Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:56
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:57:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 28525.12 | 615.82 | 615.82 |
Net Site Energy | 28525.12 | 615.82 | 615.82 |
Total Source Energy | 87550.57 | 1890.11 | 1890.11 |
Net Source Energy | 87550.57 | 1890.11 | 1890.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 766.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2661.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3314.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 657.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1987.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2164.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 298.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 873.63 | 0.00 | 0.00 | 0.00 | 0.00 | 1981.84 |
Humidification | 15.23 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 572.26 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27186.43 | 1338.69 | 0.00 | 0.00 | 0.00 | 4267.67 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 766.44 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 383.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2278.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 3314.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 657.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2164.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 298.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 25.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 848.02 | 0.00 | 0.00 | 0.00 | 0.00 | 1981.84 | |
Humidification | General | 15.23 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 572.26 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 129.82 | 28.90 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 371.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 586.92 | 28.90 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 129.82 | 28.90 | 0.00 | 0.00 | 0.00 | 0.09 |
Other | 371.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 586.92 | 28.90 | 0.00 | 0.00 | 0.00 | 0.09 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27186.431 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27186.431 | 100.00 |
Total On-Site and Utility Electric Sources | 27186.431 | 100.00 |
Total Electricity End Uses | 27186.431 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 4267.67 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 4267.67 | 100.00 |
Total Water End Uses | 4267.67 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 9.00 |
Time Setpoint Not Met During Occupied Cooling | 49.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1309.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:56 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.9438 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.9438 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.9438 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.9438 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 29-AUG-15:09 | 02-JAN-06:10 | - | - | - | 10-AUG-15:00 |
Heating | 0.00 | 959875.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 404624.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 283563.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 91242.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 137669.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 40790.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78938.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1830833.37 | 965571.26 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 959875.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 236096.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 283563.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5423.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 137669.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 40790.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 29690.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 830.82 | 0.00 | 0.00 | 0.00 |
Cooling | 8429.95 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10497.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2080.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6295.90 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6853.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 945.56 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2766.77 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 48.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 620.33 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 86099.43 | 1451.14 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.94 | 0.00 | 0.00 | 0.00 |
Cooling | 181.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 226.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 59.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.39 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1858.78 | 31.33 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 17.94 | 0.00 | 0.00 | 0.00 |
Cooling | 181.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 226.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 147.97 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 20.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 59.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.39 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1858.78 | 31.33 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.42 |
DATACENTER BOT DIRECT AIR | 0.493003 |
DATACENTER MID DIRECT AIR | 4.71 |
DATACENTER TOP DIRECT AIR | 0.478356 |
DATACENTER BASEMENT DIRECT AIR | 21.50 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.66 | 0.335993 | 0.334000 | 1.89 | 0.895981 | 0.500000 | 0.001134 | 0.000415 | 1.89 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.97 | 0.359069 | 0.348000 | 18.43 | 0.957516 | 0.500000 | 0.001061 | 0.007965 | 18.43 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.13 | 0.370462 | 0.363000 | 1.86 | 0.987898 | 0.500000 | 0.001028 | 0.001435 | 1.96 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.765530 | 0.311968 | 0.310000 | 0.237314 | 0.831914 | 0.500000 | 0.001221 | 0.000116 | 0.237314 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.11 | 0.138819 | 0.300000 | 0.332603 | 0.370183 | 0.500000 | 0.002745 | 0.000121 | 0.332603 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.39 | 0.171954 | 0.300000 | 0.416667 | 0.458545 | 0.500000 | 0.002216 | 0.000196 | 0.416667 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.33 | 0.115873 | 0.300000 | 0.398466 | 0.308995 | 0.500000 | 0.003288 | 0.000106 | 0.398466 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 6.75 | 0.353748 | 0.343000 | 2.32 | 0.943329 | 0.500000 | 0.001077 | 0.003237 | 4.43 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.33 | 0.135896 | 0.300000 | 3.40 | 0.362390 | 0.500000 | 0.002804 | 0.002263 | 3.40 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 13.97 | 0.170983 | 0.300000 | 4.19 | 0.455955 | 0.500000 | 0.002228 | 0.003236 | 4.43 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.72 | 0.131301 | 0.300000 | 3.52 | 0.350135 | 0.500000 | 0.002902 | 0.002132 | 3.52 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.772143 | 0.309296 | 0.303000 | 0.233959 | 0.824789 | 0.500000 | 0.001232 | 0.000426 | 0.583057 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.12 | 0.137340 | 0.300000 | 0.336183 | 0.366241 | 0.500000 | 0.002774 | 0.000282 | 0.386003 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.48 | 0.160973 | 0.300000 | 0.445092 | 0.429261 | 0.500000 | 0.002367 | 0.000425 | 0.581866 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.23 | 0.124867 | 0.300000 | 0.369765 | 0.332979 | 0.500000 | 0.003051 | 0.000266 | 0.369765 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18766.16 | 0.000415 | 326.63 |
CORE_MID VAV BOX REHEAT COIL | 360498.05 | 0.007965 | 6760.96 |
CORE_TOP VAV BOX REHEAT COIL | 64927.95 | 0.001435 | 1356.07 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 5229.98 | 0.000116 | 99.78 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5487.73 | 0.000121 | 100.94 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8880.00 | 0.000196 | 168.55 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4791.67 | 0.000106 | 85.34 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 146508.92 | 0.003237 | 3057.15 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 102405.54 | 0.002263 | 2081.99 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 146445.24 | 0.003236 | 3055.82 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 96503.26 | 0.002132 | 1918.52 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 19276.44 | 0.000426 | 402.16 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12760.86 | 0.000282 | 266.22 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 19237.14 | 0.000425 | 401.34 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 12037.79 | 0.000266 | 249.99 |
CAV_BAS_HEATC | 264554.94 | 0.005845 | 4885.95 |
VAV_BOT WITH REHEAT_HEATC | 52563.38 | 0.001161 | 758.17 |
VAV_MID WITH REHEAT_HEATC | 502791.93 | 0.011109 | 7215.42 |
VAV_TOP WITH REHEAT_HEATC | 51272.51 | 0.001133 | 736.93 |
DATACENTER_EXTRAWATERHEATC | 1027503.57 | 0.022701 | 19115.72 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 5.42 | 1.00 | 1.00 | 5.42 |
VAV_BOT WITH REHEAT | 5.13 | 3.28 | 10.25 | 3.28 | 8.97 | 8.97 | 0.300000 | 0.365104 | 8.97 |
VAV_MID WITH REHEAT | 48.37 | 31.85 | 96.74 | 31.85 | 82.65 | 82.65 | 0.300000 | 0.385389 | 82.65 |
VAV_TOP WITH REHEAT | 4.87 | 3.25 | 9.74 | 3.87 | 8.53 | 8.53 | 0.300000 | 0.453871 | 8.53 |
AIRLOOP DATACENTER BASEMENT | 21.50 | 21.50 | 21.50 | 21.50 | 21.50 | 21.50 | 1.00 | 1.00 | 21.50 |
AIRLOOP DATACENTER BOT | 0.493003 | 0.493003 | 0.493003 | 0.493003 | 0.493003 | 0.493003 | 1.00 | 1.00 | 0.493003 |
AIRLOOP DATACENTER MID | 4.71 | 4.71 | 4.71 | 4.71 | 4.71 | 4.71 | 1.00 | 1.00 | 4.71 |
AIRLOOP DATACENTER TOP | 0.478356 | 0.478356 | 0.478356 | 0.478356 | 0.478356 | 0.478356 | 1.00 | 1.00 | 0.478356 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.42 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.97 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 82.65 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.53 | |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.50 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.493003 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.71 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.478356 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 96713.46 | 0.004114 | 5.42 | 0.008957 | 24.99 | 6.67 | 11.40 | 0.008398 |
VAV_BOT WITH REHEAT_COOLC | 168560.20 | 0.007171 | 8.97 | 0.008854 | 25.64 | 6.67 | 11.40 | 0.008398 |
VAV_MID WITH REHEAT_COOLC | 1588938.50 | 0.067597 | 82.65 | 0.008880 | 25.83 | 6.67 | 11.40 | 0.008398 |
VAV_TOP WITH REHEAT_COOLC | 160744.11 | 0.006838 | 8.53 | 0.008849 | 25.61 | 6.67 | 11.40 | 0.008398 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.42 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.004114 | 0.000116 |
CAV_BAS_HEATC_CONTROLLER | 0.005845 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007171 | 0.000066 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001161 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.067597 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.011109 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006838 | 0.000070 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001133 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022701 | 0.000021 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.97 |
VAV_MID WITH REHEAT FAN | 82.65 |
VAV_TOP WITH REHEAT FAN | 8.53 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.50 | 423313.10 | 303441.43 | 0.010367 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.493003 | 9429.60 | 6860.58 | 0.000231 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.71 | 90108.01 | 65559.62 | 0.002207 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.478356 | 9149.28 | 6656.68 | 0.000224 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.50 | 21.50 | 21.50 | 21.50 | 423313.10 | 423313.10 | 17838.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.493003 | 0.493003 | 0.493003 | 0.493003 | 9429.60 | 9429.60 | 824.08 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.71 | 4.71 | 4.71 | 4.71 | 90108.01 | 90108.01 | 8240.84 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.478356 | 0.478356 | 0.478356 | 0.478356 | 9149.28 | 9149.28 | 824.08 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.50 |
DATACENTER BOT SUPPLY FAN | 0.493003 |
DATACENTER MID SUPPLY FAN | 4.71 |
DATACENTER TOP SUPPLY FAN | 0.478356 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.50 | 423313.10 | 0.010367 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.493003 | 9429.60 | 0.000231 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.71 | 90108.01 | 0.002207 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.478356 | 9149.28 | 0.000224 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 17838.92 | |
DATACENTER_EXTRAELECHEATC | 423313.10 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 824.08 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 8240.84 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 824.08 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000143 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.085721 | 20530.89 |
HEATSYS1 PUMP | 0.064568 | 16496.25 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.085721 | 10.29 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.064568 | 7.75 |
COOLSYS1_SUPPLY | 0.085721 | 10.29 |
SINGLE WATER PLANT LOOP | 0.013029 | 1.56 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.085721 | 0.085721 | 359813.62 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 5.96 |
COOLSYS1 PUMP | 0.085721 | 6843.63 |
PLANT CIRC PUMP | 0.013029 | 3322.96 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2922443.05 | 1461221.52 | 0.064568 |
DUMMY BOILER | 536668.50 | 93894.07 | 0.013029 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.085721 | 0.043146 | 1015326.70 | 1021506.44 | 0.051788 |
COOLSYS1 CHILLER2 | 0.085721 | 0.043146 | 1015326.70 | 1021506.44 | 0.051788 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013029 | 139666.47 | 60392.67 | 69833.23 | 7879.72 | 21522.68 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.103576 | 12.43 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.103576 | 26461.26 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 39.64 | 970787.53 | 7.93 | 121348.44 |
TOWERWATERSYS COOLTOWER 2 | 39.64 | 970787.53 | 7.93 | 121348.44 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.042004 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.944 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.786 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 7.944 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.367 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 22079.114 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22079.114 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 6225.366 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6225.366 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.092 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.5534 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4781 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.640 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.0917746 | 2.0917746 | 2.0917746 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.29758781E-14 | -0.29065710E-15 | -0.16717921E-09 | -0.54082436E-16 |
51 | 8 | 0.24322757E-07 | 0.75510264E-13 | 0.40304845E-03 | -0.27655812E-09 |
52 | 7 | -0.12993629E-01 | 0.38338009E-08 | -0.24168191E-01 | 0.14774231E-03 |
53 | 6 | 0.42578349 | 0.13225368E-05 | 0.48945559 | -0.49886206E-02 |
54 | 5 | -5.3899404 | 0.49024379E-04 | -4.5744615 | 0.65656055E-01 |
55 | 4 | 33.884590 | 0.39840510E-03 | 21.960611 | -0.43383013 |
56 | 3 | -113.10176 | 0.86320527E-03 | -56.652426 | 1.5422922 |
57 | 2 | 198.98955 | 0.48301085E-03 | 78.818690 | -2.9302292 |
58 | 1 | -171.85079 | 0.51313109E-04 | -55.530381 | 2.7576150 |
59 | 0 | 57.057407 | 0.29052359E-06 | 15.514123 | |
60 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
61 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
62 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
63 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
64 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
65 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
66 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
67 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
68 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
69 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
70 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
71 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
72 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
73 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
74 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
75 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
76 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
77 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
78 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
79 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
80 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
81 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
82 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
83 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
84 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
85 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
86 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
87 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
88 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
89 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
90 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
91 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
92 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
93 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
94 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
95 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
96 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
97 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
98 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
99 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
100 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
101 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
102 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
103 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
104 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
105 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
106 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
107 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.4 | 29 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 74202.53270 | 74202.53270 | 5.41902 | 5.41902 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 77521.40791 | 77521.40791 | 5.66096 | 5.66096 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 725604.89770 | 725604.89770 | 52.97159 | 52.97159 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 177536.08790 | 177536.08790 | 7.53697 | 10.77757 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 70334.55835 | 70334.55835 | 5.13425 | 5.13425 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 45506.53279 | 45506.53279 | 1.95678 | 1.95678 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 10386.16927 | 10386.16927 | 0.76553 | 0.76553 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 29.22667 | 8.79438E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 2885.86065 | 2885.86065 | 0.12305 | 0.13532 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 15041.99830 | 15041.99830 | 1.10868 | 1.10868 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 2200.52215 | 2200.52215 | 9.40675E-002 | 9.40675E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 18843.63262 | 18843.63262 | 1.38889 | 1.38889 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 28.88000 | 8.79438E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 4757.62203 | 4757.62203 | 0.20427 | 0.20427 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18020.58611 | 18020.58611 | 1.32822 | 1.32822 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 848.27636 | 848.27636 | 3.68845E-002 | 8.72074E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 92459.35723 | 92459.35723 | 6.75114 | 6.75114 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 102601.10005 | 102601.10005 | 4.42879 | 4.42879 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 153653.62900 | 153653.62900 | 11.32518 | 11.32518 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.79438E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 68718.57695 | 68718.57695 | 2.96666 | 2.96666 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 189506.62133 | 189506.62133 | 13.96780 | 13.96780 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.79438E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 102556.63865 | 102556.63865 | 4.42686 | 4.42686 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 159031.85616 | 159031.85616 | 11.72158 | 11.72158 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 27.59733 | 8.79438E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 61648.74891 | 61648.74891 | 2.66038 | 2.66038 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 10475.90258 | 10475.90258 | 0.77214 | 0.77214 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.79438E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 13493.21780 | 13493.21780 | 0.58306 | 0.58306 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15203.79596 | 15203.79596 | 1.12061 | 1.12061 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 8932.11868 | 8932.11868 | 0.38600 | 0.38600 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 20129.13310 | 20129.13310 | 1.48364 | 1.48364 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 13465.75721 | 13465.75721 | 0.58187 | 0.58187 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16722.56504 | 16722.56504 | 1.23255 | 1.23255 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 8370.45433 | 8370.45433 | 0.36165 | 0.36165 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8481.22767 | 8481.22767 | 0.49300 | 0.49300 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.79438E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 81047.78828 | 81047.78828 | 4.71121 | 4.71121 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.79438E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8229.25204 | 8229.25204 | 0.47836 | 0.47836 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 25.86400 | 8.79438E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369881.59961 | 369881.59961 | 21.50077 | 21.50077 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 19.20800 | 8.79438E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20000 | 2.69032E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 71144.05 | 5.41902 | 5.41902 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 63268.17 | 1.20008 | 1.20008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 127888.90 | 8.97227 | 8.97227 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 32415.19 | 1.59863 | 1.59863 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1161301.60 | 82.65437 | 82.65437 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 512199.37 | 25.26026 | 25.26026 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 130171.58 | 8.52524 | 8.52524 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 51401.73 | 3.86936 | 3.86936 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:40:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 364583.11 | 21.50077 | 21.50077 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17838.92 | 0.33837 | 0.33837 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8328.90 | 0.49300 | 0.49300 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 824.08 | 1.56314E-002 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79582.72 | 4.71121 | 4.71121 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8240.84 | 0.15631 | 0.15631 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8080.82 | 0.47836 | 0.47836 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 824.08 | 1.56314E-002 | 1.56314E-002 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.41902 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.66096 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33599 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33400 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.89076 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89598 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13395E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.14615E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.89076 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18766.15801 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.14615E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 326.62981 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.97159 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35907 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34800 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.43411 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95752 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06108E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.96476E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.43411 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 360498.04712 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.96476E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6760.95853 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.13425 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37046 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36300 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.86373 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.98790 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.02845E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43450E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.95678 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 64927.95075 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43450E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1356.06783 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76553 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31197 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23731 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83191 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22128E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.15550E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23731 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5229.98057 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.15550E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 99.78448 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.10868 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13882 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33260 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37018 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74459E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.21245E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.33260 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5487.73251 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.21245E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 100.94174 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.38889 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17195 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.41667 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45854 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21571E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96193E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41667 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8879.99746 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96193E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 168.55496 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32822 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11587 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.39847 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30900 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.28808E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05866E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39847 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4791.67128 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05866E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 85.34318 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.75114 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35375 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34300 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31564 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94333 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07704E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.23694E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.42879 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 146508.91965 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23694E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3057.15101 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.32518 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13590 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.39755 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36239 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.80361E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.26253E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.39755 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 102405.53645 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26253E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2081.99406 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 13.96780 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17098 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 4.19034 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45595 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22829E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.23553E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.42686 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 146445.23666 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.23553E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3055.82322 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.72158 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13130 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.51647 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35013 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90174E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.13212E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.51647 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 96503.26102 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13212E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1918.52127 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77214 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30930 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30300 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23396 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82479 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23183E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.25889E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58306 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19276.44248 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.25889E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 402.16126 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.12061 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13734 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33618 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.36624 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.77413E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.81936E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38600 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12760.85719 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.81936E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 266.22275 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.48364 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16097 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44509 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42926 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36686E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.25021E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.58187 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19237.14465 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.25021E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 401.34195 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23255 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12487 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.36977 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33298 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05124E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65960E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36977 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12037.78855 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65960E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 249.99203 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49300 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.71121 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47836 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.50077 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.41902 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.41902 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.41902 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.41902 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.41902 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.41902 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.12614 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.27581 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.25228 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.27581 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.97227 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.97227 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.36510 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.36865 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 31.85412 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 96.73729 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 31.85412 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 82.65437 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 82.65437 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.38539 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.87160 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.24873 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.74319 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.86936 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.52524 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.52524 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.45387 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.50077 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.50077 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.50077 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.50077 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.50077 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.50077 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49300 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49300 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49300 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49300 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49300 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49300 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.71121 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.71121 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.71121 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.71121 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.71121 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.71121 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47836 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47836 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47836 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47836 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47836 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.47836 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.41902 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.97227 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 82.65437 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.52524 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.50077 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49300 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.71121 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.47836 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.41902 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 96713.45952 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.11441E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.41902 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.95669E-003 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.99197 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40152 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 264554.94032 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.84502E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 4885.95117 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.41902 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.11441E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.15737E-004 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.84502E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.97227 |
306 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 168560.20052 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 7.17094E-003 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.97227 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.85361E-003 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.64047 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40126 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
314 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 52563.37705 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.16132E-003 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 758.16730 |
317 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.97227 |
318 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.17094E-003 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.64056E-005 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.16132E-003 |
321 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 82.65437 |
322 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 1588938.49626 |
323 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.75971E-002 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 82.65437 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.87998E-003 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.83393 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40133 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
330 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 502791.92760 |
331 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.11086E-002 |
332 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 7215.42094 |
333 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 82.65437 |
334 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.75971E-002 |
335 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.04454E-006 |
336 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.11086E-002 |
337 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.52524 |
338 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 160744.11055 |
339 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 6.83843E-003 |
340 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.52524 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 8.84879E-003 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 25.60754 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.40125 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.39822E-003 |
346 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 51272.50941 |
347 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.13280E-003 |
348 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 736.93139 |
349 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.52524 |
350 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.83843E-003 |
351 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.96345E-005 |
352 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.13280E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.50077 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.50077 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 423313.10126 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 303441.42523 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03669E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.50077 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.50077 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.50077 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.50077 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 423313.10126 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 423313.10126 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17838.91681 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.50077 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.50077 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 423313.10126 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.03669E-002 |
371 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 17838.91681 |
372 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.42843E-004 |
373 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 423313.10126 |
377 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
378 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1027503.57158 |
379 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.27014E-002 |
380 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19115.72471 |
381 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.27014E-002 |
382 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.09762E-005 |
383 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49300 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.49300 |
385 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9429.60214 |
386 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6860.57537 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.30930E-004 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49300 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49300 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49300 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49300 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9429.60214 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9429.60214 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.08405 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
396 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49300 |
397 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.49300 |
398 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9429.60214 |
399 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.30930E-004 |
400 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 824.08405 |
401 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.71121 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.71121 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 90108.00902 |
404 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 65559.61632 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.20674E-003 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.71121 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.71121 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.71121 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.71121 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 90108.00902 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 90108.00902 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8240.84054 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
414 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.71121 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.71121 |
416 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 90108.00902 |
417 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.20674E-003 |
418 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 8240.84054 |
419 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47836 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.47836 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 9149.27896 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6656.68056 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.24065E-004 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47836 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47836 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47836 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47836 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9149.27896 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9149.27896 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 824.08405 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
432 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47836 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.47836 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 9149.27896 |
435 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.24065E-004 |
436 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 824.08405 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.57209E-002 |
438 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 20530.88901 |
439 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.57209E-002 |
440 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.28651 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.57209E-002 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.57209E-002 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 359813.61908 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
445 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
446 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
447 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
448 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 5.95777 |
449 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
450 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 6.45678E-002 |
451 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 7.74814 |
452 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 6.45678E-002 |
453 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 16496.24702 |
454 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2922443.05030 |
455 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1461221.52500 |
456 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 6.45678E-002 |
457 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.57209E-002 |
458 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.28651 |
459 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.57209E-002 |
460 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 6843.62967 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.57209E-002 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.31461E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1015326.70072 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1021506.44000 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.17882E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.57209E-002 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.31461E-002 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1015326.70072 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1021506.44000 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.17882E-002 |
471 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.30286E-002 |
472 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.56344 |
473 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.30286E-002 |
474 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3322.95614 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.30286E-002 |
476 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
477 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60392.67099 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21522.68332 |
481 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 536668.50138 |
482 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
483 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.30286E-002 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10358 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.42917 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10358 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 26461.26387 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 39.63660 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 970787.52863 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.92732 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 121348.44108 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 39.63660 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 970787.52863 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.92732 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 121348.44108 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.20040E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 4.20040E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17803.84 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 342257.55 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 61604.03 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 4964.83 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5211.14 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 8430.04 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4545.05 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 139008.90 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 97172.75 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 138948.47 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 91586.20 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 18289.66 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 12107.62 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 18252.37 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 11421.72 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 210129.58 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 40379.87 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 383436.30 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 39188.38 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 824924.23 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 136341.36 | 94760.94 | 41580.42 | 0.70 | 16896.82 | 171.38 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 232737.99 | 160101.43 | 72636.56 | 0.69 | 29194.58 | 296.11 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2169179.85 | 1486195.91 | 682983.94 | 0.69 | 272651.79 | 2765.39 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 222281.84 | 152680.94 | 69600.90 | 0.69 | 28095.76 | 284.96 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.16 | 24.42 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.16 | 24.42 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.092 | 2.092 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.553 | 0.511 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 25 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.5507017573 | 0.5531104536 | Pass | Pass | 2.3361182241 | 2.9047434269 | Pass | Fail |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.2419571800E-003 | 1.6943190440E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 1.9275018357E-003 | 2.4213651588E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 3.4134716099E-002 | 1.6712238244E-002 | Pass | Pass | 0.4710925472 | 0.5587150123 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.4566993289E-002 | 1.1806087047E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.5270921774E-002 | 1.3235450489E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.3245914951E-002 | 1.2723513041E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.5310283698E-002 | 1.1861009042E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8784714377E-002 | 1.4082641774E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.9304596629E-002 | 1.5493017548E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.9672326256E-002 | 1.5785115138E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 2.0631929878E-002 | 1.4696438763E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.1974214650 | 0.1973932393 | Pass | Pass | 7.7888607985 | 23.8916625370 | Fail | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2127237396 | 0.2112299303 | Pass | Pass | 7.8020957759 | 32.9035082076 | Fail | Fail |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1947518467 | 0.1961653711 | Pass | Pass | 6.8399693469 | 21.8155102514 | Fail | Fail |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.2343798071E-002 | 0.1181064754 | Pass | Pass | 7.3541664900 | 20.4950046207 | Fail | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.0632017183E-003 | 4.1412008978E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.0820991360E-003 | 4.9334952759E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.0693367072E-002 | 5.0983552924E-002 | Pass | Pass | 0.4465204185 | 0.4838989714 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.2862601529E-014 | 3.0367390375E-014 | Pass | Pass | 8.9066302268E-004 | 7.7172410539E-004 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.0116320197E-003 | 3.7296485892E-003 | Pass | Pass | 1.6933365545E-003 | 1.5634657292E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.1470119722E-003 | 3.9501872643E-003 | Pass | Pass | 1.7119955501E-003 | 1.5879422525E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.1909787595E-014 | 5.4527657633E-014 | Pass | Pass | 3.6901670176E-005 | 2.8396827957E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.511 | 0.553 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.159 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 1043.06 | 2.159 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.159 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.593 | 2.092 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 7.9438 | 2779.43 | 22079.11 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 210.95 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 7.9438 | 2496.12 | 19828.60 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 189.45 |
CORE_MID_LIGHTS | CORE_MID | 7.9438 | 24961.20 | 198285.97 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 1894.50 |
CORE_TOP_LIGHTS | CORE_TOP | 7.9438 | 2496.12 | 19828.60 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 189.45 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 7.9438 | 313.41 | 2489.68 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 40.08 | 0.0000 | Y | 18.73 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 40.01 | 0.0000 | Y | 12.05 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 7.9438 | 313.42 | 2489.73 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.91 | 0.0000 | Y | 18.65 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.98 | 0.0000 | Y | 12.04 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 7.9438 | 3134.13 | 24896.78 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 40.10 | 0.0000 | Y | 187.40 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 7.9438 | 2019.75 | 16044.43 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 40.02 | 0.0000 | Y | 120.53 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 7.9438 | 3134.20 | 24897.33 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.92 | 0.0000 | Y | 186.59 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 7.9438 | 2019.75 | 16044.43 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.99 | 0.0000 | Y | 120.44 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 7.9438 | 313.41 | 2489.68 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 40.10 | 0.0000 | Y | 18.74 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 40.02 | 0.0000 | Y | 12.05 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 7.9438 | 313.42 | 2489.73 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.92 | 0.0000 | Y | 18.66 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.99 | 0.0000 | Y | 12.04 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 7.9438 | 783.68 | 6225.37 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 59.48 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 7.9438 | 36.20 | 287.59 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 2.75 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 7.9438 | 362.03 | 2875.86 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 27.48 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 7.9438 | 36.20 | 287.59 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 2.75 |
Interior Lighting Total | 7.9438 | 46320.38 | 367958.24 | 1031.49 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9734.40 | AstronomicalClock | - | 42.59 | 42.59 | 77.83 | |
EXTERIOR_LIGHTS_B | 43301.51 | AstronomicalClock | - | 83.55 | 71.26 | 579.22 | |
Exterior Lighting Total | 53035.91 | 657.05 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2010322.46 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1461221.52 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1021506.44 | 5.33 | 7.16 | 24.42 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1021506.44 | 5.33 | 7.16 | 24.42 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 970787.53 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 970787.53 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 96713.46 | 136341.36 | 94760.94 | 41580.42 | 0.70 | - | 16896.82 | 171.38 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 168560.20 | 232737.99 | 160101.43 | 72636.56 | 0.69 | - | 29194.58 | 296.11 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 1588938.50 | 2169179.85 | 1486195.91 | 682983.94 | 0.69 | - | 272651.79 | 2765.39 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 160744.11 | 222281.84 | 152680.94 | 69600.90 | 0.69 | - | 28095.76 | 284.96 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 423313.10 | 303441.43 | 119871.68 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9429.60 | 6860.58 | 2569.03 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 90108.01 | 65559.62 | 24548.39 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9149.28 | 6656.68 | 2492.60 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18766.16 | 17803.84 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 360498.05 | 342257.55 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 64927.95 | 61604.03 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 5229.98 | 4964.83 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5487.73 | 5211.14 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8880.00 | 8430.04 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4791.67 | 4545.05 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 146508.92 | 139008.90 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 102405.54 | 97172.75 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 146445.24 | 138948.47 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 96503.26 | 91586.20 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 19276.44 | 18289.66 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12760.86 | 12107.62 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19237.14 | 18252.37 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 12037.79 | 11421.72 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 264554.94 | 210129.58 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 52563.38 | 40379.87 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 502791.93 | 383436.30 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 51272.51 | 39188.38 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 423313.10 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9429.60 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 90108.01 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 9149.28 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 17838.92 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1027503.57 | 824924.23 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 824.08 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 8240.84 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 824.08 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.42 | 9188.78 | 1695.65 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1314.72 | 8.97 | 19388.60 | 2160.95 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 82.65 | 188760.09 | 2283.73 | 1.00 | 1.07 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.53 | 19469.33 | 2283.73 | 1.00 | 1.12 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.50 | 35647.70 | 1657.97 | 1.00 | 1.13 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 552.22 | 1120.11 | 1.00 | 1.61 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.71 | 5277.06 | 1120.11 | 1.00 | 1.16 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 535.81 | 1120.11 | 1.00 | 1.63 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.085721 | 20530.89 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.064568 | 16496.25 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.085721 | 6843.63 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013029 | 3322.96 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.103576 | 26461.26 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 74202.53 | 74202.53 | 26.70 | 5.419 | 5.419 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 21.70 | 0.00879 | 1.200 | 0.00 |
CORE_BOTTOM | 77521.41 | 77521.41 | 31.06 | 5.661 | 5.661 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 21.70 | 0.00879 | 1.078 | 0.00 |
CORE_MID | 725604.90 | 725604.90 | 290.69 | 52.972 | 52.972 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 21.70 | 0.00879 | 10.778 | 0.00 |
CORE_TOP | 70334.56 | 70334.56 | 28.18 | 5.134 | 5.134 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00895 | 21.70 | 0.00879 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10386.17 | 10386.17 | 33.14 | 0.766 | 0.766 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00887 | 29.23 | 0.00879 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 15042.00 | 15042.00 | 74.47 | 1.109 | 1.109 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00866 | 22.36 | 0.00879 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 18843.63 | 18843.63 | 60.12 | 1.389 | 1.389 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 24.00 | 0.00870 | 28.88 | 0.00879 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18020.59 | 18020.59 | 89.22 | 1.328 | 1.328 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 27.77 | 0.00879 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 92459.36 | 92459.36 | 295.01 | 6.751 | 6.751 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 21.70 | 0.00879 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 153653.63 | 153653.63 | 760.76 | 11.325 | 11.325 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 23.02 | 0.00879 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 189506.62 | 189506.62 | 604.64 | 13.968 | 13.968 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00870 | 28.97 | 0.00879 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 159031.86 | 159031.86 | 787.38 | 11.722 | 11.722 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:20:00 | 24.00 | 24.00 | 0.00866 | 27.60 | 0.00879 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10475.90 | 10475.90 | 33.43 | 0.772 | 0.772 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00886 | 29.40 | 0.00879 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15203.80 | 15203.80 | 75.28 | 1.121 | 1.121 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00866 | 23.02 | 0.00879 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 20129.13 | 20129.13 | 64.22 | 1.484 | 1.484 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00869 | 29.05 | 0.00879 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16722.57 | 16722.57 | 82.80 | 1.233 | 1.233 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 27.77 | 0.00879 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8481.23 | 8481.23 | 234.27 | 0.493 | 0.493 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 25.86 | 0.00879 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 81047.79 | 81047.79 | 2238.72 | 4.711 | 4.711 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 25.86 | 0.00879 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8229.25 | 8229.25 | 227.31 | 0.478 | 0.478 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 25.86 | 0.00879 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369881.60 | 369881.60 | 471.98 | 21.501 | 21.501 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 27.00 | 27.00 | 0.00850 | 19.21 | 0.00879 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 | |
CORE_MID | 177536.09 | 177536.09 | 71.12 | 7.537 | 10.778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 10.778 | 0.00 |
CORE_TOP | 45506.53 | 45506.53 | 18.23 | 1.957 | 1.957 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 2885.86 | 2885.86 | 9.21 | 0.123 | 0.135 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00554 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 2200.52 | 2200.52 | 10.90 | 0.094 | 0.094 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00586 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 4757.62 | 4757.62 | 15.18 | 0.204 | 0.204 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00643 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 848.28 | 848.28 | 4.20 | 0.037 | 0.087 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 21.00 | 21.00 | 0.00646 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 102601.10 | 102601.10 | 327.37 | 4.429 | 4.429 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 68718.58 | 68718.58 | 340.23 | 2.967 | 2.967 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00755 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 102556.64 | 102556.64 | 327.22 | 4.427 | 4.427 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00750 | -4.20 | 0.00269 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 61648.75 | 61648.75 | 305.23 | 2.660 | 2.660 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -4.20 | 0.00269 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13493.22 | 13493.22 | 43.05 | 0.583 | 0.583 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 8932.12 | 8932.12 | 44.22 | 0.386 | 0.386 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13465.76 | 13465.76 | 42.96 | 0.582 | 0.582 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 8370.45 | 8370.45 | 41.44 | 0.362 | 0.362 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -4.20 | 0.00269 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -4.20 | 0.00269 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.42 | 5.42 | 1.20 | 1.20 | 5.4190 | 5.4190 | 5.4190 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 8.97 | 8.97 | 1.60 | 1.60 | 8.9723 | 3.2758 | 8.9723 | 0.3651 | 0.3000 |
VAV_MID WITH REHEAT | 82.65 | 82.65 | 25.26 | 25.26 | 82.6544 | 31.8541 | 82.6544 | 0.3854 | 0.3000 |
