.00 | 567.46 | 19.41 | 33.50 | 281.67 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:00 | 1255.87 | 16.93 | 3.67 | 305.83 | 658.38 | 19.67 | 88.83 | 261.00 |
October | 330.00 | 0.74 | 0.73 | 01-OCT-06:00 | 2248.20 | 21.45 | 80.33 | 307.00 | 888.36 | 20.89 | 142.17 | 271.17 |
November | 308.00 | 0.74 | 0.73 | 01-NOV-07:49 | 6829.37 | 35.39 | 293.83 | 282.00 | 1061.95 | 22.95 | 129.17 | 262.00 |
December | 282.83 | 0.74 | 0.73 | 01-DEC-07:49 | 6813.44 | 35.13 | 260.50 | 275.83 | 1454.54 | 26.95 | 166.83 | 258.83 |
Annual Sum or Average | 4027.67 | 0.74 | 2523.84 | 21.65 | 1082.67 | 3691.67 | 756.32 | 20.79 | 910.50 | 3193.00 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 818.72 | 15.72 | 0.00 | 272.33 | 462.89 | 18.64 | 1.17 | 257.17 | |
Maximum of Months | 394.00 | 0.75 | 0.73 | 6829.37 | 35.39 | 293.83 | 345.00 | 1454.54 | 26.95 | 166.83 | 281.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.76 | 0.73 | 01-JAN-07:49 | 1567.86 | 17.07 | 81.17 | 238.00 | 804.43 | 16.46 | 53.33 | 174.67 |
February | 295.50 | 0.75 | 0.73 | 01-FEB-11:39 | 1732.25 | 16.81 | 71.67 | 237.17 | 942.65 | 17.84 | 62.00 | 192.00 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 1818.72 | 15.04 | 48.50 | 294.33 | 927.23 | 13.40 | 0.00 | 230.83 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:10 | 1847.62 | 11.49 | 0.00 | 305.50 | 993.81 | 12.85 | 0.00 | 259.17 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-06:40 | 2067.45 | 12.16 | 0.00 | 339.67 | 817.58 | 13.33 | 0.00 | 278.33 |
June | 394.00 | 0.74 | 0.73 | 01-JUN-06:10 | 1932.24 | 12.20 | 0.00 | 340.33 | 772.39 | 13.26 | 0.00 | 282.33 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:10 | 1805.88 | 12.56 | 0.00 | 347.33 | 765.52 | 13.52 | 0.00 | 285.33 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-06:49 | 1666.44 | 12.54 | 0.00 | 331.17 | 873.22 | 13.59 | 0.00 | 280.17 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:49 | 1597.15 | 12.73 | 5.67 | 296.00 | 815.09 | 13.80 | 3.67 | 246.50 |
October | 330.00 | 0.75 | 0.73 | 01-OCT-06:49 | 1660.08 | 17.12 | 75.33 | 283.50 | 828.59 | 16.69 | 46.50 | 238.17 |
November | 308.00 | 0.75 | 0.73 | 01-NOV-07:49 | 1265.57 | 15.58 | 56.83 | 236.67 | 704.06 | 16.96 | 53.33 | 189.83 |
December | 282.83 | 0.76 | 0.73 | 01-DEC-07:49 | 1484.04 | 17.34 | 75.50 | 225.67 | 804.18 | 17.83 | 59.67 | 167.00 |
Annual Sum or Average | 4027.67 | 0.75 | 1715.41 | 14.19 | 414.67 | 3475.33 | 835.88 | 14.81 | 278.50 | 2824.33 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 1265.57 | 11.49 | 0.00 | 225.67 | 704.06 | 12.85 | 0.00 | 167.00 | |
Maximum of Months | 394.00 | 0.76 | 0.73 | 2067.45 | 17.34 | 81.17 | 347.33 | 993.81 | 17.84 | 62.00 | 285.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.77 | 0.73 | 01-JAN-08:50 | 401.58 | 0.00 | 0.00 | 194.83 | 265.75 | 0.00 | 0.00 | 54.50 |
February | 295.50 | 0.76 | 0.73 | 01-FEB-11:39 | 463.65 | 0.00 | 0.00 | 215.83 | 307.75 | 0.00 | 0.00 | 112.33 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 548.12 | 0.00 | 0.00 | 281.83 | 349.30 | 0.00 | 0.00 | 157.33 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:30 | 658.39 | 0.00 | 0.00 | 313.83 | 404.41 | 0.00 | 0.00 | 241.17 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-06:49 | 815.54 | 0.00 | 0.00 | 353.67 | 473.62 | 0.00 | 0.00 | 294.50 |
June | 394.00 | 0.74 | 0.73 | 01-JUN-06:19 | 954.60 | 0.00 | 0.00 | 362.50 | 502.05 | 0.00 | 0.00 | 314.50 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:19 | 936.71 | 0.00 | 0.00 | 364.00 | 507.35 | 0.00 | 0.00 | 313.67 |
August | 380.83 | 0.74 | 0.73 | 01-AUG-06:00 | 817.78 | 0.00 | 0.00 | 342.50 | 459.65 | 0.00 | 0.00 | 286.83 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:00 | 681.55 | 0.00 | 0.00 | 301.00 | 393.15 | 0.00 | 0.00 | 215.50 |
October | 330.00 | 0.75 | 0.73 | 01-OCT-07:19 | 577.85 | 0.00 | 0.00 | 278.33 | 358.24 | 0.00 | 0.00 | 189.00 |
November | 308.00 | 0.76 | 0.73 | 01-NOV-08:30 | 411.86 | 0.00 | 0.00 | 199.17 | 274.34 | 0.00 | 0.00 | 61.33 |
December | 282.83 | 0.76 | 0.73 | 01-DEC-08:30 | 400.69 | 0.00 | 0.00 | 190.50 | 267.21 | 0.00 | 0.00 | 41.67 |
Annual Sum or Average | 4027.67 | 0.75 | 659.62 | 0.00 | 0.00 | 3398.00 | 389.19 | 0.00 | 0.00 | 2282.33 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 400.69 | 0.00 | 0.00 | 190.50 | 265.75 | 0.00 | 0.00 | 41.67 | |
Maximum of Months | 394.00 | 0.77 | 0.73 | 954.60 | 0.00 | 0.00 | 364.00 | 507.35 | 0.00 | 0.00 | 314.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.76 | 0.73 | 01-JAN-08:50 | 1767.18 | 17.50 | 83.67 | 245.33 | 1036.58 | 19.03 | 80.17 | 183.33 |
February | 295.50 | 0.75 | 0.73 | 01-FEB-11:39 | 1612.12 | 17.54 | 77.83 | 245.33 | 819.90 | 16.83 | 50.00 | 200.17 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 1727.65 | 14.61 | 45.33 | 289.33 | 868.45 | 13.25 | 0.00 | 223.33 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:49 | 1943.64 | 11.59 | 0.00 | 305.83 | 1033.90 | 12.97 | 0.00 | 263.83 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-07:30 | 1594.04 | 12.20 | 0.00 | 334.50 | 694.57 | 13.38 | 0.00 | 276.33 |
June | 394.00 | 0.75 | 0.73 | 01-JUN-06:00 | 1746.75 | 12.13 | 0.00 | 339.83 | 705.53 | 13.20 | 0.00 | 283.50 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:49 | 1602.02 | 12.53 | 0.00 | 347.83 | 682.08 | 13.50 | 0.00 | 286.17 |
August | 380.83 | 0.74 | 0.73 | 01-AUG-07:10 | 1620.83 | 12.61 | 0.00 | 331.83 | 727.36 | 13.68 | 0.00 | 279.67 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-07:30 | 1510.06 | 12.66 | 5.50 | 296.50 | 752.79 | 13.60 | 0.00 | 246.17 |
October | 330.00 | 0.74 | 0.73 | 01-OCT-07:40 | 1916.15 | 17.71 | 83.17 | 287.50 | 789.15 | 15.07 | 9.67 | 241.17 |
November | 308.00 | 0.75 | 0.73 | 01-NOV-08:00 | 1560.61 | 17.22 | 79.50 | 241.17 | 848.83 | 17.78 | 63.00 | 186.67 |
December | 282.83 | 0.75 | 0.73 | 01-DEC-08:39 | 1675.32 | 18.66 | 84.83 | 243.00 | 870.12 | 18.09 | 58.83 | 173.67 |
Annual Sum or Average | 4027.67 | 0.75 | 1689.20 | 14.51 | 459.83 | 3508.00 | 811.69 | 14.87 | 261.67 | 2844.00 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 1510.06 | 11.59 | 0.00 | 241.17 | 682.08 | 12.97 | 0.00 | 173.67 | |
Maximum of Months | 394.00 | 0.76 | 0.73 | 1943.64 | 18.66 | 84.83 | 347.83 | 1036.58 | 19.03 | 80.17 | 286.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.75 | 0.73 | 01-JAN-07:00 | 6700.89 | 33.91 | 278.83 | 287.50 | 1155.04 | 20.82 | 92.17 | 271.50 |
February | 295.50 | 0.74 | 0.73 | 01-FEB-11:39 | 2761.04 | 23.17 | 165.17 | 272.17 | 992.42 | 17.72 | 36.33 | 259.17 |
March | 296.00 | 0.74 | 0.73 | 02-MAR-12:39 | 1202.72 | 10.94 | 0.00 | 305.17 | 731.13 | 15.88 | 0.00 | 260.33 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:30 | 950.32 | 10.50 | 0.00 | 308.00 | 572.21 | 15.22 | 0.00 | 262.67 |
May | 353.67 | 0.75 | 0.73 | 01-MAY-06:00 | 847.19 | 10.49 | 0.00 | 330.33 | 498.93 | 15.30 | 0.00 | 270.67 |
June | 394.00 | 0.75 | 0.73 | 01-JUN-06:40 | 803.45 | 10.16 | 0.00 | 331.00 | 476.32 | 14.92 | 0.00 | 272.17 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:40 | 891.05 | 10.42 | 0.00 | 342.83 | 511.33 | 15.16 | 0.00 | 284.00 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-06:00 | 1039.52 | 10.82 | 0.00 | 332.67 | 583.71 | 15.50 | 0.00 | 285.67 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:00 | 1228.45 | 11.10 | 3.67 | 304.67 | 677.70 | 15.59 | 0.00 | 263.00 |
October | 330.00 | 0.74 | 0.73 | 01-OCT-06:00 | 2217.89 | 16.31 | 77.17 | 305.83 | 923.83 | 16.91 | 10.33 | 273.50 |
November | 308.00 | 0.74 | 0.73 | 01-NOV-07:49 | 6780.48 | 33.51 | 279.00 | 278.00 | 1132.03 | 20.62 | 90.83 | 269.33 |
December | 282.83 | 0.74 | 0.73 | 01-DEC-07:00 | 6755.99 | 33.16 | 248.83 | 272.17 | 1496.99 | 23.14 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.75 | 2500.80 | 17.11 | 1052.67 | 3670.33 | 784.09 | 17.02 | 340.50 | 3231.50 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 803.45 | 10.16 | 0.00 | 272.17 | 476.32 | 14.92 | 0.00 | 259.17 | |
Maximum of Months | 394.00 | 0.75 | 0.73 | 6780.48 | 33.91 | 279.00 | 342.83 | 1496.99 | 23.14 | 110.83 | 285.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.76 | 0.73 | 01-JAN-07:49 | 1567.15 | 15.09 | 81.33 | 237.67 | 823.67 | 14.59 | 53.33 | 180.33 |
February | 295.50 | 0.75 | 0.73 | 01-FEB-11:39 | 1732.77 | 14.60 | 71.67 | 236.83 | 964.46 | 16.09 | 62.17 | 197.33 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 1609.30 | 12.32 | 48.50 | 293.83 | 954.70 | 10.86 | 0.00 | 237.00 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:10 | 1838.97 | 8.14 | 0.00 | 304.17 | 1017.93 | 10.52 | 0.00 | 263.50 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-06:40 | 2050.70 | 8.64 | 0.00 | 339.50 | 843.50 | 11.02 | 0.00 | 284.67 |
June | 394.00 | 0.74 | 0.73 | 01-JUN-06:10 | 1843.28 | 8.80 | 0.00 | 338.83 | 795.99 | 11.07 | 0.00 | 287.83 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:19 | 1791.01 | 9.14 | 0.00 | 346.00 | 788.68 | 11.31 | 0.00 | 289.00 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-06:49 | 1648.61 | 9.17 | 0.00 | 330.33 | 895.08 | 11.30 | 0.00 | 285.00 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:49 | 1592.70 | 9.47 | 5.67 | 295.33 | 836.17 | 11.42 | 3.67 | 251.83 |
October | 330.00 | 0.75 | 0.73 | 01-OCT-06:49 | 1660.95 | 14.79 | 75.33 | 282.50 | 850.44 | 14.64 | 47.17 | 242.83 |
November | 308.00 | 0.75 | 0.73 | 01-NOV-07:49 | 1264.28 | 13.09 | 56.83 | 236.17 | 723.86 | 15.02 | 53.67 | 196.17 |
December | 282.83 | 0.76 | 0.73 | 01-DEC-07:49 | 1482.31 | 15.34 | 75.50 | 224.83 | 822.10 | 16.04 | 59.67 | 172.50 |
Annual Sum or Average | 4027.67 | 0.75 | 1685.43 | 11.30 | 414.83 | 3466.00 | 858.29 | 12.66 | 279.67 | 2888.00 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 1264.28 | 8.14 | 0.00 | 224.83 | 723.86 | 10.52 | 0.00 | 172.50 | |
Maximum of Months | 394.00 | 0.76 | 0.73 | 2050.70 | 15.34 | 81.33 | 346.00 | 1017.93 | 16.09 | 62.17 | 289.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.77 | 0.73 | 01-JAN-08:50 | 394.75 | 0.00 | 0.00 | 189.00 | 273.35 | 0.00 | 0.00 | 66.83 |
February | 295.50 | 0.76 | 0.73 | 01-FEB-11:39 | 456.51 | 0.00 | 0.00 | 212.50 | 316.83 | 0.00 | 0.00 | 124.17 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 540.38 | 0.00 | 0.00 | 279.00 | 360.09 | 0.00 | 0.00 | 172.17 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:30 | 648.97 | 0.00 | 0.00 | 312.33 | 416.94 | 0.00 | 0.00 | 249.00 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-06:49 | 801.70 | 0.00 | 0.00 | 353.00 | 483.41 | 0.00 | 0.00 | 294.33 |
June | 394.00 | 0.74 | 0.73 | 01-JUN-06:19 | 939.23 | 0.00 | 0.00 | 361.67 | 525.37 | 0.00 | 0.00 | 324.83 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:19 | 919.65 | 0.00 | 0.00 | 363.17 | 521.64 | 0.00 | 0.00 | 318.83 |
August | 380.83 | 0.74 | 0.73 | 01-AUG-06:00 | 802.60 | 0.00 | 0.00 | 340.67 | 472.68 | 0.00 | 0.00 | 290.50 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:00 | 669.42 | 0.00 | 0.00 | 299.50 | 404.47 | 0.00 | 0.00 | 222.50 |
October | 330.00 | 0.75 | 0.73 | 01-OCT-07:19 | 567.87 | 0.00 | 0.00 | 276.67 | 368.51 | 0.00 | 0.00 | 196.83 |
November | 308.00 | 0.76 | 0.73 | 01-NOV-08:50 | 405.04 | 0.00 | 0.00 | 195.83 | 282.22 | 0.00 | 0.00 | 77.33 |
December | 282.83 | 0.76 | 0.73 | 01-DEC-08:30 | 393.45 | 0.00 | 0.00 | 185.00 | 274.61 | 0.00 | 0.00 | 53.33 |
Annual Sum or Average | 4027.67 | 0.75 | 648.51 | 0.00 | 0.00 | 3368.33 | 400.99 | 0.00 | 0.00 | 2390.67 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 393.45 | 0.00 | 0.00 | 185.00 | 273.35 | 0.00 | 0.00 | 53.33 | |
Maximum of Months | 394.00 | 0.77 | 0.73 | 939.23 | 0.00 | 0.00 | 363.17 | 525.37 | 0.00 | 0.00 | 324.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.76 | 0.73 | 01-JAN-08:50 | 1759.89 | 15.39 | 82.67 | 244.50 | 1057.16 | 17.41 | 80.50 | 190.00 |
February | 295.50 | 0.75 | 0.73 | 01-FEB-11:39 | 1418.14 | 12.82 | 51.33 | 244.83 | 843.17 | 14.89 | 50.00 | 206.17 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 1737.06 | 11.89 | 45.33 | 288.33 | 892.32 | 10.76 | 0.00 | 230.67 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:49 | 1933.21 | 8.21 | 0.00 | 305.50 | 1058.33 | 10.61 | 0.00 | 267.50 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-07:30 | 1577.94 | 8.80 | 0.00 | 333.33 | 716.16 | 11.13 | 0.00 | 281.67 |
June | 394.00 | 0.75 | 0.73 | 01-JUN-06:00 | 1678.43 | 8.81 | 0.00 | 338.50 | 727.55 | 11.04 | 0.00 | 289.33 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:49 | 1551.72 | 9.18 | 0.00 | 345.83 | 702.84 | 11.32 | 0.00 | 290.67 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-07:10 | 1603.99 | 9.27 | 0.00 | 330.83 | 748.65 | 11.40 | 0.00 | 283.50 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-07:30 | 1505.40 | 9.40 | 5.50 | 295.67 | 773.39 | 11.19 | 0.00 | 249.50 |
October | 330.00 | 0.74 | 0.73 | 01-OCT-07:40 | 1916.72 | 15.42 | 83.17 | 286.83 | 803.43 | 12.32 | 7.00 | 244.50 |
November | 308.00 | 0.75 | 0.73 | 01-NOV-08:00 | 1559.90 | 15.08 | 79.50 | 241.00 | 820.92 | 14.63 | 50.67 | 189.67 |
December | 282.83 | 0.75 | 0.73 | 01-DEC-08:39 | 1676.24 | 16.70 | 84.83 | 242.17 | 880.37 | 15.86 | 55.83 | 178.83 |
Annual Sum or Average | 4027.67 | 0.75 | 1659.30 | 11.49 | 432.33 | 3497.33 | 828.40 | 12.55 | 244.00 | 2902.00 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 1418.14 | 8.21 | 0.00 | 241.00 | 702.84 | 10.61 | 0.00 | 178.83 | |
Maximum of Months | 394.00 | 0.76 | 0.73 | 1933.21 | 16.70 | 84.83 | 345.83 | 1058.33 | 17.41 | 80.50 | 290.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.75 | 0.73 | 01-JAN-07:00 | 6700.56 | 33.90 | 278.83 | 287.33 | 1155.96 | 20.81 | 92.17 | 271.50 |
February | 295.50 | 0.74 | 0.73 | 01-FEB-11:39 | 2761.37 | 23.14 | 165.17 | 272.17 | 993.31 | 17.70 | 36.33 | 259.17 |
March | 296.00 | 0.74 | 0.73 | 02-MAR-12:39 | 1203.20 | 10.90 | 0.00 | 305.17 | 731.88 | 15.86 | 0.00 | 260.33 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:30 | 950.69 | 10.46 | 0.00 | 308.00 | 572.79 | 15.20 | 0.00 | 262.67 |
May | 353.67 | 0.75 | 0.73 | 01-MAY-06:00 | 847.53 | 10.45 | 0.00 | 330.33 | 499.46 | 15.28 | 0.00 | 270.83 |
June | 394.00 | 0.75 | 0.73 | 01-JUN-06:40 | 803.76 | 10.12 | 0.00 | 331.00 | 476.82 | 14.91 | 0.00 | 272.50 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:40 | 891.50 | 10.38 | 0.00 | 343.17 | 511.92 | 15.14 | 0.00 | 284.17 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-06:00 | 1040.14 | 10.78 | 0.00 | 332.67 | 584.44 | 15.49 | 0.00 | 286.00 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:00 | 1229.22 | 11.06 | 3.67 | 304.67 | 678.61 | 15.57 | 0.00 | 263.00 |
October | 330.00 | 0.74 | 0.73 | 01-OCT-06:00 | 2218.54 | 16.27 | 77.17 | 305.83 | 924.90 | 16.89 | 10.33 | 273.50 |
November | 308.00 | 0.74 | 0.73 | 01-NOV-07:49 | 6780.45 | 33.49 | 279.00 | 278.00 | 1132.95 | 20.61 | 90.83 | 269.33 |
December | 282.83 | 0.74 | 0.73 | 01-DEC-07:00 | 6755.48 | 33.14 | 248.83 | 272.17 | 1497.97 | 23.12 | 110.83 | 259.50 |
Annual Sum or Average | 4027.67 | 0.75 | 2501.11 | 17.08 | 1052.67 | 3670.50 | 784.86 | 17.00 | 340.50 | 3232.50 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 803.76 | 10.12 | 0.00 | 272.17 | 476.82 | 14.91 | 0.00 | 259.17 | |
Maximum of Months | 394.00 | 0.75 | 0.73 | 6780.45 | 33.90 | 279.00 | 343.17 | 1497.97 | 23.12 | 110.83 | 286.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.76 | 0.73 | 01-JAN-07:49 | 1566.81 | 15.08 | 81.33 | 237.67 | 824.07 | 14.58 | 53.33 | 180.33 |
February | 295.50 | 0.75 | 0.73 | 01-FEB-11:39 | 1732.43 | 14.59 | 71.67 | 236.67 | 964.93 | 16.08 | 62.17 | 197.33 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 1608.94 | 12.31 | 48.50 | 294.00 | 955.29 | 10.85 | 0.00 | 237.00 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:10 | 1838.94 | 8.13 | 0.00 | 304.00 | 1018.54 | 10.51 | 0.00 | 263.83 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-06:40 | 2050.70 | 8.62 | 0.00 | 339.33 | 844.23 | 11.01 | 0.00 | 284.67 |
June | 394.00 | 0.74 | 0.73 | 01-JUN-06:10 | 1843.39 | 8.79 | 0.00 | 338.83 | 796.74 | 11.06 | 0.00 | 288.17 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:19 | 1791.25 | 9.13 | 0.00 | 346.00 | 789.50 | 11.30 | 0.00 | 289.00 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-06:49 | 1648.89 | 9.16 | 0.00 | 330.33 | 889.76 | 11.29 | 0.00 | 284.83 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:49 | 1592.93 | 9.46 | 5.67 | 295.33 | 811.89 | 11.42 | 3.67 | 249.50 |
October | 330.00 | 0.75 | 0.73 | 01-OCT-06:49 | 1660.67 | 14.78 | 75.33 | 282.50 | 851.10 | 14.63 | 47.17 | 242.83 |
November | 308.00 | 0.75 | 0.73 | 01-NOV-07:49 | 1263.93 | 13.08 | 56.83 | 236.00 | 724.29 | 15.01 | 53.67 | 196.17 |
December | 282.83 | 0.76 | 0.73 | 01-DEC-07:49 | 1481.98 | 15.33 | 75.50 | 224.50 | 822.49 | 16.03 | 59.67 | 172.50 |
Annual Sum or Average | 4027.67 | 0.75 | 1685.36 | 11.28 | 414.83 | 3465.17 | 856.22 | 12.65 | 279.67 | 2886.17 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 1263.93 | 8.13 | 0.00 | 224.50 | 724.29 | 10.51 | 0.00 | 172.50 | |
Maximum of Months | 394.00 | 0.76 | 0.73 | 2050.70 | 15.33 | 81.33 | 346.00 | 1018.54 | 16.08 | 62.17 | 289.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.77 | 0.73 | 01-JAN-08:50 | 394.59 | 0.00 | 0.00 | 188.67 | 273.52 | 0.00 | 0.00 | 66.83 |
February | 295.50 | 0.76 | 0.73 | 01-FEB-11:39 | 456.32 | 0.00 | 0.00 | 212.50 | 317.02 | 0.00 | 0.00 | 124.33 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 540.27 | 0.00 | 0.00 | 278.83 | 360.34 | 0.00 | 0.00 | 172.33 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:30 | 648.94 | 0.00 | 0.00 | 312.33 | 417.28 | 0.00 | 0.00 | 249.50 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-06:49 | 801.85 | 0.00 | 0.00 | 352.83 | 483.91 | 0.00 | 0.00 | 294.67 |
