Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:59
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2020-06-03 19:59:48
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29117.12 | 628.60 | 628.60 |
Net Site Energy | 29117.12 | 628.60 | 628.60 |
Total Source Energy | 89579.99 | 1933.92 | 1933.92 |
Net Source Energy | 89579.99 | 1933.92 | 1933.92 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 707.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3463.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 3042.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 438.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1960.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2048.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 478.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 1132.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5050.65 |
Humidification | 25.40 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 |
Heat Recovery | 49.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 557.21 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27852.63 | 1264.49 | 0.00 | 0.00 | 0.00 | 7340.27 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Boiler | 0.00 | 707.28 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 985.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 2477.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Interior Lighting | LightsWired | 3042.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 438.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1895.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2048.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 478.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 190.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Other | 941.97 | 0.00 | 0.00 | 0.00 | 0.00 | 5050.65 | |
Humidification | General | 25.40 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 |
Heat Recovery | General | 49.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 557.21 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 75.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 154.30 | 27.30 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 371.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 601.30 | 27.30 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 75.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 154.30 | 27.30 | 0.00 | 0.00 | 0.00 | 0.16 |
Other | 371.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 601.30 | 27.30 | 0.00 | 0.00 | 0.00 | 0.16 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27852.632 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27852.632 | 100.00 |
Total On-Site and Utility Electric Sources | 27852.632 | 100.00 |
Total Electricity End Uses | 27852.632 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 550.79 | 39.18 |
Air to Air Heat Recovery for Heating | 855.00 | 60.82 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1405.79 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7340.27 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7340.27 | 100.00 |
Total Water End Uses | 7340.27 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 44.83 |
Time Setpoint Not Met During Occupied Cooling | 174.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2540.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Meter |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | DUMMY BOILER |DXReportMonthly
| CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| DATACENTER_EXTRAWATERHEATC | CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS_HEATC | VAV_BOT WITH REHEAT_HEATC | VAV_MID WITH REHEAT_HEATC | VAV_TOP WITH REHEAT_HEATC | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | DATACENTER_EXTRAELECHEATC | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | CAV_BAS_COOLC | VAV_BOT WITH REHEAT_COOLC | VAV_MID WITH REHEAT_COOLC | VAV_TOP WITH REHEAT_COOLC | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP |PlantLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | DATACENTER BASEMENT SUPPLY FAN | DATACENTER BOT SUPPLY FAN | DATACENTER MID SUPPLY FAN | DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | SHWSYS1 PUMP | COOLSYS1 PUMP | PLANT CIRC PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| SHWSYS1 | HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| CAV_BAS | VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:59 |
RunPeriod | RUNPERIOD 1 |
Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Latitude [deg] | 40.65 |
Longitude [deg] | -73.8 |
Elevation [m] | 5.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6531 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6531 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6531 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6531 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6531 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6531 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6531 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6531 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6531 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6531 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6531 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6531 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6531 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6531 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6531 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6531 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6531 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6531 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6531 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6531 | 484.4232 | |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6531 | 19.08 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6531 | 19.08 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-AUG-15:09 | 02-JAN-07:10 | - | - | - | 01-SEP-14:09 |
Heating | 0.00 | 1881428.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 428106.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 259675.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 89544.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 132378.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 51160.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 89551.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1850033.16 | 1887124.39 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | Boiler | 0.00 | 1881428.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 261122.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 259675.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3725.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 85555.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 132378.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 51160.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 40303.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 766.70 | 0.00 | 0.00 | 0.00 |
Cooling | 10968.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 9636.31 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1389.49 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6209.88 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6486.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1514.34 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 3585.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 80.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 157.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 604.01 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 88209.29 | 1370.71 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.55 | 0.00 | 0.00 | 0.00 |
Cooling | 236.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 208.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 134.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 77.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1904.33 | 29.59 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 16.55 | 0.00 | 0.00 | 0.00 |
Cooling | 236.81 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 208.04 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.16 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 134.06 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 140.03 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 32.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 77.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.74 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 3.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 13.04 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1904.33 | 29.59 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
AirTerminal:SingleDuct:UncontrolledDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.25 |
DATACENTER BOT DIRECT AIR | 0.458932 |
DATACENTER MID DIRECT AIR | 4.37 |
DATACENTER TOP DIRECT AIR | 0.445360 |
DATACENTER BASEMENT DIRECT AIR | 21.19 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.53 | 0.343676 | 0.341000 | 1.89 | 0.916470 | 0.500000 | 0.001109 | 0.000420 | 1.89 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 51.95 | 0.366136 | 0.355000 | 18.44 | 0.976363 | 0.500000 | 0.001041 | 0.009372 | 18.44 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.31 | 0.358254 | 0.350000 | 1.86 | 0.955344 | 0.500000 | 0.001063 | 0.001792 | 2.41 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.838654 | 0.284766 | 0.283000 | 0.237339 | 0.759377 | 0.500000 | 0.001338 | 0.000208 | 0.280228 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.958667 | 0.160541 | 0.200000 | 0.191733 | 0.428109 | 0.500000 | 0.002373 | 0.000148 | 0.199523 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.944070 | 0.252975 | 0.251000 | 0.236962 | 0.674599 | 0.500000 | 0.001506 | 0.000264 | 0.356509 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.19 | 0.129212 | 0.200000 | 0.238221 | 0.344565 | 0.500000 | 0.002949 | 0.000123 | 0.238221 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 7.81 | 0.305856 | 0.297000 | 2.32 | 0.815617 | 0.500000 | 0.001246 | 0.004216 | 5.69 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 9.93 | 0.155055 | 0.200000 | 1.99 | 0.413480 | 0.500000 | 0.002457 | 0.002784 | 3.76 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 8.78 | 0.271949 | 0.264000 | 2.32 | 0.725198 | 0.500000 | 0.001401 | 0.004200 | 5.67 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 10.15 | 0.151687 | 0.200000 | 2.03 | 0.404498 | 0.500000 | 0.002512 | 0.002653 | 3.58 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.863908 | 0.276442 | 0.270000 | 0.233255 | 0.737179 | 0.500000 | 0.001378 | 0.000539 | 0.727701 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.01 | 0.152774 | 0.200000 | 0.201480 | 0.407398 | 0.500000 | 0.002494 | 0.000353 | 0.477450 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 0.986658 | 0.242055 | 0.237000 | 0.233838 | 0.645481 | 0.500000 | 0.001574 | 0.000536 | 0.724341 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.09 | 0.141359 | 0.200000 | 0.217751 | 0.376956 | 0.500000 | 0.002695 | 0.000343 | 0.463470 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18993.15 | 0.000420 | 330.58 |
CORE_MID VAV BOX REHEAT COIL | 424186.36 | 0.009372 | 8130.95 |
CORE_TOP VAV BOX REHEAT COIL | 81121.15 | 0.001792 | 1693.61 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 9413.72 | 0.000208 | 196.52 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6699.74 | 0.000148 | 139.85 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11965.81 | 0.000264 | 249.73 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5585.20 | 0.000123 | 107.40 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 190836.95 | 0.004216 | 3981.37 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 125997.64 | 0.002784 | 2628.60 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 190103.24 | 0.004200 | 3966.07 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 120080.88 | 0.002653 | 2505.24 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 24382.33 | 0.000539 | 508.60 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15996.85 | 0.000353 | 333.68 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 24269.97 | 0.000536 | 506.26 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 15529.12 | 0.000343 | 323.93 |
CAV_BAS_HEATC | 269723.23 | 0.005959 | 4923.34 |
VAV_BOT WITH REHEAT_HEATC | 72596.54 | 0.001604 | 999.64 |
VAV_MID WITH REHEAT_HEATC | 704473.12 | 0.015564 | 9630.72 |
VAV_TOP WITH REHEAT_HEATC | 72101.32 | 0.001593 | 986.15 |
DATACENTER_EXTRAWATERHEATC | 1029262.55 | 0.022740 | 19132.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
CAV_BAS | 5.25 | 5.25 | 5.25 | 5.25 | 5.25 | 5.25 | 1.00 | 1.00 | 5.25 |
VAV_BOT WITH REHEAT | 4.73 | 2.79 | 9.47 | 2.79 | 8.90 | 8.90 | 0.300000 | 0.313665 | 8.90 |
VAV_MID WITH REHEAT | 44.31 | 27.09 | 88.61 | 29.48 | 82.62 | 82.62 | 0.300000 | 0.356835 | 82.62 |
VAV_TOP WITH REHEAT | 4.63 | 2.74 | 9.26 | 4.81 | 8.48 | 8.48 | 0.300000 | 0.566864 | 8.48 |
AIRLOOP DATACENTER BASEMENT | 21.19 | 21.19 | 21.19 | 21.19 | 21.19 | 21.19 | 1.00 | 1.00 | 21.19 |
AIRLOOP DATACENTER BOT | 0.458932 | 0.458932 | 0.458932 | 0.458932 | 0.458932 | 0.458932 | 1.00 | 1.00 | 0.458932 |
AIRLOOP DATACENTER MID | 4.37 | 4.37 | 4.37 | 4.37 | 4.37 | 4.37 | 1.00 | 1.00 | 4.37 |
AIRLOOP DATACENTER TOP | 0.445360 | 0.445360 | 0.445360 | 0.445360 | 0.445360 | 0.445360 | 1.00 | 1.00 | 0.445360 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
CAV_BAS_OA_CONTROLLER | 5.25 | 1.20 |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.90 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 82.62 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.48 | |
AIRLOOP DATACENTER BASEMENT OA CONTROLLER | 21.19 | 0.338372 |
AIRLOOP DATACENTER BOT OA CONTROLLER | 0.458932 | |
AIRLOOP DATACENTER MID OA CONTROLLER | 4.37 | |
AIRLOOP DATACENTER TOP OA CONTROLLER | 0.445360 |
Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | Design Size Design Inlet Air Humidity Ratio | Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Outlet Air Humidity Ratio | |
CAV_BAS_COOLC | 112382.95 | 0.004781 | 5.25 | 0.010152 | 24.71 | 6.67 | 11.42 | 0.008281 |
VAV_BOT WITH REHEAT_COOLC | 225712.29 | 0.009602 | 8.90 | 0.010530 | 26.51 | 6.67 | 11.42 | 0.008281 |
VAV_MID WITH REHEAT_COOLC | 2190538.83 | 0.093191 | 82.62 | 0.010787 | 26.81 | 6.67 | 11.43 | 0.008281 |
VAV_TOP WITH REHEAT_COOLC | 212493.93 | 0.009040 | 8.48 | 0.010473 | 26.41 | 6.67 | 11.42 | 0.008281 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.25 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
CAV_BAS_COOLC_CONTROLLER | 0.004781 | 0.000100 |
CAV_BAS_HEATC_CONTROLLER | 0.005959 | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009602 | 0.000050 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.001604 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.093191 | 0.000005 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.015564 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009040 | 0.000053 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.001593 | |
DATACENTER_BAS_HEATC_CONTROLLER | 0.022740 | 0.000021 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.90 |
VAV_MID WITH REHEAT FAN | 82.62 |
VAV_TOP WITH REHEAT FAN | 8.48 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | 21.19 | 426579.85 | 308205.01 | 0.010447 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | 0.458932 | 9145.67 | 6640.18 | 0.000224 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | 4.37 | 87238.79 | 63299.51 | 0.002136 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | 0.445360 | 8883.37 | 6446.53 | 0.000218 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.19 | 21.19 | 21.19 | 21.19 | 426579.85 | 426579.85 | 20748.52 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.458932 | 0.458932 | 0.458932 | 0.458932 | 9145.67 | 9145.67 | 958.50 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.37 | 4.37 | 4.37 | 4.37 | 87238.79 | 87238.79 | 9584.96 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.445360 | 0.445360 | 0.445360 | 0.445360 | 8883.37 | 8883.37 | 958.50 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
DATACENTER BASEMENT SUPPLY FAN | 21.19 |
DATACENTER BOT SUPPLY FAN | 0.458932 |
DATACENTER MID SUPPLY FAN | 4.37 |
DATACENTER TOP SUPPLY FAN | 0.445360 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | 21.19 | 426579.85 | 0.010447 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | 0.458932 | 9145.67 | 0.000224 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | 4.37 | 87238.79 | 0.002136 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | 0.445360 | 8883.37 | 0.000218 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | 20748.52 | |
DATACENTER_EXTRAELECHEATC | 426579.85 | 10000000.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | 958.50 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | 9584.96 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | 958.50 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER BASEMENT HUMIDIFIER | 0.000172 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP SECONDARY | 0.116614 | 27930.03 |
HEATSYS1 PUMP | 0.075413 | 19267.08 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.116614 | 13.99 |
SHWSYS1 | 0.000440 | 0.052800 |
HEATSYS1 | 0.075413 | 9.05 |
COOLSYS1_SUPPLY | 0.116614 | 13.99 |
SINGLE WATER PLANT LOOP | 0.013025 | 1.56 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.116614 | 0.116614 | 489487.14 | 5.60 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000440 | 5.96 |
COOLSYS1 PUMP | 0.116614 | 9310.01 |
PLANT CIRC PUMP | 0.013025 | 3322.00 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000440 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3413318.86 | 1706659.43 | 0.075413 |