VAV_TOP WITH REHEAT | 8.53 | 8.53 | 3.87 | 3.87 | 8.5252 | 3.8694 | 8.5252 | 0.4539 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.50 | 21.50 | 0.34 | 0.34 | 21.5008 | 21.5008 | 21.5008 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4930 | 0.4930 | 0.4930 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.71 | 4.71 | 0.16 | 0.16 | 4.7112 | 4.7112 | 4.7112 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4784 | 0.4784 | 0.4784 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18766.158 | 18766.158 | 1.890762 | 0.00041462 | 326.630 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17803.84 | 18766.16 | 1.890762 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18841.65 | 18841.65 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 360498.047 | 360498.047 | 18.434113 | 0.00796476 | 6760.959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 342257.55 | 360498.05 | 18.434113 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 177536.09 | 0.00 | 362224.44 | 362224.44 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 64927.951 | 64927.951 | 1.956782 | 0.00143450 | 1356.068 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 61604.03 | 64927.95 | 1.956782 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 45506.53 | 0.00 | 65224.42 | 65224.42 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 5229.981 | 5229.981 | 0.237314 | 0.00011555 | 99.784 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4964.83 | 5229.98 | 0.237314 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00553567 | 35.4196 | 2885.86 | 0.00 | 5254.84 | 5254.84 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5487.733 | 5487.733 | 0.332603 | 0.00012124 | 100.942 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5211.14 | 5487.73 | 0.332603 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00586115 | 37.4833 | 2200.52 | 0.00 | 5514.69 | 5514.69 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 8879.997 | 8879.997 | 0.416667 | 0.00019619 | 168.555 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8430.04 | 8880.00 | 0.416667 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00643207 | 41.0969 | 4757.62 | 0.00 | 8922.28 | 8922.28 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4791.671 | 4791.671 | 0.398466 | 0.00010587 | 85.343 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 4545.05 | 4791.67 | 0.398466 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00646240 | 41.2841 | 848.28 | 0.00 | 4810.36 | 4810.36 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 146508.920 | 146508.920 | 4.428791 | 0.00323694 | 3057.151 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 139008.90 | 146508.92 | 4.428791 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00750480 | 47.8666 | 102601.10 | 0.00 | 147177.81 | 147177.81 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 102405.536 | 102405.536 | 3.397554 | 0.00226253 | 2081.994 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 97172.75 | 102405.54 | 3.397554 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00754681 | 48.1311 | 68718.58 | 0.00 | 102873.66 | 102873.66 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 146445.237 | 146445.237 | 4.426861 | 0.00323553 | 3055.823 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 138948.47 | 146445.24 | 4.426861 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00750389 | 47.8609 | 102556.64 | 0.00 | 147113.83 | 147113.83 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 96503.261 | 96503.261 | 3.516474 | 0.00213212 | 1918.521 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 91586.20 | 96503.26 | 3.516474 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00739018 | 47.1449 | 61648.75 | 0.00 | 96951.39 | 96951.39 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 19276.442 | 19276.442 | 0.583057 | 0.00042589 | 402.161 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18289.66 | 19276.44 | 0.583057 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772327 | 49.2413 | 13493.22 | 0.00 | 19364.45 | 19364.45 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 12760.857 | 12760.857 | 0.386003 | 0.00028194 | 266.223 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12107.62 | 12760.86 | 0.386003 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773011 | 49.2844 | 8932.12 | 0.00 | 12819.12 | 12819.12 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 19237.145 | 19237.145 | 0.581866 | 0.00042502 | 401.342 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18252.37 | 19237.14 | 0.581866 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772164 | 49.2311 | 13465.76 | 0.00 | 19324.97 | 19324.97 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 12037.789 | 12037.789 | 0.369765 | 0.00026596 | 249.992 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11421.72 | 12037.79 | 0.369765 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00768739 | 49.0157 | 8370.45 | 0.00 | 12092.72 | 12092.72 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 96713.460 | -999.000 | 5.419017 | 0.00411441 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 96713.46 | 87833.55 | 5.419017 | 24.99 | 16.96 | 0.00895669 | 11.40 | 11.39 | 0.00839822 | 28.05 | 0.00879438 | 17.86 | 22.1457 | 24.00 | 0.00897191 | 47.5760 | 66374.18 | 0.00 | 108793.75 | 91953.63 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 264554.940 | 264554.940 | 5.419017 | 0.00584502 | 4885.951 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 210129.58 | 264554.94 | 5.419017 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 22.1457 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 221680.19 | 221680.19 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 168560.201 | -999.000 | 8.972271 | 0.00717094 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 168560.20 | 156251.88 | 8.972271 | 25.64 | 17.09 | 0.00885361 | 11.40 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 28.2876 | 24.00 | 0.00881328 | 46.7460 | 113289.82 | 0.00 | 188585.80 | 161302.77 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 52563.377 | 52563.377 | 2.691681 | 0.00116132 | 758.167 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 40379.87 | 52563.38 | 2.691681 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 94.2920 | 21.00 | 0.00738131 | 47.0855 | 10581.12 | 0.00 | 42697.93 | 42697.93 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1588938.496 | -999.000 | 82.654371 | 0.06759712 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1588938.50 | 1468188.46 | 82.654371 | 25.83 | 17.18 | 0.00887998 | 11.40 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 30.7066 | 24.00 | 0.00883241 | 46.8461 | 1013463.79 | 0.00 | 1773683.30 | 1510774.96 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 502791.928 | 502791.928 | 24.796311 | 0.01110857 | 7215.421 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 383436.30 | 502791.93 | 24.796311 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 102.3554 | 21.00 | 0.00770878 | 49.1496 | 513061.15 | 0.00 | 405441.83 | 405441.83 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 160744.111 | -999.000 | 8.525242 | 0.00683843 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 160744.11 | 149097.32 | 8.525242 | 25.61 | 17.08 | 0.00884879 | 11.40 | 11.97 | 0.00839822 | 29.40 | 0.00879438 | 18.30 | 29.7709 | 24.00 | 0.00882984 | 46.8327 | 115608.32 | 0.00 | 179788.39 | 153494.03 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 51272.509 | 51272.509 | 2.557573 | 0.00113280 | 736.931 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39188.38 | 51272.51 | 2.557573 | -4.14 | -4.14 | 0.00270318 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 99.2363 | 21.00 | 0.00786030 | 50.1023 | 58514.74 | 0.00 | 41437.94 | 41437.94 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 423313.101 | 303441.425 | 21.500769 | 0.01036691 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 455696.28 | 455386.68 | -999.0 | 28.46 | 17.76 | 0.00850464 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 369325.47 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9429.602 | 6860.575 | 0.493003 | 0.00023093 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 10199.69 | 10185.31 | -999.0 | 27.92 | 17.58 | 0.00850933 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00879438 | 17.12 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 8481.23 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90108.009 | 65559.616 | 4.711210 | 0.00220674 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 97467.38 | 97323.63 | -999.0 | 27.92 | 17.58 | 0.00850977 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00879438 | 17.12 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 81047.79 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9149.279 | 6656.681 | 0.478356 | 0.00022407 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9896.51 | 9882.13 | -999.0 | 27.92 | 17.58 | 0.00850962 | 12.80 | 11.97 | 0.00850000 | 25.86 | 0.00879438 | 17.12 | -999.0000 | 27.00 | 0.00850000 | 37.7427 | 8229.25 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 423313.101 | 423313.101 | 21.500769 | 0.01036691 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 423313.10 | 423313.10 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5738 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9429.602 | 9429.602 | 0.493003 | 0.00023093 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9429.60 | 9429.60 | 0.493003 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1706 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 90108.009 | 90108.009 | 4.711210 | 0.00220674 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 90108.01 | 90108.01 | 4.711210 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.3179 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9149.279 | 9149.279 | 0.478356 | 0.00022407 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9149.28 | 9149.28 | 0.478356 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2677 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17838.917 | 17838.917 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17838.92 | 17838.92 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5738 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1150273.12 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5738 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1027503.572 | 1027503.572 | 21.500769 | 0.02270144 | 19115.725 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824924.23 | 1027503.57 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 1.5738 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 0.493003 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.1706 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8240.841 | 8240.841 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8240.84 | 8240.84 | 4.711210 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.3179 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 0.478356 | -4.20 | -4.20 | 0.00269032 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 3.2677 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18766.158 | 18766.158 | 1.890762 | 0.00041462 | 326.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.5972 | 0.642139 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17803.84 | 18766.16 | 1.0000 | 2.24431678 | 1.890762 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.41457304 | 60.00 | 49.00 | 11.00 | 0.000 | 17803.84 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 18841.65 | 18841.65 | 2.24431678 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 360498.047 | 360498.047 | 18.434113 | 0.00796476 | 6760.959 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 11.4803 | 12.335503 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 342257.55 | 360498.05 | 1.0000 | 21.88112210 | 18.434113 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 7.96395136 | 60.00 | 49.00 | 11.00 | 0.000 | 342257.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.57 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 177536.09 | 0.00 | 362224.44 | 362224.44 | 21.88112210 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 29.03 | 17.69 | 0.00800000 | 49614.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 64927.951 | 64927.951 | 1.956782 | 0.00143450 | 1356.068 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 2.0664 | 2.221701 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 61604.03 | 64927.95 | 1.0000 | 2.32268183 | 1.956782 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 1.43435740 | 60.00 | 49.00 | 11.00 | 0.000 | 61604.03 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 45506.53 | 0.00 | 65224.42 | 65224.42 | 2.32268183 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.34 | 21.25 | 0.00800000 | 61141.3 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5229.981 | 5229.981 | 0.237314 | 0.00011555 | 99.784 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.1665 | 0.178959 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 4964.83 | 5229.98 | 1.0000 | 0.28168971 | 0.237314 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.11553824 | 60.00 | 49.00 | 11.00 | 0.000 | 4964.83 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.82 | 0.00553567 | 21.00 | 0.00553567 | 35.4196 | 2885.86 | 0.00 | 5254.84 | 5254.84 | 0.28168971 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 31.09 | 18.38 | 0.00800000 | 51714.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5487.733 | 5487.733 | 0.332603 | 0.00012124 | 100.942 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.1748 | 0.187779 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 5211.14 | 5487.73 | 1.0000 | 0.39479658 | 0.332603 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.12123238 | 60.00 | 49.00 | 11.00 | 0.000 | 5211.14 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00586115 | 21.00 | 0.00586115 | 37.4833 | 2200.52 | 0.00 | 5514.69 | 5514.69 | 0.39479658 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 26.50 | 16.82 | 0.00800000 | 47028.3 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8879.997 | 8879.997 | 0.416667 | 0.00019619 | 168.555 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.2828 | 0.303855 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8430.04 | 8880.00 | 1.0000 | 0.49458032 | 0.416667 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.19617268 | 60.00 | 49.00 | 11.00 | 0.000 | 8430.04 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.86 | 0.00643207 | 21.00 | 0.00643207 | 41.0969 | 4757.62 | 0.00 | 8922.28 | 8922.28 | 0.49458032 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 30.49 | 18.18 | 0.00800000 | 51099.9 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4791.671 | 4791.671 | 0.398466 | 0.00010587 | 85.343 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.1525 | 0.163961 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 19:00:00 | 4545.05 | 4791.67 | 1.0000 | 0.47297540 | 0.398466 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.10585532 | 60.00 | 49.00 | 11.00 | 0.000 | 4545.05 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00646240 | 21.00 | 0.00646240 | 41.2841 | 848.28 | 0.00 | 4810.36 | 4810.36 | 0.47297540 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 22.77 | 15.49 | 0.00800000 | 43230.2 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 146508.920 | 146508.920 | 4.428791 | 0.00323694 | 3057.151 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 4.6628 | 5.013234 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 139008.90 | 146508.92 | 1.0000 | 5.25693380 | 4.428791 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 3.23660535 | 60.00 | 49.00 | 11.00 | 0.000 | 139008.90 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00750480 | 21.00 | 0.00750480 | 47.8666 | 102601.10 | 0.00 | 147177.81 | 147177.81 | 5.25693380 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61056.7 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 102405.536 | 102405.536 | 3.397554 | 0.00226253 | 2081.994 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 3.2595 | 3.504107 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 97172.75 | 102405.54 | 1.0000 | 4.03286556 | 3.397554 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 2.26229439 | 60.00 | 49.00 | 11.00 | 0.000 | 97172.75 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00754681 | 21.00 | 0.00754681 | 48.1311 | 68718.58 | 0.00 | 102873.66 | 102873.66 | 4.03286556 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 37.82 | 20.50 | 0.00800000 | 58568.7 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 146445.237 | 146445.237 | 4.426861 | 0.00323553 | 3055.823 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 4.6607 | 5.011055 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 138948.47 | 146445.24 | 1.0000 | 5.25464273 | 4.426861 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 3.23519850 | 60.00 | 49.00 | 11.00 | 0.000 | 138948.47 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00750389 | 21.00 | 0.00750389 | 47.8609 | 102556.64 | 0.00 | 147113.83 | 147113.83 | 5.25464273 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.26 | 21.23 | 0.00800000 | 61056.8 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 96503.261 | 96503.261 | 3.516474 | 0.00213212 | 1918.521 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 3.0721 | 3.302143 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 91586.20 | 96503.26 | 1.0000 | 4.17402220 | 3.516474 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 2.13190413 | 60.00 | 49.00 | 11.00 | 0.000 | 91586.20 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00739018 | 21.00 | 0.00739018 | 47.1449 | 61648.75 | 0.00 | 96951.39 | 96951.39 | 4.17402220 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 35.58 | 19.81 | 0.00800000 | 56287.2 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19276.442 | 19276.442 | 0.583057 | 0.00042589 | 402.161 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.6135 | 0.659600 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18289.66 | 19276.44 | 1.0000 | 0.69208363 | 0.583057 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.42584600 | 60.00 | 49.00 | 11.00 | 0.000 | 18289.66 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772327 | 21.00 | 0.00772327 | 49.2413 | 13493.22 | 0.00 | 19364.45 | 19364.45 | 0.69208363 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12760.857 | 12760.857 | 0.386003 | 0.00028194 | 266.223 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.4061 | 0.436650 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 12107.62 | 12760.86 | 1.0000 | 0.45818212 | 0.386003 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.28190679 | 60.00 | 49.00 | 11.00 | 0.000 | 12107.62 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00773011 | 21.00 | 0.00773011 | 49.2844 | 8932.12 | 0.00 | 12819.12 | 12819.12 | 0.45818212 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61038.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19237.145 | 19237.145 | 0.581866 | 0.00042502 | 401.342 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.6122 | 0.658256 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 18252.37 | 19237.14 | 1.0000 | 0.69066952 | 0.581866 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.42497785 | 60.00 | 49.00 | 11.00 | 0.000 | 18252.37 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772164 | 21.00 | 0.00772164 | 49.2311 | 13465.76 | 0.00 | 19324.97 | 19324.97 | 0.69066952 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12037.789 | 12037.789 | 0.369765 | 0.00026596 | 249.992 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 0.3831 | 0.411908 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11421.72 | 12037.79 | 1.0000 | 0.43890796 | 0.369765 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 0.26593310 | 60.00 | 49.00 | 11.00 | 0.000 | 11421.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00768739 | 21.00 | 0.00768739 | 49.0157 | 8370.45 | 0.00 | 12092.72 | 12092.72 | 0.43890796 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 39.82 | 21.10 | 0.00800000 | 60611.7 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 96713.460 | -999.000 | 5.419017 | 0.00411441 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4900 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.419017 | 6.43232380 | 4197.9300 | 999.8980 | 85.71215315 | 12.27 | 6.67 | 5.60 | 2014956.27 | 4.7998 | 4.799780 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 96713.46 | 87833.55 | 1.0000 | 6.43232380 | 5.419017 | 24.99 | 16.96 | 0.00895669 | 47929.2 | 11.40 | 11.39 | 0.00839822 | 32894.9 | 4.11399443 | 6.67 | 10.65 | 5.60 | 9188.781 | 87524.68 | 28.05 | 0.00879438 | 17.86 | 1.20008137 | 22.1457 | 24.00 | 0.00900945 | 24.00 | 0.00897191 | 47.5760 | 66374.18 | 0.00 | 108793.75 | 91953.63 | 6.43232380 | 24.99 | 17.11 | 0.00895669 | 47929.2 | 11.00 | 10.74 | 0.00791836 | 31015.6 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 264554.940 | 264554.940 | 5.419017 | 0.00584502 | 4885.951 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | CAV_BAS FAN | Fan:ConstantVolume | 5.419017 | 6.43232380 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 7.0484 | 9.052527 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 210129.58 | 264554.94 | 1.0000 | 6.43232380 | 5.419017 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 5.84442188 | 60.00 | 49.00 | 11.00 | 0.000 | 210129.58 | -4.20 | 0.00269032 | -4.20 | 1.20008137 | 22.1457 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 50.9797 | 0.00 | 0.00 | 221680.19 | 221680.19 | 6.43232380 | 12.80 | 2.78 | 0.00059579 | 14366.2 | 47.06 | 17.59 | 0.00059579 | 48829.6 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 168560.201 | -999.000 | 8.972271 | 0.00717094 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2984 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.972271 | 10.65000320 | 4197.9300 | 999.8980 | 85.71215315 | 12.27 | 6.67 | 5.60 | 2014956.27 | 8.3655 | 8.365452 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 168560.20 | 156251.88 | 1.0000 | 10.65000320 | 8.972271 | 25.64 | 17.09 | 0.00885361 | 48328.9 | 11.40 | 11.97 | 0.00839822 | 34322.2 | 7.17020908 | 6.67 | 10.65 | 5.60 | 19388.600 | 149171.60 | 29.40 | 0.00879438 | 18.30 | 2.53804000 | 28.2876 | 24.00 | 0.00887947 | 24.00 | 0.00881328 | 46.7460 | 113289.82 | 0.00 | 188585.80 | 161302.77 | 10.65000320 | 25.64 | 17.24 | 0.00885361 | 48328.9 | 10.81 | 10.58 | 0.00783744 | 30621.3 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52563.377 | 52563.377 | 2.691681 | 0.00116132 | 758.167 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.972271 | 10.65000320 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 1.3545 | 1.798611 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 40379.87 | 52563.38 | 1.0000 | 3.19500096 | 2.691681 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.16120512 | 60.00 | 49.00 | 11.00 | 0.000 | 40379.87 | -4.20 | 0.00269032 | -4.20 | 2.53804000 | 94.2920 | 6.80 | 0.00188435 | 21.00 | 0.00738131 | 47.0855 | 10581.12 | 0.00 | 42697.93 | 42697.93 | 3.19500096 | 12.80 | 5.50 | 0.00264431 | 19538.1 | 26.03 | 11.61 | 0.00264431 | 32902.1 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1588938.496 | -999.000 | 82.654371 | 0.06759712 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3474 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.654371 | 98.10997637 | 4197.9300 | 999.8980 | 85.71215315 | 12.27 | 6.67 | 5.60 | 2014956.27 | 78.8572 | 78.857220 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1588938.50 | 1468188.46 | 1.0000 | 98.10997637 | 82.654371 | 25.83 | 17.18 | 0.00887998 | 48593.7 | 11.40 | 11.97 | 0.00839822 | 34322.2 | 67.59022118 | 6.67 | 10.65 | 5.60 | 188760.085 | 1400178.41 | 29.40 | 0.00879438 | 18.30 | 25.38036000 | 30.7066 | 24.00 | 0.00892403 | 24.00 | 0.00883241 | 46.8461 | 1013463.79 | 0.00 | 1773683.30 | 1510774.96 | 98.10997637 | 25.83 | 17.33 | 0.00887998 | 48593.7 | 10.76 | 10.53 | 0.00781699 | 30515.2 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 502791.928 | 502791.928 | 24.796311 | 0.01110857 | 7215.421 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.654371 | 98.10997637 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 12.8616 | 17.204507 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 383436.30 | 502791.93 | 1.0000 | 29.43299291 | 24.796311 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 11.10744007 | 60.00 | 49.00 | 11.00 | 0.000 | 383436.30 | -4.20 | 0.00269032 | -4.20 | 25.38036000 | 102.3554 | 20.77 | 0.00770878 | 21.00 | 0.00770878 | 49.1496 | 513061.15 | 0.00 | 405441.83 | 405441.83 | 29.43299291 | 12.80 | 5.55 | 0.00269032 | 19654.3 | 26.44 | 11.83 | 0.00269032 | 33429.4 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 160744.111 | -999.000 | 8.525242 | 0.00683843 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2895 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.525242 | 10.11938410 | 4197.9300 | 999.8980 | 85.71215315 | 12.27 | 6.67 | 5.60 | 2014956.27 | 7.9775 | 7.977548 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 160744.11 | 149097.32 | 1.0000 | 10.11938410 | 8.525242 | 25.61 | 17.08 | 0.00884879 | 48283.0 | 11.40 | 11.97 | 0.00839822 | 34322.2 | 6.83772847 | 6.67 | 10.65 | 5.60 | 19469.333 | 141274.78 | 29.40 | 0.00879438 | 18.30 | 2.53804000 | 29.7709 | 24.00 | 0.00887187 | 24.00 | 0.00882984 | 46.8327 | 115608.32 | 0.00 | 179788.39 | 153494.03 | 10.11938410 | 25.61 | 17.23 | 0.00884879 | 48283.0 | 10.76 | 10.53 | 0.00781805 | 30516.3 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 51272.509 | 51272.509 | 2.557573 | 0.00113280 | 736.931 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.525242 | 10.11938410 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 1.3145 | 1.754440 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 12:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 39188.38 | 51272.51 | 1.0000 | 3.03581523 | 2.557573 | -4.14 | -4.14 | 0.00270318 | 2582.3 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 1.13268789 | 60.00 | 49.00 | 11.00 | 0.000 | 39188.38 | -4.20 | 0.00269032 | -4.20 | 2.53804000 | 99.2363 | 21.00 | 0.00786755 | 21.00 | 0.00786030 | 50.1023 | 58514.74 | 0.00 | 41437.94 | 41437.94 | 3.03581523 | 12.80 | 5.60 | 0.00272986 | 19754.1 | 26.32 | 11.81 | 0.00272986 | 33403.8 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 423313.101 | 303441.425 | 21.500769 | 0.01036691 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6497 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 06:00:00 | 455696.28 | 455386.68 | 0.9289 | -999.0 | -999.0 | 28.46 | 17.76 | 0.00850464 | 50315.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 455696.28 | 29.40 | 0.00879438 | 18.30 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 369325.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9429.602 | 6860.575 | 0.493003 | 0.00023093 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6584 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 10199.69 | 10185.31 | 0.9245 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850933 | 49781.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10199.69 | 25.86 | 0.00879438 | 17.12 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 8481.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 90108.009 | 65559.616 | 4.711210 | 0.00220674 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6592 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 97467.38 | 97323.63 | 0.9245 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850977 | 49781.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 97467.38 | 25.86 | 0.00879438 | 17.12 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 81047.79 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9149.279 | 6656.681 | 0.478356 | 0.00022407 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.6590 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 9896.51 | 9882.13 | 0.9245 | -999.0 | -999.0 | 27.92 | 17.58 | 0.00850962 | 49781.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9896.51 | 25.86 | 0.00879438 | 17.12 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 37.7427 | 8229.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 423313.101 | 423313.101 | 21.500769 | 0.01036691 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 423313.10 | 423313.10 | 1.0000 | 25.52121467 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 423313.10 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5738 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9429.602 | 9429.602 | 0.493003 | 0.00023093 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9429.60 | 9429.60 | 1.0000 | 0.58519059 | 0.493003 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9429.60 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.1706 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 90108.009 | 90108.009 | 4.711210 | 0.00220674 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 90108.01 | 90108.01 | 1.0000 | 5.59216248 | 4.711210 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 90108.01 | -4.20 | 0.00269032 | -4.20 | 0.15631366 | 3.3179 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9149.279 | 9149.279 | 0.478356 | 0.00022407 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 9149.28 | 9149.28 | 1.0000 | 0.56780469 | 0.478356 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9149.28 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.2677 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17838.917 | 17838.917 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.500769 | 25.52121467 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 17838.92 | 17838.92 | 1.0000 | 25.52121467 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17838.92 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5738 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.500769 | 25.52121467 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10000000.00 | 1150273.12 | 1.0000 | 25.52121467 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5738 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1027503.572 | 1027503.572 | 21.500769 | 0.02270144 | 19115.725 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.500769 | 25.52121467 | 4197.9300 | 999.8980 | 64.56122157 | 71.00 | 82.00 | 11.00 | 2981258.38 | 27.6703 | 35.159062 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824924.23 | 1027503.57 | 1.0000 | 25.52121467 | 21.500769 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | 22.69912009 | 60.00 | 49.00 | 11.00 | 0.000 | 824924.23 | -4.20 | 0.00269032 | -4.20 | 0.33837161 | 1.5738 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52121467 | 16.60 | 4.09 | 0.00004234 | 16787.5 | 16.60 | 4.09 | 0.00004234 | 16787.5 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.493003 | 0.58519059 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 1.0000 | 0.58519059 | 0.493003 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.08 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.1706 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8240.841 | 8240.841 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.711210 | 5.59216248 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8240.84 | 8240.84 | 1.0000 | 5.59216248 | 4.711210 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8240.84 | -4.20 | 0.00269032 | -4.20 | 0.15631366 | 3.3179 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 824.084 | 824.084 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.478356 | 0.56780469 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 824.08 | 824.08 | 1.0000 | 0.56780469 | 0.478356 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 824.08 | -4.20 | 0.00269032 | -4.20 | 0.01563137 | 3.2677 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 61.4353 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.42 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.97 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 82.65 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.53 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2607.83 | 188.83 | 4.33 |
CORE_BOTTOM | 2632.33 | 330.50 | 12.67 |
CORE_MID | 1226.67 | 2382.50 | 12.17 |
CORE_TOP | 1216.17 | 3717.50 | 260.33 |
PERIMETER_BOT_ZN_3 | 1404.17 | 2728.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 1054.33 | 4059.50 | 27.33 |
PERIMETER_BOT_ZN_1 | 1564.00 | 3298.67 | 39.67 |
PERIMETER_BOT_ZN_4 | 2722.33 | 1899.50 | 66.00 |
PERIMETER_MID_ZN_3 | 1118.33 | 4366.00 | 448.17 |
PERIMETER_MID_ZN_2 | 1057.67 | 4100.67 | 477.33 |
PERIMETER_MID_ZN_1 | 1339.83 | 4072.83 | 266.33 |
PERIMETER_MID_ZN_4 | 1111.33 | 4607.00 | 322.33 |
PERIMETER_TOP_ZN_3 | 1781.33 | 4629.83 | 1152.67 |
PERIMETER_TOP_ZN_2 | 1890.50 | 4750.17 | 1101.00 |
PERIMETER_TOP_ZN_1 | 1754.17 | 4427.67 | 839.83 |
PERIMETER_TOP_ZN_4 | 1595.33 | 4827.83 | 879.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 4344.50 | 5444.33 | 1309.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 92.67 | 0.00 | 7.17 |
CORE_BOTTOM | 0.00 | 1.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.67 | 0.00 | 0.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 5.17 | 0.00 | 5.17 |
PERIMETER_BOT_ZN_1 | 0.00 | 5.33 | 0.00 | 5.33 |
PERIMETER_BOT_ZN_4 | 0.00 | 33.83 | 0.00 | 14.50 |
PERIMETER_MID_ZN_3 | 1.00 | 0.00 | 0.17 | 0.00 |
PERIMETER_MID_ZN_2 | 0.67 | 4.67 | 0.00 | 4.67 |
PERIMETER_MID_ZN_1 | 0.33 | 7.67 | 0.00 | 7.67 |
PERIMETER_MID_ZN_4 | 0.33 | 9.33 | 0.00 | 4.00 |
PERIMETER_TOP_ZN_3 | 30.17 | 0.00 | 8.50 | 0.00 |
PERIMETER_TOP_ZN_2 | 16.17 | 2.83 | 1.33 | 2.83 |
PERIMETER_TOP_ZN_1 | 10.33 | 1.17 | 0.00 | 1.17 |
PERIMETER_TOP_ZN_4 | 8.17 | 9.83 | 0.00 | 4.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 17.50 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 14.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 11.50 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 59.50 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 32.50 | 223.00 | 9.00 | 49.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 1.434 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.994 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.749 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.690 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.865 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 1.491 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 1.356 | 0.042 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 1.934 | 0.043 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.670 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 1.353 | 0.105 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 1.261 | 0.095 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 1.498 | 0.098 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.667 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 1.407 | 0.122 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 1.278 | 0.118 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 1.550 | 0.122 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 60.99 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 54.77 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.86 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.88 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.88 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.43 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27186.43 | 366730.54 | 15-JAN-10:30 | 1830833.37 | 29-AUG-15:10 |
Electricity:Building | 18528.03 | 249962.80 | 01-JAN-09:50 | 1099600.76 | 01-DEC-16:20 |
Electricity:Zone:BASEMENT | 635.35 | 14476.27 | 01-JAN-06:10 | 31794.69 | 02-JAN-08:10 |
InteriorLights:Electricity | 3314.75 | 15753.54 | 01-JAN-09:50 | 305596.68 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:BASEMENT | 210.95 | 1018.73 | 01-JAN-06:10 | 18337.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3314.75 | 15753.54 | 01-JAN-09:50 | 305596.68 | 02-JAN-16:30 |
Electricity:Zone:CORE_BOTTOM | 510.73 | 6957.75 | 01-JAN-06:10 | 34596.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 189.45 | 914.89 | 01-JAN-06:10 | 16468.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5107.28 | 69577.31 | 01-JAN-06:10 | 345965.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1894.51 | 9148.91 | 01-JAN-06:10 | 164680.46 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 510.73 | 6957.73 | 01-JAN-06:10 | 34596.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 189.45 | 914.89 | 01-JAN-06:10 | 16468.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 59.07 | 842.63 | 01-JAN-09:40 | 4344.05 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.73 | 83.86 | 01-JAN-09:40 | 2067.73 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.05 | 543.02 | 01-JAN-09:20 | 2799.47 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.05 | 54.04 | 01-JAN-09:20 | 1332.52 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.99 | 842.65 | 01-JAN-09:20 | 4344.13 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.65 | 83.86 | 01-JAN-09:20 | 2067.77 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 38.04 | 543.02 | 01-JAN-09:40 | 2799.46 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 12.04 | 54.04 | 01-JAN-09:40 | 1332.52 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 590.82 | 8426.32 | 01-JAN-09:50 | 43440.45 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 187.40 | 838.59 | 01-JAN-09:50 | 20677.28 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 380.50 | 5430.24 | 01-JAN-09:20 | 27994.68 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.53 | 540.42 | 01-JAN-09:20 | 13325.22 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 590.01 | 8426.45 | 01-JAN-09:20 | 43441.26 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 186.59 | 838.61 | 01-JAN-09:20 | 20677.73 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 380.41 | 5430.21 | 01-JAN-09:40 | 27994.59 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 120.44 | 540.42 | 01-JAN-09:40 | 13325.22 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 59.08 | 842.63 | 01-JAN-09:50 | 4344.05 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.74 | 83.86 | 01-JAN-09:50 | 2067.73 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.05 | 543.02 | 01-JAN-09:20 | 2799.47 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.05 | 54.04 | 01-JAN-09:20 | 1332.52 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 59.00 | 842.65 | 01-JAN-09:20 | 4344.13 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.66 | 83.86 | 01-JAN-09:20 | 2067.77 | 02-JAN-16:30 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 38.04 | 543.02 | 01-JAN-09:40 | 2799.46 | 02-JAN-16:30 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 12.04 | 54.04 | 01-JAN-09:40 | 1332.52 | 02-JAN-16:30 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7554.34 | 95195.37 | 01-JAN-06:10 | 384802.81 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 59.48 | 287.24 | 01-JAN-06:10 | 5170.29 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.63 | 1961.87 | 01-JAN-06:10 | 8033.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.75 | 13.27 | 01-JAN-06:10 | 238.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1566.28 | 19618.75 | 01-JAN-06:10 | 80332.68 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 27.48 | 132.69 | 01-JAN-06:10 | 2388.46 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.63 | 1961.87 | 01-JAN-06:10 | 8033.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.75 | 13.27 | 01-JAN-06:10 | 238.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 4544.70 | 64723.14 | 04-JAN-03:50 | 314261.40 | 10-AUG-16:00 |
ExteriorEquipment:Electricity | 1987.97 | 13873.41 | 01-JAN-00:10 | 128039.29 | 28-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.06 | 1613.62 | 01-JAN-00:10 | 5441.84 | 01-DEC-16:30 |
ElectricityPurchased:Facility | 27186.43 | 366730.54 | 15-JAN-10:30 | 1830833.37 | 29-AUG-15:10 |
ElectricityPurchased:Plant | 27186.43 | 366730.54 | 15-JAN-10:30 | 1830833.37 | 29-AUG-15:10 |
Cogeneration:ElectricityPurchased | 27186.43 | 366730.54 | 15-JAN-10:30 | 1830833.37 | 29-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27186.43 | 366730.54 | 15-JAN-10:30 | 1830833.37 | 29-AUG-15:10 |
ElectricityNet:Plant | 27186.43 | 366730.54 | 15-JAN-10:30 | 1830833.37 | 29-AUG-15:10 |
Cogeneration:ElectricityNet | 27186.43 | 366730.54 | 15-JAN-10:30 | 1830833.37 | 29-AUG-15:10 |
Fans:Electricity | 2164.15 | 42012.79 | 01-JAN-02:00 | 139784.20 | 10-AUG-16:00 |
General:Fans:Electricity | 2164.15 | 42012.79 | 01-JAN-02:00 | 139784.20 | 10-AUG-16:00 |
ExteriorLights:Electricity | 657.05 | 0.00 | 01-JAN-08:10 | 53035.91 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 657.05 | 0.00 | 01-JAN-08:10 | 53035.91 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2661.81 | 20766.19 | 04-JAN-03:50 | 406777.37 | 29-AUG-14:40 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 15.23 | 0.00 | 01-JAN-00:10 | 33603.17 | 14-FEB-22:20 |
Electricity:Plant | 1555.74 | 5840.59 | 13-JAN-02:20 | 359692.33 | 29-AUG-14:40 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 383.55 | 0.00 | 01-JAN-00:10 | 239870.82 | 29-AUG-14:40 |
HeatRejection:Electricity | 873.63 | 2335.06 | 14-JAN-11:40 | 78938.91 | 27-APR-13:50 |
General:HeatRejection:Electricity | 25.61 | 0.00 | 01-JAN-00:10 | 29690.63 | 27-APR-13:50 |
Pumps:Electricity | 298.57 | 3322.96 | 03-JAN-00:20 | 47528.52 | 22-JUN-15:40 |
General:Pumps:Electricity | 298.57 | 3322.96 | 03-JAN-00:20 | 47528.52 | 22-JUN-15:40 |
WIRED_LTG_ELECTRICITY | 93.14 | 0.00 | 01-JAN-00:10 | 8587.27 | 02-JAN-16:40 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1338.69 | 5695.87 | 04-JAN-00:30 | 965571.26 | 02-JAN-06:10 |
Gas:Plant | 1338.69 | 5695.87 | 04-JAN-00:30 | 965571.26 | 02-JAN-06:10 |
WaterSystems:Gas | 572.26 | 5695.87 | 04-JAN-00:30 | 78085.77 | 14-FEB-12:40 |
Water Heater:WaterSystems:Gas | 572.26 | 5695.87 | 04-JAN-00:30 | 78085.77 | 14-FEB-12:40 |
Heating:Gas | 766.44 | 0.00 | 01-JAN-00:40 | 959875.39 | 02-JAN-06:10 |
Boiler:Heating:Gas | 766.44 | 0.00 | 01-JAN-00:40 | 959875.39 | 02-JAN-06:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 14271.58 | 95996.61 | 04-JAN-03:50 | 2133509.87 | 29-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 14271.58 | 95996.61 | 04-JAN-03:50 | 2133509.87 | 29-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 14271.58 | 95996.61 | 04-JAN-03:50 | 2133509.87 | 29-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 4267.67 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Water:Plant | 4262.01 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 4267.67 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
MainsWater:Plant | 4262.01 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 5.66 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-22:20 |
Humidifier:Water | 5.66 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-22:20 |
MainsWater:HVAC | 5.66 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-22:20 |
Humidifier:MainsWater | 5.66 | 0.00 | 01-JAN-00:10 | 0.00 | 14-FEB-22:20 |
HeatRejection:Water | 1981.84 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
HeatRejection:MainsWater | 1981.84 | 0.00 | 01-JAN-00:10 | 0.00 | 10-AUG-16:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 989.11 | 0.00 | 01-JAN-00:40 | 807044.39 | 02-JAN-06:20 |
PlantLoopHeatingDemand:Plant | 424.69 | 0.00 | 01-JAN-00:10 | 50359.61 | 14-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 424.69 | 0.00 | 01-JAN-00:10 | 50359.61 | 14-FEB-12:50 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 40011.23 | 154599.48 | 04-JAN-03:50 | 8236582.92 | 29-AUG-14:40 |
EnergyTransfer:Building | 18079.46 | 59202.11 | 28-JAN-18:10 | 1510759.09 | 10-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 694.03 | 0.00 | 01-JAN-00:40 | 77568.68 | 07-JAN-05:50 |
Heating:EnergyTransfer | 96.96 | 0.00 | 03-JAN-22:20 | 625018.35 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:BASEMENT | 8.52 | 0.00 | 01-JAN-00:40 | 58700.66 | 14-JAN-05:50 |
Cooling:EnergyTransfer | 17982.50 | 58981.08 | 28-JAN-18:10 | 1510759.09 | 10-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 685.51 | 0.00 | 01-JAN-00:10 | 75441.64 | 13-NOV-06:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 629.50 | 0.00 | 01-JAN-00:10 | 51761.57 | 10-OCT-09:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 629.50 | 0.00 | 01-JAN-00:10 | 51761.57 | 10-OCT-09:10 |
EnergyTransfer:Zone:CORE_MID | 4379.84 | 0.00 | 01-JAN-00:10 | 435293.12 | 10-AUG-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.68 | 0.00 | 01-JAN-00:10 | 185740.69 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4379.17 | 0.00 | 01-JAN-00:10 | 435293.12 | 10-AUG-05:10 |
EnergyTransfer:Zone:CORE_TOP | 384.32 | 0.00 | 01-JAN-00:40 | 60381.68 | 17-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 2.88 | 0.00 | 01-JAN-00:10 | 60381.68 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 381.44 | 0.00 | 01-JAN-00:40 | 48818.37 | 10-AUG-15:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.92 | 0.00 | 01-JAN-00:10 | 8697.92 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 65.92 | 0.00 | 01-JAN-00:10 | 8697.92 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.26 | 0.00 | 01-JAN-00:10 | 12539.27 | 31-JUL-08:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.26 | 0.00 | 01-JAN-00:10 | 12539.27 | 31-JUL-08:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.95 | 0.00 | 01-JAN-00:10 | 18953.12 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 01-JAN-00:10 | 1832.98 | 17-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 99.94 | 0.00 | 01-JAN-00:10 | 18953.12 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.09 | 0.00 | 01-JAN-00:10 | 16413.78 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 97.09 | 0.00 | 01-JAN-00:10 | 16413.78 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 437.26 | 0.00 | 01-JAN-00:10 | 84492.94 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 8.14 | 0.00 | 01-JAN-00:10 | 84492.94 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 429.13 | 0.00 | 01-JAN-00:10 | 73430.78 | 25-AUG-14:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 516.78 | 0.00 | 01-JAN-00:10 | 127392.41 | 10-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 6.76 | 0.00 | 01-JAN-00:10 | 63943.14 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 510.02 | 0.00 | 01-JAN-00:10 | 127392.41 | 10-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 809.83 | 0.00 | 01-JAN-00:10 | 196209.17 | 04-OCT-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 5.97 | 0.00 | 01-JAN-00:10 | 94333.22 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 803.86 | 0.00 | 01-JAN-00:10 | 196209.17 | 04-OCT-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 568.60 | 0.00 | 01-JAN-00:10 | 139954.07 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.93 | 0.00 | 01-JAN-00:10 | 49755.36 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 565.67 | 0.00 | 01-JAN-00:10 | 139954.07 | 10-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 44.65 | 0.00 | 01-JAN-00:40 | 10034.97 | 09-JAN-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 7.15 | 0.00 | 01-JAN-00:40 | 10034.97 | 09-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.50 | 0.00 | 01-JAN-00:20 | 8542.34 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 49.65 | 0.00 | 01-JAN-00:40 | 12592.58 | 10-AUG-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 4.73 | 0.00 | 01-JAN-00:40 | 10172.02 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.92 | 0.00 | 01-JAN-00:20 | 12592.58 | 10-AUG-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.40 | 0.00 | 01-JAN-00:40 | 20242.18 | 04-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 5.38 | 0.00 | 01-JAN-00:40 | 15050.30 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 72.03 | 0.00 | 01-JAN-00:20 | 20242.18 | 04-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 54.04 | 0.00 | 01-JAN-00:40 | 14609.92 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 2.64 | 0.00 | 01-JAN-00:40 | 9132.10 | 17-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 51.40 | 0.00 | 01-JAN-00:20 | 14609.92 | 10-AUG-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 64.79 | 0.00 | 01-JAN-00:10 | 7197.87 | 05-SEP-05:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 0.86 | 0.00 | 01-JAN-00:10 | 2999.51 | 01-MAY-03:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 63.93 | 0.00 | 01-JAN-00:10 | 7197.87 | 05-SEP-05:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 393.95 | 0.00 | 01-JAN-00:10 | 72485.02 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 18.34 | 0.00 | 01-JAN-00:10 | 72485.02 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 375.60 | 0.00 | 01-JAN-00:10 | 49487.32 | 10-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 61.54 | 0.00 | 01-JAN-00:40 | 16675.48 | 17-JAN-06:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 19.75 | 0.00 | 01-JAN-00:40 | 16675.48 | 17-JAN-06:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 41.78 | 0.00 | 01-JAN-00:10 | 15451.55 | 10-AUG-14:40 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.22 | 793.01 | 21-JAN-18:20 | 8035.77 | 06-AUG-19:20 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.22 | 793.01 | 21-JAN-18:20 | 8035.77 | 06-AUG-19:20 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1180.25 | 1.88 | 08-JAN-08:20 | 76218.01 | 06-AUG-19:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1.14 | 0.00 | 02-JAN-11:50 | 5313.47 | 01-JAN-22:30 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1179.11 | 0.00 | 01-JAN-00:10 | 76218.01 | 06-AUG-19:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.67 | 0.01 | 06-JAN-23:20 | 7723.73 | 06-AUG-19:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.71 | 0.00 | 02-JAN-15:20 | 584.88 | 08-JAN-17:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.96 | 0.00 | 01-JAN-00:10 | 7723.73 | 06-AUG-19:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.91 | 55783.45 | 28-JAN-18:10 | 374388.05 | 29-DEC-22:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.37 | 0.00 | 01-JAN-00:10 | 9844.20 | 04-JAN-23:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7156.55 | 55783.45 | 28-JAN-18:10 | 374388.05 | 29-DEC-22:50 |
EnergyTransfer:Plant | 9248.95 | 0.00 | 01-JAN-00:40 | 4775513.29 | 29-AUG-14:40 |
WaterSystems:EnergyTransfer | 424.69 | 0.00 | 01-JAN-00:10 | 50359.61 | 14-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 424.69 | 0.00 | 01-JAN-00:10 | 50359.61 | 14-FEB-12:50 |
EnergyTransfer:HVAC | 12682.82 | 78714.20 | 04-JAN-03:50 | 1966603.32 | 29-AUG-14:40 |
HeatingCoils:EnergyTransfer | 564.42 | 0.00 | 01-JAN-00:40 | 800849.46 | 02-JAN-06:20 |
PlantLoopHeatingDemand:HVAC | 564.42 | 0.00 | 01-JAN-00:40 | 800849.46 | 02-JAN-06:20 |
HeatingCoils:PlantLoopHeatingDemand | 564.42 | 0.00 | 01-JAN-00:40 | 800849.46 | 02-JAN-06:20 |
CoolingCoils:EnergyTransfer | 12118.40 | 78714.20 | 04-JAN-03:50 | 1966603.32 | 29-AUG-14:40 |
LoopToLoop:EnergyTransfer | 2832.84 | -7899.99 | 11-JAN-14:00 | 1500944.96 | 29-AUG-14:40 |
Boilers:EnergyTransfer | 554.41 | 0.00 | 01-JAN-00:40 | 792931.25 | 02-JAN-06:10 |
Chillers:EnergyTransfer | 2526.73 | 0.00 | 01-JAN-00:10 | 1504868.07 | 29-AUG-14:40 |
HeatRejection:EnergyTransfer | 2910.28 | 0.00 | 01-JAN-00:10 | 1744738.90 | 29-AUG-14:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 8.521 | -685.508 | 0.000 | 0.000 | 92.709 | 210.953 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -51.073 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -629.495 | 0.000 | 0.000 | 83.404 | 189.451 | 321.278 | 0.000 | 0.000 | 0.000 | 35.361 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 0.677 | -4379.146 | 0.000 | 0.000 | 841.449 | 1894.509 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1570.262 |
CORE_TOP | 0.000 | 0.000 | 2.883 | -381.432 | 0.000 | 0.000 | 86.729 | 189.451 | 321.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -218.908 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.000 | -65.919 | 0.000 | 0.000 | 10.608 | 18.729 | 40.341 | 14.633 | 0.000 | 0.017 | 38.679 | 0.000 | -50.107 | 0.000 | -6.982 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.000 | -67.260 | 0.000 | 0.000 | 7.147 | 12.050 | 25.998 | 32.380 | 0.000 | 0.015 | 24.095 | 0.000 | -30.070 | 0.000 | -4.356 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.004 | -99.943 | 0.000 | 0.000 | 10.888 | 18.651 | 40.342 | 66.144 | 0.000 | 0.018 | 15.890 | 0.000 | -45.264 | 0.000 | -6.729 | 0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -97.091 | 0.000 | 0.000 | 6.891 | 12.041 | 25.997 | 34.474 | 0.000 | 0.009 | 57.650 | 0.000 | -35.037 | 0.000 | -4.936 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 8.138 | -429.124 | 0.000 | 0.000 | 111.834 | 187.404 | 403.414 | 154.762 | 0.000 | 0.450 | 144.946 | 0.000 | -443.453 | 0.000 | -138.373 | -0.001 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 6.761 | -510.016 | 0.000 | 0.000 | 54.913 | 120.527 | 259.975 | 327.748 | 0.000 | 0.342 | 106.598 | 0.000 | -276.398 | 0.000 | -90.450 | -0.002 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 5.973 | -803.857 | 0.000 | 0.000 | 112.289 | 186.591 | 403.420 | 665.155 | 0.000 | 0.396 | 2.779 | 0.000 | -430.688 | 0.000 | -142.058 | -0.002 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.931 | -565.662 | 0.000 | 0.000 | 74.921 | 120.441 | 259.973 | 357.808 | 0.000 | 0.258 | 139.325 | 0.000 | -295.496 | 0.000 | -94.500 | 0.000 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 7.147 | -37.502 | 0.000 | 0.000 | 11.486 | 18.740 | 40.341 | 15.877 | 0.000 | 0.051 | 0.733 | 0.000 | -40.945 | 0.000 | -15.927 | -0.001 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 4.731 | -44.922 | 0.000 | 0.000 | 7.522 | 12.053 | 25.998 | 33.046 | 0.000 | 0.037 | 0.000 | 0.000 | -25.919 | 0.000 | -10.527 | -2.017 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 5.377 | -72.027 | 0.000 | 0.000 | 11.490 | 18.659 | 40.342 | 67.227 | 0.000 | 0.046 | 0.000 | 0.000 | -40.219 | 0.000 | -16.407 | -14.487 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 2.637 | -51.403 | 0.000 | 0.000 | 7.618 | 12.044 | 25.997 | 35.996 | 0.000 | 0.031 | 6.021 | 0.000 | -27.882 | 0.000 | -11.059 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.220 | 0.000 | 0.000 | 0.000 | 2.748 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -19.408 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 1.138 | -1179.114 | 0.000 | 0.000 | 0.000 | 27.477 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -388.307 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.711 | -107.959 | 0.000 | 0.000 | 0.000 | 2.748 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.380 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.366 | -7156.544 | 0.000 | 0.000 | 0.000 | 59.480 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -398.159 |
GROUNDFLOOR_PLENUM | 0.864 | -63.930 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.026 | 77.110 | 0.000 | 0.000 | 0.000 | -14.069 | 0.000 |
MIDFLOOR_PLENUM | 18.345 | -375.603 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.551 | 593.442 | 0.000 | 0.000 | 0.000 | -236.735 | -0.003 |
TOPFLOOR_PLENUM | 19.754 | -41.780 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.029 | 46.998 | 0.000 | 0.000 | 0.000 | -25.001 | -0.001 |
Total Facility | 38.963 | -481.314 | 57.994 | -17501.144 | 0.000 | 0.000 | 1531.899 | 3314.746 | 15213.288 | 1805.251 | 0.000 | 2.276 | 1289.627 | 0.000 | -1741.478 | 0.000 | -818.109 | -2712.012 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 12-NOV-15:40 | 0.00 | 0.00 | 0.00 | -116192.69 | 0.00 | 0.00 | 402.14 | 1018.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 101314.28 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 12-JUN-03:03 | 0.00 | 0.00 | 0.00 | -82308.64 | 0.00 | 0.00 | 0.00 | 991.43 | 8057.15 | 0.00 | 0.00 | 0.00 | 73260.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-AUG-04:02 | 0.00 | 0.00 | 0.00 | -722256.36 | 0.00 | 0.00 | 0.00 | 19828.60 | 80571.20 | 0.00 | 0.00 | 0.00 | 621856.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-AUG-04:02 | 0.00 | 0.00 | 0.00 | -69007.50 | 0.00 | 0.00 | 0.00 | 1982.86 | 8057.12 | 0.00 | 0.00 | 0.00 | 58967.52 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 10-AUG-05:03 | 0.00 | 0.00 | 0.00 | -9021.10 | 0.00 | 0.00 | 110.60 | 225.18 | 1011.70 | 0.00 | 0.00 | 0.00 | 8068.53 | 0.00 | -361.20 | 0.00 | -33.71 | 0.00 |
PERIMETER_BOT_ZN_2 | 30-JUL-09:32 | 0.00 | 0.00 | 0.00 | -19349.27 | 0.00 | 0.00 | 24.21 | 54.04 | 488.98 | 11428.08 | 0.00 | 0.00 | 7425.09 | 0.00 | -0.00 | 0.00 | -71.13 | 0.00 |
PERIMETER_BOT_ZN_1 | 08-OCT-12:02 | 0.00 | 0.00 | 0.00 | -21081.45 | 0.00 | 0.00 | 41.59 | 83.86 | 758.78 | 20453.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -151.79 | -104.65 |
PERIMETER_BOT_ZN_4 | 07-MAY-16:41 | 0.00 | 0.00 | 0.00 | -25091.10 | 0.00 | 0.00 | 20.77 | 54.04 | 488.98 | 16148.94 | 0.00 | 0.00 | 8511.59 | 0.00 | -0.00 | 0.00 | -133.22 | 0.00 |
PERIMETER_MID_ZN_3 | 10-AUG-05:03 | 0.00 | 0.00 | 0.00 | -77136.22 | 0.00 | 0.00 | 1130.06 | 2249.46 | 10116.97 | 0.00 | 0.00 | 0.00 | 67523.51 | 0.00 | -3139.96 | 0.00 | -743.83 | 0.00 |
PERIMETER_MID_ZN_2 | 30-JUL-09:42 | 0.00 | 0.00 | 0.00 | -200530.41 | 0.00 | 0.00 | 234.49 | 540.42 | 4889.82 | 103188.20 | 0.00 | 0.00 | 93317.04 | 0.00 | -0.00 | 0.00 | -1639.56 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-13:42 | 0.00 | 0.00 | 0.00 | -240024.14 | 0.00 | 0.00 | 353.36 | 838.61 | 7587.84 | 177669.20 | 0.00 | 0.00 | 55920.29 | 0.00 | -0.00 | 0.00 | -2345.16 | 0.00 |
PERIMETER_MID_ZN_4 | 07-MAY-16:41 | 0.00 | 0.00 | 0.00 | -221007.18 | 0.00 | 0.00 | 215.06 | 540.42 | 4889.79 | 160842.42 | 0.00 | 0.00 | 57591.23 | 0.00 | -0.00 | 0.00 | -3071.73 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -8542.25 | 0.00 | 0.00 | 1114.39 | 1509.46 | 2276.32 | 4598.70 | 0.00 | 98.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1055.46 |
PERIMETER_TOP_ZN_2 | 25-JUN-09:12 | 0.00 | 0.00 | 0.00 | -17460.87 | 0.00 | 0.00 | 26.18 | 54.04 | 488.98 | 11266.63 | 0.00 | 0.00 | 5963.47 | 0.00 | -0.00 | 0.00 | -338.43 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:42 | 0.00 | 0.00 | 0.00 | -25231.88 | 0.00 | 0.00 | 35.84 | 83.86 | 758.78 | 17753.73 | 0.00 | 0.00 | 6889.33 | 0.00 | -0.00 | 0.00 | -289.67 | 0.00 |
PERIMETER_TOP_ZN_4 | 14-MAY-17:11 | 0.00 | 0.00 | 0.00 | -23074.97 | 0.00 | 0.00 | 0.00 | 58.56 | 488.98 | 15587.53 | 0.00 | 0.00 | 7450.56 | 0.00 | -0.00 | 0.00 | -510.66 | 0.00 |
DATACENTER_BOT_ZN_6 | 06-AUG-19:20 | 0.00 | 0.00 | 0.00 | -8043.70 | 0.00 | 0.00 | 0.00 | 14.38 | 7794.42 | 0.00 | 0.00 | 0.00 | 234.89 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 06-AUG-19:12 | 0.00 | 0.00 | 0.00 | -76312.50 | 0.00 | 0.00 | 0.00 | 143.79 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1775.51 |
DATACENTER_TOP_ZN_6 | 06-AUG-19:12 | 0.00 | 0.00 | 0.00 | -7736.16 | 0.00 | 0.00 | 0.00 | 14.38 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -72.64 |
DATACENTER_BASEMENT_ZN_6 | 01-MAR-23:52 | 0.00 | 0.00 | 0.00 | -399121.38 | 0.00 | 0.00 | 0.00 | 287.24 | 284724.39 | 0.00 | 0.00 | 0.00 | 114109.75 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 10-OCT-05:05 | 0.00 | -9306.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9453.41 | 0.00 | -0.00 | 0.00 | -146.73 | 0.00 |
MIDFLOOR_PLENUM | 14-SEP-05:13 | 0.00 | -61120.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61120.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:40 | 0.00 | -15451.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.16 | 15379.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 10-AUG-05:03 | 0.00 | 4081.25 | 0.00 | -1677190.13 | 0.00 | 0.00 | 15500.80 | 33773.64 | 623236.89 | 47584.91 | 0.00 | 0.00 | 988602.54 | 0.00 | -31172.59 | 0.00 | -4417.30 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-JAN-05:46 | 0.00 | 0.00 | 127022.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2207.91 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -142688.44 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 287322.46 | -0.00 | 0.00 | 0.00 | 0.00 | 19828.60 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -387722.26 |
CORE_TOP | 17-JAN-04:01 | 0.00 | 0.00 | 68046.46 | -0.00 | 0.00 | 0.00 | 0.00 | 991.43 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -77095.01 |
PERIMETER_BOT_ZN_3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 17-JAN-06:01 | 0.00 | 0.00 | 6992.90 | -0.00 | 0.00 | 0.00 | 143.78 | 229.75 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3132.06 | 0.00 | -93.62 | -5152.46 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 02-JAN-04:01 | 0.00 | 0.00 | 95135.58 | -0.00 | 0.00 | 0.00 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -16871.14 | 0.00 | -12132.12 | -77494.13 |
PERIMETER_MID_ZN_2 | 02-JAN-04:01 | 0.00 | 0.00 | 117571.20 | -0.00 | 0.00 | 0.00 | 0.00 | 802.22 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -11360.13 | 0.00 | -8142.07 | -105390.98 |
PERIMETER_MID_ZN_1 | 02-JAN-04:01 | 0.00 | 0.00 | 164974.24 | -0.00 | 0.00 | 0.00 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -17297.51 | 0.00 | -12348.01 | -146690.70 |
PERIMETER_MID_ZN_4 | 02-JAN-04:01 | 0.00 | 0.00 | 103299.47 | -0.00 | 0.00 | 0.00 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -12421.55 | 0.00 | -8849.96 | -89349.90 |
PERIMETER_TOP_ZN_3 | 01-JAN-22:01 | 0.00 | 0.00 | 11440.11 | -0.00 | 0.00 | 0.00 | 0.00 | 124.48 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1590.90 | 0.00 | -1557.06 | -9175.41 |
PERIMETER_TOP_ZN_2 | 17-JAN-04:01 | 0.00 | 0.00 | 14657.37 | -0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1447.62 | 0.00 | -75.62 | -13866.33 |
PERIMETER_TOP_ZN_1 | 17-JAN-04:01 | 0.00 | 0.00 | 20672.16 | -0.00 | 0.00 | 0.00 | 0.00 | 124.49 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2155.32 | 0.00 | -113.42 | -19539.61 |
PERIMETER_TOP_ZN_4 | 17-JAN-04:01 | 0.00 | 0.00 | 14608.70 | -0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1487.52 | 0.00 | -76.74 | -13776.64 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-21:25 | 0.00 | 0.00 | 5315.12 | 0.00 | 0.00 | 0.00 | 0.00 | 143.79 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24944.97 |
DATACENTER_TOP_ZN_6 | 08-JAN-17:20 | 0.00 | 0.00 | 584.88 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2546.75 |
DATACENTER_BASEMENT_ZN_6 | 04-JAN-23:31 | 0.00 | 0.00 | 61031.88 | 0.00 | 0.00 | 0.00 | 0.00 | 287.24 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -156227.25 |
GROUNDFLOOR_PLENUM | 04-DEC-04:01 | 12178.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -863.33 | -11315.13 |
MIDFLOOR_PLENUM | 02-JAN-06:13 | 90408.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5460.85 | -84947.29 |
TOPFLOOR_PLENUM | 17-JAN-06:13 | 18779.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -302.42 | -18476.87 |
Total Facility | 02-JAN-05:01 | -242351.51 | 265960.09 | 855233.44 | -265960.09 | 0.00 | 0.00 | 0.00 | 36795.82 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -78840.86 | 0.00 | -67820.13 | -771379.46 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.4190 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.4190 | 0.2215 | 1.0000 | 1.2001 | 0.2215 | ||
VAV_BOT WITH REHEAT | 10.2523 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.9723 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 96.7373 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 82.6544 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.7432 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.5252 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5008 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5008 | 0.0157 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4930 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4930 | 0.0317 | 1.0000 | 0.0156 | 0.0317 | ||
AIRLOOP DATACENTER MID | 4.7112 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.7112 | 0.0332 | 1.0000 | 0.1563 | 0.0332 | ||
AIRLOOP DATACENTER TOP | 0.4784 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4784 | 0.0327 | 1.0000 | 0.0156 | 0.0327 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.4190 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.4190 | 1.0000 | 1.0000 | 1.2001 | 0.2215 | ||
VAV_BOT WITH REHEAT | 5.1261 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.2758 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.3686 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 31.8541 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.8716 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.2487 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.5008 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.5008 | 1.0000 | 1.0000 | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4930 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4930 | 1.0000 | 1.0000 | 0.0156 | 0.0317 | ||
AIRLOOP DATACENTER MID | 4.7112 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.7112 | 1.0000 | 1.0000 | 0.1563 | 0.0332 | ||
AIRLOOP DATACENTER TOP | 0.4784 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4784 | 1.0000 | 1.0000 | 0.0156 | 0.0327 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.4190 | 5.4190 | 5.4190 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6610 | 5.6610 | 1.8908 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.9716 | 52.9716 | 18.4341 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.1343 | 5.1343 | 1.8637 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7655 | 0.7655 | 0.2373 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1087 | 1.1087 | 0.3326 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3889 | 1.3889 | 0.4167 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3282 | 1.3282 | 0.3985 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7511 | 6.7511 | 2.3156 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.3252 | 11.3252 | 3.3976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 13.9678 | 13.9678 | 4.1903 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.7216 | 11.7216 | 3.5165 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7721 | 0.7721 | 0.2340 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1206 | 1.1206 | 0.3362 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4836 | 1.4836 | 0.4451 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2326 | 1.2326 | 0.3698 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4930 | 0.4930 | 0.4930 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.7112 | 4.7112 | 4.7112 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4784 | 0.4784 | 0.4784 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5008 | 21.5008 | 21.5008 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.4190 | 5.4190 | 5.4190 | 5.4190 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 10.2523 | 8.9723 | 10.2523 | 3.2758 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 96.7373 | 82.6544 | 96.7373 | 31.8541 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.7432 | 8.5252 | 9.7432 | 3.2487 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5008 | 21.5008 | 21.5008 | 21.5008 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4930 | 0.4930 | 0.4930 | 0.4930 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7112 | 4.7112 | 4.7112 | 4.7112 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4784 | 0.4784 | 0.4784 | 0.4784 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.4190 | 5.4190 | 5.4190 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8305 | 2.8305 | 1.8908 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.4858 | 26.4858 | 18.4341 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.5671 | 2.5671 | 1.8637 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3828 | 0.3828 | 0.2373 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5543 | 0.5543 | 0.3326 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6944 | 0.6944 | 0.4167 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6641 | 0.6641 | 0.3985 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3756 | 3.3756 | 2.3156 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6626 | 5.6626 | 3.3976 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.9839 | 6.9839 | 4.1903 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8608 | 5.8608 | 3.5165 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3861 | 0.3861 | 0.2340 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5603 | 0.5603 | 0.3362 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7418 | 0.7418 | 0.4451 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6163 | 0.6163 | 0.3698 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4930 | 0.4930 | 0.4930 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.7112 | 4.7112 | 4.7112 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4784 | 0.4784 | 0.4784 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.5008 | 21.5008 | 21.5008 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.4190 | 5.4190 | 5.4190 | 5.4190 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 5.1261 | 3.2758 | 3.2758 | 3.2758 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.3686 | 31.8541 | 31.8541 | 31.8541 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.8716 | 3.2487 | 3.2487 | 3.2487 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5008 | 21.5008 | 21.5008 | 21.5008 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4930 | 0.4930 | 0.4930 | 0.4930 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7112 | 4.7112 | 4.7112 | 4.7112 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4784 | 0.4784 | 0.4784 | 0.4784 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:57:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 9.00 |
Number of hours cooling loads not met | 49.33 |
Number of hours not met | 58.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 766.44 | 959875.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 383.55 | 239870.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2278.26 | 166906.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3314.75 | 305596.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 657.05 | 53035.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.06 | 5441.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2164.15 | 139784.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 298.57 | 47528.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 25.61 | 29690.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 848.02 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 15.23 | 33603.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 572.26 | 78085.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 27186.43 |
Natural Gas | 0.00 | 1338.69 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 28525.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 71.56 |
Space Heating | 0.00 |
Space Cooling | 57.47 |
Fans (All) | 46.72 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 586.92 |
Subtotal | 586.92 |
Natural Gas [MJ/m2] | |
Space Heating | 16.55 |
Service Water Heating | 12.35 |
Miscellaneous (All) | 28.90 |
Subtotal | 28.90 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.62 |
Space Heating | 2.69 |
Space Cooling | 9.33 |
Fans (All) | 7.59 |
Service Water Heating | 2.01 |
Receptacle Equipment | 53.33 |
Miscellaneous | 13.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2724. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.262944E+12 |
February | 0.000 | 0.146325E+12 |
March | 0.000 | 0.438769E+11 |
April | 0.000 | 0.153436E+11 |
May | 0.000 | 0.289856E+10 |
June | 0.000 | 0.167265E+10 |
July | 0.000 | 0.932047E+09 |
August | 0.000 | 0.797133E+09 |
September | 0.000 | 0.310800E+10 |
October | 0.000 | 0.172193E+11 |
November | 0.000 | 0.879615E+11 |
December | 0.000 | 0.183358E+12 |
Annual Sum or Average | 0.766436E+12 | |
Minimum of Months | 0.000 | 0.797133E+09 |
Maximum of Months | 0.000 | 0.262944E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.506658E+11 | 113849.41 | 02-JAN-02:52 | 6.10 | 5.29 | 0.566255E+10 | 7499.15 | 05-JAN-10:20 | 2.60 | 2.43 |
February | 0.470817E+11 | 109480.90 | 21-FEB-02:41 | 2.38 | 1.47 | 0.513679E+10 | 7499.10 | 09-FEB-10:20 | 3.67 | 2.18 |
March | 0.587308E+11 | 110676.41 | 21-MAR-03:50 | 4.60 | 3.79 | 0.613259E+10 | 7499.14 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.558547E+11 | 111035.58 | 25-APR-03:50 | 6.78 | 4.98 | 0.545012E+10 | 7499.04 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.573190E+11 | 111158.00 | 01-MAY-02:52 | 11.70 | 9.59 | 0.590051E+10 | 7499.14 | 05-MAY-09:20 | 16.33 | 13.63 |
June | 0.597303E+11 | 112259.31 | 05-JUN-03:01 | 11.02 | 10.00 | 0.588200E+10 | 7499.17 | 09-JUN-13:20 | 21.87 | 13.50 |
July | 0.596464E+11 | 111782.73 | 03-JUL-00:23 | 13.35 | 9.83 | 0.547275E+10 | 7499.11 | 11-JUL-09:20 | 16.13 | 15.49 |
August | 0.652727E+11 | 106458.74 | 21-AUG-02:42 | 12.78 | 11.65 | 0.613676E+10 | 7499.53 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.579339E+11 | 109818.31 | 04-SEP-23:12 | 13.13 | 10.15 | 0.545150E+10 | 7499.12 | 14-SEP-09:20 | 17.57 | 15.53 |
October | 0.597014E+11 | 114837.52 | 02-OCT-03:01 | 9.90 | 8.49 | 0.566932E+10 | 7499.05 | 16-OCT-09:09 | 9.78 | 7.90 |
November | 0.578207E+11 | 116196.32 | 12-NOV-15:40 | 5.37 | 4.29 | 0.561427E+10 | 7499.02 | 15-NOV-10:30 | 7.50 | 5.82 |
December | 0.557502E+11 | 114289.74 | 04-DEC-04:01 | 5.73 | 2.00 | 0.546926E+10 | 7499.27 | 13-DEC-14:20 | 6.90 | 5.04 |
Annual Sum or Average | 0.685507E+12 | 0.679784E+11 | ||||||||
Minimum of Months | 0.470817E+11 | 106458.74 | 2.38 | 1.47 | 0.513679E+10 | 7499.02 | 2.60 | 2.18 | ||
Maximum of Months | 0.652727E+11 | 116196.32 | 13.35 | 11.65 | 0.613676E+10 | 7499.53 | 26.10 | 16.35 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.391738E+11 | 71443.88 | 02-JAN-04:02 | 6.60 | 5.58 | 0.506564E+10 | 6734.78 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.399395E+11 | 74006.32 | 27-FEB-04:02 | 12.70 | 7.47 | 0.460343E+10 | 6734.75 | 09-FEB-10:20 | 3.67 | 2.18 |
March | 0.538736E+11 | 71525.60 | 13-MAR-03:02 | 6.60 | 5.52 | 0.550242E+10 | 6734.79 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.562369E+11 | 74909.25 | 17-APR-03:02 | 6.10 | 5.06 | 0.488421E+10 | 6734.73 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.526427E+11 | 74756.45 | 30-MAY-03:02 | 10.60 | 9.73 | 0.528657E+10 | 6734.80 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.569629E+11 | 82303.82 | 12-JUN-03:03 | 15.00 | 13.35 | 0.527059E+10 | 6734.84 | 05-JUN-09:00 | 14.40 | 11.88 |
July | 0.621141E+11 | 79901.43 | 17-JUL-03:03 | 14.90 | 13.03 | 0.489612E+10 | 6734.69 | 12-JUL-13:09 | 16.05 | 14.01 |
August | 0.702544E+11 | 77840.13 | 10-AUG-03:01 | 18.33 | 15.09 | 0.549530E+10 | 6735.20 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.507614E+11 | 81275.51 | 01-SEP-03:02 | 16.18 | 14.31 | 0.488194E+10 | 6734.76 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.507191E+11 | 79603.30 | 10-OCT-03:02 | 12.20 | 10.91 | 0.508025E+10 | 6734.75 | 16-OCT-09:09 | 9.78 | 7.90 |
November | 0.486481E+11 | 75935.88 | 06-NOV-04:02 | 10.10 | 7.78 | 0.503282E+10 | 6734.74 | 13-NOV-10:50 | 2.62 | 2.57 |
December | 0.481690E+11 | 72891.22 | 11-DEC-04:02 | 2.88 | 2.18 | 0.490480E+10 | 6734.88 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.629496E+12 | 0.609041E+11 | ||||||||
Minimum of Months | 0.391738E+11 | 71443.88 | 2.88 | 2.18 | 0.460343E+10 | 6734.69 | 2.62 | 2.18 | ||
Maximum of Months | 0.702544E+11 | 82303.82 | 18.33 | 15.09 | 0.550242E+10 | 6735.20 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258653E+11 | 50533.05 | 12-JAN-06:02 | 6.70 | 6.36 | 0.484679E+10 | 6734.77 | 20-JAN-10:09 | 4.18 | 2.79 |
February | 0.266975E+11 | 57702.85 | 28-FEB-06:02 | 10.60 | 9.73 | 0.451156E+10 | 6734.75 | 09-FEB-10:20 | 3.67 | 2.18 |
March | 0.358126E+11 | 59026.02 | 03-MAR-06:01 | 6.60 | 6.17 | 0.545145E+10 | 6734.78 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.357263E+11 | 60266.77 | 05-APR-05:01 | 8.22 | 7.39 | 0.484968E+10 | 6734.70 | 14-APR-09:09 | 11.78 | 11.15 |
May | 0.420259E+11 | 65684.11 | 01-MAY-04:02 | 12.20 | 10.34 | 0.526004E+10 | 6734.77 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.439562E+11 | 68953.16 | 12-JUN-03:01 | 15.00 | 13.35 | 0.524707E+10 | 6734.77 | 05-JUN-09:00 | 14.40 | 11.88 |
July | 0.444137E+11 | 67156.59 | 10-JUL-03:01 | 13.80 | 12.22 | 0.487180E+10 | 6734.70 | 12-JUL-13:09 | 16.05 | 14.01 |
August | 0.483963E+11 | 72227.28 | 10-AUG-04:02 | 17.90 | 14.45 | 0.547367E+10 | 6735.03 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.409716E+11 | 67421.23 | 01-SEP-04:02 | 16.02 | 13.74 | 0.485706E+10 | 6734.74 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.359212E+11 | 63050.03 | 10-OCT-05:01 | 12.20 | 11.22 | 0.503894E+10 | 6734.76 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.302869E+11 | 60929.66 | 07-NOV-06:02 | 12.12 | 9.84 | 0.496458E+10 | 6734.72 | 24-NOV-10:09 | 5.68 | 4.12 |
December | 0.278432E+11 | 56212.94 | 15-DEC-06:02 | 6.20 | 3.69 | 0.479088E+10 | 6734.77 | 12-DEC-10:20 | 3.87 | 3.71 |
Annual Sum or Average | 0.437917E+12 | 0.601635E+11 | ||||||||
Minimum of Months | 0.258653E+11 | 50533.05 | 6.20 | 3.69 | 0.451156E+10 | 6734.70 | 3.67 | 2.18 | ||
Maximum of Months | 0.483963E+11 | 72227.28 | 17.90 | 14.45 | 0.547367E+10 | 6735.03 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200471E+11 | 20852.19 | 11-JAN-16:00 | 14.40 | 10.48 | 0.434086E+10 | 6658.57 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.206916E+11 | 29745.71 | 28-FEB-17:00 | 14.40 | 10.81 | 0.409562E+10 | 6734.45 | 09-FEB-14:00 | 6.10 | 3.45 |
March | 0.281355E+11 | 33058.22 | 15-MAR-16:00 | 11.10 | 7.71 | 0.517982E+10 | 6734.68 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.307873E+11 | 56271.88 | 28-APR-05:03 | 11.10 | 9.92 | 0.473005E+10 | 6734.71 | 14-APR-09:09 | 11.78 | 11.15 |
May | 0.386101E+11 | 59183.24 | 05-MAY-05:03 | 12.98 | 10.75 | 0.520930E+10 | 6734.75 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.427983E+11 | 68367.55 | 12-JUN-03:01 | 15.00 | 13.35 | 0.522700E+10 | 6734.74 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.447334E+11 | 64292.86 | 20-JUL-05:02 | 13.40 | 11.30 | 0.485845E+10 | 6734.66 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.480163E+11 | 69008.99 | 10-AUG-04:02 | 17.90 | 14.45 | 0.545354E+10 | 6735.01 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.364095E+11 | 63963.37 | 01-SEP-05:02 | 15.50 | 13.56 | 0.480202E+10 | 6734.69 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.283014E+11 | 52286.49 | 10-OCT-05:01 | 12.20 | 11.22 | 0.485166E+10 | 6734.72 | 12-OCT-09:50 | 10.32 | 8.21 |
November | 0.225663E+11 | 28436.12 | 02-NOV-16:00 | 13.30 | 10.88 | 0.457357E+10 | 6734.56 | 06-NOV-14:09 | 11.60 | 10.16 |
December | 0.203390E+11 | 20036.94 | 06-DEC-16:50 | 1.47 | 1.30 | 0.425766E+10 | 6711.78 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.381436E+12 | 0.575796E+11 | ||||||||
Minimum of Months | 0.200471E+11 | 20036.94 | 1.47 | 1.30 | 0.409562E+10 | 6658.57 | 5.00 | 3.45 | ||
Maximum of Months | 0.480163E+11 | 69008.99 | 17.90 | 14.45 | 0.545354E+10 | 6735.01 | 26.20 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.297802E+10 | 3008.86 | 11-JAN-14:10 | 14.40 | 10.48 | 0.593387E+09 | 845.62 | 27-JAN-14:09 | 9.72 | 8.08 |
February | 0.317387E+10 | 5185.54 | 27-FEB-15:30 | 19.70 | 12.29 | 0.554390E+09 | 845.62 | 22-FEB-14:09 | 10.00 | 9.05 |
March | 0.475927E+10 | 5433.50 | 20-MAR-13:50 | 12.12 | 7.80 | 0.679433E+09 | 845.63 | 31-MAR-13:09 | 8.98 | 7.52 |
April | 0.582524E+10 | 7344.20 | 27-APR-15:20 | 27.20 | 17.14 | 0.608341E+09 | 845.62 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.626919E+10 | 7846.25 | 30-MAY-05:01 | 10.60 | 9.95 | 0.659652E+09 | 845.63 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.728579E+10 | 8389.39 | 12-JUN-05:03 | 14.40 | 13.42 | 0.660484E+09 | 845.64 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.840399E+10 | 8697.92 | 24-JUL-15:00 | 30.60 | 18.76 | 0.614213E+09 | 845.63 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.935038E+10 | 9021.28 | 10-AUG-05:03 | 17.33 | 14.37 | 0.689306E+09 | 845.70 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.579353E+10 | 8111.21 | 05-SEP-05:01 | 10.68 | 9.19 | 0.608853E+09 | 845.62 | 22-SEP-09:09 | 14.37 | 14.11 |
October | 0.474605E+10 | 8372.36 | 10-OCT-05:01 | 12.20 | 11.22 | 0.629035E+09 | 845.62 | 12-OCT-09:20 | 9.47 | 7.95 |
November | 0.388646E+10 | 5683.80 | 06-NOV-06:01 | 11.28 | 8.35 | 0.618630E+09 | 845.62 | 10-NOV-10:30 | 7.25 | 5.93 |
December | 0.344745E+10 | 3817.53 | 04-DEC-14:10 | 8.90 | 5.69 | 0.595977E+09 | 845.63 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.659192E+11 | 0.751170E+10 | ||||||||
Minimum of Months | 0.297802E+10 | 3008.86 | 8.90 | 5.69 | 0.554390E+09 | 845.62 | 7.10 | 5.11 | ||
Maximum of Months | 0.935038E+10 | 9021.28 | 30.60 | 18.76 | 0.689306E+09 | 845.70 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334931E+10 | 3243.00 | 11-JAN-14:20 | 14.40 | 10.48 | 0.338925E+09 | 506.97 | 05-JAN-10:09 | 2.70 | 2.49 |
February | 0.350078E+10 | 4122.36 | 27-FEB-15:00 | 20.00 | 12.15 | 0.321685E+09 | 544.95 | 08-FEB-10:09 | 2.48 | 1.47 |
March | 0.486276E+10 | 7960.65 | 14-MAR-09:00 | 7.80 | 5.89 | 0.406142E+09 | 544.96 | 02-MAR-10:09 | 7.07 | 5.03 |
April | 0.588666E+10 | 10358.37 | 26-APR-08:20 | 12.03 | 8.46 | 0.377840E+09 | 544.96 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.632548E+10 | 17520.29 | 14-MAY-08:52 | 16.70 | 11.52 | 0.411602E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.732345E+10 | 10896.61 | 25-JUN-08:43 | 16.52 | 11.94 | 0.416449E+09 | 544.96 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.814149E+10 | 19351.38 | 30-JUL-09:32 | 21.67 | 16.14 | 0.386418E+09 | 544.96 | 18-JUL-09:09 | 17.07 | 11.94 |
August | 0.906258E+10 | 17860.16 | 06-AUG-09:12 | 15.90 | 13.09 | 0.432117E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.620140E+10 | 17083.72 | 10-SEP-09:23 | 16.65 | 13.50 | 0.375704E+09 | 544.96 | 15-SEP-09:30 | 17.25 | 14.68 |
October | 0.495871E+10 | 8559.66 | 04-OCT-08:50 | 15.32 | 10.36 | 0.377373E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.398434E+10 | 4218.33 | 05-NOV-12:32 | 15.53 | 13.57 | 0.353138E+09 | 533.67 | 15-NOV-10:09 | 7.30 | 5.71 |
December | 0.366271E+10 | 3326.67 | 03-DEC-11:12 | 10.97 | 5.47 | 0.332255E+09 | 532.00 | 04-DEC-10:09 | 8.30 | 4.43 |
Annual Sum or Average | 0.672597E+11 | 0.452965E+10 | ||||||||
Minimum of Months | 0.334931E+10 | 3243.00 | 7.80 | 5.47 | 0.321685E+09 | 506.97 | 2.48 | 1.47 | ||
Maximum of Months | 0.906258E+10 | 19351.38 | 21.67 | 16.14 | 0.432117E+09 | 545.03 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.482912E+10 | 14435.93 | 20-JAN-13:20 | 6.70 | 4.71 | 0.550251E+09 | 846.01 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.588799E+10 | 18882.20 | 12-FEB-13:43 | 6.60 | 1.26 | 0.525605E+09 | 868.18 | 08-FEB-14:09 | 6.88 | 3.84 |
March | 0.828392E+10 | 16433.81 | 14-MAR-13:40 | 15.20 | 10.16 | 0.652063E+09 | 888.99 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.885874E+10 | 16004.14 | 27-APR-12:50 | 25.92 | 16.12 | 0.592973E+09 | 845.65 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.839968E+10 | 13616.61 | 07-MAY-11:11 | 19.40 | 15.54 | 0.643664E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.897381E+10 | 10140.93 | 11-JUN-12:48 | 21.70 | 15.33 | 0.648685E+09 | 845.66 | 28-JUN-13:50 | 24.90 | 15.64 |
July | 0.108388E+11 | 21046.48 | 30-JUL-13:12 | 26.30 | 17.71 | 0.605458E+09 | 845.66 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.130509E+11 | 18067.23 | 29-AUG-12:30 | 28.65 | 19.73 | 0.680531E+09 | 845.73 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.100513E+11 | 20381.51 | 10-SEP-12:43 | 20.40 | 13.97 | 0.595448E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.871038E+10 | 21081.96 | 08-OCT-12:02 | 17.80 | 13.27 | 0.607132E+09 | 876.81 | 03-OCT-13:09 | 18.30 | 10.43 |
November | 0.610796E+10 | 19503.21 | 11-NOV-12:32 | 6.13 | 4.87 | 0.579372E+09 | 846.43 | 15-NOV-14:09 | 9.82 | 6.79 |
