Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:05
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 20:05:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 30040.32 | 648.53 | 648.53 |
Net Site Energy | 30040.32 | 648.53 | 648.53 |
Total Source Energy | 92110.10 | 1988.54 | 1988.54 |
Net Source Energy | 92110.10 | 1988.54 | 1988.54 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 896.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3569.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3311.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 656.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1987.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2125.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 497.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1142.31 | 0.00 | 0.00 | 0.00 | 0.00 | 5465.21 |
Humidification | 25.52 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
Heat Recovery | 56.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 557.22 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 28586.84 | 1453.48 | 0.00 | 0.00 | 0.00 | 7754.88 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 896.27 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 1086.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2483.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 3311.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 656.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 87.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2125.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 497.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 199.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 942.69 | 0.00 | 0.00 | 0.00 | 0.00 | 5465.21 | |
Humidification | General | 25.52 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 |
Heat Recovery | General | 56.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 557.22 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 158.92 | 31.38 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 617.15 | 31.38 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 85.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 158.92 | 31.38 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 372.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 617.15 | 31.38 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 28586.840 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 28586.840 | 100.00 |
Total On-Site and Utility Electric Sources | 28586.840 | 100.00 |
Total Electricity End Uses | 28586.840 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 844.87 | 28.16 |
Air to Air Heat Recovery for Heating | 2154.94 | 71.84 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 2999.82 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7754.88 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7754.88 | 100.00 |
Total Water End Uses | 7754.88 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 39.00 |
Time Setpoint Not Met During Occupied Cooling | 232.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2503.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 20:05 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.9438 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.9438 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.9438 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.9438 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.9438 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.9438 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.9438 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:09 | 02-JAN-07:10 | - | - | - | 01-SEP-13:00 |
Heating | 0.00 | 2419237.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 460549.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 283563.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 91242.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 138750.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 52685.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 90029.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1916437.77 | 2424933.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 2419237.94 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 292974.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 283563.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 5423.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 138750.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 52685.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 40781.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 971.55 | 0.00 | 0.00 | 0.00 |
Cooling | 11305.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 10486.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 2080.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6295.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6732.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1576.24 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3617.68 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 80.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 178.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 604.02 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 90534.52 | 1575.58 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 20.97 | 0.00 | 0.00 | 0.00 |
Cooling | 244.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 226.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1954.53 | 34.01 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 20.97 | 0.00 | 0.00 | 0.00 |
Cooling | 244.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 226.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 44.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 145.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 78.10 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1954.53 | 34.01 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.34 |
DATACENTER BOT DIRECT AIR | 0.463785 |
DATACENTER MID DIRECT AIR | 4.42 |
DATACENTER TOP DIRECT AIR | 0.450499 |
DATACENTER BASEMENT DIRECT AIR | 21.20 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.61 | 0.339080 | 0.339000 | 1.90 | 0.904213 | 0.500000 | 0.001124 | 0.000423 | 1.90 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.70 | 0.360930 | 0.353000 | 18.60 | 0.962481 | 0.500000 | 0.001056 | 0.009408 | 18.60 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.38 | 0.353486 | 0.348000 | 1.87 | 0.942629 | 0.500000 | 0.001078 | 0.001792 | 2.41 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.860167 | 0.277644 | 0.300000 | 0.258050 | 0.740385 | 0.500000 | 0.001372 | 0.000208 | 0.280228 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.02 | 0.151540 | 0.300000 | 0.304683 | 0.404105 | 0.500000 | 0.002514 | 0.000171 | 0.304683 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.984442 | 0.242600 | 0.300000 | 0.295333 | 0.646933 | 0.500000 | 0.001570 | 0.000264 | 0.356509 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.25 | 0.122683 | 0.300000 | 0.376347 | 0.327155 | 0.500000 | 0.003106 | 0.000154 | 0.376347 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.03 | 0.297262 | 0.300000 | 2.41 | 0.792697 | 0.500000 | 0.001282 | 0.004216 | 5.69 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.61 | 0.145030 | 0.300000 | 3.18 | 0.386748 | 0.500000 | 0.002627 | 0.002784 | 3.76 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 9.24 | 0.258344 | 0.300000 | 2.77 | 0.688918 | 0.500000 | 0.001475 | 0.004200 | 5.67 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.88 | 0.141469 | 0.300000 | 3.26 | 0.377250 | 0.500000 | 0.002693 | 0.002653 | 3.58 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.892653 | 0.267540 | 0.300000 | 0.267796 | 0.713440 | 0.500000 | 0.001424 | 0.000539 | 0.727701 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.08 | 0.142699 | 0.300000 | 0.323558 | 0.380531 | 0.500000 | 0.002670 | 0.000353 | 0.477450 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.03 | 0.231258 | 0.300000 | 0.309817 | 0.616689 | 0.500000 | 0.001648 | 0.000536 | 0.724341 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.16 | 0.132366 | 0.300000 | 0.348818 | 0.352975 | 0.500000 | 0.002878 | 0.000343 | 0.463470 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 19137.70 | 0.000423 | 333.10 |
CORE_MID VAV BOX REHEAT COIL | 425802.64 | 0.009408 | 8155.41 |
CORE_TOP VAV BOX REHEAT COIL | 81121.15 | 0.001792 | 1693.61 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9413.72 | 0.000208 | 196.52 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7755.85 | 0.000171 | 151.37 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11965.81 | 0.000264 | 249.73 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6969.50 | 0.000154 | 129.62 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 190836.95 | 0.004216 | 3981.37 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 125997.64 | 0.002784 | 2628.60 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 190103.24 | 0.004200 | 3966.07 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 120080.88 | 0.002653 | 2505.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24382.33 | 0.000539 | 508.60 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15996.85 | 0.000353 | 333.68 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24269.97 | 0.000536 | 506.26 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15529.12 | 0.000343 | 323.93 |
CAV_BAS_HEATC | 273636.50 | 0.006046 | 4996.23 |
VAV_BOT WITH REHEAT_HEATC | 72792.47 | 0.001608 | 1005.34 |
VAV_MID WITH REHEAT_HEATC | 720889.45 | 0.015927 | 9855.15 |
VAV_TOP WITH REHEAT_HEATC | 71699.47 | 0.001584 | 985.89 |
DATACENTER_EXTRAWATERHEATC | 1029925.90 | 0.022755 | 19145.09 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.34 | 5.34 | 5.34 | 5.34 | 5.34 | 5.34 | 1.00 | 1.00 | 5.34 |
VAV_BOT WITH REHEAT | 4.86 | 3.14 | 9.72 | 3.14 | 9.09 | 9.09 | 0.300000 | 0.345128 | 9.09 |
VAV_MID WITH REHEAT | 45.73 | 30.23 | 91.47 | 30.23 | 84.55 | 84.55 | 0.300000 | 0.357596 | 84.55 |
VAV_TOP WITH REHEAT | 4.77 | 3.12 | 9.55 | 4.81 | 8.71 | 8.71 | 0.300000 | 0.551656 | 8.71 |
AIRLOOP DATACENTER BASEMENT | 21.20 | 21.20 | 21.20 | 21.20 | 21.20 | 21.20 | 1.00 | 1.00 | 21.20 |
AIRLOOP DATACENTER BOT | 0.463785 | 0.463785 | 0.463785 | 0.463785 | 0.463785 | 0.463785 | 1.00 | 1.00 | 0.463785 |
AIRLOOP DATACENTER MID | 4.42 | 4.42 | 4.42 | 4.42 | 4.42 | 4.42 | 1.00 | 1.00 | 4.42 |
AIRLOOP DATACENTER TOP | 0.450499 | 0.450499 | 0.450499 | 0.450499 | 0.450499 | 0.450499 | 1.00 | 1.00 | 0.450499 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.34 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.09 | 2.54 |
VAV_MID WITH REHEAT_OA_CONTROLLER | 84.55 | 25.38 |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.71 | 2.54 |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.20 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.463785 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.42 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.450499 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 113661.20 | 0.004835 | 5.34 | 0.010129 | 24.70 | 6.67 | 11.42 | 0.008281 |
VAV_BOT WITH REHEAT_COOLC | 228367.07 | 0.009715 | 9.09 | 0.010481 | 26.45 | 6.67 | 11.42 | 0.008281 |
VAV_MID WITH REHEAT_COOLC | 2215552.63 | 0.094255 | 84.55 | 0.010721 | 26.72 | 6.67 | 11.43 | 0.008281 |
VAV_TOP WITH REHEAT_COOLC | 215963.90 | 0.009188 | 8.71 | 0.010420 | 26.32 | 6.67 | 11.42 | 0.008281 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.34 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.004835 | 0.000098 |
CAV_BAS_HEATC_CONTROLLER | 0.006046 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009715 | 0.000049 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001608 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.094255 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.015927 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009188 | 0.000052 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001584 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022755 | 0.000021 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.09 |
VAV_MID WITH REHEAT FAN | 84.55 |
VAV_TOP WITH REHEAT FAN | 8.71 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.20 | 426851.44 | 308403.09 | 0.010454 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.463785 | 9236.33 | 6708.38 | 0.000226 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.42 | 88220.15 | 64024.21 | 0.002161 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.450499 | 8982.65 | 6519.85 | 0.000220 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.20 | 21.20 | 21.20 | 21.20 | 426851.44 | 426851.44 | 20748.52 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.463785 | 0.463785 | 0.463785 | 0.463785 | 9236.33 | 9236.33 | 958.50 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.42 | 4.42 | 4.42 | 4.42 | 88220.15 | 88220.15 | 9584.96 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.450499 | 0.450499 | 0.450499 | 0.450499 | 8982.65 | 8982.65 | 958.50 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.20 |
DATACENTER BOT SUPPLY FAN | 0.463785 |
DATACENTER MID SUPPLY FAN | 4.42 |
DATACENTER TOP SUPPLY FAN | 0.450499 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.20 | 426851.44 | 0.010454 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.463785 | 9236.33 | 0.000226 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.42 | 88220.15 | 0.002161 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.450499 | 8982.65 | 0.000220 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 20748.52 | |
DATACENTER_EXTRAELECHEATC | 426851.44 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 958.50 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 9584.96 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 958.50 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000172 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.117993 | 28260.34 |
HEATSYS1 PUMP | 0.075965 | 19408.13 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.117993 | 14.16 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.075965 | 9.12 |
COOLSYS1_SUPPLY | 0.117993 | 14.16 |
SINGLE WATER PLANT LOOP | 0.013060 | 1.57 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.117993 | 0.117993 | 495275.86 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 5.96 |
COOLSYS1 PUMP | 0.117993 | 9420.11 |
PLANT CIRC PUMP | 0.013060 | 3331.02 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3438307.10 | 1719153.55 | 0.075965 |
DUMMY BOILER | 537970.41 | 93894.07 | 0.013060 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.117993 | 0.059260 | 1396387.92 | 1403048.39 | 0.069432 |
COOLSYS1 CHILLER2 | 0.117993 | 0.059260 | 1396387.92 | 1403048.39 | 0.069432 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013060 | 139666.47 | 60253.03 | 69833.23 | 7879.72 | 21509.49 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.138863 | 16.66 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.138863 | 35476.22 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.69 | 1331744.19 | 10.74 | 166468.02 |
TOWERWATERSYS COOLTOWER 2 | 53.69 | 1331744.19 | 10.74 | 166468.02 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.057694 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.944 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.786 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.013 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.944 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 16.014 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.944 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 223.243 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 7.944 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.367 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 22079.114 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 22079.114 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 19828.597 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19828.597 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2489.678 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.678 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2489.733 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2489.733 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1604.443 | 7.944 | 147.586 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1604.443 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 6225.366 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 6225.366 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 287.586 | 7.944 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 287.586 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
51 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
52 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
53 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
54 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
55 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
56 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
57 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
58 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
59 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
60 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
61 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
62 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
63 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
64 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
65 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
66 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
67 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
68 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
69 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
70 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
71 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
72 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
73 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
74 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
75 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
76 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
77 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
78 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
79 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
80 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
81 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
82 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
83 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
84 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
85 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
86 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
87 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
88 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
89 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
90 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
91 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
92 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
93 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
94 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
95 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
96 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
97 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
98 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
99 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
100 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
101 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
102 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
103 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
104 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
105 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
106 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
107 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.4 | 29 | 1 | VerySmooth | 2.159 | 0.394 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.31435 | 0.47939 | 0.47939 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 74081.74805 | 74081.74805 | 5.33523 | 5.33523 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 77893.46032 | 77893.46032 | 5.60943 | 5.60943 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 731983.28056 | 731983.28056 | 52.69837 | 52.69837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 238586.34182 | 238586.34182 | 10.05334 | 10.77757 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 74730.07461 | 74730.07461 | 5.38082 | 5.38082 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 56824.65593 | 56824.65593 | 2.41419 | 2.41419 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11935.59930 | 11935.59930 | 0.86017 | 0.86017 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6600.65202 | 6600.65202 | 0.28023 | 0.28023 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14072.23331 | 14072.23331 | 1.01561 | 1.01561 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4695.94992 | 4695.94992 | 0.19952 | 0.19952 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 13542.90269 | 13542.90269 | 0.98444 | 0.98444 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:50:00 | 31.63133 | 1.40969E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 8383.42797 | 8383.42797 | 0.35651 | 0.35651 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 17258.10302 | 17258.10302 | 1.25449 | 1.25449 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 31.26133 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3197.74577 | 3197.74577 | 0.13544 | 0.13544 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 111500.96669 | 111500.96669 | 8.03402 | 8.03402 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 133596.19159 | 133596.19159 | 5.69280 | 5.69280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 145985.74590 | 145985.74590 | 10.61192 | 10.61192 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 27.79567 | 1.40969E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 88202.81638 | 88202.81638 | 3.75881 | 3.75881 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 127173.18214 | 127173.18214 | 9.24448 | 9.24448 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.40969E-002 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 133083.31247 | 133083.31247 | 5.67086 | 5.67086 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 149660.78579 | 149660.78579 | 10.87907 | 10.87907 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 84066.56593 | 84066.56593 | 3.58195 | 3.58195 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 12279.82813 | 12279.82813 | 0.89265 | 0.89265 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.40969E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17064.60046 | 17064.60046 | 0.72770 | 0.72770 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14836.94817 | 14836.94817 | 1.07853 | 1.07853 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 28.03000 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11195.67798 | 11195.67798 | 0.47745 | 0.47745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 14206.73111 | 14206.73111 | 1.03272 | 1.03272 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 16986.05057 | 16986.05057 | 0.72434 | 0.72434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 15995.23748 | 15995.23748 | 1.16273 | 1.16273 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10868.66331 | 10868.66331 | 0.46347 | 0.46347 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8090.17680 | 8090.17680 | 0.46378 | 0.46378 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.40969E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 77160.40331 | 77160.40331 | 4.42336 | 4.42336 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.40969E-002 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7858.42588 | 7858.42588 | 0.45050 | 0.45050 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.40969E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369787.32572 | 369787.32572 | 21.19875 | 21.19875 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 24.93433 | 1.40969E-002 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 76484.87 | 5.33523 | 5.33523 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 73587.49 | 1.20008 | 1.20008 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 137232.01 | 9.08650 | 9.08650 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 58249.57 | 2.04946 | 2.04946 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1247964.00 | 84.54623 | 84.54623 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 720762.45 | 29.48200 | 29.48200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 142197.20 | 8.71405 | 8.71405 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 71629.67 | 4.80715 | 4.80715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 365585.51 | 21.19875 | 21.19875 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20748.52 | 0.33837 | 0.33837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8013.93 | 0.46378 | 0.46378 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 958.50 | 1.56314E-002 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 76455.76 | 4.42336 | 4.42336 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9584.96 | 0.15631 | 0.15631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7789.26 | 0.45050 | 0.45050 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 958.50 | 1.56314E-002 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.33523 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.60943 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33908 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33900 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.90160 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.90421 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.12363E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.22824E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90160 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19137.69589 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.22824E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 333.09652 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.69837 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36093 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35300 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.60252 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.96248 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05561E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.40759E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.60252 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 425802.64165 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.40759E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8155.41128 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.38082 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35349 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34800 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.87252 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94263 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.07784E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.79227E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.41419 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 81121.14991 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79227E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1693.61180 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86017 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27764 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25805 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74038 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37226E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07985E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28023 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9413.71538 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07985E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 196.51990 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.01561 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15154 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30468 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40411 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51420E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.71356E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30468 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7755.85490 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71356E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 151.36939 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98444 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24260 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29533 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64693 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57049E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64370E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35651 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11965.81032 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64370E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 249.73155 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.25449 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12268 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37635 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.32716 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10556E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53983E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.37635 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6969.49797 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53983E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 129.61960 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.03402 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29726 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.41021 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79270 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28170E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21631E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.69280 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 190836.95116 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21631E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3981.36616 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.61192 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14503 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.18358 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38675 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.62704E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.78376E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.75881 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 125997.64109 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78376E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2628.60048 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.24448 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25834 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.77335 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68892 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47478E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.20010E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.67086 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 190103.23640 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.20010E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3966.06980 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.87907 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14147 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.26372 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37725 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69317E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65304E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.58195 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120080.87577 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65304E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2505.23720 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.89265 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26754 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26780 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.71344 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.42409E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.38698E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72770 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24382.32524 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38698E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 508.60451 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07853 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14270 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32356 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38053 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66995E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.53431E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47745 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15996.84914 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.53431E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 333.68356 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.03272 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23126 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30982 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61669 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64751E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.36215E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72434 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24269.96592 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.36215E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 506.26202 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16273 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13237 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34882 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35298 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87839E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43097E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46347 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15529.11934 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43097E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 323.93127 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.46378 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.42336 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45050 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.19875 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.33523 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.33523 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.33523 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.33523 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.33523 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.33523 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.86207 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.13601 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.72414 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.13601 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.08650 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.08650 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34513 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 45.73393 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 30.23337 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 91.46787 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 30.23337 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 84.54623 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 84.54623 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35760 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.77372 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.12251 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.54745 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.80715 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.71405 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.71405 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.55166 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.19875 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.19875 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.19875 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.19875 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.19875 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.19875 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.46378 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.46378 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.46378 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.46378 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.46378 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.46378 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.42336 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.42336 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.42336 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.42336 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.42336 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.42336 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45050 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45050 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45050 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45050 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45050 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.45050 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.33523 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.08650 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 84.54623 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.71405 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.19875 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.46378 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.42336 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.45050 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.33523 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 113661.19583 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.83541E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.33523 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.01289E-002 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.69716 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42375 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 273636.49922 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 6.04566E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 4996.22572 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.33523 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.83541E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.84799E-005 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.04566E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.08650 |
306 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53804 |
307 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 228367.07313 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 9.71526E-003 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 9.08650 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.04813E-002 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.44956 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42463 |
315 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 72792.46511 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.60826E-003 |
318 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 1005.34140 |
319 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.08650 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.71526E-003 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.90147E-005 |
322 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.60826E-003 |
323 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 84.54623 |
324 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 25.38036 |
325 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38036 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 2215552.62703 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 9.42547E-002 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 84.54623 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.07212E-002 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.72219 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
332 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42523 |
333 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 720889.44532 |
335 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.59272E-002 |
336 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 9855.14517 |
337 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 84.54623 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.42547E-002 |
339 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.05217E-006 |
340 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.59272E-002 |
341 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.71405 |
342 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 2.53804 |
343 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 215963.89745 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 9.18760E-003 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.71405 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.04196E-002 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.31982 |
349 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
350 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42448 |
351 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
352 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 71699.46641 |
353 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.58411E-003 |
354 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 985.89200 |
355 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.71405 |
356 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.18760E-003 |
357 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.18297E-005 |
358 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.58411E-003 |
359 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.19875 |
360 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.19875 |
362 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 426851.44061 |
363 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 308403.08965 |
364 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04536E-002 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.19875 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.19875 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.19875 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.19875 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 426851.44061 |
370 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 426851.44061 |
371 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 20748.52325 |
372 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
373 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.19875 |
374 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.19875 |
375 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 426851.44061 |
376 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04536E-002 |
377 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 20748.52325 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.71881E-004 |
379 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
380 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
381 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
382 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 426851.44061 |
383 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
384 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1029925.89674 |
385 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.27550E-002 |
386 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19145.09171 |
387 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.27550E-002 |
388 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.09269E-005 |
389 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.46378 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46378 |
391 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9236.32708 |
392 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6708.38103 |
393 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.26197E-004 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.46378 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.46378 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.46378 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.46378 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9236.32708 |
399 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9236.32708 |
400 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.49582 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
402 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46378 |
403 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.46378 |
404 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9236.32708 |
405 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.26197E-004 |
406 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 958.49582 |
407 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.42336 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.42336 |
409 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 88220.15056 |
410 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 64024.21029 |
411 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.16051E-003 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.42336 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.42336 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.42336 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.42336 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 88220.15056 |
417 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 88220.15056 |
418 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 9584.95818 |
419 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
420 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.42336 |
421 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.42336 |
422 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 88220.15056 |
423 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.16051E-003 |
424 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 9584.95818 |
425 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45050 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45050 |
427 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 8982.65290 |
428 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6519.84740 |
429 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.19985E-004 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45050 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45050 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45050 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45050 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8982.65290 |
435 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8982.65290 |
436 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.49582 |
437 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
438 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45050 |
439 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.45050 |
440 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 8982.65290 |
441 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.19985E-004 |
442 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 958.49582 |
443 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11799 |
444 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 28260.33560 |
445 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11799 |
446 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 14.15916 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11799 |
448 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11799 |
449 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 495275.85597 |
450 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
451 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
452 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
453 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
454 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 5.95777 |
455 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
456 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 7.59652E-002 |
457 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 9.11582 |
458 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 7.59652E-002 |
459 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 19408.13297 |
460 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3438307.10287 |
461 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1719153.55000 |
462 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 7.59652E-002 |
463 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11799 |
464 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 14.15916 |
465 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.11799 |
466 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 9420.11187 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11799 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.92600E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1396387.92455 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1403048.38500 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.94317E-002 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11799 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.92600E-002 |
474 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1396387.92455 |
475 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1403048.38500 |
476 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.94317E-002 |
477 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.30603E-002 |
478 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.56723 |
479 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.30603E-002 |
480 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3331.01731 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.30603E-002 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60253.02505 |
484 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
485 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
486 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21509.49029 |
487 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 537970.40649 |
488 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
489 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.30603E-002 |
490 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13886 |
491 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.66360 |
492 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13886 |
493 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 35476.22147 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.69123 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1331744.19156 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.73825 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 166468.02394 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.69123 |
499 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1331744.19156 |
500 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.73825 |
501 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 166468.02394 |
502 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.76940E-002 |
503 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.76940E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18156.07 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 404199.75 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 76965.85 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8931.52 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7361.16 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11352.89 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 6617.69 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 181062.03 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 119543.88 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 180365.90 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 113930.17 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23133.44 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15177.48 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23026.84 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14733.70 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 213559.18 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 52437.52 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 511334.98 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 51310.11 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 825792.36 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 145367.71 | 99170.46 | 46197.25 | 0.68 | 17940.75 | 181.97 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 264221.18 | 176449.37 | 87771.80 | 0.67 | 32761.37 | 332.28 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2490091.12 | 1655987.54 | 834103.58 | 0.67 | 307818.26 | 3122.06 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 252415.99 | 168787.23 | 83628.76 | 0.67 | 31371.04 | 318.18 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.16 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.16 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.4 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.3380945332E-003 | 1.2911238985E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.2838011071E-003 | 3.1585016459E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.4577844004E-002 | 1.9560075325E-002 | Pass | Pass | 0.4847858750 | 0.4926327150 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.8522028833E-002 | 6.2160911840E-002 | Pass | Pass | 2.2859373660 | 17.1779436917 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.8010589856E-002 | 2.1090904209E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.9873327393E-002 | 5.9529920740E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 8.4041792268E-002 | 9.4515075213E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.8283812224E-002 | 3.3137715045E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5460870731 | 0.4854624659 | Pass | Pass | 0.7699686735 | 0.6877263371 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4922234428 | 0.5188110971 | Pass | Pass | 0.7808906031 | 0.7786228381 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3777462433 | 0.4336991836 | Pass | Pass | 0.9541341947 | 2.7142504155 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4645726431 | 0.4778208788 | Pass | Pass | 0.7701876514 | 0.8095985829 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7382854866 | 0.6120743255 | Pass | Pass | 0.6939332214 | 0.6154783502 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6783640975 | 0.6841332532 | Pass | Pass | 0.7428075506 | 0.7210502716 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5352081960 | 0.5847002051 | Pass | Pass | 5.8158168807 | 61.2085288968 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6562767678 | 0.6580326988 | Pass | Pass | 0.7499160238 | 0.7329581595 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0495550453E-002 | 7.4676492260E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.8930008328E-002 | 4.8689177296E-002 | Pass | Pass | 0.4855878883 | 0.4824920325 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1619683648 | 0.1172179090 | Pass | Pass | 0.4893494873 | 0.4901189614 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.4261584536E-015 | 6.9798894315E-015 | Pass | Pass | 9.3579684173E-003 | 6.9977753433E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.8869436046E-003 | 8.2570546808E-003 | Pass | Pass | 3.8300268713E-003 | 4.9140213172E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.5347767184E-002 | 1.1302011757E-002 | Pass | Pass | 5.6133861831E-003 | 6.6419604138E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 9.7428238317E-014 | 7.8029033811E-014 | Pass | Pass | 5.1671052535E-005 | 3.0961480539E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.4 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_0.4 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.394 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.394 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.4 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.394 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.159 | 0.394 | 0.401 | ||||||||||||
North Total or Average | 1043.06 | 2.159 | 0.394 | 0.401 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.159 | 0.394 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 7.9438 | 2779.43 | 22079.11 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 210.95 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 7.9438 | 2496.12 | 19828.60 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 189.45 |
CORE_MID_LIGHTS | CORE_MID | 7.9438 | 24961.20 | 198285.97 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 1894.50 |
CORE_TOP_LIGHTS | CORE_TOP | 7.9438 | 2496.12 | 19828.60 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 189.45 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 7.9438 | 313.41 | 2489.68 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.85 | 0.0000 | Y | 18.63 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.85 | 0.0000 | Y | 12.00 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 7.9438 | 313.42 | 2489.73 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.75 | 0.0000 | Y | 18.58 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.75 | 0.0000 | Y | 11.97 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 7.9438 | 3134.13 | 24896.78 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.87 | 0.0000 | Y | 186.33 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 7.9438 | 2019.75 | 16044.43 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.86 | 0.0000 | Y | 120.05 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 7.9438 | 3134.20 | 24897.33 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.76 | 0.0000 | Y | 185.80 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 7.9438 | 2019.75 | 16044.43 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.76 | 0.0000 | Y | 119.74 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 7.9438 | 313.41 | 2489.68 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.87 | 0.0000 | Y | 18.63 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.86 | 0.0000 | Y | 12.01 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 7.9438 | 313.42 | 2489.73 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.76 | 0.0000 | Y | 18.58 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 7.9438 | 201.98 | 1604.44 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 39.76 | 0.0000 | Y | 11.97 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 7.9438 | 783.68 | 6225.37 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 59.48 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 7.9438 | 36.20 | 287.59 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 2.75 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 7.9438 | 362.03 | 2875.86 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 27.48 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 7.9438 | 36.20 | 287.59 | LightsWired | BLDG_LIGHT_SCH | 52.24 | 168.00 | 50.90 | 0.0000 | Y | 2.75 |
Interior Lighting Total | 7.9438 | 46320.38 | 367958.24 | 1030.59 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.68 | 960.27 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.68 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2489.73 | 960.29 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2489.73 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1604.44 | 618.83 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1604.44 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9734.40 | AstronomicalClock | - | 42.43 | 42.43 | 77.54 | |
EXTERIOR_LIGHTS_B | 43301.51 | AstronomicalClock | - | 83.64 | 71.28 | 579.38 | |
Exterior Lighting Total | 53035.91 | 656.92 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2767166.46 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1719153.55 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1403048.39 | 6.28 | 7.08 | 24.16 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1403048.39 | 6.28 | 7.08 | 24.16 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1331744.19 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1331744.19 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 113661.20 | 145367.71 | 99170.46 | 46197.25 | 0.68 | - | 17940.75 | 181.97 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 228367.07 | 264221.18 | 176449.37 | 87771.80 | 0.67 | - | 32761.37 | 332.28 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 2215552.63 | 2490091.12 | 1655987.54 | 834103.58 | 0.67 | - | 307818.26 | 3122.06 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 215963.90 | 252415.99 | 168787.23 | 83628.76 | 0.67 | - | 31371.04 | 318.18 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 426851.44 | 308403.09 | 118448.35 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9236.33 | 6708.38 | 2527.95 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 88220.15 | 64024.21 | 24195.94 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8982.65 | 6519.85 | 2462.81 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 19137.70 | 18156.07 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 425802.64 | 404199.75 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 81121.15 | 76965.85 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9413.72 | 8931.52 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 7755.85 | 7361.16 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11965.81 | 11352.89 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 6969.50 | 6617.69 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 190836.95 | 181062.03 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 125997.64 | 119543.88 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 190103.24 | 180365.90 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 120080.88 | 113930.17 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 24382.33 | 23133.44 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15996.85 | 15177.48 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24269.97 | 23026.84 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15529.12 | 14733.70 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 273636.50 | 213559.18 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 72792.47 | 52437.52 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 720889.45 | 511334.98 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 71699.47 | 51310.11 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 426851.44 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9236.33 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 88220.15 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 8982.65 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 20748.52 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1029925.90 | 825792.36 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 958.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 9584.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 958.50 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.34 | 9046.71 | 1695.65 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.09 | 20751.10 | 2283.73 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 84.55 | 193080.57 | 2283.73 | 1.00 | 1.07 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.71 | 19900.52 | 2283.73 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.20 | 35146.96 | 1657.97 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 519.49 | 1120.11 | 1.00 | 1.64 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.42 | 4954.65 | 1120.11 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 504.61 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.117993 | 28260.34 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.075965 | 19408.13 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.117993 | 9420.11 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013060 | 3331.02 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.138863 | 35476.22 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 74081.75 | 74081.75 | 26.65 | 5.335 | 5.335 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00897 | 26.62 | 0.01410 | 1.200 | 0.00 |
CORE_BOTTOM | 77893.46 | 77893.46 | 31.21 | 5.609 | 5.609 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00890 | 26.62 | 0.01410 | 1.078 | 0.00 |
CORE_MID | 731983.28 | 731983.28 | 293.25 | 52.698 | 52.698 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 26.62 | 0.01410 | 10.778 | 0.00 |
CORE_TOP | 74730.07 | 74730.07 | 29.94 | 5.381 | 5.381 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 26.62 | 0.01410 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11935.60 | 11935.60 | 38.08 | 0.860 | 0.860 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00888 | 26.62 | 0.01410 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14072.23 | 14072.23 | 69.67 | 1.016 | 1.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00870 | 26.62 | 0.01410 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13542.90 | 13542.90 | 43.21 | 0.984 | 0.984 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:50:00 | 24.00 | 24.00 | 0.00883 | 31.63 | 0.01410 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 17258.10 | 17258.10 | 85.45 | 1.254 | 1.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00867 | 31.26 | 0.01410 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 111500.97 | 111500.97 | 355.76 | 8.034 | 8.034 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 26.62 | 0.01410 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 145985.75 | 145985.75 | 722.79 | 10.612 | 10.612 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00873 | 27.80 | 0.01410 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 127173.18 | 127173.18 | 405.76 | 9.244 | 9.244 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00890 | 31.79 | 0.01410 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 149660.79 | 149660.79 | 740.99 | 10.879 | 10.879 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00872 | 31.16 | 0.01410 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 12279.83 | 12279.83 | 39.18 | 0.893 | 0.893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00894 | 32.10 | 0.01410 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14836.95 | 14836.95 | 73.46 | 1.079 | 1.079 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00874 | 28.03 | 0.01410 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 14206.73 | 14206.73 | 45.33 | 1.033 | 1.033 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00888 | 31.92 | 0.01410 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 15995.24 | 15995.24 | 79.19 | 1.163 | 1.163 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00872 | 31.16 | 0.01410 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8090.18 | 8090.18 | 223.47 | 0.464 | 0.464 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 29.58 | 0.01410 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 77160.40 | 77160.40 | 2131.34 | 4.423 | 4.423 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 29.58 | 0.01410 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7858.43 | 7858.43 | 217.07 | 0.450 | 0.450 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00850 | 29.77 | 0.01410 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369787.33 | 369787.33 | 471.86 | 21.199 | 21.199 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 24.93 | 0.01410 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 | |
CORE_MID | 238586.34 | 238586.34 | 95.58 | 10.053 | 10.778 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 56824.66 | 56824.66 | 22.77 | 2.414 | 2.414 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6600.65 | 6600.65 | 21.06 | 0.280 | 0.280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00680 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4695.95 | 4695.95 | 23.25 | 0.200 | 0.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00702 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 8383.43 | 8383.43 | 26.75 | 0.357 | 0.357 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00729 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3197.75 | 3197.75 | 15.83 | 0.135 | 0.135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00594 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 133596.19 | 133596.19 | 426.26 | 5.693 | 5.693 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 88202.82 | 88202.82 | 436.70 | 3.759 | 3.759 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 133083.31 | 133083.31 | 424.62 | 5.671 | 5.671 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 84066.57 | 84066.57 | 416.22 | 3.582 | 3.582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17064.60 | 17064.60 | 54.45 | 0.728 | 0.728 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11195.68 | 11195.68 | 55.43 | 0.477 | 0.477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16986.05 | 16986.05 | 54.20 | 0.724 | 0.724 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10868.66 | 10868.66 | 53.81 | 0.463 | 0.463 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.34 | 5.34 | 1.20 | 1.20 | 5.3352 | 5.3352 | 5.3352 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 9.09 | 9.09 | 2.05 | 2.05 | 9.0865 | 3.1360 | 9.0865 | 0.3451 | 0.3000 |
VAV_MID WITH REHEAT | 84.55 | 84.55 | 29.48 | 29.48 | 84.5462 | 30.2334 | 84.5462 | 0.3576 | 0.3000 |