DUMMY BOILER | 536514.86 | 93894.07 | 0.013025 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.116614 | 0.058565 | 1380011.12 | 1386593.32 | 0.068617 |
COOLSYS1 CHILLER2 | 0.116614 | 0.058565 | 1380011.12 | 1386593.32 | 0.068617 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013025 | 139666.47 | 60409.09 | 69833.23 | 7879.72 | 21524.19 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.137235 | 16.47 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.137235 | 35060.15 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 53.06 | 1316140.16 | 10.61 | 164517.52 |
TOWERWATERSYS COOLTOWER 2 | 53.06 | 1316140.16 | 10.61 | 164517.52 |
Design Water Flow Rate [m3/s] Equipment # 48 | |
WSHPPLANT OPERATION SCHEME | 0.057018 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 12.47 | 25.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.653 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.495 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.653 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.723 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.653 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.952 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.653 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.952 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | N/A | 0.000 | 7.653 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 222.952 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | N/A | 0.000 | 7.653 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.076 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
16 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | BLDG_LIGHT_SCH | BASEMENT | 2779.43 | 149.6 | 21271.342 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21271.342 |
2 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 19103.160 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19103.160 |
3 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 2496.12 | 134.4 | 19103.160 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19103.160 |
4 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 2496.12 | 134.4 | 19103.160 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19103.160 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2398.592 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2398.592 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1545.744 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1545.744 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2398.645 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2398.645 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1545.744 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1545.744 |
9 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2398.592 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2398.592 |
10 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1545.744 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1545.744 |
11 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2398.645 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2398.645 |
12 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1545.744 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1545.744 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2398.592 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2398.592 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1545.744 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1545.744 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2398.645 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2398.645 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1545.744 | 7.653 | 142.186 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1545.744 |
17 | DATACENTER_BASEMENT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 5997.608 | 7.653 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5997.608 |
18 | DATACENTER_BOT_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 277.065 | 7.653 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 277.065 |
19 | DATACENTER_MID_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 277.065 | 7.653 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 277.065 |
20 | DATACENTER_TOP_LIGHTS | BLDG_LIGHT_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 277.065 | 7.653 | N/A | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 277.065 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 0.0 | 379632.522 | 484.423 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 0.0 | 7794.422 | 215.299 | N/A | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL | 20 | 3 | 9 | 0.167 | 0.6478 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | BASEMENT_WALL_EAST_CFACTOR | 30 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | BASEMENT_WALL_SOUTH_CFACTOR | 31 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | BASEMENT_WALL_NORTH_CFACTOR | 32 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 33 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 34 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 35 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.376 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637443 | 3.4637443 | 3.4637443 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.49119318E-15 | -0.33550344E-15 | -0.16284357E-09 | -0.12303907E-16 |
51 | 8 | 0.23714982E-07 | 0.88106564E-13 | 0.39686193E-03 | -0.26964751E-09 |
52 | 7 | -0.12809687E-01 | 0.44996568E-08 | -0.23903550E-01 | 0.14565082E-03 |
53 | 6 | 0.42078637 | 0.15559313E-05 | 0.48521577 | -0.49297162E-02 |
54 | 5 | -5.3411857 | 0.57794581E-04 | -4.5419698 | 0.65051509E-01 |
55 | 4 | 33.669005 | 0.47055528E-03 | 21.833772 | -0.43096765 |
56 | 3 | -112.64328 | 0.10212385E-02 | -56.401742 | 1.5356680 |
57 | 2 | 198.53538 | 0.57229644E-03 | 78.588493 | -2.9230166 |
58 | 1 | -171.68312 | 0.60883279E-04 | -55.462911 | 2.7546764 |
59 | 0 | 57.057407 | 0.34515708E-06 | 15.524833 | |
60 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
61 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
62 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
63 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
64 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
65 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
66 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
67 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
68 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
69 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
70 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
71 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
72 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
73 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
74 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
75 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
76 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
77 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
78 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
79 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
80 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
81 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
82 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
83 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
84 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
85 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
86 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
87 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
88 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
89 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
90 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
91 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
92 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
93 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
94 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
95 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
96 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
97 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
98 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
99 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
100 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
101 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
102 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
103 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
104 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
105 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
106 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
107 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.38_SHGC_0.36 | 29 | 1 | VerySmooth | 2.159 | 0.355 | 0.274 | 0.361 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 3.45900E-002 | 0.27318 | 0.51781 | 0.51781 | 0.36000 | 0.14234 | 0.19141 | 0.00000 | 0.84000 | 0.84000 | 0.11893 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Zone Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Zones | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Zone Name | Number of Adjacent Zones with Windows | Adjacent Zone Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.000 | 0.0000 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.119 | 3.783E-004 | 5.690E-004 | 0.496 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.831E-002 | 3.877E-004 | 5.690E-004 | 0.509 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.642E-004 | 5.690E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.609E-002 | 3.767E-004 | 5.690E-004 | 0.494 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.744E-005 | 5.690E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.741E-005 | 4.376E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72962.79648 | 72962.79648 | 5.25434 | 5.25434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20008 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 2779.42662 | 149.60210 | 1.20008 | 0.00000 | |
3 | CORE_BOTTOM | Cooling | 76855.56555 | 76855.56555 | 5.53441 | 5.53441 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07776 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 | |
5 | CORE_MID | Cooling | 721616.96896 | 721616.96896 | 51.94908 | 51.94908 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
6 | CORE_MID | Heating | 238586.34182 | 238586.34182 | 10.05334 | 10.77757 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 10.77757 | 0.00000 |
7 | CORE_TOP | Cooling | 73739.34203 | 73739.34203 | 5.30920 | 5.30920 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
8 | CORE_TOP | Heating | 56824.65593 | 56824.65593 | 2.41419 | 2.41419 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 2496.12046 | 134.35320 | 1.07776 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 11637.96017 | 11637.96017 | 0.83865 | 0.83865 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 6600.65202 | 6600.65202 | 0.28023 | 0.28023 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 13284.24483 | 13284.24483 | 0.95867 | 0.95867 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 4695.94992 | 4695.94992 | 0.19952 | 0.19952 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 12987.49813 | 12987.49813 | 0.94407 | 0.94407 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 31.73000 | 1.40969E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 8383.42797 | 8383.42797 | 0.35651 | 0.35651 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 16386.11721 | 16386.11721 | 1.19111 | 1.19111 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 3197.74577 | 3197.74577 | 0.13544 | 0.13544 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 108377.78838 | 108377.78838 | 7.80826 | 7.80826 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 26.62400 | 1.40969E-002 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 133596.19159 | 133596.19159 | 5.69280 | 5.69280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 1.35323 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 136547.45603 | 136547.45603 | 9.92583 | 9.92583 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 27.09267 | 1.40969E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 88202.81638 | 88202.81638 | 3.75881 | 3.75881 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 120810.82283 | 120810.82283 | 8.78200 | 8.78200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 31.79167 | 1.40969E-002 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 133083.31247 | 133083.31247 | 5.67086 | 5.67086 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 1.35326 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 139579.33449 | 139579.33449 | 10.14625 | 10.14625 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 84066.56593 | 84066.56593 | 3.58195 | 3.58195 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 0.87207 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 11884.38834 | 11884.38834 | 0.86391 | 0.86391 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 32.10000 | 1.40969E-002 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 17064.60046 | 17064.60046 | 0.72770 | 0.72770 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41284 | 16.86939 | 0.13532 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 13858.45136 | 13858.45136 | 1.00740 | 1.00740 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 27.79567 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 11195.67798 | 11195.67798 | 0.47745 | 0.47745 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 13573.02273 | 13573.02273 | 0.98666 | 0.98666 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 31.91500 | 1.40969E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 16986.05057 | 16986.05057 | 0.72434 | 0.72434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 14977.64357 | 14977.64357 | 1.08876 | 1.08876 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.16267 | 1.40969E-002 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 10868.66331 | 10868.66331 | 0.46347 | 0.46347 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -10.70000 | 1.50390E-003 | 201.97515 | 10.87127 | 8.72074E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8005.52707 | 8005.52707 | 0.45893 | 0.45893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.40969E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
35 | DATACENTER_MID_ZN_6 | Cooling | 76274.21759 | 76274.21759 | 4.37256 | 4.37256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 29.58400 | 1.40969E-002 | 36.20274 | 0.00000 | 0.15631 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 0.15631 | 0.00000 | |
37 | DATACENTER_TOP_ZN_6 | Cooling | 7768.77500 | 7768.77500 | 0.44536 | 0.44536 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 29.76900 | 1.40969E-002 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 36.20274 | 0.00000 | 1.56314E-002 | 0.00000 | |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 369548.14045 | 369548.14045 | 21.18504 | 21.18504 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 24.93433 | 1.40969E-002 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70000 | 1.50390E-003 | 783.67941 | 0.00000 | 0.33837 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | CAV_BAS | Cooling | Sensible | 75403.78 | 5.25434 | 5.25434 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | CAV_BAS | Heating | Sensible | 73587.49 | 1.20008 | 1.20008 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
3 | VAV_BOT WITH REHEAT | Cooling | Sensible | 134345.20 | 8.89958 | 8.89958 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_BOT WITH REHEAT | Heating | Sensible | 58249.57 | 2.04946 | 2.04946 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
5 | VAV_MID WITH REHEAT | Cooling | Sensible | 1216984.59 | 82.62091 | 82.62091 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_MID WITH REHEAT | Heating | Sensible | 720762.45 | 29.48200 | 29.48200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 |
7 | VAV_TOP WITH REHEAT | Cooling | Sensible | 139054.92 | 8.48027 | 8.48027 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