June | 394.00 | 0.74 | 0.73 | 01-JUN-06:19 | 939.47 | 0.00 | 0.00 | 361.67 | 525.92 | 0.00 | 0.00 | 325.17 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:19 | 919.97 | 0.00 | 0.00 | 363.17 | 522.24 | 0.00 | 0.00 | 319.17 |
August | 380.83 | 0.74 | 0.73 | 01-AUG-06:00 | 802.82 | 0.00 | 0.00 | 340.67 | 473.20 | 0.00 | 0.00 | 290.83 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-06:00 | 669.53 | 0.00 | 0.00 | 299.50 | 404.89 | 0.00 | 0.00 | 223.00 |
October | 330.00 | 0.75 | 0.73 | 01-OCT-07:19 | 567.78 | 0.00 | 0.00 | 276.50 | 368.80 | 0.00 | 0.00 | 197.17 |
November | 308.00 | 0.76 | 0.73 | 01-NOV-08:50 | 404.85 | 0.00 | 0.00 | 195.83 | 282.38 | 0.00 | 0.00 | 77.83 |
December | 282.83 | 0.76 | 0.73 | 01-DEC-08:30 | 393.26 | 0.00 | 0.00 | 184.83 | 274.77 | 0.00 | 0.00 | 53.50 |
Annual Sum or Average | 4027.67 | 0.75 | 648.53 | 0.00 | 0.00 | 3367.33 | 401.35 | 0.00 | 0.00 | 2394.33 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 393.26 | 0.00 | 0.00 | 184.83 | 273.52 | 0.00 | 0.00 | 53.50 | |
Maximum of Months | 394.00 | 0.77 | 0.73 | 939.47 | 0.00 | 0.00 | 363.17 | 525.92 | 0.00 | 0.00 | 325.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 307.33 | 0.76 | 0.73 | 01-JAN-08:50 | 1759.55 | 15.38 | 82.67 | 244.67 | 1057.55 | 17.40 | 80.50 | 190.17 |
February | 295.50 | 0.75 | 0.73 | 01-FEB-11:39 | 1417.70 | 12.81 | 51.33 | 244.67 | 843.65 | 14.88 | 50.00 | 206.17 |
March | 296.00 | 0.75 | 0.73 | 02-MAR-12:39 | 1736.82 | 11.88 | 45.33 | 288.00 | 892.87 | 10.75 | 0.00 | 230.83 |
April | 347.33 | 0.75 | 0.73 | 01-APR-07:49 | 1933.17 | 8.20 | 0.00 | 305.50 | 1058.97 | 10.60 | 0.00 | 267.67 |
May | 353.67 | 0.74 | 0.73 | 01-MAY-07:30 | 1578.08 | 8.78 | 0.00 | 333.17 | 881.93 | 11.12 | 0.00 | 281.83 |
June | 394.00 | 0.75 | 0.73 | 01-JUN-06:00 | 1678.59 | 8.79 | 0.00 | 338.50 | 728.26 | 11.03 | 0.00 | 289.50 |
July | 390.00 | 0.74 | 0.73 | 01-JUL-06:49 | 1552.08 | 9.17 | 0.00 | 345.83 | 710.57 | 11.31 | 0.00 | 290.67 |
August | 380.83 | 0.75 | 0.73 | 01-AUG-07:10 | 1604.32 | 9.26 | 0.00 | 330.83 | 864.34 | 11.39 | 0.00 | 283.83 |
September | 342.17 | 0.75 | 0.73 | 01-SEP-07:30 | 1505.59 | 9.39 | 5.50 | 295.50 | 774.14 | 11.18 | 0.00 | 250.00 |
October | 330.00 | 0.74 | 0.73 | 01-OCT-07:40 | 1916.49 | 15.41 | 83.17 | 286.83 | 804.08 | 12.31 | 7.00 | 244.50 |
November | 308.00 | 0.75 | 0.73 | 01-NOV-08:00 | 1559.56 | 15.07 | 79.50 | 240.83 | 821.33 | 14.62 | 50.67 | 189.83 |
December | 282.83 | 0.75 | 0.73 | 01-DEC-08:39 | 1675.89 | 16.69 | 84.83 | 242.00 | 880.76 | 15.85 | 55.83 | 178.83 |
Annual Sum or Average | 4027.67 | 0.75 | 1659.26 | 11.47 | 432.33 | 3496.33 | 855.05 | 12.54 | 244.00 | 2903.83 | ||
Minimum of Months | 282.83 | 0.74 | 0.73 | 1417.70 | 8.20 | 0.00 | 240.83 | 710.57 | 10.60 | 0.00 | 178.83 | |
Maximum of Months | 394.00 | 0.76 | 0.73 | 1933.17 | 16.69 | 84.83 | 345.83 | 1058.97 | 17.40 | 80.50 | 290.67 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.556125E+09 | 427716.77 | 04-JAN-22:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.244998E+09 | 444550.31 | 13-FEB-22:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68535325.38 | 265532.94 | 11-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 78285894.79 | 260952.98 | 23-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149915E+09 | 100524.12 | 18-DEC-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109786E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.556125E+09 | 444550.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 78203019.10 | 63574.39 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228193E+09 | 64557.01 | 06-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 52141725.45 | 63458.42 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 756928.55 | 978.07 | 21-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.359294E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.228193E+09 | 64557.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 3716604.18 | 642.53 | 10-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 602751.75 | 908.75 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7157101.20 | 3052.35 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 11476457.13 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7157101.20 | 3052.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159807E+10 | 109298.47 | 11-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.950700E+09 | 111067.01 | 06-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.627027E+09 | 87425.23 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.936352E+09 | 112035.02 | 20-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.411215E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.159807E+10 | 112035.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177182E+10 | 103092.11 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.902651E+09 | 102980.70 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105407E+10 | 59769.12 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14570726.41 | 8546.37 | 16-NOV-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159321E+10 | 103413.62 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.533633E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177182E+10 | 103413.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.262419E+09 | 20996.13 | 21-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.191266E+09 | 125244.10 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.348133E+09 | 17239.44 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.332928E+09 | 123337.16 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113475E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.348133E+09 | 125244.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.145853E+10 | 83235.71 | 10-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.715449E+09 | 94040.66 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.677033E+09 | 25182.54 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.753765E+09 | 93442.16 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.360478E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.145853E+10 | 94040.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.116817E+10 | 13147.47 | 06-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.683579E+09 | 12827.18 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.416344E+09 | 12886.91 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2156793.63 | 451.06 | 03-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7096967.00 | 912.03 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 89213267.18 | 12814.37 | 16-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.728590E+09 | 13117.90 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.309515E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.116817E+10 | 13147.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.730588E+09 | 12341.08 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414186E+09 | 12375.83 | 06-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.352405E+09 | 12208.80 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3131996.51 | 691.44 | 03-APR-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10087677.73 | 1333.95 | 28-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 76877329.80 | 12044.68 | 16-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.607030E+09 | 12304.94 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219431E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.730588E+09 | 12375.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.450279E+09 | 14237.49 | 09-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276370E+09 | 14192.33 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315598E+09 | 14263.76 | 13-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 805558.64 | 359.24 | 28-OCT-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 7705874.00 | 1580.27 | 16-NOV-06:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.306087E+09 | 14202.84 | 30-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.135685E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.450279E+09 | 14263.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.749170E+09 | 12425.09 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.388882E+09 | 12365.37 | 06-FEB-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.292227E+09 | 12210.07 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 9755955.74 | 851.24 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 63099840.68 | 2694.40 | 16-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.461547E+09 | 12388.29 | 21-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.196468E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.749170E+09 | 12425.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113588E+10 | 224052.45 | 04-JAN-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.126123E+10 | 222675.04 | 08-FEB-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.925458E+09 | 223447.95 | 14-MAR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111818E+10 | 222543.66 | 12-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149705E+10 | 219065.07 | 30-MAY-00:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.583866E+09 | 216818.78 | 11-JUN-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.154378E+10 | 219190.14 | 04-JUL-22:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.111851E+10 | 218513.82 | 13-AUG-22:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.154421E+10 | 220110.73 | 04-SEP-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175470E+10 | 221882.93 | 27-OCT-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.121090E+10 | 222620.13 | 16-NOV-04:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.185929E+10 | 225675.00 | 21-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155531E+11 | |||||||
Minimum of Months | 0.583866E+09 | 216818.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185929E+10 | 225675.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.365696E+09 | 26946.32 | 04-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.174823E+09 | 26906.29 | 17-FEB-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123204E+09 | 26721.27 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3874745.68 | 1833.83 | 03-APR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7559573.63 | 4371.60 | 28-OCT-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9132098.99 | 6752.37 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192677E+09 | 27479.72 | 20-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876966E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.365696E+09 | 27479.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.525390E+10 | 269699.93 | 21-JAN-07:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.363903E+10 | 254327.51 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.327000E+10 | 254319.34 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.203332E+09 | 156633.68 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72696057.17 | 120798.37 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.847898E+09 | 190134.52 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.464395E+10 | 263336.31 | 20-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.179308E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.525390E+10 | 269699.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.243625E+09 | 26368.12 | 04-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128065E+09 | 26335.86 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141286E+09 | 26335.59 | 09-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 13908547.13 | 15691.26 | 11-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 7372172.11 | 12177.53 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 36554757.10 | 19315.04 | 15-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167722E+09 | 26077.38 | 20-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.738533E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.243625E+09 | 26368.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.237464E+11 | 0.182977E+11 | 136695.33 | 01-JAN-16:51 | 103624.31 | 0.17 |
February | 0.00 | 0.00 | 0.284239E+11 | 0.225019E+11 | 136648.76 | 20-FEB-14:00 | 114632.98 | 0.27 |
March | 0.00 | 0.00 | 0.378867E+11 | 0.322297E+11 | 158334.91 | 07-MAR-04:50 | 103761.86 | 0.26 |
April | 0.00 | 0.00 | 0.589657E+11 | 0.513496E+11 | 166739.81 | 29-APR-03:01 | 93583.85 | 0.45 |
May | 0.00 | 0.00 | 0.108467E+12 | 0.850011E+11 | 193008.48 | 21-MAY-22:41 | 94103.41 | 0.61 |
June | 0.00 | 0.00 | 0.112501E+12 | 0.855871E+11 | 193213.74 | 18-JUN-22:11 | 95485.25 | 0.62 |
July | 0.00 | 0.00 | 0.122143E+12 | 0.879344E+11 | 193199.14 | 02-JUL-18:20 | 98352.74 | 0.60 |
August | 0.00 | 0.00 | 0.132826E+12 | 0.978472E+11 | 189351.47 | 06-AUG-14:41 | 93208.97 | 0.65 |
September | 0.00 | 0.00 | 0.114807E+12 | 0.853235E+11 | 189087.91 | 17-SEP-13:51 | 92700.48 | 0.64 |
October | 0.00 | 0.00 | 0.996614E+11 | 0.779392E+11 | 188809.48 | 15-OCT-14:30 | 93513.68 | 0.54 |
November | 0.00 | 0.00 | 0.554520E+11 | 0.462871E+11 | 166268.86 | 11-NOV-16:30 | 97723.36 | 0.39 |
December | 0.00 | 0.00 | 0.363873E+11 | 0.299365E+11 | 156004.18 | 16-DEC-04:53 | 96564.99 | 0.25 |
Annual Sum or Average | 0.931269E+12 | 0.720235E+12 | 0.45 | |||||
Minimum of Months | 0.00 | 0.00 | 0.237464E+11 | 0.182977E+11 | 136648.76 | 92700.48 | 0.17 | |
Maximum of Months | 0.00 | 0.00 | 0.132826E+12 | 0.978472E+11 | 193213.74 | 114632.98 | 0.65 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.432714E+11 | 0.306641E+11 | 160797.83 | 19-JAN-06:01 | 135078.46 | 0.23 |
February | 0.00 | 0.00 | 0.611315E+11 | 0.422407E+11 | 152265.92 | 28-FEB-06:01 | 137054.00 | 0.38 |
March | 0.00 | 0.00 | 0.766018E+11 | 0.579895E+11 | 153440.04 | 27-MAR-05:03 | 140861.48 | 0.39 |
April | 0.00 | 0.00 | 0.125320E+12 | 0.954148E+11 | 159762.45 | 01-APR-05:01 | 129564.86 | 0.65 |
May | 0.00 | 0.00 | 0.164216E+12 | 0.119816E+12 | 205165.68 | 23-MAY-03:01 | 145569.48 | 0.68 |
June | 0.00 | 0.00 | 0.175905E+12 | 0.131756E+12 | 169390.32 | 19-JUN-05:03 | 146585.37 | 0.76 |
July | 0.00 | 0.00 | 0.191111E+12 | 0.140186E+12 | 183854.36 | 25-JUL-05:02 | 147012.42 | 0.79 |
August | 0.00 | 0.00 | 0.207811E+12 | 0.154243E+12 | 192242.78 | 15-AUG-05:02 | 154107.52 | 0.84 |
September | 0.00 | 0.00 | 0.167251E+12 | 0.112908E+12 | 224450.98 | 05-SEP-03:02 | 152144.68 | 0.68 |
October | 0.00 | 0.00 | 0.151535E+12 | 0.112903E+12 | 178807.15 | 14-OCT-05:02 | 139805.68 | 0.63 |
November | 0.00 | 0.00 | 0.942755E+11 | 0.731326E+11 | 165459.01 | 01-NOV-05:01 | 142101.88 | 0.50 |
December | 0.00 | 0.00 | 0.695551E+11 | 0.517817E+11 | 173696.77 | 11-DEC-06:02 | 146508.51 | 0.35 |
Annual Sum or Average | 0.152799E+13 | 0.112304E+13 | 0.57 | |||||
Minimum of Months | 0.00 | 0.00 | 0.432714E+11 | 0.306641E+11 | 152265.92 | 129564.86 | 0.23 | |
Maximum of Months | 0.00 | 0.00 | 0.207811E+12 | 0.154243E+12 | 224450.98 | 154107.52 | 0.84 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.350125E+12 | 0.240039E+12 | 1256387.57 | 19-JAN-06:02 | 953965.63 | 0.21 |
February | 0.00 | 0.00 | 0.491356E+12 | 0.325925E+12 | 1390707.20 | 03-FEB-06:02 | 981850.07 | 0.36 |
March | 0.00 | 0.00 | 0.589342E+12 | 0.420590E+12 | 1626805.92 | 07-MAR-06:01 | 1241008.90 | 0.34 |
April | 0.00 | 0.00 | 0.938170E+12 | 0.662627E+12 | 1763661.10 | 29-APR-05:02 | 1295496.66 | 0.50 |
May | 0.00 | 0.00 | 0.149428E+13 | 0.104160E+13 | 2530687.88 | 22-MAY-03:02 | 1365778.86 | 0.63 |
June | 0.00 | 0.00 | 0.151114E+13 | 0.106665E+13 | 1876726.25 | 24-JUN-05:02 | 1412282.84 | 0.66 |
July | 0.00 | 0.00 | 0.157611E+13 | 0.105551E+13 | 2189361.96 | 31-JUL-03:01 | 1334510.24 | 0.64 |
August | 0.00 | 0.00 | 0.163962E+13 | 0.110053E+13 | 2135296.62 | 26-AUG-05:02 | 1377079.63 | 0.65 |
September | 0.00 | 0.00 | 0.149624E+13 | 0.947253E+12 | 2672417.15 | 05-SEP-03:02 | 1352028.04 | 0.63 |
October | 0.00 | 0.00 | 0.126766E+13 | 0.883827E+12 | 2105685.69 | 21-OCT-05:02 | 1322530.73 | 0.54 |
November | 0.00 | 0.00 | 0.731981E+12 | 0.540042E+12 | 1760411.15 | 01-NOV-05:02 | 1262673.12 | 0.44 |
December | 0.00 | 0.00 | 0.513040E+12 | 0.351059E+12 | 1628569.47 | 15-DEC-06:01 | 1267960.21 | 0.28 |
Annual Sum or Average | 0.125991E+14 | 0.863565E+13 | 0.49 | |||||
Minimum of Months | 0.00 | 0.00 | 0.350125E+12 | 0.240039E+12 | 1256387.57 | 953965.63 | 0.21 | |
Maximum of Months | 0.00 | 0.00 | 0.163962E+13 | 0.110053E+13 | 2672417.15 | 1412282.84 | 0.66 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.344691E+11 | 0.227643E+11 | 139659.87 | 19-JAN-15:00 | 85307.02 | 0.20 |
February | 0.00 | 0.00 | 0.494645E+11 | 0.322581E+11 | 138148.34 | 03-FEB-06:02 | 53126.94 | 0.35 |
March | 0.00 | 0.00 | 0.611557E+11 | 0.431338E+11 | 151616.91 | 27-MAR-05:03 | 120788.39 | 0.33 |
April | 0.00 | 0.00 | 0.992689E+11 | 0.710720E+11 | 170746.67 | 29-APR-05:01 | 129018.03 | 0.49 |
May | 0.00 | 0.00 | 0.163205E+12 | 0.116851E+12 | 267307.50 | 22-MAY-03:02 | 149929.67 | 0.64 |
June | 0.00 | 0.00 | 0.167468E+12 | 0.121730E+12 | 188648.89 | 23-JUN-05:02 | 143153.62 | 0.66 |
July | 0.00 | 0.00 | 0.174327E+12 | 0.119971E+12 | 230712.90 | 31-JUL-03:01 | 140475.19 | 0.65 |
August | 0.00 | 0.00 | 0.178999E+12 | 0.123334E+12 | 226220.70 | 23-AUG-03:02 | 150307.50 | 0.66 |
September | 0.00 | 0.00 | 0.159714E+12 | 0.103147E+12 | 295297.30 | 05-SEP-03:02 | 143522.33 | 0.64 |
October | 0.00 | 0.00 | 0.134274E+12 | 0.951711E+11 | 214539.42 | 21-OCT-05:02 | 129032.18 | 0.54 |
November | 0.00 | 0.00 | 0.726729E+11 | 0.533764E+11 | 172102.87 | 01-NOV-05:01 | 126816.20 | 0.43 |
December | 0.00 | 0.00 | 0.503574E+11 | 0.340240E+11 | 170642.76 | 16-DEC-06:01 | 123447.92 | 0.28 |