December | 0.595133E+10 | 15071.85 | 05-DEC-12:10 | 10.10 | 6.08 | 0.550886E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.999439E+11 | 0.723207E+10 | ||||||||
Minimum of Months | 0.482912E+10 | 10140.93 | 6.13 | 1.26 | 0.525605E+09 | 845.65 | 6.78 | 3.84 | ||
Maximum of Months | 0.130509E+11 | 21081.96 | 28.65 | 19.73 | 0.680531E+09 | 888.99 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.450616E+10 | 4797.08 | 05-JAN-15:40 | 6.30 | 4.80 | 0.354948E+09 | 536.08 | 05-JAN-14:00 | 6.70 | 5.17 |
February | 0.499961E+10 | 9771.71 | 27-FEB-15:30 | 19.70 | 12.29 | 0.347525E+09 | 544.93 | 03-FEB-14:00 | 10.00 | 7.00 |
March | 0.735617E+10 | 12486.59 | 09-MAR-06:02 | 10.68 | 9.14 | 0.438169E+09 | 544.96 | 31-MAR-13:09 | 8.98 | 7.52 |
April | 0.939600E+10 | 20173.57 | 23-APR-16:12 | 18.13 | 9.96 | 0.394658E+09 | 544.96 | 27-APR-13:20 | 26.10 | 16.44 |
May | 0.820595E+10 | 25095.83 | 07-MAY-16:41 | 21.78 | 16.18 | 0.417642E+09 | 544.96 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.956033E+10 | 21172.86 | 18-JUN-16:42 | 17.38 | 12.19 | 0.424149E+09 | 544.97 | 28-JUN-13:50 | 24.90 | 15.64 |
July | 0.124525E+11 | 24556.83 | 30-JUL-17:11 | 26.70 | 17.78 | 0.396560E+09 | 544.96 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.140106E+11 | 24347.20 | 06-AUG-16:41 | 23.47 | 15.17 | 0.445328E+09 | 545.03 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.795659E+10 | 19466.86 | 10-SEP-16:42 | 22.20 | 14.21 | 0.382076E+09 | 544.94 | 06-SEP-13:00 | 15.00 | 11.80 |
October | 0.677401E+10 | 15075.81 | 10-OCT-03:01 | 12.20 | 10.91 | 0.398802E+09 | 544.96 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.590387E+10 | 15421.30 | 06-NOV-04:01 | 10.10 | 7.78 | 0.396625E+09 | 544.95 | 03-NOV-13:00 | 13.30 | 12.64 |
December | 0.596934E+10 | 13907.20 | 11-DEC-04:01 | 2.88 | 2.18 | 0.388917E+09 | 544.97 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.970912E+11 | 0.478540E+10 | ||||||||
Minimum of Months | 0.450616E+10 | 4797.08 | 2.88 | 2.18 | 0.347525E+09 | 536.08 | 6.70 | 5.11 | ||
Maximum of Months | 0.140106E+11 | 25095.83 | 26.70 | 17.78 | 0.445328E+09 | 545.03 | 26.10 | 16.44 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.143881E+10 | 2335.22 | 11-JAN-16:00 | 14.40 | 10.48 | 0.494880E+09 | 751.78 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.187683E+10 | 2912.11 | 27-FEB-15:00 | 20.00 | 12.15 | 0.472513E+09 | 843.11 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.287686E+10 | 3111.56 | 10-MAR-14:40 | 16.30 | 11.67 | 0.612306E+09 | 845.58 | 10-MAR-14:20 | 16.50 | 11.84 |
April | 0.331706E+10 | 5928.84 | 27-APR-15:50 | 27.20 | 16.95 | 0.573003E+09 | 845.62 | 27-APR-13:39 | 26.10 | 16.63 |
May | 0.462957E+10 | 6191.04 | 05-MAY-13:30 | 23.85 | 16.50 | 0.644216E+09 | 845.63 | 05-MAY-09:09 | 15.97 | 13.48 |
June | 0.527758E+10 | 6728.74 | 21-JUN-15:40 | 24.80 | 15.83 | 0.651845E+09 | 845.64 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.579189E+10 | 7311.88 | 24-JUL-15:00 | 30.60 | 18.76 | 0.608170E+09 | 845.62 | 28-JUL-13:00 | 20.00 | 15.25 |
August | 0.623150E+10 | 7713.74 | 10-AUG-05:03 | 17.33 | 14.37 | 0.682179E+09 | 845.67 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.438739E+10 | 5724.93 | 14-SEP-15:50 | 24.32 | 17.01 | 0.594884E+09 | 845.62 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.308906E+10 | 4001.23 | 04-OCT-15:30 | 21.40 | 11.43 | 0.582156E+09 | 845.60 | 02-OCT-13:09 | 16.20 | 11.49 |
November | 0.229629E+10 | 2563.33 | 04-NOV-14:00 | 21.10 | 15.93 | 0.531640E+09 | 812.25 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.169972E+10 | 2107.73 | 14-DEC-12:00 | 13.30 | 8.42 | 0.488134E+09 | 744.31 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.429126E+11 | 0.693593E+10 | ||||||||
Minimum of Months | 0.143881E+10 | 2107.73 | 13.30 | 8.42 | 0.472513E+09 | 744.31 | 10.60 | 8.76 | ||
Maximum of Months | 0.623150E+10 | 7713.74 | 30.60 | 18.76 | 0.682179E+09 | 845.67 | 26.10 | 16.63 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126202E+10 | 2826.15 | 11-JAN-14:00 | 14.40 | 10.48 | 0.222140E+09 | 419.51 | 05-JAN-09:50 | 2.23 | 2.02 |
February | 0.198328E+10 | 3704.27 | 27-FEB-15:30 | 19.70 | 12.29 | 0.210029E+09 | 481.32 | 08-FEB-09:00 | 2.20 | 1.26 |
March | 0.354868E+10 | 6002.93 | 14-MAR-09:00 | 7.80 | 5.89 | 0.268526E+09 | 521.21 | 14-MAR-10:20 | 10.57 | 8.08 |
April | 0.448398E+10 | 10087.18 | 27-APR-09:00 | 17.80 | 12.19 | 0.260460E+09 | 521.22 | 27-APR-12:20 | 25.37 | 15.71 |
May | 0.560047E+10 | 10306.18 | 15-MAY-08:40 | 16.47 | 11.41 | 0.286154E+09 | 521.23 | 15-MAY-10:09 | 19.18 | 13.23 |
June | 0.652685E+10 | 10906.98 | 25-JUN-08:43 | 16.52 | 11.94 | 0.295638E+09 | 521.21 | 09-JUN-12:30 | 21.15 | 12.82 |
July | 0.686639E+10 | 20056.54 | 30-JUL-09:42 | 21.93 | 16.22 | 0.277113E+09 | 521.22 | 06-JUL-10:00 | 18.30 | 13.78 |
August | 0.752919E+10 | 19957.86 | 13-AUG-09:52 | 22.70 | 16.56 | 0.309573E+09 | 521.30 | 09-AUG-10:09 | 23.92 | 15.99 |
September | 0.552159E+10 | 9629.84 | 13-SEP-09:00 | 18.30 | 15.24 | 0.262515E+09 | 521.21 | 11-SEP-10:09 | 19.08 | 14.36 |
October | 0.379444E+10 | 7426.18 | 04-OCT-09:00 | 15.60 | 10.48 | 0.253155E+09 | 521.22 | 05-OCT-10:09 | 14.08 | 9.35 |
November | 0.232355E+10 | 3334.46 | 04-NOV-13:00 | 20.60 | 16.04 | 0.228506E+09 | 467.37 | 15-NOV-09:30 | 6.95 | 5.42 |
December | 0.156117E+10 | 2669.22 | 05-DEC-09:45 | 6.42 | 4.92 | 0.216612E+09 | 434.05 | 05-DEC-09:00 | 6.70 | 5.09 |
Annual Sum or Average | 0.510016E+11 | 0.309042E+10 | ||||||||
Minimum of Months | 0.126202E+10 | 2669.22 | 6.42 | 4.92 | 0.210029E+09 | 419.51 | 2.20 | 1.26 | ||
Maximum of Months | 0.752919E+10 | 20056.54 | 22.70 | 16.56 | 0.309573E+09 | 521.30 | 25.37 | 15.99 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.315806E+10 | 14401.70 | 20-JAN-13:20 | 6.70 | 4.71 | 0.510963E+09 | 845.90 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.465906E+10 | 16459.69 | 27-FEB-13:50 | 18.22 | 11.38 | 0.494479E+09 | 890.45 | 08-FEB-14:09 | 6.88 | 3.84 |
March | 0.683179E+10 | 16773.66 | 14-MAR-14:00 | 15.60 | 10.49 | 0.615891E+09 | 907.62 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.672212E+10 | 16077.23 | 27-APR-13:10 | 26.10 | 16.35 | 0.565362E+09 | 845.65 | 27-APR-13:30 | 26.10 | 16.53 |
May | 0.735918E+10 | 11276.99 | 15-MAY-13:00 | 22.80 | 13.79 | 0.621690E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.753137E+10 | 9233.91 | 21-JUN-13:30 | 22.50 | 15.03 | 0.626861E+09 | 845.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.856229E+10 | 18069.12 | 30-JUL-13:12 | 26.30 | 17.71 | 0.589521E+09 | 845.65 | 28-JUL-13:50 | 20.55 | 15.37 |
August | 0.102731E+11 | 18220.69 | 29-AUG-12:30 | 28.65 | 19.73 | 0.664802E+09 | 845.71 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.943846E+10 | 24002.97 | 10-SEP-13:42 | 21.93 | 14.54 | 0.580224E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.758245E+10 | 23887.03 | 08-OCT-13:12 | 18.53 | 13.80 | 0.581539E+09 | 899.24 | 03-OCT-13:20 | 18.30 | 10.43 |
November | 0.446350E+10 | 14507.89 | 15-NOV-13:20 | 9.60 | 6.61 | 0.533122E+09 | 846.39 | 15-NOV-14:09 | 9.82 | 6.79 |
December | 0.380477E+10 | 14409.73 | 05-DEC-12:40 | 10.40 | 6.14 | 0.506398E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.803862E+11 | 0.689085E+10 | ||||||||
Minimum of Months | 0.315806E+10 | 9233.91 | 6.70 | 4.71 | 0.494479E+09 | 845.65 | 6.78 | 3.84 | ||
Maximum of Months | 0.102731E+11 | 24002.97 | 28.65 | 19.73 | 0.664802E+09 | 907.62 | 26.10 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171997E+10 | 3085.89 | 05-JAN-15:50 | 6.20 | 4.70 | 0.306134E+09 | 467.86 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.241493E+10 | 5882.82 | 27-FEB-15:40 | 19.60 | 12.33 | 0.290349E+09 | 526.65 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.393421E+10 | 8513.09 | 14-MAR-16:00 | 17.20 | 10.93 | 0.365181E+09 | 544.88 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.471952E+10 | 11920.04 | 26-APR-16:00 | 24.40 | 14.46 | 0.344462E+09 | 544.02 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.615055E+10 | 22104.69 | 07-MAY-16:41 | 21.78 | 16.18 | 0.385857E+09 | 544.93 | 22-MAY-13:50 | 16.10 | 10.48 |
June | 0.662236E+10 | 20020.01 | 25-JUN-16:42 | 21.70 | 13.37 | 0.391586E+09 | 544.90 | 21-JUN-13:00 | 23.30 | 15.01 |
July | 0.790357E+10 | 21255.44 | 30-JUL-17:51 | 26.70 | 17.66 | 0.373188E+09 | 544.93 | 20-JUL-13:00 | 26.70 | 16.71 |
August | 0.809406E+10 | 20518.04 | 06-AUG-17:32 | 23.67 | 15.19 | 0.415230E+09 | 544.93 | 09-AUG-13:20 | 27.77 | 17.71 |
September | 0.598511E+10 | 13836.69 | 04-SEP-16:16 | 17.60 | 13.40 | 0.353543E+09 | 541.53 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.413575E+10 | 9710.54 | 04-OCT-16:00 | 21.10 | 11.38 | 0.342819E+09 | 524.45 | 02-OCT-13:00 | 16.70 | 11.41 |
November | 0.277173E+10 | 4358.49 | 04-NOV-15:40 | 20.37 | 15.92 | 0.316038E+09 | 511.79 | 10-NOV-14:00 | 10.00 | 6.83 |
December | 0.211475E+10 | 3300.14 | 05-DEC-15:40 | 7.40 | 5.39 | 0.300300E+09 | 491.26 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.565665E+11 | 0.418469E+10 | ||||||||
Minimum of Months | 0.171997E+10 | 3085.89 | 6.20 | 4.70 | 0.290349E+09 | 467.86 | 6.10 | 4.61 | ||
Maximum of Months | 0.809406E+10 | 22104.69 | 26.70 | 17.66 | 0.415230E+09 | 544.93 | 27.77 | 17.71 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.737412E+09 | 2174.71 | 11-JAN-16:00 | 14.40 | 10.48 | 0.471208E+09 | 700.25 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.113877E+10 | 2774.97 | 27-FEB-15:50 | 19.50 | 12.37 | 0.443321E+09 | 810.59 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.226841E+10 | 2796.00 | 10-MAR-14:40 | 16.30 | 11.67 | 0.566937E+09 | 837.84 | 10-MAR-14:00 | 16.10 | 11.49 |
April | 0.290689E+10 | 6681.12 | 27-APR-15:30 | 27.20 | 17.08 | 0.544536E+09 | 845.62 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.435026E+10 | 6759.11 | 31-MAY-15:00 | 22.20 | 15.71 | 0.626048E+09 | 845.62 | 26-MAY-13:09 | 12.48 | 11.47 |
June | 0.521022E+10 | 7543.19 | 21-JUN-15:40 | 24.80 | 15.83 | 0.642893E+09 | 845.64 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.589615E+10 | 8542.34 | 24-JUL-15:00 | 30.60 | 18.76 | 0.603278E+09 | 845.63 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.625179E+10 | 8183.98 | 09-AUG-15:30 | 28.70 | 18.81 | 0.675205E+09 | 845.67 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.405509E+10 | 6257.52 | 14-SEP-15:50 | 24.32 | 17.01 | 0.575284E+09 | 845.61 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.248316E+10 | 3895.49 | 04-OCT-15:30 | 21.40 | 11.43 | 0.540722E+09 | 845.59 | 05-OCT-13:00 | 16.10 | 10.64 |
November | 0.143129E+10 | 2446.16 | 04-NOV-14:40 | 21.10 | 15.93 | 0.488747E+09 | 775.08 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.772988E+09 | 1880.03 | 29-DEC-16:00 | 10.60 | 8.76 | 0.455550E+09 | 694.85 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.375024E+11 | 0.663373E+10 | ||||||||
Minimum of Months | 0.737412E+09 | 1880.03 | 10.60 | 8.76 | 0.443321E+09 | 694.85 | 10.60 | 8.76 | ||
Maximum of Months | 0.625179E+10 | 8542.34 | 30.60 | 18.81 | 0.675205E+09 | 845.67 | 26.20 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662110E+09 | 2643.60 | 11-JAN-16:00 | 14.40 | 10.48 | 0.299769E+09 | 403.77 | 05-JAN-10:09 | 2.70 | 2.49 |
February | 0.128106E+10 | 3530.23 | 27-FEB-15:00 | 20.00 | 12.15 | 0.278097E+09 | 455.59 | 03-FEB-10:30 | 9.15 | 6.87 |
March | 0.278352E+10 | 4520.44 | 14-MAR-09:35 | 9.27 | 7.13 | 0.354260E+09 | 544.95 | 14-MAR-09:00 | 10.00 | 7.75 |
April | 0.398486E+10 | 9688.63 | 27-APR-09:10 | 17.98 | 12.32 | 0.349835E+09 | 544.96 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.524223E+10 | 12804.85 | 14-MAY-08:52 | 16.70 | 11.52 | 0.388160E+09 | 544.97 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.637955E+10 | 17461.41 | 25-JUN-09:12 | 17.07 | 12.33 | 0.404089E+09 | 544.97 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.683599E+10 | 14349.48 | 30-JUL-09:13 | 21.13 | 15.96 | 0.378702E+09 | 544.97 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.748737E+10 | 17422.56 | 06-AUG-09:02 | 15.60 | 12.96 | 0.422429E+09 | 545.04 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.509063E+10 | 11968.67 | 10-SEP-09:32 | 16.83 | 13.51 | 0.353815E+09 | 544.95 | 15-SEP-09:30 | 17.25 | 14.68 |
October | 0.302212E+10 | 6318.39 | 04-OCT-09:10 | 15.87 | 10.56 | 0.334305E+09 | 544.95 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.141498E+10 | 3148.04 | 04-NOV-16:03 | 19.82 | 15.68 | 0.301800E+09 | 451.67 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.737541E+09 | 2297.93 | 05-DEC-14:00 | 10.60 | 6.37 | 0.289746E+09 | 410.08 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.449220E+11 | 0.415501E+10 | ||||||||
Minimum of Months | 0.662110E+09 | 2297.93 | 9.27 | 6.37 | 0.278097E+09 | 403.77 | 2.70 | 2.49 | ||
Maximum of Months | 0.748737E+10 | 17461.41 | 21.13 | 15.96 | 0.422429E+09 | 545.04 | 26.20 | 16.64 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.203429E+10 | 13030.30 | 20-JAN-13:20 | 6.70 | 4.71 | 0.487928E+09 | 845.63 | 20-JAN-14:20 | 6.87 | 4.79 |
February | 0.340710E+10 | 14896.59 | 27-FEB-14:20 | 18.87 | 11.66 | 0.472349E+09 | 845.63 | 07-FEB-14:09 | 7.88 | 4.77 |
March | 0.562516E+10 | 16776.51 | 14-MAR-13:30 | 15.00 | 9.99 | 0.586455E+09 | 868.02 | 01-MAR-14:09 | 11.97 | 6.48 |
April | 0.608134E+10 | 16684.61 | 27-APR-13:10 | 26.10 | 16.35 | 0.543467E+09 | 845.67 | 27-APR-13:09 | 26.10 | 16.35 |
May | 0.708959E+10 | 11995.03 | 15-MAY-13:10 | 22.88 | 13.74 | 0.601196E+09 | 845.66 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.759450E+10 | 9960.35 | 21-JUN-13:30 | 22.50 | 15.03 | 0.611864E+09 | 845.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.876899E+10 | 14720.93 | 31-JUL-13:10 | 27.38 | 18.34 | 0.579610E+09 | 845.67 | 20-JUL-13:09 | 26.20 | 16.64 |
August | 0.104464E+11 | 18655.79 | 29-AUG-12:30 | 28.65 | 19.73 | 0.651332E+09 | 845.65 | 22-AUG-13:00 | 26.20 | 16.72 |
September | 0.901740E+10 | 25232.54 | 10-SEP-13:42 | 21.93 | 14.54 | 0.560650E+09 | 845.66 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.645586E+10 | 23691.11 | 08-OCT-13:12 | 18.53 | 13.80 | 0.553021E+09 | 868.29 | 03-OCT-13:20 | 18.30 | 10.43 |
November | 0.308367E+10 | 13499.48 | 04-NOV-13:30 | 20.85 | 15.99 | 0.500261E+09 | 845.64 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.242337E+10 | 12267.60 | 05-DEC-12:30 | 10.30 | 6.12 | 0.481465E+09 | 845.65 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.720277E+11 | 0.662960E+10 | ||||||||
Minimum of Months | 0.203429E+10 | 9960.35 | 6.70 | 4.71 | 0.472349E+09 | 845.63 | 6.87 | 4.77 | ||
Maximum of Months | 0.104464E+11 | 25232.54 | 28.65 | 19.73 | 0.651332E+09 | 868.29 | 26.20 | 16.72 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.998500E+09 | 3102.19 | 05-JAN-15:50 | 6.20 | 4.70 | 0.301599E+09 | 453.46 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.167597E+10 | 5225.92 | 27-FEB-15:40 | 19.60 | 12.33 | 0.282547E+09 | 521.19 | 27-FEB-16:10 | 19.32 | 12.37 |
March | 0.323176E+10 | 8401.39 | 14-MAR-16:00 | 17.20 | 10.93 | 0.349223E+09 | 536.11 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.435082E+10 | 12270.99 | 26-APR-16:00 | 24.40 | 14.46 | 0.330862E+09 | 544.34 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.597539E+10 | 23075.63 | 14-MAY-17:11 | 22.60 | 11.81 | 0.373767E+09 | 544.88 | 15-MAY-13:00 | 23.30 | 13.48 |
June | 0.664982E+10 | 21031.30 | 25-JUN-16:42 | 21.70 | 13.37 | 0.383020E+09 | 544.91 | 21-JUN-13:00 | 23.30 | 15.01 |
July | 0.803310E+10 | 22079.91 | 23-JUL-17:02 | 26.60 | 15.62 | 0.367072E+09 | 544.94 | 20-JUL-13:39 | 26.50 | 16.68 |
August | 0.822109E+10 | 21537.77 | 06-AUG-17:32 | 23.67 | 15.19 | 0.406268E+09 | 544.93 | 09-AUG-13:09 | 27.58 | 17.58 |
September | 0.576229E+10 | 13213.60 | 04-SEP-16:20 | 17.60 | 13.40 | 0.340850E+09 | 540.65 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.347502E+10 | 9671.60 | 04-OCT-16:00 | 21.10 | 11.38 | 0.326263E+09 | 521.19 | 03-OCT-15:00 | 18.30 | 10.42 |
November | 0.185855E+10 | 4464.09 | 04-NOV-15:40 | 20.37 | 15.92 | 0.304256E+09 | 488.21 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.117116E+10 | 3227.07 | 05-DEC-15:40 | 7.40 | 5.39 | 0.293088E+09 | 466.15 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.514035E+11 | 0.405881E+10 | ||||||||
Minimum of Months | 0.998500E+09 | 3102.19 | 6.20 | 4.70 | 0.282547E+09 | 453.46 | 6.10 | 4.61 | ||
Maximum of Months | 0.822109E+10 | 23075.63 | 26.60 | 15.92 | 0.406268E+09 | 544.94 | 27.58 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.293884E+10 | 5124.22 | 02-JAN-06:06 | 6.10 | 5.29 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.322528E+10 | 5939.33 | 28-FEB-06:02 | 10.60 | 9.73 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.500432E+10 | 6207.61 | 20-MAR-05:15 | 5.97 | 4.26 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.566425E+10 | 7148.15 | 17-APR-05:05 | 6.10 | 5.25 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.571638E+10 | 7532.73 | 30-MAY-05:13 | 10.60 | 9.91 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.652563E+10 | 7694.58 | 05-JUN-05:13 | 10.77 | 9.45 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.727931E+10 | 8026.98 | 05-JUL-05:13 | 11.87 | 8.61 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.805449E+10 | 7562.90 | 28-AUG-05:13 | 14.87 | 13.94 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.601411E+10 | 9187.76 | 05-SEP-05:05 | 10.68 | 9.19 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.522889E+10 | 9306.60 | 10-OCT-05:05 | 12.20 | 11.22 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.436748E+10 | 7750.49 | 06-NOV-06:05 | 11.28 | 8.35 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.391156E+10 | 5732.02 | 04-DEC-06:15 | 3.13 | 1.79 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.639305E+11 | 0.00 | ||||||||
Minimum of Months | 0.293884E+10 | 5124.22 | 3.13 | 1.79 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.805449E+10 | 9306.60 | 14.87 | 13.94 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.853953E+09 | 4415.16 | 14-JAN-05:01 | 2.20 | 1.44 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.132303E+10 | 4257.36 | 17-FEB-06:03 | 1.10 | -0.1 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.246611E+10 | 4217.10 | 02-MAR-06:10 | 0.60 | -0.2 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.291175E+10 | 4715.97 | 28-APR-05:10 | 11.10 | 9.92 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.394098E+10 | 5293.55 | 01-MAY-05:10 | 12.20 | 10.39 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.452927E+10 | 5200.62 | 23-JUN-05:10 | 13.80 | 11.91 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.502426E+10 | 5848.04 | 10-JUL-05:13 | 13.13 | 11.61 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.558412E+10 | 6101.19 | 10-AUG-05:13 | 17.27 | 14.45 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.452851E+10 | 6112.05 | 14-SEP-05:13 | 12.43 | 12.07 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.312947E+10 | 4796.59 | 11-OCT-05:08 | 8.22 | 6.31 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.192616E+10 | 3754.44 | 18-NOV-17:17 | 11.70 | 9.41 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.134287E+10 | 3876.75 | 16-DEC-17:15 | 7.20 | 6.48 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.375605E+11 | 0.00 | ||||||||
Minimum of Months | 0.853953E+09 | 3754.44 | 0.60 | -0.2 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.558412E+10 | 6112.05 | 17.27 | 14.45 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11746748.24 | 809.10 | 11-JAN-17:30 | 12.50 | 9.43 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.314621E+09 | 3588.48 | 27-FEB-14:40 | 19.43 | 11.91 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.147498E+10 | 6211.12 | 14-MAR-14:00 | 15.60 | 10.49 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.343308E+10 | 12996.31 | 27-APR-14:30 | 26.65 | 17.04 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.568748E+10 | 13275.60 | 15-MAY-14:40 | 23.30 | 12.89 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.700948E+10 | 13717.70 | 28-JUN-14:50 | 25.92 | 15.54 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.858542E+10 | 14621.24 | 24-JUL-14:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.842842E+10 | 15451.55 | 10-AUG-14:40 | 29.93 | 18.97 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.482824E+10 | 11803.66 | 14-SEP-14:30 | 23.90 | 17.02 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.172132E+10 | 8024.59 | 04-OCT-14:30 | 21.40 | 11.43 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.277210E+09 | 4665.21 | 04-NOV-13:50 | 21.02 | 15.95 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 9453225.41 | 632.54 | 30-DEC-12:30 | 8.60 | 7.46 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.417814E+11 | 0.00 | ||||||||
Minimum of Months | 9453225.41 | 632.54 | 8.60 | 7.46 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.858542E+10 | 15451.55 | 29.93 | 18.97 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311657E+10 | 1812.59 | 05-JAN-16:10 | 5.73 | 4.38 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.782349E+10 | 3906.51 | 07-FEB-16:50 | 7.30 | 3.82 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.141522E+11 | 5980.10 | 14-MAR-17:10 | 16.52 | 10.82 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.187880E+11 | 8008.81 | 25-APR-18:00 | 14.40 | 8.92 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.419270E+10 | 2506.01 | 29-MAY-18:23 | 15.85 | 12.22 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.910995E+10 | 4263.48 | 18-JUN-18:55 | 16.10 | 12.56 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.145964E+11 | 6618.89 | 30-JUL-18:27 | 25.55 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.195488E+11 | 8043.70 | 06-AUG-19:20 | 21.07 | 14.57 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.409588E+10 | 2363.35 | 10-SEP-17:25 | 21.40 | 13.99 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.912266E+10 | 4241.40 | 03-OCT-16:50 | 17.38 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.136220E+11 | 5794.63 | 12-NOV-15:55 | 5.00 | 4.01 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.190515E+11 | 7624.98 | 05-DEC-15:50 | 6.75 | 4.97 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.137220E+12 | 0.00 | ||||||||
Minimum of Months | 0.311657E+10 | 1812.59 | 5.00 | 3.82 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.195488E+11 | 8043.70 | 25.55 | 17.12 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106206E+10 | 1409.11 | 05-JAN-16:20 | 5.37 | 4.14 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.591849E+10 | 3556.52 | 08-FEB-16:50 | 6.78 | 3.35 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.121949E+11 | 5579.09 | 14-MAR-17:10 | 16.52 | 10.82 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.170498E+11 | 7566.54 | 25-APR-18:00 | 14.40 | 8.92 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.328010E+10 | 2243.53 | 29-MAY-18:30 | 15.85 | 12.22 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.809768E+10 | 3949.10 | 22-JUN-18:50 | 23.40 | 15.89 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.135300E+11 | 6112.80 | 30-JUL-18:40 | 25.17 | 16.93 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.183215E+11 | 7631.25 | 06-AUG-19:12 | 21.07 | 14.57 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.326166E+10 | 2142.50 | 08-SEP-17:30 | 21.65 | 14.35 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.755074E+10 | 3960.90 | 03-OCT-16:50 | 17.38 | 10.07 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.114144E+11 | 5179.94 | 10-NOV-16:10 | 8.53 | 6.27 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.162301E+11 | 6987.04 | 05-DEC-16:00 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.117911E+12 | 0.00 | ||||||||
Minimum of Months | 0.106206E+10 | 1409.11 | 5.37 | 3.35 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.183215E+11 | 7631.25 | 25.17 | 16.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.349377E+09 | 1281.64 | 05-JAN-16:20 | 5.37 | 4.14 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.441106E+10 | 3448.71 | 08-FEB-17:00 | 6.70 | 3.25 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.110205E+11 | 5584.82 | 14-MAR-17:10 | 16.52 | 10.82 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.163235E+11 | 7656.40 | 26-APR-18:10 | 22.05 | 13.16 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.281094E+10 | 2309.81 | 07-MAY-18:30 | 20.00 | 15.11 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.789036E+10 | 4080.03 | 18-JUN-18:32 | 16.30 | 12.46 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.133971E+11 | 6284.32 | 30-JUL-18:22 | 25.55 | 17.12 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.181281E+11 | 7736.16 | 06-AUG-19:12 | 21.07 | 14.57 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.276358E+10 | 2196.52 | 08-SEP-17:30 | 21.65 | 14.35 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.650283E+10 | 3981.08 | 04-OCT-16:50 | 20.68 | 11.35 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.996782E+10 | 5054.42 | 10-NOV-16:10 | 8.53 | 6.27 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.143941E+11 | 6829.59 | 05-DEC-16:00 | 6.10 | 4.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.107959E+12 | 0.00 | ||||||||
Minimum of Months | 0.349377E+09 | 1281.64 | 5.37 | 3.25 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.181281E+11 | 7736.16 | 25.55 | 17.12 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236780E+12 | 319756.50 | 20-JAN-23:05 | 1.02 | 0.39 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.434899E+12 | 365059.29 | 21-FEB-22:08 | 4.32 | 3.87 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.728031E+12 | 399117.53 | 01-MAR-23:52 | 4.40 | 3.65 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.943131E+12 | 390892.70 | 10-APR-05:04 | 8.80 | 7.54 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.239337E+12 | 317689.45 | 17-MAY-21:50 | 7.12 | 5.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.468559E+12 | 182521.19 | 20-JUN-16:00 | 24.40 | 15.00 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.730439E+12 | 274436.55 | 06-JUL-16:00 | 22.80 | 14.65 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.976666E+12 | 367736.15 | 10-AUG-19:45 | 26.32 | 17.83 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.233168E+12 | 104724.22 | 01-SEP-00:08 | 16.38 | 13.40 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.484565E+12 | 379010.82 | 22-OCT-22:16 | 9.40 | 8.65 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.706274E+12 | 376905.25 | 17-NOV-04:55 | 5.00 | 4.22 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.974699E+12 | 386042.52 | 23-DEC-17:12 | 5.60 | 5.22 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.715655E+13 | 0.00 | ||||||||
Minimum of Months | 0.233168E+12 | 104724.22 | 1.02 | 0.39 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.976666E+12 | 399117.53 | 26.32 | 17.83 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106139E+10 | 127025.81 | 25-JAN-05:46 | 5.60 |
February | 91050707.22 | 123836.61 | 22-FEB-04:53 | 7.80 |
March | 0.387374E+09 | 122268.47 | 18-MAR-03:50 | 4.50 |
April | 0.579331E+09 | 117670.65 | 20-APR-03:50 | 4.32 |
May | 0.423885E+09 | 115952.76 | 16-MAY-03:47 | 11.70 |
June | 0.773706E+09 | 115048.34 | 01-JUN-03:50 | 9.07 |
July | 0.613240E+09 | 117773.66 | 27-JUL-03:45 | 13.30 |
August | 0.513116E+09 | 120480.51 | 31-AUG-03:50 | 15.47 |
September | 0.119867E+10 | 118779.84 | 01-SEP-03:45 | 16.12 |
October | 0.908448E+09 | 115783.52 | 13-OCT-03:47 | 6.20 |
November | 0.116722E+10 | 117440.68 | 22-NOV-04:50 | 3.98 |
December | 0.804235E+09 | 119411.44 | 07-DEC-04:50 | 3.30 |
Annual Sum or Average | 0.852166E+10 | |||
Minimum of Months | 91050707.22 | 115048.34 | 3.30 | |
Maximum of Months | 0.119867E+10 | 127025.81 | 16.12 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 67718702.43 | 28733.42 | 02-JAN-05:01 | 6.10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 67718702.43 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 67718702.43 | 28733.42 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.151805E+10 | 68046.46 | 17-JAN-04:01 | 1.70 |
February | 0.510432E+09 | 63990.73 | 21-FEB-05:11 | 1.70 |
March | 72648086.92 | 58479.99 | 06-MAR-05:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 2539696.70 | 24905.51 | 30-OCT-05:01 | 7.20 |
November | 0.169337E+09 | 59271.63 | 13-NOV-05:01 | 1.20 |
December | 0.609897E+09 | 65983.20 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.288291E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.151805E+10 | 68046.46 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3918166.30 | 6992.78 | 17-JAN-06:01 | 1.20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 97671.87 | 1139.51 | 18-DEC-06:01 | 3.72 |
Annual Sum or Average | 4015838.17 | |||
Minimum of Months | 0.00 | 0.00 | 1.20 | |
Maximum of Months | 3918166.30 | 6992.78 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.473707E+09 | 9513.55 | 02-JAN-04:01 | 6.60 |
February | 0.155296E+09 | 8639.54 | 21-FEB-05:02 | 1.70 |
March | 10493737.88 | 8052.48 | 06-MAR-06:01 | 6.70 |
April | 354734.97 | 5419.64 | 11-APR-05:01 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 708507.76 | 7782.28 | 30-OCT-05:01 | 7.20 |
November | 26685398.78 | 7951.46 | 30-NOV-06:02 | 5.60 |
December | 0.146545E+09 | 8485.70 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.813791E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.473707E+09 | 9513.55 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.364233E+09 | 11757.10 | 02-JAN-04:01 | 6.60 |
February | 0.119448E+09 | 10283.06 | 21-FEB-05:02 | 1.70 |
March | 10822360.04 | 9308.19 | 06-MAR-06:01 | 6.70 |
April | 2454557.29 | 9121.26 | 11-APR-05:01 | 5.60 |
May | 3959.26 | 32.99 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 1438227.13 | 6190.68 | 31-OCT-05:01 | 8.58 |
November | 32066978.32 | 9618.64 | 30-NOV-06:02 | 5.60 |
December | 0.145598E+09 | 10298.13 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.676065E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.364233E+09 | 11757.10 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361534E+09 | 16497.40 | 02-JAN-04:01 | 6.60 |
February | 84827270.51 | 14174.88 | 21-FEB-05:02 | 1.70 |
March | 6049974.23 | 13413.48 | 06-MAR-06:01 | 6.70 |
April | 838901.88 | 7985.15 | 11-APR-05:01 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 451813.92 | 3012.09 | 28-OCT-05:03 | 8.22 |
November | 20390524.35 | 13851.13 | 30-NOV-06:02 | 5.60 |
December | 0.123175E+09 | 14499.93 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.597267E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.361534E+09 | 16497.40 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.187700E+09 | 10329.93 | 02-JAN-04:01 | 6.60 |
February | 50457555.42 | 8870.83 | 21-FEB-05:02 | 1.70 |
March | 2532229.05 | 8088.91 | 06-MAR-06:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 130253.24 | 868.35 | 28-OCT-05:03 | 8.22 |
November | 7481016.64 | 8586.10 | 30-NOV-06:02 | 5.60 |
December | 44835775.72 | 8904.05 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.293137E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.187700E+09 | 10329.93 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.247551E+10 | 11440.09 | 01-JAN-22:01 | 6.10 |
February | 0.141023E+10 | 11344.75 | 13-FEB-04:01 | 0.68 |
March | 0.480046E+09 | 10748.54 | 06-MAR-04:01 | 6.70 |
April | 0.132920E+09 | 9647.16 | 11-APR-04:02 | 5.10 |
May | 7844583.16 | 9021.98 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.157503E+09 | 9901.34 | 30-OCT-04:02 | 7.20 |
November | 0.745915E+09 | 10431.43 | 13-NOV-04:02 | 1.60 |
December | 0.173667E+10 | 11426.96 | 25-DEC-18:11 | 0.77 |
Annual Sum or Average | 0.714664E+10 | |||
Minimum of Months | 0.00 | 0.00 | 0.68 | |
Maximum of Months | 0.247551E+10 | 11440.09 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.165200E+10 | 14657.37 | 17-JAN-04:01 | 1.70 |
February | 0.856723E+09 | 14306.22 | 21-FEB-04:01 | 1.70 |
March | 0.303967E+09 | 13625.32 | 06-MAR-04:01 | 6.70 |
April | 90584251.58 | 11995.71 | 11-APR-04:02 | 5.10 |
May | 9620463.57 | 10548.84 | 18-MAY-05:02 | 5.60 |
June | 457401.91 | 6662.71 | 14-JUN-05:01 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 192238.14 | 891.67 | 27-SEP-05:03 | 7.38 |
October | 0.119113E+09 | 11929.91 | 30-OCT-04:02 | 7.20 |
November | 0.519036E+09 | 13007.49 | 13-NOV-05:01 | 1.20 |
December | 0.117905E+10 | 14427.61 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.473074E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.165200E+10 | 14657.37 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188365E+10 | 20672.15 | 17-JAN-04:01 | 1.70 |
February | 0.892650E+09 | 20216.85 | 21-FEB-04:01 | 1.70 |
March | 0.359116E+09 | 19152.00 | 06-MAR-04:01 | 6.70 |
April | 0.117488E+09 | 16980.33 | 11-APR-04:02 | 5.10 |
May | 12669158.37 | 15860.75 | 18-MAY-05:02 | 5.60 |
June | 190619.02 | 3176.98 | 14-JUN-05:01 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 78244.52 | 328.38 | 27-SEP-05:05 | 7.38 |
October | 0.115189E+09 | 16751.06 | 28-OCT-04:01 | 7.88 |
November | 0.600744E+09 | 18487.55 | 13-NOV-05:01 | 1.20 |
December | 0.139509E+10 | 20422.49 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.537687E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.188365E+10 | 20672.15 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103431E+10 | 14608.70 | 17-JAN-04:01 | 1.70 |
February | 0.473295E+09 | 14226.08 | 21-FEB-04:01 | 1.70 |
March | 0.163658E+09 | 12558.86 | 06-MAR-05:01 | 6.70 |
April | 40484782.25 | 11181.10 | 19-APR-05:01 | 1.78 |
May | 4785272.57 | 10244.67 | 18-MAY-05:02 | 5.60 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 87769.60 | 585.13 | 27-SEP-05:08 | 7.38 |
October | 43607953.80 | 11025.16 | 30-OCT-05:01 | 7.20 |
November | 0.264406E+09 | 12897.70 | 13-NOV-05:01 | 1.20 |
December | 0.612752E+09 | 14428.40 | 26-DEC-04:01 | -1.0 |
Annual Sum or Average | 0.263739E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.103431E+10 | 14608.70 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 40193403.49 | 9907.79 | 30-JAN-05:01 | 6.10 |
February | 57328496.52 | 10867.32 | 21-FEB-04:01 | 1.70 |
March | 75145325.13 | 10790.15 | 06-MAR-04:01 | 6.70 |
April | 0.103150E+09 | 11888.79 | 17-APR-03:01 | 6.10 |
May | 62460763.95 | 10801.84 | 01-MAY-03:02 | 11.78 |
June | 68987337.11 | 10378.45 | 26-JUN-03:01 | 12.80 |
July | 87362783.24 | 11594.14 | 17-JUL-03:02 | 14.90 |
August | 92516999.34 | 10848.08 | 03-AUG-03:01 | 11.78 |
September | 45502235.68 | 9941.42 | 01-SEP-03:01 | 16.18 |
October | 76445635.78 | 10331.35 | 30-OCT-03:01 | 6.78 |
November | 74277383.95 | 11793.67 | 06-NOV-04:01 | 10.10 |
December | 80322720.01 | 12177.59 | 04-DEC-04:01 | 5.73 |
Annual Sum or Average | 0.863693E+09 | |||
Minimum of Months | 40193403.49 | 9907.79 | 1.70 | |
Maximum of Months | 0.103150E+09 | 12177.59 | 16.18 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100836E+10 | 9040.96 | 02-JAN-06:13 | 6.10 |
February | 0.227559E+09 | 6990.98 | 27-FEB-06:01 | 6.28 |
March | 49691624.04 | 7360.56 | 15-MAR-05:01 | 8.03 |
April | 26946928.49 | 7387.36 | 10-APR-05:01 | 8.80 |
May | 43638514.17 | 6817.40 | 01-MAY-04:01 | 12.20 |
June | 40141840.76 | 6986.80 | 12-JUN-03:01 | 15.00 |
July | 40471050.56 | 6943.30 | 17-JUL-04:03 | 14.32 |
August | 32043685.29 | 6792.19 | 28-AUG-03:02 | 16.12 |
September | 32772083.82 | 6453.21 | 05-SEP-03:01 | 11.70 |
October | 28753105.71 | 7034.31 | 26-OCT-05:01 | 12.20 |
November | 58092214.29 | 7467.82 | 21-NOV-06:01 | 11.10 |
December | 0.245994E+09 | 7683.85 | 29-DEC-06:01 | 9.90 |
Annual Sum or Average | 0.183447E+10 | |||
Minimum of Months | 26946928.49 | 6453.21 | 6.10 | |
Maximum of Months | 0.100836E+10 | 9040.96 | 16.12 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.543170E+10 | 18779.28 | 17-JAN-06:13 | 1.30 |
February | 0.321472E+10 | 16890.12 | 21-FEB-05:23 | 1.70 |
March | 0.172869E+10 | 11228.53 | 06-MAR-06:03 | 6.70 |
April | 0.791340E+09 | 14249.43 | 29-APR-05:01 | 8.40 |
May | 0.291726E+09 | 14929.34 | 15-MAY-05:01 | 10.28 |
June | 0.108952E+09 | 15931.44 | 15-JUN-05:01 | 8.98 |
July | 72796077.46 | 14219.53 | 07-JUL-05:01 | 11.47 |
August | 88513103.81 | 13964.43 | 22-AUG-05:01 | 13.02 |
September | 0.214656E+09 | 14781.02 | 20-SEP-05:01 | 9.40 |
October | 0.983305E+09 | 15574.47 | 05-OCT-05:01 | 8.30 |
November | 0.241869E+10 | 10852.82 | 13-NOV-06:03 | 1.70 |
December | 0.440867E+10 | 17587.64 | 26-DEC-05:12 | -0.6 |
Annual Sum or Average | 0.197538E+11 | |||
Minimum of Months | 72796077.46 | 10852.82 | -0.6 | |
Maximum of Months | 0.543170E+10 | 18779.28 | 13.02 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.113771E+09 | 531.51 | 01-JAN-21:25 | 5.85 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.113771E+09 | |||
Minimum of Months | 0.00 | 0.00 | 4.40 | |
Maximum of Months | 0.113771E+09 | 531.51 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.703102E+09 | 584.88 | 08-JAN-17:20 | 2.57 |
February | 7795950.79 | 512.41 | 21-FEB-04:15 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.710898E+09 | |||
Minimum of Months | 0.00 | 0.00 | 1.70 | |
Maximum of Months | 0.703102E+09 | 584.88 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.301003E+09 | 61024.66 | 04-JAN-23:31 | 3.50 |
February | 35449626.77 | 33316.20 | 21-FEB-23:21 | 3.90 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 21912503.66 | 39439.89 | 17-MAY-22:17 | 6.83 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 16.38 |
October | 7465754.44 | 10046.92 | 22-OCT-22:18 | 9.40 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 9.22 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
Annual Sum or Average | 0.365831E+09 | |||
Minimum of Months | 0.00 | 0.00 | 3.50 | |
Maximum of Months | 0.301003E+09 | 61024.66 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.176037E+11 | 18337.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.159674E+11 | 18337.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.189649E+11 | 18337.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.169484E+11 | 18337.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.182843E+11 | 18337.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.181926E+11 | 18337.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.170401E+11 | 18337.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.189649E+11 | 18337.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.169484E+11 | 18337.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.176037E+11 | 18337.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.173949E+11 | 18337.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.170401E+11 | 18337.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.210953E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.159674E+11 | 18337.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.189649E+11 | 18337.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.165538E+10 | 2067.73 | 02-JAN-16:30 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.144517E+10 | 1943.50 | 02-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166628E+10 | 1791.82 | 22-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146639E+10 | 1578.32 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156650E+10 | 1509.46 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.154768E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145386E+10 | 1535.74 | 12-JUL-08:30 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162590E+10 | 1509.46 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148172E+10 | 1799.82 | 25-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.157592E+10 | 2050.57 | 31-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.161948E+10 | 2067.73 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.162503E+10 | 2067.73 | 01-DEC-16:19 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.187293E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.144517E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166628E+10 | 2067.73 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.105900E+10 | 1332.52 | 02-JAN-16:30 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.929574E+09 | 1261.40 | 02-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107341E+10 | 1127.70 | 22-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.945598E+09 | 972.75 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101077E+10 | 972.75 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.998987E+09 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.939108E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104956E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.953857E+09 | 1134.45 | 25-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101286E+10 | 1318.89 | 31-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103970E+10 | 1332.52 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.103768E+10 | 1332.52 | 01-DEC-16:19 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120501E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.929574E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107341E+10 | 1332.52 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.163214E+10 | 2067.77 | 02-JAN-16:30 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.143396E+10 | 1915.40 | 02-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166261E+10 | 1779.68 | 22-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146710E+10 | 1560.95 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156867E+10 | 1509.49 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.155068E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.145825E+10 | 1509.49 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.162862E+10 | 1509.49 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148072E+10 | 1790.63 | 25-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156706E+10 | 2047.46 | 31-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.160440E+10 | 2067.77 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.159662E+10 | 2067.77 | 01-DEC-16:19 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186508E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.143396E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166261E+10 | 2067.77 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.105909E+10 | 1332.52 | 02-JAN-16:30 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.926622E+09 | 1231.67 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107269E+10 | 1167.09 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.945009E+09 | 1061.81 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100992E+10 | 972.75 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.998012E+09 | 972.75 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.938585E+09 | 1084.41 | 12-JUL-07:30 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.104807E+10 | 1084.87 | 28-AUG-07:30 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.954973E+09 | 1171.00 | 25-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101326E+10 | 1321.80 | 31-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.103792E+10 | 1332.52 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.103727E+10 | 1332.52 | 01-DEC-16:19 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120414E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.926622E+09 | 972.75 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107269E+10 | 1332.52 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.165744E+10 | 2067.73 | 02-JAN-16:30 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.144648E+10 | 1947.21 | 02-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166712E+10 | 1800.01 | 22-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146672E+10 | 1592.47 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156676E+10 | 1509.46 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.154790E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145399E+10 | 1548.78 | 12-JUL-08:30 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162592E+10 | 1509.46 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148219E+10 | 1807.70 | 25-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.157716E+10 | 2051.07 | 31-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.162117E+10 | 2067.73 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.162755E+10 | 2067.73 | 01-DEC-16:19 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.187404E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.144648E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166712E+10 | 2067.73 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.105946E+10 | 1332.52 | 02-JAN-16:30 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.929823E+09 | 1261.98 | 02-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107360E+10 | 1130.19 | 22-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.945686E+09 | 972.75 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101086E+10 | 972.75 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.999063E+09 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.939197E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104969E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.953984E+09 | 1136.81 | 25-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101312E+10 | 1319.06 | 31-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.104000E+10 | 1332.52 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.103819E+10 | 1332.52 | 01-DEC-16:19 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120527E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.929823E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107360E+10 | 1332.52 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.163364E+10 | 2067.77 | 02-JAN-16:30 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.143459E+10 | 1920.46 | 02-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166320E+10 | 1788.40 | 22-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146744E+10 | 1575.73 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156901E+10 | 1509.49 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.155098E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.145856E+10 | 1513.49 | 12-JUL-07:30 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.162902E+10 | 1509.49 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148118E+10 | 1798.87 | 25-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156814E+10 | 2048.11 | 31-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.160549E+10 | 2067.77 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.159789E+10 | 2067.77 | 01-DEC-16:19 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186591E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.143459E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166320E+10 | 2067.77 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.105952E+10 | 1332.52 | 02-JAN-16:30 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.926881E+09 | 1232.47 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107288E+10 | 1168.34 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.945120E+09 | 1063.80 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100999E+10 | 972.75 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.998080E+09 | 972.75 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.938663E+09 | 1085.88 | 12-JUL-07:30 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.104818E+10 | 1086.53 | 28-AUG-07:30 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.955112E+09 | 1172.21 | 25-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101355E+10 | 1321.89 | 31-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.103830E+10 | 1332.52 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.103778E+10 | 1332.52 | 01-DEC-16:19 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120441E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.926881E+09 | 972.75 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107288E+10 | 1332.52 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.165741E+10 | 2067.73 | 02-JAN-16:30 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.144647E+10 | 1947.12 | 02-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166711E+10 | 1799.76 | 22-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146672E+10 | 1592.08 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156675E+10 | 1509.46 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.154790E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145399E+10 | 1548.39 | 12-JUL-08:30 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.162592E+10 | 1509.46 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.148219E+10 | 1807.45 | 25-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.157714E+10 | 2051.05 | 31-OCT-07:10 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.162113E+10 | 2067.73 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.162753E+10 | 2067.73 | 01-DEC-16:19 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.187403E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.144647E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166711E+10 | 2067.73 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.105945E+10 | 1332.52 | 02-JAN-16:30 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.929820E+09 | 1261.93 | 02-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107360E+10 | 1130.06 | 22-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.945685E+09 | 972.75 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101085E+10 | 972.75 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.999062E+09 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.939201E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.104969E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.953984E+09 | 1136.68 | 25-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.101312E+10 | 1319.06 | 31-OCT-07:10 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.103999E+10 | 1332.52 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.103819E+10 | 1332.52 | 01-DEC-16:19 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120527E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.929820E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107360E+10 | 1332.52 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.163364E+10 | 2067.77 | 02-JAN-16:30 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.143458E+10 | 1920.39 | 02-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166319E+10 | 1788.15 | 22-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146743E+10 | 1575.34 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.156901E+10 | 1509.49 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.155097E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.145857E+10 | 1513.18 | 12-JUL-07:30 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.162902E+10 | 1509.49 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.148118E+10 | 1798.62 | 25-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.156813E+10 | 2048.10 | 31-OCT-07:10 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.160556E+10 | 2067.77 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.159789E+10 | 2067.77 | 01-DEC-16:19 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.186592E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.143458E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166319E+10 | 2067.77 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.105951E+10 | 1332.52 | 02-JAN-16:30 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.926880E+09 | 1232.37 | 02-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107288E+10 | 1168.18 | 22-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.945118E+09 | 1063.56 | 03-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.100999E+10 | 972.75 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.998080E+09 | 972.75 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.938663E+09 | 1085.71 | 12-JUL-07:30 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.104818E+10 | 1086.48 | 28-AUG-07:30 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.955112E+09 | 1172.05 | 25-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.101354E+10 | 1321.88 | 31-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.103829E+10 | 1332.52 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.103778E+10 | 1332.52 | 01-DEC-16:19 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.120440E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.926880E+09 | 972.75 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107288E+10 | 1332.52 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.496348E+10 | 5170.29 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.450211E+10 | 5170.29 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.534729E+10 | 5170.29 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.477873E+10 | 5170.29 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.515538E+10 | 5170.29 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.512953E+10 | 5170.29 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.480458E+10 | 5170.29 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.534729E+10 | 5170.29 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.477873E+10 | 5170.29 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.496348E+10 | 5170.29 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.490462E+10 | 5170.29 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.480458E+10 | 5170.29 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.594798E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.450211E+10 | 5170.29 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.534729E+10 | 5170.29 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.176037E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.159674E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.169484E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.182843E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.181926E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.170401E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.169484E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.176037E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.173949E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.170401E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.210953E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.159674E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.165538E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.875724E+09 |
February | 0.136985E+10 | 0.144517E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.776164E+09 |
March | 0.163685E+10 | 0.166628E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738610E+09 |
April | 0.145243E+10 | 0.146639E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107756.25 | 0.691661E+09 |
May | 0.157338E+10 | 0.156650E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39928.27 | 0.525465E+09 |
June | 0.156900E+10 | 0.154768E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 401024.69 | 0.434329E+09 |
July | 0.145680E+10 | 0.145386E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6375331.10 | 0.357432E+09 |
August | 0.163685E+10 | 0.162590E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9362813.17 | 0.288271E+09 |
September | 0.145243E+10 | 0.148172E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39777.11 | 0.246120E+09 |
October | 0.150991E+10 | 0.157592E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591946E+09 |
November | 0.149516E+10 | 0.161948E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693821E+09 |
December | 0.145680E+10 | 0.162503E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762080E+09 |
Annual Sum or Average | 0.181194E+11 | 0.187293E+11 | 0.403414E+11 | 17326630.59 | 0.698162E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.144517E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246120E+09 |
Maximum of Months | 0.163685E+10 | 0.166628E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9362813.17 | 0.875724E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105900E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557369E+09 |
February | 0.882782E+09 | 0.929574E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494355E+09 |
March | 0.105485E+10 | 0.107341E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464402E+09 |
April | 0.936002E+09 | 0.945598E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1231180.93 | 0.430079E+09 |
May | 0.101394E+10 | 0.101077E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90834.39 | 0.333596E+09 |
June | 0.101113E+10 | 0.998987E+09 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409216.98 | 0.272242E+09 |
July | 0.938820E+09 | 0.939108E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5955884.61 | 0.212959E+09 |
August | 0.105485E+10 | 0.104956E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7651373.50 | 0.165078E+09 |
September | 0.936002E+09 | 0.953857E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64982.98 | 0.153823E+09 |
October | 0.973041E+09 | 0.101286E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369356E+09 |
November | 0.963541E+09 | 0.103970E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429761E+09 |
December | 0.938820E+09 | 0.103768E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.472904E+09 |
Annual Sum or Average | 0.116768E+11 | 0.120501E+11 | 0.259975E+11 | 15403473.39 | 0.435592E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.929574E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153823E+09 |
Maximum of Months | 0.105485E+10 | 0.107341E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7651373.50 | 0.557369E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.163214E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.832163E+09 |
February | 0.136988E+10 | 0.143396E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761406E+09 |
March | 0.163688E+10 | 0.166261E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718800E+09 |
April | 0.145246E+10 | 0.146710E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1238987.48 | 0.669819E+09 |
May | 0.157341E+10 | 0.156867E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43926.89 | 0.510493E+09 |
June | 0.156904E+10 | 0.155068E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 432187.83 | 0.417786E+09 |
July | 0.145684E+10 | 0.145825E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6840729.53 | 0.338751E+09 |
August | 0.163688E+10 | 0.162862E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9124304.72 | 0.271181E+09 |
September | 0.145246E+10 | 0.148072E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39768.48 | 0.243632E+09 |
October | 0.150994E+10 | 0.156706E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578946E+09 |
November | 0.149520E+10 | 0.160440E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660642E+09 |
December | 0.145684E+10 | 0.159662E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725309E+09 |
Annual Sum or Average | 0.181198E+11 | 0.186508E+11 | 0.403420E+11 | 17719904.92 | 0.672893E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.143396E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243632E+09 |
Maximum of Months | 0.163688E+10 | 0.166261E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9124304.72 | 0.832163E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105909E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587246E+09 |
February | 0.882782E+09 | 0.926622E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539529E+09 |
March | 0.105485E+10 | 0.107269E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525170E+09 |
April | 0.936002E+09 | 0.945009E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 390951.87 | 0.501549E+09 |
May | 0.101394E+10 | 0.100992E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51790.74 | 0.366382E+09 |
June | 0.101113E+10 | 0.998012E+09 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265132.04 | 0.309595E+09 |
July | 0.938820E+09 | 0.938585E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2852932.76 | 0.265122E+09 |
August | 0.105485E+10 | 0.104807E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5722486.76 | 0.215185E+09 |
September | 0.936002E+09 | 0.954973E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26266.04 | 0.172673E+09 |
October | 0.973041E+09 | 0.101326E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414796E+09 |
November | 0.963541E+09 | 0.103792E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490445E+09 |
December | 0.938820E+09 | 0.103727E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548483E+09 |
Annual Sum or Average | 0.116768E+11 | 0.120414E+11 | 0.259973E+11 | 9309560.21 | 0.493617E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.926622E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172673E+09 |
Maximum of Months | 0.105485E+10 | 0.107269E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5722486.76 | 0.587246E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.165744E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166901E+10 |
February | 0.136985E+10 | 0.144648E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150284E+10 |
March | 0.163685E+10 | 0.166712E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146289E+10 |
April | 0.145243E+10 | 0.146672E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3456804.01 | 0.138864E+10 |
May | 0.157338E+10 | 0.156676E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64003.65 | 0.109393E+10 |
June | 0.156900E+10 | 0.154790E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 795041.10 | 0.903608E+09 |
July | 0.145680E+10 | 0.145399E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18187384.62 | 0.749347E+09 |
August | 0.163685E+10 | 0.162592E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22472419.14 | 0.611974E+09 |
September | 0.145243E+10 | 0.148219E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70791.28 | 0.508438E+09 |
October | 0.150991E+10 | 0.157716E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117203E+10 |
November | 0.149516E+10 | 0.162117E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133374E+10 |
December | 0.145680E+10 | 0.162755E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144084E+10 |
Annual Sum or Average | 0.181194E+11 | 0.187404E+11 | 0.403414E+11 | 45046443.78 | 0.138373E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.144648E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508438E+09 |
Maximum of Months | 0.163685E+10 | 0.166712E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22472419.14 | 0.166901E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.105946E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109937E+10 |
February | 0.649041E+09 | 0.929823E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999808E+09 |
March | 0.773965E+09 | 0.107360E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.956823E+09 |
April | 0.688021E+09 | 0.945686E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2843974.52 | 0.913563E+09 |
May | 0.744847E+09 | 0.101086E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260669.94 | 0.709974E+09 |
June | 0.742030E+09 | 0.999063E+09 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 946986.81 | 0.591763E+09 |
July | 0.690839E+09 | 0.939197E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13201378.56 | 0.482502E+09 |
August | 0.773965E+09 | 0.104969E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16770863.82 | 0.392813E+09 |
September | 0.688021E+09 | 0.953984E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 165303.33 | 0.326042E+09 |
October | 0.715730E+09 | 0.101312E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758648E+09 |
November | 0.708685E+09 | 0.104000E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.865844E+09 |
December | 0.690839E+09 | 0.103819E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.947829E+09 |
Annual Sum or Average | 0.858171E+10 | 0.120527E+11 | 0.259975E+11 | 34189176.98 | 0.904498E+10 | ||||
Minimum of Months | 0.649041E+09 | 0.929823E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326042E+09 |
Maximum of Months | 0.773965E+09 | 0.107360E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16770863.82 | 0.109937E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.163364E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171640E+10 |
February | 0.136988E+10 | 0.143459E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160450E+10 |
March | 0.163688E+10 | 0.166320E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151453E+10 |
April | 0.145246E+10 | 0.146744E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2442273.63 | 0.142112E+10 |
May | 0.157341E+10 | 0.156901E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82549.62 | 0.109394E+10 |
June | 0.156904E+10 | 0.155098E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 999483.77 | 0.887764E+09 |
July | 0.145684E+10 | 0.145856E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15793734.93 | 0.741013E+09 |
August | 0.163688E+10 | 0.162902E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20256764.09 | 0.614368E+09 |
September | 0.145246E+10 | 0.148118E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67070.80 | 0.529806E+09 |
October | 0.150994E+10 | 0.156814E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123281E+10 |
November | 0.149520E+10 | 0.160549E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136166E+10 |
December | 0.145684E+10 | 0.159789E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148790E+10 |
Annual Sum or Average | 0.181198E+11 | 0.186591E+11 | 0.403420E+11 | 39641876.84 | 0.142058E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.143459E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529806E+09 |
Maximum of Months | 0.163688E+10 | 0.166320E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20256764.09 | 0.171640E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105952E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112911E+10 |
February | 0.882782E+09 | 0.926881E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102613E+10 |
March | 0.105485E+10 | 0.107288E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989555E+09 |
April | 0.936002E+09 | 0.945120E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1265956.58 | 0.950454E+09 |
May | 0.101394E+10 | 0.100999E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238990.99 | 0.754637E+09 |
June | 0.101113E+10 | 0.998080E+09 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 653223.96 | 0.616285E+09 |
July | 0.938820E+09 | 0.938663E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8300746.85 | 0.540713E+09 |
August | 0.105485E+10 | 0.104818E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15237949.46 | 0.433590E+09 |
September | 0.936002E+09 | 0.955112E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61553.65 | 0.352047E+09 |
October | 0.973041E+09 | 0.101355E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.788828E+09 |
November | 0.963541E+09 | 0.103830E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.891665E+09 |
December | 0.938820E+09 | 0.103778E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976945E+09 |
Annual Sum or Average | 0.116768E+11 | 0.120441E+11 | 0.259973E+11 | 25758421.50 | 0.944996E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.926881E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352047E+09 |
Maximum of Months | 0.105485E+10 | 0.107288E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15237949.46 | 0.112911E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.165741E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190044E+10 |
February | 0.136985E+10 | 0.144647E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169347E+10 |
March | 0.163685E+10 | 0.166711E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166179E+10 |
April | 0.145243E+10 | 0.146672E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4295380.08 | 0.160635E+10 |
May | 0.157338E+10 | 0.156675E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51954.89 | 0.129992E+10 |
June | 0.156900E+10 | 0.154790E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 860770.43 | 0.109641E+10 |
July | 0.145680E+10 | 0.145399E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19617139.56 | 0.912266E+09 |
August | 0.163685E+10 | 0.162592E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26090132.92 | 0.737658E+09 |
September | 0.145243E+10 | 0.148219E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58274.55 | 0.597768E+09 |
October | 0.150991E+10 | 0.157714E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131788E+10 |
November | 0.149516E+10 | 0.162113E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149353E+10 |
December | 0.145680E+10 | 0.162753E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160964E+10 |
Annual Sum or Average | 0.181194E+11 | 0.187403E+11 | 0.403414E+11 | 50973652.44 | 0.159271E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.144647E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.597768E+09 |
Maximum of Months | 0.163685E+10 | 0.166711E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26090132.92 | 0.190044E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105945E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126209E+10 |
February | 0.882782E+09 | 0.929820E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113358E+10 |
March | 0.105485E+10 | 0.107360E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110127E+10 |
April | 0.936002E+09 | 0.945685E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3325406.78 | 0.106815E+10 |
May | 0.101394E+10 | 0.101085E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172219.59 | 0.852555E+09 |
June | 0.101113E+10 | 0.999062E+09 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 803039.24 | 0.725384E+09 |
July | 0.938820E+09 | 0.939201E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13731073.77 | 0.593265E+09 |
August | 0.105485E+10 | 0.104969E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18687394.15 | 0.478331E+09 |
September | 0.936002E+09 | 0.953984E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120355.61 | 0.389389E+09 |
October | 0.973041E+09 | 0.101312E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869065E+09 |
November | 0.963541E+09 | 0.103999E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984942E+09 |
December | 0.938820E+09 | 0.103819E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106919E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120527E+11 | 0.259975E+11 | 36839489.15 | 0.105272E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.929820E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389389E+09 |
Maximum of Months | 0.105485E+10 | 0.107360E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18687394.15 | 0.126209E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.163364E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195237E+10 |
February | 0.136988E+10 | 0.143458E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181058E+10 |
March | 0.163688E+10 | 0.166319E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173780E+10 |
April | 0.145246E+10 | 0.146743E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2871505.93 | 0.165295E+10 |
May | 0.157341E+10 | 0.156901E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73026.90 | 0.129902E+10 |
June | 0.156904E+10 | 0.155097E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 998358.59 | 0.107241E+10 |
July | 0.145684E+10 | 0.145857E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17826866.29 | 0.898333E+09 |
August | 0.163688E+10 | 0.162902E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24055230.15 | 0.735535E+09 |
September | 0.145246E+10 | 0.148118E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57839.73 | 0.625848E+09 |
October | 0.150994E+10 | 0.156813E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140869E+10 |
November | 0.149520E+10 | 0.160556E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154140E+10 |
December | 0.145684E+10 | 0.159789E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167256E+10 |
Annual Sum or Average | 0.181198E+11 | 0.186592E+11 | 0.403420E+11 | 45882827.59 | 0.164075E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.143458E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625848E+09 |
Maximum of Months | 0.163688E+10 | 0.166319E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24055230.15 | 0.195237E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.105951E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129861E+10 |
February | 0.882782E+09 | 0.926880E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117994E+10 |
March | 0.105485E+10 | 0.107288E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115025E+10 |
April | 0.936002E+09 | 0.945118E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1457418.29 | 0.111688E+10 |
May | 0.101394E+10 | 0.100999E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 270915.09 | 0.903499E+09 |
June | 0.101113E+10 | 0.998080E+09 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 695737.89 | 0.747409E+09 |
July | 0.938820E+09 | 0.938663E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9949435.26 | 0.657938E+09 |
August | 0.105485E+10 | 0.104818E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18133744.68 | 0.521338E+09 |
September | 0.936002E+09 | 0.955112E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60616.21 | 0.418926E+09 |
October | 0.973041E+09 | 0.101354E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913799E+09 |
November | 0.963541E+09 | 0.103829E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102925E+10 |
December | 0.938820E+09 | 0.103778E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112154E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120440E+11 | 0.259973E+11 | 30567867.42 | 0.110594E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.926880E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418926E+09 |
Maximum of Months | 0.105485E+10 | 0.107288E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18133744.68 | 0.129861E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.496348E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.450211E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.534729E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.477873E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.515538E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.512953E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.480458E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.534729E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.477873E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.496348E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.490462E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.480458E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594798E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.450211E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.534729E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178048E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157243E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148698E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1532948.86 | 0.138428E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3567.16 | 0.105279E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276684.11 | 0.865510E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9857671.88 | 0.716726E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14022741.22 | 0.590001E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2097.00 | 0.495799E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119358E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139419E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153648E+10 |