8 | VAV_TOP WITH REHEAT | Heating | Sensible | 71629.67 | 4.80715 | 4.80715 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 365348.85 | 21.18504 | 21.18504 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 20748.52 | 0.33837 | 0.33837 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 7930.73 | 0.45893 | 0.45893 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 958.50 | 1.56314E-002 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 75583.28 | 4.37256 | 4.37256 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 9584.96 | 0.15631 | 0.15631 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7700.99 | 0.44536 | 0.44536 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 958.50 | 1.56314E-002 | 1.56314E-002 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:Uncontrolled | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.25434 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.53441 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34368 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34100 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88723 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91647 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.10860E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.19630E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88723 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18993.14959 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.19630E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 330.58066 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 51.94908 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36614 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35500 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.44192 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97636 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04060E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.37188E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.44192 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 424186.35853 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.37188E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8130.95402 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.30920 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35825 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.85822 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95534 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06349E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.79227E-003 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.41419 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 81121.14991 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.79227E-003 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1693.61180 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83865 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28477 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.28300 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23734 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75938 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33794E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07985E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.28023 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9413.71538 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07985E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 196.51990 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.95867 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16054 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19173 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42811 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37323E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.48023E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.19952 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6699.73769 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.48023E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 139.84529 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.94407 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25297 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.25100 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23696 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.67460 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.50608E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.64370E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35651 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11965.81032 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.64370E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 249.73155 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.19111 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12921 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23822 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.34456 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.94865E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23398E-004 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23822 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5585.20006 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23398E-004 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 107.40251 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 7.80826 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30586 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29700 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31905 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.81562 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.24568E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.21631E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.69280 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 190836.95116 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.21631E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3981.36616 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 9.92583 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15506 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.98517 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41348 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45719E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.78376E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.75881 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 125997.64109 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78376E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2628.60048 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.78200 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27195 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26400 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.31845 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.72520 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.40100E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.20010E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.67086 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 190103.23640 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.20010E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 3966.06980 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.14625 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15169 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02925 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40450 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51176E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.65304E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.58195 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 120080.87577 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.65304E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2505.23720 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.86391 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27644 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23326 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73718 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37823E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.38698E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72770 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24382.32524 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38698E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 508.60451 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.00740 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15277 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20148 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40740 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.49387E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.53431E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.47745 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15996.84914 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.53431E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 333.68356 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98666 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24206 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23700 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23384 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64548 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57402E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.36215E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.72434 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24269.96592 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.36215E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 506.26202 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.08876 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14136 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21775 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37696 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69527E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.43097E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.46347 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15529.11934 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.43097E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 323.93127 |
212 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BOT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.45893 |
213 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER MID DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.37256 |
214 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER TOP DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.44536 |
215 | AirTerminal:SingleDuct:Uncontrolled | DATACENTER BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.18504 |
216 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.25434 |
217 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.25434 |
218 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.25434 |
219 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.25434 |
220 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.25434 |
221 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.25434 |
222 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
223 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
224 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.73345 |
225 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.79149 |
226 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.46690 |
227 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.79149 |
228 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.89958 |
229 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.89958 |
230 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31367 |
232 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 44.30571 |
233 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 27.09384 |
234 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 88.61143 |
235 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 29.48200 |
236 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 82.62091 |
237 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 82.62091 |
238 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.35683 |
240 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.62796 |
241 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.74455 |
242 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.25593 |
243 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.80715 |
244 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.48027 |
245 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.48027 |
246 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
247 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.56686 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.18504 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.18504 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.18504 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.18504 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.18504 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.18504 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 1.00000 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.45893 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.45893 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.45893 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.45893 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.45893 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.45893 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.37256 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.37256 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.37256 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.37256 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.37256 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.37256 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.44536 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.44536 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.44536 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.44536 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.44536 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.44536 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.25434 |
281 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.89958 |
282 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 82.62091 |
283 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.48027 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.18504 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.45893 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.37256 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.44536 |
288 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.25434 |
289 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20008 |
290 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Coil Load [W] | 112382.95424 |
291 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Water Flow Rate [m3/s] | 4.78103E-003 |
292 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Air Flow Rate [m3/s] | 5.25434 |
293 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.01523E-002 |
294 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Air Temperature [C] | 24.70781 |
295 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
296 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42381 |
297 | Coil:Cooling:Water | CAV_BAS_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
298 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Rated Capacity [W] | 269723.23319 |
299 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 5.95921E-003 |
300 | Coil:Heating:Water | CAV_BAS_HEATC | Design Size U-Factor Times Area Value [W/K] | 4923.33932 |
301 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.25434 |
302 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.78103E-003 |
303 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.96000E-005 |
304 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 5.95921E-003 |
305 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.89958 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
307 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 225712.29066 |
308 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 9.60232E-003 |
309 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.89958 |
310 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.05302E-002 |
311 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.51405 |
312 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
313 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42475 |
314 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
315 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 72596.53671 |
316 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.60393E-003 |
317 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 999.64251 |
318 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.89958 |
319 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.60232E-003 |
320 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 4.95912E-005 |
321 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.60393E-003 |
322 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 82.62091 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38036 |
324 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 2190538.83265 |
325 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 9.31906E-002 |
326 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 82.62091 |
327 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.07867E-002 |
328 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.80892 |
329 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
330 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42539 |
331 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
332 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 704473.12289 |
333 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.55645E-002 |
334 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 9630.72068 |
335 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 82.62091 |
336 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.31906E-002 |
337 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.10986E-006 |
338 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.55645E-002 |
339 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.48027 |
340 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53804 |
341 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Coil Load [W] | 212493.92811 |
342 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Water Flow Rate [m3/s] | 9.03998E-003 |
343 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Air Flow Rate [m3/s] | 8.48027 |
344 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Humidity Ratio | 1.04726E-002 |
345 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Air Temperature [C] | 26.41041 |
346 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Inlet Water Temperature [C] | 6.67000 |
347 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Temperature [C] | 11.42461 |
348 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | Design Size Design Outlet Air Humidity Ratio | 8.28082E-003 |
349 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Rated Capacity [W] | 72101.32373 |
350 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size Maximum Water Flow Rate [m3/s] | 1.59299E-003 |
351 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | Design Size U-Factor Times Area Value [W/K] | 986.14655 |