Annual Sum or Average | 0.134538E+13 | 0.936832E+12 | 0.49 | |||||
Minimum of Months | 0.00 | 0.00 | 0.344691E+11 | 0.227643E+11 | 138148.34 | 53126.94 | 0.20 | |
Maximum of Months | 0.00 | 0.00 | 0.178999E+12 | 0.123334E+12 | 295297.30 | 150307.50 | 0.66 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.317721E+12 | 0.315945E+12 | 433346.41 | 21-JAN-23:40 | 430298.78 | 0.00 |
February | 0.00 | 0.00 | 0.500304E+12 | 0.496868E+12 | 443852.81 | 13-FEB-22:40 | 443852.81 | 0.00 |
March | 0.00 | 0.00 | 0.788383E+12 | 0.785082E+12 | 431733.39 | 20-MAR-21:07 | 431733.39 | 0.00 |
April | 0.00 | 0.00 | 0.993649E+12 | 0.989090E+12 | 401643.02 | 28-APR-17:40 | 386251.00 | 0.00 |
May | 0.00 | 0.00 | 0.331396E+12 | 0.320737E+12 | 134361.51 | 01-MAY-16:00 | 125454.34 | 0.00 |
June | 0.00 | 0.00 | 0.549214E+12 | 0.537418E+12 | 223170.06 | 29-JUN-15:00 | 208151.55 | 0.00 |
July | 0.00 | 0.00 | 0.804352E+12 | 0.791573E+12 | 310799.32 | 12-JUL-12:30 | 296835.68 | 0.00 |
August | 0.00 | 0.00 | 0.103708E+13 | 0.102571E+13 | 404516.43 | 07-AUG-14:00 | 387495.04 | 0.00 |
September | 0.00 | 0.00 | 0.324823E+12 | 0.313215E+12 | 137785.14 | 01-SEP-00:10 | 136083.72 | 0.00 |
October | 0.00 | 0.00 | 0.566468E+12 | 0.557443E+12 | 224055.24 | 24-OCT-14:20 | 210850.64 | 0.00 |
November | 0.00 | 0.00 | 0.769756E+12 | 0.765562E+12 | 436929.25 | 26-NOV-05:34 | 420281.12 | 0.00 |
December | 0.00 | 0.00 | 0.102752E+13 | 0.102485E+13 | 433700.18 | 18-DEC-06:10 | 433700.18 | 0.00 |
Annual Sum or Average | 0.801066E+13 | 0.792349E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.317721E+12 | 0.313215E+12 | 134361.51 | 125454.34 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103708E+13 | 0.102571E+13 | 443852.81 | 443852.81 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.506779E+10 | 0.506765E+10 | 2333.97 | 01-JAN-17:30 | 2333.97 | 0.00 |
February | 0.00 | 0.00 | 0.916635E+10 | 0.916625E+10 | 4346.52 | 26-FEB-17:47 | 4346.52 | 0.00 |
March | 0.00 | 0.00 | 0.151005E+11 | 0.151005E+11 | 5947.70 | 13-MAR-18:00 | 5947.70 | 0.00 |
April | 0.00 | 0.00 | 0.194094E+11 | 0.194094E+11 | 8049.79 | 16-APR-18:10 | 8049.79 | 0.00 |
May | 0.00 | 0.00 | 0.559171E+10 | 0.559171E+10 | 2396.89 | 01-MAY-00:10 | 2396.89 | 0.00 |
June | 0.00 | 0.00 | 0.101056E+11 | 0.101056E+11 | 4203.52 | 11-JUN-18:15 | 4203.52 | 0.00 |
July | 0.00 | 0.00 | 0.152798E+11 | 0.152798E+11 | 5931.40 | 16-JUL-18:45 | 5931.40 | 0.00 |
August | 0.00 | 0.00 | 0.201639E+11 | 0.201639E+11 | 7804.21 | 06-AUG-18:10 | 7804.21 | 0.00 |
September | 0.00 | 0.00 | 0.542425E+10 | 0.542425E+10 | 2450.12 | 03-SEP-17:55 | 2450.12 | 0.00 |
October | 0.00 | 0.00 | 0.104641E+11 | 0.104641E+11 | 4265.37 | 09-OCT-17:15 | 4265.37 | 0.00 |
November | 0.00 | 0.00 | 0.147453E+11 | 0.147453E+11 | 6121.19 | 12-NOV-16:53 | 6121.19 | 0.00 |
December | 0.00 | 0.00 | 0.199990E+11 | 0.199990E+11 | 7935.39 | 25-DEC-17:03 | 7935.39 | 0.00 |
Annual Sum or Average | 0.150518E+12 | 0.150517E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.506779E+10 | 0.506765E+10 | 2333.97 | 2333.97 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.201639E+11 | 0.201639E+11 | 8049.79 | 8049.79 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.388867E+11 | 0.388853E+11 | 21245.80 | 31-JAN-17:50 | 21245.80 | 0.00 |
February | 0.00 | 0.00 | 0.795545E+11 | 0.795535E+11 | 39424.53 | 27-FEB-17:40 | 39424.53 | 0.00 |
March | 0.00 | 0.00 | 0.137298E+12 | 0.137298E+12 | 56293.01 | 06-MAR-17:50 | 56293.01 | 0.00 |
April | 0.00 | 0.00 | 0.183120E+12 | 0.183120E+12 | 75316.06 | 16-APR-18:16 | 75316.06 | 0.00 |
May | 0.00 | 0.00 | 0.512592E+11 | 0.512592E+11 | 21881.12 | 29-MAY-18:16 | 21881.12 | 0.00 |
June | 0.00 | 0.00 | 0.954613E+11 | 0.954613E+11 | 39463.81 | 11-JUN-18:15 | 39463.81 | 0.00 |
July | 0.00 | 0.00 | 0.145427E+12 | 0.145427E+12 | 55982.44 | 07-JUL-16:00 | 55982.44 | 0.00 |
August | 0.00 | 0.00 | 0.192206E+12 | 0.192206E+12 | 74022.91 | 30-AUG-18:50 | 74022.91 | 0.00 |
September | 0.00 | 0.00 | 0.487227E+11 | 0.487227E+11 | 22900.14 | 03-SEP-17:55 | 22900.14 | 0.00 |
October | 0.00 | 0.00 | 0.967883E+11 | 0.967883E+11 | 39681.98 | 09-OCT-17:35 | 39681.98 | 0.00 |
November | 0.00 | 0.00 | 0.134450E+12 | 0.134450E+12 | 57436.39 | 06-NOV-17:00 | 57436.39 | 0.00 |
December | 0.00 | 0.00 | 0.182532E+12 | 0.182532E+12 | 74128.58 | 15-DEC-17:00 | 74128.58 | 0.00 |
Annual Sum or Average | 0.138571E+13 | 0.138570E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.388867E+11 | 0.388853E+11 | 21245.80 | 21245.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.192206E+12 | 0.192206E+12 | 75316.06 | 75316.06 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.291948E+10 | 0.291935E+10 | 2184.25 | 31-JAN-17:40 | 2184.25 | 0.00 |
February | 0.00 | 0.00 | 0.724074E+10 | 0.724064E+10 | 3990.79 | 27-FEB-17:40 | 3990.79 | 0.00 |
March | 0.00 | 0.00 | 0.132314E+11 | 0.132314E+11 | 5691.16 | 06-MAR-17:50 | 5691.16 | 0.00 |
April | 0.00 | 0.00 | 0.181717E+11 | 0.181717E+11 | 7656.62 | 16-APR-18:20 | 7656.62 | 0.00 |
May | 0.00 | 0.00 | 0.522510E+10 | 0.522510E+10 | 2440.61 | 29-MAY-18:00 | 2440.61 | 0.00 |
June | 0.00 | 0.00 | 0.967238E+10 | 0.967238E+10 | 4167.60 | 11-JUN-18:26 | 4167.60 | 0.00 |
July | 0.00 | 0.00 | 0.146723E+11 | 0.146723E+11 | 5749.81 | 16-JUL-18:53 | 5749.81 | 0.00 |
August | 0.00 | 0.00 | 0.193134E+11 | 0.193134E+11 | 7493.51 | 06-AUG-17:35 | 7493.51 | 0.00 |
September | 0.00 | 0.00 | 0.494269E+10 | 0.494269E+10 | 2510.89 | 03-SEP-17:45 | 2510.89 | 0.00 |
October | 0.00 | 0.00 | 0.960714E+10 | 0.960714E+10 | 4182.34 | 08-OCT-17:35 | 4182.34 | 0.00 |
November | 0.00 | 0.00 | 0.129735E+11 | 0.129735E+11 | 5798.81 | 06-NOV-17:00 | 5798.81 | 0.00 |
December | 0.00 | 0.00 | 0.175284E+11 | 0.175284E+11 | 7468.31 | 15-DEC-17:00 | 7468.31 | 0.00 |
Annual Sum or Average | 0.135498E+12 | 0.135498E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.291948E+10 | 0.291935E+10 | 2184.25 | 2184.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.193134E+11 | 0.193134E+11 | 7656.62 | 7656.62 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6216.72 | 38162.76 | 01-JAN-20:17 | 10956.71 | 43299.73 | 04-JAN-13:30 |
February | 5858.87 | 38198.73 | 26-FEB-23:50 | 10993.05 | 42335.89 | 01-FEB-12:40 |
March | 4801.40 | 38324.62 | 26-MAR-18:15 | 11357.65 | 41419.15 | 01-MAR-12:40 |
April | 6165.83 | 38532.29 | 30-APR-16:10 | 9832.60 | 39143.95 | 03-APR-11:30 |
May | 6259.11 | 38697.68 | 29-MAY-07:26 | 9417.93 | 36776.68 | 01-MAY-11:20 |
June | 5743.24 | 38807.94 | 25-JUN-08:40 | 8958.80 | 34302.57 | 01-JUN-11:20 |
July | 7494.00 | 38852.07 | 23-JUL-09:05 | 7737.18 | 32664.25 | 03-JUL-11:30 |
August | 5721.53 | 38843.55 | 06-AUG-09:04 | 8801.88 | 33340.47 | 31-AUG-12:00 |
September | 6577.40 | 38767.81 | 03-SEP-09:00 | 8641.93 | 35322.30 | 29-SEP-12:00 |
October | 6976.69 | 38629.99 | 01-OCT-15:26 | 9357.89 | 38042.92 | 31-OCT-11:50 |
November | 6818.59 | 38419.00 | 05-NOV-16:50 | 10239.38 | 40399.39 | 30-NOV-12:30 |
December | 6358.82 | 38266.07 | 03-DEC-20:20 | 10411.37 | 44467.64 | 20-DEC-12:30 |
Annual Sum or Average | 6251.72 | 9718.48 | ||||
Minimum of Months | 4801.40 | 38162.76 | 7737.18 | 32664.25 | ||
Maximum of Months | 7494.00 | 38852.07 | 11357.65 | 44467.64 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.35 | 4640.29 | 04-JAN-11:50 | 5609.72 | 336305.96 | 10-JAN-07:10 |
February | 2.05 | 4834.21 | 06-FEB-04:01 | 4079.54 | 451010.24 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3172.27 | 493956.66 | 22-MAR-03:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 509.92 | 291360.64 | 12-APR-03:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 547.41 | 214420.27 | 30-MAY-00:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 221.66 | 213097.85 | 01-JUN-03:47 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 565.17 | 213495.33 | 04-JUL-23:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 409.40 | 212471.27 | 13-AUG-22:48 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 584.61 | 214908.32 | 04-SEP-21:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 683.50 | 309970.28 | 29-OCT-15:35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 911.50 | 336615.32 | 26-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4650.58 | 627519.68 | 20-DEC-07:10 |
Annual Sum or Average | 0.61 | 1824.21 | ||||
Minimum of Months | 0.00 | 0.00 | 221.66 | 212471.27 | ||
Maximum of Months | 5.35 | 4834.21 | 5609.72 | 627519.68 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 265549.27 | 1997032.04 | 19-JAN-06:02 | 15.10 | 188150.06 | 16-JAN-00:31 |
February | 414661.97 | 1978375.52 | 03-FEB-06:03 | 10.54 | 189475.49 | 20-FEB-01:21 |
March | 443949.04 | 2061299.22 | 07-MAR-06:02 | 50.44 | 167522.71 | 19-MAR-08:20 |
April | 701606.45 | 2218209.72 | 29-APR-05:02 | 0.99 | 12274.46 | 09-APR-23:02 |
May | 937712.29 | 2958598.31 | 24-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 972299.60 | 2621696.04 | 08-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 972915.20 | 2691137.66 | 25-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1005344.53 | 2847195.57 | 11-AUG-05:03 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 954888.59 | 2791912.58 | 06-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 824143.98 | 2740258.03 | 21-OCT-05:03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 557194.82 | 2411859.25 | 01-NOV-05:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 375920.71 | 2256725.66 | 15-DEC-06:03 | 1.09 | 24348.57 | 09-DEC-23:02 |
Annual Sum or Average | 703511.79 | 6.55 | ||||
Minimum of Months | 265549.27 | 1978375.52 | 0.00 | 0.00 | ||
Maximum of Months | 1005344.53 | 2958598.31 | 50.44 | 189475.49 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 217077.62 | 2581458.98 | 19-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 337636.97 | 2619977.84 | 03-FEB-06:02 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 358616.55 | 2909270.58 | 07-MAR-06:01 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 580066.46 | 3373428.61 | 24-APR-05:02 | 0.00 | 0.00 | 01-APR-00:10 |
May | 832368.39 | 3775297.49 | 24-MAY-05:02 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 854729.79 | 3295969.79 | 02-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 849948.11 | 3468363.74 | 25-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 894890.32 | 3674447.56 | 11-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 856738.91 | 4054890.46 | 05-SEP-03:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 711703.14 | 3655683.78 | 12-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 454646.31 | 3313866.98 | 01-NOV-05:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 313729.71 | 3160753.51 | 15-DEC-06:02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 606486.65 | 0.00 | ||||
Minimum of Months | 217077.62 | 2581458.98 | 0.00 | 0.00 | ||
Maximum of Months | 894890.32 | 4054890.46 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 227517.92 | 699698.55 | 02-JAN-15:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 419796.74 | 974609.68 | 02-FEB-13:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 643779.15 | 1274829.48 | 26-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1010883.12 | 1687743.65 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 696663.63 | 1051206.33 | 28-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 943677.58 | 1348937.77 | 14-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1177529.25 | 1650034.77 | 21-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1365973.96 | 1835674.31 | 30-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 664563.32 | 1205372.76 | 09-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 770271.06 | 1301225.88 | 05-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 709095.36 | 1302398.09 | 02-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 788142.79 | 1506237.90 | 13-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 787307.13 | 0.00 | ||||
Minimum of Months | 227517.92 | 699698.55 | 0.00 | 0.00 | ||
Maximum of Months | 1365973.96 | 1835674.31 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 267345.17 | 4048269.47 | 19-JAN-15:00 | 1358.62 | 168916.26 | 10-JAN-06:30 |
February | 424837.82 | 4114629.22 | 24-FEB-11:00 | 967.70 | 166077.23 | 17-FEB-06:40 |
March | 504372.55 | 4625562.50 | 30-MAR-13:00 | 839.67 | 127613.47 | 22-MAR-05:30 |
April | 878690.44 | 6392203.44 | 28-APR-16:00 | 383.71 | 108877.76 | 11-APR-03:01 |
May | 2142462.16 | 6599231.69 | 26-MAY-11:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2438618.12 | 7050320.15 | 28-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2761351.61 | 7371562.32 | 03-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 2769499.10 | 7302933.84 | 07-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2331687.28 | 7196840.72 | 18-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1737607.73 | 7510797.36 | 06-OCT-14:00 | 224.77 | 111256.54 | 27-OCT-06:40 |
November | 779769.95 | 6122476.41 | 01-NOV-13:20 | 540.54 | 96853.05 | 13-NOV-08:40 |
December | 499476.45 | 5702625.46 | 12-DEC-14:10 | 1158.39 | 150122.49 | 26-DEC-08:00 |
Annual Sum or Average | 1468230.11 | 454.38 | ||||
Minimum of Months | 267345.17 | 4048269.47 | 0.00 | 0.00 | ||
Maximum of Months | 2769499.10 | 7510797.36 | 1358.62 | 168916.26 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.156967E+11 | 0.86 | 9380.27 | 01-JAN-00:20 | 1.38 |
February | 0.137025E+11 | 0.83 | 9380.27 | 01-FEB-04:01 | 1.38 |
March | 0.155942E+11 | 0.86 | 9380.27 | 01-MAR-04:01 | 1.38 |
April | 0.143457E+11 | 0.81 | 9380.27 | 01-APR-03:01 | 1.38 |
May | 0.156486E+11 | 0.85 | 9380.27 | 01-MAY-00:20 | 1.38 |
June | 0.151864E+11 | 0.86 | 9380.27 | 01-JUN-03:01 | 1.38 |
July | 0.153398E+11 | 0.84 | 9380.27 | 01-JUL-03:01 | 1.38 |
August | 0.166024E+11 | 0.91 | 9380.27 | 01-AUG-03:01 | 1.38 |
September | 0.157771E+11 | 0.89 | 9380.27 | 01-SEP-03:01 | 1.38 |
October | 0.162474E+11 | 0.89 | 9380.27 | 01-OCT-13:25 | 1.38 |
November | 0.157567E+11 | 0.89 | 9380.27 | 01-NOV-03:01 | 1.38 |
December | 0.158174E+11 | 0.87 | 9380.27 | 01-DEC-04:01 | 1.39 |
Annual Sum or Average | 0.185715E+12 | 0.86 | |||
Minimum of Months | 0.137025E+11 | 0.81 | 9380.27 | 1.38 | |
Maximum of Months | 0.166024E+11 | 0.91 | 9380.27 | 1.39 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.529191E+10 | 0.37 | 18942.29 | 02-JAN-06:03 | 1.76 |
February | 0.499918E+10 | 0.39 | 18942.29 | 28-FEB-06:01 | 1.76 |
March | 0.614201E+10 | 0.43 | 18942.29 | 06-MAR-06:01 | 1.76 |
April | 0.634575E+10 | 0.47 | 18942.29 | 22-APR-05:03 | 1.76 |
May | 0.608750E+10 | 0.43 | 18942.29 | 02-MAY-03:01 | 1.76 |
June | 0.674042E+10 | 0.49 | 18942.29 | 02-JUN-05:01 | 1.76 |
July | 0.721951E+10 | 0.51 | 18942.29 | 01-JUL-05:01 | 1.76 |
August | 0.832488E+10 | 0.56 | 18942.29 | 01-AUG-05:01 | 1.76 |
September | 0.581154E+10 | 0.43 | 18942.29 | 01-SEP-05:01 | 1.76 |
October | 0.671871E+10 | 0.46 | 18942.29 | 02-OCT-05:03 | 1.76 |
November | 0.628322E+10 | 0.44 | 18942.29 | 01-NOV-05:01 | 1.76 |
December | 0.675432E+10 | 0.45 | 18942.29 | 11-DEC-06:01 | 1.76 |
Annual Sum or Average | 0.767190E+11 | 0.45 | |||
Minimum of Months | 0.499918E+10 | 0.37 | 18942.29 | 1.76 | |
Maximum of Months | 0.832488E+10 | 0.56 | 18942.29 | 1.76 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.386766E+11 | 0.33 | 117889.84 | 02-JAN-06:03 | 1.37 |
February | 0.347048E+11 | 0.33 | 165910.16 | 28-FEB-06:01 | 1.70 |
March | 0.404699E+11 | 0.35 | 174434.66 | 27-MAR-05:03 | 1.76 |
April | 0.404768E+11 | 0.35 | 174434.66 | 24-APR-05:01 | 1.76 |
May | 0.532438E+11 | 0.41 | 174434.66 | 02-MAY-03:01 | 1.76 |
June | 0.542643E+11 | 0.42 | 174434.66 | 01-JUN-05:01 | 1.76 |
July | 0.528687E+11 | 0.41 | 174434.66 | 01-JUL-03:01 | 1.76 |
August | 0.566796E+11 | 0.43 | 174434.66 | 02-AUG-03:01 | 1.76 |
September | 0.478938E+11 | 0.39 | 174434.66 | 01-SEP-03:01 | 1.76 |
October | 0.505710E+11 | 0.39 | 174434.66 | 04-OCT-05:01 | 1.76 |
November | 0.410691E+11 | 0.35 | 174434.66 | 01-NOV-05:01 | 1.76 |
December | 0.392603E+11 | 0.33 | 173447.27 | 14-DEC-06:01 | 1.75 |
Annual Sum or Average | 0.550179E+12 | 0.37 | |||
Minimum of Months | 0.347048E+11 | 0.33 | 117889.84 | 1.37 | |
Maximum of Months | 0.566796E+11 | 0.43 | 174434.66 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.325325E+10 | 0.30 | 11288.35 | 20-JAN-06:01 | 1.30 |
February | 0.318076E+10 | 0.31 | 13295.64 | 27-FEB-06:02 | 1.44 |
March | 0.375216E+10 | 0.33 | 17042.11 | 30-MAR-05:01 | 1.69 |
April | 0.413327E+10 | 0.34 | 18123.48 | 24-APR-05:01 | 1.76 |
May | 0.606239E+10 | 0.43 | 18123.48 | 02-MAY-03:01 | 1.76 |
June | 0.635206E+10 | 0.45 | 18123.48 | 01-JUN-05:01 | 1.76 |
July | 0.611952E+10 | 0.43 | 18123.48 | 01-JUL-03:01 | 1.76 |
August | 0.647117E+10 | 0.45 | 18123.48 | 01-AUG-05:01 | 1.76 |
September | 0.520282E+10 | 0.40 | 18123.48 | 01-SEP-03:01 | 1.76 |
October | 0.533645E+10 | 0.39 | 18123.48 | 03-OCT-05:01 | 1.76 |
November | 0.372770E+10 | 0.32 | 18123.48 | 01-NOV-05:01 | 1.76 |
December | 0.334914E+10 | 0.30 | 18051.05 | 12-DEC-06:01 | 1.75 |
Annual Sum or Average | 0.569407E+11 | 0.37 | |||
Minimum of Months | 0.318076E+10 | 0.30 | 11288.35 | 1.30 | |
Maximum of Months | 0.647117E+10 | 0.45 | 18123.48 | 1.76 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.942827E+11 | 1.35 | 35201.13 | 01-JAN-00:05 | 1.35 |
February | 0.851586E+11 | 1.35 | 35201.13 | 01-FEB-00:10 | 1.35 |
March | 0.942827E+11 | 1.35 | 35201.13 | 01-MAR-00:10 | 1.35 |
April | 0.912413E+11 | 1.35 | 35201.13 | 01-APR-00:10 | 1.35 |
May | 0.942827E+11 | 1.35 | 35201.13 | 01-MAY-00:03 | 1.35 |
June | 0.912413E+11 | 1.35 | 35201.13 | 01-JUN-00:10 | 1.35 |