Annual Sum or Average | 25695710.23 | 0.140692E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495799E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14022741.22 | 0.178048E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289930E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262986E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251928E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3950490.67 | 0.234808E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8467.59 | 0.182018E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573900.93 | 0.148470E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22973698.41 | 0.122711E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27598132.15 | 0.101609E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4334.43 | 0.855707E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201942E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231977E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253403E+10 |
Annual Sum or Average | 55109024.18 | 0.236735E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855707E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27598132.15 | 0.289930E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291932E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266385E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262925E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3208473.10 | 0.254291E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204942E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62213.52 | 0.172001E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8244721.57 | 0.142873E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17796368.95 | 0.114579E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935768E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209770E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234978E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251808E+10 |
Annual Sum or Average | 29311777.14 | 0.250006E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935768E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17796368.95 | 0.291932E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 18337.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 18337.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 18337.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 18337.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 18337.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 18337.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 18337.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 18337.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 18337.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 18337.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 18337.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 18337.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 18337.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 18337.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2067.73 | 02-JAN-16:30 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1412.49 | 28-JAN-04:00 |
February | 2010.79 | 01-FEB-10:09 | 1943.50 | 02-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1328.95 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1791.82 | 22-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1232.64 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1578.32 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.80 | 01-APR-17:02 | 1269.87 | 07-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 1509.46 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 05-MAY-16:00 | 912.46 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 28-JUN-16:00 | 1230.76 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1535.74 | 12-JUL-08:30 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 165.39 | 23-JUL-16:10 | 634.78 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1509.46 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.03 | 13-AUG-15:10 | 788.15 | 04-AUG-24:00 |
September | 2010.79 | 01-SEP-09:09 | 1799.82 | 25-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 14-SEP-17:00 | 597.45 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2050.57 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1106.37 | 31-OCT-21:10 |
November | 2010.79 | 01-NOV-09:09 | 2067.73 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 1349.10 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2067.73 | 01-DEC-16:19 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1126.42 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.45 | |||||
Maximum of Months | 2010.79 | 2067.73 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 165.39 | 1412.49 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:30 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 900.94 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1261.40 | 02-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 845.66 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1127.70 | 22-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 789.66 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 972.75 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.25 | 01-APR-17:02 | 812.18 | 07-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 06-MAY-15:00 | 581.20 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 28-JUN-16:20 | 785.29 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.64 | 23-JUL-16:10 | 397.42 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.73 | 13-AUG-15:10 | 480.98 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1134.45 | 25-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 14-SEP-17:00 | 376.56 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1318.89 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 679.04 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 841.59 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:19 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 713.46 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.56 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 163.64 | 900.94 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2067.77 | 02-JAN-16:30 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1342.86 | 28-JAN-04:00 |
February | 2010.83 | 01-FEB-10:09 | 1915.40 | 02-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1279.24 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1779.68 | 22-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1224.65 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1560.95 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.14 | 01-APR-17:20 | 1251.62 | 07-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 1509.49 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 | 05-MAY-16:00 | 873.08 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.55 | 28-JUN-16:00 | 1190.53 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1509.49 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.40 | 23-JUL-16:10 | 610.79 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1509.49 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.77 | 13-AUG-17:10 | 771.66 | 04-AUG-24:00 |
September | 2010.83 | 01-SEP-09:09 | 1790.63 | 25-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 | 14-SEP-17:00 | 572.23 | 18-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 2047.46 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1039.69 | 31-OCT-21:10 |
November | 2010.83 | 01-NOV-09:09 | 2067.77 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 1282.70 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2067.77 | 01-DEC-16:19 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1025.86 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 572.23 | |||||
Maximum of Months | 2010.83 | 2067.77 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 216.40 | 1342.86 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:30 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 964.65 | 28-JAN-04:00 |
February | 1295.83 | 01-FEB-10:09 | 1231.67 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 926.94 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1167.09 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 894.96 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1061.81 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.38 | 01-APR-16:00 | 934.24 | 07-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.18 | 06-MAY-13:00 | 618.73 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 28-JUN-16:00 | 880.54 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1084.41 | 12-JUL-07:30 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.52 | 23-JUL-14:10 | 482.88 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1084.87 | 28-AUG-07:30 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.03 | 13-AUG-15:08 | 612.28 | 04-AUG-24:00 |
September | 1295.83 | 01-SEP-09:09 | 1171.00 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.73 | 14-SEP-17:00 | 412.20 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1321.80 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 745.16 | 31-OCT-21:10 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 951.80 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:19 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 828.44 | 17-DEC-21:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 412.20 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 116.52 | 964.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2067.73 | 02-JAN-16:30 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2737.38 | 12-JAN-23:51 |
February | 2010.79 | 01-FEB-10:09 | 1947.21 | 02-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2530.30 | 16-FEB-04:00 |
March | 2010.79 | 01-MAR-10:09 | 1800.01 | 22-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2393.87 | 28-MAR-24:00 |
April | 2010.79 | 03-APR-09:09 | 1592.47 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 454.44 | 01-APR-17:02 | 2526.62 | 07-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 1509.46 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 05-MAY-16:00 | 1862.26 | 18-MAY-05:00 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 28-JUN-16:00 | 2407.56 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1548.78 | 12-JUL-08:30 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.62 | 23-JUL-15:50 | 1220.08 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1509.46 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 287.02 | 13-AUG-15:00 | 1725.59 | 11-AUG-03:52 |
September | 2010.79 | 01-SEP-09:09 | 1807.70 | 25-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 | 14-SEP-17:00 | 1207.39 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2051.07 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2195.53 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2067.73 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 2586.00 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2067.73 | 01-DEC-16:19 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2086.79 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1207.39 | |||||
Maximum of Months | 2010.79 | 2067.73 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 486.62 | 2737.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1332.52 | 02-JAN-16:30 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1786.56 | 12-JAN-23:51 |
February | 1239.33 | 01-FEB-08:09 | 1261.98 | 02-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1660.06 | 16-FEB-04:00 |
March | 1239.33 | 01-MAR-08:09 | 1130.19 | 22-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1585.02 | 28-MAR-24:00 |
April | 1239.33 | 03-APR-07:10 | 972.75 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 369.58 | 01-APR-17:02 | 1677.68 | 07-APR-23:53 |
May | 1239.33 | 01-MAY-07:10 | 972.75 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 06-MAY-15:00 | 1206.51 | 18-MAY-05:00 |
June | 1239.33 | 01-JUN-07:10 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.45 | 28-JUN-16:20 | 1569.02 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 347.68 | 23-JUL-15:50 | 788.11 | 02-JUL-04:00 |
August | 1239.33 | 01-AUG-07:10 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 201.15 | 13-AUG-18:00 | 1152.57 | 11-AUG-03:52 |
September | 1239.33 | 01-SEP-07:10 | 1136.81 | 25-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.52 | 14-SEP-17:00 | 753.73 | 18-SEP-23:00 |
October | 1239.33 | 02-OCT-07:10 | 1319.06 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1447.21 | 31-OCT-21:03 |
November | 1239.33 | 01-NOV-07:10 | 1332.52 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 1696.97 | 29-NOV-23:00 |
December | 1239.33 | 01-DEC-08:09 | 1332.52 | 01-DEC-16:19 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1376.33 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 753.73 | |||||
Maximum of Months | 1239.33 | 1332.52 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 369.58 | 1786.56 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2067.77 | 02-JAN-16:30 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2720.82 | 12-JAN-23:51 |
February | 2010.83 | 01-FEB-10:09 | 1920.46 | 02-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2726.88 | 19-FEB-12:00 |
March | 2010.83 | 01-MAR-10:09 | 1788.40 | 22-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2490.93 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1575.73 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 349.06 | 01-APR-17:02 | 2549.42 | 07-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 1509.49 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.53 | 05-MAY-16:00 | 1826.31 | 18-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.56 | 28-JUN-16:00 | 2368.65 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1513.49 | 12-JUL-07:30 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.99 | 23-JUL-15:50 | 1218.60 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1509.49 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 210.55 | 13-AUG-17:20 | 1766.18 | 11-AUG-03:52 |
September | 2010.83 | 01-SEP-09:09 | 1798.87 | 25-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 | 14-SEP-17:00 | 1173.79 | 30-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 2048.11 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2176.48 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2067.77 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 2571.34 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2067.77 | 01-DEC-16:19 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2100.17 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1173.79 | |||||
Maximum of Months | 2010.83 | 2067.77 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 507.99 | 2726.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:30 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1815.25 | 12-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 1232.47 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1688.00 | 16-FEB-04:00 |
March | 1295.83 | 01-MAR-10:09 | 1168.34 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1612.81 | 28-MAR-24:00 |
April | 1295.83 | 03-APR-09:09 | 1063.80 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.67 | 01-APR-17:02 | 1675.58 | 07-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.27 | 06-MAY-13:00 | 1224.02 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.04 | 28-JUN-15:00 | 1578.69 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1085.88 | 12-JUL-07:30 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.66 | 23-JUL-13:30 | 855.00 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1086.53 | 28-AUG-07:30 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.79 | 13-AUG-12:40 | 1242.82 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 1172.21 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.58 | 14-SEP-17:00 | 783.51 | 30-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1321.89 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1451.87 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 1725.23 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:19 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1403.03 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 783.51 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 315.66 | 1815.25 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2067.73 | 02-JAN-16:30 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3148.57 | 12-JAN-23:51 |
February | 2010.79 | 01-FEB-10:09 | 1947.12 | 02-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2904.99 | 16-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1799.76 | 22-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2819.29 | 29-MAR-05:00 |
April | 2010.79 | 03-APR-09:09 | 1592.08 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 581.56 | 01-APR-17:02 | 2962.21 | 07-APR-23:53 |
May | 2010.79 | 01-MAY-09:09 | 1509.46 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2167.29 | 22-MAY-24:00 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.08 | 28-JUN-16:00 | 2773.39 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1548.39 | 12-JUL-08:30 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 507.88 | 23-JUL-15:50 | 1391.93 | 02-JUL-04:00 |
August | 2010.79 | 01-AUG-09:09 | 1509.46 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.55 | 13-AUG-15:00 | 2074.57 | 11-AUG-03:52 |
September | 2010.79 | 01-SEP-09:09 | 1807.45 | 25-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 14-SEP-17:00 | 1372.11 | 18-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 2051.05 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2691.37 | 31-OCT-21:03 |
November | 2010.79 | 01-NOV-09:09 | 2067.73 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 2975.23 | 29-NOV-23:00 |
December | 2010.79 | 01-DEC-10:09 | 2067.73 | 01-DEC-16:19 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2431.87 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1372.11 | |||||
Maximum of Months | 2010.79 | 2067.73 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 581.56 | 3148.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:30 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2097.16 | 12-JAN-22:01 |
February | 1295.83 | 01-FEB-10:09 | 1261.93 | 02-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1934.70 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1130.06 | 22-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1879.48 | 29-MAR-04:57 |
April | 1295.83 | 03-APR-09:09 | 972.75 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 460.36 | 01-APR-17:02 | 1978.01 | 07-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.89 | 06-MAY-15:00 | 1420.08 | 18-MAY-05:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.39 | 28-JUN-16:00 | 1810.40 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 389.76 | 23-JUL-15:50 | 899.96 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 225.59 | 13-AUG-17:30 | 1389.27 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 1136.68 | 25-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 | 14-SEP-17:00 | 863.54 | 18-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1319.06 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1789.37 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 1967.52 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:19 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1612.91 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 863.54 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 460.36 | 2097.16 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2067.77 | 02-JAN-16:30 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3147.18 | 12-JAN-22:01 |
February | 2010.83 | 01-FEB-10:09 | 1920.39 | 02-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2905.82 | 16-FEB-22:03 |
March | 2010.83 | 01-MAR-10:09 | 1788.15 | 22-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2853.35 | 28-MAR-24:00 |
April | 2010.83 | 03-APR-09:09 | 1575.34 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.75 | 01-APR-17:02 | 2992.36 | 07-APR-23:53 |
May | 2010.83 | 01-MAY-09:09 | 1509.49 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 05-MAY-16:00 | 2147.06 | 22-MAY-24:00 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.08 | 28-JUN-16:00 | 2720.39 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1513.18 | 12-JUL-07:30 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 610.86 | 23-JUL-15:50 | 1388.86 | 02-JUL-04:00 |
August | 2010.83 | 01-AUG-09:09 | 1509.49 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 261.97 | 13-AUG-17:30 | 2121.29 | 11-AUG-03:52 |
September | 2010.83 | 01-SEP-09:09 | 1798.62 | 25-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.40 | 14-SEP-17:00 | 1339.03 | 30-SEP-05:00 |
October | 2010.83 | 02-OCT-09:09 | 2048.10 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2688.24 | 31-OCT-21:03 |
November | 2010.83 | 01-NOV-09:09 | 2067.77 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 2974.72 | 29-NOV-23:00 |
December | 2010.83 | 01-DEC-10:09 | 2067.77 | 01-DEC-16:19 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2453.30 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1339.03 | |||||
Maximum of Months | 2010.83 | 2067.77 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 610.86 | 3147.18 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:30 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2120.82 | 12-JAN-23:51 |
February | 1295.83 | 01-FEB-10:09 | 1232.37 | 02-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1940.05 | 16-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1168.18 | 22-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1879.53 | 29-MAR-04:53 |
April | 1295.83 | 03-APR-09:09 | 1063.56 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.79 | 01-APR-17:02 | 1970.17 | 07-APR-23:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.34 | 06-MAY-13:00 | 1453.75 | 22-MAY-24:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.38 | 28-JUN-15:40 | 1819.24 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 1085.71 | 12-JUL-07:30 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 407.53 | 23-JUL-13:50 | 986.35 | 02-JUL-04:00 |
August | 1295.83 | 01-AUG-09:09 | 1086.48 | 28-AUG-07:30 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 213.56 | 13-AUG-12:50 | 1491.79 | 11-AUG-03:52 |
September | 1295.83 | 01-SEP-09:09 | 1172.05 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.27 | 14-SEP-17:00 | 901.38 | 30-SEP-05:00 |
October | 1295.83 | 02-OCT-09:09 | 1321.88 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1796.50 | 31-OCT-21:03 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 2021.87 | 29-NOV-23:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:19 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1659.89 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 901.38 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 407.53 | 2120.82 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 5170.29 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 5170.29 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 5170.29 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 5170.29 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 5170.29 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 5170.29 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 5170.29 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 5170.29 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 5170.29 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 5170.29 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 5170.29 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 5170.29 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 5170.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 5170.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2899.41 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2701.67 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2501.25 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.42 | 01-APR-17:02 | 2535.64 | 07-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 05-MAY-16:00 | 1867.95 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 28-JUN-15:00 | 2487.45 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.92 | 23-JUL-15:51 | 1255.91 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.77 | 13-AUG-14:52 | 1592.23 | 11-AUG-03:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 14-SEP-17:00 | 1183.31 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2241.86 | 31-OCT-21:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 2739.27 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2280.14 | 17-DEC-21:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1183.31 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.92 | 2899.41 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 4904.49 | 28-JAN-04:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4536.49 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4232.47 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.45 | 01-APR-17:02 | 4346.86 | 07-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 | 05-MAY-16:00 | 3267.51 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 | 28-JUN-15:00 | 4235.98 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.93 | 23-JUL-16:00 | 2104.62 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 398.92 | 13-AUG-15:00 | 2900.48 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.15 | 14-SEP-17:00 | 2021.52 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3812.94 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 4584.77 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3660.84 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2021.52 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.93 | 4904.49 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 5034.78 | 12-JAN-23:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4564.98 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4355.07 | 29-MAR-04:53 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.52 | 01-APR-17:02 | 4673.30 | 07-APR-23:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 3352.75 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.24 | 28-JUN-17:00 | 4364.84 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.84 | 23-JUL-16:00 | 2156.24 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.61 | 13-AUG-15:50 | 3205.24 | 11-AUG-03:52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 2089.00 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4172.41 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 4741.43 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3880.70 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2089.00 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.52 | 5034.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 113849.41 | 02-JAN-02:52 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 109480.90 | 21-FEB-02:41 | 0.00 | 11039.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 110676.41 | 21-MAR-03:50 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 111035.58 | 25-APR-03:50 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 111158.00 | 01-MAY-02:52 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 112259.31 | 05-JUN-03:01 | 0.00 | 8831.65 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 111782.73 | 03-JUL-00:23 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 106458.74 | 21-AUG-02:42 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 109818.31 | 04-SEP-23:12 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 114837.52 | 02-OCT-03:01 | 0.00 | 8831.65 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 116196.32 | 12-NOV-15:40 | 4488.06 | 5093.65 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 114289.74 | 04-DEC-04:01 | 0.00 | 8831.65 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 106458.74 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 116196.32 | 4488.06 | 11039.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 71443.88 | 02-JAN-04:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 74006.32 | 27-FEB-04:02 | 0.00 | 8922.87 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71525.60 | 13-MAR-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74909.25 | 17-APR-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74756.45 | 30-MAY-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82303.82 | 12-JUN-03:03 | 0.00 | 6940.01 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 79901.43 | 17-JUL-03:03 | 0.00 | 5948.58 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 77840.13 | 10-AUG-03:01 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81275.51 | 01-SEP-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79603.30 | 10-OCT-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 75935.88 | 06-NOV-04:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 72891.22 | 11-DEC-04:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 71443.88 | 0.00 | 5948.58 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 82303.82 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 50533.05 | 12-JAN-06:02 | 8061.19 | 9148.91 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57702.85 | 28-FEB-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 59026.02 | 03-MAR-06:01 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 60266.77 | 05-APR-05:01 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 65684.11 | 01-MAY-04:02 | 0.00 | 19828.60 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68953.16 | 12-JUN-03:01 | 0.00 | 6940.01 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 67156.59 | 10-JUL-03:01 | 0.00 | 6940.01 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 72227.28 | 10-AUG-04:02 | 0.00 | 9914.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67421.23 | 01-SEP-04:02 | 0.00 | 9914.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 63050.03 | 10-OCT-05:01 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 60929.66 | 07-NOV-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 56212.94 | 15-DEC-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 50533.05 | 0.00 | 6940.01 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72227.28 | 16122.38 | 19828.60 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20852.19 | 11-JAN-16:00 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29745.71 | 28-FEB-17:00 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33058.22 | 15-MAR-16:00 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 56271.88 | 28-APR-05:03 | 6448.95 | 7319.13 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 59183.24 | 05-MAY-05:03 | 6448.95 | 7319.13 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 68367.55 | 12-JUN-03:01 | 0.00 | 6940.01 | 56399.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 64292.86 | 20-JUL-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69008.99 | 10-AUG-04:02 | 0.00 | 9914.30 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 63963.37 | 01-SEP-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52286.49 | 10-OCT-05:01 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 28436.12 | 02-NOV-16:00 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20036.94 | 06-DEC-16:50 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20036.94 | 0.00 | 6940.01 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 69008.99 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3008.86 | 11-JAN-14:10 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.02 |
February | 5185.54 | 27-FEB-15:30 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 |
March | 5433.50 | 20-MAR-13:50 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.66 |
April | 7344.20 | 27-APR-15:20 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 0.00 |
May | 7846.25 | 30-MAY-05:01 | 2024.33 | 1945.77 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.30 |
June | 8389.39 | 12-JUN-05:03 | 809.73 | 670.87 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.05 |
July | 8697.92 | 24-JUL-15:00 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 0.00 |
August | 9021.28 | 10-AUG-05:03 | 809.73 | 900.71 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.71 |
September | 8111.21 | 05-SEP-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.12 |
October | 8372.36 | 10-OCT-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.25 |
November | 5683.80 | 06-NOV-06:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.20 |
December | 3817.53 | 04-DEC-14:10 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3008.86 | 809.73 | 670.87 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9021.28 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 36.47 | 150.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3243.00 | 11-JAN-14:20 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.15 |
February | 4122.36 | 27-FEB-15:00 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 |
March | 7960.65 | 14-MAR-09:00 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.08 |
April | 10358.37 | 26-APR-08:20 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.52 |
May | 17520.29 | 14-MAY-08:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.07 |
June | 10896.61 | 25-JUN-08:43 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.16 |
July | 19351.38 | 30-JUL-09:32 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.13 |
August | 17860.16 | 06-AUG-09:12 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.61 |
September | 17083.72 | 10-SEP-09:23 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.65 |
October | 8559.66 | 04-OCT-08:50 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.89 |
November | 4218.33 | 05-NOV-12:32 | 391.37 | 324.25 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 |
December | 3326.67 | 03-DEC-11:12 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3243.00 | 260.91 | 216.17 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.63 | |
Maximum of Months | 19351.38 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14435.93 | 20-JAN-13:20 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 |
February | 18882.20 | 12-FEB-13:43 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 905.51 |
March | 16433.81 | 14-MAR-13:40 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.78 |
April | 16004.14 | 27-APR-12:50 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 0.00 |
May | 13616.61 | 07-MAY-11:11 | 708.53 | 587.03 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.36 |
June | 10140.93 | 11-JUN-12:48 | 607.31 | 503.16 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.68 |
July | 21046.48 | 30-JUL-13:12 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.42 |
August | 18067.23 | 29-AUG-12:30 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 0.00 |
September | 20381.51 | 10-SEP-12:43 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.61 |
October | 21081.96 | 08-OCT-12:02 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.79 |
November | 19503.21 | 11-NOV-12:32 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 401.94 |
December | 15071.85 | 05-DEC-12:10 | 1058.33 | 1509.49 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10140.93 | 404.87 | 335.44 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21081.96 | 2010.83 | 1509.49 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 25.89 | 905.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4797.08 | 05-JAN-15:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 |
February | 9771.71 | 27-FEB-15:30 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 |
March | 12486.59 | 09-MAR-06:02 | 652.28 | 740.29 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.63 |
April | 20173.57 | 23-APR-16:12 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.55 |
May | 25095.83 | 07-MAY-16:41 | 456.59 | 378.29 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.22 |
June | 21172.86 | 18-JUN-16:42 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.83 |
July | 24556.83 | 30-JUL-17:11 | 0.00 | 468.50 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.01 |
August | 24347.20 | 06-AUG-16:41 | 456.59 | 378.29 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.34 |
September | 19466.86 | 10-SEP-16:42 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
October | 15075.81 | 10-OCT-03:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.84 |
November | 15421.30 | 06-NOV-04:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.73 |
December | 13907.20 | 11-DEC-04:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.25 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4797.08 | 0.00 | 270.21 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.68 | |
Maximum of Months | 25095.83 | 1239.33 | 972.75 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 456.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2335.22 | 11-JAN-16:00 | 1923.11 | 1822.40 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.93 |
February | 2912.11 | 27-FEB-15:00 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 |
March | 3111.56 | 10-MAR-14:40 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.16 |
April | 5928.84 | 27-APR-15:50 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 51.52 | 0.00 |
May | 6191.04 | 05-MAY-13:30 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.29 |
June | 6728.74 | 21-JUN-15:40 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 0.00 |
July | 7311.88 | 24-JUL-15:00 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 0.00 |
August | 7713.74 | 10-AUG-05:03 | 809.73 | 899.79 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.38 |
September | 5724.93 | 14-SEP-15:50 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 2.24 | 0.00 |
October | 4001.23 | 04-OCT-15:30 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.15 |
November | 2563.33 | 04-NOV-14:00 | 211.66 | 251.58 | 885.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2107.73 | 14-DEC-12:00 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 536.39 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2107.73 | 211.66 | 251.58 | 885.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7713.74 | 2010.79 | 1822.40 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 80.97 | 536.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2826.15 | 11-JAN-14:00 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.75 |
February | 3704.27 | 27-FEB-15:30 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.88 |
March | 6002.93 | 14-MAR-09:00 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.07 |
April | 10087.18 | 27-APR-09:00 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.03 |
May | 10306.18 | 15-MAY-08:40 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.59 |
June | 10906.98 | 25-JUN-08:43 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.80 |
July | 20056.54 | 30-JUL-09:42 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.96 |
August | 19957.86 | 13-AUG-09:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.99 |
September | 9629.84 | 13-SEP-09:00 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 |
October | 7426.18 | 04-OCT-09:00 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.53 |
November | 3334.46 | 04-NOV-13:00 | 130.46 | 162.13 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2669.22 | 05-DEC-09:45 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2669.22 | 130.46 | 162.13 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20056.54 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14401.70 | 20-JAN-13:20 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 |
February | 16459.69 | 27-FEB-13:50 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.45 |
March | 16773.66 | 14-MAR-14:00 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.25 |
April | 16077.23 | 27-APR-13:10 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 27.92 | 0.00 |
May | 11276.99 | 15-MAY-13:00 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.15 |
June | 9233.91 | 21-JUN-13:30 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.35 |
July | 18069.12 | 30-JUL-13:12 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 |
August | 18220.69 | 29-AUG-12:30 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 0.00 |
September | 24002.97 | 10-SEP-13:42 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.52 |
October | 23887.03 | 08-OCT-13:12 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.58 |
November | 14507.89 | 15-NOV-13:20 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.15 |
December | 14409.73 | 05-DEC-12:40 | 1058.33 | 1509.49 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.83 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9233.91 | 506.09 | 419.30 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24002.97 | 2010.83 | 1509.49 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 57.07 | 507.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3085.89 | 05-JAN-15:50 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.62 |
February | 5882.82 | 27-FEB-15:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 |
March | 8513.09 | 14-MAR-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
April | 11920.04 | 26-APR-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 0.00 |
May | 22104.69 | 07-MAY-16:41 | 456.59 | 378.29 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.17 |
June | 20020.01 | 25-JUN-16:42 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 242.26 |
July | 21255.44 | 30-JUL-17:51 | 0.00 | 468.50 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.82 |
August | 20518.04 | 06-AUG-17:32 | 0.00 | 351.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.04 |
September | 13836.69 | 04-SEP-16:16 | 652.28 | 540.42 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.20 |
October | 9710.54 | 04-OCT-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.08 |
November | 4358.49 | 04-NOV-15:40 | 130.46 | 162.13 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.74 |
December | 3300.14 | 05-DEC-15:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.56 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3085.89 | 0.00 | 162.13 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22104.69 | 1239.33 | 972.75 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 | 391.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2174.71 | 11-JAN-16:00 | 1923.11 | 1822.20 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.49 |
February | 2774.97 | 27-FEB-15:50 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.41 |
March | 2796.00 | 10-MAR-14:40 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.58 |
April | 6681.12 | 27-APR-15:30 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 61.72 | 0.00 |
May | 6759.11 | 31-MAY-15:00 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.35 |
June | 7543.19 | 21-JUN-15:40 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10.72 | 0.00 |
July | 8542.34 | 24-JUL-15:00 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 98.84 | 0.00 |
August | 8183.98 | 09-AUG-15:30 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 0.00 |
September | 6257.52 | 14-SEP-15:50 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 0.00 |
October | 3895.49 | 04-OCT-15:30 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.10 |
November | 2446.16 | 04-NOV-14:40 | 202.43 | 251.58 | 885.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.88 |
December | 1880.03 | 29-DEC-16:00 | 1923.11 | 1931.12 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.74 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1880.03 | 202.43 | 251.58 | 885.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8542.34 | 2010.79 | 1931.12 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 116.37 | 261.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2643.60 | 11-JAN-16:00 | 1239.33 | 1175.66 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.62 |
February | 3530.23 | 27-FEB-15:00 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.95 |
March | 4520.44 | 14-MAR-09:35 | 2591.66 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.41 |
April | 9688.63 | 27-APR-09:10 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.44 |
May | 12804.85 | 14-MAY-08:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.67 |
June | 17461.41 | 25-JUN-09:12 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.43 |
July | 14349.48 | 30-JUL-09:13 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.98 |
August | 17422.56 | 06-AUG-09:02 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.05 |
September | 11968.67 | 10-SEP-09:32 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.40 |
October | 6318.39 | 04-OCT-09:10 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.34 |
November | 3148.04 | 04-NOV-16:03 | 195.68 | 194.80 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2297.93 | 05-DEC-14:00 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.11 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2297.93 | 195.68 | 194.80 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17461.41 | 2591.66 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 586.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 13030.30 | 20-JAN-13:20 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.09 |
February | 14896.59 | 27-FEB-14:20 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.43 |
March | 16776.51 | 14-MAR-13:30 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.73 |
April | 16684.61 | 27-APR-13:10 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 32.77 | 0.00 |
May | 11995.03 | 15-MAY-13:10 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.03 |
June | 9960.35 | 21-JUN-13:30 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.01 |
July | 14720.93 | 31-JUL-13:10 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 64.61 | 0.00 |
August | 18655.79 | 29-AUG-12:30 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 | 0.00 |
September | 25232.54 | 10-SEP-13:42 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.67 |
October | 23691.11 | 08-OCT-13:12 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.97 |
November | 13499.48 | 04-NOV-13:30 | 211.67 | 251.58 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12267.60 | 05-DEC-12:30 | 1058.33 | 1509.49 | 2023.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9960.35 | 211.67 | 251.58 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25232.54 | 2010.83 | 1509.49 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 69.16 | 575.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3102.19 | 05-JAN-15:50 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.04 |
February | 5225.92 | 27-FEB-15:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 |
March | 8401.39 | 14-MAR-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.55 |
April | 12270.99 | 26-APR-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 0.00 |
May | 23075.63 | 14-MAY-17:11 | 0.00 | 409.94 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.66 |
June | 21031.30 | 25-JUN-16:42 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.22 |
July | 22079.91 | 23-JUL-17:02 | 0.00 | 351.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.91 |
August | 21537.77 | 06-AUG-17:32 | 0.00 | 351.38 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.93 |
September | 13213.60 | 04-SEP-16:20 | 652.28 | 540.42 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 491.36 |
October | 9671.60 | 04-OCT-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.43 |
November | 4464.09 | 04-NOV-15:40 | 130.46 | 162.13 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 |
December | 3227.07 | 05-DEC-15:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.35 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3102.19 | 0.00 | 162.13 | 570.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23075.63 | 1239.33 | 972.75 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1.94 | 510.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5124.22 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.56 |
February | 5939.33 | 28-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.64 |
March | 6207.61 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.48 |
April | 7148.15 | 17-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.96 |
May | 7532.73 | 30-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.19 |
June | 7694.58 | 05-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.16 |
July | 8026.98 | 05-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.48 |
August | 7562.90 | 28-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.64 |
September | 9187.76 | 05-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.22 |
October | 9306.60 | 10-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.73 |
November | 7750.49 | 06-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.94 |
December | 5732.02 | 04-DEC-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5124.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9306.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4415.16 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3026.10 |
February | 4257.36 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.55 |
March | 4217.10 | 02-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.21 |
April | 4715.97 | 28-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.69 |
May | 5293.55 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385.45 |
June | 5200.62 | 23-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 355.18 |
July | 5848.04 | 10-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.27 |
August | 6101.19 | 10-AUG-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.43 |
September | 6112.05 | 14-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4796.59 | 11-OCT-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.66 |
November | 3754.44 | 18-NOV-17:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 400.01 |
December | 3876.75 | 16-DEC-17:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 522.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3754.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6112.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3026.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 809.10 | 11-JAN-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.20 |
February | 3588.48 | 27-FEB-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.17 |
March | 6211.12 | 14-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.46 |
April | 12996.31 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.15 | 0.00 |
May | 13275.60 | 15-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.73 |
June | 13717.70 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 |
July | 14621.24 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.53 | 0.00 |
August | 15451.55 | 10-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.16 | 0.00 |
September | 11803.66 | 14-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.58 |
October | 8024.59 | 04-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.15 |
November | 4665.21 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 632.54 | 30-DEC-12:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 632.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15451.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.53 | 454.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1812.59 | 05-JAN-16:10 | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3906.51 | 07-FEB-16:50 | 0.00 | 238.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5980.10 | 14-MAR-17:10 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8008.81 | 25-APR-18:00 | 0.00 | 79.62 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2506.01 | 29-MAY-18:23 | 0.00 | 43.14 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4263.48 | 18-JUN-18:55 | 0.00 | 57.52 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6618.89 | 30-JUL-18:27 | 0.00 | 115.03 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8043.70 | 06-AUG-19:20 | 0.00 | 71.90 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2363.35 | 10-SEP-17:25 | 0.00 | 57.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4241.40 | 03-OCT-16:50 | 0.00 | 132.69 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5794.63 | 12-NOV-15:55 | 0.00 | 53.08 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7624.98 | 05-DEC-15:50 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1812.59 | 0.00 | 43.14 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8043.70 | 0.00 | 238.85 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1409.11 | 05-JAN-16:20 | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3556.52 | 08-FEB-16:50 | 0.00 | 238.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5579.09 | 14-MAR-17:10 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7566.54 | 25-APR-18:00 | 0.00 | 79.62 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2243.53 | 29-MAY-18:30 | 0.00 | 43.14 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3949.10 | 22-JUN-18:50 | 0.00 | 79.62 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6112.80 | 30-JUL-18:40 | 0.00 | 100.66 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7631.25 | 06-AUG-19:12 | 0.00 | 71.90 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2142.50 | 08-SEP-17:30 | 0.00 | 79.62 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3960.90 | 03-OCT-16:50 | 0.00 | 132.69 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5179.94 | 10-NOV-16:10 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6987.04 | 05-DEC-16:00 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1409.11 | 0.00 | 43.14 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7631.25 | 0.00 | 238.85 | 40920.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1281.64 | 05-JAN-16:20 | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3448.71 | 08-FEB-17:00 | 0.00 | 238.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5584.82 | 14-MAR-17:10 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7656.40 | 26-APR-18:10 | 0.00 | 79.62 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2309.81 | 07-MAY-18:30 | 0.00 | 28.76 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4080.03 | 18-JUN-18:32 | 0.00 | 71.90 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6284.32 | 30-JUL-18:22 | 0.00 | 115.03 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7736.16 | 06-AUG-19:12 | 0.00 | 71.90 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2196.52 | 08-SEP-17:30 | 0.00 | 79.62 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3981.08 | 04-OCT-16:50 | 0.00 | 132.69 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5054.42 | 10-NOV-16:10 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6829.59 | 05-DEC-16:00 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1281.64 | 0.00 | 28.76 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7736.16 | 0.00 | 238.85 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 319756.50 | 20-JAN-23:05 | 0.00 | 2872.38 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 365059.29 | 21-FEB-22:08 | 0.00 | 5744.77 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 399117.53 | 01-MAR-23:52 | 0.00 | 2872.38 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 390892.70 | 10-APR-05:04 | 0.00 | 5744.77 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 317689.45 | 17-MAY-21:50 | 0.00 | 5744.77 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 182521.19 | 20-JUN-16:00 | 0.00 | 5170.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 274436.55 | 06-JUL-16:00 | 0.00 | 5170.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367736.15 | 10-AUG-19:45 | 0.00 | 2297.91 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 104724.22 | 01-SEP-00:08 | 0.00 | 1245.07 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 379010.82 | 22-OCT-22:16 | 0.00 | 3112.68 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 376905.25 | 17-NOV-04:55 | 0.00 | 3112.68 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 386042.52 | 23-DEC-17:12 | 0.00 | 1148.95 | 1518530.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 104724.22 | 0.00 | 1148.95 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 399117.53 | 0.00 | 5744.77 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.162181E+13 | 1050799.07 | 12-JAN-16:00 | 0.313866E+12 | 965571.26 | 02-JAN-06:10 |
February | 0.182487E+13 | 1228238.83 | 27-FEB-16:10 | 0.192882E+12 | 493406.74 | 21-FEB-07:00 |
March | 0.246972E+13 | 1373376.82 | 14-MAR-15:00 | 0.978176E+11 | 278652.16 | 25-MAR-06:00 |
April | 0.276439E+13 | 1730130.71 | 27-APR-15:09 | 0.631780E+11 | 264091.11 | 18-APR-03:49 |
May | 0.171000E+13 | 1241998.90 | 05-MAY-15:09 | 0.521108E+11 | 127769.49 | 18-MAY-06:49 |
June | 0.212503E+13 | 1402106.08 | 22-JUN-15:39 | 0.486356E+11 | 148856.69 | 15-JUN-03:49 |
July | 0.261394E+13 | 1632725.31 | 31-JUL-15:00 | 0.447491E+11 | 143968.86 | 17-JUL-02:39 |
August | 0.313087E+13 | 1830833.37 | 29-AUG-15:09 | 0.480033E+11 | 145420.18 | 21-AUG-02:39 |
September | 0.169664E+13 | 1269983.54 | 14-SEP-15:20 | 0.467125E+11 | 182938.76 | 27-SEP-05:10 |
October | 0.207072E+13 | 1275391.15 | 04-OCT-15:09 | 0.636089E+11 | 304382.16 | 23-OCT-06:40 |
November | 0.236636E+13 | 1354750.78 | 09-NOV-16:00 | 0.135154E+12 | 460064.47 | 20-NOV-03:39 |
December | 0.279208E+13 | 1496871.52 | 01-DEC-16:40 | 0.231974E+12 | 602984.67 | 26-DEC-07:19 |
Annual Sum or Average | 0.271864E+14 | 0.133869E+13 | ||||
Minimum of Months | 0.162181E+13 | 1050799.07 | 0.447491E+11 | 127769.49 | ||
Maximum of Months | 0.313087E+13 | 1830833.37 | 0.313866E+12 | 965571.26 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.279947E+12 | 0.752203E+11 | 0.811612E+12 | 0.168781E+12 | 0.169514E+12 | 0.149371E+11 | 0.00 | 0.871707E+11 | 0.118287E+11 | 0.280284E+10 | 0.00 | 0.00 | 0.00 |
February | 0.251894E+12 | 0.608139E+11 | 0.102011E+13 | 0.152457E+12 | 0.157538E+12 | 0.123717E+11 | 0.00 | 0.140802E+12 | 0.264023E+11 | 0.248712E+10 | 0.00 | 0.00 | 0.00 |
March | 0.297378E+12 | 0.575593E+11 | 0.146224E+13 | 0.169058E+12 | 0.185959E+12 | 0.136572E+11 | 0.00 | 0.220626E+12 | 0.606241E+11 | 0.261488E+10 | 0.00 | 0.00 | 0.00 |
April | 0.264925E+12 | 0.458943E+11 | 0.170426E+13 | 0.163308E+12 | 0.180045E+12 | 0.192577E+11 | 0.00 | 0.290822E+12 | 0.942119E+11 | 0.166070E+10 | 0.00 | 0.00 | 0.00 |
May | 0.285223E+12 | 0.397436E+11 | 0.820095E+12 | 0.168918E+12 | 0.188545E+12 | 0.271670E+11 | 0.00 | 0.127646E+12 | 0.520035E+11 | 0.656368E+09 | 0.00 | 0.00 | 0.00 |
June | 0.283376E+12 | 0.346064E+11 | 0.110647E+13 | 0.163570E+12 | 0.185585E+12 | 0.353190E+11 | 0.00 | 0.215695E+12 | 0.100234E+12 | 0.174703E+09 | 0.00 | 0.00 | 0.00 |
July | 0.265631E+12 | 0.372160E+11 | 0.143833E+13 | 0.168655E+12 | 0.189278E+12 | 0.465301E+11 | 0.00 | 0.334824E+12 | 0.133427E+12 | 46389001.26 | 0.00 | 0.00 | 0.00 |
August | 0.295891E+12 | 0.435896E+11 | 0.177907E+13 | 0.169058E+12 | 0.197590E+12 | 0.531525E+11 | 0.00 | 0.449052E+12 | 0.143467E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.265495E+12 | 0.514313E+11 | 0.784429E+12 | 0.163308E+12 | 0.183460E+12 | 0.324327E+11 | 0.00 | 0.143858E+12 | 0.722138E+11 | 16740454.20 | 0.00 | 0.00 | 0.00 |
October | 0.277091E+12 | 0.632872E+11 | 0.112844E+13 | 0.168779E+12 | 0.183352E+12 | 0.181829E+11 | 0.00 | 0.168760E+12 | 0.620842E+11 | 0.735708E+09 | 0.00 | 0.00 | 0.00 |
November | 0.276137E+12 | 0.701424E+11 | 0.140306E+13 | 0.163417E+12 | 0.170532E+12 | 0.135776E+11 | 0.00 | 0.210632E+12 | 0.574764E+11 | 0.138037E+10 | 0.00 | 0.00 | 0.00 |
December | 0.271759E+12 | 0.775432E+11 | 0.175516E+13 | 0.168659E+12 | 0.172750E+12 | 0.119823E+11 | 0.00 | 0.271923E+12 | 0.596529E+11 | 0.265171E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331475E+13 | 0.657047E+12 | 0.152133E+14 | 0.198797E+13 | 0.216415E+13 | 0.298568E+12 | 0.00 | 0.266181E+13 | 0.873626E+12 | 0.152275E+11 | |||
Minimum of Months | 0.251894E+12 | 0.346064E+11 | 0.784429E+12 | 0.152457E+12 | 0.157538E+12 | 0.119823E+11 | 0.00 | 0.871707E+11 | 0.118287E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.297378E+12 | 0.775432E+11 | 0.177907E+13 | 0.169058E+12 | 0.197590E+12 | 0.531525E+11 | 0.00 | 0.449052E+12 | 0.143467E+12 | 0.280284E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.262944E+12 | 0.00 | 0.509225E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.146325E+12 | 0.00 | 0.465576E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.438769E+11 | 0.00 | 0.539407E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.153436E+11 | 0.00 | 0.478343E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.289856E+10 | 0.00 | 0.492123E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.167265E+10 | 0.00 | 0.469629E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.932047E+09 | 0.00 | 0.438170E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.797133E+09 | 0.00 | 0.472061E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.310800E+10 | 0.00 | 0.436045E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.172193E+11 | 0.00 | 0.463896E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.879615E+11 | 0.00 | 0.471928E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.183358E+12 | 0.00 | 0.486169E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.766436E+12 | 0.572257E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.797133E+09 | 0.00 | 0.436045E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.262944E+12 | 0.00 | 0.539407E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 305596.68 | 02-JAN-16:30 | 53035.91 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 128036.92 | 04-JAN-08:20 | 113140.84 | 20-JAN-13:39 | 32143.02 | 02-JAN-06:19 | 0.00 | 01-JAN-00:10 |
February | 300201.35 | 02-FEB-16:00 | 53035.91 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 128034.13 | 02-FEB-08:20 | 128011.33 | 08-FEB-14:00 | 27058.87 | 21-FEB-06:19 | 0.00 | 01-FEB-00:10 |
March | 294611.97 | 22-MAR-07:10 | 53035.91 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 128030.69 | 22-MAR-07:19 | 132735.65 | 01-MAR-15:30 | 24968.75 | 24-MAR-05:10 | 0.00 | 01-MAR-00:10 |
April | 286415.32 | 03-APR-07:10 | 53035.91 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 128023.89 | 03-APR-07:19 | 124674.88 | 24-APR-15:20 | 45054.27 | 26-APR-15:39 | 0.00 | 01-APR-00:10 |
May | 283563.73 | 01-MAY-07:10 | 53035.91 | 01-MAY-19:19 | 439129.89 | 01-MAY-07:10 | 128021.52 | 01-MAY-07:19 | 127429.45 | 25-MAY-15:00 | 45994.73 | 04-MAY-14:39 | 0.00 | 01-MAY-00:10 |
June | 283563.73 | 01-JUN-07:10 | 53035.91 | 01-JUN-19:00 | 557421.28 | 01-JUN-07:10 | 128021.52 | 01-JUN-07:19 | 122997.17 | 28-JUN-15:00 | 47528.52 | 22-JUN-15:39 | 0.00 | 01-JUN-00:10 |
July | 285162.59 | 12-JUL-08:30 | 53035.91 | 01-JUL-20:10 | 675712.68 | 03-JUL-07:10 | 128022.68 | 12-JUL-07:40 | 127720.22 | 05-JUL-15:00 | 44819.76 | 06-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 284927.33 | 28-AUG-07:30 | 53035.91 | 01-AUG-19:40 | 794004.08 | 01-AUG-07:10 | 128022.65 | 28-AUG-07:40 | 139784.20 | 10-AUG-15:00 | 43118.44 | 21-AUG-14:39 | 0.00 | 01-AUG-00:10 |
September | 294956.77 | 25-SEP-07:10 | 53035.91 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 128030.98 | 25-SEP-07:19 | 129603.45 | 05-SEP-14:30 | 45271.22 | 08-SEP-14:39 | 0.00 | 01-SEP-00:10 |
October | 304870.30 | 31-OCT-07:10 | 53035.91 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 128039.22 | 31-OCT-07:19 | 134617.98 | 11-OCT-12:09 | 37313.61 | 03-OCT-14:00 | 0.00 | 01-OCT-00:10 |
November | 305596.68 | 06-NOV-16:49 | 53035.91 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 128039.25 | 03-NOV-07:19 | 124657.02 | 15-NOV-13:50 | 37500.30 | 04-NOV-14:39 | 0.00 | 01-NOV-00:10 |
December | 305596.68 | 01-DEC-16:19 | 53035.91 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 128039.29 | 28-DEC-08:20 | 120135.25 | 05-DEC-11:00 | 27252.87 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 283563.73 | 53035.91 | 439129.89 | 128021.52 | 113140.84 | 24968.75 | 0.00 | |||||||
Maximum of Months | 305596.68 | 53035.91 | 794004.08 | 128039.29 | 139784.20 | 47528.52 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 93763.55 | 13-JAN-00:20 | 20447.77 | 11-JAN-15:30 | 22749.71 | 13-JAN-00:20 | 0.00 | 0.00 | 0.00 |
February | 136467.02 | 27-FEB-14:00 | 50333.27 | 27-FEB-15:09 | 33603.17 | 14-FEB-22:19 | 0.00 | 0.00 | 0.00 |
March | 153694.18 | 18-MAR-15:00 | 49656.42 | 18-MAR-14:09 | 20431.46 | 07-MAR-22:30 | 0.00 | 0.00 | 0.00 |
April | 321514.06 | 26-APR-15:39 | 78938.91 | 27-APR-13:50 | 6799.32 | 01-APR-16:10 | 0.00 | 0.00 | 0.00 |
May | 217391.39 | 04-MAY-14:39 | 78938.91 | 05-MAY-12:39 | 18381.39 | 23-MAY-21:19 | 0.00 | 0.00 | 0.00 |
June | 254161.04 | 22-JUN-15:39 | 78938.91 | 28-JUN-16:40 | 2187.91 | 09-JUN-09:00 | 0.00 | 0.00 | 0.00 |
July | 337645.15 | 31-JUL-15:00 | 78938.91 | 07-JUL-12:39 | 1164.17 | 18-JUL-18:00 | 0.00 | 0.00 | 0.00 |
August | 406777.37 | 29-AUG-14:39 | 78938.91 | 07-AUG-10:20 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 230202.97 | 14-SEP-12:00 | 78938.91 | 11-SEP-15:09 | 979.26 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 141967.87 | 04-OCT-14:00 | 50229.66 | 04-OCT-14:00 | 33358.62 | 16-OCT-21:19 | 0.00 | 0.00 | 0.00 |
November | 167722.54 | 04-NOV-14:50 | 51908.88 | 04-NOV-13:20 | 18677.72 | 17-NOV-22:19 | 0.00 | 0.00 | 0.00 |
December | 107038.81 | 30-DEC-21:19 | 47970.39 | 14-DEC-11:00 | 6767.06 | 09-DEC-22:49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||
Minimum of Months | 93763.55 | 20447.77 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 406777.37 | 78938.91 | 33603.17 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1050799.07 | 12-JAN-16:00 | 305596.68 | 439129.89 | 53035.91 | 91260.43 | 94241.14 | 25400.69 | 0.00 | 35071.02 | 5100.62 |
February | 1228238.83 | 27-FEB-16:10 | 283563.73 | 557421.28 | 0.00 | 91242.13 | 94633.97 | 23761.68 | 0.00 | 127041.32 | 50151.99 |
March | 1373376.82 | 14-MAR-15:00 | 283563.73 | 675712.68 | 0.00 | 91242.13 | 112099.85 | 23586.31 | 0.00 | 136417.61 | 49531.17 |
April | 1730130.71 | 27-APR-15:09 | 283563.73 | 794004.08 | 0.00 | 91242.13 | 123195.57 | 38866.71 | 0.00 | 320319.60 | 78938.91 |
May | 1241998.90 | 05-MAY-15:09 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 101227.67 | 39417.73 | 0.00 | 208478.84 | 78938.91 |
June | 1402106.08 | 22-JUN-15:39 | 283563.73 | 557421.28 | 0.00 | 91242.13 | 116094.94 | 47528.52 | 0.00 | 254161.04 | 52094.44 |
July | 1632725.31 | 31-JUL-15:00 | 283563.73 | 675712.68 | 0.00 | 91242.13 | 125712.62 | 39910.09 | 0.00 | 337645.15 | 78938.91 |
August | 1830833.37 | 29-AUG-15:09 | 283563.73 | 794004.08 | 0.00 | 91242.13 | 137669.97 | 40790.35 | 0.00 | 404624.21 | 78938.91 |
September | 1269983.54 | 14-SEP-15:20 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 128224.96 | 39482.98 | 0.00 | 209400.95 | 78938.91 |
October | 1275391.15 | 04-OCT-15:09 | 283563.73 | 557421.28 | 0.00 | 91242.13 | 124474.79 | 25007.89 | 0.00 | 140921.76 | 50213.37 |
November | 1354750.78 | 09-NOV-16:00 | 305596.68 | 675712.68 | 53035.91 | 91260.43 | 101077.27 | 23963.63 | 0.00 | 82860.72 | 19788.01 |
December | 1496871.52 | 01-DEC-16:40 | 305596.68 | 794004.08 | 53035.91 | 91260.43 | 97074.90 | 23462.05 | 0.00 | 104723.28 | 25920.58 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1050799.07 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 94241.14 | 23462.05 | 0.00 | 35071.02 | 5100.62 | |
Maximum of Months | 1830833.37 | 305596.68 | 794004.08 | 53035.91 | 91260.43 | 137669.97 | 47528.52 | 0.00 | 404624.21 | 78938.91 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 959875.39 | 02-JAN-06:10 | 0.00 | 78023.04 | 30-JAN-12:00 | 0.00 |
February | 0.00 | 0.00 | 487710.87 | 21-FEB-07:00 | 0.00 | 78085.77 | 14-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 272956.29 | 25-MAR-06:00 | 0.00 | 77942.77 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 258395.24 | 18-APR-03:49 | 0.00 | 76977.57 | 04-APR-11:00 | 0.00 |
May | 0.00 | 0.00 | 122073.62 | 18-MAY-06:49 | 0.00 | 75550.81 | 02-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 143160.82 | 15-JUN-03:49 | 0.00 | 73827.86 | 01-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 138272.99 | 17-JUL-02:39 | 0.00 | 72146.17 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 139724.31 | 21-AUG-02:39 | 0.00 | 71337.90 | 30-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 177242.89 | 27-SEP-05:10 | 0.00 | 72433.30 | 29-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 298686.29 | 23-OCT-06:40 | 0.00 | 74141.57 | 30-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 454368.60 | 20-NOV-03:39 | 0.00 | 75863.82 | 28-NOV-12:39 | 0.00 |
December | 0.00 | 0.00 | 597288.80 | 26-DEC-07:19 | 0.00 | 77250.32 | 29-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 122073.62 | 0.00 | 71337.90 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 959875.39 | 0.00 | 78085.77 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.29 | 1.50 | 28.39 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 26.25 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 | 26.28 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.65 | 0.83 | 27.34 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.45 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.70 | 0.17 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.45 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 26.94 | 1.17 | 27.99 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.79 | 0.67 | 28.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.08 | 2.17 | 28.20 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.66 | 0.67 | 27.30 |
Annual Sum or Average | 0.00 | 0.00 | 92.67 | 26.70 | 7.17 | 28.02 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.03 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.29 | 2.17 | 28.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.57 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.17 | 25.59 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.61 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.67 | 19.25 | 0.33 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.50 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 19.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.67 | 19.19 | 0.33 | 20.25 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.67 | 19.36 | 0.33 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.60 | 0.67 | 27.60 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.70 | 0.67 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.11 | 1.50 | 28.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.91 | 1.67 | 27.91 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.79 | 0.67 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 5.17 | 27.89 | 5.17 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.11 | 1.67 | 28.11 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.47 | 0.67 | 27.47 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 25.06 | 1.00 | 25.06 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.28 | 0.33 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.17 | 27.38 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.94 | 1.00 | 27.94 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.56 | 1.00 | 27.56 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.17 | 27.34 |
Annual Sum or Average | 0.00 | 0.00 | 5.33 | 27.13 | 5.33 | 27.13 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.94 | 1.00 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.49 | 2.17 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 28.10 | 2.33 | 28.06 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.84 | 1.50 | 27.72 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 28.07 | 3.50 | 28.05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 27.68 | 3.00 | 28.08 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.72 | 1.17 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.17 | 27.31 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.29 | 0.33 | 27.29 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 33.83 | 27.80 | 14.50 | 27.89 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | 28.10 | 3.50 | 28.08 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.19 | 0.17 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.00 | 19.19 | 0.17 | 20.28 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.19 | 0.17 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.67 | 18.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.48 | 0.50 | 27.48 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.68 | 0.50 | 27.68 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.06 | 1.67 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 28.02 | 1.50 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.66 | 0.50 | 27.66 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 18.91 | 0.00 | 4.67 | 27.90 | 4.67 | 27.90 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 18.91 | 0.00 | 0.00 | 1.67 | 28.06 | 1.67 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.85 | 1.50 | 25.85 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.72 | 1.83 | 24.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.06 | 1.17 | 28.06 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 25.45 | 2.50 | 25.45 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.63 | 0.50 | 27.63 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
Annual Sum or Average | 0.33 | 18.56 | 0.00 | 7.67 | 25.93 | 7.67 | 25.93 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.56 | 0.00 | 0.00 | 2.50 | 28.06 | 2.50 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 18.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.14 | 1.33 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.86 | 0.33 | 27.56 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 28.47 | 1.17 | 28.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.05 | 0.83 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.89 | 0.33 | 28.03 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 18.81 | 0.00 | 9.33 | 28.19 | 4.00 | 28.09 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 18.81 | 0.00 | 0.00 | 3.17 | 28.47 | 1.33 | 28.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.17 | 18.57 | 4.33 | 19.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 7.67 | 18.05 | 2.33 | 18.23 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.83 | 19.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.83 | 19.13 | 0.17 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6.50 | 19.13 | 1.67 | 20.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 30.17 | 18.61 | 8.50 | 19.04 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.17 | 19.44 | 4.33 | 20.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 6.33 | 17.61 | 0.83 | 15.01 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.67 | 17.73 | 0.50 | 14.98 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.00 | 19.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.17 | 19.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.97 | 1.33 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.78 | 1.17 | 27.78 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 18.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.67 | 18.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 16.17 | 18.07 | 1.33 | 15.00 | 2.83 | 27.83 | 2.83 | 27.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.33 | 19.41 | 0.83 | 15.01 | 1.33 | 27.97 | 1.33 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.17 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2.00 | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 18.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.91 | 1.17 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.67 | 18.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 10.33 | 18.59 | 0.00 | 1.17 | 27.91 | 1.17 | 27.91 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4.17 | 18.93 | 0.00 | 0.00 | 1.17 | 27.91 | 1.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.83 | 18.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 18.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.15 | 1.33 | 28.03 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.86 | 0.50 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 28.49 | 1.33 | 28.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.98 | 1.00 | 27.93 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.81 | 0.33 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.50 | 18.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 8.17 | 18.60 | 0.00 | 9.83 | 28.17 | 4.50 | 28.11 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 19.14 | 0.00 | 0.00 | 3.33 | 28.49 | 1.33 | 28.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.89 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 17.50 | 27.89 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 17.50 | 27.89 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.92 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 14.00 | 27.92 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 27.92 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.95 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 11.50 | 27.95 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 27.95 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.17 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.69 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.93 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 28.05 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.97 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 28.06 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.35 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.92 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 59.50 | 28.07 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 28.69 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 68.33 | 24.07 | 94.83 | 26.09 | 1.50 | 26.84 |