VAV_TOP WITH REHEAT | 8.71 | 8.71 | 4.81 | 4.81 | 8.7141 | 4.8072 | 8.7141 | 0.5517 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.20 | 21.20 | 0.34 | 0.34 | 21.1988 | 21.1988 | 21.1988 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4638 | 0.4638 | 0.4638 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.42 | 4.42 | 0.16 | 0.16 | 4.4234 | 4.4234 | 4.4234 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4505 | 0.4505 | 0.4505 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 19137.696 | 19137.696 | 1.901595 | 0.00042282 | 333.097 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18156.07 | 19137.70 | 1.901595 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19214.68 | 19214.68 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 425802.642 | 425802.642 | 18.602524 | 0.00940759 | 8155.411 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 404199.75 | 425802.64 | 18.602524 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 238586.34 | 0.00 | 427825.13 | 427825.13 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 81121.150 | 81121.150 | 2.414193 | 0.00179227 | 1693.612 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76965.85 | 81121.15 | 2.414193 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 56824.66 | 0.00 | 81491.54 | 81491.54 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9413.715 | 9413.715 | 0.280228 | 0.00020798 | 196.520 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8931.52 | 9413.72 | 0.280228 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00679752 | 44.0146 | 6600.65 | 0.00 | 9456.70 | 9456.70 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7755.855 | 7755.855 | 0.304683 | 0.00017136 | 151.369 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7361.16 | 7755.85 | 0.304683 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00702090 | 45.4441 | 4695.95 | 0.00 | 7792.02 | 7792.02 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11965.810 | 11965.810 | 0.356509 | 0.00026437 | 249.732 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11352.89 | 11965.81 | 0.356509 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00729368 | 47.1878 | 8383.43 | 0.00 | 12020.44 | 12020.44 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 6969.498 | 6969.498 | 0.376347 | 0.00015398 | 129.620 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6617.69 | 6969.50 | 0.376347 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00594297 | 38.5352 | 3197.75 | 0.00 | 7003.61 | 7003.61 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 190836.951 | 190836.951 | 5.692801 | 0.00421631 | 3981.366 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181062.03 | 190836.95 | 5.692801 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00761022 | 49.2094 | 133596.19 | 0.00 | 191708.19 | 191708.19 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 125997.641 | 125997.641 | 3.758813 | 0.00278376 | 2628.600 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 119543.88 | 125997.64 | 3.758813 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00761332 | 49.2292 | 88202.82 | 0.00 | 126572.87 | 126572.87 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 190103.236 | 190103.236 | 5.670863 | 0.00420010 | 3966.070 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180365.90 | 190103.24 | 5.670863 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00760809 | 49.1958 | 133083.31 | 0.00 | 190971.13 | 190971.13 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 120080.876 | 120080.876 | 3.581951 | 0.00265304 | 2505.237 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113930.17 | 120080.88 | 3.581951 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00758471 | 49.0467 | 84066.57 | 0.00 | 120629.09 | 120629.09 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 24382.325 | 24382.325 | 0.727701 | 0.00053870 | 508.605 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23133.44 | 24382.33 | 0.727701 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766583 | 49.5646 | 17064.60 | 0.00 | 24493.64 | 24493.64 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15996.849 | 15996.849 | 0.477450 | 0.00035343 | 333.684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15177.48 | 15996.85 | 0.477450 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766266 | 49.5445 | 11195.68 | 0.00 | 16069.88 | 16069.88 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 24269.966 | 24269.966 | 0.724341 | 0.00053622 | 506.262 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23026.84 | 24269.97 | 0.724341 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766397 | 49.5527 | 16986.05 | 0.00 | 24380.77 | 24380.77 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15529.119 | 15529.119 | 0.463470 | 0.00034310 | 323.931 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14733.70 | 15529.12 | 0.463470 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00764963 | 49.4614 | 10868.66 | 0.00 | 15600.01 | 15600.01 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 113661.196 | -999.000 | 5.335230 | 0.00483541 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 113661.20 | 84703.46 | 5.335230 | 24.70 | 17.97 | 0.01012894 | 11.42 | 11.42 | 0.00828082 | 27.09 | 0.01409688 | 21.69 | 22.4935 | 24.00 | 0.00897292 | 48.2468 | 73124.84 | 0.00 | 126391.10 | 90863.43 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 273636.499 | 273636.499 | 5.335230 | 0.00604566 | 4996.226 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 213559.18 | 273636.50 | 5.335230 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.4935 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 225260.72 | 225260.72 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 228367.073 | -999.000 | 9.086504 | 0.00971526 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 228367.07 | 167826.94 | 9.086504 | 26.45 | 18.82 | 0.01048129 | 11.42 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 27.9320 | 24.00 | 0.00884119 | 47.5481 | 114359.73 | 0.00 | 250057.68 | 177064.94 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 72792.465 | 72792.465 | 2.725951 | 0.00160826 | 1005.341 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52437.52 | 72792.47 | 2.725951 | -10.70 | -10.70 | 0.00150390 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 93.1066 | 21.00 | 0.00748145 | 48.3857 | 22877.78 | 0.00 | 55426.15 | 55426.15 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2215552.627 | -999.000 | 84.546227 | 0.09425473 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2215552.63 | 1590362.45 | 84.546227 | 26.72 | 19.10 | 0.01072122 | 11.43 | 12.09 | 0.00828082 | 31.95 | 0.01409688 | 23.06 | 30.0195 | 24.00 | 0.00888253 | 47.7676 | 1019592.05 | 0.00 | 2417459.82 | 1677441.42 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 720889.445 | 720889.445 | 25.363868 | 0.01592717 | 9855.145 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 511334.98 | 720889.45 | 25.363868 | -10.63 | -10.63 | 0.00151869 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 100.0650 | 21.00 | 0.00774959 | 50.0978 | 512657.92 | 0.00 | 540431.96 | 540431.96 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 215963.897 | -999.000 | 8.714050 | 0.00918760 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 215963.90 | 159547.84 | 8.714050 | 26.32 | 18.73 | 0.01041965 | 11.42 | 12.09 | 0.00828082 | 31.95 | 0.01409688 | 23.06 | 29.1258 | 24.00 | 0.00887344 | 47.7195 | 119633.25 | 0.00 | 236839.86 | 168420.47 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 71699.466 | 71699.466 | 2.614215 | 0.00158411 | 985.892 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51310.11 | 71699.47 | 2.614215 | -9.75 | -9.75 | 0.00169134 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 97.0861 | 21.00 | 0.00783150 | 50.6200 | 54973.19 | 0.00 | 54233.63 | 54233.63 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426851.441 | 308403.090 | 21.198751 | 0.01045356 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 456699.39 | 450725.10 | -999.0 | 28.48 | 17.98 | 0.00858948 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 369207.55 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9236.327 | 6708.381 | 0.463785 | 0.00022620 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 9900.77 | 9624.57 | -999.0 | 28.03 | 17.91 | 0.00868864 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01409688 | 22.40 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 8090.18 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88220.151 | 64024.210 | 4.423365 | 0.00216051 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 94543.75 | 91782.77 | -999.0 | 28.04 | 17.92 | 0.00869778 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01409688 | 22.40 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 77160.40 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8982.653 | 6519.847 | 0.450499 | 0.00021998 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9626.87 | 9350.76 | -999.0 | 28.04 | 17.92 | 0.00869420 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01409688 | 22.45 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 7858.43 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426851.441 | 426851.441 | 21.198751 | 0.01045356 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 426851.44 | 426851.44 | 21.198751 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5962 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9236.327 | 9236.327 | 0.463785 | 0.00022620 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9236.33 | 9236.33 | 0.463785 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3704 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 88220.151 | 88220.151 | 4.423365 | 0.00216051 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 88220.15 | 88220.15 | 4.423365 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.5338 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8982.653 | 8982.653 | 0.450499 | 0.00021998 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8982.65 | 8982.65 | 0.450499 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4698 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 20748.523 | 20748.523 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20748.52 | 20748.52 | 21.198751 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5962 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 1319094.64 | 21.198751 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5962 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1029925.897 | 1029925.897 | 21.198751 | 0.02275495 | 19145.092 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 825792.36 | 1029925.90 | 21.198751 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5962 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 0.463785 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.3704 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 9584.958 | 9584.958 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9584.96 | 9584.96 | 4.423365 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.5338 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 0.450499 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4698 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 19137.696 | 19137.696 | 1.901595 | 0.00042282 | 333.097 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.5176 | 0.556602 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18156.07 | 19137.70 | 1.0000 | 2.28875042 | 1.901595 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.42278087 | 60.00 | 49.00 | 11.00 | 0.000 | 18156.07 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19214.68 | 19214.68 | 2.28875042 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 425802.642 | 425802.642 | 18.602524 | 0.00940759 | 8155.411 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 11.5239 | 12.384078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 404199.75 | 425802.64 | 1.0000 | 22.38990491 | 18.602524 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 9.40662939 | 60.00 | 49.00 | 11.00 | 0.000 | 404199.75 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 238586.34 | 0.00 | 427825.13 | 427825.13 | 22.38990491 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 31.54 | 18.52 | 0.00800000 | 52167.8 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 81121.150 | 81121.150 | 2.414193 | 0.00179227 | 1693.612 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 2.1943 | 2.359334 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76965.85 | 81121.15 | 1.0000 | 2.90571086 | 2.414193 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.79208985 | 60.00 | 49.00 | 11.00 | 0.000 | 76965.85 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 56824.66 | 0.00 | 81491.54 | 81491.54 | 2.90571086 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.30 | 21.24 | 0.00800000 | 61105.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9413.715 | 9413.715 | 0.280228 | 0.00020798 | 196.520 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.2546 | 0.273789 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8931.52 | 9413.72 | 1.0000 | 0.33728155 | 0.280228 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.20796332 | 60.00 | 49.00 | 11.00 | 0.000 | 8931.52 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00679752 | 21.00 | 0.00679752 | 44.0146 | 6600.65 | 0.00 | 9456.70 | 9456.70 | 0.33728155 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.30 | 21.24 | 0.00800000 | 61097.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7755.855 | 7755.855 | 0.304683 | 0.00017136 | 151.369 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.2099 | 0.225572 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7361.16 | 7755.85 | 1.0000 | 0.36671492 | 0.304683 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.17133866 | 60.00 | 49.00 | 11.00 | 0.000 | 7361.16 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00702090 | 21.00 | 0.00702090 | 45.4441 | 4695.95 | 0.00 | 7792.02 | 7792.02 | 0.36671492 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 33.64 | 19.20 | 0.00800000 | 54308.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11965.810 | 11965.810 | 0.356509 | 0.00026437 | 249.732 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.3237 | 0.348015 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11352.89 | 11965.81 | 1.0000 | 0.42909252 | 0.356509 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26434299 | 60.00 | 49.00 | 11.00 | 0.000 | 11352.89 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00729368 | 21.00 | 0.00729368 | 47.1878 | 8383.43 | 0.00 | 12020.44 | 12020.44 | 0.42909252 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61073.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6969.498 | 6969.498 | 0.376347 | 0.00015398 | 129.620 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.1887 | 0.202701 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6617.69 | 6969.50 | 1.0000 | 0.45296963 | 0.376347 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.15396683 | 60.00 | 49.00 | 11.00 | 0.000 | 6617.69 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00594297 | 21.00 | 0.00594297 | 38.5352 | 3197.75 | 0.00 | 7003.61 | 7003.61 | 0.45296963 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 27.96 | 17.33 | 0.00800000 | 48521.4 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 190836.951 | 190836.951 | 5.692801 | 0.00421631 | 3981.366 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 5.1621 | 5.550317 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181062.03 | 190836.95 | 1.0000 | 6.85182712 | 5.692801 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 4.21587914 | 60.00 | 49.00 | 11.00 | 0.000 | 181062.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00761022 | 21.00 | 0.00761022 | 49.2094 | 133596.19 | 0.00 | 191708.19 | 191708.19 | 6.85182712 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 125997.641 | 125997.641 | 3.758813 | 0.00278376 | 2628.600 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 3.4082 | 3.664526 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 119543.88 | 125997.64 | 1.0000 | 4.52408902 | 3.758813 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.78347995 | 60.00 | 49.00 | 11.00 | 0.000 | 119543.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00761332 | 21.00 | 0.00761332 | 49.2292 | 88202.82 | 0.00 | 126572.87 | 126572.87 | 4.52408902 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61037.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 190103.236 | 190103.236 | 5.670863 | 0.00420010 | 3966.070 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 5.1423 | 5.528978 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180365.90 | 190103.24 | 1.0000 | 6.82542172 | 5.670863 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 4.19967026 | 60.00 | 49.00 | 11.00 | 0.000 | 180365.90 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00760809 | 21.00 | 0.00760809 | 49.1958 | 133083.31 | 0.00 | 190971.13 | 190971.13 | 6.82542172 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 120080.876 | 120080.876 | 3.581951 | 0.00265304 | 2505.237 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 3.2482 | 3.492442 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113930.17 | 120080.88 | 1.0000 | 4.31121846 | 3.581951 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.65276958 | 60.00 | 49.00 | 11.00 | 0.000 | 113930.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00758471 | 21.00 | 0.00758471 | 49.0467 | 84066.57 | 0.00 | 120629.09 | 120629.09 | 4.31121846 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61040.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24382.325 | 24382.325 | 0.727701 | 0.00053870 | 508.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.6595 | 0.709138 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23133.44 | 24382.33 | 1.0000 | 0.87585679 | 0.727701 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.53864273 | 60.00 | 49.00 | 11.00 | 0.000 | 23133.44 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766583 | 21.00 | 0.00766583 | 49.5646 | 17064.60 | 0.00 | 24493.64 | 24493.64 | 0.87585679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61025.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15996.849 | 15996.849 | 0.477450 | 0.00035343 | 333.684 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.4327 | 0.465254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15177.48 | 15996.85 | 1.0000 | 0.57465619 | 0.477450 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.35339478 | 60.00 | 49.00 | 11.00 | 0.000 | 15177.48 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766266 | 21.00 | 0.00766266 | 49.5445 | 11195.68 | 0.00 | 16069.88 | 16069.88 | 0.57465619 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61024.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24269.966 | 24269.966 | 0.724341 | 0.00053622 | 506.262 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.6565 | 0.705870 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23026.84 | 24269.97 | 1.0000 | 0.87181333 | 0.724341 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.53616054 | 60.00 | 49.00 | 11.00 | 0.000 | 23026.84 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766397 | 21.00 | 0.00766397 | 49.5527 | 16986.05 | 0.00 | 24380.77 | 24380.77 | 0.87181333 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61025.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15529.119 | 15529.119 | 0.463470 | 0.00034310 | 323.931 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 0.4201 | 0.451650 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14733.70 | 15529.12 | 1.0000 | 0.55782967 | 0.463470 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.34306192 | 60.00 | 49.00 | 11.00 | 0.000 | 14733.70 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764963 | 21.00 | 0.00764963 | 49.4614 | 10868.66 | 0.00 | 15600.01 | 15600.01 | 0.55782967 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61025.4 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 113661.196 | -999.000 | 5.335230 | 0.00483541 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6692 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.335230 | 6.42145581 | 4197.9300 | 999.8980 | 117.98097061 | 12.27 | 6.67 | 5.60 | 2773544.79 | 4.0980 | 4.098048 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 113661.20 | 84703.46 | 1.0000 | 6.42145581 | 5.335230 | 24.70 | 17.97 | 0.01012894 | 50613.6 | 11.42 | 11.42 | 0.00828082 | 32917.5 | 4.83491676 | 6.67 | 10.65 | 5.60 | 9046.706 | 104614.49 | 27.09 | 0.01409688 | 21.69 | 1.20008137 | 22.4935 | 24.00 | 0.00897187 | 24.00 | 0.00897292 | 48.2468 | 73124.84 | 0.00 | 126391.10 | 90863.43 | 6.42145581 | 24.70 | 17.97 | 0.01012894 | 50613.6 | 10.87 | 10.71 | 0.00793445 | 30931.0 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 273636.499 | 273636.499 | 5.335230 | 0.00604566 | 4996.226 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.335230 | 6.42145581 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 6.0886 | 7.958466 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 213559.18 | 273636.50 | 1.0000 | 6.42145581 | 5.335230 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 6.04504736 | 60.00 | 49.00 | 11.00 | 0.000 | 213559.18 | -10.70 | 0.00150390 | -10.70 | 1.20008137 | 22.4935 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 225260.72 | 225260.72 | 6.42145581 | 12.80 | 2.42 | 0.00033828 | 13716.0 | 47.69 | 17.58 | 0.00033828 | 48795.4 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 228367.073 | -999.000 | 9.086504 | 0.00971526 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3242 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.086504 | 10.93647048 | 4197.9300 | 999.8980 | 117.98097061 | 12.27 | 6.67 | 5.60 | 2773544.79 | 8.2338 | 8.233762 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 228367.07 | 167826.94 | 1.0000 | 10.93647048 | 9.086504 | 26.45 | 18.82 | 0.01048129 | 53306.0 | 11.42 | 12.09 | 0.00828082 | 34322.2 | 9.71427215 | 6.67 | 10.65 | 5.60 | 20751.102 | 207615.97 | 32.03 | 0.01409687 | 23.08 | 2.53804000 | 27.9320 | 24.00 | 0.00889225 | 24.00 | 0.00884119 | 47.5481 | 114359.73 | 0.00 | 250057.68 | 177064.94 | 10.93647048 | 26.45 | 18.83 | 0.01048129 | 53306.0 | 10.64 | 10.50 | 0.00783355 | 30441.4 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 72792.465 | 72792.465 | 2.725951 | 0.00160826 | 1005.341 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.086504 | 10.93647048 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 1.4950 | 2.117102 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52437.52 | 72792.47 | 1.0000 | 3.28094115 | 2.725951 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.60809651 | 60.00 | 49.00 | 11.00 | 0.000 | 52437.52 | -10.70 | 0.00150390 | -10.70 | 2.53804000 | 93.1066 | 9.91 | 0.00327446 | 21.00 | 0.00748145 | 48.3857 | 22877.78 | 0.00 | 55426.15 | 55426.15 | 3.28094115 | 12.80 | 4.18 | 0.00162595 | 16967.0 | 29.56 | 12.02 | 0.00162595 | 33860.4 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2215552.627 | -999.000 | 84.546227 | 0.09425473 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.7702 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.546227 | 101.75941481 | 4197.9300 | 999.8980 | 117.98097061 | 12.27 | 6.67 | 5.60 | 2773544.79 | 79.8816 | 79.881624 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2215552.63 | 1590362.45 | 1.0000 | 101.75941481 | 84.546227 | 26.72 | 19.10 | 0.01072122 | 54197.2 | 11.43 | 12.09 | 0.00828082 | 34322.2 | 94.24511549 | 6.67 | 10.65 | 5.60 | 193080.570 | 2022472.06 | 31.95 | 0.01409688 | 23.06 | 25.38036000 | 30.0195 | 24.00 | 0.00896324 | 24.00 | 0.00888253 | 47.7676 | 1019592.05 | 0.00 | 2417459.82 | 1677441.42 | 101.75941481 | 26.72 | 19.11 | 0.01072122 | 54197.2 | 10.64 | 10.50 | 0.00783623 | 30440.6 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 720889.445 | 720889.445 | 25.363868 | 0.01592717 | 9855.145 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 84.546227 | 101.75941481 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 14.5783 | 20.966407 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 511334.98 | 720889.45 | 1.0000 | 30.52782444 | 25.363868 | -10.63 | -10.63 | 0.00151869 | -6908.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 15.92554668 | 60.00 | 49.00 | 11.00 | 0.000 | 511334.98 | -10.70 | 0.00150390 | -10.70 | 25.38036000 | 100.0650 | 21.00 | 0.00776923 | 21.00 | 0.00774959 | 50.0978 | 512657.92 | 0.00 | 540431.96 | 540431.96 | 30.52782444 | 12.80 | 4.02 | 0.00150390 | 16658.9 | 30.37 | 12.23 | 0.00150390 | 34361.8 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 215963.897 | -999.000 | 8.714050 | 0.00918760 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.2096 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.714050 | 10.48818717 | 4197.9300 | 999.8980 | 117.98097061 | 12.27 | 6.67 | 5.60 | 2773544.79 | 7.7866 | 7.786566 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 215963.90 | 159547.84 | 1.0000 | 10.48818717 | 8.714050 | 26.32 | 18.73 | 0.01041965 | 53015.9 | 11.42 | 12.09 | 0.00828082 | 34322.2 | 9.18666621 | 6.67 | 10.65 | 5.60 | 19900.519 | 196063.38 | 31.95 | 0.01409688 | 23.06 | 2.53804000 | 29.1258 | 24.00 | 0.00890413 | 24.00 | 0.00887344 | 47.7195 | 119633.25 | 0.00 | 236839.86 | 168420.47 | 10.48818717 | 26.32 | 18.74 | 0.01041965 | 53015.9 | 10.64 | 10.50 | 0.00783171 | 30434.3 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 71699.466 | 71699.466 | 2.614215 | 0.00158411 | 985.892 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.714050 | 10.48818717 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 1.4629 | 2.085313 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51310.11 | 71699.47 | 1.0000 | 3.14645615 | 2.614215 | -9.75 | -9.75 | 0.00169134 | -5597.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.58395050 | 60.00 | 49.00 | 11.00 | 0.000 | 51310.11 | -10.70 | 0.00150390 | -10.70 | 2.53804000 | 97.0861 | 17.54 | 0.00707568 | 21.00 | 0.00783150 | 50.6200 | 54973.19 | 0.00 | 54233.63 | 54233.63 | 3.14645615 | 12.80 | 4.23 | 0.00166625 | 17068.8 | 29.90 | 12.20 | 0.00166625 | 34305.2 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 426851.441 | 308403.090 | 21.198751 | 0.01045356 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8074 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 456699.39 | 450725.10 | 0.9346 | -999.0 | -999.0 | 28.48 | 17.98 | 0.00858948 | 50557.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 456699.39 | 32.10 | 0.01409687 | 23.10 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 369207.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9236.327 | 6708.381 | 0.463785 | 0.00022620 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9917 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 9900.77 | 9624.57 | 0.9329 | -999.0 | -999.0 | 28.03 | 17.91 | 0.00868864 | 50351.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9900.77 | 29.58 | 0.01409688 | 22.40 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 8090.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 88220.151 | 64024.210 | 4.423365 | 0.00216051 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0087 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 94543.75 | 91782.77 | 0.9331 | -999.0 | -999.0 | 28.04 | 17.92 | 0.00869778 | 50379.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 94543.75 | 29.58 | 0.01409688 | 22.40 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 77160.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8982.653 | 6519.847 | 0.450499 | 0.00021998 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0021 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9626.87 | 9350.76 | 0.9331 | -999.0 | -999.0 | 28.04 | 17.92 | 0.00869420 | 50375.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9626.87 | 29.77 | 0.01409688 | 22.45 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 7858.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 426851.441 | 426851.441 | 21.198751 | 0.01045356 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 426851.44 | 426851.44 | 1.0000 | 25.51470993 | 21.198751 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 426851.44 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5962 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9236.327 | 9236.327 | 0.463785 | 0.00022620 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9236.33 | 9236.33 | 1.0000 | 0.55820873 | 0.463785 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9236.33 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.3704 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 88220.151 | 88220.151 | 4.423365 | 0.00216051 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 88220.15 | 88220.15 | 1.0000 | 5.32393939 | 4.423365 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 88220.15 | -10.70 | 0.00150390 | -10.70 | 0.15631366 | 3.5338 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8982.653 | 8982.653 | 0.450499 | 0.00021998 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8982.65 | 8982.65 | 1.0000 | 0.54221830 | 0.450499 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8982.65 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.4698 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20748.523 | 20748.523 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.198751 | 25.51470993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20748.52 | 20748.52 | 1.0000 | 25.51470993 | 21.198751 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20748.52 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5962 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.198751 | 25.51470993 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 1319094.64 | 1.0000 | 25.51470993 | 21.198751 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5962 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1029925.897 | 1029925.897 | 21.198751 | 0.02275495 | 19145.092 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.198751 | 25.51470993 | 4197.9300 | 999.8980 | 75.95744481 | 71.00 | 82.00 | 11.00 | 3507504.40 | 23.5436 | 29.954448 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 825792.36 | 1029925.90 | 1.0000 | 25.51470993 | 21.198751 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 22.75263294 | 60.00 | 49.00 | 11.00 | 0.000 | 825792.36 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5962 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | 0.00 | 0.00 | 25.51470993 | 16.60 | 4.06 | 0.00002401 | 16741.1 | 16.60 | 4.06 | 0.00002401 | 16741.1 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.463785 | 0.55820873 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 1.0000 | 0.55820873 | 0.463785 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.50 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.3704 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9584.958 | 9584.958 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.423365 | 5.32393939 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9584.96 | 9584.96 | 1.0000 | 5.32393939 | 4.423365 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9584.96 | -10.70 | 0.00150390 | -10.70 | 0.15631366 | 3.5338 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.450499 | 0.54221830 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 1.0000 | 0.54221830 | 0.450499 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.50 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.4698 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.34 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 9.09 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 25.38 | 84.55 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 2.54 | 8.71 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3041.83 | 1427.67 | 596.17 |
CORE_BOTTOM | 2848.83 | 961.67 | 0.00 |
CORE_MID | 1668.00 | 2826.17 | 55.33 |
CORE_TOP | 2099.00 | 3401.17 | 520.17 |
PERIMETER_BOT_ZN_3 | 2329.67 | 2892.67 | 151.83 |
PERIMETER_BOT_ZN_2 | 1831.50 | 3502.50 | 190.83 |
PERIMETER_BOT_ZN_1 | 2627.17 | 2482.67 | 197.67 |
PERIMETER_BOT_ZN_4 | 2931.50 | 2023.33 | 138.00 |
PERIMETER_MID_ZN_3 | 2814.00 | 3768.17 | 1226.83 |
PERIMETER_MID_ZN_2 | 2043.00 | 3578.50 | 1007.50 |
PERIMETER_MID_ZN_1 | 2732.33 | 3033.50 | 678.50 |
PERIMETER_MID_ZN_4 | 2382.17 | 3938.00 | 931.50 |
PERIMETER_TOP_ZN_3 | 3314.33 | 4010.00 | 1856.50 |
PERIMETER_TOP_ZN_2 | 2993.67 | 4145.33 | 1615.50 |
PERIMETER_TOP_ZN_1 | 3005.50 | 3431.17 | 1222.67 |
PERIMETER_TOP_ZN_4 | 2798.00 | 4154.67 | 1457.50 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5026.50 | 4997.50 | 2503.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 82.50 | 0.00 | 3.00 |
CORE_BOTTOM | 0.00 | 0.33 | 0.00 | 0.00 |
CORE_MID | 2.17 | 0.67 | 1.33 | 0.67 |
CORE_TOP | 4.67 | 0.00 | 0.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 7.17 | 0.00 | 7.17 |
PERIMETER_BOT_ZN_1 | 0.33 | 118.83 | 0.00 | 118.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 49.33 | 0.00 | 19.50 |
PERIMETER_MID_ZN_3 | 35.50 | 0.00 | 9.33 | 0.00 |
PERIMETER_MID_ZN_2 | 21.50 | 7.33 | 2.67 | 7.33 |
PERIMETER_MID_ZN_1 | 20.17 | 154.83 | 4.00 | 154.83 |
PERIMETER_MID_ZN_4 | 18.00 | 9.50 | 2.83 | 7.00 |
PERIMETER_TOP_ZN_3 | 126.83 | 0.00 | 38.33 | 0.00 |
PERIMETER_TOP_ZN_2 | 76.17 | 7.33 | 13.00 | 7.33 |
PERIMETER_TOP_ZN_1 | 72.00 | 56.83 | 12.50 | 56.67 |
PERIMETER_TOP_ZN_4 | 52.00 | 10.83 | 8.50 | 8.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 827.50 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 776.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 699.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 139.83 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 138.83 | 1142.17 | 39.00 | 232.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 1.138 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.861 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.735 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.705 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.820 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 1.291 | 0.058 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 1.099 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 1.744 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.750 | 0.128 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 1.341 | 0.141 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 1.069 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 1.485 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.808 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 1.429 | 0.165 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 1.096 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 1.556 | 0.165 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 28586.84 | 364913.24 | 01-JAN-14:00 | 1916437.77 | 02-AUG-15:10 |
Electricity:Building | 18524.41 | 249962.80 | 01-JAN-08:20 | 1099600.76 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 635.35 | 14476.27 | 01-JAN-06:10 | 31794.69 | 02-JAN-08:10 |
InteriorLights:Electricity | 3311.12 | 15753.54 | 01-JAN-08:20 | 305596.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 210.95 | 1018.73 | 01-JAN-06:10 | 18337.15 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3311.12 | 15753.54 | 01-JAN-08:20 | 305596.68 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 510.73 | 6957.75 | 01-JAN-06:10 | 34596.64 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 189.45 | 914.89 | 01-JAN-06:10 | 16468.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 5107.28 | 69577.31 | 01-JAN-06:10 | 345965.66 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1894.51 | 9148.91 | 01-JAN-06:10 | 164680.46 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 510.73 | 6957.73 | 01-JAN-06:10 | 34596.57 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 189.45 | 914.89 | 01-JAN-06:10 | 16468.05 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 58.97 | 842.63 | 01-JAN-08:20 | 4344.05 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 18.63 | 83.86 | 01-JAN-08:20 | 2067.73 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 38.00 | 543.02 | 01-JAN-07:50 | 2799.47 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 12.00 | 54.04 | 01-JAN-07:50 | 1332.52 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 58.92 | 842.65 | 01-JAN-07:50 | 4344.13 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 18.58 | 83.86 | 01-JAN-07:50 | 2067.77 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 37.97 | 543.02 | 01-JAN-08:20 | 2799.46 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.97 | 54.04 | 01-JAN-08:20 | 1332.52 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 589.75 | 8426.32 | 01-JAN-08:20 | 43440.45 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 186.33 | 838.59 | 01-JAN-08:20 | 20677.28 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 380.03 | 5430.24 | 01-JAN-07:50 | 27994.68 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 120.05 | 540.42 | 01-JAN-07:50 | 13325.22 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 589.22 | 8426.45 | 01-JAN-07:50 | 43441.26 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 185.80 | 838.61 | 01-JAN-07:50 | 20677.73 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 379.72 | 5430.21 | 01-JAN-08:20 | 27994.59 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 119.74 | 540.42 | 01-JAN-08:20 | 13325.22 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 58.97 | 842.63 | 01-JAN-08:20 | 4344.05 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 18.63 | 83.86 | 01-JAN-08:20 | 2067.73 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 38.00 | 543.02 | 01-JAN-07:50 | 2799.47 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 12.01 | 54.04 | 01-JAN-07:50 | 1332.52 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 58.92 | 842.65 | 01-JAN-07:50 | 4344.13 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 18.58 | 83.86 | 01-JAN-07:50 | 2067.77 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 37.97 | 543.02 | 01-JAN-08:20 | 2799.46 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.97 | 54.04 | 01-JAN-08:20 | 1332.52 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7554.34 | 95195.37 | 01-JAN-06:10 | 384802.81 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 59.48 | 287.24 | 01-JAN-06:10 | 5170.29 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.63 | 1961.87 | 01-JAN-06:10 | 8033.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.75 | 13.27 | 01-JAN-06:10 | 238.85 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1566.28 | 19618.75 | 01-JAN-06:10 | 80332.68 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 27.48 | 132.69 | 01-JAN-06:10 | 2388.46 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.63 | 1961.87 | 01-JAN-06:10 | 8033.27 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.75 | 13.27 | 01-JAN-06:10 | 238.85 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 4778.18 | 64049.96 | 22-JAN-22:30 | 347291.53 | 25-AUG-14:10 |
ExteriorEquipment:Electricity | 1987.97 | 13873.41 | 01-JAN-00:10 | 128033.79 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 87.06 | 1613.62 | 01-JAN-00:10 | 5441.84 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 28586.84 | 364913.24 | 01-JAN-14:00 | 1916437.77 | 02-AUG-15:10 |
ElectricityPurchased:Plant | 28586.84 | 364913.24 | 01-JAN-14:00 | 1916437.77 | 02-AUG-15:10 |
Cogeneration:ElectricityPurchased | 28586.84 | 364913.24 | 01-JAN-14:00 | 1916437.77 | 02-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 28586.84 | 364913.24 | 01-JAN-14:00 | 1916437.77 | 02-AUG-15:10 |
ElectricityNet:Plant | 28586.84 | 364913.24 | 01-JAN-14:00 | 1916437.77 | 02-AUG-15:10 |
Cogeneration:ElectricityNet | 28586.84 | 364913.24 | 01-JAN-14:00 | 1916437.77 | 02-AUG-15:10 |
Fans:Electricity | 2125.89 | 41125.70 | 01-JAN-20:00 | 189208.44 | 22-FEB-15:10 |
General:Fans:Electricity | 2125.89 | 41125.70 | 01-JAN-20:00 | 189208.44 | 22-FEB-15:10 |
ExteriorLights:Electricity | 656.92 | 0.00 | 01-JAN-07:30 | 53035.91 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 656.92 | 0.00 | 01-JAN-07:30 | 53035.91 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 56.48 | 0.00 | 01-JAN-00:10 | 5613.05 | 02-JAN-07:10 |
Cooling:Electricity | 3569.64 | 18433.87 | 02-JAN-08:30 | 462566.15 | 02-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 25.52 | 0.00 | 01-JAN-00:10 | 37678.37 | 19-FEB-13:10 |
Electricity:Plant | 2726.42 | 4828.89 | 06-JAN-00:50 | 437537.65 | 02-AUG-15:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 1086.40 | 0.00 | 01-JAN-00:10 | 294802.43 | 02-AUG-15:00 |
HeatRejection:Electricity | 1142.31 | 961.90 | 02-JAN-08:30 | 90029.42 | 18-JUN-10:20 |
General:HeatRejection:Electricity | 199.61 | 0.00 | 01-JAN-00:10 | 40781.15 | 18-JUN-10:20 |
Pumps:Electricity | 497.71 | 3331.02 | 04-JAN-06:00 | 55639.69 | 25-AUG-16:00 |
General:Pumps:Electricity | 497.71 | 3331.02 | 04-JAN-06:00 | 55639.69 | 25-AUG-16:00 |
WIRED_LTG_ELECTRICITY | 93.04 | 0.00 | 01-JAN-00:10 | 8587.27 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1453.48 | 5695.87 | 06-JAN-02:10 | 2424933.81 | 02-JAN-07:10 |
Gas:Plant | 1453.48 | 5695.87 | 06-JAN-02:10 | 2424933.81 | 02-JAN-07:10 |
WaterSystems:Gas | 557.22 | 5695.87 | 02-JAN-06:00 | 82925.36 | 23-FEB-13:00 |
Water Heater:WaterSystems:Gas | 557.22 | 5695.87 | 02-JAN-06:00 | 82925.36 | 23-FEB-13:00 |
Heating:Gas | 896.27 | 0.00 | 01-JAN-00:40 | 2419237.94 | 02-JAN-07:10 |
Boiler:Heating:Gas | 896.27 | 0.00 | 01-JAN-00:40 | 2419237.94 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 19225.02 | 63936.13 | 04-JAN-20:40 | 2458534.44 | 02-AUG-15:00 |
PlantLoopCoolingDemand:HVAC | 19225.02 | 63936.13 | 04-JAN-20:40 | 2458534.44 | 02-AUG-15:00 |
CoolingCoils:PlantLoopCoolingDemand | 19225.02 | 63936.13 | 04-JAN-20:40 | 2458534.44 | 02-AUG-15:00 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7754.88 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:00 |
Water:Plant | 7745.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 7754.88 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:00 |
MainsWater:Plant | 7745.38 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 9.49 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:10 |
Humidifier:Water | 9.49 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:10 |
MainsWater:HVAC | 9.49 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:10 |
Humidifier:MainsWater | 9.49 | 0.00 | 01-JAN-00:10 | 0.00 | 19-FEB-13:10 |
HeatRejection:Water | 5465.21 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:00 |
HeatRejection:MainsWater | 5465.21 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 1070.43 | 0.00 | 01-JAN-00:40 | 2040833.61 | 02-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 412.73 | 0.00 | 01-JAN-00:10 | 52095.45 | 10-FEB-13:00 |
WaterSystems:PlantLoopHeatingDemand | 412.73 | 0.00 | 01-JAN-00:10 | 52095.45 | 10-FEB-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 63433.42 | 134863.70 | 22-JAN-20:30 | 10314407.89 | 02-AUG-15:00 |
EnergyTransfer:Building | 18870.03 | 64103.08 | 22-JAN-21:50 | 1561490.61 | 18-AUG-15:50 |
EnergyTransfer:Zone:BASEMENT | 695.53 | 0.00 | 01-JAN-00:10 | 79968.29 | 10-OCT-05:10 |
Heating:EnergyTransfer | 331.25 | 0.00 | 12-JAN-22:10 | 1147197.72 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 7.39 | 0.00 | 01-JAN-00:10 | 60249.11 | 01-FEB-05:50 |
Cooling:EnergyTransfer | 18538.78 | 60938.56 | 22-JAN-20:30 | 1561490.61 | 18-AUG-15:50 |
Cooling:EnergyTransfer:Zone:BASEMENT | 688.13 | 0.00 | 01-JAN-00:10 | 79968.29 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 647.62 | 0.00 | 01-JAN-00:10 | 54050.69 | 11-JUL-14:20 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 647.62 | 0.00 | 01-JAN-00:10 | 54050.69 | 11-JUL-14:20 |
EnergyTransfer:Zone:CORE_MID | 4607.73 | 0.00 | 01-JAN-00:40 | 492641.50 | 17-MAR-15:50 |
Heating:EnergyTransfer:Zone:CORE_MID | 6.53 | 0.00 | 01-JAN-00:10 | 394676.65 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4601.20 | 0.00 | 01-JAN-00:40 | 492641.50 | 17-MAR-15:50 |
EnergyTransfer:Zone:CORE_TOP | 432.63 | 0.00 | 01-JAN-00:40 | 69225.78 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 6.68 | 0.00 | 01-JAN-00:40 | 69225.78 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 425.96 | 0.00 | 01-JAN-00:20 | 55993.65 | 01-SEP-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 76.73 | 0.00 | 01-JAN-00:10 | 9967.23 | 19-JUN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.07 | 0.00 | 01-JAN-00:10 | 4100.93 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 76.66 | 0.00 | 01-JAN-00:10 | 9967.23 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.71 | 0.00 | 01-JAN-00:10 | 12084.79 | 26-JUN-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.07 | 0.00 | 01-JAN-00:10 | 3200.52 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 71.63 | 0.00 | 01-JAN-00:10 | 12084.79 | 26-JUN-07:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.27 | 0.00 | 01-JAN-00:10 | 15147.96 | 04-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.26 | 0.00 | 01-JAN-00:10 | 8111.98 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 101.00 | 0.00 | 01-JAN-00:10 | 15147.96 | 04-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.21 | 0.00 | 01-JAN-00:10 | 16722.35 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 1995.38 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 105.20 | 0.00 | 01-JAN-00:10 | 16722.35 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 575.64 | 0.00 | 01-JAN-00:40 | 115223.54 | 06-FEB-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 59.57 | 0.00 | 01-JAN-00:40 | 115223.54 | 06-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 516.07 | 0.00 | 01-JAN-00:10 | 93218.81 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 598.71 | 0.00 | 01-JAN-00:40 | 128990.50 | 14-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 34.80 | 0.00 | 01-JAN-00:40 | 120571.94 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 563.91 | 0.00 | 01-JAN-00:10 | 128990.50 | 14-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 842.45 | 0.00 | 01-JAN-00:40 | 149734.68 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 34.14 | 0.00 | 01-JAN-00:40 | 122200.16 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 808.31 | 0.00 | 01-JAN-00:10 | 149734.68 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 643.01 | 0.00 | 01-JAN-00:40 | 143715.34 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 26.82 | 0.00 | 01-JAN-00:40 | 114495.81 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 616.19 | 0.00 | 01-JAN-00:10 | 143715.34 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 68.21 | 0.00 | 01-JAN-00:40 | 13804.53 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 17.79 | 0.00 | 01-JAN-00:40 | 13804.53 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 50.42 | 0.00 | 01-JAN-00:10 | 10777.82 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 63.55 | 0.00 | 01-JAN-00:40 | 14423.22 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 10.05 | 0.00 | 01-JAN-00:40 | 14423.22 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 53.50 | 0.00 | 01-JAN-00:10 | 13134.55 | 14-JUL-08:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 88.82 | 0.00 | 01-JAN-00:40 | 16219.85 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 11.48 | 0.00 | 01-JAN-00:40 | 15572.31 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 77.34 | 0.00 | 01-JAN-00:10 | 16219.85 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 67.28 | 0.00 | 01-JAN-00:40 | 15009.55 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 7.74 | 0.00 | 01-JAN-00:40 | 14777.08 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 59.54 | 0.00 | 01-JAN-00:10 | 15009.55 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 63.68 | 0.00 | 01-JAN-00:10 | 7940.26 | 30-MAY-13:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.36 | 0.00 | 01-JAN-00:10 | 3731.11 | 18-JAN-06:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 62.32 | 0.00 | 01-JAN-00:10 | 7940.26 | 30-MAY-13:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 462.64 | 0.00 | 01-JAN-00:40 | 151531.12 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 70.91 | 0.00 | 01-JAN-00:40 | 151531.12 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 391.73 | 0.00 | 01-JAN-00:10 | 62042.09 | 25-AUG-14:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 89.21 | 0.00 | 01-JAN-00:40 | 25603.85 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.41 | 0.00 | 01-JAN-00:40 | 25603.85 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.80 | 0.00 | 01-JAN-00:10 | 18729.76 | 19-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.90 | 436.59 | 01-JAN-00:40 | 7562.13 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.90 | 436.59 | 01-JAN-00:40 | 7562.13 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1166.34 | 0.03 | 03-JAN-12:10 | 71733.76 | 12-APR-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.53 | 0.00 | 03-JAN-12:30 | 5252.96 | 02-JAN-23:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1162.80 | 0.00 | 01-JAN-00:10 | 71733.76 | 12-APR-17:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.45 | 0.64 | 28-JAN-16:40 | 7269.80 | 12-APR-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.85 | 0.00 | 03-JAN-11:50 | 558.00 | 16-JAN-17:50 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.60 | 0.00 | 01-JAN-00:10 | 7269.80 | 12-APR-17:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.73 | 56586.89 | 28-JAN-13:20 | 377077.88 | 09-DEC-16:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.79 | 0.00 | 01-JAN-00:10 | 10948.69 | 06-JAN-22:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7157.94 | 56586.89 | 28-JAN-13:20 | 377077.88 | 09-DEC-16:40 |
EnergyTransfer:Plant | 24036.67 | 0.00 | 01-JAN-00:40 | 6046549.94 | 26-JUL-16:00 |
WaterSystems:EnergyTransfer | 412.73 | 0.00 | 01-JAN-00:10 | 52095.45 | 10-FEB-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 412.73 | 0.00 | 01-JAN-00:10 | 52095.45 | 10-FEB-13:00 |
EnergyTransfer:HVAC | 20526.72 | 61667.28 | 22-JAN-20:30 | 2973618.71 | 02-AUG-15:00 |
HeatingCoils:EnergyTransfer | 657.70 | 0.00 | 01-JAN-00:40 | 2023615.10 | 02-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 657.70 | 0.00 | 01-JAN-00:40 | 2023615.10 | 02-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 657.70 | 0.00 | 01-JAN-00:40 | 2023615.10 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 16869.21 | 52063.01 | 04-JAN-20:40 | 2290770.72 | 02-AUG-15:00 |
HeatRecoveryForHeating:EnergyTransfer | 2154.94 | 0.00 | 01-JAN-00:10 | 896548.82 | 06-FEB-07:20 |
HeatRecoveryForCooling:EnergyTransfer | 844.87 | 0.00 | 01-JAN-00:10 | 734631.24 | 08-JUL-12:00 |
LoopToLoop:EnergyTransfer | 7952.09 | -3981.31 | 13-JAN-14:50 | 1907984.94 | 26-JUL-16:00 |
Boilers:EnergyTransfer | 645.57 | 0.00 | 01-JAN-00:40 | 1980696.16 | 02-JAN-07:10 |
Chillers:EnergyTransfer | 6969.94 | 0.00 | 01-JAN-00:10 | 1910195.22 | 26-JUL-16:00 |
HeatRejection:EnergyTransfer | 8056.34 | 0.00 | 01-JAN-00:10 | 2198474.46 | 26-JUL-16:00 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 7.394 | -688.134 | 0.000 | 0.000 | 92.735 | 210.953 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.345 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -647.616 | 0.000 | 0.000 | 83.458 | 189.451 | 321.278 | 0.000 | 0.000 | 0.000 | 53.429 | 0.000 | 0.000 | 0.000 | 0.000 | -0.002 |
CORE_MID | 0.000 | 0.000 | 6.532 | -4601.179 | 0.000 | 0.000 | 846.466 | 1894.509 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1359.100 |
CORE_TOP | 0.000 | 0.000 | 6.677 | -425.955 | 0.000 | 0.000 | 87.232 | 189.451 | 321.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -178.681 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.073 | -76.657 | 0.000 | 0.000 | 10.742 | 18.625 | 40.341 | 21.513 | 0.000 | 0.133 | 42.447 | 0.000 | -48.158 | 0.000 | -9.059 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.075 | -71.631 | 0.000 | 0.000 | 7.081 | 12.003 | 25.998 | 41.490 | 0.000 | 0.114 | 19.302 | 0.000 | -28.651 | 0.000 | -5.780 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.262 | -101.003 | 0.000 | 0.000 | 10.679 | 18.576 | 40.342 | 80.082 | 0.000 | 0.130 | 2.836 | 0.000 | -42.905 | 0.000 | -8.999 | -0.001 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.007 | -105.202 | 0.000 | 0.000 | 6.903 | 11.973 | 25.997 | 41.517 | 0.000 | 0.083 | 58.350 | 0.000 | -33.194 | 0.000 | -6.434 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 59.569 | -516.063 | 0.000 | 0.000 | 112.697 | 186.331 | 403.414 | 223.297 | 0.000 | 2.819 | 133.438 | 0.000 | -426.930 | 0.000 | -178.573 | -0.003 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 34.802 | -563.903 | 0.000 | 0.000 | 54.107 | 120.052 | 259.975 | 418.349 | 0.000 | 2.103 | 56.717 | 0.000 | -263.328 | 0.000 | -118.874 | -0.001 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 34.139 | -808.301 | 0.000 | 0.000 | 108.746 | 185.805 | 403.420 | 802.715 | 0.000 | 2.641 | 0.001 | 0.000 | -409.161 | 0.000 | -189.427 | -130.576 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 26.817 | -616.183 | 0.000 | 0.000 | 73.796 | 119.745 | 259.973 | 428.253 | 0.000 | 1.942 | 110.619 | 0.000 | -281.806 | 0.000 | -123.157 | -0.017 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 17.792 | -50.418 | 0.000 | 0.000 | 11.474 | 18.633 | 40.341 | 22.615 | 0.000 | 0.327 | 0.000 | 0.000 | -39.931 | 0.000 | -20.769 | -0.064 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 10.048 | -53.498 | 0.000 | 0.000 | 7.412 | 12.005 | 25.998 | 42.046 | 0.000 | 0.240 | 0.000 | 0.000 | -24.875 | 0.000 | -13.922 | -5.454 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 11.478 | -77.339 | 0.000 | 0.000 | 11.115 | 18.580 | 40.342 | 80.843 | 0.000 | 0.313 | 0.000 | 0.000 | -38.326 | 0.000 | -21.944 | -25.063 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 7.738 | -59.543 | 0.000 | 0.000 | 7.481 | 11.974 | 25.997 | 42.984 | 0.000 | 0.237 | 4.336 | 0.000 | -26.728 | 0.000 | -14.476 | -0.000 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -134.899 | 0.000 | 0.000 | 0.000 | 2.748 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.729 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 3.535 | -1162.803 | 0.000 | 0.000 | 0.000 | 27.477 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -407.015 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.848 | -107.598 | 0.000 | 0.000 | 0.000 | 2.748 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.878 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.788 | -7157.941 | 0.000 | 0.000 | 0.000 | 59.480 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -397.183 |
GROUNDFLOOR_PLENUM | 1.357 | -62.322 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.206 | 79.365 | 0.000 | 0.000 | 0.000 | -18.606 | 0.000 |
MIDFLOOR_PLENUM | 70.913 | -391.721 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.854 | 627.264 | 0.000 | 0.000 | 0.000 | -310.310 | -0.000 |
TOPFLOOR_PLENUM | 30.412 | -58.798 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.291 | 60.669 | 0.000 | 0.000 | 0.000 | -32.574 | -0.001 |
Total Facility | 102.682 | -512.841 | 228.572 | -18025.869 | 0.000 | 0.000 | 1532.126 | 3311.119 | 15213.288 | 2245.703 | 0.000 | 15.431 | 1248.774 | 0.000 | -1663.992 | 0.000 | -1072.904 | -2622.114 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-DEC-14:30 | 0.00 | 0.00 | 0.00 | -115225.43 | 0.00 | 0.00 | 400.46 | 1018.73 | 13457.54 | 0.00 | 0.00 | 0.00 | 100348.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 06-SEP-03:02 | 0.00 | 0.00 | 0.00 | -94775.74 | 0.00 | 0.00 | 0.00 | 991.43 | 8057.15 | 0.00 | 0.00 | 0.00 | 85727.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 07-AUG-03:02 | 0.00 | 0.00 | 0.00 | -855636.01 | 0.00 | 0.00 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 765150.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 20-JUN-03:02 | 0.00 | 0.00 | 0.00 | -89802.70 | 0.00 | 0.00 | 0.00 | 991.43 | 8057.12 | 0.00 | 0.00 | 0.00 | 80754.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 10-JUL-03:01 | 0.00 | 0.00 | 0.00 | -12918.05 | 0.00 | 0.00 | 0.00 | 124.48 | 1011.70 | 0.00 | 0.00 | 10.84 | 11942.69 | 0.00 | -171.66 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 02-JUL-08:12 | 0.00 | 0.00 | 0.00 | -18703.64 | 0.00 | 0.00 | 22.95 | 54.04 | 488.98 | 15467.34 | 0.00 | 0.00 | 2713.65 | 0.00 | -0.00 | 0.00 | -43.33 | 0.00 |
PERIMETER_BOT_ZN_1 | 22-OCT-12:22 | 0.00 | 0.00 | 0.00 | -18243.31 | 0.00 | 0.00 | 37.89 | 83.86 | 758.78 | 20022.78 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -84.09 | -2575.91 |
PERIMETER_BOT_ZN_4 | 04-JUL-16:11 | 0.00 | 0.00 | 0.00 | -24535.58 | 0.00 | 0.00 | 19.97 | 54.04 | 488.98 | 13019.51 | 0.00 | 0.00 | 11032.32 | 0.00 | -0.00 | 0.00 | -79.24 | 0.00 |
PERIMETER_MID_ZN_3 | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 | -139164.30 | 0.00 | 0.00 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 345.92 | 129213.10 | 0.00 | -1756.53 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:32 | 0.00 | 0.00 | 0.00 | -201598.97 | 0.00 | 0.00 | 218.50 | 540.42 | 4889.82 | 146849.68 | 0.00 | 0.00 | 50263.83 | 0.00 | -0.00 | 0.00 | -1163.28 | 0.00 |
PERIMETER_MID_ZN_1 | 21-DEC-17:35 | 0.00 | 0.00 | 0.00 | -178672.65 | 0.00 | 0.00 | 3535.61 | 11487.63 | 12646.40 | 0.00 | 0.00 | 0.00 | 192016.53 | 0.00 | -39268.09 | 0.00 | -1745.44 | 0.00 |
PERIMETER_MID_ZN_4 | 18-JUN-16:11 | 0.00 | 0.00 | 0.00 | -211288.93 | 0.00 | 0.00 | 211.27 | 540.42 | 4889.79 | 141676.22 | 0.00 | 0.00 | 66440.84 | 0.00 | -0.00 | 0.00 | -2469.60 | 0.00 |
PERIMETER_TOP_ZN_3 | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 | -14671.55 | 0.00 | 0.00 | 0.00 | 124.48 | 1011.70 | 0.00 | 0.00 | 7.15 | 13767.00 | 0.00 | -238.78 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 29-MAY-08:52 | 0.00 | 0.00 | 0.00 | -20241.14 | 0.00 | 0.00 | 22.25 | 54.04 | 488.98 | 13044.23 | 0.00 | 0.00 | 6758.83 | 0.00 | -0.00 | 0.00 | -127.19 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:02 | 0.00 | 0.00 | 0.00 | -19494.26 | 0.00 | 0.00 | 36.31 | 83.86 | 758.78 | 17246.40 | 0.00 | 0.00 | 1544.90 | 0.00 | -0.00 | 0.00 | -175.99 | 0.00 |
PERIMETER_TOP_ZN_4 | 18-JUN-16:11 | 0.00 | 0.00 | 0.00 | -22802.05 | 0.00 | 0.00 | 20.28 | 54.04 | 488.98 | 14093.64 | 0.00 | 0.00 | 8476.22 | 0.00 | -0.00 | 0.00 | -331.11 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:43 | 0.00 | 0.00 | 0.00 | -7573.94 | 0.00 | 0.00 | 0.00 | 14.38 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -234.86 |
DATACENTER_MID_ZN_6 | 12-APR-17:20 | 0.00 | 0.00 | 0.00 | -71733.76 | 0.00 | 0.00 | 0.00 | 796.15 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7006.62 |
DATACENTER_TOP_ZN_6 | 12-APR-17:20 | 0.00 | 0.00 | 0.00 | -7269.80 | 0.00 | 0.00 | 0.00 | 79.62 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -604.24 |
DATACENTER_BASEMENT_ZN_6 | 04-MAR-16:52 | 0.00 | 0.00 | 0.00 | -413507.28 | 0.00 | 0.00 | 0.00 | 861.72 | 284724.39 | 0.00 | 0.00 | 0.00 | 127921.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 30-MAY-05:13 | 0.00 | -10511.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10562.78 | 0.00 | -0.00 | 0.00 | -51.68 | 0.00 |
MIDFLOOR_PLENUM | 21-JUL-05:01 | 0.00 | -90290.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90473.71 | 0.00 | -0.00 | 0.00 | -183.08 | 0.00 |
TOPFLOOR_PLENUM | 01-SEP-14:30 | 0.00 | -18802.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.43 | 18617.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 18-AUG-03:01 | 0.00 | 79556.14 | 0.00 | -1950128.45 | 0.00 | 0.00 | 0.00 | 18397.91 | 623236.89 | 0.00 | 0.00 | 84.90 | 1250004.14 | 0.00 | -18389.44 | 0.00 | -2762.09 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 07-FEB-05:53 | 0.00 | 0.00 | 136209.04 | 0.00 | 0.00 | 0.00 | 0.00 | 2207.91 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -151874.49 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 454460.37 | -0.00 | 0.00 | 0.00 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -544945.87 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 79041.06 | -0.00 | 0.00 | 0.00 | 0.00 | 991.43 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -88089.61 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 9511.31 | -0.00 | 0.00 | 0.00 | 0.00 | 248.97 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5613.72 | 0.00 | -2193.03 | -2965.22 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 7479.01 | -0.00 | 0.00 | 0.00 | 0.00 | 160.44 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3605.77 | 0.00 | -1440.49 | -3245.18 |
PERIMETER_BOT_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 12225.59 | -0.00 | 0.00 | 0.00 | 0.00 | 248.97 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5224.32 | 0.00 | -2120.09 | -6141.86 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:01 | 0.00 | 0.00 | 5150.37 | -0.00 | 0.00 | 0.00 | 94.15 | 148.06 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3571.62 | 0.00 | -151.70 | -2321.24 |
PERIMETER_MID_ZN_3 | 02-JAN-01:22 | 0.00 | 0.00 | 127524.95 | -0.00 | 0.00 | 0.00 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43825.94 | 0.00 | -31555.38 | -63505.44 |
PERIMETER_MID_ZN_2 | 02-JAN-01:22 | 0.00 | 0.00 | 155531.13 | -0.00 | 0.00 | 0.00 | 0.00 | 802.22 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28408.72 | 0.00 | -21473.32 | -112971.07 |
PERIMETER_MID_ZN_1 | 02-JAN-01:22 | 0.00 | 0.00 | 144898.54 | -0.00 | 0.00 | 0.00 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43005.85 | 0.00 | -31939.38 | -81315.30 |
PERIMETER_MID_ZN_4 | 02-JAN-01:22 | 0.00 | 0.00 | 152757.09 | -0.00 | 0.00 | 0.00 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29593.72 | 0.00 | -21640.05 | -108845.25 |
PERIMETER_TOP_ZN_3 | 06-FEB-04:11 | 0.00 | 0.00 | 14680.38 | -0.00 | 0.00 | 0.00 | 0.00 | 124.48 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4648.12 | 0.00 | -4661.75 | -6506.69 |
PERIMETER_TOP_ZN_2 | 06-FEB-04:11 | 0.00 | 0.00 | 17498.03 | -0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3008.15 | 0.00 | -3151.71 | -12070.38 |
PERIMETER_TOP_ZN_1 | 06-FEB-04:11 | 0.00 | 0.00 | 16801.79 | -0.00 | 0.00 | 0.00 | 0.00 | 124.49 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4558.58 | 0.00 | -4718.30 | -8661.11 |
PERIMETER_TOP_ZN_4 | 06-FEB-04:11 | 0.00 | 0.00 | 18452.12 | -0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3170.33 | 0.00 | -3210.63 | -12803.35 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 07-JAN-19:32 | 0.00 | 0.00 | 5297.48 | 0.00 | 0.00 | 0.00 | 0.00 | 143.79 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24927.32 |
DATACENTER_TOP_ZN_6 | 16-JAN-17:50 | 0.00 | 0.00 | 558.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.27 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2519.87 |
DATACENTER_BASEMENT_ZN_6 | 14-JAN-17:41 | 0.00 | 0.00 | 58404.39 | 0.00 | 0.00 | 0.00 | 0.00 | 287.24 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -153599.76 |
GROUNDFLOOR_PLENUM | 26-DEC-04:01 | 12875.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -918.65 | -11956.50 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 155665.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6547.19 | -149118.58 |
TOPFLOOR_PLENUM | 06-FEB-05:10 | 27317.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7857.77 | -19460.19 |
Total Facility | 02-JAN-04:01 | -155566.39 | 193316.05 | 1161016.57 | -193316.05 | 0.00 | 0.00 | 0.00 | 18397.91 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -177404.63 | 0.00 | -78157.90 | -1036648.26 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.3352 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.3352 | 0.2249 | 1.0000 | 1.2001 | 0.2249 | ||
VAV_BOT WITH REHEAT | 9.7241 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 9.0865 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 91.4679 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 84.5462 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.5474 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.7141 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.1988 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.1988 | 0.0160 | 1.0000 | 0.3384 | 0.0160 | ||
AIRLOOP DATACENTER BOT | 0.4638 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4638 | 0.0337 | 1.0000 | 0.0156 | 0.0337 | ||
AIRLOOP DATACENTER MID | 4.4234 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4234 | 0.0353 | 1.0000 | 0.1563 | 0.0353 | ||
AIRLOOP DATACENTER TOP | 0.4505 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4505 | 0.0347 | 1.0000 | 0.0156 | 0.0347 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.3352 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.3352 | 1.0000 | 1.0000 | 1.2001 | 0.2249 | ||
VAV_BOT WITH REHEAT | 4.8621 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.1360 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 45.7339 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 30.2334 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.7737 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 3.1225 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.1988 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.1988 | 1.0000 | 1.0000 | 0.3384 | 0.0160 | ||
AIRLOOP DATACENTER BOT | 0.4638 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4638 | 1.0000 | 1.0000 | 0.0156 | 0.0337 | ||
AIRLOOP DATACENTER MID | 4.4234 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.4234 | 1.0000 | 1.0000 | 0.1563 | 0.0353 | ||
AIRLOOP DATACENTER TOP | 0.4505 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4505 | 1.0000 | 1.0000 | 0.0156 | 0.0347 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.3352 | 5.3352 | 5.3352 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6094 | 5.6094 | 1.9016 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.6984 | 52.6984 | 18.6025 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3808 | 5.3808 | 1.8725 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8602 | 0.8602 | 0.2581 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0156 | 1.0156 | 0.3047 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9844 | 0.9844 | 0.2953 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2545 | 1.2545 | 0.3763 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.0340 | 8.0340 | 2.4102 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.6119 | 10.6119 | 3.1836 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.2445 | 9.2445 | 2.7733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.8791 | 10.8791 | 3.2637 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8927 | 0.8927 | 0.2678 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0785 | 1.0785 | 0.3236 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0327 | 1.0327 | 0.3098 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1627 | 1.1627 | 0.3488 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4638 | 0.4638 | 0.4638 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4234 | 4.4234 | 4.4234 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4505 | 0.4505 | 0.4505 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.1988 | 21.1988 | 21.1988 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.3352 | 5.3352 | 5.3352 | 5.3352 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 9.7241 | 9.0865 | 9.7241 | 3.1360 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 91.4679 | 84.5462 | 91.4679 | 30.2334 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.5474 | 8.7141 | 9.5474 | 3.1225 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.1988 | 21.1988 | 21.1988 | 21.1988 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4638 | 0.4638 | 0.4638 | 0.4638 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4234 | 4.4234 | 4.4234 | 4.4234 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4505 | 0.4505 | 0.4505 | 0.4505 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.3352 | 5.3352 | 5.3352 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8047 | 2.8047 | 1.9016 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.3492 | 26.3492 | 18.6025 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6904 | 2.6904 | 1.8725 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4301 | 0.4301 | 0.2581 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5078 | 0.5078 | 0.3047 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4922 | 0.4922 | 0.2953 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6272 | 0.6272 | 0.3763 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.0170 | 4.0170 | 2.4102 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3060 | 5.3060 | 3.1836 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.6222 | 4.6222 | 2.7733 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4395 | 5.4395 | 3.2637 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4463 | 0.4463 | 0.2678 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5393 | 0.5393 | 0.3236 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5164 | 0.5164 | 0.3098 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5814 | 0.5814 | 0.3488 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4638 | 0.4638 | 0.4638 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.4234 | 4.4234 | 4.4234 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4505 | 0.4505 | 0.4505 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.1988 | 21.1988 | 21.1988 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.3352 | 5.3352 | 5.3352 | 5.3352 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 4.8621 | 3.1360 | 3.1360 | 3.1360 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 45.7339 | 30.2334 | 30.2334 | 30.2334 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.7737 | 3.1225 | 3.1225 | 3.1225 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.1988 | 21.1988 | 21.1988 | 21.1988 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4638 | 0.4638 | 0.4638 | 0.4638 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.4234 | 4.4234 | 4.4234 | 4.4234 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4505 | 0.4505 | 0.4505 | 0.4505 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 20:05:19
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 39.00 |
Number of hours cooling loads not met | 232.00 |
Number of hours not met | 271.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 896.27 | 2419237.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 1086.40 | 294802.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2483.23 | 167763.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3311.12 | 305596.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 656.92 | 53035.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 87.06 | 5441.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2125.89 | 189208.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 497.71 | 55639.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 199.61 | 40781.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 942.69 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 25.52 | 37678.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 56.48 | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 557.22 | 82925.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 28586.84 |
Natural Gas | 0.00 | 1453.48 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 30040.32 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 71.48 |
Space Heating | 0.00 |
Space Cooling | 77.06 |
Fans (All) | 45.90 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 617.15 |
Subtotal | 617.15 |
Natural Gas [MJ/m2] | |
Space Heating | 19.35 |
Service Water Heating | 12.03 |
Miscellaneous (All) | 31.38 |
Subtotal | 31.38 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 11.02 |
Space Heating | 2.98 |
Space Cooling | 11.88 |
Fans (All) | 7.08 |
Service Water Heating | 1.85 |
Receptacle Equipment | 50.64 |
Miscellaneous | 14.54 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2724. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 2347. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2015
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.288266E+12 |
February | 0.000 | 0.210294E+12 |
March | 0.000 | 0.888464E+11 |
April | 0.000 | 0.276697E+11 |
May | 0.000 | 0.228148E+10 |
June | 0.000 | 0.181024E+10 |
July | 0.000 | 0.983974E+09 |
August | 0.000 | 0.259374E+10 |
September | 0.000 | 0.217914E+10 |
October | 0.000 | 0.890723E+10 |
November | 0.000 | 0.866764E+11 |
December | 0.000 | 0.175759E+12 |
Annual Sum or Average | 0.896267E+12 | |
Minimum of Months | 0.000 | 0.983974E+09 |
Maximum of Months | 0.000 | 0.288266E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.479414E+11 | 108607.89 | 26-JAN-05:50 | -1.1 | -3.2 | 0.564931E+10 | 7499.17 | 03-JAN-10:00 | 12.00 | 11.46 |
February | 0.450276E+11 | 112381.52 | 21-FEB-03:52 | 1.70 | 0.96 | 0.512325E+10 | 7499.22 | 15-FEB-14:20 | 1.70 | 0.73 |
March | 0.564826E+11 | 109948.62 | 28-MAR-03:50 | 10.00 | 7.81 | 0.613069E+10 | 7499.21 | 23-MAR-13:00 | 5.00 | 1.06 |
April | 0.539127E+11 | 110876.41 | 11-APR-03:50 | 6.20 | 1.59 | 0.544783E+10 | 7499.18 | 13-APR-13:39 | 7.23 | 5.04 |
May | 0.561011E+11 | 114938.87 | 01-MAY-02:41 | 7.77 | 5.31 | 0.589950E+10 | 7499.53 | 25-MAY-09:20 | 16.87 | 13.21 |
June | 0.593129E+11 | 105776.45 | 03-JUN-03:53 | 13.30 | 9.02 | 0.588159E+10 | 7499.20 | 23-JUN-09:00 | 30.00 | 18.37 |
July | 0.599143E+11 | 96356.98 | 11-JUL-03:01 | 20.50 | 15.25 | 0.547331E+10 | 7499.17 | 12-JUL-09:09 | 27.30 | 18.59 |
August | 0.672280E+11 | 99920.61 | 20-AUG-23:08 | 21.60 | 19.09 | 0.613810E+10 | 7499.15 | 30-AUG-13:39 | 28.33 | 15.51 |
September | 0.608926E+11 | 110643.64 | 11-SEP-02:32 | 13.17 | 9.14 | 0.545265E+10 | 7499.25 | 19-SEP-09:20 | 18.87 | 14.30 |
October | 0.644744E+11 | 114047.69 | 09-OCT-10:50 | 12.62 | 7.05 | 0.567222E+10 | 7499.50 | 16-OCT-09:20 | 17.07 | 14.17 |
November | 0.601996E+11 | 114900.47 | 12-NOV-15:10 | 11.10 | 8.01 | 0.561455E+10 | 7499.12 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.566442E+11 | 115229.61 | 25-DEC-14:30 | 10.00 | 8.54 | 0.546924E+10 | 7499.15 | 12-DEC-10:09 | 2.88 | 2.37 |
Annual Sum or Average | 0.688132E+12 | 0.679522E+11 | ||||||||
Minimum of Months | 0.450276E+11 | 96356.98 | -1.1 | -3.2 | 0.512325E+10 | 7499.12 | 1.70 | 0.73 | ||
Maximum of Months | 0.672280E+11 | 115229.61 | 21.60 | 19.09 | 0.613810E+10 | 7499.53 | 30.00 | 18.59 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359732E+11 | 63497.33 | 25-JAN-06:02 | 3.30 | 0.41 | 0.504913E+10 | 6836.36 | 31-JAN-10:50 | -5.8 | -8.7 |
February | 0.360687E+11 | 67514.34 | 21-FEB-04:02 | 1.78 | 1.01 | 0.459753E+10 | 6884.67 | 03-FEB-10:09 | -4.6 | -7.1 |
March | 0.513455E+11 | 71488.59 | 27-MAR-03:02 | 8.22 | 7.71 | 0.550181E+10 | 6859.68 | 17-MAR-13:39 | -0.8 | -1.6 |
April | 0.552144E+11 | 81199.60 | 28-APR-03:02 | 16.32 | 14.18 | 0.488252E+10 | 6734.82 | 05-APR-09:09 | 11.28 | 8.50 |
May | 0.540149E+11 | 88765.11 | 30-MAY-03:03 | 18.22 | 15.07 | 0.528174E+10 | 6735.05 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.620029E+11 | 87365.56 | 28-JUN-03:02 | 18.98 | 18.21 | 0.526618E+10 | 6734.83 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.691860E+11 | 83576.70 | 19-JUL-03:01 | 21.70 | 20.88 | 0.488887E+10 | 6734.46 | 05-JUL-09:09 | 24.08 | 21.68 |
August | 0.773141E+11 | 80563.46 | 07-AUG-05:02 | 19.40 | 16.74 | 0.549019E+10 | 6734.79 | 30-AUG-13:39 | 28.33 | 15.51 |
September | 0.547419E+11 | 94782.99 | 06-SEP-03:02 | 21.60 | 19.31 | 0.487750E+10 | 6734.95 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.553417E+11 | 87721.69 | 06-OCT-03:02 | 19.40 | 17.99 | 0.507808E+10 | 6735.13 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.487027E+11 | 73265.07 | 13-NOV-04:02 | 5.60 | 4.34 | 0.503469E+10 | 6777.92 | 22-NOV-10:20 | 0.20 | -2.3 |
December | 0.477111E+11 | 71543.52 | 26-DEC-04:02 | 5.60 | 4.99 | 0.490245E+10 | 6808.06 | 22-DEC-10:39 | -1.5 | -4.2 |
Annual Sum or Average | 0.647617E+12 | 0.608507E+11 | ||||||||
Minimum of Months | 0.359732E+11 | 63497.33 | 1.78 | 0.41 | 0.459753E+10 | 6734.46 | -5.8 | -8.7 | ||
Maximum of Months | 0.773141E+11 | 94782.99 | 21.70 | 20.88 | 0.550181E+10 | 6884.67 | 29.15 | 21.68 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.238099E+11 | 53271.01 | 30-JAN-11:40 | 0.73 | -2.3 | 0.464802E+10 | 6774.57 | 27-JAN-14:30 | 5.30 | 2.34 |
February | 0.242960E+11 | 54344.17 | 22-FEB-10:10 | 0.87 | -2.8 | 0.435192E+10 | 6870.84 | 22-FEB-10:20 | 1.13 | -2.6 |
March | 0.331942E+11 | 58312.66 | 29-MAR-05:02 | 2.12 | 0.18 | 0.541257E+10 | 6906.90 | 17-MAR-14:50 | -0.6 | -1.5 |
April | 0.350444E+11 | 65263.45 | 28-APR-04:02 | 14.22 | 11.80 | 0.483248E+10 | 6745.57 | 04-APR-09:39 | 10.20 | 5.19 |
May | 0.442762E+11 | 79046.43 | 30-MAY-04:02 | 17.80 | 14.10 | 0.525278E+10 | 6734.98 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.493599E+11 | 79708.49 | 17-JUN-04:02 | 20.00 | 19.21 | 0.524361E+10 | 6734.71 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.507314E+11 | 80158.55 | 26-JUL-03:01 | 21.70 | 20.81 | 0.486726E+10 | 6734.46 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.549339E+11 | 85568.68 | 07-AUG-03:02 | 18.80 | 17.42 | 0.547657E+10 | 6734.74 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.452027E+11 | 78061.04 | 02-SEP-05:02 | 22.12 | 16.29 | 0.484969E+10 | 6734.92 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.411835E+11 | 74895.83 | 06-OCT-05:02 | 19.40 | 18.22 | 0.504333E+10 | 6735.03 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.304530E+11 | 65819.27 | 10-NOV-06:02 | 14.60 | 14.60 | 0.493496E+10 | 6792.75 | 24-NOV-14:39 | 2.03 | -1.4 |
December | 0.276345E+11 | 78025.75 | 21-DEC-17:35 | 1.70 | -2.4 | 0.474862E+10 | 7190.24 | 22-DEC-14:09 | 1.20 | -2.4 |
Annual Sum or Average | 0.460120E+12 | 0.596618E+11 | ||||||||
Minimum of Months | 0.238099E+11 | 53271.01 | 0.73 | -2.8 | 0.435192E+10 | 6734.46 | -0.6 | -2.6 | ||
Maximum of Months | 0.549339E+11 | 85568.68 | 22.12 | 20.81 | 0.547657E+10 | 7190.24 | 26.20 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.189648E+11 | 21217.01 | 20-JAN-17:00 | 5.60 | 3.18 | 0.421052E+10 | 6659.05 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.182577E+11 | 22100.29 | 24-FEB-17:00 | 6.70 | 1.40 | 0.386583E+10 | 6705.55 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.267181E+11 | 34323.76 | 03-MAR-17:00 | 14.00 | 7.83 | 0.503541E+10 | 6734.69 | 30-MAR-13:20 | 6.70 | 4.49 |
April | 0.306935E+11 | 65216.77 | 08-APR-05:02 | 14.32 | 11.96 | 0.468256E+10 | 6736.81 | 13-APR-13:39 | 7.23 | 5.04 |
May | 0.425376E+11 | 76079.95 | 30-MAY-03:02 | 18.22 | 15.07 | 0.520692E+10 | 6734.96 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.520097E+11 | 89808.34 | 20-JUN-03:02 | 22.02 | 19.38 | 0.524102E+10 | 6734.81 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.553397E+11 | 89221.49 | 24-JUL-03:03 | 22.02 | 21.19 | 0.487471E+10 | 6734.44 | 05-JUL-09:09 | 24.08 | 21.68 |
August | 0.586888E+11 | 89163.94 | 18-AUG-03:02 | 25.50 | 18.50 | 0.547711E+10 | 6734.82 | 30-AUG-13:39 | 28.33 | 15.51 |
September | 0.440936E+11 | 80765.02 | 06-SEP-05:02 | 21.52 | 18.83 | 0.482300E+10 | 6734.88 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.353007E+11 | 74950.83 | 06-OCT-05:02 | 19.40 | 18.22 | 0.493202E+10 | 6734.73 | 31-OCT-13:00 | 12.80 | 10.34 |
November | 0.231497E+11 | 33787.35 | 03-NOV-16:00 | 15.00 | 10.24 | 0.453806E+10 | 6734.74 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.202043E+11 | 20148.17 | 21-DEC-16:20 | 2.43 | -2.1 | 0.418944E+10 | 6662.61 | 20-DEC-14:00 | 8.30 | 4.99 |
Annual Sum or Average | 0.425958E+12 | 0.570766E+11 | ||||||||
Minimum of Months | 0.182577E+11 | 20148.17 | 2.43 | -2.1 | 0.386583E+10 | 6659.05 | 6.70 | 2.25 | ||
Maximum of Months | 0.586888E+11 | 89808.34 | 25.50 | 21.19 | 0.547711E+10 | 6736.81 | 29.15 | 21.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.265046E+10 | 2911.58 | 17-JAN-09:55 | 6.10 | 3.87 | 0.551751E+09 | 830.45 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.256696E+10 | 3277.05 | 22-FEB-10:10 | 0.87 | -2.8 | 0.506834E+09 | 845.59 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.430798E+10 | 6245.23 | 27-MAR-13:30 | 20.85 | 16.75 | 0.663596E+09 | 845.63 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.580967E+10 | 8529.47 | 10-APR-05:03 | 15.10 | 13.73 | 0.603646E+09 | 845.63 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.705571E+10 | 11263.46 | 30-MAY-03:02 | 18.22 | 15.07 | 0.660152E+09 | 845.66 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.961533E+10 | 11290.14 | 19-JUN-05:01 | 24.08 | 22.05 | 0.661338E+09 | 845.65 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.114019E+11 | 12919.08 | 10-JUL-03:01 | 26.10 | 21.75 | 0.614953E+09 | 845.60 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.122509E+11 | 12108.30 | 04-AUG-05:02 | 24.08 | 23.26 | 0.689710E+09 | 845.64 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.740884E+10 | 12361.63 | 14-SEP-03:01 | 22.20 | 21.85 | 0.610094E+09 | 845.65 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.615465E+10 | 9264.05 | 14-OCT-05:01 | 14.40 | 13.43 | 0.630374E+09 | 845.67 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.402507E+10 | 5228.65 | 03-NOV-13:40 | 17.60 | 10.63 | 0.609783E+09 | 845.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.341052E+10 | 3980.72 | 26-DEC-13:30 | 9.45 | 5.01 | 0.574682E+09 | 845.61 | 18-DEC-14:00 | 6.10 | 2.60 |
Annual Sum or Average | 0.766580E+11 | 0.737692E+10 | ||||||||
Minimum of Months | 0.256696E+10 | 2911.58 | 0.87 | -2.8 | 0.506834E+09 | 830.45 | 6.10 | 2.25 | ||
Maximum of Months | 0.122509E+11 | 12919.08 | 26.10 | 23.26 | 0.689710E+09 | 845.67 | 29.15 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.264656E+10 | 3729.66 | 17-JAN-09:55 | 6.10 | 3.87 | 0.339127E+09 | 543.60 | 19-JAN-10:09 | 7.80 | 4.24 |
February | 0.266170E+10 | 5473.91 | 22-FEB-09:15 | 0.20 | -3.1 | 0.314908E+09 | 544.96 | 22-FEB-10:09 | 0.87 | -2.8 |
March | 0.449833E+10 | 8017.30 | 29-MAR-08:40 | 5.20 | 2.68 | 0.407961E+09 | 546.93 | 23-MAR-09:20 | 1.13 | -3.0 |
April | 0.561846E+10 | 14352.69 | 23-APR-08:13 | 10.97 | 7.34 | 0.375975E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.55 |
May | 0.704709E+10 | 18340.05 | 29-MAY-09:01 | 26.20 | 16.86 | 0.415892E+09 | 545.00 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.837470E+10 | 18052.34 | 25-JUN-08:52 | 25.60 | 23.63 | 0.419319E+09 | 544.97 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.975586E+10 | 18705.76 | 02-JUL-08:12 | 24.80 | 21.40 | 0.391401E+09 | 544.94 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.108515E+11 | 11933.53 | 02-AUG-08:30 | 28.85 | 24.78 | 0.440603E+09 | 544.96 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.704999E+10 | 18429.37 | 04-SEP-08:11 | 23.17 | 18.66 | 0.384442E+09 | 544.98 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.594299E+10 | 8797.52 | 03-OCT-08:40 | 18.33 | 16.57 | 0.397883E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.386549E+10 | 5463.16 | 02-NOV-08:50 | 10.82 | 5.70 | 0.368911E+09 | 544.95 | 07-NOV-10:09 | 10.18 | 7.15 |
December | 0.331843E+10 | 3954.97 | 20-DEC-09:15 | 6.83 | 4.41 | 0.339522E+09 | 542.41 | 26-DEC-10:09 | 8.40 | 5.01 |
Annual Sum or Average | 0.716311E+11 | 0.459595E+10 | ||||||||
Minimum of Months | 0.264656E+10 | 3729.66 | 0.20 | -3.1 | 0.314908E+09 | 542.41 | 0.87 | -3.0 | ||
Maximum of Months | 0.108515E+11 | 18705.76 | 28.85 | 24.78 | 0.440603E+09 | 546.93 | 29.15 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422818E+10 | 11373.10 | 05-JAN-11:30 | -3.6 | -6.2 | 0.572206E+09 | 900.61 | 19-JAN-14:09 | 9.32 | 3.66 |
February | 0.447717E+10 | 13411.94 | 20-FEB-12:53 | 9.40 | 4.35 | 0.534269E+09 | 914.46 | 22-FEB-14:09 | 4.90 | -0.5 |
March | 0.687862E+10 | 12645.81 | 01-MAR-13:30 | 13.90 | 6.34 | 0.662540E+09 | 940.03 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.710012E+10 | 13024.06 | 07-APR-12:30 | 26.15 | 15.88 | 0.595915E+09 | 845.66 | 10-APR-13:09 | 20.10 | 10.08 |
May | 0.764161E+10 | 12803.20 | 30-MAY-03:02 | 18.22 | 15.07 | 0.656033E+09 | 845.69 | 15-MAY-13:50 | 18.27 | 11.31 |
June | 0.101638E+11 | 12172.21 | 12-JUN-05:03 | 18.40 | 17.59 | 0.659977E+09 | 845.67 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.123363E+11 | 16708.18 | 30-JUL-12:52 | 27.20 | 24.01 | 0.614609E+09 | 845.61 | 11-JUL-13:09 | 27.98 | 17.96 |
August | 0.146840E+11 | 14438.04 | 30-AUG-12:20 | 26.87 | 14.94 | 0.690939E+09 | 913.67 | 30-AUG-13:00 | 28.90 | 15.44 |
September | 0.104524E+11 | 17912.57 | 04-SEP-12:51 | 26.10 | 18.29 | 0.613935E+09 | 953.86 | 28-SEP-13:09 | 22.98 | 13.53 |
October | 0.108800E+11 | 18244.45 | 22-OCT-12:22 | 21.65 | 16.56 | 0.644289E+09 | 986.59 | 30-OCT-13:20 | 15.77 | 9.68 |
November | 0.652242E+10 | 13754.33 | 02-NOV-13:20 | 15.77 | 8.35 | 0.616262E+09 | 980.63 | 02-NOV-13:09 | 15.68 | 8.27 |
December | 0.563976E+10 | 15267.35 | 17-DEC-12:02 | 12.20 | 4.55 | 0.579343E+09 | 925.84 | 21-DEC-14:09 | 3.30 | -1.3 |
Annual Sum or Average | 0.101004E+12 | 0.744032E+10 | ||||||||
Minimum of Months | 0.422818E+10 | 11373.10 | -3.6 | -6.2 | 0.534269E+09 | 845.61 | 3.30 | -1.3 | ||
Maximum of Months | 0.146840E+11 | 18244.45 | 27.20 | 24.01 | 0.690939E+09 | 986.59 | 29.15 | 17.96 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.386018E+10 | 6012.55 | 20-JAN-15:50 | 7.30 | 3.82 | 0.348628E+09 | 544.93 | 19-JAN-14:00 | 8.90 | 3.58 |
February | 0.420024E+10 | 8390.17 | 24-FEB-15:30 | 8.05 | 2.02 | 0.332499E+09 | 544.95 | 14-FEB-14:50 | 0.60 | -3.5 |
March | 0.725385E+10 | 14089.89 | 27-MAR-03:01 | 8.22 | 7.71 | 0.434905E+09 | 544.96 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.932699E+10 | 22298.16 | 16-APR-17:22 | 21.40 | 12.95 | 0.393966E+09 | 544.97 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.864880E+10 | 19205.79 | 14-MAY-16:22 | 13.30 | 9.03 | 0.418958E+09 | 544.99 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.116801E+11 | 22869.97 | 25-JUN-16:12 | 25.93 | 22.77 | 0.425549E+09 | 544.98 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.141328E+11 | 24537.53 | 04-JUL-16:11 | 25.73 | 18.05 | 0.396637E+09 | 544.94 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.171606E+11 | 22641.99 | 13-AUG-15:32 | 30.20 | 20.60 | 0.445386E+09 | 544.98 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.891906E+10 | 23341.93 | 10-SEP-15:42 | 23.48 | 13.04 | 0.386734E+09 | 544.97 | 11-SEP-13:09 | 20.60 | 11.99 |