July | 0.942827E+11 | 1.35 | 35201.13 | 01-JUL-00:05 | 1.35 |
August | 0.942827E+11 | 1.35 | 35201.13 | 01-AUG-00:05 | 1.35 |
September | 0.912413E+11 | 1.35 | 35201.13 | 01-SEP-00:03 | 1.35 |
October | 0.942827E+11 | 1.35 | 35201.13 | 01-OCT-00:10 | 1.35 |
November | 0.912413E+11 | 1.35 | 35201.13 | 01-NOV-00:10 | 1.35 |
December | 0.942827E+11 | 1.35 | 35201.13 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.111010E+13 | 1.35 | |||
Minimum of Months | 0.851586E+11 | 1.35 | 35201.13 | 1.35 | |
Maximum of Months | 0.942827E+11 | 1.35 | 35201.13 | 1.35 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.138056E+10 | 0.91 | 515.44 | 01-JAN-00:05 | 0.91 |
February | 0.124696E+10 | 0.91 | 515.44 | 01-FEB-00:10 | 0.91 |
March | 0.138056E+10 | 0.91 | 515.44 | 01-MAR-00:10 | 0.91 |
April | 0.133603E+10 | 0.91 | 515.44 | 01-APR-00:10 | 0.91 |
May | 0.138056E+10 | 0.91 | 515.44 | 01-MAY-00:03 | 0.91 |
June | 0.133603E+10 | 0.91 | 515.44 | 01-JUN-00:10 | 0.91 |
July | 0.138056E+10 | 0.91 | 515.44 | 01-JUL-00:05 | 0.91 |
August | 0.138056E+10 | 0.91 | 515.44 | 01-AUG-00:05 | 0.91 |
September | 0.133603E+10 | 0.91 | 515.44 | 01-SEP-00:03 | 0.91 |
October | 0.138056E+10 | 0.91 | 515.44 | 01-OCT-00:10 | 0.91 |
November | 0.133603E+10 | 0.91 | 515.44 | 01-NOV-00:10 | 0.91 |
December | 0.138056E+10 | 0.91 | 515.44 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.162550E+11 | 0.91 | |||
Minimum of Months | 0.124696E+10 | 0.91 | 515.44 | 0.91 | |
Maximum of Months | 0.138056E+10 | 0.91 | 515.44 | 0.91 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131030E+11 | 0.91 | 4892.12 | 01-JAN-00:05 | 0.91 |
February | 0.118350E+11 | 0.91 | 4892.12 | 01-FEB-00:10 | 0.91 |
March | 0.131030E+11 | 0.91 | 4892.12 | 01-MAR-00:10 | 0.91 |
April | 0.126804E+11 | 0.91 | 4892.12 | 01-APR-00:10 | 0.91 |
May | 0.131030E+11 | 0.91 | 4892.12 | 01-MAY-00:03 | 0.91 |
June | 0.126804E+11 | 0.91 | 4892.12 | 01-JUN-00:10 | 0.91 |
July | 0.131030E+11 | 0.91 | 4892.12 | 01-JUL-00:05 | 0.91 |
August | 0.131030E+11 | 0.91 | 4892.12 | 01-AUG-00:05 | 0.91 |
September | 0.126804E+11 | 0.91 | 4892.12 | 01-SEP-00:03 | 0.91 |
October | 0.131030E+11 | 0.91 | 4892.12 | 01-OCT-00:10 | 0.91 |
November | 0.126804E+11 | 0.91 | 4892.12 | 01-NOV-00:10 | 0.91 |
December | 0.131030E+11 | 0.91 | 4892.12 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.154278E+12 | 0.91 | |||
Minimum of Months | 0.118350E+11 | 0.91 | 4892.12 | 0.91 | |
Maximum of Months | 0.131030E+11 | 0.91 | 4892.12 | 0.91 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131656E+10 | 0.91 | 491.55 | 01-JAN-00:05 | 0.91 |
February | 0.118915E+10 | 0.91 | 491.55 | 01-FEB-00:10 | 0.91 |
March | 0.131656E+10 | 0.91 | 491.55 | 01-MAR-00:10 | 0.91 |
April | 0.127409E+10 | 0.91 | 491.55 | 01-APR-00:10 | 0.91 |
May | 0.131656E+10 | 0.91 | 491.55 | 01-MAY-00:03 | 0.91 |
June | 0.127409E+10 | 0.91 | 491.55 | 01-JUN-00:10 | 0.91 |
July | 0.131656E+10 | 0.91 | 491.55 | 01-JUL-00:05 | 0.91 |
August | 0.131656E+10 | 0.91 | 491.55 | 01-AUG-00:05 | 0.91 |
September | 0.127409E+10 | 0.91 | 491.55 | 01-SEP-00:03 | 0.91 |
October | 0.131656E+10 | 0.91 | 491.55 | 01-OCT-00:10 | 0.91 |
November | 0.127409E+10 | 0.91 | 491.55 | 01-NOV-00:10 | 0.91 |
December | 0.131656E+10 | 0.91 | 491.55 | 01-DEC-00:10 | 0.91 |
Annual Sum or Average | 0.155015E+11 | 0.91 | |||
Minimum of Months | 0.118915E+10 | 0.91 | 491.55 | 0.91 | |
Maximum of Months | 0.131656E+10 | 0.91 | 491.55 | 0.91 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.877187E+09 | 0.789468E+09 | 6057.83 | 10-JAN-06:03 | 5452.05 | 5452.05 | 77.80 | 9.23 |
February | 0.344220E+09 | 0.309798E+09 | 7193.62 | 06-FEB-06:01 | 6474.26 | 6474.26 | 73.30 | 11.86 |
March | 0.166146E+09 | 0.149531E+09 | 5004.26 | 09-MAR-07:10 | 4503.84 | 4503.84 | 67.89 | 7.23 |
April | 25173486.97 | 22656138.27 | 4169.25 | 19-APR-04:00 | 3752.32 | 3752.32 | 72.71 | 5.76 |
May | 28905126.56 | 26014613.90 | 4165.13 | 01-MAY-00:20 | 3748.62 | 3748.62 | 70.72 | 5.76 |
June | 11328818.18 | 10195936.36 | 4165.10 | 25-JUN-23:08 | 3748.59 | 3748.59 | 70.70 | 5.76 |
July | 29863165.35 | 26876848.82 | 4165.16 | 02-JUL-23:00 | 3748.65 | 3748.65 | 70.73 | 5.76 |
August | 21616364.82 | 19454728.34 | 4165.11 | 06-AUG-19:10 | 3748.60 | 3748.60 | 70.71 | 5.76 |
September | 29779370.94 | 26801433.85 | 4165.07 | 17-SEP-21:40 | 3748.56 | 3748.56 | 70.69 | 5.76 |
October | 34435139.50 | 30991625.55 | 4165.08 | 22-OCT-16:50 | 3748.57 | 3748.57 | 70.69 | 5.76 |
November | 56730548.10 | 51057493.29 | 4691.01 | 16-NOV-04:47 | 4221.91 | 4221.91 | 77.73 | 6.63 |
December | 0.152478E+09 | 0.137231E+09 | 6150.22 | 20-DEC-06:01 | 5535.20 | 5535.20 | 66.49 | 9.49 |
Annual Sum or Average | 0.177786E+10 | 0.160008E+10 | ||||||
Minimum of Months | 11328818.18 | 10195936.36 | 4165.07 | 3748.56 | 3748.56 | 66.49 | 5.76 | |
Maximum of Months | 0.877187E+09 | 0.789468E+09 | 7193.62 | 6474.26 | 6474.26 | 77.80 | 11.86 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.713354E+09 | 0.642019E+09 | 8668.35 | 19-JAN-06:02 | 7801.51 | 7801.51 | 8.90 | 76.87 |
February | 0.106878E+10 | 0.961901E+09 | 9177.70 | 03-FEB-06:02 | 8259.93 | 8259.93 | 8.51 | 78.72 |
March | 0.122193E+10 | 0.109974E+10 | 13125.32 | 07-MAR-06:02 | 11812.79 | 11812.79 | 8.18 | 91.24 |
April | 0.194867E+10 | 0.175380E+10 | 19105.41 | 24-APR-05:02 | 17194.87 | 17194.87 | 8.33 | 106.21 |
May | 0.338926E+10 | 0.305033E+10 | 27811.97 | 24-MAY-05:02 | 25030.77 | 25030.77 | 7.69 | 123.31 |
June | 0.329215E+10 | 0.296293E+10 | 19386.53 | 01-JUN-05:02 | 17447.88 | 17447.88 | 8.16 | 106.84 |
July | 0.333667E+10 | 0.300300E+10 | 21937.73 | 25-JUL-05:02 | 19743.96 | 19743.96 | 7.71 | 112.25 |
August | 0.364198E+10 | 0.327779E+10 | 26110.30 | 29-AUG-05:02 | 23499.27 | 23499.27 | 7.95 | 120.27 |
September | 0.338297E+10 | 0.304468E+10 | 26309.02 | 13-SEP-05:02 | 23678.12 | 23678.12 | 7.90 | 120.63 |
October | 0.279813E+10 | 0.251832E+10 | 26171.61 | 12-OCT-05:02 | 23554.45 | 23554.45 | 8.10 | 120.38 |
November | 0.156133E+10 | 0.140519E+10 | 19244.90 | 01-NOV-05:02 | 17320.41 | 17320.41 | 8.00 | 106.53 |
December | 0.111937E+10 | 0.100744E+10 | 17338.93 | 15-DEC-06:02 | 15605.04 | 15605.04 | 8.22 | 102.15 |
Annual Sum or Average | 0.274746E+11 | 0.247271E+11 | ||||||
Minimum of Months | 0.713354E+09 | 0.642019E+09 | 8668.35 | 7801.51 | 7801.51 | 7.69 | 76.87 | |
Maximum of Months | 0.364198E+10 | 0.327779E+10 | 27811.97 | 25030.77 | 25030.77 | 8.90 | 123.31 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967962.60 | 3590388.78 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 75.44 | 0.44 |
February | 10809772.67 | 3242931.80 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 59.90 | 0.44 |
March | 11967962.60 | 3590388.78 | 5.96 | 01-MAR-06:01 | 1.79 | 1.79 | 60.26 | 0.44 |
April | 11581899.29 | 3474569.79 | 5.96 | 01-APR-05:01 | 1.79 | 1.79 | 59.85 | 0.44 |
May | 11967962.60 | 3590388.78 | 5.96 | 01-MAY-05:01 | 1.79 | 1.79 | 80.20 | 0.44 |
June | 11581899.29 | 3474569.79 | 5.96 | 01-JUN-05:01 | 1.79 | 1.79 | 61.44 | 0.44 |
July | 11967962.60 | 3590388.78 | 5.96 | 01-JUL-05:01 | 1.79 | 1.79 | 61.94 | 0.44 |
August | 11967962.60 | 3590388.78 | 5.96 | 01-AUG-05:01 | 1.79 | 1.79 | 61.91 | 0.44 |
September | 11581899.29 | 3474569.79 | 5.96 | 01-SEP-05:01 | 1.79 | 1.79 | 62.09 | 0.44 |
October | 11967962.60 | 3590388.78 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 72.94 | 0.44 |
November | 11581899.29 | 3474569.79 | 5.96 | 01-NOV-05:01 | 1.79 | 1.79 | 60.80 | 0.44 |
December | 11967962.60 | 3590388.78 | 5.96 | 01-DEC-06:01 | 1.79 | 1.79 | 60.94 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273932.42 | ||||||
Minimum of Months | 10809772.67 | 3242931.80 | 5.96 | 1.79 | 1.79 | 59.85 | 0.44 | |
Maximum of Months | 11967962.60 | 3590388.78 | 5.96 | 1.79 | 1.79 | 80.20 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.954979E+10 | 0.859481E+10 | 10276.82 | 01-JAN-00:20 | 9249.14 | 9249.14 | 8.54 | 128.71 |
February | 0.115634E+11 | 0.104071E+11 | 10276.82 | 01-FEB-04:01 | 9249.14 | 9249.14 | 10.24 | 128.71 |
March | 0.142909E+11 | 0.128619E+11 | 10276.82 | 01-MAR-04:01 | 9249.14 | 9249.14 | 10.02 | 128.71 |
April | 0.194999E+11 | 0.175499E+11 | 10276.82 | 01-APR-03:01 | 9249.14 | 9249.14 | 9.95 | 128.71 |
May | 0.198611E+11 | 0.178750E+11 | 10276.82 | 01-MAY-00:20 | 9249.14 | 9249.14 | 7.75 | 128.71 |
June | 0.214611E+11 | 0.193150E+11 | 10276.82 | 01-JUN-03:01 | 9249.14 | 9249.14 | 10.21 | 128.71 |
July | 0.234875E+11 | 0.211387E+11 | 10276.82 | 01-JUL-00:42 | 9249.14 | 9249.14 | 7.18 | 128.71 |
August | 0.242969E+11 | 0.218672E+11 | 10276.82 | 01-AUG-00:32 | 9249.14 | 9249.14 | 7.17 | 128.71 |
September | 0.199698E+11 | 0.179728E+11 | 10276.82 | 01-SEP-00:03 | 9249.14 | 9249.14 | 7.20 | 128.71 |
October | 0.202927E+11 | 0.182634E+11 | 10276.82 | 01-OCT-07:42 | 9249.14 | 9249.14 | 9.11 | 128.71 |
November | 0.166748E+11 | 0.150073E+11 | 10276.82 | 01-NOV-01:32 | 9249.14 | 9249.14 | 9.54 | 128.71 |
December | 0.126495E+11 | 0.113845E+11 | 10276.82 | 01-DEC-04:01 | 9249.14 | 9249.14 | 8.67 | 128.71 |
Annual Sum or Average | 0.213597E+12 | 0.192238E+12 | ||||||
Minimum of Months | 0.954979E+10 | 0.859481E+10 | 10276.82 | 9249.14 | 9249.14 | 7.17 | 128.71 | |
Maximum of Months | 0.242969E+11 | 0.218672E+11 | 10276.82 | 9249.14 | 9249.14 | 10.24 | 128.71 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.896536E+10 | 0.806882E+10 | 3347.28 | 01-JAN-00:05 | 3012.55 | 3012.55 | 22.18 | 13.98 |
February | 0.809774E+10 | 0.728797E+10 | 3347.28 | 01-FEB-00:10 | 3012.55 | 3012.55 | 26.29 | 13.98 |
March | 0.896536E+10 | 0.806882E+10 | 3347.28 | 01-MAR-00:10 | 3012.55 | 3012.55 | 29.86 | 13.98 |
April | 0.867615E+10 | 0.780854E+10 | 3347.28 | 01-APR-00:10 | 3012.55 | 3012.55 | 37.05 | 13.98 |
May | 0.896536E+10 | 0.806882E+10 | 3347.28 | 01-MAY-00:03 | 3012.55 | 3012.55 | 34.09 | 13.98 |
June | 0.867615E+10 | 0.780854E+10 | 3347.28 | 01-JUN-00:10 | 3012.55 | 3012.55 | 31.51 | 13.98 |
July | 0.896536E+10 | 0.806882E+10 | 3347.28 | 01-JUL-00:05 | 3012.55 | 3012.55 | 37.33 | 13.98 |
August | 0.896536E+10 | 0.806882E+10 | 3347.28 | 01-AUG-00:05 | 3012.55 | 3012.55 | 41.63 | 13.98 |
September | 0.867615E+10 | 0.780854E+10 | 3347.28 | 01-SEP-00:03 | 3012.55 | 3012.55 | 35.96 | 13.98 |
October | 0.896536E+10 | 0.806882E+10 | 3347.28 | 01-OCT-00:10 | 3012.55 | 3012.55 | 30.75 | 13.98 |
November | 0.867615E+10 | 0.780854E+10 | 3347.28 | 01-NOV-00:10 | 3012.55 | 3012.55 | 34.13 | 13.98 |
December | 0.896536E+10 | 0.806882E+10 | 3347.28 | 01-DEC-00:10 | 3012.55 | 3012.55 | 30.04 | 13.98 |
Annual Sum or Average | 0.105560E+12 | 0.950039E+11 | ||||||
Minimum of Months | 0.809774E+10 | 0.728797E+10 | 3347.28 | 3012.55 | 3012.55 | 22.18 | 13.98 | |
Maximum of Months | 0.896536E+10 | 0.806882E+10 | 3347.28 | 3012.55 | 3012.55 | 41.63 | 13.98 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.189310E+11 | 0.170379E+11 | 38741.02 | 19-JAN-15:00 | 34866.92 | 34866.92 | 27.50 | 151.40 |
February | 0.236810E+11 | 0.213129E+11 | 38744.43 | 24-FEB-11:00 | 34869.99 | 34869.99 | 27.60 | 151.40 |
March | 0.292949E+11 | 0.263654E+11 | 38770.71 | 30-MAR-13:00 | 34893.64 | 34893.64 | 28.41 | 151.40 |
April | 0.411354E+11 | 0.370219E+11 | 38783.67 | 24-APR-10:10 | 34905.31 | 34905.31 | 28.90 | 151.40 |
May | 0.519946E+11 | 0.467952E+11 | 38783.67 | 01-MAY-05:03 | 34905.31 | 34905.31 | 29.32 | 151.40 |
June | 0.549678E+11 | 0.494710E+11 | 38783.67 | 01-JUN-09:00 | 34905.31 | 34905.31 | 28.83 | 151.40 |
July | 0.583572E+11 | 0.525215E+11 | 38783.67 | 01-JUL-05:03 | 34905.31 | 34905.31 | 29.04 | 151.40 |
August | 0.621999E+11 | 0.559799E+11 | 38783.67 | 01-AUG-07:20 | 34905.31 | 34905.31 | 29.08 | 151.40 |
September | 0.516469E+11 | 0.464823E+11 | 38783.67 | 01-SEP-06:30 | 34905.31 | 34905.31 | 28.96 | 151.40 |
October | 0.487334E+11 | 0.438601E+11 | 38783.67 | 04-OCT-08:30 | 34905.31 | 34905.31 | 28.82 | 151.40 |
November | 0.357679E+11 | 0.321911E+11 | 38783.67 | 01-NOV-07:40 | 34905.31 | 34905.31 | 28.87 | 151.40 |
December | 0.266111E+11 | 0.239500E+11 | 38783.67 | 11-DEC-14:50 | 34905.31 | 34905.31 | 29.00 | 151.40 |
Annual Sum or Average | 0.503321E+12 | 0.452989E+12 | ||||||
Minimum of Months | 0.189310E+11 | 0.170379E+11 | 38741.02 | 34866.92 | 34866.92 | 27.50 | 151.40 | |
Maximum of Months | 0.621999E+11 | 0.559799E+11 | 38783.67 | 34905.31 | 34905.31 | 29.32 | 151.40 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6216.72 | 38162.76 | 01-JAN-20:17 | 80.65 | 82.22 | 10956.71 | 43299.73 | 04-JAN-13:30 |
February | 5858.87 | 38198.73 | 26-FEB-23:50 | 80.67 | 82.22 | 10993.05 | 42335.89 | 01-FEB-12:40 |
March | 4801.40 | 38324.62 | 26-MAR-18:15 | 80.74 | 82.22 | 11357.65 | 41419.15 | 01-MAR-12:40 |
April | 6165.83 | 38532.29 | 30-APR-16:10 | 80.85 | 82.22 | 9832.60 | 39143.95 | 03-APR-11:30 |
May | 6259.11 | 38697.68 | 29-MAY-07:26 | 80.94 | 82.22 | 9417.93 | 36776.68 | 01-MAY-11:20 |
June | 5743.24 | 38807.94 | 25-JUN-08:40 | 81.00 | 82.22 | 8958.80 | 34302.57 | 01-JUN-11:20 |
July | 7494.00 | 38852.07 | 23-JUL-09:05 | 81.02 | 82.22 | 7737.18 | 32664.25 | 03-JUL-11:30 |
August | 5721.53 | 38843.55 | 06-AUG-09:04 | 81.02 | 82.22 | 8801.88 | 33340.47 | 31-AUG-12:00 |
September | 6577.40 | 38767.81 | 03-SEP-09:00 | 80.98 | 82.22 | 8641.93 | 35322.30 | 29-SEP-12:00 |
October | 6976.69 | 38629.99 | 01-OCT-15:26 | 80.90 | 82.22 | 9357.89 | 38042.92 | 31-OCT-11:50 |
November | 6818.59 | 38419.00 | 05-NOV-16:50 | 80.79 | 82.22 | 10239.38 | 40399.39 | 30-NOV-12:30 |
December | 6358.82 | 38266.07 | 03-DEC-20:20 | 80.71 | 82.22 | 10411.37 | 44467.64 | 20-DEC-12:30 |
Annual Sum or Average | 6251.72 | 9718.48 | ||||||
Minimum of Months | 4801.40 | 38162.76 | 80.65 | 82.22 | 7737.18 | 32664.25 | ||
Maximum of Months | 7494.00 | 38852.07 | 81.02 | 82.22 | 11357.65 | 44467.64 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 5.35 | 4640.29 | 04-JAN-11:50 | 79.87 | 79.87 | 5609.72 | 336305.96 | 10-JAN-07:10 |
February | 2.05 | 4834.21 | 06-FEB-04:01 | 81.00 | 81.00 | 4079.54 | 451010.24 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 70.52 | 70.52 | 3172.27 | 493956.66 | 22-MAR-03:50 |
April | 0.00 | 0.00 | 01-APR-00:10 | 70.54 | 70.54 | 509.92 | 291360.64 | 12-APR-03:50 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 70.73 | 70.73 | 547.41 | 214420.27 | 30-MAY-00:20 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 70.56 | 70.56 | 221.66 | 213097.85 | 01-JUN-03:47 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 70.69 | 70.69 | 565.17 | 213495.33 | 04-JUL-23:10 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 70.65 | 70.65 | 409.40 | 212471.27 | 13-AUG-22:48 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 70.60 | 70.60 | 584.61 | 214908.32 | 04-SEP-21:00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 70.64 | 70.64 | 683.50 | 309970.28 | 29-OCT-15:35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 70.27 | 70.27 | 911.50 | 336615.32 | 26-NOV-13:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 69.07 | 69.07 | 4650.58 | 627519.68 | 20-DEC-07:10 |
Annual Sum or Average | 0.61 | 1824.21 | ||||||
Minimum of Months | 0.00 | 0.00 | 69.07 | 69.07 | 221.66 | 212471.27 | ||
Maximum of Months | 5.35 | 4834.21 | 81.00 | 81.00 | 5609.72 | 627519.68 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 265549.27 | 1997032.04 | 19-JAN-06:02 | 11.59 | 7.88 | 15.10 | 188150.06 | 16-JAN-00:31 |
February | 414661.97 | 1978375.52 | 03-FEB-06:03 | 11.54 | 7.87 | 10.54 | 189475.49 | 20-FEB-01:21 |
March | 443949.04 | 2061299.22 | 07-MAR-06:02 | 11.37 | 7.54 | 50.44 | 167522.71 | 19-MAR-08:20 |
April | 701606.45 | 2218209.72 | 29-APR-05:02 | 11.34 | 7.23 | 0.99 | 12274.46 | 09-APR-23:02 |
May | 937712.29 | 2958598.31 | 24-MAY-05:03 | 12.44 | 6.96 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 972299.60 | 2621696.04 | 08-JUN-05:02 | 12.24 | 7.38 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 972915.20 | 2691137.66 | 25-JUL-05:03 | 12.02 | 7.03 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1005344.53 | 2847195.57 | 11-AUG-05:03 | 12.35 | 7.07 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 954888.59 | 2791912.58 | 06-SEP-05:03 | 12.31 | 7.13 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 824143.98 | 2740258.03 | 21-OCT-05:03 | 12.31 | 7.23 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 557194.82 | 2411859.25 | 01-NOV-05:03 | 11.79 | 7.31 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 375920.71 | 2256725.66 | 15-DEC-06:03 | 11.74 | 7.56 | 1.09 | 24348.57 | 09-DEC-23:02 |
Annual Sum or Average | 703511.79 | 6.55 | ||||||
Minimum of Months | 265549.27 | 1978375.52 | 11.34 | 6.96 | 0.00 | 0.00 | ||
Maximum of Months | 1005344.53 | 2958598.31 | 12.44 | 7.88 | 50.44 | 189475.49 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 217077.62 | 2581458.98 | 19-JAN-06:02 | 14.72 | 8.67 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 337636.97 | 2619977.84 | 03-FEB-06:02 | 14.65 | 8.25 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 358616.55 | 2909270.58 | 07-MAR-06:01 | 14.82 | 7.98 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 580066.46 | 3373428.61 | 24-APR-05:02 | 14.29 | 8.14 | 0.00 | 0.00 | 01-APR-00:10 |
May | 832368.39 | 3775297.49 | 24-MAY-05:02 | 14.01 | 7.50 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 854729.79 | 3295969.79 | 02-JUN-05:02 | 14.08 | 7.49 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 849948.11 | 3468363.74 | 25-JUL-05:02 | 14.08 | 7.53 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 894890.32 | 3674447.56 | 11-AUG-05:02 | 14.03 | 7.57 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 856738.91 | 4054890.46 | 05-SEP-03:02 | 15.19 | 7.35 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 711703.14 | 3655683.78 | 12-OCT-05:02 | 13.95 | 7.91 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 454646.31 | 3313866.98 | 01-NOV-05:02 | 14.13 | 7.79 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 313729.71 | 3160753.51 | 15-DEC-06:02 | 14.09 | 8.02 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 606486.65 | 0.00 | ||||||