352 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.48027 |
353 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.03998E-003 |
354 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.26760E-005 |
355 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 1.59299E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.18504 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT OA CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33837 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.18504 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Total Cooling Capacity [W] | 426579.84682 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Sensible Cooling Capacity [W] | 308205.00987 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04469E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.18504 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.18504 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.18504 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.18504 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 426579.84682 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 426579.84682 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 20748.52325 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.18504 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Air Flow Rate [m3/s] | 21.18504 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Heating Capacity [W] | 426579.84682 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Design Size Rated Water Flow Rate [m3/s] | 1.04469E-002 |
374 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Design Size Nominal Capacity [W] | 20748.52325 |
375 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.71770E-004 |
376 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER BASEMENT HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | Design Size Nominal Capacity [W] | 426579.84682 |
380 | Coil:Heating:Electric | DATACENTER_EXTRAELECHEATC | User-Specified Nominal Capacity [W] | 10000000.00000 |
381 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Rated Capacity [W] | 1029262.55398 |
382 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size Maximum Water Flow Rate [m3/s] | 2.27403E-002 |
383 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | Design Size U-Factor Times Area Value [W/K] | 19132.74387 |
384 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.27403E-002 |
385 | Controller:WaterCoil | DATACENTER_BAS_HEATC_CONTROLLER | Controller Convergence Tolerance | 2.09404E-005 |
386 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.45893 |
387 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.45893 |
388 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Total Cooling Capacity [W] | 9145.67071 |
389 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Sensible Cooling Capacity [W] | 6640.18187 |
390 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.23977E-004 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.45893 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.45893 |
393 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.45893 |
394 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.45893 |
395 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9145.67071 |
396 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9145.67071 |
397 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.49582 |
398 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
399 | Fan:OnOff | DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.45893 |
400 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Air Flow Rate [m3/s] | 0.45893 |
401 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Heating Capacity [W] | 9145.67071 |
402 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Design Size Rated Water Flow Rate [m3/s] | 2.23977E-004 |
403 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Design Size Nominal Capacity [W] | 958.49582 |
404 | Controller:OutdoorAir | AIRLOOP DATACENTER MID OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.37256 |
405 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.37256 |
406 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Total Cooling Capacity [W] | 87238.79464 |
407 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Sensible Cooling Capacity [W] | 63299.51151 |
408 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.13647E-003 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.37256 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.37256 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.37256 |
412 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.37256 |
413 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 87238.79464 |
414 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 87238.79464 |
415 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 9584.95818 |
416 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
417 | Fan:OnOff | DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.37256 |
418 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Air Flow Rate [m3/s] | 4.37256 |
419 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Heating Capacity [W] | 87238.79464 |
420 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Design Size Rated Water Flow Rate [m3/s] | 2.13647E-003 |
421 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Design Size Nominal Capacity [W] | 9584.95818 |
422 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP OA CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.44536 |
423 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.44536 |
424 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Total Cooling Capacity [W] | 8883.37368 |
425 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Sensible Cooling Capacity [W] | 6446.53422 |
426 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.17553E-004 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.44536 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.44536 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.44536 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.44536 |
431 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 8883.37368 |
432 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 8883.37368 |
433 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 958.49582 |
434 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
435 | Fan:OnOff | DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.44536 |
436 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Air Flow Rate [m3/s] | 0.44536 |
437 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Heating Capacity [W] | 8883.37368 |
438 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Design Size Rated Water Flow Rate [m3/s] | 2.17553E-004 |
439 | Coil:Heating:Electric | HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Design Size Nominal Capacity [W] | 958.49582 |
440 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.11661 |
441 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 27930.03291 |
442 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.11661 |
443 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.99367 |
444 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.11661 |
445 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.11661 |
446 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 489487.14387 |
447 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
448 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
449 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
450 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
451 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 5.95777 |
452 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
453 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 7.54131E-002 |
454 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 9.04957 |
455 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 7.54131E-002 |
456 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 19267.08238 |
457 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3413318.85606 |
458 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1706659.43000 |
459 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 7.54131E-002 |
460 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.11661 |
461 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.99367 |
462 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.11661 |
463 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 9310.01097 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11661 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.85650E-002 |
466 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1380011.11713 |
467 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1386593.32500 |
468 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.86174E-002 |
469 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.11661 |
470 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.85650E-002 |
471 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1380011.11713 |
472 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1386593.32500 |
473 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.86174E-002 |
474 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.30249E-002 |
475 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.56299 |
476 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.30249E-002 |
477 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3322.00482 |
478 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.30249E-002 |
479 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
480 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60409.09382 |
481 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
482 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
483 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21524.19224 |
484 | Boiler:HotWater | DUMMY BOILER | Design Size Nominal Capacity [W] | 536514.85931 |
485 | Boiler:HotWater | DUMMY BOILER | User-Specified Nominal Capacity [W] | 93894.07000 |
486 | Boiler:HotWater | DUMMY BOILER | Design Size Design Water Flow Rate [m3/s] | 1.30249E-002 |
487 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.13723 |
488 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 16.46817 |
489 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.13723 |
490 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 35060.15360 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 53.06213 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1316140.15867 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.61243 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 164517.51983 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 53.06213 |
496 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1316140.15867 |
497 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.61243 |
498 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 164517.51983 |
499 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.70180E-002 |
500 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 48 | 5.70180E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 18018.94 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 402663.88 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 76965.85 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 8931.52 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 6356.56 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11352.89 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 5301.74 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 181062.03 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 119543.88 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 180365.90 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 113930.17 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 23133.44 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 15177.48 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 23026.84 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14733.70 |
16 | Coil:Heating:Water | CAV_BAS_HEATC | 210412.38 |
17 | Coil:Heating:Water | VAV_BOT WITH REHEAT_HEATC | 52063.20 |
18 | Coil:Heating:Water | VAV_MID WITH REHEAT_HEATC | 499690.70 |
19 | Coil:Heating:Water | VAV_TOP WITH REHEAT_HEATC | 51179.07 |
20 | Coil:Heating:Water | DATACENTER_EXTRAWATERHEATC | 825259.38 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | CAV_BAS_COOLC | 143367.30 | 97756.74 | 45610.55 | 0.68 | 17684.80 | 179.37 |
2 | Coil:Cooling:Water | VAV_BOT WITH REHEAT_COOLC | 259506.91 | 173142.33 | 86364.59 | 0.67 | 32151.51 | 326.10 |
3 | Coil:Cooling:Water | VAV_MID WITH REHEAT_COOLC | 2441874.40 | 1622097.14 | 819777.26 | 0.66 | 301624.51 | 3059.24 |
4 | Coil:Cooling:Water | VAV_TOP WITH REHEAT_COOLC | 246384.17 | 164584.61 | 81799.56 | 0.67 | 30563.05 | 309.99 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.16 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.16 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.38_SHGC_0.36 | N/A | 2.159 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.648 | 0.591 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 12 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 1.2399182029E-003 | 1.2472987653E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.0278784045E-003 | 2.8716812145E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 3.2097134336E-002 | 1.7815462825E-002 | Pass | Pass | 0.4862794233 | 0.4932849202 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.4231493458E-002 | 6.9109250068E-002 | Pass | Pass | 1.7795934730 | 11.2381228222 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.6843602225E-002 | 2.0759489605E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.5703826738E-002 | 5.2673578515E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.7114595082E-002 | 8.5818391910E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.5842998346E-002 | 3.0473714465E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.5543808732 | 0.4819390981 | Pass | Pass | 0.7450564189 | 0.6713727877 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.5119368761 | 0.5243791375 | Pass | Pass | 0.7059182406 | 0.6474808529 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.3862448307 | 0.4392835137 | Pass | Pass | 1.4052584770 | 6.6649611599 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.4775114344 | 0.4832479688 | Pass | Pass | 0.7058842913 | 0.6556949792 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.7405133813 | 0.6041850707 | Pass | Pass | 0.6668784414 | 0.5946529959 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.6871018369 | 0.6851297378 | Pass | Pass | 0.6762751643 | 0.6105394719 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.5523698219 | 0.5821631224 | Pass | Pass | 2.5703579332 | 18.4258843263 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.6623311036 | 0.6631339240 | Pass | Pass | 0.6965729404 | 0.6453232079 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 1.0449080131E-002 | 7.3986949136E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.7221164981E-002 | 4.7896294745E-002 | Pass | Pass | 0.4853174730 | 0.4834362445 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1502431668 | 0.1117122262 | Pass | Pass | 0.4952692429 | 0.4895645272 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.2287854714E-015 | 5.9124966165E-015 | Pass | Pass | 9.7476315136E-003 | 7.0436375957E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.9235942467E-003 | 7.2504925969E-003 | Pass | Pass | 3.2937909426E-003 | 4.1755952757E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.4301744501E-002 | 1.0408509229E-002 | Pass | Pass | 4.9679290673E-003 | 5.8039599910E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.2699279523E-014 | 7.4900641287E-014 | Pass | Pass | 4.7343270030E-005 | 2.8833815006E-005 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.591 | 0.648 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E | |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S | |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N | |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S | |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.38_SHGC_0.36 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.38_SHGC_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.38_SHGC_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.38_SHGC_0.36 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.159 | 0.355 | 0.361 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.355 | 0.361 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.355 | 0.361 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.159 | 0.355 | 0.361 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.159 | 0.355 | 0.361 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.355 | 0.361 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.355 | 0.361 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.159 | 0.355 | 0.361 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.38_SHGC_0.36 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.159 | 0.355 | 0.361 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 3476.85 | 2.159 | 0.355 | 0.361 | ||||||||||||
North Total or Average | 1043.06 | 2.159 | 0.355 | 0.361 | ||||||||||||
Non-North Total or Average | 2433.80 | 2.159 | 0.355 | 0.361 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 2.281 | 3.464 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | 7.6531 | 2779.43 | 21271.34 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 193.76 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 7.6531 | 2496.12 | 19103.16 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 174.01 |
CORE_MID_LIGHTS | CORE_MID | 7.6531 | 24961.20 | 191031.60 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 1740.12 |