October | 0.843615E+10 | 18275.17 | 06-OCT-03:01 | 19.40 | 17.99 | 0.406276E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.588952E+10 | 14461.63 | 04-NOV-03:01 | 10.10 | 9.12 | 0.397577E+09 | 544.97 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.569464E+10 | 9028.97 | 26-DEC-04:01 | 5.60 | 4.99 | 0.386244E+09 | 544.95 | 22-DEC-14:20 | 1.30 | -2.3 |
Annual Sum or Average | 0.105203E+12 | 0.477336E+10 | ||||||||
Minimum of Months | 0.386018E+10 | 6012.55 | 5.60 | 2.02 | 0.332499E+09 | 544.93 | 0.60 | -3.5 | ||
Maximum of Months | 0.171606E+11 | 24537.53 | 30.20 | 22.77 | 0.445386E+09 | 544.99 | 29.15 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.819754E+09 | 3734.55 | 27-JAN-13:20 | 5.00 | 1.96 | 0.475768E+09 | 721.03 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.840946E+09 | 3893.83 | 17-FEB-17:40 | 4.47 | 0.57 | 0.435851E+09 | 735.30 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.235494E+10 | 4113.26 | 22-MAR-16:10 | 1.70 | -3.3 | 0.572167E+09 | 845.60 | 28-MAR-13:50 | 13.40 | 8.45 |
April | 0.331959E+10 | 5495.09 | 07-APR-15:20 | 25.60 | 15.99 | 0.558314E+09 | 845.62 | 06-APR-13:09 | 18.90 | 14.06 |
May | 0.547366E+10 | 10327.33 | 31-MAY-05:02 | 16.38 | 14.98 | 0.648273E+09 | 845.66 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.764226E+10 | 11762.99 | 22-JUN-05:02 | 22.88 | 15.42 | 0.659077E+09 | 845.63 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.866154E+10 | 13922.18 | 10-JUL-03:02 | 26.10 | 21.75 | 0.614625E+09 | 845.60 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.895241E+10 | 11544.02 | 17-AUG-05:02 | 25.10 | 24.25 | 0.689096E+09 | 845.64 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.592544E+10 | 11606.71 | 02-SEP-05:02 | 22.12 | 16.29 | 0.602412E+09 | 845.64 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.424277E+10 | 5734.47 | 05-OCT-14:00 | 23.30 | 18.85 | 0.602896E+09 | 845.60 | 26-OCT-13:09 | 13.98 | 6.19 |
November | 0.215410E+10 | 3524.94 | 16-NOV-11:00 | 6.10 | 2.99 | 0.524799E+09 | 840.39 | 03-NOV-13:00 | 17.80 | 10.65 |
December | 0.121973E+10 | 4696.63 | 22-DEC-14:07 | 1.20 | -2.4 | 0.466370E+09 | 734.10 | 20-DEC-14:20 | 9.43 | 5.61 |
Annual Sum or Average | 0.516071E+11 | 0.684965E+10 | ||||||||
Minimum of Months | 0.819754E+09 | 3524.94 | 1.20 | -3.3 | 0.435851E+09 | 721.03 | 7.80 | 2.25 | ||
Maximum of Months | 0.895241E+10 | 13922.18 | 26.10 | 24.25 | 0.689096E+09 | 845.66 | 26.20 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.910182E+09 | 4735.87 | 27-JAN-13:20 | 5.00 | 1.96 | 0.222828E+09 | 457.64 | 27-JAN-09:50 | 4.22 | 1.39 |
February | 0.118510E+10 | 4952.66 | 17-FEB-17:40 | 4.47 | 0.57 | 0.205217E+09 | 486.57 | 22-FEB-09:50 | 0.50 | -3.0 |
March | 0.299863E+10 | 8791.28 | 29-MAR-08:55 | 5.60 | 2.97 | 0.269827E+09 | 529.32 | 29-MAR-08:00 | 5.60 | 2.97 |
April | 0.412875E+10 | 9537.74 | 28-APR-08:40 | 15.53 | 8.73 | 0.259660E+09 | 532.86 | 03-APR-08:50 | 6.02 | 2.03 |
May | 0.647561E+10 | 19927.90 | 29-MAY-08:42 | 25.73 | 16.71 | 0.295547E+09 | 521.24 | 30-MAY-08:00 | 26.10 | 16.89 |
June | 0.758719E+10 | 18042.67 | 04-JUN-08:52 | 23.30 | 12.86 | 0.302182E+09 | 521.22 | 05-JUN-07:00 | 18.90 | 15.20 |
July | 0.839042E+10 | 20160.82 | 02-JUL-08:32 | 25.20 | 21.53 | 0.286886E+09 | 521.20 | 11-JUL-14:39 | 28.50 | 17.65 |
August | 0.930175E+10 | 19149.06 | 13-AUG-09:12 | 28.17 | 19.19 | 0.323092E+09 | 521.23 | 25-AUG-14:20 | 26.70 | 15.30 |
September | 0.649762E+10 | 19425.50 | 04-SEP-09:12 | 24.47 | 18.40 | 0.273707E+09 | 521.22 | 01-SEP-14:39 | 30.77 | 17.40 |
October | 0.505454E+10 | 7869.97 | 05-OCT-08:50 | 18.72 | 16.70 | 0.276406E+09 | 521.22 | 16-OCT-08:00 | 16.70 | 14.03 |
November | 0.248327E+10 | 4739.65 | 06-NOV-08:20 | 6.67 | 3.54 | 0.237840E+09 | 521.04 | 02-NOV-08:00 | 11.10 | 5.84 |
December | 0.137804E+10 | 4566.31 | 01-DEC-13:27 | 4.70 | 0.40 | 0.217801E+09 | 473.25 | 20-DEC-09:39 | 7.57 | 4.72 |
Annual Sum or Average | 0.563911E+11 | 0.317099E+10 | ||||||||
Minimum of Months | 0.910182E+09 | 4566.31 | 4.47 | 0.40 | 0.205217E+09 | 457.64 | 0.50 | -3.0 | ||
Maximum of Months | 0.930175E+10 | 20160.82 | 28.17 | 21.53 | 0.323092E+09 | 532.86 | 30.77 | 17.65 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.296471E+10 | 12442.99 | 30-JAN-13:00 | 1.70 | -1.9 | 0.537855E+09 | 968.61 | 30-JAN-11:50 | 0.92 | -2.2 |
February | 0.338880E+10 | 15739.19 | 22-FEB-12:05 | 3.40 | -1.2 | 0.505461E+09 | 944.96 | 02-FEB-14:09 | 5.50 | -0.7 |
March | 0.531701E+10 | 13258.63 | 22-MAR-12:10 | 1.20 | -3.7 | 0.630199E+09 | 965.66 | 01-MAR-14:09 | 13.62 | 5.83 |
April | 0.501526E+10 | 12392.51 | 07-APR-12:30 | 26.15 | 15.88 | 0.570312E+09 | 848.14 | 07-APR-13:50 | 26.20 | 16.00 |
May | 0.644762E+10 | 11726.74 | 31-MAY-05:02 | 16.38 | 14.98 | 0.645538E+09 | 845.69 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.833416E+10 | 13060.45 | 20-JUN-05:02 | 20.78 | 18.12 | 0.657563E+09 | 845.65 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.962398E+10 | 16019.70 | 10-JUL-03:02 | 26.10 | 21.75 | 0.614113E+09 | 845.62 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.116126E+11 | 14602.29 | 30-AUG-13:40 | 28.33 | 15.51 | 0.691826E+09 | 937.70 | 30-AUG-13:20 | 27.77 | 15.55 |
September | 0.956751E+10 | 17453.75 | 04-SEP-11:52 | 26.10 | 17.77 | 0.614217E+09 | 1013.62 | 28-SEP-13:30 | 23.35 | 13.51 |
October | 0.979614E+10 | 16426.20 | 15-OCT-11:32 | 19.80 | 13.57 | 0.643971E+09 | 1030.91 | 30-OCT-13:39 | 15.93 | 9.65 |
November | 0.504272E+10 | 13533.19 | 02-NOV-13:30 | 15.85 | 8.44 | 0.591098E+09 | 1023.17 | 02-NOV-13:20 | 15.77 | 8.35 |
December | 0.372085E+10 | 17871.49 | 21-DEC-17:35 | 1.70 | -2.4 | 0.543030E+09 | 937.11 | 15-DEC-14:09 | 3.98 | 0.24 |
Annual Sum or Average | 0.808314E+11 | 0.724518E+10 | ||||||||
Minimum of Months | 0.296471E+10 | 11726.74 | 1.20 | -3.7 | 0.505461E+09 | 845.62 | 0.92 | -2.2 | ||
Maximum of Months | 0.116126E+11 | 17871.49 | 28.33 | 21.75 | 0.691826E+09 | 1030.91 | 27.77 | 16.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121078E+10 | 4178.80 | 26-JAN-15:35 | 4.40 | 0.99 | 0.308058E+09 | 510.68 | 20-JAN-16:10 | 6.93 | 3.70 |
February | 0.140459E+10 | 5701.90 | 17-FEB-17:40 | 4.47 | 0.57 | 0.284330E+09 | 524.55 | 22-FEB-16:10 | 4.22 | -0.4 |
March | 0.353462E+10 | 9588.46 | 17-MAR-15:25 | -0.6 | -1.5 | 0.363797E+09 | 561.70 | 17-MAR-15:30 | -0.6 | -1.5 |
April | 0.464785E+10 | 12747.90 | 09-APR-16:23 | 16.65 | 13.96 | 0.344372E+09 | 544.94 | 26-APR-13:00 | 18.30 | 12.91 |
May | 0.659097E+10 | 15841.17 | 14-MAY-15:52 | 13.30 | 9.03 | 0.393138E+09 | 544.98 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.827233E+10 | 21124.09 | 18-JUN-16:11 | 25.40 | 22.05 | 0.412467E+09 | 544.94 | 09-JUN-13:00 | 21.10 | 14.09 |
July | 0.891389E+10 | 19548.87 | 02-JUL-15:22 | 25.00 | 20.59 | 0.390212E+09 | 544.93 | 12-JUL-13:09 | 28.80 | 18.60 |
August | 0.103229E+11 | 19163.13 | 13-AUG-15:52 | 30.00 | 20.44 | 0.439678E+09 | 544.97 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.682869E+10 | 19954.27 | 10-SEP-16:52 | 22.80 | 12.67 | 0.367723E+09 | 544.95 | 15-SEP-13:00 | 22.80 | 15.48 |
October | 0.557457E+10 | 10515.74 | 04-OCT-15:30 | 23.35 | 19.11 | 0.368157E+09 | 544.92 | 04-OCT-13:00 | 24.40 | 18.94 |
November | 0.263978E+10 | 5639.71 | 03-NOV-15:40 | 15.73 | 10.51 | 0.324785E+09 | 539.02 | 06-NOV-14:00 | 13.30 | 7.70 |
December | 0.167834E+10 | 6063.98 | 21-DEC-17:35 | 1.70 | -2.4 | 0.300449E+09 | 500.78 | 08-DEC-14:00 | 6.70 | 2.35 |
Annual Sum or Average | 0.616193E+11 | 0.429717E+10 | ||||||||
Minimum of Months | 0.121078E+10 | 4178.80 | -0.6 | -2.4 | 0.284330E+09 | 500.78 | -0.6 | -1.5 | ||
Maximum of Months | 0.103229E+11 | 21124.09 | 30.00 | 22.05 | 0.439678E+09 | 561.70 | 28.80 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.418027E+09 | 2042.16 | 20-JAN-16:00 | 7.20 | 3.79 | 0.465699E+09 | 675.73 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.414675E+09 | 2047.15 | 24-FEB-15:50 | 7.88 | 1.86 | 0.423920E+09 | 680.26 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.172821E+10 | 3471.53 | 27-MAR-16:00 | 22.20 | 16.33 | 0.538383E+09 | 825.80 | 28-MAR-13:00 | 13.30 | 8.40 |
April | 0.302454E+10 | 6309.70 | 07-APR-15:20 | 25.60 | 15.99 | 0.529530E+09 | 845.63 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.558059E+10 | 10158.76 | 30-MAY-05:03 | 18.17 | 14.30 | 0.629756E+09 | 845.66 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.814340E+10 | 12054.73 | 22-JUN-05:02 | 22.88 | 15.42 | 0.656213E+09 | 845.64 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.946751E+10 | 14677.83 | 10-JUL-03:02 | 26.10 | 21.75 | 0.613835E+09 | 845.60 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.962587E+10 | 12789.02 | 17-AUG-05:02 | 25.10 | 24.25 | 0.687212E+09 | 845.64 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.605487E+10 | 12681.33 | 02-SEP-05:02 | 22.12 | 16.29 | 0.591364E+09 | 845.63 | 11-SEP-13:09 | 20.60 | 11.99 |
October | 0.394832E+10 | 6075.13 | 04-OCT-14:00 | 24.40 | 18.94 | 0.571321E+09 | 845.59 | 11-OCT-13:50 | 20.60 | 17.27 |
November | 0.155291E+10 | 3191.51 | 03-NOV-14:00 | 17.80 | 10.65 | 0.488038E+09 | 795.55 | 03-NOV-13:00 | 17.80 | 10.65 |
December | 0.460098E+09 | 1996.21 | 20-DEC-14:20 | 9.43 | 5.61 | 0.449640E+09 | 674.76 | 20-DEC-14:30 | 9.15 | 5.46 |
Annual Sum or Average | 0.504190E+11 | 0.664491E+10 | ||||||||
Minimum of Months | 0.414675E+09 | 1996.21 | 7.20 | 1.86 | 0.423920E+09 | 674.76 | 7.80 | 2.25 | ||
Maximum of Months | 0.962587E+10 | 14677.83 | 26.10 | 24.25 | 0.687212E+09 | 845.66 | 29.15 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.516743E+09 | 2458.13 | 19-JAN-09:40 | 6.67 | 3.81 | 0.300228E+09 | 435.70 | 19-JAN-10:09 | 7.80 | 4.24 |
February | 0.677464E+09 | 2551.50 | 17-FEB-09:35 | 3.87 | 0.10 | 0.273885E+09 | 449.68 | 17-FEB-10:09 | 4.68 | 0.59 |
March | 0.231849E+10 | 5011.99 | 29-MAR-09:25 | 6.15 | 3.18 | 0.355959E+09 | 544.95 | 29-MAR-09:20 | 5.97 | 3.11 |
April | 0.364743E+10 | 8942.49 | 28-APR-08:50 | 15.82 | 8.78 | 0.348369E+09 | 544.97 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.635838E+10 | 20237.68 | 29-MAY-08:52 | 26.10 | 16.70 | 0.399476E+09 | 545.00 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.789805E+10 | 19559.30 | 25-JUN-08:52 | 25.60 | 23.63 | 0.412313E+09 | 544.97 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.893369E+10 | 19527.07 | 09-JUL-10:02 | 29.90 | 25.41 | 0.390866E+09 | 544.95 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.974690E+10 | 19603.33 | 13-AUG-09:12 | 28.17 | 19.19 | 0.441106E+09 | 544.97 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.643853E+10 | 19513.29 | 04-SEP-09:22 | 24.75 | 18.33 | 0.371925E+09 | 544.98 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.454167E+10 | 7252.16 | 05-OCT-09:00 | 18.90 | 16.76 | 0.369963E+09 | 544.97 | 16-OCT-09:20 | 17.07 | 14.17 |
November | 0.177092E+10 | 3622.78 | 03-NOV-14:00 | 17.80 | 10.65 | 0.310974E+09 | 502.80 | 03-NOV-09:30 | 13.05 | 8.23 |
December | 0.650309E+09 | 2489.86 | 20-DEC-09:25 | 7.20 | 4.57 | 0.289817E+09 | 434.61 | 20-DEC-10:09 | 8.40 | 5.02 |
Annual Sum or Average | 0.534986E+11 | 0.426488E+10 | ||||||||
Minimum of Months | 0.516743E+09 | 2458.13 | 3.87 | 0.10 | 0.273885E+09 | 434.61 | 4.68 | 0.59 | ||
Maximum of Months | 0.974690E+10 | 20237.68 | 29.90 | 25.41 | 0.441106E+09 | 545.00 | 29.15 | 17.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218843E+10 | 10906.27 | 19-JAN-13:40 | 9.40 | 3.84 | 0.518349E+09 | 866.03 | 19-JAN-14:09 | 9.32 | 3.66 |
February | 0.257221E+10 | 11047.93 | 02-FEB-14:15 | 5.40 | -0.8 | 0.479076E+09 | 878.86 | 02-FEB-14:20 | 5.40 | -0.8 |
March | 0.444063E+10 | 12944.07 | 01-MAR-13:40 | 13.90 | 6.18 | 0.596803E+09 | 917.13 | 01-MAR-14:09 | 13.62 | 5.83 |
April | 0.457555E+10 | 13035.56 | 07-APR-12:40 | 26.33 | 16.04 | 0.545963E+09 | 845.66 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.657336E+10 | 11726.92 | 30-MAY-05:03 | 18.17 | 14.30 | 0.626186E+09 | 845.69 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.888047E+10 | 13907.63 | 20-JUN-03:01 | 22.02 | 19.38 | 0.652974E+09 | 845.67 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.104705E+11 | 16883.11 | 10-JUL-03:02 | 26.10 | 21.75 | 0.612793E+09 | 845.62 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.123263E+11 | 17662.42 | 13-AUG-15:52 | 30.00 | 20.44 | 0.688678E+09 | 972.75 | 30-AUG-13:39 | 28.33 | 15.51 |
September | 0.965334E+10 | 19494.44 | 04-SEP-12:02 | 26.10 | 17.86 | 0.602056E+09 | 979.83 | 28-SEP-13:39 | 23.53 | 13.50 |
October | 0.910041E+10 | 17859.49 | 15-OCT-14:02 | 21.02 | 13.38 | 0.617098E+09 | 970.01 | 04-OCT-13:39 | 24.60 | 18.81 |
November | 0.400233E+10 | 14128.04 | 02-NOV-13:30 | 15.85 | 8.44 | 0.554458E+09 | 956.04 | 02-NOV-13:30 | 15.85 | 8.44 |
December | 0.255699E+10 | 10819.34 | 15-DEC-13:30 | 3.35 | -0.3 | 0.510454E+09 | 856.74 | 21-DEC-14:09 | 3.30 | -1.3 |
Annual Sum or Average | 0.773405E+11 | 0.700489E+10 | ||||||||
Minimum of Months | 0.218843E+10 | 10819.34 | 3.35 | -0.8 | 0.479076E+09 | 845.62 | 3.30 | -1.3 | ||
Maximum of Months | 0.123263E+11 | 19494.44 | 30.00 | 21.75 | 0.688678E+09 | 979.83 | 29.15 | 18.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801087E+09 | 3341.89 | 20-JAN-16:00 | 7.20 | 3.79 | 0.304175E+09 | 494.18 | 20-JAN-16:10 | 6.93 | 3.70 |
February | 0.943667E+09 | 4023.15 | 22-FEB-16:30 | 3.85 | -0.4 | 0.279789E+09 | 521.19 | 22-FEB-16:00 | 3.30 | -0.4 |
March | 0.288945E+10 | 8292.44 | 29-MAR-16:00 | 7.20 | 4.87 | 0.351565E+09 | 544.91 | 03-MAR-14:00 | 15.00 | 8.37 |
April | 0.427797E+10 | 12401.15 | 09-APR-16:23 | 16.65 | 13.96 | 0.331798E+09 | 544.92 | 10-APR-13:00 | 20.60 | 10.42 |
May | 0.664754E+10 | 15602.97 | 21-MAY-15:42 | 19.27 | 12.81 | 0.381644E+09 | 544.98 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.867320E+10 | 22796.66 | 18-JUN-16:11 | 25.40 | 22.05 | 0.406611E+09 | 544.97 | 22-JUN-13:30 | 29.15 | 17.43 |
July | 0.950328E+10 | 22224.72 | 02-JUL-16:51 | 24.40 | 20.56 | 0.387446E+09 | 544.93 | 12-JUL-13:09 | 28.80 | 18.60 |
August | 0.107755E+11 | 20622.75 | 13-AUG-15:52 | 30.00 | 20.44 | 0.435418E+09 | 544.97 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.690791E+10 | 19902.02 | 04-SEP-16:42 | 24.60 | 18.77 | 0.359087E+09 | 544.95 | 15-SEP-13:00 | 22.80 | 15.48 |
October | 0.517764E+10 | 10783.16 | 04-OCT-15:30 | 23.35 | 19.11 | 0.353612E+09 | 544.91 | 04-OCT-13:00 | 24.40 | 18.94 |
November | 0.201424E+10 | 5219.92 | 03-NOV-15:40 | 15.73 | 10.51 | 0.311122E+09 | 521.18 | 03-NOV-15:39 | 15.73 | 10.51 |
December | 0.932717E+09 | 3201.24 | 08-DEC-15:50 | 6.20 | 1.94 | 0.293893E+09 | 479.79 | 08-DEC-15:00 | 6.10 | 1.86 |
Annual Sum or Average | 0.595442E+11 | 0.419616E+10 | ||||||||
Minimum of Months | 0.801087E+09 | 3201.24 | 3.85 | -0.4 | 0.279789E+09 | 479.79 | 3.30 | -0.4 | ||
Maximum of Months | 0.107755E+11 | 22796.66 | 30.00 | 22.05 | 0.435418E+09 | 544.98 | 29.15 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144847E+10 | 4452.74 | 14-JAN-06:01 | -7.8 | -8.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.164012E+10 | 4440.90 | 24-FEB-06:10 | 4.60 | 4.47 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.359196E+10 | 5280.30 | 27-MAR-05:03 | 7.88 | 7.88 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.493460E+10 | 7753.98 | 10-APR-05:13 | 15.20 | 13.75 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.576306E+10 | 10511.27 | 30-MAY-05:13 | 18.53 | 14.50 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.747361E+10 | 9565.03 | 12-JUN-05:13 | 18.50 | 17.63 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.842368E+10 | 9478.04 | 10-JUL-05:01 | 26.10 | 20.73 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.954051E+10 | 9073.27 | 22-AUG-05:01 | 25.00 | 18.09 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.663962E+10 | 8899.27 | 06-SEP-05:01 | 21.52 | 18.83 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.600335E+10 | 7820.96 | 16-OCT-05:05 | 8.90 | 8.38 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.384012E+10 | 7237.21 | 13-NOV-06:13 | 5.77 | 4.70 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.302334E+10 | 4441.69 | 26-DEC-06:08 | 6.20 | 5.34 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.623225E+11 | 0.00 | ||||||||
Minimum of Months | 0.144847E+10 | 4440.90 | -7.8 | -8.5 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.954051E+10 | 10511.27 | 26.10 | 20.73 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359658E+09 | 4598.58 | 14-JAN-05:01 | -7.3 | -7.9 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.528121E+09 | 6519.63 | 13-FEB-04:01 | -8.9 | -10.8 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.127099E+10 | 4163.70 | 17-MAR-04:01 | -1.6 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.237733E+10 | 4378.69 | 28-APR-05:17 | 12.93 | 9.27 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.400581E+10 | 6183.45 | 31-MAY-05:13 | 16.67 | 15.20 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.580139E+10 | 5980.52 | 12-JUN-05:13 | 18.50 | 17.63 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.659416E+10 | 9029.62 | 21-JUL-05:01 | 24.50 | 23.34 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.734966E+10 | 8696.85 | 05-AUG-05:01 | 26.20 | 23.65 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.511943E+10 | 5965.10 | 08-SEP-05:10 | 21.70 | 21.23 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.362848E+10 | 4977.65 | 06-OCT-05:10 | 19.40 | 18.22 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.141159E+10 | 5091.70 | 24-NOV-05:01 | -4.0 | -5.9 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.725971E+09 | 4403.56 | 22-DEC-06:02 | -4.1 | -6.4 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.391726E+11 | 0.00 | ||||||||
Minimum of Months | 0.359658E+09 | 4163.70 | -8.9 | -10.8 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.734966E+10 | 9029.62 | 26.20 | 23.65 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6154563.42 | 890.30 | 19-JAN-13:10 | 9.40 | 4.08 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 76243563.21 | 2047.69 | 17-FEB-13:10 | 6.70 | 1.65 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.126726E+10 | 6492.09 | 28-MAR-13:10 | 13.80 | 8.63 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.314553E+10 | 12412.36 | 07-APR-13:10 | 26.60 | 16.30 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.671499E+10 | 17917.09 | 30-MAY-13:10 | 29.90 | 17.80 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.103608E+11 | 18729.76 | 19-JUN-13:50 | 34.50 | 23.72 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.123153E+11 | 17594.85 | 10-JUL-14:00 | 32.80 | 20.87 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.130983E+11 | 17458.80 | 22-AUG-15:30 | 29.70 | 17.30 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.719167E+10 | 18802.17 | 01-SEP-14:30 | 30.85 | 17.38 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.403531E+10 | 10497.37 | 04-OCT-14:30 | 24.15 | 19.03 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.578661E+09 | 4865.28 | 04-NOV-13:00 | 17.80 | 12.72 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 8358266.39 | 1678.52 | 17-DEC-13:20 | 12.20 | 5.04 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.587986E+11 | 0.00 | ||||||||
Minimum of Months | 6154563.42 | 890.30 | 6.70 | 1.65 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.130983E+11 | 18802.17 | 34.50 | 23.72 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.271284E+10 | 1895.16 | 20-JAN-16:30 | 6.40 | 3.50 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.744591E+10 | 4005.12 | 14-FEB-17:00 | 0.00 | -3.8 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.140754E+11 | 5994.92 | 27-MAR-17:20 | 20.37 | 15.14 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.185796E+11 | 7573.94 | 23-APR-17:43 | 12.38 | 8.82 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.422189E+10 | 2060.69 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.919657E+10 | 4072.65 | 18-JUN-17:55 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.145484E+11 | 6019.32 | 12-JUL-18:20 | 25.40 | 21.22 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.180178E+11 | 7241.04 | 08-AUG-04:53 | 15.00 | 12.46 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.419616E+10 | 3964.90 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.936609E+10 | 4094.73 | 15-OCT-16:40 | 18.67 | 11.87 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.135907E+11 | 5777.05 | 06-NOV-16:10 | 13.03 | 7.65 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.189480E+11 | 7448.64 | 18-DEC-15:50 | 5.68 | 2.50 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.134899E+12 | 0.00 | ||||||||
Minimum of Months | 0.271284E+10 | 1895.16 | 0.00 | -3.8 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.189480E+11 | 7573.94 | 25.40 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.758019E+09 | 1587.74 | 20-JAN-16:40 | 6.13 | 3.40 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.523877E+10 | 3583.02 | 22-FEB-17:00 | 3.30 | -0.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.119337E+11 | 5623.13 | 29-MAR-17:20 | 5.73 | 4.14 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.168014E+11 | 7173.38 | 12-APR-17:20 | 12.03 | 3.26 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.339855E+10 | 1956.03 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.849234E+10 | 3880.50 | 18-JUN-17:55 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.137707E+11 | 5755.93 | 12-JUL-18:20 | 25.40 | 21.22 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.171840E+11 | 6901.82 | 08-AUG-04:21 | 15.30 | 12.58 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.345011E+10 | 3699.97 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.803930E+10 | 3823.32 | 04-OCT-16:30 | 22.25 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.112809E+11 | 5386.41 | 03-NOV-16:00 | 15.00 | 10.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.159327E+11 | 7020.54 | 08-DEC-16:10 | 5.92 | 1.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.116280E+12 | 0.00 | ||||||||
Minimum of Months | 0.758019E+09 | 1587.74 | 3.30 | -0.4 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.171840E+11 | 7173.38 | 25.40 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.294609E+09 | 1506.87 | 20-JAN-16:40 | 6.13 | 3.40 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.361297E+10 | 3474.98 | 02-FEB-16:50 | 3.07 | -2.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.106517E+11 | 5617.74 | 29-MAR-17:20 | 5.73 | 4.14 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.160183E+11 | 7269.80 | 12-APR-17:20 | 12.03 | 3.26 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.306338E+10 | 2041.28 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.846924E+10 | 4094.07 | 18-JUN-17:55 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.138561E+11 | 5846.85 | 12-JUL-18:20 | 25.40 | 21.22 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.174201E+11 | 6924.11 | 20-AUG-01:42 | 16.28 | 13.55 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.319200E+10 | 3224.67 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.725584E+10 | 3880.08 | 04-OCT-16:30 | 22.25 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.975792E+10 | 5359.17 | 03-NOV-16:00 | 15.00 | 10.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.140058E+11 | 6870.11 | 08-DEC-16:10 | 5.92 | 1.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.107598E+12 | 0.00 | ||||||||
Minimum of Months | 0.294609E+09 | 1506.87 | 3.07 | -2.5 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.174201E+11 | 7269.80 | 25.40 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236729E+12 | 358551.12 | 13-JAN-20:51 | -2.0 | -2.7 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.433321E+12 | 407303.15 | 03-FEB-23:01 | -0.6 | -2.3 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.727188E+12 | 413509.17 | 04-MAR-16:52 | 7.20 | 7.20 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.942342E+12 | 394914.29 | 05-APR-03:03 | 6.60 | 3.38 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.238599E+12 | 339327.51 | 16-MAY-04:21 | 8.90 | 7.22 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.468461E+12 | 182312.72 | 20-JUN-16:00 | 25.60 | 17.02 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.730331E+12 | 274518.35 | 06-JUL-16:00 | 28.30 | 24.26 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.977003E+12 | 368679.63 | 13-AUG-18:42 | 26.15 | 20.53 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.234461E+12 | 105356.63 | 01-SEP-00:05 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.486756E+12 | 354129.85 | 28-OCT-17:24 | 8.85 | 2.88 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.707383E+12 | 411422.26 | 18-NOV-19:52 | 4.40 | 2.09 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.975367E+12 | 394405.85 | 14-DEC-04:57 | 1.10 | -1.6 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.715794E+13 | 0.00 | ||||||||
Minimum of Months | 0.234461E+12 | 105356.63 | -2.0 | -2.7 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.977003E+12 | 413509.17 | 28.30 | 24.26 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228900E+09 | 129881.33 | 03-JAN-05:49 | 3.98 |
February | 0.343041E+09 | 136210.58 | 07-FEB-05:53 | -9.4 |
March | 0.254922E+09 | 124210.73 | 22-MAR-03:47 | -1.7 |
April | 0.429251E+09 | 121001.69 | 08-APR-03:47 | 14.60 |
May | 0.484787E+09 | 122327.18 | 10-MAY-03:08 | 14.82 |
June | 0.726915E+09 | 132822.98 | 24-JUN-03:47 | 22.20 |
July | 0.628294E+09 | 134111.50 | 27-JUL-03:50 | 21.78 |
August | 0.889598E+09 | 133196.07 | 11-AUG-03:50 | 21.78 |
September | 0.105052E+10 | 132124.67 | 08-SEP-03:45 | 21.78 |
October | 0.100398E+10 | 124215.61 | 13-OCT-03:50 | 15.40 |
November | 0.951985E+09 | 126568.26 | 22-NOV-04:47 | -2.1 |
December | 0.402776E+09 | 125469.30 | 02-DEC-04:50 | 1.10 |
Annual Sum or Average | 0.739497E+10 | |||
Minimum of Months | 0.228900E+09 | 121001.69 | -9.4 | |
Maximum of Months | 0.105052E+10 | 136210.58 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.570117E+09 | 45446.09 | 02-JAN-04:01 | -11.8 |
February | 18552275.55 | 33474.86 | 06-FEB-06:01 | -12.9 |
March | 32587827.28 | 22509.67 | 17-MAR-15:20 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 23026166.36 | 18982.42 | 22-NOV-12:55 | 0.60 |
December | 8863920.34 | 18409.61 | 11-DEC-15:55 | 1.10 |
Annual Sum or Average | 0.653147E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.570117E+09 | 45446.09 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.299737E+10 | 79041.15 | 02-JAN-04:01 | -11.8 |
February | 0.196654E+10 | 76429.53 | 06-FEB-04:11 | -13.3 |
March | 0.285544E+09 | 68850.69 | 20-MAR-04:01 | -0.8 |
April | 38198749.19 | 64574.26 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.659208E+09 | 70815.98 | 24-NOV-05:01 | -4.0 |
December | 0.729930E+09 | 72041.17 | 26-DEC-05:01 | 5.68 |
Annual Sum or Average | 0.667679E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.299737E+10 | 79041.15 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32492904.17 | 9074.67 | 05-JAN-06:01 | -7.8 |
February | 40380291.32 | 9511.15 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 72873195.50 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 40380291.32 | 9511.15 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 39722447.00 | 7004.09 | 02-JAN-05:01 | -12.1 |
February | 33395032.11 | 7478.78 | 06-FEB-05:01 | -13.2 |
March | 317810.82 | 3735.43 | 22-MAR-05:01 | -2.3 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 270089.73 | 3653.67 | 22-NOV-06:01 | -2.2 |
December | 913916.32 | 6588.93 | 15-DEC-06:01 | -3.4 |
Annual Sum or Average | 74619295.98 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 39722447.00 | 7478.78 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153499E+09 | 12094.09 | 02-JAN-05:01 | -12.1 |
February | 0.104670E+09 | 12225.37 | 06-FEB-05:01 | -13.2 |
March | 931928.00 | 10689.95 | 13-MAR-05:01 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 1645147.99 | 8944.83 | 22-NOV-06:01 | -2.2 |
December | 1602744.72 | 10502.75 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.262348E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.153499E+09 | 12225.37 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4965464.90 | 5149.95 | 02-JAN-06:01 | -11.7 |
February | 2186880.35 | 5131.87 | 06-FEB-06:01 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 7152345.25 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 4965464.90 | 5149.95 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.267582E+10 | 12752.77 | 02-JAN-01:22 | -11.4 |
February | 0.181570E+10 | 12231.16 | 06-FEB-01:21 | -13.3 |
March | 0.296988E+09 | 10721.70 | 13-MAR-04:01 | -0.1 |
April | 26049601.20 | 9854.77 | 03-APR-04:01 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 413964.49 | 2721.78 | 28-OCT-05:03 | 3.90 |
November | 0.333920E+09 | 10756.91 | 22-NOV-05:01 | -2.2 |
December | 0.807962E+09 | 11992.33 | 31-DEC-21:52 | -7.2 |
Annual Sum or Average | 0.595685E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.267582E+10 | 12752.77 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162552E+10 | 15553.30 | 02-JAN-01:22 | -11.4 |
February | 0.943642E+09 | 14925.77 | 06-FEB-04:01 | -13.3 |
March | 0.180753E+09 | 12558.81 | 13-MAR-04:01 | -0.1 |
April | 19797670.75 | 11238.22 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 332111.08 | 1852.76 | 28-OCT-05:03 | 3.90 |
November | 0.201323E+09 | 12783.09 | 22-NOV-05:01 | -2.2 |
December | 0.508768E+09 | 12659.25 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.348014E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.162552E+10 | 15553.30 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.171092E+10 | 14490.18 | 02-JAN-01:22 | -11.4 |
February | 0.903203E+09 | 13816.86 | 06-FEB-04:01 | -13.3 |
March | 0.175623E+09 | 11971.17 | 13-MAR-04:01 | -0.1 |
April | 16256352.96 | 11022.95 | 03-APR-05:01 | 2.70 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.162767E+09 | 11963.26 | 22-NOV-05:01 | -2.2 |
December | 0.445047E+09 | 12091.15 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.341382E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.171092E+10 | 14490.18 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.131681E+10 | 15275.89 | 02-JAN-01:22 | -11.4 |
February | 0.799152E+09 | 14626.61 | 06-FEB-04:01 | -13.3 |
March | 0.102761E+09 | 12005.81 | 13-MAR-04:01 | -0.1 |
April | 5700178.77 | 9710.31 | 21-APR-05:02 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.138823E+09 | 12479.12 | 24-NOV-05:01 | -4.0 |
December | 0.318455E+09 | 12215.75 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.268170E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.131681E+10 | 15275.89 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.576326E+10 | 14531.38 | 02-JAN-01:22 | -11.4 |
February | 0.498680E+10 | 14680.71 | 06-FEB-04:11 | -13.3 |
March | 0.143815E+10 | 13282.17 | 13-MAR-03:01 | 0.50 |
April | 0.357471E+09 | 12540.85 | 03-APR-03:01 | 3.22 |
May | 5621472.31 | 10607.59 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.102786E+09 | 10958.68 | 28-OCT-04:03 | 4.32 |
November | 0.168175E+10 | 13522.49 | 23-NOV-23:33 | -3.1 |
December | 0.345553E+10 | 14549.17 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.177914E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.576326E+10 | 14680.71 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.342482E+10 | 17175.38 | 02-JAN-01:22 | -11.4 |
February | 0.267052E+10 | 17498.71 | 06-FEB-04:11 | -13.3 |
March | 0.761246E+09 | 15834.60 | 13-MAR-03:01 | 0.50 |
April | 0.209604E+09 | 14831.01 | 03-APR-03:01 | 3.22 |
May | 3146118.61 | 11839.66 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 52546915.90 | 12738.39 | 27-OCT-05:01 | 6.02 |
November | 0.936770E+09 | 15937.76 | 24-NOV-04:11 | -3.5 |
December | 0.198917E+10 | 17222.70 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.100478E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.342482E+10 | 17498.71 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.397824E+10 | 16617.15 | 02-JAN-01:22 | -11.4 |
February | 0.298260E+10 | 16802.30 | 06-FEB-04:11 | -13.3 |
March | 0.998493E+09 | 15206.56 | 13-MAR-03:01 | 0.50 |
April | 0.294850E+09 | 14136.66 | 03-APR-03:01 | 3.22 |
May | 5920046.72 | 12229.86 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 27218240.14 | 12314.57 | 27-OCT-05:01 | 6.02 |
November | 0.984925E+09 | 15226.31 | 24-NOV-04:11 | -3.5 |
December | 0.220598E+10 | 16684.13 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.114782E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.397824E+10 | 16802.30 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284671E+10 | 18256.68 | 02-JAN-01:22 | -11.4 |
February | 0.218322E+10 | 18452.87 | 06-FEB-04:11 | -13.3 |
March | 0.522043E+09 | 16129.44 | 13-MAR-03:01 | 0.50 |
April | 0.112864E+09 | 14344.64 | 03-APR-04:01 | 2.80 |
May | 155077.91 | 1287.65 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 23818451.57 | 12913.30 | 27-OCT-05:01 | 6.02 |
November | 0.679711E+09 | 16588.19 | 24-NOV-04:11 | -3.5 |
December | 0.136957E+10 | 18032.54 | 31-DEC-22:02 | -7.3 |
Annual Sum or Average | 0.773809E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.284671E+10 | 18452.87 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.344044E+09 | 12265.27 | 03-JAN-06:01 | 4.27 |
February | 0.243931E+09 | 10651.00 | 27-FEB-05:01 | -0.8 |
March | 82924441.72 | 12030.91 | 13-MAR-03:01 | 0.50 |
April | 0.117432E+09 | 12562.29 | 24-APR-03:01 | 7.88 |
May | 56777262.30 | 9935.60 | 01-MAY-03:02 | 7.45 |
June | 62311318.79 | 9517.72 | 12-JUN-03:02 | 18.90 |
July | 89461853.58 | 8807.12 | 24-JUL-03:02 | 22.02 |
August | 67953711.91 | 5483.38 | 08-AUG-03:01 | 16.02 |
September | 46402560.87 | 9180.03 | 14-SEP-03:01 | 22.20 |
October | 72017409.17 | 10372.76 | 23-OCT-03:02 | 14.13 |
November | 79647614.83 | 12325.75 | 27-NOV-04:01 | 6.60 |
December | 94505363.26 | 12874.06 | 26-DEC-04:01 | 5.60 |
Annual Sum or Average | 0.135741E+10 | |||
Minimum of Months | 46402560.87 | 5483.38 | -0.8 | |
Maximum of Months | 0.344044E+09 | 12874.06 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328083E+10 | 15566.58 | 02-JAN-06:12 | -11.7 |
February | 0.159726E+10 | 9505.25 | 22-FEB-10:10 | 0.87 |
March | 0.624631E+09 | 7884.98 | 13-MAR-10:00 | 2.20 |
April | 0.130106E+09 | 7522.01 | 18-APR-05:01 | 7.12 |
May | 42980786.26 | 7742.77 | 08-MAY-05:01 | 12.83 |
June | 29546120.71 | 7440.90 | 12-JUN-03:02 | 18.90 |
July | 35407877.15 | 7856.95 | 07-JUL-03:01 | 26.10 |
August | 25919755.50 | 7729.14 | 02-AUG-03:01 | 25.00 |
September | 34231707.46 | 6802.87 | 25-SEP-04:03 | 14.40 |
October | 40683570.08 | 7047.81 | 11-OCT-05:01 | 12.70 |
November | 0.441033E+09 | 9875.43 | 24-NOV-17:20 | 1.33 |
December | 0.808471E+09 | 9464.79 | 11-DEC-17:00 | 1.10 |
Annual Sum or Average | 0.709110E+10 | |||
Minimum of Months | 25919755.50 | 6802.87 | -11.7 | |
Maximum of Months | 0.328083E+10 | 15566.58 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.876224E+10 | 25226.33 | 02-JAN-05:33 | -11.9 |
February | 0.722972E+10 | 27317.97 | 06-FEB-05:10 | -13.2 |
March | 0.291653E+10 | 16133.84 | 13-MAR-05:03 | -0.6 |
April | 0.112753E+10 | 16256.57 | 26-APR-05:01 | 8.68 |
May | 0.160812E+09 | 16447.25 | 15-MAY-05:01 | 8.07 |
June | 53104811.25 | 15368.08 | 05-JUN-05:01 | 14.68 |
July | 35675759.07 | 9862.17 | 17-JUL-03:01 | 22.62 |
August | 48284712.78 | 12104.87 | 08-AUG-04:02 | 15.50 |
September | 88851516.68 | 15327.74 | 29-SEP-05:01 | 11.78 |
October | 0.610094E+09 | 17132.99 | 17-OCT-05:01 | 10.10 |
November | 0.333929E+10 | 18518.99 | 24-NOV-05:13 | -4.1 |
December | 0.603935E+10 | 16437.93 | 11-DEC-05:12 | 1.70 |
Annual Sum or Average | 0.304115E+11 | |||
Minimum of Months | 35675759.07 | 9862.17 | -13.2 | |
Maximum of Months | 0.876224E+10 | 27317.97 | 22.62 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353481E+09 | 529.75 | 07-JAN-19:32 | -2.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.353481E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.0 | |
Maximum of Months | 0.353481E+09 | 529.75 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.806866E+09 | 558.00 | 16-JAN-17:50 | 3.98 |
February | 40972460.78 | 515.48 | 27-FEB-04:02 | -0.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.847839E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.806866E+09 | 558.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.682457E+09 | 58396.83 | 14-JAN-17:41 | -5.7 |
February | 50543308.35 | 29803.39 | 06-FEB-23:11 | -8.3 |
March | 1111591.29 | 18526.52 | 04-MAR-16:51 | 7.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 52021233.73 | 41698.71 | 16-MAY-05:03 | 9.18 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 591521.95 | 3558.36 | 28-OCT-17:28 | 8.85 |
November | 843865.17 | 5685.21 | 18-NOV-19:51 | 4.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.787568E+09 | |||
Minimum of Months | 0.00 | 0.00 | -8.3 | |
Maximum of Months | 0.682457E+09 | 58396.83 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.176037E+11 | 18337.15 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.159674E+11 | 18337.15 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.189649E+11 | 18337.15 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.169484E+11 | 18337.15 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.182843E+11 | 18337.15 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.181926E+11 | 18337.15 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.170401E+11 | 18337.15 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.189649E+11 | 18337.15 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.169484E+11 | 18337.15 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.176037E+11 | 18337.15 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.173949E+11 | 18337.15 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.170401E+11 | 18337.15 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.210953E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.159674E+11 | 18337.15 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.189649E+11 | 18337.15 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.158093E+11 | 16468.05 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.143398E+11 | 16468.05 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.170318E+11 | 16468.05 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.152209E+11 | 16468.05 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.164206E+11 | 16468.05 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.163382E+11 | 16468.05 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.153032E+11 | 16468.05 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.170318E+11 | 16468.05 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.152209E+11 | 16468.05 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.158093E+11 | 16468.05 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.156219E+11 | 16468.05 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.153032E+11 | 16468.05 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.189451E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.143398E+11 | 16468.05 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.170318E+11 | 16468.05 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.162658E+10 | 2067.73 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143475E+10 | 1941.94 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166724E+10 | 1696.61 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146773E+10 | 1509.46 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156973E+10 | 1509.46 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155259E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145897E+10 | 1509.46 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.163311E+10 | 1509.46 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147735E+10 | 1576.58 | 27-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.155847E+10 | 1785.14 | 31-OCT-15:00 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.159247E+10 | 2067.73 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158624E+10 | 2067.73 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186252E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.143475E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166724E+10 | 2067.73 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.104565E+10 | 1332.52 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.923872E+09 | 1260.90 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107469E+10 | 1167.74 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.946741E+09 | 972.75 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101353E+10 | 972.75 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100250E+10 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.941858E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105391E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.952560E+09 | 972.75 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100405E+10 | 1158.04 | 31-OCT-15:00 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.102589E+10 | 1332.52 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101794E+10 | 1332.52 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120032E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.923872E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107469E+10 | 1332.52 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161134E+10 | 2067.77 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142605E+10 | 1933.03 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166410E+10 | 1613.03 | 02-MAR-16:00 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146868E+10 | 1509.49 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.157233E+10 | 1509.49 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.155556E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.146147E+10 | 1509.49 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163493E+10 | 1509.49 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147674E+10 | 1541.96 | 27-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.155341E+10 | 1745.63 | 31-OCT-15:00 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.158409E+10 | 2067.77 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.156728E+10 | 2067.77 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185760E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.142605E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166410E+10 | 2067.77 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.104062E+10 | 1332.52 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.920195E+09 | 1240.90 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107179E+10 | 1082.34 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.945974E+09 | 973.86 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101156E+10 | 972.75 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100093E+10 | 972.75 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.940627E+09 | 972.75 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105226E+10 | 972.75 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.951565E+09 | 1053.49 | 27-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100183E+10 | 1131.83 | 06-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.102140E+10 | 1332.52 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.101387E+10 | 1332.52 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119726E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.920195E+09 | 972.75 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107179E+10 | 1332.52 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.162811E+10 | 2067.73 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143581E+10 | 1945.71 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166769E+10 | 1707.54 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146802E+10 | 1509.46 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156991E+10 | 1509.46 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155284E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145924E+10 | 1509.46 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.163328E+10 | 1509.46 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147776E+10 | 1590.75 | 27-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.155907E+10 | 1793.48 | 31-OCT-15:00 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.159333E+10 | 2067.73 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158808E+10 | 2067.73 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186331E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.143581E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166769E+10 | 2067.73 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.104597E+10 | 1332.52 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.924120E+09 | 1261.48 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107482E+10 | 1168.97 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.946832E+09 | 972.75 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101359E+10 | 972.75 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100259E+10 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.941941E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105399E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.952684E+09 | 972.75 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100424E+10 | 1159.42 | 31-OCT-15:00 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.102608E+10 | 1332.52 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101830E+10 | 1332.52 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120052E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.924120E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107482E+10 | 1332.52 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161223E+10 | 2067.77 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142659E+10 | 1937.20 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166360E+10 | 1603.63 | 16-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146900E+10 | 1509.49 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.157258E+10 | 1509.49 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.155591E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.146181E+10 | 1509.49 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163515E+10 | 1509.49 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147711E+10 | 1557.41 | 27-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.155372E+10 | 1755.90 | 31-OCT-15:00 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.158463E+10 | 2067.77 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.156812E+10 | 2067.77 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185805E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.142659E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166360E+10 | 2067.77 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.104092E+10 | 1332.52 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.920411E+09 | 1241.89 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107193E+10 | 1084.24 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.946077E+09 | 976.08 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101163E+10 | 972.75 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100100E+10 | 972.75 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.940695E+09 | 972.75 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105235E+10 | 972.75 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.951710E+09 | 1055.57 | 27-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100192E+10 | 1133.35 | 06-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.102159E+10 | 1332.52 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.101424E+10 | 1332.52 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119745E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.920411E+09 | 972.75 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107193E+10 | 1332.52 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.162809E+10 | 2067.73 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.143581E+10 | 1945.63 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.166769E+10 | 1707.43 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.146802E+10 | 1509.46 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.156991E+10 | 1509.46 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.155284E+10 | 1509.46 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.145923E+10 | 1509.46 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.163328E+10 | 1509.46 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.147776E+10 | 1590.34 | 27-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.155907E+10 | 1793.22 | 31-OCT-15:00 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.159332E+10 | 2067.73 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.158808E+10 | 2067.73 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.186331E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.143581E+10 | 1509.46 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.166769E+10 | 2067.73 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.104597E+10 | 1332.52 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.924120E+09 | 1261.42 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.107482E+10 | 1168.89 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.946830E+09 | 972.75 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.101359E+10 | 972.75 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.100259E+10 | 972.75 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.941938E+09 | 972.75 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.105399E+10 | 972.75 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.952684E+09 | 972.75 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.100424E+10 | 1159.26 | 31-OCT-15:00 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.102608E+10 | 1332.52 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.101831E+10 | 1332.52 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.120052E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.924120E+09 | 972.75 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.107482E+10 | 1332.52 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161223E+10 | 2067.77 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.142659E+10 | 1937.08 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.166360E+10 | 1603.28 | 16-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.146900E+10 | 1509.49 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.157258E+10 | 1509.49 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.155590E+10 | 1509.49 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.146181E+10 | 1509.49 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.163515E+10 | 1509.49 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.147710E+10 | 1557.00 | 27-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.155373E+10 | 1755.66 | 31-OCT-15:00 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.158463E+10 | 2067.77 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.156812E+10 | 2067.77 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.185804E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.142659E+10 | 1509.49 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.166360E+10 | 2067.77 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.104092E+10 | 1332.52 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.920413E+09 | 1241.82 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.107193E+10 | 1084.01 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.946076E+09 | 975.87 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.101163E+10 | 972.75 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.100100E+10 | 972.75 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.940693E+09 | 972.75 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.105236E+10 | 972.75 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.951710E+09 | 1055.32 | 27-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.100192E+10 | 1133.16 | 06-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.102160E+10 | 1332.52 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.101424E+10 | 1332.52 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.119745E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.920413E+09 | 972.75 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.107193E+10 | 1332.52 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.496348E+10 | 5170.29 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.450211E+10 | 5170.29 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.534729E+10 | 5170.29 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.477873E+10 | 5170.29 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.515538E+10 | 5170.29 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.512953E+10 | 5170.29 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.480458E+10 | 5170.29 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.534729E+10 | 5170.29 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.477873E+10 | 5170.29 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.496348E+10 | 5170.29 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.490462E+10 | 5170.29 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.480458E+10 | 5170.29 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.594798E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.450211E+10 | 5170.29 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.534729E+10 | 5170.29 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.229292E+09 | 238.85 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.207979E+09 | 238.85 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.247022E+09 | 238.85 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.220757E+09 | 238.85 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.238157E+09 | 238.85 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.236963E+09 | 238.85 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.221952E+09 | 238.85 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.247022E+09 | 238.85 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.220757E+09 | 238.85 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.229292E+09 | 238.85 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.226573E+09 | 238.85 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.221952E+09 | 238.85 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.207979E+09 | 238.85 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.247022E+09 | 238.85 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.176037E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.159674E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.169484E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.182843E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.181926E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.170401E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.169484E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.176037E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.173949E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.170401E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.210953E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.159674E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.189649E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.164206E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.163382E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.152209E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.158093E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.156219E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.153032E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.189451E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.143398E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.170318E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162658E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159090E+10 |
February | 0.136985E+10 | 0.143475E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138404E+10 |
March | 0.163685E+10 | 0.166724E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115320E+10 |
April | 0.145243E+10 | 0.146773E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522877.56 | 0.767715E+09 |
May | 0.157338E+10 | 0.156973E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3115868.34 | 0.427061E+09 |
June | 0.156900E+10 | 0.155259E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18996897.43 | 0.208662E+09 |
July | 0.145680E+10 | 0.145897E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47351293.09 | 57384863.66 |
August | 0.163685E+10 | 0.163311E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56119450.70 | 75664461.59 |
September | 0.145243E+10 | 0.147735E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6496326.40 | 0.231280E+09 |
October | 0.150991E+10 | 0.155847E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99051.60 | 0.597389E+09 |
November | 0.149516E+10 | 0.159247E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116584E+10 |
December | 0.145680E+10 | 0.158624E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140031E+10 |
Annual Sum or Average | 0.181194E+11 | 0.186252E+11 | 0.403414E+11 | 0.132702E+09 | 0.905945E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.143475E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57384863.66 |
Maximum of Months | 0.163685E+10 | 0.166724E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56119450.70 | 0.159090E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104565E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103648E+10 |
February | 0.882782E+09 | 0.923872E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.906635E+09 |
March | 0.105485E+10 | 0.107469E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738388E+09 |
April | 0.936002E+09 | 0.946741E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 397270.67 | 0.485219E+09 |
May | 0.101394E+10 | 0.101353E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2016026.09 | 0.273668E+09 |
June | 0.101113E+10 | 0.100250E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15529060.31 | 0.121020E+09 |
July | 0.938820E+09 | 0.941858E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42755609.82 | 22811004.81 |
August | 0.105485E+10 | 0.105391E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47453333.30 | 34642562.03 |
September | 0.936002E+09 | 0.952560E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5363257.82 | 0.145042E+09 |
October | 0.973041E+09 | 0.100405E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66392.55 | 0.381080E+09 |
November | 0.963541E+09 | 0.102589E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.744708E+09 |
December | 0.938820E+09 | 0.101794E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890745E+09 |
Annual Sum or Average | 0.116768E+11 | 0.120032E+11 | 0.259975E+11 | 0.113581E+09 | 0.578043E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.923872E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22811004.81 |
Maximum of Months | 0.105485E+10 | 0.107469E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47453333.30 | 0.103648E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.161134E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156271E+10 |
February | 0.136988E+10 | 0.142605E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139431E+10 |
March | 0.163688E+10 | 0.166410E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114135E+10 |
April | 0.145246E+10 | 0.146868E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522862.65 | 0.751913E+09 |
May | 0.157341E+10 | 0.157233E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2853860.62 | 0.418832E+09 |
June | 0.156904E+10 | 0.155556E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18931287.68 | 0.203518E+09 |
July | 0.145684E+10 | 0.146147E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47268531.32 | 55272210.67 |
August | 0.163688E+10 | 0.163493E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54326777.46 | 76489172.36 |
September | 0.145246E+10 | 0.147674E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5781672.41 | 0.239720E+09 |
October | 0.150994E+10 | 0.155341E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41758.92 | 0.621926E+09 |
November | 0.149520E+10 | 0.158409E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115283E+10 |
December | 0.145684E+10 | 0.156728E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138023E+10 |
Annual Sum or Average | 0.181198E+11 | 0.185760E+11 | 0.403420E+11 | 0.129727E+09 | 0.899910E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.142605E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55272210.67 |
Maximum of Months | 0.163688E+10 | 0.166410E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54326777.46 | 0.156271E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104062E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108097E+10 |
February | 0.882782E+09 | 0.920195E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959844E+09 |
March | 0.105485E+10 | 0.107179E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822326E+09 |
April | 0.936002E+09 | 0.945974E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 345307.26 | 0.563867E+09 |
May | 0.101394E+10 | 0.101156E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2493887.72 | 0.299940E+09 |
June | 0.101113E+10 | 0.100093E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12061979.65 | 0.157763E+09 |
July | 0.938820E+09 | 0.940627E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29730103.96 | 51780232.46 |
August | 0.105485E+10 | 0.105226E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33813200.26 | 64716619.82 |
September | 0.936002E+09 | 0.951565E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4715229.89 | 0.166268E+09 |
October | 0.973041E+09 | 0.100183E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65440.78 | 0.430012E+09 |
November | 0.963541E+09 | 0.102140E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.830259E+09 |
December | 0.938820E+09 | 0.101387E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100607E+10 |
Annual Sum or Average | 0.116768E+11 | 0.119726E+11 | 0.259973E+11 | 83225149.52 | 0.643381E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.920195E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51780232.46 |
Maximum of Months | 0.105485E+10 | 0.107179E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33813200.26 | 0.108097E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162811E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310771E+10 |
February | 0.136985E+10 | 0.143581E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275531E+10 |
March | 0.163685E+10 | 0.166769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226421E+10 |
April | 0.145243E+10 | 0.146802E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1177192.44 | 0.151415E+10 |
May | 0.157338E+10 | 0.156991E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8184455.86 | 0.884478E+09 |
June | 0.156900E+10 | 0.155284E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41356078.86 | 0.449168E+09 |
July | 0.145680E+10 | 0.145924E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100284E+09 | 0.151454E+09 |
August | 0.163685E+10 | 0.163328E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114903E+09 | 0.199814E+09 |
September | 0.145243E+10 | 0.147776E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15818945.53 | 0.467449E+09 |
October | 0.150991E+10 | 0.155907E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172964.11 | 0.117761E+10 |
November | 0.149516E+10 | 0.159333E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222014E+10 |
December | 0.145680E+10 | 0.158808E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266580E+10 |
Annual Sum or Average | 0.181194E+11 | 0.186331E+11 | 0.403414E+11 | 0.281897E+09 | 0.178573E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.143581E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151454E+09 |
Maximum of Months | 0.163685E+10 | 0.166769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114903E+09 | 0.310771E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.104597E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207055E+10 |
February | 0.649041E+09 | 0.924120E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185756E+10 |
March | 0.773965E+09 | 0.107482E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151322E+10 |
April | 0.688021E+09 | 0.946832E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 898417.91 | 0.102320E+10 |
May | 0.744847E+09 | 0.101359E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4156926.27 | 0.581303E+09 |
June | 0.742030E+09 | 0.100259E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31472964.44 | 0.280130E+09 |
July | 0.690839E+09 | 0.941941E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77278144.76 | 89764883.17 |
August | 0.773965E+09 | 0.105399E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83798893.33 | 0.127017E+09 |
September | 0.688021E+09 | 0.952684E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12481831.70 | 0.304345E+09 |
October | 0.715730E+09 | 0.100424E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 173386.83 | 0.780498E+09 |
November | 0.708685E+09 | 0.102608E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148020E+10 |
December | 0.690839E+09 | 0.101830E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177956E+10 |
Annual Sum or Average | 0.858171E+10 | 0.120052E+11 | 0.259975E+11 | 0.210261E+09 | 0.118874E+11 | ||||
Minimum of Months | 0.649041E+09 | 0.924120E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89764883.17 |
Maximum of Months | 0.773965E+09 | 0.107482E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83798893.33 | 0.207055E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.161223E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322624E+10 |
February | 0.136988E+10 | 0.142659E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294675E+10 |
March | 0.163688E+10 | 0.166360E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239070E+10 |
April | 0.145246E+10 | 0.146900E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1107241.88 | 0.157343E+10 |
May | 0.157341E+10 | 0.157258E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6565200.27 | 0.896224E+09 |
June | 0.156904E+10 | 0.155591E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40218032.67 | 0.449659E+09 |
July | 0.145684E+10 | 0.146181E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96785626.97 | 0.155097E+09 |
August | 0.163688E+10 | 0.163515E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107545E+09 | 0.214569E+09 |
September | 0.145246E+10 | 0.147711E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11820305.96 | 0.524287E+09 |
October | 0.150994E+10 | 0.155372E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61881.71 | 0.134250E+10 |
November | 0.149520E+10 | 0.158463E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237988E+10 |
December | 0.145684E+10 | 0.156812E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284339E+10 |
Annual Sum or Average | 0.181198E+11 | 0.185805E+11 | 0.403420E+11 | 0.264104E+09 | 0.189427E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.142659E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155097E+09 |
Maximum of Months | 0.163688E+10 | 0.166360E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107545E+09 | 0.322624E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104092E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211454E+10 |
February | 0.882782E+09 | 0.920411E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188640E+10 |
March | 0.105485E+10 | 0.107193E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157250E+10 |
April | 0.936002E+09 | 0.946077E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1019399.73 | 0.105912E+10 |
May | 0.101394E+10 | 0.101163E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6410211.67 | 0.608165E+09 |
June | 0.101113E+10 | 0.100100E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28322447.02 | 0.322574E+09 |
July | 0.938820E+09 | 0.940695E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70437632.49 | 0.122903E+09 |
August | 0.105485E+10 | 0.105235E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75617664.53 | 0.159272E+09 |
September | 0.936002E+09 | 0.951710E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12042759.74 | 0.323171E+09 |
October | 0.973041E+09 | 0.100192E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 320687.07 | 0.820331E+09 |
November | 0.963541E+09 | 0.102159E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150269E+10 |
December | 0.938820E+09 | 0.101424E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182398E+10 |
Annual Sum or Average | 0.116768E+11 | 0.119745E+11 | 0.259973E+11 | 0.194171E+09 | 0.123157E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.920411E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122903E+09 |
Maximum of Months | 0.105485E+10 | 0.107193E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75617664.53 | 0.211454E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.162809E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368606E+10 |
February | 0.136985E+10 | 0.143581E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326965E+10 |
March | 0.163685E+10 | 0.166769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261201E+10 |
April | 0.145243E+10 | 0.146802E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1406337.88 | 0.173596E+10 |
May | 0.157338E+10 | 0.156991E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9569113.35 | 0.104321E+10 |
June | 0.156900E+10 | 0.155284E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46945931.69 | 0.553808E+09 |
July | 0.145680E+10 | 0.145923E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115340E+09 | 0.196043E+09 |
August | 0.163685E+10 | 0.163328E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135434E+09 | 0.250671E+09 |
September | 0.145243E+10 | 0.147776E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18414833.76 | 0.545597E+09 |
October | 0.150991E+10 | 0.155907E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160790.02 | 0.133106E+10 |
November | 0.149516E+10 | 0.159332E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248723E+10 |
December | 0.145680E+10 | 0.158808E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305781E+10 |
Annual Sum or Average | 0.181194E+11 | 0.186331E+11 | 0.403414E+11 | 0.327271E+09 | 0.207691E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.143581E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196043E+09 |
Maximum of Months | 0.163685E+10 | 0.166769E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135434E+09 | 0.368606E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104597E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246266E+10 |
February | 0.882782E+09 | 0.924120E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219947E+10 |
March | 0.105485E+10 | 0.107482E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175648E+10 |
April | 0.936002E+09 | 0.946830E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 973414.56 | 0.119114E+10 |
May | 0.101394E+10 | 0.101359E+10 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4747553.28 | 0.696740E+09 |
June | 0.101113E+10 | 0.100259E+10 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35277278.49 | 0.350822E+09 |
July | 0.938820E+09 | 0.941938E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88135652.19 | 0.118360E+09 |
August | 0.105485E+10 | 0.105399E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97052177.84 | 0.162442E+09 |
September | 0.936002E+09 | 0.952684E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13634686.71 | 0.363172E+09 |
October | 0.973041E+09 | 0.100424E+10 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 117250.37 | 0.901119E+09 |
November | 0.963541E+09 | 0.102608E+10 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167125E+10 |
December | 0.938820E+09 | 0.101831E+10 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204860E+10 |
Annual Sum or Average | 0.116768E+11 | 0.120052E+11 | 0.259975E+11 | 0.239938E+09 | 0.139223E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.924120E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118360E+09 |
Maximum of Months | 0.105485E+10 | 0.107482E+10 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97052177.84 | 0.246266E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.161223E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379138E+10 |
February | 0.136988E+10 | 0.142659E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343175E+10 |
March | 0.163688E+10 | 0.166360E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275948E+10 |
April | 0.145246E+10 | 0.146900E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1304300.17 | 0.181094E+10 |
May | 0.157341E+10 | 0.157258E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7860037.94 | 0.105650E+10 |
June | 0.156904E+10 | 0.155590E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46647969.26 | 0.552429E+09 |
July | 0.145684E+10 | 0.146181E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113826E+09 | 0.199604E+09 |
August | 0.163688E+10 | 0.163515E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128681E+09 | 0.267905E+09 |
September | 0.145246E+10 | 0.147710E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14480357.23 | 0.616699E+09 |
October | 0.150994E+10 | 0.155373E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68395.65 | 0.155250E+10 |
November | 0.149520E+10 | 0.158463E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266638E+10 |
December | 0.145684E+10 | 0.156812E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323819E+10 |
Annual Sum or Average | 0.181198E+11 | 0.185804E+11 | 0.403420E+11 | 0.312868E+09 | 0.219438E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.142659E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199604E+09 |
Maximum of Months | 0.163688E+10 | 0.166360E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128681E+09 | 0.379138E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.104092E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250787E+10 |
February | 0.882782E+09 | 0.920413E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224347E+10 |
March | 0.105485E+10 | 0.107193E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184201E+10 |
April | 0.936002E+09 | 0.946076E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1232274.28 | 0.123971E+10 |
May | 0.101394E+10 | 0.101163E+10 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8017649.80 | 0.724212E+09 |
June | 0.101113E+10 | 0.100100E+10 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34022880.45 | 0.394492E+09 |
July | 0.938820E+09 | 0.940693E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85950871.61 | 0.154298E+09 |
August | 0.105485E+10 | 0.105236E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91996809.94 | 0.196818E+09 |
September | 0.936002E+09 | 0.951710E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14911729.46 | 0.382200E+09 |
October | 0.973041E+09 | 0.100192E+10 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 429565.61 | 0.954260E+09 |
November | 0.963541E+09 | 0.102160E+10 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171808E+10 |
December | 0.938820E+09 | 0.101424E+10 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211826E+10 |
Annual Sum or Average | 0.116768E+11 | 0.119745E+11 | 0.259973E+11 | 0.236562E+09 | 0.144757E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.920413E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154298E+09 |
Maximum of Months | 0.105485E+10 | 0.107193E+10 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91996809.94 | 0.250787E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.496348E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.450211E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.534729E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.477873E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.515538E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.512953E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.480458E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.534729E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.477873E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.496348E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.490462E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.480458E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.594798E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.450211E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.534729E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.229292E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.207979E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.247022E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.220757E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.238157E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.236963E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.221952E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.220757E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.229292E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.226573E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.221952E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274772E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.207979E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.247022E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328741E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286292E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234756E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613245.37 | 0.156083E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5254325.00 | 0.863201E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29683016.55 | 0.425504E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76330216.67 | 0.124351E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85995574.02 | 0.172389E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8132384.45 | 0.471639E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5733.64 | 0.123189E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237983E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287829E+10 |