Minimum of Months | 217077.62 | 2581458.98 | 13.95 | 7.35 | 0.00 | 0.00 | ||
Maximum of Months | 894890.32 | 4054890.46 | 15.19 | 8.67 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 227517.92 | 699698.55 | 02-JAN-15:00 | 32.59 | 28.65 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 419796.74 | 974609.68 | 02-FEB-13:10 | 38.09 | 31.13 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 643779.15 | 1274829.48 | 26-MAR-14:00 | 44.03 | 34.19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 1010883.12 | 1687743.65 | 28-APR-15:00 | 52.09 | 38.96 | 0.00 | 0.00 | 01-APR-00:10 |
May | 696663.63 | 1051206.33 | 28-MAY-16:00 | 39.61 | 35.60 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 943677.58 | 1348937.77 | 14-JUN-14:00 | 45.48 | 38.14 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1177529.25 | 1650034.77 | 21-JUL-16:00 | 51.36 | 40.69 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1365973.96 | 1835674.31 | 30-AUG-16:10 | 54.96 | 41.78 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 664563.32 | 1205372.76 | 09-SEP-17:00 | 42.66 | 38.27 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 770271.06 | 1301225.88 | 05-OCT-15:00 | 44.55 | 37.15 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 709095.36 | 1302398.09 | 02-NOV-13:00 | 44.57 | 34.35 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 788142.79 | 1506237.90 | 13-DEC-15:00 | 48.56 | 35.57 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 787307.13 | 0.00 | ||||||
Minimum of Months | 227517.92 | 699698.55 | 32.59 | 28.65 | 0.00 | 0.00 | ||
Maximum of Months | 1365973.96 | 1835674.31 | 54.96 | 41.78 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 267345.17 | 4048269.47 | 19-JAN-15:00 | 27.50 | 24.58 | 1358.62 | 168916.26 | 10-JAN-06:30 |
February | 424837.82 | 4114629.22 | 24-FEB-11:00 | 27.60 | 24.53 | 967.70 | 166077.23 | 17-FEB-06:40 |
March | 504372.55 | 4625562.50 | 30-MAR-13:00 | 28.41 | 25.56 | 839.67 | 127613.47 | 22-MAR-05:30 |
April | 878690.44 | 6392203.44 | 28-APR-16:00 | 31.20 | 28.15 | 383.71 | 108877.76 | 11-APR-03:01 |
May | 2142462.16 | 6599231.69 | 26-MAY-11:00 | 31.53 | 28.43 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 2438618.12 | 7050320.15 | 28-JUN-14:00 | 32.24 | 29.05 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 2761351.61 | 7371562.32 | 03-JUL-16:00 | 32.75 | 29.39 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 2769499.10 | 7302933.84 | 07-AUG-13:00 | 32.64 | 29.34 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 2331687.28 | 7196840.72 | 18-SEP-14:00 | 32.47 | 29.24 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 1737607.73 | 7510797.36 | 06-OCT-14:00 | 32.97 | 29.49 | 224.77 | 111256.54 | 27-OCT-06:40 |
November | 779769.95 | 6122476.41 | 01-NOV-13:20 | 30.77 | 27.62 | 540.54 | 96853.05 | 13-NOV-08:40 |
December | 499476.45 | 5702625.46 | 12-DEC-14:10 | 30.11 | 26.97 | 1158.39 | 150122.49 | 26-DEC-08:00 |
Annual Sum or Average | 1468230.11 | 454.38 | ||||||
Minimum of Months | 267345.17 | 4048269.47 | 27.50 | 24.53 | 0.00 | 0.00 | ||
Maximum of Months | 2769499.10 | 7510797.36 | 32.97 | 29.49 | 1358.62 | 168916.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 7.48 |
February | 0.35 | 7.48 |
March | 0.44 | 7.48 |
April | 0.74 | 7.14 |
May | 0.24 | 6.45 |
June | 0.25 | 7.48 |
July | 0.38 | 7.48 |
August | 0.29 | 7.48 |
September | 0.51 | 7.48 |
October | 0.62 | 7.48 |
November | 0.64 | 7.48 |
December | 1.30 | 7.10 |
Annual Sum or Average | 5.94 | 7.31 |
Minimum of Months | 0.17 | 6.45 |
Maximum of Months | 1.30 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.30 | 6.95 |
February | 4.16 | 4.68 |
March | 6.86 | 2.39 |
April | 19.16 | 2.01 |
May | 10.14 | 1.89 |
June | 19.88 | 1.69 |
July | 15.84 | 1.91 |
August | 15.24 | 1.66 |
September | 7.74 | 1.37 |
October | 16.56 | 2.00 |
November | 8.90 | 1.97 |
December | 12.24 | 2.39 |
Annual Sum or Average | 141.03 | 2.15 |
Minimum of Months | 4.16 | 1.37 |
Maximum of Months | 19.88 | 6.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.10 | 7.31 |
February | 1.14 | 5.17 |
March | 1.46 | 4.51 |
April | 2.50 | 2.65 |
May | 4.58 | 2.84 |
June | 4.76 | 2.52 |
July | 7.38 | 3.02 |
August | 5.68 | 2.29 |
September | 3.73 | 2.23 |
October | 5.39 | 4.99 |
November | 2.29 | 5.88 |
December | 1.43 | 7.11 |
Annual Sum or Average | 41.44 | 3.53 |
Minimum of Months | 1.10 | 2.23 |
Maximum of Months | 7.38 | 7.31 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.02 | 8.46 |
February | 0.63 | 6.27 |
March | 0.78 | 7.08 |
April | 2.11 | 6.25 |
May | 4.24 | 2.52 |
June | 6.07 | 3.14 |
July | 7.11 | 3.51 |
August | 6.04 | 2.28 |
September | 3.45 | 2.19 |
October | 3.60 | 4.48 |
November | 1.51 | 5.84 |
December | 0.55 | 4.33 |
Annual Sum or Average | 37.10 | 3.63 |
Minimum of Months | 0.55 | 2.19 |
Maximum of Months | 7.11 | 8.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.75 | 0.48 |
February | 2.25 | 0.35 |
March | 3.39 | 0.24 |
April | 8.20 | 0.28 |
May | 6.83 | 0.27 |
June | 12.36 | 0.25 |
July | 11.83 | 0.27 |
August | 12.74 | 0.22 |
September | 5.66 | 0.19 |
October | 9.15 | 0.27 |
November | 4.00 | 0.18 |
December | 4.44 | 0.56 |
Annual Sum or Average | 82.59 | 0.27 |
Minimum of Months | 1.75 | 0.18 |
Maximum of Months | 12.74 | 0.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 4.53 | 0.57 |
February | 4.23 | 0.31 |
March | 5.89 | 0.30 |
April | 16.47 | 0.21 |
May | 12.33 | 0.17 |
June | 19.05 | 0.18 |
July | 20.72 | 0.17 |
August | 25.78 | 0.12 |
September | 11.61 | 0.12 |
October | 14.22 | 0.18 |
November | 7.97 | 0.20 |
December | 8.60 | 0.26 |
Annual Sum or Average | 151.40 | 0.19 |
Minimum of Months | 4.23 | 0.12 |
Maximum of Months | 25.78 | 0.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.18 | 0.38 |
February | 2.26 | 0.23 |
March | 4.45 | 0.25 |
April | 11.46 | 0.27 |
May | 9.65 | 0.27 |
June | 13.96 | 0.24 |
July | 13.78 | 0.27 |
August | 15.05 | 0.22 |
September | 8.16 | 0.16 |
October | 10.50 | 0.19 |
November | 5.65 | 0.21 |
December | 6.21 | 0.40 |
Annual Sum or Average | 103.31 | 0.25 |
Minimum of Months | 2.18 | 0.16 |
Maximum of Months | 15.05 | 0.40 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 5.92 | 0.38 |
February | 5.12 | 0.28 |
March | 8.36 | 0.18 |
April | 22.00 | 0.16 |
May | 13.82 | 0.16 |
June | 21.54 | 0.17 |
July | 24.15 | 0.15 |
August | 28.33 | 0.13 |
September | 12.44 | 0.13 |
October | 17.57 | 0.15 |
November | 10.05 | 0.17 |
December | 13.36 | 0.18 |
Annual Sum or Average | 182.65 | 0.17 |
Minimum of Months | 5.12 | 0.13 |
Maximum of Months | 28.33 | 0.38 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.54 | 0.67 |
February | 1.01 | 0.52 |
March | 0.98 | 0.33 |
April | 1.64 | 0.41 |
May | 2.34 | 0.38 |
June | 2.61 | 0.28 |
July | 4.80 | 0.30 |
August | 3.40 | 0.38 |
September | 2.96 | 0.29 |
October | 2.48 | 0.27 |
November | 1.01 | 0.10 |
December | 0.53 | 7.59 |
Annual Sum or Average | 24.27 | 0.49 |
Minimum of Months | 0.53 | 0.10 |
Maximum of Months | 4.80 | 7.59 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.04 | 2.21 |
February | 3.00 | 0.92 |
March | 2.86 | 1.01 |
April | 4.91 | 0.37 |
May | 6.24 | 0.22 |
June | 7.91 | 0.27 |
July | 11.74 | 0.33 |
August | 8.07 | 0.24 |
September | 6.29 | 0.19 |
October | 6.04 | 0.26 |
November | 3.42 | 0.38 |
December | 1.89 | 1.18 |
Annual Sum or Average | 64.42 | 0.43 |
Minimum of Months | 1.89 | 0.19 |
Maximum of Months | 11.74 | 2.21 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.13 | 5.57 |
February | 1.10 | 1.27 |
March | 1.30 | 0.39 |
April | 2.13 | 0.47 |
May | 3.32 | 0.44 |
June | 3.78 | 0.40 |
July | 6.13 | 0.32 |
August | 4.29 | 0.38 |
September | 2.97 | 0.23 |
October | 2.30 | 0.39 |
November | 1.15 | 0.23 |
December | 0.74 | 5.55 |
Annual Sum or Average | 30.33 | 0.72 |
Minimum of Months | 0.74 | 0.23 |
Maximum of Months | 6.13 | 5.57 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.76 | 0.54 |
February | 2.11 | 0.42 |
March | 2.95 | 0.39 |
April | 5.41 | 0.37 |
May | 6.53 | 0.33 |
June | 8.66 | 0.34 |
July | 11.96 | 0.33 |
August | 7.87 | 0.30 |
September | 5.99 | 0.20 |
October | 5.64 | 0.27 |
November | 3.24 | 0.35 |
December | 2.18 | 1.46 |
Annual Sum or Average | 64.29 | 0.36 |
Minimum of Months | 1.76 | 0.20 |
Maximum of Months | 11.96 | 1.46 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.38 | 1.09 |
February | 0.65 | 0.93 |
March | 1.09 | 0.86 |
April | 1.80 | 0.91 |
May | 2.96 | 0.35 |
June | 4.33 | 0.32 |
July | 5.86 | 0.33 |
August | 4.34 | 0.26 |
September | 3.41 | 0.27 |
October | 2.19 | 0.23 |
November | 1.15 | 0.62 |
December | 0.26 | 0.58 |
Annual Sum or Average | 28.42 | 0.40 |
Minimum of Months | 0.26 | 0.23 |
Maximum of Months | 5.86 | 1.09 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.13 | 0.56 |
February | 1.56 | 0.67 |
March | 2.35 | 0.54 |
April | 4.12 | 0.46 |
May | 6.09 | 0.17 |
June | 7.94 | 0.19 |
July | 10.61 | 0.31 |
August | 7.77 | 0.17 |
September | 5.60 | 0.17 |
October | 5.15 | 0.27 |
November | 2.81 | 0.47 |
December | 1.00 | 0.55 |
Annual Sum or Average | 56.14 | 0.29 |
Minimum of Months | 1.00 | 0.17 |
Maximum of Months | 10.61 | 0.67 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.65 | 0.93 |
February | 0.84 | 6.81 |
March | 1.16 | 0.83 |
April | 2.17 | 0.82 |
May | 3.99 | 0.38 |
June | 5.11 | 0.36 |
July | 7.34 | 0.44 |
August | 4.90 | 0.30 |
September | 3.71 | 0.29 |
October | 2.64 | 0.61 |
November | 1.01 | 0.56 |
December | 0.26 | 0.47 |
Annual Sum or Average | 33.79 | 0.61 |
Minimum of Months | 0.26 | 0.29 |
Maximum of Months | 7.34 | 6.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.09 | 0.60 |
February | 1.14 | 0.70 |
March | 2.46 | 0.53 |
April | 4.67 | 0.49 |
May | 6.90 | 0.26 |
June | 9.14 | 0.29 |
July | 10.60 | 0.31 |
August | 8.12 | 0.24 |
September | 5.83 | 0.19 |
October | 4.13 | 0.21 |
November | 2.81 | 0.49 |
December | 0.94 | 0.45 |
Annual Sum or Average | 57.81 | 0.32 |
Minimum of Months | 0.94 | 0.19 |
Maximum of Months | 10.60 | 0.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 8.53 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 8.53 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 8.53 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.87 | 0.00 |
February | 1.27 | 0.00 |
March | 0.14 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.80 | 0.00 |
December | 1.21 | 0.00 |
Annual Sum or Average | 4.30 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.27 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.113588E+10 | 0.00 | 0.237464E+11 | 0.156967E+11 | 0.00 | 0.00 |
February | 0.126123E+10 | 0.00 | 0.284239E+11 | 0.137025E+11 | 0.00 | 0.00 |
March | 0.925458E+09 | 0.00 | 0.378867E+11 | 0.155942E+11 | 0.00 | 0.00 |
April | 0.111818E+10 | 0.00 | 0.589657E+11 | 0.143457E+11 | 0.00 | 0.00 |
May | 0.149705E+10 | 0.00 | 0.108467E+12 | 0.156486E+11 | 0.00 | 0.00 |
June | 0.583866E+09 | 0.00 | 0.112501E+12 | 0.151864E+11 | 0.00 | 0.00 |
July | 0.154378E+10 | 0.00 | 0.122143E+12 | 0.153398E+11 | 0.00 | 0.00 |
August | 0.111851E+10 | 0.00 | 0.132826E+12 | 0.166024E+11 | 0.00 | 0.00 |
September | 0.154421E+10 | 0.00 | 0.114807E+12 | 0.157771E+11 | 0.00 | 0.00 |
October | 0.175470E+10 | 0.00 | 0.996614E+11 | 0.162474E+11 | 0.00 | 0.00 |
November | 0.121090E+10 | 0.00 | 0.554520E+11 | 0.157567E+11 | 0.00 | 0.00 |
December | 0.185929E+10 | 0.00 | 0.363873E+11 | 0.158174E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.155531E+11 | 0.00 | 0.931269E+12 | 0.185715E+12 | 0.00 | 0.00 |
Minimum of Months | 0.583866E+09 | 0.00 | 0.237464E+11 | 0.137025E+11 | 0.00 | 0.00 |
Maximum of Months | 0.185929E+10 | 0.00 | 0.132826E+12 | 0.166024E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.369413E+09 | 0.00 | 0.432714E+11 | 0.529191E+10 | 0.00 | 0.00 |
February | 0.175426E+09 | 0.00 | 0.611315E+11 | 0.499918E+10 | 0.00 | 0.00 |
March | 0.123204E+09 | 0.00 | 0.766018E+11 | 0.614201E+10 | 0.00 | 0.00 |
April | 3874745.68 | 0.00 | 0.125320E+12 | 0.634575E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.164216E+12 | 0.608750E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.175905E+12 | 0.674042E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.191111E+12 | 0.721951E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.207811E+12 | 0.832488E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.167251E+12 | 0.581154E+10 | 0.00 | 0.00 |
October | 7559573.63 | 0.00 | 0.151535E+12 | 0.671871E+10 | 0.00 | 0.00 |
November | 9132098.99 | 0.00 | 0.942755E+11 | 0.628322E+10 | 0.00 | 0.00 |
December | 0.199834E+09 | 0.00 | 0.695551E+11 | 0.675432E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.888443E+09 | 0.00 | 0.152799E+13 | 0.767190E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.432714E+11 | 0.499918E+10 | 0.00 | 0.00 |
Maximum of Months | 0.369413E+09 | 0.00 | 0.207811E+12 | 0.832488E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.103447E+11 | 0.00 | 0.350125E+12 | 0.386766E+11 | 0.00 | 0.00 |
February | 0.639909E+10 | 0.00 | 0.491356E+12 | 0.347048E+11 | 0.00 | 0.00 |
March | 0.597627E+10 | 0.00 | 0.589342E+12 | 0.404699E+11 | 0.00 | 0.00 |
April | 0.203332E+09 | 0.00 | 0.938170E+12 | 0.404768E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.149428E+13 | 0.532438E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.151114E+13 | 0.542643E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.157611E+13 | 0.528687E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.163962E+13 | 0.566796E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.149624E+13 | 0.478938E+11 | 0.00 | 0.00 |
October | 72696057.17 | 0.00 | 0.126766E+13 | 0.505710E+11 | 0.00 | 0.00 |
November | 0.862468E+09 | 0.00 | 0.731981E+12 | 0.410691E+11 | 0.00 | 0.00 |
December | 0.826021E+10 | 0.00 | 0.513040E+12 | 0.392603E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.321188E+11 | 0.00 | 0.125991E+14 | 0.550179E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.350125E+12 | 0.347048E+11 | 0.00 | 0.00 |
Maximum of Months | 0.103447E+11 | 0.00 | 0.163962E+13 | 0.566796E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.342004E+10 | 0.00 | 0.344691E+11 | 0.325325E+10 | 0.00 | 0.00 |
February | 0.211928E+10 | 0.00 | 0.494645E+11 | 0.318076E+10 | 0.00 | 0.00 |
March | 0.157000E+10 | 0.00 | 0.611557E+11 | 0.375216E+10 | 0.00 | 0.00 |
April | 19197337.28 | 0.00 | 0.992689E+11 | 0.413327E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.163205E+12 | 0.606239E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167468E+12 | 0.635206E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.174327E+12 | 0.611952E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.178999E+12 | 0.647117E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.159714E+12 | 0.520282E+10 | 0.00 | 0.00 |
October | 35118331.22 | 0.00 | 0.134274E+12 | 0.533645E+10 | 0.00 | 0.00 |
November | 0.273451E+09 | 0.00 | 0.726729E+11 | 0.372770E+10 | 0.00 | 0.00 |
December | 0.227173E+10 | 0.00 | 0.503574E+11 | 0.334914E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.970882E+10 | 0.00 | 0.134538E+13 | 0.569407E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.344691E+11 | 0.318076E+10 | 0.00 | 0.00 |
Maximum of Months | 0.342004E+10 | 0.00 | 0.178999E+12 | 0.647117E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.556125E+09 | 0.00 | 0.389269E+12 | 0.178488E+12 | 0.00 | 0.53 |
February | 0.244998E+09 | 0.00 | 0.616522E+12 | 0.213210E+12 | 0.00 | 0.29 |
March | 68535325.38 | 0.00 | 0.982323E+12 | 0.298502E+12 | 0.00 | 0.33 |
April | 0.00 | 0.00 | 0.126932E+13 | 0.369441E+12 | 0.00 | 0.10 |
May | 0.00 | 0.00 | 0.428115E+12 | 0.204934E+12 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.719030E+12 | 0.275355E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.106463E+13 | 0.364491E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137748E+13 | 0.435309E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.417716E+12 | 0.197455E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.726890E+12 | 0.268774E+12 | 0.00 | 0.08 |
November | 78285894.79 | 0.00 | 0.965399E+12 | 0.296438E+12 | 0.00 | 0.16 |
December | 0.149915E+09 | 0.00 | 0.128097E+13 | 0.351529E+12 | 0.00 | 0.36 |
Annual Sum or Average | 0.109786E+10 | 0.00 | 0.102377E+14 | 0.345393E+13 | 0.00 | 1.85 |
Minimum of Months | 0.00 | 0.00 | 0.389269E+12 | 0.178488E+12 | 0.00 | 0.00 |