CORE_TOP_LIGHTS | CORE_TOP | 7.6531 | 2496.12 | 19103.16 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 174.01 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 7.6531 | 313.41 | 2398.59 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 38.08 | 0.0000 | Y | 17.15 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 7.6531 | 201.98 | 1545.74 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 38.08 | 0.0000 | Y | 11.05 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 7.6531 | 313.42 | 2398.64 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 37.96 | 0.0000 | Y | 17.09 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 7.6531 | 201.98 | 1545.74 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 37.98 | 0.0000 | Y | 11.02 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 7.6531 | 3134.13 | 23985.92 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 38.10 | 0.0000 | Y | 171.56 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 7.6531 | 2019.75 | 15457.44 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 38.09 | 0.0000 | Y | 110.51 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 7.6531 | 3134.20 | 23986.45 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 37.97 | 0.0000 | Y | 170.97 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 7.6531 | 2019.75 | 15457.44 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 37.98 | 0.0000 | Y | 110.21 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 7.6531 | 313.41 | 2398.59 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 38.10 | 0.0000 | Y | 17.16 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 7.6531 | 201.98 | 1545.74 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 38.09 | 0.0000 | Y | 11.05 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 7.6531 | 313.42 | 2398.64 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 37.97 | 0.0000 | Y | 17.10 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 7.6531 | 201.98 | 1545.74 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 37.98 | 0.0000 | Y | 11.02 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | 7.6531 | 783.68 | 5997.61 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 54.63 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | 7.6531 | 36.20 | 277.06 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 2.52 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | 7.6531 | 362.03 | 2770.65 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 25.24 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | 7.6531 | 36.20 | 277.06 | LightsWired | BLDG_LIGHT_SCH | 49.80 | 168.00 | 48.53 | 0.0000 | Y | 2.52 |
Interior Lighting Total | 7.6531 | 46320.38 | 354496.35 | 946.96 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2398.59 | 925.14 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2398.59 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1545.74 | 596.19 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1545.74 | 0.00 |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2398.64 | 925.16 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2398.64 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1545.74 | 596.19 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1545.74 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2398.59 | 925.14 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2398.59 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1545.74 | 596.19 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1545.74 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2398.64 | 925.16 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2398.64 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1545.74 | 596.19 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1545.74 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2398.59 | 925.14 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2398.59 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1545.74 | 596.19 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1545.74 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.39 | 2398.64 | 925.16 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous | 0.00 | 2398.64 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.39 | 1545.74 | 596.19 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous | 0.00 | 1545.74 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9734.40 | AstronomicalClock | - | 42.43 | 42.43 | 77.54 | |
EXTERIOR_LIGHTS_B | 26995.00 | AstronomicalClock | - | 83.64 | 71.28 | 361.20 | |
Exterior Lighting Total | 36729.40 | 438.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2734824.22 | |||
HEATSYS1 BOILER | Boiler:HotWater | 1706659.43 | 0.81 | ||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1386593.32 | 6.28 | 7.08 | 24.16 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1386593.32 | 6.28 | 7.08 | 24.16 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||
DUMMY BOILER | Boiler:HotWater | 93894.07 | 0.80 | ||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1316140.16 | |||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1316140.16 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
CAV_BAS_COOLC | Coil:Cooling:Water | 112382.95 | 143367.30 | 97756.74 | 45610.55 | 0.68 | - | 17684.80 | 179.37 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | 225712.29 | 259506.91 | 173142.33 | 86364.59 | 0.67 | - | 32151.51 | 326.10 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | 2190538.83 | 2441874.40 | 1622097.14 | 819777.26 | 0.66 | - | 301624.51 | 3059.24 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | 212493.93 | 246384.17 | 164584.61 | 81799.56 | 0.67 | - | 30563.05 | 309.99 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 426579.85 | 308205.01 | 118374.84 | 0.72 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9145.67 | 6640.18 | 2505.49 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | Coil:Cooling:WaterToAirHeatPump:EquationFit | 87238.79 | 63299.51 | 23939.28 | 0.73 | 0.00 | |||
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | Coil:Cooling:WaterToAirHeatPump:EquationFit | 8883.37 | 6446.53 | 2436.84 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18993.15 | 18018.94 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 424186.36 | 402663.88 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 81121.15 | 76965.85 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 9413.72 | 8931.52 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 6699.74 | 6356.56 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11965.81 | 11352.89 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 5585.20 | 5301.74 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 190836.95 | 181062.03 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 125997.64 | 119543.88 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 190103.24 | 180365.90 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 120080.88 | 113930.17 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 24382.33 | 23133.44 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 15996.85 | 15177.48 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24269.97 | 23026.84 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 15529.12 | 14733.70 | - |
CAV_BAS_HEATC | Coil:Heating:Water | 269723.23 | 210412.38 | - |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | 72596.54 | 52063.20 | - |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | 704473.12 | 499690.70 | - |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | 72101.32 | 51179.07 | - |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | Coil:Heating:WaterToAirHeatPump:EquationFit | 426579.85 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | Coil:Heating:WaterToAirHeatPump:EquationFit | 9145.67 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | Coil:Heating:WaterToAirHeatPump:EquationFit | 87238.79 | 0.00 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | Coil:Heating:WaterToAirHeatPump:EquationFit | 8883.37 | 0.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | 20748.52 | 1.00 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | 10000000.00 | 1.00 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | 1029262.55 | 825259.38 | - |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | 958.50 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | 9584.96 | 1.00 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | 958.50 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.25 | 8909.54 | 1695.65 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.90 | 20324.21 | 2283.73 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 82.62 | 188683.68 | 2283.73 | 1.00 | 1.07 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.48 | 19366.62 | 2283.73 | 1.00 | 1.12 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 |
DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.19 | 35124.23 | 1657.97 | 1.00 | 1.13 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.46 | 514.05 | 1120.11 | 1.00 | 1.65 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.37 | 4897.74 | 1120.11 | 1.00 | 1.16 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.45 | 498.85 | 1120.11 | 1.00 | 1.66 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 168135.01 | 0.116614 | 27930.03 | 239508.57 | 0.90 | General |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 179352.00 | 0.075413 | 19267.08 | 255487.18 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 56045.00 | 0.116614 | 9310.01 | 79836.19 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013025 | 3322.00 | 255050.01 | 0.90 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 179344.01 | 0.137235 | 35060.15 | 255475.80 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.00 | 0.00 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72962.80 | 72962.80 | 26.25 | 5.254 | 5.254 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 26.62 | 0.01410 | 1.200 | 0.00 |
CORE_BOTTOM | 76855.57 | 76855.57 | 30.79 | 5.534 | 5.534 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 26.62 | 0.01410 | 1.078 | 0.00 |
CORE_MID | 721616.97 | 721616.97 | 289.10 | 51.949 | 51.949 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 26.62 | 0.01410 | 10.778 | 0.00 |
CORE_TOP | 73739.34 | 73739.34 | 29.54 | 5.309 | 5.309 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00892 | 26.62 | 0.01410 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 11637.96 | 11637.96 | 37.13 | 0.839 | 0.839 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 26.62 | 0.01410 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 13284.24 | 13284.24 | 65.77 | 0.959 | 0.959 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00872 | 26.62 | 0.01410 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12987.50 | 12987.50 | 41.44 | 0.944 | 0.944 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 24.00 | 0.00884 | 31.73 | 0.01410 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 16386.12 | 16386.12 | 81.13 | 1.191 | 1.191 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00867 | 31.16 | 0.01410 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 108377.79 | 108377.79 | 345.80 | 7.808 | 7.808 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00900 | 26.62 | 0.01410 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 136547.46 | 136547.46 | 676.06 | 9.926 | 9.926 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.00 | 24.00 | 0.00875 | 27.09 | 0.01410 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 120810.82 | 120810.82 | 385.46 | 8.782 | 8.782 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00892 | 31.79 | 0.01410 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 139579.33 | 139579.33 | 691.07 | 10.146 | 10.146 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00874 | 31.16 | 0.01410 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 11884.39 | 11884.39 | 37.92 | 0.864 | 0.864 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00896 | 32.10 | 0.01410 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 13858.45 | 13858.45 | 68.61 | 1.007 | 1.007 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:50:00 | 24.00 | 24.00 | 0.00876 | 27.80 | 0.01410 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 13573.02 | 13573.02 | 43.31 | 0.987 | 0.987 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00890 | 31.92 | 0.01410 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14977.64 | 14977.64 | 74.16 | 1.089 | 1.089 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00874 | 31.16 | 0.01410 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8005.53 | 8005.53 | 221.13 | 0.459 | 0.459 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 29.58 | 0.01410 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 76274.22 | 76274.22 | 2106.86 | 4.373 | 4.373 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00850 | 29.58 | 0.01410 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 7768.78 | 7768.78 | 214.59 | 0.445 | 0.445 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 27.00 | 27.00 | 0.00850 | 29.77 | 0.01410 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 369548.14 | 369548.14 | 471.56 | 21.185 | 21.185 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 27.00 | 27.00 | 0.00850 | 24.93 | 0.01410 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.200 | 0.00 | |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 | |
CORE_MID | 238586.34 | 238586.34 | 95.58 | 10.053 | 10.778 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 10.778 | 0.00 |
CORE_TOP | 56824.66 | 56824.66 | 22.77 | 2.414 | 2.414 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -10.70 | 0.00150 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 6600.65 | 6600.65 | 21.06 | 0.280 | 0.280 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00680 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 4695.95 | 4695.95 | 23.25 | 0.200 | 0.200 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00702 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 8383.43 | 8383.43 | 26.75 | 0.357 | 0.357 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00729 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 3197.75 | 3197.75 | 15.83 | 0.135 | 0.135 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00594 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 133596.19 | 133596.19 | 426.26 | 5.693 | 5.693 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 88202.82 | 88202.82 | 436.70 | 3.759 | 3.759 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 133083.31 | 133083.31 | 424.62 | 5.671 | 5.671 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00761 | -10.70 | 0.00150 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 84066.57 | 84066.57 | 416.22 | 3.582 | 3.582 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00758 | -10.70 | 0.00150 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 17064.60 | 17064.60 | 54.45 | 0.728 | 0.728 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 11195.68 | 11195.68 | 55.43 | 0.477 | 0.477 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -10.70 | 0.00150 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 16986.05 | 16986.05 | 54.20 | 0.724 | 0.724 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00766 | -10.70 | 0.00150 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 10868.66 | 10868.66 | 53.81 | 0.463 | 0.463 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00765 | -10.70 | 0.00150 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.016 | 0.00 | |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.156 | 0.00 | |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.016 | 0.00 | |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 0.00 | 18.00 | 0.00800 | -10.70 | 0.00150 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
CAV_BAS | 5.25 | 5.25 | 1.20 | 1.20 | 5.2543 | 5.2543 | 5.2543 | 1.0000 | 1.0000 |
VAV_BOT WITH REHEAT | 8.90 | 8.90 | 2.05 | 2.05 | 8.8996 | 2.7915 | 8.8996 | 0.3137 | 0.3000 |
VAV_MID WITH REHEAT | 82.62 | 82.62 | 29.48 | 29.48 | 82.6209 | 29.4820 | 82.6209 | 0.3568 | 0.3000 |
VAV_TOP WITH REHEAT | 8.48 | 8.48 | 4.81 | 4.81 | 8.4803 | 4.8072 | 8.4803 | 0.5669 | 0.3000 |