Annual Sum or Average | 0.206014E+09 | 0.186058E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124351E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85995574.02 | 0.328741E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.531743E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480850E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395175E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1304534.47 | 0.262248E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12509032.03 | 0.148206E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57275526.33 | 0.729461E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144546E+09 | 0.218213E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154001E+09 | 0.317828E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15787846.18 | 0.796146E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25319.37 | 0.209013E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395111E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474589E+10 |
Annual Sum or Average | 0.385449E+09 | 0.310310E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218213E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154001E+09 | 0.531743E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555038E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499047E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.417492E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204808.95 | 0.280779E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4429458.14 | 0.168307E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38556478.95 | 0.880795E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102912E+09 | 0.288601E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133284E+09 | 0.377231E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11114705.17 | 0.881131E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220340E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397627E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475983E+10 |
Annual Sum or Average | 0.290501E+09 | 0.325739E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288601E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133284E+09 | 0.555038E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 18337.15 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 18337.15 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 18337.15 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 18337.15 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 18337.15 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 18337.15 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 18337.15 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 18337.15 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 18337.15 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 18337.15 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 18337.15 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 18337.15 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 18337.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 18337.15 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 16468.05 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 16468.05 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 16468.05 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 16468.05 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 16468.05 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 16468.05 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 16468.05 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 16468.05 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 16468.05 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 16468.05 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 16468.05 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 16468.05 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2067.73 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2658.67 | 31-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 1941.94 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2654.20 | 06-FEB-00:52 |
March | 2010.79 | 01-MAR-10:09 | 1696.61 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2070.58 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 1509.46 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 07-APR-13:00 | 1605.60 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 1509.46 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.46 | 29-MAY-12:00 | 962.80 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.05 | 19-JUN-21:02 | 540.79 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1509.46 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 250.85 | 09-JUL-14:00 | 225.09 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1509.46 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 308.46 | 12-AUG-18:52 | 359.11 | 20-AUG-05:55 |
September | 2010.79 | 01-SEP-09:09 | 1576.58 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 14-SEP-14:00 | 497.69 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 1785.14 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 25-OCT-11:00 | 1407.97 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 2067.73 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2206.13 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2067.73 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2859.02 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.09 | |||||
Maximum of Months | 2010.79 | 2067.73 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 308.46 | 2859.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1739.66 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 1260.90 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1834.24 | 05-FEB-08:40 |
March | 1295.83 | 01-MAR-10:09 | 1167.74 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1470.84 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 972.75 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.77 | 07-APR-17:00 | 1013.40 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.72 | 29-MAY-12:10 | 619.12 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.50 | 25-JUN-19:00 | 342.63 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 190.40 | 09-JUL-14:00 | 130.39 | 11-JUL-05:00 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.45 | 12-AUG-18:52 | 227.48 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 972.75 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 14-SEP-14:00 | 319.39 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1158.04 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 25-OCT-11:00 | 1011.00 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1426.92 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1854.62 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.39 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 243.45 | 1854.62 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2067.77 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2661.21 | 31-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 1933.03 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2588.39 | 05-FEB-10:00 |
March | 2010.83 | 01-MAR-10:09 | 1613.03 | 02-MAR-16:00 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2175.95 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1509.49 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.64 | 07-APR-13:00 | 1583.35 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 1509.49 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.97 | 29-MAY-12:00 | 946.62 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.67 | 19-JUN-21:02 | 537.06 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1509.49 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.49 | 09-JUL-14:00 | 219.46 | 11-JUL-05:00 |
August | 2010.83 | 01-AUG-09:09 | 1509.49 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.93 | 12-AUG-18:52 | 358.31 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 1541.96 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.78 | 14-SEP-14:00 | 491.44 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1745.63 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 25-OCT-11:00 | 1411.25 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 2067.77 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2175.02 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2067.77 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2785.26 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.46 | |||||
Maximum of Months | 2010.83 | 2067.77 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 310.93 | 2785.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1807.78 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 1240.90 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1832.00 | 05-FEB-08:00 |
March | 1295.83 | 01-MAR-10:09 | 1082.34 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1525.71 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 973.86 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 07-APR-13:00 | 1173.04 | 11-APR-03:50 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.63 | 29-MAY-12:10 | 684.70 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.95 | 19-JUN-21:02 | 416.57 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.45 | 09-JUL-14:00 | 220.82 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.15 | 12-AUG-18:52 | 293.88 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 1053.49 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 14-SEP-14:00 | 363.02 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1131.83 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 25-OCT-11:00 | 1004.33 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1558.82 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2052.32 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.82 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 186.15 | 2052.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2067.73 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5201.71 | 31-JAN-00:53 |
February | 2010.79 | 01-FEB-10:09 | 1945.71 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5374.57 | 06-FEB-00:58 |
March | 2010.79 | 01-MAR-10:09 | 1707.54 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4087.34 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1509.46 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 | 07-APR-13:00 | 3188.11 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 1509.46 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 408.65 | 29-MAY-12:10 | 1922.15 | 03-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.18 | 19-JUN-21:02 | 1121.98 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1509.46 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 549.88 | 09-JUL-13:52 | 502.54 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1509.46 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 641.10 | 04-AUG-21:02 | 745.35 | 20-AUG-05:55 |
September | 2010.79 | 01-SEP-09:09 | 1590.75 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.44 | 14-SEP-14:00 | 980.97 | 23-SEP-03:51 |
October | 2010.79 | 02-OCT-09:09 | 1793.48 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 25-OCT-11:00 | 2639.21 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 2067.73 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4217.33 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 2067.73 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5341.45 | 31-DEC-21:55 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.54 | |||||
Maximum of Months | 2010.79 | 2067.73 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 641.10 | 5374.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1332.52 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3472.39 | 31-JAN-00:53 |
February | 1239.33 | 01-FEB-08:09 | 1261.48 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3583.09 | 06-FEB-00:58 |
March | 1239.33 | 01-MAR-08:09 | 1168.97 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2748.32 | 12-MAR-10:00 |
April | 1239.33 | 03-APR-07:10 | 972.75 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 | 07-APR-17:00 | 2104.64 | 11-APR-03:53 |
May | 1239.33 | 01-MAY-07:10 | 972.75 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.29 | 29-MAY-12:10 | 1276.17 | 03-MAY-03:55 |
June | 1239.33 | 01-JUN-07:10 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 364.89 | 25-JUN-19:00 | 723.95 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 380.09 | 09-JUL-13:50 | 326.44 | 11-JUL-05:00 |
August | 1239.33 | 01-AUG-07:10 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 471.94 | 04-AUG-21:02 | 523.51 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 972.75 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.29 | 14-SEP-14:00 | 660.08 | 10-SEP-08:10 |
October | 1239.33 | 02-OCT-07:10 | 1159.42 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.70 | 25-OCT-14:00 | 1961.88 | 08-OCT-08:00 |
November | 1239.33 | 01-NOV-07:10 | 1332.52 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2816.91 | 23-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1332.52 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3578.76 | 31-DEC-21:53 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.44 | |||||
Maximum of Months | 1239.33 | 1332.52 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 471.94 | 3583.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2067.77 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5502.37 | 31-JAN-00:53 |
February | 2010.83 | 01-FEB-10:09 | 1937.20 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5374.56 | 06-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1603.63 | 16-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4219.03 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1509.49 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 | 07-APR-13:00 | 3257.37 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 1509.49 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 324.04 | 29-MAY-12:10 | 1957.34 | 03-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.31 | 19-JUN-21:02 | 1121.32 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1509.49 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 505.40 | 09-JUL-13:52 | 501.34 | 11-JUL-05:00 |
August | 2010.83 | 01-AUG-09:09 | 1509.49 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 639.16 | 04-AUG-21:02 | 770.62 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 1557.41 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.71 | 14-SEP-14:00 | 1079.40 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1755.90 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.42 | 25-OCT-11:00 | 2834.68 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 2067.77 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4383.69 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 2067.77 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5398.07 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.34 | |||||
Maximum of Months | 2010.83 | 2067.77 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 639.16 | 5502.37 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3524.77 | 31-JAN-00:53 |
February | 1295.83 | 01-FEB-10:09 | 1241.89 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3583.08 | 06-FEB-00:52 |
March | 1295.83 | 01-MAR-10:09 | 1084.24 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2746.16 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 976.08 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 | 07-APR-13:00 | 2218.72 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 365.60 | 29-MAY-12:10 | 1346.10 | 03-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 315.54 | 19-JUN-21:02 | 816.46 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.24 | 09-JUL-13:42 | 465.81 | 02-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.05 | 04-AUG-21:02 | 558.70 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 1055.57 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 136.23 | 04-SEP-13:20 | 705.20 | 30-SEP-24:00 |
October | 1295.83 | 02-OCT-09:09 | 1133.35 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.37 | 25-OCT-11:00 | 1811.48 | 17-OCT-24:00 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2855.60 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3567.00 | 31-DEC-21:53 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.81 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 431.05 | 3583.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 2067.73 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6221.92 | 14-JAN-06:00 |
February | 2010.79 | 01-FEB-10:09 | 1945.63 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6633.44 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1707.43 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5061.01 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1509.46 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.96 | 07-APR-13:00 | 3644.10 | 11-APR-03:53 |
May | 2010.79 | 01-MAY-09:09 | 1509.46 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.60 | 29-MAY-11:53 | 2189.99 | 03-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1509.46 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.45 | 19-JUN-21:02 | 1344.46 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1509.46 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.26 | 09-JUL-13:52 | 613.57 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1509.46 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 826.34 | 12-AUG-19:00 | 870.78 | 20-AUG-05:55 |
September | 2010.79 | 01-SEP-09:09 | 1590.34 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.61 | 14-SEP-14:00 | 1134.43 | 23-SEP-03:51 |
October | 2010.79 | 02-OCT-09:09 | 1793.22 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-OCT-11:00 | 2996.98 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 2067.73 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4954.23 | 22-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 2067.73 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6534.33 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.57 | |||||
Maximum of Months | 2010.79 | 2067.73 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 826.34 | 6633.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4326.15 | 14-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1261.42 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4465.65 | 06-FEB-00:58 |
March | 1295.83 | 01-MAR-10:09 | 1168.89 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3376.56 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 972.75 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.64 | 07-APR-13:00 | 2411.80 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 258.14 | 29-MAY-12:20 | 1462.01 | 03-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 444.90 | 25-JUN-19:10 | 872.63 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 417.58 | 09-JUL-13:50 | 402.39 | 11-JUL-05:00 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 643.18 | 12-AUG-19:00 | 613.99 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 972.75 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.41 | 14-SEP-14:00 | 759.23 | 10-SEP-08:20 |
October | 1295.83 | 02-OCT-09:09 | 1159.26 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 25-OCT-11:00 | 2064.92 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3303.70 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4355.54 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 402.39 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 643.18 | 4465.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 2067.77 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6379.08 | 14-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 1937.08 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6698.36 | 06-FEB-00:58 |
March | 2010.83 | 01-MAR-10:09 | 1603.28 | 16-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5089.90 | 21-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1509.49 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.95 | 07-APR-13:00 | 3726.82 | 11-APR-03:53 |
May | 2010.83 | 01-MAY-09:09 | 1509.49 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.41 | 29-MAY-11:53 | 2234.81 | 03-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 1509.49 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 551.47 | 19-JUN-21:02 | 1341.76 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1509.49 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.69 | 09-JUL-13:42 | 615.03 | 23-JUL-17:53 |
August | 2010.83 | 01-AUG-09:09 | 1509.49 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 830.35 | 12-AUG-19:00 | 901.03 | 20-AUG-05:55 |
September | 2010.83 | 01-SEP-09:09 | 1557.00 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.36 | 14-SEP-14:00 | 1240.74 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1755.66 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.73 | 25-OCT-11:00 | 3224.43 | 17-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 2067.77 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4970.95 | 22-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 2067.77 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6553.79 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 615.03 | |||||
Maximum of Months | 2010.83 | 2067.77 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 830.35 | 6698.36 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1332.52 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4326.16 | 14-JAN-05:55 |
February | 1295.83 | 01-FEB-10:09 | 1241.82 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4465.67 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1084.01 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3400.38 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 975.87 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.03 | 07-APR-13:00 | 2550.31 | 11-APR-03:53 |
May | 1295.83 | 01-MAY-09:09 | 972.75 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 432.68 | 29-MAY-12:20 | 1550.15 | 03-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 972.75 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.99 | 19-JUN-21:02 | 1024.59 | 03-JUN-17:06 |
July | 1295.83 | 03-JUL-09:09 | 972.75 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 481.10 | 09-JUL-13:42 | 603.18 | 02-JUL-17:30 |
August | 1295.83 | 01-AUG-09:09 | 972.75 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 580.35 | 12-AUG-19:00 | 653.08 | 20-AUG-05:55 |
September | 1295.83 | 01-SEP-09:09 | 1055.32 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.30 | 04-SEP-12:50 | 817.89 | 30-SEP-24:00 |
October | 1295.83 | 02-OCT-09:09 | 1133.16 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 | 25-OCT-11:00 | 2082.18 | 17-OCT-24:00 |
November | 1295.83 | 01-NOV-09:09 | 1332.52 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3309.82 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1332.52 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4372.34 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 603.18 | |||||
Maximum of Months | 1295.83 | 1332.52 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 580.35 | 4465.67 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 5170.29 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 5170.29 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 5170.29 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 5170.29 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 5170.29 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 5170.29 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 5170.29 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 5170.29 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 5170.29 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 5170.29 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 5170.29 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 5170.29 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 5170.29 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 5170.29 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 238.85 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 238.85 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 238.85 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 238.85 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 238.85 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 238.85 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 238.85 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 238.85 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 238.85 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 238.85 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 238.85 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 238.85 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5595.59 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5598.24 | 06-FEB-00:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4161.19 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.42 | 07-APR-13:00 | 3356.43 | 11-APR-03:55 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.47 | 29-MAY-12:00 | 1984.10 | 03-MAY-03:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.79 | 19-JUN-21:02 | 1073.38 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.18 | 09-JUL-14:00 | 446.71 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.56 | 12-AUG-18:52 | 709.93 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.65 | 14-SEP-14:00 | 968.60 | 23-SEP-03:51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 | 25-OCT-11:00 | 2899.71 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4638.34 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5988.74 | 31-DEC-21:52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.71 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 567.56 | 5988.74 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9479.90 | 31-JAN-00:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9346.66 | 05-FEB-08:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6869.12 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.44 | 07-APR-13:00 | 5735.67 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 600.83 | 29-MAY-11:53 | 3404.97 | 03-MAY-03:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.39 | 19-JUN-21:02 | 1875.76 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.28 | 09-JUL-13:52 | 796.04 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.81 | 12-AUG-18:52 | 1246.89 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.77 | 14-SEP-14:00 | 1672.14 | 23-SEP-03:51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | 25-OCT-11:00 | 4902.55 | 08-OCT-07:55 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7827.52 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9594.27 | 31-DEC-21:52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 796.04 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 986.81 | 9594.27 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9598.82 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9262.40 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7730.69 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.88 | 08-APR-10:00 | 5866.82 | 11-APR-03:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.08 | 29-MAY-11:53 | 3540.92 | 03-MAY-03:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.18 | 19-JUN-21:02 | 1945.71 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 666.15 | 07-JUL-22:00 | 864.16 | 11-JUL-04:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1076.98 | 12-AUG-19:00 | 1272.91 | 20-AUG-05:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.65 | 14-SEP-14:00 | 1757.70 | 23-SEP-03:51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4844.10 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7648.60 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9388.24 | 31-DEC-21:52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.16 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1076.98 | 9598.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 108607.89 | 26-JAN-05:50 | 0.00 | 6623.73 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 112381.52 | 21-FEB-03:52 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 109948.62 | 28-MAR-03:50 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 110876.41 | 11-APR-03:50 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 114938.87 | 01-MAY-02:41 | 0.00 | 11039.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 105776.45 | 03-JUN-03:53 | 0.00 | 3311.87 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 96356.98 | 11-JUL-03:01 | 0.00 | 11039.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99920.61 | 20-AUG-23:08 | 0.00 | 4415.82 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 110643.64 | 11-SEP-02:32 | 0.00 | 5519.78 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 114047.69 | 09-OCT-10:50 | 2692.84 | 3056.19 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 114900.47 | 12-NOV-15:10 | 4488.06 | 5093.65 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 115229.61 | 25-DEC-14:30 | 4488.06 | 5093.65 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 96356.98 | 0.00 | 3056.19 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 115229.61 | 4488.06 | 11039.56 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 63497.33 | 25-JAN-06:02 | 8061.19 | 9148.91 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67514.34 | 21-FEB-04:02 | 0.00 | 5948.58 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 71488.59 | 27-MAR-03:02 | 0.00 | 8922.87 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 81199.60 | 28-APR-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 88765.11 | 30-MAY-03:03 | 0.00 | 5948.58 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 87365.56 | 28-JUN-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 83576.70 | 19-JUL-03:01 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80563.46 | 07-AUG-05:02 | 16122.38 | 18297.83 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 94782.99 | 06-SEP-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 87721.69 | 06-OCT-03:02 | 0.00 | 9914.30 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73265.07 | 13-NOV-04:02 | 0.00 | 4957.15 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 71543.52 | 26-DEC-04:02 | 0.00 | 7931.44 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 63497.33 | 0.00 | 4957.15 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 94782.99 | 16122.38 | 18297.83 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 53271.01 | 30-JAN-11:40 | 61265.06 | 65872.18 | 72514.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 54344.17 | 22-FEB-10:10 | 64058.32 | 65872.18 | 72514.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 58312.66 | 29-MAR-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65263.45 | 28-APR-04:02 | 0.00 | 11897.16 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 79046.43 | 30-MAY-04:02 | 0.00 | 19828.60 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79708.49 | 17-JUN-04:02 | 0.00 | 9914.30 | 60428.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80158.55 | 26-JUL-03:01 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85568.68 | 07-AUG-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78061.04 | 02-SEP-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74895.83 | 06-OCT-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65819.27 | 10-NOV-06:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 78025.75 | 21-DEC-17:35 | 9673.43 | 18297.83 | 20142.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 53271.01 | 0.00 | 9914.30 | 20142.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 85568.68 | 64058.32 | 65872.18 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 21217.01 | 20-JAN-17:00 | 30632.53 | 32936.09 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22100.29 | 24-FEB-17:00 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 34323.76 | 03-MAR-17:00 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 65216.77 | 08-APR-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76079.95 | 30-MAY-03:02 | 0.00 | 5948.58 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 89808.34 | 20-JUN-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 89221.49 | 24-JUL-03:03 | 0.00 | 5948.58 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 89163.94 | 18-AUG-03:02 | 0.00 | 9914.30 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80765.02 | 06-SEP-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74950.83 | 06-OCT-05:02 | 16122.38 | 18297.83 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 33787.35 | 03-NOV-16:00 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20148.17 | 21-DEC-16:20 | 15316.26 | 16468.05 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20148.17 | 0.00 | 5948.58 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89808.34 | 30632.53 | 32936.09 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2911.58 | 17-JAN-09:55 | 3846.22 | 3018.92 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.56 |
February | 3277.05 | 22-FEB-10:10 | 8043.16 | 6037.85 | 9105.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.52 |
March | 6245.23 | 27-MAR-13:30 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 |
April | 8529.47 | 10-APR-05:03 | 809.73 | 918.99 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 |
May | 11263.46 | 30-MAY-03:02 | 0.00 | 746.90 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.25 |
June | 11290.14 | 19-JUN-05:01 | 2024.33 | 1677.18 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 0.00 |
July | 12919.08 | 10-JUL-03:01 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 0.00 |
August | 12108.30 | 04-AUG-05:02 | 2024.33 | 2234.67 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 | 0.00 |
September | 12361.63 | 14-SEP-03:01 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.36 |
October | 9264.05 | 14-OCT-05:01 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.58 |
November | 5228.65 | 03-NOV-13:40 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 |
December | 3980.72 | 26-DEC-13:30 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2911.58 | 0.00 | 746.90 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12919.08 | 8043.16 | 6037.85 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 277.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3729.66 | 17-JAN-09:55 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.51 |
February | 5473.91 | 22-FEB-09:15 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.47 |
March | 8017.30 | 29-MAR-08:40 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
April | 14352.69 | 23-APR-08:13 | 260.91 | 216.17 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.36 |
May | 18340.05 | 29-MAY-09:01 | 652.28 | 540.42 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 |
June | 18052.34 | 25-JUN-08:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.24 |
July | 18705.76 | 02-JUL-08:12 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 |
August | 11933.53 | 02-AUG-08:30 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 0.00 |
September | 18429.37 | 04-SEP-08:11 | 652.28 | 540.42 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.06 |
October | 8797.52 | 03-OCT-08:40 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.09 |
November | 5463.16 | 02-NOV-08:50 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.78 |
December | 3954.97 | 20-DEC-09:15 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.71 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3729.66 | 260.91 | 216.17 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18705.76 | 2478.65 | 1945.51 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 347.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11373.10 | 05-JAN-11:30 | 3846.30 | 3018.99 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.25 |
February | 13411.94 | 20-FEB-12:53 | 303.66 | 251.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.06 |
March | 12645.81 | 01-MAR-13:30 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.30 |
April | 13024.06 | 07-APR-12:30 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 0.00 |
May | 12803.20 | 30-MAY-03:02 | 0.00 | 746.92 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.34 |
June | 12172.21 | 12-JUN-05:03 | 809.75 | 806.89 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.21 |
July | 16708.18 | 30-JUL-12:52 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 | 0.00 |
August | 14438.04 | 30-AUG-12:20 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 13.99 | 0.00 |
September | 17912.57 | 04-SEP-12:51 | 1012.19 | 838.61 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.61 |
October | 18244.45 | 22-OCT-12:22 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.09 |
November | 13754.33 | 02-NOV-13:20 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.55 |
December | 15267.35 | 17-DEC-12:02 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11373.10 | 0.00 | 251.58 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18244.45 | 3846.30 | 3018.99 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 553.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6012.55 | 20-JAN-15:50 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 |
February | 8390.17 | 24-FEB-15:30 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.24 |
March | 14089.89 | 27-MAR-03:01 | 0.00 | 722.00 | 5867.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.42 |
April | 22298.16 | 16-APR-17:22 | 0.00 | 292.81 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.11 |
May | 19205.79 | 14-MAY-16:22 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.84 |
June | 22869.97 | 25-JUN-16:12 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.99 |
July | 24537.53 | 04-JUL-16:11 | 456.59 | 378.29 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.24 |
August | 22641.99 | 13-AUG-15:32 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 49.55 | 0.00 |
September | 23341.93 | 10-SEP-15:42 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.77 |
October | 18275.17 | 06-OCT-03:01 | 0.00 | 802.22 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.89 |
November | 14461.63 | 04-NOV-03:01 | 0.00 | 802.22 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 |
December | 9028.97 | 26-DEC-04:01 | 0.00 | 641.78 | 5215.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.07 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6012.55 | 0.00 | 270.21 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24537.53 | 1239.33 | 972.75 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 49.55 | 359.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3734.55 | 27-JAN-13:20 | 3846.22 | 3018.92 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.17 |
February | 3893.83 | 17-FEB-17:40 | 1821.89 | 3446.21 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.04 |
March | 4113.26 | 22-MAR-16:10 | 1214.60 | 1677.18 | 2529.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.62 |
April | 5495.09 | 07-APR-15:20 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 | 0.00 |
May | 10327.33 | 31-MAY-05:02 | 2024.33 | 1677.18 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11762.99 | 22-JUN-05:02 | 2024.33 | 1677.18 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.76 |
July | 13922.18 | 10-JUL-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 34.59 | 0.00 |
August | 11544.02 | 17-AUG-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 14.18 | 0.00 |
September | 11606.71 | 02-SEP-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 |
October | 5734.47 | 05-OCT-14:00 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
November | 3524.94 | 16-NOV-11:00 | 4021.58 | 3018.92 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.03 |
December | 4696.63 | 22-DEC-14:07 | 6032.37 | 4528.39 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.84 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3524.94 | 0.00 | 1244.84 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13922.18 | 6032.37 | 4528.39 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 | 589.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4735.87 | 27-JAN-13:20 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.93 |
February | 4952.66 | 17-FEB-17:40 | 1174.10 | 2220.87 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.11 |
March | 8791.28 | 29-MAR-08:55 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.35 |
April | 9537.74 | 28-APR-08:40 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.76 |
May | 19927.90 | 29-MAY-08:42 | 391.37 | 324.25 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.52 |
June | 18042.67 | 04-JUN-08:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.10 |
July | 20160.82 | 02-JUL-08:32 | 391.37 | 324.25 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.33 |
August | 19149.06 | 13-AUG-09:12 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 | 0.00 |
September | 19425.50 | 04-SEP-09:12 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.52 |
October | 7869.97 | 05-OCT-08:50 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.22 |
November | 4739.65 | 06-NOV-08:20 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 283.53 |
December | 4566.31 | 01-DEC-13:27 | 3717.98 | 2918.26 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.21 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4566.31 | 326.14 | 270.21 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20160.82 | 3717.98 | 2918.26 | 4400.84 | 0.00 | 0.00 | 0.00 | 0.00 | 28.45 | 574.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12442.99 | 30-JAN-13:00 | 3175.00 | 4528.48 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.67 |
February | 15739.19 | 22-FEB-12:05 | 2116.67 | 3018.99 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.30 |
March | 13258.63 | 22-MAR-12:10 | 3846.30 | 3018.99 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.37 |
April | 12392.51 | 07-APR-12:30 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
May | 11726.74 | 31-MAY-05:02 | 2024.37 | 1677.22 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 13060.45 | 20-JUN-05:02 | 2024.37 | 1792.32 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.60 |
July | 16019.70 | 10-JUL-03:02 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 34.24 | 0.00 |
August | 14602.29 | 30-AUG-13:40 | 4021.67 | 3018.99 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 38.61 | 0.00 |
September | 17453.75 | 04-SEP-11:52 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.54 |
October | 16426.20 | 15-OCT-11:32 | 404.87 | 335.44 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.35 |
November | 13533.19 | 02-NOV-13:30 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.61 |
December | 17871.49 | 21-DEC-17:35 | 1214.62 | 2297.53 | 2529.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.54 |
Annual Sum or Average | |||||||||||
Minimum of Months | 11726.74 | 0.00 | 335.44 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17871.49 | 4021.67 | 4528.48 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 1144.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4178.80 | 26-JAN-15:35 | 2478.65 | 1945.51 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 336.26 |
February | 5701.90 | 17-FEB-17:40 | 1174.10 | 2220.87 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.20 |
March | 9588.46 | 17-MAR-15:25 | 2478.65 | 1945.51 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.13 |
April | 12747.90 | 09-APR-16:23 | 260.91 | 216.17 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.32 |
May | 15841.17 | 14-MAY-15:52 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 727.24 |
June | 21124.09 | 18-JUN-16:11 | 456.59 | 378.29 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.96 |
July | 19548.87 | 02-JUL-15:22 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.98 |
August | 19163.13 | 13-AUG-15:52 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 119.15 | 0.00 |
September | 19954.27 | 10-SEP-16:52 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.81 |
October | 10515.74 | 04-OCT-15:30 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 |
November | 5639.71 | 03-NOV-15:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.50 |
December | 6063.98 | 21-DEC-17:35 | 782.73 | 1480.58 | 1629.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.86 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4178.80 | 260.91 | 216.17 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21124.09 | 2478.65 | 2220.87 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 119.15 | 727.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2042.16 | 20-JAN-16:00 | 1923.11 | 1583.56 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.77 |
February | 2047.15 | 24-FEB-15:50 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 719.92 |
March | 3471.53 | 27-MAR-16:00 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.31 |
April | 6309.70 | 07-APR-15:20 | 1923.11 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 0.00 |
May | 10158.76 | 30-MAY-05:03 | 809.73 | 670.87 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.61 |
June | 12054.73 | 22-JUN-05:02 | 2024.33 | 1677.18 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.34 |
July | 14677.83 | 10-JUL-03:02 | 0.00 | 1244.84 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 7.15 | 0.00 |
August | 12789.02 | 17-AUG-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 17.48 | 0.00 |
September | 12681.33 | 02-SEP-05:02 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.29 |
October | 6075.13 | 04-OCT-14:00 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
November | 3191.51 | 03-NOV-14:00 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.64 |
December | 1996.21 | 20-DEC-14:20 | 2010.79 | 1509.46 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.48 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1996.21 | 0.00 | 670.87 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14677.83 | 2024.33 | 2297.48 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 719.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2458.13 | 19-JAN-09:40 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.44 |
February | 2551.50 | 17-FEB-09:35 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.36 |
March | 5011.99 | 29-MAR-09:25 | 2591.66 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.05 |
April | 8942.49 | 28-APR-08:50 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.06 |
May | 20237.68 | 29-MAY-08:52 | 391.37 | 324.25 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.19 |
June | 19559.30 | 25-JUN-08:52 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.61 |
July | 19527.07 | 09-JUL-10:02 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 | 0.00 |
August | 19603.33 | 13-AUG-09:12 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 21.22 | 0.00 |
September | 19513.29 | 04-SEP-09:22 | 326.14 | 270.21 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.39 |
October | 7252.16 | 05-OCT-09:00 | 1239.33 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.27 |
November | 3622.78 | 03-NOV-14:00 | 1295.83 | 972.75 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.76 |
December | 2489.86 | 20-DEC-09:25 | 2478.65 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2458.13 | 326.14 | 270.21 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20237.68 | 2591.66 | 1945.51 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 | 347.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10906.27 | 19-JAN-13:40 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 702.68 |
February | 11047.93 | 02-FEB-14:15 | 4021.67 | 3018.99 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.88 |
March | 12944.07 | 01-MAR-13:40 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.97 |
April | 13035.56 | 07-APR-12:40 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 67.37 | 0.00 |
May | 11726.92 | 30-MAY-05:03 | 809.75 | 670.89 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.39 |
June | 13907.63 | 20-JUN-03:01 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.69 |
July | 16883.11 | 10-JUL-03:02 | 0.00 | 1244.87 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 15.58 | 0.00 |
August | 17662.42 | 13-AUG-15:52 | 607.31 | 503.16 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 241.95 | 0.00 |
September | 19494.44 | 04-SEP-12:02 | 506.09 | 419.30 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.99 |
October | 17859.49 | 15-OCT-14:02 | 607.31 | 503.16 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1155.14 |
November | 14128.04 | 02-NOV-13:30 | 2010.83 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.14 |
December | 10819.34 | 15-DEC-13:30 | 1923.15 | 1509.49 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 819.40 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10819.34 | 0.00 | 419.30 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19494.44 | 4021.67 | 3018.99 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 241.95 | 1155.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3341.89 | 20-JAN-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.48 |
February | 4023.15 | 22-FEB-16:30 | 2478.65 | 1945.51 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.72 |
March | 8292.44 | 29-MAR-16:00 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.06 |
April | 12401.15 | 09-APR-16:23 | 260.91 | 216.17 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.54 |
May | 15602.97 | 21-MAY-15:42 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 672.12 |
June | 22796.66 | 18-JUN-16:11 | 456.59 | 378.29 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.11 |
July | 22224.72 | 02-JUL-16:51 | 456.59 | 378.29 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.07 |
August | 20622.75 | 13-AUG-15:52 | 391.37 | 324.25 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 132.55 | 0.00 |
September | 19902.02 | 04-SEP-16:42 | 326.14 | 270.21 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.86 |
October | 10783.16 | 04-OCT-15:30 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.73 |
November | 5219.92 | 03-NOV-15:40 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.70 |
December | 3201.24 | 08-DEC-15:50 | 1239.33 | 972.75 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.87 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3201.24 | 260.91 | 216.17 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22796.66 | 2478.65 | 1945.51 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 132.55 | 672.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4452.74 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1171.96 |
February | 4440.90 | 24-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 259.48 |
March | 5280.30 | 27-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7753.98 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.15 |
May | 10511.27 | 30-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.68 |
June | 9565.03 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.31 |
July | 9478.04 | 10-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 0.00 |
August | 9073.27 | 22-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
September | 8899.27 | 06-SEP-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.48 |
October | 7820.96 | 16-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.73 |
November | 7237.21 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.49 |
December | 4441.69 | 26-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.42 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4440.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10511.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 1171.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4598.58 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7009.73 |
February | 6519.63 | 13-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4591.89 |
March | 4163.70 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4111.08 |
April | 4378.69 | 28-APR-05:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.35 |
May | 6183.45 | 31-MAY-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5980.52 | 12-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.42 |
July | 9029.62 | 21-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.31 |
August | 8696.85 | 05-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 0.00 |
September | 5965.10 | 08-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.03 |
October | 4977.65 | 06-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.16 |
November | 5091.70 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2658.74 |
December | 4403.56 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 482.23 |
Annual Sum or Average | |||||||||||
Minimum of Months | 4163.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9029.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.53 | 7009.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 890.30 | 19-JAN-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1034.61 |
February | 2047.69 | 17-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.91 |
March | 6492.09 | 28-MAR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 797.42 |
April | 12412.36 | 07-APR-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.89 | 0.00 |
May | 17917.09 | 30-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.24 | 0.00 |
June | 18729.76 | 19-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.34 | 0.00 |
July | 17594.85 | 10-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.45 | 0.00 |
August | 17458.80 | 22-AUG-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.72 | 0.00 |
September | 18802.17 | 01-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.43 | 0.00 |
October | 10497.37 | 04-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.04 |
November | 4865.28 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.85 |
December | 1678.52 | 17-DEC-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1166.76 |
Annual Sum or Average | |||||||||||
Minimum of Months | 890.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18802.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 349.45 | 1166.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1895.16 | 20-JAN-16:30 | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4005.12 | 14-FEB-17:00 | 0.00 | 477.69 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5994.92 | 27-MAR-17:20 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7573.94 | 23-APR-17:43 | 0.00 | 43.14 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2060.69 | 30-MAY-18:00 | 0.00 | 79.62 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4072.65 | 18-JUN-17:55 | 0.00 | 28.76 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6019.32 | 12-JUL-18:20 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7241.04 | 08-AUG-04:53 | 0.00 | 115.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3964.90 | 01-SEP-00:03 | 0.00 | 57.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4094.73 | 15-OCT-16:40 | 0.00 | 53.08 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5777.05 | 06-NOV-16:10 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7448.64 | 18-DEC-15:50 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1895.16 | 0.00 | 28.76 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7573.94 | 0.00 | 477.69 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1587.74 | 20-JAN-16:40 | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3583.02 | 22-FEB-17:00 | 0.00 | 238.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5623.13 | 29-MAR-17:20 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7173.38 | 12-APR-17:20 | 0.00 | 79.62 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1956.03 | 30-MAY-18:00 | 0.00 | 79.62 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3880.50 | 18-JUN-17:55 | 0.00 | 28.76 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5755.93 | 12-JUL-18:20 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6901.82 | 08-AUG-04:21 | 0.00 | 287.59 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3699.97 | 01-SEP-00:03 | 0.00 | 57.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3823.32 | 04-OCT-16:30 | 0.00 | 132.69 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5386.41 | 03-NOV-16:00 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7020.54 | 08-DEC-16:10 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1587.74 | 0.00 | 28.76 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7173.38 | 0.00 | 287.59 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1506.87 | 20-JAN-16:40 | 0.00 | 238.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3474.98 | 02-FEB-16:50 | 0.00 | 238.85 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5617.74 | 29-MAR-17:20 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7269.80 | 12-APR-17:20 | 0.00 | 79.62 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2041.28 | 30-MAY-18:00 | 0.00 | 79.62 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4094.07 | 18-JUN-17:55 | 0.00 | 28.76 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5846.85 | 12-JUL-18:20 | 0.00 | 79.62 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6924.11 | 20-AUG-01:42 | 0.00 | 71.90 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3224.67 | 01-SEP-00:03 | 0.00 | 57.52 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3880.08 | 04-OCT-16:30 | 0.00 | 132.69 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5359.17 | 03-NOV-16:00 | 0.00 | 238.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6870.11 | 08-DEC-16:10 | 0.00 | 238.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1506.87 | 0.00 | 28.76 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7269.80 | 0.00 | 238.85 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 358551.12 | 13-JAN-20:51 | 0.00 | 11489.53 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 407303.15 | 03-FEB-23:01 | 0.00 | 2872.38 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 413509.17 | 04-MAR-16:52 | 0.00 | 8617.15 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 394914.29 | 05-APR-03:03 | 0.00 | 3112.68 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 339327.51 | 16-MAY-04:21 | 0.00 | 6225.37 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 182312.72 | 20-JUN-16:00 | 0.00 | 5170.29 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 274518.35 | 06-JUL-16:00 | 0.00 | 5170.29 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368679.63 | 13-AUG-18:42 | 0.00 | 1556.34 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105356.63 | 01-SEP-00:05 | 0.00 | 1245.07 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 354129.85 | 28-OCT-17:24 | 0.00 | 2872.38 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 411422.26 | 18-NOV-19:52 | 0.00 | 3112.68 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 394405.85 | 14-DEC-04:57 | 0.00 | 3112.68 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 105356.63 | 0.00 | 1245.07 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 413509.17 | 0.00 | 11489.53 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.162323E+13 | 1059194.72 | 26-JAN-16:00 | 0.340626E+12 | 2424933.81 | 02-JAN-07:10 |
February | 0.181560E+13 | 1167853.78 | 22-FEB-16:49 | 0.258279E+12 | 2004924.87 | 06-FEB-07:10 |
March | 0.245745E+13 | 1424438.15 | 27-MAR-15:00 | 0.143907E+12 | 1039987.67 | 23-MAR-06:10 |
April | 0.277758E+13 | 1687870.76 | 07-APR-13:50 | 0.753769E+11 | 539736.54 | 01-APR-06:10 |
May | 0.181520E+13 | 1365408.89 | 31-MAY-15:30 | 0.498569E+11 | 296806.63 | 01-MAY-02:39 |
June | 0.241644E+13 | 1557151.78 | 19-JUN-15:09 | 0.456451E+11 | 152974.54 | 12-JUN-00:40 |
July | 0.298157E+13 | 1740585.03 | 20-JUL-15:20 | 0.410190E+11 | 168718.83 | 16-JUL-23:10 |
August | 0.343136E+13 | 1916437.77 | 02-AUG-15:09 | 0.453729E+11 | 179841.39 | 28-AUG-02:39 |
September | 0.190410E+13 | 1392173.17 | 07-SEP-15:09 | 0.424275E+11 | 184826.35 | 03-SEP-23:40 |
October | 0.220056E+13 | 1497685.85 | 03-OCT-15:00 | 0.530440E+11 | 231524.16 | 28-OCT-06:10 |
November | 0.237439E+13 | 1398162.07 | 22-NOV-16:49 | 0.133045E+12 | 1185065.57 | 24-NOV-07:10 |
December | 0.278937E+13 | 1554024.86 | 12-DEC-16:49 | 0.224885E+12 | 1359831.12 | 22-DEC-07:10 |
Annual Sum or Average | 0.285868E+14 | 0.145348E+13 | ||||
Minimum of Months | 0.162323E+13 | 1059194.72 | 0.410190E+11 | 152974.54 | ||
Maximum of Months | 0.343136E+13 | 1916437.77 | 0.340626E+12 | 2424933.81 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.278954E+12 | 0.709562E+11 | 0.811612E+12 | 0.168781E+12 | 0.166317E+12 | 0.174993E+11 | 0.00 | 0.876554E+11 | 0.994160E+10 | 0.473275E+10 | 0.678327E+10 | 0.00 | 0.00 |
February | 0.251524E+12 | 0.585227E+11 | 0.102011E+13 | 0.152457E+12 | 0.152235E+12 | 0.148778E+11 | 0.00 | 0.140487E+12 | 0.138403E+11 | 0.533682E+10 | 0.620906E+10 | 0.00 | 0.00 |
March | 0.297394E+12 | 0.571456E+11 | 0.146224E+13 | 0.169058E+12 | 0.176769E+12 | 0.171141E+11 | 0.00 | 0.223349E+12 | 0.451759E+11 | 0.376343E+10 | 0.543623E+10 | 0.00 | 0.00 |
April | 0.264985E+12 | 0.476445E+11 | 0.170426E+13 | 0.163308E+12 | 0.170924E+12 | 0.240655E+11 | 0.00 | 0.303293E+12 | 0.941722E+11 | 0.190756E+10 | 0.301767E+10 | 0.00 | 0.00 |
May | 0.285356E+12 | 0.433303E+11 | 0.820095E+12 | 0.168918E+12 | 0.180524E+12 | 0.470815E+11 | 0.00 | 0.181424E+12 | 0.869078E+11 | 0.746732E+09 | 0.816885E+09 | 0.00 | 0.00 |
June | 0.283572E+12 | 0.389797E+11 | 0.110647E+13 | 0.163570E+12 | 0.183718E+12 | 0.713676E+11 | 0.00 | 0.396573E+12 | 0.166794E+12 | 67451624.70 | 0.532341E+10 | 0.00 | 0.00 |
July | 0.265790E+12 | 0.412847E+11 | 0.143833E+13 | 0.168655E+12 | 0.192240E+12 | 0.850597E+11 | 0.00 | 0.583904E+12 | 0.199292E+12 | 0.00 | 0.701294E+10 | 0.00 | 0.00 |
August | 0.296155E+12 | 0.462035E+11 | 0.177907E+13 | 0.169058E+12 | 0.204994E+12 | 0.872886E+11 | 0.00 | 0.655623E+12 | 0.186759E+12 | 50530843.33 | 0.615639E+10 | 0.00 | 0.00 |
September | 0.265337E+12 | 0.519404E+11 | 0.784429E+12 | 0.163308E+12 | 0.178559E+12 | 0.600021E+11 | 0.00 | 0.261085E+12 | 0.136225E+12 | 0.110661E+09 | 0.310401E+10 | 0.00 | 0.00 |
October | 0.276457E+12 | 0.616325E+11 | 0.112844E+13 | 0.168779E+12 | 0.182730E+12 | 0.390978E+11 | 0.00 | 0.241102E+12 | 0.987363E+11 | 0.127447E+10 | 0.230424E+10 | 0.00 | 0.00 |
November | 0.275186E+12 | 0.666420E+11 | 0.140306E+13 | 0.163416E+12 | 0.167242E+12 | 0.173855E+11 | 0.00 | 0.218405E+12 | 0.562672E+11 | 0.269831E+10 | 0.408920E+10 | 0.00 | 0.00 |
December | 0.270408E+12 | 0.726427E+11 | 0.175516E+13 | 0.168658E+12 | 0.169633E+12 | 0.168692E+11 | 0.00 | 0.276737E+12 | 0.481951E+11 | 0.483437E+10 | 0.623132E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.331112E+13 | 0.656925E+12 | 0.152133E+14 | 0.198797E+13 | 0.212589E+13 | 0.497709E+12 | 0.00 | 0.356964E+13 | 0.114231E+13 | 0.255231E+11 | 0.564846E+11 | ||
Minimum of Months | 0.251524E+12 | 0.389797E+11 | 0.784429E+12 | 0.152457E+12 | 0.152235E+12 | 0.148778E+11 | 0.00 | 0.876554E+11 | 0.994160E+10 | 0.00 | 0.816885E+09 | 0.00 | 0.00 |
Maximum of Months | 0.297394E+12 | 0.726427E+11 | 0.177907E+13 | 0.169058E+12 | 0.204994E+12 | 0.872886E+11 | 0.00 | 0.655623E+12 | 0.199292E+12 | 0.533682E+10 | 0.701294E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.288266E+12 | 0.00 | 0.523597E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.210294E+12 | 0.00 | 0.479851E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.888464E+11 | 0.00 | 0.550609E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.276697E+11 | 0.00 | 0.477072E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.228148E+10 | 0.00 | 0.475754E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.181024E+10 | 0.00 | 0.438348E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.983974E+09 | 0.00 | 0.400350E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259374E+10 | 0.00 | 0.427792E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.217914E+10 | 0.00 | 0.402483E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.890723E+10 | 0.00 | 0.441368E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.866764E+11 | 0.00 | 0.463684E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.175759E+12 | 0.00 | 0.491262E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.896267E+12 | 0.557217E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.983974E+09 | 0.00 | 0.400350E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.288266E+12 | 0.00 | 0.550609E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 305596.68 | 02-JAN-16:40 | 53035.91 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 128033.79 | 03-JAN-08:20 | 145956.18 | 30-JAN-11:00 | 37248.53 | 05-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 300516.92 | 15-FEB-16:00 | 53035.91 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 128023.78 | 28-FEB-08:20 | 189208.44 | 22-FEB-15:09 | 36378.91 | 06-FEB-04:10 | 0.00 | 01-FEB-00:10 |
March | 289146.20 | 02-MAR-16:00 | 53035.91 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 128024.87 | 16-MAR-07:19 | 179370.78 | 22-MAR-12:00 | 49328.72 | 27-MAR-13:20 | 0.00 | 01-MAR-00:10 |
April | 283601.18 | 14-APR-07:10 | 53035.91 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 128021.55 | 14-APR-07:19 | 141049.07 | 12-APR-07:40 | 52474.15 | 07-APR-13:50 | 0.00 | 01-APR-00:10 |
May | 283563.73 | 01-MAY-07:10 | 53035.91 | 01-MAY-18:49 | 439129.89 | 01-MAY-07:10 | 128021.52 | 01-MAY-07:19 | 149683.55 | 30-MAY-13:30 | 52657.08 | 30-MAY-13:00 | 0.00 | 01-MAY-00:10 |
June | 283563.73 | 01-JUN-07:10 | 53035.91 | 01-JUN-19:19 | 557421.28 | 01-JUN-07:10 | 128021.52 | 01-JUN-07:19 | 157322.88 | 01-JUN-15:20 | 53534.51 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 283563.73 | 03-JUL-07:10 | 53035.91 | 01-JUL-19:30 | 675712.68 | 03-JUL-07:10 | 128021.52 | 03-JUL-07:19 | 168348.63 | 11-JUL-15:50 | 53488.30 | 26-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 283563.73 | 01-AUG-07:10 | 53035.91 | 01-AUG-19:10 | 794004.08 | 01-AUG-07:10 | 128021.52 | 01-AUG-07:19 | 183248.84 | 25-AUG-14:09 | 55639.69 | 25-AUG-15:00 | 0.00 | 01-AUG-00:10 |
September | 286075.20 | 27-SEP-07:10 | 53035.91 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 128023.61 | 27-SEP-07:19 | 158260.03 | 01-SEP-14:20 | 53767.77 | 01-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 293856.55 | 31-OCT-15:00 | 53035.91 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 128028.80 | 06-OCT-07:19 | 126034.84 | 27-OCT-14:00 | 53496.40 | 24-OCT-15:20 | 0.00 | 01-OCT-00:10 |
November | 305596.68 | 06-NOV-16:49 | 53035.91 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 128030.39 | 30-NOV-08:20 | 150664.21 | 24-NOV-16:00 | 35365.23 | 24-NOV-05:10 | 0.00 | 01-NOV-00:10 |
December | 305596.68 | 01-DEC-16:30 | 53035.91 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 128030.85 | 11-DEC-08:20 | 157175.86 | 01-DEC-10:00 | 36231.71 | 22-DEC-14:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 283563.73 | 53035.91 | 439129.89 | 128021.52 | 126034.84 | 35365.23 | 0.00 | |||||||
Maximum of Months | 305596.68 | 53035.91 | 794004.08 | 128033.79 | 189208.44 | 55639.69 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 94482.99 | 21-JAN-05:19 | 15002.67 | 28-JAN-17:30 | 37505.29 | 14-JAN-17:00 | 5613.05 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 100755.36 | 02-FEB-22:19 | 24627.15 | 19-FEB-15:09 | 37678.37 | 19-FEB-13:09 | 5613.05 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 199959.07 | 27-MAR-15:00 | 69638.85 | 27-MAR-13:39 | 16128.34 | 18-MAR-07:30 | 5613.05 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 353257.81 | 07-APR-13:50 | 57488.94 | 07-APR-13:50 | 9695.09 | 01-APR-14:00 | 5613.05 | 01-APR-06:10 | 0.00 | 0.00 |
May | 287649.41 | 30-MAY-13:30 | 90029.42 | 30-MAY-10:30 | 17221.38 | 16-MAY-03:20 | 5613.05 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 354117.78 | 19-JUN-14:09 | 90029.42 | 18-JUN-10:20 | 1988.94 | 02-JUN-19:00 | 5613.05 | 01-JUN-09:39 | 0.00 | 0.00 |
July | 411956.59 | 20-JUL-14:50 | 90029.42 | 09-JUL-13:50 | 0.00 | 01-JUL-00:10 | 5613.05 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 462566.15 | 02-AUG-14:00 | 90029.42 | 02-AUG-23:30 | 4011.49 | 30-AUG-15:20 | 5613.05 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 306154.36 | 14-SEP-10:09 | 90029.42 | 01-SEP-05:30 | 2650.69 | 28-SEP-17:00 | 5613.05 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 307924.54 | 04-OCT-13:39 | 90029.42 | 03-OCT-10:00 | 33333.33 | 28-OCT-17:19 | 5613.05 | 03-OCT-11:30 | 0.00 | 0.00 |
November | 154817.79 | 03-NOV-13:00 | 51139.76 | 10-NOV-09:00 | 19811.71 | 25-NOV-17:10 | 5613.05 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 117826.59 | 11-DEC-11:50 | 43140.39 | 17-DEC-14:00 | 14701.51 | 09-DEC-17:40 | 5613.05 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||
Minimum of Months | 94482.99 | 15002.67 | 0.00 | 5613.05 | 0.00 | 0.00 | ||||
Maximum of Months | 462566.15 | 90029.42 | 37678.37 | 5613.05 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1059194.72 | 26-JAN-16:00 | 305596.68 | 439129.89 | 53035.91 | 91258.20 | 86922.32 | 32495.12 | 0.00 | 36601.61 | 4288.00 |
February | 1167853.78 | 22-FEB-16:49 | 285821.83 | 557421.28 | 0.00 | 91242.72 | 152774.91 | 4655.31 | 0.00 | 60629.11 | 6586.29 |
March | 1424438.15 | 27-MAR-15:00 | 283563.73 | 675712.68 | 0.00 | 91242.13 | 89399.04 | 31474.28 | 0.00 | 199959.07 | 53087.22 |
April | 1687870.76 | 07-APR-13:50 | 283563.73 | 794004.08 | 0.00 | 42202.94 | 104879.12 | 52474.15 | 0.00 | 353257.81 | 57488.94 |
May | 1365408.89 | 31-MAY-15:30 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 123494.89 | 52230.67 | 0.00 | 280105.11 | 90029.42 |
June | 1557151.78 | 19-JUN-15:09 | 283563.73 | 557421.28 | 0.00 | 91242.13 | 130340.30 | 51441.05 | 0.00 | 347500.82 | 90029.42 |
July | 1740585.03 | 20-JUL-15:20 | 283563.73 | 675712.68 | 0.00 | 91242.13 | 130657.93 | 52199.54 | 0.00 | 411566.56 | 90029.42 |
August | 1916437.77 | 02-AUG-15:09 | 283563.73 | 794004.08 | 0.00 | 91242.13 | 138750.26 | 52685.61 | 0.00 | 460549.49 | 90029.42 |
September | 1392173.17 | 07-SEP-15:09 | 283563.73 | 439129.89 | 0.00 | 91242.13 | 131594.80 | 51715.70 | 0.00 | 299284.46 | 90029.42 |
October | 1497685.85 | 03-OCT-15:00 | 283563.73 | 557421.28 | 0.00 | 91242.13 | 115642.13 | 52564.26 | 0.00 | 301609.85 | 90029.42 |
November | 1398162.07 | 22-NOV-16:49 | 305596.68 | 675712.68 | 53035.91 | 91260.43 | 138370.23 | 31622.72 | 0.00 | 85077.83 | 7386.08 |
December | 1554024.86 | 12-DEC-16:49 | 305596.68 | 794004.08 | 53035.91 | 91260.43 | 150491.00 | 30566.00 | 0.00 | 106290.88 | 18138.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1059194.72 | 283563.73 | 439129.89 | 0.00 | 42202.94 | 86922.32 | 4655.31 | 0.00 | 36601.61 | 4288.00 | |
Maximum of Months | 1916437.77 | 305596.68 | 794004.08 | 53035.91 | 91260.43 | 152774.91 | 52685.61 | 0.00 | 460549.49 | 90029.42 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 2419237.94 | 02-JAN-07:10 | 0.00 | 81594.94 | 13-JAN-12:30 | 0.00 |
February | 0.00 | 0.00 | 1999229.00 | 06-FEB-07:10 | 0.00 | 82925.36 | 23-FEB-12:00 | 0.00 |
March | 0.00 | 0.00 | 1034291.80 | 23-MAR-06:10 | 0.00 | 81639.28 | 07-MAR-12:00 | 0.00 |
April | 0.00 | 0.00 | 534040.67 | 01-APR-06:10 | 0.00 | 78924.36 | 19-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 291110.76 | 01-MAY-02:39 | 0.00 | 74593.99 | 02-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 147278.67 | 12-JUN-00:40 | 0.00 | 71086.05 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 163022.96 | 16-JUL-23:10 | 0.00 | 67272.85 | 05-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 174145.52 | 28-AUG-02:39 | 0.00 | 66194.84 | 31-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 179130.48 | 03-SEP-23:40 | 0.00 | 68545.88 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 225828.29 | 28-OCT-06:10 | 0.00 | 75342.28 | 27-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 1179369.70 | 24-NOV-07:10 | 0.00 | 78740.43 | 29-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 1354135.25 | 22-DEC-07:10 | 0.00 | 79752.77 | 28-DEC-13:00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 147278.67 | 0.00 | 66194.84 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 2419237.94 | 0.00 | 82925.36 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.95 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.42 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 26.15 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.27 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.60 | 0.33 | 27.88 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.50 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.48 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.52 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.77 | 0.17 | 28.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.79 | 1.00 | 28.11 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.77 | 0.83 | 28.21 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 26.44 | 0.67 | 27.39 |
Annual Sum or Average | 0.00 | 0.00 | 82.50 | 26.57 | 3.00 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.95 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 26.79 | 1.00 | 28.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.63 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.49 | 1.33 | 19.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.71 | 0.50 | 24.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.57 | 0.17 | 24.57 |
Annual Sum or Average | 2.17 | 19.49 | 1.33 | 19.97 | 0.67 | 24.68 | 0.67 | 24.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.17 | 19.49 | 1.33 | 19.97 | 0.50 | 24.71 | 0.50 | 24.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.87 | 0.67 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.17 | 18.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4.67 | 18.85 | 0.67 | 20.02 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.40 | 0.67 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.47 | 0.67 | 27.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.86 | 2.00 | 27.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.57 | 0.67 | 27.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.96 | 1.50 | 27.96 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.46 | 0.33 | 27.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.95 | 2.00 | 27.95 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 7.17 | 27.82 | 7.17 | 27.82 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.96 | 2.00 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.26 | 0.00 | 0.00 | 4.83 | 24.67 | 4.83 | 24.67 |
February | 0.17 | 19.14 | 0.00 | 0.00 | 9.50 | 24.81 | 9.50 | 24.81 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 24.82 | 17.67 | 24.82 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 25.33 | 4.50 | 25.33 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 25.60 | 14.17 | 25.60 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 42.00 | 25.19 | 42.00 | 25.19 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 13.00 | 25.11 | 13.00 | 25.11 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 25.36 | 13.17 | 25.36 |
Annual Sum or Average | 0.33 | 19.20 | 0.00 | 118.83 | 25.15 | 118.83 | 25.15 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.26 | 0.00 | 0.00 | 42.00 | 25.60 | 42.00 | 25.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.49 | 0.67 | 27.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.89 | 2.83 | 28.05 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.56 | 1.50 | 27.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 27.71 | 3.50 | 27.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.56 | 5.50 | 28.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.99 | 2.83 | 28.30 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.89 | 1.83 | 27.97 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.68 | 0.50 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.17 | 27.27 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.17 | 27.32 |
Annual Sum or Average | 0.00 | 0.00 | 49.33 | 27.49 | 19.50 | 27.96 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 27.89 | 5.50 | 28.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 17.15 | 6.83 | 17.38 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11.83 | 17.91 | 2.50 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 17.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 35.50 | 17.54 | 9.33 | 18.04 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.67 | 19.22 | 6.83 | 19.84 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.17 | 16.28 | 2.50 | 15.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.00 | 17.38 | 0.17 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.90 | 1.50 | 27.90 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.53 | 1.00 | 27.53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.94 | 2.33 | 27.94 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.79 | 0.83 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.93 | 1.67 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.83 | 18.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.50 | 16.94 | 2.67 | 15.42 | 7.33 | 27.86 | 7.33 | 27.86 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.17 | 19.23 | 2.50 | 20.28 | 2.33 | 27.94 | 2.33 | 27.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 13.00 | 17.11 | 3.33 | 18.06 | 5.67 | 24.90 | 5.67 | 24.90 |
February | 5.50 | 17.88 | 0.67 | 19.89 | 11.67 | 24.87 | 11.67 | 24.87 |
March | 0.50 | 19.32 | 0.00 | 0.00 | 20.17 | 24.91 | 20.17 | 24.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 25.20 | 8.17 | 25.20 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 25.37 | 30.67 | 25.37 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 58.00 | 25.28 | 58.00 | 25.28 |
November | 0.33 | 19.07 | 0.00 | 0.00 | 12.67 | 25.26 | 12.67 | 25.26 |
December | 0.83 | 19.26 | 0.00 | 0.00 | 7.83 | 25.45 | 7.83 | 25.45 |