February | 51.67 | 24.02 | 109.83 | 25.66 | 0.00 | 0.00 |
March | 39.00 | 24.03 | 101.67 | 25.84 | 0.00 | 0.00 |
April | 3.50 | 24.03 | 151.50 | 25.54 | 0.00 | 0.00 |
May | 0.83 | 24.00 | 218.33 | 25.07 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 254.67 | 24.86 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 390.83 | 24.74 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 466.00 | 24.50 | 0.00 | 0.00 |
September | 0.83 | 26.82 | 350.50 | 24.72 | 0.83 | 26.82 |
October | 0.67 | 26.83 | 175.67 | 25.55 | 0.67 | 26.83 |
November | 3.00 | 25.29 | 186.83 | 25.45 | 1.33 | 26.82 |
December | 21.00 | 24.04 | 107.17 | 26.32 | 0.00 | 0.00 |
Annual Sum or Average | 188.83 | 24.08 | 2607.83 | 25.08 | 4.33 | 26.83 |
Minimum of Months | 0.00 | 0.00 | 94.83 | 24.50 | 0.00 | 0.00 |
Maximum of Months | 68.33 | 26.83 | 466.00 | 26.32 | 1.50 | 26.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 151.67 | 24.02 | 39.33 | 25.54 | 12.67 | 26.25 |
February | 71.17 | 23.93 | 89.83 | 25.16 | 0.00 | 0.00 |
March | 32.17 | 23.95 | 115.00 | 25.38 | 0.00 | 0.00 |
April | 7.67 | 23.73 | 161.83 | 24.98 | 0.00 | 0.00 |
May | 16.00 | 23.60 | 220.17 | 24.69 | 0.00 | 0.00 |
June | 7.33 | 23.60 | 290.17 | 24.49 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 406.67 | 24.37 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 471.50 | 24.24 | 0.00 | 0.00 |
September | 1.33 | 23.67 | 348.83 | 24.47 | 0.00 | 0.00 |
October | 8.00 | 23.69 | 194.67 | 25.01 | 0.00 | 0.00 |
November | 5.67 | 23.93 | 190.67 | 25.09 | 0.00 | 0.00 |
December | 29.50 | 23.97 | 103.67 | 25.93 | 0.00 | 0.00 |
Annual Sum or Average | 330.50 | 23.94 | 2632.33 | 24.69 | 12.67 | 26.25 |
Minimum of Months | 0.00 | 0.00 | 39.33 | 24.24 | 0.00 | 0.00 |
Maximum of Months | 151.67 | 24.02 | 471.50 | 25.93 | 12.67 | 26.25 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 439.83 | 23.08 | 12.17 | 19.96 | 12.17 | 19.96 |
February | 335.00 | 23.42 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 273.67 | 23.68 | 4.33 | 24.43 | 0.00 | 0.00 |
April | 169.17 | 23.55 | 46.83 | 24.69 | 0.00 | 0.00 |
May | 114.17 | 23.51 | 115.17 | 24.50 | 0.00 | 0.00 |
June | 72.17 | 23.40 | 161.33 | 24.50 | 0.00 | 0.00 |
July | 59.00 | 23.23 | 250.33 | 24.44 | 0.00 | 0.00 |
August | 48.33 | 23.24 | 327.83 | 24.26 | 0.00 | 0.00 |
September | 57.50 | 23.30 | 225.83 | 24.46 | 0.00 | 0.00 |
October | 164.50 | 23.52 | 55.83 | 24.94 | 0.00 | 0.00 |
November | 253.00 | 23.52 | 27.00 | 24.45 | 0.00 | 0.00 |
December | 396.17 | 23.45 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2382.50 | 23.41 | 1226.67 | 24.40 | 12.17 | 19.96 |
Minimum of Months | 48.33 | 23.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 439.83 | 23.68 | 327.83 | 24.94 | 12.17 | 19.96 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.61 | 102.00 | 19.35 | 102.00 | 19.35 |
February | 437.33 | 22.10 | 55.00 | 19.72 | 55.00 | 19.72 |
March | 446.83 | 22.86 | 12.67 | 20.85 | 12.33 | 20.76 |
April | 315.00 | 23.13 | 31.33 | 24.34 | 0.00 | 0.00 |
May | 214.50 | 23.32 | 71.33 | 24.18 | 0.00 | 0.00 |
June | 125.67 | 23.36 | 147.17 | 24.35 | 0.00 | 0.00 |
July | 97.83 | 23.32 | 250.67 | 24.30 | 0.00 | 0.00 |
August | 89.17 | 23.24 | 295.17 | 24.18 | 0.00 | 0.00 |
September | 180.83 | 23.17 | 154.33 | 24.21 | 0.00 | 0.00 |
October | 364.00 | 22.92 | 3.00 | 24.02 | 0.00 | 0.00 |
November | 447.67 | 22.44 | 18.83 | 20.91 | 16.33 | 20.44 |
December | 496.67 | 21.93 | 74.67 | 20.27 | 74.67 | 20.27 |
Annual Sum or Average | 3717.50 | 22.54 | 1216.17 | 23.30 | 260.33 | 19.83 |
Minimum of Months | 89.17 | 21.61 | 3.00 | 19.35 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.36 | 295.17 | 24.35 | 102.00 | 20.76 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.83 | 22.81 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 390.17 | 23.07 | 2.33 | 24.52 | 0.00 | 0.00 |
March | 348.50 | 23.50 | 2.50 | 24.54 | 0.00 | 0.00 |
April | 174.67 | 23.65 | 58.83 | 24.43 | 0.00 | 0.00 |
May | 140.83 | 23.60 | 120.17 | 24.44 | 0.00 | 0.00 |
June | 26.00 | 23.66 | 193.33 | 24.41 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 363.67 | 24.31 | 0.00 | 0.00 |
August | 0.83 | 23.70 | 413.67 | 24.20 | 0.00 | 0.00 |
September | 85.50 | 23.47 | 199.67 | 24.36 | 0.00 | 0.00 |
October | 247.17 | 23.45 | 28.00 | 25.08 | 0.00 | 0.00 |
November | 344.17 | 23.42 | 22.00 | 24.61 | 0.00 | 0.00 |
December | 474.17 | 23.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2728.83 | 23.29 | 1404.17 | 24.33 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.83 | 23.70 | 413.67 | 25.08 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.81 | 4.17 | 20.70 | 4.17 | 20.70 |
February | 437.17 | 22.14 | 3.17 | 22.00 | 2.33 | 20.58 |
March | 472.67 | 22.63 | 2.33 | 24.00 | 0.00 | 0.00 |
April | 302.33 | 22.79 | 57.33 | 24.21 | 0.00 | 0.00 |
May | 248.67 | 22.80 | 128.83 | 24.41 | 1.33 | 26.60 |
June | 169.00 | 22.86 | 188.33 | 24.34 | 2.67 | 26.43 |
July | 166.17 | 22.92 | 237.67 | 24.19 | 7.17 | 26.75 |
August | 180.67 | 22.84 | 235.50 | 24.08 | 6.50 | 26.77 |
September | 237.33 | 22.63 | 149.33 | 24.41 | 3.00 | 26.56 |
October | 380.33 | 22.57 | 42.00 | 24.66 | 0.17 | 25.74 |
November | 466.17 | 22.31 | 5.67 | 24.59 | 0.00 | 0.00 |
December | 497.00 | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4059.50 | 22.41 | 1054.33 | 24.25 | 27.33 | 25.24 |
Minimum of Months | 166.17 | 21.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 22.92 | 237.67 | 24.66 | 7.17 | 26.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 461.83 | 21.90 | 30.50 | 22.25 | 19.67 | 20.67 |
February | 355.67 | 22.28 | 61.67 | 24.34 | 6.83 | 20.92 |
March | 356.83 | 22.80 | 53.33 | 24.30 | 0.00 | 0.00 |
April | 249.83 | 23.06 | 100.33 | 24.27 | 0.33 | 26.19 |
May | 239.17 | 23.03 | 124.00 | 24.35 | 0.83 | 26.01 |
June | 165.83 | 23.07 | 170.67 | 24.32 | 0.00 | 0.00 |
July | 105.50 | 23.13 | 271.00 | 24.22 | 0.83 | 25.94 |
August | 96.00 | 23.14 | 319.50 | 24.15 | 2.50 | 26.12 |
September | 165.67 | 22.99 | 230.67 | 24.34 | 4.00 | 26.86 |
October | 291.50 | 22.89 | 121.17 | 24.55 | 3.00 | 26.64 |
November | 384.83 | 22.55 | 47.50 | 24.78 | 1.50 | 26.60 |
December | 426.00 | 22.28 | 33.67 | 24.57 | 0.17 | 26.43 |
Annual Sum or Average | 3298.67 | 22.61 | 1564.00 | 24.27 | 39.67 | 22.65 |
Minimum of Months | 96.00 | 21.90 | 30.50 | 22.25 | 0.00 | 0.00 |
Maximum of Months | 461.83 | 23.14 | 319.50 | 24.78 | 19.67 | 26.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.83 | 22.37 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 337.17 | 22.89 | 49.50 | 25.02 | 0.17 | 25.54 |
March | 157.00 | 23.23 | 129.83 | 24.98 | 0.00 | 0.00 |
April | 28.50 | 23.94 | 298.50 | 24.74 | 5.83 | 26.09 |
May | 137.33 | 23.19 | 237.83 | 24.61 | 8.50 | 26.60 |
June | 22.50 | 23.91 | 361.83 | 24.47 | 5.17 | 26.24 |
July | 20.33 | 26.54 | 475.00 | 24.50 | 20.33 | 26.54 |
August | 18.33 | 26.39 | 513.33 | 24.38 | 18.33 | 26.39 |
September | 116.33 | 23.01 | 261.67 | 24.55 | 5.17 | 26.26 |
October | 175.33 | 23.01 | 163.50 | 24.96 | 1.17 | 26.09 |
November | 189.67 | 23.13 | 131.00 | 25.05 | 1.33 | 26.08 |
December | 209.17 | 23.22 | 100.33 | 25.49 | 0.00 | 0.00 |
Annual Sum or Average | 1899.50 | 22.99 | 2722.33 | 24.64 | 66.00 | 26.40 |
Minimum of Months | 18.33 | 22.37 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 487.83 | 26.54 | 513.33 | 25.49 | 20.33 | 26.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.87 | 181.33 | 19.93 | 181.33 | 19.93 |
February | 450.83 | 21.35 | 93.50 | 19.87 | 93.50 | 19.87 |
March | 510.00 | 22.26 | 19.00 | 20.38 | 19.00 | 20.38 |
April | 410.17 | 22.73 | 13.83 | 24.15 | 0.00 | 0.00 |
May | 293.50 | 23.03 | 46.17 | 24.15 | 0.00 | 0.00 |
June | 198.83 | 23.32 | 79.17 | 24.20 | 0.00 | 0.00 |
July | 137.00 | 23.40 | 194.67 | 24.15 | 0.00 | 0.00 |
August | 143.67 | 23.28 | 250.67 | 24.11 | 0.00 | 0.00 |
September | 273.17 | 23.08 | 85.67 | 24.14 | 0.00 | 0.00 |
October | 460.83 | 22.52 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 489.00 | 21.79 | 36.67 | 20.49 | 36.67 | 20.49 |
December | 497.00 | 21.17 | 117.67 | 20.25 | 117.67 | 20.25 |
Annual Sum or Average | 4366.00 | 22.12 | 1118.33 | 22.51 | 448.17 | 20.07 |
Minimum of Months | 137.00 | 20.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 510.00 | 23.40 | 250.67 | 24.20 | 181.33 | 20.49 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.55 | 182.67 | 19.91 | 182.67 | 19.91 |
February | 385.00 | 21.02 | 89.17 | 20.17 | 89.17 | 20.17 |
March | 426.17 | 21.59 | 17.50 | 20.28 | 17.33 | 20.24 |
April | 340.00 | 22.13 | 30.33 | 24.41 | 0.33 | 21.00 |
May | 316.83 | 22.33 | 59.67 | 24.74 | 0.83 | 26.33 |
June | 242.83 | 22.58 | 112.17 | 24.62 | 2.00 | 26.51 |
July | 213.00 | 22.68 | 145.00 | 24.49 | 7.17 | 26.83 |
August | 217.50 | 22.59 | 161.50 | 24.31 | 6.67 | 26.77 |
September | 296.00 | 22.27 | 79.00 | 24.48 | 2.50 | 26.52 |
October | 397.33 | 21.78 | 12.00 | 24.92 | 0.00 | 0.00 |
November | 417.00 | 21.18 | 40.83 | 20.43 | 40.83 | 20.43 |
December | 422.00 | 20.81 | 127.83 | 20.26 | 127.83 | 20.26 |
Annual Sum or Average | 4100.67 | 21.64 | 1057.67 | 22.60 | 477.33 | 20.38 |
Minimum of Months | 213.00 | 20.55 | 12.00 | 19.91 | 0.00 | 0.00 |
Maximum of Months | 427.00 | 22.68 | 182.67 | 24.92 | 182.67 | 26.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.33 | 21.09 | 125.67 | 20.31 | 118.33 | 20.00 |
February | 375.17 | 21.52 | 87.67 | 22.35 | 46.50 | 20.33 |
March | 398.00 | 21.98 | 50.83 | 23.49 | 11.17 | 20.35 |
April | 326.17 | 22.33 | 75.17 | 24.49 | 0.00 | 0.00 |
May | 322.00 | 22.60 | 85.17 | 24.43 | 0.50 | 26.14 |
June | 291.83 | 22.77 | 83.17 | 24.45 | 0.00 | 0.00 |
July | 220.83 | 22.86 | 179.83 | 24.29 | 0.50 | 25.92 |
August | 200.33 | 22.79 | 230.17 | 24.23 | 0.83 | 25.93 |
September | 238.50 | 22.73 | 186.83 | 24.33 | 4.50 | 26.91 |
October | 345.50 | 22.27 | 101.50 | 24.67 | 2.17 | 26.68 |
November | 432.50 | 21.68 | 47.33 | 23.46 | 16.50 | 20.79 |
December | 447.67 | 21.31 | 86.50 | 21.37 | 65.33 | 20.28 |
Annual Sum or Average | 4072.83 | 22.02 | 1339.83 | 23.60 | 266.33 | 20.40 |
Minimum of Months | 200.33 | 21.09 | 47.33 | 20.31 | 0.00 | 0.00 |
Maximum of Months | 474.33 | 22.86 | 230.17 | 24.67 | 118.33 | 26.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.78 | 145.33 | 20.04 | 145.33 | 20.04 |
February | 444.00 | 21.17 | 65.50 | 20.12 | 63.50 | 19.98 |
March | 488.33 | 21.74 | 18.67 | 21.94 | 10.83 | 20.32 |
April | 387.33 | 22.19 | 51.33 | 24.58 | 0.00 | 0.00 |
May | 352.83 | 22.57 | 83.50 | 24.59 | 5.83 | 26.66 |
June | 294.00 | 22.64 | 115.00 | 24.43 | 1.17 | 26.26 |
July | 179.33 | 22.85 | 223.17 | 24.50 | 7.33 | 26.76 |
August | 208.50 | 22.63 | 192.00 | 24.35 | 4.67 | 26.57 |
September | 316.83 | 22.42 | 111.33 | 24.49 | 2.67 | 26.26 |
October | 454.17 | 21.93 | 23.17 | 24.68 | 1.17 | 27.09 |
November | 482.67 | 21.37 | 15.83 | 21.23 | 13.33 | 20.59 |
December | 497.00 | 21.06 | 66.50 | 20.34 | 66.50 | 20.34 |
Annual Sum or Average | 4607.00 | 21.78 | 1111.33 | 23.30 | 322.33 | 20.59 |
Minimum of Months | 179.33 | 20.78 | 15.83 | 20.04 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 22.85 | 223.17 | 24.68 | 145.33 | 27.09 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 302.00 | 19.57 | 302.00 | 19.57 |
February | 454.00 | 20.62 | 216.17 | 19.72 | 216.17 | 19.72 |
March | 512.67 | 21.45 | 115.00 | 20.16 | 115.00 | 20.16 |
April | 435.67 | 22.15 | 46.33 | 21.18 | 35.83 | 20.35 |
May | 337.33 | 22.60 | 44.17 | 24.08 | 0.17 | 20.91 |
June | 231.33 | 23.03 | 85.17 | 24.20 | 0.00 | 0.00 |
July | 165.00 | 23.12 | 193.67 | 24.12 | 0.00 | 0.00 |
August | 180.50 | 22.97 | 231.17 | 24.09 | 0.00 | 0.00 |
September | 334.17 | 22.66 | 64.17 | 24.07 | 0.00 | 0.00 |
October | 491.17 | 21.77 | 46.67 | 19.98 | 46.67 | 19.98 |
November | 489.00 | 20.90 | 152.67 | 19.76 | 152.67 | 19.76 |
December | 497.00 | 20.37 | 284.17 | 19.80 | 284.17 | 19.80 |
Annual Sum or Average | 4629.83 | 21.53 | 1781.33 | 21.31 | 1152.67 | 19.78 |
Minimum of Months | 165.00 | 20.20 | 44.17 | 19.57 | 0.00 | 0.00 |
Maximum of Months | 512.67 | 23.12 | 302.00 | 24.20 | 302.00 | 20.91 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.15 | 299.50 | 19.58 | 299.50 | 19.58 |
February | 454.00 | 20.54 | 204.00 | 19.83 | 204.00 | 19.83 |
March | 511.17 | 21.22 | 90.17 | 20.00 | 90.17 | 20.00 |
April | 397.33 | 21.83 | 54.50 | 22.15 | 27.67 | 20.30 |
May | 354.50 | 22.12 | 81.00 | 24.31 | 1.17 | 22.39 |
June | 254.83 | 22.46 | 162.00 | 24.41 | 0.67 | 25.92 |
July | 225.33 | 22.62 | 218.67 | 24.25 | 6.83 | 26.63 |
August | 238.00 | 22.46 | 217.50 | 24.17 | 5.17 | 26.52 |
September | 341.00 | 22.02 | 96.33 | 24.26 | 0.67 | 26.07 |
October | 486.00 | 21.47 | 43.17 | 20.20 | 41.50 | 20.05 |
November | 489.00 | 20.70 | 148.17 | 19.79 | 148.17 | 19.79 |
December | 497.00 | 20.32 | 275.50 | 19.77 | 275.50 | 19.77 |
Annual Sum or Average | 4750.17 | 21.29 | 1890.50 | 21.68 | 1101.00 | 19.86 |
Minimum of Months | 225.33 | 20.15 | 43.17 | 19.58 | 0.67 | 19.58 |
Maximum of Months | 511.17 | 22.62 | 299.50 | 24.41 | 299.50 | 26.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.67 | 20.52 | 237.17 | 19.61 | 235.00 | 19.57 |
February | 404.17 | 20.97 | 164.67 | 20.55 | 142.50 | 19.97 |
March | 426.50 | 21.42 | 104.17 | 21.14 | 76.83 | 20.11 |
April | 355.00 | 21.84 | 85.67 | 22.92 | 30.00 | 20.34 |
May | 355.50 | 22.20 | 71.17 | 24.35 | 1.50 | 24.63 |
June | 321.67 | 22.50 | 88.67 | 24.38 | 0.33 | 25.65 |
July | 246.67 | 22.62 | 174.67 | 24.25 | 0.50 | 25.95 |
August | 239.67 | 22.49 | 208.17 | 24.19 | 1.67 | 26.00 |
September | 284.00 | 22.27 | 159.33 | 24.27 | 3.83 | 26.86 |
October | 379.83 | 21.65 | 108.83 | 23.49 | 24.83 | 20.20 |
November | 453.50 | 21.04 | 133.67 | 20.76 | 110.67 | 19.95 |
December | 467.50 | 20.65 | 218.00 | 19.92 | 212.17 | 19.80 |
Annual Sum or Average | 4427.67 | 21.53 | 1754.17 | 22.18 | 839.83 | 19.90 |
Minimum of Months | 239.67 | 20.52 | 71.17 | 19.61 | 0.33 | 19.57 |
Maximum of Months | 493.67 | 22.62 | 237.17 | 24.38 | 235.00 | 26.86 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 253.00 | 19.57 | 253.00 | 19.57 |
February | 450.67 | 20.74 | 164.17 | 19.86 | 163.83 | 19.85 |
March | 495.50 | 21.28 | 74.33 | 20.59 | 67.50 | 20.24 |
April | 404.33 | 21.76 | 61.83 | 23.41 | 15.50 | 20.39 |
May | 381.17 | 22.21 | 77.50 | 24.53 | 5.50 | 26.53 |
June | 316.50 | 22.39 | 110.83 | 24.39 | 1.50 | 26.35 |
July | 209.67 | 22.62 | 211.00 | 24.41 | 8.00 | 26.69 |
August | 259.67 | 22.42 | 177.17 | 24.30 | 5.00 | 26.58 |
September | 353.17 | 22.10 | 94.00 | 24.40 | 2.67 | 26.22 |
October | 471.17 | 21.47 | 35.83 | 21.96 | 20.83 | 20.16 |
November | 487.00 | 20.91 | 112.83 | 20.04 | 112.83 | 20.04 |
December | 497.00 | 20.58 | 222.83 | 19.98 | 222.83 | 19.98 |
Annual Sum or Average | 4827.83 | 21.40 | 1595.33 | 21.97 | 879.00 | 20.05 |
Minimum of Months | 209.67 | 20.30 | 35.83 | 19.57 | 1.50 | 19.57 |
Maximum of Months | 502.00 | 22.62 | 253.00 | 24.53 | 253.00 | 26.69 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.45908 | 26.76058 | 0.37634 | 8.36152 |
February | 454.00000 | 24.45153 | 28.12831 | 0.38917 | 8.58545 |
March | 514.00000 | 24.39548 | 28.02241 | 0.38610 | 8.45702 |
April | 485.00000 | 24.49708 | 31.61050 | 0.43633 | 9.51332 |
May | 508.00000 | 24.46792 | 36.37617 | -0.3945 | 9.16519 |
June | 496.00000 | 24.44278 | 38.48679 | -0.3772 | 8.77239 |
July | 497.00000 | 24.58001 | 43.88898 | -0.2955 | 7.95570 |
August | 514.00000 | 24.45102 | 47.87668 | -0.2980 | 7.69764 |
September | 485.00000 | 24.51604 | 43.91775 | -0.3160 | 8.17140 |
October | 502.00000 | 24.55022 | 34.84902 | 0.47466 | 10.32395 |
November | 489.00000 | 24.56319 | 32.82188 | 0.46131 | 10.09027 |
December | 497.00000 | 24.53009 | 27.34836 | 0.40921 | 9.02940 |
Annual Sum or Average | 5943.00000 | 24.49177 | 35.06058 | 0.10132 | 8.84086 |
Minimum of Months | 454.00000 | 24.39548 | 26.76058 | -0.3945 | 7.69764 |
Maximum of Months | 514.00000 | 24.58001 | 47.87668 | 0.47466 | 10.32395 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.22951 | 30.98890 | 0.34679 | 8.14425 |
February | 454.00000 | 24.29928 | 29.86322 | 0.36749 | 8.11010 |
March | 514.00000 | 24.32628 | 29.30831 | 0.38958 | 8.46637 |
April | 485.00000 | 24.33656 | 32.60780 | 0.42805 | 9.15530 |
May | 508.00000 | 24.29128 | 37.78722 | -0.4252 | 9.35409 |
June | 496.00000 | 24.26950 | 40.09398 | -0.3962 | 8.75234 |
July | 497.00000 | 24.29066 | 44.15650 | -0.3523 | 8.01775 |
August | 514.00000 | 24.21339 | 47.11278 | -0.3448 | 7.75776 |
September | 485.00000 | 24.31484 | 45.10078 | -0.3617 | 8.40251 |
October | 502.00000 | 24.38998 | 36.40089 | 0.45236 | 9.67554 |
November | 489.00000 | 24.42920 | 34.44454 | 0.44367 | 9.54017 |
December | 497.00000 | 24.42710 | 29.30760 | 0.40328 | 8.82430 |
Annual Sum or Average | 5943.00000 | 24.31776 | 36.47892 | 0.07622 | 8.68433 |
Minimum of Months | 454.00000 | 24.21339 | 29.30760 | -0.4252 | 7.75776 |
Maximum of Months | 514.00000 | 24.42920 | 47.11278 | 0.45236 | 9.67554 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.18533 | 33.58272 | 0.06450 | 5.88239 |
February | 454.00000 | 23.58806 | 32.22632 | 0.17038 | 6.09352 |
March | 514.00000 | 23.89432 | 31.25831 | 0.25507 | 6.57679 |
April | 485.00000 | 24.00805 | 34.49601 | 0.31343 | 7.32925 |
May | 508.00000 | 24.04201 | 38.82301 | -0.5395 | 11.54313 |
June | 496.00000 | 24.04591 | 41.11122 | -0.5086 | 10.84057 |
July | 497.00000 | 24.06569 | 45.57185 | -0.4699 | 10.15954 |
August | 514.00000 | 24.02671 | 48.21247 | -0.4545 | 9.76810 |
September | 485.00000 | 24.06767 | 46.22456 | -0.4727 | 10.21401 |
October | 502.00000 | 23.99415 | 38.16932 | 0.33109 | 7.57977 |
November | 489.00000 | 23.81979 | 37.25040 | 0.26566 | 6.76753 |
December | 497.00000 | 23.56272 | 32.41870 | 0.16080 | 5.87504 |
Annual Sum or Average | 5943.00000 | 23.86009 | 38.32033 | -0.0764 | 8.23718 |
Minimum of Months | 454.00000 | 23.18533 | 31.25831 | -0.5395 | 5.87504 |
Maximum of Months | 514.00000 | 24.06767 | 48.21247 | 0.33109 | 11.54313 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.59953 | 34.42302 | -0.3387 | 10.62688 |
February | 454.00000 | 22.15477 | 34.66770 | -0.1879 | 8.41745 |
March | 514.00000 | 22.99860 | 33.61059 | 0.02663 | 6.16516 |
April | 485.00000 | 23.46279 | 36.04459 | 0.17519 | 6.43886 |
May | 508.00000 | 23.76258 | 39.69240 | -0.6390 | 14.40708 |
June | 496.00000 | 23.95770 | 41.36198 | -0.5373 | 11.62634 |
July | 497.00000 | 24.00031 | 45.66273 | -0.4846 | 10.45873 |
August | 514.00000 | 23.91906 | 48.49795 | -0.4882 | 10.53647 |
September | 485.00000 | 23.74997 | 47.50316 | -0.5897 | 13.10394 |
October | 502.00000 | 23.21169 | 40.77634 | 0.13136 | 6.24774 |
November | 489.00000 | 22.55403 | 40.80389 | -0.0523 | 6.46418 |
December | 497.00000 | 21.91953 | 35.71717 | -0.2501 | 7.91269 |
Annual Sum or Average | 5943.00000 | 23.11507 | 39.92796 | -0.2708 | 9.37784 |
Minimum of Months | 454.00000 | 21.59953 | 33.61059 | -0.6390 | 6.16516 |
Maximum of Months | 514.00000 | 24.00031 | 48.49795 | 0.17519 | 14.40708 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.82025 | 30.24644 | -0.0316 | 5.81880 |
February | 454.00000 | 23.20248 | 30.39322 | 0.07101 | 5.97784 |
March | 514.00000 | 23.67866 | 29.92343 | 0.19703 | 6.17271 |
April | 485.00000 | 23.96659 | 32.59290 | 0.30716 | 7.26283 |
May | 508.00000 | 24.00986 | 37.39041 | -0.5434 | 11.80394 |
June | 496.00000 | 24.15126 | 39.45174 | -0.4556 | 9.67656 |
July | 497.00000 | 24.22536 | 43.29360 | -0.3868 | 8.39156 |
August | 514.00000 | 24.14783 | 46.45329 | -0.3848 | 8.30153 |
September | 485.00000 | 24.02558 | 44.99169 | -0.4941 | 10.65580 |
October | 502.00000 | 23.81165 | 37.00567 | 0.27927 | 6.98620 |
November | 489.00000 | 23.61630 | 35.35855 | 0.20723 | 6.36438 |
December | 497.00000 | 23.37530 | 30.32660 | 0.10666 | 5.61591 |
Annual Sum or Average | 5943.00000 | 23.75637 | 36.49457 | -0.0960 | 7.76413 |
Minimum of Months | 454.00000 | 22.82025 | 29.92343 | -0.5434 | 5.61591 |
Maximum of Months | 514.00000 | 24.22536 | 46.45329 | 0.30716 | 11.80394 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.81032 | 30.78946 | -0.2312 | 6.64597 |
February | 454.00000 | 22.21449 | 31.14420 | -0.1182 | 6.23742 |
March | 514.00000 | 22.73981 | 30.87379 | 0.02274 | 5.74336 |
April | 485.00000 | 23.22651 | 33.64808 | 0.18758 | 6.65056 |
May | 508.00000 | 23.47595 | 38.13004 | -0.6451 | 15.85675 |
June | 496.00000 | 23.66065 | 40.26453 | -0.5316 | 12.77102 |
July | 497.00000 | 23.61804 | 44.57223 | -0.5057 | 12.19929 |
August | 514.00000 | 23.48592 | 47.99708 | -0.5167 | 12.48566 |
September | 485.00000 | 23.35837 | 46.23261 | -0.6282 | 15.58938 |
October | 502.00000 | 22.93776 | 38.22486 | 0.12248 | 6.29678 |
November | 489.00000 | 22.38491 | 36.94120 | -0.0402 | 5.77207 |
December | 497.00000 | 22.00521 | 31.59701 | -0.1734 | 6.11554 |
Annual Sum or Average | 5943.00000 | 22.91520 | 37.57833 | -0.2565 | 9.38916 |
Minimum of Months | 454.00000 | 21.81032 | 30.78946 | -0.6451 | 5.74336 |
Maximum of Months | 514.00000 | 23.66065 | 47.99708 | 0.18758 | 15.85675 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.08671 | 30.56244 | -0.1746 | 7.08899 |
February | 454.00000 | 22.74620 | 30.33381 | 0.00795 | 7.12703 |
March | 514.00000 | 23.18895 | 30.07440 | 0.13315 | 6.55239 |
April | 485.00000 | 23.55274 | 32.97883 | 0.25544 | 7.32711 |
May | 508.00000 | 23.60767 | 37.91972 | -0.6313 | 15.01872 |
June | 496.00000 | 23.75352 | 40.23396 | -0.5513 | 12.43417 |
July | 497.00000 | 23.87255 | 43.97350 | -0.4597 | 10.35455 |
August | 514.00000 | 23.83768 | 47.05775 | -0.4237 | 9.82189 |
September | 485.00000 | 23.75053 | 45.14551 | -0.4947 | 12.19759 |
October | 502.00000 | 23.46865 | 37.06391 | 0.25642 | 7.80429 |
November | 489.00000 | 22.91178 | 36.01172 | 0.07740 | 6.65881 |
December | 497.00000 | 22.55358 | 30.81324 | -0.0468 | 6.50602 |
Annual Sum or Average | 5943.00000 | 23.28141 | 36.89285 | -0.1731 | 9.09148 |
Minimum of Months | 454.00000 | 22.08671 | 30.07440 | -0.6313 | 6.50602 |
Maximum of Months | 514.00000 | 23.87255 | 47.05775 | 0.25642 | 15.01872 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.42181 | 29.58736 | -0.0672 | 5.66446 |
February | 454.00000 | 23.27837 | 29.11189 | 0.15727 | 6.54769 |
March | 514.00000 | 23.99363 | 28.40926 | 0.35451 | 8.26384 |
April | 485.00000 | 24.38085 | 31.11205 | 0.51488 | 11.31807 |
May | 508.00000 | 23.94689 | 36.92015 | -0.4426 | 11.14243 |
June | 496.00000 | 24.19244 | 38.84548 | -0.3020 | 8.21429 |
July | 497.00000 | 24.45012 | 42.17410 | -0.1306 | 6.87716 |
August | 514.00000 | 24.36103 | 45.28101 | -0.1207 | 6.45887 |
September | 485.00000 | 23.88767 | 44.64014 | -0.4073 | 10.47630 |
October | 502.00000 | 23.88750 | 35.96759 | 0.37352 | 8.79544 |
November | 489.00000 | 23.91110 | 33.68262 | 0.34499 | 8.36625 |
December | 497.00000 | 23.98288 | 28.04234 | 0.32068 | 7.83400 |
Annual Sum or Average | 5943.00000 | 23.89507 | 35.35809 | 0.04813 | 8.33021 |
Minimum of Months | 454.00000 | 22.42181 | 28.04234 | -0.4426 | 5.66446 |
Maximum of Months | 514.00000 | 24.45012 | 45.28101 | 0.51488 | 11.31807 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.87181 | 33.42595 | -0.5121 | 12.14608 |
February | 454.00000 | 21.36332 | 33.49429 | -0.3710 | 9.83162 |
March | 514.00000 | 22.26312 | 33.16850 | -0.1449 | 6.52433 |
April | 485.00000 | 22.92020 | 35.43822 | 0.04263 | 6.09805 |
May | 508.00000 | 23.44698 | 39.03451 | -0.7512 | 18.20484 |
June | 496.00000 | 23.75185 | 40.86866 | -0.6185 | 13.72537 |
July | 497.00000 | 23.87571 | 44.57066 | -0.5405 | 11.63833 |
August | 514.00000 | 23.81555 | 47.94010 | -0.5353 | 11.62367 |
September | 485.00000 | 23.49485 | 46.83636 | -0.6912 | 16.00789 |
October | 502.00000 | 22.63772 | 40.23017 | -0.0063 | 5.92185 |
November | 489.00000 | 21.78519 | 39.48350 | -0.2306 | 7.21242 |
December | 497.00000 | 21.16443 | 34.42649 | -0.4251 | 9.55901 |
Annual Sum or Average | 5943.00000 | 22.62601 | 39.11226 | -0.3995 | 10.71864 |
Minimum of Months | 454.00000 | 20.87181 | 33.16850 | -0.7512 | 5.92185 |
Maximum of Months | 514.00000 | 23.87571 | 47.94010 | 0.04263 | 18.20484 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.54038 | 32.36425 | -0.5881 | 13.49683 |
February | 385.00000 | 21.01197 | 32.53348 | -0.4387 | 10.04353 |
March | 433.00000 | 21.61532 | 32.75511 | -0.2597 | 7.24162 |
April | 410.00000 | 22.46416 | 34.83341 | -0.0126 | 6.57115 |
May | 430.00000 | 22.82205 | 39.18590 | -0.8796 | 24.41979 |
June | 418.00000 | 23.27455 | 41.00136 | -0.6811 | 17.89912 |
July | 422.00000 | 23.38114 | 44.85737 | -0.6138 | 15.88738 |
August | 433.00000 | 23.28414 | 48.36140 | -0.6104 | 15.79101 |
September | 410.00000 | 22.78163 | 47.52357 | -0.8398 | 23.09476 |
October | 427.00000 | 21.94270 | 40.33680 | -0.1287 | 6.51052 |
November | 417.00000 | 21.17390 | 39.19950 | -0.3574 | 8.27332 |
December | 422.00000 | 20.80358 | 33.48618 | -0.5051 | 10.74965 |
Annual Sum or Average | 5034.00000 | 22.09770 | 38.90628 | -0.4937 | 13.35304 |
Minimum of Months | 385.00000 | 20.54038 | 32.36425 | -0.8796 | 6.51052 |
Maximum of Months | 433.00000 | 23.38114 | 48.36140 | -0.0126 | 24.41979 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.26932 | 32.01930 | -0.3901 | 10.53557 |
February | 454.00000 | 22.00894 | 31.67792 | -0.1736 | 8.60557 |
March | 514.00000 | 22.46069 | 31.76838 | -0.0409 | 7.12029 |
April | 485.00000 | 22.94078 | 34.44163 | 0.10067 | 7.11634 |
May | 508.00000 | 23.14967 | 39.04642 | -0.7893 | 20.62746 |
June | 496.00000 | 23.29990 | 41.46661 | -0.7152 | 17.54225 |
July | 497.00000 | 23.53359 | 45.01691 | -0.5936 | 14.11830 |
August | 514.00000 | 23.55625 | 48.05672 | -0.5384 | 13.05987 |
September | 485.00000 | 23.44066 | 46.03515 | -0.6002 | 15.69243 |
October | 502.00000 | 22.91792 | 38.50544 | 0.12445 | 7.73796 |
November | 489.00000 | 22.00201 | 38.18667 | -0.1452 | 7.63358 |
December | 497.00000 | 21.60246 | 32.77288 | -0.2901 | 8.90558 |
Annual Sum or Average | 5943.00000 | 22.68722 | 38.29453 | -0.3396 | 11.58851 |
Minimum of Months | 454.00000 | 21.26932 | 31.67792 | -0.7893 | 7.11634 |
Maximum of Months | 514.00000 | 23.55625 | 48.05672 | 0.12445 | 20.62746 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.77861 | 32.51800 | -0.5118 | 11.40348 |
February | 454.00000 | 21.22544 | 32.77905 | -0.3688 | 9.21938 |
March | 514.00000 | 21.85175 | 32.69541 | -0.1906 | 6.81039 |
April | 485.00000 | 22.59741 | 35.02701 | 0.03106 | 6.72855 |
May | 508.00000 | 23.02071 | 39.15959 | -0.7893 | 21.34081 |
June | 496.00000 | 23.21499 | 41.41363 | -0.6880 | 17.33013 |
July | 497.00000 | 23.65838 | 44.48928 | -0.4835 | 12.55523 |
August | 514.00000 | 23.41400 | 48.34672 | -0.5425 | 13.72524 |
September | 485.00000 | 23.02709 | 47.12633 | -0.7350 | 19.29045 |
October | 502.00000 | 22.13819 | 40.16136 | -0.0701 | 6.30954 |
November | 489.00000 | 21.39864 | 39.22998 | -0.2874 | 7.44922 |
December | 497.00000 | 21.05238 | 33.49929 | -0.4250 | 9.21337 |
Annual Sum or Average | 5943.00000 | 22.28999 | 38.91044 | -0.4227 | 11.80390 |
Minimum of Months | 454.00000 | 20.77861 | 32.51800 | -0.7893 | 6.30954 |
Maximum of Months | 514.00000 | 23.65838 | 48.34672 | 0.03106 | 21.34081 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19872 | 34.52964 | -0.7166 | 18.86289 |
February | 454.00000 | 20.61667 | 34.88830 | -0.5849 | 15.37369 |
March | 514.00000 | 21.44910 | 34.74693 | -0.3534 | 9.43085 |
April | 485.00000 | 22.32328 | 36.68711 | -0.1038 | 7.13742 |
May | 508.00000 | 23.06105 | 39.93883 | -0.8789 | 23.75984 |
June | 496.00000 | 23.56893 | 41.26670 | -0.6745 | 15.97333 |
July | 497.00000 | 23.73590 | 44.81918 | -0.5781 | 13.05316 |
August | 514.00000 | 23.64625 | 48.37629 | -0.5869 | 13.41861 |
September | 485.00000 | 23.06679 | 48.09071 | -0.8364 | 21.63714 |
October | 502.00000 | 21.80538 | 42.29036 | -0.2128 | 7.43601 |
November | 489.00000 | 20.90011 | 41.49998 | -0.4694 | 11.54120 |
December | 497.00000 | 20.37354 | 36.11728 | -0.6592 | 16.09044 |
Annual Sum or Average | 5943.00000 | 22.07420 | 40.30315 | -0.5548 | 14.47127 |
Minimum of Months | 454.00000 | 20.19872 | 34.52964 | -0.8789 | 7.13742 |
Maximum of Months | 514.00000 | 23.73590 | 48.37629 | -0.1038 | 23.75984 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.15234 | 33.63294 | -0.7253 | 18.87708 |
February | 454.00000 | 20.54440 | 34.13835 | -0.5850 | 14.45815 |
March | 514.00000 | 21.22902 | 34.13347 | -0.3712 | 9.35644 |
April | 485.00000 | 22.19813 | 36.00477 | -0.0792 | 7.28156 |
May | 508.00000 | 22.69189 | 40.00081 | -0.9181 | 26.34168 |
June | 496.00000 | 23.28085 | 41.20482 | -0.6677 | 17.69756 |
July | 497.00000 | 23.38360 | 45.18999 | -0.5946 | 15.45246 |
August | 514.00000 | 23.25991 | 48.68735 | -0.6044 | 15.82507 |
September | 485.00000 | 22.60497 | 48.41823 | -0.8979 | 25.68306 |
October | 502.00000 | 21.53477 | 41.82373 | -0.2408 | 7.63348 |
November | 489.00000 | 20.69406 | 40.99396 | -0.5066 | 11.77675 |
December | 497.00000 | 20.32528 | 35.24842 | -0.6668 | 16.13226 |
Annual Sum or Average | 5943.00000 | 21.83550 | 39.99244 | -0.5718 | 15.55097 |
Minimum of Months | 454.00000 | 20.15234 | 33.63294 | -0.9181 | 7.28156 |
Maximum of Months | 514.00000 | 23.38360 | 48.68735 | -0.0792 | 26.34168 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.57237 | 33.08667 | -0.5975 | 16.00149 |
February | 454.00000 | 21.31165 | 32.91415 | -0.3762 | 11.94497 |
March | 514.00000 | 21.84588 | 33.06959 | -0.2088 | 9.01196 |
April | 485.00000 | 22.43249 | 35.54621 | -0.0277 | 7.78782 |
May | 508.00000 | 22.74516 | 39.96779 | -0.9214 | 26.36906 |
June | 496.00000 | 23.04441 | 41.98729 | -0.7907 | 20.73828 |
July | 497.00000 | 23.33213 | 45.42836 | -0.6478 | 16.26262 |
August | 514.00000 | 23.30583 | 48.69091 | -0.6125 | 15.76815 |
September | 485.00000 | 23.02239 | 47.22665 | -0.7416 | 21.12399 |
October | 502.00000 | 22.28007 | 40.13756 | -0.0426 | 8.13999 |
November | 489.00000 | 21.28627 | 39.81728 | -0.3497 | 10.29788 |
December | 497.00000 | 20.85964 | 34.38348 | -0.5118 | 13.75649 |
Annual Sum or Average | 5943.00000 | 22.17699 | 39.39724 | -0.4871 | 14.79692 |
Minimum of Months | 454.00000 | 20.57237 | 32.91415 | -0.9214 | 7.78782 |
Maximum of Months | 514.00000 | 23.33213 | 48.69091 | -0.0277 | 26.36906 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29609 | 33.27389 | -0.6671 | 16.91184 |
February | 454.00000 | 20.75532 | 33.65006 | -0.5156 | 12.98045 |
March | 514.00000 | 21.36290 | 33.72625 | -0.3269 | 8.73185 |
April | 485.00000 | 22.15427 | 35.99240 | -0.0802 | 7.40615 |
May | 508.00000 | 22.66907 | 39.95875 | -0.9036 | 26.27323 |
June | 496.00000 | 22.98632 | 41.90203 | -0.7551 | 20.16263 |
July | 497.00000 | 23.46129 | 44.90737 | -0.5361 | 14.45708 |
August | 514.00000 | 23.17025 | 48.96945 | -0.6141 | 16.29259 |
September | 485.00000 | 22.64148 | 48.22459 | -0.8634 | 24.44725 |
October | 502.00000 | 21.62008 | 41.50915 | -0.2077 | 7.24951 |
November | 489.00000 | 20.91882 | 40.38473 | -0.4354 | 10.06356 |
December | 497.00000 | 20.57768 | 34.59962 | -0.5822 | 13.37325 |
Annual Sum or Average | 5943.00000 | 21.89375 | 39.79717 | -0.5413 | 14.88033 |
Minimum of Months | 454.00000 | 20.29609 | 33.27389 | -0.9036 | 7.24951 |
Maximum of Months | 514.00000 | 23.46129 | 48.96945 | -0.0802 | 26.27323 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.228888E+09 | 8057.69 | 11-JAN-16:00 | 31.60 | 0.784771E+09 | 0.00 | 0.101366E+10 | 0.15 | 3.49 | 07-JAN-06:40 | 0.00 | 0.00 |
February | 0.180236E+10 | 67762.16 | 27-FEB-15:00 | 38.27 | 0.106883E+11 | 0.00 | 0.124907E+11 | 0.23 | 7.55 | 27-FEB-15:00 | 0.00 | 0.00 |
March | 0.383592E+10 | 55210.15 | 18-MAR-14:00 | 57.52 | 0.187007E+11 | 0.00 | 0.225366E+11 | 0.31 | 7.29 | 18-MAR-14:00 | 0.00 | 0.00 |
April | 0.147703E+11 | 87141.85 | 26-APR-15:40 | 137.37 | 0.902668E+11 | 0.00 | 0.105037E+12 | 0.93 | 7.58 | 27-APR-10:30 | 0.00 | 0.00 |
May | 0.305035E+11 | 85627.35 | 04-MAY-14:40 | 237.08 | 0.187998E+12 | 0.00 | 0.218502E+12 | 1.68 | 7.58 | 15-MAY-10:00 | 0.00 | 0.00 |
June | 0.499079E+11 | 87775.02 | 22-JUN-15:40 | 343.91 | 0.325140E+12 | 0.00 | 0.375048E+12 | 2.73 | 7.61 | 19-JUN-15:50 | 0.00 | 0.00 |
July | 0.744705E+11 | 104873.41 | 31-JUL-16:00 | 463.93 | 0.498747E+12 | 0.00 | 0.573217E+12 | 3.66 | 7.62 | 11-JUL-10:00 | 0.00 | 0.00 |
August | 0.882228E+11 | 119935.41 | 29-AUG-14:40 | 511.59 | 0.593360E+12 | 0.00 | 0.681583E+12 | 4.05 | 7.71 | 30-AUG-05:05 | 0.00 | 0.00 |
September | 0.438964E+11 | 93397.67 | 14-SEP-13:00 | 299.14 | 0.280895E+12 | 0.00 | 0.324792E+12 | 2.32 | 7.65 | 14-SEP-09:10 | 0.00 | 0.00 |
October | 0.110272E+11 | 68384.27 | 04-OCT-11:50 | 121.56 | 0.607666E+11 | 0.00 | 0.717938E+11 | 0.74 | 7.60 | 03-OCT-15:00 | 0.00 | 0.00 |
November | 0.207350E+10 | 69125.21 | 04-NOV-14:50 | 57.75 | 0.121229E+11 | 0.00 | 0.141964E+11 | 0.31 | 7.54 | 04-NOV-12:50 | 0.00 | 0.00 |
December | 0.202609E+09 | 8164.89 | 16-DEC-06:03 | 30.04 | 0.694770E+09 | 0.00 | 0.897379E+09 | 0.14 | 3.49 | 26-DEC-07:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.320942E+12 | 2329.77 | 0.208016E+13 | 0.240111E+13 | 1.45 | |||||||
Minimum of Months | 0.202609E+09 | 8057.69 | 30.04 | 0.694770E+09 | 0.00 | 0.897379E+09 | 0.14 | 3.49 | 0.00 | 0.00 | ||
Maximum of Months | 0.882228E+11 | 119935.41 | 511.59 | 0.593360E+12 | 0.00 | 0.681583E+12 | 4.05 | 7.71 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.198836E+10 | 87141.85 | 26-APR-15:40 | 7.33 | 0.145576E+11 | 0.00 | 0.165459E+11 | 0.07 | 7.54 | 27-APR-11:20 | 0.00 | 0.00 |
May | 0.207248E+10 | 85627.35 | 04-MAY-14:40 | 7.83 | 0.153260E+11 | 0.00 | 0.173985E+11 | 0.08 | 7.48 | 04-MAY-14:30 | 0.00 | 0.00 |
June | 0.412421E+10 | 87775.02 | 22-JUN-15:40 | 15.33 | 0.306437E+11 | 0.00 | 0.347679E+11 | 0.16 | 7.49 | 22-JUN-15:20 | 0.00 | 0.00 |
July | 0.147115E+11 | 104873.41 | 31-JUL-16:00 | 52.29 | 0.105391E+12 | 0.00 | 0.120103E+12 | 0.51 | 7.55 | 11-JUL-14:00 | 0.00 | 0.00 |
August | 0.322462E+11 | 119935.41 | 29-AUG-14:40 | 106.50 | 0.225733E+12 | 0.00 | 0.257980E+12 | 1.01 | 7.56 | 08-AUG-08:20 | 0.00 | 0.00 |
September | 0.746268E+10 | 93397.67 | 14-SEP-13:00 | 27.00 | 0.549142E+11 | 0.00 | 0.623769E+11 | 0.28 | 7.62 | 14-SEP-10:40 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.626055E+11 | 216.29 | 0.446566E+12 | 0.509171E+12 | 0.18 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.322462E+11 | 119935.41 | 106.50 | 0.225733E+12 | 0.00 | 0.257980E+12 | 1.01 | 7.62 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.118287E+11 | 744.00 | 26312.49 | 10-JAN-22:25 | 544064.00 | 13-JAN-00:20 | 21.60 | 18.33 | 13.88 |
February | 0.263874E+11 | 672.00 | 49248.27 | 27-FEB-11:50 | 573276.46 | 14-FEB-22:41 | 24.47 | 18.36 | 13.88 |
March | 0.606076E+11 | 744.00 | 49248.27 | 08-MAR-10:50 | 591804.06 | 21-MAR-21:23 | 27.39 | 18.41 | 13.88 |
April | 0.936739E+11 | 720.00 | 49248.27 | 01-APR-09:00 | 641646.27 | 27-APR-18:30 | 31.06 | 19.17 | 13.88 |
May | 0.510521E+11 | 744.00 | 49248.27 | 02-MAY-13:00 | 445274.93 | 17-MAY-22:35 | 22.46 | 18.88 | 13.88 |
June | 0.991869E+11 | 720.00 | 49248.27 | 01-JUN-11:20 | 343593.49 | 28-JUN-17:10 | 26.25 | 19.82 | 13.88 |
July | 0.126615E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 510038.43 | 30-JUL-18:21 | 31.16 | 21.81 | 13.88 |
August | 0.130651E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 659437.85 | 10-AUG-19:45 | 36.22 | 23.94 | 13.88 |
September | 0.689121E+11 | 720.00 | 49248.27 | 01-SEP-00:03 | 391200.75 | 01-SEP-00:03 | 22.70 | 19.09 | 13.88 |
October | 0.620160E+11 | 744.00 | 49248.27 | 01-OCT-08:30 | 574017.86 | 12-OCT-21:21 | 24.76 | 18.49 | 13.88 |
November | 0.574317E+11 | 720.00 | 49248.27 | 03-NOV-19:30 | 590651.33 | 17-NOV-05:30 | 27.34 | 18.40 | 13.88 |
December | 0.596529E+11 | 744.00 | 47970.39 | 14-DEC-12:00 | 606872.58 | 29-DEC-22:50 | 29.98 | 18.33 | 13.88 |
Annual Sum or Average | 0.848015E+12 | 8760.00 | 27.14 | 19.43 | 13.88 | ||||
Minimum of Months | 0.118287E+11 | 672.00 | 26312.49 | 343593.49 | 21.60 | 18.33 | 13.88 | ||
Maximum of Months | 0.130651E+12 | 744.00 | 49248.27 | 659437.85 | 36.22 | 23.94 | 13.88 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 161948.94 | 20-JAN-06:50 | 21.02 | 21.01 | 0.36 |
February | 14864632.10 | 7.67 | 1085.00 | 27-FEB-15:10 | 585141.03 | 27-FEB-15:10 | 21.07 | 21.04 | 1.08 |
March | 16491532.80 | 26.03 | 408.15 | 18-MAR-14:10 | 467081.86 | 18-MAR-14:10 | 21.10 | 21.05 | 2.02 |
April | 0.367531E+09 | 79.03 | 14845.32 | 27-APR-13:50 | 742181.78 | 26-APR-15:40 | 21.29 | 21.04 | 6.09 |
May | 0.747784E+09 | 175.45 | 14845.32 | 05-MAY-12:40 | 739535.98 | 04-MAY-14:40 | 21.73 | 21.24 | 11.99 |
June | 0.910981E+09 | 277.92 | 14845.32 | 28-JUN-16:30 | 750926.26 | 22-JUN-15:40 | 22.23 | 21.38 | 18.69 |
July | 0.457741E+10 | 376.04 | 14845.32 | 07-JUL-12:40 | 800941.08 | 31-JUL-16:00 | 22.57 | 21.29 | 24.61 |
August | 0.768118E+10 | 415.01 | 14845.32 | 07-AUG-10:10 | 887719.98 | 29-AUG-14:40 | 22.88 | 21.37 | 27.31 |
September | 0.213749E+10 | 245.27 | 14845.32 | 11-SEP-15:10 | 762473.51 | 14-SEP-13:10 | 22.06 | 21.32 | 16.38 |
October | 68246646.19 | 64.89 | 981.39 | 04-OCT-15:00 | 610664.70 | 04-OCT-15:00 | 21.24 | 21.08 | 5.43 |
November | 44748157.04 | 8.17 | 2660.61 | 04-NOV-13:20 | 574026.85 | 04-NOV-15:20 | 21.13 | 21.09 | 1.40 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 161476.42 | 26-DEC-06:15 | 21.01 | 21.01 | 0.26 |
Annual Sum or Average | 0.165667E+11 | 1675.49 | 21.62 | 21.16 | 9.69 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 161476.42 | 21.01 | 21.01 | 0.26 | ||
Maximum of Months | 0.768118E+10 | 415.01 | 14845.32 | 887719.98 | 22.88 | 21.38 | 27.31 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.02 | 21.02 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.07 | 21.07 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.10 | 21.10 | 0.00 |
April | 0.170395E+09 | 7.33 | 14845.32 | 27-APR-13:50 | 742181.78 | 26-APR-15:40 | 21.29 | 21.25 | 0.43 |
May | 0.203578E+09 | 7.83 | 14845.32 | 05-MAY-12:40 | 739535.98 | 04-MAY-14:40 | 21.73 | 21.69 | 0.44 |
June | 0.136396E+09 | 15.33 | 14845.32 | 28-JUN-16:40 | 750926.26 | 22-JUN-15:40 | 22.23 | 22.15 | 0.89 |
July | 0.223438E+10 | 52.40 | 14845.32 | 07-JUL-12:40 | 800941.08 | 31-JUL-16:00 | 22.57 | 22.31 | 2.96 |
August | 0.513516E+10 | 106.95 | 14845.32 | 07-AUG-10:20 | 887719.98 | 29-AUG-14:40 | 22.88 | 22.31 | 6.04 |
September | 0.116419E+10 | 27.00 | 14845.32 | 11-SEP-15:10 | 762473.51 | 14-SEP-13:10 | 22.06 | 21.92 | 1.57 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.24 | 21.24 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 01-NOV-00:02 | 21.13 | 21.13 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.01 | 21.01 | 0.00 |
Annual Sum or Average | 0.904411E+10 | 216.85 | 21.62 | 21.52 | 1.04 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 | 21.01 | 0.00 | ||
Maximum of Months | 0.513516E+10 | 106.95 | 14845.32 | 887719.98 | 22.88 | 22.31 | 6.04 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.197213E+12 | 0.00 | 446.25 | 1219872.59 | 02-JAN-06:01 | 0.00 | 69.45 | 75.14 | 1.78 | 0.00 | 0.05 | 0.83 | 02-JAN-06:01 |
February | 0.107122E+12 | 0.00 | 334.99 | 668405.60 | 21-FEB-06:03 | 0.00 | 65.43 | 72.28 | 0.80 | 0.00 | 0.03 | 0.46 | 21-FEB-06:03 |
March | 0.288173E+11 | 0.00 | 260.92 | 468513.82 | 13-MAR-05:01 | 0.00 | 69.40 | 73.29 | 0.26 | 0.00 | 0.01 | 0.32 | 13-MAR-05:01 |
April | 0.102671E+11 | 0.00 | 131.95 | 647685.24 | 18-APR-03:47 | 0.00 | 64.60 | 67.74 | 0.05 | 0.00 | 0.00 | 0.44 | 18-APR-03:47 |
May | 0.189251E+10 | 0.00 | 43.61 | 280391.75 | 02-MAY-03:47 | 0.00 | 77.82 | 77.97 | 0.15 | 0.00 | 0.00 | 0.19 | 02-MAY-03:47 |
June | 0.125401E+10 | 0.00 | 14.68 | 350948.59 | 15-JUN-03:50 | 0.00 | 71.80 | 71.96 | 0.02 | 0.00 | 0.00 | 0.24 | 15-JUN-03:50 |
July | 0.725966E+09 | 0.00 | 0.94 | 215661.06 | 20-JUL-03:45 | 0.00 | 70.63 | 70.64 | 0.01 | 0.00 | 0.00 | 0.15 | 20-JUL-03:45 |
August | 0.621547E+09 | 0.00 | 5.92 | 219549.77 | 19-AUG-03:45 | 0.00 | 70.53 | 70.60 | 0.01 | 0.00 | 0.00 | 0.15 | 19-AUG-03:45 |
September | 0.230780E+10 | 0.00 | 55.71 | 266040.42 | 20-SEP-03:47 | 0.00 | 72.06 | 72.60 | 0.05 | 0.00 | 0.00 | 0.18 | 20-SEP-03:47 |
October | 0.112085E+11 | 0.00 | 194.33 | 677655.56 | 22-OCT-22:15 | 0.00 | 72.60 | 74.45 | 0.20 | 0.00 | 0.00 | 0.46 | 22-OCT-22:15 |
November | 0.601961E+11 | 0.00 | 336.60 | 800001.65 | 27-NOV-06:02 | 0.00 | 59.55 | 67.38 | 0.35 | 0.00 | 0.02 | 0.55 | 27-NOV-06:02 |
December | 0.132781E+12 | 0.00 | 409.73 | 1213056.84 | 18-DEC-05:01 | 0.00 | 50.75 | 66.11 | 0.42 | 0.00 | 0.03 | 0.83 | 18-DEC-05:01 |
Annual Sum or Average | 0.554407E+12 | 2235.63 | 67.91 | 71.70 | 0.34 | 0.00 | 0.01 | ||||||
Minimum of Months | 0.621547E+09 | 0.00 | 0.94 | 215661.06 | 0.00 | 50.75 | 66.11 | 0.01 | 0.00 | 0.00 | 0.15 | ||
Maximum of Months | 0.197213E+12 | 0.00 | 446.25 | 1219872.59 | 0.00 | 77.82 | 77.97 | 1.78 | 0.00 | 0.05 | 0.83 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.60 | 21.60 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.47 | 24.47 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.39 | 27.39 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.06 | 31.06 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 22.46 | 22.46 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 26.25 | 26.25 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 31.16 | 31.16 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 36.22 | 36.22 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 22.70 | 22.70 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.76 | 24.76 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 27.34 | 27.34 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.98 | 29.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 27.14 | 27.14 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.60 | 21.60 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.22 | 36.22 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 2145849.21 | 0.00 | 0.10 | 2145849.21 | 0.00 | 0.00 | 0.00 | 0.00 | 9188.43 | 11-JAN-05:01 | 9188.43 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 |
February | 0.489577E+09 | 0.00 | 7.31 | 0.483094E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 37353.58 | 24-FEB-05:01 | 32034.67 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.147244E+09 | 0.00 | 7.26 | 0.138764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26207.36 | 10-MAR-04:01 | 17195.83 | 09-MAR-04:51 | 0.00 | 0.00 | 0.00 |
April | 0.399442E+10 | 0.00 | 46.99 | 0.398979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58172.14 | 27-APR-15:40 | 58172.14 | 27-APR-15:40 | 0.00 | 0.00 | 0.00 |
May | 0.762963E+10 | 0.00 | 103.99 | 0.761592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56226.45 | 15-MAY-16:00 | 56226.45 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.159732E+11 | 0.00 | 203.67 | 0.158858E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 59854.43 | 12-JUN-00:01 | 56252.88 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.291708E+11 | 0.00 | 280.20 | 0.289218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75979.47 | 31-JUL-00:01 | 69737.50 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.405719E+11 | 0.00 | 315.75 | 0.400087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93941.93 | 13-AUG-21:40 | 78121.83 | 13-AUG-21:42 | 0.00 | 0.00 | 0.00 |
September | 0.126964E+11 | 0.00 | 167.71 | 0.124581E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 58203.96 | 01-SEP-03:01 | 56351.46 | 11-SEP-15:00 | 0.00 | 0.00 | 0.00 |
October | 0.195552E+10 | 0.00 | 42.22 | 0.192614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49802.94 | 09-OCT-14:21 | 49802.94 | 09-OCT-14:21 | 0.00 | 0.00 | 0.00 |
November | 0.327782E+09 | 0.00 | 6.99 | 0.313402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 39621.72 | 04-NOV-03:01 | 23241.88 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 |
December | 10253593.82 | 0.00 | 0.41 | 10253593.82 | 0.00 | 0.00 | 0.00 | 0.00 | 11613.11 | 16-DEC-06:03 | 11613.11 | 16-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112969E+12 | 1182.59 | 0.111754E+12 | ||||||||||||
Minimum of Months | 2145849.21 | 0.00 | 0.10 | 2145849.21 | 0.00 | 0.00 | 0.00 | 0.00 | 9188.43 | 9188.43 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.405719E+11 | 0.00 | 315.75 | 0.400087E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93941.93 | 78121.83 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 27656625.38 | 0.00 | 2.92 | 27656625.38 | 0.00 | 0.00 | 0.00 | 0.00 | 3679.21 | 11-JAN-14:00 | 3679.21 | 11-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.106027E+10 | 0.00 | 19.61 | 0.106027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56936.63 | 27-FEB-15:00 | 56936.63 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.183859E+10 | 0.00 | 38.41 | 0.183859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34889.16 | 18-MAR-16:00 | 34889.16 | 18-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.114805E+11 | 0.00 | 119.26 | 0.114520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 107787.79 | 27-APR-15:00 | 102427.09 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.193883E+11 | 0.00 | 217.11 | 0.189340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 88732.86 | 05-MAY-15:40 | 83542.07 | 15-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.351596E+11 | 0.00 | 326.84 | 0.349537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 94981.78 | 28-JUN-16:00 | 94981.78 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.635157E+11 | 0.00 | 444.60 | 0.591122E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 124368.40 | 31-JUL-10:30 | 108736.36 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.861724E+11 | 0.00 | 496.84 | 0.774856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133692.24 | 29-AUG-14:30 | 117075.12 | 29-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.309195E+11 | 0.00 | 280.60 | 0.282549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109834.35 | 14-SEP-13:00 | 89238.45 | 12-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.629104E+10 | 0.00 | 103.56 | 0.628759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72160.95 | 04-OCT-15:00 | 72160.95 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.106392E+10 | 0.00 | 19.08 | 0.977443E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47667.50 | 04-NOV-13:10 | 41677.17 | 04-NOV-14:20 | 0.00 | 0.00 | 0.00 |
December | 3312.75 | 0.00 | 1.77 | 3312.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 26-DEC-06:30 | 0.77 | 26-DEC-06:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256917E+12 | 2070.61 | 0.240384E+12 | ||||||||||||
Minimum of Months | 3312.75 | 0.00 | 1.77 | 3312.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 | 0.77 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.861724E+11 | 0.00 | 496.84 | 0.774856E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 133692.24 | 117075.12 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.198139E+09 | 0.00 | 30.30 | 0.198139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25338.57 | 11-JAN-16:00 | 25338.57 | 11-JAN-16:00 | 0.00 | 0.00 | 0.00 |
February | 0.772822E+10 | 0.00 | 33.85 | 0.772822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 408579.69 | 27-FEB-15:00 | 408579.69 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.142188E+11 | 0.00 | 54.04 | 0.142188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 336579.52 | 18-MAR-14:00 | 336579.52 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.851643E+11 | 0.00 | 113.78 | 0.849892E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 889676.70 | 27-APR-15:00 | 854271.82 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.170308E+12 | 0.00 | 220.07 | 0.166092E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 798589.02 | 05-MAY-15:50 | 743245.15 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.292298E+12 | 0.00 | 313.35 | 0.290984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 832115.05 | 28-JUN-16:00 | 832115.05 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.506262E+12 | 0.00 | 386.67 | 0.470939E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1045655.34 | 31-JUL-16:00 | 898393.58 | 31-JUL-16:00 | 0.00 | 0.00 | 0.00 |
August | 0.667121E+12 | 0.00 | 411.24 | 0.599289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1164483.15 | 29-AUG-14:40 | 1025657.58 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.277063E+12 | 0.00 | 275.65 | 0.252266E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1040814.12 | 14-SEP-13:00 | 812783.64 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.497579E+11 | 0.00 | 107.65 | 0.497579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 635590.83 | 04-OCT-15:00 | 635590.83 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.948525E+10 | 0.00 | 52.54 | 0.860043E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 470334.52 | 04-NOV-13:20 | 408630.88 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 75935.95 | 0.00 | 29.11 | 75935.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 26-DEC-07:00 | 2.41 | 26-DEC-07:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207961E+13 | 2028.26 | 0.194506E+13 | ||||||||||||
Minimum of Months | 75935.95 | 0.00 | 29.11 | 75935.95 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | 2.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.667121E+12 | 0.00 | 411.24 | 0.599289E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1164483.15 | 1025657.58 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 14921378.95 | 0.00 | 3.37 | 14921378.95 | 0.00 | 0.00 | 0.00 | 0.00 | 1904.91 | 11-JAN-15:30 | 1904.91 | 11-JAN-15:30 | 0.00 | 0.00 | 0.00 |
February | 0.686519E+09 | 0.00 | 16.50 | 0.686519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 35487.60 | 27-FEB-15:00 | 35487.60 | 27-FEB-15:00 | 0.00 | 0.00 | 0.00 |
March | 0.132873E+10 | 0.00 | 36.00 | 0.132873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33162.61 | 18-MAR-14:00 | 33162.61 | 18-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.883481E+10 | 0.00 | 95.71 | 0.880875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 108004.98 | 27-APR-15:00 | 102828.43 | 27-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.177016E+11 | 0.00 | 206.79 | 0.172671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 87014.26 | 05-MAY-16:00 | 86184.56 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.312912E+11 | 0.00 | 302.54 | 0.311516E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 103251.17 | 28-JUN-16:00 | 103251.17 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 |
July | 0.547946E+11 | 0.00 | 380.85 | 0.508866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132019.98 | 27-JUL-15:40 | 112863.37 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 |
August | 0.710279E+11 | 0.00 | 402.88 | 0.639897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132761.33 | 29-AUG-14:40 | 122729.94 | 10-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.278436E+11 | 0.00 | 263.59 | 0.253196E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110573.75 | 14-SEP-13:00 | 88613.05 | 14-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.457706E+10 | 0.00 | 91.08 | 0.457706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63512.34 | 04-OCT-15:00 | 63512.34 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.933283E+09 | 0.00 | 15.37 | 0.848375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46449.86 | 04-NOV-13:30 | 40581.08 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 258.10 | 0.00 | 0.22 | 258.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 12-DEC-05:07 | 0.35 | 12-DEC-05:07 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219034E+12 | 1814.90 | 0.204879E+12 | ||||||||||||
Minimum of Months | 258.10 | 0.00 | 0.22 | 258.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 0.35 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.710279E+11 | 0.00 | 402.88 | 0.639897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 132761.33 | 122729.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.311062E+12 | 0.792812E+11 | 735.82 | 0.310994E+12 | 68594977.63 | 0.00 | 1.00 | 02-JAN-22:10 | 0.01 | 03-JAN-05:34 | 434146.97 | 13-JAN-00:20 | 434146.97 | 13-JAN-00:20 | 46067.09 | 13-JAN-02:65 | 90772.60 | 13-JAN-00:20 | 0.00 |
February | 0.493530E+12 | 0.118222E+12 | 668.54 | 0.493439E+12 | 90972135.57 | 0.00 | 1.00 | 01-FEB-21:34 | 0.01 | 05-FEB-01:44 | 435974.83 | 14-FEB-22:40 | 435974.83 | 14-FEB-22:40 | 35100.02 | 14-FEB-23:22 | 90803.95 | 14-FEB-22:40 | 0.00 |
March | 0.783224E+12 | 0.179501E+12 | 743.96 | 0.783197E+12 | 27720623.62 | 0.00 | 1.00 | 01-MAR-23:37 | 0.03 | 03-MAR-23:14 | 425486.72 | 01-MAR-23:37 | 424652.11 | 07-MAR-22:30 | 21232.11 | 02-MAR-00:24 | 90624.08 | 01-MAR-23:37 | 0.00 |
April | 0.988660E+12 | 0.224261E+12 | 720.00 | 0.988659E+12 | 190229.21 | 0.00 | 1.00 | 01-APR-13:10 | 0.76 | 22-APR-04:26 | 417875.36 | 22-APR-04:28 | 417875.36 | 22-APR-04:28 | 317.05 | 15-APR-06:10 | 125508.95 | 27-APR-16:00 | 0.00 |
May | 0.315863E+12 | 0.805449E+11 | 743.53 | 0.315659E+12 | 0.203349E+09 | 0.00 | 1.00 | 08-MAY-04:37 | 0.10 | 17-MAY-22:24 | 425273.81 | 08-MAY-04:37 | 425151.68 | 08-MAY-04:37 | 19631.46 | 17-MAY-22:35 | 90620.43 | 08-MAY-04:37 | 0.00 |
June | 0.534210E+12 | 0.133295E+12 | 720.00 | 0.534104E+12 | 0.105769E+09 | 0.00 | 0.59 | 28-JUN-17:00 | 0.51 | 01-JUN-06:20 | 209273.04 | 28-JUN-16:00 | 209273.04 | 28-JUN-16:00 | 3469.69 | 12-JUN-17:00 | 69880.66 | 28-JUN-17:00 | 0.00 |
July | 0.790553E+12 | 0.199992E+12 | 744.00 | 0.789631E+12 | 0.922409E+09 | 0.00 | 0.82 | 24-JUL-15:00 | 0.72 | 01-JUL-06:10 | 299773.92 | 31-JUL-16:00 | 298470.88 | 24-JUL-15:00 | 4872.55 | 27-JUL-19:50 | 107843.63 | 24-JUL-15:00 | 0.00 |
August | 0.102664E+13 | 0.266354E+12 | 744.00 | 0.102557E+13 | 0.107125E+10 | 0.00 | 1.00 | 07-AUG-13:10 | 0.90 | 01-AUG-07:00 | 392172.48 | 29-AUG-19:30 | 388914.67 | 10-AUG-19:45 | 5916.29 | 29-AUG-19:40 | 137230.34 | 10-AUG-17:00 | 0.00 |
September | 0.308280E+12 | 0.781027E+11 | 720.00 | 0.307417E+12 | 0.863171E+09 | 0.00 | 0.37 | 01-SEP-00:03 | 0.31 | 27-SEP-06:10 | 135826.97 | 01-SEP-00:08 | 134751.60 | 01-SEP-00:10 | 3507.83 | 22-SEP-17:50 | 38655.52 | 14-SEP-17:00 | 0.00 |
October | 0.551191E+12 | 0.131983E+12 | 742.63 | 0.551152E+12 | 38726067.97 | 0.00 | 1.00 | 05-OCT-03:55 | 0.05 | 17-OCT-00:31 | 433609.83 | 22-OCT-22:16 | 433609.83 | 22-OCT-22:16 | 16500.99 | 22-OCT-23:05 | 90763.39 | 22-OCT-22:16 | 0.00 |
November | 0.759741E+12 | 0.173433E+12 | 719.95 | 0.759609E+12 | 0.132291E+09 | 0.00 | 1.00 | 01-NOV-00:05 | 0.08 | 01-NOV-00:29 | 426494.12 | 17-NOV-05:30 | 426494.12 | 17-NOV-05:30 | 14069.92 | 17-NOV-06:03 | 90641.35 | 17-NOV-05:30 | 0.00 |
December | 0.101938E+13 | 0.225050E+12 | 744.00 | 0.101938E+13 | 0.00 | 0.00 | 1.00 | 02-DEC-16:38 | 0.86 | 23-DEC-17:15 | 417003.67 | 16-DEC-18:25 | 417003.67 | 16-DEC-18:25 | 0.00 | 01-DEC-00:10 | 90478.60 | 16-DEC-18:25 | 0.00 |
Annual Sum or Average | 0.788233E+13 | 0.189002E+13 | 8746.43 | 0.787880E+13 | 0.352445E+10 | ||||||||||||||
Minimum of Months | 0.308280E+12 | 0.781027E+11 | 668.54 | 0.307417E+12 | 0.00 | 0.00 | 0.37 | 0.01 | 135826.97 | 134751.60 | 0.00 | 38655.52 | 0.00 | ||||||
Maximum of Months | 0.102664E+13 | 0.266354E+12 | 744.00 | 0.102557E+13 | 0.107125E+10 | 0.00 | 1.00 | 0.90 | 435974.83 | 435974.83 | 46067.09 | 137230.34 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.443821E+10 | 0.115519E+10 | 744.00 | 0.443821E+10 | 0.00 | 0.00 | 0.30 | 05-JAN-16:10 | 0.18 | 21-JAN-18:15 | 2283.80 | 05-JAN-16:10 | 2283.80 | 05-JAN-16:10 | 0.00 | 01-JAN-00:05 | 579.33 | 05-JAN-16:10 | 0.00 |
February | 0.884568E+10 | 0.215484E+10 | 672.00 | 0.884568E+10 | 0.00 | 0.00 | 0.54 | 27-FEB-16:20 | 0.41 | 18-FEB-18:19 | 4306.00 | 07-FEB-16:50 | 4306.00 | 07-FEB-16:50 | 0.00 | 01-FEB-00:10 | 1147.39 | 27-FEB-16:10 | 0.00 |
March | 0.150959E+11 | 0.351298E+10 | 744.00 | 0.150959E+11 | 0.00 | 0.00 | 0.76 | 14-MAR-17:10 | 0.64 | 01-MAR-08:00 | 6308.57 | 14-MAR-17:10 | 6308.57 | 14-MAR-17:10 | 0.00 | 01-MAR-00:10 | 1622.37 | 18-MAR-17:00 | 0.00 |
April | 0.195267E+11 | 0.450160E+10 | 720.00 | 0.195267E+11 | 0.00 | 0.00 | 1.00 | 26-APR-17:00 | 0.84 | 01-APR-07:00 | 8279.30 | 26-APR-18:30 | 8279.30 | 26-APR-18:30 | 0.00 | 01-APR-00:10 | 2679.61 | 27-APR-16:00 | 0.00 |
May | 0.547749E+10 | 0.143126E+10 | 744.00 | 0.547749E+10 | 0.00 | 0.00 | 0.38 | 29-MAY-18:27 | 0.23 | 18-MAY-07:00 | 2953.47 | 29-MAY-18:27 | 2953.47 | 29-MAY-18:27 | 0.00 | 01-MAY-00:10 | 827.20 | 14-MAY-18:02 | 0.00 |
June | 0.101802E+11 | 0.259427E+10 | 720.00 | 0.101802E+11 | 0.00 | 0.00 | 0.60 | 22-JUN-18:50 | 0.46 | 14-JUN-07:00 | 4650.74 | 18-JUN-18:57 | 4650.74 | 18-JUN-18:57 | 0.00 | 01-JUN-00:10 | 1419.91 | 28-JUN-17:00 | 0.00 |
July | 0.155248E+11 | 0.405310E+10 | 744.00 | 0.155248E+11 | 0.00 | 0.00 | 0.89 | 30-JUL-18:15 | 0.67 | 01-JUL-07:00 | 6925.48 | 30-JUL-18:27 | 6925.48 | 30-JUL-18:27 | 0.00 | 01-JUL-00:10 | 2287.70 | 30-JUL-18:02 | 0.00 |
August | 0.203051E+11 | 0.548013E+10 | 744.00 | 0.203051E+11 | 0.00 | 0.00 | 1.00 | 06-AUG-17:05 | 0.86 | 19-AUG-06:50 | 8337.42 | 06-AUG-19:37 | 8337.42 | 06-AUG-19:37 | 0.00 | 01-AUG-00:05 | 2927.12 | 10-AUG-17:00 | 0.00 |
September | 0.533790E+10 | 0.140467E+10 | 720.00 | 0.533790E+10 | 0.00 | 0.00 | 0.38 | 10-SEP-17:23 | 0.23 | 28-SEP-07:00 | 2815.70 | 10-SEP-17:23 | 2815.70 | 10-SEP-17:23 | 0.00 | 01-SEP-00:03 | 828.60 | 10-SEP-17:12 | 0.00 |
October | 0.102386E+11 | 0.249424E+10 | 744.00 | 0.102386E+11 | 0.00 | 0.00 | 0.59 | 04-OCT-16:50 | 0.44 | 28-OCT-07:00 | 4629.42 | 03-OCT-16:50 | 4629.42 | 03-OCT-16:50 | 0.00 | 01-OCT-00:10 | 1307.93 | 04-OCT-16:40 | 0.00 |
November | 0.145377E+11 | 0.338287E+10 | 720.00 | 0.145377E+11 | 0.00 | 0.00 | 0.74 | 04-NOV-16:00 | 0.64 | 18-NOV-18:13 | 6129.45 | 12-NOV-15:58 | 6129.45 | 12-NOV-15:58 | 0.00 | 01-NOV-00:02 | 1660.40 | 04-NOV-15:40 | 0.00 |
December | 0.198273E+11 | 0.444074E+10 | 744.00 | 0.198273E+11 | 0.00 | 0.00 | 0.91 | 05-DEC-15:50 | 0.82 | 23-DEC-18:13 | 7897.10 | 05-DEC-15:50 | 7897.10 | 05-DEC-15:50 | 0.00 | 01-DEC-00:10 | 1756.31 | 05-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.149336E+12 | 0.366059E+11 | 8760.00 | 0.149336E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.443821E+10 | 0.115519E+10 | 672.00 | 0.443821E+10 | 0.00 | 0.00 | 0.30 | 0.18 | 2283.80 | 2283.80 | 0.00 | 579.33 | 0.00 | ||||||
Maximum of Months | 0.203051E+11 | 0.548013E+10 | 744.00 | 0.203051E+11 | 0.00 | 0.00 | 1.00 | 0.86 | 8337.42 | 8337.42 | 0.00 | 2927.12 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.228011E+11 | 0.621250E+10 | 688.38 | 0.228011E+11 | 0.00 | 0.00 | 0.26 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 18704.77 | 05-JAN-16:20 | 18704.77 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 4805.84 | 05-JAN-16:20 | 0.00 |
February | 0.694866E+11 | 0.172326E+11 | 672.00 | 0.694866E+11 | 0.00 | 0.00 | 0.52 | 27-FEB-16:20 | 0.29 | 19-FEB-08:15 | 39443.31 | 08-FEB-16:50 | 39443.31 | 08-FEB-16:50 | 0.00 | 01-FEB-00:10 | 10502.15 | 27-FEB-16:20 | 0.00 |
March | 0.131422E+12 | 0.309146E+11 | 744.00 | 0.131422E+12 | 0.00 | 0.00 | 0.74 | 14-MAR-17:10 | 0.56 | 05-MAR-07:40 | 58976.13 | 14-MAR-17:10 | 58976.13 | 14-MAR-17:10 | 0.00 | 01-MAR-00:10 | 14698.95 | 18-MAR-16:50 | 0.00 |
April | 0.177867E+12 | 0.412973E+11 | 720.00 | 0.177867E+12 | 0.00 | 0.00 | 1.00 | 26-APR-17:10 | 0.79 | 01-APR-07:00 | 78745.41 | 26-APR-18:20 | 78745.41 | 26-APR-18:20 | 0.00 | 01-APR-00:10 | 25460.69 | 27-APR-16:00 | 0.00 |
May | 0.453274E+11 | 0.119964E+11 | 744.00 | 0.453274E+11 | 0.00 | 0.00 | 0.37 | 07-MAY-18:12 | 0.17 | 18-MAY-07:00 | 26763.08 | 29-MAY-18:23 | 26763.08 | 29-MAY-18:23 | 0.00 | 01-MAY-00:10 | 7735.22 | 14-MAY-18:02 | 0.00 |
June | 0.914127E+11 | 0.234621E+11 | 720.00 | 0.914127E+11 | 0.00 | 0.00 | 0.59 | 22-JUN-18:50 | 0.41 | 14-JUN-07:00 | 43234.57 | 22-JUN-18:50 | 43234.57 | 22-JUN-18:50 | 0.00 | 01-JUN-00:10 | 13445.99 | 28-JUN-17:00 | 0.00 |
July | 0.144316E+12 | 0.378260E+11 | 744.00 | 0.144316E+12 | 0.00 | 0.00 | 0.86 | 30-JUL-18:15 | 0.64 | 01-JUL-11:10 | 64130.50 | 30-JUL-18:33 | 64130.50 | 30-JUL-18:33 | 0.00 | 01-JUL-00:10 | 21320.46 | 24-JUL-15:00 | 0.00 |
August | 0.190570E+12 | 0.516079E+11 | 744.00 | 0.190570E+12 | 0.00 | 0.00 | 1.00 | 06-AUG-17:32 | 0.82 | 04-AUG-07:00 | 79138.08 | 06-AUG-19:23 | 79138.08 | 06-AUG-19:23 | 0.00 | 01-AUG-00:05 | 27970.72 | 10-AUG-17:00 | 0.00 |
September | 0.447090E+11 | 0.119095E+11 | 720.00 | 0.447090E+11 | 0.00 | 0.00 | 0.36 | 08-SEP-17:30 | 0.19 | 28-SEP-07:00 | 25787.43 | 08-SEP-17:30 | 25787.43 | 08-SEP-17:30 | 0.00 | 01-SEP-00:03 | 7784.47 | 08-SEP-17:10 | 0.00 |
October | 0.865710E+11 | 0.213420E+11 | 744.00 | 0.865710E+11 | 0.00 | 0.00 | 0.58 | 04-OCT-16:50 | 0.38 | 29-OCT-07:20 | 43348.60 | 03-OCT-16:50 | 43348.60 | 03-OCT-16:50 | 0.00 | 01-OCT-00:10 | 12275.42 | 04-OCT-16:50 | 0.00 |
November | 0.123444E+12 | 0.291186E+11 | 720.00 | 0.123444E+12 | 0.00 | 0.00 | 0.70 | 04-NOV-16:00 | 0.56 | 26-NOV-05:20 | 55121.36 | 10-NOV-16:10 | 55121.36 | 10-NOV-16:10 | 0.00 | 01-NOV-00:02 | 14969.48 | 04-NOV-15:40 | 0.00 |
December | 0.170392E+12 | 0.387056E+11 | 744.00 | 0.170392E+12 | 0.00 | 0.00 | 0.88 | 05-DEC-16:00 | 0.72 | 26-DEC-04:47 | 72573.40 | 05-DEC-16:00 | 72573.40 | 05-DEC-16:00 | 0.00 | 01-DEC-00:10 | 16229.55 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.129832E+13 | 0.321625E+12 | 8704.38 | 0.129832E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.228011E+11 | 0.621250E+10 | 672.00 | 0.228011E+11 | 0.00 | 0.00 | 0.26 | 0.00 | 18704.77 | 18704.77 | 0.00 | 4805.84 | 0.00 | ||||||
Maximum of Months | 0.190570E+12 | 0.516079E+11 | 744.00 | 0.190570E+12 | 0.00 | 0.00 | 1.00 | 0.82 | 79138.08 | 79138.08 | 0.00 | 27970.72 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.104326E+10 | 0.292869E+09 | 419.24 | 0.104326E+10 | 0.00 | 0.00 | 0.24 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 1755.20 | 05-JAN-16:20 | 1755.20 | 05-JAN-16:20 | 0.00 | 01-JAN-00:05 | 453.90 | 05-JAN-16:20 | 0.00 |
February | 0.550426E+10 | 0.139004E+10 | 667.60 | 0.550426E+10 | 0.00 | 0.00 | 0.50 | 27-FEB-16:30 | 0.00 | 20-FEB-02:65 | 3848.04 | 08-FEB-17:00 | 3848.04 | 08-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1034.09 | 27-FEB-16:20 | 0.00 |
March | 0.120290E+11 | 0.286101E+10 | 744.00 | 0.120290E+11 | 0.00 | 0.00 | 0.74 | 14-MAR-17:10 | 0.40 | 06-MAR-05:04 | 5910.98 | 14-MAR-17:10 | 5910.98 | 14-MAR-17:10 | 0.00 | 01-MAR-00:10 | 1463.97 | 14-MAR-17:00 | 0.00 |
April | 0.171055E+11 | 0.400366E+10 | 720.00 | 0.171055E+11 | 0.00 | 0.00 | 1.00 | 26-APR-17:20 | 0.69 | 09-APR-06:40 | 7949.83 | 26-APR-18:20 | 7949.83 | 26-APR-18:20 | 0.00 | 01-APR-00:10 | 2578.31 | 27-APR-16:00 | 0.00 |
May | 0.410061E+10 | 0.109744E+10 | 744.00 | 0.410061E+10 | 0.00 | 0.00 | 0.38 | 14-MAY-18:12 | 0.10 | 18-MAY-05:30 | 2748.15 | 07-MAY-18:25 | 2748.15 | 07-MAY-18:25 | 0.00 | 01-MAY-00:10 | 809.82 | 14-MAY-18:02 | 0.00 |
June | 0.896134E+10 | 0.231162E+10 | 720.00 | 0.896134E+10 | 0.00 | 0.00 | 0.60 | 22-JUN-18:50 | 0.37 | 14-JUN-06:50 | 4457.73 | 18-JUN-18:38 | 4457.73 | 18-JUN-18:38 | 0.00 | 01-JUN-00:10 | 1378.92 | 28-JUN-17:00 | 0.00 |
July | 0.143242E+11 | 0.377073E+10 | 744.00 | 0.143242E+11 | 0.00 | 0.00 | 0.87 | 30-JUL-18:21 | 0.60 | 02-JUL-05:50 | 6586.52 | 30-JUL-18:25 | 6586.52 | 30-JUL-18:25 | 0.00 | 01-JUL-00:10 | 2176.05 | 24-JUL-15:00 | 0.00 |
August | 0.188913E+11 | 0.514106E+10 | 744.00 | 0.188913E+11 | 0.00 | 0.00 | 1.00 | 06-AUG-17:32 | 0.79 | 19-AUG-07:00 | 8019.84 | 06-AUG-19:14 | 8019.84 | 06-AUG-19:14 | 0.00 | 01-AUG-00:05 | 2840.05 | 10-AUG-17:00 | 0.00 |
September | 0.401017E+10 | 0.108197E+10 | 720.00 | 0.401017E+10 | 0.00 | 0.00 | 0.37 | 08-SEP-17:30 | 0.12 | 27-SEP-07:00 | 2638.74 | 08-SEP-17:30 | 2638.74 | 08-SEP-17:30 | 0.00 | 01-SEP-00:03 | 795.56 | 08-SEP-17:10 | 0.00 |
October | 0.766604E+10 | 0.191331E+10 | 744.00 | 0.766604E+10 | 0.00 | 0.00 | 0.58 | 04-OCT-16:50 | 0.26 | 29-OCT-07:55 | 4362.17 | 04-OCT-16:50 | 4362.17 | 04-OCT-16:50 | 0.00 | 01-OCT-00:10 | 1237.04 | 04-OCT-16:40 | 0.00 |
November | 0.109676E+11 | 0.262369E+10 | 720.00 | 0.109676E+11 | 0.00 | 0.00 | 0.68 | 04-NOV-16:00 | 0.40 | 27-NOV-01:40 | 5398.75 | 10-NOV-16:10 | 5398.75 | 10-NOV-16:10 | 0.00 | 01-NOV-00:02 | 1477.98 | 04-NOV-15:50 | 0.00 |
December | 0.152870E+11 | 0.352498E+10 | 744.00 | 0.152870E+11 | 0.00 | 0.00 | 0.85 | 05-DEC-16:00 | 0.51 | 26-DEC-04:10 | 7113.11 | 05-DEC-16:00 | 7113.11 | 05-DEC-16:00 | 0.00 | 01-DEC-00:10 | 1598.51 | 05-DEC-16:00 | 0.00 |
Annual Sum or Average | 0.119890E+12 | 0.300124E+11 | 8430.85 | 0.119890E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.104326E+10 | 0.292869E+09 | 419.24 | 0.104326E+10 | 0.00 | 0.00 | 0.24 | 0.00 | 1755.20 | 1755.20 | 0.00 | 453.90 | 0.00 | ||||||
Maximum of Months | 0.188913E+11 | 0.514106E+10 | 744.00 | 0.188913E+11 | 0.00 | 0.00 | 1.00 | 0.79 | 8019.84 | 8019.84 | 0.00 | 2840.05 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.13 | 520.40 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.19 | 459.83 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 37.09 | 368.41 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.48 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.71 | 180.70 | 219.33 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 207.09 | 166.28 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.39 | 148.22 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.99 | 147.22 | 0.00 | 0.00 | 744.00 |
September | 192.81 | 0.06 | 192.75 | 109.49 | 221.52 | 0.00 | 0.00 | 720.00 |
October | 132.11 | 0.00 | 132.11 | 33.11 | 320.79 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.49 | 430.18 | 0.00 | 0.00 | 720.00 |
December | 62.46 | 0.00 | 62.46 | 0.01 | 533.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.83 | 5.20 | 182.63 | 92.80 | 317.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.46 | 0.00 | 62.46 | 0.01 | 147.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.39 | 533.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.13 | 520.40 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.19 | 459.83 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 37.09 | 368.41 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.48 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.70 | 180.69 | 219.33 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 207.09 | 166.28 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.38 | 148.22 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.99 | 147.22 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.75 | 109.48 | 221.52 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 33.11 | 320.79 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.49 | 430.18 | 0.00 | 0.00 | 720.00 |
December | 62.45 | 0.00 | 62.45 | 0.01 | 533.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.80 | 317.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.45 | 0.00 | 62.45 | 0.01 | 147.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.38 | 533.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.13 | 520.40 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.19 | 459.83 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 37.09 | 368.41 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.48 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.71 | 180.69 | 219.33 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 207.09 | 166.28 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.38 | 148.22 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.99 | 147.22 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.75 | 109.49 | 221.52 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 33.11 | 320.79 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.49 | 430.18 | 0.00 | 0.00 | 720.00 |
December | 62.46 | 0.00 | 62.46 | 0.01 | 533.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.80 | 317.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.46 | 0.00 | 62.46 | 0.01 | 147.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.38 | 533.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.13 | 520.40 | 0.00 | 0.00 | 744.00 |
February | 114.37 | 0.00 | 114.37 | 8.19 | 459.83 | 0.00 | 0.00 | 672.00 |
March | 168.50 | 0.00 | 168.50 | 37.09 | 368.41 | 0.00 | 0.00 | 744.00 |
April | 238.44 | 0.84 | 237.60 | 104.48 | 286.20 | 0.00 | 0.00 | 720.00 |
May | 306.80 | 9.09 | 297.70 | 180.69 | 219.33 | 0.00 | 0.00 | 744.00 |
June | 322.58 | 21.27 | 301.31 | 207.09 | 166.28 | 0.00 | 0.00 | 720.00 |
July | 306.59 | 24.00 | 282.59 | 226.38 | 148.22 | 0.00 | 0.00 | 744.00 |
August | 248.19 | 6.68 | 241.51 | 196.99 | 147.22 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.75 | 109.48 | 221.52 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 33.11 | 320.79 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.49 | 430.18 | 0.00 | 0.00 | 720.00 |
December | 62.45 | 0.00 | 62.45 | 0.01 | 533.30 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.80 | 317.78 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.45 | 0.00 | 62.45 | 0.01 | 147.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.58 | 24.00 | 301.31 | 226.38 | 533.30 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.50 | 0.00 | 73.50 | 0.13 | 520.38 | 0.00 | 0.00 | 744.00 |
February | 114.36 | 0.00 | 114.36 | 8.19 | 459.81 | 0.00 | 0.00 | 672.00 |
March | 168.49 | 0.00 | 168.49 | 37.09 | 368.40 | 0.00 | 0.00 | 744.00 |
April | 238.43 | 0.84 | 237.59 | 104.47 | 286.19 | 0.00 | 0.00 | 720.00 |
May | 306.79 | 9.09 | 297.69 | 180.69 | 219.32 | 0.00 | 0.00 | 744.00 |
June | 322.57 | 21.27 | 301.30 | 207.08 | 166.27 | 0.00 | 0.00 | 720.00 |
July | 306.57 | 24.00 | 282.58 | 226.37 | 148.21 | 0.00 | 0.00 | 744.00 |
August | 248.18 | 6.68 | 241.50 | 196.98 | 147.22 | 0.00 | 0.00 | 744.00 |
September | 192.80 | 0.06 | 192.74 | 109.48 | 221.51 | 0.00 | 0.00 | 720.00 |
October | 132.10 | 0.00 | 132.10 | 33.11 | 320.78 | 0.00 | 0.00 | 744.00 |
November | 83.21 | 0.00 | 83.21 | 3.49 | 430.16 | 0.00 | 0.00 | 720.00 |
December | 62.45 | 0.00 | 62.45 | 0.01 | 533.28 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 187.82 | 5.20 | 182.62 | 92.80 | 317.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 62.45 | 0.00 | 62.45 | 0.01 | 147.22 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 322.57 | 24.00 | 301.30 | 226.37 | 533.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.23 | 33.28 | 97.96 | 24.81 | 528.58 | 0.00 | 0.00 | 744.00 |
February | 240.80 | 85.47 | 155.33 | 103.75 | 450.17 | 0.00 | 0.00 | 672.00 |
March | 359.53 | 130.16 | 229.37 | 225.49 | 364.29 | 0.00 | 0.00 | 744.00 |
April | 557.34 | 231.60 | 325.74 | 460.55 | 282.15 | 0.00 | 0.00 | 720.00 |
May | 592.99 | 206.14 | 386.85 | 513.41 | 230.74 | 0.00 | 0.00 | 744.00 |
June | 710.14 | 308.94 | 401.20 | 676.99 | 177.17 | 0.00 | 0.00 | 720.00 |
July | 661.28 | 296.77 | 364.52 | 660.07 | 149.14 | 0.00 | 0.00 | 744.00 |
August | 650.02 | 325.17 | 324.86 | 687.02 | 141.63 | 0.00 | 0.00 | 744.00 |
September | 480.67 | 221.72 | 258.95 | 439.92 | 222.75 | 0.00 | 0.00 | 720.00 |
October | 313.26 | 133.11 | 180.16 | 218.60 | 319.54 | 0.00 | 0.00 | 744.00 |
November | 153.55 | 43.35 | 110.20 | 49.25 | 426.77 | 0.00 | 0.00 | 720.00 |
December | 125.95 | 40.55 | 85.40 | 32.47 | 528.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 415.49 | 171.73 | 243.76 | 342.26 | 317.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 125.95 | 33.28 | 85.40 | 24.81 | 141.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 710.14 | 325.17 | 401.20 | 687.02 | 528.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.23 | 33.28 | 97.96 | 24.81 | 528.58 | 0.00 | 0.00 | 744.00 |
February | 240.80 | 85.47 | 155.33 | 103.75 | 450.17 | 0.00 | 0.00 | 672.00 |
March | 359.53 | 130.16 | 229.37 | 225.49 | 364.29 | 0.00 | 0.00 | 744.00 |
April | 557.34 | 231.60 | 325.74 | 460.55 | 282.15 | 0.00 | 0.00 | 720.00 |
May | 592.99 | 206.14 | 386.85 | 513.41 | 230.74 | 0.00 | 0.00 | 744.00 |
June | 710.14 | 308.94 | 401.20 | 676.99 | 177.17 | 0.00 | 0.00 | 720.00 |
July | 661.28 | 296.77 | 364.52 | 660.07 | 149.14 | 0.00 | 0.00 | 744.00 |
August | 650.02 | 325.17 | 324.86 | 687.02 | 141.63 | 0.00 | 0.00 | 744.00 |
September | 480.67 | 221.72 | 258.95 | 439.92 | 222.75 | 0.00 | 0.00 | 720.00 |
October | 313.26 | 133.11 | 180.16 | 218.60 | 319.54 | 0.00 | 0.00 | 744.00 |
November | 153.55 | 43.35 | 110.20 | 49.25 | 426.77 | 0.00 | 0.00 | 720.00 |
December | 125.95 | 40.55 | 85.40 | 32.47 | 528.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 415.49 | 171.73 | 243.76 | 342.26 | 317.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 125.95 | 33.28 | 85.40 | 24.81 | 141.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 710.14 | 325.17 | 401.20 | 687.02 | 528.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 131.23 | 33.28 | 97.96 | 24.81 | 528.57 | 0.00 | 0.00 | 744.00 |
February | 240.79 | 85.47 | 155.33 | 103.75 | 450.16 | 0.00 | 0.00 | 672.00 |
March | 359.52 | 130.15 | 229.36 | 225.49 | 364.28 | 0.00 | 0.00 | 744.00 |
April | 557.33 | 231.60 | 325.74 | 460.54 | 282.14 | 0.00 | 0.00 | 720.00 |
May | 592.98 | 206.14 | 386.84 | 513.40 | 230.73 | 0.00 | 0.00 | 744.00 |
June | 710.12 | 308.93 | 401.19 | 676.98 | 177.17 | 0.00 | 0.00 | 720.00 |
July | 661.27 | 296.76 | 364.51 | 660.05 | 149.13 | 0.00 | 0.00 | 744.00 |
August | 650.01 | 325.16 | 324.85 | 687.01 | 141.63 | 0.00 | 0.00 | 744.00 |
September | 480.66 | 221.71 | 258.95 | 439.91 | 222.74 | 0.00 | 0.00 | 720.00 |
October | 313.26 | 133.10 | 180.15 | 218.59 | 319.54 | 0.00 | 0.00 | 744.00 |
November | 153.55 | 43.35 | 110.20 | 49.25 | 426.76 | 0.00 | 0.00 | 720.00 |
December | 125.95 | 40.55 | 85.40 | 32.47 | 528.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 415.49 | 171.73 | 243.76 | 342.25 | 317.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 125.95 | 33.28 | 85.40 | 24.81 | 141.63 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 710.12 | 325.16 | 401.19 | 687.01 | 528.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.64 | 192.73 | 131.91 | 255.26 | 427.86 | 0.00 | 0.00 | 744.00 |
February | 499.42 | 309.15 | 190.27 | 439.39 | 385.28 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 470.43 | 338.64 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 470.04 | 277.69 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 392.68 | 223.28 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.33 | 347.10 | 345.41 | 175.60 | 0.00 | 0.00 | 720.00 |
July | 517.37 | 189.43 | 327.94 | 421.51 | 155.16 | 0.00 | 0.00 | 744.00 |
August | 555.90 | 259.20 | 296.70 | 522.54 | 148.32 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.35 | 275.81 | 600.17 | 214.03 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 541.03 | 294.11 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.92 | 364.80 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.75 | 445.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 419.49 | 287.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.64 | 127.33 | 121.79 | 255.26 | 148.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 600.17 | 445.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.63 | 192.73 | 131.91 | 255.26 | 427.86 | 0.00 | 0.00 | 744.00 |