AIRLOOP DATACENTER BASEMENT | 21.19 | 21.19 | 0.34 | 0.34 | 21.1850 | 21.1850 | 21.1850 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.46 | 0.46 | 0.02 | 0.02 | 0.4589 | 0.4589 | 0.4589 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.37 | 4.37 | 0.16 | 0.16 | 4.3726 | 4.3726 | 4.3726 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.45 | 0.45 | 0.02 | 0.02 | 0.4454 | 0.4454 | 0.4454 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18993.150 | 18993.150 | 1.887233 | 0.00041963 | 330.581 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18018.94 | 18993.15 | 1.887233 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19069.55 | 19069.55 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 424186.359 | 424186.359 | 18.441924 | 0.00937188 | 8130.954 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 402663.88 | 424186.36 | 18.441924 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 238586.34 | 0.00 | 426200.89 | 426200.89 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 81121.150 | 81121.150 | 2.414193 | 0.00179227 | 1693.612 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76965.85 | 81121.15 | 2.414193 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00800000 | 51.6928 | 56824.66 | 0.00 | 81491.54 | 81491.54 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 9413.715 | 9413.715 | 0.280228 | 0.00020798 | 196.520 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8931.52 | 9413.72 | 0.280228 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00679752 | 44.0146 | 6600.65 | 0.00 | 9456.70 | 9456.70 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 6699.738 | 6699.738 | 0.199523 | 0.00014802 | 139.845 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6356.56 | 6699.74 | 0.199523 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00702090 | 45.4441 | 4695.95 | 0.00 | 6730.33 | 6730.33 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11965.810 | 11965.810 | 0.356509 | 0.00026437 | 249.732 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11352.89 | 11965.81 | 0.356509 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00729368 | 47.1878 | 8383.43 | 0.00 | 12020.44 | 12020.44 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 5585.200 | 5585.200 | 0.238221 | 0.00012340 | 107.403 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5301.74 | 5585.20 | 0.238221 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00594297 | 38.5352 | 3197.75 | 0.00 | 5611.71 | 5611.71 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 190836.951 | 190836.951 | 5.692801 | 0.00421631 | 3981.366 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181062.03 | 190836.95 | 5.692801 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00761022 | 49.2094 | 133596.19 | 0.00 | 191708.19 | 191708.19 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 125997.641 | 125997.641 | 3.758813 | 0.00278376 | 2628.600 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 119543.88 | 125997.64 | 3.758813 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00761332 | 49.2292 | 88202.82 | 0.00 | 126572.87 | 126572.87 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 190103.236 | 190103.236 | 5.670863 | 0.00420010 | 3966.070 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180365.90 | 190103.24 | 5.670863 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00760809 | 49.1958 | 133083.31 | 0.00 | 190971.13 | 190971.13 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 120080.876 | 120080.876 | 3.581951 | 0.00265304 | 2505.237 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113930.17 | 120080.88 | 3.581951 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00758471 | 49.0467 | 84066.57 | 0.00 | 120629.09 | 120629.09 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 24382.325 | 24382.325 | 0.727701 | 0.00053870 | 508.605 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23133.44 | 24382.33 | 0.727701 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766583 | 49.5646 | 17064.60 | 0.00 | 24493.64 | 24493.64 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 15996.849 | 15996.849 | 0.477450 | 0.00035343 | 333.684 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15177.48 | 15996.85 | 0.477450 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766266 | 49.5445 | 11195.68 | 0.00 | 16069.88 | 16069.88 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 24269.966 | 24269.966 | 0.724341 | 0.00053622 | 506.262 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23026.84 | 24269.97 | 0.724341 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00766397 | 49.5527 | 16986.05 | 0.00 | 24380.77 | 24380.77 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 15529.119 | 15529.119 | 0.463470 | 0.00034310 | 323.931 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14733.70 | 15529.12 | 0.463470 | 12.80 | 11.59 | 0.00800000 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 0.0000 | 21.00 | 0.00764963 | 49.4614 | 10868.66 | 0.00 | 15600.01 | 15600.01 |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 112382.954 | -999.000 | 5.254340 | 0.00478103 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 112382.95 | 83498.91 | 5.254340 | 24.71 | 17.99 | 0.01015229 | 11.42 | 11.42 | 0.00828082 | 27.09 | 0.01409688 | 21.69 | 22.8398 | 24.00 | 0.00898055 | 48.2873 | 72026.77 | 0.00 | 124920.03 | 89565.34 |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 269723.233 | 269723.233 | 5.254340 | 0.00595921 | 4923.339 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 210412.38 | 269723.23 | 5.254340 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 22.8398 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 221941.73 | 221941.73 |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 225712.291 | -999.000 | 8.899577 | 0.00960232 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 225712.29 | 165089.84 | 8.899577 | 26.51 | 18.88 | 0.01053019 | 11.42 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 28.5187 | 24.00 | 0.00885057 | 47.5979 | 111427.57 | 0.00 | 246958.47 | 174161.15 |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 72596.537 | 72596.537 | 2.669873 | 0.00160393 | 999.643 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52063.20 | 72596.54 | 2.669873 | -10.70 | -10.70 | 0.00150390 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 95.0622 | 21.00 | 0.00748145 | 48.3857 | 22877.78 | 0.00 | 55029.18 | 55029.18 |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2190538.833 | -999.000 | 82.620914 | 0.09319058 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2190538.83 | 1563066.34 | 82.620914 | 26.81 | 19.18 | 0.01078667 | 11.43 | 12.09 | 0.00828082 | 31.95 | 0.01409688 | 23.06 | 30.7191 | 24.00 | 0.00889503 | 47.8339 | 988125.96 | 0.00 | 2387875.16 | 1648467.33 |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 704473.123 | 704473.123 | 24.786274 | 0.01556447 | 9630.721 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 499690.70 | 704473.12 | 24.786274 | -10.63 | -10.63 | 0.00151869 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 102.3968 | 21.00 | 0.00774959 | 50.0978 | 512657.92 | 0.00 | 528125.08 | 528125.08 |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 212493.928 | -999.000 | 8.480266 | 0.00903998 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 212493.93 | 156221.25 | 8.480266 | 26.41 | 18.80 | 0.01047255 | 11.42 | 12.09 | 0.00828082 | 32.03 | 0.01409687 | 23.08 | 29.9288 | 24.00 | 0.00888510 | 47.7813 | 116210.89 | 0.00 | 232736.78 | 164839.96 |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 72101.324 | 72101.324 | 2.544080 | 0.00159299 | 986.147 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51179.07 | 70410.24 | 2.544080 | -9.75 | -9.75 | 0.00169134 | 12.80 | 11.59 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 99.7626 | 21.00 | 0.00783150 | 50.6200 | 54973.19 | 0.00 | 54091.68 | 54091.68 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426579.847 | 308205.010 | 21.185039 | 0.01044691 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 456408.03 | 450433.73 | -999.0 | 28.48 | 17.98 | 0.00858954 | 12.80 | 12.09 | 0.00850000 | 32.10 | 0.01409687 | 23.10 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 368967.18 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9145.671 | 6640.182 | 0.458932 | 0.00022398 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 9802.50 | 9526.23 | -999.0 | 28.04 | 17.92 | 0.00869071 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01409688 | 22.45 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 8002.12 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87238.795 | 63299.512 | 4.372562 | 0.00213647 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 93486.39 | 90725.67 | -999.0 | 28.04 | 17.92 | 0.00870008 | 12.80 | 12.09 | 0.00850000 | 29.58 | 0.01409688 | 22.40 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 76274.22 | 0.00 | -999.00 | -999.00 |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8883.374 | 6446.534 | 0.445360 | 0.00021755 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9519.90 | 9243.82 | -999.0 | 28.04 | 17.92 | 0.00869644 | 12.80 | 12.09 | 0.00850000 | 29.77 | 0.01409688 | 22.45 | -999.0000 | 27.00 | 0.00850000 | 38.2706 | 7768.78 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 426579.847 | 426579.847 | 21.185039 | 0.01044691 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 426579.85 | 426579.85 | 21.185039 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5972 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9145.671 | 9145.671 | 0.458932 | 0.00022398 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9145.67 | 9145.67 | 0.458932 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4060 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 87238.795 | 87238.795 | 4.372562 | 0.00213647 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 87238.79 | 87238.79 | 4.372562 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.5749 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 8883.374 | 8883.374 | 0.445360 | 0.00021755 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8883.37 | 8883.37 | 0.445360 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.5098 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 20748.523 | 20748.523 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20748.52 | 20748.52 | 21.185039 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5972 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 1318241.42 | 21.185039 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5972 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 1029262.554 | 1029262.554 | 21.185039 | 0.02274030 | 19132.744 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 825259.38 | 1029262.55 | 21.185039 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 1.5972 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | 0.00 | 0.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 0.458932 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.4060 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 9584.958 | 9584.958 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9584.96 | 9584.96 | 4.372562 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.5749 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 0.445360 | -10.70 | -10.70 | 0.00150390 | 40.00 | 21.14 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 3.5098 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18993.150 | 18993.150 | 1.887233 | 0.00041963 | 330.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.5175 | 0.556442 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 18018.94 | 18993.15 | 1.0000 | 2.27146357 | 1.887233 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.41958763 | 60.00 | 49.00 | 11.00 | 0.000 | 18018.94 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 19069.55 | 19069.55 | 2.27146357 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 21.03 | 14.85 | 0.00800000 | 41455.1 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 424186.359 | 424186.359 | 18.441924 | 0.00937188 | 8130.954 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 11.5641 | 12.427387 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 402663.88 | 424186.36 | 1.0000 | 22.19660750 | 18.441924 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 9.37092323 | 60.00 | 49.00 | 11.00 | 0.000 | 402663.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 238586.34 | 0.00 | 426200.89 | 426200.89 | 22.19660750 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 31.63 | 18.55 | 0.00800000 | 52261.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 81121.150 | 81121.150 | 2.414193 | 0.00179227 | 1693.612 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 2.2104 | 2.376606 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 76965.85 | 81121.15 | 1.0000 | 2.90571086 | 2.414193 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 1.79208985 | 60.00 | 49.00 | 11.00 | 0.000 | 76965.85 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 51.6928 | 56824.66 | 0.00 | 81491.54 | 81491.54 | 2.90571086 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.30 | 21.24 | 0.00800000 | 61105.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9413.715 | 9413.715 | 0.280228 | 0.00020798 | 196.520 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.2565 | 0.275794 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 8931.52 | 9413.72 | 1.0000 | 0.33728155 | 0.280228 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.20796332 | 60.00 | 49.00 | 11.00 | 0.000 | 8931.52 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00679752 | 21.00 | 0.00679752 | 44.0146 | 6600.65 | 0.00 | 9456.70 | 9456.70 | 0.33728155 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.30 | 21.24 | 0.00800000 | 61097.8 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6699.738 | 6699.738 | 0.199523 | 0.00014802 | 139.845 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.1826 | 0.196282 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 6356.56 | 6699.74 | 1.0000 | 0.24014435 | 0.199523 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.14800742 | 60.00 | 49.00 | 11.00 | 0.000 | 6356.56 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00702090 | 21.00 | 0.00702090 | 45.4441 | 4695.95 | 0.00 | 6730.33 | 6730.33 | 0.24014435 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.28 | 21.23 | 0.00800000 | 61086.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11965.810 | 11965.810 | 0.356509 | 0.00026437 | 249.732 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.3260 | 0.350562 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 11352.89 | 11965.81 | 1.0000 | 0.42909252 | 0.356509 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.26434299 | 60.00 | 49.00 | 11.00 | 0.000 | 11352.89 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.91 | 0.00729368 | 21.00 | 0.00729368 | 47.1878 | 8383.43 | 0.00 | 12020.44 | 12020.44 | 0.42909252 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.27 | 21.23 | 0.00800000 | 61073.5 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5585.200 | 5585.200 | 0.238221 | 0.00012340 | 107.403 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.1523 | 0.163630 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5301.74 | 5585.20 | 1.0000 | 0.28672199 | 0.238221 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.12338558 | 60.00 | 49.00 | 11.00 | 0.000 | 5301.74 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.86 | 0.00594297 | 21.00 | 0.00594297 | 38.5352 | 3197.75 | 0.00 | 5611.71 | 5611.71 | 0.28672199 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 31.99 | 18.67 | 0.00800000 | 52631.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 190836.951 | 190836.951 | 5.692801 | 0.00421631 | 3981.366 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 5.1999 | 5.590950 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181062.03 | 190836.95 | 1.0000 | 6.85182712 | 5.692801 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 4.21587914 | 60.00 | 49.00 | 11.00 | 0.000 | 181062.03 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00761022 | 21.00 | 0.00761022 | 49.2094 | 133596.19 | 0.00 | 191708.19 | 191708.19 | 6.85182712 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 125997.641 | 125997.641 | 3.758813 | 0.00278376 | 2628.600 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 3.4332 | 3.691353 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 119543.88 | 125997.64 | 1.0000 | 4.52408902 | 3.758813 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.78347995 | 60.00 | 49.00 | 11.00 | 0.000 | 119543.88 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00761332 | 21.00 | 0.00761332 | 49.2292 | 88202.82 | 0.00 | 126572.87 | 126572.87 | 4.52408902 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61037.4 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 190103.236 | 190103.236 | 5.670863 | 0.00420010 | 3966.070 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 5.1799 | 5.569454 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 180365.90 | 190103.24 | 1.0000 | 6.82542172 | 5.670863 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 4.19967026 | 60.00 | 49.00 | 11.00 | 0.000 | 180365.90 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00760809 | 21.00 | 0.00760809 | 49.1958 | 133083.31 | 0.00 | 190971.13 | 190971.13 | 6.82542172 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61039.2 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 120080.876 | 120080.876 | 3.581951 | 0.00265304 | 2505.237 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 3.2720 | 3.518009 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 113930.17 | 120080.88 | 1.0000 | 4.31121846 | 3.581951 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 2.65276958 | 60.00 | 49.00 | 11.00 | 0.000 | 113930.17 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00758471 | 21.00 | 0.00758471 | 49.0467 | 84066.57 | 0.00 | 120629.09 | 120629.09 | 4.31121846 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.24 | 21.22 | 0.00800000 | 61040.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24382.325 | 24382.325 | 0.727701 | 0.00053870 | 508.605 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.6644 | 0.714329 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23133.44 | 24382.33 | 1.0000 | 0.87585679 | 0.727701 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.53864273 | 60.00 | 49.00 | 11.00 | 0.000 | 23133.44 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766583 | 21.00 | 0.00766583 | 49.5646 | 17064.60 | 0.00 | 24493.64 | 24493.64 | 0.87585679 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61025.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15996.849 | 15996.849 | 0.477450 | 0.00035343 | 333.684 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.4359 | 0.468660 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 15177.48 | 15996.85 | 1.0000 | 0.57465619 | 0.477450 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.35339478 | 60.00 | 49.00 | 11.00 | 0.000 | 15177.48 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766266 | 21.00 | 0.00766266 | 49.5445 | 11195.68 | 0.00 | 16069.88 | 16069.88 | 0.57465619 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61024.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24269.966 | 24269.966 | 0.724341 | 0.00053622 | 506.262 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.6613 | 0.711037 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23026.84 | 24269.97 | 1.0000 | 0.87181333 | 0.724341 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.53616054 | 60.00 | 49.00 | 11.00 | 0.000 | 23026.84 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00766397 | 21.00 | 0.00766397 | 49.5527 | 16986.05 | 0.00 | 24380.77 | 24380.77 | 0.87181333 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61025.4 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15529.119 | 15529.119 | 0.463470 | 0.00034310 | 323.931 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 0.4231 | 0.454957 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14733.70 | 15529.12 | 1.0000 | 0.55782967 | 0.463470 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 0.34306192 | 60.00 | 49.00 | 11.00 | 0.000 | 14733.70 | -10.70 | 0.00150390 | -10.70 | 0.00000000 | 0.0000 | 20.95 | 0.00764963 | 21.00 | 0.00764963 | 49.4614 | 10868.66 | 0.00 | 15600.01 | 15600.01 | 0.55782967 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 40.22 | 21.22 | 0.00800000 | 61025.4 | |