Annual Sum or Average | 20.17 | 17.50 | 4.00 | 18.36 | 154.83 | 25.21 | 154.83 | 25.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 13.00 | 19.32 | 3.33 | 19.89 | 58.00 | 25.45 | 58.00 | 25.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.00 | 16.20 | 2.67 | 15.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.17 | 17.44 | 0.17 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.88 | 0.33 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.41 | 0.33 | 27.41 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.93 | 1.83 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.89 | 2.17 | 27.92 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.05 | 1.17 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.75 | 1.17 | 27.78 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.00 | 16.87 | 2.83 | 15.41 | 9.50 | 27.89 | 7.00 | 27.90 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.00 | 19.29 | 2.67 | 20.34 | 3.33 | 28.05 | 2.17 | 28.10 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.17 | 16.79 | 15.00 | 17.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 42.00 | 16.83 | 15.83 | 17.39 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7.00 | 18.79 | 1.17 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 18.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10.17 | 17.87 | 1.83 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16.83 | 17.34 | 4.50 | 16.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 126.83 | 17.08 | 38.33 | 17.53 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 50.17 | 18.93 | 15.83 | 20.19 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 30.00 | 15.70 | 6.33 | 14.83 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 21.50 | 16.03 | 3.83 | 14.94 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.00 | 18.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 18.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.97 | 1.17 | 27.97 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.87 | 0.50 | 27.87 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.93 | 2.67 | 27.93 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.67 | 1.50 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.70 | 1.50 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5.33 | 16.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.67 | 16.56 | 2.83 | 14.80 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 76.17 | 16.22 | 13.00 | 14.86 | 7.33 | 27.83 | 7.33 | 27.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 30.00 | 18.96 | 6.33 | 14.94 | 2.67 | 27.97 | 2.67 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 29.67 | 16.65 | 6.17 | 17.33 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 22.67 | 17.03 | 5.00 | 18.17 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.67 | 18.82 | 0.17 | 20.08 | 4.83 | 24.73 | 4.83 | 24.73 |
April | 0.67 | 19.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.38 | 1.33 | 27.38 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 25.73 | 5.83 | 25.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 17.17 | 25.57 | 17.17 | 25.57 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 25.11 | 24.17 | 25.11 |
November | 4.33 | 18.37 | 0.17 | 20.30 | 3.33 | 25.08 | 3.33 | 25.08 |
December | 11.00 | 17.45 | 1.00 | 16.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 72.00 | 17.13 | 12.50 | 17.68 | 56.83 | 25.33 | 56.67 | 25.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 29.67 | 19.02 | 6.17 | 20.30 | 24.17 | 27.38 | 24.17 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.83 | 15.82 | 4.33 | 14.77 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16.33 | 16.25 | 3.17 | 14.70 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.33 | 18.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 19.29 | 0.00 | 0.00 | 0.50 | 27.86 | 0.33 | 28.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 28.03 | 2.00 | 27.96 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.03 | 2.83 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.27 | 1.17 | 28.40 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.70 | 1.17 | 27.76 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 18.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.50 | 17.46 | 1.00 | 14.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.00 | 16.58 | 8.50 | 14.76 | 10.83 | 27.98 | 8.00 | 28.01 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 19.83 | 19.29 | 4.33 | 14.88 | 3.83 | 28.27 | 2.83 | 28.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 102.83 | 28.22 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 723.50 | 29.11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.58 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 827.50 | 28.99 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 723.50 | 29.11 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 59.50 | 28.13 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 716.50 | 29.04 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 776.00 | 28.97 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 716.50 | 29.04 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 28.16 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 656.67 | 28.99 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 699.00 | 28.94 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 656.67 | 28.99 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.40 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 29.03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.95 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.63 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.97 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 132.50 | 28.07 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.82 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.68 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 139.83 | 28.08 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 132.50 | 29.03 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 217.50 | 23.91 | 65.50 | 25.56 | 0.00 | 0.00 |
February | 264.17 | 23.95 | 56.83 | 26.23 | 0.00 | 0.00 |
March | 108.33 | 24.01 | 98.33 | 25.60 | 0.00 | 0.00 |
April | 36.50 | 24.01 | 153.00 | 25.38 | 0.00 | 0.00 |
May | 30.50 | 24.01 | 279.83 | 24.81 | 24.67 | 24.00 |
June | 146.50 | 24.82 | 439.50 | 24.50 | 146.50 | 24.82 |
July | 230.83 | 25.24 | 497.00 | 24.59 | 230.83 | 25.24 |
August | 112.17 | 25.17 | 476.83 | 24.51 | 112.17 | 25.17 |
September | 58.83 | 25.13 | 393.50 | 24.66 | 58.83 | 25.13 |
October | 49.00 | 24.45 | 344.00 | 24.84 | 22.50 | 24.95 |
November | 35.50 | 24.08 | 145.83 | 25.80 | 0.67 | 26.84 |
December | 137.83 | 24.02 | 91.67 | 26.43 | 0.00 | 0.00 |
Annual Sum or Average | 1427.67 | 24.42 | 3041.83 | 24.86 | 596.17 | 25.05 |
Minimum of Months | 30.50 | 23.91 | 56.83 | 24.50 | 0.00 | 0.00 |
Maximum of Months | 264.17 | 25.24 | 497.00 | 26.43 | 230.83 | 26.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 308.33 | 23.88 | 43.50 | 24.63 | 0.00 | 0.00 |
February | 262.33 | 23.92 | 14.33 | 25.84 | 0.00 | 0.00 |
March | 100.67 | 23.98 | 97.33 | 25.23 | 0.00 | 0.00 |
April | 25.33 | 23.97 | 166.83 | 24.83 | 0.00 | 0.00 |
May | 23.50 | 23.64 | 265.67 | 24.44 | 0.00 | 0.00 |
June | 0.83 | 23.61 | 421.50 | 24.26 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 475.00 | 24.21 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 478.83 | 24.15 | 0.00 | 0.00 |
September | 9.33 | 23.68 | 369.33 | 24.36 | 0.00 | 0.00 |
October | 40.67 | 24.01 | 311.00 | 24.52 | 0.00 | 0.00 |
November | 52.00 | 23.98 | 135.67 | 25.45 | 0.00 | 0.00 |
December | 138.67 | 23.99 | 69.83 | 25.96 | 0.00 | 0.00 |
Annual Sum or Average | 961.67 | 23.92 | 2848.83 | 24.47 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 14.33 | 24.15 | 0.00 | 0.00 |
Maximum of Months | 308.33 | 24.01 | 478.83 | 25.96 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 22.61 | 49.00 | 19.89 | 49.00 | 19.89 |
February | 451.17 | 23.13 | 6.33 | 21.03 | 6.33 | 21.03 |
March | 405.67 | 23.59 | 9.17 | 23.99 | 0.00 | 0.00 |
April | 249.33 | 23.58 | 49.83 | 24.59 | 0.00 | 0.00 |
May | 121.50 | 23.49 | 156.17 | 24.27 | 0.00 | 0.00 |
June | 38.50 | 23.26 | 297.67 | 24.28 | 0.00 | 0.00 |
July | 32.33 | 23.14 | 313.00 | 24.27 | 0.00 | 0.00 |
August | 23.83 | 23.31 | 328.33 | 24.29 | 0.00 | 0.00 |
September | 65.83 | 23.35 | 233.50 | 24.30 | 0.00 | 0.00 |
October | 137.17 | 23.64 | 177.67 | 24.29 | 0.00 | 0.00 |
November | 319.67 | 23.47 | 47.33 | 24.65 | 0.00 | 0.00 |
December | 487.33 | 23.35 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2826.17 | 23.27 | 1668.00 | 24.16 | 55.33 | 20.02 |
Minimum of Months | 23.83 | 22.61 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 493.83 | 23.64 | 328.33 | 24.65 | 49.00 | 21.03 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.29 | 163.33 | 19.68 | 163.33 | 19.68 |
February | 454.00 | 21.58 | 136.83 | 20.25 | 136.83 | 20.25 |
March | 482.67 | 22.58 | 27.17 | 20.81 | 26.17 | 20.69 |
April | 345.67 | 22.91 | 42.83 | 23.60 | 8.00 | 20.66 |
May | 191.83 | 23.32 | 132.00 | 24.14 | 0.00 | 0.00 |
June | 44.00 | 23.37 | 322.17 | 24.27 | 0.00 | 0.00 |
July | 9.83 | 23.20 | 372.17 | 24.28 | 0.00 | 0.00 |
August | 8.83 | 23.42 | 363.50 | 24.29 | 0.00 | 0.00 |
September | 123.00 | 23.18 | 223.33 | 24.17 | 0.00 | 0.00 |
October | 287.00 | 23.07 | 124.17 | 24.08 | 0.00 | 0.00 |
November | 455.33 | 22.38 | 68.67 | 20.75 | 63.00 | 20.45 |
December | 497.00 | 21.68 | 122.83 | 20.12 | 122.83 | 20.12 |
Annual Sum or Average | 3401.17 | 22.25 | 2099.00 | 23.21 | 520.17 | 20.09 |
Minimum of Months | 8.83 | 21.29 | 27.17 | 19.68 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.42 | 372.17 | 24.29 | 163.33 | 20.69 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.99 | 85.17 | 20.73 | 85.17 | 20.73 |
February | 454.00 | 22.20 | 61.67 | 20.81 | 61.67 | 20.81 |
March | 446.17 | 23.14 | 11.33 | 24.06 | 0.00 | 0.00 |
April | 262.50 | 23.44 | 70.17 | 24.31 | 0.00 | 0.00 |
May | 100.33 | 23.59 | 190.33 | 24.30 | 0.00 | 0.00 |
June | 4.83 | 24.33 | 428.00 | 24.27 | 1.50 | 25.58 |
July | 0.00 | 0.00 | 496.83 | 24.33 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 473.17 | 24.21 | 0.00 | 0.00 |
September | 69.83 | 23.66 | 313.50 | 24.29 | 3.50 | 26.10 |
October | 185.67 | 23.51 | 179.33 | 24.20 | 0.00 | 0.00 |
November | 376.00 | 23.14 | 20.17 | 24.29 | 0.00 | 0.00 |
December | 491.33 | 22.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2892.67 | 22.82 | 2329.67 | 24.05 | 151.83 | 20.93 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 24.33 | 496.83 | 24.33 | 85.17 | 26.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.67 | 21.57 | 93.17 | 20.72 | 93.17 | 20.72 |
February | 444.33 | 21.82 | 53.83 | 21.00 | 51.83 | 20.82 |
March | 442.83 | 22.40 | 10.33 | 24.40 | 1.00 | 21.00 |
April | 305.67 | 22.63 | 79.50 | 24.43 | 1.83 | 26.26 |
May | 201.33 | 22.97 | 195.50 | 24.46 | 6.83 | 26.60 |
June | 101.83 | 22.89 | 309.67 | 24.22 | 3.17 | 26.24 |
July | 71.17 | 23.20 | 347.33 | 24.22 | 7.17 | 26.58 |
August | 81.50 | 23.03 | 342.50 | 24.05 | 2.83 | 26.24 |
September | 166.33 | 22.96 | 230.33 | 24.44 | 12.33 | 26.51 |
October | 261.50 | 22.81 | 149.33 | 24.22 | 0.83 | 25.98 |
November | 435.50 | 22.47 | 12.17 | 24.21 | 2.33 | 20.88 |
December | 489.83 | 21.97 | 7.83 | 20.94 | 7.50 | 20.73 |
Annual Sum or Average | 3502.50 | 22.31 | 1831.50 | 23.97 | 190.83 | 21.80 |
Minimum of Months | 71.17 | 21.57 | 7.83 | 20.72 | 0.83 | 20.72 |
Maximum of Months | 500.67 | 23.20 | 347.33 | 24.46 | 93.17 | 26.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 437.50 | 21.82 | 107.83 | 21.09 | 91.83 | 20.40 |
February | 369.17 | 22.23 | 75.50 | 22.20 | 52.50 | 20.75 |
March | 364.17 | 22.79 | 52.00 | 24.46 | 1.33 | 21.00 |
April | 263.00 | 23.05 | 88.67 | 24.38 | 0.00 | 0.00 |
May | 146.50 | 23.33 | 177.83 | 24.31 | 0.17 | 26.24 |
June | 12.50 | 23.74 | 384.00 | 24.28 | 1.17 | 25.88 |
July | 2.67 | 25.99 | 484.50 | 24.32 | 2.67 | 25.99 |
August | 5.50 | 26.58 | 475.33 | 24.26 | 5.50 | 26.58 |
September | 66.33 | 24.10 | 358.17 | 24.46 | 16.00 | 26.68 |
October | 124.67 | 23.75 | 294.67 | 24.61 | 12.50 | 26.66 |
November | 301.33 | 22.85 | 86.00 | 24.46 | 4.00 | 20.82 |
December | 389.33 | 22.48 | 42.67 | 24.54 | 10.00 | 21.63 |
Annual Sum or Average | 2482.67 | 22.65 | 2627.17 | 24.17 | 197.67 | 21.76 |
Minimum of Months | 2.67 | 21.82 | 42.67 | 21.09 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 26.58 | 484.50 | 24.61 | 91.83 | 26.68 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 485.33 | 21.97 | 23.17 | 21.15 | 21.50 | 20.79 |
February | 410.00 | 22.49 | 11.33 | 24.42 | 4.17 | 20.99 |
March | 223.50 | 23.26 | 119.67 | 24.67 | 1.83 | 26.35 |
April | 64.17 | 23.93 | 262.67 | 24.73 | 11.00 | 26.61 |
May | 93.50 | 23.15 | 280.67 | 24.44 | 4.00 | 26.11 |
June | 21.33 | 26.47 | 464.17 | 24.36 | 21.33 | 26.47 |
July | 35.50 | 26.34 | 496.67 | 24.44 | 35.50 | 26.34 |
August | 23.83 | 26.22 | 514.00 | 24.37 | 23.83 | 26.22 |
September | 78.50 | 23.45 | 311.00 | 24.40 | 11.17 | 26.71 |
October | 84.50 | 23.39 | 297.50 | 24.40 | 2.83 | 26.16 |
November | 205.17 | 23.15 | 110.83 | 25.01 | 0.83 | 26.58 |
December | 298.00 | 23.27 | 39.83 | 25.77 | 0.00 | 0.00 |
Annual Sum or Average | 2023.33 | 22.94 | 2931.50 | 24.46 | 138.00 | 25.35 |
Minimum of Months | 21.33 | 21.97 | 11.33 | 21.15 | 0.00 | 0.00 |
Maximum of Months | 485.33 | 26.47 | 514.00 | 25.77 | 35.50 | 26.71 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.37 | 327.00 | 19.90 | 327.00 | 19.90 |
February | 454.00 | 20.57 | 313.50 | 20.19 | 313.50 | 20.19 |
March | 510.50 | 21.55 | 97.00 | 20.32 | 97.00 | 20.32 |
April | 413.83 | 22.33 | 34.33 | 22.11 | 19.17 | 20.41 |
May | 262.33 | 23.18 | 105.83 | 24.15 | 0.00 | 0.00 |
June | 54.83 | 24.11 | 358.17 | 24.22 | 18.67 | 25.32 |
July | 32.67 | 25.63 | 474.50 | 24.33 | 32.67 | 25.63 |
August | 29.00 | 24.94 | 420.67 | 24.29 | 18.33 | 25.79 |
September | 160.17 | 23.21 | 211.17 | 24.13 | 7.50 | 24.61 |
October | 365.67 | 22.62 | 86.33 | 23.69 | 7.50 | 20.58 |
November | 486.17 | 21.54 | 108.00 | 20.09 | 108.00 | 20.09 |
December | 497.00 | 20.71 | 277.50 | 20.22 | 277.50 | 20.22 |
Annual Sum or Average | 3768.17 | 21.63 | 2814.00 | 22.56 | 1226.83 | 20.46 |
Minimum of Months | 29.00 | 20.37 | 34.33 | 19.90 | 0.00 | 0.00 |
Maximum of Months | 510.50 | 25.63 | 474.50 | 24.33 | 327.00 | 25.79 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.22 | 281.67 | 19.76 | 281.67 | 19.76 |
February | 385.00 | 20.61 | 225.67 | 20.10 | 225.67 | 20.10 |
March | 421.33 | 21.36 | 76.33 | 20.33 | 75.00 | 20.24 |
April | 325.17 | 21.92 | 49.50 | 24.45 | 5.83 | 20.50 |
May | 259.67 | 22.51 | 112.50 | 24.75 | 5.50 | 26.62 |
June | 152.33 | 22.95 | 201.00 | 24.42 | 16.50 | 25.81 |
July | 112.50 | 23.80 | 280.83 | 24.53 | 37.00 | 26.06 |
August | 96.67 | 23.47 | 289.83 | 24.37 | 20.83 | 26.08 |
September | 226.67 | 22.59 | 145.67 | 24.50 | 15.17 | 25.72 |
October | 333.83 | 22.21 | 59.33 | 23.97 | 3.67 | 21.86 |
November | 416.33 | 21.25 | 93.50 | 20.09 | 93.50 | 20.09 |
December | 422.00 | 20.63 | 227.17 | 20.16 | 227.17 | 20.16 |
Annual Sum or Average | 3578.50 | 21.54 | 2043.00 | 22.49 | 1007.50 | 20.59 |
Minimum of Months | 96.67 | 20.22 | 49.50 | 19.76 | 3.67 | 19.76 |
Maximum of Months | 427.00 | 23.80 | 289.83 | 24.75 | 281.67 | 26.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 452.00 | 20.92 | 205.17 | 19.99 | 192.67 | 19.66 |
February | 387.83 | 21.49 | 160.00 | 20.99 | 136.67 | 20.23 |
March | 402.83 | 21.95 | 90.17 | 22.60 | 45.17 | 20.55 |
April | 343.33 | 22.37 | 70.00 | 23.88 | 10.00 | 20.54 |
May | 235.83 | 23.04 | 120.00 | 24.30 | 0.00 | 0.00 |
June | 62.50 | 23.85 | 342.83 | 24.25 | 15.67 | 25.50 |
July | 37.67 | 25.66 | 455.00 | 24.37 | 35.67 | 25.80 |
August | 32.00 | 25.52 | 453.83 | 24.37 | 25.00 | 26.14 |
September | 107.50 | 23.74 | 323.50 | 24.47 | 23.67 | 26.22 |
October | 186.33 | 23.37 | 262.17 | 24.70 | 20.50 | 26.28 |
November | 363.17 | 22.08 | 100.33 | 22.55 | 45.67 | 20.22 |
December | 422.50 | 21.55 | 149.33 | 21.12 | 127.83 | 20.35 |
Annual Sum or Average | 3033.50 | 22.10 | 2732.33 | 23.55 | 678.50 | 21.14 |
Minimum of Months | 32.00 | 20.92 | 70.00 | 19.99 | 0.00 | 0.00 |
Maximum of Months | 452.00 | 25.66 | 455.00 | 24.70 | 192.67 | 26.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.53 | 271.83 | 19.94 | 271.83 | 19.94 |
February | 448.00 | 20.80 | 225.00 | 20.20 | 225.00 | 20.20 |
March | 467.67 | 21.54 | 65.50 | 21.19 | 54.83 | 20.57 |
April | 390.00 | 22.09 | 61.83 | 24.04 | 9.67 | 21.80 |
May | 305.50 | 22.62 | 120.83 | 24.42 | 1.67 | 25.88 |
June | 117.50 | 23.34 | 306.83 | 24.36 | 20.33 | 26.11 |
July | 81.00 | 24.33 | 387.00 | 24.41 | 37.33 | 26.27 |
August | 48.83 | 24.58 | 415.33 | 24.38 | 23.33 | 26.47 |
September | 246.67 | 22.66 | 170.67 | 24.30 | 11.17 | 25.64 |
October | 355.17 | 22.33 | 83.67 | 23.99 | 3.50 | 20.51 |
November | 478.67 | 21.34 | 80.33 | 20.21 | 79.50 | 20.17 |
December | 497.00 | 20.88 | 193.33 | 20.30 | 193.33 | 20.30 |
Annual Sum or Average | 3938.00 | 21.65 | 2382.17 | 22.89 | 931.50 | 20.79 |
Minimum of Months | 48.83 | 20.53 | 61.83 | 19.94 | 1.67 | 19.94 |
Maximum of Months | 502.00 | 24.58 | 415.33 | 24.42 | 271.83 | 26.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.99 | 397.67 | 19.70 | 397.67 | 19.70 |
February | 454.00 | 20.12 | 385.83 | 19.93 | 385.83 | 19.93 |
March | 514.00 | 20.93 | 216.67 | 20.06 | 216.67 | 20.06 |
April | 425.50 | 21.70 | 87.83 | 20.77 | 72.33 | 20.04 |
May | 303.17 | 22.71 | 91.50 | 24.17 | 0.33 | 20.98 |
June | 89.67 | 23.64 | 338.83 | 24.23 | 20.17 | 25.25 |
July | 42.67 | 25.33 | 454.33 | 24.35 | 38.17 | 25.58 |
August | 58.00 | 24.17 | 405.67 | 24.29 | 20.67 | 25.85 |
September | 219.67 | 22.82 | 183.83 | 24.09 | 8.67 | 23.90 |
October | 415.33 | 21.96 | 117.00 | 21.97 | 60.83 | 20.12 |
November | 489.00 | 20.73 | 216.50 | 19.75 | 216.50 | 19.75 |
December | 497.00 | 20.11 | 418.67 | 19.93 | 418.67 | 19.93 |
Annual Sum or Average | 4010.00 | 21.18 | 3314.33 | 21.92 | 1856.50 | 20.15 |
Minimum of Months | 42.67 | 19.99 | 87.83 | 19.70 | 0.33 | 19.70 |
Maximum of Months | 514.00 | 25.33 | 454.33 | 24.35 | 418.67 | 25.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 378.67 | 19.67 | 378.67 | 19.67 |
February | 454.00 | 20.25 | 351.17 | 19.99 | 351.17 | 19.99 |
March | 507.17 | 21.03 | 149.83 | 19.76 | 149.83 | 19.76 |
April | 381.67 | 21.62 | 110.00 | 22.40 | 53.83 | 20.23 |
May | 288.50 | 22.23 | 156.33 | 24.48 | 5.50 | 26.32 |
June | 167.00 | 23.06 | 268.67 | 24.30 | 23.00 | 26.15 |
July | 110.17 | 23.90 | 368.50 | 24.40 | 41.33 | 26.02 |
August | 93.50 | 23.53 | 377.67 | 24.29 | 23.00 | 26.10 |
September | 262.17 | 22.40 | 182.50 | 24.32 | 14.00 | 25.16 |
October | 393.17 | 21.86 | 102.83 | 23.02 | 27.67 | 20.21 |
November | 489.00 | 20.72 | 180.67 | 19.67 | 180.67 | 19.67 |
December | 497.00 | 20.18 | 366.83 | 19.88 | 366.83 | 19.88 |
Annual Sum or Average | 4145.33 | 21.20 | 2993.67 | 22.07 | 1615.50 | 20.24 |
Minimum of Months | 93.50 | 20.01 | 102.83 | 19.67 | 5.50 | 19.67 |
Maximum of Months | 507.17 | 23.90 | 378.67 | 24.48 | 378.67 | 26.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 472.00 | 20.48 | 272.67 | 19.49 | 270.33 | 19.45 |
February | 409.33 | 20.84 | 237.17 | 19.93 | 235.17 | 19.90 |
March | 424.83 | 21.29 | 167.17 | 20.71 | 138.83 | 19.99 |
April | 371.33 | 21.78 | 116.50 | 22.12 | 62.17 | 20.20 |
May | 291.17 | 22.60 | 115.67 | 24.27 | 0.33 | 20.98 |
June | 102.33 | 23.38 | 320.33 | 24.25 | 16.50 | 25.33 |
July | 56.83 | 25.18 | 436.83 | 24.38 | 43.50 | 25.82 |
August | 57.00 | 24.68 | 430.83 | 24.36 | 29.17 | 26.20 |
September | 160.33 | 23.20 | 276.50 | 24.40 | 24.17 | 25.89 |
October | 230.00 | 22.48 | 225.00 | 24.20 | 28.67 | 22.38 |
November | 408.33 | 21.32 | 152.50 | 20.53 | 126.33 | 19.77 |
December | 447.67 | 20.80 | 254.33 | 20.00 | 247.50 | 19.82 |
Annual Sum or Average | 3431.17 | 21.58 | 3005.50 | 22.70 | 1222.67 | 20.41 |
Minimum of Months | 56.83 | 20.48 | 115.67 | 19.49 | 0.33 | 19.45 |
Maximum of Months | 472.00 | 25.18 | 436.83 | 24.40 | 270.33 | 26.20 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.18 | 333.67 | 19.68 | 333.67 | 19.68 |
February | 452.17 | 20.45 | 306.83 | 20.00 | 306.83 | 20.00 |
March | 477.00 | 21.11 | 147.17 | 20.41 | 138.67 | 20.18 |
April | 400.33 | 21.63 | 94.00 | 22.49 | 44.50 | 20.40 |
May | 328.00 | 22.26 | 115.67 | 24.37 | 2.50 | 25.79 |
June | 154.67 | 23.06 | 287.67 | 24.33 | 22.17 | 26.06 |
July | 100.67 | 23.94 | 371.67 | 24.40 | 38.67 | 26.16 |
August | 79.50 | 23.84 | 391.17 | 24.38 | 24.83 | 26.44 |
September | 288.00 | 22.40 | 150.17 | 24.23 | 12.67 | 25.26 |
October | 390.83 | 21.86 | 97.17 | 22.93 | 30.17 | 20.29 |
November | 484.50 | 20.80 | 171.33 | 19.86 | 171.33 | 19.86 |
December | 497.00 | 20.42 | 331.50 | 20.04 | 331.50 | 20.04 |
Annual Sum or Average | 4154.67 | 21.30 | 2798.00 | 22.21 | 1457.50 | 20.37 |
Minimum of Months | 79.50 | 20.18 | 94.00 | 19.68 | 2.50 | 19.68 |
Maximum of Months | 502.00 | 23.94 | 391.17 | 24.40 | 333.67 | 26.44 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.35537 | 21.46914 | 0.31028 | 7.51268 |
February | 454.00000 | 24.38725 | 17.19259 | 0.29111 | 7.23074 |
March | 514.00000 | 24.36960 | 24.86839 | 0.35439 | 8.03001 |
April | 485.00000 | 24.46532 | 31.12796 | 0.42176 | 9.28251 |
May | 508.00000 | 24.45410 | 40.70230 | -0.3727 | 8.75165 |
June | 496.00000 | 24.43714 | 55.98729 | -0.2549 | 7.33848 |
July | 497.00000 | 24.58623 | 61.92450 | -0.1625 | 6.95988 |
August | 514.00000 | 24.46777 | 56.29597 | -0.2265 | 7.27401 |
September | 485.00000 | 24.53390 | 49.76365 | -0.2596 | 7.71091 |
October | 502.00000 | 24.59175 | 40.68703 | 0.53407 | 11.83997 |
November | 489.00000 | 24.56825 | 27.07474 | 0.42640 | 9.48715 |
December | 497.00000 | 24.52859 | 19.60948 | 0.35626 | 8.22374 |
Annual Sum or Average | 5943.00000 | 24.47884 | 37.38300 | 0.11602 | 8.30844 |
Minimum of Months | 454.00000 | 24.35537 | 17.19259 | -0.3727 | 6.95988 |
Maximum of Months | 514.00000 | 24.59175 | 61.92450 | 0.53407 | 11.83997 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.05571 | 24.74671 | 0.25170 | 6.64387 |
February | 454.00000 | 24.21149 | 19.01051 | 0.25875 | 6.64526 |
March | 514.00000 | 24.29506 | 26.15641 | 0.35444 | 7.94898 |
April | 485.00000 | 24.30718 | 32.41316 | 0.41600 | 8.97060 |
May | 508.00000 | 24.22037 | 40.77107 | -0.4200 | 9.19077 |
June | 496.00000 | 24.20648 | 46.99666 | -0.3590 | 8.04695 |
July | 497.00000 | 24.18200 | 48.81482 | -0.3449 | 7.68373 |
August | 514.00000 | 24.13731 | 47.33917 | -0.3550 | 7.75614 |
September | 485.00000 | 24.24764 | 45.29770 | -0.3678 | 8.36411 |
October | 502.00000 | 24.35154 | 38.34762 | 0.47015 | 10.07714 |
November | 489.00000 | 24.45215 | 28.91150 | 0.40987 | 9.09567 |
December | 497.00000 | 24.37461 | 21.25244 | 0.33390 | 7.66705 |
Annual Sum or Average | 5943.00000 | 24.25305 | 35.12600 | 0.05156 | 8.18240 |
Minimum of Months | 454.00000 | 24.05571 | 19.01051 | -0.4200 | 6.64387 |
Maximum of Months | 514.00000 | 24.45215 | 48.81482 | 0.47015 | 10.07714 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.62153 | 26.09384 | -0.1272 | 7.82539 |
February | 454.00000 | 23.12976 | 21.45990 | -0.0252 | 5.74899 |
March | 514.00000 | 23.69447 | 28.42499 | 0.17838 | 6.06680 |
April | 485.00000 | 23.88171 | 34.35660 | 0.27879 | 6.98996 |
May | 508.00000 | 23.96235 | 41.69415 | -0.5342 | 11.49143 |
June | 496.00000 | 24.02369 | 47.93428 | -0.4478 | 9.66215 |
July | 497.00000 | 24.01444 | 49.86999 | -0.4323 | 9.35463 |
August | 514.00000 | 24.07079 | 48.16467 | -0.4182 | 9.10507 |
September | 485.00000 | 23.98930 | 46.38285 | -0.4799 | 10.35619 |
October | 502.00000 | 23.99605 | 39.76239 | 0.35959 | 8.13373 |
November | 489.00000 | 23.74893 | 31.67718 | 0.21035 | 6.61951 |
December | 497.00000 | 23.35787 | 24.29141 | 0.05502 | 5.53268 |
Annual Sum or Average | 5943.00000 | 23.71153 | 36.78828 | -0.1167 | 8.09335 |
Minimum of Months | 454.00000 | 22.62153 | 21.45990 | -0.5342 | 5.53268 |
Maximum of Months | 514.00000 | 24.07079 | 49.86999 | 0.35959 | 11.49143 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.27540 | 28.27288 | -0.4613 | 12.99914 |
February | 454.00000 | 21.56685 | 22.78864 | -0.4190 | 10.92551 |
March | 514.00000 | 22.65028 | 30.83358 | -0.0820 | 6.61528 |
April | 485.00000 | 23.24409 | 36.07441 | 0.12068 | 6.73206 |
May | 508.00000 | 23.77996 | 42.48690 | -0.5942 | 13.20130 |
June | 496.00000 | 24.05029 | 47.69264 | -0.4272 | 9.34230 |
July | 497.00000 | 24.11465 | 49.27067 | -0.3811 | 8.46696 |
August | 514.00000 | 24.11881 | 47.73737 | -0.3872 | 8.63112 |
September | 485.00000 | 23.83196 | 46.84145 | -0.5316 | 11.71028 |
October | 502.00000 | 23.46184 | 41.33266 | 0.22336 | 7.29212 |
November | 489.00000 | 22.47311 | 34.51993 | -0.1103 | 7.42182 |
December | 497.00000 | 21.66917 | 27.20783 | -0.3642 | 9.75552 |
Annual Sum or Average | 5943.00000 | 23.03108 | 38.03073 | -0.2841 | 9.41502 |
Minimum of Months | 454.00000 | 21.27540 | 22.78864 | -0.5942 | 6.61528 |
Maximum of Months | 514.00000 | 24.11881 | 49.27067 | 0.22336 | 13.20130 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.98290 | 24.44810 | -0.2636 | 7.81074 |
February | 454.00000 | 22.19253 | 19.24589 | -0.2428 | 7.41541 |
March | 514.00000 | 23.24760 | 26.95143 | 0.07340 | 5.90986 |
April | 485.00000 | 23.74609 | 32.67826 | 0.25421 | 6.96113 |
May | 508.00000 | 24.02795 | 40.33113 | -0.4982 | 10.76598 |
June | 496.00000 | 24.22531 | 46.85436 | -0.3354 | 7.78148 |
July | 497.00000 | 24.31925 | 48.79727 | -0.2655 | 6.98681 |
August | 514.00000 | 24.18904 | 46.85151 | -0.3177 | 7.40426 |
September | 485.00000 | 24.09526 | 45.42604 | -0.4275 | 9.45320 |
October | 502.00000 | 23.84641 | 38.55111 | 0.32563 | 7.91892 |
November | 489.00000 | 23.36193 | 29.65196 | 0.11706 | 6.27022 |
December | 497.00000 | 22.85843 | 22.22969 | -0.0617 | 5.78629 |
Annual Sum or Average | 5943.00000 | 23.51682 | 35.28634 | -0.1369 | 7.54003 |
Minimum of Months | 454.00000 | 21.98290 | 19.24589 | -0.4982 | 5.78629 |
Maximum of Months | 514.00000 | 24.31925 | 48.79727 | 0.32563 | 10.76598 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.57088 | 24.31053 | -0.3374 | 8.36737 |
February | 454.00000 | 21.88156 | 18.86981 | -0.2884 | 7.84491 |
March | 514.00000 | 22.62507 | 27.24238 | -0.0292 | 6.25003 |
April | 485.00000 | 23.16955 | 33.39005 | 0.16571 | 7.19827 |
May | 508.00000 | 23.68455 | 40.80540 | -0.5315 | 13.24878 |
June | 496.00000 | 23.79574 | 47.54274 | -0.4160 | 9.98479 |
July | 497.00000 | 23.87940 | 49.43246 | -0.3525 | 9.03287 |
August | 514.00000 | 23.76351 | 47.57787 | -0.3853 | 9.27704 |
September | 485.00000 | 23.68551 | 46.02779 | -0.4883 | 12.29352 |
October | 502.00000 | 23.40712 | 39.13880 | 0.27013 | 7.79153 |
November | 489.00000 | 22.65042 | 30.18912 | -0.0154 | 6.27157 |
December | 497.00000 | 22.00369 | 22.44537 | -0.2309 | 6.92424 |
Annual Sum or Average | 5943.00000 | 23.01800 | 35.70416 | -0.2201 | 8.71413 |
Minimum of Months | 454.00000 | 21.57088 | 18.86981 | -0.5315 | 6.25003 |
Maximum of Months | 514.00000 | 23.87940 | 49.43246 | 0.27013 | 13.24878 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.13467 | 23.98291 | -0.2106 | 8.76607 |
February | 454.00000 | 22.65996 | 18.39212 | -0.1090 | 7.98123 |
March | 514.00000 | 23.19421 | 26.52281 | 0.09618 | 6.82056 |
April | 485.00000 | 23.54966 | 32.82172 | 0.22674 | 7.30387 |
May | 508.00000 | 23.89799 | 40.59760 | -0.5293 | 11.83795 |
June | 496.00000 | 24.15507 | 46.92099 | -0.3496 | 8.12048 |
July | 497.00000 | 24.29674 | 48.66253 | -0.2588 | 7.04103 |
August | 514.00000 | 24.22179 | 46.50379 | -0.2657 | 7.07403 |
September | 485.00000 | 24.22008 | 44.75833 | -0.3247 | 8.85088 |
October | 502.00000 | 24.21498 | 37.23006 | 0.47663 | 11.26506 |
November | 489.00000 | 23.40384 | 29.12001 | 0.16255 | 7.43371 |
December | 497.00000 | 22.90221 | 21.71094 | -0.0199 | 7.27395 |
Annual Sum or Average | 5943.00000 | 23.57711 | 34.89023 | -0.0929 | 8.32022 |
Minimum of Months | 454.00000 | 22.13467 | 18.39212 | -0.5293 | 6.82056 |
Maximum of Months | 514.00000 | 24.29674 | 48.66253 | 0.47663 | 11.83795 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.04719 | 23.41347 | -0.2015 | 7.04651 |
February | 454.00000 | 22.68418 | 17.79492 | -0.0696 | 6.40683 |
March | 514.00000 | 23.84824 | 25.03126 | 0.30169 | 7.80018 |
April | 485.00000 | 24.30458 | 30.88042 | 0.49321 | 11.11008 |
May | 508.00000 | 23.96590 | 39.97248 | -0.3973 | 9.83579 |
June | 496.00000 | 24.29875 | 45.72243 | -0.1684 | 6.98970 |
July | 497.00000 | 24.43002 | 47.36861 | -0.0728 | 6.46711 |
August | 514.00000 | 24.35637 | 45.50643 | -0.0499 | 6.02546 |
September | 485.00000 | 23.95308 | 45.02663 | -0.3504 | 9.41486 |
October | 502.00000 | 24.09967 | 37.32608 | 0.47531 | 10.70448 |
November | 489.00000 | 23.86104 | 27.87937 | 0.29925 | 7.97343 |
December | 497.00000 | 23.76076 | 20.07024 | 0.21532 | 6.73851 |
Annual Sum or Average | 5943.00000 | 23.80821 | 33.95186 | 0.03977 | 8.04414 |
Minimum of Months | 454.00000 | 22.04719 | 17.79492 | -0.3973 | 6.02546 |
Maximum of Months | 514.00000 | 24.43002 | 47.36861 | 0.49321 | 11.11008 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.37504 | 26.79891 | -0.6982 | 17.79702 |
February | 454.00000 | 20.56934 | 21.01392 | -0.6700 | 16.42295 |
March | 514.00000 | 21.55965 | 29.79021 | -0.3376 | 8.89518 |
April | 485.00000 | 22.56592 | 35.44609 | -0.0417 | 6.85143 |
May | 508.00000 | 23.59139 | 41.79961 | -0.6646 | 15.40380 |
June | 496.00000 | 24.08691 | 49.06060 | -0.3983 | 8.94886 |
July | 497.00000 | 24.30466 | 51.91638 | -0.2853 | 7.45008 |
August | 514.00000 | 24.19437 | 48.97693 | -0.3452 | 8.14388 |
September | 485.00000 | 23.74083 | 47.31443 | -0.5640 | 12.68041 |
October | 502.00000 | 22.96565 | 41.02677 | 0.10523 | 6.97902 |
November | 489.00000 | 21.55355 | 33.11599 | -0.3223 | 9.28156 |
December | 497.00000 | 20.71142 | 25.34194 | -0.5935 | 13.57491 |
Annual Sum or Average | 5943.00000 | 22.53341 | 37.75422 | -0.3998 | 11.00059 |
Minimum of Months | 454.00000 | 20.37504 | 21.01392 | -0.6982 | 6.85143 |
Maximum of Months | 514.00000 | 24.30466 | 51.91638 | 0.10523 | 17.79702 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.22375 | 25.58961 | -0.7212 | 18.45088 |
February | 385.00000 | 20.60094 | 19.69167 | -0.6392 | 15.40200 |
March | 433.00000 | 21.42678 | 28.86982 | -0.3358 | 8.97242 |
April | 410.00000 | 22.42375 | 34.66251 | -0.0317 | 7.63594 |
May | 430.00000 | 23.22012 | 41.89415 | -0.6990 | 19.11289 |
June | 418.00000 | 23.64344 | 49.33287 | -0.4745 | 12.16923 |
July | 422.00000 | 23.99237 | 51.59406 | -0.3220 | 9.71104 |
August | 433.00000 | 23.92365 | 48.76139 | -0.3499 | 9.51041 |
September | 410.00000 | 23.27581 | 47.63857 | -0.6369 | 16.96448 |
October | 427.00000 | 22.57119 | 40.56713 | 0.06053 | 6.93362 |
November | 417.00000 | 21.24040 | 32.54831 | -0.3691 | 9.42466 |
December | 422.00000 | 20.62596 | 24.17437 | -0.6008 | 13.63397 |
Annual Sum or Average | 5034.00000 | 22.27496 | 37.22100 | -0.4254 | 12.30535 |
Minimum of Months | 385.00000 | 20.22375 | 19.69167 | -0.7212 | 6.93362 |
Maximum of Months | 433.00000 | 23.99237 | 51.59406 | 0.06053 | 19.11289 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.25969 | 25.42993 | -0.4391 | 13.92355 |
February | 454.00000 | 21.93826 | 19.36736 | -0.2908 | 10.99466 |
March | 514.00000 | 22.44654 | 27.94494 | -0.0860 | 8.03574 |
April | 485.00000 | 22.88632 | 34.35496 | 0.05882 | 7.38102 |
May | 508.00000 | 23.60038 | 41.58163 | -0.6410 | 15.10698 |
June | 496.00000 | 24.04727 | 48.93324 | -0.3978 | 9.16623 |
July | 497.00000 | 24.30007 | 51.53150 | -0.2694 | 7.50768 |
August | 514.00000 | 24.28884 | 48.22148 | -0.2648 | 7.47704 |
September | 485.00000 | 24.11673 | 45.73825 | -0.3659 | 10.15582 |
October | 502.00000 | 24.01579 | 37.90385 | 0.42587 | 11.14287 |
November | 489.00000 | 22.62825 | 30.84829 | -0.0240 | 8.23163 |
December | 497.00000 | 21.99443 | 23.44670 | -0.2487 | 10.01688 |
Annual Sum or Average | 5943.00000 | 23.13591 | 36.39987 | -0.2120 | 9.92927 |
Minimum of Months | 454.00000 | 21.25969 | 19.36736 | -0.6410 | 7.38102 |
Maximum of Months | 514.00000 | 24.30007 | 51.53150 | 0.42587 | 15.10698 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.53134 | 25.80262 | -0.6329 | 15.74278 |
February | 454.00000 | 20.84138 | 19.99378 | -0.5714 | 13.97378 |
March | 514.00000 | 21.75351 | 28.60493 | -0.2419 | 8.09604 |
April | 485.00000 | 22.48605 | 34.69971 | 0.00057 | 7.39243 |
May | 508.00000 | 23.21284 | 42.03392 | -0.6893 | 17.69330 |
June | 496.00000 | 23.85052 | 48.54895 | -0.3776 | 10.13122 |
July | 497.00000 | 24.08836 | 50.97740 | -0.2661 | 8.60526 |
August | 514.00000 | 24.15107 | 47.97963 | -0.2352 | 7.84188 |
September | 485.00000 | 23.29410 | 47.49202 | -0.6123 | 15.55048 |
October | 502.00000 | 22.77863 | 40.52813 | 0.12713 | 7.17736 |
November | 489.00000 | 21.39164 | 32.54949 | -0.3260 | 8.75175 |
December | 497.00000 | 20.87846 | 24.25307 | -0.5271 | 11.80969 |
Annual Sum or Average | 5943.00000 | 22.45212 | 37.07596 | -0.3612 | 11.03963 |
Minimum of Months | 454.00000 | 20.53134 | 19.99378 | -0.6893 | 7.17736 |
Maximum of Months | 514.00000 | 24.15107 | 50.97740 | 0.12713 | 17.69330 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.99620 | 27.39977 | -0.8326 | 22.73142 |
February | 454.00000 | 20.12743 | 21.70340 | -0.8270 | 21.99319 |
March | 514.00000 | 20.93018 | 31.01866 | -0.5115 | 12.68288 |
April | 485.00000 | 21.96728 | 36.58336 | -0.1908 | 8.68125 |
May | 508.00000 | 23.22912 | 42.74411 | -0.7747 | 19.88369 |
June | 496.00000 | 23.99903 | 49.36539 | -0.4111 | 9.59703 |
July | 497.00000 | 24.28140 | 52.05700 | -0.2709 | 7.53829 |
August | 514.00000 | 24.14393 | 49.05842 | -0.3442 | 8.45732 |
September | 485.00000 | 23.44943 | 48.15925 | -0.6514 | 15.82052 |
October | 502.00000 | 22.28692 | 42.42616 | -0.0570 | 8.17848 |
November | 489.00000 | 20.73057 | 34.90940 | -0.5449 | 14.11413 |
December | 497.00000 | 20.11969 | 26.87907 | -0.7863 | 20.38627 |
Annual Sum or Average | 5943.00000 | 22.12143 | 38.64495 | -0.5148 | 14.11618 |
Minimum of Months | 454.00000 | 19.99620 | 21.70340 | -0.8326 | 7.53829 |
Maximum of Months | 514.00000 | 24.28140 | 52.05700 | -0.0570 | 22.73142 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02464 | 26.73148 | -0.8076 | 21.88111 |
February | 454.00000 | 20.25577 | 21.02216 | -0.7637 | 19.64149 |
March | 514.00000 | 21.06693 | 30.23953 | -0.4423 | 11.53781 |
April | 485.00000 | 22.15443 | 35.55238 | -0.1049 | 8.57397 |
May | 508.00000 | 23.07189 | 42.63182 | -0.7360 | 20.80441 |
June | 496.00000 | 23.65164 | 49.38781 | -0.4477 | 11.71414 |
July | 497.00000 | 24.00886 | 51.44818 | -0.2848 | 9.09383 |
August | 514.00000 | 23.95237 | 48.54590 | -0.3096 | 8.88935 |
September | 485.00000 | 23.17162 | 48.10056 | -0.6585 | 17.81227 |
October | 502.00000 | 22.28266 | 41.75009 | -0.0099 | 7.76889 |
November | 489.00000 | 20.71889 | 34.30407 | -0.5208 | 13.19425 |
December | 497.00000 | 20.18788 | 26.17868 | -0.7515 | 19.09686 |
Annual Sum or Average | 5943.00000 | 22.06066 | 38.11169 | -0.4845 | 14.12419 |
Minimum of Months | 454.00000 | 20.02464 | 21.02216 | -0.8076 | 7.76889 |
Maximum of Months | 514.00000 | 24.00886 | 51.44818 | -0.0099 | 21.88111 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.69671 | 26.32173 | -0.6074 | 18.36433 |
February | 454.00000 | 21.16715 | 20.36406 | -0.5094 | 15.63172 |
March | 514.00000 | 21.76761 | 29.37309 | -0.2671 | 10.64746 |
April | 485.00000 | 22.32195 | 35.54577 | -0.0825 | 8.72908 |
May | 508.00000 | 23.22394 | 42.57486 | -0.7548 | 19.71825 |
June | 496.00000 | 23.93384 | 49.29672 | -0.4184 | 10.04371 |
July | 497.00000 | 24.25539 | 51.73421 | -0.2617 | 7.74670 |
August | 514.00000 | 24.21476 | 48.37629 | -0.2714 | 7.89731 |
September | 485.00000 | 23.82830 | 46.58989 | -0.4533 | 12.63090 |
October | 502.00000 | 23.45414 | 39.13113 | 0.28649 | 10.29382 |
November | 489.00000 | 21.76296 | 32.77399 | -0.2518 | 10.84030 |
December | 497.00000 | 21.15138 | 25.32408 | -0.4866 | 14.94615 |
Annual Sum or Average | 5943.00000 | 22.66021 | 37.40623 | -0.3391 | 12.27538 |
Minimum of Months | 454.00000 | 20.69671 | 20.36406 | -0.7548 | 7.74670 |
Maximum of Months | 514.00000 | 24.25539 | 51.73421 | 0.28649 | 19.71825 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.18865 | 26.41489 | -0.7508 | 20.00847 |
February | 454.00000 | 20.46253 | 20.75571 | -0.7006 | 18.16195 |
March | 514.00000 | 21.31061 | 29.65744 | -0.3690 | 10.42271 |
April | 485.00000 | 22.06024 | 35.63887 | -0.1088 | 8.52540 |
May | 508.00000 | 22.88929 | 42.94770 | -0.7859 | 21.77400 |
June | 496.00000 | 23.70117 | 49.03175 | -0.4091 | 11.31489 |
July | 497.00000 | 24.00356 | 51.32764 | -0.2715 | 9.06100 |
August | 514.00000 | 24.03730 | 48.25076 | -0.2555 | 8.54371 |
September | 485.00000 | 23.01287 | 48.34227 | -0.6955 | 18.70679 |
October | 502.00000 | 22.31004 | 41.60766 | 0.01092 | 7.79227 |
November | 489.00000 | 20.82623 | 33.99005 | -0.4858 | 12.16398 |
December | 497.00000 | 20.41985 | 25.70415 | -0.6777 | 16.52600 |
Annual Sum or Average | 5943.00000 | 22.11671 | 37.92516 | -0.4563 | 13.54470 |
Minimum of Months | 454.00000 | 20.18865 | 20.75571 | -0.7859 | 7.79227 |
Maximum of Months | 514.00000 | 24.03730 | 51.32764 | 0.01092 | 21.77400 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.399197E+09 | 3782.95 | 30-JAN-11:30 | 39.80 | 0.121167E+10 | 0.00 | 0.161087E+10 | 0.16 | 3.04 | 09-JAN-19:30 | 0.00 | 0.00 |
February | 0.439157E+09 | 12785.31 | 10-FEB-12:20 | 40.65 | 0.133307E+10 | 0.00 | 0.177222E+10 | 0.18 | 3.04 | 22-FEB-11:10 | 0.00 | 0.00 |
March | 0.432585E+10 | 96835.64 | 27-MAR-13:30 | 72.15 | 0.202890E+11 | 0.00 | 0.246148E+11 | 0.33 | 7.28 | 27-MAR-13:20 | 0.00 | 0.00 |
April | 0.233874E+11 | 100888.27 | 07-APR-11:40 | 153.99 | 0.128306E+12 | 0.00 | 0.151694E+12 | 0.95 | 7.19 | 07-APR-10:50 | 0.00 | 0.00 |
May | 0.776081E+11 | 116011.13 | 31-MAY-14:10 | 375.57 | 0.446915E+12 | 0.00 | 0.524523E+12 | 2.56 | 7.41 | 19-MAY-16:00 | 0.00 | 0.00 |
June | 0.152118E+12 | 156277.63 | 20-JUN-05:02 | 518.18 | 0.100125E+13 | 0.00 | 0.115337E+13 | 4.40 | 7.75 | 14-JUN-05:02 | 0.00 | 0.00 |
July | 0.185259E+12 | 202239.85 | 22-JUL-05:03 | 600.94 | 0.118188E+13 | 0.00 | 0.136714E+13 | 4.69 | 7.73 | 01-JUL-05:02 | 0.00 | 0.00 |
August | 0.185833E+12 | 199684.53 | 17-AUG-05:02 | 637.06 | 0.119011E+13 | 0.00 | 0.137594E+13 | 4.92 | 7.72 | 28-AUG-05:04 | 0.00 | 0.00 |
September | 0.122423E+12 | 173424.83 | 08-SEP-05:03 | 446.44 | 0.783284E+12 | 0.00 | 0.905708E+12 | 3.68 | 7.67 | 13-SEP-05:02 | 0.00 | 0.00 |
October | 0.650955E+11 | 129179.97 | 06-OCT-05:03 | 280.16 | 0.407254E+12 | 0.00 | 0.472349E+12 | 2.10 | 7.69 | 06-OCT-05:03 | 0.00 | 0.00 |
November | 0.618033E+10 | 61404.38 | 10-NOV-10:00 | 79.59 | 0.240176E+11 | 0.00 | 0.301979E+11 | 0.37 | 6.17 | 10-NOV-10:00 | 0.00 | 0.00 |
December | 0.854550E+09 | 31446.95 | 25-DEC-16:01 | 70.66 | 0.259412E+10 | 0.00 | 0.344867E+10 | 0.29 | 3.04 | 22-DEC-13:45 | 0.00 | 0.00 |
Annual Sum or Average | 0.823923E+12 | 3315.19 | 0.518845E+13 | 0.601237E+13 | 2.07 | |||||||
Minimum of Months | 0.399197E+09 | 3782.95 | 39.80 | 0.121167E+10 | 0.00 | 0.161087E+10 | 0.16 | 3.04 | 0.00 | 0.00 | ||
Maximum of Months | 0.185833E+12 | 202239.85 | 637.06 | 0.119011E+13 | 0.00 | 0.137594E+13 | 4.92 | 7.75 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 59950380.92 | 99917.30 | 07-APR-13:50 | 0.17 | 0.424984E+09 | 0.00 | 0.484934E+09 | 0.00 | 7.09 | 07-APR-13:50 | 0.00 | 0.00 |
May | 0.436079E+10 | 116011.13 | 31-MAY-14:10 | 11.25 | 0.306708E+11 | 0.00 | 0.350316E+11 | 0.11 | 7.17 | 31-MAY-07:15 | 0.00 | 0.00 |
June | 0.528747E+11 | 156277.63 | 20-JUN-05:02 | 135.25 | 0.366172E+12 | 0.00 | 0.419047E+12 | 1.30 | 7.75 | 14-JUN-05:02 | 0.00 | 0.00 |
July | 0.864900E+11 | 202239.85 | 22-JUL-05:03 | 210.54 | 0.578723E+12 | 0.00 | 0.665213E+12 | 1.90 | 7.73 | 01-JUL-05:02 | 0.00 | 0.00 |
August | 0.768722E+11 | 199684.53 | 17-AUG-05:02 | 185.69 | 0.514680E+12 | 0.00 | 0.591552E+12 | 1.68 | 7.72 | 28-AUG-05:04 | 0.00 | 0.00 |
September | 0.330102E+11 | 173424.83 | 08-SEP-05:03 | 84.24 | 0.228136E+12 | 0.00 | 0.261146E+12 | 0.81 | 7.67 | 13-SEP-05:02 | 0.00 | 0.00 |
October | 0.881378E+10 | 129179.97 | 06-OCT-05:03 | 23.40 | 0.626842E+11 | 0.00 | 0.714980E+11 | 0.22 | 7.69 | 06-OCT-05:03 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.262481E+12 | 650.52 | 0.178149E+13 | 0.204397E+13 | 0.51 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.864900E+11 | 202239.85 | 210.54 | 0.578723E+12 | 0.00 | 0.665213E+12 | 1.90 | 7.75 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.994160E+10 | 744.00 | 22246.86 | 21-JAN-19:13 | 543031.03 | 21-JAN-05:20 | 21.69 | 18.33 | 13.68 |
February | 0.138403E+11 | 672.00 | 31160.26 | 19-FEB-14:42 | 575481.87 | 15-FEB-23:01 | 24.54 | 18.33 | 13.65 |
March | 0.450927E+11 | 744.00 | 49248.27 | 02-MAR-15:40 | 605715.33 | 04-MAR-21:31 | 27.45 | 18.40 | 13.76 |
April | 0.937885E+11 | 720.00 | 49248.27 | 05-APR-10:50 | 631695.44 | 07-APR-17:20 | 31.25 | 19.37 | 13.90 |
May | 0.819015E+11 | 744.00 | 49248.27 | 01-MAY-10:50 | 455854.19 | 01-MAY-02:30 | 23.24 | 19.62 | 13.90 |
June | 0.126854E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 380527.64 | 19-JUN-12:20 | 31.14 | 24.48 | 13.91 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 528796.49 | 07-JUL-12:20 | 38.99 | 29.14 | 13.91 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 661380.26 | 04-AUG-21:02 | 42.69 | 30.06 | 13.91 |
September | 0.113114E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 434032.70 | 01-SEP-00:03 | 25.79 | 22.03 | 13.91 |
October | 0.899256E+11 | 744.00 | 49248.27 | 02-OCT-08:20 | 580113.61 | 28-OCT-17:20 | 25.96 | 19.53 | 13.87 |
November | 0.562260E+11 | 720.00 | 49248.27 | 02-NOV-11:40 | 599325.03 | 14-NOV-22:13 | 27.40 | 18.40 | 13.84 |
December | 0.481951E+11 | 744.00 | 43146.39 | 17-DEC-15:00 | 616448.83 | 27-DEC-22:20 | 30.00 | 18.33 | 13.87 |
Annual Sum or Average | 0.942692E+12 | 8760.00 | 29.22 | 21.36 | 13.84 | ||||
Minimum of Months | 0.994160E+10 | 672.00 | 22246.86 | 380527.64 | 21.69 | 18.33 | 13.65 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 661380.26 | 42.69 | 30.06 | 13.91 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 217703.86 | 07-JAN-09:15 | 21.03 | 21.02 | 0.33 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 219174.05 | 10-FEB-12:20 | 20.99 | 20.99 | 0.41 |
March | 83230151.16 | 11.33 | 20390.58 | 27-MAR-13:40 | 806109.77 | 27-MAR-13:40 | 21.05 | 21.01 | 2.31 |
April | 0.381216E+09 | 93.35 | 4467.21 | 08-APR-10:00 | 855847.37 | 07-APR-15:40 | 21.32 | 21.07 | 9.90 |
May | 0.410711E+10 | 319.61 | 20390.58 | 18-MAY-08:50 | 949747.38 | 30-MAY-11:30 | 22.23 | 21.38 | 27.70 |
June | 0.264556E+11 | 503.08 | 20390.58 | 01-JUN-07:40 | 1034468.13 | 27-JUN-16:00 | 24.71 | 22.79 | 39.77 |
July | 0.418622E+11 | 600.58 | 20390.58 | 01-JUL-03:01 | 1102784.33 | 26-JUL-16:00 | 26.37 | 24.18 | 42.65 |
August | 0.346882E+11 | 617.51 | 20390.58 | 01-AUG-00:20 | 1084302.29 | 02-AUG-15:10 | 25.48 | 23.28 | 46.41 |
September | 0.149712E+11 | 424.44 | 20390.58 | 01-SEP-02:22 | 1012398.13 | 14-SEP-10:10 | 23.91 | 22.41 | 34.60 |
October | 0.704659E+10 | 238.03 | 20390.58 | 02-OCT-14:50 | 945286.16 | 24-OCT-13:50 | 22.24 | 21.47 | 20.55 |
November | 41231434.25 | 27.17 | 1891.49 | 10-NOV-10:00 | 445864.09 | 10-NOV-10:00 | 21.16 | 21.11 | 3.38 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 218488.88 | 21-DEC-12:50 | 21.03 | 21.02 | 0.73 |
Annual Sum or Average | 0.129637E+12 | 2835.10 | 22.64 | 21.82 | 19.18 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 217703.86 | 20.99 | 20.99 | 0.33 | ||
Maximum of Months | 0.418622E+11 | 617.51 | 20390.58 | 1102784.33 | 26.37 | 24.18 | 46.41 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.03 | 21.03 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 20.99 | 20.99 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.05 | 21.05 | 0.00 |
April | 2472201.34 | 0.17 | 4120.34 | 07-APR-13:50 | 845770.50 | 07-APR-13:50 | 21.32 | 21.32 | 0.01 |
May | 0.899224E+09 | 12.25 | 20390.58 | 30-MAY-10:30 | 949747.38 | 30-MAY-11:30 | 22.23 | 22.17 | 0.93 |
June | 0.134848E+11 | 183.73 | 20390.58 | 01-JUN-09:40 | 1034468.13 | 27-JUN-16:00 | 24.71 | 23.81 | 13.39 |
July | 0.255235E+11 | 347.70 | 20390.58 | 01-JUL-05:03 | 1102784.33 | 26-JUL-16:00 | 26.37 | 24.73 | 23.02 |
August | 0.201639E+11 | 278.12 | 20390.58 | 01-AUG-04:29 | 1084302.29 | 02-AUG-15:10 | 25.48 | 24.14 | 18.90 |
September | 0.813949E+10 | 110.90 | 20390.58 | 01-SEP-05:03 | 1012398.13 | 14-SEP-10:10 | 23.91 | 23.36 | 8.12 |
October | 0.176419E+10 | 24.03 | 20390.58 | 03-OCT-11:00 | 945286.16 | 24-OCT-13:50 | 22.24 | 22.12 | 1.86 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.16 | 21.16 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.03 | 21.03 | 0.00 |
Annual Sum or Average | 0.699776E+11 | 956.90 | 22.64 | 22.25 | 5.57 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 20.99 | 0.00 | ||
Maximum of Months | 0.255235E+11 | 347.70 | 20390.58 | 1102784.33 | 26.37 | 24.73 | 23.02 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.215634E+12 | 0.00 | 507.57 | 1980696.16 | 02-JAN-07:10 | 0.00 | 72.90 | 78.15 | 2.27 | 0.00 | 0.05 | 1.15 | 02-JAN-07:10 |
February | 0.152405E+12 | 0.00 | 444.80 | 1628723.13 | 06-FEB-07:10 | 0.00 | 72.41 | 78.25 | 1.49 | 0.00 | 0.04 | 0.95 | 06-FEB-07:10 |
March | 0.606398E+11 | 0.00 | 377.18 | 862889.27 | 23-MAR-06:10 | 0.00 | 71.77 | 76.69 | 0.52 | 0.00 | 0.01 | 0.50 | 23-MAR-06:10 |
April | 0.186291E+11 | 0.00 | 205.22 | 1043829.86 | 03-APR-05:01 | 0.00 | 63.84 | 68.75 | 0.10 | 0.00 | 0.00 | 0.61 | 03-APR-05:01 |
May | 0.170653E+10 | 0.00 | 44.38 | 514721.26 | 16-MAY-03:50 | 0.00 | 67.56 | 68.10 | 0.03 | 0.00 | 0.00 | 0.30 | 16-MAY-03:50 |
June | 0.136681E+10 | 0.00 | 10.82 | 290664.47 | 23-JUN-03:47 | 0.00 | 69.87 | 70.03 | 0.01 | 0.00 | 0.00 | 0.17 | 23-JUN-03:47 |
July | 0.759055E+09 | 0.00 | 5.19 | 303802.17 | 13-JUL-03:45 | 0.00 | 70.01 | 70.08 | 0.01 | 0.00 | 0.00 | 0.18 | 13-JUL-03:45 |
August | 0.190273E+10 | 0.00 | 17.51 | 399454.90 | 31-AUG-03:50 | 0.00 | 69.55 | 69.81 | 0.02 | 0.00 | 0.00 | 0.23 | 31-AUG-03:50 |
September | 0.168515E+10 | 0.00 | 21.40 | 323448.07 | 02-SEP-03:45 | 0.00 | 70.05 | 70.34 | 0.02 | 0.00 | 0.00 | 0.19 | 02-SEP-03:45 |
October | 0.593092E+10 | 0.00 | 93.55 | 372782.25 | 07-OCT-03:47 | 0.00 | 72.47 | 73.17 | 0.11 | 0.00 | 0.00 | 0.22 | 07-OCT-03:47 |
November | 0.598455E+11 | 0.00 | 327.46 | 980956.40 | 24-NOV-07:10 | 0.00 | 69.56 | 74.34 | 0.47 | 0.00 | 0.01 | 0.57 | 24-NOV-07:10 |
December | 0.125064E+12 | 0.00 | 445.30 | 1326065.03 | 28-DEC-05:01 | 0.00 | 56.10 | 69.98 | 0.49 | 0.00 | 0.03 | 0.77 | 28-DEC-05:01 |
Annual Sum or Average | 0.645568E+12 | 2500.40 | 68.82 | 72.28 | 0.46 | 0.00 | 0.01 | ||||||
Minimum of Months | 0.759055E+09 | 0.00 | 5.19 | 290664.47 | 0.00 | 56.10 | 68.10 | 0.01 | 0.00 | 0.00 | 0.17 | ||
Maximum of Months | 0.215634E+12 | 0.00 | 507.57 | 1980696.16 | 0.00 | 72.90 | 78.25 | 2.27 | 0.00 | 0.05 | 1.15 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 21.69 | 21.69 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.54 | 24.54 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.45 | 27.45 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.25 | 31.25 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 23.24 | 23.24 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 31.14 | 31.14 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 38.99 | 38.99 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 42.69 | 42.69 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 25.79 | 25.79 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.96 | 25.96 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.40 | 27.40 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.00 | 30.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.22 | 29.22 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 | 21.69 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.69 | 42.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 8852447.20 | 0.00 | 0.74 | 3950100.46 | 0.00 | 0.00 | 0.00 | 0.00 | 37064.77 | 24-JAN-06:02 | 16254.47 | 24-JAN-06:02 | 0.00 | 0.00 | 0.00 |
February | 206.81 | 0.00 | 0.09 | 206.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 06-FEB-05:25 | 0.65 | 06-FEB-05:25 | 0.00 | 0.00 | 0.00 |
March | 0.677044E+09 | 0.00 | 8.26 | 0.676742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44027.06 | 27-MAR-16:00 | 44027.06 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.586349E+10 | 0.00 | 73.51 | 0.582344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66597.95 | 07-APR-13:50 | 66597.95 | 07-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.172950E+11 | 0.00 | 193.50 | 0.162190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104685.04 | 29-MAY-11:30 | 104685.04 | 29-MAY-11:30 | 0.00 | 0.00 | 0.00 |
June | 0.696316E+11 | 0.00 | 395.77 | 0.578800E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 171447.19 | 19-JUN-00:08 | 105495.31 | 12-JUN-00:42 | 0.00 | 0.00 | 0.00 |
July | 0.984115E+11 | 0.00 | 420.43 | 0.774105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176762.93 | 09-JUL-20:01 | 97527.47 | 03-JUL-02:61 | 0.00 | 0.00 | 0.00 |
August | 0.985475E+11 | 0.00 | 446.82 | 0.819854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 157193.26 | 13-AUG-21:51 | 111285.70 | 20-AUG-23:08 | 0.00 | 0.00 | 0.00 |
September | 0.528878E+11 | 0.00 | 347.18 | 0.459533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 150117.68 | 01-SEP-03:01 | 109984.75 | 04-SEP-19:42 | 0.00 | 0.00 | 0.00 |
October | 0.209233E+11 | 0.00 | 191.40 | 0.173112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 110840.09 | 06-OCT-05:03 | 63018.91 | 04-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.278698E+09 | 0.00 | 10.34 | 0.239712E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 65358.21 | 10-NOV-06:02 | 26051.00 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 2931514.16 | 0.00 | 0.13 | 2521637.97 | 0.00 | 0.00 | 0.00 | 0.00 | 10277.62 | 25-DEC-10:11 | 8774.80 | 25-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.364528E+12 | 2088.18 | 0.303506E+12 | ||||||||||||
Minimum of Months | 206.81 | 0.00 | 0.09 | 206.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.65 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.985475E+11 | 0.00 | 446.82 | 0.819854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 176762.93 | 111285.70 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 22739308.61 | 0.00 | 17.47 | 22739308.61 | 0.00 | 0.00 | 0.00 | 0.00 | 7186.78 | 17-JAN-08:20 | 7186.78 | 17-JAN-08:20 | 0.00 | 0.00 | 0.00 |
February | 15070375.75 | 0.00 | 7.85 | 15070375.75 | 0.00 | 0.00 | 0.00 | 0.00 | 10740.90 | 22-FEB-10:00 | 10740.90 | 22-FEB-10:00 | 0.00 | 0.00 | 0.00 |
March | 0.206955E+10 | 0.00 | 43.90 | 0.175559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88227.15 | 27-MAR-13:00 | 69500.92 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.145356E+11 | 0.00 | 141.07 | 0.143753E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104466.64 | 07-APR-13:30 | 104466.64 | 07-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.451761E+11 | 0.00 | 358.04 | 0.377360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 149409.57 | 30-MAY-13:20 | 149409.57 | 30-MAY-13:20 | 0.00 | 0.00 | 0.00 |
June | 0.136119E+12 | 0.00 | 498.23 | 0.988123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 159431.29 | 21-JUN-05:01 | 145653.55 | 22-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.179293E+12 | 0.00 | 566.36 | 0.133577E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 172895.67 | 24-JUL-03:02 | 148108.28 | 31-JUL-05:01 | 0.00 | 0.00 | 0.00 |
August | 0.179317E+12 | 0.00 | 612.23 | 0.147225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 180701.44 | 15-AUG-05:02 | 160568.37 | 22-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.937192E+11 | 0.00 | 424.75 | 0.724840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 196277.74 | 14-SEP-03:01 | 162352.45 | 01-SEP-14:30 | 0.00 | 0.00 | 0.00 |
October | 0.492143E+11 | 0.00 | 269.66 | 0.340681E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143621.15 | 06-OCT-03:02 | 109520.21 | 06-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 0.224935E+10 | 0.00 | 50.81 | 0.194979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45519.70 | 10-NOV-10:00 | 37056.03 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 16987377.55 | 0.00 | 16.53 | 16987377.55 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.60 | 27-DEC-14:10 | 3253.60 | 27-DEC-14:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701748E+12 | 3006.89 | 0.542038E+12 | ||||||||||||
Minimum of Months | 15070375.75 | 0.00 | 7.85 | 15070375.75 | 0.00 | 0.00 | 0.00 | 0.00 | 3253.60 | 3253.60 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.179317E+12 | 0.00 | 612.23 | 0.147225E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 196277.74 | 162352.45 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 45543857.28 | 0.00 | 20.25 | 45543857.28 | 0.00 | 0.00 | 0.00 | 0.00 | 45287.87 | 25-JAN-17:40 | 45287.87 | 25-JAN-17:40 | 0.00 | 0.00 | 0.00 |
February | 0.182768E+09 | 0.00 | 17.11 | 0.182768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 142039.44 | 10-FEB-12:20 | 142039.44 | 10-FEB-12:20 | 0.00 | 0.00 | 0.00 |
March | 0.144735E+11 | 0.00 | 39.80 | 0.126116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 583572.04 | 27-MAR-13:00 | 485170.53 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.100698E+12 | 0.00 | 116.53 | 0.100293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 851262.26 | 07-APR-13:30 | 851262.26 | 07-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.387869E+12 | 0.00 | 347.01 | 0.322741E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1210735.76 | 30-MAY-13:30 | 1210735.76 | 30-MAY-13:30 | 0.00 | 0.00 | 0.00 |
June | 0.114969E+13 | 0.00 | 441.47 | 0.791996E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1832665.87 | 27-JUN-05:01 | 1373069.31 | 20-JUN-03:01 | 0.00 | 0.00 | 0.00 |
July | 0.145073E+13 | 0.00 | 454.96 | 0.995070E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2354068.95 | 24-JUL-03:02 | 1390633.81 | 10-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.139121E+13 | 0.00 | 476.89 | 0.107866E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1992036.84 | 04-AUG-03:01 | 1536391.32 | 22-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.823002E+12 | 0.00 | 404.02 | 0.619438E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2006057.91 | 14-SEP-05:01 | 1398057.81 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.401871E+12 | 0.00 | 260.04 | 0.269890E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1401854.53 | 06-OCT-05:02 | 813074.08 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.173156E+11 | 0.00 | 53.14 | 0.151405E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 303690.80 | 10-NOV-10:00 | 279337.95 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.392039E+09 | 0.00 | 20.27 | 0.392039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 219404.58 | 11-DEC-11:50 | 219404.58 | 11-DEC-11:50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.573747E+13 | 2651.49 | 0.420646E+13 | ||||||||||||
Minimum of Months | 45543857.28 | 0.00 | 17.11 | 45543857.28 | 0.00 | 0.00 | 0.00 | 0.00 | 45287.87 | 45287.87 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.145073E+13 | 0.00 | 476.89 | 0.107866E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2354068.95 | 1536391.32 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 10373092.09 | 0.00 | 22.32 | 10373092.09 | 0.00 | 0.00 | 0.00 | 0.00 | 2943.54 | 15-JAN-10:10 | 2943.54 | 15-JAN-10:10 | 0.00 | 0.00 | 0.00 |
February | 14773896.69 | 0.00 | 28.44 | 14773896.69 | 0.00 | 0.00 | 0.00 | 0.00 | 942.60 | 02-FEB-10:50 | 942.60 | 02-FEB-10:50 | 0.00 | 0.00 | 0.00 |
March | 0.134886E+10 | 0.00 | 58.51 | 0.118811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51500.96 | 27-MAR-13:00 | 42164.33 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.104179E+11 | 0.00 | 117.56 | 0.103821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 95110.95 | 07-APR-15:30 | 95110.95 | 07-APR-15:30 | 0.00 | 0.00 | 0.00 |
May | 0.409778E+11 | 0.00 | 344.64 | 0.342645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144031.12 | 30-MAY-13:10 | 144031.12 | 30-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.124874E+12 | 0.00 | 439.88 | 0.874184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 200864.98 | 19-JUN-03:01 | 156274.69 | 01-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.161695E+12 | 0.00 | 457.87 | 0.112840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264102.74 | 24-JUL-03:02 | 149346.91 | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.152893E+12 | 0.00 | 474.27 | 0.119837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 215062.27 | 04-AUG-03:01 | 186755.23 | 30-AUG-14:40 | 0.00 | 0.00 | 0.00 |
September | 0.856150E+11 | 0.00 | 395.43 | 0.644816E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 208800.20 | 14-SEP-05:01 | 174455.09 | 01-SEP-14:30 | 0.00 | 0.00 | 0.00 |
October | 0.394714E+11 | 0.00 | 251.68 | 0.264521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 140665.76 | 06-OCT-05:03 | 93142.75 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.155004E+10 | 0.00 | 67.36 | 0.135406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27207.68 | 10-NOV-08:00 | 26587.82 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 18886879.32 | 0.00 | 61.46 | 18886879.32 | 0.00 | 0.00 | 0.00 | 0.00 | 875.12 | 21-DEC-12:00 | 875.12 | 21-DEC-12:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.618887E+12 | 2719.43 | 0.458262E+12 | ||||||||||||
Minimum of Months | 10373092.09 | 0.00 | 22.32 | 10373092.09 | 0.00 | 0.00 | 0.00 | 0.00 | 875.12 | 875.12 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.161695E+12 | 0.00 | 474.27 | 0.119837E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 264102.74 | 186755.23 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.310203E+12 | 0.807320E+11 | 725.23 | 0.310082E+12 | 0.121078E+09 | 0.00 | 1.00 | 02-JAN-08:15 | 0.01 | 14-JAN-17:10 | 443523.07 | 03-JAN-22:40 | 443523.07 | 03-JAN-22:40 | 32788.77 | 22-JAN-19:43 | 91629.90 | 03-JAN-22:40 | 0.00 |
February | 0.490328E+12 | 0.119131E+12 | 663.79 | 0.490140E+12 | 0.188261E+09 | 0.00 | 1.00 | 01-FEB-22:10 | 0.01 | 28-FEB-05:28 | 438550.43 | 15-FEB-23:00 | 438550.43 | 15-FEB-23:00 | 26663.51 | 19-FEB-15:13 | 91544.62 | 15-FEB-23:00 | 0.00 |
March | 0.779530E+12 | 0.178576E+12 | 743.71 | 0.779418E+12 | 0.111128E+09 | 0.00 | 1.00 | 01-MAR-23:46 | 0.02 | 04-MAR-21:09 | 436914.37 | 04-MAR-21:30 | 436914.37 | 04-MAR-21:30 | 19581.42 | 01-MAR-23:46 | 91516.56 | 04-MAR-21:30 | 0.00 |
April | 0.986795E+12 | 0.225299E+12 | 720.00 | 0.986779E+12 | 15737000.46 | 0.00 | 1.00 | 01-APR-12:02 | 0.77 | 05-APR-04:30 | 424855.17 | 17-APR-21:25 | 424855.17 | 17-APR-21:25 | 1506.71 | 27-APR-19:00 | 125012.01 | 07-APR-13:00 | 0.00 |
May | 0.316447E+12 | 0.826162E+11 | 742.82 | 0.315099E+12 | 0.134772E+10 | 0.00 | 1.00 | 01-MAY-01:56 | 0.06 | 01-MAY-02:15 | 425245.26 | 02-MAY-03:36 | 425245.26 | 02-MAY-03:36 | 5363.88 | 31-MAY-17:00 | 91316.44 | 02-MAY-03:36 | 0.00 |
June | 0.540642E+12 | 0.153455E+12 | 720.00 | 0.535140E+12 | 0.550209E+10 | 0.00 | 0.63 | 19-JUN-12:00 | 0.52 | 01-JUN-06:05 | 218911.43 | 15-JUN-12:50 | 211617.50 | 19-JUN-12:00 | 10589.80 | 15-JUN-13:50 | 91460.17 | 19-JUN-12:00 | 0.00 |
July | 0.799386E+12 | 0.247540E+12 | 744.00 | 0.790746E+12 | 0.863932E+10 | 0.00 | 0.84 | 07-JUL-12:00 | 0.74 | 01-JUL-00:10 | 308654.25 | 20-JUL-15:00 | 299113.37 | 10-JUL-15:00 | 11407.98 | 20-JUL-15:00 | 118570.15 | 07-JUL-12:00 | 0.00 |
August | 0.103211E+13 | 0.316276E+12 | 744.00 | 0.102644E+13 | 0.567615E+10 | 0.00 | 1.00 | 01-AUG-08:40 | 0.92 | 08-AUG-05:00 | 396954.93 | 18-AUG-19:00 | 388731.96 | 13-AUG-18:42 | 11940.73 | 16-AUG-20:00 | 143760.67 | 24-AUG-16:00 | 0.00 |
September | 0.313629E+12 | 0.872715E+11 | 720.00 | 0.309755E+12 | 0.387464E+10 | 0.00 | 0.38 | 01-SEP-00:03 | 0.31 | 23-SEP-06:20 | 136300.72 | 01-SEP-00:10 | 134810.51 | 01-SEP-00:10 | 8897.83 | 22-SEP-18:20 | 47849.78 | 01-SEP-14:00 | 0.00 |
October | 0.555396E+12 | 0.136143E+12 | 743.91 | 0.552879E+12 | 0.251704E+10 | 0.00 | 1.00 | 07-OCT-07:25 | 0.07 | 07-OCT-07:31 | 435270.41 | 28-OCT-17:17 | 435270.41 | 28-OCT-17:17 | 7453.87 | 28-OCT-17:50 | 91488.37 | 28-OCT-17:17 | 0.00 |
November | 0.759684E+12 | 0.173768E+12 | 719.73 | 0.759566E+12 | 0.117502E+09 | 0.00 | 1.00 | 07-NOV-22:17 | 0.01 | 18-NOV-14:58 | 434488.97 | 18-NOV-20:34 | 434488.97 | 18-NOV-20:34 | 16128.92 | 25-NOV-13:00 | 91474.97 | 18-NOV-20:34 | 0.00 |
December | 0.101796E+13 | 0.225071E+12 | 744.00 | 0.101796E+13 | 0.00 | 0.00 | 1.00 | 01-DEC-22:08 | 0.72 | 14-DEC-04:56 | 422687.56 | 27-DEC-22:17 | 422687.56 | 27-DEC-22:17 | 0.00 | 01-DEC-00:10 | 91272.58 | 27-DEC-22:17 | 0.00 |
Annual Sum or Average | 0.790211E+13 | 0.202588E+13 | 8731.19 | 0.787400E+13 | 0.281107E+11 | ||||||||||||||
Minimum of Months | 0.310203E+12 | 0.807320E+11 | 663.79 | 0.309755E+12 | 0.00 | 0.00 | 0.38 | 0.01 | 136300.72 | 134810.51 | 0.00 | 47849.78 | 0.00 | ||||||
Maximum of Months | 0.103211E+13 | 0.316276E+12 | 744.00 | 0.102644E+13 | 0.863932E+10 | 0.00 | 1.00 | 0.92 | 443523.07 | 443523.07 | 32788.77 | 143760.67 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.399200E+10 | 0.116071E+10 | 744.00 | 0.399200E+10 | 0.00 | 0.00 | 0.35 | 20-JAN-16:30 | 0.15 | 01-JAN-00:30 | 2348.61 | 20-JAN-16:30 | 2348.61 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 | 658.35 | 20-JAN-16:30 | 0.00 |
February | 0.846466E+10 | 0.228726E+10 | 672.00 | 0.846466E+10 | 0.00 | 0.00 | 0.62 | 14-FEB-16:55 | 0.43 | 06-FEB-06:30 | 4400.88 | 14-FEB-16:55 | 4400.88 | 14-FEB-16:55 | 0.00 | 01-FEB-00:10 | 1157.58 | 14-FEB-16:55 | 0.00 |
March | 0.150438E+11 | 0.385740E+10 | 744.00 | 0.150438E+11 | 0.00 | 0.00 | 0.90 | 27-MAR-17:10 | 0.71 | 01-MAR-00:10 | 6336.26 | 27-MAR-17:20 | 6336.26 | 27-MAR-17:20 | 0.00 | 01-MAR-00:10 | 2001.23 | 27-MAR-17:00 | 0.00 |
April | 0.193687E+11 | 0.493459E+10 | 720.00 | 0.193687E+11 | 0.00 | 0.00 | 1.00 | 02-APR-16:22 | 0.95 | 01-APR-07:00 | 7804.29 | 23-APR-17:52 | 7804.29 | 23-APR-17:52 | 0.00 | 01-APR-00:10 | 2580.73 | 07-APR-13:00 | 0.00 |
May | 0.545978E+10 | 0.163007E+10 | 744.00 | 0.545978E+10 | 0.00 | 0.00 | 0.39 | 30-MAY-17:50 | 0.26 | 04-MAY-21:17 | 2509.62 | 30-MAY-18:00 | 2509.62 | 30-MAY-18:00 | 0.00 | 01-MAY-00:10 | 972.48 | 30-MAY-16:00 | 0.00 |
June | 0.102548E+11 | 0.338950E+10 | 720.00 | 0.102548E+11 | 0.00 | 0.00 | 0.70 | 19-JUN-18:00 | 0.54 | 03-JUN-07:00 | 4466.56 | 18-JUN-17:55 | 4466.56 | 18-JUN-17:55 | 0.00 | 01-JUN-00:10 | 2093.88 | 19-JUN-12:00 | 0.00 |
July | 0.155038E+11 | 0.564811E+10 | 744.00 | 0.155038E+11 | 0.00 | 0.00 | 0.96 | 10-JUL-15:00 | 0.80 | 01-JUL-06:00 | 6359.99 | 12-JUL-18:20 | 6359.99 | 12-JUL-18:20 | 0.00 | 01-JUL-00:10 | 2774.29 | 07-JUL-12:00 | 0.00 |
August | 0.187482E+11 | 0.665137E+10 | 744.00 | 0.187482E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-00:05 | 1.00 | 01-AUG-00:05 | 7554.86 | 08-AUG-04:55 | 7554.86 | 08-AUG-04:55 | 0.00 | 01-AUG-00:05 | 2965.49 | 24-AUG-16:00 | 0.00 |
September | 0.539126E+10 | 0.175311E+10 | 720.00 | 0.539126E+10 | 0.00 | 0.00 | 0.75 | 01-SEP-00:03 | 0.26 | 23-SEP-17:12 | 5080.83 | 01-SEP-00:03 | 5080.83 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 1762.92 | 01-SEP-00:03 | 0.00 |
October | 0.104633E+11 | 0.292299E+10 | 744.00 | 0.104633E+11 | 0.00 | 0.00 | 0.66 | 04-OCT-16:30 | 0.51 | 28-OCT-06:55 | 4488.03 | 15-OCT-16:40 | 4488.03 | 15-OCT-16:40 | 0.00 | 01-OCT-00:10 | 1503.92 | 02-OCT-16:40 | 0.00 |
November | 0.145287E+11 | 0.373073E+10 | 720.00 | 0.145287E+11 | 0.00 | 0.00 | 0.83 | 03-NOV-16:00 | 0.71 | 25-NOV-18:17 | 6124.34 | 06-NOV-16:10 | 6124.34 | 06-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1659.80 | 03-NOV-14:00 | 0.00 |
December | 0.197825E+11 | 0.488002E+10 | 744.00 | 0.197825E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-15:25 | 0.93 | 30-DEC-18:17 | 7716.03 | 21-DEC-16:20 | 7716.03 | 21-DEC-16:20 | 0.00 | 01-DEC-00:10 | 1876.78 | 21-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.147002E+12 | 0.428459E+11 | 8760.00 | 0.147002E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.399200E+10 | 0.116071E+10 | 672.00 | 0.399200E+10 | 0.00 | 0.00 | 0.35 | 0.15 | 2348.61 | 2348.61 | 0.00 | 658.35 | 0.00 | ||||||
Maximum of Months | 0.197825E+11 | 0.665137E+10 | 744.00 | 0.197825E+11 | 0.00 | 0.00 | 1.00 | 1.00 | 7804.29 | 7804.29 | 0.00 | 2965.49 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.168258E+11 | 0.511053E+10 | 559.84 | 0.168258E+11 | 0.00 | 0.00 | 0.32 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 20262.32 | 20-JAN-16:40 | 20262.32 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 5729.63 | 20-JAN-16:40 | 0.00 |
February | 0.626136E+11 | 0.173135E+11 | 672.00 | 0.626136E+11 | 0.00 | 0.00 | 0.59 | 22-FEB-17:00 | 0.19 | 06-FEB-04:12 | 39669.51 | 22-FEB-17:00 | 39669.51 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 10526.29 | 22-FEB-17:00 | 0.00 |
March | 0.128981E+12 | 0.335163E+11 | 744.00 | 0.128981E+12 | 0.00 | 0.00 | 0.88 | 27-MAR-17:10 | 0.60 | 13-MAR-04:14 | 59512.70 | 29-MAR-17:20 | 59512.70 | 29-MAR-17:20 | 0.00 | 01-MAR-00:10 | 18659.80 | 27-MAR-17:00 | 0.00 |
April | 0.175841E+12 | 0.452334E+11 | 720.00 | 0.175841E+12 | 0.00 | 0.00 | 1.00 | 03-APR-16:50 | 0.85 | 02-APR-06:44 | 74142.78 | 12-APR-18:00 | 74142.78 | 12-APR-18:00 | 0.00 | 01-APR-00:10 | 24641.69 | 07-APR-13:00 | 0.00 |
May | 0.459637E+11 | 0.138958E+11 | 744.00 | 0.459637E+11 | 0.00 | 0.00 | 0.39 | 30-MAY-17:50 | 0.21 | 04-MAY-07:00 | 23844.55 | 30-MAY-18:00 | 23844.55 | 30-MAY-18:00 | 0.00 | 01-MAY-00:10 | 9107.09 | 30-MAY-16:00 | 0.00 |
June | 0.950922E+11 | 0.315670E+11 | 720.00 | 0.950922E+11 | 0.00 | 0.00 | 0.70 | 19-JUN-18:00 | 0.50 | 06-JUN-21:20 | 42562.94 | 18-JUN-18:00 | 42562.94 | 18-JUN-18:00 | 0.00 | 01-JUN-00:10 | 19871.37 | 19-JUN-12:00 | 0.00 |
July | 0.146848E+12 | 0.535615E+11 | 744.00 | 0.146848E+12 | 0.00 | 0.00 | 0.96 | 10-JUL-15:00 | 0.78 | 15-JUL-08:70 | 60804.34 | 12-JUL-18:20 | 60804.34 | 12-JUL-18:20 | 0.00 | 01-JUL-00:10 | 26487.79 | 07-JUL-12:00 | 0.00 |
August | 0.178858E+12 | 0.635263E+11 | 744.00 | 0.178858E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-00:05 | 0.99 | 08-AUG-04:55 | 72017.78 | 08-AUG-04:37 | 72017.78 | 08-AUG-04:37 | 0.00 | 01-AUG-00:05 | 28323.53 | 24-AUG-16:00 | 0.00 |
September | 0.460504E+11 | 0.151688E+11 | 720.00 | 0.460504E+11 | 0.00 | 0.00 | 0.74 | 01-SEP-00:03 | 0.20 | 23-SEP-17:20 | 47746.30 | 01-SEP-00:03 | 47746.30 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 16601.42 | 01-SEP-00:03 | 0.00 |
October | 0.911021E+11 | 0.257327E+11 | 744.00 | 0.911021E+11 | 0.00 | 0.00 | 0.66 | 04-OCT-16:30 | 0.44 | 08-OCT-07:10 | 42006.82 | 04-OCT-16:30 | 42006.82 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 14092.26 | 02-OCT-16:40 | 0.00 |
November | 0.122215E+12 | 0.318743E+11 | 720.00 | 0.122215E+12 | 0.00 | 0.00 | 0.81 | 03-NOV-16:00 | 0.57 | 24-NOV-05:17 | 57210.26 | 03-NOV-16:00 | 57210.26 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 15442.61 | 03-NOV-15:00 | 0.00 |
December | 0.167877E+12 | 0.421190E+11 | 744.00 | 0.167877E+12 | 0.00 | 0.00 | 1.00 | 08-DEC-16:00 | 0.71 | 31-DEC-23:52 | 73071.08 | 08-DEC-16:20 | 73071.08 | 08-DEC-16:20 | 0.00 | 01-DEC-00:10 | 17915.59 | 08-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.127827E+13 | 0.378619E+12 | 8575.84 | 0.127827E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.168258E+11 | 0.511053E+10 | 559.84 | 0.168258E+11 | 0.00 | 0.00 | 0.32 | 0.00 | 20262.32 | 20262.32 | 0.00 | 5729.63 | 0.00 | ||||||
Maximum of Months | 0.178858E+12 | 0.635263E+11 | 744.00 | 0.178858E+12 | 0.00 | 0.00 | 1.00 | 0.99 | 74142.78 | 74142.78 | 0.00 | 28323.53 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.814275E+09 | 0.252997E+09 | 340.05 | 0.814275E+09 | 0.00 | 0.00 | 0.30 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 1956.47 | 20-JAN-16:40 | 1956.47 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 555.73 | 20-JAN-16:40 | 0.00 |
February | 0.466135E+10 | 0.131605E+10 | 653.23 | 0.466135E+10 | 0.00 | 0.00 | 0.57 | 02-FEB-16:50 | 0.00 | 05-FEB-06:35 | 3870.76 | 02-FEB-16:50 | 3870.76 | 02-FEB-16:50 | 0.00 | 01-FEB-00:10 | 1033.71 | 02-FEB-16:50 | 0.00 |
March | 0.116750E+11 | 0.307347E+10 | 744.00 | 0.116750E+11 | 0.00 | 0.00 | 0.86 | 27-MAR-17:10 | 0.41 | 13-MAR-03:13 | 5954.92 | 29-MAR-17:20 | 5954.92 | 29-MAR-17:20 | 0.00 | 01-MAR-00:10 | 1864.25 | 27-MAR-17:00 | 0.00 |
April | 0.168473E+11 | 0.437818E+10 | 720.00 | 0.168473E+11 | 0.00 | 0.00 | 1.00 | 03-APR-17:10 | 0.70 | 02-APR-06:56 | 7522.41 | 12-APR-17:50 | 7522.41 | 12-APR-17:50 | 0.00 | 01-APR-00:10 | 2509.03 | 07-APR-13:00 | 0.00 |
May | 0.429419E+10 | 0.131259E+10 | 744.00 | 0.429419E+10 | 0.00 | 0.00 | 0.40 | 30-MAY-17:50 | 0.11 | 01-MAY-06:00 | 2476.26 | 30-MAY-18:00 | 2476.26 | 30-MAY-18:00 | 0.00 | 01-MAY-00:10 | 956.23 | 30-MAY-16:00 | 0.00 |
June | 0.950981E+10 | 0.316841E+10 | 720.00 | 0.950981E+10 | 0.00 | 0.00 | 0.70 | 19-JUN-18:00 | 0.46 | 03-JUN-07:00 | 4472.92 | 18-JUN-17:55 | 4472.92 | 18-JUN-17:55 | 0.00 | 01-JUN-00:10 | 2045.25 | 19-JUN-12:00 | 0.00 |
July | 0.147918E+11 | 0.540563E+10 | 744.00 | 0.147918E+11 | 0.00 | 0.00 | 0.96 | 10-JUL-15:00 | 0.76 | 15-JUL-08:40 | 6177.76 | 12-JUL-18:20 | 6177.76 | 12-JUL-18:20 | 0.00 | 01-JUL-00:10 | 2691.93 | 07-JUL-12:00 | 0.00 |
August | 0.181484E+11 | 0.646454E+10 | 744.00 | 0.181484E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-00:05 | 0.96 | 08-AUG-05:00 | 7231.87 | 20-AUG-01:42 | 7231.87 | 20-AUG-01:42 | 0.00 | 01-AUG-00:05 | 2884.04 | 24-AUG-16:00 | 0.00 |
September | 0.437701E+10 | 0.145785E+10 | 720.00 | 0.437701E+10 | 0.00 | 0.00 | 0.65 | 01-SEP-00:03 | 0.12 | 24-SEP-06:40 | 4187.72 | 01-SEP-00:03 | 4187.72 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 1488.99 | 01-SEP-00:03 | 0.00 |
October | 0.837199E+10 | 0.239425E+10 | 744.00 | 0.837199E+10 | 0.00 | 0.00 | 0.66 | 04-OCT-16:30 | 0.29 | 29-OCT-07:20 | 4264.78 | 04-OCT-16:30 | 4264.78 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 1427.65 | 04-OCT-16:10 | 0.00 |
November | 0.107632E+11 | 0.285137E+10 | 720.00 | 0.107632E+11 | 0.00 | 0.00 | 0.80 | 03-NOV-16:00 | 0.34 | 24-NOV-04:27 | 5703.42 | 03-NOV-16:00 | 5703.42 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 1541.30 | 03-NOV-15:00 | 0.00 |
December | 0.149373E+11 | 0.381291E+10 | 744.00 | 0.149373E+11 | 0.00 | 0.00 | 0.97 | 08-DEC-16:10 | 0.53 | 31-DEC-23:47 | 7173.04 | 08-DEC-16:10 | 7173.04 | 08-DEC-16:10 | 0.00 | 01-DEC-00:10 | 1768.62 | 08-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.119192E+12 | 0.358882E+11 | 8337.28 | 0.119192E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.814275E+09 | 0.252997E+09 | 340.05 | 0.814275E+09 | 0.00 | 0.00 | 0.30 | 0.00 | 1956.47 | 1956.47 | 0.00 | 555.73 | 0.00 | ||||||
Maximum of Months | 0.181484E+11 | 0.646454E+10 | 744.00 | 0.181484E+11 | 0.00 | 0.00 | 1.00 | 0.96 | 7522.41 | 7522.41 | 0.00 | 2884.04 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.55 | 591.57 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.63 | 609.34 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.46 | 417.74 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 98.07 | 294.82 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 213.15 | 167.53 | 0.00 | 0.00 | 744.00 |
June | 321.52 | 17.24 | 304.28 | 309.82 | 86.60 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.52 | 356.55 | 44.80 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.04 | 317.47 | 61.94 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.18 | 136.90 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.29 | 262.66 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.68 | 435.79 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 576.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.44 | 305.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 44.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.52 | 17.24 | 304.28 | 356.55 | 609.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.55 | 591.57 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.63 | 609.34 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.46 | 417.74 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 98.07 | 294.82 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 213.15 | 167.53 | 0.00 | 0.00 | 744.00 |
June | 321.51 | 17.24 | 304.27 | 309.82 | 86.60 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.51 | 356.55 | 44.80 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.03 | 317.47 | 61.94 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.17 | 136.90 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.29 | 262.66 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.68 | 435.79 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 576.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.44 | 305.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 44.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.51 | 17.24 | 304.27 | 356.55 | 609.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.55 | 591.57 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.63 | 609.34 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.46 | 417.74 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 98.07 | 294.82 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 213.15 | 167.53 | 0.00 | 0.00 | 744.00 |
June | 321.51 | 17.24 | 304.28 | 309.82 | 86.60 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.51 | 356.55 | 44.80 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.04 | 317.47 | 61.94 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.17 | 136.90 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.29 | 262.66 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.68 | 435.79 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 576.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.44 | 305.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 44.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.51 | 17.24 | 304.28 | 356.55 | 609.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.27 | 0.00 | 100.27 | 0.55 | 591.57 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.63 | 609.34 | 0.00 | 0.00 | 672.00 |
March | 190.28 | 0.00 | 190.28 | 36.46 | 417.74 | 0.00 | 0.00 | 744.00 |
April | 228.54 | 0.64 | 227.90 | 98.07 | 294.82 | 0.00 | 0.00 | 720.00 |
May | 303.18 | 10.07 | 293.11 | 213.15 | 167.53 | 0.00 | 0.00 | 744.00 |
June | 321.51 | 17.24 | 304.27 | 309.82 | 86.60 | 0.00 | 0.00 | 720.00 |
July | 310.72 | 11.20 | 299.51 | 356.55 | 44.80 | 0.00 | 0.00 | 744.00 |
August | 275.29 | 3.25 | 272.03 | 317.47 | 61.94 | 0.00 | 0.00 | 744.00 |
September | 207.54 | 0.04 | 207.50 | 178.17 | 136.90 | 0.00 | 0.00 | 720.00 |
October | 179.61 | 0.00 | 179.61 | 95.29 | 262.66 | 0.00 | 0.00 | 744.00 |
November | 125.98 | 0.00 | 125.98 | 16.68 | 435.79 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 576.10 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.03 | 3.56 | 202.47 | 136.44 | 305.42 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 44.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.51 | 17.24 | 304.27 | 356.55 | 609.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 100.26 | 0.00 | 100.26 | 0.55 | 591.55 | 0.00 | 0.00 | 744.00 |
February | 137.21 | 0.00 | 137.21 | 3.63 | 609.31 | 0.00 | 0.00 | 672.00 |
March | 190.27 | 0.00 | 190.27 | 36.46 | 417.73 | 0.00 | 0.00 | 744.00 |
April | 228.53 | 0.64 | 227.89 | 98.06 | 294.81 | 0.00 | 0.00 | 720.00 |
May | 303.17 | 10.07 | 293.10 | 213.14 | 167.53 | 0.00 | 0.00 | 744.00 |
June | 321.50 | 17.24 | 304.26 | 309.81 | 86.59 | 0.00 | 0.00 | 720.00 |
July | 310.71 | 11.20 | 299.50 | 356.54 | 44.80 | 0.00 | 0.00 | 744.00 |
August | 275.28 | 3.25 | 272.02 | 317.46 | 61.94 | 0.00 | 0.00 | 744.00 |
September | 207.53 | 0.04 | 207.49 | 178.17 | 136.89 | 0.00 | 0.00 | 720.00 |
October | 179.60 | 0.00 | 179.60 | 95.28 | 262.65 | 0.00 | 0.00 | 744.00 |
November | 125.97 | 0.00 | 125.97 | 16.68 | 435.77 | 0.00 | 0.00 | 720.00 |
December | 87.46 | 0.00 | 87.46 | 0.40 | 576.07 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 206.02 | 3.56 | 202.46 | 136.43 | 305.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 87.46 | 0.00 | 87.46 | 0.40 | 44.80 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 321.50 | 17.24 | 304.26 | 356.54 | 609.31 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.75 | 93.33 | 139.42 | 96.23 | 594.61 | 0.00 | 0.00 | 744.00 |
February | 360.91 | 168.36 | 192.54 | 186.83 | 590.02 | 0.00 | 0.00 | 672.00 |
March | 460.40 | 195.81 | 264.59 | 319.73 | 422.40 | 0.00 | 0.00 | 744.00 |
April | 552.54 | 242.05 | 310.50 | 458.87 | 293.18 | 0.00 | 0.00 | 720.00 |
May | 670.02 | 267.74 | 402.28 | 653.94 | 179.27 | 0.00 | 0.00 | 744.00 |
June | 620.96 | 224.74 | 396.22 | 681.52 | 89.45 | 0.00 | 0.00 | 720.00 |
July | 623.69 | 225.03 | 398.65 | 752.70 | 39.52 | 0.00 | 0.00 | 744.00 |
August | 702.34 | 316.68 | 385.66 | 847.81 | 55.77 | 0.00 | 0.00 | 744.00 |
September | 523.86 | 235.06 | 288.80 | 548.64 | 137.79 | 0.00 | 0.00 | 720.00 |
October | 474.89 | 215.25 | 259.65 | 424.06 | 267.34 | 0.00 | 0.00 | 744.00 |
November | 293.70 | 112.80 | 180.90 | 167.89 | 427.12 | 0.00 | 0.00 | 720.00 |
December | 228.82 | 107.46 | 121.36 | 103.31 | 556.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.50 | 200.59 | 278.91 | 438.55 | 302.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 228.82 | 93.33 | 121.36 | 96.23 | 39.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 702.34 | 316.68 | 402.28 | 847.81 | 594.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.75 | 93.33 | 139.42 | 96.23 | 594.61 | 0.00 | 0.00 | 744.00 |
February | 360.91 | 168.36 | 192.54 | 186.83 | 590.02 | 0.00 | 0.00 | 672.00 |
March | 460.40 | 195.81 | 264.59 | 319.73 | 422.40 | 0.00 | 0.00 | 744.00 |
April | 552.54 | 242.05 | 310.50 | 458.87 | 293.18 | 0.00 | 0.00 | 720.00 |
May | 670.02 | 267.74 | 402.28 | 653.94 | 179.27 | 0.00 | 0.00 | 744.00 |