February | 499.41 | 309.15 | 190.26 | 439.38 | 385.28 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 470.43 | 338.64 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 470.03 | 277.69 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 392.68 | 223.28 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.32 | 347.10 | 345.40 | 175.60 | 0.00 | 0.00 | 720.00 |
July | 517.36 | 189.43 | 327.94 | 421.51 | 155.16 | 0.00 | 0.00 | 744.00 |
August | 555.89 | 259.20 | 296.70 | 522.54 | 148.32 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.34 | 275.81 | 600.17 | 214.03 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 541.03 | 294.11 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.92 | 364.80 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.75 | 445.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 419.48 | 287.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.63 | 127.32 | 121.79 | 255.26 | 148.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 600.17 | 445.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.64 | 192.73 | 131.91 | 255.26 | 427.86 | 0.00 | 0.00 | 744.00 |
February | 499.42 | 309.15 | 190.27 | 439.39 | 385.28 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 470.43 | 338.64 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 470.04 | 277.69 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 392.68 | 223.28 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.33 | 347.10 | 345.41 | 175.60 | 0.00 | 0.00 | 720.00 |
July | 517.37 | 189.43 | 327.94 | 421.51 | 155.16 | 0.00 | 0.00 | 744.00 |
August | 555.90 | 259.20 | 296.70 | 522.54 | 148.32 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.35 | 275.81 | 600.17 | 214.03 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 541.03 | 294.11 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.92 | 364.80 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.75 | 445.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 419.49 | 287.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.64 | 127.33 | 121.79 | 255.26 | 148.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 600.17 | 445.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.63 | 192.73 | 131.91 | 255.26 | 427.86 | 0.00 | 0.00 | 744.00 |
February | 499.41 | 309.15 | 190.26 | 439.38 | 385.28 | 0.00 | 0.00 | 672.00 |
March | 537.42 | 286.70 | 250.72 | 470.43 | 338.64 | 0.00 | 0.00 | 744.00 |
April | 567.24 | 246.32 | 320.92 | 470.03 | 277.69 | 0.00 | 0.00 | 720.00 |
May | 518.55 | 154.43 | 364.12 | 392.68 | 223.28 | 0.00 | 0.00 | 744.00 |
June | 474.42 | 127.32 | 347.10 | 345.40 | 175.60 | 0.00 | 0.00 | 720.00 |
July | 517.36 | 189.43 | 327.94 | 421.51 | 155.16 | 0.00 | 0.00 | 744.00 |
August | 555.89 | 259.20 | 296.70 | 522.54 | 148.32 | 0.00 | 0.00 | 744.00 |
September | 616.15 | 340.34 | 275.81 | 600.17 | 214.03 | 0.00 | 0.00 | 720.00 |
October | 558.10 | 344.64 | 213.46 | 541.03 | 294.11 | 0.00 | 0.00 | 744.00 |
November | 329.81 | 188.98 | 140.83 | 273.92 | 364.80 | 0.00 | 0.00 | 720.00 |
December | 345.03 | 223.24 | 121.79 | 303.75 | 445.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.79 | 238.10 | 248.69 | 419.48 | 287.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.63 | 127.32 | 121.79 | 255.26 | 148.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.15 | 344.64 | 364.12 | 600.17 | 445.75 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 324.62 | 192.72 | 131.90 | 255.25 | 427.84 | 0.00 | 0.00 | 744.00 |
February | 499.40 | 309.14 | 190.26 | 439.37 | 385.26 | 0.00 | 0.00 | 672.00 |
March | 537.40 | 286.69 | 250.71 | 470.41 | 338.63 | 0.00 | 0.00 | 744.00 |
April | 567.22 | 246.31 | 320.91 | 470.01 | 277.68 | 0.00 | 0.00 | 720.00 |
May | 518.53 | 154.42 | 364.11 | 392.66 | 223.27 | 0.00 | 0.00 | 744.00 |
June | 474.40 | 127.32 | 347.08 | 345.39 | 175.59 | 0.00 | 0.00 | 720.00 |
July | 517.34 | 189.42 | 327.92 | 421.49 | 155.16 | 0.00 | 0.00 | 744.00 |
August | 555.87 | 259.19 | 296.68 | 522.52 | 148.32 | 0.00 | 0.00 | 744.00 |
September | 616.13 | 340.33 | 275.79 | 600.15 | 214.03 | 0.00 | 0.00 | 720.00 |
October | 558.08 | 344.63 | 213.45 | 541.01 | 294.10 | 0.00 | 0.00 | 744.00 |
November | 329.80 | 188.97 | 140.83 | 273.91 | 364.78 | 0.00 | 0.00 | 720.00 |
December | 345.02 | 223.23 | 121.78 | 303.74 | 445.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 486.77 | 238.09 | 248.68 | 419.47 | 287.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 324.62 | 127.32 | 121.78 | 255.25 | 148.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 616.13 | 344.63 | 364.11 | 600.15 | 445.74 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.42 | 40.83 | 97.60 | 32.93 | 560.48 | 0.00 | 0.00 | 744.00 |
February | 248.18 | 93.28 | 154.90 | 114.83 | 503.57 | 0.00 | 0.00 | 672.00 |
March | 347.75 | 117.38 | 230.37 | 209.18 | 427.87 | 0.00 | 0.00 | 744.00 |
April | 529.07 | 202.30 | 326.78 | 412.00 | 349.22 | 0.00 | 0.00 | 720.00 |
May | 680.69 | 276.48 | 404.21 | 618.34 | 262.98 | 0.00 | 0.00 | 744.00 |
June | 654.62 | 254.11 | 400.51 | 600.80 | 214.03 | 0.00 | 0.00 | 720.00 |
July | 808.67 | 425.01 | 383.66 | 839.95 | 197.73 | 0.00 | 0.00 | 744.00 |
August | 669.05 | 341.62 | 327.43 | 701.14 | 195.64 | 0.00 | 0.00 | 744.00 |
September | 544.89 | 261.46 | 283.42 | 520.17 | 257.65 | 0.00 | 0.00 | 720.00 |
October | 310.19 | 126.39 | 183.80 | 213.69 | 370.52 | 0.00 | 0.00 | 744.00 |
November | 154.48 | 43.58 | 110.91 | 50.08 | 493.10 | 0.00 | 0.00 | 720.00 |
December | 129.88 | 44.51 | 85.36 | 39.50 | 618.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 435.79 | 186.28 | 249.51 | 364.39 | 370.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.88 | 40.83 | 85.36 | 32.93 | 195.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 808.67 | 425.01 | 404.21 | 839.95 | 618.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.42 | 40.83 | 97.60 | 32.93 | 560.48 | 0.00 | 0.00 | 744.00 |
February | 248.18 | 93.28 | 154.90 | 114.83 | 503.57 | 0.00 | 0.00 | 672.00 |
March | 347.75 | 117.38 | 230.37 | 209.18 | 427.87 | 0.00 | 0.00 | 744.00 |
April | 529.07 | 202.30 | 326.78 | 412.00 | 349.22 | 0.00 | 0.00 | 720.00 |
May | 680.69 | 276.48 | 404.21 | 618.34 | 262.98 | 0.00 | 0.00 | 744.00 |
June | 654.62 | 254.11 | 400.51 | 600.80 | 214.03 | 0.00 | 0.00 | 720.00 |
July | 808.67 | 425.01 | 383.66 | 839.95 | 197.73 | 0.00 | 0.00 | 744.00 |
August | 669.05 | 341.62 | 327.43 | 701.14 | 195.64 | 0.00 | 0.00 | 744.00 |
September | 544.89 | 261.46 | 283.42 | 520.17 | 257.65 | 0.00 | 0.00 | 720.00 |
October | 310.19 | 126.39 | 183.80 | 213.69 | 370.52 | 0.00 | 0.00 | 744.00 |
November | 154.48 | 43.58 | 110.91 | 50.08 | 493.10 | 0.00 | 0.00 | 720.00 |
December | 129.88 | 44.51 | 85.36 | 39.50 | 618.81 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 435.79 | 186.28 | 249.51 | 364.39 | 370.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.88 | 40.83 | 85.36 | 32.93 | 195.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 808.67 | 425.01 | 404.21 | 839.95 | 618.81 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 138.42 | 40.82 | 97.60 | 32.93 | 560.47 | 0.00 | 0.00 | 744.00 |
February | 248.17 | 93.28 | 154.89 | 114.83 | 503.56 | 0.00 | 0.00 | 672.00 |
March | 347.74 | 117.38 | 230.37 | 209.18 | 427.86 | 0.00 | 0.00 | 744.00 |
April | 529.06 | 202.30 | 326.77 | 412.00 | 349.22 | 0.00 | 0.00 | 720.00 |
May | 680.67 | 276.47 | 404.20 | 618.33 | 262.97 | 0.00 | 0.00 | 744.00 |
June | 654.60 | 254.10 | 400.50 | 600.79 | 214.02 | 0.00 | 0.00 | 720.00 |
July | 808.65 | 425.00 | 383.65 | 839.93 | 197.73 | 0.00 | 0.00 | 744.00 |
August | 669.04 | 341.62 | 327.42 | 701.13 | 195.64 | 0.00 | 0.00 | 744.00 |
September | 544.88 | 261.46 | 283.42 | 520.16 | 257.65 | 0.00 | 0.00 | 720.00 |
October | 310.18 | 126.38 | 183.80 | 213.69 | 370.51 | 0.00 | 0.00 | 744.00 |
November | 154.48 | 43.58 | 110.90 | 50.08 | 493.09 | 0.00 | 0.00 | 720.00 |
December | 129.87 | 44.51 | 85.36 | 39.50 | 618.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 435.79 | 186.28 | 249.50 | 364.39 | 370.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 129.87 | 40.82 | 85.36 | 32.93 | 195.64 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 808.65 | 425.00 | 404.20 | 839.93 | 618.79 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 367.50 | 0.00 | 367.50 | 2.98 | 2247.62 | 0.00 | 0.00 | 744.00 |
February | 571.84 | 0.00 | 571.84 | 60.89 | 2002.70 | 0.00 | 0.00 | 672.00 |
March | 842.52 | 0.00 | 842.52 | 225.40 | 1632.97 | 0.00 | 0.00 | 744.00 |
April | 1192.20 | 4.19 | 1188.02 | 572.53 | 1283.12 | 0.00 | 0.00 | 720.00 |
May | 1534.01 | 45.47 | 1488.54 | 935.25 | 1021.30 | 0.00 | 0.00 | 744.00 |
June | 1612.92 | 106.35 | 1506.57 | 1069.47 | 772.64 | 0.00 | 0.00 | 720.00 |
July | 1532.95 | 120.00 | 1412.95 | 1169.49 | 688.84 | 0.00 | 0.00 | 744.00 |
August | 1240.96 | 33.41 | 1207.55 | 1020.07 | 683.29 | 0.00 | 0.00 | 744.00 |
September | 964.03 | 0.28 | 963.76 | 572.24 | 1027.81 | 0.00 | 0.00 | 720.00 |
October | 660.53 | 0.00 | 660.53 | 198.49 | 1424.92 | 0.00 | 0.00 | 744.00 |
November | 416.07 | 0.00 | 416.07 | 28.41 | 1848.94 | 0.00 | 0.00 | 720.00 |
December | 312.28 | 0.00 | 312.28 | 1.18 | 2275.39 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 939.13 | 26.00 | 913.13 | 490.75 | 1406.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 312.28 | 0.00 | 312.28 | 1.18 | 683.29 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1612.92 | 120.00 | 1506.57 | 1169.49 | 2275.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 393.70 | 99.83 | 293.87 | 83.11 | 1413.40 | 0.00 | 0.00 | 744.00 |
February | 722.38 | 256.40 | 465.98 | 336.08 | 1228.67 | 0.00 | 0.00 | 672.00 |
March | 1078.57 | 390.47 | 688.10 | 700.80 | 1003.45 | 0.00 | 0.00 | 744.00 |
April | 1672.01 | 694.79 | 977.21 | 1397.74 | 794.82 | 0.00 | 0.00 | 720.00 |
May | 1778.95 | 618.42 | 1160.53 | 1555.33 | 651.31 | 0.00 | 0.00 | 744.00 |
June | 2130.39 | 926.80 | 1203.59 | 2033.50 | 505.72 | 0.00 | 0.00 | 720.00 |
July | 1983.83 | 890.29 | 1093.53 | 1982.57 | 434.41 | 0.00 | 0.00 | 744.00 |
August | 1950.04 | 975.49 | 974.56 | 2059.93 | 423.51 | 0.00 | 0.00 | 744.00 |
September | 1441.99 | 665.15 | 776.84 | 1331.87 | 627.50 | 0.00 | 0.00 | 720.00 |
October | 939.78 | 399.32 | 540.46 | 677.12 | 875.88 | 0.00 | 0.00 | 744.00 |
November | 460.64 | 130.05 | 330.59 | 162.97 | 1149.90 | 0.00 | 0.00 | 720.00 |
December | 377.84 | 121.65 | 256.19 | 107.13 | 1429.15 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1246.47 | 515.19 | 731.28 | 1039.28 | 876.45 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 377.84 | 99.83 | 256.19 | 83.11 | 423.51 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2130.39 | 975.49 | 1203.59 | 2059.93 | 1429.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1623.21 | 963.66 | 659.55 | 1287.37 | 2017.85 | 0.00 | 0.00 | 744.00 |
February | 2497.13 | 1545.79 | 951.34 | 2207.82 | 1841.46 | 0.00 | 0.00 | 672.00 |
March | 2687.17 | 1433.54 | 1253.63 | 2358.40 | 1608.10 | 0.00 | 0.00 | 744.00 |
April | 2836.25 | 1231.61 | 1604.63 | 2364.08 | 1322.40 | 0.00 | 0.00 | 720.00 |
May | 2592.81 | 772.17 | 1820.64 | 1976.06 | 1074.30 | 0.00 | 0.00 | 744.00 |
June | 2372.15 | 636.64 | 1735.51 | 1750.61 | 834.43 | 0.00 | 0.00 | 720.00 |
July | 2586.86 | 947.16 | 1639.70 | 2129.02 | 745.04 | 0.00 | 0.00 | 744.00 |
August | 2779.53 | 1296.03 | 1483.50 | 2627.09 | 723.80 | 0.00 | 0.00 | 744.00 |
September | 3080.82 | 1701.77 | 1379.05 | 2999.96 | 1041.28 | 0.00 | 0.00 | 720.00 |
October | 2790.56 | 1723.25 | 1067.31 | 2703.10 | 1408.30 | 0.00 | 0.00 | 744.00 |
November | 1649.10 | 944.93 | 704.17 | 1385.01 | 1711.85 | 0.00 | 0.00 | 720.00 |
December | 1725.20 | 1116.24 | 608.96 | 1533.38 | 2087.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2434.01 | 1190.53 | 1243.48 | 2109.19 | 1365.70 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1623.21 | 636.64 | 608.96 | 1287.37 | 723.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3080.82 | 1723.25 | 1820.64 | 2999.96 | 2087.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.27 | 122.47 | 292.79 | 109.92 | 1452.12 | 0.00 | 0.00 | 744.00 |
February | 744.52 | 279.83 | 464.69 | 381.73 | 1277.42 | 0.00 | 0.00 | 672.00 |
March | 1043.24 | 352.14 | 691.10 | 683.27 | 1061.07 | 0.00 | 0.00 | 744.00 |
April | 1587.21 | 606.89 | 980.32 | 1309.64 | 871.03 | 0.00 | 0.00 | 720.00 |
May | 2042.04 | 829.43 | 1212.61 | 1889.66 | 718.61 | 0.00 | 0.00 | 744.00 |
June | 1963.83 | 762.31 | 1201.51 | 1854.51 | 561.77 | 0.00 | 0.00 | 720.00 |
July | 2425.98 | 1275.02 | 1150.96 | 2567.73 | 522.24 | 0.00 | 0.00 | 744.00 |
August | 2007.13 | 1024.86 | 982.27 | 2165.33 | 501.54 | 0.00 | 0.00 | 744.00 |
September | 1634.64 | 784.37 | 850.27 | 1591.56 | 697.85 | 0.00 | 0.00 | 720.00 |
October | 930.56 | 379.15 | 551.40 | 685.68 | 934.42 | 0.00 | 0.00 | 744.00 |
November | 463.44 | 130.73 | 332.71 | 177.31 | 1185.16 | 0.00 | 0.00 | 720.00 |
December | 389.63 | 133.54 | 256.09 | 138.77 | 1479.91 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1307.37 | 558.85 | 748.52 | 1134.60 | 937.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 389.63 | 122.47 | 256.09 | 109.92 | 501.54 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2425.98 | 1275.02 | 1212.61 | 2567.73 | 1479.91 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 367.50 | 0.00 | 367.50 | 7.14 | 2055.60 | 0.00 | 0.00 | 744.00 |
February | 571.84 | 0.00 | 571.84 | 77.78 | 1821.37 | 0.00 | 0.00 | 672.00 |
March | 842.52 | 0.00 | 842.52 | 257.16 | 1493.85 | 0.00 | 0.00 | 744.00 |
April | 1192.20 | 4.19 | 1188.02 | 601.55 | 1200.10 | 0.00 | 0.00 | 720.00 |
May | 1534.01 | 45.47 | 1488.54 | 950.58 | 973.63 | 0.00 | 0.00 | 744.00 |
June | 1612.92 | 106.35 | 1506.57 | 1069.95 | 752.37 | 0.00 | 0.00 | 720.00 |
July | 1532.95 | 120.00 | 1412.95 | 1165.05 | 675.09 | 0.00 | 0.00 | 744.00 |
August | 1240.96 | 33.41 | 1207.55 | 1020.36 | 662.31 | 0.00 | 0.00 | 744.00 |
September | 964.03 | 0.28 | 963.76 | 587.29 | 970.12 | 0.00 | 0.00 | 720.00 |
October | 660.53 | 0.00 | 660.53 | 229.40 | 1293.95 | 0.00 | 0.00 | 744.00 |
November | 416.07 | 0.00 | 416.07 | 38.96 | 1656.36 | 0.00 | 0.00 | 720.00 |
December | 312.28 | 0.00 | 312.28 | 4.19 | 2056.47 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 939.13 | 26.00 | 913.13 | 503.46 | 1298.37 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 312.28 | 0.00 | 312.28 | 4.19 | 662.31 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1612.92 | 120.00 | 1506.57 | 1165.05 | 2056.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 393.70 | 99.83 | 293.87 | 90.86 | 1305.77 | 0.00 | 0.00 | 744.00 |
February | 722.38 | 256.40 | 465.98 | 357.85 | 1134.30 | 0.00 | 0.00 | 672.00 |
March | 1078.57 | 390.47 | 688.10 | 721.99 | 935.26 | 0.00 | 0.00 | 744.00 |
April | 1672.01 | 694.79 | 977.21 | 1413.43 | 753.89 | 0.00 | 0.00 | 720.00 |
May | 1778.95 | 618.42 | 1160.53 | 1561.06 | 629.40 | 0.00 | 0.00 | 744.00 |
June | 2130.39 | 926.80 | 1203.59 | 2027.77 | 497.86 | 0.00 | 0.00 | 720.00 |
July | 1983.83 | 890.29 | 1093.53 | 1975.42 | 431.39 | 0.00 | 0.00 | 744.00 |
August | 1950.04 | 975.49 | 974.56 | 2056.69 | 415.80 | 0.00 | 0.00 | 744.00 |
September | 1441.99 | 665.15 | 776.84 | 1338.38 | 601.72 | 0.00 | 0.00 | 720.00 |
October | 939.78 | 399.32 | 540.46 | 697.40 | 813.24 | 0.00 | 0.00 | 744.00 |
November | 460.64 | 130.05 | 330.59 | 174.95 | 1052.05 | 0.00 | 0.00 | 720.00 |
December | 377.84 | 121.65 | 256.19 | 116.53 | 1309.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1246.47 | 515.19 | 731.28 | 1047.87 | 821.88 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 377.84 | 99.83 | 256.19 | 90.86 | 415.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2130.39 | 975.49 | 1203.59 | 2056.69 | 1309.80 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1623.21 | 963.66 | 659.55 | 1321.43 | 1855.78 | 0.00 | 0.00 | 744.00 |
February | 2497.13 | 1545.79 | 951.34 | 2252.62 | 1695.88 | 0.00 | 0.00 | 672.00 |
March | 2687.17 | 1433.54 | 1253.63 | 2386.57 | 1491.33 | 0.00 | 0.00 | 744.00 |
April | 2836.25 | 1231.61 | 1604.63 | 2389.97 | 1247.93 | 0.00 | 0.00 | 720.00 |
May | 2592.81 | 772.17 | 1820.64 | 1993.05 | 1028.19 | 0.00 | 0.00 | 744.00 |
June | 2372.15 | 636.64 | 1735.51 | 1755.36 | 812.13 | 0.00 | 0.00 | 720.00 |
July | 2586.86 | 947.16 | 1639.70 | 2129.99 | 731.11 | 0.00 | 0.00 | 744.00 |
August | 2779.53 | 1296.03 | 1483.50 | 2632.23 | 701.50 | 0.00 | 0.00 | 744.00 |
September | 3080.82 | 1701.77 | 1379.05 | 3014.78 | 989.28 | 0.00 | 0.00 | 720.00 |
October | 2790.56 | 1723.25 | 1067.31 | 2732.90 | 1301.42 | 0.00 | 0.00 | 744.00 |
November | 1649.10 | 944.93 | 704.17 | 1419.07 | 1564.34 | 0.00 | 0.00 | 720.00 |
December | 1725.20 | 1116.24 | 608.96 | 1566.35 | 1910.17 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2434.01 | 1190.53 | 1243.48 | 2131.74 | 1275.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1623.21 | 636.64 | 608.96 | 1321.43 | 701.50 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3080.82 | 1723.25 | 1820.64 | 3014.78 | 1910.17 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.27 | 122.47 | 292.79 | 115.01 | 1351.11 | 0.00 | 0.00 | 744.00 |
February | 744.52 | 279.83 | 464.69 | 395.45 | 1193.72 | 0.00 | 0.00 | 672.00 |
March | 1043.24 | 352.14 | 691.10 | 697.05 | 995.49 | 0.00 | 0.00 | 744.00 |
April | 1587.21 | 606.89 | 980.32 | 1322.25 | 827.88 | 0.00 | 0.00 | 720.00 |
May | 2042.04 | 829.43 | 1212.61 | 1895.45 | 691.62 | 0.00 | 0.00 | 744.00 |
June | 1963.83 | 762.31 | 1201.51 | 1853.10 | 547.43 | 0.00 | 0.00 | 720.00 |
July | 2425.98 | 1275.02 | 1150.96 | 2563.59 | 512.20 | 0.00 | 0.00 | 744.00 |
August | 2007.13 | 1024.86 | 982.27 | 2166.17 | 487.12 | 0.00 | 0.00 | 744.00 |
September | 1634.64 | 784.37 | 850.27 | 1599.14 | 667.24 | 0.00 | 0.00 | 720.00 |
October | 930.56 | 379.15 | 551.40 | 700.22 | 873.65 | 0.00 | 0.00 | 744.00 |
November | 463.44 | 130.73 | 332.71 | 185.85 | 1101.09 | 0.00 | 0.00 | 720.00 |
December | 389.63 | 133.54 | 256.09 | 144.53 | 1378.26 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1307.37 | 558.85 | 748.52 | 1141.44 | 884.13 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 389.63 | 122.47 | 256.09 | 115.01 | 487.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2425.98 | 1275.02 | 1212.61 | 2563.59 | 1378.26 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196862E+09 | 0.00 | 0.196862E+09 | 353200.36 | 0.139383E+10 |
February | 0.276679E+09 | 0.00 | 0.276679E+09 | 19819566.54 | 0.111241E+10 |
March | 0.451319E+09 | 0.00 | 0.451319E+09 | 99345899.15 | 0.986748E+09 |
April | 0.618038E+09 | 2170238.44 | 0.615868E+09 | 0.270811E+09 | 0.741834E+09 |
May | 0.821739E+09 | 24355703.09 | 0.797384E+09 | 0.483980E+09 | 0.587452E+09 |
June | 0.836139E+09 | 55132976.26 | 0.781006E+09 | 0.536777E+09 | 0.430991E+09 |
July | 0.821170E+09 | 64281622.84 | 0.756889E+09 | 0.606352E+09 | 0.396989E+09 |
August | 0.664759E+09 | 17898763.80 | 0.646860E+09 | 0.527631E+09 | 0.394319E+09 |
September | 0.499754E+09 | 142594.85 | 0.499612E+09 | 0.283790E+09 | 0.574179E+09 |
October | 0.353832E+09 | 0.00 | 0.353832E+09 | 88690953.47 | 0.859213E+09 |
November | 0.215689E+09 | 0.00 | 0.215689E+09 | 9058019.07 | 0.111501E+10 |
December | 0.167282E+09 | 0.00 | 0.167282E+09 | 26749.31 | 0.142840E+10 |
Annual Sum or Average | 0.592326E+10 | 0.163982E+09 | 0.575928E+10 | 0.292664E+10 | 0.100214E+11 |
Minimum of Months | 0.167282E+09 | 0.00 | 0.167282E+09 | 26749.31 | 0.394319E+09 |
Maximum of Months | 0.836139E+09 | 64281622.84 | 0.797384E+09 | 0.606352E+09 | 0.142840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+09 | 0.00 | 0.196859E+09 | 353106.74 | 0.139383E+10 |
February | 0.276674E+09 | 0.00 | 0.276674E+09 | 19818500.48 | 0.111241E+10 |
March | 0.451312E+09 | 0.00 | 0.451312E+09 | 99341603.24 | 0.986749E+09 |
April | 0.618029E+09 | 2170190.73 | 0.615859E+09 | 0.270804E+09 | 0.741835E+09 |
May | 0.821727E+09 | 24355167.66 | 0.797372E+09 | 0.483969E+09 | 0.587452E+09 |
June | 0.836126E+09 | 55131764.23 | 0.780995E+09 | 0.536766E+09 | 0.430991E+09 |
July | 0.821159E+09 | 64280209.68 | 0.756879E+09 | 0.606342E+09 | 0.396988E+09 |
August | 0.664750E+09 | 17898370.31 | 0.646851E+09 | 0.527623E+09 | 0.394318E+09 |
September | 0.499747E+09 | 142591.72 | 0.499605E+09 | 0.283784E+09 | 0.574178E+09 |
October | 0.353827E+09 | 0.00 | 0.353827E+09 | 88687597.71 | 0.859213E+09 |
November | 0.215686E+09 | 0.00 | 0.215686E+09 | 9057463.37 | 0.111502E+10 |
December | 0.167279E+09 | 0.00 | 0.167279E+09 | 26739.72 | 0.142840E+10 |
Annual Sum or Average | 0.592318E+10 | 0.163978E+09 | 0.575920E+10 | 0.292657E+10 | 0.100214E+11 |
Minimum of Months | 0.167279E+09 | 0.00 | 0.167279E+09 | 26739.72 | 0.394318E+09 |
Maximum of Months | 0.836126E+09 | 64280209.68 | 0.797372E+09 | 0.606342E+09 | 0.142840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196860E+09 | 0.00 | 0.196860E+09 | 353137.95 | 0.139383E+10 |
February | 0.276676E+09 | 0.00 | 0.276676E+09 | 19818855.84 | 0.111241E+10 |
March | 0.451314E+09 | 0.00 | 0.451314E+09 | 99343035.21 | 0.986749E+09 |
April | 0.618032E+09 | 2170206.63 | 0.615862E+09 | 0.270806E+09 | 0.741835E+09 |
May | 0.821731E+09 | 24355346.14 | 0.797376E+09 | 0.483973E+09 | 0.587452E+09 |
June | 0.836130E+09 | 55132168.24 | 0.780998E+09 | 0.536769E+09 | 0.430991E+09 |
July | 0.821163E+09 | 64280680.74 | 0.756882E+09 | 0.606345E+09 | 0.396988E+09 |
August | 0.664753E+09 | 17898501.47 | 0.646854E+09 | 0.527626E+09 | 0.394319E+09 |
September | 0.499750E+09 | 142592.76 | 0.499607E+09 | 0.283786E+09 | 0.574179E+09 |
October | 0.353828E+09 | 0.00 | 0.353828E+09 | 88688716.30 | 0.859213E+09 |
November | 0.215687E+09 | 0.00 | 0.215687E+09 | 9057648.61 | 0.111502E+10 |
December | 0.167280E+09 | 0.00 | 0.167280E+09 | 26742.92 | 0.142840E+10 |
Annual Sum or Average | 0.592321E+10 | 0.163979E+09 | 0.575923E+10 | 0.292659E+10 | 0.100214E+11 |
Minimum of Months | 0.167280E+09 | 0.00 | 0.167280E+09 | 26742.92 | 0.394319E+09 |
Maximum of Months | 0.836130E+09 | 64280680.74 | 0.797376E+09 | 0.606345E+09 | 0.142840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196859E+09 | 0.00 | 0.196859E+09 | 353106.74 | 0.139383E+10 |
February | 0.276674E+09 | 0.00 | 0.276674E+09 | 19818500.48 | 0.111241E+10 |
March | 0.451312E+09 | 0.00 | 0.451312E+09 | 99341603.24 | 0.986749E+09 |
April | 0.618029E+09 | 2170190.73 | 0.615859E+09 | 0.270804E+09 | 0.741835E+09 |
May | 0.821727E+09 | 24355167.66 | 0.797372E+09 | 0.483969E+09 | 0.587452E+09 |
June | 0.836126E+09 | 55131764.23 | 0.780995E+09 | 0.536766E+09 | 0.430991E+09 |
July | 0.821159E+09 | 64280209.68 | 0.756879E+09 | 0.606342E+09 | 0.396988E+09 |
August | 0.664750E+09 | 17898370.31 | 0.646851E+09 | 0.527623E+09 | 0.394318E+09 |
September | 0.499747E+09 | 142591.72 | 0.499605E+09 | 0.283784E+09 | 0.574178E+09 |
October | 0.353827E+09 | 0.00 | 0.353827E+09 | 88687597.71 | 0.859213E+09 |
November | 0.215686E+09 | 0.00 | 0.215686E+09 | 9057463.37 | 0.111502E+10 |
December | 0.167279E+09 | 0.00 | 0.167279E+09 | 26739.72 | 0.142840E+10 |
Annual Sum or Average | 0.592318E+10 | 0.163978E+09 | 0.575920E+10 | 0.292657E+10 | 0.100214E+11 |
Minimum of Months | 0.167279E+09 | 0.00 | 0.167279E+09 | 26739.72 | 0.394318E+09 |
Maximum of Months | 0.836126E+09 | 64280209.68 | 0.797372E+09 | 0.606342E+09 | 0.142840E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196852E+09 | 0.00 | 0.196852E+09 | 353108.11 | 0.139378E+10 |
February | 0.276664E+09 | 0.00 | 0.276664E+09 | 19817879.38 | 0.111237E+10 |
March | 0.451295E+09 | 0.00 | 0.451295E+09 | 99338315.29 | 0.986709E+09 |
April | 0.618006E+09 | 2170111.21 | 0.615836E+09 | 0.270794E+09 | 0.741805E+09 |
May | 0.821696E+09 | 24354275.27 | 0.797342E+09 | 0.483952E+09 | 0.587429E+09 |
June | 0.836095E+09 | 55129744.18 | 0.780965E+09 | 0.536746E+09 | 0.430973E+09 |
July | 0.821128E+09 | 64277854.42 | 0.756850E+09 | 0.606319E+09 | 0.396972E+09 |
August | 0.664724E+09 | 17897714.51 | 0.646827E+09 | 0.527603E+09 | 0.394303E+09 |
September | 0.499728E+09 | 142586.49 | 0.499586E+09 | 0.283774E+09 | 0.574155E+09 |
October | 0.353813E+09 | 0.00 | 0.353813E+09 | 88684582.48 | 0.859179E+09 |
November | 0.215678E+09 | 0.00 | 0.215678E+09 | 9057190.93 | 0.111497E+10 |
December | 0.167273E+09 | 0.00 | 0.167273E+09 | 26740.24 | 0.142834E+10 |
Annual Sum or Average | 0.592295E+10 | 0.163972E+09 | 0.575898E+10 | 0.292647E+10 | 0.100210E+11 |
Minimum of Months | 0.167273E+09 | 0.00 | 0.167273E+09 | 26740.24 | 0.394303E+09 |
Maximum of Months | 0.836095E+09 | 64277854.42 | 0.797342E+09 | 0.606319E+09 | 0.142834E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351499E+09 | 89130193.07 | 0.262369E+09 | 66442552.43 | 0.141576E+10 |
February | 0.582536E+09 | 0.206765E+09 | 0.375772E+09 | 0.251002E+09 | 0.108904E+10 |
March | 0.962954E+09 | 0.348612E+09 | 0.614342E+09 | 0.603950E+09 | 0.975703E+09 |
April | 0.144463E+10 | 0.600307E+09 | 0.844322E+09 | 0.119375E+10 | 0.731325E+09 |
May | 0.158826E+10 | 0.552131E+09 | 0.103613E+10 | 0.137512E+10 | 0.618010E+09 |
June | 0.184067E+10 | 0.800765E+09 | 0.103991E+10 | 0.175476E+10 | 0.459229E+09 |
July | 0.177118E+10 | 0.794862E+09 | 0.976318E+09 | 0.176792E+10 | 0.399443E+09 |
August | 0.174102E+10 | 0.870925E+09 | 0.870093E+09 | 0.184012E+10 | 0.379344E+09 |
September | 0.124589E+10 | 0.574696E+09 | 0.671199E+09 | 0.114028E+10 | 0.577365E+09 |
October | 0.839042E+09 | 0.356513E+09 | 0.482529E+09 | 0.585486E+09 | 0.855866E+09 |
November | 0.397999E+09 | 0.112368E+09 | 0.285631E+09 | 0.127655E+09 | 0.110618E+10 |
December | 0.337341E+09 | 0.108614E+09 | 0.228727E+09 | 86962771.69 | 0.141620E+10 |
Annual Sum or Average | 0.131030E+11 | 0.541569E+10 | 0.768734E+10 | 0.107934E+11 | 0.100235E+11 |
Minimum of Months | 0.337341E+09 | 89130193.07 | 0.228727E+09 | 66442552.43 | 0.379344E+09 |
Maximum of Months | 0.184067E+10 | 0.870925E+09 | 0.103991E+10 | 0.184012E+10 | 0.141620E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351499E+09 | 89130193.07 | 0.262369E+09 | 66442552.43 | 0.141576E+10 |
February | 0.582536E+09 | 0.206765E+09 | 0.375772E+09 | 0.251002E+09 | 0.108904E+10 |
March | 0.962954E+09 | 0.348612E+09 | 0.614342E+09 | 0.603950E+09 | 0.975703E+09 |
April | 0.144463E+10 | 0.600307E+09 | 0.844322E+09 | 0.119375E+10 | 0.731325E+09 |
May | 0.158826E+10 | 0.552131E+09 | 0.103613E+10 | 0.137512E+10 | 0.618010E+09 |
June | 0.184067E+10 | 0.800765E+09 | 0.103991E+10 | 0.175476E+10 | 0.459229E+09 |
July | 0.177118E+10 | 0.794862E+09 | 0.976318E+09 | 0.176792E+10 | 0.399443E+09 |
August | 0.174102E+10 | 0.870925E+09 | 0.870093E+09 | 0.184012E+10 | 0.379344E+09 |
September | 0.124589E+10 | 0.574696E+09 | 0.671199E+09 | 0.114028E+10 | 0.577365E+09 |
October | 0.839042E+09 | 0.356513E+09 | 0.482529E+09 | 0.585486E+09 | 0.855866E+09 |
November | 0.397999E+09 | 0.112368E+09 | 0.285631E+09 | 0.127655E+09 | 0.110618E+10 |
December | 0.337341E+09 | 0.108614E+09 | 0.228727E+09 | 86962771.69 | 0.141620E+10 |
Annual Sum or Average | 0.131030E+11 | 0.541569E+10 | 0.768734E+10 | 0.107934E+11 | 0.100235E+11 |
Minimum of Months | 0.337341E+09 | 89130193.07 | 0.228727E+09 | 66442552.43 | 0.379344E+09 |
Maximum of Months | 0.184067E+10 | 0.870925E+09 | 0.103991E+10 | 0.184012E+10 | 0.141620E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.351493E+09 | 89128564.47 | 0.262364E+09 | 66441338.38 | 0.141573E+10 |
February | 0.582526E+09 | 0.206761E+09 | 0.375765E+09 | 0.250997E+09 | 0.108902E+10 |
March | 0.962937E+09 | 0.348606E+09 | 0.614331E+09 | 0.603939E+09 | 0.975685E+09 |
April | 0.144460E+10 | 0.600296E+09 | 0.844307E+09 | 0.119373E+10 | 0.731312E+09 |
May | 0.158824E+10 | 0.552121E+09 | 0.103611E+10 | 0.137509E+10 | 0.617998E+09 |
June | 0.184064E+10 | 0.800750E+09 | 0.103989E+10 | 0.175473E+10 | 0.459221E+09 |
July | 0.177115E+10 | 0.794847E+09 | 0.976300E+09 | 0.176789E+10 | 0.399436E+09 |
August | 0.174099E+10 | 0.870909E+09 | 0.870077E+09 | 0.184009E+10 | 0.379337E+09 |
September | 0.124587E+10 | 0.574685E+09 | 0.671187E+09 | 0.114026E+10 | 0.577355E+09 |
October | 0.839027E+09 | 0.356507E+09 | 0.482520E+09 | 0.585475E+09 | 0.855850E+09 |
November | 0.397992E+09 | 0.112366E+09 | 0.285626E+09 | 0.127653E+09 | 0.110616E+10 |
December | 0.337335E+09 | 0.108612E+09 | 0.228722E+09 | 86961182.69 | 0.141618E+10 |
Annual Sum or Average | 0.131028E+11 | 0.541559E+10 | 0.768720E+10 | 0.107932E+11 | 0.100233E+11 |
Minimum of Months | 0.337335E+09 | 89128564.47 | 0.228722E+09 | 66441338.38 | 0.379337E+09 |
Maximum of Months | 0.184064E+10 | 0.870909E+09 | 0.103989E+10 | 0.184009E+10 | 0.141618E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869507E+09 | 0.516204E+09 | 0.353303E+09 | 0.683695E+09 | 0.114598E+10 |
February | 0.120819E+10 | 0.747899E+09 | 0.460290E+09 | 0.106297E+10 | 0.932058E+09 |
March | 0.143944E+10 | 0.767901E+09 | 0.671537E+09 | 0.126001E+10 | 0.907013E+09 |
April | 0.147029E+10 | 0.638455E+09 | 0.831831E+09 | 0.121833E+10 | 0.719776E+09 |
May | 0.138890E+10 | 0.413628E+09 | 0.975268E+09 | 0.105175E+10 | 0.598022E+09 |
June | 0.122971E+10 | 0.330027E+09 | 0.899680E+09 | 0.895290E+09 | 0.455145E+09 |
July | 0.138571E+10 | 0.507366E+09 | 0.878347E+09 | 0.112898E+10 | 0.415586E+09 |
August | 0.148892E+10 | 0.694241E+09 | 0.794674E+09 | 0.139958E+10 | 0.397272E+09 |
September | 0.159707E+10 | 0.882177E+09 | 0.714891E+09 | 0.155565E+10 | 0.554777E+09 |
October | 0.149482E+10 | 0.923089E+09 | 0.571728E+09 | 0.144910E+10 | 0.787740E+09 |
November | 0.854877E+09 | 0.489842E+09 | 0.365035E+09 | 0.710000E+09 | 0.945558E+09 |
December | 0.924137E+09 | 0.597936E+09 | 0.326201E+09 | 0.813577E+09 | 0.119391E+10 |
Annual Sum or Average | 0.153516E+11 | 0.750877E+10 | 0.784278E+10 | 0.132289E+11 | 0.905283E+10 |
Minimum of Months | 0.854877E+09 | 0.330027E+09 | 0.326201E+09 | 0.683695E+09 | 0.397272E+09 |
Maximum of Months | 0.159707E+10 | 0.923089E+09 | 0.975268E+09 | 0.155565E+10 | 0.119391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869501E+09 | 0.516200E+09 | 0.353301E+09 | 0.683688E+09 | 0.114598E+10 |
February | 0.120818E+10 | 0.747894E+09 | 0.460287E+09 | 0.106296E+10 | 0.932058E+09 |
March | 0.143943E+10 | 0.767895E+09 | 0.671533E+09 | 0.126000E+10 | 0.907013E+09 |
April | 0.147028E+10 | 0.638451E+09 | 0.831826E+09 | 0.121832E+10 | 0.719776E+09 |
May | 0.138889E+10 | 0.413625E+09 | 0.975263E+09 | 0.105174E+10 | 0.598022E+09 |
June | 0.122970E+10 | 0.330024E+09 | 0.899676E+09 | 0.895284E+09 | 0.455145E+09 |
July | 0.138570E+10 | 0.507362E+09 | 0.878343E+09 | 0.112897E+10 | 0.415586E+09 |
August | 0.148891E+10 | 0.694236E+09 | 0.794670E+09 | 0.139957E+10 | 0.397272E+09 |
September | 0.159706E+10 | 0.882171E+09 | 0.714887E+09 | 0.155564E+10 | 0.554777E+09 |
October | 0.149481E+10 | 0.923083E+09 | 0.571725E+09 | 0.144909E+10 | 0.787740E+09 |
November | 0.854871E+09 | 0.489839E+09 | 0.365033E+09 | 0.709993E+09 | 0.945558E+09 |
December | 0.924131E+09 | 0.597932E+09 | 0.326199E+09 | 0.813570E+09 | 0.119391E+10 |
Annual Sum or Average | 0.153515E+11 | 0.750871E+10 | 0.784274E+10 | 0.132288E+11 | 0.905283E+10 |
Minimum of Months | 0.854871E+09 | 0.330024E+09 | 0.326199E+09 | 0.683688E+09 | 0.397272E+09 |
Maximum of Months | 0.159706E+10 | 0.923083E+09 | 0.975263E+09 | 0.155564E+10 | 0.119391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869507E+09 | 0.516204E+09 | 0.353303E+09 | 0.683695E+09 | 0.114598E+10 |
February | 0.120819E+10 | 0.747899E+09 | 0.460290E+09 | 0.106297E+10 | 0.932058E+09 |
March | 0.143944E+10 | 0.767901E+09 | 0.671537E+09 | 0.126001E+10 | 0.907013E+09 |
April | 0.147029E+10 | 0.638455E+09 | 0.831831E+09 | 0.121833E+10 | 0.719776E+09 |
May | 0.138890E+10 | 0.413628E+09 | 0.975268E+09 | 0.105175E+10 | 0.598022E+09 |
June | 0.122971E+10 | 0.330027E+09 | 0.899680E+09 | 0.895290E+09 | 0.455145E+09 |
July | 0.138571E+10 | 0.507366E+09 | 0.878347E+09 | 0.112898E+10 | 0.415586E+09 |
August | 0.148892E+10 | 0.694241E+09 | 0.794674E+09 | 0.139958E+10 | 0.397272E+09 |
September | 0.159707E+10 | 0.882177E+09 | 0.714891E+09 | 0.155565E+10 | 0.554777E+09 |
October | 0.149482E+10 | 0.923089E+09 | 0.571728E+09 | 0.144910E+10 | 0.787740E+09 |
November | 0.854877E+09 | 0.489842E+09 | 0.365035E+09 | 0.710000E+09 | 0.945558E+09 |
December | 0.924137E+09 | 0.597936E+09 | 0.326201E+09 | 0.813577E+09 | 0.119391E+10 |
Annual Sum or Average | 0.153516E+11 | 0.750877E+10 | 0.784278E+10 | 0.132289E+11 | 0.905283E+10 |
Minimum of Months | 0.854877E+09 | 0.330027E+09 | 0.326201E+09 | 0.683695E+09 | 0.397272E+09 |
Maximum of Months | 0.159707E+10 | 0.923089E+09 | 0.975268E+09 | 0.155565E+10 | 0.119391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869501E+09 | 0.516200E+09 | 0.353301E+09 | 0.683688E+09 | 0.114598E+10 |
February | 0.120818E+10 | 0.747894E+09 | 0.460287E+09 | 0.106296E+10 | 0.932058E+09 |
March | 0.143943E+10 | 0.767895E+09 | 0.671533E+09 | 0.126000E+10 | 0.907013E+09 |
April | 0.147028E+10 | 0.638451E+09 | 0.831826E+09 | 0.121832E+10 | 0.719776E+09 |
May | 0.138889E+10 | 0.413625E+09 | 0.975263E+09 | 0.105174E+10 | 0.598022E+09 |
June | 0.122970E+10 | 0.330024E+09 | 0.899676E+09 | 0.895284E+09 | 0.455145E+09 |
July | 0.138570E+10 | 0.507362E+09 | 0.878343E+09 | 0.112897E+10 | 0.415586E+09 |
August | 0.148891E+10 | 0.694236E+09 | 0.794670E+09 | 0.139957E+10 | 0.397272E+09 |
September | 0.159706E+10 | 0.882171E+09 | 0.714887E+09 | 0.155564E+10 | 0.554777E+09 |
October | 0.149481E+10 | 0.923083E+09 | 0.571725E+09 | 0.144909E+10 | 0.787740E+09 |
November | 0.854871E+09 | 0.489839E+09 | 0.365033E+09 | 0.709993E+09 | 0.945558E+09 |
December | 0.924131E+09 | 0.597932E+09 | 0.326199E+09 | 0.813570E+09 | 0.119391E+10 |
Annual Sum or Average | 0.153515E+11 | 0.750871E+10 | 0.784274E+10 | 0.132288E+11 | 0.905283E+10 |
Minimum of Months | 0.854871E+09 | 0.330024E+09 | 0.326199E+09 | 0.683688E+09 | 0.397272E+09 |
Maximum of Months | 0.159706E+10 | 0.923083E+09 | 0.975263E+09 | 0.155564E+10 | 0.119391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.869469E+09 | 0.516181E+09 | 0.353288E+09 | 0.683664E+09 | 0.114593E+10 |
February | 0.120814E+10 | 0.747867E+09 | 0.460270E+09 | 0.106292E+10 | 0.932021E+09 |
March | 0.143937E+10 | 0.767867E+09 | 0.671508E+09 | 0.125995E+10 | 0.906977E+09 |
April | 0.147022E+10 | 0.638427E+09 | 0.831795E+09 | 0.121828E+10 | 0.719747E+09 |
May | 0.138884E+10 | 0.413610E+09 | 0.975227E+09 | 0.105170E+10 | 0.597998E+09 |
June | 0.122965E+10 | 0.330012E+09 | 0.899642E+09 | 0.895251E+09 | 0.455126E+09 |
July | 0.138565E+10 | 0.507343E+09 | 0.878309E+09 | 0.112893E+10 | 0.415569E+09 |
August | 0.148885E+10 | 0.694211E+09 | 0.794640E+09 | 0.139952E+10 | 0.397256E+09 |
September | 0.159700E+10 | 0.882138E+09 | 0.714860E+09 | 0.155558E+10 | 0.554755E+09 |
October | 0.149475E+10 | 0.923049E+09 | 0.571703E+09 | 0.144904E+10 | 0.787708E+09 |
November | 0.854840E+09 | 0.489821E+09 | 0.365019E+09 | 0.709968E+09 | 0.945519E+09 |
December | 0.924097E+09 | 0.597910E+09 | 0.326187E+09 | 0.813541E+09 | 0.119386E+10 |
Annual Sum or Average | 0.153509E+11 | 0.750844E+10 | 0.784245E+10 | 0.132283E+11 | 0.905247E+10 |
Minimum of Months | 0.854840E+09 | 0.330012E+09 | 0.326187E+09 | 0.683664E+09 | 0.397256E+09 |
Maximum of Months | 0.159700E+10 | 0.923049E+09 | 0.975227E+09 | 0.155558E+10 | 0.119386E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370753E+09 | 0.109347E+09 | 0.261406E+09 | 88198239.34 | 0.150119E+10 |
February | 0.600386E+09 | 0.225658E+09 | 0.374728E+09 | 0.277808E+09 | 0.121824E+10 |
March | 0.931417E+09 | 0.314394E+09 | 0.617023E+09 | 0.560275E+09 | 0.114601E+10 |
April | 0.137136E+10 | 0.524358E+09 | 0.847001E+09 | 0.106791E+10 | 0.905186E+09 |
May | 0.182315E+10 | 0.740520E+09 | 0.108263E+10 | 0.165617E+10 | 0.704354E+09 |
June | 0.169676E+10 | 0.658645E+09 | 0.103812E+10 | 0.155726E+10 | 0.554755E+09 |
July | 0.216593E+10 | 0.113835E+10 | 0.102759E+10 | 0.224972E+10 | 0.529604E+09 |
August | 0.179198E+10 | 0.915004E+09 | 0.876980E+09 | 0.187794E+10 | 0.524014E+09 |
September | 0.141234E+10 | 0.677707E+09 | 0.734637E+09 | 0.134828E+10 | 0.667839E+09 |
October | 0.830811E+09 | 0.338513E+09 | 0.492298E+09 | 0.572356E+09 | 0.992392E+09 |
November | 0.400418E+09 | 0.112951E+09 | 0.287467E+09 | 0.129818E+09 | 0.127812E+10 |
December | 0.347862E+09 | 0.119225E+09 | 0.228637E+09 | 0.105803E+09 | 0.165741E+10 |
Annual Sum or Average | 0.137432E+11 | 0.587467E+10 | 0.786851E+10 | 0.114915E+11 | 0.116791E+11 |
Minimum of Months | 0.347862E+09 | 0.109347E+09 | 0.228637E+09 | 88198239.34 | 0.524014E+09 |
Maximum of Months | 0.216593E+10 | 0.113835E+10 | 0.108263E+10 | 0.224972E+10 | 0.165741E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370753E+09 | 0.109347E+09 | 0.261406E+09 | 88198239.34 | 0.150119E+10 |
February | 0.600386E+09 | 0.225658E+09 | 0.374728E+09 | 0.277808E+09 | 0.121824E+10 |
March | 0.931417E+09 | 0.314394E+09 | 0.617023E+09 | 0.560275E+09 | 0.114601E+10 |
April | 0.137136E+10 | 0.524358E+09 | 0.847001E+09 | 0.106791E+10 | 0.905186E+09 |
May | 0.182315E+10 | 0.740520E+09 | 0.108263E+10 | 0.165617E+10 | 0.704354E+09 |
June | 0.169676E+10 | 0.658645E+09 | 0.103812E+10 | 0.155726E+10 | 0.554755E+09 |
July | 0.216593E+10 | 0.113835E+10 | 0.102759E+10 | 0.224972E+10 | 0.529604E+09 |
August | 0.179198E+10 | 0.915004E+09 | 0.876980E+09 | 0.187794E+10 | 0.524014E+09 |
September | 0.141234E+10 | 0.677707E+09 | 0.734637E+09 | 0.134828E+10 | 0.667839E+09 |
October | 0.830811E+09 | 0.338513E+09 | 0.492298E+09 | 0.572356E+09 | 0.992392E+09 |
November | 0.400418E+09 | 0.112951E+09 | 0.287467E+09 | 0.129818E+09 | 0.127812E+10 |
December | 0.347862E+09 | 0.119225E+09 | 0.228637E+09 | 0.105803E+09 | 0.165741E+10 |
Annual Sum or Average | 0.137432E+11 | 0.587467E+10 | 0.786851E+10 | 0.114915E+11 | 0.116791E+11 |
Minimum of Months | 0.347862E+09 | 0.109347E+09 | 0.228637E+09 | 88198239.34 | 0.524014E+09 |
Maximum of Months | 0.216593E+10 | 0.113835E+10 | 0.108263E+10 | 0.224972E+10 | 0.165741E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.370746E+09 | 0.109345E+09 | 0.261402E+09 | 88196627.76 | 0.150116E+10 |
February | 0.600375E+09 | 0.225654E+09 | 0.374721E+09 | 0.277803E+09 | 0.121822E+10 |
March | 0.931400E+09 | 0.314389E+09 | 0.617011E+09 | 0.560265E+09 | 0.114599E+10 |
April | 0.137133E+10 | 0.524349E+09 | 0.846986E+09 | 0.106789E+10 | 0.905170E+09 |
May | 0.182312E+10 | 0.740507E+09 | 0.108261E+10 | 0.165614E+10 | 0.704341E+09 |
June | 0.169673E+10 | 0.658633E+09 | 0.103810E+10 | 0.155724E+10 | 0.554745E+09 |
July | 0.216589E+10 | 0.113833E+10 | 0.102757E+10 | 0.224968E+10 | 0.529594E+09 |
August | 0.179195E+10 | 0.914987E+09 | 0.876964E+09 | 0.187790E+10 | 0.524004E+09 |
September | 0.141232E+10 | 0.677694E+09 | 0.734624E+09 | 0.134826E+10 | 0.667827E+09 |
October | 0.830795E+09 | 0.338506E+09 | 0.492289E+09 | 0.572345E+09 | 0.992374E+09 |
November | 0.400410E+09 | 0.112949E+09 | 0.287461E+09 | 0.129816E+09 | 0.127809E+10 |
December | 0.347856E+09 | 0.119223E+09 | 0.228633E+09 | 0.105801E+09 | 0.165738E+10 |
Annual Sum or Average | 0.137429E+11 | 0.587456E+10 | 0.786837E+10 | 0.114913E+11 | 0.116789E+11 |
Minimum of Months | 0.347856E+09 | 0.109345E+09 | 0.228633E+09 | 88196627.76 | 0.524004E+09 |
Maximum of Months | 0.216589E+10 | 0.113833E+10 | 0.108261E+10 | 0.224968E+10 | 0.165738E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.984313E+09 | 0.00 | 0.984313E+09 | 7982836.22 | 0.602003E+10 |
February | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.147313E+09 | 0.484493E+10 |
March | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.603703E+09 | 0.437374E+10 |
April | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.148401E+10 | 0.332584E+10 |
May | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.250496E+10 | 0.273545E+10 |
June | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.277206E+10 | 0.200269E+10 |
July | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.313237E+10 | 0.184500E+10 |
August | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.273215E+10 | 0.183013E+10 |
September | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.148324E+10 | 0.266409E+10 |
October | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.531629E+09 | 0.381651E+10 |
November | 0.107845E+10 | 0.00 | 0.107845E+10 | 73647402.41 | 0.479244E+10 |
December | 0.836412E+09 | 0.00 | 0.836412E+09 | 3160393.97 | 0.609439E+10 |
Annual Sum or Average | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.154762E+11 | 0.443453E+11 |
Minimum of Months | 0.836412E+09 | 0.00 | 0.836412E+09 | 3160393.97 | 0.183013E+10 |
Maximum of Months | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.313237E+10 | 0.609439E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.222608E+09 | 0.378565E+10 |
February | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.813051E+09 | 0.297240E+10 |
March | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.187702E+10 | 0.268764E+10 |
April | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.362294E+10 | 0.206018E+10 |
May | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.416580E+10 | 0.174447E+10 |
June | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.527082E+10 | 0.131082E+10 |
July | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.531011E+10 | 0.116354E+10 |
August | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.551733E+10 | 0.113433E+10 |
September | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.345221E+10 | 0.162647E+10 |
October | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.181360E+10 | 0.234596E+10 |
November | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.422414E+09 | 0.298054E+10 |
December | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.286929E+09 | 0.382783E+10 |
Annual Sum or Average | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.327748E+11 | 0.276398E+11 |
Minimum of Months | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.222608E+09 | 0.113433E+10 |
Maximum of Months | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.551733E+10 | 0.382783E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.344809E+10 | 0.540461E+10 |
February | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.534116E+10 | 0.445487E+10 |
March | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.631675E+10 | 0.430714E+10 |
April | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.612768E+10 | 0.342766E+10 |
May | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.529267E+10 | 0.287740E+10 |
June | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.453758E+10 | 0.216284E+10 |
July | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.570236E+10 | 0.199552E+10 |
August | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.703639E+10 | 0.193862E+10 |
September | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.777589E+10 | 0.269900E+10 |
October | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.723999E+10 | 0.377199E+10 |
November | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.358996E+10 | 0.443712E+10 |
December | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.410700E+10 | 0.559206E+10 |
Annual Sum or Average | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.665155E+11 | 0.430688E+11 |
Minimum of Months | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.344809E+10 | 0.193862E+10 |
Maximum of Months | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.777589E+10 | 0.559206E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.294401E+09 | 0.388937E+10 |
February | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.923476E+09 | 0.309033E+10 |
March | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.183007E+10 | 0.284198E+10 |
April | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.339458E+10 | 0.225770E+10 |
May | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.506126E+10 | 0.192472E+10 |
June | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.480689E+10 | 0.145610E+10 |
July | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.687741E+10 | 0.139877E+10 |
August | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.579962E+10 | 0.134331E+10 |
September | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.412531E+10 | 0.180882E+10 |
October | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.183652E+10 | 0.250276E+10 |
November | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.459596E+09 | 0.307194E+10 |
December | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.371684E+09 | 0.396380E+10 |
Annual Sum or Average | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.357808E+11 | 0.295496E+11 |
Minimum of Months | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.294401E+09 | 0.134331E+10 |
Maximum of Months | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.687741E+10 | 0.396380E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.984313E+09 | 0.00 | 0.984313E+09 | 19131591.40 | 0.550572E+10 |
February | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.188169E+09 | 0.440625E+10 |
March | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.688790E+09 | 0.400112E+10 |
April | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.155923E+10 | 0.311067E+10 |
May | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.254602E+10 | 0.260776E+10 |
June | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.277332E+10 | 0.195014E+10 |
July | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.312048E+10 | 0.180817E+10 |
August | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.273294E+10 | 0.177392E+10 |
September | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.152227E+10 | 0.251456E+10 |
October | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.614436E+09 | 0.346572E+10 |
November | 0.107845E+10 | 0.00 | 0.107845E+10 | 0.100983E+09 | 0.429329E+10 |
December | 0.836412E+09 | 0.00 | 0.836412E+09 | 11226970.69 | 0.550804E+10 |
Annual Sum or Average | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.158770E+11 | 0.409454E+11 |
Minimum of Months | 0.836412E+09 | 0.00 | 0.836412E+09 | 11226970.69 | 0.177392E+10 |
Maximum of Months | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.312048E+10 | 0.550804E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.243370E+09 | 0.349737E+10 |
February | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.865702E+09 | 0.274410E+10 |
March | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.193378E+10 | 0.250500E+10 |
April | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.366362E+10 | 0.195408E+10 |
May | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.418114E+10 | 0.168580E+10 |
June | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.525597E+10 | 0.129046E+10 |
July | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.529096E+10 | 0.115542E+10 |
August | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.550865E+10 | 0.111369E+10 |
September | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.346909E+10 | 0.155965E+10 |
October | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.186791E+10 | 0.217819E+10 |
November | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.453475E+09 | 0.272692E+10 |
December | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.312112E+09 | 0.350816E+10 |
Annual Sum or Average | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.330458E+11 | 0.259188E+11 |
Minimum of Months | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.243370E+09 | 0.111369E+10 |
Maximum of Months | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.550865E+10 | 0.350816E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.353932E+10 | 0.497053E+10 |
February | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.544953E+10 | 0.410268E+10 |
March | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.639219E+10 | 0.399439E+10 |
April | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.619480E+10 | 0.323462E+10 |
May | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.533820E+10 | 0.275389E+10 |
June | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.454989E+10 | 0.210504E+10 |
July | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.570496E+10 | 0.195820E+10 |
August | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.705018E+10 | 0.187889E+10 |
September | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.781430E+10 | 0.256421E+10 |
October | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.731979E+10 | 0.348572E+10 |
November | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.367824E+10 | 0.405477E+10 |
December | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.419530E+10 | 0.511620E+10 |
Annual Sum or Average | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.672267E+11 | 0.402192E+11 |
Minimum of Months | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.353932E+10 | 0.187889E+10 |
Maximum of Months | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.781430E+10 | 0.511620E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.308050E+09 | 0.361882E+10 |
February | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.956664E+09 | 0.288784E+10 |
March | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.186699E+10 | 0.266632E+10 |
April | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.342727E+10 | 0.214587E+10 |
May | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.507679E+10 | 0.185244E+10 |
June | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.480324E+10 | 0.141895E+10 |
July | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.686632E+10 | 0.137188E+10 |
August | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.580187E+10 | 0.130470E+10 |
September | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.414498E+10 | 0.172948E+10 |
October | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.187548E+10 | 0.233999E+10 |
November | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.481719E+09 | 0.285403E+10 |
December | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.387105E+09 | 0.369152E+10 |
Annual Sum or Average | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.359965E+11 | 0.278818E+11 |
Minimum of Months | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.308050E+09 | 0.130470E+10 |
Maximum of Months | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.686632E+10 | 0.369152E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.66 | 2601.97 | 367.49 | 0.00 | 367.49 | 0.00 | 0.00 |
February | 40.96 | 2299.12 | 571.83 | 0.00 | 571.83 | 0.00 | 0.00 |
March | 185.45 | 1842.03 | 842.50 | 0.00 | 842.50 | 0.00 | 0.00 |
April | 522.38 | 1431.00 | 1192.18 | 4.19 | 1188.00 | 0.00 | 0.00 |
May | 903.47 | 1096.64 | 1533.98 | 45.47 | 1488.52 | 0.00 | 0.00 |
June | 1035.43 | 831.38 | 1612.89 | 106.35 | 1506.54 | 0.00 | 0.00 |
July | 1131.91 | 741.09 | 1532.92 | 120.00 | 1412.92 | 0.00 | 0.00 |
August | 984.96 | 736.10 | 1240.94 | 33.41 | 1207.53 | 0.00 | 0.00 |
September | 547.42 | 1107.59 | 964.02 | 0.28 | 963.74 | 0.00 | 0.00 |
October | 165.56 | 1603.95 | 660.52 | 0.00 | 660.52 | 0.00 | 0.00 |
November | 17.47 | 2150.86 | 416.06 | 0.00 | 416.06 | 0.00 | 0.00 |
December | 0.05 | 2666.50 | 312.27 | 0.00 | 312.27 | 0.00 | 0.00 |
Annual Sum or Average | 464.00 | 1588.87 | 939.11 | 26.00 | 913.11 | 0.00 | 0.00 |
Minimum of Months | 0.05 | 736.10 | 312.27 | 0.00 | 312.27 | 0.00 | 0.00 |
Maximum of Months | 1131.91 | 2666.50 | 1612.89 | 120.00 | 1506.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 74.42 | 1585.74 | 393.70 | 99.83 | 293.87 | 0.00 | 0.00 |
February | 311.26 | 1350.49 | 722.39 | 256.40 | 465.98 | 0.00 | 0.00 |
March | 676.46 | 1092.85 | 1078.57 | 390.47 | 688.10 | 0.00 | 0.00 |
April | 1381.65 | 846.44 | 1672.01 | 694.80 | 977.22 | 0.00 | 0.00 |
May | 1540.22 | 692.21 | 1778.96 | 618.42 | 1160.54 | 0.00 | 0.00 |
June | 2030.96 | 531.51 | 2130.40 | 926.81 | 1203.59 | 0.00 | 0.00 |
July | 1980.18 | 447.40 | 1983.84 | 890.30 | 1093.54 | 0.00 | 0.00 |
August | 2061.05 | 424.89 | 1950.05 | 975.49 | 974.56 | 0.00 | 0.00 |
September | 1319.76 | 668.24 | 1442.00 | 665.15 | 776.85 | 0.00 | 0.00 |
October | 655.78 | 958.63 | 939.78 | 399.32 | 540.46 | 0.00 | 0.00 |
November | 147.75 | 1280.29 | 460.64 | 130.06 | 330.59 | 0.00 | 0.00 |
December | 97.40 | 1586.24 | 377.84 | 121.66 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1026.77 | 953.52 | 1246.48 | 515.19 | 731.29 | 0.00 | 0.00 |
Minimum of Months | 74.42 | 424.89 | 377.84 | 99.83 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 2061.05 | 1586.24 | 2130.40 | 975.49 | 1203.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1276.30 | 2139.28 | 1623.16 | 963.63 | 659.53 | 0.00 | 0.00 |
February | 2196.92 | 1926.36 | 2497.06 | 1545.74 | 951.32 | 0.00 | 0.00 |
March | 2352.13 | 1693.19 | 2687.09 | 1433.49 | 1253.60 | 0.00 | 0.00 |
April | 2350.15 | 1388.44 | 2836.17 | 1231.57 | 1604.59 | 0.00 | 0.00 |
May | 1963.37 | 1116.37 | 2592.74 | 772.15 | 1820.60 | 0.00 | 0.00 |
June | 1727.01 | 877.97 | 2372.09 | 636.62 | 1735.48 | 0.00 | 0.00 |
July | 2107.54 | 775.80 | 2586.80 | 947.13 | 1639.67 | 0.00 | 0.00 |
August | 2612.69 | 741.62 | 2779.46 | 1295.98 | 1483.47 | 0.00 | 0.00 |
September | 3000.83 | 1070.16 | 3080.73 | 1701.71 | 1379.02 | 0.00 | 0.00 |
October | 2705.14 | 1470.53 | 2790.47 | 1723.19 | 1067.28 | 0.00 | 0.00 |
November | 1369.58 | 1823.98 | 1649.05 | 944.90 | 704.15 | 0.00 | 0.00 |
December | 1518.76 | 2228.76 | 1725.15 | 1116.21 | 608.94 | 0.00 | 0.00 |
Annual Sum or Average | 2097.41 | 1435.31 | 2433.95 | 1190.49 | 1243.45 | 0.00 | 0.00 |
Minimum of Months | 1276.30 | 741.62 | 1623.16 | 636.62 | 608.94 | 0.00 | 0.00 |
Maximum of Months | 3000.83 | 2228.76 | 3080.73 | 1723.19 | 1820.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 98.79 | 1681.43 | 415.27 | 122.48 | 292.79 | 0.00 | 0.00 |
February | 344.50 | 1510.71 | 744.52 | 279.83 | 464.69 | 0.00 | 0.00 |
March | 627.54 | 1283.61 | 1043.25 | 352.14 | 691.11 | 0.00 | 0.00 |
April | 1236.00 | 1047.66 | 1587.21 | 606.89 | 980.32 | 0.00 | 0.00 |
May | 1855.01 | 788.92 | 2042.05 | 829.43 | 1212.62 | 0.00 | 0.00 |
June | 1802.38 | 642.07 | 1963.83 | 762.32 | 1201.52 | 0.00 | 0.00 |
July | 2519.83 | 593.19 | 2425.99 | 1275.02 | 1150.96 | 0.00 | 0.00 |
August | 2103.41 | 586.93 | 2007.14 | 1024.86 | 982.27 | 0.00 | 0.00 |
September | 1560.50 | 772.96 | 1634.65 | 784.38 | 850.27 | 0.00 | 0.00 |
October | 641.08 | 1111.54 | 930.56 | 379.16 | 551.41 | 0.00 | 0.00 |
November | 150.25 | 1479.29 | 463.44 | 130.73 | 332.71 | 0.00 | 0.00 |
December | 118.51 | 1856.40 | 389.63 | 133.54 | 256.09 | 0.00 | 0.00 |
Annual Sum or Average | 1093.18 | 1111.02 | 1307.37 | 558.85 | 748.52 | 0.00 | 0.00 |
Minimum of Months | 98.79 | 586.93 | 389.63 | 122.48 | 256.09 | 0.00 | 0.00 |
Maximum of Months | 2519.83 | 1856.40 | 2425.99 | 1275.02 | 1212.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.98 | 2247.62 | 367.50 | 0.00 | 367.50 | 0.00 | 0.00 |
February | 60.89 | 2002.70 | 571.84 | 0.00 | 571.84 | 0.00 | 0.00 |
March | 225.40 | 1632.97 | 842.52 | 0.00 | 842.52 | 0.00 | 0.00 |
April | 572.53 | 1283.12 | 1192.20 | 4.19 | 1188.02 | 0.00 | 0.00 |
May | 935.25 | 1021.30 | 1534.01 | 45.47 | 1488.54 | 0.00 | 0.00 |
June | 1069.47 | 772.64 | 1612.92 | 106.35 | 1506.57 | 0.00 | 0.00 |
July | 1169.49 | 688.84 | 1532.95 | 120.00 | 1412.95 | 0.00 | 0.00 |
August | 1020.07 | 683.29 | 1240.96 | 33.41 | 1207.55 | 0.00 | 0.00 |
September | 572.24 | 1027.81 | 964.03 | 0.28 | 963.76 | 0.00 | 0.00 |
October | 198.49 | 1424.92 | 660.53 | 0.00 | 660.53 | 0.00 | 0.00 |
November | 28.41 | 1848.94 | 416.07 | 0.00 | 416.07 | 0.00 | 0.00 |
December | 1.18 | 2275.39 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Annual Sum or Average | 490.75 | 1406.18 | 939.13 | 26.00 | 913.13 | 0.00 | 0.00 |
Minimum of Months | 1.18 | 683.29 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Maximum of Months | 1169.49 | 2275.39 | 1612.92 | 120.00 | 1506.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 83.11 | 1413.40 | 393.70 | 99.83 | 293.87 | 0.00 | 0.00 |
February | 336.08 | 1228.67 | 722.38 | 256.40 | 465.98 | 0.00 | 0.00 |
March | 700.80 | 1003.45 | 1078.57 | 390.47 | 688.10 | 0.00 | 0.00 |
April | 1397.74 | 794.82 | 1672.01 | 694.79 | 977.21 | 0.00 | 0.00 |
May | 1555.33 | 651.31 | 1778.95 | 618.42 | 1160.53 | 0.00 | 0.00 |
June | 2033.50 | 505.72 | 2130.39 | 926.80 | 1203.59 | 0.00 | 0.00 |
July | 1982.57 | 434.41 | 1983.83 | 890.29 | 1093.53 | 0.00 | 0.00 |
August | 2059.93 | 423.51 | 1950.04 | 975.49 | 974.56 | 0.00 | 0.00 |
September | 1331.87 | 627.50 | 1441.99 | 665.15 | 776.84 | 0.00 | 0.00 |
October | 677.12 | 875.88 | 939.78 | 399.32 | 540.46 | 0.00 | 0.00 |
November | 162.97 | 1149.90 | 460.64 | 130.05 | 330.59 | 0.00 | 0.00 |
December | 107.13 | 1429.15 | 377.84 | 121.65 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1039.28 | 876.45 | 1246.47 | 515.19 | 731.28 | 0.00 | 0.00 |
Minimum of Months | 83.11 | 423.51 | 377.84 | 99.83 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 2059.93 | 1429.15 | 2130.39 | 975.49 | 1203.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1287.37 | 2017.85 | 1623.21 | 963.66 | 659.55 | 0.00 | 0.00 |
February | 2207.82 | 1841.46 | 2497.13 | 1545.79 | 951.34 | 0.00 | 0.00 |
March | 2358.40 | 1608.10 | 2687.17 | 1433.54 | 1253.63 | 0.00 | 0.00 |
April | 2364.08 | 1322.40 | 2836.25 | 1231.61 | 1604.63 | 0.00 | 0.00 |
May | 1976.06 | 1074.30 | 2592.81 | 772.17 | 1820.64 | 0.00 | 0.00 |
June | 1750.61 | 834.43 | 2372.15 | 636.64 | 1735.51 | 0.00 | 0.00 |
July | 2129.02 | 745.04 | 2586.86 | 947.16 | 1639.70 | 0.00 | 0.00 |
August | 2627.09 | 723.80 | 2779.53 | 1296.03 | 1483.50 | 0.00 | 0.00 |
September | 2999.96 | 1041.28 | 3080.82 | 1701.77 | 1379.05 | 0.00 | 0.00 |
October | 2703.10 | 1408.30 | 2790.56 | 1723.25 | 1067.31 | 0.00 | 0.00 |
November | 1385.01 | 1711.85 | 1649.10 | 944.93 | 704.17 | 0.00 | 0.00 |
December | 1533.38 | 2087.84 | 1725.20 | 1116.24 | 608.96 | 0.00 | 0.00 |
Annual Sum or Average | 2109.19 | 1365.70 | 2434.01 | 1190.53 | 1243.48 | 0.00 | 0.00 |
Minimum of Months | 1287.37 | 723.80 | 1623.21 | 636.64 | 608.96 | 0.00 | 0.00 |
Maximum of Months | 2999.96 | 2087.84 | 3080.82 | 1723.25 | 1820.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 109.92 | 1452.12 | 415.27 | 122.47 | 292.79 | 0.00 | 0.00 |
February | 381.73 | 1277.42 | 744.52 | 279.83 | 464.69 | 0.00 | 0.00 |
March | 683.27 | 1061.07 | 1043.24 | 352.14 | 691.10 | 0.00 | 0.00 |
April | 1309.64 | 871.03 | 1587.21 | 606.89 | 980.32 | 0.00 | 0.00 |
May | 1889.66 | 718.61 | 2042.04 | 829.43 | 1212.61 | 0.00 | 0.00 |
June | 1854.51 | 561.77 | 1963.83 | 762.31 | 1201.51 | 0.00 | 0.00 |
July | 2567.73 | 522.24 | 2425.98 | 1275.02 | 1150.96 | 0.00 | 0.00 |
August | 2165.33 | 501.54 | 2007.13 | 1024.86 | 982.27 | 0.00 | 0.00 |
September | 1591.56 | 697.85 | 1634.64 | 784.37 | 850.27 | 0.00 | 0.00 |
October | 685.68 | 934.42 | 930.56 | 379.15 | 551.40 | 0.00 | 0.00 |
November | 177.31 | 1185.16 | 463.44 | 130.73 | 332.71 | 0.00 | 0.00 |
December | 138.77 | 1479.91 | 389.63 | 133.54 | 256.09 | 0.00 | 0.00 |
Annual Sum or Average | 1134.60 | 937.01 | 1307.37 | 558.85 | 748.52 | 0.00 | 0.00 |
Minimum of Months | 109.92 | 501.54 | 389.63 | 122.47 | 256.09 | 0.00 | 0.00 |
Maximum of Months | 2567.73 | 1479.91 | 2425.98 | 1275.02 | 1212.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 7.14 | 2055.60 | 367.50 | 0.00 | 367.50 | 0.00 | 0.00 |
February | 77.78 | 1821.37 | 571.84 | 0.00 | 571.84 | 0.00 | 0.00 |
March | 257.16 | 1493.85 | 842.52 | 0.00 | 842.52 | 0.00 | 0.00 |
April | 601.55 | 1200.10 | 1192.20 | 4.19 | 1188.02 | 0.00 | 0.00 |
May | 950.58 | 973.63 | 1534.01 | 45.47 | 1488.54 | 0.00 | 0.00 |
June | 1069.95 | 752.37 | 1612.92 | 106.35 | 1506.57 | 0.00 | 0.00 |
July | 1165.05 | 675.09 | 1532.95 | 120.00 | 1412.95 | 0.00 | 0.00 |
August | 1020.36 | 662.31 | 1240.96 | 33.41 | 1207.55 | 0.00 | 0.00 |
September | 587.29 | 970.12 | 964.03 | 0.28 | 963.76 | 0.00 | 0.00 |
October | 229.40 | 1293.95 | 660.53 | 0.00 | 660.53 | 0.00 | 0.00 |
November | 38.96 | 1656.36 | 416.07 | 0.00 | 416.07 | 0.00 | 0.00 |
December | 4.19 | 2056.47 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Annual Sum or Average | 503.46 | 1298.37 | 939.13 | 26.00 | 913.13 | 0.00 | 0.00 |
Minimum of Months | 4.19 | 662.31 | 312.28 | 0.00 | 312.28 | 0.00 | 0.00 |
Maximum of Months | 1165.05 | 2056.47 | 1612.92 | 120.00 | 1506.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 90.86 | 1305.77 | 393.70 | 99.83 | 293.87 | 0.00 | 0.00 |
February | 357.85 | 1134.30 | 722.38 | 256.40 | 465.98 | 0.00 | 0.00 |
March | 721.99 | 935.26 | 1078.57 | 390.47 | 688.10 | 0.00 | 0.00 |
April | 1413.43 | 753.89 | 1672.01 | 694.79 | 977.21 | 0.00 | 0.00 |
May | 1561.06 | 629.40 | 1778.95 | 618.42 | 1160.53 | 0.00 | 0.00 |
June | 2027.77 | 497.86 | 2130.39 | 926.80 | 1203.59 | 0.00 | 0.00 |
July | 1975.42 | 431.39 | 1983.83 | 890.29 | 1093.53 | 0.00 | 0.00 |
August | 2056.69 | 415.80 | 1950.04 | 975.49 | 974.56 | 0.00 | 0.00 |
September | 1338.38 | 601.72 | 1441.99 | 665.15 | 776.84 | 0.00 | 0.00 |
October | 697.40 | 813.24 | 939.78 | 399.32 | 540.46 | 0.00 | 0.00 |
November | 174.95 | 1052.05 | 460.64 | 130.05 | 330.59 | 0.00 | 0.00 |
December | 116.53 | 1309.80 | 377.84 | 121.65 | 256.19 | 0.00 | 0.00 |
Annual Sum or Average | 1047.87 | 821.88 | 1246.47 | 515.19 | 731.28 | 0.00 | 0.00 |
Minimum of Months | 90.86 | 415.80 | 377.84 | 99.83 | 256.19 | 0.00 | 0.00 |
Maximum of Months | 2056.69 | 1309.80 | 2130.39 | 975.49 | 1203.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1321.43 | 1855.78 | 1623.21 | 963.66 | 659.55 | 0.00 | 0.00 |
February | 2252.62 | 1695.88 | 2497.13 | 1545.79 | 951.34 | 0.00 | 0.00 |
March | 2386.57 | 1491.33 | 2687.17 | 1433.54 | 1253.63 | 0.00 | 0.00 |
April | 2389.97 | 1247.93 | 2836.25 | 1231.61 | 1604.63 | 0.00 | 0.00 |
May | 1993.05 | 1028.19 | 2592.81 | 772.17 | 1820.64 | 0.00 | 0.00 |
June | 1755.36 | 812.13 | 2372.15 | 636.64 | 1735.51 | 0.00 | 0.00 |
July | 2129.99 | 731.11 | 2586.86 | 947.16 | 1639.70 | 0.00 | 0.00 |
August | 2632.23 | 701.50 | 2779.53 | 1296.03 | 1483.50 | 0.00 | 0.00 |
September | 3014.78 | 989.28 | 3080.82 | 1701.77 | 1379.05 | 0.00 | 0.00 |
October | 2732.90 | 1301.42 | 2790.56 | 1723.25 | 1067.31 | 0.00 | 0.00 |
November | 1419.07 | 1564.34 | 1649.10 | 944.93 | 704.17 | 0.00 | 0.00 |
December | 1566.35 | 1910.17 | 1725.20 | 1116.24 | 608.96 | 0.00 | 0.00 |
Annual Sum or Average | 2131.74 | 1275.34 | 2434.01 | 1190.53 | 1243.48 | 0.00 | 0.00 |
Minimum of Months | 1321.43 | 701.50 | 1623.21 | 636.64 | 608.96 | 0.00 | 0.00 |
Maximum of Months | 3014.78 | 1910.17 | 3080.82 | 1723.25 | 1820.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 115.01 | 1351.11 | 415.27 | 122.47 | 292.79 | 0.00 | 0.00 |
February | 395.45 | 1193.72 | 744.52 | 279.83 | 464.69 | 0.00 | 0.00 |
March | 697.05 | 995.49 | 1043.24 | 352.14 | 691.10 | 0.00 | 0.00 |
April | 1322.25 | 827.88 | 1587.21 | 606.89 | 980.32 | 0.00 | 0.00 |
May | 1895.45 | 691.62 | 2042.04 | 829.43 | 1212.61 | 0.00 | 0.00 |
June | 1853.10 | 547.43 | 1963.83 | 762.31 | 1201.51 | 0.00 | 0.00 |
July | 2563.59 | 512.20 | 2425.98 | 1275.02 | 1150.96 | 0.00 | 0.00 |
August | 2166.17 | 487.12 | 2007.13 | 1024.86 | 982.27 | 0.00 | 0.00 |
September | 1599.14 | 667.24 | 1634.64 | 784.37 | 850.27 | 0.00 | 0.00 |
October | 700.22 | 873.65 | 930.56 | 379.15 | 551.40 | 0.00 | 0.00 |
November | 185.85 | 1101.09 | 463.44 | 130.73 | 332.71 | 0.00 | 0.00 |
December | 144.53 | 1378.26 | 389.63 | 133.54 | 256.09 | 0.00 | 0.00 |
Annual Sum or Average | 1141.44 | 884.13 | 1307.37 | 558.85 | 748.52 | 0.00 | 0.00 |
Minimum of Months | 115.01 | 487.12 | 389.63 | 122.47 | 256.09 | 0.00 | 0.00 |
Maximum of Months | 2563.59 | 1378.26 | 2425.98 | 1275.02 | 1212.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1765659.90 | 0.696912E+10 | 0.984292E+09 | 0.00 | 0.984292E+09 | 0.00 | 0.00 |
February | 99093302.72 | 0.556202E+10 | 0.138337E+10 | 0.00 | 0.138337E+10 | 0.00 | 0.00 |
March | 0.496710E+09 | 0.493370E+10 | 0.225655E+10 | 0.00 | 0.225655E+10 | 0.00 | 0.00 |
April | 0.135402E+10 | 0.370914E+10 | 0.309013E+10 | 10850937.75 | 0.307928E+10 | 0.00 | 0.00 |
May | 0.241984E+10 | 0.293724E+10 | 0.410862E+10 | 0.121776E+09 | 0.398685E+10 | 0.00 | 0.00 |
June | 0.268382E+10 | 0.215494E+10 | 0.418062E+10 | 0.275658E+09 | 0.390496E+10 | 0.00 | 0.00 |
July | 0.303170E+10 | 0.198492E+10 | 0.410578E+10 | 0.321401E+09 | 0.378438E+10 | 0.00 | 0.00 |
August | 0.263811E+10 | 0.197158E+10 | 0.332374E+10 | 89491720.40 | 0.323424E+10 | 0.00 | 0.00 |
September | 0.141892E+10 | 0.287087E+10 | 0.249873E+10 | 712957.55 | 0.249801E+10 | 0.00 | 0.00 |
October | 0.443439E+09 | 0.429603E+10 | 0.176913E+10 | 0.00 | 0.176913E+10 | 0.00 | 0.00 |
November | 45287785.35 | 0.557503E+10 | 0.107843E+10 | 0.00 | 0.107843E+10 | 0.00 | 0.00 |
December | 133711.92 | 0.714195E+10 | 0.836394E+09 | 0.00 | 0.836394E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.146328E+11 | 0.501065E+11 | 0.296158E+11 | 0.819890E+09 | 0.287959E+11 | 0.00 | 0.00 |
Minimum of Months | 133711.92 | 0.197158E+10 | 0.836394E+09 | 0.00 | 0.836394E+09 | 0.00 | 0.00 |
Maximum of Months | 0.303170E+10 | 0.714195E+10 | 0.418062E+10 | 0.321401E+09 | 0.398685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.199326E+09 | 0.424725E+10 | 0.105449E+10 | 0.267389E+09 | 0.787102E+09 | 0.00 | 0.00 |
February | 0.753001E+09 | 0.326711E+10 | 0.174760E+10 | 0.620290E+09 | 0.112731E+10 | 0.00 | 0.00 |
March | 0.181184E+10 | 0.292709E+10 | 0.288885E+10 | 0.104583E+10 | 0.184301E+10 | 0.00 | 0.00 |
April | 0.358124E+10 | 0.219396E+10 | 0.433386E+10 | 0.180091E+10 | 0.253295E+10 | 0.00 | 0.00 |
May | 0.412532E+10 | 0.185402E+10 | 0.476476E+10 | 0.165638E+10 | 0.310838E+10 | 0.00 | 0.00 |
June | 0.526425E+10 | 0.137768E+10 | 0.552199E+10 | 0.240228E+10 | 0.311971E+10 | 0.00 | 0.00 |
July | 0.530372E+10 | 0.119832E+10 | 0.531351E+10 | 0.238457E+10 | 0.292894E+10 | 0.00 | 0.00 |
August | 0.552032E+10 | 0.113802E+10 | 0.522302E+10 | 0.261276E+10 | 0.261026E+10 | 0.00 | 0.00 |
September | 0.342081E+10 | 0.173208E+10 | 0.373766E+10 | 0.172408E+10 | 0.201359E+10 | 0.00 | 0.00 |
October | 0.175645E+10 | 0.256758E+10 | 0.251711E+10 | 0.106953E+10 | 0.144758E+10 | 0.00 | 0.00 |
November | 0.382964E+09 | 0.331851E+10 | 0.119399E+10 | 0.337103E+09 | 0.856888E+09 | 0.00 | 0.00 |
December | 0.260887E+09 | 0.424858E+10 | 0.101202E+10 | 0.325841E+09 | 0.686176E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.323801E+11 | 0.300702E+11 | 0.393089E+11 | 0.162470E+11 | 0.230619E+11 | 0.00 | 0.00 |
Minimum of Months | 0.199326E+09 | 0.113802E+10 | 0.101202E+10 | 0.267389E+09 | 0.686176E+09 | 0.00 | 0.00 |
Maximum of Months | 0.552032E+10 | 0.424858E+10 | 0.552199E+10 | 0.261276E+10 | 0.311971E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.341843E+10 | 0.572984E+10 | 0.434749E+10 | 0.258099E+10 | 0.176650E+10 | 0.00 | 0.00 |
February | 0.531478E+10 | 0.466025E+10 | 0.604088E+10 | 0.373945E+10 | 0.230142E+10 | 0.00 | 0.00 |
March | 0.629996E+10 | 0.453503E+10 | 0.719711E+10 | 0.383946E+10 | 0.335765E+10 | 0.00 | 0.00 |
April | 0.609159E+10 | 0.359885E+10 | 0.735135E+10 | 0.319224E+10 | 0.415911E+10 | 0.00 | 0.00 |
May | 0.525869E+10 | 0.299009E+10 | 0.694441E+10 | 0.206812E+10 | 0.487629E+10 | 0.00 | 0.00 |
June | 0.447640E+10 | 0.227570E+10 | 0.614847E+10 | 0.165011E+10 | 0.449835E+10 | 0.00 | 0.00 |
July | 0.564483E+10 | 0.207791E+10 | 0.692849E+10 | 0.253680E+10 | 0.439169E+10 | 0.00 | 0.00 |
August | 0.699782E+10 | 0.198635E+10 | 0.744449E+10 | 0.347117E+10 | 0.397333E+10 | 0.00 | 0.00 |
September | 0.777816E+10 | 0.277386E+10 | 0.798525E+10 | 0.441083E+10 | 0.357441E+10 | 0.00 | 0.00 |
October | 0.724543E+10 | 0.393867E+10 | 0.747400E+10 | 0.461539E+10 | 0.285861E+10 | 0.00 | 0.00 |
November | 0.354995E+10 | 0.472775E+10 | 0.427434E+10 | 0.244918E+10 | 0.182515E+10 | 0.00 | 0.00 |
December | 0.406783E+10 | 0.596950E+10 | 0.462063E+10 | 0.298965E+10 | 0.163099E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.661439E+11 | 0.452638E+11 | 0.767569E+11 | 0.375434E+11 | 0.392135E+11 | 0.00 | 0.00 |
Minimum of Months | 0.341843E+10 | 0.198635E+10 | 0.427434E+10 | 0.165011E+10 | 0.163099E+10 | 0.00 | 0.00 |
Maximum of Months | 0.777816E+10 | 0.596950E+10 | 0.798525E+10 | 0.461539E+10 | 0.487629E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.264593E+09 | 0.450353E+10 | 0.111225E+10 | 0.328038E+09 | 0.784214E+09 | 0.00 | 0.00 |
February | 0.833420E+09 | 0.365470E+10 | 0.180115E+10 | 0.676970E+09 | 0.112418E+10 | 0.00 | 0.00 |
March | 0.168082E+10 | 0.343801E+10 | 0.279423E+10 | 0.943177E+09 | 0.185106E+10 | 0.00 | 0.00 |
April | 0.320371E+10 | 0.271554E+10 | 0.411405E+10 | 0.157307E+10 | 0.254099E+10 | 0.00 | 0.00 |
May | 0.496847E+10 | 0.211305E+10 | 0.546942E+10 | 0.222155E+10 | 0.324788E+10 | 0.00 | 0.00 |
June | 0.467176E+10 | 0.166425E+10 | 0.509026E+10 | 0.197592E+10 | 0.311434E+10 | 0.00 | 0.00 |
July | 0.674912E+10 | 0.158880E+10 | 0.649776E+10 | 0.341502E+10 | 0.308274E+10 | 0.00 | 0.00 |
August | 0.563378E+10 | 0.157203E+10 | 0.537592E+10 | 0.274499E+10 | 0.263092E+10 | 0.00 | 0.00 |
September | 0.404483E+10 | 0.200350E+10 | 0.423701E+10 | 0.203311E+10 | 0.220390E+10 | 0.00 | 0.00 |
October | 0.171706E+10 | 0.297716E+10 | 0.249242E+10 | 0.101553E+10 | 0.147689E+10 | 0.00 | 0.00 |
November | 0.389452E+09 | 0.383433E+10 | 0.120125E+10 | 0.338851E+09 | 0.862395E+09 | 0.00 | 0.00 |
December | 0.317406E+09 | 0.497219E+10 | 0.104358E+10 | 0.357672E+09 | 0.685907E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.344744E+11 | 0.350371E+11 | 0.412293E+11 | 0.176239E+11 | 0.236054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.264593E+09 | 0.157203E+10 | 0.104358E+10 | 0.328038E+09 | 0.685907E+09 | 0.00 | 0.00 |
Maximum of Months | 0.674912E+10 | 0.497219E+10 | 0.649776E+10 | 0.341502E+10 | 0.324788E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7982836.22 | 0.602003E+10 | 0.984313E+09 | 0.00 | 0.984313E+09 | 0.00 | 0.00 |
February | 0.147313E+09 | 0.484493E+10 | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.00 | 0.00 |
March | 0.603703E+09 | 0.437374E+10 | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.00 | 0.00 |
April | 0.148401E+10 | 0.332584E+10 | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.00 | 0.00 |
May | 0.250496E+10 | 0.273545E+10 | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.00 | 0.00 |
June | 0.277206E+10 | 0.200269E+10 | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.00 | 0.00 |
July | 0.313237E+10 | 0.184500E+10 | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.00 | 0.00 |
August | 0.273215E+10 | 0.183013E+10 | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.00 | 0.00 |
September | 0.148324E+10 | 0.266409E+10 | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.00 | 0.00 |
October | 0.531629E+09 | 0.381651E+10 | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.00 | 0.00 |
November | 73647402.41 | 0.479244E+10 | 0.107845E+10 | 0.00 | 0.107845E+10 | 0.00 | 0.00 |
December | 3160393.97 | 0.609439E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.154762E+11 | 0.443453E+11 | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.00 | 0.00 |
Minimum of Months | 3160393.97 | 0.183013E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.313237E+10 | 0.609439E+10 | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.222608E+09 | 0.378565E+10 | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.00 | 0.00 |
February | 0.813051E+09 | 0.297240E+10 | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.00 | 0.00 |
March | 0.187702E+10 | 0.268764E+10 | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.00 | 0.00 |
April | 0.362294E+10 | 0.206018E+10 | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.00 | 0.00 |
May | 0.416580E+10 | 0.174447E+10 | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.00 | 0.00 |
June | 0.527082E+10 | 0.131082E+10 | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.00 | 0.00 |
July | 0.531011E+10 | 0.116354E+10 | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.00 | 0.00 |
August | 0.551733E+10 | 0.113433E+10 | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.00 | 0.00 |
September | 0.345221E+10 | 0.162647E+10 | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.00 | 0.00 |
October | 0.181360E+10 | 0.234596E+10 | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.00 | 0.00 |
November | 0.422414E+09 | 0.298054E+10 | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.00 | 0.00 |
December | 0.286929E+09 | 0.382783E+10 | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.327748E+11 | 0.276398E+11 | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.222608E+09 | 0.113433E+10 | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.00 | 0.00 |
Maximum of Months | 0.551733E+10 | 0.382783E+10 | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.344809E+10 | 0.540461E+10 | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.00 | 0.00 |
February | 0.534116E+10 | 0.445487E+10 | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.00 | 0.00 |
March | 0.631675E+10 | 0.430714E+10 | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.00 | 0.00 |
April | 0.612768E+10 | 0.342766E+10 | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.00 | 0.00 |
May | 0.529267E+10 | 0.287740E+10 | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.00 | 0.00 |
June | 0.453758E+10 | 0.216284E+10 | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.00 | 0.00 |
July | 0.570236E+10 | 0.199552E+10 | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.00 | 0.00 |
August | 0.703639E+10 | 0.193862E+10 | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.00 | 0.00 |
September | 0.777589E+10 | 0.269900E+10 | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.00 | 0.00 |
October | 0.723999E+10 | 0.377199E+10 | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.00 | 0.00 |
November | 0.358996E+10 | 0.443712E+10 | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.00 | 0.00 |
December | 0.410700E+10 | 0.559206E+10 | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.665155E+11 | 0.430688E+11 | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.344809E+10 | 0.193862E+10 | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.00 | 0.00 |
Maximum of Months | 0.777589E+10 | 0.559206E+10 | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.294401E+09 | 0.388937E+10 | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.00 | 0.00 |
February | 0.923476E+09 | 0.309033E+10 | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.00 | 0.00 |
March | 0.183007E+10 | 0.284198E+10 | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.00 | 0.00 |
April | 0.339458E+10 | 0.225770E+10 | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.00 | 0.00 |
May | 0.506126E+10 | 0.192472E+10 | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.00 | 0.00 |
June | 0.480689E+10 | 0.145610E+10 | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.00 | 0.00 |
July | 0.687741E+10 | 0.139877E+10 | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.00 | 0.00 |
August | 0.579962E+10 | 0.134331E+10 | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.00 | 0.00 |
September | 0.412531E+10 | 0.180882E+10 | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.00 | 0.00 |
October | 0.183652E+10 | 0.250276E+10 | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.00 | 0.00 |
November | 0.459596E+09 | 0.307194E+10 | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.00 | 0.00 |
December | 0.371684E+09 | 0.396380E+10 | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357808E+11 | 0.295496E+11 | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.294401E+09 | 0.134331E+10 | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.687741E+10 | 0.396380E+10 | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 19131591.40 | 0.550572E+10 | 0.984313E+09 | 0.00 | 0.984313E+09 | 0.00 | 0.00 |
February | 0.188169E+09 | 0.440625E+10 | 0.138340E+10 | 0.00 | 0.138340E+10 | 0.00 | 0.00 |
March | 0.688790E+09 | 0.400112E+10 | 0.225660E+10 | 0.00 | 0.225660E+10 | 0.00 | 0.00 |
April | 0.155923E+10 | 0.311067E+10 | 0.309019E+10 | 10851261.36 | 0.307934E+10 | 0.00 | 0.00 |