CAV_BAS_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 112382.954 | -999.000 | 5.254340 | 0.00478103 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7126 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.254340 | 6.32409719 | 4197.9300 | 999.8980 | 116.60202621 | 12.27 | 6.67 | 5.60 | 2741128.01 | 4.0999 | 4.099880 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 112382.95 | 83498.91 | 1.0000 | 6.32409719 | 5.254340 | 24.71 | 17.99 | 0.01015229 | 50684.0 | 11.42 | 11.42 | 0.00828082 | 32917.6 | 4.78054295 | 6.67 | 10.65 | 5.60 | 8909.544 | 103473.41 | 27.09 | 0.01409688 | 21.69 | 1.20008137 | 22.8398 | 24.00 | 0.00897928 | 24.00 | 0.00898055 | 48.2873 | 72026.77 | 0.00 | 124920.03 | 89565.34 | 6.32409719 | 24.71 | 18.00 | 0.01015229 | 50684.0 | 10.87 | 10.71 | 0.00793486 | 30930.9 | |
CAV_BAS_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 269723.233 | 269723.233 | 5.254340 | 0.00595921 | 4923.339 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | CAV_BAS FAN | Fan:ConstantVolume | 5.254340 | 6.32409719 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 6.0428 | 7.902081 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 210412.38 | 269723.23 | 1.0000 | 6.32409719 | 5.254340 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 5.95859735 | 60.00 | 49.00 | 11.00 | 0.000 | 210412.38 | -10.70 | 0.00150390 | -10.70 | 1.20008137 | 22.8398 | 0.00 | 0.00000000 | 21.00 | 0.00800000 | 51.6928 | 0.00 | 0.00 | 221941.73 | 221941.73 | 6.32409719 | 12.80 | 2.43 | 0.00034349 | 13729.2 | 47.70 | 17.59 | 0.00034349 | 48823.8 | |
VAV_BOT WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 225712.291 | -999.000 | 8.899577 | 0.00960232 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4151 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.899577 | 10.71148635 | 4197.9300 | 999.8980 | 116.60202621 | 12.27 | 6.67 | 5.60 | 2741128.01 | 8.2343 | 8.234285 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 225712.29 | 165089.84 | 1.0000 | 10.71148635 | 8.899577 | 26.51 | 18.88 | 0.01053019 | 53496.8 | 11.42 | 12.09 | 0.00828082 | 34322.2 | 9.60134309 | 6.67 | 10.65 | 5.60 | 20324.212 | 205388.08 | 32.03 | 0.01409687 | 23.08 | 2.53804000 | 28.5187 | 24.00 | 0.00890256 | 24.00 | 0.00885057 | 47.5979 | 111427.57 | 0.00 | 246958.47 | 174161.15 | 10.71148635 | 26.51 | 18.89 | 0.01053019 | 53496.8 | 10.64 | 10.50 | 0.00783406 | 30441.3 | |
VAV_BOT WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 72596.537 | 72596.537 | 2.669873 | 0.00160393 | 999.643 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.899577 | 10.71148635 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 1.4952 | 2.126861 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52063.20 | 72596.54 | 1.0000 | 3.21344590 | 2.669873 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.60376815 | 60.00 | 49.00 | 11.00 | 0.000 | 52063.20 | -10.70 | 0.00150390 | -10.70 | 2.53804000 | 95.0622 | 9.91 | 0.00327446 | 21.00 | 0.00748145 | 48.3857 | 22877.78 | 0.00 | 55029.18 | 55029.18 | 3.21344590 | 12.80 | 4.13 | 0.00159132 | 16879.6 | 29.79 | 12.08 | 0.00159132 | 34004.3 | |
VAV_MID WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2190538.833 | -999.000 | 82.620914 | 0.09319058 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8919 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.620914 | 99.44211723 | 4197.9300 | 999.8980 | 116.60202621 | 12.27 | 6.67 | 5.60 | 2741128.01 | 79.9138 | 79.913774 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2190538.83 | 1563066.34 | 1.0000 | 99.44211723 | 82.620914 | 26.81 | 19.18 | 0.01078667 | 54453.1 | 11.43 | 12.09 | 0.00828082 | 34322.2 | 93.18107941 | 6.67 | 10.65 | 5.60 | 188683.679 | 2001855.15 | 31.95 | 0.01409688 | 23.06 | 25.38036000 | 30.7191 | 24.00 | 0.00897788 | 24.00 | 0.00889503 | 47.8339 | 988125.96 | 0.00 | 2387875.16 | 1648467.33 | 99.44211723 | 26.81 | 19.18 | 0.01078667 | 54453.1 | 10.63 | 10.50 | 0.00783688 | 30440.3 | |
VAV_MID WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 704473.123 | 704473.123 | 24.786274 | 0.01556447 | 9630.721 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 82.620914 | 99.44211723 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 14.3506 | 20.638949 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:20:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 499690.70 | 704473.12 | 1.0000 | 29.83263517 | 24.786274 | -10.63 | -10.63 | 0.00151869 | -6908.4 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 15.56288509 | 60.00 | 49.00 | 11.00 | 0.000 | 499690.70 | -10.70 | 0.00150390 | -10.70 | 25.38036000 | 102.3968 | 21.00 | 0.00776923 | 21.00 | 0.00774959 | 50.0978 | 512657.92 | 0.00 | 528125.08 | 528125.08 | 29.83263517 | 12.80 | 4.02 | 0.00150390 | 16658.9 | 30.37 | 12.23 | 0.00150390 | 34361.8 | |
VAV_TOP WITH REHEAT_COOLC | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 212493.928 | -999.000 | 8.480266 | 0.00903998 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.3080 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.480266 | 10.20680617 | 4197.9300 | 999.8980 | 116.60202621 | 12.27 | 6.67 | 5.60 | 2741128.01 | 7.7521 | 7.752061 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 212493.93 | 156221.25 | 1.0000 | 10.20680617 | 8.480266 | 26.41 | 18.80 | 0.01047255 | 53243.6 | 11.42 | 12.09 | 0.00828082 | 34322.2 | 9.03906075 | 6.67 | 10.65 | 5.60 | 19366.620 | 193127.31 | 32.03 | 0.01409687 | 23.08 | 2.53804000 | 29.9288 | 24.00 | 0.00891597 | 24.00 | 0.00888510 | 47.7813 | 116210.89 | 0.00 | 232736.78 | 164839.96 | 10.20680617 | 26.41 | 18.81 | 0.01047255 | 53243.6 | 10.64 | 10.50 | 0.00783359 | 30441.5 | |
VAV_TOP WITH REHEAT_HEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 72101.324 | 72101.324 | 2.544080 | 0.00159299 | 986.147 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.480266 | 10.20680617 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 1.4698 | 2.112352 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:50:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51179.07 | 70410.24 | 1.0000 | 3.06204185 | 2.544080 | -9.75 | -9.75 | 0.00169134 | -5597.9 | 12.80 | 11.59 | 0.00800000 | 33059.8 | 1.59282814 | 60.00 | 49.00 | 11.00 | 0.000 | 51179.07 | -10.70 | 0.00150390 | -10.70 | 2.53804000 | 99.7626 | 17.54 | 0.00707568 | 21.00 | 0.00783150 | 50.6200 | 54973.19 | 0.00 | 54091.68 | 54091.68 | 3.06204185 | 12.80 | 4.03 | 0.00151713 | 16692.3 | 30.33 | 12.22 | 0.00151713 | 34357.5 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 426579.847 | 308205.010 | 21.185039 | 0.01044691 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8075 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 06:10:00 | 456408.03 | 450433.73 | 0.9346 | -999.0 | -999.0 | 28.48 | 17.98 | 0.00858954 | 50557.3 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 456408.03 | 32.10 | 0.01409687 | 23.10 | 0.33837161 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 368967.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9145.671 | 6640.182 | 0.458932 | 0.00022398 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.9956 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 9802.50 | 9526.23 | 0.9330 | -999.0 | -999.0 | 28.04 | 17.92 | 0.00869071 | 50364.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9802.50 | 29.77 | 0.01409688 | 22.45 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 8002.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 87238.795 | 63299.512 | 4.372562 | 0.00213647 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0130 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 93486.39 | 90725.67 | 0.9332 | -999.0 | -999.0 | 28.04 | 17.92 | 0.00870008 | 50386.5 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 93486.39 | 29.58 | 0.01409688 | 22.40 | 0.15631366 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 76274.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 8883.374 | 6446.534 | 0.445360 | 0.00021755 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0062 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9519.90 | 9243.82 | 0.9331 | -999.0 | -999.0 | 28.04 | 17.92 | 0.00869644 | 50382.2 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9519.90 | 29.77 | 0.01409688 | 22.45 | 0.01563137 | -999.0000 | 27.00 | 0.00850000 | 27.00 | 0.00850000 | 38.2706 | 7768.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 426579.847 | 426579.847 | 21.185039 | 0.01044691 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 426579.85 | 426579.85 | 1.0000 | 25.49820654 | 21.185039 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 426579.85 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5972 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9145.671 | 9145.671 | 0.458932 | 0.00022398 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9145.67 | 9145.67 | 1.0000 | 0.55236804 | 0.458932 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9145.67 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.4060 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 87238.795 | 87238.795 | 4.372562 | 0.00213647 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 87238.79 | 87238.79 | 1.0000 | 5.26279405 | 4.372562 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 87238.79 | -10.70 | 0.00150390 | -10.70 | 0.15631366 | 3.5749 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8883.374 | 8883.374 | 0.445360 | 0.00021755 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.2036 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8883.37 | 8883.37 | 1.0000 | 0.53603254 | 0.445360 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8883.37 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.5098 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 20748.523 | 20748.523 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.185039 | 25.49820654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 20748.52 | 20748.52 | 1.0000 | 25.49820654 | 21.185039 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20748.52 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5972 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAELECHEATC | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | No | No | unknown | No | 10000000.000 | 10000000.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.185039 | 25.49820654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10000000.00 | 1318241.42 | 1.0000 | 25.49820654 | 21.185039 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10000000.00 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5972 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
DATACENTER_EXTRAWATERHEATC | Coil:Heating:Water | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 1029262.554 | 1029262.554 | 21.185039 | 0.02274030 | 19132.744 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.185039 | 25.49820654 | 4197.9300 | 999.8980 | 75.40541635 | 71.00 | 82.00 | 11.00 | 3482013.25 | 23.7006 | 30.154304 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 825259.38 | 1029262.55 | 1.0000 | 25.49820654 | 21.185039 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | 22.73797869 | 60.00 | 49.00 | 11.00 | 0.000 | 825259.38 | -10.70 | 0.00150390 | -10.70 | 0.33837161 | 1.5972 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | 0.00 | 0.00 | 25.49820654 | 16.60 | 4.06 | 0.00002402 | 16741.2 | 16.60 | 4.06 | 0.00002402 | 16741.2 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.458932 | 0.55236804 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 1.0000 | 0.55236804 | 0.458932 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.50 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.4060 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9584.958 | 9584.958 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.372562 | 5.26279405 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9584.96 | 9584.96 | 1.0000 | 5.26279405 | 4.372562 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9584.96 | -10.70 | 0.00150390 | -10.70 | 0.15631366 | 3.5749 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 958.496 | 958.496 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.445360 | 0.53603254 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 958.50 | 958.50 | 1.0000 | 0.53603254 | 0.445360 | -10.70 | -10.70 | 0.00150390 | -7020.5 | 40.00 | 21.14 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 958.50 | -10.70 | 0.00150390 | -10.70 | 0.01563137 | 3.5098 | 0.00 | 0.00000000 | 18.00 | 0.00800000 | 62.2947 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
CAV_BAS_OA_CONTROLLER | DifferentialEnthalpy | 1.20 | 5.25 | - | |||
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.90 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 82.62 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialEnthalpy | 0.00 | 8.48 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Sum | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 3017.83 | 1504.17 | 616.67 |
CORE_BOTTOM | 2835.50 | 970.50 | 0.00 |
CORE_MID | 1643.50 | 2829.00 | 56.17 |
CORE_TOP | 2106.00 | 3388.17 | 537.33 |
PERIMETER_BOT_ZN_3 | 2312.67 | 2888.83 | 147.17 |
PERIMETER_BOT_ZN_2 | 2267.83 | 2952.67 | 184.83 |
PERIMETER_BOT_ZN_1 | 2662.50 | 2465.67 | 193.67 |
PERIMETER_BOT_ZN_4 | 3167.17 | 1558.33 | 172.50 |
PERIMETER_MID_ZN_3 | 2813.67 | 3789.83 | 1257.33 |
PERIMETER_MID_ZN_2 | 2410.33 | 3145.00 | 1018.83 |
PERIMETER_MID_ZN_1 | 2764.67 | 3027.50 | 698.67 |
PERIMETER_MID_ZN_4 | 2892.50 | 3405.00 | 944.00 |
PERIMETER_TOP_ZN_3 | 3387.83 | 3939.17 | 1882.33 |
PERIMETER_TOP_ZN_2 | 3384.33 | 3750.67 | 1651.50 |
PERIMETER_TOP_ZN_1 | 3122.67 | 3357.33 | 1247.50 |
PERIMETER_TOP_ZN_4 | 3260.50 | 3670.83 | 1478.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5015.83 | 4608.00 | 2540.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 87.00 | 0.00 | 4.83 |
CORE_BOTTOM | 0.00 | 1.67 | 0.00 | 0.00 |
CORE_MID | 2.33 | 0.00 | 1.50 | 0.00 |
CORE_TOP | 5.67 | 0.00 | 0.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.17 | 9.83 | 0.00 | 9.83 |
PERIMETER_BOT_ZN_1 | 0.33 | 64.00 | 0.00 | 64.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 75.50 | 0.00 | 26.67 |
PERIMETER_MID_ZN_3 | 37.33 | 0.00 | 10.00 | 0.00 |
PERIMETER_MID_ZN_2 | 21.83 | 10.33 | 2.83 | 10.33 |
PERIMETER_MID_ZN_1 | 21.83 | 92.17 | 4.50 | 92.17 |
PERIMETER_MID_ZN_4 | 18.33 | 15.00 | 3.00 | 10.50 |
PERIMETER_TOP_ZN_3 | 137.83 | 0.00 | 44.17 | 0.00 |
PERIMETER_TOP_ZN_2 | 81.83 | 12.00 | 15.17 | 12.00 |
PERIMETER_TOP_ZN_1 | 78.17 | 35.00 | 16.17 | 34.83 |
PERIMETER_TOP_ZN_4 | 54.33 | 17.00 | 9.67 | 12.17 |
DATACENTER_BOT_ZN_6 | 0.00 | 858.17 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 808.83 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 748.83 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 139.67 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 149.00 | 1129.83 | 44.83 | 174.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 1.123 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.756 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.606 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.580 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.678 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.867 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.878 | 0.057 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 1.326 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.594 | 0.128 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.797 | 0.142 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.802 | 0.129 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.913 | 0.133 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.601 | 0.159 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.857 | 0.165 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.779 | 0.160 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.939 | 0.165 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.32 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.97 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.96 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.03 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.03 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.53 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27852.63 | 360050.52 | 01-JAN-00:40 | 1850033.16 | 02-AUG-15:10 |
Electricity:Building | 18256.01 | 248635.65 | 01-JAN-08:30 | 1073855.91 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 618.16 | 14390.45 | 01-JAN-06:10 | 30249.89 | 02-JAN-08:10 |
InteriorLights:Electricity | 3042.73 | 14426.39 | 01-JAN-08:30 | 279851.83 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:BASEMENT | 193.76 | 932.91 | 01-JAN-06:10 | 16792.34 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 3042.73 | 14426.39 | 01-JAN-08:30 | 279851.83 | 02-JAN-16:40 |