June | 620.96 | 224.74 | 396.22 | 681.52 | 89.45 | 0.00 | 0.00 | 720.00 |
July | 623.69 | 225.03 | 398.65 | 752.70 | 39.52 | 0.00 | 0.00 | 744.00 |
August | 702.34 | 316.68 | 385.66 | 847.81 | 55.77 | 0.00 | 0.00 | 744.00 |
September | 523.86 | 235.06 | 288.80 | 548.64 | 137.79 | 0.00 | 0.00 | 720.00 |
October | 474.89 | 215.25 | 259.65 | 424.06 | 267.34 | 0.00 | 0.00 | 744.00 |
November | 293.70 | 112.80 | 180.90 | 167.89 | 427.12 | 0.00 | 0.00 | 720.00 |
December | 228.82 | 107.46 | 121.36 | 103.31 | 556.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.50 | 200.59 | 278.91 | 438.55 | 302.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 228.82 | 93.33 | 121.36 | 96.23 | 39.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 702.34 | 316.68 | 402.28 | 847.81 | 594.61 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 232.74 | 93.33 | 139.42 | 96.23 | 594.60 | 0.00 | 0.00 | 744.00 |
February | 360.90 | 168.36 | 192.54 | 186.82 | 590.01 | 0.00 | 0.00 | 672.00 |
March | 460.39 | 195.80 | 264.58 | 319.73 | 422.39 | 0.00 | 0.00 | 744.00 |
April | 552.53 | 242.04 | 310.49 | 458.86 | 293.18 | 0.00 | 0.00 | 720.00 |
May | 670.01 | 267.74 | 402.27 | 653.92 | 179.27 | 0.00 | 0.00 | 744.00 |
June | 620.95 | 224.74 | 396.21 | 681.50 | 89.45 | 0.00 | 0.00 | 720.00 |
July | 623.67 | 225.03 | 398.64 | 752.69 | 39.52 | 0.00 | 0.00 | 744.00 |
August | 702.32 | 316.67 | 385.65 | 847.80 | 55.77 | 0.00 | 0.00 | 744.00 |
September | 523.85 | 235.05 | 288.80 | 548.63 | 137.79 | 0.00 | 0.00 | 720.00 |
October | 474.88 | 215.24 | 259.64 | 424.06 | 267.34 | 0.00 | 0.00 | 744.00 |
November | 293.69 | 112.79 | 180.90 | 167.89 | 427.11 | 0.00 | 0.00 | 720.00 |
December | 228.82 | 107.46 | 121.36 | 103.31 | 556.89 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.49 | 200.58 | 278.91 | 438.54 | 302.84 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 228.82 | 93.33 | 121.36 | 96.23 | 39.52 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 702.32 | 316.67 | 402.27 | 847.80 | 594.60 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.49 | 496.83 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.92 | 506.62 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.69 | 384.24 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.80 | 284.58 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.95 | 173.19 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.13 | 333.69 | 364.08 | 90.71 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.36 | 45.12 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.01 | 64.20 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 612.81 | 136.31 | 0.00 | 0.00 | 720.00 |
October | 819.94 | 514.30 | 305.63 | 855.74 | 252.86 | 0.00 | 0.00 | 744.00 |
November | 568.36 | 341.35 | 227.00 | 529.82 | 377.06 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.05 | 163.07 | 522.03 | 469.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.88 | 272.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.13 | 163.07 | 312.95 | 45.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.94 | 514.30 | 346.86 | 855.74 | 506.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.48 | 496.83 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.92 | 506.62 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.68 | 384.24 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.80 | 284.58 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.94 | 173.19 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.12 | 333.69 | 364.07 | 90.71 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.36 | 45.12 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.01 | 64.20 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 612.81 | 136.31 | 0.00 | 0.00 | 720.00 |
October | 819.93 | 514.30 | 305.63 | 855.73 | 252.86 | 0.00 | 0.00 | 744.00 |
November | 568.35 | 341.35 | 227.00 | 529.82 | 377.06 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.04 | 163.07 | 522.03 | 469.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.88 | 272.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.12 | 163.07 | 312.94 | 45.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.93 | 514.30 | 346.86 | 855.73 | 506.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.49 | 496.83 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.92 | 506.62 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.69 | 384.24 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.80 | 284.58 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.95 | 173.19 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.13 | 333.69 | 364.08 | 90.71 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.36 | 45.12 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.01 | 64.20 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 612.81 | 136.31 | 0.00 | 0.00 | 720.00 |
October | 819.94 | 514.30 | 305.63 | 855.74 | 252.86 | 0.00 | 0.00 | 744.00 |
November | 568.36 | 341.35 | 227.00 | 529.82 | 377.06 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.05 | 163.07 | 522.03 | 469.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.88 | 272.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.13 | 163.07 | 312.95 | 45.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.94 | 514.30 | 346.86 | 855.74 | 506.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.71 | 339.66 | 179.05 | 454.48 | 496.83 | 0.00 | 0.00 | 744.00 |
February | 684.44 | 453.14 | 231.30 | 590.92 | 506.62 | 0.00 | 0.00 | 672.00 |
March | 617.44 | 342.78 | 274.66 | 510.68 | 384.24 | 0.00 | 0.00 | 744.00 |
April | 478.88 | 189.32 | 289.56 | 340.80 | 284.58 | 0.00 | 0.00 | 720.00 |
May | 419.67 | 87.48 | 332.18 | 312.94 | 173.19 | 0.00 | 0.00 | 744.00 |
June | 393.82 | 60.12 | 333.69 | 364.07 | 90.71 | 0.00 | 0.00 | 720.00 |
July | 412.82 | 71.65 | 341.17 | 435.36 | 45.12 | 0.00 | 0.00 | 744.00 |
August | 551.29 | 204.43 | 346.86 | 567.01 | 64.20 | 0.00 | 0.00 | 744.00 |
September | 598.33 | 309.52 | 288.81 | 612.81 | 136.31 | 0.00 | 0.00 | 720.00 |
October | 819.93 | 514.30 | 305.63 | 855.73 | 252.86 | 0.00 | 0.00 | 744.00 |
November | 568.35 | 341.35 | 227.00 | 529.82 | 377.06 | 0.00 | 0.00 | 720.00 |
December | 562.12 | 399.04 | 163.07 | 522.03 | 469.78 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.53 | 275.17 | 276.36 | 507.88 | 272.10 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.82 | 60.12 | 163.07 | 312.94 | 45.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.93 | 514.30 | 346.86 | 855.73 | 506.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 518.69 | 339.65 | 179.05 | 454.47 | 496.81 | 0.00 | 0.00 | 744.00 |
February | 684.41 | 453.12 | 231.29 | 590.90 | 506.59 | 0.00 | 0.00 | 672.00 |
March | 617.42 | 342.77 | 274.65 | 510.66 | 384.22 | 0.00 | 0.00 | 744.00 |
April | 478.86 | 189.31 | 289.55 | 340.78 | 284.57 | 0.00 | 0.00 | 720.00 |
May | 419.65 | 87.48 | 332.17 | 312.93 | 173.18 | 0.00 | 0.00 | 744.00 |
June | 393.80 | 60.12 | 333.68 | 364.06 | 90.70 | 0.00 | 0.00 | 720.00 |
July | 412.80 | 71.64 | 341.16 | 435.34 | 45.12 | 0.00 | 0.00 | 744.00 |
August | 551.27 | 204.42 | 346.84 | 566.99 | 64.20 | 0.00 | 0.00 | 744.00 |
September | 598.30 | 309.51 | 288.80 | 612.79 | 136.31 | 0.00 | 0.00 | 720.00 |
October | 819.90 | 514.28 | 305.62 | 855.70 | 252.85 | 0.00 | 0.00 | 744.00 |
November | 568.33 | 341.34 | 226.99 | 529.80 | 377.05 | 0.00 | 0.00 | 720.00 |
December | 562.10 | 399.03 | 163.07 | 522.01 | 469.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 551.50 | 275.16 | 276.34 | 507.86 | 272.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 393.80 | 60.12 | 163.07 | 312.93 | 45.12 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 819.90 | 514.28 | 346.84 | 855.70 | 506.59 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 229.77 | 94.13 | 135.64 | 98.24 | 635.33 | 0.00 | 0.00 | 744.00 |
February | 338.80 | 148.80 | 190.00 | 168.01 | 658.23 | 0.00 | 0.00 | 672.00 |
March | 500.31 | 231.00 | 269.31 | 352.99 | 473.81 | 0.00 | 0.00 | 744.00 |
April | 546.80 | 233.97 | 312.83 | 442.45 | 358.36 | 0.00 | 0.00 | 720.00 |
May | 636.88 | 241.82 | 395.06 | 612.10 | 204.45 | 0.00 | 0.00 | 744.00 |
June | 697.04 | 281.09 | 415.95 | 762.64 | 116.67 | 0.00 | 0.00 | 720.00 |
July | 652.83 | 245.80 | 407.03 | 767.65 | 66.77 | 0.00 | 0.00 | 744.00 |
August | 722.26 | 334.35 | 387.91 | 852.23 | 91.97 | 0.00 | 0.00 | 744.00 |
September | 512.79 | 224.11 | 288.68 | 536.75 | 163.39 | 0.00 | 0.00 | 720.00 |
October | 508.36 | 247.20 | 261.16 | 461.01 | 309.47 | 0.00 | 0.00 | 744.00 |
November | 238.73 | 69.00 | 169.73 | 103.04 | 499.41 | 0.00 | 0.00 | 720.00 |
December | 212.37 | 91.91 | 120.46 | 85.58 | 653.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 484.09 | 204.07 | 280.03 | 438.83 | 350.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 212.37 | 69.00 | 120.46 | 85.58 | 66.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 722.26 | 334.35 | 415.95 | 852.23 | 658.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 229.77 | 94.13 | 135.64 | 98.24 | 635.33 | 0.00 | 0.00 | 744.00 |
February | 338.80 | 148.80 | 190.00 | 168.01 | 658.23 | 0.00 | 0.00 | 672.00 |
March | 500.31 | 231.00 | 269.31 | 352.99 | 473.81 | 0.00 | 0.00 | 744.00 |
April | 546.80 | 233.97 | 312.83 | 442.45 | 358.36 | 0.00 | 0.00 | 720.00 |
May | 636.88 | 241.82 | 395.06 | 612.10 | 204.45 | 0.00 | 0.00 | 744.00 |
June | 697.04 | 281.09 | 415.95 | 762.64 | 116.67 | 0.00 | 0.00 | 720.00 |
July | 652.83 | 245.80 | 407.03 | 767.65 | 66.77 | 0.00 | 0.00 | 744.00 |
August | 722.26 | 334.35 | 387.91 | 852.23 | 91.97 | 0.00 | 0.00 | 744.00 |
September | 512.79 | 224.11 | 288.68 | 536.75 | 163.39 | 0.00 | 0.00 | 720.00 |
October | 508.36 | 247.20 | 261.16 | 461.01 | 309.47 | 0.00 | 0.00 | 744.00 |
November | 238.73 | 69.00 | 169.73 | 103.04 | 499.41 | 0.00 | 0.00 | 720.00 |
December | 212.37 | 91.91 | 120.46 | 85.58 | 653.69 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 484.09 | 204.07 | 280.03 | 438.83 | 350.87 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 212.37 | 69.00 | 120.46 | 85.58 | 66.77 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 722.26 | 334.35 | 415.95 | 852.23 | 658.23 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 229.77 | 94.13 | 135.64 | 98.24 | 635.32 | 0.00 | 0.00 | 744.00 |
February | 338.79 | 148.80 | 189.99 | 168.00 | 658.22 | 0.00 | 0.00 | 672.00 |
March | 500.31 | 231.00 | 269.31 | 352.99 | 473.80 | 0.00 | 0.00 | 744.00 |
April | 546.79 | 233.97 | 312.82 | 442.44 | 358.36 | 0.00 | 0.00 | 720.00 |
May | 636.87 | 241.82 | 395.05 | 612.09 | 204.45 | 0.00 | 0.00 | 744.00 |
June | 697.03 | 281.08 | 415.94 | 762.63 | 116.66 | 0.00 | 0.00 | 720.00 |
July | 652.82 | 245.80 | 407.02 | 767.63 | 66.76 | 0.00 | 0.00 | 744.00 |
August | 722.25 | 334.35 | 387.90 | 852.22 | 91.97 | 0.00 | 0.00 | 744.00 |
September | 512.78 | 224.10 | 288.68 | 536.74 | 163.39 | 0.00 | 0.00 | 720.00 |
October | 508.35 | 247.20 | 261.15 | 461.00 | 309.47 | 0.00 | 0.00 | 744.00 |
November | 238.72 | 69.00 | 169.73 | 103.04 | 499.40 | 0.00 | 0.00 | 720.00 |
December | 212.36 | 91.91 | 120.46 | 85.58 | 653.68 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 484.08 | 204.06 | 280.02 | 438.83 | 350.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 212.36 | 69.00 | 120.46 | 85.58 | 66.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 722.25 | 334.35 | 415.94 | 852.22 | 658.22 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.34 | 0.00 | 501.34 | 12.21 | 2608.02 | 0.00 | 0.00 | 744.00 |
February | 686.07 | 0.00 | 686.07 | 33.86 | 2728.50 | 0.00 | 0.00 | 672.00 |
March | 951.40 | 0.00 | 951.40 | 228.68 | 1836.53 | 0.00 | 0.00 | 744.00 |
April | 1142.71 | 3.20 | 1139.51 | 543.51 | 1301.84 | 0.00 | 0.00 | 720.00 |
May | 1515.92 | 50.36 | 1465.57 | 1095.51 | 780.01 | 0.00 | 0.00 | 744.00 |
June | 1607.59 | 86.19 | 1521.40 | 1568.61 | 408.13 | 0.00 | 0.00 | 720.00 |
July | 1553.61 | 56.03 | 1497.58 | 1798.24 | 219.36 | 0.00 | 0.00 | 744.00 |
August | 1376.45 | 16.27 | 1360.19 | 1607.66 | 305.42 | 0.00 | 0.00 | 744.00 |
September | 1037.70 | 0.19 | 1037.51 | 916.17 | 625.55 | 0.00 | 0.00 | 720.00 |
October | 898.06 | 0.00 | 898.06 | 517.24 | 1178.36 | 0.00 | 0.00 | 744.00 |
November | 629.90 | 0.00 | 629.90 | 112.41 | 1873.84 | 0.00 | 0.00 | 720.00 |
December | 437.30 | 0.00 | 437.30 | 7.46 | 2474.00 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1030.15 | 17.78 | 1012.37 | 708.07 | 1353.79 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 437.30 | 0.00 | 437.30 | 7.46 | 219.36 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1607.59 | 86.19 | 1521.40 | 1798.24 | 2728.50 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.24 | 279.98 | 418.26 | 309.25 | 1604.07 | 0.00 | 0.00 | 744.00 |
February | 1082.71 | 505.09 | 577.62 | 585.42 | 1624.15 | 0.00 | 0.00 | 672.00 |
March | 1381.18 | 587.42 | 793.76 | 980.63 | 1161.33 | 0.00 | 0.00 | 744.00 |
April | 1657.61 | 726.13 | 931.48 | 1391.47 | 818.08 | 0.00 | 0.00 | 720.00 |
May | 2010.04 | 803.22 | 1206.82 | 1967.47 | 506.69 | 0.00 | 0.00 | 744.00 |
June | 1862.87 | 674.23 | 1188.64 | 2042.79 | 262.70 | 0.00 | 0.00 | 720.00 |
July | 1871.04 | 675.10 | 1195.94 | 2246.05 | 135.57 | 0.00 | 0.00 | 744.00 |
August | 2106.99 | 950.02 | 1156.97 | 2527.38 | 190.98 | 0.00 | 0.00 | 744.00 |
September | 1571.56 | 705.17 | 866.39 | 1654.53 | 383.78 | 0.00 | 0.00 | 720.00 |
October | 1424.67 | 645.73 | 778.94 | 1290.56 | 738.93 | 0.00 | 0.00 | 744.00 |
November | 881.08 | 338.38 | 542.70 | 532.59 | 1145.41 | 0.00 | 0.00 | 720.00 |
December | 686.47 | 322.38 | 364.09 | 329.21 | 1501.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1438.48 | 601.75 | 836.73 | 1326.58 | 835.01 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 686.47 | 279.98 | 364.09 | 309.25 | 135.57 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2106.99 | 950.02 | 1206.82 | 2527.38 | 1624.15 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2593.62 | 1698.34 | 895.28 | 2284.05 | 2345.13 | 0.00 | 0.00 | 744.00 |
February | 3422.28 | 2265.77 | 1156.51 | 2954.37 | 2433.90 | 0.00 | 0.00 | 672.00 |
March | 3087.27 | 1713.95 | 1373.31 | 2556.02 | 1821.63 | 0.00 | 0.00 | 744.00 |
April | 2394.45 | 946.63 | 1447.82 | 1725.32 | 1338.45 | 0.00 | 0.00 | 720.00 |
May | 2098.37 | 437.43 | 1660.93 | 1577.34 | 833.12 | 0.00 | 0.00 | 744.00 |
June | 1969.12 | 300.63 | 1668.49 | 1832.36 | 437.71 | 0.00 | 0.00 | 720.00 |
July | 2064.13 | 358.24 | 1705.89 | 2189.24 | 227.84 | 0.00 | 0.00 | 744.00 |
August | 2756.49 | 1022.17 | 1734.32 | 2845.21 | 329.58 | 0.00 | 0.00 | 744.00 |
September | 2991.70 | 1547.63 | 1444.07 | 3057.97 | 661.77 | 0.00 | 0.00 | 720.00 |
October | 4099.76 | 2571.57 | 1528.19 | 4258.27 | 1231.15 | 0.00 | 0.00 | 744.00 |
November | 2841.85 | 1706.81 | 1135.04 | 2655.84 | 1779.17 | 0.00 | 0.00 | 720.00 |
December | 2810.67 | 1995.28 | 815.39 | 2618.95 | 2208.44 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2757.69 | 1375.89 | 1381.80 | 2545.39 | 1297.44 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1969.12 | 300.63 | 815.39 | 1577.34 | 227.84 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 4099.76 | 2571.57 | 1734.32 | 4258.27 | 2433.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 689.32 | 282.39 | 406.93 | 314.97 | 1675.05 | 0.00 | 0.00 | 744.00 |
February | 1016.39 | 446.40 | 569.99 | 536.20 | 1731.25 | 0.00 | 0.00 | 672.00 |
March | 1500.93 | 692.99 | 807.93 | 1113.55 | 1193.63 | 0.00 | 0.00 | 744.00 |
April | 1640.38 | 701.91 | 938.47 | 1396.00 | 881.38 | 0.00 | 0.00 | 720.00 |
May | 1910.62 | 725.46 | 1185.16 | 1871.77 | 552.76 | 0.00 | 0.00 | 744.00 |
June | 2091.09 | 843.26 | 1247.84 | 2321.61 | 306.95 | 0.00 | 0.00 | 720.00 |
July | 1958.47 | 737.40 | 1221.08 | 2344.55 | 170.38 | 0.00 | 0.00 | 744.00 |
August | 2166.76 | 1003.05 | 1163.71 | 2599.78 | 242.51 | 0.00 | 0.00 | 744.00 |
September | 1538.35 | 672.31 | 866.04 | 1643.62 | 427.92 | 0.00 | 0.00 | 720.00 |
October | 1525.07 | 741.61 | 783.46 | 1432.77 | 798.28 | 0.00 | 0.00 | 744.00 |
November | 716.17 | 206.99 | 509.19 | 358.46 | 1212.93 | 0.00 | 0.00 | 720.00 |
December | 637.09 | 275.72 | 361.38 | 292.27 | 1587.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1452.26 | 612.19 | 840.07 | 1357.98 | 893.60 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 637.09 | 206.99 | 361.38 | 292.27 | 170.38 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2166.76 | 1003.05 | 1247.84 | 2599.78 | 1731.25 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 501.34 | 0.00 | 501.34 | 17.26 | 2472.24 | 0.00 | 0.00 | 744.00 |
February | 686.07 | 0.00 | 686.07 | 44.17 | 2570.87 | 0.00 | 0.00 | 672.00 |
March | 951.40 | 0.00 | 951.40 | 252.99 | 1702.80 | 0.00 | 0.00 | 744.00 |
April | 1142.71 | 3.20 | 1139.51 | 571.06 | 1208.50 | 0.00 | 0.00 | 720.00 |
May | 1515.92 | 50.36 | 1465.57 | 1108.42 | 744.76 | 0.00 | 0.00 | 744.00 |
June | 1607.59 | 86.19 | 1521.40 | 1558.21 | 402.89 | 0.00 | 0.00 | 720.00 |
July | 1553.61 | 56.03 | 1497.58 | 1779.26 | 224.06 | 0.00 | 0.00 | 744.00 |
August | 1376.45 | 16.27 | 1360.19 | 1594.26 | 305.13 | 0.00 | 0.00 | 744.00 |
September | 1037.70 | 0.19 | 1037.51 | 923.17 | 594.02 | 0.00 | 0.00 | 720.00 |
October | 898.06 | 0.00 | 898.06 | 548.04 | 1085.67 | 0.00 | 0.00 | 744.00 |
November | 629.90 | 0.00 | 629.90 | 138.87 | 1698.17 | 0.00 | 0.00 | 720.00 |
December | 437.30 | 0.00 | 437.30 | 14.82 | 2274.04 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1030.15 | 17.78 | 1012.37 | 717.10 | 1266.20 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 437.30 | 0.00 | 437.30 | 14.82 | 224.06 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1607.59 | 86.19 | 1521.40 | 1779.26 | 2570.87 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 698.24 | 279.98 | 418.26 | 318.18 | 1525.14 | 0.00 | 0.00 | 744.00 |
February | 1082.71 | 505.09 | 577.62 | 603.23 | 1534.40 | 0.00 | 0.00 | 672.00 |
March | 1381.18 | 587.42 | 793.76 | 999.57 | 1088.28 | 0.00 | 0.00 | 744.00 |
April | 1657.61 | 726.13 | 931.48 | 1406.81 | 773.19 | 0.00 | 0.00 | 720.00 |
May | 2010.04 | 803.22 | 1206.82 | 1969.14 | 491.08 | 0.00 | 0.00 | 744.00 |
June | 1862.87 | 674.23 | 1188.64 | 2031.81 | 262.60 | 0.00 | 0.00 | 720.00 |
July | 1871.04 | 675.10 | 1195.94 | 2230.90 | 140.37 | 0.00 | 0.00 | 744.00 |
August | 2106.99 | 950.02 | 1156.97 | 2515.04 | 193.64 | 0.00 | 0.00 | 744.00 |
September | 1571.56 | 705.17 | 866.39 | 1654.66 | 370.86 | 0.00 | 0.00 | 720.00 |
October | 1424.67 | 645.73 | 778.94 | 1307.43 | 693.67 | 0.00 | 0.00 | 744.00 |
November | 881.08 | 338.38 | 542.70 | 557.27 | 1053.59 | 0.00 | 0.00 | 720.00 |
December | 686.47 | 322.38 | 364.09 | 344.68 | 1388.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1438.48 | 601.75 | 836.73 | 1333.26 | 788.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 686.47 | 279.98 | 364.09 | 318.18 | 140.37 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2106.99 | 950.02 | 1206.82 | 2515.04 | 1534.40 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2593.62 | 1698.34 | 895.28 | 2307.41 | 2212.07 | 0.00 | 0.00 | 744.00 |
February | 3422.28 | 2265.77 | 1156.51 | 2993.58 | 2275.90 | 0.00 | 0.00 | 672.00 |
March | 3087.27 | 1713.95 | 1373.31 | 2583.97 | 1692.08 | 0.00 | 0.00 | 744.00 |
April | 2394.45 | 946.63 | 1447.82 | 1753.58 | 1250.98 | 0.00 | 0.00 | 720.00 |
May | 2098.37 | 437.43 | 1660.93 | 1590.84 | 796.79 | 0.00 | 0.00 | 744.00 |
June | 1969.12 | 300.63 | 1668.49 | 1824.72 | 432.07 | 0.00 | 0.00 | 720.00 |
July | 2064.13 | 358.24 | 1705.89 | 2174.22 | 232.02 | 0.00 | 0.00 | 744.00 |
August | 2756.49 | 1022.17 | 1734.32 | 2835.81 | 328.69 | 0.00 | 0.00 | 744.00 |
September | 2991.70 | 1547.63 | 1444.07 | 3064.90 | 632.42 | 0.00 | 0.00 | 720.00 |
October | 4099.76 | 2571.57 | 1528.19 | 4283.60 | 1151.47 | 0.00 | 0.00 | 744.00 |
November | 2841.85 | 1706.81 | 1135.04 | 2700.66 | 1624.37 | 0.00 | 0.00 | 720.00 |
December | 2810.67 | 1995.28 | 815.39 | 2661.18 | 2027.74 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2757.69 | 1375.89 | 1381.80 | 2563.52 | 1215.31 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1969.12 | 300.63 | 815.39 | 1590.84 | 232.02 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 4099.76 | 2571.57 | 1734.32 | 4283.60 | 2275.90 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 689.32 | 282.39 | 406.93 | 320.61 | 1597.68 | 0.00 | 0.00 | 744.00 |
February | 1016.39 | 446.40 | 569.99 | 543.88 | 1648.54 | 0.00 | 0.00 | 672.00 |
March | 1500.93 | 692.99 | 807.93 | 1125.05 | 1126.14 | 0.00 | 0.00 | 744.00 |
April | 1640.38 | 701.91 | 938.47 | 1407.54 | 833.51 | 0.00 | 0.00 | 720.00 |
May | 1910.62 | 725.46 | 1185.16 | 1876.42 | 532.02 | 0.00 | 0.00 | 744.00 |
June | 2091.09 | 843.26 | 1247.84 | 2316.05 | 301.62 | 0.00 | 0.00 | 720.00 |
July | 1958.47 | 737.40 | 1221.08 | 2335.03 | 170.73 | 0.00 | 0.00 | 744.00 |
August | 2166.76 | 1003.05 | 1163.71 | 2593.67 | 239.66 | 0.00 | 0.00 | 744.00 |
September | 1538.35 | 672.31 | 866.04 | 1647.35 | 410.44 | 0.00 | 0.00 | 720.00 |
October | 1525.07 | 741.61 | 783.46 | 1445.41 | 751.65 | 0.00 | 0.00 | 744.00 |
November | 716.17 | 206.99 | 509.19 | 374.20 | 1126.55 | 0.00 | 0.00 | 720.00 |
December | 637.09 | 275.72 | 361.38 | 301.03 | 1486.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1452.26 | 612.19 | 840.07 | 1363.00 | 847.53 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 637.09 | 206.99 | 361.38 | 301.03 | 170.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2166.76 | 1003.05 | 1247.84 | 2593.67 | 1648.54 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268559E+09 | 0.00 | 0.268559E+09 | 1463557.79 | 0.158447E+10 |
February | 0.331947E+09 | 0.00 | 0.331947E+09 | 8789032.16 | 0.147411E+10 |
March | 0.509647E+09 | 0.00 | 0.509647E+09 | 97657186.70 | 0.111888E+10 |
April | 0.592383E+09 | 1658662.77 | 0.590724E+09 | 0.254195E+09 | 0.764174E+09 |
May | 0.812050E+09 | 26974361.52 | 0.785076E+09 | 0.570902E+09 | 0.448725E+09 |
June | 0.833375E+09 | 44682914.63 | 0.788692E+09 | 0.803066E+09 | 0.224458E+09 |
July | 0.832237E+09 | 30011298.19 | 0.802225E+09 | 0.954996E+09 | 0.119985E+09 |
August | 0.737338E+09 | 8712936.52 | 0.728625E+09 | 0.850322E+09 | 0.165909E+09 |
September | 0.537942E+09 | 96941.75 | 0.537845E+09 | 0.461831E+09 | 0.354842E+09 |
October | 0.481072E+09 | 0.00 | 0.481072E+09 | 0.255218E+09 | 0.703513E+09 |
November | 0.326541E+09 | 0.00 | 0.326541E+09 | 43230918.34 | 0.112957E+10 |
December | 0.234255E+09 | 0.00 | 0.234255E+09 | 1076404.03 | 0.154302E+10 |
Annual Sum or Average | 0.649735E+10 | 0.112137E+09 | 0.638521E+10 | 0.430275E+10 | 0.963166E+10 |
Minimum of Months | 0.234255E+09 | 0.00 | 0.234255E+09 | 1076404.03 | 0.119985E+09 |
Maximum of Months | 0.833375E+09 | 44682914.63 | 0.802225E+09 | 0.954996E+09 | 0.158447E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268555E+09 | 0.00 | 0.268555E+09 | 1463312.68 | 0.158447E+10 |
February | 0.331942E+09 | 0.00 | 0.331942E+09 | 8788234.93 | 0.147411E+10 |
March | 0.509640E+09 | 0.00 | 0.509640E+09 | 97653216.33 | 0.111888E+10 |
April | 0.592375E+09 | 1658626.30 | 0.590716E+09 | 0.254189E+09 | 0.764174E+09 |
May | 0.812038E+09 | 26973768.52 | 0.785064E+09 | 0.570890E+09 | 0.448725E+09 |
June | 0.833363E+09 | 44681932.32 | 0.788681E+09 | 0.803054E+09 | 0.224457E+09 |
July | 0.832225E+09 | 30010638.43 | 0.802214E+09 | 0.954983E+09 | 0.119984E+09 |
August | 0.737328E+09 | 8712744.97 | 0.728615E+09 | 0.850313E+09 | 0.165907E+09 |
September | 0.537935E+09 | 96939.62 | 0.537838E+09 | 0.461824E+09 | 0.354840E+09 |
October | 0.481065E+09 | 0.00 | 0.481065E+09 | 0.255212E+09 | 0.703512E+09 |
November | 0.326536E+09 | 0.00 | 0.326536E+09 | 43228927.33 | 0.112957E+10 |
December | 0.234252E+09 | 0.00 | 0.234252E+09 | 1076255.07 | 0.154302E+10 |
Annual Sum or Average | 0.649725E+10 | 0.112135E+09 | 0.638512E+10 | 0.430267E+10 | 0.963166E+10 |
Minimum of Months | 0.234252E+09 | 0.00 | 0.234252E+09 | 1076255.07 | 0.119984E+09 |
Maximum of Months | 0.833363E+09 | 44681932.32 | 0.802214E+09 | 0.954983E+09 | 0.158447E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268557E+09 | 0.00 | 0.268557E+09 | 1463394.38 | 0.158447E+10 |
February | 0.331944E+09 | 0.00 | 0.331944E+09 | 8788500.67 | 0.147411E+10 |
March | 0.509643E+09 | 0.00 | 0.509643E+09 | 97654539.79 | 0.111888E+10 |
April | 0.592377E+09 | 1658638.46 | 0.590719E+09 | 0.254191E+09 | 0.764174E+09 |
May | 0.812042E+09 | 26973966.19 | 0.785068E+09 | 0.570894E+09 | 0.448725E+09 |
June | 0.833367E+09 | 44682259.76 | 0.788684E+09 | 0.803058E+09 | 0.224457E+09 |
July | 0.832229E+09 | 30010858.35 | 0.802218E+09 | 0.954988E+09 | 0.119984E+09 |
August | 0.737331E+09 | 8712808.82 | 0.728619E+09 | 0.850316E+09 | 0.165908E+09 |
September | 0.537937E+09 | 96940.33 | 0.537840E+09 | 0.461826E+09 | 0.354841E+09 |
October | 0.481068E+09 | 0.00 | 0.481068E+09 | 0.255214E+09 | 0.703512E+09 |
November | 0.326537E+09 | 0.00 | 0.326537E+09 | 43229591.00 | 0.112957E+10 |
December | 0.234253E+09 | 0.00 | 0.234253E+09 | 1076304.72 | 0.154302E+10 |
Annual Sum or Average | 0.649728E+10 | 0.112135E+09 | 0.638515E+10 | 0.430270E+10 | 0.963166E+10 |
Minimum of Months | 0.234253E+09 | 0.00 | 0.234253E+09 | 1076304.72 | 0.119984E+09 |
Maximum of Months | 0.833367E+09 | 44682259.76 | 0.802218E+09 | 0.954988E+09 | 0.158447E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268555E+09 | 0.00 | 0.268555E+09 | 1463312.68 | 0.158447E+10 |
February | 0.331942E+09 | 0.00 | 0.331942E+09 | 8788234.93 | 0.147411E+10 |
March | 0.509640E+09 | 0.00 | 0.509640E+09 | 97653216.33 | 0.111888E+10 |
April | 0.592375E+09 | 1658626.30 | 0.590716E+09 | 0.254189E+09 | 0.764174E+09 |
May | 0.812038E+09 | 26973768.52 | 0.785064E+09 | 0.570890E+09 | 0.448725E+09 |
June | 0.833363E+09 | 44681932.32 | 0.788681E+09 | 0.803054E+09 | 0.224457E+09 |
July | 0.832225E+09 | 30010638.43 | 0.802214E+09 | 0.954983E+09 | 0.119984E+09 |
August | 0.737328E+09 | 8712744.97 | 0.728615E+09 | 0.850313E+09 | 0.165907E+09 |
September | 0.537935E+09 | 96939.62 | 0.537838E+09 | 0.461824E+09 | 0.354840E+09 |
October | 0.481065E+09 | 0.00 | 0.481065E+09 | 0.255212E+09 | 0.703512E+09 |
November | 0.326536E+09 | 0.00 | 0.326536E+09 | 43228927.33 | 0.112957E+10 |
December | 0.234252E+09 | 0.00 | 0.234252E+09 | 1076255.07 | 0.154302E+10 |
Annual Sum or Average | 0.649725E+10 | 0.112135E+09 | 0.638512E+10 | 0.430267E+10 | 0.963166E+10 |
Minimum of Months | 0.234252E+09 | 0.00 | 0.234252E+09 | 1076255.07 | 0.119984E+09 |
Maximum of Months | 0.833363E+09 | 44681932.32 | 0.802214E+09 | 0.954983E+09 | 0.158447E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.268545E+09 | 0.00 | 0.268545E+09 | 1463294.55 | 0.158441E+10 |
February | 0.331929E+09 | 0.00 | 0.331929E+09 | 8788013.59 | 0.147405E+10 |
March | 0.509621E+09 | 0.00 | 0.509621E+09 | 97649942.18 | 0.111884E+10 |
April | 0.592352E+09 | 1658565.53 | 0.590694E+09 | 0.254179E+09 | 0.764143E+09 |
May | 0.812007E+09 | 26972780.19 | 0.785035E+09 | 0.570869E+09 | 0.448707E+09 |
June | 0.833331E+09 | 44680295.16 | 0.788651E+09 | 0.803023E+09 | 0.224448E+09 |
July | 0.832193E+09 | 30009538.83 | 0.802184E+09 | 0.954947E+09 | 0.119979E+09 |
August | 0.737300E+09 | 8712425.73 | 0.728588E+09 | 0.850280E+09 | 0.165901E+09 |
September | 0.537914E+09 | 96936.07 | 0.537817E+09 | 0.461806E+09 | 0.354826E+09 |
October | 0.481047E+09 | 0.00 | 0.481047E+09 | 0.255203E+09 | 0.703484E+09 |
November | 0.326523E+09 | 0.00 | 0.326523E+09 | 43227516.84 | 0.112953E+10 |
December | 0.234243E+09 | 0.00 | 0.234243E+09 | 1076236.51 | 0.154296E+10 |
Annual Sum or Average | 0.649701E+10 | 0.112131E+09 | 0.638488E+10 | 0.430251E+10 | 0.963127E+10 |
Minimum of Months | 0.234243E+09 | 0.00 | 0.234243E+09 | 1076236.51 | 0.119979E+09 |
Maximum of Months | 0.833331E+09 | 44680295.16 | 0.802184E+09 | 0.954947E+09 | 0.158441E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623391E+09 | 0.249968E+09 | 0.373423E+09 | 0.257746E+09 | 0.159261E+10 |
February | 0.873106E+09 | 0.407308E+09 | 0.465798E+09 | 0.451968E+09 | 0.142737E+10 |
March | 0.123313E+10 | 0.524454E+09 | 0.708677E+09 | 0.856371E+09 | 0.113134E+10 |
April | 0.143219E+10 | 0.627383E+09 | 0.804805E+09 | 0.118939E+10 | 0.759935E+09 |
May | 0.179458E+10 | 0.717120E+09 | 0.107746E+10 | 0.175150E+10 | 0.480165E+09 |
June | 0.160954E+10 | 0.582537E+09 | 0.102700E+10 | 0.176649E+10 | 0.231846E+09 |
July | 0.167048E+10 | 0.602734E+09 | 0.106774E+10 | 0.201604E+10 | 0.105854E+09 |
August | 0.188114E+10 | 0.848184E+09 | 0.103295E+10 | 0.227078E+10 | 0.149368E+09 |
September | 0.135784E+10 | 0.609273E+09 | 0.748572E+09 | 0.142207E+10 | 0.357160E+09 |
October | 0.127195E+10 | 0.576514E+09 | 0.695440E+09 | 0.113581E+10 | 0.716045E+09 |
November | 0.761261E+09 | 0.292365E+09 | 0.468896E+09 | 0.435179E+09 | 0.110710E+10 |
December | 0.612885E+09 | 0.287822E+09 | 0.325062E+09 | 0.276710E+09 | 0.149161E+10 |
Annual Sum or Average | 0.151215E+11 | 0.632566E+10 | 0.879583E+10 | 0.138301E+11 | 0.955041E+10 |
Minimum of Months | 0.612885E+09 | 0.249968E+09 | 0.325062E+09 | 0.257746E+09 | 0.105854E+09 |
Maximum of Months | 0.188114E+10 | 0.848184E+09 | 0.107746E+10 | 0.227078E+10 | 0.159261E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623391E+09 | 0.249968E+09 | 0.373423E+09 | 0.257746E+09 | 0.159261E+10 |
February | 0.873106E+09 | 0.407308E+09 | 0.465798E+09 | 0.451968E+09 | 0.142737E+10 |
March | 0.123313E+10 | 0.524454E+09 | 0.708677E+09 | 0.856371E+09 | 0.113134E+10 |
April | 0.143219E+10 | 0.627383E+09 | 0.804805E+09 | 0.118939E+10 | 0.759935E+09 |
May | 0.179458E+10 | 0.717120E+09 | 0.107746E+10 | 0.175150E+10 | 0.480165E+09 |
June | 0.160954E+10 | 0.582537E+09 | 0.102700E+10 | 0.176649E+10 | 0.231846E+09 |
July | 0.167048E+10 | 0.602734E+09 | 0.106774E+10 | 0.201604E+10 | 0.105854E+09 |
August | 0.188114E+10 | 0.848184E+09 | 0.103295E+10 | 0.227078E+10 | 0.149368E+09 |
September | 0.135784E+10 | 0.609273E+09 | 0.748572E+09 | 0.142207E+10 | 0.357160E+09 |
October | 0.127195E+10 | 0.576514E+09 | 0.695440E+09 | 0.113581E+10 | 0.716045E+09 |
November | 0.761261E+09 | 0.292365E+09 | 0.468896E+09 | 0.435179E+09 | 0.110710E+10 |
December | 0.612885E+09 | 0.287822E+09 | 0.325062E+09 | 0.276710E+09 | 0.149161E+10 |
Annual Sum or Average | 0.151215E+11 | 0.632566E+10 | 0.879583E+10 | 0.138301E+11 | 0.955041E+10 |
Minimum of Months | 0.612885E+09 | 0.249968E+09 | 0.325062E+09 | 0.257746E+09 | 0.105854E+09 |
Maximum of Months | 0.188114E+10 | 0.848184E+09 | 0.107746E+10 | 0.227078E+10 | 0.159261E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.623380E+09 | 0.249964E+09 | 0.373416E+09 | 0.257741E+09 | 0.159258E+10 |
February | 0.873090E+09 | 0.407301E+09 | 0.465790E+09 | 0.451960E+09 | 0.142734E+10 |
March | 0.123311E+10 | 0.524444E+09 | 0.708664E+09 | 0.856356E+09 | 0.113132E+10 |
April | 0.143216E+10 | 0.627372E+09 | 0.804790E+09 | 0.118937E+10 | 0.759921E+09 |
May | 0.179455E+10 | 0.717107E+09 | 0.107744E+10 | 0.175147E+10 | 0.480157E+09 |
June | 0.160951E+10 | 0.582527E+09 | 0.102698E+10 | 0.176646E+10 | 0.231842E+09 |
July | 0.167045E+10 | 0.602723E+09 | 0.106773E+10 | 0.201600E+10 | 0.105852E+09 |
August | 0.188110E+10 | 0.848168E+09 | 0.103294E+10 | 0.227074E+10 | 0.149365E+09 |
September | 0.135782E+10 | 0.609261E+09 | 0.748558E+09 | 0.142204E+10 | 0.357154E+09 |
October | 0.127193E+10 | 0.576504E+09 | 0.695428E+09 | 0.113579E+10 | 0.716032E+09 |
November | 0.761247E+09 | 0.292359E+09 | 0.468888E+09 | 0.435171E+09 | 0.110708E+10 |
December | 0.612873E+09 | 0.287817E+09 | 0.325056E+09 | 0.276705E+09 | 0.149159E+10 |
Annual Sum or Average | 0.151212E+11 | 0.632555E+10 | 0.879567E+10 | 0.138298E+11 | 0.955023E+10 |
Minimum of Months | 0.612873E+09 | 0.249964E+09 | 0.325056E+09 | 0.257741E+09 | 0.105852E+09 |
Maximum of Months | 0.188110E+10 | 0.848168E+09 | 0.107744E+10 | 0.227074E+10 | 0.159258E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138933E+10 | 0.909750E+09 | 0.479576E+09 | 0.121730E+10 | 0.133070E+10 |
February | 0.165580E+10 | 0.109624E+10 | 0.559559E+09 | 0.142956E+10 | 0.122560E+10 |
March | 0.165376E+10 | 0.918111E+09 | 0.735648E+09 | 0.136782E+10 | 0.102914E+10 |
April | 0.124127E+10 | 0.490723E+09 | 0.750543E+09 | 0.883353E+09 | 0.737639E+09 |
May | 0.112404E+10 | 0.234319E+09 | 0.889719E+09 | 0.838197E+09 | 0.463861E+09 |
June | 0.102078E+10 | 0.155844E+09 | 0.864935E+09 | 0.943685E+09 | 0.235111E+09 |
July | 0.110570E+10 | 0.191900E+09 | 0.913799E+09 | 0.116607E+10 | 0.120853E+09 |
August | 0.147657E+10 | 0.547544E+09 | 0.929029E+09 | 0.151868E+10 | 0.171960E+09 |
September | 0.155087E+10 | 0.802273E+09 | 0.748597E+09 | 0.158841E+10 | 0.353321E+09 |
October | 0.219612E+10 | 0.137751E+10 | 0.818608E+09 | 0.229200E+10 | 0.677252E+09 |
November | 0.147318E+10 | 0.884792E+09 | 0.588393E+09 | 0.137330E+10 | 0.977351E+09 |
December | 0.150559E+10 | 0.106881E+10 | 0.436779E+09 | 0.139821E+10 | 0.125827E+10 |
Annual Sum or Average | 0.173930E+11 | 0.867782E+10 | 0.871518E+10 | 0.160166E+11 | 0.858106E+10 |
Minimum of Months | 0.102078E+10 | 0.155844E+09 | 0.436779E+09 | 0.838197E+09 | 0.120853E+09 |
Maximum of Months | 0.219612E+10 | 0.137751E+10 | 0.929029E+09 | 0.229200E+10 | 0.133070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138932E+10 | 0.909744E+09 | 0.479573E+09 | 0.121729E+10 | 0.133070E+10 |
February | 0.165579E+10 | 0.109624E+10 | 0.559556E+09 | 0.142954E+10 | 0.122560E+10 |
March | 0.165375E+10 | 0.918104E+09 | 0.735644E+09 | 0.136781E+10 | 0.102914E+10 |
April | 0.124126E+10 | 0.490719E+09 | 0.750539E+09 | 0.883346E+09 | 0.737640E+09 |
May | 0.112403E+10 | 0.234318E+09 | 0.889714E+09 | 0.838192E+09 | 0.463860E+09 |
June | 0.102077E+10 | 0.155843E+09 | 0.864931E+09 | 0.943680E+09 | 0.235111E+09 |
July | 0.110569E+10 | 0.191899E+09 | 0.913795E+09 | 0.116606E+10 | 0.120853E+09 |
August | 0.147656E+10 | 0.547540E+09 | 0.929024E+09 | 0.151867E+10 | 0.171959E+09 |
September | 0.155086E+10 | 0.802267E+09 | 0.748593E+09 | 0.158840E+10 | 0.353321E+09 |
October | 0.219611E+10 | 0.137750E+10 | 0.818604E+09 | 0.229199E+10 | 0.677252E+09 |
November | 0.147317E+10 | 0.884785E+09 | 0.588389E+09 | 0.137328E+10 | 0.977351E+09 |
December | 0.150558E+10 | 0.106880E+10 | 0.436777E+09 | 0.139820E+10 | 0.125827E+10 |
Annual Sum or Average | 0.173929E+11 | 0.867776E+10 | 0.871514E+10 | 0.160165E+11 | 0.858105E+10 |
Minimum of Months | 0.102077E+10 | 0.155843E+09 | 0.436777E+09 | 0.838192E+09 | 0.120853E+09 |
Maximum of Months | 0.219611E+10 | 0.137750E+10 | 0.929024E+09 | 0.229199E+10 | 0.133070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138933E+10 | 0.909750E+09 | 0.479576E+09 | 0.121730E+10 | 0.133070E+10 |
February | 0.165580E+10 | 0.109624E+10 | 0.559559E+09 | 0.142956E+10 | 0.122560E+10 |
March | 0.165376E+10 | 0.918111E+09 | 0.735648E+09 | 0.136782E+10 | 0.102914E+10 |
April | 0.124127E+10 | 0.490723E+09 | 0.750543E+09 | 0.883353E+09 | 0.737639E+09 |
May | 0.112404E+10 | 0.234319E+09 | 0.889719E+09 | 0.838197E+09 | 0.463861E+09 |
June | 0.102078E+10 | 0.155844E+09 | 0.864935E+09 | 0.943685E+09 | 0.235111E+09 |
July | 0.110570E+10 | 0.191900E+09 | 0.913799E+09 | 0.116607E+10 | 0.120853E+09 |
August | 0.147657E+10 | 0.547544E+09 | 0.929029E+09 | 0.151868E+10 | 0.171960E+09 |
September | 0.155087E+10 | 0.802273E+09 | 0.748597E+09 | 0.158841E+10 | 0.353321E+09 |
October | 0.219612E+10 | 0.137751E+10 | 0.818608E+09 | 0.229200E+10 | 0.677252E+09 |
November | 0.147318E+10 | 0.884792E+09 | 0.588393E+09 | 0.137330E+10 | 0.977351E+09 |
December | 0.150559E+10 | 0.106881E+10 | 0.436779E+09 | 0.139821E+10 | 0.125827E+10 |
Annual Sum or Average | 0.173930E+11 | 0.867782E+10 | 0.871518E+10 | 0.160166E+11 | 0.858106E+10 |
Minimum of Months | 0.102078E+10 | 0.155844E+09 | 0.436779E+09 | 0.838197E+09 | 0.120853E+09 |
Maximum of Months | 0.219612E+10 | 0.137751E+10 | 0.929029E+09 | 0.229200E+10 | 0.133070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138932E+10 | 0.909744E+09 | 0.479573E+09 | 0.121729E+10 | 0.133070E+10 |
February | 0.165579E+10 | 0.109624E+10 | 0.559556E+09 | 0.142954E+10 | 0.122560E+10 |
March | 0.165375E+10 | 0.918104E+09 | 0.735644E+09 | 0.136781E+10 | 0.102914E+10 |
April | 0.124126E+10 | 0.490719E+09 | 0.750539E+09 | 0.883346E+09 | 0.737640E+09 |
May | 0.112403E+10 | 0.234318E+09 | 0.889714E+09 | 0.838192E+09 | 0.463860E+09 |
June | 0.102077E+10 | 0.155843E+09 | 0.864931E+09 | 0.943680E+09 | 0.235111E+09 |
July | 0.110569E+10 | 0.191899E+09 | 0.913795E+09 | 0.116606E+10 | 0.120853E+09 |
August | 0.147656E+10 | 0.547540E+09 | 0.929024E+09 | 0.151867E+10 | 0.171959E+09 |
September | 0.155086E+10 | 0.802267E+09 | 0.748593E+09 | 0.158840E+10 | 0.353321E+09 |
October | 0.219611E+10 | 0.137750E+10 | 0.818604E+09 | 0.229199E+10 | 0.677252E+09 |
November | 0.147317E+10 | 0.884785E+09 | 0.588389E+09 | 0.137328E+10 | 0.977351E+09 |
December | 0.150558E+10 | 0.106880E+10 | 0.436777E+09 | 0.139820E+10 | 0.125827E+10 |
Annual Sum or Average | 0.173929E+11 | 0.867776E+10 | 0.871514E+10 | 0.160165E+11 | 0.858105E+10 |
Minimum of Months | 0.102077E+10 | 0.155843E+09 | 0.436777E+09 | 0.838192E+09 | 0.120853E+09 |
Maximum of Months | 0.219611E+10 | 0.137750E+10 | 0.929024E+09 | 0.229199E+10 | 0.133070E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138927E+10 | 0.909710E+09 | 0.479555E+09 | 0.121725E+10 | 0.133064E+10 |
February | 0.165573E+10 | 0.109620E+10 | 0.559535E+09 | 0.142949E+10 | 0.122555E+10 |
March | 0.165369E+10 | 0.918071E+09 | 0.735616E+09 | 0.136776E+10 | 0.102910E+10 |
April | 0.124121E+10 | 0.490701E+09 | 0.750510E+09 | 0.883314E+09 | 0.737610E+09 |
May | 0.112399E+10 | 0.234309E+09 | 0.889681E+09 | 0.838161E+09 | 0.463842E+09 |
June | 0.102074E+10 | 0.155838E+09 | 0.864898E+09 | 0.943644E+09 | 0.235101E+09 |
July | 0.110565E+10 | 0.191892E+09 | 0.913760E+09 | 0.116602E+10 | 0.120848E+09 |
August | 0.147651E+10 | 0.547520E+09 | 0.928989E+09 | 0.151861E+10 | 0.171953E+09 |
September | 0.155080E+10 | 0.802238E+09 | 0.748565E+09 | 0.158834E+10 | 0.353307E+09 |
October | 0.219602E+10 | 0.137745E+10 | 0.818573E+09 | 0.229190E+10 | 0.677225E+09 |
November | 0.147312E+10 | 0.884753E+09 | 0.588368E+09 | 0.137324E+10 | 0.977311E+09 |
December | 0.150552E+10 | 0.106876E+10 | 0.436760E+09 | 0.139815E+10 | 0.125822E+10 |
Annual Sum or Average | 0.173923E+11 | 0.867744E+10 | 0.871481E+10 | 0.160159E+11 | 0.858071E+10 |
Minimum of Months | 0.102074E+10 | 0.155838E+09 | 0.436760E+09 | 0.838161E+09 | 0.120848E+09 |
Maximum of Months | 0.219602E+10 | 0.137745E+10 | 0.928989E+09 | 0.229190E+10 | 0.133064E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.615427E+09 | 0.252119E+09 | 0.363308E+09 | 0.263118E+09 | 0.170168E+10 |
February | 0.819626E+09 | 0.359984E+09 | 0.459642E+09 | 0.406440E+09 | 0.159239E+10 |
March | 0.134004E+10 | 0.618712E+09 | 0.721330E+09 | 0.945457E+09 | 0.126905E+10 |
April | 0.141730E+10 | 0.606454E+09 | 0.810849E+09 | 0.114683E+10 | 0.928878E+09 |
May | 0.170582E+10 | 0.647694E+09 | 0.105812E+10 | 0.163945E+10 | 0.547607E+09 |
June | 0.180672E+10 | 0.728583E+09 | 0.107814E+10 | 0.197678E+10 | 0.302396E+09 |
July | 0.174854E+10 | 0.658353E+09 | 0.109019E+10 | 0.205607E+10 | 0.178824E+09 |
August | 0.193451E+10 | 0.895535E+09 | 0.103897E+10 | 0.228262E+10 | 0.246327E+09 |
September | 0.132915E+10 | 0.580885E+09 | 0.748265E+09 | 0.139124E+10 | 0.423518E+09 |
October | 0.136159E+10 | 0.662112E+09 | 0.699481E+09 | 0.123478E+10 | 0.828897E+09 |
November | 0.618780E+09 | 0.178839E+09 | 0.439942E+09 | 0.267083E+09 | 0.129448E+10 |
December | 0.568802E+09 | 0.246163E+09 | 0.322639E+09 | 0.229210E+09 | 0.175084E+10 |
Annual Sum or Average | 0.152663E+11 | 0.643543E+10 | 0.883088E+10 | 0.138391E+11 | 0.110649E+11 |
Minimum of Months | 0.568802E+09 | 0.178839E+09 | 0.322639E+09 | 0.229210E+09 | 0.178824E+09 |
Maximum of Months | 0.193451E+10 | 0.895535E+09 | 0.109019E+10 | 0.228262E+10 | 0.175084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.615427E+09 | 0.252119E+09 | 0.363308E+09 | 0.263118E+09 | 0.170168E+10 |
February | 0.819626E+09 | 0.359984E+09 | 0.459642E+09 | 0.406440E+09 | 0.159239E+10 |
March | 0.134004E+10 | 0.618712E+09 | 0.721330E+09 | 0.945457E+09 | 0.126905E+10 |
April | 0.141730E+10 | 0.606454E+09 | 0.810849E+09 | 0.114683E+10 | 0.928878E+09 |
May | 0.170582E+10 | 0.647694E+09 | 0.105812E+10 | 0.163945E+10 | 0.547607E+09 |
June | 0.180672E+10 | 0.728583E+09 | 0.107814E+10 | 0.197678E+10 | 0.302396E+09 |
July | 0.174854E+10 | 0.658353E+09 | 0.109019E+10 | 0.205607E+10 | 0.178824E+09 |
August | 0.193451E+10 | 0.895535E+09 | 0.103897E+10 | 0.228262E+10 | 0.246327E+09 |
September | 0.132915E+10 | 0.580885E+09 | 0.748265E+09 | 0.139124E+10 | 0.423518E+09 |
October | 0.136159E+10 | 0.662112E+09 | 0.699481E+09 | 0.123478E+10 | 0.828897E+09 |
November | 0.618780E+09 | 0.178839E+09 | 0.439942E+09 | 0.267083E+09 | 0.129448E+10 |
December | 0.568802E+09 | 0.246163E+09 | 0.322639E+09 | 0.229210E+09 | 0.175084E+10 |
Annual Sum or Average | 0.152663E+11 | 0.643543E+10 | 0.883088E+10 | 0.138391E+11 | 0.110649E+11 |
Minimum of Months | 0.568802E+09 | 0.178839E+09 | 0.322639E+09 | 0.229210E+09 | 0.178824E+09 |
Maximum of Months | 0.193451E+10 | 0.895535E+09 | 0.109019E+10 | 0.228262E+10 | 0.175084E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.615416E+09 | 0.252114E+09 | 0.363302E+09 | 0.263114E+09 | 0.170164E+10 |
February | 0.819611E+09 | 0.359977E+09 | 0.459633E+09 | 0.406432E+09 | 0.159236E+10 |
March | 0.134002E+10 | 0.618701E+09 | 0.721317E+09 | 0.945440E+09 | 0.126903E+10 |
April | 0.141728E+10 | 0.606443E+09 | 0.810835E+09 | 0.114681E+10 | 0.928861E+09 |
May | 0.170579E+10 | 0.647682E+09 | 0.105810E+10 | 0.163942E+10 | 0.547597E+09 |
June | 0.180669E+10 | 0.728569E+09 | 0.107812E+10 | 0.197674E+10 | 0.302391E+09 |
July | 0.174851E+10 | 0.658341E+09 | 0.109017E+10 | 0.205603E+10 | 0.178821E+09 |
August | 0.193447E+10 | 0.895518E+09 | 0.103895E+10 | 0.228258E+10 | 0.246323E+09 |
September | 0.132912E+10 | 0.580874E+09 | 0.748251E+09 | 0.139122E+10 | 0.423511E+09 |
October | 0.136157E+10 | 0.662100E+09 | 0.699468E+09 | 0.123476E+10 | 0.828882E+09 |
November | 0.618769E+09 | 0.178835E+09 | 0.439934E+09 | 0.267078E+09 | 0.129445E+10 |
December | 0.568791E+09 | 0.246158E+09 | 0.322633E+09 | 0.229206E+09 | 0.175081E+10 |
Annual Sum or Average | 0.152660E+11 | 0.643531E+10 | 0.883072E+10 | 0.138388E+11 | 0.110647E+11 |
Minimum of Months | 0.568791E+09 | 0.178835E+09 | 0.322633E+09 | 0.229206E+09 | 0.178821E+09 |
Maximum of Months | 0.193447E+10 | 0.895518E+09 | 0.109017E+10 | 0.228258E+10 | 0.175081E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134280E+10 | 0.00 | 0.134280E+10 | 32690698.17 | 0.698532E+10 |
February | 0.165973E+10 | 0.00 | 0.165973E+10 | 81902515.14 | 0.660078E+10 |
March | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.612508E+09 | 0.491897E+10 |
April | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.140877E+10 | 0.337436E+10 |
May | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.293420E+10 | 0.208919E+10 |
June | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.406583E+10 | 0.105787E+10 |
July | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.481640E+10 | 0.587530E+09 |
August | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.430596E+10 | 0.818034E+09 |
September | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.237472E+10 | 0.162143E+10 |
October | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.138537E+10 | 0.315613E+10 |
November | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.291365E+09 | 0.485700E+10 |
December | 0.117128E+10 | 0.00 | 0.117128E+10 | 19976154.40 | 0.662636E+10 |
Annual Sum or Average | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.223297E+11 | 0.426930E+11 |
Minimum of Months | 0.117128E+10 | 0.00 | 0.117128E+10 | 19976154.40 | 0.587530E+09 |
Maximum of Months | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.481640E+10 | 0.698532E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.828284E+09 | 0.429635E+10 |
February | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.141625E+10 | 0.392914E+10 |
March | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.262651E+10 | 0.311051E+10 |
April | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.360670E+10 | 0.212046E+10 |
May | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.526967E+10 | 0.135711E+10 |
June | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.529492E+10 | 0.680905E+09 |
July | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.601581E+10 | 0.363122E+09 |
August | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.676933E+10 | 0.511531E+09 |
September | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.428854E+10 | 0.994750E+09 |
October | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.345663E+10 | 0.197915E+10 |
November | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.138047E+10 | 0.296891E+10 |
December | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.881766E+09 | 0.402081E+10 |
Annual Sum or Average | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.418349E+11 | 0.263328E+11 |
Minimum of Months | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.828284E+09 | 0.363122E+09 |
Maximum of Months | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.676933E+10 | 0.429635E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.611760E+10 | 0.628120E+10 |
February | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.714721E+10 | 0.588808E+10 |
March | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.684604E+10 | 0.487906E+10 |
April | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.447203E+10 | 0.346927E+10 |
May | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.422476E+10 | 0.223143E+10 |
June | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.474948E+10 | 0.113455E+10 |
July | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.586367E+10 | 0.610249E+09 |
August | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.762061E+10 | 0.882750E+09 |
September | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.792625E+10 | 0.171531E+10 |
October | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.114053E+11 | 0.329750E+10 |
November | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.688393E+10 | 0.461161E+10 |
December | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.701460E+10 | 0.591508E+10 |
Annual Sum or Average | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.802715E+11 | 0.409161E+11 |
Minimum of Months | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.422476E+10 | 0.610249E+09 |
Maximum of Months | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.114053E+11 | 0.628120E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.843605E+09 | 0.448646E+10 |
February | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.129717E+10 | 0.418824E+10 |
March | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.298254E+10 | 0.319702E+10 |
April | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.361844E+10 | 0.228454E+10 |
May | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.501334E+10 | 0.148050E+10 |
June | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.601760E+10 | 0.795602E+09 |
July | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.627964E+10 | 0.456348E+09 |
August | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.696324E+10 | 0.649544E+09 |
September | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.426025E+10 | 0.110917E+10 |
October | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.383753E+10 | 0.213811E+10 |
November | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.929135E+09 | 0.314392E+10 |
December | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.782817E+09 | 0.425115E+10 |
Annual Sum or Average | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.428253E+11 | 0.281806E+11 |
Minimum of Months | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.782817E+09 | 0.456348E+09 |
Maximum of Months | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.696324E+10 | 0.448646E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.134280E+10 | 0.00 | 0.134280E+10 | 46239301.06 | 0.662165E+10 |
February | 0.165973E+10 | 0.00 | 0.165973E+10 | 0.106862E+09 | 0.621944E+10 |
March | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.677604E+09 | 0.456077E+10 |
April | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.148018E+10 | 0.313244E+10 |
May | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.296880E+10 | 0.199477E+10 |
June | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.403887E+10 | 0.104430E+10 |
July | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.476557E+10 | 0.600114E+09 |
August | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.427006E+10 | 0.817268E+09 |
September | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.239286E+10 | 0.153970E+10 |
October | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.146788E+10 | 0.290786E+10 |
November | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.359951E+09 | 0.440165E+10 |
December | 0.117128E+10 | 0.00 | 0.117128E+10 | 39697438.30 | 0.609080E+10 |
Annual Sum or Average | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.226146E+11 | 0.399308E+11 |
Minimum of Months | 0.117128E+10 | 0.00 | 0.117128E+10 | 39697438.30 | 0.600114E+09 |
Maximum of Months | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.476557E+10 | 0.662165E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.852217E+09 | 0.408495E+10 |
February | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.145932E+10 | 0.371202E+10 |
March | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.267724E+10 | 0.291485E+10 |
April | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.364646E+10 | 0.200410E+10 |
May | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.527415E+10 | 0.131530E+10 |
June | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.526646E+10 | 0.680648E+09 |
July | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.597524E+10 | 0.375980E+09 |
August | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.673627E+10 | 0.518637E+09 |
September | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.428887E+10 | 0.961277E+09 |
October | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.350183E+10 | 0.185792E+10 |
November | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.144444E+10 | 0.273090E+10 |
December | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.923180E+09 | 0.371813E+10 |
Annual Sum or Average | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.420457E+11 | 0.248747E+11 |
Minimum of Months | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.852217E+09 | 0.375980E+09 |
Maximum of Months | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.673627E+10 | 0.408495E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.618018E+10 | 0.592481E+10 |
February | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.724206E+10 | 0.550585E+10 |
March | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.692092E+10 | 0.453206E+10 |
April | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.454528E+10 | 0.324254E+10 |
May | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.426091E+10 | 0.213411E+10 |
June | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.472966E+10 | 0.111992E+10 |
July | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.582344E+10 | 0.621445E+09 |
August | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.759543E+10 | 0.880370E+09 |
September | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.794423E+10 | 0.163923E+10 |
October | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.114732E+11 | 0.308411E+10 |
November | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.700012E+10 | 0.421036E+10 |
December | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.712770E+10 | 0.543109E+10 |
Annual Sum or Average | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.808431E+11 | 0.383259E+11 |
Minimum of Months | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.426091E+10 | 0.621445E+09 |
Maximum of Months | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.114732E+11 | 0.592481E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.858716E+09 | 0.427924E+10 |
February | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.131575E+10 | 0.398815E+10 |
March | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.301333E+10 | 0.301624E+10 |
April | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.364833E+10 | 0.216045E+10 |
May | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.502581E+10 | 0.142495E+10 |
June | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.600321E+10 | 0.781793E+09 |
July | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.625415E+10 | 0.457294E+09 |
August | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.694690E+10 | 0.641899E+09 |
September | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.426994E+10 | 0.106385E+10 |
October | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.387139E+10 | 0.201323E+10 |
November | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.969917E+09 | 0.292002E+10 |
December | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.806282E+09 | 0.398062E+10 |
Annual Sum or Average | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.429837E+11 | 0.267277E+11 |
Minimum of Months | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.806282E+09 | 0.457294E+09 |
Maximum of Months | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.694690E+10 | 0.427924E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2.73 | 2957.85 | 501.33 | 0.00 | 501.33 | 0.00 | 0.00 |
February | 18.16 | 3046.67 | 686.05 | 0.00 | 686.05 | 0.00 | 0.00 |
March | 182.30 | 2088.69 | 951.39 | 0.00 | 951.39 | 0.00 | 0.00 |
April | 490.33 | 1474.09 | 1142.69 | 3.20 | 1139.49 | 0.00 | 0.00 |
May | 1065.73 | 837.67 | 1515.90 | 50.35 | 1465.54 | 0.00 | 0.00 |
June | 1549.09 | 432.98 | 1607.56 | 86.19 | 1521.37 | 0.00 | 0.00 |
July | 1782.74 | 223.98 | 1553.58 | 56.02 | 1497.56 | 0.00 | 0.00 |
August | 1587.35 | 309.71 | 1376.43 | 16.26 | 1360.16 | 0.00 | 0.00 |
September | 890.86 | 684.49 | 1037.68 | 0.19 | 1037.49 | 0.00 | 0.00 |
October | 476.43 | 1313.30 | 898.04 | 0.00 | 898.04 | 0.00 | 0.00 |
November | 83.39 | 2178.94 | 629.89 | 0.00 | 629.89 | 0.00 | 0.00 |
December | 2.01 | 2880.47 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Annual Sum or Average | 682.18 | 1527.08 | 1030.13 | 17.78 | 1012.35 | 0.00 | 0.00 |
Minimum of Months | 2.01 | 223.98 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Maximum of Months | 1782.74 | 3046.67 | 1607.56 | 86.19 | 1521.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 288.69 | 1783.83 | 698.24 | 279.98 | 418.26 | 0.00 | 0.00 |
February | 560.47 | 1770.04 | 1082.71 | 505.09 | 577.62 | 0.00 | 0.00 |
March | 959.19 | 1267.18 | 1381.19 | 587.42 | 793.76 | 0.00 | 0.00 |
April | 1376.61 | 879.55 | 1657.61 | 726.13 | 931.48 | 0.00 | 0.00 |
May | 1961.79 | 537.82 | 2010.05 | 803.22 | 1206.83 | 0.00 | 0.00 |
June | 2044.54 | 268.34 | 1862.88 | 674.23 | 1188.65 | 0.00 | 0.00 |
July | 2258.09 | 118.56 | 1871.04 | 675.10 | 1195.94 | 0.00 | 0.00 |
August | 2543.42 | 167.30 | 2107.00 | 950.02 | 1156.98 | 0.00 | 0.00 |
September | 1645.90 | 413.38 | 1571.57 | 705.17 | 866.40 | 0.00 | 0.00 |
October | 1272.18 | 802.02 | 1424.67 | 645.73 | 778.94 | 0.00 | 0.00 |
November | 503.68 | 1281.36 | 881.08 | 338.38 | 542.70 | 0.00 | 0.00 |
December | 309.93 | 1670.70 | 686.47 | 322.38 | 364.09 | 0.00 | 0.00 |
Annual Sum or Average | 1315.64 | 908.52 | 1438.49 | 601.75 | 836.74 | 0.00 | 0.00 |
Minimum of Months | 288.69 | 118.56 | 686.47 | 279.98 | 364.09 | 0.00 | 0.00 |
Maximum of Months | 2543.42 | 1783.83 | 2107.00 | 950.02 | 1206.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2272.41 | 2484.11 | 2593.54 | 1698.29 | 895.26 | 0.00 | 0.00 |
February | 2954.57 | 2533.06 | 3422.18 | 2265.69 | 1156.48 | 0.00 | 0.00 |
March | 2553.40 | 1921.16 | 3087.18 | 1713.90 | 1373.28 | 0.00 | 0.00 |
April | 1703.98 | 1422.90 | 2394.39 | 946.60 | 1447.79 | 0.00 | 0.00 |
May | 1564.72 | 865.92 | 2098.32 | 437.42 | 1660.90 | 0.00 | 0.00 |
June | 1820.36 | 453.53 | 1969.07 | 300.62 | 1668.45 | 0.00 | 0.00 |
July | 2176.77 | 225.60 | 2064.08 | 358.23 | 1705.85 | 0.00 | 0.00 |
August | 2835.02 | 321.01 | 2756.42 | 1022.14 | 1734.28 | 0.00 | 0.00 |
September | 3064.03 | 681.56 | 2991.61 | 1547.58 | 1444.04 | 0.00 | 0.00 |
October | 4278.63 | 1264.27 | 4099.64 | 2571.49 | 1528.15 | 0.00 | 0.00 |
November | 2649.07 | 1885.31 | 2841.76 | 1706.75 | 1135.00 | 0.00 | 0.00 |
December | 2610.12 | 2348.90 | 2810.58 | 1995.22 | 815.36 | 0.00 | 0.00 |
Annual Sum or Average | 2539.38 | 1360.51 | 2757.61 | 1375.84 | 1381.77 | 0.00 | 0.00 |
Minimum of Months | 1564.72 | 225.60 | 1969.07 | 300.62 | 815.36 | 0.00 | 0.00 |
Maximum of Months | 4278.63 | 2533.06 | 4099.64 | 2571.49 | 1734.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 294.71 | 1905.99 | 689.32 | 282.39 | 406.93 | 0.00 | 0.00 |
February | 504.01 | 1974.68 | 1016.39 | 446.41 | 569.99 | 0.00 | 0.00 |
March | 1058.97 | 1421.42 | 1500.93 | 693.00 | 807.94 | 0.00 | 0.00 |
April | 1327.34 | 1075.08 | 1640.39 | 701.91 | 938.48 | 0.00 | 0.00 |
May | 1836.29 | 613.35 | 1910.63 | 725.46 | 1185.17 | 0.00 | 0.00 |
June | 2287.92 | 349.99 | 2091.10 | 843.26 | 1247.84 | 0.00 | 0.00 |
July | 2302.93 | 200.29 | 1958.48 | 737.40 | 1221.08 | 0.00 | 0.00 |
August | 2556.68 | 275.90 | 2166.77 | 1003.06 | 1163.71 | 0.00 | 0.00 |
September | 1610.23 | 490.18 | 1538.36 | 672.32 | 866.04 | 0.00 | 0.00 |
October | 1383.03 | 928.42 | 1525.07 | 741.61 | 783.46 | 0.00 | 0.00 |
November | 309.12 | 1498.23 | 716.18 | 206.99 | 509.19 | 0.00 | 0.00 |
December | 256.73 | 1961.06 | 637.09 | 275.72 | 361.38 | 0.00 | 0.00 |
Annual Sum or Average | 1316.49 | 1052.59 | 1452.27 | 612.19 | 840.07 | 0.00 | 0.00 |
Minimum of Months | 256.73 | 200.29 | 637.09 | 206.99 | 361.38 | 0.00 | 0.00 |
Maximum of Months | 2556.68 | 1974.68 | 2166.77 | 1003.06 | 1247.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 12.21 | 2608.02 | 501.34 | 0.00 | 501.34 | 0.00 | 0.00 |
February | 33.86 | 2728.50 | 686.07 | 0.00 | 686.07 | 0.00 | 0.00 |
March | 228.68 | 1836.53 | 951.40 | 0.00 | 951.40 | 0.00 | 0.00 |
April | 543.51 | 1301.84 | 1142.71 | 3.20 | 1139.51 | 0.00 | 0.00 |
May | 1095.51 | 780.01 | 1515.92 | 50.36 | 1465.57 | 0.00 | 0.00 |
June | 1568.61 | 408.13 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
July | 1798.24 | 219.36 | 1553.61 | 56.03 | 1497.58 | 0.00 | 0.00 |
August | 1607.66 | 305.42 | 1376.45 | 16.27 | 1360.19 | 0.00 | 0.00 |
September | 916.17 | 625.55 | 1037.70 | 0.19 | 1037.51 | 0.00 | 0.00 |
October | 517.24 | 1178.36 | 898.06 | 0.00 | 898.06 | 0.00 | 0.00 |
November | 112.41 | 1873.84 | 629.90 | 0.00 | 629.90 | 0.00 | 0.00 |
December | 7.46 | 2474.00 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Annual Sum or Average | 708.07 | 1353.79 | 1030.15 | 17.78 | 1012.37 | 0.00 | 0.00 |
Minimum of Months | 7.46 | 219.36 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Maximum of Months | 1798.24 | 2728.50 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 309.25 | 1604.07 | 698.24 | 279.98 | 418.26 | 0.00 | 0.00 |
February | 585.42 | 1624.15 | 1082.71 | 505.09 | 577.62 | 0.00 | 0.00 |
March | 980.63 | 1161.33 | 1381.18 | 587.42 | 793.76 | 0.00 | 0.00 |
April | 1391.47 | 818.08 | 1657.61 | 726.13 | 931.48 | 0.00 | 0.00 |
May | 1967.47 | 506.69 | 2010.04 | 803.22 | 1206.82 | 0.00 | 0.00 |
June | 2042.79 | 262.70 | 1862.87 | 674.23 | 1188.64 | 0.00 | 0.00 |
July | 2246.05 | 135.57 | 1871.04 | 675.10 | 1195.94 | 0.00 | 0.00 |
August | 2527.38 | 190.98 | 2106.99 | 950.02 | 1156.97 | 0.00 | 0.00 |
September | 1654.53 | 383.78 | 1571.56 | 705.17 | 866.39 | 0.00 | 0.00 |
October | 1290.56 | 738.93 | 1424.67 | 645.73 | 778.94 | 0.00 | 0.00 |
November | 532.59 | 1145.41 | 881.08 | 338.38 | 542.70 | 0.00 | 0.00 |
December | 329.21 | 1501.20 | 686.47 | 322.38 | 364.09 | 0.00 | 0.00 |
Annual Sum or Average | 1326.58 | 835.01 | 1438.48 | 601.75 | 836.73 | 0.00 | 0.00 |
Minimum of Months | 309.25 | 135.57 | 686.47 | 279.98 | 364.09 | 0.00 | 0.00 |
Maximum of Months | 2527.38 | 1624.15 | 2106.99 | 950.02 | 1206.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2284.05 | 2345.13 | 2593.62 | 1698.34 | 895.28 | 0.00 | 0.00 |
February | 2954.37 | 2433.90 | 3422.28 | 2265.77 | 1156.51 | 0.00 | 0.00 |
March | 2556.02 | 1821.63 | 3087.27 | 1713.95 | 1373.31 | 0.00 | 0.00 |
April | 1725.32 | 1338.45 | 2394.45 | 946.63 | 1447.82 | 0.00 | 0.00 |
May | 1577.34 | 833.12 | 2098.37 | 437.43 | 1660.93 | 0.00 | 0.00 |
June | 1832.36 | 437.71 | 1969.12 | 300.63 | 1668.49 | 0.00 | 0.00 |
July | 2189.24 | 227.84 | 2064.13 | 358.24 | 1705.89 | 0.00 | 0.00 |
August | 2845.21 | 329.58 | 2756.49 | 1022.17 | 1734.32 | 0.00 | 0.00 |
September | 3057.97 | 661.77 | 2991.70 | 1547.63 | 1444.07 | 0.00 | 0.00 |
October | 4258.27 | 1231.15 | 4099.76 | 2571.57 | 1528.19 | 0.00 | 0.00 |
November | 2655.84 | 1779.17 | 2841.85 | 1706.81 | 1135.04 | 0.00 | 0.00 |
December | 2618.95 | 2208.44 | 2810.67 | 1995.28 | 815.39 | 0.00 | 0.00 |
Annual Sum or Average | 2545.39 | 1297.44 | 2757.69 | 1375.89 | 1381.80 | 0.00 | 0.00 |
Minimum of Months | 1577.34 | 227.84 | 1969.12 | 300.63 | 815.39 | 0.00 | 0.00 |
Maximum of Months | 4258.27 | 2433.90 | 4099.76 | 2571.57 | 1734.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 314.97 | 1675.05 | 689.32 | 282.39 | 406.93 | 0.00 | 0.00 |
February | 536.20 | 1731.25 | 1016.39 | 446.40 | 569.99 | 0.00 | 0.00 |
March | 1113.55 | 1193.63 | 1500.93 | 692.99 | 807.93 | 0.00 | 0.00 |
April | 1396.00 | 881.38 | 1640.38 | 701.91 | 938.47 | 0.00 | 0.00 |
May | 1871.77 | 552.76 | 1910.62 | 725.46 | 1185.16 | 0.00 | 0.00 |
June | 2321.61 | 306.95 | 2091.09 | 843.26 | 1247.84 | 0.00 | 0.00 |
July | 2344.55 | 170.38 | 1958.47 | 737.40 | 1221.08 | 0.00 | 0.00 |
August | 2599.78 | 242.51 | 2166.76 | 1003.05 | 1163.71 | 0.00 | 0.00 |
September | 1643.62 | 427.92 | 1538.35 | 672.31 | 866.04 | 0.00 | 0.00 |
October | 1432.77 | 798.28 | 1525.07 | 741.61 | 783.46 | 0.00 | 0.00 |
November | 358.46 | 1212.93 | 716.17 | 206.99 | 509.19 | 0.00 | 0.00 |
December | 292.27 | 1587.20 | 637.09 | 275.72 | 361.38 | 0.00 | 0.00 |
Annual Sum or Average | 1357.98 | 893.60 | 1452.26 | 612.19 | 840.07 | 0.00 | 0.00 |
Minimum of Months | 292.27 | 170.38 | 637.09 | 206.99 | 361.38 | 0.00 | 0.00 |
Maximum of Months | 2599.78 | 1731.25 | 2166.76 | 1003.05 | 1247.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 17.26 | 2472.24 | 501.34 | 0.00 | 501.34 | 0.00 | 0.00 |
February | 44.17 | 2570.87 | 686.07 | 0.00 | 686.07 | 0.00 | 0.00 |
March | 252.99 | 1702.80 | 951.40 | 0.00 | 951.40 | 0.00 | 0.00 |
April | 571.06 | 1208.50 | 1142.71 | 3.20 | 1139.51 | 0.00 | 0.00 |
May | 1108.42 | 744.76 | 1515.92 | 50.36 | 1465.57 | 0.00 | 0.00 |
June | 1558.21 | 402.89 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
July | 1779.26 | 224.06 | 1553.61 | 56.03 | 1497.58 | 0.00 | 0.00 |
August | 1594.26 | 305.13 | 1376.45 | 16.27 | 1360.19 | 0.00 | 0.00 |
September | 923.17 | 594.02 | 1037.70 | 0.19 | 1037.51 | 0.00 | 0.00 |
October | 548.04 | 1085.67 | 898.06 | 0.00 | 898.06 | 0.00 | 0.00 |
November | 138.87 | 1698.17 | 629.90 | 0.00 | 629.90 | 0.00 | 0.00 |
December | 14.82 | 2274.04 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Annual Sum or Average | 717.10 | 1266.20 | 1030.15 | 17.78 | 1012.37 | 0.00 | 0.00 |
Minimum of Months | 14.82 | 224.06 | 437.30 | 0.00 | 437.30 | 0.00 | 0.00 |
Maximum of Months | 1779.26 | 2570.87 | 1607.59 | 86.19 | 1521.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 318.18 | 1525.14 | 698.24 | 279.98 | 418.26 | 0.00 | 0.00 |
February | 603.23 | 1534.40 | 1082.71 | 505.09 | 577.62 | 0.00 | 0.00 |
March | 999.57 | 1088.28 | 1381.18 | 587.42 | 793.76 | 0.00 | 0.00 |
April | 1406.81 | 773.19 | 1657.61 | 726.13 | 931.48 | 0.00 | 0.00 |
May | 1969.14 | 491.08 | 2010.04 | 803.22 | 1206.82 | 0.00 | 0.00 |
June | 2031.81 | 262.60 | 1862.87 | 674.23 | 1188.64 | 0.00 | 0.00 |
July | 2230.90 | 140.37 | 1871.04 | 675.10 | 1195.94 | 0.00 | 0.00 |
August | 2515.04 | 193.64 | 2106.99 | 950.02 | 1156.97 | 0.00 | 0.00 |
September | 1654.66 | 370.86 | 1571.56 | 705.17 | 866.39 | 0.00 | 0.00 |
October | 1307.43 | 693.67 | 1424.67 | 645.73 | 778.94 | 0.00 | 0.00 |
November | 557.27 | 1053.59 | 881.08 | 338.38 | 542.70 | 0.00 | 0.00 |
December | 344.68 | 1388.19 | 686.47 | 322.38 | 364.09 | 0.00 | 0.00 |
Annual Sum or Average | 1333.26 | 788.77 | 1438.48 | 601.75 | 836.73 | 0.00 | 0.00 |
Minimum of Months | 318.18 | 140.37 | 686.47 | 279.98 | 364.09 | 0.00 | 0.00 |
Maximum of Months | 2515.04 | 1534.40 | 2106.99 | 950.02 | 1206.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 2307.41 | 2212.07 | 2593.62 | 1698.34 | 895.28 | 0.00 | 0.00 |
February | 2993.58 | 2275.90 | 3422.28 | 2265.77 | 1156.51 | 0.00 | 0.00 |
March | 2583.97 | 1692.08 | 3087.27 | 1713.95 | 1373.31 | 0.00 | 0.00 |
April | 1753.58 | 1250.98 | 2394.45 | 946.63 | 1447.82 | 0.00 | 0.00 |
May | 1590.84 | 796.79 | 2098.37 | 437.43 | 1660.93 | 0.00 | 0.00 |
June | 1824.72 | 432.07 | 1969.12 | 300.63 | 1668.49 | 0.00 | 0.00 |
July | 2174.22 | 232.02 | 2064.13 | 358.24 | 1705.89 | 0.00 | 0.00 |
August | 2835.81 | 328.69 | 2756.49 | 1022.17 | 1734.32 | 0.00 | 0.00 |
September | 3064.90 | 632.42 | 2991.70 | 1547.63 | 1444.07 | 0.00 | 0.00 |
October | 4283.60 | 1151.47 | 4099.76 | 2571.57 | 1528.19 | 0.00 | 0.00 |
November | 2700.66 | 1624.37 | 2841.85 | 1706.81 | 1135.04 | 0.00 | 0.00 |
December | 2661.18 | 2027.74 | 2810.67 | 1995.28 | 815.39 | 0.00 | 0.00 |
Annual Sum or Average | 2563.52 | 1215.31 | 2757.69 | 1375.89 | 1381.80 | 0.00 | 0.00 |
Minimum of Months | 1590.84 | 232.02 | 1969.12 | 300.63 | 815.39 | 0.00 | 0.00 |
Maximum of Months | 4283.60 | 2275.90 | 4099.76 | 2571.57 | 1734.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 320.61 | 1597.68 | 689.32 | 282.39 | 406.93 | 0.00 | 0.00 |
February | 543.88 | 1648.54 | 1016.39 | 446.40 | 569.99 | 0.00 | 0.00 |
March | 1125.05 | 1126.14 | 1500.93 | 692.99 | 807.93 | 0.00 | 0.00 |
April | 1407.54 | 833.51 | 1640.38 | 701.91 | 938.47 | 0.00 | 0.00 |
May | 1876.42 | 532.02 | 1910.62 | 725.46 | 1185.16 | 0.00 | 0.00 |
June | 2316.05 | 301.62 | 2091.09 | 843.26 | 1247.84 | 0.00 | 0.00 |
July | 2335.03 | 170.73 | 1958.47 | 737.40 | 1221.08 | 0.00 | 0.00 |
August | 2593.67 | 239.66 | 2166.76 | 1003.05 | 1163.71 | 0.00 | 0.00 |
September | 1647.35 | 410.44 | 1538.35 | 672.31 | 866.04 | 0.00 | 0.00 |
October | 1445.41 | 751.65 | 1525.07 | 741.61 | 783.46 | 0.00 | 0.00 |
November | 374.20 | 1126.55 | 716.17 | 206.99 | 509.19 | 0.00 | 0.00 |
December | 301.03 | 1486.19 | 637.09 | 275.72 | 361.38 | 0.00 | 0.00 |
Annual Sum or Average | 1363.00 | 847.53 | 1452.26 | 612.19 | 840.07 | 0.00 | 0.00 |
Minimum of Months | 301.03 | 170.73 | 637.09 | 206.99 | 361.38 | 0.00 | 0.00 |
Maximum of Months | 2593.67 | 1648.54 | 2166.76 | 1003.05 | 1247.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 7316872.08 | 0.792229E+10 | 0.134277E+10 | 0.00 | 0.134277E+10 | 0.00 | 0.00 |
February | 43942016.29 | 0.737050E+10 | 0.165970E+10 | 0.00 | 0.165970E+10 | 0.00 | 0.00 |
March | 0.488268E+09 | 0.559436E+10 | 0.254819E+10 | 0.00 | 0.254819E+10 | 0.00 | 0.00 |
April | 0.127094E+10 | 0.382084E+10 | 0.296186E+10 | 8293119.36 | 0.295357E+10 | 0.00 | 0.00 |
May | 0.285445E+10 | 0.224361E+10 | 0.406018E+10 | 0.134869E+09 | 0.392531E+10 | 0.00 | 0.00 |
June | 0.401525E+10 | 0.112228E+10 | 0.416680E+10 | 0.223409E+09 | 0.394339E+10 | 0.00 | 0.00 |
July | 0.477490E+10 | 0.599917E+09 | 0.416111E+10 | 0.150053E+09 | 0.401106E+10 | 0.00 | 0.00 |
August | 0.425154E+10 | 0.829531E+09 | 0.368663E+10 | 43563661.02 | 0.364306E+10 | 0.00 | 0.00 |
September | 0.230911E+10 | 0.177419E+10 | 0.268966E+10 | 484697.40 | 0.268918E+10 | 0.00 | 0.00 |
October | 0.127606E+10 | 0.351753E+10 | 0.240532E+10 | 0.00 | 0.240532E+10 | 0.00 | 0.00 |
November | 0.216146E+09 | 0.564782E+10 | 0.163267E+10 | 0.00 | 0.163267E+10 | 0.00 | 0.00 |
December | 5381455.39 | 0.771504E+10 | 0.117125E+10 | 0.00 | 0.117125E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.215133E+11 | 0.481579E+11 | 0.324861E+11 | 0.560672E+09 | 0.319255E+11 | 0.00 | 0.00 |
Minimum of Months | 5381455.39 | 0.599917E+09 | 0.117125E+10 | 0.00 | 0.117125E+10 | 0.00 | 0.00 |
Maximum of Months | 0.477490E+10 | 0.792229E+10 | 0.416680E+10 | 0.223409E+09 | 0.401106E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.773233E+09 | 0.477781E+10 | 0.187016E+10 | 0.749900E+09 | 0.112026E+10 | 0.00 | 0.00 |
February | 0.135590E+10 | 0.428208E+10 | 0.261930E+10 | 0.122192E+10 | 0.139739E+10 | 0.00 | 0.00 |
March | 0.256910E+10 | 0.339401E+10 | 0.369937E+10 | 0.157335E+10 | 0.212602E+10 | 0.00 | 0.00 |
April | 0.356816E+10 | 0.227979E+10 | 0.429654E+10 | 0.188214E+10 | 0.241440E+10 | 0.00 | 0.00 |
May | 0.525447E+10 | 0.144049E+10 | 0.538371E+10 | 0.215135E+10 | 0.323236E+10 | 0.00 | 0.00 |
June | 0.529944E+10 | 0.695533E+09 | 0.482858E+10 | 0.174760E+10 | 0.308098E+10 | 0.00 | 0.00 |
July | 0.604807E+10 | 0.317559E+09 | 0.501140E+10 | 0.180819E+10 | 0.320321E+10 | 0.00 | 0.00 |
August | 0.681231E+10 | 0.448101E+09 | 0.564338E+10 | 0.254454E+10 | 0.309884E+10 | 0.00 | 0.00 |
September | 0.426618E+10 | 0.107147E+10 | 0.407351E+10 | 0.182781E+10 | 0.224570E+10 | 0.00 | 0.00 |
October | 0.340741E+10 | 0.214812E+10 | 0.381584E+10 | 0.172953E+10 | 0.208631E+10 | 0.00 | 0.00 |
November | 0.130553E+10 | 0.332127E+10 | 0.228377E+10 | 0.877089E+09 | 0.140668E+10 | 0.00 | 0.00 |
December | 0.830126E+09 | 0.447481E+10 | 0.183864E+10 | 0.863462E+09 | 0.975181E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.414899E+11 | 0.286510E+11 | 0.453642E+11 | 0.189769E+11 | 0.263873E+11 | 0.00 | 0.00 |
Minimum of Months | 0.773233E+09 | 0.317559E+09 | 0.183864E+10 | 0.749900E+09 | 0.975181E+09 | 0.00 | 0.00 |
Maximum of Months | 0.681231E+10 | 0.477781E+10 | 0.564338E+10 | 0.254454E+10 | 0.323236E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.608644E+10 | 0.665343E+10 | 0.694655E+10 | 0.454870E+10 | 0.239785E+10 | 0.00 | 0.00 |
February | 0.714770E+10 | 0.612797E+10 | 0.827893E+10 | 0.548116E+10 | 0.279777E+10 | 0.00 | 0.00 |
March | 0.683904E+10 | 0.514564E+10 | 0.826870E+10 | 0.459050E+10 | 0.367820E+10 | 0.00 | 0.00 |
April | 0.441671E+10 | 0.368817E+10 | 0.620626E+10 | 0.245359E+10 | 0.375267E+10 | 0.00 | 0.00 |
May | 0.419094E+10 | 0.231928E+10 | 0.562013E+10 | 0.117158E+10 | 0.444855E+10 | 0.00 | 0.00 |
June | 0.471837E+10 | 0.117554E+10 | 0.510384E+10 | 0.779213E+09 | 0.432463E+10 | 0.00 | 0.00 |
July | 0.583027E+10 | 0.604260E+09 | 0.552844E+10 | 0.959489E+09 | 0.456895E+10 | 0.00 | 0.00 |
August | 0.759331E+10 | 0.859792E+09 | 0.738278E+10 | 0.273769E+10 | 0.464509E+10 | 0.00 | 0.00 |
September | 0.794198E+10 | 0.176659E+10 | 0.775426E+10 | 0.401132E+10 | 0.374294E+10 | 0.00 | 0.00 |
October | 0.114599E+11 | 0.338623E+10 | 0.109805E+11 | 0.688748E+10 | 0.409300E+10 | 0.00 | 0.00 |
November | 0.686640E+10 | 0.488671E+10 | 0.736584E+10 | 0.442391E+10 | 0.294193E+10 | 0.00 | 0.00 |
December | 0.699096E+10 | 0.629130E+10 | 0.752786E+10 | 0.534399E+10 | 0.218387E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.800820E+11 | 0.429049E+11 | 0.869641E+11 | 0.433886E+11 | 0.435755E+11 | 0.00 | 0.00 |
Minimum of Months | 0.419094E+10 | 0.604260E+09 | 0.510384E+10 | 0.779213E+09 | 0.218387E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114599E+11 | 0.665343E+10 | 0.109805E+11 | 0.688748E+10 | 0.464509E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.789351E+09 | 0.510500E+10 | 0.184627E+10 | 0.756352E+09 | 0.108992E+10 | 0.00 | 0.00 |
February | 0.121931E+10 | 0.477714E+10 | 0.245886E+10 | 0.107994E+10 | 0.137892E+10 | 0.00 | 0.00 |
March | 0.283635E+10 | 0.380713E+10 | 0.402010E+10 | 0.185612E+10 | 0.216398E+10 | 0.00 | 0.00 |
April | 0.344047E+10 | 0.278662E+10 | 0.425188E+10 | 0.181935E+10 | 0.243253E+10 | 0.00 | 0.00 |
May | 0.491832E+10 | 0.164281E+10 | 0.511742E+10 | 0.194307E+10 | 0.317435E+10 | 0.00 | 0.00 |
June | 0.593029E+10 | 0.907183E+09 | 0.542014E+10 | 0.218573E+10 | 0.323441E+10 | 0.00 | 0.00 |
July | 0.616817E+10 | 0.536468E+09 | 0.524560E+10 | 0.197505E+10 | 0.327055E+10 | 0.00 | 0.00 |
August | 0.684782E+10 | 0.738977E+09 | 0.580348E+10 | 0.268659E+10 | 0.311689E+10 | 0.00 | 0.00 |
September | 0.417370E+10 | 0.127055E+10 | 0.398742E+10 | 0.174264E+10 | 0.224478E+10 | 0.00 | 0.00 |
October | 0.370431E+10 | 0.248668E+10 | 0.408475E+10 | 0.198633E+10 | 0.209843E+10 | 0.00 | 0.00 |
November | 0.801244E+09 | 0.388341E+10 | 0.185633E+10 | 0.536513E+09 | 0.131982E+10 | 0.00 | 0.00 |
December | 0.687626E+09 | 0.525250E+10 | 0.170640E+10 | 0.738484E+09 | 0.967911E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.415170E+11 | 0.331945E+11 | 0.457987E+11 | 0.193062E+11 | 0.264925E+11 | 0.00 | 0.00 |
Minimum of Months | 0.687626E+09 | 0.536468E+09 | 0.170640E+10 | 0.536513E+09 | 0.967911E+09 | 0.00 | 0.00 |
Maximum of Months | 0.684782E+10 | 0.525250E+10 | 0.580348E+10 | 0.268659E+10 | 0.327055E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 32690698.17 | 0.698532E+10 | 0.134280E+10 | 0.00 | 0.134280E+10 | 0.00 | 0.00 |
February | 81902515.14 | 0.660078E+10 | 0.165973E+10 | 0.00 | 0.165973E+10 | 0.00 | 0.00 |
March | 0.612508E+09 | 0.491897E+10 | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.00 | 0.00 |
April | 0.140877E+10 | 0.337436E+10 | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.00 | 0.00 |
May | 0.293420E+10 | 0.208919E+10 | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.00 | 0.00 |
June | 0.406583E+10 | 0.105787E+10 | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.00 | 0.00 |
July | 0.481640E+10 | 0.587530E+09 | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.00 | 0.00 |
August | 0.430596E+10 | 0.818034E+09 | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.00 | 0.00 |
September | 0.237472E+10 | 0.162143E+10 | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.00 | 0.00 |
October | 0.138537E+10 | 0.315613E+10 | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.00 | 0.00 |
November | 0.291365E+09 | 0.485700E+10 | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.00 | 0.00 |
December | 19976154.40 | 0.662636E+10 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.223297E+11 | 0.426930E+11 | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.00 | 0.00 |
Minimum of Months | 19976154.40 | 0.587530E+09 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Maximum of Months | 0.481640E+10 | 0.698532E+10 | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.828284E+09 | 0.429635E+10 | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.00 | 0.00 |
February | 0.141625E+10 | 0.392914E+10 | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.00 | 0.00 |
March | 0.262651E+10 | 0.311051E+10 | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.00 | 0.00 |
April | 0.360670E+10 | 0.212046E+10 | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.00 | 0.00 |
May | 0.526967E+10 | 0.135711E+10 | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.00 | 0.00 |
June | 0.529492E+10 | 0.680905E+09 | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.00 | 0.00 |
July | 0.601581E+10 | 0.363122E+09 | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.00 | 0.00 |
August | 0.676933E+10 | 0.511531E+09 | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.00 | 0.00 |
September | 0.428854E+10 | 0.994750E+09 | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.00 | 0.00 |
October | 0.345663E+10 | 0.197915E+10 | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.00 | 0.00 |
November | 0.138047E+10 | 0.296891E+10 | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.00 | 0.00 |
December | 0.881766E+09 | 0.402081E+10 | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.418349E+11 | 0.263328E+11 | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.828284E+09 | 0.363122E+09 | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.00 | 0.00 |
Maximum of Months | 0.676933E+10 | 0.429635E+10 | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.611760E+10 | 0.628120E+10 | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.00 | 0.00 |
February | 0.714721E+10 | 0.588808E+10 | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.00 | 0.00 |
March | 0.684604E+10 | 0.487906E+10 | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.00 | 0.00 |
April | 0.447203E+10 | 0.346927E+10 | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.00 | 0.00 |
May | 0.422476E+10 | 0.223143E+10 | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.00 | 0.00 |
June | 0.474948E+10 | 0.113455E+10 | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.00 | 0.00 |
July | 0.586367E+10 | 0.610249E+09 | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.00 | 0.00 |
August | 0.762061E+10 | 0.882750E+09 | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.00 | 0.00 |
September | 0.792625E+10 | 0.171531E+10 | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.00 | 0.00 |
October | 0.114053E+11 | 0.329750E+10 | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.00 | 0.00 |
November | 0.688393E+10 | 0.461161E+10 | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.00 | 0.00 |
December | 0.701460E+10 | 0.591508E+10 | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.802715E+11 | 0.409161E+11 | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.422476E+10 | 0.610249E+09 | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114053E+11 | 0.628120E+10 | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.843605E+09 | 0.448646E+10 | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.00 | 0.00 |
February | 0.129717E+10 | 0.418824E+10 | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.00 | 0.00 |
March | 0.298254E+10 | 0.319702E+10 | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.00 | 0.00 |
April | 0.361844E+10 | 0.228454E+10 | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.00 | 0.00 |
May | 0.501334E+10 | 0.148050E+10 | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.00 | 0.00 |
June | 0.601760E+10 | 0.795602E+09 | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.00 | 0.00 |
July | 0.627964E+10 | 0.456348E+09 | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.00 | 0.00 |