May | 0.254602E+10 | 0.260776E+10 | 0.410870E+10 | 0.121779E+09 | 0.398692E+10 | 0.00 | 0.00 |
June | 0.277332E+10 | 0.195014E+10 | 0.418069E+10 | 0.275667E+09 | 0.390503E+10 | 0.00 | 0.00 |
July | 0.312048E+10 | 0.180817E+10 | 0.410585E+10 | 0.321410E+09 | 0.378444E+10 | 0.00 | 0.00 |
August | 0.273294E+10 | 0.177392E+10 | 0.332379E+10 | 89494389.29 | 0.323430E+10 | 0.00 | 0.00 |
September | 0.152227E+10 | 0.251456E+10 | 0.249877E+10 | 712978.81 | 0.249806E+10 | 0.00 | 0.00 |
October | 0.614436E+09 | 0.346572E+10 | 0.176916E+10 | 0.00 | 0.176916E+10 | 0.00 | 0.00 |
November | 0.100983E+09 | 0.429329E+10 | 0.107845E+10 | 0.00 | 0.107845E+10 | 0.00 | 0.00 |
December | 11226970.69 | 0.550804E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.158770E+11 | 0.409454E+11 | 0.296163E+11 | 0.819915E+09 | 0.287964E+11 | 0.00 | 0.00 |
Minimum of Months | 11226970.69 | 0.177392E+10 | 0.836412E+09 | 0.00 | 0.836412E+09 | 0.00 | 0.00 |
Maximum of Months | 0.312048E+10 | 0.550804E+10 | 0.418069E+10 | 0.321410E+09 | 0.398692E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.243370E+09 | 0.349737E+10 | 0.105449E+10 | 0.267388E+09 | 0.787099E+09 | 0.00 | 0.00 |
February | 0.865702E+09 | 0.274410E+10 | 0.174759E+10 | 0.620287E+09 | 0.112730E+10 | 0.00 | 0.00 |
March | 0.193378E+10 | 0.250500E+10 | 0.288883E+10 | 0.104583E+10 | 0.184301E+10 | 0.00 | 0.00 |
April | 0.366362E+10 | 0.195408E+10 | 0.433384E+10 | 0.180090E+10 | 0.253294E+10 | 0.00 | 0.00 |
May | 0.418114E+10 | 0.168580E+10 | 0.476474E+10 | 0.165638E+10 | 0.310837E+10 | 0.00 | 0.00 |
June | 0.525597E+10 | 0.129046E+10 | 0.552196E+10 | 0.240227E+10 | 0.311969E+10 | 0.00 | 0.00 |
July | 0.529096E+10 | 0.115542E+10 | 0.531349E+10 | 0.238456E+10 | 0.292892E+10 | 0.00 | 0.00 |
August | 0.550865E+10 | 0.111369E+10 | 0.522300E+10 | 0.261275E+10 | 0.261025E+10 | 0.00 | 0.00 |
September | 0.346909E+10 | 0.155965E+10 | 0.373765E+10 | 0.172407E+10 | 0.201358E+10 | 0.00 | 0.00 |
October | 0.186791E+10 | 0.217819E+10 | 0.251710E+10 | 0.106953E+10 | 0.144757E+10 | 0.00 | 0.00 |
November | 0.453475E+09 | 0.272692E+10 | 0.119399E+10 | 0.337102E+09 | 0.856885E+09 | 0.00 | 0.00 |
December | 0.312112E+09 | 0.350816E+10 | 0.101201E+10 | 0.325839E+09 | 0.686173E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.330458E+11 | 0.259188E+11 | 0.393087E+11 | 0.162469E+11 | 0.230618E+11 | 0.00 | 0.00 |
Minimum of Months | 0.243370E+09 | 0.111369E+10 | 0.101201E+10 | 0.267388E+09 | 0.686173E+09 | 0.00 | 0.00 |
Maximum of Months | 0.550865E+10 | 0.350816E+10 | 0.552196E+10 | 0.261275E+10 | 0.311969E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.353932E+10 | 0.497053E+10 | 0.434762E+10 | 0.258107E+10 | 0.176654E+10 | 0.00 | 0.00 |
February | 0.544953E+10 | 0.410268E+10 | 0.604106E+10 | 0.373958E+10 | 0.230149E+10 | 0.00 | 0.00 |
March | 0.639219E+10 | 0.399439E+10 | 0.719732E+10 | 0.383958E+10 | 0.335773E+10 | 0.00 | 0.00 |
April | 0.619480E+10 | 0.323462E+10 | 0.735155E+10 | 0.319234E+10 | 0.415921E+10 | 0.00 | 0.00 |
May | 0.533820E+10 | 0.275389E+10 | 0.694458E+10 | 0.206818E+10 | 0.487640E+10 | 0.00 | 0.00 |
June | 0.454989E+10 | 0.210504E+10 | 0.614862E+10 | 0.165017E+10 | 0.449845E+10 | 0.00 | 0.00 |
July | 0.570496E+10 | 0.195820E+10 | 0.692866E+10 | 0.253688E+10 | 0.439178E+10 | 0.00 | 0.00 |
August | 0.705018E+10 | 0.187889E+10 | 0.744469E+10 | 0.347128E+10 | 0.397341E+10 | 0.00 | 0.00 |
September | 0.781430E+10 | 0.256421E+10 | 0.798548E+10 | 0.441098E+10 | 0.357450E+10 | 0.00 | 0.00 |
October | 0.731979E+10 | 0.348572E+10 | 0.747423E+10 | 0.461554E+10 | 0.285868E+10 | 0.00 | 0.00 |
November | 0.367824E+10 | 0.405477E+10 | 0.427447E+10 | 0.244926E+10 | 0.182520E+10 | 0.00 | 0.00 |
December | 0.419530E+10 | 0.511620E+10 | 0.462078E+10 | 0.298974E+10 | 0.163103E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.672267E+11 | 0.402192E+11 | 0.767590E+11 | 0.375446E+11 | 0.392144E+11 | 0.00 | 0.00 |
Minimum of Months | 0.353932E+10 | 0.187889E+10 | 0.427447E+10 | 0.165017E+10 | 0.163103E+10 | 0.00 | 0.00 |
Maximum of Months | 0.781430E+10 | 0.511620E+10 | 0.798548E+10 | 0.461554E+10 | 0.487640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.308050E+09 | 0.361882E+10 | 0.111225E+10 | 0.328036E+09 | 0.784211E+09 | 0.00 | 0.00 |
February | 0.956664E+09 | 0.288784E+10 | 0.180114E+10 | 0.676967E+09 | 0.112417E+10 | 0.00 | 0.00 |
March | 0.186699E+10 | 0.266632E+10 | 0.279422E+10 | 0.943173E+09 | 0.185105E+10 | 0.00 | 0.00 |
April | 0.342727E+10 | 0.214587E+10 | 0.411404E+10 | 0.157306E+10 | 0.254098E+10 | 0.00 | 0.00 |
May | 0.507679E+10 | 0.185244E+10 | 0.546940E+10 | 0.222154E+10 | 0.324786E+10 | 0.00 | 0.00 |
June | 0.480324E+10 | 0.141895E+10 | 0.509024E+10 | 0.197591E+10 | 0.311432E+10 | 0.00 | 0.00 |
July | 0.686632E+10 | 0.137188E+10 | 0.649773E+10 | 0.341501E+10 | 0.308273E+10 | 0.00 | 0.00 |
August | 0.580187E+10 | 0.130470E+10 | 0.537590E+10 | 0.274498E+10 | 0.263091E+10 | 0.00 | 0.00 |
September | 0.414498E+10 | 0.172948E+10 | 0.423699E+10 | 0.203310E+10 | 0.220389E+10 | 0.00 | 0.00 |
October | 0.187548E+10 | 0.233999E+10 | 0.249241E+10 | 0.101553E+10 | 0.147688E+10 | 0.00 | 0.00 |
November | 0.481719E+09 | 0.285403E+10 | 0.120124E+10 | 0.338849E+09 | 0.862391E+09 | 0.00 | 0.00 |
December | 0.387105E+09 | 0.369152E+10 | 0.104358E+10 | 0.357671E+09 | 0.685904E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.359965E+11 | 0.278818E+11 | 0.412291E+11 | 0.176238E+11 | 0.236053E+11 | 0.00 | 0.00 |
Minimum of Months | 0.308050E+09 | 0.130470E+10 | 0.104358E+10 | 0.328036E+09 | 0.685904E+09 | 0.00 | 0.00 |
Maximum of Months | 0.686632E+10 | 0.369152E+10 | 0.649773E+10 | 0.341501E+10 | 0.324786E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.284319E+11 | -.379375E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121288E+10 | 65.18 | 0.00 | 0.00 |
February | 0.261542E+11 | -.347195E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.109243E+10 | 65.08 | 0.00 | 0.00 |
March | 0.309484E+11 | -.403579E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.118325E+10 | 64.16 | 0.00 | 0.00 |
April | 0.263399E+11 | -.356099E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.116292E+10 | 64.91 | 0.00 | 0.00 |
May | 0.270227E+11 | -.365975E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121495E+10 | 65.29 | 0.00 | 0.00 |
June | 0.256122E+11 | -.349142E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.116729E+10 | 64.99 | 0.00 | 0.00 |
July | 0.225234E+11 | -.323032E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.123477E+10 | 66.10 | 0.00 | 0.00 |
August | 0.253855E+11 | -.350497E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120909E+10 | 65.11 | 0.00 | 0.00 |
September | 0.228072E+11 | -.322319E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.118455E+10 | 65.67 | 0.00 | 0.00 |
October | 0.246290E+11 | -.343074E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122896E+10 | 65.86 | 0.00 | 0.00 |
November | 0.257297E+11 | -.350027E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.118669E+10 | 65.78 | 0.00 | 0.00 |
December | 0.265239E+11 | -.361279E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121060E+10 | 65.23 | 0.00 | 0.00 |
Annual Sum or Average | 0.312108E+12 | -.425159E+12 | 8760.00 | -.142884E+11 | 65.28 | |||||
Minimum of Months | 0.225234E+11 | -.403579E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.123477E+10 | 64.16 | 0.00 | 0.00 |
Maximum of Months | 0.309484E+11 | -.322319E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.109243E+10 | 66.10 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.74 | 0.73 | 01-JAN-09:20 | 2462.14 | 29.20 | 191.67 | 210.33 | 2051.04 | 33.59 | 225.83 | 177.33 |
February | 259.50 | 0.74 | 0.73 | 01-FEB-08:20 | 4372.68 | 31.23 | 222.33 | 236.83 | 1867.46 | 28.79 | 216.17 | 211.17 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:40 | 7413.95 | 32.41 | 207.00 | 306.67 | 1438.49 | 21.58 | 144.67 | 256.83 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:40 | 1913.72 | 17.60 | 0.00 | 339.00 | 1036.05 | 20.57 | 197.17 | 295.00 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 1760.52 | 17.44 | 0.00 | 377.83 | 940.15 | 20.37 | 185.50 | 331.00 |
June | 375.17 | 0.75 | 0.73 | 01-JUN-05:30 | 1526.92 | 16.93 | 0.00 | 385.17 | 862.23 | 19.89 | 160.50 | 330.17 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-04:00 | 1357.47 | 15.72 | 0.00 | 381.00 | 780.35 | 18.67 | 136.33 | 319.00 |
August | 366.67 | 0.75 | 0.73 | 01-AUG-05:49 | 1600.09 | 16.76 | 0.00 | 361.67 | 938.19 | 19.75 | 141.83 | 312.83 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2642.79 | 19.77 | 27.00 | 312.67 | 1243.81 | 21.34 | 173.67 | 275.33 |
October | 245.33 | 0.74 | 0.73 | 01-OCT-07:19 | 6834.37 | 33.69 | 216.50 | 278.67 | 1716.18 | 22.83 | 150.17 | 249.83 |
November | 242.67 | 0.74 | 0.73 | 01-NOV-07:49 | 2802.97 | 29.34 | 201.50 | 217.67 | 2318.11 | 33.22 | 229.83 | 184.83 |
December | 160.33 | 0.74 | 0.73 | 01-DEC-09:39 | 3164.10 | 30.08 | 111.33 | 199.33 | 2941.85 | 36.90 | 149.67 | 153.83 |
Annual Sum or Average | 3714.00 | 0.74 | 2824.46 | 22.42 | 1177.33 | 3606.83 | 1343.02 | 23.38 | 2111.33 | 3097.17 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 1357.47 | 15.72 | 0.00 | 199.33 | 780.35 | 18.67 | 136.33 | 153.83 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 7413.95 | 33.69 | 222.33 | 385.17 | 2941.85 | 36.90 | 229.83 | 331.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.75 | 0.73 | 01-JAN-09:20 | 772.55 | 15.61 | 44.00 | 188.67 | 507.92 | 18.19 | 61.17 | 110.17 |
February | 259.50 | 0.75 | 0.73 | 01-FEB-08:20 | 1326.25 | 17.77 | 63.67 | 218.83 | 671.38 | 17.10 | 37.17 | 162.17 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:30 | 2443.40 | 19.75 | 77.83 | 293.83 | 1002.40 | 17.72 | 36.67 | 232.83 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:10 | 2412.04 | 15.71 | 47.83 | 338.17 | 1404.26 | 14.71 | 0.00 | 292.67 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 2614.57 | 15.26 | 43.33 | 381.67 | 1110.68 | 14.67 | 0.00 | 335.00 |
June | 375.17 | 0.75 | 0.73 | 01-JUN-04:00 | 2643.92 | 13.09 | 0.00 | 393.33 | 1481.88 | 14.39 | 0.00 | 341.00 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-04:49 | 2569.25 | 12.14 | 3.67 | 392.83 | 1147.35 | 13.22 | 0.00 | 352.83 |
August | 366.67 | 0.74 | 0.73 | 01-AUG-05:30 | 3023.62 | 15.01 | 48.33 | 365.33 | 1289.19 | 14.16 | 3.17 | 322.67 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2365.26 | 17.92 | 65.17 | 315.50 | 1370.43 | 17.66 | 39.67 | 269.50 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:19 | 2246.57 | 19.70 | 80.50 | 260.67 | 927.57 | 17.72 | 39.17 | 205.67 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:49 | 1003.84 | 17.27 | 63.33 | 197.33 | 529.18 | 17.76 | 52.67 | 121.67 |
December | 160.33 | 0.75 | 0.73 | 01-DEC-09:39 | 872.80 | 17.23 | 38.17 | 170.33 | 510.40 | 19.06 | 39.17 | 88.00 |
Annual Sum or Average | 3714.00 | 0.75 | 2187.16 | 15.89 | 575.83 | 3516.50 | 1069.01 | 15.84 | 308.83 | 2834.17 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 772.55 | 12.14 | 0.00 | 170.33 | 507.92 | 13.22 | 0.00 | 88.00 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 3023.62 | 19.75 | 80.50 | 393.33 | 1481.88 | 19.06 | 61.17 | 352.83 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.76 | 0.73 | 01-JAN-09:39 | 433.49 | 0.00 | 0.00 | 159.83 | 235.83 | 0.00 | 0.00 | 14.00 |
February | 259.50 | 0.75 | 0.73 | 01-FEB-08:50 | 546.83 | 0.00 | 0.00 | 200.17 | 309.67 | 0.00 | 0.00 | 97.17 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:00 | 730.76 | 0.00 | 0.00 | 286.17 | 435.72 | 0.00 | 0.00 | 179.50 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:40 | 862.15 | 0.00 | 0.00 | 342.67 | 500.18 | 0.00 | 0.00 | 279.67 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 1053.35 | 0.00 | 0.00 | 394.00 | 610.32 | 0.00 | 0.00 | 353.33 |
June | 375.17 | 0.74 | 0.73 | 01-JUN-05:10 | 1118.57 | 0.00 | 0.00 | 407.17 | 640.06 | 0.00 | 0.00 | 369.33 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-04:00 | 946.31 | 0.00 | 0.00 | 415.67 | 545.29 | 0.00 | 0.00 | 358.50 |
August | 366.67 | 0.74 | 0.73 | 01-AUG-05:40 | 803.25 | 0.00 | 0.00 | 378.33 | 512.34 | 0.00 | 0.00 | 324.33 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 789.94 | 0.00 | 0.00 | 306.67 | 484.26 | 0.00 | 0.00 | 235.00 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 588.32 | 0.00 | 0.00 | 245.67 | 360.48 | 0.00 | 0.00 | 137.17 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:00 | 467.65 | 0.00 | 0.00 | 173.00 | 254.07 | 0.00 | 0.00 | 33.67 |
December | 160.33 | 0.77 | 0.73 | 01-DEC-09:50 | 396.96 | 0.00 | 0.00 | 130.50 | 234.85 | 0.00 | 0.00 | 14.17 |
Annual Sum or Average | 3714.00 | 0.75 | 786.91 | 0.00 | 0.00 | 3439.83 | 461.34 | 0.00 | 0.00 | 2395.83 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 396.96 | 0.00 | 0.00 | 130.50 | 234.85 | 0.00 | 0.00 | 14.00 | |
Maximum of Months | 471.00 | 0.77 | 0.73 | 1118.57 | 0.00 | 0.00 | 415.67 | 640.06 | 0.00 | 0.00 | 369.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.75 | 0.73 | 01-JAN-09:39 | 918.30 | 17.63 | 67.83 | 191.00 | 477.09 | 16.69 | 40.17 | 110.33 |
February | 259.50 | 0.74 | 0.73 | 01-FEB-08:50 | 1204.73 | 16.13 | 42.17 | 219.33 | 662.15 | 17.22 | 38.00 | 164.33 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:00 | 2039.72 | 18.12 | 58.83 | 295.33 | 1128.82 | 17.80 | 38.50 | 232.33 |
April | 379.50 | 0.74 | 0.73 | 01-APR-07:10 | 2554.07 | 15.68 | 48.50 | 336.17 | 1089.15 | 14.75 | 0.00 | 293.17 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:00 | 2552.02 | 13.59 | 0.00 | 384.17 | 1394.59 | 14.82 | 1.50 | 337.00 |
June | 375.17 | 0.74 | 0.73 | 01-JUN-05:49 | 2688.40 | 13.17 | 0.00 | 390.83 | 1179.35 | 16.54 | 36.50 | 349.83 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-05:10 | 2961.71 | 11.82 | 0.00 | 392.67 | 1267.29 | 15.21 | 45.50 | 347.00 |
August | 366.67 | 0.74 | 0.73 | 01-AUG-05:00 | 2672.77 | 12.93 | 8.50 | 369.83 | 1608.55 | 14.30 | 5.50 | 327.00 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2925.92 | 18.74 | 78.00 | 307.33 | 1723.60 | 18.33 | 49.83 | 254.67 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 1993.13 | 18.41 | 66.50 | 261.50 | 900.07 | 18.06 | 42.83 | 204.33 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:00 | 979.84 | 17.14 | 59.17 | 198.33 | 500.81 | 16.36 | 37.67 | 117.33 |
December | 160.33 | 0.75 | 0.73 | 01-DEC-09:39 | 870.74 | 16.42 | 31.83 | 171.50 | 514.24 | 18.02 | 31.50 | 81.33 |
Annual Sum or Average | 3714.00 | 0.75 | 2215.15 | 15.30 | 461.33 | 3518.00 | 1116.62 | 16.21 | 367.50 | 2818.67 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 870.74 | 11.82 | 0.00 | 171.50 | 477.09 | 14.30 | 0.00 | 81.33 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 2961.71 | 18.74 | 78.00 | 392.67 | 1723.60 | 18.33 | 49.83 | 349.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.74 | 0.73 | 01-JAN-09:20 | 2199.71 | 22.46 | 139.83 | 210.00 | 2051.37 | 31.64 | 208.50 | 176.50 |
February | 259.50 | 0.74 | 0.73 | 01-FEB-08:20 | 4324.71 | 30.37 | 218.17 | 236.17 | 1908.46 | 27.13 | 156.50 | 214.33 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:40 | 7365.19 | 31.34 | 206.50 | 304.33 | 1486.27 | 16.92 | 7.50 | 258.67 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:49 | 1873.37 | 11.37 | 0.00 | 337.83 | 1070.17 | 16.16 | 0.00 | 296.67 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 1722.19 | 11.35 | 0.00 | 376.17 | 969.69 | 16.07 | 0.00 | 333.00 |
June | 375.17 | 0.75 | 0.73 | 01-JUN-05:40 | 1501.31 | 11.23 | 0.00 | 384.17 | 890.80 | 15.96 | 0.00 | 332.33 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-05:10 | 1338.91 | 9.84 | 0.00 | 379.33 | 808.87 | 14.56 | 0.00 | 321.50 |
August | 366.67 | 0.75 | 0.73 | 01-AUG-05:49 | 1581.00 | 10.90 | 0.00 | 360.50 | 974.54 | 15.77 | 0.00 | 315.50 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2602.99 | 14.15 | 27.00 | 311.17 | 1288.57 | 17.05 | 0.00 | 277.50 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 6770.99 | 32.86 | 216.33 | 276.00 | 1761.74 | 18.37 | 26.17 | 251.33 |
November | 242.67 | 0.74 | 0.73 | 01-NOV-07:49 | 2748.15 | 27.65 | 190.83 | 216.50 | 2340.80 | 32.75 | 226.17 | 186.50 |
December | 160.33 | 0.74 | 0.73 | 01-DEC-09:39 | 2579.32 | 20.87 | 72.00 | 196.83 | 2970.49 | 36.30 | 149.67 | 155.00 |
Annual Sum or Average | 3714.00 | 0.74 | 2749.45 | 17.60 | 1070.67 | 3589.00 | 1375.43 | 19.87 | 774.50 | 3118.83 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 1338.91 | 9.84 | 0.00 | 196.83 | 808.87 | 14.56 | 0.00 | 155.00 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 7365.19 | 32.86 | 218.17 | 384.17 | 2970.49 | 36.30 | 226.17 | 333.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.75 | 0.73 | 01-JAN-09:20 | 765.02 | 13.06 | 44.17 | 187.67 | 518.35 | 16.43 | 62.00 | 114.00 |
February | 259.50 | 0.75 | 0.73 | 01-FEB-08:20 | 1319.12 | 15.54 | 63.67 | 218.50 | 687.96 | 14.95 | 38.00 | 165.33 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:30 | 2277.03 | 15.70 | 58.00 | 293.00 | 1029.97 | 15.51 | 36.83 | 237.17 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:19 | 2410.83 | 12.85 | 48.00 | 337.50 | 1434.60 | 12.12 | 0.00 | 295.00 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 2608.86 | 12.34 | 43.33 | 381.00 | 1141.37 | 12.21 | 0.00 | 338.83 |
June | 375.17 | 0.75 | 0.73 | 01-JUN-04:00 | 2634.35 | 9.68 | 0.00 | 392.33 | 1520.25 | 11.99 | 0.00 | 344.00 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-04:49 | 2568.80 | 8.79 | 3.67 | 392.17 | 1165.95 | 10.84 | 0.00 | 356.33 |
August | 366.67 | 0.75 | 0.73 | 01-AUG-05:30 | 3028.11 | 12.13 | 48.33 | 364.50 | 1259.93 | 11.65 | 3.17 | 324.33 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2355.78 | 15.37 | 63.17 | 314.17 | 1401.05 | 15.50 | 39.67 | 272.33 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:19 | 2052.22 | 15.81 | 62.83 | 260.00 | 944.55 | 15.33 | 37.67 | 210.17 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:49 | 997.06 | 15.05 | 64.00 | 196.67 | 520.08 | 14.48 | 41.50 | 125.67 |
December | 160.33 | 0.75 | 0.73 | 01-DEC-09:39 | 865.74 | 14.85 | 38.17 | 168.50 | 522.23 | 17.03 | 38.83 | 90.83 |
Annual Sum or Average | 3714.00 | 0.75 | 2159.40 | 12.91 | 537.33 | 3506.00 | 1086.17 | 13.46 | 297.67 | 2874.00 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 765.02 | 8.79 | 0.00 | 168.50 | 518.35 | 10.84 | 0.00 | 90.83 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 3028.11 | 15.81 | 64.00 | 392.33 | 1520.25 | 17.03 | 62.00 | 356.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.76 | 0.73 | 01-JAN-09:50 | 422.69 | 0.00 | 0.00 | 155.17 | 241.74 | 0.00 | 0.00 | 17.83 |
February | 259.50 | 0.75 | 0.73 | 01-FEB-08:50 | 534.38 | 0.00 | 0.00 | 197.17 | 317.81 | 0.00 | 0.00 | 103.67 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:00 | 716.56 | 0.00 | 0.00 | 283.17 | 447.79 | 0.00 | 0.00 | 187.50 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:40 | 846.04 | 0.00 | 0.00 | 340.83 | 514.61 | 0.00 | 0.00 | 283.83 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 1050.03 | 0.00 | 0.00 | 393.00 | 629.15 | 0.00 | 0.00 | 355.83 |
June | 375.17 | 0.74 | 0.73 | 01-JUN-05:10 | 1102.46 | 0.00 | 0.00 | 406.00 | 684.17 | 0.00 | 0.00 | 376.17 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-04:00 | 938.55 | 0.00 | 0.00 | 415.67 | 586.96 | 0.00 | 0.00 | 366.83 |
August | 366.67 | 0.74 | 0.73 | 01-AUG-05:40 | 813.20 | 0.00 | 0.00 | 380.00 | 528.41 | 0.00 | 0.00 | 329.50 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 775.19 | 0.00 | 0.00 | 304.83 | 497.94 | 0.00 | 0.00 | 239.17 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 576.27 | 0.00 | 0.00 | 241.50 | 370.09 | 0.00 | 0.00 | 142.17 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:00 | 456.32 | 0.00 | 0.00 | 170.50 | 260.64 | 0.00 | 0.00 | 39.33 |
December | 160.33 | 0.77 | 0.73 | 01-DEC-09:50 | 386.50 | 0.00 | 0.00 | 125.67 | 240.10 | 0.00 | 0.00 | 16.83 |
Annual Sum or Average | 3714.00 | 0.75 | 777.57 | 0.00 | 0.00 | 3413.50 | 480.46 | 0.00 | 0.00 | 2458.67 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 386.50 | 0.00 | 0.00 | 125.67 | 240.10 | 0.00 | 0.00 | 16.83 | |
Maximum of Months | 471.00 | 0.77 | 0.73 | 1102.46 | 0.00 | 0.00 | 415.67 | 684.17 | 0.00 | 0.00 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.75 | 0.73 | 01-JAN-09:39 | 911.71 | 15.51 | 68.50 | 190.33 | 488.29 | 14.61 | 40.67 | 115.00 |
February | 259.50 | 0.74 | 0.73 | 01-FEB-08:50 | 1198.91 | 13.50 | 42.17 | 218.67 | 679.22 | 15.07 | 38.00 | 168.33 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:00 | 2032.41 | 15.74 | 58.83 | 294.33 | 1154.82 | 15.63 | 38.50 | 235.83 |
April | 379.50 | 0.74 | 0.73 | 01-APR-07:10 | 2551.46 | 12.82 | 48.50 | 335.33 | 1076.92 | 12.19 | 0.00 | 293.50 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:00 | 2541.87 | 10.08 | 0.00 | 383.17 | 1428.36 | 12.33 | 1.50 | 340.33 |
June | 375.17 | 0.74 | 0.73 | 01-JUN-05:49 | 2678.06 | 9.80 | 0.00 | 389.50 | 1213.86 | 14.39 | 35.17 | 352.50 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-05:10 | 2961.75 | 8.31 | 0.00 | 391.83 | 1258.58 | 10.65 | 0.00 | 347.00 |
August | 366.67 | 0.74 | 0.73 | 01-AUG-05:00 | 2677.27 | 9.52 | 8.50 | 368.83 | 1647.14 | 11.79 | 5.50 | 330.00 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2931.32 | 16.42 | 77.83 | 306.50 | 1759.88 | 16.24 | 49.83 | 257.50 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 1961.93 | 15.85 | 63.50 | 260.67 | 924.44 | 15.93 | 43.00 | 209.17 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:00 | 887.22 | 12.90 | 41.33 | 197.50 | 513.02 | 14.25 | 38.67 | 120.50 |
December | 160.33 | 0.75 | 0.73 | 01-DEC-09:39 | 863.99 | 13.88 | 31.83 | 170.50 | 526.02 | 15.83 | 31.67 | 83.83 |
Annual Sum or Average | 3714.00 | 0.75 | 2203.84 | 12.26 | 441.00 | 3507.17 | 1134.95 | 13.64 | 322.50 | 2853.50 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 863.99 | 8.31 | 0.00 | 170.50 | 488.29 | 10.65 | 0.00 | 83.83 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 2961.75 | 16.42 | 77.83 | 391.83 | 1759.88 | 16.24 | 49.83 | 352.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.74 | 0.73 | 01-JAN-09:20 | 2198.90 | 22.44 | 139.83 | 210.00 | 2052.20 | 31.63 | 208.50 | 176.67 |
February | 259.50 | 0.74 | 0.73 | 01-FEB-08:20 | 4324.04 | 30.35 | 218.17 | 236.00 | 1909.75 | 27.12 | 156.33 | 214.33 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:40 | 7365.29 | 31.32 | 206.50 | 304.33 | 1487.93 | 16.90 | 7.50 | 258.83 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:49 | 1874.39 | 11.33 | 0.00 | 337.83 | 1071.55 | 16.14 | 0.00 | 296.67 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 1723.30 | 11.31 | 0.00 | 376.17 | 970.95 | 16.06 | 0.00 | 333.17 |
June | 375.17 | 0.75 | 0.73 | 01-JUN-05:40 | 1502.03 | 11.19 | 0.00 | 384.17 | 891.77 | 15.94 | 0.00 | 332.50 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-05:10 | 1339.57 | 9.80 | 0.00 | 379.17 | 809.73 | 14.54 | 0.00 | 322.17 |
August | 366.67 | 0.75 | 0.73 | 01-AUG-05:49 | 1581.62 | 10.86 | 0.00 | 360.50 | 975.54 | 15.75 | 0.00 | 315.50 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2603.46 | 14.11 | 27.00 | 311.17 | 1290.02 | 17.03 | 0.00 | 277.67 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 6743.97 | 32.52 | 213.33 | 275.83 | 1763.19 | 18.35 | 26.17 | 251.33 |
November | 242.67 | 0.74 | 0.73 | 01-NOV-07:49 | 2661.97 | 25.63 | 172.17 | 215.17 | 2341.81 | 32.74 | 226.17 | 186.50 |
December | 160.33 | 0.74 | 0.73 | 01-DEC-09:39 | 2577.64 | 20.84 | 72.00 | 196.67 | 2971.17 | 36.30 | 149.67 | 155.33 |
Annual Sum or Average | 3714.00 | 0.74 | 2742.36 | 17.41 | 1049.00 | 3587.00 | 1376.58 | 19.85 | 774.33 | 3120.67 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 1339.57 | 9.80 | 0.00 | 196.67 | 809.73 | 14.54 | 0.00 | 155.33 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 7365.29 | 32.52 | 218.17 | 384.17 | 2971.17 | 36.30 | 226.17 | 333.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.75 | 0.73 | 01-JAN-09:20 | 764.99 | 13.05 | 44.17 | 187.83 | 518.84 | 16.43 | 62.00 | 114.50 |
February | 259.50 | 0.75 | 0.73 | 01-FEB-08:20 | 1319.02 | 15.53 | 63.67 | 218.50 | 688.59 | 14.94 | 38.00 | 165.50 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:30 | 2276.79 | 15.69 | 58.00 | 293.00 | 1030.83 | 15.50 | 36.83 | 237.67 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:19 | 2410.80 | 12.84 | 48.00 | 337.50 | 1435.58 | 12.11 | 0.00 | 295.00 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 2609.23 | 12.33 | 43.33 | 381.00 | 1142.43 | 12.20 | 0.00 | 338.83 |
June | 375.17 | 0.75 | 0.73 | 01-JUN-04:00 | 2634.30 | 9.66 | 0.00 | 392.33 | 1521.25 | 11.98 | 0.00 | 344.17 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-04:49 | 2568.86 | 8.77 | 3.67 | 392.17 | 1166.73 | 10.83 | 0.00 | 356.33 |
August | 366.67 | 0.75 | 0.73 | 01-AUG-05:30 | 3027.81 | 12.12 | 48.33 | 364.50 | 1260.71 | 11.64 | 3.17 | 324.33 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2355.31 | 15.36 | 63.17 | 314.17 | 1401.82 | 15.50 | 39.67 | 273.00 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:19 | 2051.82 | 15.80 | 62.83 | 259.83 | 945.20 | 15.32 | 37.67 | 210.33 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:49 | 997.04 | 15.04 | 64.00 | 196.83 | 520.62 | 14.48 | 41.50 | 125.83 |
December | 160.33 | 0.75 | 0.73 | 01-DEC-09:39 | 865.45 | 14.84 | 38.17 | 168.67 | 522.65 | 17.02 | 38.83 | 91.17 |
Annual Sum or Average | 3714.00 | 0.75 | 2159.31 | 12.89 | 537.33 | 3506.33 | 1086.97 | 13.45 | 297.67 | 2876.67 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 764.99 | 8.77 | 0.00 | 168.67 | 518.84 | 10.83 | 0.00 | 91.17 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 3027.81 | 15.80 | 64.00 | 392.33 | 1521.25 | 17.02 | 62.00 | 356.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.76 | 0.73 | 01-JAN-09:50 | 422.80 | 0.00 | 0.00 | 155.67 | 242.05 | 0.00 | 0.00 | 17.83 |
February | 259.50 | 0.75 | 0.73 | 01-FEB-08:50 | 534.46 | 0.00 | 0.00 | 197.17 | 318.17 | 0.00 | 0.00 | 104.00 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:00 | 716.52 | 0.00 | 0.00 | 283.17 | 448.22 | 0.00 | 0.00 | 187.67 |
April | 379.50 | 0.74 | 0.73 | 01-APR-06:40 | 846.12 | 0.00 | 0.00 | 340.83 | 515.13 | 0.00 | 0.00 | 284.00 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:49 | 1050.23 | 0.00 | 0.00 | 393.17 | 629.82 | 0.00 | 0.00 | 356.00 |
June | 375.17 | 0.74 | 0.73 | 01-JUN-05:10 | 1102.43 | 0.00 | 0.00 | 406.00 | 684.75 | 0.00 | 0.00 | 376.17 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-04:00 | 938.58 | 0.00 | 0.00 | 415.67 | 587.47 | 0.00 | 0.00 | 366.83 |
August | 366.67 | 0.74 | 0.73 | 01-AUG-05:40 | 813.09 | 0.00 | 0.00 | 380.00 | 528.83 | 0.00 | 0.00 | 329.83 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 775.07 | 0.00 | 0.00 | 304.83 | 498.37 | 0.00 | 0.00 | 239.50 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 576.15 | 0.00 | 0.00 | 241.50 | 370.41 | 0.00 | 0.00 | 142.33 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:00 | 456.46 | 0.00 | 0.00 | 170.50 | 260.97 | 0.00 | 0.00 | 39.50 |
December | 160.33 | 0.77 | 0.73 | 01-DEC-09:50 | 386.43 | 0.00 | 0.00 | 125.67 | 240.33 | 0.00 | 0.00 | 16.83 |
Annual Sum or Average | 3714.00 | 0.75 | 777.59 | 0.00 | 0.00 | 3414.17 | 480.91 | 0.00 | 0.00 | 2460.50 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 386.43 | 0.00 | 0.00 | 125.67 | 240.33 | 0.00 | 0.00 | 16.83 | |
Maximum of Months | 471.00 | 0.77 | 0.73 | 1102.43 | 0.00 | 0.00 | 415.67 | 684.75 | 0.00 | 0.00 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 237.83 | 0.75 | 0.73 | 01-JAN-09:39 | 911.68 | 15.50 | 68.50 | 190.33 | 488.78 | 14.60 | 40.67 | 115.17 |
February | 259.50 | 0.74 | 0.73 | 01-FEB-08:50 | 1198.80 | 13.49 | 42.17 | 218.67 | 679.85 | 15.06 | 38.00 | 168.50 |
March | 247.00 | 0.74 | 0.73 | 01-MAR-07:00 | 2032.16 | 15.73 | 58.83 | 294.50 | 1155.70 | 15.62 | 38.50 | 235.83 |
April | 379.50 | 0.74 | 0.73 | 01-APR-07:10 | 2551.42 | 12.81 | 48.50 | 335.33 | 1077.90 | 12.18 | 0.00 | 293.50 |
May | 427.83 | 0.74 | 0.73 | 01-MAY-06:00 | 2542.11 | 10.06 | 0.00 | 383.17 | 1429.50 | 12.32 | 1.50 | 340.33 |
June | 375.17 | 0.74 | 0.73 | 01-JUN-05:49 | 2678.06 | 9.78 | 0.00 | 390.00 | 1214.86 | 14.38 | 35.17 | 352.67 |
July | 471.00 | 0.75 | 0.73 | 01-JUL-05:10 | 2961.77 | 8.30 | 0.00 | 391.83 | 1259.45 | 10.64 | 0.00 | 347.00 |
August | 366.67 | 0.74 | 0.73 | 01-AUG-05:00 | 2676.95 | 9.51 | 8.50 | 368.67 | 1647.92 | 11.78 | 5.50 | 330.00 |
September | 301.17 | 0.74 | 0.73 | 01-SEP-07:40 | 2930.79 | 16.41 | 77.83 | 306.50 | 1760.84 | 16.23 | 49.83 | 257.67 |
October | 245.33 | 0.75 | 0.73 | 01-OCT-07:40 | 1961.49 | 15.84 | 63.50 | 260.83 | 925.11 | 15.92 | 43.00 | 209.33 |
November | 242.67 | 0.75 | 0.73 | 01-NOV-07:00 | 887.22 | 12.89 | 41.33 | 197.50 | 513.56 | 14.25 | 38.67 | 120.50 |
December | 160.33 | 0.75 | 0.73 | 01-DEC-09:39 | 863.68 | 13.87 | 31.83 | 170.50 | 526.43 | 15.82 | 31.67 | 83.83 |
Annual Sum or Average | 3714.00 | 0.75 | 2203.72 | 12.25 | 441.00 | 3507.83 | 1135.78 | 13.64 | 322.50 | 2854.33 | ||
Minimum of Months | 160.33 | 0.74 | 0.73 | 863.68 | 8.30 | 0.00 | 170.50 | 488.78 | 10.64 | 0.00 | 83.83 | |
Maximum of Months | 471.00 | 0.75 | 0.73 | 2961.77 | 16.41 | 77.83 | 391.83 | 1760.84 | 16.23 | 49.83 | 352.67 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.209629E+10 | 486997.97 | 13-JAN-00:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122023E+10 | 435951.51 | 01-FEB-23:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.494849E+09 | 248058.76 | 04-MAR-18:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182087E+09 | 67694.79 | 04-APR-22:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.309835E+09 | 426483.87 | 08-MAY-04:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.594774E+09 | 441535.69 | 22-OCT-22:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511231E+09 | 257124.20 | 17-NOV-23:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71061374.41 | 70491.25 | 16-DEC-21:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548036E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209629E+10 | 486997.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206210E+10 | 402563.77 | 02-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.206210E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206210E+10 | 402563.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.330111E+10 | 72058.90 | 09-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130254E+10 | 71552.44 | 14-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.238491E+09 | 70414.30 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 72538705.24 | 36777.70 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.657978E+09 | 71405.45 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170723E+10 | 71975.34 | 26-DEC-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.727989E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.330111E+10 | 72058.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130956E+09 | 2002.38 | 06-JAN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 40247296.29 | 2072.68 | 18-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 99846.85 | 116.47 | 24-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3137440.02 | 348.76 | 30-NOV-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 34069436.56 | 1460.31 | 20-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208510E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130956E+09 | 2072.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177014E+09 | 10757.03 | 17-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45522579.45 | 2361.48 | 17-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 192741.76 | 240.24 | 06-MAR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1329375.78 | 573.27 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24484091.94 | 3662.31 | 18-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.248543E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177014E+09 | 10757.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 107749.37 | 156.63 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 107749.37 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107749.37 | 156.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.130970E+11 | 100534.96 | 02-JAN-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526863E+10 | 102703.26 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.898097E+09 | 99596.72 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105666E+09 | 68080.72 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.203535E+09 | 96333.87 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.203879E+10 | 100920.76 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.706557E+10 | 102415.20 | 05-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286773E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.130970E+11 | 102703.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.224939E+11 | 127159.64 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118666E+11 | 126799.93 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.415660E+10 | 124294.65 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.103696E+10 | 123460.60 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218530E+09 | 21266.21 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26731425.51 | 10374.64 | 14-JUN-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.162035E+09 | 13017.11 | 27-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.275550E+10 | 81532.65 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.918481E+10 | 124631.48 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.167112E+11 | 126730.29 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.686129E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.224939E+11 | 127159.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169121E+11 | 177944.69 | 06-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.715847E+10 | 177710.64 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196029E+10 | 173831.75 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.714812E+09 | 104413.63 | 11-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 74347857.75 | 17547.16 | 18-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.872118E+09 | 54170.02 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.506869E+10 | 173346.04 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116809E+11 | 177629.48 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.444417E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169121E+11 | 177944.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.176090E+11 | 119256.80 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.859558E+10 | 118843.49 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.268261E+10 | 116207.97 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.760785E+09 | 23213.43 | 01-APR-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.103126E+09 | 18373.61 | 18-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 496003.09 | 469.18 | 26-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164357E+10 | 28874.03 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.623015E+10 | 115234.99 | 30-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118360E+11 | 118771.21 | 26-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.494614E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.176090E+11 | 119256.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.400514E+10 | 11433.61 | 30-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.245523E+10 | 11464.39 | 22-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.987710E+09 | 11443.20 | 06-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351843E+09 | 11397.05 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 40092820.76 | 11296.22 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 923007.68 | 311.23 | 14-JUN-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9723494.61 | 1283.10 | 27-SEP-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.473839E+09 | 11480.50 | 23-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164230E+10 | 11734.17 | 27-NOV-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.319613E+10 | 11439.70 | 16-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131629E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.400514E+10 | 11734.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.415933E+10 | 14916.47 | 07-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.258919E+10 | 14840.15 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132757E+10 | 14642.26 | 25-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451549E+09 | 14636.97 | 19-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159607E+09 | 13708.38 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 26673049.55 | 8597.94 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6481051.34 | 1137.97 | 19-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145296E+09 | 3081.97 | 27-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.901492E+09 | 14504.31 | 13-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227501E+10 | 14778.77 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.357393E+10 | 14902.40 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156161E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.415933E+10 | 14916.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.437651E+10 | 21001.13 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253151E+10 | 20921.43 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.138972E+10 | 20654.78 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.628591E+09 | 20638.12 | 19-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.189512E+09 | 20552.26 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30783253.88 | 5741.07 | 14-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78419989.34 | 3231.19 | 27-SEP-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.763104E+09 | 20442.59 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230878E+10 | 20837.10 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.366126E+10 | 21009.94 | 26-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159582E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.437651E+10 | 21009.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.353912E+10 | 15016.56 | 09-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.217072E+10 | 14958.67 | 18-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.119409E+10 | 14721.75 | 28-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466634E+09 | 14751.24 | 19-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.148458E+09 | 13571.75 | 18-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 21581819.38 | 1612.33 | 14-JUN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78100297.99 | 2997.33 | 27-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.771877E+09 | 14607.77 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191915E+10 | 14891.07 | 13-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.292074E+10 | 14993.39 | 26-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.132305E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.353912E+10 | 15016.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172034E+10 | 226802.85 | 07-JAN-05:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 57571943.22 | 223327.83 | 22-FEB-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.498378E+09 | 222075.77 | 23-MAR-03:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.820805E+09 | 222944.31 | 20-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.525159E+09 | 222233.82 | 16-MAY-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.118971E+10 | 220569.87 | 16-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.745834E+09 | 220318.90 | 10-JUL-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.627853E+09 | 220336.82 | 11-AUG-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191899E+10 | 220723.13 | 29-SEP-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138854E+10 | 221154.22 | 25-OCT-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181033E+10 | 224342.93 | 12-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.123058E+10 | 226119.63 | 26-DEC-01:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.125341E+11 | |||||||
Minimum of Months | 57571943.22 | 220318.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.191899E+10 | 226802.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413876E+10 | 23750.21 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216780E+10 | 18995.29 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.245769E+09 | 13315.41 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25339356.19 | 5670.83 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3358896.86 | 1364.82 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.368779E+09 | 7751.98 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.128246E+10 | 14308.62 | 21-DEC-22:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.823227E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413876E+10 | 23750.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.893952E+11 | 266117.44 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.534707E+11 | 216726.95 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.104580E+11 | 170272.56 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.381158E+10 | 118162.48 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.269052E+09 | 43037.02 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.768508E+09 | 42382.41 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.226546E+11 | 162424.19 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.592804E+11 | 229898.70 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.240108E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.893952E+11 | 266117.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120825E+11 | 31043.94 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.786317E+10 | 27086.85 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288110E+10 | 22041.47 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.105941E+10 | 16466.67 | 19-APR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.159574E+09 | 8317.63 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12895063.82 | 2101.89 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.444144E+09 | 9337.91 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.471923E+10 | 21605.85 | 13-NOV-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.988730E+10 | 27383.50 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.391093E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120825E+11 | 31043.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2145849.21 | 2145849.21 | 9188.43 | 11-JAN-05:01 | 9188.43 | 0.00 |
February | 0.00 | 0.00 | 0.489577E+09 | 0.483094E+09 | 37353.58 | 24-FEB-05:01 | 27606.38 | 0.00 |
March | 0.00 | 0.00 | 0.147244E+09 | 0.138764E+09 | 26207.36 | 10-MAR-04:01 | 13421.60 | 0.00 |
April | 0.00 | 0.00 | 0.399442E+10 | 0.398979E+10 | 58172.14 | 27-APR-15:40 | 58172.14 | 0.02 |
May | 0.00 | 0.00 | 0.762963E+10 | 0.761592E+10 | 56226.45 | 15-MAY-16:00 | 56226.45 | 0.09 |
June | 0.00 | 0.00 | 0.159732E+11 | 0.158858E+11 | 59854.43 | 12-JUN-00:01 | 35449.24 | 0.16 |
July | 0.00 | 0.00 | 0.291708E+11 | 0.289218E+11 | 75979.47 | 31-JUL-00:01 | 54690.50 | 0.31 |
August | 0.00 | 0.00 | 0.405719E+11 | 0.400087E+11 | 93941.93 | 13-AUG-21:40 | 78095.29 | 0.42 |
September | 0.00 | 0.00 | 0.126964E+11 | 0.124581E+11 | 58203.96 | 01-SEP-03:01 | 35080.43 | 0.20 |
October | 0.00 | 0.00 | 0.195552E+10 | 0.192614E+10 | 49802.94 | 09-OCT-14:21 | 49802.94 | 0.00 |
November | 0.00 | 0.00 | 0.327782E+09 | 0.313402E+09 | 39621.72 | 04-NOV-03:01 | 20949.03 | 0.01 |
December | 0.00 | 0.00 | 10253593.82 | 10253593.82 | 11613.11 | 16-DEC-06:03 | 11613.11 | 0.00 |
Annual Sum or Average | 0.112969E+12 | 0.111754E+12 | 0.10 | |||||
Minimum of Months | 0.00 | 0.00 | 2145849.21 | 2145849.21 | 9188.43 | 9188.43 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.405719E+11 | 0.400087E+11 | 93941.93 | 78095.29 | 0.42 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 27656625.38 | 27656625.38 | 3679.21 | 11-JAN-14:00 | 3679.21 | 0.00 |
February | 0.00 | 0.00 | 0.106027E+10 | 0.106027E+10 | 56936.63 | 27-FEB-15:00 | 56936.63 | 0.01 |
March | 0.00 | 0.00 | 0.183859E+10 | 0.183859E+10 | 34889.16 | 18-MAR-16:00 | 34889.16 | 0.01 |
April | 0.00 | 0.00 | 0.114805E+11 | 0.114520E+11 | 107787.79 | 27-APR-15:00 | 102427.09 | 0.04 |
May | 0.00 | 0.00 | 0.193883E+11 | 0.189340E+11 | 88732.86 | 05-MAY-15:40 | 78135.19 | 0.13 |
June | 0.00 | 0.00 | 0.351596E+11 | 0.349537E+11 | 94981.78 | 28-JUN-16:00 | 94981.78 | 0.25 |
July | 0.00 | 0.00 | 0.635157E+11 | 0.591122E+11 | 124368.40 | 31-JUL-10:30 | 90584.81 | 0.49 |
August | 0.00 | 0.00 | 0.861724E+11 | 0.774856E+11 | 133692.24 | 29-AUG-14:30 | 115404.15 | 0.66 |
September | 0.00 | 0.00 | 0.309195E+11 | 0.282549E+11 | 109834.35 | 14-SEP-13:00 | 75521.10 | 0.34 |
October | 0.00 | 0.00 | 0.629104E+10 | 0.628759E+10 | 72160.95 | 04-OCT-15:00 | 72160.95 | 0.02 |
November | 0.00 | 0.00 | 0.106392E+10 | 0.977443E+09 | 47667.50 | 04-NOV-13:10 | 40035.55 | 0.03 |
December | 0.00 | 0.00 | 3312.75 | 3312.75 | 0.77 | 26-DEC-06:30 | 0.77 | 0.00 |
Annual Sum or Average | 0.256917E+12 | 0.240384E+12 | 0.17 | |||||
Minimum of Months | 0.00 | 0.00 | 3312.75 | 3312.75 | 0.77 | 0.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.861724E+11 | 0.774856E+11 | 133692.24 | 115404.15 | 0.66 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.198139E+09 | 0.198139E+09 | 25338.57 | 11-JAN-16:00 | 25338.57 | 0.00 |
February | 0.00 | 0.00 | 0.772822E+10 | 0.772822E+10 | 408579.69 | 27-FEB-15:00 | 408579.69 | 0.01 |
March | 0.00 | 0.00 | 0.142188E+11 | 0.142188E+11 | 336579.52 | 18-MAR-14:00 | 336579.52 | 0.01 |
April | 0.00 | 0.00 | 0.851643E+11 | 0.849892E+11 | 889676.70 | 27-APR-15:00 | 854271.82 | 0.04 |
May | 0.00 | 0.00 | 0.170308E+12 | 0.166092E+12 | 798589.02 | 05-MAY-15:50 | 697487.31 | 0.13 |
June | 0.00 | 0.00 | 0.292298E+12 | 0.290984E+12 | 832115.05 | 28-JUN-16:00 | 832115.05 | 0.24 |
July | 0.00 | 0.00 | 0.506262E+12 | 0.470939E+12 | 1045655.34 | 31-JUL-16:00 | 898393.58 | 0.44 |
August | 0.00 | 0.00 | 0.667121E+12 | 0.599289E+12 | 1164483.15 | 29-AUG-14:40 | 997866.48 | 0.54 |
September | 0.00 | 0.00 | 0.277063E+12 | 0.252266E+12 | 1040814.12 | 14-SEP-13:00 | 712991.89 | 0.33 |
October | 0.00 | 0.00 | 0.497579E+11 | 0.497579E+11 | 635590.83 | 04-OCT-15:00 | 635590.83 | 0.01 |
November | 0.00 | 0.00 | 0.948525E+10 | 0.860043E+10 | 470334.52 | 04-NOV-13:20 | 396777.99 | 0.03 |
December | 0.00 | 0.00 | 75935.95 | 75935.95 | 2.41 | 26-DEC-07:00 | 2.41 | 0.00 |
Annual Sum or Average | 0.207961E+13 | 0.194506E+13 | 0.15 | |||||
Minimum of Months | 0.00 | 0.00 | 75935.95 | 75935.95 | 2.41 | 2.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.667121E+12 | 0.599289E+12 | 1164483.15 | 997866.48 | 0.54 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 14921378.95 | 14921378.95 | 1904.91 | 11-JAN-15:30 | 1904.91 | 0.00 |
February | 0.00 | 0.00 | 0.686519E+09 | 0.686519E+09 | 35487.60 | 27-FEB-15:00 | 35487.60 | 0.01 |
March | 0.00 | 0.00 | 0.132873E+10 | 0.132873E+10 | 33162.61 | 18-MAR-14:00 | 33162.61 | 0.01 |
April | 0.00 | 0.00 | 0.883481E+10 | 0.880875E+10 | 108004.98 | 27-APR-15:00 | 102828.43 | 0.04 |
May | 0.00 | 0.00 | 0.177016E+11 | 0.172671E+11 | 87014.26 | 05-MAY-16:00 | 76847.31 | 0.12 |
June | 0.00 | 0.00 | 0.312912E+11 | 0.311516E+11 | 103251.17 | 28-JUN-16:00 | 103251.17 | 0.23 |
July | 0.00 | 0.00 | 0.547946E+11 | 0.508866E+11 | 132019.98 | 27-JUL-15:40 | 99078.68 | 0.43 |
August | 0.00 | 0.00 | 0.710279E+11 | 0.639897E+11 | 132761.33 | 29-AUG-14:40 | 114872.32 | 0.53 |
September | 0.00 | 0.00 | 0.278436E+11 | 0.253196E+11 | 110573.75 | 14-SEP-13:00 | 75597.21 | 0.32 |
October | 0.00 | 0.00 | 0.457706E+10 | 0.457706E+10 | 63512.34 | 04-OCT-15:00 | 63512.34 | 0.01 |
November | 0.00 | 0.00 | 0.933283E+09 | 0.848375E+09 | 46449.86 | 04-NOV-13:30 | 39776.21 | 0.02 |
December | 0.00 | 0.00 | 258.10 | 258.10 | 0.35 | 12-DEC-05:07 | 0.35 | 0.00 |
Annual Sum or Average | 0.219034E+12 | 0.204879E+12 | 0.14 | |||||
Minimum of Months | 0.00 | 0.00 | 258.10 | 258.10 | 0.35 | 0.35 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.710279E+11 | 0.639897E+11 | 132761.33 | 114872.32 | 0.53 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.311062E+12 | 0.310994E+12 | 434146.97 | 13-JAN-00:20 | 434146.97 | 0.00 |
February | 0.00 | 0.00 | 0.493530E+12 | 0.493439E+12 | 435974.83 | 14-FEB-22:40 | 435974.83 | 0.00 |
March | 0.00 | 0.00 | 0.783224E+12 | 0.783197E+12 | 425486.72 | 01-MAR-23:37 | 424095.68 | 0.00 |
April | 0.00 | 0.00 | 0.988660E+12 | 0.988659E+12 | 417875.36 | 22-APR-04:28 | 417875.36 | 0.00 |
May | 0.00 | 0.00 | 0.315863E+12 | 0.315659E+12 | 425273.81 | 08-MAY-04:37 | 425151.68 | 0.00 |
June | 0.00 | 0.00 | 0.534210E+12 | 0.534104E+12 | 209273.04 | 28-JUN-16:00 | 209273.04 | 0.00 |
July | 0.00 | 0.00 | 0.790553E+12 | 0.789631E+12 | 299773.92 | 31-JUL-16:00 | 298048.64 | 0.00 |
August | 0.00 | 0.00 | 0.102664E+13 | 0.102557E+13 | 392172.48 | 29-AUG-19:30 | 386350.63 | 0.00 |
September | 0.00 | 0.00 | 0.308280E+12 | 0.307417E+12 | 135826.97 | 01-SEP-00:08 | 134751.32 | 0.00 |
October | 0.00 | 0.00 | 0.551191E+12 | 0.551152E+12 | 433609.83 | 22-OCT-22:16 | 433609.83 | 0.00 |
November | 0.00 | 0.00 | 0.759741E+12 | 0.759609E+12 | 426494.12 | 17-NOV-05:30 | 426494.12 | 0.00 |
December | 0.00 | 0.00 | 0.101938E+13 | 0.101938E+13 | 417003.67 | 16-DEC-18:25 | 417003.67 | 0.00 |
Annual Sum or Average | 0.788233E+13 | 0.787880E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.308280E+12 | 0.307417E+12 | 135826.97 | 134751.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.102664E+13 | 0.102557E+13 | 435974.83 | 435974.83 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.443821E+10 | 0.443821E+10 | 2283.80 | 05-JAN-16:10 | 2283.80 | 0.00 |
February | 0.00 | 0.00 | 0.884568E+10 | 0.884568E+10 | 4306.00 | 07-FEB-16:50 | 4306.00 | 0.00 |
March | 0.00 | 0.00 | 0.150959E+11 | 0.150959E+11 | 6308.57 | 14-MAR-17:10 | 6308.57 | 0.00 |
April | 0.00 | 0.00 | 0.195267E+11 | 0.195267E+11 | 8279.30 | 26-APR-18:30 | 8279.30 | 0.00 |
May | 0.00 | 0.00 | 0.547749E+10 | 0.547749E+10 | 2953.47 | 29-MAY-18:27 | 2953.47 | 0.00 |
June | 0.00 | 0.00 | 0.101802E+11 | 0.101802E+11 | 4650.74 | 18-JUN-18:57 | 4650.74 | 0.00 |
July | 0.00 | 0.00 | 0.155248E+11 | 0.155248E+11 | 6925.48 | 30-JUL-18:27 | 6925.48 | 0.00 |
August | 0.00 | 0.00 | 0.203051E+11 | 0.203051E+11 | 8337.42 | 06-AUG-19:37 | 8337.42 | 0.00 |
September | 0.00 | 0.00 | 0.533790E+10 | 0.533790E+10 | 2815.70 | 10-SEP-17:23 | 2815.70 | 0.00 |
October | 0.00 | 0.00 | 0.102386E+11 | 0.102386E+11 | 4629.42 | 03-OCT-16:50 | 4629.42 | 0.00 |
November | 0.00 | 0.00 | 0.145377E+11 | 0.145377E+11 | 6129.45 | 12-NOV-15:58 | 6129.45 | 0.00 |
December | 0.00 | 0.00 | 0.198273E+11 | 0.198273E+11 | 7897.10 | 05-DEC-15:50 | 7897.10 | 0.00 |
Annual Sum or Average | 0.149336E+12 | 0.149336E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.443821E+10 | 0.443821E+10 | 2283.80 | 2283.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203051E+11 | 0.203051E+11 | 8337.42 | 8337.42 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.228011E+11 | 0.228011E+11 | 18704.77 | 05-JAN-16:20 | 18704.77 | 0.00 |
February | 0.00 | 0.00 | 0.694866E+11 | 0.694866E+11 | 39443.31 | 08-FEB-16:50 | 39443.31 | 0.00 |
March | 0.00 | 0.00 | 0.131422E+12 | 0.131422E+12 | 58976.13 | 14-MAR-17:10 | 58976.13 | 0.00 |
April | 0.00 | 0.00 | 0.177867E+12 | 0.177867E+12 | 78745.41 | 26-APR-18:20 | 78745.41 | 0.00 |
May | 0.00 | 0.00 | 0.453274E+11 | 0.453274E+11 | 26763.08 | 29-MAY-18:23 | 26763.08 | 0.00 |
June | 0.00 | 0.00 | 0.914127E+11 | 0.914127E+11 | 43234.57 | 22-JUN-18:50 | 43234.57 | 0.00 |
July | 0.00 | 0.00 | 0.144316E+12 | 0.144316E+12 | 64130.50 | 30-JUL-18:33 | 64130.50 | 0.00 |
August | 0.00 | 0.00 | 0.190570E+12 | 0.190570E+12 | 79138.08 | 06-AUG-19:23 | 79138.08 | 0.00 |
September | 0.00 | 0.00 | 0.447090E+11 | 0.447090E+11 | 25787.43 | 08-SEP-17:30 | 25787.43 | 0.00 |
October | 0.00 | 0.00 | 0.865710E+11 | 0.865710E+11 | 43348.60 | 03-OCT-16:50 | 43348.60 | 0.00 |
November | 0.00 | 0.00 | 0.123444E+12 | 0.123444E+12 | 55121.36 | 10-NOV-16:10 | 55121.36 | 0.00 |
December | 0.00 | 0.00 | 0.170392E+12 | 0.170392E+12 | 72573.40 | 05-DEC-16:00 | 72573.40 | 0.00 |
Annual Sum or Average | 0.129832E+13 | 0.129832E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.228011E+11 | 0.228011E+11 | 18704.77 | 18704.77 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.190570E+12 | 0.190570E+12 | 79138.08 | 79138.08 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.104326E+10 | 0.104326E+10 | 1755.20 | 05-JAN-16:20 | 1755.20 | 0.00 |
February | 0.00 | 0.00 | 0.550426E+10 | 0.550426E+10 | 3848.04 | 08-FEB-17:00 | 3848.04 | 0.00 |
March | 0.00 | 0.00 | 0.120290E+11 | 0.120290E+11 | 5910.98 | 14-MAR-17:10 | 5910.98 | 0.00 |
April | 0.00 | 0.00 | 0.171055E+11 | 0.171055E+11 | 7949.83 | 26-APR-18:20 | 7949.83 | 0.00 |
May | 0.00 | 0.00 | 0.410061E+10 | 0.410061E+10 | 2748.15 | 07-MAY-18:25 | 2748.15 | 0.00 |
June | 0.00 | 0.00 | 0.896134E+10 | 0.896134E+10 | 4457.73 | 18-JUN-18:38 | 4457.73 | 0.00 |
July | 0.00 | 0.00 | 0.143242E+11 | 0.143242E+11 | 6586.52 | 30-JUL-18:25 | 6586.52 | 0.00 |
August | 0.00 | 0.00 | 0.188913E+11 | 0.188913E+11 | 8019.84 | 06-AUG-19:14 | 8019.84 | 0.00 |
September | 0.00 | 0.00 | 0.401017E+10 | 0.401017E+10 | 2638.74 | 08-SEP-17:30 | 2638.74 | 0.00 |
October | 0.00 | 0.00 | 0.766604E+10 | 0.766604E+10 | 4362.17 | 04-OCT-16:50 | 4362.17 | 0.00 |
November | 0.00 | 0.00 | 0.109676E+11 | 0.109676E+11 | 5398.75 | 10-NOV-16:10 | 5398.75 | 0.00 |
December | 0.00 | 0.00 | 0.152870E+11 | 0.152870E+11 | 7113.11 | 05-DEC-16:00 | 7113.11 | 0.00 |
Annual Sum or Average | 0.119890E+12 | 0.119890E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.104326E+10 | 0.104326E+10 | 1755.20 | 1755.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.188913E+11 | 0.188913E+11 | 8019.84 | 8019.84 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4185.27 | 35251.85 | 16-JAN-11:00 | 13635.31 | 52070.99 | 31-JAN-12:40 |
February | 3958.02 | 35048.58 | 20-FEB-11:00 | 13804.08 | 52136.84 | 08-FEB-12:40 |
March | 2969.74 | 33708.34 | 27-MAR-05:10 | 14783.06 | 51941.56 | 02-MAR-12:50 |
April | 3869.68 | 33911.05 | 17-APR-05:08 | 13257.56 | 50818.76 | 03-APR-11:40 |
May | 4292.72 | 37723.03 | 29-MAY-10:00 | 13254.97 | 49276.18 | 01-MAY-11:30 |
June | 4048.00 | 33613.09 | 26-JUN-05:20 | 13157.83 | 47334.73 | 01-JUN-11:40 |
July | 5450.56 | 33922.25 | 31-JUL-05:20 | 11533.36 | 45717.56 | 03-JUL-11:30 |
August | 4177.29 | 33945.52 | 27-AUG-23:00 | 12764.35 | 45101.80 | 31-AUG-11:50 |
September | 4952.31 | 37943.10 | 04-SEP-09:13 | 12006.17 | 46054.99 | 29-SEP-12:00 |
October | 5165.40 | 37846.55 | 09-OCT-10:00 | 12315.38 | 47795.15 | 31-OCT-11:40 |
November | 4911.38 | 36877.01 | 12-NOV-11:00 | 12960.91 | 49637.53 | 30-NOV-12:40 |
December | 4348.54 | 35894.11 | 25-DEC-11:00 | 12947.58 | 51150.58 | 29-DEC-12:40 |
Annual Sum or Average | 4363.12 | 13030.80 | ||||
Minimum of Months | 2969.74 | 33613.09 | 11533.36 | 45101.80 | ||
Maximum of Months | 5450.56 | 37943.10 | 14783.06 | 52136.84 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 33.46 | 6453.62 | 15-JAN-16:55 | 73630.81 | 1219872.59 | 02-JAN-06:01 |
February | 8.53 | 3072.60 | 20-FEB-18:45 | 44279.88 | 668405.60 | 21-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 10759.14 | 468513.82 | 13-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3961.09 | 647685.24 | 18-APR-03:47 |
May | 20.30 | 6929.58 | 13-MAY-06:40 | 706.58 | 280391.75 | 02-MAY-03:47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 483.80 | 350948.59 | 15-JUN-03:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 271.04 | 215661.06 | 20-JUL-03:45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 232.06 | 219549.77 | 19-AUG-03:45 |
September | 0.51 | 1486.80 | 28-SEP-07:40 | 890.36 | 266040.42 | 20-SEP-03:47 |
October | 0.00 | 1.17 | 13-OCT-17:20 | 4184.78 | 677655.56 | 22-OCT-22:15 |
November | 0.26 | 151.39 | 09-NOV-16:10 | 23223.80 | 800001.65 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 49574.83 | 1213056.84 | 18-DEC-05:01 |
Annual Sum or Average | 5.28 | 17580.12 | ||||
Minimum of Months | 0.00 | 0.00 | 232.06 | 215661.06 | ||
Maximum of Months | 33.46 | 6929.58 | 73630.81 | 1219872.59 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 582.12 | 54966.56 | 11-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 8777.76 | 1016952.02 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13871.62 | 799800.06 | 18-MAR-14:00 | 31.12 | 84291.63 | 22-MAR-05:10 |
April | 69285.45 | 1301315.03 | 26-APR-15:40 | 7.94 | 42631.91 | 02-APR-03:02 |
May | 139555.17 | 1280177.21 | 04-MAY-14:50 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 249439.13 | 1315077.61 | 22-JUN-15:40 | 33.00 | 170840.86 | 11-JUN-23:01 |
July | 370522.01 | 1369713.87 | 31-JUL-16:00 | 15.93 | 49172.02 | 25-JUL-00:42 |
August | 441323.74 | 1504868.07 | 29-AUG-14:40 | 34.14 | 79564.79 | 23-AUG-00:32 |
September | 215606.85 | 1313583.17 | 14-SEP-13:00 | 102.84 | 192787.76 | 24-SEP-14:12 |
October | 45079.45 | 1034124.10 | 04-OCT-11:50 | 1.52 | 36125.89 | 08-OCT-17:12 |
November | 9298.48 | 1035399.11 | 04-NOV-14:50 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 515.36 | 55534.29 | 16-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 131259.20 | 18.84 | ||||
Minimum of Months | 515.36 | 54966.56 | 0.00 | 0.00 | ||
Maximum of Months | 441323.74 | 1504868.07 | 102.84 | 192787.76 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 56.81 | 30383.67 | 11-JAN-16:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5585.05 | 709276.18 | 27-FEB-15:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8874.17 | 522186.04 | 18-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 53051.91 | 1382079.97 | 26-APR-15:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 108182.50 | 1376608.60 | 04-MAY-14:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 197943.17 | 1426690.22 | 22-JUN-15:40 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 318767.66 | 1366355.43 | 31-JUL-16:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 398428.16 | 1503817.55 | 30-AUG-13:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 181613.96 | 1418630.04 | 14-SEP-13:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 31549.31 | 1065150.24 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6298.76 | 807536.93 | 04-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 25.28 | 59052.44 | 16-DEC-04:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 110043.88 | 0.00 | ||||
Minimum of Months | 25.28 | 30383.67 | 0.00 | 0.00 | ||
Maximum of Months | 398428.16 | 1503817.55 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 157802.96 | 544064.00 | 13-JAN-00:20 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 296699.18 | 573276.46 | 14-FEB-22:41 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 439024.57 | 752688.95 | 18-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 619373.91 | 1335124.20 | 27-APR-16:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 199499.24 | 590696.07 | 05-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 383630.07 | 891139.21 | 28-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 624740.88 | 1315631.88 | 24-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 875540.89 | 1580100.66 | 10-AUG-17:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 211136.86 | 599948.82 | 14-SEP-17:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 311104.92 | 624568.86 | 04-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 436948.22 | 780117.17 | 04-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 566383.68 | 606872.58 | 29-DEC-22:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 428047.29 | 0.00 | ||||
Minimum of Months | 157802.96 | 544064.00 | 0.00 | 0.00 | ||
Maximum of Months | 875540.89 | 1580100.66 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 49.30 | 18586.42 | 11-JAN-15:10 | 922.06 | 106245.87 | 06-JAN-05:48 |
February | 5942.61 | 718580.69 | 27-FEB-15:10 | 659.83 | 77231.51 | 06-FEB-06:40 |
March | 10038.91 | 573598.48 | 18-MAR-14:10 | 678.79 | 68997.17 | 22-MAR-13:40 |
April | 59181.97 | 2030131.29 | 27-APR-15:10 | 1002.82 | 78914.64 | 19-APR-12:00 |
May | 112181.95 | 2014630.58 | 05-MAY-15:20 | 629.61 | 70549.88 | 10-MAY-05:40 |
June | 200802.53 | 1844345.48 | 22-JUN-15:40 | 467.95 | 47368.07 | 01-JUN-09:30 |
July | 357646.08 | 3262190.77 | 31-JUL-16:00 | 390.14 | 55678.34 | 05-JUL-06:50 |
August | 531401.35 | 3859096.68 | 29-AUG-14:30 | 314.20 | 44632.68 | 19-AUG-07:20 |
September | 197032.01 | 2567199.05 | 14-SEP-13:00 | 381.36 | 55810.92 | 27-SEP-05:30 |
October | 32180.75 | 909756.15 | 04-OCT-11:30 | 696.20 | 87331.81 | 14-OCT-03:01 |
November | 6105.06 | 911188.70 | 04-NOV-14:40 | 1116.18 | 84243.51 | 13-NOV-12:50 |
December | 32.62 | 16837.54 | 15-DEC-06:40 | 797.01 | 82838.89 | 11-DEC-06:09 |
Annual Sum or Average | 127149.32 | 670.67 | ||||
Minimum of Months | 32.62 | 16837.54 | 314.20 | 44632.68 | ||
Maximum of Months | 531401.35 | 3859096.68 | 1116.18 | 106245.87 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141365E+11 | 0.81 | 9188.78 | 01-JAN-00:10 | 1.41 |
February | 0.125012E+11 | 0.79 | 9188.78 | 01-FEB-05:01 | 1.40 |
March | 0.150446E+11 | 0.86 | 9188.78 | 01-MAR-04:01 | 1.41 |
April | 0.138098E+11 | 0.82 | 9188.78 | 01-APR-03:31 | 1.41 |
May | 0.147933E+11 | 0.84 | 9188.78 | 01-MAY-02:61 | 1.40 |
June | 0.147020E+11 | 0.87 | 9188.78 | 01-JUN-03:01 | 1.40 |
July | 0.143711E+11 | 0.82 | 9188.78 | 01-JUL-03:01 | 1.41 |
August | 0.154792E+11 | 0.88 | 9188.78 | 01-AUG-03:01 | 1.40 |
September | 0.145600E+11 | 0.86 | 9188.78 | 01-SEP-03:01 | 1.40 |
October | 0.147342E+11 | 0.84 | 9188.78 | 02-OCT-00:31 | 1.40 |
November | 0.142761E+11 | 0.84 | 9188.78 | 01-NOV-03:01 | 1.40 |
December | 0.141682E+11 | 0.81 | 9188.78 | 01-DEC-04:01 | 1.41 |
Annual Sum or Average | 0.172576E+12 | 0.84 | |||
Minimum of Months | 0.125012E+11 | 0.79 | 9188.78 | 1.40 | |
Maximum of Months | 0.154792E+11 | 0.88 | 9188.78 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.468194E+10 | 0.34 | 11193.34 | 02-JAN-06:01 | 1.26 |
February | 0.505776E+10 | 0.38 | 10845.55 | 24-FEB-05:01 | 1.24 |
March | 0.743255E+10 | 0.45 | 13641.64 | 09-MAR-06:02 | 1.43 |
April | 0.786531E+10 | 0.48 | 16479.53 | 03-APR-05:01 | 1.61 |
May | 0.627624E+10 | 0.42 | 15610.96 | 30-MAY-05:01 | 1.56 |
June | 0.660643E+10 | 0.45 | 16717.49 | 20-JUN-05:01 | 1.63 |
July | 0.702878E+10 | 0.47 | 16717.49 | 03-JUL-05:01 | 1.63 |
August | 0.806038E+10 | 0.52 | 19204.76 | 30-AUG-05:03 | 1.77 |
September | 0.590895E+10 | 0.41 | 16085.68 | 01-SEP-05:01 | 1.58 |
October | 0.650929E+10 | 0.41 | 14820.53 | 10-OCT-05:01 | 1.50 |
November | 0.624081E+10 | 0.41 | 15632.76 | 06-NOV-06:01 | 1.56 |
December | 0.637856E+10 | 0.40 | 13646.55 | 11-DEC-04:01 | 1.44 |
Annual Sum or Average | 0.780470E+11 | 0.43 | |||
Minimum of Months | 0.468194E+10 | 0.34 | 10845.55 | 1.24 | |
Maximum of Months | 0.806038E+10 | 0.52 | 19204.76 | 1.77 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.343738E+11 | 0.32 | 104483.58 | 11-JAN-06:02 | 1.31 |
February | 0.350211E+11 | 0.33 | 124972.05 | 06-FEB-06:01 | 1.46 |
March | 0.471050E+11 | 0.37 | 118178.05 | 29-MAR-05:01 | 1.41 |
April | 0.455641E+11 | 0.36 | 114323.28 | 11-APR-05:01 | 1.38 |
May | 0.503676E+11 | 0.39 | 145598.78 | 15-MAY-05:01 | 1.61 |
June | 0.504712E+11 | 0.40 | 123072.52 | 21-JUN-05:01 | 1.44 |
July | 0.502052E+11 | 0.39 | 167904.79 | 20-JUL-05:01 | 1.75 |
August | 0.558834E+11 | 0.42 | 165524.60 | 10-AUG-05:03 | 1.73 |
September | 0.497201E+11 | 0.39 | 169145.36 | 14-SEP-05:01 | 1.76 |
October | 0.459147E+11 | 0.36 | 108903.32 | 30-OCT-05:01 | 1.34 |
November | 0.378883E+11 | 0.33 | 143770.77 | 30-NOV-06:02 | 1.60 |
December | 0.362910E+11 | 0.32 | 143770.77 | 05-DEC-06:01 | 1.60 |
Annual Sum or Average | 0.538806E+12 | 0.37 | |||
Minimum of Months | 0.343738E+11 | 0.32 | 104483.58 | 1.31 | |
Maximum of Months | 0.558834E+11 | 0.42 | 169145.36 | 1.76 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.379513E+10 | 0.36 | 4738.23 | 02-JAN-05:22 | 0.81 |
February | 0.332105E+10 | 0.34 | 4738.23 | 13-FEB-06:01 | 0.81 |
March | 0.385025E+10 | 0.35 | 4934.12 | 01-MAR-14:40 | 0.83 |
April | 0.390869E+10 | 0.34 | 9490.49 | 03-APR-05:01 | 1.20 |
May | 0.458101E+10 | 0.37 | 9490.49 | 01-MAY-05:03 | 1.20 |
June | 0.490796E+10 | 0.39 | 10702.90 | 21-JUN-05:01 | 1.29 |
July | 0.514587E+10 | 0.38 | 13684.35 | 20-JUL-05:01 | 1.51 |
August | 0.563978E+10 | 0.41 | 19461.55 | 14-AUG-05:02 | 1.88 |
September | 0.437405E+10 | 0.35 | 13010.65 | 14-SEP-05:01 | 1.46 |
October | 0.366720E+10 | 0.32 | 9490.49 | 04-OCT-05:01 | 1.21 |
November | 0.322967E+10 | 0.31 | 4738.23 | 13-NOV-05:01 | 0.81 |
December | 0.338534E+10 | 0.32 | 4738.23 | 19-DEC-06:01 | 0.81 |
Annual Sum or Average | 0.498060E+11 | 0.35 | |||
Minimum of Months | 0.322967E+10 | 0.31 | 4738.23 | 0.81 | |
Maximum of Months | 0.563978E+10 | 0.41 | 19461.55 | 1.88 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.954788E+11 | 1.37 | 35647.70 | 01-JAN-00:05 | 1.37 |
February | 0.862389E+11 | 1.37 | 35647.70 | 01-FEB-00:30 | 1.37 |
March | 0.954788E+11 | 1.37 | 35647.70 | 01-MAR-00:10 | 1.37 |
April | 0.923988E+11 | 1.37 | 35647.70 | 01-APR-00:10 | 1.37 |
May | 0.954788E+11 | 1.37 | 35647.70 | 01-MAY-00:10 | 1.37 |
June | 0.923988E+11 | 1.37 | 35647.70 | 01-JUN-00:10 | 1.37 |
July | 0.954788E+11 | 1.37 | 35647.70 | 01-JUL-00:20 | 1.37 |
August | 0.954788E+11 | 1.37 | 35647.70 | 01-AUG-00:05 | 1.37 |
September | 0.923988E+11 | 1.37 | 35647.70 | 01-SEP-00:03 | 1.37 |
October | 0.954788E+11 | 1.37 | 35647.70 | 01-OCT-00:10 | 1.37 |
November | 0.923988E+11 | 1.37 | 35647.70 | 01-NOV-00:02 | 1.37 |
December | 0.954788E+11 | 1.37 | 35647.70 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112419E+13 | 1.37 | |||
Minimum of Months | 0.862389E+11 | 1.37 | 35647.70 | 1.37 | |
Maximum of Months | 0.954788E+11 | 1.37 | 35647.70 | 1.37 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147906E+10 | 0.93 | 552.22 | 01-JAN-00:05 | 0.93 |
February | 0.133592E+10 | 0.93 | 552.22 | 01-FEB-00:10 | 0.93 |
March | 0.147906E+10 | 0.93 | 552.22 | 01-MAR-00:10 | 0.93 |
April | 0.143135E+10 | 0.93 | 552.22 | 01-APR-00:10 | 0.93 |
May | 0.147906E+10 | 0.93 | 552.22 | 01-MAY-00:10 | 0.93 |
June | 0.143135E+10 | 0.93 | 552.22 | 01-JUN-00:10 | 0.93 |
July | 0.147906E+10 | 0.93 | 552.22 | 01-JUL-00:10 | 0.93 |
August | 0.147906E+10 | 0.93 | 552.22 | 01-AUG-00:05 | 0.93 |
September | 0.143135E+10 | 0.93 | 552.22 | 01-SEP-00:03 | 0.93 |
October | 0.147906E+10 | 0.93 | 552.22 | 01-OCT-00:10 | 0.93 |
November | 0.143135E+10 | 0.93 | 552.22 | 01-NOV-00:02 | 0.93 |
December | 0.147906E+10 | 0.93 | 552.22 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.174147E+11 | 0.93 | |||
Minimum of Months | 0.133592E+10 | 0.93 | 552.22 | 0.93 | |
Maximum of Months | 0.147906E+10 | 0.93 | 552.22 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141341E+11 | 0.93 | 5277.06 | 01-JAN-00:05 | 0.93 |
February | 0.127663E+11 | 0.93 | 5277.06 | 01-FEB-00:10 | 0.93 |
March | 0.141341E+11 | 0.93 | 5277.06 | 01-MAR-00:10 | 0.93 |
April | 0.136781E+11 | 0.93 | 5277.06 | 01-APR-00:10 | 0.93 |
May | 0.141341E+11 | 0.93 | 5277.06 | 01-MAY-00:10 | 0.93 |
June | 0.136781E+11 | 0.93 | 5277.06 | 01-JUN-00:10 | 0.93 |
July | 0.141341E+11 | 0.93 | 5277.06 | 01-JUL-00:10 | 0.93 |
August | 0.141341E+11 | 0.93 | 5277.06 | 01-AUG-00:05 | 0.93 |
September | 0.136781E+11 | 0.93 | 5277.06 | 01-SEP-00:03 | 0.93 |
October | 0.141341E+11 | 0.93 | 5277.06 | 01-OCT-00:10 | 0.93 |
November | 0.136781E+11 | 0.93 | 5277.06 | 01-NOV-00:02 | 0.93 |
December | 0.141341E+11 | 0.93 | 5277.06 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.166417E+12 | 0.93 | |||
Minimum of Months | 0.127663E+11 | 0.93 | 5277.06 | 0.93 | |
Maximum of Months | 0.141341E+11 | 0.93 | 5277.06 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143512E+10 | 0.93 | 535.81 | 01-JAN-00:05 | 0.93 |
February | 0.129623E+10 | 0.93 | 535.81 | 01-FEB-00:10 | 0.93 |
March | 0.143512E+10 | 0.93 | 535.81 | 01-MAR-00:10 | 0.93 |
April | 0.138882E+10 | 0.93 | 535.81 | 01-APR-00:10 | 0.93 |
May | 0.143512E+10 | 0.93 | 535.81 | 01-MAY-00:10 | 0.93 |
June | 0.138882E+10 | 0.93 | 535.81 | 01-JUN-00:10 | 0.93 |
July | 0.143512E+10 | 0.93 | 535.81 | 01-JUL-00:10 | 0.93 |
August | 0.143512E+10 | 0.93 | 535.81 | 01-AUG-00:05 | 0.93 |
September | 0.138882E+10 | 0.93 | 535.81 | 01-SEP-00:03 | 0.93 |
October | 0.143512E+10 | 0.93 | 535.81 | 01-OCT-00:10 | 0.93 |
November | 0.138882E+10 | 0.93 | 535.81 | 01-NOV-00:02 | 0.93 |
December | 0.143512E+10 | 0.93 | 535.81 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.168973E+11 | 0.93 | |||
Minimum of Months | 0.129623E+10 | 0.93 | 535.81 | 0.93 | |
Maximum of Months | 0.143512E+10 | 0.93 | 535.81 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.375243E+10 | 0.337719E+10 | 11027.64 | 02-JAN-06:02 | 9924.87 | 9924.87 | 67.62 | 22.44 |
February | 0.156061E+10 | 0.140455E+10 | 8184.38 | 21-FEB-06:03 | 7365.95 | 7365.95 | 68.76 | 13.26 |
March | 0.581710E+09 | 0.523539E+09 | 7894.30 | 06-MAR-06:01 | 7104.87 | 7104.87 | 71.59 | 12.55 |
April | 0.107316E+09 | 96584809.75 | 4580.27 | 11-APR-05:01 | 4122.24 | 4122.24 | 63.59 | 6.28 |
May | 0.311877E+09 | 0.280689E+09 | 5887.10 | 02-MAY-03:47 | 5298.39 | 5298.39 | 71.54 | 8.47 |
June | 30414781.17 | 27373303.06 | 5360.82 | 01-JUN-03:50 | 4824.74 | 4824.74 | 71.86 | 7.54 |
July | 14661668.70 | 13195501.83 | 4325.47 | 01-JUL-03:50 | 3892.92 | 3892.92 | 70.88 | 5.84 |
August | 12396344.41 | 11156709.97 | 4324.88 | 16-AUG-03:50 | 3892.39 | 3892.39 | 70.62 | 5.84 |
September | 90790409.12 | 81711368.21 | 4342.40 | 29-SEP-03:50 | 3908.16 | 3908.16 | 78.40 | 5.84 |
October | 0.439430E+09 | 0.395487E+09 | 5319.95 | 17-OCT-03:47 | 4787.95 | 4787.95 | 73.44 | 7.46 |
November | 0.751042E+09 | 0.675938E+09 | 7227.03 | 30-NOV-06:02 | 6504.32 | 6504.32 | 63.61 | 11.13 |
December | 0.909467E+09 | 0.818520E+09 | 7663.06 | 18-DEC-06:01 | 6896.75 | 6896.75 | 58.27 | 12.12 |
Annual Sum or Average | 0.856214E+10 | 0.770593E+10 | ||||||
Minimum of Months | 12396344.41 | 11156709.97 | 4324.88 | 3892.39 | 3892.39 | 58.27 | 5.84 | |
Maximum of Months | 0.375243E+10 | 0.337719E+10 | 11027.64 | 9924.87 | 9924.87 | 78.40 | 22.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 60302.86 | 54272.58 | 14.78 | 11-JAN-14:00 | 13.30 | 13.30 | 7.10 | 2.02 |
February | 8797412.50 | 7917671.25 | 664.18 | 27-FEB-15:00 | 597.76 | 597.76 | 9.05 | 19.41 |
March | 12544881.03 | 11290392.92 | 547.90 | 10-MAR-13:20 | 493.11 | 493.11 | 8.70 | 17.66 |
April | 0.179838E+09 | 0.161854E+09 | 8534.54 | 26-APR-15:40 | 7681.08 | 7681.08 | 7.22 | 60.18 |
May | 0.368764E+09 | 0.331888E+09 | 9475.33 | 04-MAY-14:40 | 8527.80 | 8527.80 | 7.27 | 62.80 |
June | 0.859507E+09 | 0.773557E+09 | 11007.69 | 22-JUN-15:40 | 9906.92 | 9906.92 | 7.30 | 66.73 |
July | 0.147831E+10 | 0.133047E+10 | 8308.38 | 06-JUL-16:00 | 7477.55 | 7477.55 | 7.49 | 59.52 |
August | 0.195396E+10 | 0.175856E+10 | 6601.87 | 21-AUG-14:40 | 5941.68 | 5941.68 | 7.26 | 54.14 |
September | 0.778906E+09 | 0.701015E+09 | 8761.31 | 08-SEP-14:40 | 7885.17 | 7885.17 | 7.57 | 60.82 |
October | 60540655.07 | 54486589.56 | 1733.11 | 04-OCT-15:00 | 1559.80 | 1559.80 | 7.91 | 30.38 |
November | 16787503.41 | 15108753.07 | 1166.31 | 04-NOV-13:00 | 1049.68 | 1049.68 | 8.97 | 25.34 |
December | 52182.20 | 46963.98 | 40.91 | 16-DEC-04:01 | 36.82 | 36.82 | 8.47 | 4.11 |
Annual Sum or Average | 0.571806E+10 | 0.514626E+10 | ||||||
Minimum of Months | 52182.20 | 46963.98 | 14.78 | 13.30 | 13.30 | 7.10 | 2.02 | |
Maximum of Months | 0.195396E+10 | 0.175856E+10 | 11007.69 | 9906.92 | 9906.92 | 9.05 | 66.73 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967962.60 | 3590388.78 | 5.96 | 01-JAN-06:01 | 1.79 | 1.79 | 73.36 | 0.44 |
February | 10809772.67 | 3242931.80 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 63.70 | 0.44 |
March | 11967962.60 | 3590388.78 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 63.78 | 0.44 |
April | 11581899.29 | 3474569.79 | 5.96 | 01-APR-05:02 | 1.79 | 1.79 | 61.55 | 0.44 |
May | 11967962.60 | 3590388.78 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 69.29 | 0.44 |
June | 11581899.29 | 3474569.79 | 5.96 | 01-JUN-05:01 | 1.79 | 1.79 | 58.43 | 0.44 |
July | 11967962.60 | 3590388.78 | 5.96 | 01-JUL-05:01 | 1.79 | 1.79 | 58.69 | 0.44 |
August | 11967962.60 | 3590388.78 | 5.96 | 01-AUG-05:01 | 1.79 | 1.79 | 58.87 | 0.44 |
September | 11581899.29 | 3474569.79 | 5.96 | 01-SEP-05:01 | 1.79 | 1.79 | 59.15 | 0.44 |
October | 11967962.60 | 3590388.78 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 71.89 | 0.44 |
November | 11581899.29 | 3474569.79 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 64.07 | 0.44 |
December | 11967962.60 | 3590388.78 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 61.80 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273932.42 | ||||||
Minimum of Months | 10809772.67 | 3242931.80 | 5.96 | 1.79 | 1.79 | 58.43 | 0.44 | |
Maximum of Months | 11967962.60 | 3590388.78 | 5.96 | 1.79 | 1.79 | 73.36 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.778531E+09 | 0.700678E+09 | 6843.63 | 01-JAN-10:52 | 6159.27 | 6159.27 | 8.40 | 85.71 |
February | 0.942801E+09 | 0.848521E+09 | 6843.63 | 01-FEB-06:03 | 6159.27 | 6159.27 | 8.49 | 85.71 |
March | 0.142998E+10 | 0.128698E+10 | 6843.63 | 01-MAR-05:03 | 6159.27 | 6159.27 | 8.42 | 85.71 |
April | 0.339154E+10 | 0.305239E+10 | 6843.63 | 01-APR-05:02 | 6159.27 | 6159.27 | 8.40 | 85.71 |
May | 0.584106E+10 | 0.525695E+10 | 6843.63 | 01-MAY-02:61 | 6159.27 | 6159.27 | 8.49 | 85.71 |
June | 0.848166E+10 | 0.763350E+10 | 6843.63 | 01-JUN-03:01 | 6159.27 | 6159.27 | 8.98 | 85.71 |
July | 0.114465E+11 | 0.103018E+11 | 6843.63 | 01-JUL-03:01 | 6159.27 | 6159.27 | 9.05 | 85.71 |
August | 0.126249E+11 | 0.113624E+11 | 6843.63 | 01-AUG-00:42 | 6159.27 | 6159.27 | 8.20 | 85.71 |
September | 0.739166E+10 | 0.665249E+10 | 6843.63 | 01-SEP-01:02 | 6159.27 | 6159.27 | 8.35 | 85.71 |
October | 0.299622E+10 | 0.269660E+10 | 6843.63 | 01-OCT-13:10 | 6159.27 | 6159.27 | 8.37 | 85.71 |
November | 0.142274E+10 | 0.128047E+10 | 6843.63 | 01-NOV-03:01 | 6159.27 | 6159.27 | 8.46 | 85.71 |
December | 0.740207E+09 | 0.666186E+09 | 6843.63 | 01-DEC-11:50 | 6159.27 | 6159.27 | 8.40 | 85.71 |
Annual Sum or Average | 0.574878E+11 | 0.517390E+11 | ||||||
Minimum of Months | 0.740207E+09 | 0.666186E+09 | 6843.63 | 6159.27 | 6159.27 | 8.20 | 85.71 | |
Maximum of Months | 0.126249E+11 | 0.113624E+11 | 6843.63 | 6159.27 | 6159.27 | 9.05 | 85.71 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.890021E+10 | 0.801019E+10 | 3322.96 | 01-JAN-00:05 | 2990.66 | 2990.66 | 21.46 | 13.88 |
February | 0.803890E+10 | 0.723501E+10 | 3322.96 | 01-FEB-00:10 | 2990.66 | 2990.66 | 24.06 | 13.88 |
March | 0.890021E+10 | 0.801019E+10 | 3322.96 | 01-MAR-00:10 | 2990.66 | 2990.66 | 26.90 | 13.88 |
April | 0.861310E+10 | 0.775179E+10 | 3322.96 | 01-APR-00:10 | 2990.66 | 2990.66 | 29.71 | 13.88 |
May | 0.890021E+10 | 0.801019E+10 | 3322.96 | 01-MAY-00:10 | 2990.66 | 2990.66 | 23.12 | 13.88 |
June | 0.861310E+10 | 0.775179E+10 | 3322.96 | 01-JUN-00:10 | 2990.66 | 2990.66 | 24.32 | 13.88 |
July | 0.890021E+10 | 0.801019E+10 | 3322.96 | 01-JUL-00:10 | 2990.66 | 2990.66 | 27.47 | 13.88 |
August | 0.890021E+10 | 0.801019E+10 | 3322.96 | 01-AUG-00:05 | 2990.66 | 2990.66 | 33.00 | 13.88 |
September | 0.861310E+10 | 0.775179E+10 | 3322.96 | 01-SEP-00:03 | 2990.66 | 2990.66 | 27.71 | 13.88 |
October | 0.890021E+10 | 0.801019E+10 | 3322.96 | 01-OCT-00:10 | 2990.66 | 2990.66 | 24.22 | 13.88 |
November | 0.861310E+10 | 0.775179E+10 | 3322.96 | 01-NOV-00:02 | 2990.66 | 2990.66 | 22.59 | 13.88 |
December | 0.890021E+10 | 0.801019E+10 | 3322.96 | 01-DEC-00:10 | 2990.66 | 2990.66 | 29.64 | 13.88 |
Annual Sum or Average | 0.104793E+12 | 0.943135E+11 | ||||||
Minimum of Months | 0.803890E+10 | 0.723501E+10 | 3322.96 | 2990.66 | 2990.66 | 21.46 | 13.88 | |