Maximum of Months | 0.556125E+09 | 0.00 | 0.137748E+13 | 0.435309E+12 | 0.00 | 0.53 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.616149E+10 | 0.267241E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.112253E+11 | 0.353345E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.186880E+11 | 0.519095E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.246783E+11 | 0.670473E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.720829E+10 | 0.326283E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.132003E+11 | 0.473454E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201768E+11 | 0.652289E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.267677E+11 | 0.805304E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.696147E+10 | 0.312639E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133731E+11 | 0.458301E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.183830E+11 | 0.519137E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.247620E+11 | 0.625943E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.191586E+12 | 0.598350E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.616149E+10 | 0.267241E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.267677E+11 | 0.805304E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.473092E+11 | 0.232189E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.974846E+11 | 0.319061E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.170007E+12 | 0.480087E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.232894E+12 | 0.634401E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.660896E+11 | 0.304212E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124704E+12 | 0.448133E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.192044E+12 | 0.620483E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.255162E+12 | 0.766906E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.625420E+11 | 0.288491E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.123762E+12 | 0.428689E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.167711E+12 | 0.480906E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.226121E+12 | 0.579783E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.176583E+13 | 0.558334E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.473092E+11 | 0.232189E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.255162E+12 | 0.766906E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.356049E+10 | 0.209998E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.888523E+10 | 0.304392E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.164009E+11 | 0.471461E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.231260E+11 | 0.633908E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.674169E+10 | 0.308605E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126417E+11 | 0.453634E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.193842E+11 | 0.626575E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.256507E+11 | 0.772420E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.634969E+10 | 0.291941E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.122977E+11 | 0.428960E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.161990E+11 | 0.472470E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.217349E+11 | 0.567413E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.172972E+12 | 0.554178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.356049E+10 | 0.209998E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.256507E+11 | 0.772420E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.156967E+11 | 0.237464E+11 | 0.113588E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137025E+11 | 0.284239E+11 | 0.126123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155942E+11 | 0.378867E+11 | 0.925458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143457E+11 | 0.589657E+11 | 0.111818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156486E+11 | 0.108467E+12 | 0.149705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151864E+11 | 0.112501E+12 | 0.583866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153398E+11 | 0.122143E+12 | 0.154378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166024E+11 | 0.132826E+12 | 0.111851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157771E+11 | 0.114807E+12 | 0.154421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162474E+11 | 0.996614E+11 | 0.175470E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157567E+11 | 0.554520E+11 | 0.121090E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158174E+11 | 0.363873E+11 | 0.185929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185715E+12 | 0.931269E+12 | 0.155531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.137025E+11 | 0.237464E+11 | 0.583866E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166024E+11 | 0.132826E+12 | 0.185929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.529191E+10 | 0.432714E+11 | 0.369413E+09 | 0.395251E+10 | 0.120155E+10 | 0.00 | 0.00 | 0.00 |
February | 0.499918E+10 | 0.611315E+11 | 0.175426E+09 | 0.174833E+10 | 0.201325E+10 | 0.00 | 0.00 | 0.00 |
March | 0.614201E+10 | 0.766018E+11 | 0.123204E+09 | 0.118013E+10 | 0.395853E+10 | 0.00 | 0.00 | 0.00 |
April | 0.634575E+10 | 0.125320E+12 | 3874745.68 | 0.00 | 0.107437E+11 | 0.00 | 0.00 | 0.00 |
May | 0.608750E+10 | 0.164216E+12 | 0.00 | 0.00 | 0.467176E+11 | 0.00 | 0.00 | 0.00 |
June | 0.674042E+10 | 0.175905E+12 | 0.00 | 0.00 | 0.563046E+11 | 0.00 | 0.00 | 0.00 |
July | 0.721951E+10 | 0.191111E+12 | 0.00 | 0.00 | 0.615415E+11 | 0.00 | 0.00 | 0.00 |
August | 0.832488E+10 | 0.207811E+12 | 0.00 | 0.00 | 0.609109E+11 | 0.00 | 0.00 | 0.00 |
September | 0.581154E+10 | 0.167251E+12 | 0.00 | 0.00 | 0.406487E+11 | 0.00 | 0.00 | 0.00 |
October | 0.671871E+10 | 0.151535E+12 | 7559573.63 | 17911522.71 | 0.341608E+11 | 0.00 | 0.00 | 0.00 |
November | 0.628322E+10 | 0.942755E+11 | 9132098.99 | 96195694.52 | 0.852052E+10 | 0.00 | 0.00 | 0.00 |
December | 0.675432E+10 | 0.695551E+11 | 0.199834E+09 | 0.122099E+10 | 0.445567E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767190E+11 | 0.152799E+13 | 0.888443E+09 | 0.821607E+10 | 0.331177E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.499918E+10 | 0.432714E+11 | 0.00 | 0.00 | 0.120155E+10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.832488E+10 | 0.207811E+12 | 0.369413E+09 | 0.395251E+10 | 0.615415E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.386766E+11 | 0.350125E+12 | 0.103447E+11 | 0.619587E+11 | 0.136680E+11 | 0.00 | 0.00 | 0.00 |
February | 0.347048E+11 | 0.491356E+12 | 0.639909E+10 | 0.293549E+11 | 0.223958E+11 | 0.00 | 0.00 | 0.00 |
March | 0.404699E+11 | 0.589342E+12 | 0.597627E+10 | 0.226645E+11 | 0.452500E+11 | 0.00 | 0.00 | 0.00 |
April | 0.404768E+11 | 0.938170E+12 | 0.203332E+09 | 0.317714E+09 | 0.106445E+12 | 0.00 | 0.00 | 0.00 |
May | 0.532438E+11 | 0.149428E+13 | 0.00 | 0.00 | 0.465976E+12 | 0.00 | 0.00 | 0.00 |
June | 0.542643E+11 | 0.151114E+13 | 0.00 | 0.00 | 0.560509E+12 | 0.00 | 0.00 | 0.00 |
July | 0.528687E+11 | 0.157611E+13 | 0.00 | 0.00 | 0.610531E+12 | 0.00 | 0.00 | 0.00 |
August | 0.566796E+11 | 0.163962E+13 | 0.00 | 0.00 | 0.603405E+12 | 0.00 | 0.00 | 0.00 |
September | 0.478938E+11 | 0.149624E+13 | 0.00 | 0.00 | 0.409930E+12 | 0.00 | 0.00 | 0.00 |
October | 0.505710E+11 | 0.126766E+13 | 72696057.17 | 0.105082E+10 | 0.340592E+12 | 0.00 | 0.00 | 0.00 |
November | 0.410691E+11 | 0.731981E+12 | 0.862468E+09 | 0.409416E+10 | 0.901086E+11 | 0.00 | 0.00 | 0.00 |
December | 0.392603E+11 | 0.513040E+12 | 0.826021E+10 | 0.364901E+11 | 0.462526E+11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550179E+12 | 0.125991E+14 | 0.321188E+11 | 0.155931E+12 | 0.331506E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.347048E+11 | 0.350125E+12 | 0.00 | 0.00 | 0.136680E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.566796E+11 | 0.163962E+13 | 0.103447E+11 | 0.619587E+11 | 0.610531E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.325325E+10 | 0.344691E+11 | 0.342004E+10 | 0.815056E+10 | 0.346919E+09 | 0.00 | 0.00 | 0.00 |
February | 0.318076E+10 | 0.494645E+11 | 0.211928E+10 | 0.381351E+10 | 0.110168E+10 | 0.00 | 0.00 | 0.00 |
March | 0.375216E+10 | 0.611557E+11 | 0.157000E+10 | 0.305657E+10 | 0.305906E+10 | 0.00 | 0.00 | 0.00 |
April | 0.413327E+10 | 0.992689E+11 | 19197337.28 | 45291063.21 | 0.919007E+10 | 0.00 | 0.00 | 0.00 |
May | 0.606239E+10 | 0.163205E+12 | 0.00 | 0.00 | 0.456174E+11 | 0.00 | 0.00 | 0.00 |
June | 0.635206E+10 | 0.167468E+12 | 0.00 | 0.00 | 0.544123E+11 | 0.00 | 0.00 | 0.00 |
July | 0.611952E+10 | 0.174327E+12 | 0.00 | 0.00 | 0.591450E+11 | 0.00 | 0.00 | 0.00 |
August | 0.647117E+10 | 0.178999E+12 | 0.00 | 0.00 | 0.587755E+11 | 0.00 | 0.00 | 0.00 |
September | 0.520282E+10 | 0.159714E+12 | 0.00 | 0.00 | 0.398221E+11 | 0.00 | 0.00 | 0.00 |
October | 0.533645E+10 | 0.134274E+12 | 35118331.22 | 0.108488E+09 | 0.333497E+11 | 0.00 | 0.00 | 0.00 |
November | 0.372770E+10 | 0.726729E+11 | 0.273451E+09 | 0.631202E+09 | 0.854353E+10 | 0.00 | 0.00 | 0.00 |
December | 0.334914E+10 | 0.503574E+11 | 0.227173E+10 | 0.573445E+10 | 0.414936E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569407E+11 | 0.134538E+13 | 0.970882E+10 | 0.215401E+11 | 0.317513E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.318076E+10 | 0.344691E+11 | 0.00 | 0.00 | 0.346919E+09 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.647117E+10 | 0.178999E+12 | 0.342004E+10 | 0.815056E+10 | 0.591450E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.942827E+11 | 0.330431E+12 | 0.556125E+09 | 0.00 | 0.00 | 0.142848E+10 | 0.00 | 0.00 |
February | 0.851586E+11 | 0.520607E+12 | 0.244998E+09 | 0.00 | 0.00 | 0.776296E+09 | 0.00 | 0.00 |
March | 0.942827E+11 | 0.820330E+12 | 68535325.38 | 0.00 | 0.00 | 0.893552E+09 | 0.00 | 0.00 |
April | 0.912413E+11 | 0.103512E+13 | 0.00 | 0.00 | 0.00 | 0.266250E+09 | 0.00 | 0.00 |
May | 0.942827E+11 | 0.345570E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.912413E+11 | 0.572689E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.942827E+11 | 0.838693E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.942827E+11 | 0.108300E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.912413E+11 | 0.338714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.942827E+11 | 0.590239E+12 | 0.00 | 0.00 | 0.00 | 0.203981E+09 | 0.00 | 0.00 |
November | 0.912413E+11 | 0.801286E+12 | 78285894.79 | 0.00 | 0.00 | 0.423071E+09 | 0.00 | 0.00 |
December | 0.942827E+11 | 0.106910E+13 | 0.149915E+09 | 0.00 | 0.00 | 0.959939E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.111010E+13 | 0.834578E+13 | 0.109786E+10 | 0.00 | 0.00 | 0.495157E+10 | 0.00 | 0.00 |
Minimum of Months | 0.851586E+11 | 0.330431E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942827E+11 | 0.108300E+13 | 0.556125E+09 | 0.00 | 0.00 | 0.142848E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.138056E+10 | 0.526794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124696E+10 | 0.952684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138056E+10 | 0.156940E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133603E+10 | 0.201723E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138056E+10 | 0.581149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133603E+10 | 0.105028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138056E+10 | 0.158804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138056E+10 | 0.209568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133603E+10 | 0.563745E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138056E+10 | 0.108754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133603E+10 | 0.153249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138056E+10 | 0.207850E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162550E+11 | 0.156435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124696E+10 | 0.526794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138056E+10 | 0.209568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131030E+11 | 0.404219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118350E+11 | 0.826816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131030E+11 | 0.142692E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126804E+11 | 0.190314E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131030E+11 | 0.532729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126804E+11 | 0.992115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131030E+11 | 0.151140E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131030E+11 | 0.199761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126804E+11 | 0.506368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131030E+11 | 0.100591E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126804E+11 | 0.139732E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131030E+11 | 0.189703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154278E+12 | 0.144016E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118350E+11 | 0.404219E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131030E+11 | 0.199761E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131656E+10 | 0.303450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118915E+10 | 0.752465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131656E+10 | 0.137499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127409E+10 | 0.188838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131656E+10 | 0.542985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127409E+10 | 0.100514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131656E+10 | 0.152473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131656E+10 | 0.200707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127409E+10 | 0.513638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131656E+10 | 0.998361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127409E+10 | 0.134819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131656E+10 | 0.182153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155015E+11 | 0.140809E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118915E+10 | 0.303450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131656E+10 | 0.200707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.156967E+11 | 0.113588E+10 | 0.237464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.137025E+11 | 0.126123E+10 | 0.284239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.155942E+11 | 0.925458E+09 | 0.378867E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143457E+11 | 0.111818E+10 | 0.589657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.156486E+11 | 0.149705E+10 | 0.108467E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.151864E+11 | 0.583866E+09 | 0.112501E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.153398E+11 | 0.154378E+10 | 0.122143E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166024E+11 | 0.111851E+10 | 0.132826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.157771E+11 | 0.154421E+10 | 0.114807E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.162474E+11 | 0.175470E+10 | 0.996614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.157567E+11 | 0.121090E+10 | 0.554520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158174E+11 | 0.185929E+10 | 0.363873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.185715E+12 | 0.155531E+11 | 0.931269E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.137025E+11 | 0.583866E+09 | 0.237464E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166024E+11 | 0.185929E+10 | 0.132826E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.529191E+10 | 0.369413E+09 | 0.432714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.499918E+10 | 0.175426E+09 | 0.611315E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.614201E+10 | 0.123204E+09 | 0.766018E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.634575E+10 | 3874745.68 | 0.125320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.608750E+10 | 0.00 | 0.164216E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.674042E+10 | 0.00 | 0.175905E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.721951E+10 | 0.00 | 0.191111E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.832488E+10 | 0.00 | 0.207811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.581154E+10 | 0.00 | 0.167251E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.671871E+10 | 7559573.63 | 0.151535E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.628322E+10 | 9132098.99 | 0.942755E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.675432E+10 | 0.199834E+09 | 0.695551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.767190E+11 | 0.888443E+09 | 0.152799E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.499918E+10 | 0.00 | 0.432714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.832488E+10 | 0.369413E+09 | 0.207811E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.386766E+11 | 0.103447E+11 | 0.350125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347048E+11 | 0.639909E+10 | 0.491356E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.404699E+11 | 0.597627E+10 | 0.589342E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.404768E+11 | 0.203332E+09 | 0.938170E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.532438E+11 | 0.00 | 0.149428E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.542643E+11 | 0.00 | 0.151114E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.528687E+11 | 0.00 | 0.157611E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.566796E+11 | 0.00 | 0.163962E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.478938E+11 | 0.00 | 0.149624E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.505710E+11 | 72696057.17 | 0.126766E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.410691E+11 | 0.862468E+09 | 0.731981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.392603E+11 | 0.826021E+10 | 0.513040E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550179E+12 | 0.321188E+11 | 0.125991E+14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.347048E+11 | 0.00 | 0.350125E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.566796E+11 | 0.103447E+11 | 0.163962E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.325325E+10 | 0.342004E+10 | 0.344691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.318076E+10 | 0.211928E+10 | 0.494645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.375216E+10 | 0.157000E+10 | 0.611557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.413327E+10 | 19197337.28 | 0.992689E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.606239E+10 | 0.00 | 0.163205E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.635206E+10 | 0.00 | 0.167468E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.611952E+10 | 0.00 | 0.174327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.647117E+10 | 0.00 | 0.178999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.520282E+10 | 0.00 | 0.159714E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.533645E+10 | 35118331.22 | 0.134274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.372770E+10 | 0.273451E+09 | 0.726729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.334914E+10 | 0.227173E+10 | 0.503574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.569407E+11 | 0.970882E+10 | 0.134538E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.318076E+10 | 0.00 | 0.344691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.647117E+10 | 0.342004E+10 | 0.178999E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.942827E+11 | 0.556125E+09 | 0.389269E+12 | 0.00 | 0.827699E+11 | 0.00 | 0.00 | 0.00 | 0.143491E+10 | 0.00 | 0.00 | 0.00 |