August | 0.696324E+10 | 0.649544E+09 | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.00 | 0.00 |
September | 0.426025E+10 | 0.110917E+10 | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.00 | 0.00 |
October | 0.383753E+10 | 0.213811E+10 | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.00 | 0.00 |
November | 0.929135E+09 | 0.314392E+10 | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.00 | 0.00 |
December | 0.782817E+09 | 0.425115E+10 | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.428253E+11 | 0.281806E+11 | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.782817E+09 | 0.456348E+09 | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.00 | 0.00 |
Maximum of Months | 0.696324E+10 | 0.448646E+10 | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 46239301.06 | 0.662165E+10 | 0.134280E+10 | 0.00 | 0.134280E+10 | 0.00 | 0.00 |
February | 0.106862E+09 | 0.621944E+10 | 0.165973E+10 | 0.00 | 0.165973E+10 | 0.00 | 0.00 |
March | 0.677604E+09 | 0.456077E+10 | 0.254824E+10 | 0.00 | 0.254824E+10 | 0.00 | 0.00 |
April | 0.148018E+10 | 0.313244E+10 | 0.296191E+10 | 8293366.68 | 0.295362E+10 | 0.00 | 0.00 |
May | 0.296880E+10 | 0.199477E+10 | 0.406025E+10 | 0.134873E+09 | 0.392538E+10 | 0.00 | 0.00 |
June | 0.403887E+10 | 0.104430E+10 | 0.416687E+10 | 0.223416E+09 | 0.394346E+10 | 0.00 | 0.00 |
July | 0.476557E+10 | 0.600114E+09 | 0.416118E+10 | 0.150057E+09 | 0.401113E+10 | 0.00 | 0.00 |
August | 0.427006E+10 | 0.817268E+09 | 0.368669E+10 | 43564960.21 | 0.364312E+10 | 0.00 | 0.00 |
September | 0.239286E+10 | 0.153970E+10 | 0.268971E+10 | 484711.86 | 0.268922E+10 | 0.00 | 0.00 |
October | 0.146788E+10 | 0.290786E+10 | 0.240536E+10 | 0.00 | 0.240536E+10 | 0.00 | 0.00 |
November | 0.359951E+09 | 0.440165E+10 | 0.163271E+10 | 0.00 | 0.163271E+10 | 0.00 | 0.00 |
December | 39697438.30 | 0.609080E+10 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.226146E+11 | 0.399308E+11 | 0.324867E+11 | 0.560689E+09 | 0.319260E+11 | 0.00 | 0.00 |
Minimum of Months | 39697438.30 | 0.600114E+09 | 0.117128E+10 | 0.00 | 0.117128E+10 | 0.00 | 0.00 |
Maximum of Months | 0.476557E+10 | 0.662165E+10 | 0.416687E+10 | 0.223416E+09 | 0.401113E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.852217E+09 | 0.408495E+10 | 0.187015E+10 | 0.749897E+09 | 0.112026E+10 | 0.00 | 0.00 |
February | 0.145932E+10 | 0.371202E+10 | 0.261929E+10 | 0.122191E+10 | 0.139738E+10 | 0.00 | 0.00 |
March | 0.267724E+10 | 0.291485E+10 | 0.369935E+10 | 0.157334E+10 | 0.212601E+10 | 0.00 | 0.00 |
April | 0.364646E+10 | 0.200410E+10 | 0.429652E+10 | 0.188213E+10 | 0.241439E+10 | 0.00 | 0.00 |
May | 0.527415E+10 | 0.131530E+10 | 0.538369E+10 | 0.215134E+10 | 0.323235E+10 | 0.00 | 0.00 |
June | 0.526646E+10 | 0.680648E+09 | 0.482856E+10 | 0.174759E+10 | 0.308096E+10 | 0.00 | 0.00 |
July | 0.597524E+10 | 0.375980E+09 | 0.501138E+10 | 0.180818E+10 | 0.320320E+10 | 0.00 | 0.00 |
August | 0.673627E+10 | 0.518637E+09 | 0.564335E+10 | 0.254452E+10 | 0.309883E+10 | 0.00 | 0.00 |
September | 0.428887E+10 | 0.961277E+09 | 0.407349E+10 | 0.182780E+10 | 0.224569E+10 | 0.00 | 0.00 |
October | 0.350183E+10 | 0.185792E+10 | 0.381583E+10 | 0.172953E+10 | 0.208630E+10 | 0.00 | 0.00 |
November | 0.144444E+10 | 0.273090E+10 | 0.228376E+10 | 0.877085E+09 | 0.140667E+10 | 0.00 | 0.00 |
December | 0.923180E+09 | 0.371813E+10 | 0.183864E+10 | 0.863458E+09 | 0.975177E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.420457E+11 | 0.248747E+11 | 0.453640E+11 | 0.189768E+11 | 0.263872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.852217E+09 | 0.375980E+09 | 0.183864E+10 | 0.749897E+09 | 0.975177E+09 | 0.00 | 0.00 |
Maximum of Months | 0.673627E+10 | 0.408495E+10 | 0.564335E+10 | 0.254452E+10 | 0.323235E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.618018E+10 | 0.592481E+10 | 0.694676E+10 | 0.454885E+10 | 0.239792E+10 | 0.00 | 0.00 |
February | 0.724206E+10 | 0.550585E+10 | 0.827918E+10 | 0.548134E+10 | 0.279784E+10 | 0.00 | 0.00 |
March | 0.692092E+10 | 0.453206E+10 | 0.826894E+10 | 0.459065E+10 | 0.367829E+10 | 0.00 | 0.00 |
April | 0.454528E+10 | 0.324254E+10 | 0.620642E+10 | 0.245367E+10 | 0.375276E+10 | 0.00 | 0.00 |
May | 0.426091E+10 | 0.213411E+10 | 0.562026E+10 | 0.117162E+10 | 0.444864E+10 | 0.00 | 0.00 |
June | 0.472966E+10 | 0.111992E+10 | 0.510396E+10 | 0.779238E+09 | 0.432472E+10 | 0.00 | 0.00 |
July | 0.582344E+10 | 0.621445E+09 | 0.552856E+10 | 0.959520E+09 | 0.456904E+10 | 0.00 | 0.00 |
August | 0.759543E+10 | 0.880370E+09 | 0.738297E+10 | 0.273778E+10 | 0.464519E+10 | 0.00 | 0.00 |
September | 0.794423E+10 | 0.163923E+10 | 0.775448E+10 | 0.401145E+10 | 0.374303E+10 | 0.00 | 0.00 |
October | 0.114732E+11 | 0.308411E+10 | 0.109808E+11 | 0.688770E+10 | 0.409310E+10 | 0.00 | 0.00 |
November | 0.700012E+10 | 0.421036E+10 | 0.736606E+10 | 0.442405E+10 | 0.294201E+10 | 0.00 | 0.00 |
December | 0.712770E+10 | 0.543109E+10 | 0.752809E+10 | 0.534416E+10 | 0.218393E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.808431E+11 | 0.383259E+11 | 0.869665E+11 | 0.433900E+11 | 0.435765E+11 | 0.00 | 0.00 |
Minimum of Months | 0.426091E+10 | 0.621445E+09 | 0.510396E+10 | 0.779238E+09 | 0.218393E+10 | 0.00 | 0.00 |
Maximum of Months | 0.114732E+11 | 0.592481E+10 | 0.109808E+11 | 0.688770E+10 | 0.464519E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.858716E+09 | 0.427924E+10 | 0.184626E+10 | 0.756349E+09 | 0.108991E+10 | 0.00 | 0.00 |
February | 0.131575E+10 | 0.398815E+10 | 0.245885E+10 | 0.107994E+10 | 0.137891E+10 | 0.00 | 0.00 |
March | 0.301333E+10 | 0.301624E+10 | 0.402009E+10 | 0.185612E+10 | 0.216397E+10 | 0.00 | 0.00 |
April | 0.364833E+10 | 0.216045E+10 | 0.425187E+10 | 0.181934E+10 | 0.243252E+10 | 0.00 | 0.00 |
May | 0.502581E+10 | 0.142495E+10 | 0.511740E+10 | 0.194306E+10 | 0.317434E+10 | 0.00 | 0.00 |
June | 0.600321E+10 | 0.781793E+09 | 0.542012E+10 | 0.218573E+10 | 0.323439E+10 | 0.00 | 0.00 |
July | 0.625415E+10 | 0.457294E+09 | 0.524558E+10 | 0.197504E+10 | 0.327054E+10 | 0.00 | 0.00 |
August | 0.694690E+10 | 0.641899E+09 | 0.580346E+10 | 0.268658E+10 | 0.311688E+10 | 0.00 | 0.00 |
September | 0.426994E+10 | 0.106385E+10 | 0.398741E+10 | 0.174264E+10 | 0.224477E+10 | 0.00 | 0.00 |
October | 0.387139E+10 | 0.201323E+10 | 0.408474E+10 | 0.198632E+10 | 0.209842E+10 | 0.00 | 0.00 |
November | 0.969917E+09 | 0.292002E+10 | 0.185632E+10 | 0.536511E+09 | 0.131981E+10 | 0.00 | 0.00 |
December | 0.806282E+09 | 0.398062E+10 | 0.170639E+10 | 0.738481E+09 | 0.967907E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.429837E+11 | 0.267277E+11 | 0.457985E+11 | 0.193061E+11 | 0.264924E+11 | 0.00 | 0.00 |
Minimum of Months | 0.806282E+09 | 0.457294E+09 | 0.170639E+10 | 0.536511E+09 | 0.967907E+09 | 0.00 | 0.00 |
Maximum of Months | 0.694690E+10 | 0.427924E+10 | 0.580346E+10 | 0.268658E+10 | 0.327054E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.296419E+11 | -.390897E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121083E+10 | 64.98 | 0.00 | 0.00 |
February | 0.273518E+11 | -.358671E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.108303E+10 | 64.65 | 0.00 | 0.00 |
March | 0.318669E+11 | -.412313E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.118164E+10 | 64.07 | 0.00 | 0.00 |
April | 0.262207E+11 | -.354933E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.116570E+10 | 64.95 | 0.00 | 0.00 |
May | 0.256492E+11 | -.352847E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122240E+10 | 65.52 | 0.00 | 0.00 |
June | 0.230347E+11 | -.324557E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.117857E+10 | 65.37 | 0.00 | 0.00 |
July | 0.193498E+11 | -.292650E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.125689E+10 | 66.84 | 0.00 | 0.00 |
August | 0.217306E+11 | -.315656E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122280E+10 | 65.58 | 0.00 | 0.00 |
September | 0.200051E+11 | -.295533E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.120079E+10 | 66.26 | 0.00 | 0.00 |
October | 0.227320E+11 | -.324926E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124059E+10 | 66.30 | 0.00 | 0.00 |
November | 0.250543E+11 | -.343618E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.118654E+10 | 65.78 | 0.00 | 0.00 |
December | 0.269592E+11 | -.365451E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120741E+10 | 65.12 | 0.00 | 0.00 |
Annual Sum or Average | 0.299596E+12 | -.413205E+12 | 8760.00 | -.143572E+11 | 65.46 | |||||
Minimum of Months | 0.193498E+11 | -.412313E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.125689E+10 | 64.07 | 0.00 | 0.00 |
Maximum of Months | 0.318669E+11 | -.292650E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.108303E+10 | 66.84 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.74 | 0.73 | 01-JAN-07:49 | 5987.28 | 33.14 | 169.17 | 232.33 | 3121.88 | 33.44 | 187.33 | 190.33 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 8855.59 | 36.42 | 203.17 | 253.33 | 1841.21 | 27.35 | 186.83 | 229.83 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-06:00 | 3165.20 | 22.93 | 90.50 | 313.67 | 1337.17 | 21.46 | 162.00 | 270.00 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 1800.40 | 17.78 | 0.00 | 333.17 | 1040.12 | 20.77 | 129.50 | 286.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1586.61 | 17.66 | 0.00 | 385.00 | 875.35 | 20.59 | 196.17 | 333.67 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:19 | 1510.43 | 17.59 | 0.00 | 375.50 | 847.58 | 20.60 | 168.83 | 328.67 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:19 | 1670.23 | 17.90 | 0.00 | 383.00 | 915.07 | 20.89 | 209.33 | 332.67 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:49 | 1837.24 | 17.89 | 0.00 | 364.00 | 1043.57 | 20.85 | 209.17 | 329.17 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 3478.15 | 20.28 | 29.50 | 318.00 | 1232.22 | 21.15 | 161.50 | 280.00 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 9696.37 | 35.30 | 278.50 | 301.67 | 1730.06 | 23.21 | 249.50 | 282.33 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:49 | 6035.31 | 34.11 | 217.50 | 252.83 | 2001.08 | 28.78 | 218.50 | 227.83 |
December | 211.17 | 0.74 | 0.73 | 01-DEC-07:40 | 5596.09 | 33.93 | 179.17 | 234.33 | 5125.00 | 37.91 | 198.00 | 205.50 |
Annual Sum or Average | 3472.67 | 0.74 | 3882.99 | 24.08 | 1167.50 | 3746.83 | 1574.66 | 23.79 | 2276.67 | 3296.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1510.43 | 17.59 | 0.00 | 232.33 | 847.58 | 20.59 | 129.50 | 190.33 | |
Maximum of Months | 389.17 | 0.74 | 0.73 | 9696.37 | 36.42 | 278.50 | 385.00 | 5125.00 | 37.91 | 249.50 | 333.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:49 | 1789.16 | 19.51 | 60.33 | 211.67 | 949.71 | 18.89 | 40.00 | 146.67 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 2418.80 | 19.69 | 61.33 | 237.00 | 1484.15 | 21.01 | 58.50 | 192.17 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-06:49 | 2550.49 | 17.59 | 57.00 | 306.83 | 1463.49 | 17.49 | 38.50 | 239.83 |
April | 261.17 | 0.74 | 0.73 | 01-APR-05:00 | 3550.20 | 16.12 | 38.83 | 333.00 | 1314.24 | 14.87 | 0.00 | 286.50 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 2793.15 | 13.70 | 0.00 | 390.50 | 1537.93 | 14.92 | 0.00 | 340.00 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 2567.29 | 13.68 | 0.00 | 379.67 | 1400.30 | 14.96 | 0.00 | 341.83 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:49 | 2573.98 | 14.09 | 1.83 | 388.83 | 1405.76 | 15.26 | 0.00 | 346.17 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 3542.18 | 16.32 | 57.67 | 365.33 | 1428.13 | 15.11 | 0.00 | 336.33 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-05:49 | 2928.87 | 17.87 | 61.33 | 313.17 | 1284.31 | 15.54 | 5.50 | 271.00 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2639.94 | 19.22 | 74.17 | 285.67 | 1422.72 | 19.08 | 50.17 | 251.67 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:49 | 1674.30 | 18.18 | 52.00 | 236.33 | 921.02 | 19.20 | 46.17 | 185.33 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-07:40 | 1653.13 | 19.24 | 64.17 | 206.67 | 995.77 | 20.64 | 59.17 | 138.83 |
Annual Sum or Average | 3472.67 | 0.74 | 2638.68 | 16.71 | 528.67 | 3654.67 | 1331.20 | 16.85 | 298.00 | 3076.33 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1653.13 | 13.68 | 0.00 | 206.67 | 921.02 | 14.87 | 0.00 | 138.83 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 3550.20 | 19.69 | 74.17 | 390.50 | 1537.93 | 21.01 | 59.17 | 346.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.76 | 0.73 | 01-JAN-08:20 | 551.15 | 0.00 | 0.00 | 193.50 | 336.99 | 0.00 | 0.00 | 94.50 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:20 | 593.21 | 0.00 | 0.00 | 218.17 | 386.87 | 0.00 | 0.00 | 140.17 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-07:10 | 792.89 | 0.00 | 0.00 | 302.33 | 494.09 | 0.00 | 0.00 | 215.00 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:10 | 892.41 | 0.00 | 0.00 | 337.83 | 558.02 | 0.00 | 0.00 | 276.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1161.78 | 0.00 | 0.00 | 398.17 | 662.73 | 0.00 | 0.00 | 349.00 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 1303.94 | 0.00 | 0.00 | 395.17 | 717.74 | 0.00 | 0.00 | 358.33 |
July | 365.17 | 0.73 | 0.73 | 01-JUL-04:00 | 1290.57 | 0.00 | 0.00 | 401.17 | 716.24 | 0.00 | 0.00 | 356.83 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 1054.90 | 0.00 | 0.00 | 374.83 | 634.65 | 0.00 | 0.00 | 340.17 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-05:00 | 816.57 | 0.00 | 0.00 | 312.33 | 516.41 | 0.00 | 0.00 | 251.00 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 735.18 | 0.00 | 0.00 | 282.00 | 477.72 | 0.00 | 0.00 | 225.17 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-07:10 | 617.40 | 0.00 | 0.00 | 224.17 | 368.70 | 0.00 | 0.00 | 129.17 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-08:09 | 441.96 | 0.00 | 0.00 | 175.33 | 279.93 | 0.00 | 0.00 | 62.33 |
Annual Sum or Average | 3472.67 | 0.74 | 910.41 | 0.00 | 0.00 | 3615.00 | 541.72 | 0.00 | 0.00 | 2798.50 | ||
Minimum of Months | 199.50 | 0.73 | 0.73 | 441.96 | 0.00 | 0.00 | 175.33 | 279.93 | 0.00 | 0.00 | 62.33 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 1303.94 | 0.00 | 0.00 | 401.17 | 717.74 | 0.00 | 0.00 | 358.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-08:20 | 1713.14 | 19.38 | 57.50 | 216.33 | 1000.26 | 20.69 | 52.33 | 148.17 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-08:30 | 1982.86 | 19.16 | 56.50 | 235.83 | 1009.14 | 18.68 | 36.17 | 188.67 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-07:10 | 2749.17 | 18.67 | 69.83 | 310.33 | 1616.50 | 18.40 | 47.67 | 250.50 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:40 | 3338.73 | 15.90 | 36.00 | 331.67 | 1280.28 | 14.82 | 0.00 | 288.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:49 | 3081.59 | 13.76 | 0.00 | 388.67 | 1336.62 | 15.10 | 1.83 | 342.50 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:30 | 2900.75 | 13.86 | 0.00 | 384.83 | 1586.51 | 17.24 | 43.00 | 334.67 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 2728.89 | 14.20 | 3.50 | 388.50 | 1473.70 | 15.30 | 0.00 | 342.00 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:00 | 3610.47 | 16.17 | 54.33 | 365.33 | 1535.94 | 15.11 | 0.00 | 335.67 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:19 | 2783.43 | 16.67 | 45.67 | 314.17 | 1500.95 | 15.66 | 5.50 | 272.83 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2958.27 | 19.95 | 83.50 | 297.00 | 1263.85 | 19.56 | 53.17 | 264.33 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-07:19 | 1498.45 | 19.24 | 68.50 | 239.33 | 777.00 | 18.71 | 43.50 | 184.00 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-08:20 | 1410.13 | 19.47 | 67.33 | 208.67 | 751.50 | 18.61 | 43.67 | 142.17 |
Annual Sum or Average | 3472.67 | 0.74 | 2684.73 | 16.81 | 542.67 | 3680.67 | 1309.63 | 17.03 | 326.83 | 3093.50 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1410.13 | 13.76 | 0.00 | 208.67 | 751.50 | 14.82 | 0.00 | 142.17 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 3610.47 | 19.95 | 83.50 | 388.67 | 1616.50 | 20.69 | 53.17 | 342.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.74 | 0.73 | 01-JAN-07:49 | 5937.34 | 32.01 | 169.00 | 230.33 | 3166.32 | 31.57 | 144.00 | 190.50 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 8818.12 | 35.85 | 202.83 | 252.83 | 1897.34 | 23.51 | 80.00 | 231.00 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-06:00 | 3178.68 | 18.40 | 89.83 | 315.33 | 1386.91 | 17.17 | 4.33 | 273.50 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 1777.44 | 11.91 | 0.00 | 331.00 | 1078.00 | 16.82 | 0.00 | 288.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1556.39 | 11.99 | 0.00 | 383.83 | 902.32 | 16.72 | 0.00 | 335.67 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:19 | 1481.97 | 11.95 | 0.00 | 373.17 | 873.31 | 16.76 | 0.00 | 331.33 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 1636.06 | 12.14 | 0.00 | 380.50 | 942.08 | 16.94 | 0.00 | 335.00 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:49 | 1808.52 | 12.28 | 0.00 | 363.67 | 1078.75 | 17.06 | 0.00 | 331.00 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 3450.91 | 14.83 | 29.50 | 315.50 | 1278.64 | 16.94 | 0.00 | 281.67 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 9650.57 | 34.59 | 278.50 | 301.00 | 1868.22 | 18.96 | 19.33 | 284.17 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:00 | 5957.61 | 32.90 | 213.50 | 251.50 | 2468.02 | 27.74 | 136.83 | 229.50 |
December | 211.17 | 0.74 | 0.73 | 01-DEC-07:40 | 5347.14 | 29.66 | 155.00 | 232.17 | 5165.20 | 37.11 | 195.83 | 205.50 |
Annual Sum or Average | 3472.67 | 0.74 | 3837.41 | 19.92 | 1138.17 | 3730.83 | 1650.57 | 20.32 | 580.33 | 3317.67 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1481.97 | 11.91 | 0.00 | 230.33 | 873.31 | 16.72 | 0.00 | 190.50 | |
Maximum of Months | 389.17 | 0.74 | 0.73 | 9650.57 | 35.85 | 278.50 | 383.83 | 5165.20 | 37.11 | 195.83 | 335.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:49 | 1782.47 | 17.55 | 60.50 | 211.00 | 970.48 | 16.80 | 40.00 | 149.17 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 2414.03 | 17.50 | 61.33 | 236.17 | 1511.60 | 19.18 | 58.50 | 195.17 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-06:49 | 2554.13 | 15.27 | 57.00 | 306.00 | 1495.96 | 15.42 | 38.50 | 243.67 |
April | 261.17 | 0.74 | 0.73 | 01-APR-05:00 | 3554.47 | 13.27 | 38.83 | 332.67 | 1352.72 | 12.28 | 0.00 | 290.17 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 2764.86 | 10.30 | 0.00 | 389.83 | 1573.86 | 12.55 | 0.00 | 342.33 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 2450.65 | 10.29 | 0.00 | 379.33 | 1436.11 | 12.62 | 0.00 | 343.50 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:49 | 2553.70 | 10.68 | 1.83 | 387.83 | 1442.29 | 12.86 | 0.00 | 348.17 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 3534.91 | 13.59 | 57.67 | 364.67 | 1465.76 | 12.64 | 0.00 | 338.33 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-05:49 | 2935.25 | 15.39 | 61.33 | 312.83 | 1321.07 | 12.97 | 5.50 | 274.17 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2632.22 | 16.97 | 74.17 | 285.00 | 1455.40 | 16.92 | 50.33 | 254.50 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:49 | 1666.48 | 15.69 | 52.00 | 235.67 | 943.52 | 17.00 | 46.33 | 190.17 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-07:40 | 1650.86 | 17.23 | 64.17 | 205.83 | 1014.66 | 18.82 | 59.50 | 142.17 |
Annual Sum or Average | 3472.67 | 0.74 | 2619.97 | 13.99 | 528.83 | 3646.83 | 1363.71 | 14.57 | 298.67 | 3111.50 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1650.86 | 10.29 | 0.00 | 205.83 | 943.52 | 12.28 | 0.00 | 142.17 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 3554.47 | 17.55 | 74.17 | 389.83 | 1573.86 | 19.18 | 59.50 | 348.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.76 | 0.73 | 01-JAN-08:20 | 538.35 | 0.00 | 0.00 | 188.67 | 345.32 | 0.00 | 0.00 | 99.83 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:20 | 581.50 | 0.00 | 0.00 | 216.17 | 397.14 | 0.00 | 0.00 | 145.17 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-07:10 | 778.72 | 0.00 | 0.00 | 300.83 | 508.26 | 0.00 | 0.00 | 219.00 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 878.82 | 0.00 | 0.00 | 335.83 | 574.83 | 0.00 | 0.00 | 281.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1141.39 | 0.00 | 0.00 | 397.17 | 682.53 | 0.00 | 0.00 | 353.00 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 1283.80 | 0.00 | 0.00 | 393.83 | 747.53 | 0.00 | 0.00 | 364.00 |
July | 365.17 | 0.73 | 0.73 | 01-JUL-04:00 | 1269.08 | 0.00 | 0.00 | 399.50 | 736.99 | 0.00 | 0.00 | 359.00 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 1038.12 | 0.00 | 0.00 | 373.83 | 653.25 | 0.00 | 0.00 | 342.33 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 803.14 | 0.00 | 0.00 | 309.83 | 531.51 | 0.00 | 0.00 | 254.50 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 720.28 | 0.00 | 0.00 | 280.33 | 490.17 | 0.00 | 0.00 | 229.50 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-07:10 | 603.51 | 0.00 | 0.00 | 221.50 | 378.05 | 0.00 | 0.00 | 134.17 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-08:20 | 431.44 | 0.00 | 0.00 | 171.50 | 286.61 | 0.00 | 0.00 | 67.00 |
Annual Sum or Average | 3472.67 | 0.74 | 894.42 | 0.00 | 0.00 | 3589.00 | 558.02 | 0.00 | 0.00 | 2848.50 | ||
Minimum of Months | 199.50 | 0.73 | 0.73 | 431.44 | 0.00 | 0.00 | 171.50 | 286.61 | 0.00 | 0.00 | 67.00 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 1283.80 | 0.00 | 0.00 | 399.50 | 747.53 | 0.00 | 0.00 | 364.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-08:20 | 1693.85 | 17.20 | 56.50 | 215.00 | 1020.41 | 18.79 | 52.50 | 151.33 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-08:30 | 1738.28 | 14.47 | 37.00 | 234.67 | 1036.79 | 16.47 | 36.50 | 191.50 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-07:19 | 2746.73 | 16.34 | 68.83 | 309.50 | 1650.52 | 16.32 | 47.83 | 255.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:40 | 3106.66 | 13.03 | 36.00 | 331.00 | 1317.81 | 12.27 | 0.00 | 290.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:49 | 3062.36 | 10.34 | 0.00 | 388.50 | 1371.85 | 12.71 | 1.83 | 345.33 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:30 | 2876.07 | 10.35 | 0.00 | 384.17 | 1627.13 | 15.25 | 43.33 | 339.33 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 2706.57 | 10.76 | 3.50 | 388.17 | 1511.40 | 12.88 | 0.00 | 344.83 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:00 | 3604.34 | 13.39 | 54.33 | 365.00 | 1574.44 | 12.63 | 0.00 | 337.67 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:19 | 2787.39 | 13.93 | 45.67 | 313.00 | 1535.73 | 13.10 | 5.50 | 274.33 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2954.43 | 17.73 | 83.50 | 296.67 | 1296.82 | 17.37 | 53.17 | 267.00 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-07:19 | 1475.35 | 16.75 | 65.00 | 238.67 | 795.97 | 16.48 | 43.67 | 187.17 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-08:20 | 1219.87 | 14.79 | 45.67 | 207.00 | 769.76 | 16.54 | 43.67 | 146.17 |
Annual Sum or Average | 3472.67 | 0.74 | 2629.98 | 13.72 | 496.00 | 3671.33 | 1342.38 | 14.75 | 328.00 | 3129.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1219.87 | 10.34 | 0.00 | 207.00 | 769.76 | 12.27 | 0.00 | 146.17 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 3604.34 | 17.73 | 83.50 | 388.50 | 1650.52 | 18.79 | 53.17 | 345.33 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.74 | 0.73 | 01-JAN-07:49 | 5935.82 | 32.00 | 169.00 | 230.33 | 3167.77 | 31.56 | 144.00 | 190.50 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 8817.12 | 35.84 | 202.83 | 252.83 | 1898.89 | 23.50 | 80.00 | 231.17 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-06:00 | 3179.23 | 18.37 | 89.83 | 315.33 | 1388.40 | 17.15 | 4.33 | 274.00 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 1778.18 | 11.87 | 0.00 | 331.17 | 1079.11 | 16.80 | 0.00 | 289.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1557.16 | 11.95 | 0.00 | 383.83 | 903.36 | 16.70 | 0.00 | 335.83 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:19 | 1482.62 | 11.91 | 0.00 | 373.17 | 874.26 | 16.75 | 0.00 | 331.67 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 1636.91 | 12.10 | 0.00 | 380.50 | 943.18 | 16.92 | 0.00 | 335.00 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:49 | 1809.31 | 12.24 | 0.00 | 363.67 | 1079.90 | 17.05 | 0.00 | 331.17 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 3451.66 | 14.80 | 29.50 | 315.50 | 1279.99 | 16.92 | 0.00 | 281.83 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 9650.16 | 34.57 | 278.50 | 301.00 | 1870.05 | 18.94 | 19.33 | 284.17 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:00 | 5956.27 | 32.88 | 213.50 | 251.33 | 2469.73 | 27.73 | 136.83 | 229.50 |
December | 211.17 | 0.74 | 0.73 | 01-DEC-07:40 | 5313.67 | 29.26 | 152.00 | 232.17 | 5166.32 | 37.11 | 195.83 | 205.50 |
Annual Sum or Average | 3472.67 | 0.74 | 3835.58 | 19.86 | 1135.17 | 3730.83 | 1651.86 | 20.31 | 580.33 | 3319.33 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1482.62 | 11.87 | 0.00 | 230.33 | 874.26 | 16.70 | 0.00 | 190.50 | |
Maximum of Months | 389.17 | 0.74 | 0.73 | 9650.16 | 35.84 | 278.50 | 383.83 | 5166.32 | 37.11 | 195.83 | 335.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:49 | 1781.98 | 17.54 | 60.50 | 211.00 | 971.09 | 16.80 | 40.00 | 149.17 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 2413.39 | 17.48 | 61.33 | 236.17 | 1512.20 | 19.17 | 58.50 | 195.17 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-06:49 | 2553.41 | 15.26 | 57.00 | 306.00 | 1496.79 | 15.42 | 38.50 | 243.67 |
April | 261.17 | 0.74 | 0.73 | 01-APR-05:00 | 3554.18 | 13.25 | 38.83 | 332.67 | 1353.63 | 12.27 | 0.00 | 290.67 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 2764.88 | 10.28 | 0.00 | 390.00 | 1574.98 | 12.54 | 0.00 | 342.33 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 2450.65 | 10.27 | 0.00 | 379.33 | 1437.14 | 12.61 | 0.00 | 343.83 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:49 | 2553.87 | 10.66 | 1.83 | 388.00 | 1443.45 | 12.86 | 0.00 | 348.17 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 3534.78 | 13.57 | 57.67 | 364.67 | 1466.81 | 12.63 | 0.00 | 338.33 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-05:49 | 2934.84 | 15.38 | 61.33 | 312.83 | 1321.93 | 12.96 | 5.50 | 274.17 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2631.44 | 16.96 | 74.17 | 285.00 | 1456.19 | 16.91 | 50.33 | 254.67 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:49 | 1666.08 | 15.68 | 52.00 | 235.67 | 941.27 | 16.82 | 45.00 | 190.17 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-07:40 | 1650.38 | 17.22 | 64.17 | 205.83 | 926.22 | 16.52 | 42.67 | 139.50 |
Annual Sum or Average | 3472.67 | 0.74 | 2619.67 | 13.97 | 528.83 | 3647.17 | 1358.99 | 14.41 | 280.50 | 3109.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1650.38 | 10.27 | 0.00 | 205.83 | 926.22 | 12.27 | 0.00 | 139.50 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 3554.18 | 17.54 | 74.17 | 390.00 | 1574.98 | 19.17 | 58.50 | 348.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.76 | 0.73 | 01-JAN-08:20 | 538.23 | 0.00 | 0.00 | 188.67 | 345.61 | 0.00 | 0.00 | 100.00 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:20 | 581.23 | 0.00 | 0.00 | 216.17 | 397.40 | 0.00 | 0.00 | 145.33 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-07:10 | 778.57 | 0.00 | 0.00 | 300.83 | 508.67 | 0.00 | 0.00 | 219.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 878.64 | 0.00 | 0.00 | 335.83 | 575.27 | 0.00 | 0.00 | 281.17 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1141.46 | 0.00 | 0.00 | 397.17 | 683.21 | 0.00 | 0.00 | 353.33 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 1283.83 | 0.00 | 0.00 | 394.17 | 748.23 | 0.00 | 0.00 | 364.00 |
July | 365.17 | 0.73 | 0.73 | 01-JUL-04:00 | 1269.16 | 0.00 | 0.00 | 399.50 | 737.71 | 0.00 | 0.00 | 359.00 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 1037.96 | 0.00 | 0.00 | 373.83 | 653.78 | 0.00 | 0.00 | 342.33 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 802.94 | 0.00 | 0.00 | 309.83 | 531.91 | 0.00 | 0.00 | 254.67 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 719.94 | 0.00 | 0.00 | 280.17 | 490.49 | 0.00 | 0.00 | 229.67 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-07:10 | 603.44 | 0.00 | 0.00 | 221.67 | 378.41 | 0.00 | 0.00 | 134.50 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-08:20 | 431.26 | 0.00 | 0.00 | 171.83 | 286.82 | 0.00 | 0.00 | 67.00 |
Annual Sum or Average | 3472.67 | 0.74 | 894.32 | 0.00 | 0.00 | 3589.67 | 558.49 | 0.00 | 0.00 | 2850.17 | ||
Minimum of Months | 199.50 | 0.73 | 0.73 | 431.26 | 0.00 | 0.00 | 171.83 | 286.82 | 0.00 | 0.00 | 67.00 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 1283.83 | 0.00 | 0.00 | 399.50 | 748.23 | 0.00 | 0.00 | 364.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-08:20 | 1693.39 | 17.19 | 56.50 | 215.17 | 936.54 | 16.58 | 36.83 | 149.83 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-08:30 | 1737.71 | 14.46 | 37.00 | 234.67 | 1037.41 | 16.46 | 36.50 | 191.67 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-07:19 | 2746.02 | 16.33 | 68.83 | 309.67 | 1651.37 | 16.31 | 47.83 | 255.33 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:40 | 3106.28 | 13.02 | 36.00 | 331.00 | 1318.74 | 12.26 | 0.00 | 290.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:49 | 3062.42 | 10.32 | 0.00 | 388.50 | 1372.95 | 12.70 | 1.83 | 345.50 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:30 | 2876.05 | 10.34 | 0.00 | 384.17 | 1628.37 | 15.24 | 43.33 | 339.67 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 2706.72 | 10.75 | 3.50 | 388.17 | 1512.62 | 12.88 | 0.00 | 344.83 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:00 | 3604.21 | 13.37 | 54.33 | 365.00 | 1575.48 | 12.62 | 0.00 | 337.67 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:19 | 2786.94 | 13.92 | 45.67 | 312.83 | 1536.62 | 13.10 | 5.50 | 274.33 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2953.60 | 17.72 | 83.50 | 297.00 | 1297.63 | 17.36 | 53.17 | 267.17 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-07:19 | 1475.09 | 16.74 | 65.00 | 238.67 | 796.67 | 16.48 | 43.67 | 187.17 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-08:20 | 1219.43 | 14.77 | 45.67 | 207.00 | 770.21 | 16.54 | 43.67 | 146.33 |
Annual Sum or Average | 3472.67 | 0.74 | 2629.69 | 13.70 | 496.00 | 3671.83 | 1338.45 | 14.61 | 312.33 | 3129.50 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1219.43 | 10.32 | 0.00 | 207.00 | 770.21 | 12.26 | 0.00 | 146.33 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 3604.21 | 17.72 | 83.50 | 388.50 | 1651.37 | 17.36 | 53.17 | 345.50 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379368E+10 | 515782.49 | 14-JAN-17:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134289E+10 | 436192.81 | 19-FEB-13:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312884E+09 | 288345.95 | 04-MAR-19:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225393E+09 | 85856.18 | 02-APR-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.374901E+09 | 432983.55 | 16-MAY-03:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.152547E+09 | 435588.49 | 28-OCT-17:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.485056E+09 | 278198.33 | 18-NOV-20:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.293954E+09 | 88152.99 | 23-DEC-17:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.698131E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379368E+10 | 515782.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.141565E+11 | 491754.16 | 02-JAN-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.886251E+09 | 491321.47 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.150428E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.141565E+11 | 491754.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.624590E+10 | 80407.66 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.451065E+10 | 80286.76 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.820901E+09 | 80333.03 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138178E+09 | 80066.25 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172963E+10 | 80491.57 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.261066E+10 | 80352.88 | 26-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160559E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.624590E+10 | 80491.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.213450E+09 | 11474.63 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159537E+09 | 11469.51 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.372987E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.213450E+09 | 11474.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.485169E+09 | 9678.49 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352554E+09 | 9676.23 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 41741869.69 | 5504.82 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 112456.80 | 88.13 | 21-APR-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 29562493.70 | 5532.08 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.127725E+09 | 9484.95 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.103686E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.485169E+09 | 9678.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486515E+09 | 13838.39 | 05-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.321726E+09 | 13824.10 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 19970440.63 | 13477.99 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 18535768.89 | 11333.22 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 36053359.43 | 13438.02 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.882800E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.486515E+09 | 13838.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.198675E+09 | 8682.73 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 55109530.16 | 8679.66 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253785E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198675E+09 | 8682.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.419140E+11 | 121445.44 | 24-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314406E+11 | 126872.74 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.766652E+10 | 122328.23 | 07-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111229E+10 | 119379.01 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100218E+09 | 41915.66 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.783843E+10 | 119991.07 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189545E+11 | 122896.72 | 29-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.109027E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.419140E+11 | 126872.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.373344E+11 | 147376.89 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257846E+11 | 147406.45 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.925017E+10 | 145827.74 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.306320E+10 | 142652.54 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35985411.76 | 5104.21 | 04-MAY-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.492302E+09 | 37915.94 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.949541E+10 | 146078.11 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212530E+11 | 145449.68 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.106709E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.373344E+11 | 147406.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.268672E+11 | 139367.22 | 24-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164023E+11 | 137905.87 | 28-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468046E+10 | 137327.20 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.111527E+10 | 137232.34 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 362283.24 | 603.81 | 28-OCT-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.393926E+10 | 138256.60 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112110E+11 | 137697.30 | 12-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.642159E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.268672E+11 | 139367.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.323789E+11 | 145706.81 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.236349E+11 | 145734.41 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.657554E+10 | 143396.91 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172681E+10 | 121123.77 | 21-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 371010.41 | 304.64 | 04-MAY-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.310759E+09 | 17986.49 | 28-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.850216E+10 | 144414.17 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175867E+11 | 143791.82 | 15-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.907162E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.323789E+11 | 145734.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.800638E+10 | 13536.79 | 24-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.699747E+10 | 14052.86 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.275731E+10 | 13415.30 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.850016E+09 | 13418.95 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33957780.67 | 13306.92 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.286946E+09 | 13522.43 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.289235E+10 | 13427.93 | 27-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.557918E+10 | 13363.29 | 26-DEC-05:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274036E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.800638E+10 | 14052.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.602916E+10 | 16104.90 | 12-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486207E+10 | 16101.37 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.217039E+10 | 16106.48 | 20-MAR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.861932E+09 | 16083.61 | 03-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 69906424.13 | 15106.02 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19069567.68 | 1048.67 | 30-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.295943E+09 | 15962.68 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.241098E+10 | 16124.05 | 25-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.440786E+10 | 16111.65 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211273E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.602916E+10 | 16124.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.570788E+10 | 15599.38 | 24-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.435055E+10 | 16297.08 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.196933E+10 | 15471.52 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.810185E+09 | 15461.97 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43525257.47 | 15403.71 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135142E+09 | 15319.54 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179456E+10 | 15514.59 | 27-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 15479.56 | 26-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184539E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.570788E+10 | 16297.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.545246E+10 | 17081.81 | 31-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.440485E+10 | 17080.82 | 07-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187629E+10 | 16828.63 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.704385E+09 | 16556.88 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 64397172.85 | 3568.40 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 12687738.69 | 630.24 | 27-SEP-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.256908E+09 | 16404.92 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.217345E+10 | 16927.38 | 24-NOV-05:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379270E+10 | 16991.47 | 31-DEC-22:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187381E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.545246E+10 | 17081.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.293204E+09 | 229977.91 | 26-JAN-05:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.481784E+09 | 233138.22 | 07-FEB-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.316592E+09 | 228566.32 | 22-MAR-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.617808E+09 | 225506.18 | 04-APR-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.626994E+09 | 224268.55 | 09-MAY-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.974511E+09 | 223718.63 | 09-JUN-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.622617E+09 | 218684.63 | 04-JUL-20:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.112077E+10 | 221728.04 | 09-AUG-03:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.151082E+10 | 223949.22 | 24-SEP-23:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147942E+10 | 225882.19 | 09-OCT-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143931E+10 | 231173.00 | 24-NOV-03:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.504864E+09 | 229542.80 | 15-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.998870E+10 | |||||||
Minimum of Months | 0.293204E+09 | 218684.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151082E+10 | 233138.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254735E+10 | 71580.68 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.398156E+10 | 72401.28 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170061E+10 | 51613.24 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.246952E+09 | 30853.04 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 20223960.57 | 4938.01 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29024611.93 | 7453.94 | 01-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10116162.59 | 3404.89 | 11-JUL-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 52610971.46 | 6999.41 | 22-AUG-17:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 20484555.39 | 4690.86 | 01-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147839E+09 | 25056.12 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.750054E+09 | 48098.00 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164068E+10 | 50520.36 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.111475E+11 | |||||||
Minimum of Months | 10116162.59 | 3404.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.398156E+10 | 72401.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.250850E+11 | 763868.28 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.228631E+11 | 750873.80 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.208333E+11 | 614045.86 | 17-MAR-16:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.721097E+10 | 343981.24 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.391982E+09 | 124192.88 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.313241E+09 | 51375.11 | 01-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.121445E+09 | 30975.10 | 11-JUL-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.848866E+09 | 106855.08 | 30-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 50429620.69 | 54810.69 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.228793E+10 | 294119.36 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169128E+11 | 614720.62 | 24-NOV-16:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341369E+11 | 644722.82 | 22-DEC-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131056E+12 | |||||||
Minimum of Months | 50429620.69 | 30975.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.341369E+11 | 763868.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.310748E+10 | 77017.64 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.262012E+10 | 76615.02 | 06-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.741322E+09 | 57956.98 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.353620E+09 | 35520.16 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 43506801.86 | 13023.50 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 40155912.47 | 9090.06 | 01-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 10942469.84 | 3548.47 | 11-JUL-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 37950948.99 | 6115.59 | 22-AUG-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19826870.56 | 5768.29 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157417E+09 | 30548.47 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.556119E+09 | 56522.34 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.797625E+09 | 58588.35 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.848608E+10 | |||||||
Minimum of Months | 10942469.84 | 3548.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.310748E+10 | 77017.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 8852447.20 | 3950100.46 | 37064.77 | 24-JAN-06:02 | 16254.47 | 0.00 |
February | 0.00 | 0.00 | 206.81 | 206.81 | 0.65 | 06-FEB-05:25 | 0.65 | 0.00 |
March | 0.00 | 0.00 | 0.677044E+09 | 0.676742E+09 | 44027.06 | 27-MAR-16:00 | 44027.06 | 0.01 |
April | 0.00 | 0.00 | 0.586349E+10 | 0.582344E+10 | 66597.95 | 07-APR-13:50 | 66597.95 | 0.05 |
May | 0.00 | 0.00 | 0.172950E+11 | 0.162190E+11 | 104685.04 | 29-MAY-11:30 | 104685.04 | 0.13 |
June | 0.00 | 0.00 | 0.696316E+11 | 0.578800E+11 | 171447.19 | 19-JUN-00:08 | 97970.49 | 0.52 |
July | 0.00 | 0.00 | 0.984115E+11 | 0.774105E+11 | 176762.93 | 09-JUL-20:01 | 90019.24 | 0.57 |
August | 0.00 | 0.00 | 0.985475E+11 | 0.819854E+11 | 157193.26 | 13-AUG-21:51 | 93880.92 | 0.58 |
September | 0.00 | 0.00 | 0.528878E+11 | 0.459533E+11 | 150117.68 | 01-SEP-03:01 | 89884.41 | 0.43 |
October | 0.00 | 0.00 | 0.209233E+11 | 0.173112E+11 | 110840.09 | 06-OCT-05:03 | 47533.98 | 0.22 |
November | 0.00 | 0.00 | 0.278698E+09 | 0.239712E+09 | 65358.21 | 10-NOV-06:02 | 26051.00 | 0.00 |
December | 0.00 | 0.00 | 2931514.16 | 2521637.97 | 10277.62 | 25-DEC-10:11 | 4627.66 | 0.00 |
Annual Sum or Average | 0.364528E+12 | 0.303506E+12 | 0.21 | |||||
Minimum of Months | 0.00 | 0.00 | 206.81 | 206.81 | 0.65 | 0.65 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.985475E+11 | 0.819854E+11 | 176762.93 | 104685.04 | 0.58 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 22739308.61 | 22739308.61 | 7186.78 | 17-JAN-08:20 | 7186.78 | 0.00 |
February | 0.00 | 0.00 | 15070375.75 | 15070375.75 | 10740.90 | 22-FEB-10:00 | 10740.90 | 0.00 |
March | 0.00 | 0.00 | 0.206955E+10 | 0.175559E+10 | 88227.15 | 27-MAR-13:00 | 57657.19 | 0.02 |
April | 0.00 | 0.00 | 0.145356E+11 | 0.143753E+11 | 104466.64 | 07-APR-13:30 | 104466.64 | 0.11 |
May | 0.00 | 0.00 | 0.451761E+11 | 0.377360E+11 | 149409.57 | 30-MAY-13:20 | 149409.57 | 0.26 |
June | 0.00 | 0.00 | 0.136119E+12 | 0.988123E+11 | 159431.29 | 21-JUN-05:01 | 142107.24 | 0.63 |
July | 0.00 | 0.00 | 0.179293E+12 | 0.133577E+12 | 172895.67 | 24-JUL-03:02 | 144676.12 | 0.76 |
August | 0.00 | 0.00 | 0.179317E+12 | 0.147225E+12 | 180701.44 | 15-AUG-05:02 | 153278.53 | 0.79 |
September | 0.00 | 0.00 | 0.937192E+11 | 0.724840E+11 | 196277.74 | 14-SEP-03:01 | 144926.96 | 0.50 |
October | 0.00 | 0.00 | 0.492143E+11 | 0.340681E+11 | 143621.15 | 06-OCT-03:02 | 64135.68 | 0.30 |
November | 0.00 | 0.00 | 0.224935E+10 | 0.194979E+10 | 45519.70 | 10-NOV-10:00 | 18876.68 | 0.02 |
December | 0.00 | 0.00 | 16987377.55 | 16987377.55 | 3253.60 | 27-DEC-14:10 | 3253.60 | 0.00 |
Annual Sum or Average | 0.701748E+12 | 0.542038E+12 | 0.29 | |||||
Minimum of Months | 0.00 | 0.00 | 15070375.75 | 15070375.75 | 3253.60 | 3253.60 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.179317E+12 | 0.147225E+12 | 196277.74 | 153278.53 | 0.79 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 45543857.28 | 45543857.28 | 45287.87 | 25-JAN-17:40 | 45287.87 | 0.00 |
February | 0.00 | 0.00 | 0.182768E+09 | 0.182768E+09 | 142039.44 | 10-FEB-12:20 | 142039.44 | 0.00 |
March | 0.00 | 0.00 | 0.144735E+11 | 0.126116E+11 | 583572.04 | 27-MAR-13:00 | 388767.19 | 0.02 |
April | 0.00 | 0.00 | 0.100698E+12 | 0.100293E+12 | 851262.26 | 07-APR-13:30 | 851262.26 | 0.08 |
May | 0.00 | 0.00 | 0.387869E+12 | 0.322741E+12 | 1210735.76 | 30-MAY-13:30 | 1210735.76 | 0.25 |
June | 0.00 | 0.00 | 0.114969E+13 | 0.791996E+12 | 1832665.87 | 27-JUN-05:01 | 1343544.04 | 0.56 |
July | 0.00 | 0.00 | 0.145073E+13 | 0.995070E+12 | 2354068.95 | 24-JUL-03:02 | 1301041.28 | 0.61 |
August | 0.00 | 0.00 | 0.139121E+13 | 0.107866E+13 | 1992036.84 | 04-AUG-03:01 | 1390523.47 | 0.61 |
September | 0.00 | 0.00 | 0.823002E+12 | 0.619438E+12 | 2006057.91 | 14-SEP-05:01 | 1304447.42 | 0.48 |
October | 0.00 | 0.00 | 0.401871E+12 | 0.269890E+12 | 1401854.53 | 06-OCT-05:02 | 600508.82 | 0.29 |
November | 0.00 | 0.00 | 0.173156E+11 | 0.151405E+11 | 303690.80 | 10-NOV-10:00 | 126599.46 | 0.02 |
December | 0.00 | 0.00 | 0.392039E+09 | 0.392039E+09 | 219404.58 | 11-DEC-11:50 | 219404.58 | 0.00 |
Annual Sum or Average | 0.573747E+13 | 0.420646E+13 | 0.25 | |||||
Minimum of Months | 0.00 | 0.00 | 45543857.28 | 45543857.28 | 45287.87 | 45287.87 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.145073E+13 | 0.107866E+13 | 2354068.95 | 1390523.47 | 0.61 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 10373092.09 | 10373092.09 | 2943.54 | 15-JAN-10:10 | 2943.54 | 0.00 |
February | 0.00 | 0.00 | 14773896.69 | 14773896.69 | 942.60 | 02-FEB-10:50 | 942.60 | 0.00 |
March | 0.00 | 0.00 | 0.134886E+10 | 0.118811E+10 | 51500.96 | 27-MAR-13:00 | 34484.57 | 0.02 |
April | 0.00 | 0.00 | 0.104179E+11 | 0.103821E+11 | 95110.95 | 07-APR-15:30 | 95110.95 | 0.08 |
May | 0.00 | 0.00 | 0.409778E+11 | 0.342645E+11 | 144031.12 | 30-MAY-13:10 | 144031.12 | 0.25 |
June | 0.00 | 0.00 | 0.124874E+12 | 0.874184E+11 | 200864.98 | 19-JUN-03:01 | 139449.74 | 0.56 |
July | 0.00 | 0.00 | 0.161695E+12 | 0.112840E+12 | 264102.74 | 24-JUL-03:02 | 145260.21 | 0.62 |
August | 0.00 | 0.00 | 0.152893E+12 | 0.119837E+12 | 215062.27 | 04-AUG-03:01 | 143175.46 | 0.60 |
September | 0.00 | 0.00 | 0.856150E+11 | 0.644816E+11 | 208800.20 | 14-SEP-05:01 | 130390.64 | 0.47 |
October | 0.00 | 0.00 | 0.394714E+11 | 0.264521E+11 | 140665.76 | 06-OCT-05:03 | 60304.09 | 0.28 |
November | 0.00 | 0.00 | 0.155004E+10 | 0.135406E+10 | 27207.68 | 10-NOV-08:00 | 9988.76 | 0.02 |
December | 0.00 | 0.00 | 18886879.32 | 18886879.32 | 875.12 | 21-DEC-12:00 | 875.12 | 0.00 |
Annual Sum or Average | 0.618887E+12 | 0.458262E+12 | 0.24 | |||||
Minimum of Months | 0.00 | 0.00 | 10373092.09 | 10373092.09 | 875.12 | 875.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161695E+12 | 0.119837E+12 | 264102.74 | 145260.21 | 0.62 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.310203E+12 | 0.310082E+12 | 443523.07 | 03-JAN-22:40 | 443523.07 | 0.00 |
February | 0.00 | 0.00 | 0.490328E+12 | 0.490140E+12 | 438550.43 | 15-FEB-23:00 | 438550.43 | 0.00 |
March | 0.00 | 0.00 | 0.779530E+12 | 0.779418E+12 | 436914.37 | 04-MAR-21:30 | 436914.37 | 0.00 |
April | 0.00 | 0.00 | 0.986795E+12 | 0.986779E+12 | 424855.17 | 17-APR-21:25 | 424855.17 | 0.00 |
May | 0.00 | 0.00 | 0.316447E+12 | 0.315099E+12 | 425245.26 | 02-MAY-03:36 | 425245.26 | 0.00 |
June | 0.00 | 0.00 | 0.540642E+12 | 0.535140E+12 | 218911.43 | 15-JUN-12:50 | 208635.17 | 0.00 |
July | 0.00 | 0.00 | 0.799386E+12 | 0.790746E+12 | 308654.25 | 20-JUL-15:00 | 297246.27 | 0.00 |
August | 0.00 | 0.00 | 0.103211E+13 | 0.102644E+13 | 396954.93 | 18-AUG-19:00 | 388112.61 | 0.00 |
September | 0.00 | 0.00 | 0.313629E+12 | 0.309755E+12 | 136300.72 | 01-SEP-00:10 | 134810.51 | 0.00 |
October | 0.00 | 0.00 | 0.555396E+12 | 0.552879E+12 | 435270.41 | 28-OCT-17:17 | 435270.41 | 0.00 |
November | 0.00 | 0.00 | 0.759684E+12 | 0.759566E+12 | 434488.97 | 18-NOV-20:34 | 434488.97 | 0.00 |
December | 0.00 | 0.00 | 0.101796E+13 | 0.101796E+13 | 422687.56 | 27-DEC-22:17 | 422687.56 | 0.00 |
Annual Sum or Average | 0.790211E+13 | 0.787400E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.310203E+12 | 0.309755E+12 | 136300.72 | 134810.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103211E+13 | 0.102644E+13 | 443523.07 | 443523.07 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.399200E+10 | 0.399200E+10 | 2348.61 | 20-JAN-16:30 | 2348.61 | 0.00 |
February | 0.00 | 0.00 | 0.846466E+10 | 0.846466E+10 | 4400.88 | 14-FEB-16:55 | 4400.88 | 0.00 |
March | 0.00 | 0.00 | 0.150438E+11 | 0.150438E+11 | 6336.26 | 27-MAR-17:20 | 6336.26 | 0.00 |
April | 0.00 | 0.00 | 0.193687E+11 | 0.193687E+11 | 7804.29 | 23-APR-17:52 | 7804.29 | 0.00 |
May | 0.00 | 0.00 | 0.545978E+10 | 0.545978E+10 | 2509.62 | 30-MAY-18:00 | 2509.62 | 0.00 |
June | 0.00 | 0.00 | 0.102548E+11 | 0.102548E+11 | 4466.56 | 18-JUN-17:55 | 4466.56 | 0.00 |
July | 0.00 | 0.00 | 0.155038E+11 | 0.155038E+11 | 6359.99 | 12-JUL-18:20 | 6359.99 | 0.00 |
August | 0.00 | 0.00 | 0.187482E+11 | 0.187482E+11 | 7554.86 | 08-AUG-04:55 | 7554.86 | 0.00 |
September | 0.00 | 0.00 | 0.539126E+10 | 0.539126E+10 | 5080.83 | 01-SEP-00:03 | 5080.83 | 0.00 |
October | 0.00 | 0.00 | 0.104633E+11 | 0.104633E+11 | 4488.03 | 15-OCT-16:40 | 4488.03 | 0.00 |
November | 0.00 | 0.00 | 0.145287E+11 | 0.145287E+11 | 6124.34 | 06-NOV-16:10 | 6124.34 | 0.00 |
December | 0.00 | 0.00 | 0.197825E+11 | 0.197825E+11 | 7716.03 | 21-DEC-16:20 | 7716.03 | 0.00 |
Annual Sum or Average | 0.147002E+12 | 0.147002E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.399200E+10 | 0.399200E+10 | 2348.61 | 2348.61 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.197825E+11 | 0.197825E+11 | 7804.29 | 7804.29 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.168258E+11 | 0.168258E+11 | 20262.32 | 20-JAN-16:40 | 20262.32 | 0.00 |
February | 0.00 | 0.00 | 0.626136E+11 | 0.626136E+11 | 39669.51 | 22-FEB-17:00 | 39669.51 | 0.00 |
March | 0.00 | 0.00 | 0.128981E+12 | 0.128981E+12 | 59512.70 | 29-MAR-17:20 | 59512.70 | 0.00 |
April | 0.00 | 0.00 | 0.175841E+12 | 0.175841E+12 | 74142.78 | 12-APR-18:00 | 74142.78 | 0.00 |
May | 0.00 | 0.00 | 0.459637E+11 | 0.459637E+11 | 23844.55 | 30-MAY-18:00 | 23844.55 | 0.00 |
June | 0.00 | 0.00 | 0.950922E+11 | 0.950922E+11 | 42562.94 | 18-JUN-18:00 | 42562.94 | 0.00 |
July | 0.00 | 0.00 | 0.146848E+12 | 0.146848E+12 | 60804.34 | 12-JUL-18:20 | 60804.34 | 0.00 |
August | 0.00 | 0.00 | 0.178858E+12 | 0.178858E+12 | 72017.78 | 08-AUG-04:37 | 72017.78 | 0.00 |
September | 0.00 | 0.00 | 0.460504E+11 | 0.460504E+11 | 47746.30 | 01-SEP-00:03 | 47746.30 | 0.00 |
October | 0.00 | 0.00 | 0.911021E+11 | 0.911021E+11 | 42006.82 | 04-OCT-16:30 | 42006.82 | 0.00 |
November | 0.00 | 0.00 | 0.122215E+12 | 0.122215E+12 | 57210.26 | 03-NOV-16:00 | 57210.26 | 0.00 |
December | 0.00 | 0.00 | 0.167877E+12 | 0.167877E+12 | 73071.08 | 08-DEC-16:20 | 73071.08 | 0.00 |
Annual Sum or Average | 0.127827E+13 | 0.127827E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.168258E+11 | 0.168258E+11 | 20262.32 | 20262.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.178858E+12 | 0.178858E+12 | 74142.78 | 74142.78 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.814275E+09 | 0.814275E+09 | 1956.47 | 20-JAN-16:40 | 1956.47 | 0.00 |
February | 0.00 | 0.00 | 0.466135E+10 | 0.466135E+10 | 3870.76 | 02-FEB-16:50 | 3870.76 | 0.00 |
March | 0.00 | 0.00 | 0.116750E+11 | 0.116750E+11 | 5954.92 | 29-MAR-17:20 | 5954.92 | 0.00 |
April | 0.00 | 0.00 | 0.168473E+11 | 0.168473E+11 | 7522.41 | 12-APR-17:50 | 7522.41 | 0.00 |
May | 0.00 | 0.00 | 0.429419E+10 | 0.429419E+10 | 2476.26 | 30-MAY-18:00 | 2476.26 | 0.00 |
June | 0.00 | 0.00 | 0.950981E+10 | 0.950981E+10 | 4472.92 | 18-JUN-17:55 | 4472.92 | 0.00 |
July | 0.00 | 0.00 | 0.147918E+11 | 0.147918E+11 | 6177.76 | 12-JUL-18:20 | 6177.76 | 0.00 |
August | 0.00 | 0.00 | 0.181484E+11 | 0.181484E+11 | 7231.87 | 20-AUG-01:42 | 7231.87 | 0.00 |
September | 0.00 | 0.00 | 0.437701E+10 | 0.437701E+10 | 4187.72 | 01-SEP-00:03 | 4187.72 | 0.00 |
October | 0.00 | 0.00 | 0.837199E+10 | 0.837199E+10 | 4264.78 | 04-OCT-16:30 | 4264.78 | 0.00 |
November | 0.00 | 0.00 | 0.107632E+11 | 0.107632E+11 | 5703.42 | 03-NOV-16:00 | 5703.42 | 0.00 |
December | 0.00 | 0.00 | 0.149373E+11 | 0.149373E+11 | 7173.04 | 08-DEC-16:10 | 7173.04 | 0.00 |
Annual Sum or Average | 0.119192E+12 | 0.119192E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.814275E+09 | 0.814275E+09 | 1956.47 | 1956.47 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.181484E+11 | 0.181484E+11 | 7522.41 | 7522.41 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3898.76 | 34138.37 | 16-JAN-11:00 | 14032.02 | 64949.58 | 26-JAN-12:07 |
February | 3523.19 | 33944.41 | 20-FEB-11:00 | 14333.22 | 62614.12 | 02-FEB-13:08 |
March | 2813.98 | 33555.71 | 27-MAR-05:08 | 15090.39 | 62284.79 | 13-MAR-11:47 |
April | 3952.50 | 33656.93 | 03-APR-05:08 | 13226.73 | 53996.92 | 12-APR-11:10 |
May | 4652.18 | 37944.34 | 29-MAY-09:25 | 12778.76 | 48337.45 | 01-MAY-11:30 |
June | 4539.01 | 38129.90 | 25-JUN-22:52 | 12170.24 | 44841.86 | 01-JUN-11:20 |
July | 6433.11 | 38262.07 | 30-JUL-18:27 | 10312.00 | 41945.78 | 03-JUL-11:40 |
August | 4889.95 | 38270.08 | 13-AUG-19:05 | 11444.25 | 43277.87 | 08-AUG-11:10 |
September | 5734.58 | 38231.42 | 03-SEP-22:50 | 10922.35 | 42871.53 | 29-SEP-12:00 |
October | 5769.93 | 38041.82 | 09-OCT-09:10 | 11614.14 | 48902.66 | 27-OCT-11:30 |
November | 4949.32 | 37726.93 | 12-NOV-11:00 | 12719.19 | 58530.32 | 22-NOV-12:58 |
December | 4180.64 | 35159.20 | 25-DEC-11:00 | 13084.72 | 61122.33 | 13-DEC-12:18 |
Annual Sum or Average | 4618.37 | 12634.33 | ||||
Minimum of Months | 2813.98 | 33555.71 | 10312.00 | 41945.78 | ||
Maximum of Months | 6433.11 | 38270.08 | 15090.39 | 64949.58 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13.12 | 4735.13 | 16-JAN-15:15 | 80508.36 | 1980696.16 | 02-JAN-07:10 |
February | 3.23 | 1848.52 | 26-FEB-16:30 | 62997.97 | 1628723.13 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 22640.29 | 862889.27 | 23-MAR-06:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7187.15 | 1043829.86 | 03-APR-05:01 |
May | 0.27 | 822.91 | 01-MAY-21:00 | 637.15 | 514721.26 | 16-MAY-03:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 527.32 | 290664.47 | 23-JUN-03:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 283.40 | 303802.17 | 13-JUL-03:45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 710.40 | 399454.90 | 31-AUG-03:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 650.13 | 323448.07 | 02-SEP-03:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 2214.35 | 372782.25 | 07-OCT-03:47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23088.54 | 980956.40 | 24-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 46693.55 | 1326065.03 | 28-DEC-05:01 |
Annual Sum or Average | 1.39 | 20470.82 | ||||
Minimum of Months | 0.00 | 0.00 | 283.40 | 290664.47 | ||
Maximum of Months | 13.12 | 4735.13 | 80508.36 | 1980696.16 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 902.02 | 22859.28 | 30-JAN-11:30 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1098.22 | 77257.34 | 10-FEB-12:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15084.12 | 1404586.72 | 27-MAR-13:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 98567.54 | 1448286.15 | 07-APR-11:40 | 6.28 | 35994.13 | 08-APR-00:52 |
May | 332357.43 | 1660209.40 | 30-MAY-13:30 | 0.54 | 15013.71 | 29-MAY-20:51 |
June | 770483.65 | 2397474.90 | 20-JUN-05:02 | 5.78 | 45860.45 | 11-JUN-05:52 |
July | 880627.51 | 2849722.10 | 22-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 886565.21 | 2708856.94 | 17-AUG-05:02 | 2.59 | 24869.82 | 20-AUG-01:42 |
September | 602549.13 | 2564630.83 | 08-SEP-05:03 | 11.37 | 93709.23 | 24-SEP-22:51 |
October | 302979.48 | 1986873.50 | 06-OCT-05:03 | 0.64 | 28375.15 | 01-OCT-19:41 |
November | 18451.97 | 754652.87 | 10-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1932.08 | 189890.93 | 25-DEC-16:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 328126.58 | 2.25 | ||||
Minimum of Months | 902.02 | 22859.28 | 0.00 | 0.00 | ||
Maximum of Months | 886565.21 | 2849722.10 | 11.37 | 93709.23 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6.39 | 15605.46 | 24-JAN-06:02 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 60.24 | 71452.90 | 10-FEB-12:20 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9410.67 | 1055305.33 | 27-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 66864.78 | 1404004.81 | 07-APR-12:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 238838.44 | 1685784.89 | 31-MAY-08:40 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 698873.91 | 3448380.17 | 15-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 798089.14 | 3561631.08 | 15-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 778770.09 | 3232398.87 | 12-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 507386.56 | 3555621.08 | 14-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 256467.00 | 2639078.74 | 06-OCT-05:02 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11257.15 | 576649.07 | 04-NOV-12:40 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 207.81 | 180588.07 | 11-DEC-11:50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 282379.82 | 0.00 | ||||
Minimum of Months | 6.39 | 15605.46 | 0.00 | 0.00 | ||
Maximum of Months | 798089.14 | 3561631.08 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 154485.96 | 543031.03 | 21-JAN-05:20 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 290517.35 | 575481.87 | 15-FEB-23:01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 436767.55 | 847640.69 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 629902.21 | 1295063.87 | 07-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237558.40 | 854000.59 | 30-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 625439.57 | 1445720.64 | 19-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1015451.43 | 1520355.59 | 07-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1201736.80 | 1687875.30 | 24-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 362633.70 | 921926.34 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 368984.09 | 803335.23 | 04-OCT-13:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 437910.54 | 617723.91 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 566497.66 | 616448.83 | 27-DEC-22:20 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 529416.45 | 0.00 | ||||
Minimum of Months | 154485.96 | 543031.03 | 0.00 | 0.00 | ||
Maximum of Months | 1201736.80 | 1687875.30 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21.11 | 13903.22 | 19-JAN-14:05 | 1660.18 | 134848.98 | 06-JAN-06:41 |
February | 64.53 | 46077.74 | 10-FEB-12:20 | 1805.01 | 133668.35 | 22-FEB-13:40 |
March | 9621.19 | 1214717.57 | 27-MAR-13:20 | 2021.96 | 123923.30 | 13-MAR-06:20 |
April | 70556.74 | 2027609.39 | 07-APR-13:50 | 889.37 | 92207.85 | 03-APR-09:00 |
May | 285207.75 | 4054556.80 | 31-MAY-13:50 | 598.67 | 87708.16 | 13-MAY-09:20 |
June | 1284759.19 | 6158906.34 | 15-JUN-12:20 | 126.88 | 90750.63 | 02-JUN-06:50 |
July | 2105060.72 | 6969633.80 | 20-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1809955.72 | 7323725.03 | 02-AUG-15:00 | 46.32 | 30063.15 | 26-AUG-00:10 |
September | 860814.08 | 5768377.13 | 07-SEP-14:10 | 79.97 | 41568.91 | 23-SEP-10:00 |
October | 307179.90 | 3751884.14 | 24-OCT-13:50 | 576.58 | 97723.77 | 18-OCT-14:50 |
November | 12857.32 | 534446.53 | 10-NOV-10:00 | 1779.81 | 123315.96 | 22-NOV-15:50 |
December | 99.09 | 70018.04 | 11-DEC-11:50 | 2937.99 | 135411.66 | 11-DEC-15:55 |
Annual Sum or Average | 566857.36 | 1040.86 | ||||
Minimum of Months | 21.11 | 13903.22 | 0.00 | 0.00 | ||
Maximum of Months | 2105060.72 | 7323725.03 | 2937.99 | 135411.66 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132351E+11 | 0.76 | 9046.71 | 02-JAN-04:01 | 1.39 |
February | 0.123144E+11 | 0.78 | 9046.71 | 01-FEB-05:01 | 1.40 |
March | 0.145742E+11 | 0.84 | 9046.71 | 01-MAR-05:01 | 1.39 |
April | 0.135217E+11 | 0.80 | 9046.71 | 01-APR-04:01 | 1.39 |
May | 0.144267E+11 | 0.82 | 9046.71 | 01-MAY-01:41 | 1.39 |
June | 0.144815E+11 | 0.85 | 9046.71 | 01-JUN-03:01 | 1.38 |
July | 0.142841E+11 | 0.81 | 9046.71 | 01-JUL-03:01 | 1.38 |
August | 0.155113E+11 | 0.88 | 9046.71 | 01-AUG-03:01 | 1.38 |
September | 0.147188E+11 | 0.87 | 9046.71 | 01-SEP-03:01 | 1.38 |
October | 0.150478E+11 | 0.86 | 9046.71 | 01-OCT-19:41 | 1.38 |
November | 0.142670E+11 | 0.85 | 9046.71 | 01-NOV-03:01 | 1.39 |
December | 0.140001E+11 | 0.80 | 9046.71 | 01-DEC-04:01 | 1.39 |
Annual Sum or Average | 0.170383E+12 | 0.83 | |||
Minimum of Months | 0.123144E+11 | 0.76 | 9046.71 | 1.38 | |
Maximum of Months | 0.155113E+11 | 0.88 | 9046.71 | 1.40 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.460445E+10 | 0.34 | 16395.27 | 31-JAN-16:30 | 1.62 |
February | 0.493436E+10 | 0.37 | 16773.30 | 14-FEB-15:40 | 1.64 |
March | 0.708757E+10 | 0.44 | 15882.63 | 11-MAR-09:47 | 1.58 |
April | 0.718450E+10 | 0.47 | 17169.57 | 10-APR-05:03 | 1.65 |
May | 0.585093E+10 | 0.41 | 20742.80 | 30-MAY-03:02 | 1.86 |
June | 0.649433E+10 | 0.47 | 20742.80 | 12-JUN-05:03 | 1.86 |
July | 0.737938E+10 | 0.51 | 20282.30 | 06-JUL-05:01 | 1.83 |
August | 0.896658E+10 | 0.58 | 20282.30 | 04-AUG-05:01 | 1.83 |
September | 0.579166E+10 | 0.42 | 20742.80 | 05-SEP-03:01 | 1.86 |
October | 0.683793E+10 | 0.43 | 20282.30 | 14-OCT-05:01 | 1.83 |
November | 0.640536E+10 | 0.41 | 13325.06 | 04-NOV-03:01 | 1.41 |
December | 0.650559E+10 | 0.41 | 14578.16 | 15-DEC-17:25 | 1.50 |
Annual Sum or Average | 0.780426E+11 | 0.44 | |||
Minimum of Months | 0.460445E+10 | 0.34 | 13325.06 | 1.41 | |
Maximum of Months | 0.896658E+10 | 0.58 | 20742.80 | 1.86 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342873E+11 | 0.33 | 119238.64 | 27-JAN-13:47 | 1.38 |
February | 0.319527E+11 | 0.33 | 156906.55 | 22-FEB-16:30 | 1.65 |
March | 0.412689E+11 | 0.35 | 156906.55 | 23-MAR-15:25 | 1.64 |
April | 0.399637E+11 | 0.34 | 123561.22 | 12-APR-07:07 | 1.42 |
May | 0.455884E+11 | 0.37 | 193003.34 | 30-MAY-04:01 | 1.86 |
June | 0.505394E+11 | 0.40 | 193003.34 | 05-JUN-05:01 | 1.86 |
July | 0.541408E+11 | 0.41 | 193003.34 | 01-JUL-05:01 | 1.86 |
August | 0.631877E+11 | 0.45 | 193003.34 | 02-AUG-03:01 | 1.86 |
September | 0.467238E+11 | 0.38 | 193003.34 | 02-SEP-05:01 | 1.86 |
October | 0.466391E+11 | 0.36 | 119238.64 | 04-OCT-05:01 | 1.37 |
November | 0.366872E+11 | 0.32 | 125057.58 | 15-NOV-06:01 | 1.42 |
December | 0.354992E+11 | 0.32 | 125057.58 | 21-DEC-06:01 | 1.43 |
Annual Sum or Average | 0.526478E+12 | 0.36 | |||
Minimum of Months | 0.319527E+11 | 0.32 | 119238.64 | 1.37 | |
Maximum of Months | 0.631877E+11 | 0.45 | 193003.34 | 1.86 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.403908E+10 | 0.39 | 4423.45 | 02-JAN-04:01 | 0.76 |
February | 0.354262E+10 | 0.37 | 4423.45 | 01-FEB-06:01 | 0.76 |
March | 0.368721E+10 | 0.34 | 16642.97 | 23-MAR-15:10 | 1.67 |
April | 0.365661E+10 | 0.32 | 9578.92 | 07-APR-05:03 | 1.18 |
May | 0.450717E+10 | 0.36 | 19892.56 | 30-MAY-05:03 | 1.86 |
June | 0.560504E+10 | 0.41 | 19892.56 | 08-JUN-05:01 | 1.86 |
July | 0.628469E+10 | 0.43 | 19892.56 | 01-JUL-05:01 | 1.86 |
August | 0.717689E+10 | 0.47 | 19892.56 | 01-AUG-05:01 | 1.86 |
September | 0.472651E+10 | 0.37 | 19892.56 | 02-SEP-05:01 | 1.86 |
October | 0.405448E+10 | 0.33 | 10454.23 | 17-OCT-05:01 | 1.24 |
November | 0.328437E+10 | 0.32 | 4423.45 | 20-NOV-05:01 | 0.76 |
December | 0.347712E+10 | 0.34 | 4423.45 | 02-DEC-06:01 | 0.76 |
Annual Sum or Average | 0.540418E+11 | 0.37 | |||
Minimum of Months | 0.328437E+10 | 0.32 | 4423.45 | 0.76 | |
Maximum of Months | 0.717689E+10 | 0.47 | 19892.56 | 1.86 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.941376E+11 | 1.35 | 35146.96 | 01-JAN-00:01 | 1.35 |
February | 0.850275E+11 | 1.35 | 35146.96 | 01-FEB-00:10 | 1.35 |
March | 0.941376E+11 | 1.35 | 35146.96 | 01-MAR-00:10 | 1.35 |
April | 0.911009E+11 | 1.35 | 35146.96 | 01-APR-00:10 | 1.35 |
May | 0.941376E+11 | 1.35 | 35146.96 | 01-MAY-00:10 | 1.35 |
June | 0.911009E+11 | 1.35 | 35146.96 | 01-JUN-00:10 | 1.35 |
July | 0.941376E+11 | 1.35 | 35146.96 | 01-JUL-00:10 | 1.35 |
August | 0.941376E+11 | 1.35 | 35146.96 | 01-AUG-00:05 | 1.35 |
September | 0.911009E+11 | 1.35 | 35146.96 | 01-SEP-00:03 | 1.35 |
October | 0.941376E+11 | 1.35 | 35146.96 | 01-OCT-00:10 | 1.35 |
November | 0.911009E+11 | 1.35 | 35146.96 | 01-NOV-00:10 | 1.35 |
December | 0.941376E+11 | 1.35 | 35146.96 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.110839E+13 | 1.35 | |||
Minimum of Months | 0.850275E+11 | 1.35 | 35146.96 | 1.35 | |
Maximum of Months | 0.941376E+11 | 1.35 | 35146.96 | 1.35 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.139140E+10 | 0.93 | 519.49 | 01-JAN-00:01 | 0.93 |
February | 0.125675E+10 | 0.93 | 519.49 | 01-FEB-00:10 | 0.93 |
March | 0.139140E+10 | 0.93 | 519.49 | 01-MAR-00:10 | 0.93 |
April | 0.134651E+10 | 0.93 | 519.49 | 01-APR-00:10 | 0.93 |
May | 0.139140E+10 | 0.93 | 519.49 | 01-MAY-00:10 | 0.93 |
June | 0.134651E+10 | 0.93 | 519.49 | 01-JUN-00:10 | 0.93 |
July | 0.139140E+10 | 0.93 | 519.49 | 01-JUL-00:10 | 0.93 |
August | 0.139140E+10 | 0.93 | 519.49 | 01-AUG-00:05 | 0.93 |
September | 0.134651E+10 | 0.93 | 519.49 | 01-SEP-00:03 | 0.93 |
October | 0.139140E+10 | 0.93 | 519.49 | 01-OCT-00:10 | 0.93 |
November | 0.134651E+10 | 0.93 | 519.49 | 01-NOV-00:10 | 0.93 |
December | 0.139140E+10 | 0.93 | 519.49 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.163826E+11 | 0.93 | |||
Minimum of Months | 0.125675E+10 | 0.93 | 519.49 | 0.93 | |
Maximum of Months | 0.139140E+10 | 0.93 | 519.49 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.132705E+11 | 0.93 | 4954.65 | 01-JAN-00:01 | 0.93 |
February | 0.119863E+11 | 0.93 | 4954.65 | 01-FEB-00:10 | 0.93 |
March | 0.132705E+11 | 0.93 | 4954.65 | 01-MAR-00:10 | 0.93 |
April | 0.128424E+11 | 0.93 | 4954.65 | 01-APR-00:10 | 0.93 |
May | 0.132705E+11 | 0.93 | 4954.65 | 01-MAY-00:10 | 0.93 |
June | 0.128424E+11 | 0.93 | 4954.65 | 01-JUN-00:10 | 0.93 |
July | 0.132705E+11 | 0.93 | 4954.65 | 01-JUL-00:10 | 0.93 |
August | 0.132705E+11 | 0.93 | 4954.65 | 01-AUG-00:05 | 0.93 |
September | 0.128424E+11 | 0.93 | 4954.65 | 01-SEP-00:03 | 0.93 |
October | 0.132705E+11 | 0.93 | 4954.65 | 01-OCT-00:20 | 0.93 |
November | 0.128424E+11 | 0.93 | 4954.65 | 01-NOV-00:10 | 0.93 |
December | 0.132705E+11 | 0.93 | 4954.65 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.156250E+12 | 0.93 | |||
Minimum of Months | 0.119863E+11 | 0.93 | 4954.65 | 0.93 | |
Maximum of Months | 0.132705E+11 | 0.93 | 4954.65 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.135154E+10 | 0.93 | 504.61 | 01-JAN-00:01 | 0.93 |
February | 0.122075E+10 | 0.93 | 504.61 | 01-FEB-00:10 | 0.93 |
March | 0.135154E+10 | 0.93 | 504.61 | 01-MAR-00:10 | 0.93 |
April | 0.130794E+10 | 0.93 | 504.61 | 01-APR-00:10 | 0.93 |
May | 0.135154E+10 | 0.93 | 504.61 | 01-MAY-00:10 | 0.93 |
June | 0.130794E+10 | 0.93 | 504.61 | 01-JUN-00:10 | 0.93 |
July | 0.135154E+10 | 0.93 | 504.61 | 01-JUL-00:10 | 0.93 |
August | 0.135154E+10 | 0.93 | 504.61 | 01-AUG-00:05 | 0.93 |
September | 0.130794E+10 | 0.93 | 504.61 | 01-SEP-00:03 | 0.93 |
October | 0.135154E+10 | 0.93 | 504.61 | 01-OCT-00:10 | 0.93 |
November | 0.130794E+10 | 0.93 | 504.61 | 01-NOV-00:10 | 0.93 |
December | 0.135154E+10 | 0.93 | 504.61 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.159133E+11 | 0.93 | |||
Minimum of Months | 0.122075E+10 | 0.93 | 504.61 | 0.93 | |
Maximum of Months | 0.135154E+10 | 0.93 | 504.61 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.469618E+10 | 0.422656E+10 | 14682.96 | 02-JAN-07:10 | 13214.67 | 13214.67 | 69.62 | 37.55 |
February | 0.286768E+10 | 0.258091E+10 | 13604.50 | 06-FEB-07:10 | 12244.05 | 12244.05 | 69.07 | 29.59 |
March | 0.112889E+10 | 0.101600E+10 | 8565.65 | 13-MAR-05:01 | 7709.09 | 7709.09 | 66.01 | 13.22 |
April | 0.205010E+09 | 0.184509E+09 | 8245.95 | 03-APR-05:01 | 7421.36 | 7421.36 | 60.81 | 12.58 |
May | 57426478.78 | 51683830.90 | 6739.59 | 02-MAY-03:57 | 6065.64 | 6065.64 | 74.22 | 9.62 |
June | 25402064.64 | 22861858.17 | 4550.20 | 20-JUN-03:45 | 4095.18 | 4095.18 | 70.92 | 6.05 |
July | 14390715.29 | 12951643.76 | 4549.91 | 08-JUL-03:45 | 4094.92 | 4094.92 | 70.80 | 6.05 |
August | 34235798.84 | 30812218.95 | 4550.39 | 18-AUG-03:50 | 4095.35 | 4095.35 | 71.00 | 6.05 |
September | 32458356.74 | 29212521.06 | 4549.84 | 22-SEP-03:45 | 4094.85 | 4094.85 | 70.77 | 6.05 |
October | 0.246692E+09 | 0.222023E+09 | 5617.63 | 19-OCT-03:47 | 5055.87 | 5055.87 | 78.36 | 7.69 |
November | 0.978764E+09 | 0.880888E+09 | 8841.84 | 24-NOV-07:10 | 7957.65 | 7957.65 | 64.86 | 13.82 |
December | 0.105962E+10 | 0.953659E+09 | 8589.97 | 26-DEC-06:01 | 7730.97 | 7730.97 | 61.57 | 13.30 |
Annual Sum or Average | 0.113468E+11 | 0.102121E+11 | ||||||
Minimum of Months | 14390715.29 | 12951643.76 | 4549.84 | 4094.85 | 4094.85 | 60.81 | 6.05 | |
Maximum of Months | 0.469618E+10 | 0.422656E+10 | 14682.96 | 13214.67 | 13214.67 | 78.36 | 37.55 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 20831.52 | 18748.37 | 32.68 | 24-JAN-06:02 | 29.42 | 29.42 | 7.08 | 3.92 |
February | 44181.55 | 39763.39 | 27.04 | 10-FEB-12:20 | 24.34 | 24.34 | 7.73 | 3.43 |
March | 19820993.06 | 17838893.75 | 1396.83 | 27-MAR-13:00 | 1257.15 | 1257.15 | 9.00 | 32.69 |
April | 0.172843E+09 | 0.155558E+09 | 4472.99 | 07-APR-14:30 | 4025.69 | 4025.69 | 7.21 | 55.19 |
May | 0.641702E+09 | 0.577532E+09 | 4570.54 | 30-MAY-14:00 | 4113.48 | 4113.48 | 6.72 | 55.71 |
June | 0.288219E+10 | 0.259397E+10 | 24549.93 | 15-JUN-05:02 | 22094.94 | 22094.94 | 8.31 | 111.36 |
July | 0.334005E+10 | 0.300605E+10 | 27164.49 | 15-JUL-05:02 | 24448.04 | 24448.04 | 8.21 | 115.88 |
August | 0.338142E+10 | 0.304328E+10 | 21516.13 | 12-AUG-05:02 | 19364.52 | 19364.52 | 7.97 | 105.69 |
September | 0.196063E+10 | 0.176457E+10 | 27076.76 | 08-SEP-05:02 | 24369.09 | 24369.09 | 8.18 | 115.74 |
October | 0.979432E+09 | 0.881489E+09 | 11802.12 | 06-OCT-05:02 | 10621.91 | 10621.91 | 8.46 | 82.98 |
November | 12180749.02 | 10962674.12 | 498.36 | 04-NOV-12:40 | 448.52 | 448.52 | 8.64 | 19.75 |
December | 110206.87 | 99186.19 | 52.56 | 11-DEC-11:50 | 47.30 | 47.30 | 8.41 | 5.41 |
Annual Sum or Average | 0.133904E+11 | 0.120514E+11 | ||||||
Minimum of Months | 20831.52 | 18748.37 | 27.04 | 24.34 | 24.34 | 6.72 | 3.43 | |
Maximum of Months | 0.338142E+10 | 0.304328E+10 | 27164.49 | 24448.04 | 24448.04 | 9.00 | 115.88 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967962.60 | 3590388.78 | 5.96 | 01-JAN-06:02 | 1.79 | 1.79 | 70.60 | 0.44 |
February | 10809772.67 | 3242931.80 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 59.27 | 0.44 |
March | 11967962.60 | 3590388.78 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 62.79 | 0.44 |
April | 11581899.29 | 3474569.79 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 62.74 | 0.44 |
May | 11967962.60 | 3590388.78 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 71.68 | 0.44 |
June | 11581899.29 | 3474569.79 | 5.96 | 01-JUN-05:01 | 1.79 | 1.79 | 59.22 | 0.44 |
July | 11967962.60 | 3590388.78 | 5.96 | 01-JUL-05:01 | 1.79 | 1.79 | 60.50 | 0.44 |
August | 11967962.60 | 3590388.78 | 5.96 | 01-AUG-05:01 | 1.79 | 1.79 | 60.70 | 0.44 |
September | 11581899.29 | 3474569.79 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 65.49 | 0.44 |
October | 11967962.60 | 3590388.78 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 72.11 | 0.44 |
November | 11581899.29 | 3474569.79 | 5.96 | 01-NOV-05:01 | 1.79 | 1.79 | 59.91 | 0.44 |
December | 11967962.60 | 3590388.78 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 63.74 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273932.42 | ||||||
Minimum of Months | 10809772.67 | 3242931.80 | 5.96 | 1.79 | 1.79 | 59.22 | 0.44 | |
Maximum of Months | 11967962.60 | 3590388.78 | 5.96 | 1.79 | 1.79 | 72.11 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.135175E+10 | 0.121657E+10 | 9420.11 | 02-JAN-08:50 | 8478.10 | 8478.10 | 8.40 | 117.98 |
February | 0.138006E+10 | 0.124206E+10 | 9420.11 | 01-FEB-14:00 | 8478.10 | 8478.10 | 8.40 | 117.98 |
March | 0.244681E+10 | 0.220213E+10 | 9420.11 | 01-MAR-09:00 | 8478.10 | 8478.10 | 8.40 | 117.98 |
April | 0.523079E+10 | 0.470771E+10 | 9420.11 | 01-APR-06:20 | 8478.10 | 8478.10 | 8.40 | 117.98 |
May | 0.127376E+11 | 0.114638E+11 | 9420.11 | 01-MAY-01:41 | 8478.10 | 8478.10 | 8.44 | 117.98 |
June | 0.175793E+11 | 0.158214E+11 | 9420.11 | 01-JUN-03:01 | 8478.10 | 8478.10 | 9.81 | 117.98 |
July | 0.203793E+11 | 0.183413E+11 | 9420.11 | 01-JUL-03:01 | 8478.10 | 8478.10 | 10.18 | 117.98 |
August | 0.216086E+11 | 0.194477E+11 | 9420.11 | 01-AUG-00:20 | 8478.10 | 8478.10 | 7.37 | 117.98 |
September | 0.151443E+11 | 0.136299E+11 | 9420.11 | 01-SEP-00:03 | 8478.10 | 8478.10 | 7.44 | 117.98 |
October | 0.950136E+10 | 0.855122E+10 | 9420.11 | 01-OCT-19:41 | 8478.10 | 8478.10 | 8.31 | 117.98 |
November | 0.270255E+10 | 0.243229E+10 | 9420.11 | 01-NOV-03:08 | 8478.10 | 8478.10 | 8.46 | 117.98 |
December | 0.240085E+10 | 0.216077E+10 | 9420.11 | 01-DEC-09:40 | 8478.10 | 8478.10 | 8.40 | 117.98 |
Annual Sum or Average | 0.112463E+12 | 0.101217E+12 | ||||||
Minimum of Months | 0.135175E+10 | 0.121657E+10 | 9420.11 | 8478.10 | 8478.10 | 7.37 | 117.98 | |
Maximum of Months | 0.216086E+11 | 0.194477E+11 | 9420.11 | 8478.10 | 8478.10 | 10.18 | 117.98 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.892180E+10 | 0.802962E+10 | 3331.02 | 01-JAN-00:01 | 2997.92 | 2997.92 | 21.36 | 13.91 |
February | 0.805840E+10 | 0.725256E+10 | 3331.02 | 01-FEB-00:10 | 2997.92 | 2997.92 | 24.00 | 13.91 |
March | 0.892180E+10 | 0.802962E+10 | 3331.02 | 01-MAR-00:10 | 2997.92 | 2997.92 | 26.74 | 13.91 |
April | 0.863400E+10 | 0.777060E+10 | 3331.02 | 01-APR-00:10 | 2997.92 | 2997.92 | 29.69 | 13.91 |
May | 0.892180E+10 | 0.802962E+10 | 3331.02 | 01-MAY-00:10 | 2997.92 | 2997.92 | 23.11 | 13.91 |
June | 0.863400E+10 | 0.777060E+10 | 3331.02 | 01-JUN-00:10 | 2997.92 | 2997.92 | 26.53 | 13.91 |
July | 0.892180E+10 | 0.802962E+10 | 3331.02 | 01-JUL-00:10 | 2997.92 | 2997.92 | 32.23 | 13.91 |
August | 0.892180E+10 | 0.802962E+10 | 3331.02 | 01-AUG-00:05 | 2997.92 | 2997.92 | 40.18 | 13.91 |
September | 0.863400E+10 | 0.777060E+10 | 3331.02 | 01-SEP-00:03 | 2997.92 | 2997.92 | 35.95 | 13.91 |
October | 0.892180E+10 | 0.802962E+10 | 3331.02 | 01-OCT-00:10 | 2997.92 | 2997.92 | 24.30 | 13.91 |