Maximum of Months | 0.890021E+10 | 0.801019E+10 | 3322.96 | 2990.66 | 2990.66 | 33.00 | 13.88 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.149391E+10 | 0.134452E+10 | 13133.85 | 11-JAN-15:10 | 11820.46 | 11820.46 | 21.19 | 51.58 |
February | 0.180981E+10 | 0.162883E+10 | 13164.56 | 27-FEB-15:10 | 11848.10 | 11848.10 | 24.43 | 51.58 |
March | 0.272082E+10 | 0.244874E+10 | 13158.19 | 18-MAR-14:10 | 11842.37 | 11842.37 | 23.76 | 51.58 |
April | 0.695435E+10 | 0.625892E+10 | 26357.80 | 27-APR-15:10 | 23722.02 | 23722.02 | 25.81 | 103.16 |
May | 0.117331E+11 | 0.105598E+11 | 26357.01 | 05-MAY-15:20 | 23721.31 | 23721.31 | 25.77 | 103.16 |
June | 0.173228E+11 | 0.155905E+11 | 26348.29 | 22-JUN-15:40 | 23713.46 | 23713.46 | 25.38 | 103.16 |
July | 0.246786E+11 | 0.222107E+11 | 26421.08 | 31-JUL-16:00 | 23778.97 | 23778.97 | 28.67 | 103.16 |
August | 0.296490E+11 | 0.266841E+11 | 26424.22 | 09-AUG-15:50 | 23781.80 | 23781.80 | 28.83 | 103.16 |
September | 0.155466E+11 | 0.139920E+11 | 26385.35 | 14-SEP-13:00 | 23746.82 | 23746.82 | 27.05 | 103.16 |
October | 0.577451E+10 | 0.519705E+10 | 26306.13 | 04-OCT-11:30 | 23675.51 | 23675.51 | 23.21 | 103.16 |
November | 0.276235E+10 | 0.248612E+10 | 26306.19 | 04-NOV-14:40 | 23675.57 | 23675.57 | 23.21 | 103.16 |
December | 0.142038E+10 | 0.127834E+10 | 13133.77 | 15-DEC-06:40 | 11820.39 | 11820.39 | 21.18 | 51.58 |
Annual Sum or Average | 0.121866E+12 | 0.109680E+12 | ||||||
Minimum of Months | 0.142038E+10 | 0.127834E+10 | 13133.77 | 11820.39 | 11820.39 | 21.18 | 51.58 | |
Maximum of Months | 0.296490E+11 | 0.266841E+11 | 26424.22 | 23781.80 | 23781.80 | 28.83 | 103.16 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 4185.27 | 35251.85 | 16-JAN-11:00 | 79.08 | 81.03 | 13635.31 | 52070.99 | 31-JAN-12:40 |
February | 3958.02 | 35048.58 | 20-FEB-11:00 | 78.97 | 80.93 | 13804.08 | 52136.84 | 08-FEB-12:40 |
March | 2969.74 | 33708.34 | 27-MAR-05:10 | 78.25 | 81.56 | 14783.06 | 51941.56 | 02-MAR-12:50 |
April | 3869.68 | 33911.05 | 17-APR-05:08 | 78.36 | 81.62 | 13257.56 | 50818.76 | 03-APR-11:40 |
May | 4292.72 | 37723.03 | 29-MAY-10:00 | 80.41 | 82.21 | 13254.97 | 49276.18 | 01-MAY-11:30 |
June | 4048.00 | 33613.09 | 26-JUN-05:20 | 78.20 | 81.22 | 13157.83 | 47334.73 | 01-JUN-11:40 |
July | 5450.56 | 33922.25 | 31-JUL-05:20 | 78.36 | 81.31 | 11533.36 | 45717.56 | 03-JUL-11:30 |
August | 4177.29 | 33945.52 | 27-AUG-23:00 | 78.38 | 80.08 | 12764.35 | 45101.80 | 31-AUG-11:50 |
September | 4952.31 | 37943.10 | 04-SEP-09:13 | 80.53 | 82.22 | 12006.17 | 46054.99 | 29-SEP-12:00 |
October | 5165.40 | 37846.55 | 09-OCT-10:00 | 80.48 | 82.22 | 12315.38 | 47795.15 | 31-OCT-11:40 |
November | 4911.38 | 36877.01 | 12-NOV-11:00 | 79.96 | 81.79 | 12960.91 | 49637.53 | 30-NOV-12:40 |
December | 4348.54 | 35894.11 | 25-DEC-11:00 | 79.43 | 81.35 | 12947.58 | 51150.58 | 29-DEC-12:40 |
Annual Sum or Average | 4363.12 | 13030.80 | ||||||
Minimum of Months | 2969.74 | 33613.09 | 78.20 | 80.08 | 11533.36 | 45101.80 | ||
Maximum of Months | 5450.56 | 37943.10 | 80.53 | 82.22 | 14783.06 | 52136.84 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 33.46 | 6453.62 | 15-JAN-16:55 | 81.51 | 81.51 | 73630.81 | 1219872.59 | 02-JAN-06:01 |
February | 8.53 | 3072.60 | 20-FEB-18:45 | 80.48 | 80.48 | 44279.88 | 668405.60 | 21-FEB-06:03 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 73.76 | 73.76 | 10759.14 | 468513.82 | 13-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 74.18 | 74.18 | 3961.09 | 647685.24 | 18-APR-03:47 |
May | 20.30 | 6929.58 | 13-MAY-06:40 | 80.09 | 80.09 | 706.58 | 280391.75 | 02-MAY-03:47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 71.70 | 71.70 | 483.80 | 350948.59 | 15-JUN-03:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 70.93 | 70.93 | 271.04 | 215661.06 | 20-JUL-03:45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 70.60 | 70.60 | 232.06 | 219549.77 | 19-AUG-03:45 |
September | 0.51 | 1486.80 | 28-SEP-07:40 | 79.60 | 79.60 | 890.36 | 266040.42 | 20-SEP-03:47 |
October | 0.00 | 1.17 | 13-OCT-17:20 | 79.47 | 79.47 | 4184.78 | 677655.56 | 22-OCT-22:15 |
November | 0.26 | 151.39 | 09-NOV-16:10 | 79.75 | 79.75 | 23223.80 | 800001.65 | 27-NOV-06:02 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 47.89 | 47.89 | 49574.83 | 1213056.84 | 18-DEC-05:01 |
Annual Sum or Average | 5.28 | 17580.12 | ||||||
Minimum of Months | 0.00 | 0.00 | 47.89 | 47.89 | 232.06 | 215661.06 | ||
Maximum of Months | 33.46 | 6929.58 | 81.51 | 81.51 | 73630.81 | 1219872.59 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 582.12 | 54966.56 | 11-JAN-16:00 | 8.52 | 8.45 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 8777.76 | 1016952.02 | 27-FEB-15:00 | 10.54 | 9.11 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13871.62 | 799800.06 | 18-MAR-14:00 | 9.93 | 8.81 | 31.12 | 84291.63 | 22-MAR-05:10 |
April | 69285.45 | 1301315.03 | 26-APR-15:40 | 10.64 | 7.02 | 7.94 | 42631.91 | 02-APR-03:02 |
May | 139555.17 | 1280177.21 | 04-MAY-14:50 | 10.62 | 8.47 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 249439.13 | 1315077.61 | 22-JUN-15:40 | 10.76 | 7.10 | 33.00 | 170840.86 | 11-JUN-23:01 |
July | 370522.01 | 1369713.87 | 31-JUL-16:00 | 10.51 | 6.70 | 15.93 | 49172.02 | 25-JUL-00:42 |
August | 441323.74 | 1504868.07 | 29-AUG-14:40 | 10.89 | 6.70 | 34.14 | 79564.79 | 23-AUG-00:32 |
September | 215606.85 | 1313583.17 | 14-SEP-13:00 | 10.94 | 7.29 | 102.84 | 192787.76 | 24-SEP-14:12 |
October | 45079.45 | 1034124.10 | 04-OCT-11:50 | 10.54 | 9.08 | 1.52 | 36125.89 | 08-OCT-17:12 |
November | 9298.48 | 1035399.11 | 04-NOV-14:50 | 10.43 | 8.96 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 515.36 | 55534.29 | 16-DEC-06:03 | 8.52 | 8.45 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 131259.20 | 18.84 | ||||||
Minimum of Months | 515.36 | 54966.56 | 8.52 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 441323.74 | 1504868.07 | 10.94 | 9.11 | 102.84 | 192787.76 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 56.81 | 30383.67 | 11-JAN-16:00 | 12.88 | 8.45 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5585.05 | 709276.18 | 27-FEB-15:00 | 15.43 | 9.04 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8874.17 | 522186.04 | 18-MAR-14:00 | 15.74 | 8.78 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 53051.91 | 1382079.97 | 26-APR-15:40 | 12.18 | 7.01 | 0.00 | 0.00 | 01-APR-00:10 |
May | 108182.50 | 1376608.60 | 04-MAY-14:40 | 11.93 | 8.33 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 197943.17 | 1426690.22 | 22-JUN-15:40 | 11.80 | 7.10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 318767.66 | 1366355.43 | 31-JUL-16:00 | 14.77 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 398428.16 | 1503817.55 | 30-AUG-13:00 | 14.50 | 7.20 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 181613.96 | 1418630.04 | 14-SEP-13:00 | 14.31 | 7.29 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 31549.31 | 1065150.24 | 04-OCT-15:00 | 15.08 | 8.72 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 6298.76 | 807536.93 | 04-NOV-13:00 | 14.31 | 8.99 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 25.28 | 59052.44 | 16-DEC-04:01 | 10.13 | 8.39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 110043.88 | 0.00 | ||||||
Minimum of Months | 25.28 | 30383.67 | 10.13 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 398428.16 | 1503817.55 | 15.74 | 9.04 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 157802.96 | 544064.00 | 13-JAN-00:20 | 29.53 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 296699.18 | 573276.46 | 14-FEB-22:41 | 30.12 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 439024.57 | 752688.95 | 18-MAR-16:00 | 33.76 | 24.42 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 619373.91 | 1335124.20 | 27-APR-16:00 | 45.40 | 32.55 | 0.00 | 0.00 | 01-APR-00:10 |
May | 199499.24 | 590696.07 | 05-MAY-16:00 | 30.48 | 26.58 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 383630.07 | 891139.21 | 28-JUN-17:00 | 36.56 | 29.57 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 624740.88 | 1315631.88 | 24-JUL-15:00 | 45.02 | 34.84 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 875540.89 | 1580100.66 | 10-AUG-17:00 | 50.23 | 37.25 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 211136.86 | 599948.82 | 14-SEP-17:00 | 30.67 | 26.64 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 311104.92 | 624568.86 | 04-OCT-15:00 | 31.17 | 24.44 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 436948.22 | 780117.17 | 04-NOV-15:00 | 34.32 | 24.93 | 0.00 | 0.00 | 01-NOV-00:02 |
December | 566383.68 | 606872.58 | 29-DEC-22:50 | 30.81 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 428047.29 | 0.00 | ||||||
Minimum of Months | 157802.96 | 544064.00 | 29.53 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 875540.89 | 1580100.66 | 50.23 | 37.25 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 49.30 | 18586.42 | 11-JAN-15:10 | 21.19 | 20.77 | 922.06 | 106245.87 | 06-JAN-05:48 |
February | 5942.61 | 718580.69 | 27-FEB-15:10 | 24.43 | 21.72 | 659.83 | 77231.51 | 06-FEB-06:40 |
March | 10038.91 | 573598.48 | 18-MAR-14:10 | 23.76 | 21.59 | 678.79 | 68997.17 | 22-MAR-13:40 |
April | 59181.97 | 2030131.29 | 27-APR-15:10 | 25.81 | 22.65 | 1002.82 | 78914.64 | 19-APR-12:00 |
May | 112181.95 | 2014630.58 | 05-MAY-15:20 | 25.77 | 22.61 | 629.61 | 70549.88 | 10-MAY-05:40 |
June | 200802.53 | 1844345.48 | 22-JUN-15:40 | 25.38 | 21.89 | 467.95 | 47368.07 | 01-JUN-09:30 |
July | 357646.08 | 3262190.77 | 31-JUL-16:00 | 28.67 | 24.95 | 390.14 | 55678.34 | 05-JUL-06:50 |
August | 531401.35 | 3859096.68 | 29-AUG-14:30 | 30.05 | 25.95 | 314.20 | 44632.68 | 19-AUG-07:20 |
September | 197032.01 | 2567199.05 | 14-SEP-13:00 | 27.05 | 23.54 | 381.36 | 55810.92 | 27-SEP-05:30 |
October | 32180.75 | 909756.15 | 04-OCT-11:30 | 23.21 | 22.35 | 696.20 | 87331.81 | 14-OCT-03:01 |
November | 6105.06 | 911188.70 | 04-NOV-14:40 | 23.21 | 22.35 | 1116.18 | 84243.51 | 13-NOV-12:50 |
December | 32.62 | 16837.54 | 15-DEC-06:40 | 21.18 | 20.55 | 797.01 | 82838.89 | 11-DEC-06:09 |
Annual Sum or Average | 127149.32 | 670.67 | ||||||
Minimum of Months | 32.62 | 16837.54 | 21.18 | 20.55 | 314.20 | 44632.68 | ||
Maximum of Months | 531401.35 | 3859096.68 | 30.05 | 25.95 | 1116.18 | 106245.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.12 | 7.48 |
February | 0.22 | 7.48 |
March | 0.14 | 7.48 |
April | 0.92 | 7.48 |
May | 0.75 | 7.48 |
June | 0.43 | 7.48 |
July | 1.71 | 7.48 |
August | 0.56 | 7.48 |
September | 0.89 | 7.48 |
October | 0.64 | 7.48 |
November | 0.33 | 7.48 |
December | 0.36 | 7.48 |
Annual Sum or Average | 7.07 | 7.48 |
Minimum of Months | 0.12 | 7.48 |
Maximum of Months | 1.71 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.56 | 12.60 |
February | 1.86 | 10.63 |
March | 2.82 | 7.39 |
April | 6.40 | 3.28 |
May | 3.97 | 6.42 |
June | 4.49 | 3.37 |
July | 12.87 | 3.00 |
August | 14.26 | 1.70 |
September | 2.56 | 3.54 |
October | 3.69 | 3.94 |
November | 2.96 | 4.29 |
December | 1.77 | 4.99 |
Annual Sum or Average | 59.21 | 3.88 |
Minimum of Months | 1.56 | 1.70 |
Maximum of Months | 14.26 | 12.60 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 9.70 |
February | 0.35 | 9.14 |
March | 0.06 | 6.72 |
April | 1.13 | 7.81 |
May | 2.06 | 8.99 |
June | 2.54 | 9.59 |
July | 1.66 | 2.98 |
August | 1.39 | 4.17 |
September | 1.24 | 5.98 |
October | 1.70 | 11.18 |
November | 0.14 | 6.72 |
December | 0.50 | 11.20 |
Annual Sum or Average | 13.26 | 7.82 |
Minimum of Months | 0.06 | 2.98 |
Maximum of Months | 2.54 | 11.20 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.25 | 10.45 |
March | 0.93 | 6.00 |
April | 0.96 | 5.74 |
May | 1.33 | 9.38 |
June | 0.78 | 7.79 |
July | 1.18 | 5.50 |
August | 0.94 | 6.72 |
September | 0.67 | 7.84 |
October | 0.69 | 8.60 |
November | 0.40 | 2.55 |
December | 0.22 | 0.00 |
Annual Sum or Average | 8.37 | 6.86 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.33 | 10.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.17 | 0.56 |
March | 0.28 | 0.34 |
April | 0.60 | 0.27 |
May | 0.81 | 0.44 |
June | 0.75 | 0.52 |
July | 2.48 | 0.30 |
August | 3.69 | 0.25 |
September | 0.78 | 0.32 |
October | 0.55 | 0.28 |
November | 0.42 | 0.28 |
December | 0.11 | 0.84 |
Annual Sum or Average | 10.63 | 0.32 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.69 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.63 | 0.71 |
February | 1.74 | 0.67 |
March | 2.29 | 0.36 |
April | 6.12 | 0.28 |
May | 4.76 | 0.41 |
June | 5.75 | 0.23 |
July | 11.84 | 0.24 |
August | 14.07 | 0.17 |
September | 4.46 | 0.23 |
October | 3.93 | 0.33 |
November | 2.67 | 0.32 |
December | 1.08 | 0.35 |
Annual Sum or Average | 59.34 | 0.27 |
Minimum of Months | 0.63 | 0.17 |
Maximum of Months | 14.07 | 0.71 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.22 | 0.84 |
February | 1.04 | 0.90 |
March | 2.12 | 0.52 |
April | 5.74 | 0.42 |
May | 4.54 | 0.68 |
June | 5.42 | 0.37 |
July | 10.66 | 0.33 |
August | 12.96 | 0.26 |
September | 4.02 | 0.34 |
October | 2.95 | 0.49 |
November | 1.94 | 0.42 |
December | 0.82 | 0.44 |
Annual Sum or Average | 52.44 | 0.39 |
Minimum of Months | 0.22 | 0.26 |
Maximum of Months | 12.96 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.91 | 0.77 |
February | 3.41 | 0.54 |
March | 6.32 | 0.31 |
April | 8.43 | 0.27 |
May | 7.18 | 0.34 |
June | 6.14 | 0.26 |
July | 14.20 | 0.23 |
August | 16.80 | 0.17 |
September | 5.96 | 0.22 |
October | 6.96 | 0.28 |
November | 4.92 | 0.27 |
December | 4.77 | 0.23 |
Annual Sum or Average | 87.00 | 0.27 |
Minimum of Months | 1.91 | 0.17 |
Maximum of Months | 16.80 | 0.77 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.04 | 0.84 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.11 | 0.00 |
May | 0.27 | 0.49 |
June | 0.23 | 0.64 |
July | 0.79 | 0.04 |
August | 0.94 | 0.19 |
September | 0.69 | 0.39 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 3.08 | 0.26 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.94 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.10 | 0.54 |
February | 0.14 | 0.54 |
March | 0.14 | 0.87 |
April | 0.94 | 0.46 |
May | 2.99 | 0.47 |
June | 3.12 | 0.31 |
July | 4.58 | 0.34 |
August | 4.51 | 0.32 |
September | 3.08 | 0.36 |
October | 1.07 | 0.44 |
November | 0.14 | 0.54 |
December | 0.25 | 0.54 |
Annual Sum or Average | 21.04 | 0.37 |
Minimum of Months | 0.10 | 0.31 |
Maximum of Months | 4.58 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.28 | 0.84 |
February | 0.19 | 0.84 |
March | 0.28 | 1.52 |
April | 0.85 | 0.80 |
May | 2.72 | 0.77 |
June | 2.47 | 0.46 |
July | 3.29 | 0.54 |
August | 3.62 | 0.45 |
September | 2.71 | 0.50 |
October | 0.88 | 0.66 |
November | 0.14 | 0.84 |
December | 0.49 | 0.84 |
Annual Sum or Average | 17.90 | 0.59 |
Minimum of Months | 0.14 | 0.45 |
Maximum of Months | 3.62 | 1.52 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.11 | 0.54 |
February | 0.19 | 0.54 |
March | 0.36 | 1.00 |
April | 1.64 | 0.52 |
May | 3.67 | 0.54 |
June | 3.53 | 0.33 |
July | 5.19 | 0.35 |
August | 3.75 | 0.30 |
September | 3.15 | 0.33 |
October | 1.18 | 0.45 |
November | 0.22 | 0.54 |
December | 0.23 | 0.54 |
Annual Sum or Average | 23.23 | 0.40 |
Minimum of Months | 0.11 | 0.30 |
Maximum of Months | 5.19 | 1.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.54 | 0.76 |
February | 0.28 | 0.67 |
March | 0.04 | 0.84 |
April | 0.06 | 0.00 |
May | 0.21 | 1.29 |
June | 0.09 | 0.84 |
July | 0.35 | 0.41 |
August | 0.68 | 0.70 |
September | 0.22 | 1.05 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.18 | 0.65 |
Annual Sum or Average | 2.65 | 0.74 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.68 | 1.29 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.26 | 0.54 |
February | 0.33 | 0.54 |
March | 0.10 | 0.54 |
April | 0.78 | 0.52 |
May | 1.76 | 0.52 |
June | 1.73 | 0.54 |
July | 3.42 | 0.46 |
August | 3.07 | 0.37 |
September | 1.30 | 0.66 |
October | 0.24 | 0.54 |
November | 0.00 | 0.00 |
December | 0.22 | 0.54 |
Annual Sum or Average | 13.22 | 0.49 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.42 | 0.66 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.26 | 0.84 |
February | 0.06 | 0.84 |
March | 0.00 | 0.00 |
April | 0.73 | 0.81 |
May | 1.77 | 0.95 |
June | 1.26 | 0.83 |
July | 3.14 | 0.79 |
August | 2.47 | 0.56 |
September | 1.30 | 1.02 |
October | 0.44 | 1.00 |
November | 0.07 | 0.84 |
December | 0.14 | 0.84 |
Annual Sum or Average | 11.65 | 0.81 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.14 | 1.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.18 | 0.54 |
February | 0.06 | 0.54 |
March | 0.10 | 0.54 |
April | 0.93 | 0.53 |
May | 2.47 | 0.64 |
June | 1.89 | 0.53 |
July | 3.37 | 0.49 |
August | 2.96 | 0.39 |
September | 1.65 | 0.69 |
October | 0.53 | 0.63 |
November | 0.03 | 0.54 |
December | 0.06 | 0.54 |
Annual Sum or Average | 14.23 | 0.54 |
Minimum of Months | 0.03 | 0.39 |
Maximum of Months | 3.37 | 0.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 7.72 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 7.72 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.72 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 51.61 | 0.00 |
February | 2.42 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 54.02 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 51.61 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 4.25 | 0.00 |
February | 3.13 | 0.00 |
March | 2.30 | 0.00 |
April | 0.54 | 0.00 |
May | 0.18 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 2.09 | 0.00 |
November | 1.68 | 0.00 |
December | 0.64 | 0.00 |
Annual Sum or Average | 14.80 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.25 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.172034E+10 | 0.00 | 2145849.21 | 0.141365E+11 | 0.00 | 0.00 |
February | 57571943.22 | 0.00 | 0.489577E+09 | 0.125012E+11 | 0.00 | 0.00 |
March | 0.498378E+09 | 0.00 | 0.147244E+09 | 0.150446E+11 | 0.00 | 0.00 |
April | 0.820805E+09 | 0.00 | 0.399442E+10 | 0.138098E+11 | 0.00 | 0.00 |
May | 0.525159E+09 | 0.00 | 0.762963E+10 | 0.147933E+11 | 0.00 | 0.00 |
June | 0.118971E+10 | 0.00 | 0.159732E+11 | 0.147020E+11 | 0.00 | 0.00 |
July | 0.745834E+09 | 0.00 | 0.291708E+11 | 0.143711E+11 | 0.00 | 0.00 |
August | 0.627853E+09 | 0.00 | 0.405719E+11 | 0.154792E+11 | 0.00 | 0.00 |
September | 0.191899E+10 | 0.00 | 0.126964E+11 | 0.145600E+11 | 0.00 | 0.00 |
October | 0.138854E+10 | 0.00 | 0.195552E+10 | 0.147342E+11 | 0.00 | 0.00 |
November | 0.181033E+10 | 0.00 | 0.327782E+09 | 0.142761E+11 | 0.00 | 0.00 |
December | 0.123058E+10 | 0.00 | 10253593.82 | 0.141682E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.125341E+11 | 0.00 | 0.112969E+12 | 0.172576E+12 | 0.00 | 0.00 |
Minimum of Months | 57571943.22 | 0.00 | 2145849.21 | 0.125012E+11 | 0.00 | 0.00 |
Maximum of Months | 0.191899E+10 | 0.00 | 0.405719E+11 | 0.154792E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.444684E+10 | 0.00 | 27656625.38 | 0.468194E+10 | 0.00 | 0.00 |
February | 0.225357E+10 | 0.00 | 0.106027E+10 | 0.505776E+10 | 0.00 | 0.00 |
March | 0.246062E+09 | 0.00 | 0.183859E+10 | 0.743255E+10 | 0.00 | 0.00 |
April | 25339356.19 | 0.00 | 0.114805E+11 | 0.786531E+10 | 0.00 | 0.00 |
May | 3358896.86 | 0.00 | 0.193883E+11 | 0.627624E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.351596E+11 | 0.660643E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.635157E+11 | 0.702878E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.861724E+11 | 0.806038E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.309195E+11 | 0.590895E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.629104E+10 | 0.650929E+10 | 0.00 | 0.00 |
November | 0.373246E+09 | 0.00 | 0.106392E+10 | 0.624081E+10 | 0.00 | 0.00 |
December | 0.134102E+10 | 0.00 | 3312.75 | 0.637856E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.868943E+10 | 0.00 | 0.256917E+12 | 0.780470E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 3312.75 | 0.468194E+10 | 0.00 | 0.00 |
Maximum of Months | 0.444684E+10 | 0.00 | 0.861724E+11 | 0.806038E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.161569E+12 | 0.00 | 0.198139E+09 | 0.343738E+11 | 0.00 | 0.00 |
February | 0.863599E+11 | 0.00 | 0.772822E+10 | 0.350211E+11 | 0.00 | 0.00 |
March | 0.201556E+11 | 0.00 | 0.142188E+11 | 0.471050E+11 | 0.00 | 0.00 |
April | 0.642980E+10 | 0.00 | 0.851643E+11 | 0.455641E+11 | 0.00 | 0.00 |
May | 0.665055E+09 | 0.00 | 0.170308E+12 | 0.503676E+11 | 0.00 | 0.00 |
June | 26731425.51 | 0.00 | 0.292298E+12 | 0.504712E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.506262E+12 | 0.502052E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.667121E+12 | 0.558834E+11 | 0.00 | 0.00 |
September | 0.162531E+09 | 0.00 | 0.277063E+12 | 0.497201E+11 | 0.00 | 0.00 |
October | 0.624323E+10 | 0.00 | 0.497579E+11 | 0.459147E+11 | 0.00 | 0.00 |
November | 0.451771E+11 | 0.00 | 0.948525E+10 | 0.378883E+11 | 0.00 | 0.00 |
December | 0.106574E+12 | 0.00 | 75935.95 | 0.362910E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.433363E+12 | 0.00 | 0.207961E+13 | 0.538806E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 75935.95 | 0.343738E+11 | 0.00 | 0.00 |
Maximum of Months | 0.161569E+12 | 0.00 | 0.667121E+12 | 0.558834E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.314637E+11 | 0.00 | 14921378.95 | 0.379513E+10 | 0.00 | 0.00 |
February | 0.189124E+11 | 0.00 | 0.686519E+09 | 0.332105E+10 | 0.00 | 0.00 |
March | 0.801869E+10 | 0.00 | 0.132873E+10 | 0.385025E+10 | 0.00 | 0.00 |
April | 0.295803E+10 | 0.00 | 0.883481E+10 | 0.390869E+10 | 0.00 | 0.00 |
May | 0.697244E+09 | 0.00 | 0.177016E+11 | 0.458101E+10 | 0.00 | 0.00 |
June | 79961130.49 | 0.00 | 0.312912E+11 | 0.490796E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.547946E+11 | 0.514587E+10 | 0.00 | 0.00 |
August | 6481051.34 | 0.00 | 0.710279E+11 | 0.563978E+10 | 0.00 | 0.00 |
September | 0.324435E+09 | 0.00 | 0.278436E+11 | 0.437405E+10 | 0.00 | 0.00 |
October | 0.342700E+10 | 0.00 | 0.457706E+10 | 0.366720E+10 | 0.00 | 0.00 |
November | 0.135225E+11 | 0.00 | 0.933283E+09 | 0.322967E+10 | 0.00 | 0.00 |
December | 0.249466E+11 | 0.00 | 258.10 | 0.338534E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.104357E+12 | 0.00 | 0.219034E+12 | 0.498060E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 258.10 | 0.322967E+10 | 0.00 | 0.00 |
Maximum of Months | 0.314637E+11 | 0.00 | 0.710279E+11 | 0.563978E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.209629E+10 | 0.00 | 0.378827E+12 | 0.177563E+12 | 0.00 | 1.04 |
February | 0.122023E+10 | 0.00 | 0.600897E+12 | 0.206948E+12 | 0.00 | 0.93 |
March | 0.494849E+09 | 0.00 | 0.954263E+12 | 0.277595E+12 | 0.00 | 0.97 |
April | 0.182087E+09 | 0.00 | 0.121032E+13 | 0.318320E+12 | 0.00 | 0.62 |
May | 0.309835E+09 | 0.00 | 0.385749E+12 | 0.176680E+12 | 0.00 | 0.24 |
June | 0.00 | 0.00 | 0.656288E+12 | 0.225868E+12 | 0.00 | 0.06 |
July | 0.00 | 0.00 | 0.981626E+12 | 0.295517E+12 | 0.00 | 0.02 |
August | 0.00 | 0.00 | 0.129077E+13 | 0.361833E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.376076E+12 | 0.170518E+12 | 0.00 | 0.01 |
October | 0.594774E+09 | 0.00 | 0.671659E+12 | 0.228198E+12 | 0.00 | 0.27 |
November | 0.511231E+09 | 0.00 | 0.924960E+12 | 0.267212E+12 | 0.00 | 0.51 |
December | 71061374.41 | 0.00 | 0.124157E+13 | 0.323180E+12 | 0.00 | 0.99 |
Annual Sum or Average | 0.548036E+10 | 0.00 | 0.967301E+13 | 0.302943E+13 | 0.00 | 5.66 |
Minimum of Months | 0.00 | 0.00 | 0.376076E+12 | 0.170518E+12 | 0.00 | 0.00 |
Maximum of Months | 0.209629E+10 | 0.00 | 0.129077E+13 | 0.361833E+12 | 0.00 | 1.04 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.540742E+10 | 0.263425E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107820E+11 | 0.349077E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.184022E+11 | 0.499204E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.239308E+11 | 0.593294E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.670001E+10 | 0.291032E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.125312E+11 | 0.402561E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.193693E+11 | 0.553216E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.257073E+11 | 0.695918E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.653866E+10 | 0.283602E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.124898E+11 | 0.397330E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.177196E+11 | 0.481421E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.241548E+11 | 0.591980E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.183733E+12 | 0.540206E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.540742E+10 | 0.263425E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.257073E+11 | 0.695918E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.277798E+11 | 0.203466E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.846992E+11 | 0.299989E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160209E+12 | 0.450487E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.218013E+12 | 0.549755E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.554595E+11 | 0.261305E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.112550E+12 | 0.371403E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.180080E+12 | 0.519600E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.241325E+12 | 0.657419E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.547851E+11 | 0.255877E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105613E+12 | 0.354761E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.150464E+12 | 0.427967E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.207583E+12 | 0.528396E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.159856E+13 | 0.488043E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.277798E+11 | 0.203466E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.241325E+12 | 0.657419E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.127107E+10 | 0.172799E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.670958E+10 | 0.268627E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.146644E+11 | 0.429613E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.209712E+11 | 0.539248E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.502029E+10 | 0.253255E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.110380E+11 | 0.370044E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.178812E+11 | 0.520585E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.239326E+11 | 0.657618E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.491762E+10 | 0.247079E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.935339E+10 | 0.334842E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.133691E+11 | 0.401251E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.186237E+11 | 0.496010E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.147752E+12 | 0.469097E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.127107E+10 | 0.172799E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.239326E+11 | 0.657618E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141365E+11 | 2145849.21 | 0.172034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125012E+11 | 0.489577E+09 | 57571943.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150446E+11 | 0.147244E+09 | 0.498378E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138098E+11 | 0.399442E+10 | 0.820805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147933E+11 | 0.762963E+10 | 0.525159E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147020E+11 | 0.159732E+11 | 0.118971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143711E+11 | 0.291708E+11 | 0.745834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154792E+11 | 0.405719E+11 | 0.627853E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145600E+11 | 0.126964E+11 | 0.191899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147342E+11 | 0.195552E+10 | 0.138854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142761E+11 | 0.327782E+09 | 0.181033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141682E+11 | 10253593.82 | 0.123058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172576E+12 | 0.112969E+12 | 0.125341E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125012E+11 | 2145849.21 | 57571943.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154792E+11 | 0.405719E+11 | 0.191899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.468194E+10 | 27656625.38 | 0.444684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.505776E+10 | 0.106027E+10 | 0.225357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.743255E+10 | 0.183859E+10 | 0.246062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786531E+10 | 0.114805E+11 | 25339356.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.627624E+10 | 0.193883E+11 | 3358896.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.660643E+10 | 0.351596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702878E+10 | 0.635157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.806038E+10 | 0.861724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.590895E+10 | 0.309195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.650929E+10 | 0.629104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.624081E+10 | 0.106392E+10 | 0.373246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.637856E+10 | 3312.75 | 0.134102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780470E+11 | 0.256917E+12 | 0.868943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.468194E+10 | 3312.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.806038E+10 | 0.861724E+11 | 0.444684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.343738E+11 | 0.198139E+09 | 0.161569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350211E+11 | 0.772822E+10 | 0.863599E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.471050E+11 | 0.142188E+11 | 0.201556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.455641E+11 | 0.851643E+11 | 0.642980E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.503676E+11 | 0.170308E+12 | 0.665055E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.504712E+11 | 0.292298E+12 | 26731425.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.502052E+11 | 0.506262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.558834E+11 | 0.667121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.497201E+11 | 0.277063E+12 | 0.162531E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.459147E+11 | 0.497579E+11 | 0.624323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378883E+11 | 0.948525E+10 | 0.451771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362910E+11 | 75935.95 | 0.106574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538806E+12 | 0.207961E+13 | 0.433363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.343738E+11 | 75935.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.558834E+11 | 0.667121E+12 | 0.161569E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.379513E+10 | 14921378.95 | 0.314637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332105E+10 | 0.686519E+09 | 0.189124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385025E+10 | 0.132873E+10 | 0.801869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390869E+10 | 0.883481E+10 | 0.295803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.458101E+10 | 0.177016E+11 | 0.697244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490796E+10 | 0.312912E+11 | 79961130.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.514587E+10 | 0.547946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.563978E+10 | 0.710279E+11 | 6481051.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.437405E+10 | 0.278436E+11 | 0.324435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.366720E+10 | 0.457706E+10 | 0.342700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322967E+10 | 0.933283E+09 | 0.135225E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338534E+10 | 258.10 | 0.249466E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498060E+11 | 0.219034E+12 | 0.104357E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.322967E+10 | 258.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.563978E+10 | 0.710279E+11 | 0.314637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.954788E+11 | 0.323277E+12 | 0.209629E+10 | 0.00 | 0.00 | 0.279028E+10 | 0.00 | 0.00 |
February | 0.862389E+11 | 0.513086E+12 | 0.122023E+10 | 0.00 | 0.00 | 0.247597E+10 | 0.00 | 0.00 |
March | 0.954788E+11 | 0.814082E+12 | 0.494849E+09 | 0.00 | 0.00 | 0.260316E+10 | 0.00 | 0.00 |
April | 0.923988E+11 | 0.102793E+13 | 0.182087E+09 | 0.00 | 0.00 | 0.165325E+10 | 0.00 | 0.00 |
May | 0.954788E+11 | 0.328473E+12 | 0.309835E+09 | 0.00 | 0.00 | 0.653427E+09 | 0.00 | 0.00 |
June | 0.923988E+11 | 0.555632E+12 | 0.00 | 0.00 | 0.00 | 0.173920E+09 | 0.00 | 0.00 |
July | 0.954788E+11 | 0.823042E+12 | 0.00 | 0.00 | 0.00 | 46181121.32 | 0.00 | 0.00 |
August | 0.954788E+11 | 0.106965E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.923988E+11 | 0.320937E+12 | 0.00 | 0.00 | 0.00 | 16665436.32 | 0.00 | 0.00 |
October | 0.954788E+11 | 0.573088E+12 | 0.594774E+09 | 0.00 | 0.00 | 0.732412E+09 | 0.00 | 0.00 |
November | 0.923988E+11 | 0.789899E+12 | 0.511231E+09 | 0.00 | 0.00 | 0.137418E+10 | 0.00 | 0.00 |
December | 0.954788E+11 | 0.105941E+13 | 71061374.41 | 0.00 | 0.00 | 0.263982E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112419E+13 | 0.819851E+13 | 0.548036E+10 | 0.00 | 0.00 | 0.151593E+11 | 0.00 | 0.00 |
Minimum of Months | 0.862389E+11 | 0.320937E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.954788E+11 | 0.106965E+13 | 0.209629E+10 | 0.00 | 0.00 | 0.279028E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147906E+10 | 0.459563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133592E+10 | 0.915942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147906E+10 | 0.156313E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143135E+10 | 0.202194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147906E+10 | 0.567176E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143135E+10 | 0.105413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147906E+10 | 0.160754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147906E+10 | 0.210278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143135E+10 | 0.552722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147906E+10 | 0.106017E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143135E+10 | 0.150534E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147906E+10 | 0.205305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174147E+11 | 0.154635E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133592E+10 | 0.459563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147906E+10 | 0.210278E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141341E+11 | 0.236102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127663E+11 | 0.719512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141341E+11 | 0.136083E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136781E+11 | 0.184176E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141341E+11 | 0.469351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136781E+11 | 0.946549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141341E+11 | 0.149434E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141341E+11 | 0.197348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136781E+11 | 0.462947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141341E+11 | 0.896415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136781E+11 | 0.127822E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141341E+11 | 0.176435E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166417E+12 | 0.134439E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127663E+11 | 0.236102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141341E+11 | 0.197348E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143512E+10 | 0.108041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129623E+10 | 0.569950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143512E+10 | 0.124556E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138882E+10 | 0.177123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143512E+10 | 0.424606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138882E+10 | 0.927918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143512E+10 | 0.148322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143512E+10 | 0.195631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138882E+10 | 0.415241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143512E+10 | 0.793794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138882E+10 | 0.113566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143512E+10 | 0.158292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168973E+11 | 0.124145E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129623E+10 | 0.108041E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143512E+10 | 0.195631E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.141365E+11 | 0.172034E+10 | 2145849.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125012E+11 | 57571943.22 | 0.489577E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.150446E+11 | 0.498378E+09 | 0.147244E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138098E+11 | 0.820805E+09 | 0.399442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147933E+11 | 0.525159E+09 | 0.762963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147020E+11 | 0.118971E+10 | 0.159732E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143711E+11 | 0.745834E+09 | 0.291708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.154792E+11 | 0.627853E+09 | 0.405719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145600E+11 | 0.191899E+10 | 0.126964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147342E+11 | 0.138854E+10 | 0.195552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142761E+11 | 0.181033E+10 | 0.327782E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141682E+11 | 0.123058E+10 | 10253593.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.172576E+12 | 0.125341E+11 | 0.112969E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.125012E+11 | 57571943.22 | 2145849.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.154792E+11 | 0.191899E+10 | 0.405719E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.468194E+10 | 0.444684E+10 | 27656625.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.505776E+10 | 0.225357E+10 | 0.106027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.743255E+10 | 0.246062E+09 | 0.183859E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.786531E+10 | 25339356.19 | 0.114805E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.627624E+10 | 3358896.86 | 0.193883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.660643E+10 | 0.00 | 0.351596E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.702878E+10 | 0.00 | 0.635157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.806038E+10 | 0.00 | 0.861724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.590895E+10 | 0.00 | 0.309195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.650929E+10 | 0.00 | 0.629104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.624081E+10 | 0.373246E+09 | 0.106392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.637856E+10 | 0.134102E+10 | 3312.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780470E+11 | 0.868943E+10 | 0.256917E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.468194E+10 | 0.00 | 3312.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.806038E+10 | 0.444684E+10 | 0.861724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.343738E+11 | 0.161569E+12 | 0.198139E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.350211E+11 | 0.863599E+11 | 0.772822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.471050E+11 | 0.201556E+11 | 0.142188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.455641E+11 | 0.642980E+10 | 0.851643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.503676E+11 | 0.665055E+09 | 0.170308E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.504712E+11 | 26731425.51 | 0.292298E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.502052E+11 | 0.00 | 0.506262E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.558834E+11 | 0.00 | 0.667121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.497201E+11 | 0.162531E+09 | 0.277063E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.459147E+11 | 0.624323E+10 | 0.497579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.378883E+11 | 0.451771E+11 | 0.948525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.362910E+11 | 0.106574E+12 | 75935.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.538806E+12 | 0.433363E+12 | 0.207961E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.343738E+11 | 0.00 | 75935.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.558834E+11 | 0.161569E+12 | 0.667121E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.379513E+10 | 0.314637E+11 | 14921378.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.332105E+10 | 0.189124E+11 | 0.686519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.385025E+10 | 0.801869E+10 | 0.132873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.390869E+10 | 0.295803E+10 | 0.883481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.458101E+10 | 0.697244E+09 | 0.177016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490796E+10 | 79961130.49 | 0.312912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.514587E+10 | 0.00 | 0.547946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.563978E+10 | 6481051.34 | 0.710279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.437405E+10 | 0.324435E+09 | 0.278436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.366720E+10 | 0.342700E+10 | 0.457706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.322967E+10 | 0.135225E+11 | 0.933283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.338534E+10 | 0.249466E+11 | 258.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.498060E+11 | 0.104357E+12 | 0.219034E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.322967E+10 | 0.00 | 258.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.563978E+10 | 0.314637E+11 | 0.710279E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.954788E+11 | 0.209629E+10 | 0.378827E+12 | 0.00 | 0.792812E+11 | 0.00 | 0.00 | 0.00 | 0.280284E+10 | 0.00 | 0.00 | 0.00 |
February | 0.862389E+11 | 0.122023E+10 | 0.600897E+12 | 0.00 | 0.118222E+12 | 0.00 | 0.00 | 0.00 | 0.248712E+10 | 0.00 | 0.00 | 0.00 |
March | 0.954788E+11 | 0.494849E+09 | 0.954263E+12 | 0.00 | 0.179501E+12 | 0.00 | 0.00 | 0.00 | 0.261488E+10 | 0.00 | 0.00 | 0.00 |
April | 0.923988E+11 | 0.182087E+09 | 0.121032E+13 | 0.00 | 0.224261E+12 | 0.00 | 0.00 | 0.00 | 0.166070E+10 | 0.00 | 0.00 | 0.00 |
May | 0.954788E+11 | 0.309835E+09 | 0.385749E+12 | 0.00 | 0.805449E+11 | 0.00 | 0.00 | 0.00 | 0.656368E+09 | 0.00 | 0.00 | 0.00 |
June | 0.923988E+11 | 0.00 | 0.656288E+12 | 0.00 | 0.133295E+12 | 0.00 | 0.00 | 0.00 | 0.174703E+09 | 0.00 | 0.00 | 0.00 |
July | 0.954788E+11 | 0.00 | 0.981626E+12 | 0.00 | 0.199992E+12 | 0.00 | 0.00 | 0.00 | 46389001.26 | 0.00 | 0.00 | 0.00 |
August | 0.954788E+11 | 0.00 | 0.129077E+13 | 0.00 | 0.266354E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.923988E+11 | 0.00 | 0.376076E+12 | 0.00 | 0.781027E+11 | 0.00 | 0.00 | 0.00 | 16740454.20 | 0.00 | 0.00 | 0.00 |
October | 0.954788E+11 | 0.594774E+09 | 0.671659E+12 | 0.00 | 0.131983E+12 | 0.00 | 0.00 | 0.00 | 0.735708E+09 | 0.00 | 0.00 | 0.00 |
November | 0.923988E+11 | 0.511231E+09 | 0.924960E+12 | 0.00 | 0.173433E+12 | 0.00 | 0.00 | 0.00 | 0.138037E+10 | 0.00 | 0.00 | 0.00 |
December | 0.954788E+11 | 71061374.41 | 0.124157E+13 | 0.00 | 0.225050E+12 | 0.00 | 0.00 | 0.00 | 0.265171E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112419E+13 | 0.548036E+10 | 0.967301E+13 | 0.00 | 0.189002E+13 | 0.00 | 0.00 | 0.00 | 0.152275E+11 | 0.00 | 0.00 | |
Minimum of Months | 0.862389E+11 | 0.00 | 0.376076E+12 | 0.00 | 0.781027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.954788E+11 | 0.209629E+10 | 0.129077E+13 | 0.00 | 0.266354E+12 | 0.00 | 0.00 | 0.00 | 0.280284E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.147906E+10 | 0.00 | 0.540742E+10 | 0.00 | 0.115519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133592E+10 | 0.00 | 0.107820E+11 | 0.00 | 0.215484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147906E+10 | 0.00 | 0.184022E+11 | 0.00 | 0.351298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143135E+10 | 0.00 | 0.239308E+11 | 0.00 | 0.450160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147906E+10 | 0.00 | 0.670001E+10 | 0.00 | 0.143126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.143135E+10 | 0.00 | 0.125312E+11 | 0.00 | 0.259427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147906E+10 | 0.00 | 0.193693E+11 | 0.00 | 0.405310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147906E+10 | 0.00 | 0.257073E+11 | 0.00 | 0.548013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143135E+10 | 0.00 | 0.653866E+10 | 0.00 | 0.140467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147906E+10 | 0.00 | 0.124898E+11 | 0.00 | 0.249424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143135E+10 | 0.00 | 0.177196E+11 | 0.00 | 0.338287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147906E+10 | 0.00 | 0.241548E+11 | 0.00 | 0.444074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174147E+11 | 0.00 | 0.183733E+12 | 0.00 | 0.366059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.133592E+10 | 0.00 | 0.540742E+10 | 0.00 | 0.115519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147906E+10 | 0.00 | 0.257073E+11 | 0.00 | 0.548013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.141341E+11 | 0.00 | 0.277798E+11 | 0.00 | 0.621250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127663E+11 | 0.00 | 0.846992E+11 | 0.00 | 0.172326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.141341E+11 | 0.00 | 0.160209E+12 | 0.00 | 0.309146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136781E+11 | 0.00 | 0.218013E+12 | 0.00 | 0.412973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141341E+11 | 0.00 | 0.554595E+11 | 0.00 | 0.119964E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136781E+11 | 0.00 | 0.112550E+12 | 0.00 | 0.234621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141341E+11 | 0.00 | 0.180080E+12 | 0.00 | 0.378260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.141341E+11 | 0.00 | 0.241325E+12 | 0.00 | 0.516079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136781E+11 | 0.00 | 0.547851E+11 | 0.00 | 0.119095E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141341E+11 | 0.00 | 0.105613E+12 | 0.00 | 0.213420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136781E+11 | 0.00 | 0.150464E+12 | 0.00 | 0.291186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141341E+11 | 0.00 | 0.207583E+12 | 0.00 | 0.387056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166417E+12 | 0.00 | 0.159856E+13 | 0.00 | 0.321625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.127663E+11 | 0.00 | 0.277798E+11 | 0.00 | 0.621250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.141341E+11 | 0.00 | 0.241325E+12 | 0.00 | 0.516079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.143512E+10 | 0.00 | 0.127107E+10 | 0.00 | 0.292869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129623E+10 | 0.00 | 0.670958E+10 | 0.00 | 0.139004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143512E+10 | 0.00 | 0.146644E+11 | 0.00 | 0.286101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138882E+10 | 0.00 | 0.209712E+11 | 0.00 | 0.400366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143512E+10 | 0.00 | 0.502029E+10 | 0.00 | 0.109744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138882E+10 | 0.00 | 0.110380E+11 | 0.00 | 0.231162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143512E+10 | 0.00 | 0.178812E+11 | 0.00 | 0.377073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143512E+10 | 0.00 | 0.239326E+11 | 0.00 | 0.514106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138882E+10 | 0.00 | 0.491762E+10 | 0.00 | 0.108197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143512E+10 | 0.00 | 0.935339E+10 | 0.00 | 0.191331E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138882E+10 | 0.00 | 0.133691E+11 | 0.00 | 0.262369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143512E+10 | 0.00 | 0.186237E+11 | 0.00 | 0.352498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168973E+11 | 0.00 | 0.147752E+12 | 0.00 | 0.300124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.129623E+10 | 0.00 | 0.127107E+10 | 0.00 | 0.292869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143512E+10 | 0.00 | 0.239326E+11 | 0.00 | 0.514106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.472575E+09 | 0.00 | 0.00 | 0.137734E+09 | 0.00 | 0.00 | 0.706168E+11 | 0.00 | 0.60 |
February | 0.417031E+09 | 0.00 | 0.00 | 0.116607E+09 | 0.00 | 0.00 | 0.637804E+11 | 0.00 | 0.69 |
March | 0.303910E+09 | 0.00 | 0.00 | 0.145565E+09 | 0.00 | 0.00 | 0.795567E+11 | 0.00 | 0.88 |
April | 0.280063E+09 | 21312353.97 | 0.00 | 0.142882E+09 | 0.00 | 0.00 | 0.709784E+11 | 0.00 | 0.96 |
May | 0.266369E+09 | 13111763.98 | 0.00 | 0.142581E+09 | 0.00 | 0.00 | 0.702283E+11 | 0.00 | 1.18 |
June | 0.103984E+09 | 15222368.36 | 0.00 | 0.159072E+09 | 1396388.26 | 0.00 | 0.645764E+11 | 0.00 | 1.41 |
July | 0.150708E+09 | 0.155506E+09 | 0.00 | 0.152647E+09 | 3464245.23 | 0.00 | 0.503330E+11 | 0.00 | 1.35 |
August | 97731912.43 | 0.423924E+09 | 0.00 | 0.157443E+09 | 198625.13 | 0.00 | 0.466628E+11 | 0.00 | 1.32 |
September | 0.245768E+09 | 0.00 | 0.00 | 0.163914E+09 | 0.00 | 0.00 | 0.656473E+11 | 0.00 | 1.36 |
October | 0.330970E+09 | 0.00 | 0.00 | 0.166158E+09 | 0.00 | 0.00 | 0.783322E+11 | 0.00 | 1.06 |
November | 0.291604E+09 | 0.00 | 0.00 | 0.156015E+09 | 0.00 | 0.00 | 0.777303E+11 | 0.00 | 0.84 |
December | 0.608825E+09 | 0.00 | 0.00 | 0.149847E+09 | 0.00 | 0.00 | 0.751447E+11 | 0.00 | 0.66 |
Annual Sum or Average | 0.356954E+10 | 0.629076E+09 | 0.00 | 0.179046E+10 | 5059258.61 | 0.00 | 0.813587E+12 | 0.00 | 1.03 |
Minimum of Months | 97731912.43 | 0.00 | 0.00 | 0.116607E+09 | 0.00 | 0.00 | 0.466628E+11 | 0.00 | 0.60 |
Maximum of Months | 0.608825E+09 | 0.423924E+09 | 0.00 | 0.166158E+09 | 3464245.23 | 0.00 | 0.795567E+11 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.256394E+10 | 0.00 | 0.00 | 71620113.73 | 0.00 | 0.00 | 0.472725E+11 | 0.00 | 0.41 |
February | 0.196728E+10 | 0.00 | 0.00 | 79471442.21 | 0.00 | 0.00 | 0.473954E+11 | 0.00 | 0.51 |
March | 0.265814E+10 | 0.00 | 0.00 | 0.110144E+09 | 0.00 | 0.00 | 0.634142E+11 | 0.00 | 0.69 |
April | 0.555397E+10 | 10879951.36 | 0.00 | 0.111823E+09 | 499087.51 | 0.00 | 0.573908E+11 | 0.00 | 0.80 |
May | 0.375479E+10 | 16409292.04 | 0.00 | 98188948.91 | 0.00 | 0.00 | 0.501447E+11 | 0.00 | 0.80 |
June | 0.412926E+10 | 9746287.12 | 0.00 | 0.111331E+09 | 5153597.49 | 0.00 | 0.453028E+11 | 0.00 | 0.92 |
July | 0.779300E+10 | 0.532133E+09 | 0.00 | 96688809.12 | 45079890.22 | 0.00 | 0.311116E+11 | 0.00 | 0.90 |
August | 0.856432E+10 | 0.141865E+10 | 0.00 | 91686764.13 | 18646070.95 | 0.00 | 0.275859E+11 | 0.00 | 0.94 |
September | 0.386435E+10 | 77983738.01 | 0.00 | 97661060.74 | 99385.73 | 0.00 | 0.410537E+11 | 0.00 | 0.83 |
October | 0.337185E+10 | 0.00 | 0.00 | 0.104479E+09 | 0.00 | 0.00 | 0.559567E+11 | 0.00 | 0.75 |
November | 0.267732E+10 | 0.00 | 0.00 | 98477658.97 | 0.00 | 0.00 | 0.572273E+11 | 0.00 | 0.61 |
December | 0.244560E+10 | 0.00 | 0.00 | 0.101423E+09 | 0.00 | 0.00 | 0.572313E+11 | 0.00 | 0.50 |
Annual Sum or Average | 0.493438E+11 | 0.206580E+10 | 0.00 | 0.117299E+10 | 69478031.89 | 0.00 | 0.581087E+12 | 0.00 | 0.72 |
Minimum of Months | 0.196728E+10 | 0.00 | 0.00 | 71620113.73 | 0.00 | 0.00 | 0.275859E+11 | 0.00 | 0.41 |
Maximum of Months | 0.856432E+10 | 0.141865E+10 | 0.00 | 0.111823E+09 | 45079890.22 | 0.00 | 0.634142E+11 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183351E+12 | 0.00 | 0.00 | 0.196006E+09 | 0.00 | 0.159359E+10 | 0.166683E+12 | 0.00 | 0.30 |
February | 0.125809E+12 | 0.00 | 0.00 | 0.288714E+09 | 0.00 | 0.00 | 0.214954E+12 | 0.00 | 0.36 |
March | 0.866289E+11 | 0.00 | 0.00 | 0.532032E+09 | 0.00 | 0.00 | 0.344815E+12 | 0.00 | 0.46 |
April | 0.398424E+11 | 0.115594E+09 | 0.00 | 0.600995E+09 | 92322042.10 | 0.00 | 0.351301E+12 | 0.00 | 0.51 |
May | 0.352665E+11 | 44505634.28 | 0.00 | 0.644071E+09 | 0.219095E+09 | 0.00 | 0.383678E+12 | 0.00 | 0.65 |
June | 0.280854E+11 | 97604714.26 | 0.00 | 0.764489E+09 | 67953668.47 | 0.00 | 0.342056E+12 | 0.00 | 0.72 |
July | 0.281036E+11 | 0.436040E+10 | 0.00 | 0.638774E+09 | 0.120200E+10 | 0.00 | 0.230921E+12 | 0.00 | 0.65 |
August | 0.206030E+11 | 0.128757E+11 | 0.00 | 0.645568E+09 | 0.320049E+09 | 0.00 | 0.206159E+12 | 0.00 | 0.65 |
September | 0.364392E+11 | 0.439677E+09 | 0.00 | 0.670112E+09 | 0.533818E+09 | 0.00 | 0.312925E+12 | 0.00 | 0.68 |
October | 0.650646E+11 | 0.00 | 0.00 | 0.591998E+09 | 0.00 | 0.00 | 0.345573E+12 | 0.00 | 0.54 |
November | 0.102324E+12 | 0.00 | 0.00 | 0.403558E+09 | 0.00 | 0.00 | 0.265605E+12 | 0.00 | 0.39 |
December | 0.145838E+12 | 0.00 | 0.00 | 0.295781E+09 | 0.00 | 0.00 | 0.213327E+12 | 0.00 | 0.31 |
Annual Sum or Average | 0.897355E+12 | 0.179335E+11 | 0.00 | 0.627210E+10 | 0.243524E+10 | 0.159359E+10 | 0.337800E+13 | 0.00 | 0.52 |
Minimum of Months | 0.206030E+11 | 0.00 | 0.00 | 0.196006E+09 | 0.00 | 0.00 | 0.166683E+12 | 0.00 | 0.30 |
Maximum of Months | 0.183351E+12 | 0.128757E+11 | 0.00 | 0.764489E+09 | 0.120200E+10 | 0.159359E+10 | 0.383678E+12 | 0.00 | 0.72 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264696E+11 | 0.00 | 0.00 | 1550720.97 | 0.00 | 0.771859E+09 | 0.297407E+10 | 0.00 | 0.28 |
February | 0.216449E+11 | 0.00 | 0.00 | 5334102.42 | 0.00 | 0.380702E+09 | 0.602843E+10 | 0.00 | 0.32 |
March | 0.173172E+11 | 0.00 | 0.00 | 18088955.66 | 0.00 | 99351693.69 | 0.168284E+11 | 0.00 | 0.38 |
April | 0.106809E+11 | 0.00 | 0.00 | 30988914.33 | 3159434.55 | 0.00 | 0.227621E+11 | 0.00 | 0.45 |
May | 0.850687E+10 | 2084071.07 | 0.00 | 46765161.21 | 7392309.86 | 0.00 | 0.299631E+11 | 0.00 | 0.60 |
June | 0.610438E+10 | 1499609.75 | 0.00 | 64814778.51 | 5215981.98 | 0.00 | 0.296687E+11 | 0.00 | 0.70 |
July | 0.466510E+10 | 0.382679E+09 | 0.00 | 60187427.00 | 59551674.97 | 0.00 | 0.209774E+11 | 0.00 | 0.66 |
August | 0.456648E+10 | 0.104393E+10 | 0.00 | 54837195.49 | 42465999.59 | 0.00 | 0.165146E+11 | 0.00 | 0.65 |
September | 0.884866E+10 | 6025966.50 | 0.00 | 46297317.30 | 30673941.90 | 0.00 | 0.207307E+11 | 0.00 | 0.61 |
October | 0.134224E+11 | 0.00 | 0.00 | 23130284.03 | 0.00 | 1305249.79 | 0.181318E+11 | 0.00 | 0.44 |
November | 0.199932E+11 | 0.00 | 0.00 | 7639292.24 | 0.00 | 0.238102E+09 | 0.808680E+10 | 0.00 | 0.33 |
December | 0.249606E+11 | 0.00 | 0.00 | 2132222.28 | 0.00 | 0.531208E+09 | 0.352425E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.167180E+12 | 0.143622E+10 | 0.00 | 0.361766E+09 | 0.148459E+09 | 0.202253E+10 | 0.196191E+12 | 0.00 | 0.48 |
Minimum of Months | 0.456648E+10 | 0.00 | 0.00 | 1550720.97 | 0.00 | 0.00 | 0.297407E+10 | 0.00 | 0.28 |
Maximum of Months | 0.264696E+11 | 0.104393E+10 | 0.00 | 64814778.51 | 59551674.97 | 0.771859E+09 | 0.299631E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.335963E+10 | 0.00 | 0.00 | 749981.05 | 0.00 | 0.00 | 0.102168E+10 | 0.00 | 0.28 |
February | 0.241107E+10 | 0.00 | 0.00 | 2010531.15 | 0.00 | 0.00 | 0.186810E+10 | 0.00 | 0.36 |
March | 0.207567E+10 | 0.00 | 0.00 | 4963293.84 | 0.00 | 0.00 | 0.399708E+10 | 0.00 | 0.51 |
April | 0.148337E+10 | 1685055.31 | 0.00 | 7000888.45 | 0.00 | 0.00 | 0.503022E+10 | 0.00 | 0.68 |
May | 0.114503E+10 | 2593802.32 | 0.00 | 8142752.96 | 0.00 | 0.00 | 0.515195E+10 | 0.00 | 0.78 |
June | 0.701332E+09 | 1586558.62 | 0.00 | 10918983.59 | 646840.67 | 0.00 | 0.533713E+10 | 0.00 | 0.94 |
July | 0.109053E+10 | 86715578.73 | 0.00 | 10570855.61 | 5658087.68 | 0.00 | 0.381548E+10 | 0.00 | 0.96 |
August | 0.115629E+10 | 0.228621E+09 | 0.00 | 9726085.20 | 2340314.13 | 0.00 | 0.323723E+10 | 0.00 | 0.97 |
September | 0.125720E+10 | 10352737.36 | 0.00 | 6918539.00 | 12474.15 | 0.00 | 0.370738E+10 | 0.00 | 0.76 |
October | 0.194753E+10 | 0.00 | 0.00 | 5032479.03 | 0.00 | 0.00 | 0.374538E+10 | 0.00 | 0.58 |
November | 0.207880E+10 | 0.00 | 0.00 | 3465221.44 | 0.00 | 0.00 | 0.293380E+10 | 0.00 | 0.42 |
December | 0.256796E+10 | 0.00 | 0.00 | 2348824.26 | 0.00 | 0.00 | 0.206552E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.212744E+11 | 0.331555E+09 | 0.00 | 71848435.58 | 8657716.63 | 0.00 | 0.419109E+11 | 0.00 | 0.63 |
Minimum of Months | 0.701332E+09 | 0.00 | 0.00 | 749981.05 | 0.00 | 0.00 | 0.102168E+10 | 0.00 | 0.28 |
Maximum of Months | 0.335963E+10 | 0.228621E+09 | 0.00 | 10918983.59 | 5658087.68 | 0.00 | 0.533713E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.611413E+10 | 0.00 | 0.00 | 1482.97 | 0.00 | 0.00 | 7212312.11 | 0.00 | 0.61 |
February | 0.520137E+10 | 0.00 | 0.00 | 385826.26 | 0.00 | 0.00 | 0.473178E+09 | 0.00 | 0.72 |
March | 0.468922E+10 | 0.00 | 0.00 | 1926749.04 | 0.00 | 0.00 | 0.235992E+10 | 0.00 | 0.90 |
April | 0.359721E+10 | 1055914.84 | 0.00 | 4374894.51 | 245648.81 | 0.00 | 0.360286E+10 | 0.00 | 1.15 |
May | 0.294201E+10 | 2310580.50 | 0.00 | 5384535.64 | 558259.78 | 0.00 | 0.388059E+10 | 0.00 | 1.28 |
June | 0.225656E+10 | 1422092.56 | 0.00 | 7463216.92 | 985776.99 | 0.00 | 0.435949E+10 | 0.00 | 1.54 |
July | 0.271391E+10 | 62780716.33 | 0.00 | 6739878.85 | 19557189.78 | 0.00 | 0.268588E+10 | 0.00 | 1.56 |
August | 0.279231E+10 | 0.169361E+09 | 0.00 | 6062114.76 | 13802210.01 | 0.00 | 0.224013E+10 | 0.00 | 1.65 |
September | 0.308990E+10 | 4372074.94 | 0.00 | 4646489.98 | 6865448.28 | 0.00 | 0.280274E+10 | 0.00 | 1.36 |
October | 0.451737E+10 | 0.00 | 0.00 | 2388828.64 | 0.00 | 0.00 | 0.220257E+10 | 0.00 | 1.05 |
November | 0.578976E+10 | 0.00 | 0.00 | 145805.48 | 0.00 | 0.00 | 0.396590E+09 | 0.00 | 0.79 |
December | 0.610788E+10 | 0.00 | 0.00 | 33536.32 | 0.00 | 0.00 | 84199783.51 | 0.00 | 0.64 |
Annual Sum or Average | 0.498116E+11 | 0.241302E+09 | 0.00 | 39553359.36 | 42014533.64 | 0.00 | 0.250954E+11 | 0.00 | 1.11 |
Minimum of Months | 0.225656E+10 | 0.00 | 0.00 | 1482.97 | 0.00 | 0.00 | 7212312.11 | 0.00 | 0.61 |
Maximum of Months | 0.611413E+10 | 0.169361E+09 | 0.00 | 7463216.92 | 19557189.78 | 0.00 | 0.435949E+10 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.653994E+10 | 0.00 | 0.00 | 1845943.98 | 0.00 | 21495029.43 | 0.154153E+10 | 0.00 | 0.52 |
February | 0.518559E+10 | 0.00 | 0.00 | 4324819.67 | 0.00 | 0.00 | 0.330654E+10 | 0.00 | 0.70 |
March | 0.472420E+10 | 0.00 | 0.00 | 7969250.90 | 0.00 | 0.00 | 0.637477E+10 | 0.00 | 0.94 |
April | 0.397886E+10 | 3328181.30 | 0.00 | 8346464.30 | 0.00 | 0.00 | 0.611038E+10 | 0.00 | 1.08 |
May | 0.348190E+10 | 3826514.92 | 0.00 | 7741371.98 | 0.00 | 0.00 | 0.524290E+10 | 0.00 | 1.08 |
June | 0.296415E+10 | 1896857.57 | 0.00 | 8687816.47 | 1135698.80 | 0.00 | 0.473675E+10 | 0.00 | 1.20 |
July | 0.318352E+10 | 0.112789E+09 | 0.00 | 8849477.25 | 11402419.93 | 0.00 | 0.343535E+10 | 0.00 | 1.28 |
August | 0.319690E+10 | 0.345158E+09 | 0.00 | 8671347.05 | 3976640.69 | 0.00 | 0.301548E+10 | 0.00 | 1.38 |
September | 0.323714E+10 | 27560845.97 | 0.00 | 10812739.06 | 21901.64 | 0.00 | 0.493301E+10 | 0.00 | 1.35 |
October | 0.429694E+10 | 0.00 | 0.00 | 8974425.90 | 0.00 | 0.00 | 0.628071E+10 | 0.00 | 1.12 |
November | 0.544148E+10 | 0.00 | 0.00 | 3694029.54 | 0.00 | 0.00 | 0.308264E+10 | 0.00 | 0.71 |
December | 0.606746E+10 | 0.00 | 0.00 | 3479819.46 | 0.00 | 503103.36 | 0.280951E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.522981E+11 | 0.494560E+09 | 0.00 | 83397505.56 | 16536661.06 | 21998132.79 | 0.508696E+11 | 0.00 | 1.00 |
Minimum of Months | 0.296415E+10 | 0.00 | 0.00 | 1845943.98 | 0.00 | 0.00 | 0.154153E+10 | 0.00 | 0.52 |
Maximum of Months | 0.653994E+10 | 0.345158E+09 | 0.00 | 10812739.06 | 11402419.93 | 21495029.43 | 0.637477E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.692515E+10 | 0.00 | 0.00 | 196042.15 | 0.00 | 0.00 | 0.411492E+09 | 0.00 | 0.73 |
February | 0.386319E+10 | 0.00 | 0.00 | 2455601.34 | 0.00 | 0.00 | 0.312667E+10 | 0.00 | 0.89 |
March | 0.157860E+10 | 0.00 | 0.00 | 8660663.65 | 0.00 | 0.00 | 0.770988E+10 | 0.00 | 1.22 |
April | 0.127755E+10 | 2658672.74 | 0.00 | 14266536.01 | 0.00 | 0.00 | 0.879398E+10 | 0.00 | 1.66 |
May | 0.210767E+10 | 3440818.47 | 0.00 | 10145539.64 | 0.00 | 0.00 | 0.604923E+10 | 0.00 | 1.59 |
June | 0.106079E+10 | 4407440.32 | 0.00 | 13688173.29 | 974476.79 | 0.00 | 0.659953E+10 | 0.00 | 1.90 |
July | 0.158561E+10 | 0.163523E+09 | 0.00 | 16598886.14 | 1150001.37 | 0.00 | 0.528394E+10 | 0.00 | 2.16 |
August | 0.163843E+10 | 0.354399E+09 | 0.00 | 17574581.86 | 3581707.62 | 0.00 | 0.477802E+10 | 0.00 | 2.20 |
September | 0.241219E+10 | 16437946.79 | 0.00 | 7669576.59 | 20944.91 | 0.00 | 0.443754E+10 | 0.00 | 1.66 |
October | 0.263603E+10 | 0.00 | 0.00 | 6185300.75 | 0.00 | 0.00 | 0.557759E+10 | 0.00 | 1.31 |
November | 0.228597E+10 | 0.00 | 0.00 | 5167282.07 | 0.00 | 0.00 | 0.534760E+10 | 0.00 | 0.98 |
December | 0.194594E+10 | 0.00 | 0.00 | 5757122.03 | 0.00 | 0.00 | 0.584642E+10 | 0.00 | 0.82 |
Annual Sum or Average | 0.293171E+11 | 0.544866E+09 | 0.00 | 0.108365E+09 | 5727130.68 | 0.00 | 0.639619E+11 | 0.00 | 1.43 |
Minimum of Months | 0.106079E+10 | 0.00 | 0.00 | 196042.15 | 0.00 | 0.00 | 0.411492E+09 | 0.00 | 0.73 |
Maximum of Months | 0.692515E+10 | 0.354399E+09 | 0.00 | 17574581.86 | 3581707.62 | 0.00 | 0.879398E+10 | 0.00 | 2.20 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.305704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107930E+11 | 0.00 | 0.00 | 0.28 |
February | 0.324668E+11 | 0.00 | 0.00 | 642971.84 | 0.00 | 0.410135E+10 | 0.797223E+09 | 0.00 | 0.31 |
March | 0.359984E+11 | 0.00 | 0.00 | 3547771.50 | 0.00 | 0.392170E+09 | 0.570474E+10 | 0.00 | 0.36 |
April | 0.238672E+11 | 16905977.07 | 0.00 | 18619174.00 | 11597236.97 | 3054243.39 | 0.148813E+11 | 0.00 | 0.41 |
May | 0.182570E+11 | 33281949.37 | 0.00 | 44366573.83 | 0.00 | 0.00 | 0.277681E+11 | 0.00 | 0.59 |
June | 0.124387E+11 | 14393364.55 | 0.00 | 61060952.52 | 8536149.96 | 0.00 | 0.301235E+11 | 0.00 | 0.69 |
July | 0.980895E+10 | 0.772718E+09 | 0.00 | 59985157.89 | 85364514.65 | 0.00 | 0.214237E+11 | 0.00 | 0.66 |
August | 0.100335E+11 | 0.208379E+10 | 0.00 | 49923533.23 | 20244121.95 | 0.00 | 0.162152E+11 | 0.00 | 0.65 |
September | 0.184892E+11 | 59187680.83 | 0.00 | 36825521.74 | 67056788.17 | 0.00 | 0.184687E+11 | 0.00 | 0.60 |
October | 0.308395E+11 | 0.00 | 0.00 | 10173879.69 | 0.00 | 24399769.28 | 0.927495E+10 | 0.00 | 0.42 |
November | 0.362104E+11 | 0.00 | 0.00 | 126385.81 | 0.00 | 0.102213E+10 | 0.625694E+09 | 0.00 | 0.32 |
December | 0.350065E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469540E+10 | 0.00 | 0.00 | 0.27 |
Annual Sum or Average | 0.293987E+12 | 0.298028E+10 | 0.00 | 0.285272E+09 | 0.192799E+09 | 0.210315E+11 | 0.145283E+12 | 0.00 | 0.46 |
Minimum of Months | 0.980895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.362104E+11 | 0.208379E+10 | 0.00 | 61060952.52 | 85364514.65 | 0.107930E+11 | 0.301235E+11 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.435675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170513E+11 | 0.00 | 0.00 | 0.63 |
February | 0.480881E+11 | 0.00 | 0.00 | 3971.03 | 0.00 | 0.666092E+10 | 53479675.83 | 0.00 | 0.71 |
March | 0.561940E+11 | 0.00 | 0.00 | 5745326.23 | 0.00 | 0.723823E+09 | 0.527148E+10 | 0.00 | 0.82 |
April | 0.365509E+11 | 14711719.98 | 0.00 | 24498161.85 | 17015689.72 | 0.104726E+09 | 0.210533E+11 | 0.00 | 0.94 |
May | 0.372314E+11 | 25373041.92 | 0.00 | 33419998.87 | 23103989.77 | 4649659.95 | 0.245214E+11 | 0.00 | 1.21 |
June | 0.264374E+11 | 10794860.64 | 0.00 | 56918006.37 | 19492053.97 | 0.00 | 0.319030E+11 | 0.00 | 1.41 |
July | 0.205815E+11 | 0.613447E+09 | 0.00 | 56564941.89 | 0.352390E+09 | 0.00 | 0.209818E+11 | 0.00 | 1.32 |
August | 0.194074E+11 | 0.187796E+10 | 0.00 | 49883888.10 | 0.195663E+09 | 0.00 | 0.171917E+11 | 0.00 | 1.35 |
September | 0.361856E+11 | 48278936.12 | 0.00 | 31913932.40 | 0.107074E+09 | 0.00 | 0.168032E+11 | 0.00 | 1.28 |
October | 0.505539E+11 | 0.00 | 0.00 | 8790158.43 | 0.00 | 51162165.65 | 0.833570E+10 | 0.00 | 0.95 |
November | 0.527824E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276516E+10 | 0.00 | 0.00 | 0.73 |
December | 0.486096E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.964380E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.476190E+12 | 0.259057E+10 | 0.00 | 0.267738E+09 | 0.714739E+09 | 0.370056E+11 | 0.146115E+12 | 0.00 | 1.00 |
Minimum of Months | 0.194074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.561940E+11 | 0.187796E+10 | 0.00 | 56918006.37 | 0.352390E+09 | 0.170513E+11 | 0.319030E+11 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.568957E+11 | 0.00 | 0.00 | 11209857.63 | 0.00 | 0.109466E+11 | 0.939609E+10 | 0.00 | 0.52 |
February | 0.509189E+11 | 0.00 | 0.00 | 36372554.51 | 0.00 | 0.347932E+10 | 0.248126E+11 | 0.00 | 0.67 |
March | 0.514235E+11 | 0.00 | 0.00 | 60905416.22 | 0.00 | 0.311624E+09 | 0.439437E+11 | 0.00 | 0.83 |
April | 0.405880E+11 | 68878807.47 | 0.00 | 54896111.27 | 0.00 | 8437485.87 | 0.375877E+11 | 0.00 | 0.85 |
May | 0.418283E+11 | 59839136.09 | 0.00 | 53597443.74 | 0.00 | 0.00 | 0.349195E+11 | 0.00 | 0.98 |
June | 0.356302E+11 | 19832620.11 | 0.00 | 52824342.68 | 17521455.10 | 0.00 | 0.294405E+11 | 0.00 | 1.04 |
July | 0.266066E+11 | 0.115546E+10 | 0.00 | 57920043.31 | 0.233458E+09 | 0.00 | 0.220108E+11 | 0.00 | 1.02 |
August | 0.239315E+11 | 0.372596E+10 | 0.00 | 57541412.20 | 79401281.44 | 0.00 | 0.188831E+11 | 0.00 | 1.07 |
September | 0.363461E+11 | 0.394562E+09 | 0.00 | 96880706.76 | 4499303.51 | 0.00 | 0.372171E+11 | 0.00 | 1.28 |
October | 0.444323E+11 | 0.00 | 0.00 | 77181326.45 | 0.00 | 6800212.12 | 0.482707E+11 | 0.00 | 1.02 |
November | 0.580373E+11 | 0.00 | 0.00 | 21299309.71 | 0.00 | 0.118358E+10 | 0.139685E+11 | 0.00 | 0.63 |
December | 0.559393E+11 | 0.00 | 0.00 | 21792486.31 | 0.00 | 0.624758E+10 | 0.162076E+11 | 0.00 | 0.54 |
Annual Sum or Average | 0.522578E+12 | 0.542453E+10 | 0.00 | 0.602421E+09 | 0.334880E+09 | 0.221840E+11 | 0.336658E+12 | 0.00 | 0.87 |
Minimum of Months | 0.239315E+11 | 0.00 | 0.00 | 11209857.63 | 0.00 | 0.00 | 0.939609E+10 | 0.00 | 0.52 |
Maximum of Months | 0.580373E+11 | 0.372596E+10 | 0.00 | 96880706.76 | 0.233458E+09 | 0.109466E+11 | 0.482707E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.538267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.888697E+10 | 0.00 | 0.00 | 0.65 |
February | 0.519505E+11 | 0.00 | 0.00 | 2143410.98 | 0.00 | 0.290029E+10 | 0.194615E+10 | 0.00 | 0.74 |
March | 0.568898E+11 | 0.00 | 0.00 | 7768445.50 | 0.00 | 0.141207E+09 | 0.804493E+10 | 0.00 | 0.86 |
April | 0.430187E+11 | 27708096.76 | 0.00 | 22001410.26 | 9616966.19 | 0.00 | 0.160555E+11 | 0.00 | 0.98 |
May | 0.383277E+11 | 12258993.34 | 0.00 | 50534366.80 | 37924861.67 | 0.00 | 0.253664E+11 | 0.00 | 1.29 |
June | 0.304075E+11 | 43890274.09 | 0.00 | 47646068.28 | 12962777.68 | 0.00 | 0.249038E+11 | 0.00 | 1.42 |
July | 0.194281E+11 | 0.146904E+10 | 0.00 | 58146859.22 | 44016932.35 | 0.00 | 0.224304E+11 | 0.00 | 1.43 |
August | 0.207788E+11 | 0.291707E+10 | 0.00 | 44131955.08 | 72439968.19 | 0.00 | 0.146168E+11 | 0.00 | 1.35 |
September | 0.397878E+11 | 0.128075E+09 | 0.00 | 31379698.00 | 55150402.20 | 0.00 | 0.137208E+11 | 0.00 | 1.35 |
October | 0.539884E+11 | 0.00 | 0.00 | 9435206.07 | 0.00 | 5706640.50 | 0.718838E+10 | 0.00 | 1.00 |
November | 0.561799E+11 | 0.00 | 0.00 | 293949.87 | 0.00 | 0.650511E+09 | 0.648617E+09 | 0.00 | 0.75 |
December | 0.569066E+11 | 0.00 | 0.00 | 50330.14 | 0.00 | 0.317692E+10 | 0.178308E+09 | 0.00 | 0.64 |
Annual Sum or Average | 0.521490E+12 | 0.459805E+10 | 0.00 | 0.273532E+09 | 0.232112E+09 | 0.157616E+11 | 0.135100E+12 | 0.00 | 1.04 |
Minimum of Months | 0.194281E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
Maximum of Months | 0.569066E+11 | 0.291707E+10 | 0.00 | 58146859.22 | 72439968.19 | 0.888697E+10 | 0.253664E+11 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205840E+10 | 0.00 | 0.00 | 0.28 |
February | 0.215004E+10 | 0.00 | 0.00 | 5917.29 | 0.00 | 0.131757E+10 | 36404939.93 | 0.00 | 0.32 |
March | 0.343164E+10 | 0.00 | 0.00 | 55035.90 | 0.00 | 0.497316E+09 | 0.102082E+09 | 0.00 | 0.36 |
April | 0.253319E+10 | 0.00 | 0.00 | 1412096.66 | 396612.30 | 0.176914E+09 | 0.995881E+09 | 0.00 | 0.40 |
May | 0.197787E+10 | 1198034.90 | 0.00 | 3828940.84 | 0.00 | 19179079.31 | 0.244618E+10 | 0.00 | 0.57 |
June | 0.133623E+10 | 233263.06 | 0.00 | 5878856.32 | 654776.23 | 0.00 | 0.289139E+10 | 0.00 | 0.69 |
July | 0.938328E+09 | 64741035.13 | 0.00 | 6151775.16 | 4926329.94 | 0.00 | 0.224018E+10 | 0.00 | 0.68 |
August | 0.102925E+10 | 0.167581E+09 | 0.00 | 4918679.99 | 4021631.09 | 0.00 | 0.149148E+10 | 0.00 | 0.65 |
September | 0.202360E+10 | 810251.49 | 0.00 | 2955604.50 | 3850582.30 | 0.00 | 0.136311E+10 | 0.00 | 0.57 |
October | 0.305393E+10 | 0.00 | 0.00 | 378428.83 | 0.00 | 0.210184E+09 | 0.376458E+09 | 0.00 | 0.40 |
November | 0.260397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.900000E+09 | 0.00 | 0.00 | 0.32 |
December | 0.178696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189002E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.246446E+11 | 0.234563E+09 | 0.00 | 25585335.48 | 13849931.87 | 0.706958E+10 | 0.119432E+11 | 0.00 | 0.46 |
Minimum of Months | 0.938328E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.343164E+10 | 0.167581E+09 | 0.00 | 6151775.16 | 4926329.94 | 0.205840E+10 | 0.289139E+10 | 0.00 | 0.69 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.262710E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282941E+10 | 0.00 | 0.00 | 0.62 |
February | 0.331803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168119E+10 | 0.00 | 0.00 | 0.70 |
March | 0.499882E+10 | 0.00 | 0.00 | 192673.34 | 0.00 | 0.572521E+09 | 0.217194E+09 | 0.00 | 0.80 |
April | 0.330641E+10 | 0.00 | 0.00 | 2198941.50 | 569903.90 | 0.197163E+09 | 0.186695E+10 | 0.00 | 0.90 |
May | 0.337282E+10 | 1075348.25 | 0.00 | 3344297.24 | 634016.62 | 32159929.68 | 0.249322E+10 | 0.00 | 1.16 |
June | 0.234308E+10 | 215412.46 | 0.00 | 5986798.20 | 957562.66 | 508509.77 | 0.334187E+10 | 0.00 | 1.39 |
July | 0.177983E+10 | 55507369.48 | 0.00 | 6111009.30 | 15092279.31 | 0.00 | 0.229606E+10 | 0.00 | 1.32 |
August | 0.177498E+10 | 0.146969E+09 | 0.00 | 5155572.20 | 16875437.60 | 0.00 | 0.169439E+10 | 0.00 | 1.35 |
September | 0.320596E+10 | 725360.51 | 0.00 | 3124192.67 | 5533015.09 | 2145662.24 | 0.161488E+10 | 0.00 | 1.22 |
October | 0.439323E+10 | 0.00 | 0.00 | 542256.20 | 0.00 | 0.320438E+09 | 0.534134E+09 | 0.00 | 0.89 |
November | 0.369963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131973E+10 | 0.00 | 0.00 | 0.71 |
December | 0.275954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247936E+10 | 0.00 | 0.00 | 0.61 |
Annual Sum or Average | 0.375795E+11 | 0.204493E+09 | 0.00 | 26655740.65 | 39662215.19 | 0.943463E+10 | 0.140587E+11 | 0.00 | 0.97 |
Minimum of Months | 0.177498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.61 |
Maximum of Months | 0.499882E+10 | 0.146969E+09 | 0.00 | 6111009.30 | 16875437.60 | 0.282941E+10 | 0.334187E+10 | 0.00 | 1.39 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.415098E+10 | 0.00 | 0.00 | 486615.46 | 0.00 | 0.267259E+10 | 0.506897E+09 | 0.00 | 0.53 |
February | 0.395062E+10 | 0.00 | 0.00 | 2453056.13 | 0.00 | 0.152505E+10 | 0.187569E+10 | 0.00 | 0.66 |
March | 0.472382E+10 | 0.00 | 0.00 | 4665428.45 | 0.00 | 0.736269E+09 | 0.363509E+10 | 0.00 | 0.81 |
April | 0.405613E+10 | 776505.62 | 0.00 | 5037356.17 | 0.00 | 0.288995E+09 | 0.340811E+10 | 0.00 | 0.85 |
May | 0.443234E+10 | 2263124.11 | 0.00 | 4746130.06 | 0.00 | 37884707.05 | 0.335734E+10 | 0.00 | 1.00 |
June | 0.391311E+10 | 307300.66 | 0.00 | 4960563.10 | 1245666.95 | 207391.15 | 0.287118E+10 | 0.00 | 1.09 |
July | 0.277677E+10 | 90332484.71 | 0.00 | 5999381.05 | 14630232.30 | 0.00 | 0.232172E+10 | 0.00 | 1.07 |
August | 0.257823E+10 | 0.281562E+09 | 0.00 | 5846512.96 | 12998511.69 | 0.00 | 0.179660E+10 | 0.00 | 1.13 |
September | 0.382605E+10 | 15983208.27 | 0.00 | 9103027.38 | 0.00 | 1078300.80 | 0.341572E+10 | 0.00 | 1.27 |
October | 0.424063E+10 | 0.00 | 0.00 | 5872544.82 | 0.00 | 0.320266E+09 | 0.400327E+10 | 0.00 | 0.97 |
November | 0.489466E+10 | 0.00 | 0.00 | 1199204.93 | 0.00 | 0.121274E+10 | 0.773548E+09 | 0.00 | 0.64 |
December | 0.385463E+10 | 0.00 | 0.00 | 1216023.36 | 0.00 | 0.239171E+10 | 0.953920E+09 | 0.00 | 0.54 |
Annual Sum or Average | 0.473980E+11 | 0.391224E+09 | 0.00 | 51585843.87 | 28874410.95 | 0.918679E+10 | 0.289191E+11 | 0.00 | 0.88 |
Minimum of Months | 0.257823E+10 | 0.00 | 0.00 | 486615.46 | 0.00 | 0.00 | 0.506897E+09 | 0.00 | 0.53 |
Maximum of Months | 0.489466E+10 | 0.281562E+09 | 0.00 | 9103027.38 | 14630232.30 | 0.267259E+10 | 0.400327E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.365607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234129E+10 | 0.00 | 0.00 | 0.68 |
February | 0.412463E+10 | 0.00 | 0.00 | 115002.08 | 0.00 | 0.124328E+10 | 0.127992E+09 | 0.00 | 0.77 |
March | 0.532211E+10 | 0.00 | 0.00 | 581738.03 | 0.00 | 0.517430E+09 | 0.611429E+09 | 0.00 | 0.89 |
April | 0.430100E+10 | 345343.96 | 0.00 | 2137004.44 | 282028.45 | 0.178597E+09 | 0.146451E+10 | 0.00 | 1.01 |
May | 0.412572E+10 | 494972.62 | 0.00 | 4504785.12 | 1385144.70 | 23581735.44 | 0.237878E+10 | 0.00 | 1.31 |
June | 0.338533E+10 | 616927.61 | 0.00 | 4755248.14 | 1034852.66 | 0.00 | 0.234595E+10 | 0.00 | 1.47 |
July | 0.212354E+10 | 0.119311E+09 | 0.00 | 6269028.03 | 2567175.92 | 0.00 | 0.224731E+10 | 0.00 | 1.49 |
August | 0.225946E+10 | 0.223494E+09 | 0.00 | 4365938.96 | 11313741.09 | 0.00 | 0.132049E+10 | 0.00 | 1.41 |
September | 0.399171E+10 | 3601661.45 | 0.00 | 3090140.27 | 3565536.68 | 527017.27 | 0.123963E+10 | 0.00 | 1.36 |
October | 0.509033E+10 | 0.00 | 0.00 | 738719.45 | 0.00 | 0.161056E+09 | 0.560129E+09 | 0.00 | 0.99 |
November | 0.471175E+10 | 0.00 | 0.00 | 1743.13 | 0.00 | 0.801785E+09 | 4365032.27 | 0.00 | 0.78 |
December | 0.399613E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176229E+10 | 0.00 | 0.00 | 0.67 |
Annual Sum or Average | 0.470878E+11 | 0.347864E+09 | 0.00 | 26559347.65 | 20148479.49 | 0.702984E+10 | 0.123006E+11 | 0.00 | 1.07 |
Minimum of Months | 0.212354E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 |
Maximum of Months | 0.532211E+10 | 0.223494E+09 | 0.00 | 6269028.03 | 11313741.09 | 0.234129E+10 | 0.237878E+10 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:57:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 25916450.11 | 0.00 | 0.00 | 0.218652E+09 | 0.00 | 0.00 | 0.139950E+11 | 0.00 | 0.32 |
February | 9275446.40 | 0.00 | 0.00 | 0.400350E+09 | 0.00 | 0.00 | 0.116137E+11 | 0.00 | 0.32 |
March | 440883.06 | 0.00 | 0.00 | 0.684870E+09 | 0.00 | 0.00 | 0.119092E+11 | 0.00 | 0.34 |
April | 0.00 | 3604763.48 | 0.00 | 0.814543E+09 | 0.00 | 0.00 | 0.856506E+10 | 0.00 | 0.32 |
May | 0.00 | 5507792.72 | 0.00 | 0.207538E+09 | 0.00 | 0.00 | 0.722679E+10 | 0.00 | 0.33 |
June | 0.00 | 2433475.42 | 0.00 | 0.420936E+09 | 0.00 | 0.00 | 0.512373E+10 | 0.00 | 0.34 |
July | 0.00 | 0.129166E+09 | 0.00 | 0.512117E+09 | 0.00 | 0.00 | 0.282205E+10 | 0.00 | 0.31 |
August | 0.00 | 0.288891E+09 | 0.00 | 0.669412E+09 | 0.00 | 0.00 | 0.215494E+10 | 0.00 | 0.34 |
September | 0.00 | 9474650.94 | 0.00 | 0.197653E+09 | 0.00 | 0.00 | 0.470450E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.415195E+09 | 0.00 | 0.00 | 0.817361E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.598885E+09 | 0.00 | 0.00 | 0.102024E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.833419E+09 | 0.00 | 0.00 | 0.126848E+11 | 0.00 | 0.31 |
Annual Sum or Average | 35632779.56 | 0.439077E+09 | 0.00 | 0.597357E+10 | 0.00 | 0.00 | 0.991758E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.197653E+09 | 0.00 | 0.00 | 0.215494E+10 | 0.00 | 0.31 |
Maximum of Months | 25916450.11 | 0.288891E+09 | 0.00 | 0.833419E+09 | 0.00 | 0.00 | 0.139950E+11 | 0.00 | 0.34 |