February | 0.851586E+11 | 0.244998E+09 | 0.616522E+12 | 0.00 | 0.127271E+12 | 0.00 | 0.00 | 0.00 | 0.779791E+09 | 0.00 | 0.00 | 0.00 |
March | 0.942827E+11 | 68535325.38 | 0.982323E+12 | 0.00 | 0.203322E+12 | 0.00 | 0.00 | 0.00 | 0.897574E+09 | 0.00 | 0.00 | 0.00 |
April | 0.912413E+11 | 0.00 | 0.126932E+13 | 0.00 | 0.277932E+12 | 0.00 | 0.00 | 0.00 | 0.267448E+09 | 0.00 | 0.00 | 0.00 |
May | 0.942827E+11 | 0.00 | 0.428115E+12 | 0.00 | 0.110651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.912413E+11 | 0.00 | 0.719030E+12 | 0.00 | 0.184114E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.942827E+11 | 0.00 | 0.106463E+13 | 0.00 | 0.270208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.942827E+11 | 0.00 | 0.137748E+13 | 0.00 | 0.341026E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.912413E+11 | 0.00 | 0.417716E+12 | 0.00 | 0.106214E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.942827E+11 | 0.00 | 0.726890E+12 | 0.00 | 0.174287E+12 | 0.00 | 0.00 | 0.00 | 0.204899E+09 | 0.00 | 0.00 | 0.00 |
November | 0.912413E+11 | 78285894.79 | 0.965399E+12 | 0.00 | 0.204772E+12 | 0.00 | 0.00 | 0.00 | 0.424975E+09 | 0.00 | 0.00 | 0.00 |
December | 0.942827E+11 | 0.149915E+09 | 0.128097E+13 | 0.00 | 0.256282E+12 | 0.00 | 0.00 | 0.00 | 0.964260E+09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111010E+13 | 0.109786E+10 | 0.102377E+14 | 0.00 | 0.233885E+13 | 0.00 | 0.00 | 0.00 | 0.497386E+10 | 0.00 | 0.00 | |
Minimum of Months | 0.851586E+11 | 0.00 | 0.389269E+12 | 0.00 | 0.827699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.942827E+11 | 0.556125E+09 | 0.137748E+13 | 0.00 | 0.341026E+12 | 0.00 | 0.00 | 0.00 | 0.143491E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.138056E+10 | 0.00 | 0.616149E+10 | 0.00 | 0.129185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124696E+10 | 0.00 | 0.112253E+11 | 0.00 | 0.228649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138056E+10 | 0.00 | 0.186880E+11 | 0.00 | 0.381039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133603E+10 | 0.00 | 0.246783E+11 | 0.00 | 0.536870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.138056E+10 | 0.00 | 0.720829E+10 | 0.00 | 0.188226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133603E+10 | 0.00 | 0.132003E+11 | 0.00 | 0.339851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.138056E+10 | 0.00 | 0.201768E+11 | 0.00 | 0.514233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.138056E+10 | 0.00 | 0.267677E+11 | 0.00 | 0.667248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133603E+10 | 0.00 | 0.696147E+10 | 0.00 | 0.179036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138056E+10 | 0.00 | 0.133731E+11 | 0.00 | 0.320245E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133603E+10 | 0.00 | 0.183830E+11 | 0.00 | 0.385534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.138056E+10 | 0.00 | 0.247620E+11 | 0.00 | 0.487887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162550E+11 | 0.00 | 0.191586E+12 | 0.00 | 0.435800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124696E+10 | 0.00 | 0.616149E+10 | 0.00 | 0.129185E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.138056E+10 | 0.00 | 0.267677E+11 | 0.00 | 0.667248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131030E+11 | 0.00 | 0.473092E+11 | 0.00 | 0.101158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118350E+11 | 0.00 | 0.974846E+11 | 0.00 | 0.200711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131030E+11 | 0.00 | 0.170007E+12 | 0.00 | 0.349057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126804E+11 | 0.00 | 0.232894E+12 | 0.00 | 0.507598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131030E+11 | 0.00 | 0.660896E+11 | 0.00 | 0.173181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126804E+11 | 0.00 | 0.124704E+12 | 0.00 | 0.321330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131030E+11 | 0.00 | 0.192044E+12 | 0.00 | 0.489452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131030E+11 | 0.00 | 0.255162E+12 | 0.00 | 0.635876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126804E+11 | 0.00 | 0.625420E+11 | 0.00 | 0.161687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131030E+11 | 0.00 | 0.123762E+12 | 0.00 | 0.297658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126804E+11 | 0.00 | 0.167711E+12 | 0.00 | 0.354103E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131030E+11 | 0.00 | 0.226121E+12 | 0.00 | 0.448752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154278E+12 | 0.00 | 0.176583E+13 | 0.00 | 0.404056E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118350E+11 | 0.00 | 0.473092E+11 | 0.00 | 0.101158E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131030E+11 | 0.00 | 0.255162E+12 | 0.00 | 0.635876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131656E+10 | 0.00 | 0.356049E+10 | 0.00 | 0.783413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118915E+10 | 0.00 | 0.888523E+10 | 0.00 | 0.185477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131656E+10 | 0.00 | 0.164009E+11 | 0.00 | 0.339805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127409E+10 | 0.00 | 0.231260E+11 | 0.00 | 0.506499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131656E+10 | 0.00 | 0.674169E+10 | 0.00 | 0.176949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.127409E+10 | 0.00 | 0.126417E+11 | 0.00 | 0.326225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131656E+10 | 0.00 | 0.193842E+11 | 0.00 | 0.494919E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131656E+10 | 0.00 | 0.256507E+11 | 0.00 | 0.640763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.127409E+10 | 0.00 | 0.634969E+10 | 0.00 | 0.164532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131656E+10 | 0.00 | 0.122977E+11 | 0.00 | 0.297304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.127409E+10 | 0.00 | 0.161990E+11 | 0.00 | 0.345060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131656E+10 | 0.00 | 0.217349E+11 | 0.00 | 0.435757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.155015E+11 | 0.00 | 0.172972E+12 | 0.00 | 0.399163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118915E+10 | 0.00 | 0.356049E+10 | 0.00 | 0.783413E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131656E+10 | 0.00 | 0.256507E+11 | 0.00 | 0.640763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.345718E+09 | 0.151282E+10 | 0.00 | 0.149271E+09 | 0.00 | 0.00 | 0.593699E+11 | 0.00 | 1.03 |
February | 0.259998E+09 | 0.154211E+10 | 0.00 | 0.127305E+09 | 4012832.42 | 0.00 | 0.451472E+11 | 0.00 | 1.14 |
March | 0.136238E+09 | 0.314683E+10 | 0.00 | 0.124219E+09 | 4540589.84 | 0.00 | 0.477528E+11 | 0.00 | 1.12 |
April | 0.160476E+09 | 0.556912E+10 | 0.00 | 85355908.86 | 71206125.10 | 0.00 | 0.221444E+11 | 0.00 | 0.98 |
May | 2313465.68 | 0.262077E+11 | 0.00 | 4431935.15 | 0.141668E+09 | 0.00 | 88733575.23 | 0.00 | 0.34 |
June | 2996977.36 | 0.316167E+11 | 0.00 | 3970211.68 | 0.203100E+09 | 0.00 | 0.125099E+09 | 0.00 | 0.35 |
July | 0.00 | 0.382885E+11 | 0.00 | 0.00 | 0.396682E+09 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.389069E+11 | 0.00 | 163302.00 | 0.221311E+09 | 0.00 | 8504493.57 | 0.00 | 0.34 |
September | 457141.85 | 0.291920E+11 | 0.00 | 2158951.75 | 0.285355E+09 | 0.00 | 94496686.26 | 0.00 | 0.34 |
October | 54686417.00 | 0.219797E+11 | 0.00 | 55460107.78 | 0.224931E+09 | 0.00 | 0.125018E+11 | 0.00 | 0.65 |
November | 0.119462E+09 | 0.653811E+10 | 0.00 | 0.142150E+09 | 6486277.33 | 0.00 | 0.384477E+11 | 0.00 | 1.16 |
December | 0.215419E+09 | 0.413559E+10 | 0.00 | 0.148870E+09 | 10987939.58 | 0.00 | 0.538445E+11 | 0.00 | 0.99 |
Annual Sum or Average | 0.129777E+10 | 0.208636E+12 | 0.00 | 0.843355E+09 | 0.157028E+10 | 0.00 | 0.279525E+12 | 0.00 | 0.73 |
Minimum of Months | 0.00 | 0.151282E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.345718E+09 | 0.389069E+11 | 0.00 | 0.149271E+09 | 0.396682E+09 | 0.00 | 0.593699E+11 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199836E+10 | 0.344018E+10 | 0.00 | 74552647.45 | 0.00 | 0.00 | 0.359044E+11 | 0.00 | 0.64 |
February | 0.188494E+10 | 0.392532E+10 | 0.00 | 62780316.46 | 50863723.17 | 0.00 | 0.231067E+11 | 0.00 | 0.65 |
March | 0.246153E+10 | 0.625164E+10 | 0.00 | 79497707.71 | 0.127925E+09 | 0.00 | 0.306623E+11 | 0.00 | 0.73 |
April | 0.349478E+10 | 0.980864E+10 | 0.00 | 36247238.36 | 0.124323E+09 | 0.00 | 0.829585E+10 | 0.00 | 0.65 |
May | 0.00 | 0.211836E+11 | 0.00 | 0.00 | 0.212037E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
June | 0.00 | 0.218755E+11 | 0.00 | 0.00 | 0.221710E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
July | 0.00 | 0.251068E+11 | 0.00 | 0.00 | 0.379205E+09 | 0.00 | 0.00 | 0.00 | 0.38 |
August | 5038658.19 | 0.261749E+11 | 0.00 | 0.00 | 0.239554E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
September | 0.00 | 0.258105E+11 | 0.00 | 0.00 | 0.409760E+09 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.853539E+09 | 0.167734E+11 | 0.00 | 23726631.26 | 0.261797E+09 | 0.00 | 0.651493E+10 | 0.00 | 0.50 |
November | 0.326684E+10 | 0.783208E+10 | 0.00 | 68534663.30 | 70849711.63 | 0.00 | 0.204982E+11 | 0.00 | 0.71 |
December | 0.374838E+10 | 0.653140E+10 | 0.00 | 80586614.07 | 0.118917E+09 | 0.00 | 0.349038E+11 | 0.00 | 0.70 |
Annual Sum or Average | 0.177134E+11 | 0.174714E+12 | 0.00 | 0.425926E+09 | 0.221694E+10 | 0.00 | 0.159886E+12 | 0.00 | 0.55 |
Minimum of Months | 0.00 | 0.344018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.374838E+10 | 0.261749E+11 | 0.00 | 80586614.07 | 0.409760E+09 | 0.00 | 0.359044E+11 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.490359E+11 | 0.273835E+11 | 0.00 | 0.404884E+09 | 0.509646E+10 | 0.00 | 0.238904E+12 | 0.00 | 0.53 |
February | 0.333792E+11 | 0.334404E+11 | 0.00 | 0.352221E+09 | 0.432009E+10 | 0.00 | 0.144450E+12 | 0.00 | 0.53 |
March | 0.292995E+11 | 0.511891E+11 | 0.00 | 0.480351E+09 | 0.812222E+10 | 0.00 | 0.205056E+12 | 0.00 | 0.59 |
April | 0.952898E+10 | 0.888830E+11 | 0.00 | 0.251017E+09 | 0.100673E+11 | 0.00 | 0.600889E+11 | 0.00 | 0.53 |
May | 0.00 | 0.199848E+12 | 0.00 | 0.00 | 0.115159E+11 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 6639277.76 | 0.209044E+12 | 0.00 | 1431432.96 | 0.102888E+11 | 0.00 | 2180889.56 | 0.00 | 0.42 |
July | 0.00 | 0.236456E+12 | 0.00 | 0.00 | 0.157142E+11 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.247417E+12 | 0.00 | 0.00 | 0.113923E+11 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.236676E+12 | 0.00 | 0.00 | 0.189888E+11 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.570158E+10 | 0.153939E+12 | 0.00 | 0.171806E+09 | 0.117646E+11 | 0.00 | 0.505199E+11 | 0.00 | 0.46 |
November | 0.252861E+11 | 0.695227E+11 | 0.00 | 0.398654E+09 | 0.431518E+10 | 0.00 | 0.136698E+12 | 0.00 | 0.57 |
December | 0.434936E+11 | 0.575986E+11 | 0.00 | 0.417681E+09 | 0.652649E+10 | 0.00 | 0.200146E+12 | 0.00 | 0.53 |
Annual Sum or Average | 0.195731E+12 | 0.161140E+13 | 0.00 | 0.247805E+10 | 0.118112E+12 | 0.00 | 0.103586E+13 | 0.00 | 0.48 |
Minimum of Months | 0.00 | 0.273835E+11 | 0.00 | 0.00 | 0.431518E+10 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.490359E+11 | 0.247417E+12 | 0.00 | 0.480351E+09 | 0.189888E+11 | 0.00 | 0.238904E+12 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.116139E+11 | 0.299152E+10 | 0.00 | 14127164.52 | 0.669925E+09 | 10171150.64 | 0.995080E+10 | 0.00 | 0.47 |
February | 0.676129E+10 | 0.348984E+10 | 0.00 | 16165912.67 | 0.736215E+09 | 83501594.47 | 0.722088E+10 | 0.00 | 0.49 |
March | 0.674747E+10 | 0.514885E+10 | 0.00 | 26919286.71 | 0.130124E+10 | 1531533.93 | 0.121132E+11 | 0.00 | 0.54 |
April | 0.168708E+10 | 0.867059E+10 | 0.00 | 18389710.46 | 0.131868E+10 | 0.00 | 0.437553E+10 | 0.00 | 0.50 |
May | 0.00 | 0.200030E+11 | 0.00 | 0.00 | 0.664840E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
June | 0.00 | 0.214792E+11 | 0.00 | 0.00 | 0.218757E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.248054E+11 | 0.00 | 0.00 | 0.499675E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
August | 0.00 | 0.253885E+11 | 0.00 | 0.00 | 0.332733E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
September | 0.00 | 0.237136E+11 | 0.00 | 0.00 | 0.160167E+10 | 0.00 | 0.00 | 0.00 | 0.41 |
October | 0.122281E+10 | 0.154107E+11 | 0.00 | 12256038.14 | 0.768109E+09 | 0.00 | 0.344885E+10 | 0.00 | 0.45 |
November | 0.514607E+10 | 0.595939E+10 | 0.00 | 21381720.55 | 0.146781E+10 | 0.00 | 0.781798E+10 | 0.00 | 0.51 |
December | 0.922466E+10 | 0.472792E+10 | 0.00 | 13563723.16 | 0.172935E+10 | 0.00 | 0.844370E+10 | 0.00 | 0.46 |
Annual Sum or Average | 0.424033E+11 | 0.161788E+12 | 0.00 | 0.122804E+09 | 0.113090E+11 | 95204279.04 | 0.533710E+11 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.299152E+10 | 0.00 | 0.00 | 0.218757E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.116139E+11 | 0.253885E+11 | 0.00 | 26919286.71 | 0.172935E+10 | 83501594.47 | 0.121132E+11 | 0.00 | 0.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.212200E+10 | 0.440360E+09 | 0.00 | 1886966.34 | 3404585.40 | 0.00 | 0.138479E+10 | 0.00 | 0.51 |
February | 0.134387E+10 | 0.512204E+09 | 0.00 | 2251570.31 | 7835919.58 | 0.00 | 0.109386E+10 | 0.00 | 0.56 |
March | 0.138454E+10 | 0.865762E+09 | 0.00 | 3753045.30 | 17088632.24 | 0.00 | 0.185168E+10 | 0.00 | 0.64 |
April | 0.623598E+09 | 0.144500E+10 | 0.00 | 2919939.40 | 16607353.22 | 0.00 | 0.712299E+09 | 0.00 | 0.68 |
May | 0.00 | 0.356617E+10 | 0.00 | 0.00 | 28324536.08 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.399250E+10 | 0.00 | 0.00 | 29616583.93 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.456047E+10 | 0.00 | 0.00 | 50655273.19 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 673077.54 | 0.453224E+10 | 0.00 | 0.00 | 32000333.41 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.403810E+10 | 0.00 | 0.00 | 54736873.03 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.282376E+09 | 0.264708E+10 | 0.00 | 1665849.08 | 34971602.43 | 0.00 | 0.539982E+09 | 0.00 | 0.57 |
November | 0.999543E+09 | 0.106167E+10 | 0.00 | 3743793.78 | 9464295.47 | 0.00 | 0.144343E+10 | 0.00 | 0.64 |
December | 0.181834E+10 | 0.841953E+09 | 0.00 | 2835797.13 | 17267546.80 | 0.00 | 0.163733E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.857494E+10 | 0.285035E+11 | 0.00 | 19056961.34 | 0.301974E+09 | 0.00 | 0.866337E+10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.440360E+09 | 0.00 | 0.00 | 3404585.40 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.212200E+10 | 0.456047E+10 | 0.00 | 3753045.30 | 54736873.03 | 0.00 | 0.185168E+10 | 0.00 | 0.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219700E+10 | 0.242939E+09 | 0.00 | 1556089.39 | 0.132442E+09 | 0.00 | 0.150642E+10 | 0.00 | 0.80 |
February | 0.142952E+10 | 0.317037E+09 | 0.00 | 1665793.50 | 0.122799E+09 | 0.00 | 0.108184E+10 | 0.00 | 0.85 |
March | 0.182563E+10 | 0.569773E+09 | 0.00 | 2693608.12 | 0.205569E+09 | 0.00 | 0.145488E+10 | 0.00 | 0.96 |
April | 0.859788E+09 | 0.977889E+09 | 0.00 | 2033130.90 | 0.287075E+09 | 0.00 | 0.559921E+09 | 0.00 | 0.96 |
May | 0.00 | 0.289718E+10 | 0.00 | 0.00 | 0.123155E+09 | 0.00 | 0.00 | 0.00 | 0.73 |
June | 0.00 | 0.306614E+10 | 0.00 | 0.00 | 69494205.99 | 0.00 | 0.00 | 0.00 | 0.74 |
July | 0.00 | 0.332394E+10 | 0.00 | 0.00 | 0.161875E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
August | 709325.04 | 0.306807E+10 | 0.00 | 0.00 | 0.255889E+09 | 0.00 | 0.00 | 0.00 | 0.66 |
September | 0.00 | 0.281581E+10 | 0.00 | 0.00 | 0.527082E+09 | 0.00 | 0.00 | 0.00 | 0.65 |
October | 0.424567E+09 | 0.192485E+10 | 0.00 | 977383.60 | 0.270059E+09 | 0.00 | 0.339958E+09 | 0.00 | 0.74 |
November | 0.140885E+10 | 0.629005E+09 | 0.00 | 2493014.40 | 0.261138E+09 | 0.00 | 0.100902E+10 | 0.00 | 0.90 |
December | 0.244127E+10 | 0.395692E+09 | 0.00 | 1459427.01 | 0.277415E+09 | 183952.85 | 0.998149E+09 | 0.00 | 0.81 |
Annual Sum or Average | 0.105873E+11 | 0.202283E+11 | 0.00 | 12878446.92 | 0.269399E+10 | 183952.85 | 0.695019E+10 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.242939E+09 | 0.00 | 0.00 | 69494205.99 | 0.00 | 0.00 | 0.00 | 0.65 |
Maximum of Months | 0.244127E+10 | 0.332394E+10 | 0.00 | 2693608.12 | 0.527082E+09 | 183952.85 | 0.150642E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.144854E+10 | 0.624646E+09 | 0.00 | 8798071.74 | 7006127.40 | 0.00 | 0.494924E+10 | 0.00 | 0.91 |
February | 0.109412E+10 | 0.853958E+09 | 0.00 | 5647924.39 | 8092962.29 | 0.00 | 0.271447E+10 | 0.00 | 0.88 |
March | 0.150641E+10 | 0.107448E+10 | 0.00 | 5471379.83 | 20294947.09 | 0.00 | 0.252735E+10 | 0.00 | 0.83 |