November | 0.863400E+10 | 0.777060E+10 | 3331.02 | 01-NOV-00:10 | 2997.92 | 2997.92 | 26.96 | 13.91 |
December | 0.892180E+10 | 0.802962E+10 | 3331.02 | 01-DEC-00:10 | 2997.92 | 2997.92 | 29.64 | 13.91 |
Annual Sum or Average | 0.105047E+12 | 0.945423E+11 | ||||||
Minimum of Months | 0.805840E+10 | 0.725256E+10 | 3331.02 | 2997.92 | 2997.92 | 21.36 | 13.91 | |
Maximum of Months | 0.892180E+10 | 0.802962E+10 | 3331.02 | 2997.92 | 2997.92 | 40.18 | 13.91 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.251757E+10 | 0.226581E+10 | 17607.87 | 19-JAN-14:05 | 15847.08 | 15847.08 | 21.15 | 69.15 |
February | 0.256082E+10 | 0.230474E+10 | 17609.28 | 10-FEB-12:20 | 15848.35 | 15848.35 | 21.26 | 69.15 |
March | 0.458482E+10 | 0.412634E+10 | 35268.01 | 27-MAR-13:20 | 31741.21 | 31741.21 | 23.20 | 138.30 |
April | 0.981127E+10 | 0.883014E+10 | 35303.63 | 07-APR-13:50 | 31773.26 | 31773.26 | 24.61 | 138.30 |
May | 0.247111E+11 | 0.222400E+11 | 35405.93 | 31-MAY-13:50 | 31865.34 | 31865.34 | 28.11 | 138.30 |
June | 0.422351E+11 | 0.380116E+11 | 35426.55 | 07-JUN-09:40 | 31883.90 | 31883.90 | 29.04 | 138.30 |
July | 0.523923E+11 | 0.471530E+11 | 35426.55 | 03-JUL-12:10 | 31883.90 | 31883.90 | 28.92 | 138.30 |
August | 0.533306E+11 | 0.479975E+11 | 35426.55 | 01-AUG-08:00 | 31883.90 | 31883.90 | 29.04 | 138.30 |
September | 0.342191E+11 | 0.307972E+11 | 35426.55 | 05-SEP-14:40 | 31883.90 | 31883.90 | 28.87 | 138.30 |
October | 0.194366E+11 | 0.174929E+11 | 35390.37 | 24-OCT-13:50 | 31851.34 | 31851.34 | 27.59 | 138.30 |
November | 0.504647E+10 | 0.454182E+10 | 17630.69 | 10-NOV-10:00 | 15867.62 | 15867.62 | 22.95 | 69.15 |
December | 0.447480E+10 | 0.402732E+10 | 17610.33 | 11-DEC-11:50 | 15849.30 | 15849.30 | 21.34 | 69.15 |
Annual Sum or Average | 0.255320E+12 | 0.229788E+12 | ||||||
Minimum of Months | 0.251757E+10 | 0.226581E+10 | 17607.87 | 15847.08 | 15847.08 | 21.15 | 69.15 | |
Maximum of Months | 0.533306E+11 | 0.479975E+11 | 35426.55 | 31883.90 | 31883.90 | 29.04 | 138.30 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3898.76 | 34138.37 | 16-JAN-11:00 | 78.48 | 80.49 | 14032.02 | 64949.58 | 26-JAN-12:07 |
February | 3523.19 | 33944.41 | 20-FEB-11:00 | 78.38 | 80.40 | 14333.22 | 62614.12 | 02-FEB-13:08 |
March | 2813.98 | 33555.71 | 27-MAR-05:08 | 78.17 | 81.55 | 15090.39 | 62284.79 | 13-MAR-11:47 |
April | 3952.50 | 33656.93 | 03-APR-05:08 | 78.22 | 81.56 | 13226.73 | 53996.92 | 12-APR-11:10 |
May | 4652.18 | 37944.34 | 29-MAY-09:25 | 80.53 | 82.22 | 12778.76 | 48337.45 | 01-MAY-11:30 |
June | 4539.01 | 38129.90 | 25-JUN-22:52 | 80.63 | 82.22 | 12170.24 | 44841.86 | 01-JUN-11:20 |
July | 6433.11 | 38262.07 | 30-JUL-18:27 | 80.70 | 82.22 | 10312.00 | 41945.78 | 03-JUL-11:40 |
August | 4889.95 | 38270.08 | 13-AUG-19:05 | 80.71 | 82.22 | 11444.25 | 43277.87 | 08-AUG-11:10 |
September | 5734.58 | 38231.42 | 03-SEP-22:50 | 80.69 | 82.22 | 10922.35 | 42871.53 | 29-SEP-12:00 |
October | 5769.93 | 38041.82 | 09-OCT-09:10 | 80.59 | 82.22 | 11614.14 | 48902.66 | 27-OCT-11:30 |
November | 4949.32 | 37726.93 | 12-NOV-11:00 | 80.42 | 82.21 | 12719.19 | 58530.32 | 22-NOV-12:58 |
December | 4180.64 | 35159.20 | 25-DEC-11:00 | 79.03 | 80.99 | 13084.72 | 61122.33 | 13-DEC-12:18 |
Annual Sum or Average | 4618.37 | 12634.33 | ||||||
Minimum of Months | 2813.98 | 33555.71 | 78.17 | 80.40 | 10312.00 | 41945.78 | ||
Maximum of Months | 6433.11 | 38270.08 | 80.71 | 82.22 | 15090.39 | 64949.58 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 13.12 | 4735.13 | 16-JAN-15:15 | 80.56 | 80.56 | 80508.36 | 1980696.16 | 02-JAN-07:10 |
February | 3.23 | 1848.52 | 26-FEB-16:30 | 81.60 | 81.60 | 62997.97 | 1628723.13 | 06-FEB-07:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 69.19 | 69.19 | 22640.29 | 862889.27 | 23-MAR-06:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 73.56 | 73.56 | 7187.15 | 1043829.86 | 03-APR-05:01 |
May | 0.27 | 822.91 | 01-MAY-21:00 | 79.57 | 79.57 | 637.15 | 514721.26 | 16-MAY-03:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 68.44 | 68.44 | 527.32 | 290664.47 | 23-JUN-03:47 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 70.30 | 70.30 | 283.40 | 303802.17 | 13-JUL-03:45 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 70.74 | 70.74 | 710.40 | 399454.90 | 31-AUG-03:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 64.33 | 64.33 | 650.13 | 323448.07 | 02-SEP-03:45 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 68.72 | 68.72 | 2214.35 | 372782.25 | 07-OCT-03:47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 71.39 | 71.39 | 23088.54 | 980956.40 | 24-NOV-07:10 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 66.87 | 66.87 | 46693.55 | 1326065.03 | 28-DEC-05:01 |
Annual Sum or Average | 1.39 | 20470.82 | ||||||
Minimum of Months | 0.00 | 0.00 | 64.33 | 64.33 | 283.40 | 290664.47 | ||
Maximum of Months | 13.12 | 4735.13 | 81.60 | 81.60 | 80508.36 | 1980696.16 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 902.02 | 22859.28 | 30-JAN-11:30 | 8.42 | 8.39 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1098.22 | 77257.34 | 10-FEB-12:20 | 8.53 | 8.45 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 15084.12 | 1404586.72 | 27-MAR-13:20 | 10.43 | 8.99 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 98567.54 | 1448286.15 | 07-APR-11:40 | 9.91 | 8.37 | 6.28 | 35994.13 | 08-APR-00:52 |
May | 332357.43 | 1660209.40 | 30-MAY-13:30 | 10.06 | 6.70 | 0.54 | 15013.71 | 29-MAY-20:51 |
June | 770483.65 | 2397474.90 | 20-JUN-05:02 | 12.44 | 7.59 | 5.78 | 45860.45 | 11-JUN-05:52 |
July | 880627.51 | 2849722.10 | 22-JUL-05:03 | 12.80 | 7.12 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 886565.21 | 2708856.94 | 17-AUG-05:02 | 12.42 | 6.94 | 2.59 | 24869.82 | 20-AUG-01:42 |
September | 602549.13 | 2564630.83 | 08-SEP-05:03 | 12.64 | 7.45 | 11.37 | 93709.23 | 24-SEP-22:51 |
October | 302979.48 | 1986873.50 | 06-OCT-05:03 | 11.82 | 7.80 | 0.64 | 28375.15 | 01-OCT-19:41 |
November | 18451.97 | 754652.87 | 10-NOV-10:00 | 9.82 | 9.05 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1932.08 | 189890.93 | 25-DEC-16:01 | 8.75 | 8.56 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 328126.58 | 2.25 | ||||||
Minimum of Months | 902.02 | 22859.28 | 8.42 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 886565.21 | 2849722.10 | 12.80 | 9.05 | 11.37 | 93709.23 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 6.39 | 15605.46 | 24-JAN-06:02 | 7.65 | 8.38 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 60.24 | 71452.90 | 10-FEB-12:20 | 11.67 | 8.39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 9410.67 | 1055305.33 | 27-MAR-13:00 | 14.41 | 8.99 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 66864.78 | 1404004.81 | 07-APR-12:00 | 12.99 | 8.05 | 0.00 | 0.00 | 01-APR-00:10 |
May | 238838.44 | 1685784.89 | 31-MAY-08:40 | 14.48 | 7.07 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 698873.91 | 3448380.17 | 15-JUN-05:02 | 14.10 | 8.12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 798089.14 | 3561631.08 | 15-JUL-05:02 | 14.04 | 8.04 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 778770.09 | 3232398.87 | 12-AUG-05:02 | 14.01 | 7.78 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 507386.56 | 3555621.08 | 14-SEP-05:02 | 14.05 | 7.95 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 256467.00 | 2639078.74 | 06-OCT-05:02 | 14.30 | 8.21 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 11257.15 | 576649.07 | 04-NOV-12:40 | 13.67 | 8.62 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 207.81 | 180588.07 | 11-DEC-11:50 | 14.67 | 8.39 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 282379.82 | 0.00 | ||||||
Minimum of Months | 6.39 | 15605.46 | 7.65 | 7.07 | 0.00 | 0.00 | ||
Maximum of Months | 798089.14 | 3561631.08 | 14.67 | 8.99 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 154485.96 | 543031.03 | 21-JAN-05:20 | 29.48 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 290517.35 | 575481.87 | 15-FEB-23:01 | 30.14 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 436767.55 | 847640.69 | 27-MAR-16:00 | 35.64 | 26.13 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 629902.21 | 1295063.87 | 07-APR-13:00 | 44.55 | 31.97 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237558.40 | 854000.59 | 30-MAY-13:00 | 35.77 | 31.69 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 625439.57 | 1445720.64 | 19-JUN-12:00 | 47.52 | 39.91 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1015451.43 | 1520355.59 | 07-JUL-12:00 | 48.98 | 38.38 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1201736.80 | 1687875.30 | 24-AUG-16:00 | 52.26 | 39.37 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 362633.70 | 921926.34 | 01-SEP-14:00 | 37.13 | 32.87 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 368984.09 | 803335.23 | 04-OCT-13:00 | 34.75 | 27.85 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 437910.54 | 617723.91 | 03-NOV-14:00 | 31.00 | 21.64 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 566497.66 | 616448.83 | 27-DEC-22:20 | 30.97 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 529416.45 | 0.00 | ||||||
Minimum of Months | 154485.96 | 543031.03 | 29.48 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1201736.80 | 1687875.30 | 52.26 | 39.91 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 21.11 | 13903.22 | 19-JAN-14:05 | 21.15 | 20.52 | 1660.18 | 134848.98 | 06-JAN-06:41 |
February | 64.53 | 46077.74 | 10-FEB-12:20 | 21.26 | 20.50 | 1805.01 | 133668.35 | 22-FEB-13:40 |
March | 9621.19 | 1214717.57 | 27-MAR-13:20 | 23.20 | 22.32 | 2021.96 | 123923.30 | 13-MAR-06:20 |
April | 70556.74 | 2027609.39 | 07-APR-13:50 | 24.61 | 21.68 | 889.37 | 92207.85 | 03-APR-09:00 |
May | 285207.75 | 4054556.80 | 31-MAY-13:50 | 28.11 | 25.03 | 598.67 | 87708.16 | 13-MAY-09:20 |
June | 1284759.19 | 6158906.34 | 15-JUN-12:20 | 31.75 | 28.55 | 126.88 | 90750.63 | 02-JUN-06:50 |
July | 2105060.72 | 6969633.80 | 20-JUL-15:00 | 33.16 | 29.57 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1809955.72 | 7323725.03 | 02-AUG-15:00 | 33.77 | 30.03 | 46.32 | 30063.15 | 26-AUG-00:10 |
September | 860814.08 | 5768377.13 | 07-SEP-14:10 | 31.08 | 27.77 | 79.97 | 41568.91 | 23-SEP-10:00 |
October | 307179.90 | 3751884.14 | 24-OCT-13:50 | 27.59 | 24.32 | 576.58 | 97723.77 | 18-OCT-14:50 |
November | 12857.32 | 534446.53 | 10-NOV-10:00 | 22.95 | 21.41 | 1779.81 | 123315.96 | 22-NOV-15:50 |
December | 99.09 | 70018.04 | 11-DEC-11:50 | 21.34 | 20.62 | 2937.99 | 135411.66 | 11-DEC-15:55 |
Annual Sum or Average | 566857.36 | 1040.86 | ||||||
Minimum of Months | 21.11 | 13903.22 | 21.15 | 20.50 | 0.00 | 0.00 | ||
Maximum of Months | 2105060.72 | 7323725.03 | 33.77 | 30.03 | 2937.99 | 135411.66 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.19 | 8.78 |
February | 0.30 | 7.48 |
March | 0.42 | 7.48 |
April | 0.49 | 7.48 |
May | 0.71 | 7.13 |
June | 1.21 | 7.27 |
July | 0.46 | 7.48 |
August | 0.50 | 7.48 |
September | 1.00 | 7.48 |
October | 0.61 | 7.48 |
November | 0.75 | 7.48 |
December | 1.03 | 7.33 |
Annual Sum or Average | 7.67 | 7.43 |
Minimum of Months | 0.19 | 7.13 |
Maximum of Months | 1.21 | 8.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.68 | 10.28 |
February | 1.59 | 12.35 |
March | 3.87 | 8.74 |
April | 8.16 | 3.45 |
May | 4.48 | 5.44 |
June | 9.82 | 2.58 |
July | 18.61 | 1.88 |
August | 15.59 | 1.87 |
September | 4.58 | 3.38 |
October | 3.80 | 3.22 |
November | 2.77 | 3.31 |
December | 2.08 | 8.26 |
Annual Sum or Average | 76.03 | 3.37 |
Minimum of Months | 0.68 | 1.87 |
Maximum of Months | 18.61 | 12.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 1.12 | 40.57 |
March | 0.67 | 42.88 |
April | 0.89 | 7.12 |
May | 2.17 | 6.31 |
June | 2.92 | 4.39 |
July | 4.37 | 3.10 |
August | 4.26 | 1.75 |
September | 1.84 | 3.26 |
October | 1.42 | 7.11 |
November | 1.50 | 115.49 |
December | 0.43 | 45.72 |
Annual Sum or Average | 21.61 | 15.60 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.37 | 115.49 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.03 | 0.00 |
March | 0.81 | 5.56 |
April | 0.84 | 7.27 |
May | 1.33 | 7.91 |
June | 2.13 | 3.63 |
July | 3.39 | 4.34 |
August | 3.12 | 3.15 |
September | 1.09 | 3.22 |
October | 0.62 | 6.11 |
November | 0.39 | 2.88 |
December | 0.06 | 0.00 |
Annual Sum or Average | 13.81 | 4.48 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.39 | 7.91 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 16.03 |
February | 0.64 | 14.71 |
March | 0.75 | 9.03 |
April | 2.03 | 0.35 |
May | 1.42 | 0.47 |
June | 5.93 | 0.27 |
July | 12.55 | 0.26 |
August | 10.61 | 0.28 |
September | 2.04 | 0.18 |
October | 1.51 | 0.26 |
November | 0.49 | 5.57 |
December | 0.53 | 12.74 |
Annual Sum or Average | 38.67 | 0.99 |
Minimum of Months | 0.17 | 0.18 |
Maximum of Months | 12.55 | 16.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.74 | 9.78 |
February | 2.81 | 8.10 |
March | 2.52 | 3.55 |
April | 6.66 | 0.26 |
May | 4.45 | 0.41 |
June | 10.52 | 0.22 |
July | 17.21 | 0.19 |
August | 20.85 | 0.16 |
September | 6.32 | 0.19 |
October | 5.62 | 0.27 |
November | 2.03 | 2.11 |
December | 1.22 | 2.57 |
Annual Sum or Average | 81.95 | 0.87 |
Minimum of Months | 1.22 | 0.16 |
Maximum of Months | 20.85 | 9.78 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 11.70 |
February | 1.47 | 14.83 |
March | 1.03 | 5.52 |
April | 3.20 | 0.38 |
May | 2.72 | 0.54 |
June | 7.47 | 0.31 |
July | 13.65 | 0.26 |
August | 13.60 | 0.26 |
September | 3.30 | 0.25 |
October | 2.38 | 0.23 |
November | 0.89 | 3.93 |
December | 0.81 | 9.31 |
Annual Sum or Average | 50.97 | 1.12 |
Minimum of Months | 0.47 | 0.23 |
Maximum of Months | 13.65 | 14.83 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.23 | 7.26 |
February | 4.94 | 8.00 |
March | 7.36 | 2.53 |
April | 9.67 | 0.24 |
May | 7.55 | 0.40 |
June | 11.30 | 0.23 |
July | 19.54 | 0.19 |
August | 25.69 | 0.16 |
September | 6.67 | 0.20 |
October | 6.82 | 0.25 |
November | 4.30 | 0.21 |
December | 4.40 | 1.68 |
Annual Sum or Average | 110.47 | 0.92 |
Minimum of Months | 2.23 | 0.16 |
Maximum of Months | 25.69 | 8.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.65 | 0.75 |
February | 0.45 | 0.90 |
March | 0.29 | 2.85 |
April | 0.19 | 7.11 |
May | 0.67 | 0.50 |
June | 1.54 | 0.18 |
July | 2.36 | 0.39 |
August | 2.10 | 0.22 |
September | 0.99 | 0.07 |
October | 0.70 | 2.00 |
November | 0.17 | 16.03 |
December | 0.38 | 1.78 |
Annual Sum or Average | 10.49 | 0.95 |
Minimum of Months | 0.17 | 0.07 |
Maximum of Months | 2.36 | 16.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.11 | 0.54 |
February | 1.46 | 2.76 |
March | 0.94 | 4.94 |
April | 1.53 | 3.11 |
May | 3.54 | 0.50 |
June | 5.95 | 0.28 |
July | 8.44 | 0.31 |
August | 7.86 | 0.18 |
September | 4.06 | 0.27 |
October | 3.37 | 1.38 |
November | 0.50 | 8.76 |
December | 0.50 | 2.08 |
Annual Sum or Average | 38.26 | 0.84 |
Minimum of Months | 0.11 | 0.18 |
Maximum of Months | 8.44 | 8.76 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.26 | 4.18 |
February | 0.48 | 7.49 |
March | 0.60 | 9.95 |
April | 0.53 | 3.10 |
May | 1.13 | 0.74 |
June | 2.27 | 0.25 |
July | 3.28 | 0.43 |
August | 2.95 | 0.27 |
September | 1.45 | 0.13 |
October | 1.43 | 1.37 |
November | 0.68 | 14.27 |
December | 0.31 | 2.22 |
Annual Sum or Average | 15.36 | 1.85 |
Minimum of Months | 0.26 | 0.13 |
Maximum of Months | 3.28 | 14.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 5.89 |
February | 1.30 | 2.19 |
March | 0.74 | 5.24 |
April | 1.90 | 3.06 |
May | 4.29 | 0.53 |
June | 6.26 | 0.31 |
July | 7.45 | 0.29 |
August | 7.53 | 0.19 |
September | 3.80 | 0.26 |
October | 2.76 | 1.57 |
November | 0.42 | 5.00 |
December | 0.74 | 5.02 |
Annual Sum or Average | 37.53 | 0.89 |
Minimum of Months | 0.35 | 0.19 |
Maximum of Months | 7.53 | 5.89 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.96 | 0.68 |
February | 1.71 | 0.79 |
March | 0.60 | 0.89 |
April | 0.39 | 0.99 |
May | 0.57 | 0.62 |
June | 1.66 | 0.31 |
July | 2.90 | 0.44 |
August | 2.71 | 0.36 |
September | 0.98 | 0.30 |
October | 0.13 | 1.20 |
November | 0.12 | 1.41 |
December | 1.10 | 0.88 |
Annual Sum or Average | 13.83 | 0.55 |
Minimum of Months | 0.12 | 0.30 |
Maximum of Months | 2.90 | 1.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.36 | 0.54 |
February | 0.89 | 0.52 |
March | 0.57 | 0.54 |
April | 0.86 | 0.53 |
May | 2.79 | 0.48 |
June | 4.95 | 0.32 |
July | 7.69 | 0.29 |
August | 6.59 | 0.23 |
September | 2.87 | 0.45 |
October | 0.67 | 0.72 |
November | 0.04 | 0.54 |
December | 0.97 | 0.54 |
Annual Sum or Average | 29.25 | 0.36 |
Minimum of Months | 0.04 | 0.23 |
Maximum of Months | 7.69 | 0.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.47 | 0.65 |
February | 0.55 | 0.63 |
March | 0.10 | 0.84 |
April | 0.56 | 0.95 |
May | 1.07 | 0.70 |
June | 2.33 | 0.36 |
July | 3.49 | 0.39 |
August | 3.14 | 0.29 |
September | 1.11 | 0.46 |
October | 0.39 | 0.96 |
November | 0.02 | 0.84 |
December | 0.57 | 0.84 |
Annual Sum or Average | 13.81 | 0.47 |
Minimum of Months | 0.02 | 0.29 |
Maximum of Months | 3.49 | 0.96 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.29 | 0.54 |
February | 0.50 | 0.54 |
March | 0.21 | 0.54 |
April | 1.07 | 0.52 |
May | 3.39 | 0.52 |
June | 5.25 | 0.34 |
July | 6.74 | 0.28 |
August | 6.70 | 0.21 |
September | 3.02 | 0.44 |
October | 0.85 | 0.74 |
November | 0.04 | 0.54 |
December | 0.81 | 0.54 |
Annual Sum or Average | 28.86 | 0.36 |
Minimum of Months | 0.04 | 0.21 |
Maximum of Months | 6.74 | 0.74 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 16.41 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 16.41 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 16.41 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 22.33 | 0.00 |
February | 0.42 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 22.74 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 22.33 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 9.48 | 0.00 |
February | 12.84 | 0.00 |
March | 1.53 | 0.00 |
April | 1.84 | 0.00 |
May | 0.40 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.14 | 0.00 |
November | 1.66 | 0.00 |
December | 4.14 | 0.00 |
Annual Sum or Average | 32.03 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 12.84 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.293204E+09 | 0.00 | 8852447.20 | 0.132351E+11 | 0.00 | 0.00 |
February | 0.481784E+09 | 0.00 | 206.81 | 0.123144E+11 | 0.00 | 0.00 |
March | 0.316592E+09 | 0.00 | 0.677044E+09 | 0.145742E+11 | 0.00 | 0.00 |
April | 0.617808E+09 | 0.00 | 0.586349E+10 | 0.135217E+11 | 0.00 | 0.00 |
May | 0.626994E+09 | 0.00 | 0.172950E+11 | 0.144267E+11 | 0.00 | 0.00 |
June | 0.974511E+09 | 0.00 | 0.696316E+11 | 0.144815E+11 | 0.00 | 0.00 |
July | 0.622617E+09 | 0.00 | 0.984115E+11 | 0.142841E+11 | 0.00 | 0.00 |
August | 0.112077E+10 | 0.00 | 0.985475E+11 | 0.155113E+11 | 0.00 | 0.00 |
September | 0.151082E+10 | 0.00 | 0.528878E+11 | 0.147188E+11 | 0.00 | 0.00 |
October | 0.147942E+10 | 0.00 | 0.209233E+11 | 0.150478E+11 | 0.00 | 0.00 |
November | 0.143931E+10 | 0.00 | 0.278698E+09 | 0.142670E+11 | 0.00 | 0.00 |
December | 0.504864E+09 | 0.00 | 2931514.16 | 0.140001E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.998870E+10 | 0.00 | 0.364528E+12 | 0.170383E+12 | 0.00 | 0.00 |
Minimum of Months | 0.293204E+09 | 0.00 | 206.81 | 0.123144E+11 | 0.00 | 0.00 |
Maximum of Months | 0.151082E+10 | 0.00 | 0.985475E+11 | 0.155113E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.393116E+10 | 0.00 | 22739308.61 | 0.460445E+10 | 0.00 | 0.00 |
February | 0.487049E+10 | 0.00 | 15070375.75 | 0.493436E+10 | 0.00 | 0.00 |
March | 0.176232E+10 | 0.00 | 0.206955E+10 | 0.708757E+10 | 0.00 | 0.00 |
April | 0.247064E+09 | 0.00 | 0.145356E+11 | 0.718450E+10 | 0.00 | 0.00 |
May | 20223960.57 | 0.00 | 0.451761E+11 | 0.585093E+10 | 0.00 | 0.00 |
June | 29024611.93 | 0.00 | 0.136119E+12 | 0.649433E+10 | 0.00 | 0.00 |
July | 10116162.59 | 0.00 | 0.179293E+12 | 0.737938E+10 | 0.00 | 0.00 |
August | 52610971.46 | 0.00 | 0.179317E+12 | 0.896658E+10 | 0.00 | 0.00 |
September | 20484555.39 | 0.00 | 0.937192E+11 | 0.579166E+10 | 0.00 | 0.00 |
October | 0.147839E+09 | 0.00 | 0.492143E+11 | 0.683793E+10 | 0.00 | 0.00 |
November | 0.798152E+09 | 0.00 | 0.224935E+10 | 0.640536E+10 | 0.00 | 0.00 |
December | 0.180445E+10 | 0.00 | 16987377.55 | 0.650559E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.136939E+11 | 0.00 | 0.701748E+12 | 0.780426E+11 | 0.00 | 0.00 |
Minimum of Months | 10116162.59 | 0.00 | 15070375.75 | 0.460445E+10 | 0.00 | 0.00 |
Maximum of Months | 0.487049E+10 | 0.00 | 0.179317E+12 | 0.896658E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.177736E+12 | 0.00 | 45543857.28 | 0.342873E+11 | 0.00 | 0.00 |
February | 0.121012E+12 | 0.00 | 0.182768E+09 | 0.319527E+11 | 0.00 | 0.00 |
March | 0.490059E+11 | 0.00 | 0.144735E+11 | 0.412689E+11 | 0.00 | 0.00 |
April | 0.142286E+11 | 0.00 | 0.100698E+12 | 0.399637E+11 | 0.00 | 0.00 |
May | 0.428338E+09 | 0.00 | 0.387869E+12 | 0.455884E+11 | 0.00 | 0.00 |
June | 0.313241E+09 | 0.00 | 0.114969E+13 | 0.505394E+11 | 0.00 | 0.00 |
July | 0.121445E+09 | 0.00 | 0.145073E+13 | 0.541408E+11 | 0.00 | 0.00 |
August | 0.848866E+09 | 0.00 | 0.139121E+13 | 0.631877E+11 | 0.00 | 0.00 |
September | 50429620.69 | 0.00 | 0.823002E+12 | 0.467238E+11 | 0.00 | 0.00 |
October | 0.319157E+10 | 0.00 | 0.401871E+12 | 0.466391E+11 | 0.00 | 0.00 |
November | 0.466880E+11 | 0.00 | 0.173156E+11 | 0.366872E+11 | 0.00 | 0.00 |
December | 0.103142E+12 | 0.00 | 0.392039E+09 | 0.354992E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.516766E+12 | 0.00 | 0.573747E+13 | 0.526478E+12 | 0.00 | 0.00 |
Minimum of Months | 50429620.69 | 0.00 | 45543857.28 | 0.319527E+11 | 0.00 | 0.00 |
Maximum of Months | 0.177736E+12 | 0.00 | 0.145073E+13 | 0.631877E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.345493E+11 | 0.00 | 10373092.09 | 0.403908E+10 | 0.00 | 0.00 |
February | 0.277457E+11 | 0.00 | 14773896.69 | 0.354262E+10 | 0.00 | 0.00 |
March | 0.103356E+11 | 0.00 | 0.134886E+10 | 0.368721E+10 | 0.00 | 0.00 |
April | 0.371832E+10 | 0.00 | 0.104179E+11 | 0.365661E+10 | 0.00 | 0.00 |
May | 0.255293E+09 | 0.00 | 0.409778E+11 | 0.450717E+10 | 0.00 | 0.00 |
June | 40155912.47 | 0.00 | 0.124874E+12 | 0.560504E+10 | 0.00 | 0.00 |
July | 10942469.84 | 0.00 | 0.161695E+12 | 0.628469E+10 | 0.00 | 0.00 |
August | 37950948.99 | 0.00 | 0.152893E+12 | 0.717689E+10 | 0.00 | 0.00 |
September | 51584176.93 | 0.00 | 0.856150E+11 | 0.472651E+10 | 0.00 | 0.00 |
October | 0.113236E+10 | 0.00 | 0.394714E+11 | 0.405448E+10 | 0.00 | 0.00 |
November | 0.115571E+11 | 0.00 | 0.155004E+10 | 0.328437E+10 | 0.00 | 0.00 |
December | 0.208307E+11 | 0.00 | 18886879.32 | 0.347712E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110265E+12 | 0.00 | 0.618887E+12 | 0.540418E+11 | 0.00 | 0.00 |
Minimum of Months | 10942469.84 | 0.00 | 10373092.09 | 0.328437E+10 | 0.00 | 0.00 |
Maximum of Months | 0.345493E+11 | 0.00 | 0.161695E+12 | 0.717689E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.379368E+10 | 0.00 | 0.377928E+12 | 0.179602E+12 | 0.00 | 1.76 |
February | 0.134289E+10 | 0.00 | 0.597685E+12 | 0.209495E+12 | 0.00 | 1.99 |
March | 0.312884E+09 | 0.00 | 0.949307E+12 | 0.276477E+12 | 0.00 | 1.40 |
April | 0.225393E+09 | 0.00 | 0.120914E+13 | 0.318308E+12 | 0.00 | 0.71 |
May | 0.374901E+09 | 0.00 | 0.387981E+12 | 0.177501E+12 | 0.00 | 0.28 |
June | 0.00 | 0.00 | 0.681489E+12 | 0.244623E+12 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.103719E+13 | 0.341678E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.134727E+13 | 0.410464E+12 | 0.00 | 0.02 |
September | 0.00 | 0.00 | 0.389573E+12 | 0.178483E+12 | 0.00 | 0.04 |
October | 0.152547E+09 | 0.00 | 0.679872E+12 | 0.231555E+12 | 0.00 | 0.47 |
November | 0.485056E+09 | 0.00 | 0.925024E+12 | 0.267567E+12 | 0.00 | 1.00 |
December | 0.293954E+09 | 0.00 | 0.123987E+13 | 0.324043E+12 | 0.00 | 1.80 |
Annual Sum or Average | 0.698131E+10 | 0.00 | 0.982233E+13 | 0.315980E+13 | 0.00 | 9.49 |
Minimum of Months | 0.00 | 0.00 | 0.377928E+12 | 0.177501E+12 | 0.00 | 0.00 |
Maximum of Months | 0.379368E+10 | 0.00 | 0.134727E+13 | 0.410464E+12 | 0.00 | 1.99 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.496957E+10 | 0.255211E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.105408E+11 | 0.354400E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187384E+11 | 0.524880E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.242915E+11 | 0.628111E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.687003E+10 | 0.302147E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133937E+11 | 0.473602E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210182E+11 | 0.703951E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.253996E+11 | 0.804276E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.691419E+10 | 0.309963E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131506E+11 | 0.431439E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181016E+11 | 0.507724E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.246378E+11 | 0.627142E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188026E+12 | 0.592285E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.496957E+10 | 0.255211E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.253996E+11 | 0.804276E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.209456E+11 | 0.183811E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.779704E+11 | 0.292998E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160664E+12 | 0.467868E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220657E+12 | 0.580758E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.578680E+11 | 0.271663E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124238E+12 | 0.444095E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.199083E+12 | 0.668320E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.242384E+12 | 0.767969E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.591147E+11 | 0.280112E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.114543E+12 | 0.390033E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.152276E+12 | 0.447168E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.209084E+12 | 0.553895E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163883E+13 | 0.534869E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.209456E+11 | 0.183811E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.242384E+12 | 0.767969E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.101368E+10 | 0.160454E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.580460E+10 | 0.253680E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.145435E+11 | 0.442501E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.211510E+11 | 0.568612E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.541290E+10 | 0.266413E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124309E+11 | 0.447635E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200565E+11 | 0.675717E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.246124E+11 | 0.781608E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.562739E+10 | 0.276579E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.105339E+11 | 0.374579E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.134115E+11 | 0.415931E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.186038E+11 | 0.516445E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.153202E+12 | 0.518015E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.101368E+10 | 0.160454E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.246124E+11 | 0.781608E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132351E+11 | 8852447.20 | 0.293204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123144E+11 | 206.81 | 0.481784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145742E+11 | 0.677044E+09 | 0.316592E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135217E+11 | 0.586349E+10 | 0.617808E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144267E+11 | 0.172950E+11 | 0.626994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144815E+11 | 0.696316E+11 | 0.974511E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142841E+11 | 0.984115E+11 | 0.622617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155113E+11 | 0.985475E+11 | 0.112077E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147188E+11 | 0.528878E+11 | 0.151082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150478E+11 | 0.209233E+11 | 0.147942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142670E+11 | 0.278698E+09 | 0.143931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140001E+11 | 2931514.16 | 0.504864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170383E+12 | 0.364528E+12 | 0.998870E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.123144E+11 | 206.81 | 0.293204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155113E+11 | 0.985475E+11 | 0.151082E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.460445E+10 | 22739308.61 | 0.393116E+10 | 0.342486E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.493436E+10 | 15070375.75 | 0.487049E+10 | 0.295515E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708757E+10 | 0.206955E+10 | 0.176232E+10 | 0.130851E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.718450E+10 | 0.145356E+11 | 0.247064E+09 | 0.370068E+10 | 13947976.76 | 0.00 | 0.00 | 0.00 |
May | 0.585093E+10 | 0.451761E+11 | 20223960.57 | 46820839.31 | 0.512050E+09 | 0.00 | 0.00 | 0.00 |
June | 0.649433E+10 | 0.136119E+12 | 29024611.93 | 0.00 | 0.761212E+10 | 0.00 | 0.00 | 0.00 |
July | 0.737938E+10 | 0.179293E+12 | 10116162.59 | 0.00 | 0.299579E+11 | 0.00 | 0.00 | 0.00 |
August | 0.896658E+10 | 0.179317E+12 | 52610971.46 | 0.00 | 0.288165E+11 | 0.00 | 0.00 | 0.00 |
September | 0.579166E+10 | 0.937192E+11 | 20484555.39 | 2009927.18 | 0.403051E+10 | 0.00 | 0.00 | 0.00 |
October | 0.683793E+10 | 0.492143E+11 | 0.147839E+09 | 0.691347E+09 | 29546880.57 | 0.00 | 0.00 | 0.00 |
November | 0.640536E+10 | 0.224935E+10 | 0.798152E+09 | 0.798527E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.650559E+10 | 16987377.55 | 0.180445E+10 | 0.171428E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780426E+11 | 0.701748E+12 | 0.136939E+11 | 0.106454E+12 | 0.709726E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.460445E+10 | 15070375.75 | 10116162.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896658E+10 | 0.179317E+12 | 0.487049E+10 | 0.342486E+11 | 0.299579E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.342873E+11 | 45543857.28 | 0.177736E+12 | 0.476859E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319527E+11 | 0.182768E+09 | 0.121012E+12 | 0.461077E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412689E+11 | 0.144735E+11 | 0.490059E+11 | 0.261001E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399637E+11 | 0.100698E+12 | 0.142286E+11 | 0.825433E+11 | 0.155761E+09 | 0.00 | 0.00 | 0.00 |
May | 0.455884E+11 | 0.387869E+12 | 0.428338E+09 | 0.291842E+10 | 0.516631E+10 | 0.00 | 0.00 | 0.00 |
June | 0.505394E+11 | 0.114969E+13 | 0.313241E+09 | 0.00 | 0.769741E+11 | 0.00 | 0.00 | 0.00 |
July | 0.541408E+11 | 0.145073E+13 | 0.121445E+09 | 0.00 | 0.300413E+12 | 0.00 | 0.00 | 0.00 |
August | 0.631877E+11 | 0.139121E+13 | 0.848866E+09 | 0.00 | 0.285888E+12 | 0.00 | 0.00 | 0.00 |
September | 0.467238E+11 | 0.823002E+12 | 50429620.69 | 0.142779E+09 | 0.415452E+11 | 0.00 | 0.00 | 0.00 |
October | 0.466391E+11 | 0.401871E+12 | 0.319157E+10 | 0.192528E+11 | 0.517281E+09 | 0.00 | 0.00 | 0.00 |
November | 0.366872E+11 | 0.173156E+11 | 0.466880E+11 | 0.176459E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354992E+11 | 0.392039E+09 | 0.103142E+12 | 0.359864E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.526478E+12 | 0.573747E+13 | 0.516766E+12 | 0.184012E+13 | 0.710659E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.319527E+11 | 45543857.28 | 50429620.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631877E+11 | 0.145073E+13 | 0.177736E+12 | 0.476859E+12 | 0.300413E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.403908E+10 | 10373092.09 | 0.345493E+11 | 0.488326E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354262E+10 | 14773896.69 | 0.277457E+11 | 0.482182E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368721E+10 | 0.134886E+10 | 0.103356E+11 | 0.318780E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365661E+10 | 0.104179E+11 | 0.371832E+10 | 0.110178E+11 | 1556366.67 | 0.00 | 0.00 | 0.00 |
May | 0.450717E+10 | 0.409778E+11 | 0.255293E+09 | 0.353803E+09 | 0.176575E+09 | 0.00 | 0.00 | 0.00 |
June | 0.560504E+10 | 0.124874E+12 | 40155912.47 | 0.00 | 0.621331E+10 | 0.00 | 0.00 | 0.00 |
July | 0.628469E+10 | 0.161695E+12 | 10942469.84 | 0.00 | 0.269368E+11 | 0.00 | 0.00 | 0.00 |
August | 0.717689E+10 | 0.152893E+12 | 37950948.99 | 0.00 | 0.266872E+11 | 0.00 | 0.00 | 0.00 |
September | 0.472651E+10 | 0.856150E+11 | 51584176.93 | 15355411.21 | 0.322569E+10 | 0.00 | 0.00 | 0.00 |
October | 0.405448E+10 | 0.394714E+11 | 0.113236E+10 | 0.279562E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328437E+10 | 0.155004E+10 | 0.115571E+11 | 0.221606E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347712E+10 | 18886879.32 | 0.208307E+11 | 0.430988E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.540418E+11 | 0.618887E+12 | 0.110265E+12 | 0.208371E+12 | 0.632412E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.328437E+10 | 10373092.09 | 10942469.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.717689E+10 | 0.161695E+12 | 0.345493E+11 | 0.488326E+11 | 0.269368E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.941376E+11 | 0.322253E+12 | 0.379368E+10 | 0.00 | 0.00 | 0.471155E+10 | 0.00 | 0.00 |
February | 0.850275E+11 | 0.509227E+12 | 0.134289E+10 | 0.00 | 0.00 | 0.531291E+10 | 0.00 | 0.00 |
March | 0.941376E+11 | 0.810092E+12 | 0.312884E+09 | 0.00 | 0.00 | 0.374657E+10 | 0.00 | 0.00 |
April | 0.911009E+11 | 0.102571E+13 | 0.225393E+09 | 0.00 | 0.00 | 0.189901E+10 | 0.00 | 0.00 |
May | 0.941376E+11 | 0.329136E+12 | 0.374901E+09 | 0.00 | 0.00 | 0.743385E+09 | 0.00 | 0.00 |
June | 0.911009E+11 | 0.563165E+12 | 0.00 | 0.00 | 0.00 | 67149358.22 | 0.00 | 0.00 |
July | 0.941376E+11 | 0.833236E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.941376E+11 | 0.107656E+13 | 0.00 | 0.00 | 0.00 | 50304402.82 | 0.00 | 0.00 |
September | 0.911009E+11 | 0.326588E+12 | 0.00 | 0.00 | 0.00 | 0.110165E+09 | 0.00 | 0.00 |
October | 0.941376E+11 | 0.577855E+12 | 0.152547E+09 | 0.00 | 0.00 | 0.126876E+10 | 0.00 | 0.00 |
November | 0.911009E+11 | 0.789606E+12 | 0.485056E+09 | 0.00 | 0.00 | 0.268622E+10 | 0.00 | 0.00 |
December | 0.941376E+11 | 0.105761E+13 | 0.293954E+09 | 0.00 | 0.00 | 0.481270E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110839E+13 | 0.822104E+13 | 0.698131E+10 | 0.00 | 0.00 | 0.254087E+11 | 0.00 | 0.00 |
Minimum of Months | 0.850275E+11 | 0.322253E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941376E+11 | 0.107656E+13 | 0.379368E+10 | 0.00 | 0.00 | 0.531291E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.139140E+10 | 0.410423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125675E+10 | 0.870265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139140E+10 | 0.154668E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134651E+10 | 0.199263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139140E+10 | 0.561328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134651E+10 | 0.105431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139140E+10 | 0.159398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139140E+10 | 0.194056E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134651E+10 | 0.554285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139140E+10 | 0.107575E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134651E+10 | 0.149372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139140E+10 | 0.203393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163826E+11 | 0.151279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.125675E+10 | 0.410423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139140E+10 | 0.203393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.132705E+11 | 0.172994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119863E+11 | 0.643740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132705E+11 | 0.132608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128424E+11 | 0.180856E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132705E+11 | 0.472560E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128424E+11 | 0.977658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132705E+11 | 0.150977E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132705E+11 | 0.185080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128424E+11 | 0.473452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132705E+11 | 0.936635E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128424E+11 | 0.125651E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132705E+11 | 0.172597E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156250E+12 | 0.131547E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.119863E+11 | 0.172994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132705E+11 | 0.185080E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.135154E+10 | 0.837247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122075E+10 | 0.479241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135154E+10 | 0.120033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130794E+10 | 0.173263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135154E+10 | 0.441493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130794E+10 | 0.977718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135154E+10 | 0.152076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135154E+10 | 0.187678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130794E+10 | 0.450008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135154E+10 | 0.860738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130794E+10 | 0.110659E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135154E+10 | 0.153573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159133E+11 | 0.122657E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.122075E+10 | 0.837247E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135154E+10 | 0.187678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.132351E+11 | 0.293204E+09 | 8852447.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.123144E+11 | 0.481784E+09 | 206.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145742E+11 | 0.316592E+09 | 0.677044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.135217E+11 | 0.617808E+09 | 0.586349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144267E+11 | 0.626994E+09 | 0.172950E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144815E+11 | 0.974511E+09 | 0.696316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142841E+11 | 0.622617E+09 | 0.984115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.155113E+11 | 0.112077E+10 | 0.985475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.147188E+11 | 0.151082E+10 | 0.528878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150478E+11 | 0.147942E+10 | 0.209233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142670E+11 | 0.143931E+10 | 0.278698E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140001E+11 | 0.504864E+09 | 2931514.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170383E+12 | 0.998870E+10 | 0.364528E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.123144E+11 | 0.293204E+09 | 206.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.155113E+11 | 0.151082E+10 | 0.985475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.460445E+10 | 0.393116E+10 | 22739308.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.493436E+10 | 0.487049E+10 | 15070375.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.708757E+10 | 0.176232E+10 | 0.206955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.718450E+10 | 0.247064E+09 | 0.145356E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.585093E+10 | 20223960.57 | 0.451761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.649433E+10 | 29024611.93 | 0.136119E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.737938E+10 | 10116162.59 | 0.179293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.896658E+10 | 52610971.46 | 0.179317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.579166E+10 | 20484555.39 | 0.937192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.683793E+10 | 0.147839E+09 | 0.492143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.640536E+10 | 0.798152E+09 | 0.224935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.650559E+10 | 0.180445E+10 | 16987377.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.780426E+11 | 0.136939E+11 | 0.701748E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.460445E+10 | 10116162.59 | 15070375.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.896658E+10 | 0.487049E+10 | 0.179317E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.342873E+11 | 0.177736E+12 | 45543857.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.319527E+11 | 0.121012E+12 | 0.182768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.412689E+11 | 0.490059E+11 | 0.144735E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.399637E+11 | 0.142286E+11 | 0.100698E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.455884E+11 | 0.428338E+09 | 0.387869E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.505394E+11 | 0.313241E+09 | 0.114969E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.541408E+11 | 0.121445E+09 | 0.145073E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.631877E+11 | 0.848866E+09 | 0.139121E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.467238E+11 | 50429620.69 | 0.823002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466391E+11 | 0.319157E+10 | 0.401871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.366872E+11 | 0.466880E+11 | 0.173156E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.354992E+11 | 0.103142E+12 | 0.392039E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.526478E+12 | 0.516766E+12 | 0.573747E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.319527E+11 | 50429620.69 | 45543857.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.631877E+11 | 0.177736E+12 | 0.145073E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.403908E+10 | 0.345493E+11 | 10373092.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.354262E+10 | 0.277457E+11 | 14773896.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.368721E+10 | 0.103356E+11 | 0.134886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.365661E+10 | 0.371832E+10 | 0.104179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.450717E+10 | 0.255293E+09 | 0.409778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.560504E+10 | 40155912.47 | 0.124874E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.628469E+10 | 10942469.84 | 0.161695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.717689E+10 | 37950948.99 | 0.152893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.472651E+10 | 51584176.93 | 0.856150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.405448E+10 | 0.113236E+10 | 0.394714E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.328437E+10 | 0.115571E+11 | 0.155004E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.347712E+10 | 0.208307E+11 | 18886879.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.540418E+11 | 0.110265E+12 | 0.618887E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.328437E+10 | 10942469.84 | 10373092.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.717689E+10 | 0.345493E+11 | 0.161695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.941376E+11 | 0.379368E+10 | 0.377928E+12 | 0.00 | 0.807320E+11 | 0.00 | 0.00 | 0.00 | 0.473275E+10 | 0.00 | 0.00 | 0.00 |
February | 0.850275E+11 | 0.134289E+10 | 0.597685E+12 | 0.00 | 0.119131E+12 | 0.00 | 0.00 | 0.00 | 0.533682E+10 | 0.00 | 0.00 | 0.00 |
March | 0.941376E+11 | 0.312884E+09 | 0.949307E+12 | 0.00 | 0.178576E+12 | 0.00 | 0.00 | 0.00 | 0.376343E+10 | 0.00 | 0.00 | 0.00 |
April | 0.911009E+11 | 0.225393E+09 | 0.120914E+13 | 0.00 | 0.225299E+12 | 0.00 | 0.00 | 0.00 | 0.190756E+10 | 0.00 | 0.00 | 0.00 |
May | 0.941376E+11 | 0.374901E+09 | 0.387981E+12 | 0.00 | 0.826162E+11 | 0.00 | 0.00 | 0.00 | 0.746732E+09 | 0.00 | 0.00 | 0.00 |
June | 0.911009E+11 | 0.00 | 0.681489E+12 | 0.00 | 0.153455E+12 | 0.00 | 0.00 | 0.00 | 67451624.70 | 0.00 | 0.00 | 0.00 |
July | 0.941376E+11 | 0.00 | 0.103719E+13 | 0.00 | 0.247540E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.941376E+11 | 0.00 | 0.134727E+13 | 0.00 | 0.316276E+12 | 0.00 | 0.00 | 0.00 | 50530843.33 | 0.00 | 0.00 | 0.00 |
September | 0.911009E+11 | 0.00 | 0.389573E+12 | 0.00 | 0.872715E+11 | 0.00 | 0.00 | 0.00 | 0.110661E+09 | 0.00 | 0.00 | 0.00 |
October | 0.941376E+11 | 0.152547E+09 | 0.679872E+12 | 0.00 | 0.136143E+12 | 0.00 | 0.00 | 0.00 | 0.127447E+10 | 0.00 | 0.00 | 0.00 |
November | 0.911009E+11 | 0.485056E+09 | 0.925024E+12 | 0.00 | 0.173768E+12 | 0.00 | 0.00 | 0.00 | 0.269831E+10 | 0.00 | 0.00 | 0.00 |
December | 0.941376E+11 | 0.293954E+09 | 0.123987E+13 | 0.00 | 0.225071E+12 | 0.00 | 0.00 | 0.00 | 0.483437E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110839E+13 | 0.698131E+10 | 0.982233E+13 | 0.00 | 0.202588E+13 | 0.00 | 0.00 | 0.00 | 0.255231E+11 | 0.00 | 0.00 | |
Minimum of Months | 0.850275E+11 | 0.00 | 0.377928E+12 | 0.00 | 0.807320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.941376E+11 | 0.379368E+10 | 0.134727E+13 | 0.00 | 0.316276E+12 | 0.00 | 0.00 | 0.00 | 0.533682E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.139140E+10 | 0.00 | 0.496957E+10 | 0.00 | 0.116071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.125675E+10 | 0.00 | 0.105408E+11 | 0.00 | 0.228726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139140E+10 | 0.00 | 0.187384E+11 | 0.00 | 0.385740E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134651E+10 | 0.00 | 0.242915E+11 | 0.00 | 0.493459E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139140E+10 | 0.00 | 0.687003E+10 | 0.00 | 0.163007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.134651E+10 | 0.00 | 0.133937E+11 | 0.00 | 0.338950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139140E+10 | 0.00 | 0.210182E+11 | 0.00 | 0.564811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139140E+10 | 0.00 | 0.253996E+11 | 0.00 | 0.665137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.134651E+10 | 0.00 | 0.691419E+10 | 0.00 | 0.175311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.139140E+10 | 0.00 | 0.131506E+11 | 0.00 | 0.292299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.134651E+10 | 0.00 | 0.181016E+11 | 0.00 | 0.373073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139140E+10 | 0.00 | 0.246378E+11 | 0.00 | 0.488002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163826E+11 | 0.00 | 0.188026E+12 | 0.00 | 0.428459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.125675E+10 | 0.00 | 0.496957E+10 | 0.00 | 0.116071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139140E+10 | 0.00 | 0.253996E+11 | 0.00 | 0.665137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.132705E+11 | 0.00 | 0.209456E+11 | 0.00 | 0.511053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119863E+11 | 0.00 | 0.779704E+11 | 0.00 | 0.173135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.132705E+11 | 0.00 | 0.160664E+12 | 0.00 | 0.335163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128424E+11 | 0.00 | 0.220657E+12 | 0.00 | 0.452334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.132705E+11 | 0.00 | 0.578680E+11 | 0.00 | 0.138958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128424E+11 | 0.00 | 0.124238E+12 | 0.00 | 0.315670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.132705E+11 | 0.00 | 0.199083E+12 | 0.00 | 0.535615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.132705E+11 | 0.00 | 0.242384E+12 | 0.00 | 0.635263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128424E+11 | 0.00 | 0.591147E+11 | 0.00 | 0.151688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.132705E+11 | 0.00 | 0.114543E+12 | 0.00 | 0.257327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.128424E+11 | 0.00 | 0.152276E+12 | 0.00 | 0.318743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.132705E+11 | 0.00 | 0.209084E+12 | 0.00 | 0.421190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.156250E+12 | 0.00 | 0.163883E+13 | 0.00 | 0.378619E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.119863E+11 | 0.00 | 0.209456E+11 | 0.00 | 0.511053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.132705E+11 | 0.00 | 0.242384E+12 | 0.00 | 0.635263E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.135154E+10 | 0.00 | 0.101368E+10 | 0.00 | 0.252997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122075E+10 | 0.00 | 0.580460E+10 | 0.00 | 0.131605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.135154E+10 | 0.00 | 0.145435E+11 | 0.00 | 0.307347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.130794E+10 | 0.00 | 0.211510E+11 | 0.00 | 0.437818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.135154E+10 | 0.00 | 0.541290E+10 | 0.00 | 0.131259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.130794E+10 | 0.00 | 0.124309E+11 | 0.00 | 0.316841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135154E+10 | 0.00 | 0.200565E+11 | 0.00 | 0.540563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.135154E+10 | 0.00 | 0.246124E+11 | 0.00 | 0.646454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.130794E+10 | 0.00 | 0.562739E+10 | 0.00 | 0.145785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135154E+10 | 0.00 | 0.105339E+11 | 0.00 | 0.239425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.130794E+10 | 0.00 | 0.134115E+11 | 0.00 | 0.285137E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.135154E+10 | 0.00 | 0.186038E+11 | 0.00 | 0.381291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.159133E+11 | 0.00 | 0.153202E+12 | 0.00 | 0.358882E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.122075E+10 | 0.00 | 0.101368E+10 | 0.00 | 0.252997E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.135154E+10 | 0.00 | 0.246124E+11 | 0.00 | 0.646454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211720E+10 | 0.00 | 0.00 | 0.135880E+09 | 0.00 | 0.00 | 0.649576E+11 | 0.00 | 0.49 |
February | 0.695103E+09 | 0.00 | 0.00 | 0.128573E+09 | 0.00 | 0.00 | 0.616410E+11 | 0.00 | 0.47 |
March | 0.419398E+09 | 0.00 | 0.00 | 0.154946E+09 | 0.00 | 0.00 | 0.760198E+11 | 0.00 | 0.72 |
April | 0.380955E+09 | 16383358.23 | 0.00 | 0.136951E+09 | 0.00 | 0.00 | 0.667415E+11 | 0.00 | 0.95 |
May | 0.193600E+09 | 0.217545E+09 | 0.00 | 0.133796E+09 | 0.00 | 0.00 | 0.590920E+11 | 0.00 | 1.30 |
June | 74297785.12 | 0.635207E+10 | 0.00 | 85263902.03 | 35146147.55 | 0.00 | 0.163478E+11 | 0.00 | 0.95 |
July | 14214667.84 | 0.201910E+11 | 0.00 | 22006705.16 | 0.121107E+09 | 0.00 | 0.128039E+10 | 0.00 | 0.39 |
August | 36780507.72 | 0.168569E+11 | 0.00 | 72372573.92 | 0.147152E+09 | 0.00 | 0.730544E+10 | 0.00 | 0.74 |
September | 0.220427E+09 | 0.423619E+10 | 0.00 | 0.128905E+09 | 3689030.55 | 0.00 | 0.326328E+11 | 0.00 | 1.15 |
October | 0.421771E+09 | 0.171965E+09 | 0.00 | 0.182601E+09 | 0.00 | 0.00 | 0.643209E+11 | 0.00 | 1.26 |
November | 0.398440E+09 | 0.00 | 0.00 | 0.178828E+09 | 0.00 | 0.00 | 0.799715E+11 | 0.00 | 0.87 |
December | 0.645050E+09 | 0.00 | 0.00 | 0.165157E+09 | 0.00 | 0.00 | 0.754222E+11 | 0.00 | 0.59 |
Annual Sum or Average | 0.561724E+10 | 0.480420E+11 | 0.00 | 0.152528E+10 | 0.307094E+09 | 0.00 | 0.605733E+12 | 0.00 | 0.82 |
Minimum of Months | 14214667.84 | 0.00 | 0.00 | 22006705.16 | 0.00 | 0.00 | 0.128039E+10 | 0.00 | 0.39 |
Maximum of Months | 0.211720E+10 | 0.201910E+11 | 0.00 | 0.182601E+09 | 0.147152E+09 | 0.00 | 0.799715E+11 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.588210E+10 | 0.00 | 0.00 | 66578079.87 | 0.00 | 0.00 | 0.387428E+11 | 0.00 | 0.46 |
February | 0.257578E+10 | 0.00 | 0.00 | 79633756.36 | 0.00 | 0.00 | 0.432078E+11 | 0.00 | 0.47 |
March | 0.258353E+10 | 0.00 | 0.00 | 0.119184E+09 | 0.00 | 0.00 | 0.605539E+11 | 0.00 | 0.63 |
April | 0.597442E+10 | 3941439.57 | 0.00 | 0.107054E+09 | 0.00 | 0.00 | 0.530914E+11 | 0.00 | 0.80 |
May | 0.330871E+10 | 0.384702E+09 | 0.00 | 91693276.83 | 0.00 | 0.00 | 0.359897E+11 | 0.00 | 0.80 |
June | 0.148707E+10 | 0.118975E+11 | 0.00 | 32992520.21 | 0.196127E+09 | 0.00 | 0.574691E+10 | 0.00 | 0.60 |
July | 0.108037E+09 | 0.197274E+11 | 0.00 | 2468236.75 | 0.340935E+09 | 0.00 | 0.204776E+09 | 0.00 | 0.39 |
August | 0.168373E+10 | 0.126088E+11 | 0.00 | 23756984.01 | 0.251207E+09 | 0.00 | 0.233611E+10 | 0.00 | 0.56 |
September | 0.232992E+10 | 0.732525E+10 | 0.00 | 60139056.17 | 0.101559E+09 | 0.00 | 0.162409E+11 | 0.00 | 0.66 |
October | 0.414178E+10 | 0.136046E+10 | 0.00 | 96946010.03 | 0.00 | 0.00 | 0.361474E+11 | 0.00 | 0.76 |
November | 0.237290E+10 | 0.00 | 0.00 | 0.109917E+09 | 0.00 | 0.00 | 0.573343E+11 | 0.00 | 0.66 |
December | 0.263947E+10 | 0.00 | 0.00 | 0.113065E+09 | 0.00 | 0.00 | 0.568034E+11 | 0.00 | 0.53 |
Annual Sum or Average | 0.350875E+11 | 0.533082E+11 | 0.00 | 0.903429E+09 | 0.889827E+09 | 0.00 | 0.406399E+12 | 0.00 | 0.61 |
Minimum of Months | 0.108037E+09 | 0.00 | 0.00 | 2468236.75 | 0.00 | 0.00 | 0.204776E+09 | 0.00 | 0.39 |
Maximum of Months | 0.597442E+10 | 0.197274E+11 | 0.00 | 0.119184E+09 | 0.340935E+09 | 0.00 | 0.605539E+11 | 0.00 | 0.80 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.190408E+12 | 0.00 | 0.00 | 0.120399E+09 | 0.00 | 0.591444E+10 | 0.911266E+11 | 0.00 | 0.42 |
February | 0.169873E+12 | 0.00 | 0.00 | 0.166720E+09 | 0.00 | 65014006.70 | 0.117540E+12 | 0.00 | 0.43 |
March | 0.126773E+12 | 0.00 | 0.00 | 0.436903E+09 | 0.00 | 0.00 | 0.269936E+12 | 0.00 | 0.49 |
April | 0.769252E+11 | 38241203.95 | 0.00 | 0.512838E+09 | 4319144.94 | 0.00 | 0.292490E+12 | 0.00 | 0.55 |
May | 0.412308E+11 | 0.383609E+10 | 0.00 | 0.611876E+09 | 0.00 | 0.00 | 0.269681E+12 | 0.00 | 0.67 |
June | 0.828158E+10 | 0.109432E+12 | 0.00 | 0.254872E+09 | 0.801717E+10 | 0.00 | 0.466442E+11 | 0.00 | 0.53 |
July | 0.534713E+09 | 0.179825E+12 | 0.00 | 23858991.62 | 0.140737E+11 | 0.00 | 0.189272E+10 | 0.00 | 0.39 |
August | 0.522174E+10 | 0.116397E+12 | 0.00 | 0.227009E+09 | 0.692231E+10 | 0.00 | 0.217861E+11 | 0.00 | 0.51 |
September | 0.238422E+11 | 0.650609E+11 | 0.00 | 0.409028E+09 | 0.715049E+10 | 0.00 | 0.121324E+12 | 0.00 | 0.58 |
October | 0.423902E+11 | 0.121032E+11 | 0.00 | 0.577879E+09 | 0.487825E+09 | 0.00 | 0.241633E+12 | 0.00 | 0.60 |
November | 0.965640E+11 | 0.00 | 0.00 | 0.437857E+09 | 0.00 | 0.00 | 0.267673E+12 | 0.00 | 0.49 |
December | 0.153589E+12 | 0.00 | 0.00 | 0.268979E+09 | 0.00 | 0.00 | 0.185435E+12 | 0.00 | 0.43 |
Annual Sum or Average | 0.935634E+12 | 0.486692E+12 | 0.00 | 0.404822E+10 | 0.366558E+11 | 0.597945E+10 | 0.192716E+13 | 0.00 | 0.51 |
Minimum of Months | 0.534713E+09 | 0.00 | 0.00 | 23858991.62 | 0.00 | 0.00 | 0.189272E+10 | 0.00 | 0.39 |
Maximum of Months | 0.190408E+12 | 0.179825E+12 | 0.00 | 0.611876E+09 | 0.140737E+11 | 0.591444E+10 | 0.292490E+12 | 0.00 | 0.67 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209037E+11 | 0.00 | 0.00 | 835326.24 | 0.00 | 0.161527E+10 | 0.104726E+10 | 0.00 | 0.40 |
February | 0.189966E+11 | 0.00 | 0.00 | 1451946.56 | 0.00 | 0.100690E+10 | 0.191315E+10 | 0.00 | 0.40 |
March | 0.194115E+11 | 0.00 | 0.00 | 12689162.82 | 0.00 | 0.213279E+09 | 0.113337E+11 | 0.00 | 0.46 |
April | 0.117355E+11 | 792392.26 | 0.00 | 29065683.43 | 285945.89 | 62905720.25 | 0.197941E+11 | 0.00 | 0.51 |
May | 0.827074E+10 | 0.460645E+09 | 0.00 | 47401034.42 | 2907052.38 | 0.00 | 0.212447E+11 | 0.00 | 0.65 |
June | 0.138859E+10 | 0.108912E+11 | 0.00 | 24624607.13 | 0.917224E+09 | 0.00 | 0.442401E+10 | 0.00 | 0.55 |
July | 50763740.60 | 0.192746E+11 | 0.00 | 2906367.58 | 0.813467E+09 | 0.00 | 0.206899E+09 | 0.00 | 0.39 |
August | 0.497316E+09 | 0.120405E+11 | 0.00 | 22561198.49 | 0.467395E+09 | 0.00 | 0.223510E+10 | 0.00 | 0.52 |
September | 0.451850E+10 | 0.638528E+10 | 0.00 | 31860240.44 | 0.104778E+10 | 0.00 | 0.877696E+10 | 0.00 | 0.56 |
October | 0.907070E+10 | 0.989873E+09 | 0.00 | 30664968.44 | 0.157470E+09 | 0.00 | 0.133097E+11 | 0.00 | 0.53 |
November | 0.175460E+11 | 0.00 | 0.00 | 9308996.81 | 0.00 | 0.427420E+09 | 0.879000E+10 | 0.00 | 0.43 |
December | 0.209729E+11 | 0.00 | 0.00 | 1537345.86 | 0.00 | 0.428212E+09 | 0.206326E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.133363E+12 | 0.500430E+11 | 0.00 | 0.214907E+09 | 0.340653E+10 | 0.375399E+10 | 0.951388E+11 | 0.00 | 0.49 |
Minimum of Months | 50763740.60 | 0.00 | 0.00 | 835326.24 | 0.00 | 0.00 | 0.206899E+09 | 0.00 | 0.39 |
Maximum of Months | 0.209729E+11 | 0.192746E+11 | 0.00 | 47401034.42 | 0.104778E+10 | 0.161527E+10 | 0.212447E+11 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.404658E+10 | 0.00 | 0.00 | 66432.77 | 0.00 | 0.131704E+09 | 0.210403E+09 | 0.00 | 0.37 |
February | 0.365352E+10 | 0.00 | 0.00 | 250671.91 | 0.00 | 99879391.45 | 0.450366E+09 | 0.00 | 0.37 |
March | 0.312124E+10 | 0.00 | 0.00 | 3434605.34 | 0.00 | 0.00 | 0.259441E+10 | 0.00 | 0.47 |
April | 0.225082E+10 | 592904.81 | 0.00 | 6137315.13 | 0.00 | 0.00 | 0.397544E+10 | 0.00 | 0.71 |
May | 0.108570E+10 | 65151187.09 | 0.00 | 8102022.16 | 0.00 | 0.00 | 0.378263E+10 | 0.00 | 0.83 |
June | 0.231661E+09 | 0.193689E+10 | 0.00 | 3579554.74 | 26614748.37 | 0.00 | 0.751425E+09 | 0.00 | 0.73 |
July | 14887363.80 | 0.337264E+10 | 0.00 | 334924.96 | 46265554.61 | 0.00 | 30858871.63 | 0.00 | 0.55 |
August | 0.237521E+09 | 0.217724E+10 | 0.00 | 3014581.78 | 34089211.36 | 0.00 | 0.306705E+09 | 0.00 | 0.72 |
September | 0.657615E+09 | 0.105373E+10 | 0.00 | 4782683.64 | 14942155.05 | 0.00 | 0.162568E+10 | 0.00 | 0.70 |
October | 0.157428E+10 | 0.182181E+09 | 0.00 | 5324070.64 | 0.00 | 0.00 | 0.268610E+10 | 0.00 | 0.69 |
November | 0.261919E+10 | 0.00 | 0.00 | 3316296.78 | 0.00 | 0.00 | 0.266515E+10 | 0.00 | 0.48 |
December | 0.375258E+10 | 0.00 | 0.00 | 976383.72 | 0.00 | 0.00 | 0.111295E+10 | 0.00 | 0.36 |
Annual Sum or Average | 0.232456E+11 | 0.878841E+10 | 0.00 | 39319543.58 | 0.121912E+09 | 0.231583E+09 | 0.201921E+11 | 0.00 | 0.58 |
Minimum of Months | 14887363.80 | 0.00 | 0.00 | 66432.77 | 0.00 | 0.00 | 30858871.63 | 0.00 | 0.36 |
Maximum of Months | 0.404658E+10 | 0.337264E+10 | 0.00 | 8102022.16 | 46265554.61 | 0.131704E+09 | 0.397544E+10 | 0.00 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.478012E+10 | 0.00 | 0.00 | 199931.68 | 0.00 | 0.244577E+09 | 0.165427E+09 | 0.00 | 0.68 |
February | 0.464741E+10 | 0.00 | 0.00 | 371406.97 | 0.00 | 0.121399E+09 | 0.222461E+09 | 0.00 | 0.67 |
March | 0.438944E+10 | 0.00 | 0.00 | 3000704.92 | 0.00 | 445786.09 | 0.223395E+10 | 0.00 | 0.83 |
April | 0.369755E+10 | 414094.75 | 0.00 | 4637412.45 | 0.00 | 0.00 | 0.292308E+10 | 0.00 | 1.13 |
May | 0.212618E+10 | 56748985.27 | 0.00 | 6354764.93 | 3090118.15 | 0.00 | 0.321246E+10 | 0.00 | 1.34 |
June | 0.403765E+09 | 0.123766E+10 | 0.00 | 2809333.81 | 0.406441E+09 | 0.00 | 0.738476E+09 | 0.00 | 1.05 |
July | 19181314.72 | 0.227780E+10 | 0.00 | 296594.63 | 0.571262E+09 | 0.00 | 36639848.65 | 0.00 | 0.71 |
August | 0.345481E+09 | 0.163496E+10 | 0.00 | 2178458.32 | 0.232274E+09 | 0.00 | 0.284564E+09 | 0.00 | 1.01 |
September | 0.119154E+10 | 0.647360E+09 | 0.00 | 3678843.92 | 0.368361E+09 | 0.00 | 0.132038E+10 | 0.00 | 1.10 |
October | 0.250426E+10 | 0.119853E+09 | 0.00 | 4070863.00 | 38609366.07 | 0.00 | 0.209717E+10 | 0.00 | 1.10 |
November | 0.432928E+10 | 0.00 | 0.00 | 1221551.92 | 0.00 | 666178.13 | 0.141560E+10 | 0.00 | 0.80 |
December | 0.532039E+10 | 0.00 | 0.00 | 292301.14 | 0.00 | 1220263.44 | 0.347200E+09 | 0.00 | 0.65 |
Annual Sum or Average | 0.337546E+11 | 0.597479E+10 | 0.00 | 29112167.70 | 0.162004E+10 | 0.368308E+09 | 0.149974E+11 | 0.00 | 0.92 |
Minimum of Months | 19181314.72 | 0.00 | 0.00 | 199931.68 | 0.00 | 0.00 | 36639848.65 | 0.00 | 0.65 |
Maximum of Months | 0.532039E+10 | 0.227780E+10 | 0.00 | 6354764.93 | 0.571262E+09 | 0.244577E+09 | 0.321246E+10 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.327432E+10 | 0.00 | 0.00 | 5469678.22 | 0.00 | 0.380970E+09 | 0.295465E+10 | 0.00 | 0.53 |
February | 0.287179E+10 | 0.00 | 0.00 | 6903496.29 | 0.00 | 0.191815E+09 | 0.362761E+10 | 0.00 | 0.55 |
March | 0.320200E+10 | 0.00 | 0.00 | 9871874.39 | 0.00 | 1579579.37 | 0.578881E+10 | 0.00 | 0.74 |
April | 0.291099E+10 | 1056052.02 | 0.00 | 7479243.29 | 0.00 | 0.00 | 0.465248E+10 | 0.00 | 0.88 |
May | 0.168488E+10 | 69992764.02 | 0.00 | 7834993.48 | 52738.75 | 0.00 | 0.361244E+10 | 0.00 | 0.91 |
June | 0.316831E+09 | 0.202182E+10 | 0.00 | 3227630.68 | 30459995.34 | 0.00 | 0.739514E+09 | 0.00 | 0.78 |
July | 17038261.11 | 0.355993E+10 | 0.00 | 325644.69 | 52949911.78 | 0.00 | 30061174.23 | 0.00 | 0.58 |
August | 0.275227E+09 | 0.255354E+10 | 0.00 | 3572513.86 | 39014354.18 | 0.00 | 0.359200E+09 | 0.00 | 0.87 |
September | 0.793983E+09 | 0.129393E+10 | 0.00 | 9066839.48 | 32541589.71 | 0.00 | 0.239558E+10 | 0.00 | 0.99 |
October | 0.126777E+10 | 0.331624E+09 | 0.00 | 14392207.98 | 1043049.04 | 0.00 | 0.590781E+10 | 0.00 | 1.16 |
November | 0.252541E+10 | 0.00 | 0.00 | 9354019.90 | 0.00 | 1979752.68 | 0.580876E+10 | 0.00 | 0.76 |
December | 0.340306E+10 | 0.00 | 0.00 | 7816375.89 | 0.00 | 1532544.23 | 0.435952E+10 | 0.00 | 0.56 |
Annual Sum or Average | 0.225433E+11 | 0.983189E+10 | 0.00 | 85314518.15 | 0.156062E+09 | 0.577877E+09 | 0.402365E+11 | 0.00 | 0.78 |
Minimum of Months | 17038261.11 | 0.00 | 0.00 | 325644.69 | 0.00 | 0.00 | 30061174.23 | 0.00 | 0.53 |
Maximum of Months | 0.340306E+10 | 0.355993E+10 | 0.00 | 14392207.98 | 52949911.78 | 0.380970E+09 | 0.590781E+10 | 0.00 | 1.16 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.577160E+10 | 0.00 | 0.00 | 613047.60 | 0.00 | 44506283.72 | 0.650270E+09 | 0.00 | 0.85 |
February | 0.461428E+10 | 0.00 | 0.00 | 1809344.19 | 0.00 | 7657410.77 | 0.179509E+10 | 0.00 | 0.86 |
March | 0.211932E+10 | 0.00 | 0.00 | 9299759.36 | 0.00 | 0.00 | 0.707784E+10 | 0.00 | 1.18 |
April | 0.128963E+10 | 687309.79 | 0.00 | 14973085.03 | 0.00 | 0.00 | 0.835969E+10 | 0.00 | 1.70 |
May | 0.147440E+10 | 79957366.97 | 0.00 | 8725324.43 | 0.00 | 0.00 | 0.480140E+10 | 0.00 | 1.61 |
June | 0.306649E+09 | 0.228739E+10 | 0.00 | 4744302.91 | 29111443.30 | 0.00 | 0.991087E+09 | 0.00 | 1.40 |
July | 20889692.63 | 0.400240E+10 | 0.00 | 402156.99 | 42777637.14 | 0.00 | 32945155.98 | 0.00 | 1.00 |
August | 0.297030E+09 | 0.299248E+10 | 0.00 | 5140050.24 | 39382556.33 | 0.00 | 0.464409E+09 | 0.00 | 1.56 |
September | 0.106945E+10 | 0.122297E+10 | 0.00 | 5314958.86 | 53747584.07 | 0.00 | 0.188878E+10 | 0.00 | 1.37 |
October | 0.139609E+10 | 0.250165E+09 | 0.00 | 8354734.16 | 0.00 | 0.00 | 0.452421E+10 | 0.00 | 1.46 |
November | 0.221574E+10 | 0.00 | 0.00 | 6250185.77 | 0.00 | 0.00 | 0.536393E+10 | 0.00 | 1.07 |
December | 0.268272E+10 | 0.00 | 0.00 | 5641623.43 | 0.00 | 0.00 | 0.483537E+10 | 0.00 | 0.86 |
Annual Sum or Average | 0.232578E+11 | 0.108360E+11 | 0.00 | 71268572.99 | 0.165019E+09 | 52163694.48 | 0.407850E+11 | 0.00 | 1.24 |
Minimum of Months | 20889692.63 | 0.00 | 0.00 | 402156.99 | 0.00 | 0.00 | 32945155.98 | 0.00 | 0.85 |
Maximum of Months | 0.577160E+10 | 0.400240E+10 | 0.00 | 14973085.03 | 53747584.07 | 44506283.72 | 0.835969E+10 | 0.00 | 1.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.187633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178538E+11 | 0.00 | 0.00 | 0.42 |
February | 0.186683E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169812E+11 | 0.00 | 0.00 | 0.42 |
March | 0.370554E+11 | 0.00 | 0.00 | 1243160.57 | 0.00 | 0.475081E+10 | 0.139954E+10 | 0.00 | 0.44 |
April | 0.286565E+11 | 6024914.20 | 0.00 | 15514200.38 | 0.00 | 0.721601E+09 | 0.101913E+11 | 0.00 | 0.49 |
May | 0.160803E+11 | 0.653191E+09 | 0.00 | 47022364.17 | 4857829.01 | 0.00 | 0.205590E+11 | 0.00 | 0.66 |
June | 0.231658E+10 | 0.180742E+11 | 0.00 | 25546819.09 | 0.353290E+09 | 0.00 | 0.494066E+10 | 0.00 | 0.64 |
July | 71561061.49 | 0.318205E+11 | 0.00 | 3311568.51 | 0.452451E+09 | 0.00 | 0.277358E+09 | 0.00 | 0.53 |
August | 0.117394E+10 | 0.207903E+11 | 0.00 | 23179816.87 | 0.252826E+09 | 0.00 | 0.237062E+10 | 0.00 | 0.65 |
September | 0.895272E+10 | 0.921497E+10 | 0.00 | 28278837.44 | 0.825496E+09 | 0.00 | 0.837953E+10 | 0.00 | 0.60 |
October | 0.214238E+11 | 0.133476E+10 | 0.00 | 18013881.48 | 0.268129E+09 | 8088031.84 | 0.834361E+10 | 0.00 | 0.53 |
November | 0.323613E+11 | 0.00 | 0.00 | 1267886.21 | 0.00 | 0.493818E+10 | 0.204131E+10 | 0.00 | 0.42 |
December | 0.267324E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131807E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.212256E+12 | 0.818940E+11 | 0.00 | 0.163379E+09 | 0.215705E+10 | 0.584344E+11 | 0.585030E+11 | 0.00 | 0.52 |
Minimum of Months | 71561061.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.370554E+11 | 0.318205E+11 | 0.00 | 47022364.17 | 0.825496E+09 | 0.178538E+11 | 0.205590E+11 | 0.00 | 0.66 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204498E+11 | 0.00 | 0.00 | 0.85 |
February | 0.298730E+11 | 0.00 | 0.00 | 5182.05 | 0.00 | 0.165052E+11 | 5953353.33 | 0.00 | 0.86 |
March | 0.467115E+11 | 0.00 | 0.00 | 8172696.50 | 0.00 | 0.460093E+10 | 0.646975E+10 | 0.00 | 0.90 |
April | 0.357722E+11 | 5705096.37 | 0.00 | 26120594.02 | 0.00 | 0.870894E+09 | 0.173344E+11 | 0.00 | 1.01 |
May | 0.259782E+11 | 0.632086E+09 | 0.00 | 48904636.69 | 64910255.36 | 0.00 | 0.225333E+11 | 0.00 | 1.29 |
June | 0.312004E+10 | 0.116539E+11 | 0.00 | 26106878.99 | 0.652609E+10 | 0.00 | 0.673398E+10 | 0.00 | 1.07 |
July | 0.106429E+09 | 0.237325E+11 | 0.00 | 3489015.58 | 0.816519E+10 | 0.00 | 0.407896E+09 | 0.00 | 0.82 |
August | 0.185466E+10 | 0.180769E+11 | 0.00 | 23451653.62 | 0.346130E+10 | 0.00 | 0.297480E+10 | 0.00 | 1.08 |
September | 0.132594E+11 | 0.453628E+10 | 0.00 | 27148598.30 | 0.658731E+10 | 0.00 | 0.920262E+10 | 0.00 | 1.09 |
October | 0.267756E+11 | 0.115560E+10 | 0.00 | 20286979.19 | 0.595948E+09 | 7355540.10 | 0.124453E+11 | 0.00 | 1.05 |
November | 0.443895E+11 | 0.00 | 0.00 | 970492.26 | 0.00 | 0.578727E+10 | 0.171390E+10 | 0.00 | 0.87 |
December | 0.375707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150275E+11 | 0.00 | 0.00 | 0.84 |
Annual Sum or Average | 0.292672E+12 | 0.597930E+11 | 0.00 | 0.184657E+09 | 0.254008E+11 | 0.632490E+11 | 0.798218E+11 | 0.00 | 0.98 |
Minimum of Months | 0.106429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 |
Maximum of Months | 0.467115E+11 | 0.237325E+11 | 0.00 | 48904636.69 | 0.816519E+10 | 0.204498E+11 | 0.225333E+11 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213143E+11 | 0.00 | 0.00 | 41116030.50 | 0.00 | 0.115712E+11 | 0.188815E+11 | 0.00 | 0.58 |
February | 0.206933E+11 | 0.00 | 0.00 | 54377955.39 | 0.00 | 0.909651E+10 | 0.241744E+11 | 0.00 | 0.61 |
March | 0.284241E+11 | 0.00 | 0.00 | 76119280.91 | 0.00 | 0.325882E+10 | 0.406743E+11 | 0.00 | 0.71 |
April | 0.266902E+11 | 13195068.52 | 0.00 | 47443511.00 | 0.00 | 0.631569E+09 | 0.274490E+11 | 0.00 | 0.69 |
May | 0.184468E+11 | 0.724147E+09 | 0.00 | 57372876.00 | 9463471.80 | 0.00 | 0.249974E+11 | 0.00 | 0.78 |
June | 0.315189E+10 | 0.189515E+11 | 0.00 | 26251735.27 | 0.994053E+09 | 0.00 | 0.498152E+10 | 0.00 | 0.71 |
July | 82342948.74 | 0.347569E+11 | 0.00 | 3360152.28 | 0.808082E+09 | 0.00 | 0.290300E+09 | 0.00 | 0.59 |
August | 0.129116E+10 | 0.259723E+11 | 0.00 | 32963547.63 | 0.290918E+09 | 0.00 | 0.312120E+10 | 0.00 | 0.84 |
September | 0.769227E+10 | 0.124389E+11 | 0.00 | 88147498.43 | 0.842602E+09 | 0.00 | 0.197594E+11 | 0.00 | 0.94 |
October | 0.115543E+11 | 0.348303E+10 | 0.00 | 0.134051E+09 | 66138879.07 | 0.00 | 0.488433E+11 | 0.00 | 1.08 |
November | 0.232735E+11 | 0.00 | 0.00 | 68934525.51 | 0.00 | 0.235865E+10 | 0.400265E+11 | 0.00 | 0.71 |
December | 0.240934E+11 | 0.00 | 0.00 | 50114458.97 | 0.00 | 0.812769E+10 | 0.277409E+11 | 0.00 | 0.59 |
Annual Sum or Average | 0.186708E+12 | 0.963401E+11 | 0.00 | 0.680253E+09 | 0.301126E+10 | 0.350444E+11 | 0.280940E+12 | 0.00 | 0.74 |
Minimum of Months | 82342948.74 | 0.00 | 0.00 | 3360152.28 | 0.00 | 0.00 | 0.290300E+09 | 0.00 | 0.58 |
Maximum of Months | 0.284241E+11 | 0.347569E+11 | 0.00 | 0.134051E+09 | 0.994053E+09 | 0.115712E+11 | 0.488433E+11 | 0.00 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.297995E+11 | 0.00 | 0.00 | 435065.62 | 0.00 | 0.182170E+11 | 0.846977E+09 | 0.00 | 0.87 |
February | 0.310839E+11 | 0.00 | 0.00 | 2585419.29 | 0.00 | 0.145747E+11 | 0.207578E+10 | 0.00 | 0.88 |
March | 0.459352E+11 | 0.00 | 0.00 | 15409673.36 | 0.00 | 0.348164E+10 | 0.119452E+11 | 0.00 | 0.96 |
April | 0.393319E+11 | 4664777.52 | 0.00 | 29083364.29 | 757772.93 | 0.333762E+09 | 0.174020E+11 | 0.00 | 1.09 |
May | 0.281955E+11 | 0.777196E+09 | 0.00 | 39486305.47 | 19143495.48 | 0.00 | 0.203164E+11 | 0.00 | 1.31 |
June | 0.394257E+10 | 0.172362E+11 | 0.00 | 22442099.68 | 0.283726E+10 | 0.00 | 0.501750E+10 | 0.00 | 1.13 |
July | 0.174287E+09 | 0.288788E+11 | 0.00 | 2505310.43 | 0.498491E+10 | 0.00 | 0.184656E+09 | 0.00 | 0.86 |
August | 0.189252E+10 | 0.235518E+11 | 0.00 | 23406623.04 | 0.723993E+09 | 0.00 | 0.234590E+10 | 0.00 | 1.18 |
September | 0.151158E+11 | 0.779019E+10 | 0.00 | 24791381.03 | 0.391442E+10 | 0.00 | 0.765029E+10 | 0.00 | 1.14 |
October | 0.315545E+11 | 0.168717E+10 | 0.00 | 21213005.94 | 0.478323E+09 | 0.00 | 0.995049E+10 | 0.00 | 1.13 |
November | 0.466585E+11 | 0.00 | 0.00 | 2808928.09 | 0.00 | 0.400417E+10 | 0.265855E+10 | 0.00 | 0.89 |
December | 0.415509E+11 | 0.00 | 0.00 | 227088.03 | 0.00 | 0.116264E+11 | 0.721354E+09 | 0.00 | 0.86 |
Annual Sum or Average | 0.315235E+12 | 0.799261E+11 | 0.00 | 0.184394E+09 | 0.129588E+11 | 0.522377E+11 | 0.811151E+11 | 0.00 | 1.03 |
Minimum of Months | 0.174287E+09 | 0.00 | 0.00 | 227088.03 | 0.00 | 0.00 | 0.184656E+09 | 0.00 | 0.86 |
Maximum of Months | 0.466585E+11 | 0.288788E+11 | 0.00 | 39486305.47 | 0.498491E+10 | 0.182170E+11 | 0.203164E+11 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245163E+10 | 0.00 | 0.00 | 0.46 |
February | 0.988447E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224894E+10 | 0.00 | 0.00 | 0.47 |
March | 0.302054E+10 | 0.00 | 0.00 | 35128.89 | 0.00 | 0.115103E+10 | 88309902.48 | 0.00 | 0.50 |
April | 0.288057E+10 | 109426.23 | 0.00 | 1291103.16 | 40894.09 | 0.419790E+09 | 0.767501E+09 | 0.00 | 0.53 |
May | 0.200199E+10 | 76374114.75 | 0.00 | 4050714.94 | 1648648.61 | 15064501.39 | 0.188567E+10 | 0.00 | 0.70 |
June | 0.284311E+09 | 0.173899E+10 | 0.00 | 2692404.80 | 0.135885E+09 | 0.00 | 0.536953E+09 | 0.00 | 0.67 |
July | 7784168.47 | 0.327270E+10 | 0.00 | 380983.39 | 0.116460E+09 | 0.00 | 30607831.13 | 0.00 | 0.54 |
August | 0.128720E+09 | 0.203610E+10 | 0.00 | 2654977.53 | 0.102386E+09 | 0.00 | 0.261592E+09 | 0.00 | 0.67 |
September | 0.998753E+09 | 0.833868E+09 | 0.00 | 2398958.79 | 0.238518E+09 | 0.00 | 0.765394E+09 | 0.00 | 0.61 |
October | 0.226988E+10 | 99918185.27 | 0.00 | 1082047.40 | 51583733.42 | 0.127148E+09 | 0.463029E+09 | 0.00 | 0.55 |
November | 0.262360E+10 | 0.00 | 0.00 | 2974.02 | 0.00 | 0.110987E+10 | 23304563.78 | 0.00 | 0.48 |
December | 0.132105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208309E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.175588E+11 | 0.805806E+10 | 0.00 | 14589292.92 | 0.646523E+09 | 0.960656E+10 | 0.482237E+10 | 0.00 | 0.56 |
Minimum of Months | 7784168.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.302054E+10 | 0.327270E+10 | 0.00 | 4050714.94 | 0.238518E+09 | 0.245163E+10 | 0.188567E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240056E+10 | 0.00 | 0.00 | 0.85 |
February | 0.179052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200224E+10 | 0.00 | 0.00 | 0.86 |
March | 0.391854E+10 | 0.00 | 0.00 | 318055.28 | 0.00 | 0.893797E+09 | 0.321337E+09 | 0.00 | 0.94 |
April | 0.306207E+10 | 159670.14 | 0.00 | 2355749.68 | 0.00 | 0.440160E+09 | 0.151421E+10 | 0.00 | 1.02 |
May | 0.243332E+10 | 76505263.08 | 0.00 | 4968434.95 | 6233745.81 | 7184784.21 | 0.234412E+10 | 0.00 | 1.30 |
June | 0.286332E+09 | 0.120120E+10 | 0.00 | 2859674.48 | 0.617265E+09 | 0.00 | 0.729842E+09 | 0.00 | 1.08 |
July | 10141643.08 | 0.250882E+10 | 0.00 | 414089.16 | 0.726044E+09 | 0.00 | 44047204.01 | 0.00 | 0.81 |
August | 0.143291E+09 | 0.183667E+10 | 0.00 | 2732326.75 | 0.312308E+09 | 0.00 | 0.343822E+09 | 0.00 | 1.09 |
September | 0.119722E+10 | 0.507284E+09 | 0.00 | 2545016.41 | 0.653439E+09 | 0.00 | 0.907890E+09 | 0.00 | 1.08 |
October | 0.242866E+10 | 98559824.92 | 0.00 | 1469512.38 | 67485977.35 | 0.122440E+09 | 0.896827E+09 | 0.00 | 1.01 |
November | 0.345018E+10 | 0.00 | 0.00 | 1192.19 | 0.00 | 0.103723E+10 | 14677209.71 | 0.00 | 0.90 |
December | 0.199839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206536E+10 | 0.00 | 0.00 | 0.86 |
Annual Sum or Average | 0.223979E+11 | 0.622920E+10 | 0.00 | 17664051.29 | 0.238278E+10 | 0.896897E+10 | 0.711677E+10 | 0.00 | 0.98 |
Minimum of Months | 10141643.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 |
Maximum of Months | 0.391854E+10 | 0.250882E+10 | 0.00 | 4968434.95 | 0.726044E+09 | 0.240056E+10 | 0.234412E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168886E+10 | 0.00 | 0.00 | 2310326.64 | 0.00 | 0.155300E+10 | 0.128226E+10 | 0.00 | 0.59 |
February | 0.166740E+10 | 0.00 | 0.00 | 3143131.58 | 0.00 | 0.123354E+10 | 0.161126E+10 | 0.00 | 0.62 |
March | 0.256620E+10 | 0.00 | 0.00 | 5286920.40 | 0.00 | 0.714140E+09 | 0.343588E+10 | 0.00 | 0.75 |
April | 0.256457E+10 | 286546.44 | 0.00 | 4155317.30 | 0.00 | 0.427393E+09 | 0.249981E+10 | 0.00 | 0.73 |
May | 0.232194E+10 | 83596254.59 | 0.00 | 5040995.76 | 2621316.90 | 19789365.64 | 0.232460E+10 | 0.00 | 0.83 |
June | 0.350152E+09 | 0.180401E+10 | 0.00 | 2794729.21 | 0.229202E+09 | 0.00 | 0.578788E+09 | 0.00 | 0.74 |
July | 8660910.33 | 0.348943E+10 | 0.00 | 390113.85 | 0.232824E+09 | 0.00 | 32702633.72 | 0.00 | 0.59 |
August | 0.141437E+09 | 0.252308E+10 | 0.00 | 3818644.33 | 0.111137E+09 | 0.00 | 0.365785E+09 | 0.00 | 0.86 |
September | 0.857577E+09 | 0.120987E+10 | 0.00 | 7831076.99 | 0.192043E+09 | 0.00 | 0.199654E+10 | 0.00 | 0.95 |
October | 0.131902E+10 | 0.293344E+09 | 0.00 | 10202353.46 | 21122356.68 | 64804869.71 | 0.421889E+10 | 0.00 | 1.06 |
November | 0.220012E+10 | 0.00 | 0.00 | 4074255.57 | 0.00 | 0.652820E+09 | 0.274137E+10 | 0.00 | 0.70 |
December | 0.187312E+10 | 0.00 | 0.00 | 2398397.22 | 0.00 | 0.127093E+10 | 0.141311E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.175590E+11 | 0.940361E+10 | 0.00 | 51446262.31 | 0.788949E+09 | 0.593641E+10 | 0.225010E+11 | 0.00 | 0.75 |
Minimum of Months | 8660910.33 | 0.00 | 0.00 | 390113.85 | 0.00 | 0.00 | 32702633.72 | 0.00 | 0.59 |
Maximum of Months | 0.256620E+10 | 0.348943E+10 | 0.00 | 10202353.46 | 0.232824E+09 | 0.155300E+10 | 0.421889E+10 | 0.00 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.208795E+10 | 0.00 | 0.00 | 10189.56 | 0.00 | 0.225853E+10 | 45326620.59 | 0.00 | 0.92 |
February | 0.204900E+10 | 0.00 | 0.00 | 173890.41 | 0.00 | 0.186949E+10 | 0.164204E+09 | 0.00 | 0.93 |
March | 0.393061E+10 | 0.00 | 0.00 | 1251046.99 | 0.00 | 0.739600E+09 | 0.105852E+10 | 0.00 | 1.04 |
April | 0.367667E+10 | 87831.73 | 0.00 | 2770727.19 | 53266.59 | 0.278925E+09 | 0.171143E+10 | 0.00 | 1.15 |
May | 0.298465E+10 | 80535946.03 | 0.00 | 3883061.51 | 3824276.35 | 611767.11 | 0.210890E+10 | 0.00 | 1.38 |
June | 0.418472E+09 | 0.160275E+10 | 0.00 | 2427416.55 | 0.442445E+09 | 0.00 | 0.571871E+09 | 0.00 | 1.17 |
July | 19530631.56 | 0.282448E+10 | 0.00 | 354295.00 | 0.695215E+09 | 0.00 | 18784152.30 | 0.00 | 0.86 |
August | 0.180124E+09 | 0.224982E+10 | 0.00 | 2643687.81 | 0.175329E+09 | 0.00 | 0.271530E+09 | 0.00 | 1.20 |
September | 0.153762E+10 | 0.711678E+09 | 0.00 | 2364974.43 | 0.542824E+09 | 0.00 | 0.746003E+09 | 0.00 | 1.17 |
October | 0.285515E+10 | 0.129337E+09 | 0.00 | 1929259.43 | 75669014.22 | 90913811.52 | 0.899518E+09 | 0.00 | 1.14 |
November | 0.369665E+10 | 0.00 | 0.00 | 156010.69 | 0.00 | 0.957038E+09 | 0.199839E+09 | 0.00 | 0.97 |
December | 0.260303E+10 | 0.00 | 0.00 | 379.40 | 0.00 | 0.176872E+10 | 5359884.44 | 0.00 | 0.92 |
Annual Sum or Average | 0.260394E+11 | 0.759868E+10 | 0.00 | 17964938.97 | 0.193536E+10 | 0.796383E+10 | 0.780128E+10 | 0.00 | 1.07 |
Minimum of Months | 19530631.56 | 0.00 | 0.00 | 379.40 | 0.00 | 0.00 | 5359884.44 | 0.00 | 0.86 |
Maximum of Months | 0.393061E+10 | 0.282448E+10 | 0.00 | 3883061.51 | 0.695215E+09 | 0.225853E+10 | 0.210890E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 20:05:19
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.287605E+09 | 0.00 | 0.00 | 0.274314E+09 | 0.00 | 0.00 | 0.171566E+11 | 0.00 | 0.32 |
February | 50686058.51 | 0.00 | 0.00 | 0.487639E+09 | 0.00 | 0.00 | 0.172341E+11 | 0.00 | 0.32 |
March | 5724748.86 | 428186.27 | 0.00 | 0.816841E+09 | 0.00 | 0.00 | 0.148177E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.837880E+09 | 0.00 | 0.00 | 0.900342E+10 | 0.00 | 0.32 |
May | 0.00 | 0.198836E+09 | 0.00 | 0.186271E+09 | 0.00 | 0.00 | 0.489017E+10 | 0.00 | 0.33 |
June | 0.00 | 0.359525E+10 | 0.00 | 0.109616E+09 | 0.00 | 0.00 | 0.768167E+09 | 0.00 | 0.34 |
July | 0.00 | 0.816225E+10 | 0.00 | 10278505.54 | 0.00 | 0.00 | 10903977.12 | 0.00 | 0.31 |
August | 0.00 | 0.606510E+10 | 0.00 | 0.173361E+09 | 0.00 | 0.00 | 0.310629E+09 | 0.00 | 0.35 |
September | 0.00 | 0.201145E+10 | 0.00 | 0.115117E+09 | 0.00 | 0.00 | 0.208231E+10 | 0.00 | 0.32 |
October | 690258.17 | 0.358533E+09 | 0.00 | 0.325829E+09 | 0.00 | 0.00 | 0.536403E+10 | 0.00 | 0.32 |
November | 1999594.79 | 0.00 | 0.00 | 0.684422E+09 | 0.00 | 0.00 | 0.116023E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.960212E+09 | 0.00 | 0.00 | 0.159714E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.346705E+09 | 0.203918E+11 | 0.00 | 0.498178E+10 | 0.00 | 0.00 | 0.992117E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10278505.54 | 0.00 | 0.00 | 10903977.12 | 0.00 | 0.31 |
Maximum of Months | 0.287605E+09 | 0.816225E+10 | 0.00 | 0.960212E+09 | 0.00 | 0.00 | 0.172341E+11 | 0.00 | 0.35 |