April | 0.768192E+09 | 0.158263E+10 | 0.00 | 2956262.83 | 27358765.07 | 0.00 | 0.697682E+09 | 0.00 | 0.76 |
May | 0.00 | 0.360910E+10 | 0.00 | 0.00 | 31806821.82 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.389829E+10 | 0.00 | 0.00 | 33257717.10 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.452100E+10 | 0.00 | 0.00 | 56882952.79 | 0.00 | 0.00 | 0.00 | 0.55 |
August | 755827.30 | 0.475870E+10 | 0.00 | 0.00 | 35934530.40 | 0.00 | 0.00 | 0.00 | 0.62 |
September | 0.00 | 0.464143E+10 | 0.00 | 0.00 | 61466354.20 | 0.00 | 0.00 | 0.00 | 0.61 |
October | 0.255949E+09 | 0.355011E+10 | 0.00 | 2709236.90 | 39271094.29 | 0.00 | 0.793868E+09 | 0.00 | 0.78 |
November | 0.746269E+09 | 0.154582E+10 | 0.00 | 9964407.97 | 10627858.44 | 0.00 | 0.312869E+10 | 0.00 | 1.04 |
December | 0.137940E+10 | 0.123312E+10 | 0.00 | 10318273.76 | 17838186.80 | 0.00 | 0.431267E+10 | 0.00 | 0.97 |
Annual Sum or Average | 0.719964E+10 | 0.318933E+11 | 0.00 | 45865557.41 | 0.349838E+09 | 0.00 | 0.191240E+11 | 0.00 | 0.76 |
Minimum of Months | 0.00 | 0.624646E+09 | 0.00 | 0.00 | 7006127.40 | 0.00 | 0.00 | 0.00 | 0.55 |
Maximum of Months | 0.150641E+10 | 0.475870E+10 | 0.00 | 10318273.76 | 61466354.20 | 0.00 | 0.494924E+10 | 0.00 | 1.04 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252226E+10 | 0.494763E+09 | 0.00 | 2778920.02 | 16838810.38 | 0.00 | 0.233926E+10 | 0.00 | 1.06 |
February | 0.114920E+10 | 0.643024E+09 | 0.00 | 4143016.91 | 9158970.08 | 0.00 | 0.220147E+10 | 0.00 | 1.17 |
March | 0.819583E+09 | 0.105491E+10 | 0.00 | 7948031.15 | 20102866.13 | 0.00 | 0.371802E+10 | 0.00 | 1.36 |
April | 0.534957E+09 | 0.199708E+10 | 0.00 | 6787551.34 | 11417706.94 | 0.00 | 0.135099E+10 | 0.00 | 1.47 |
May | 0.00 | 0.357469E+10 | 0.00 | 0.00 | 38181333.77 | 0.00 | 0.00 | 0.00 | 0.87 |
June | 0.00 | 0.405701E+10 | 0.00 | 0.00 | 24656034.47 | 0.00 | 0.00 | 0.00 | 0.97 |
July | 0.00 | 0.487967E+10 | 0.00 | 0.00 | 33459886.57 | 0.00 | 0.00 | 0.00 | 0.92 |
August | 760062.87 | 0.536954E+10 | 0.00 | 8570.88 | 26048049.00 | 0.00 | 138671.43 | 0.00 | 1.08 |
September | 0.00 | 0.417120E+10 | 0.00 | 0.00 | 67269677.01 | 0.00 | 0.00 | 0.00 | 0.83 |
October | 0.205828E+09 | 0.290573E+10 | 0.00 | 2357943.54 | 37504735.84 | 0.00 | 0.819869E+09 | 0.00 | 1.01 |
November | 0.683187E+09 | 0.129180E+10 | 0.00 | 7151912.57 | 10071006.36 | 0.00 | 0.263710E+10 | 0.00 | 1.31 |
December | 0.877993E+09 | 0.111447E+10 | 0.00 | 8110541.80 | 21413197.71 | 0.00 | 0.422687E+10 | 0.00 | 1.28 |
Annual Sum or Average | 0.679376E+10 | 0.315539E+11 | 0.00 | 39286488.21 | 0.316122E+09 | 0.00 | 0.172937E+11 | 0.00 | 1.11 |
Minimum of Months | 0.00 | 0.494763E+09 | 0.00 | 0.00 | 9158970.08 | 0.00 | 0.00 | 0.00 | 0.83 |
Maximum of Months | 0.252226E+10 | 0.536954E+10 | 0.00 | 8110541.80 | 67269677.01 | 0.00 | 0.422687E+10 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.252042E+11 | 0.268868E+10 | 0.00 | 1955125.43 | 0.120179E+10 | 0.119933E+10 | 0.211687E+10 | 0.00 | 0.45 |
February | 0.152599E+11 | 0.345724E+10 | 0.00 | 4610845.17 | 0.116144E+10 | 0.518284E+09 | 0.243957E+10 | 0.00 | 0.46 |
March | 0.178351E+11 | 0.595144E+10 | 0.00 | 9436528.38 | 0.174629E+10 | 0.280444E+09 | 0.501129E+10 | 0.00 | 0.51 |
April | 0.448150E+10 | 0.122960E+11 | 0.00 | 14278575.00 | 0.127823E+10 | 0.00 | 0.290150E+10 | 0.00 | 0.53 |
May | 0.00 | 0.346667E+11 | 0.00 | 0.00 | 0.271968E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 1060668.97 | 0.393128E+11 | 0.00 | 0.00 | 0.355983E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
July | 0.00 | 0.452464E+11 | 0.00 | 0.00 | 0.488041E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.442937E+11 | 0.00 | 0.00 | 0.308344E+09 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.382592E+11 | 0.00 | 0.00 | 0.608241E+09 | 0.00 | 0.00 | 0.00 | 0.51 |
October | 0.317333E+10 | 0.245641E+11 | 0.00 | 9896537.99 | 0.738735E+09 | 0.00 | 0.297381E+10 | 0.00 | 0.51 |
November | 0.126441E+11 | 0.827210E+10 | 0.00 | 11854180.20 | 0.128471E+10 | 0.00 | 0.420199E+10 | 0.00 | 0.50 |
December | 0.224895E+11 | 0.580417E+10 | 0.00 | 2385004.12 | 0.202132E+10 | 0.411273E+09 | 0.124047E+10 | 0.00 | 0.45 |
Annual Sum or Average | 0.101089E+12 | 0.264813E+12 | 0.00 | 54416796.27 | 0.114651E+11 | 0.240933E+10 | 0.208855E+11 | 0.00 | 0.52 |
Minimum of Months | 0.00 | 0.268868E+10 | 0.00 | 0.00 | 0.271968E+09 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.252042E+11 | 0.452464E+11 | 0.00 | 14278575.00 | 0.202132E+10 | 0.119933E+10 | 0.501129E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.294193E+11 | 0.160724E+10 | 0.00 | 1546690.43 | 0.249607E+10 | 0.972100E+09 | 0.271944E+10 | 0.00 | 0.78 |
February | 0.170823E+11 | 0.287357E+10 | 0.00 | 5075203.65 | 0.182657E+10 | 0.377962E+09 | 0.364758E+10 | 0.00 | 0.81 |
March | 0.191501E+11 | 0.518264E+10 | 0.00 | 14539514.28 | 0.291606E+10 | 0.320008E+09 | 0.793360E+10 | 0.00 | 0.90 |
April | 0.464712E+10 | 0.100644E+11 | 0.00 | 17164313.88 | 0.413502E+10 | 0.00 | 0.475823E+10 | 0.00 | 0.89 |
May | 0.00 | 0.297384E+11 | 0.00 | 0.00 | 0.225951E+10 | 0.00 | 0.00 | 0.00 | 0.79 |
June | 1231324.23 | 0.332492E+11 | 0.00 | 0.00 | 0.109543E+10 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.373865E+11 | 0.00 | 0.00 | 0.209633E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.350706E+11 | 0.00 | 0.00 | 0.325111E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.272422E+11 | 0.00 | 0.00 | 0.770677E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 0.423862E+10 | 0.189079E+11 | 0.00 | 6714029.79 | 0.472680E+10 | 0.00 | 0.236807E+10 | 0.00 | 0.76 |
November | 0.135822E+11 | 0.552878E+10 | 0.00 | 8981904.79 | 0.400232E+10 | 0.00 | 0.581519E+10 | 0.00 | 0.85 |
December | 0.250501E+11 | 0.311690E+10 | 0.00 | 2165437.32 | 0.472646E+10 | 0.502018E+09 | 0.247233E+10 | 0.00 | 0.77 |
Annual Sum or Average | 0.113171E+12 | 0.209968E+12 | 0.00 | 56187094.14 | 0.412384E+11 | 0.217209E+10 | 0.297144E+11 | 0.00 | 0.80 |
Minimum of Months | 0.00 | 0.160724E+10 | 0.00 | 0.00 | 0.109543E+10 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.294193E+11 | 0.373865E+11 | 0.00 | 17164313.88 | 0.770677E+10 | 0.972100E+09 | 0.793360E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.125346E+11 | 0.586757E+10 | 0.00 | 79606204.65 | 0.436418E+09 | 48913329.96 | 0.417454E+11 | 0.00 | 0.84 |
February | 0.935743E+10 | 0.878281E+10 | 0.00 | 46340094.77 | 0.106556E+09 | 0.117500E+09 | 0.206956E+11 | 0.00 | 0.81 |
March | 0.150787E+11 | 0.937630E+10 | 0.00 | 36904018.30 | 0.872637E+09 | 0.00 | 0.154648E+11 | 0.00 | 0.71 |
April | 0.460963E+10 | 0.144543E+11 | 0.00 | 19492094.48 | 0.117288E+10 | 0.00 | 0.400257E+10 | 0.00 | 0.63 |
May | 0.00 | 0.354265E+11 | 0.00 | 0.00 | 0.302631E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 1180256.12 | 0.383923E+11 | 0.00 | 0.00 | 0.396119E+09 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.451069E+11 | 0.00 | 0.00 | 0.543066E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.477291E+11 | 0.00 | 0.00 | 0.343109E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.456679E+11 | 0.00 | 0.00 | 0.856808E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.246273E+10 | 0.360374E+11 | 0.00 | 22856233.52 | 0.353233E+09 | 0.00 | 0.597553E+10 | 0.00 | 0.77 |
November | 0.624432E+10 | 0.150564E+11 | 0.00 | 86570406.63 | 0.393664E+09 | 0.00 | 0.239845E+11 | 0.00 | 0.94 |
December | 0.115929E+11 | 0.122344E+11 | 0.00 | 81196840.65 | 0.506428E+09 | 0.322557E+09 | 0.306295E+11 | 0.00 | 0.85 |
Annual Sum or Average | 0.618815E+11 | 0.314132E+12 | 0.00 | 0.372966E+09 | 0.628355E+10 | 0.488970E+09 | 0.142498E+12 | 0.00 | 0.71 |
Minimum of Months | 0.00 | 0.586757E+10 | 0.00 | 0.00 | 0.106556E+09 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.150787E+11 | 0.477291E+11 | 0.00 | 86570406.63 | 0.117288E+10 | 0.322557E+09 | 0.417454E+11 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286383E+11 | 0.270566E+10 | 0.00 | 7187634.10 | 0.185541E+10 | 0.527132E+09 | 0.572921E+10 | 0.00 | 0.83 |
February | 0.176917E+11 | 0.409587E+10 | 0.00 | 7591510.56 | 0.134800E+10 | 0.263151E+09 | 0.429755E+10 | 0.00 | 0.87 |
March | 0.221413E+11 | 0.547051E+10 | 0.00 | 15150303.29 | 0.261232E+10 | 10262186.12 | 0.672639E+10 | 0.00 | 0.95 |
April | 0.532191E+10 | 0.126878E+11 | 0.00 | 14543593.98 | 0.238287E+10 | 0.00 | 0.365938E+10 | 0.00 | 0.94 |
May | 0.00 | 0.297459E+11 | 0.00 | 0.00 | 0.193815E+10 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 1282030.73 | 0.336323E+11 | 0.00 | 0.00 | 0.668545E+09 | 0.00 | 0.00 | 0.00 | 0.83 |
July | 0.00 | 0.379377E+11 | 0.00 | 0.00 | 0.121460E+10 | 0.00 | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.394027E+11 | 0.00 | 0.00 | 0.106181E+10 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 0.00 | 0.308551E+11 | 0.00 | 0.00 | 0.576334E+10 | 0.00 | 0.00 | 0.00 | 0.74 |
October | 0.428573E+10 | 0.220736E+11 | 0.00 | 7461296.39 | 0.243717E+10 | 0.00 | 0.270762E+10 | 0.00 | 0.81 |
November | 0.161738E+11 | 0.715573E+10 | 0.00 | 11978824.43 | 0.297519E+10 | 0.00 | 0.445354E+10 | 0.00 | 0.91 |
December | 0.252373E+11 | 0.539429E+10 | 0.00 | 7195353.20 | 0.329743E+10 | 0.475628E+09 | 0.385365E+10 | 0.00 | 0.83 |
Annual Sum or Average | 0.119491E+12 | 0.231157E+12 | 0.00 | 71108515.94 | 0.275548E+11 | 0.127617E+10 | 0.314273E+11 | 0.00 | 0.84 |
Minimum of Months | 0.00 | 0.270566E+10 | 0.00 | 0.00 | 0.668545E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.286383E+11 | 0.394027E+11 | 0.00 | 15150303.29 | 0.576334E+10 | 0.527132E+09 | 0.672639E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.228349E+10 | 0.275354E+09 | 0.00 | 14735.17 | 0.200296E+09 | 0.499894E+09 | 36231027.22 | 0.00 | 0.49 |
February | 0.141561E+10 | 0.358329E+09 | 0.00 | 179241.84 | 0.188563E+09 | 0.251023E+09 | 0.127738E+09 | 0.00 | 0.50 |
March | 0.183565E+10 | 0.613830E+09 | 0.00 | 558059.20 | 0.260689E+09 | 0.197113E+09 | 0.307487E+09 | 0.00 | 0.55 |
April | 0.489512E+09 | 0.114070E+10 | 0.00 | 1195818.97 | 0.285407E+09 | 0.00 | 0.262792E+09 | 0.00 | 0.54 |
May | 0.00 | 0.340458E+10 | 0.00 | 0.00 | 30182265.02 | 0.00 | 0.00 | 0.00 | 0.56 |
June | 0.00 | 0.385446E+10 | 0.00 | 0.00 | 43045715.49 | 0.00 | 0.00 | 0.00 | 0.61 |
July | 0.00 | 0.449703E+10 | 0.00 | 0.00 | 65769662.11 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.435584E+10 | 0.00 | 0.00 | 73394882.97 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 0.00 | 0.366537E+10 | 0.00 | 0.00 | 0.261547E+09 | 0.00 | 0.00 | 0.00 | 0.52 |
October | 0.338794E+09 | 0.236484E+10 | 0.00 | 744997.24 | 0.144684E+09 | 0.00 | 0.239937E+09 | 0.00 | 0.52 |
November | 0.132056E+10 | 0.699054E+09 | 440780.64 | 654893.28 | 0.310679E+09 | 40679926.60 | 0.279741E+09 | 196.78 | 0.53 |
December | 0.194945E+10 | 0.493910E+09 | 276217.73 | 69125.39 | 0.353425E+09 | 0.359892E+09 | 40910702.83 | 320.21 | 0.49 |
Annual Sum or Average | 0.963306E+10 | 0.257233E+11 | 716998.37 | 3416871.08 | 0.221768E+10 | 0.134860E+10 | 0.129484E+10 | 516.99 | 0.54 |
Minimum of Months | 0.00 | 0.275354E+09 | 0.00 | 0.00 | 30182265.02 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.228349E+10 | 0.449703E+10 | 440780.64 | 1195818.97 | 0.353425E+09 | 0.499894E+09 | 0.307487E+09 | 320.21 | 0.61 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259514E+10 | 0.205282E+09 | 0.00 | 7660.98 | 0.260481E+09 | 0.329000E+09 | 14227640.66 | 0.00 | 0.79 |
February | 0.155221E+10 | 0.330974E+09 | 0.00 | 317427.90 | 0.195184E+09 | 0.128288E+09 | 0.186184E+09 | 0.00 | 0.80 |
March | 0.157180E+10 | 0.588621E+09 | 0.00 | 1167486.77 | 0.292692E+09 | 0.190519E+09 | 0.694042E+09 | 0.00 | 0.89 |
April | 0.376797E+09 | 0.103956E+10 | 0.00 | 1687425.59 | 0.400167E+09 | 0.00 | 0.481231E+09 | 0.00 | 0.87 |
May | 0.00 | 0.287397E+10 | 0.00 | 0.00 | 0.205493E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
June | 0.00 | 0.323292E+10 | 0.00 | 0.00 | 0.114508E+09 | 0.00 | 0.00 | 0.00 | 0.81 |
July | 0.00 | 0.370884E+10 | 0.00 | 0.00 | 0.199241E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
August | 0.00 | 0.349752E+10 | 0.00 | 0.00 | 0.267323E+09 | 0.00 | 0.00 | 0.00 | 0.78 |
September | 0.00 | 0.277406E+10 | 0.00 | 0.00 | 0.684691E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
October | 0.360548E+09 | 0.185827E+10 | 0.00 | 605973.54 | 0.453823E+09 | 0.00 | 0.218396E+09 | 0.00 | 0.75 |
November | 0.125122E+10 | 0.545411E+09 | 0.00 | 569122.56 | 0.437949E+09 | 14902872.82 | 0.430887E+09 | 0.00 | 0.83 |
December | 0.211879E+10 | 0.294743E+09 | 0.00 | 66370.86 | 0.517753E+09 | 0.264714E+09 | 66856390.48 | 0.00 | 0.77 |
Annual Sum or Average | 0.982652E+10 | 0.209502E+11 | 0.00 | 4421468.19 | 0.402930E+10 | 0.927423E+09 | 0.209183E+10 | 0.00 | 0.79 |
Minimum of Months | 0.00 | 0.205282E+09 | 0.00 | 0.00 | 0.114508E+09 | 0.00 | 0.00 | 0.00 | 0.70 |
Maximum of Months | 0.259514E+10 | 0.370884E+10 | 0.00 | 1687425.59 | 0.684691E+09 | 0.329000E+09 | 0.694042E+09 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118618E+10 | 0.670801E+09 | 0.00 | 5437326.69 | 87238842.79 | 0.223763E+09 | 0.316444E+10 | 0.00 | 0.78 |
February | 0.916580E+09 | 0.928388E+09 | 0.00 | 3396139.91 | 70450993.28 | 0.124020E+09 | 0.161246E+10 | 0.00 | 0.77 |
March | 0.152928E+10 | 0.980805E+09 | 0.00 | 2918517.61 | 0.157829E+09 | 0.171912E+09 | 0.125777E+10 | 0.00 | 0.72 |
April | 0.484439E+09 | 0.133192E+10 | 0.00 | 1720002.21 | 0.294417E+09 | 0.00 | 0.388734E+09 | 0.00 | 0.63 |
May | 0.00 | 0.346024E+10 | 0.00 | 0.00 | 59503048.76 | 0.00 | 0.00 | 0.00 | 0.57 |
June | 0.00 | 0.376561E+10 | 0.00 | 0.00 | 69681589.55 | 0.00 | 0.00 | 0.00 | 0.60 |
July | 0.00 | 0.446664E+10 | 0.00 | 0.00 | 97662353.31 | 0.00 | 0.00 | 0.00 | 0.56 |
August | 0.00 | 0.464445E+10 | 0.00 | 0.00 | 0.103611E+09 | 0.00 | 0.00 | 0.00 | 0.64 |
September | 0.00 | 0.437654E+10 | 0.00 | 0.00 | 0.264168E+09 | 0.00 | 0.00 | 0.00 | 0.62 |
October | 0.275609E+09 | 0.346350E+10 | 0.00 | 1824045.09 | 62259287.33 | 0.00 | 0.497166E+09 | 0.00 | 0.76 |
November | 0.748699E+09 | 0.140730E+10 | 0.00 | 6290987.64 | 0.147982E+09 | 0.00 | 0.201604E+10 | 0.00 | 0.90 |
December | 0.129726E+10 | 0.115354E+10 | 0.00 | 5574394.35 | 0.150644E+09 | 0.136977E+09 | 0.226722E+10 | 0.00 | 0.82 |
Annual Sum or Average | 0.643805E+10 | 0.306497E+11 | 0.00 | 27161413.50 | 0.156545E+10 | 0.656672E+09 | 0.112038E+11 | 0.00 | 0.70 |
Minimum of Months | 0.00 | 0.670801E+09 | 0.00 | 0.00 | 59503048.76 | 0.00 | 0.00 | 0.00 | 0.56 |
Maximum of Months | 0.152928E+10 | 0.464445E+10 | 0.00 | 6290987.64 | 0.294417E+09 | 0.223763E+09 | 0.316444E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.250786E+10 | 0.262330E+09 | 0.00 | 415394.60 | 0.282378E+09 | 0.331467E+09 | 0.426597E+09 | 0.00 | 0.88 |
February | 0.161509E+10 | 0.413622E+09 | 0.00 | 545452.72 | 0.221082E+09 | 0.152740E+09 | 0.319686E+09 | 0.00 | 0.91 |
March | 0.201648E+10 | 0.566135E+09 | 0.00 | 1388951.68 | 0.340870E+09 | 0.159495E+09 | 0.619151E+09 | 0.00 | 0.99 |
April | 0.550012E+09 | 0.118990E+10 | 0.00 | 1347889.45 | 0.383330E+09 | 0.00 | 0.341672E+09 | 0.00 | 0.95 |
May | 0.00 | 0.268787E+10 | 0.00 | 0.00 | 0.397329E+09 | 0.00 | 0.00 | 0.00 | 0.77 |
June | 0.00 | 0.314948E+10 | 0.00 | 0.00 | 0.188824E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
July | 0.00 | 0.368264E+10 | 0.00 | 0.00 | 0.184551E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
August | 0.00 | 0.375207E+10 | 0.00 | 0.00 | 0.221364E+09 | 0.00 | 0.00 | 0.00 | 0.82 |
September | 0.00 | 0.293608E+10 | 0.00 | 0.00 | 0.752210E+09 | 0.00 | 0.00 | 0.00 | 0.75 |
October | 0.454700E+09 | 0.200517E+10 | 0.00 | 594166.69 | 0.430351E+09 | 0.00 | 0.197894E+09 | 0.00 | 0.82 |
November | 0.151216E+10 | 0.618727E+09 | 0.00 | 989763.02 | 0.465497E+09 | 272961.93 | 0.407379E+09 | 0.00 | 0.93 |
December | 0.223312E+10 | 0.442893E+09 | 0.00 | 492922.17 | 0.502221E+09 | 0.191718E+09 | 0.306075E+09 | 0.00 | 0.87 |
Annual Sum or Average | 0.108894E+11 | 0.217069E+11 | 0.00 | 5774540.33 | 0.437001E+10 | 0.835693E+09 | 0.261845E+10 | 0.00 | 0.85 |
Minimum of Months | 0.00 | 0.262330E+09 | 0.00 | 0.00 | 0.184551E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
Maximum of Months | 0.250786E+10 | 0.375207E+10 | 0.00 | 1388951.68 | 0.752210E+09 | 0.331467E+09 | 0.619151E+09 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:04:07
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.911782E+09 | 0.00 | 0.161364E+09 | 0.00 | 0.00 | 0.716366E+10 | 0.00 | 0.32 |
February | 0.00 | 0.120519E+10 | 0.00 | 0.216891E+09 | 0.00 | 0.00 | 0.380540E+10 | 0.00 | 0.32 |
March | 0.00 | 0.191304E+10 | 0.00 | 0.427372E+09 | 0.00 | 0.00 | 0.446869E+10 | 0.00 | 0.34 |
April | 0.00 | 0.351818E+10 | 0.00 | 0.212438E+09 | 0.00 | 0.00 | 0.949534E+09 | 0.00 | 0.32 |
May | 0.00 | 0.102271E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
June | 0.00 | 0.118740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
July | 0.00 | 0.134489E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
August | 0.00 | 0.128205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
September | 0.00 | 0.104240E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
October | 0.00 | 0.802048E+10 | 0.00 | 74854985.62 | 0.00 | 0.00 | 0.908757E+09 | 0.00 | 0.32 |
November | 0.00 | 0.282433E+10 | 0.00 | 0.316503E+09 | 0.00 | 0.00 | 0.242149E+10 | 0.00 | 0.32 |
December | 0.00 | 0.201545E+10 | 0.00 | 0.546086E+09 | 0.00 | 0.00 | 0.493636E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 0.792029E+11 | 0.00 | 0.195551E+10 | 0.00 | 0.00 | 0.246539E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.911782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.134489E+11 | 0.00 | 0.546086E+09 | 0.00 | 0.00 | 0.716366E+10 | 0.00 | 0.35 |