Electricity:Zone:CORE_BOTTOM | 495.29 | 6880.68 | 01-JAN-06:10 | 33209.29 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 174.01 | 837.82 | 01-JAN-06:10 | 15080.70 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4952.90 | 68806.57 | 01-JAN-06:10 | 332092.23 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1740.13 | 8378.17 | 01-JAN-06:10 | 150807.03 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 495.29 | 6880.66 | 01-JAN-06:10 | 33209.22 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 174.01 | 837.82 | 01-JAN-06:10 | 15080.70 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 57.49 | 835.57 | 01-JAN-08:30 | 4169.85 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 17.15 | 76.79 | 01-JAN-08:30 | 1893.53 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 37.05 | 538.47 | 01-JAN-07:50 | 2687.21 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 11.05 | 49.49 | 01-JAN-07:50 | 1220.26 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 57.43 | 835.58 | 01-JAN-07:50 | 4169.93 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 17.09 | 76.80 | 01-JAN-07:50 | 1893.57 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 37.02 | 538.47 | 01-JAN-08:30 | 2687.20 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 11.02 | 49.49 | 01-JAN-08:30 | 1220.26 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 574.97 | 8355.67 | 01-JAN-08:30 | 41698.51 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 171.56 | 767.94 | 01-JAN-08:30 | 18935.33 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 370.49 | 5384.71 | 01-JAN-07:50 | 26872.11 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 110.51 | 494.89 | 01-JAN-07:50 | 12202.65 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 574.39 | 8355.80 | 01-JAN-08:00 | 41699.27 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 170.97 | 767.96 | 01-JAN-08:00 | 18935.74 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 370.18 | 5384.68 | 01-JAN-08:30 | 26872.01 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 110.21 | 494.89 | 01-JAN-08:30 | 12202.65 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 57.50 | 835.57 | 01-JAN-08:30 | 4169.85 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 17.16 | 76.79 | 01-JAN-08:30 | 1893.53 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 37.05 | 538.47 | 01-JAN-07:50 | 2687.21 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 11.05 | 49.49 | 01-JAN-07:50 | 1220.26 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 57.44 | 835.58 | 01-JAN-08:00 | 4169.93 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 17.10 | 76.80 | 01-JAN-08:00 | 1893.57 | 02-JAN-16:40 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 37.02 | 538.47 | 01-JAN-08:30 | 2687.20 | 02-JAN-16:40 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 11.02 | 49.49 | 01-JAN-08:30 | 1220.26 | 02-JAN-16:40 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7549.49 | 95171.17 | 01-JAN-06:10 | 384367.24 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 54.63 | 263.04 | 01-JAN-06:10 | 4734.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 156.40 | 1960.76 | 01-JAN-06:10 | 8013.15 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 2.52 | 12.15 | 01-JAN-06:10 | 218.72 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1564.04 | 19607.57 | 01-JAN-06:10 | 80131.47 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 25.24 | 121.51 | 01-JAN-06:10 | 2187.25 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 156.40 | 1960.76 | 01-JAN-06:10 | 8013.15 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 2.52 | 12.15 | 01-JAN-06:10 | 218.72 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.29 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.86 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.28 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.77 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.41 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.42 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.97 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 01-APR-00:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 01-APR-00:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 01-APR-00:10 |
Electricity:HVAC | 4660.88 | 61829.18 | 04-JAN-00:50 | 333886.04 | 30-AUG-13:30 |
ExteriorEquipment:Electricity | 1960.81 | 13372.41 | 01-JAN-00:10 | 126332.05 | 03-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 59.90 | 1112.61 | 01-JAN-00:10 | 3737.48 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 27852.63 | 360050.52 | 01-JAN-00:40 | 1850033.16 | 02-AUG-15:10 |
ElectricityPurchased:Plant | 27852.63 | 360050.52 | 01-JAN-00:40 | 1850033.16 | 02-AUG-15:10 |
Cogeneration:ElectricityPurchased | 27852.63 | 360050.52 | 01-JAN-00:40 | 1850033.16 | 02-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27852.63 | 360050.52 | 01-JAN-00:40 | 1850033.16 | 02-AUG-15:10 |
ElectricityNet:Plant | 27852.63 | 360050.52 | 01-JAN-00:40 | 1850033.16 | 02-AUG-15:10 |
Cogeneration:ElectricityNet | 27852.63 | 360050.52 | 01-JAN-00:40 | 1850033.16 | 02-AUG-15:10 |
Fans:Electricity | 2048.00 | 41034.87 | 03-JAN-00:20 | 192923.61 | 01-SEP-14:10 |
General:Fans:Electricity | 2048.00 | 41034.87 | 03-JAN-00:20 | 192923.61 | 01-SEP-14:10 |
ExteriorLights:Electricity | 438.74 | 0.00 | 01-JAN-07:30 | 36729.40 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 438.74 | 0.00 | 01-JAN-07:30 | 36729.40 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1895.08 | 12222.20 | 01-JAN-00:10 | 122221.98 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 49.79 | 0.00 | 01-JAN-00:10 | 5613.05 | 02-JAN-07:10 |
Cooling:Electricity | 3463.52 | 19286.07 | 14-JAN-18:00 | 429397.02 | 02-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 25.40 | 0.00 | 01-JAN-00:10 | 41323.61 | 06-FEB-20:00 |
Electricity:Plant | 2596.09 | 4465.50 | 14-JAN-11:40 | 402934.46 | 02-AUG-15:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cooling:Electricity | 985.74 | 0.00 | 01-JAN-00:10 | 262224.24 | 02-AUG-15:00 |
HeatRejection:Electricity | 1132.19 | 1095.90 | 14-JAN-11:40 | 89551.59 | 30-MAY-10:20 |
General:HeatRejection:Electricity | 190.21 | 0.00 | 01-JAN-00:10 | 40303.32 | 30-MAY-10:20 |
Pumps:Electricity | 478.16 | 3322.00 | 02-JAN-00:40 | 55529.08 | 01-SEP-14:10 |
General:Pumps:Electricity | 478.16 | 3322.00 | 02-JAN-00:40 | 55529.08 | 01-SEP-14:10 |
WIRED_LTG_ELECTRICITY | 85.50 | 0.00 | 01-JAN-00:10 | 7863.84 | 02-JAN-16:50 |
WIRED_INT_EQUIP | 5871.86 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 1264.49 | 5695.87 | 18-JAN-02:40 | 1887124.39 | 02-JAN-07:10 |
Gas:Plant | 1264.49 | 5695.87 | 18-JAN-02:40 | 1887124.39 | 02-JAN-07:10 |
WaterSystems:Gas | 557.21 | 5695.87 | 02-JAN-06:00 | 81935.08 | 25-JAN-12:10 |
Water Heater:WaterSystems:Gas | 557.21 | 5695.87 | 02-JAN-06:00 | 81935.08 | 25-JAN-12:10 |
Heating:Gas | 707.28 | 0.00 | 01-JAN-00:40 | 1881428.52 | 02-JAN-07:10 |
Boiler:Heating:Gas | 707.28 | 0.00 | 01-JAN-00:40 | 1881428.52 | 02-JAN-07:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 18532.36 | 65803.35 | 28-JAN-16:10 | 2319411.91 | 22-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 18532.36 | 65803.35 | 28-JAN-16:10 | 2319411.91 | 22-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 18532.36 | 65803.35 | 28-JAN-16:10 | 2319411.91 | 22-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7340.27 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:10 |
Water:Plant | 7330.82 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 7340.27 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:10 |
MainsWater:Plant | 7330.82 | 0.00 | 01-JAN-00:10 | 0.00 | 01-SEP-14:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:HVAC | 9.45 | 0.00 | 01-JAN-00:10 | 0.00 | 06-FEB-20:00 |
Humidifier:Water | 9.45 | 0.00 | 01-JAN-00:10 | 0.00 | 06-FEB-20:00 |
MainsWater:HVAC | 9.45 | 0.00 | 01-JAN-00:10 | 0.00 | 06-FEB-20:00 |
Humidifier:MainsWater | 9.45 | 0.00 | 01-JAN-00:10 | 0.00 | 06-FEB-20:00 |
HeatRejection:Water | 5050.65 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
HeatRejection:MainsWater | 5050.65 | 0.00 | 01-JAN-00:10 | 0.00 | 24-AUG-17:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 922.75 | 0.00 | 01-JAN-00:40 | 1637140.84 | 02-JAN-07:10 |
PlantLoopHeatingDemand:Plant | 412.73 | 0.00 | 01-JAN-00:10 | 52102.71 | 09-FEB-13:00 |
WaterSystems:PlantLoopHeatingDemand | 412.73 | 0.00 | 01-JAN-00:10 | 52102.71 | 09-FEB-13:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 58128.65 | 124258.35 | 19-JAN-03:40 | 9201989.37 | 02-AUG-15:00 |
EnergyTransfer:Building | 18318.18 | 60235.96 | 11-JAN-22:50 | 1515224.91 | 18-AUG-16:00 |
EnergyTransfer:Zone:BASEMENT | 681.66 | 0.00 | 01-JAN-00:10 | 79268.82 | 10-OCT-05:10 |
Heating:EnergyTransfer | 357.06 | 0.00 | 18-JAN-22:10 | 1135478.99 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 8.98 | 0.00 | 01-JAN-00:10 | 61538.60 | 15-JUL-04:00 |
Cooling:EnergyTransfer | 17961.12 | 59916.49 | 11-JAN-22:50 | 1515224.91 | 18-AUG-16:00 |
Cooling:EnergyTransfer:Zone:BASEMENT | 672.69 | 0.00 | 01-JAN-00:10 | 79268.82 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 639.84 | 0.00 | 01-JAN-00:10 | 50909.68 | 11-JUL-14:00 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 639.84 | 0.00 | 01-JAN-00:10 | 50909.68 | 11-JUL-14:00 |
EnergyTransfer:Zone:CORE_MID | 4522.74 | 0.00 | 01-JAN-00:40 | 459224.26 | 22-JUN-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 6.28 | 0.00 | 01-JAN-00:10 | 393940.38 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4516.46 | 0.00 | 01-JAN-00:40 | 459224.26 | 22-JUN-13:10 |
EnergyTransfer:Zone:CORE_TOP | 426.12 | 0.00 | 01-JAN-00:40 | 68419.09 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 7.25 | 0.00 | 01-JAN-00:40 | 68419.09 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 418.87 | 0.00 | 01-JAN-00:10 | 51156.49 | 01-SEP-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.13 | 0.00 | 01-JAN-00:10 | 9523.96 | 19-JUN-14:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.08 | 0.00 | 01-JAN-00:10 | 4337.91 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 73.05 | 0.00 | 01-JAN-00:10 | 9523.96 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.27 | 0.00 | 01-JAN-00:10 | 11334.95 | 26-JUN-07:50 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.08 | 0.00 | 01-JAN-00:10 | 3585.55 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 58.19 | 0.00 | 01-JAN-00:10 | 11334.95 | 26-JUN-07:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.98 | 0.00 | 01-JAN-00:10 | 14257.10 | 04-OCT-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.28 | 0.00 | 01-JAN-00:10 | 8434.64 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 91.70 | 0.00 | 01-JAN-00:10 | 14257.10 | 04-OCT-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 93.18 | 0.00 | 01-JAN-00:10 | 15838.34 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.01 | 0.00 | 01-JAN-00:10 | 2034.97 | 02-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 93.17 | 0.00 | 01-JAN-00:10 | 15838.34 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 554.04 | 0.00 | 01-JAN-00:40 | 111893.53 | 02-JAN-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 63.95 | 0.00 | 01-JAN-00:40 | 111893.53 | 02-JAN-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 490.09 | 0.00 | 01-JAN-00:10 | 88584.61 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 495.26 | 0.00 | 01-JAN-00:40 | 123468.54 | 06-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 36.85 | 0.00 | 01-JAN-00:40 | 123468.54 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 458.40 | 0.00 | 01-JAN-00:10 | 120150.14 | 14-JUL-08:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 760.64 | 0.00 | 01-JAN-00:40 | 138799.72 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 36.93 | 0.00 | 01-JAN-00:40 | 120358.04 | 02-JAN-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 723.72 | 0.00 | 01-JAN-00:10 | 138799.72 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 539.47 | 0.00 | 01-JAN-00:40 | 133529.20 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 27.97 | 0.00 | 01-JAN-00:40 | 117248.65 | 06-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 511.50 | 0.00 | 01-JAN-00:10 | 133529.20 | 15-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 65.44 | 0.00 | 01-JAN-00:40 | 13304.47 | 02-JAN-01:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 18.71 | 0.00 | 01-JAN-00:40 | 13304.47 | 02-JAN-01:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 46.74 | 0.00 | 01-JAN-00:10 | 10302.32 | 19-JUN-14:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 54.82 | 0.00 | 01-JAN-00:40 | 13468.24 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 10.61 | 0.00 | 01-JAN-00:40 | 13468.24 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 44.21 | 0.00 | 01-JAN-00:10 | 12156.26 | 14-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 80.03 | 0.00 | 01-JAN-00:40 | 15131.18 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 12.19 | 0.00 | 01-JAN-00:40 | 14613.58 | 06-FEB-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 67.84 | 0.00 | 01-JAN-00:10 | 15131.18 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 57.90 | 0.00 | 01-JAN-00:40 | 14054.44 | 06-FEB-05:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 8.11 | 0.00 | 01-JAN-00:40 | 14054.44 | 06-FEB-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 49.80 | 0.00 | 01-JAN-00:10 | 14023.26 | 15-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 56.58 | 0.00 | 01-JAN-00:10 | 7843.53 | 30-MAY-13:50 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.52 | 0.00 | 01-JAN-00:10 | 3710.16 | 18-JAN-06:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 55.06 | 0.00 | 01-JAN-00:10 | 7843.53 | 30-MAY-13:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 417.04 | 0.00 | 01-JAN-00:40 | 147044.78 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 81.15 | 0.00 | 01-JAN-00:40 | 147044.78 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 335.89 | 0.00 | 01-JAN-00:10 | 58891.47 | 18-AUG-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 84.73 | 0.00 | 01-JAN-00:40 | 24320.88 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.85 | 0.00 | 01-JAN-00:40 | 24320.88 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 53.88 | 0.00 | 01-JAN-00:10 | 18178.94 | 19-JUN-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.97 | 381.72 | 01-JAN-00:40 | 7481.04 | 23-APR-17:50 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.97 | 381.72 | 01-JAN-00:40 | 7481.04 | 23-APR-17:50 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1166.93 | 2.50 | 19-JAN-06:00 | 70879.50 | 12-APR-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 3.71 | 0.00 | 03-JAN-15:00 | 5199.02 | 02-JAN-23:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1163.22 | 0.00 | 01-JAN-00:10 | 70879.50 | 12-APR-17:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.40 | 2.66 | 17-JAN-20:30 | 7182.47 | 12-APR-17:20 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.87 | 0.00 | 03-JAN-13:30 | 548.04 | 16-JAN-17:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.53 | 0.00 | 01-JAN-00:10 | 7182.47 | 12-APR-17:20 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7154.99 | 57075.47 | 11-JAN-22:50 | 375953.72 | 23-DEC-17:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.69 | 0.00 | 01-JAN-00:10 | 10113.45 | 30-JAN-22:20 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7154.30 | 57075.47 | 11-JAN-22:50 | 375953.72 | 23-DEC-17:40 |
EnergyTransfer:Plant | 21713.50 | 0.00 | 01-JAN-00:40 | 5892407.65 | 01-SEP-14:10 |
WaterSystems:EnergyTransfer | 412.73 | 0.00 | 01-JAN-00:10 | 52102.71 | 09-FEB-13:00 |
WaterUse:WaterSystems:EnergyTransfer | 412.73 | 0.00 | 01-JAN-00:10 | 52102.71 | 09-FEB-13:00 |
EnergyTransfer:HVAC | 18096.97 | 56970.21 | 19-JAN-03:40 | 2538668.79 | 02-AUG-15:00 |
HeatingCoils:EnergyTransfer | 510.02 | 0.00 | 01-JAN-00:40 | 1619922.33 | 02-JAN-07:10 |
PlantLoopHeatingDemand:HVAC | 510.02 | 0.00 | 01-JAN-00:40 | 1619922.33 | 02-JAN-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 510.02 | 0.00 | 01-JAN-00:40 | 1619922.33 | 02-JAN-07:10 |
CoolingCoils:EnergyTransfer | 16181.16 | 53389.36 | 28-JAN-16:10 | 2153113.55 | 22-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 855.00 | 0.00 | 01-JAN-00:10 | 591219.89 | 06-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 550.79 | 0.00 | 01-JAN-00:10 | 518680.49 | 08-JUL-12:00 |
LoopToLoop:EnergyTransfer | 7283.34 | -2425.60 | 24-JAN-06:10 | 1883933.87 | 01-SEP-14:10 |
Boilers:EnergyTransfer | 508.47 | 0.00 | 01-JAN-00:40 | 1535039.18 | 02-JAN-07:10 |
Chillers:EnergyTransfer | 6261.60 | 0.00 | 01-JAN-00:10 | 1852064.69 | 01-SEP-14:10 |
HeatRejection:EnergyTransfer | 7247.35 | 0.00 | 01-JAN-00:10 | 2107819.48 | 01-SEP-14:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 8.973 | -672.691 | 0.000 | 0.000 | 92.750 | 193.763 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -47.192 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -639.843 | 0.000 | 0.000 | 83.475 | 174.013 | 321.278 | 0.000 | 0.000 | 0.000 | 61.077 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 6.277 | -4516.448 | 0.000 | 0.000 | 847.466 | 1740.127 | 3212.773 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1290.195 |
CORE_TOP | 0.000 | 0.000 | 7.248 | -418.865 | 0.000 | 0.000 | 87.426 | 174.013 | 321.277 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -171.099 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.082 | -73.049 | 0.000 | 0.000 | 10.741 | 17.148 | 40.341 | 18.340 | 0.000 | 0.137 | 44.460 | 0.000 | -49.155 | 0.000 | -9.044 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.078 | -58.191 | 0.000 | 0.000 | 6.950 | 11.049 | 25.998 | 35.790 | 0.000 | 0.095 | 13.725 | 0.000 | -29.626 | 0.000 | -5.868 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.285 | -91.699 | 0.000 | 0.000 | 10.668 | 17.093 | 40.342 | 69.230 | 0.000 | 0.128 | 6.428 | 0.000 | -43.483 | 0.000 | -8.992 | -0.000 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.007 | -93.168 | 0.000 | 0.000 | 6.817 | 11.019 | 25.997 | 35.941 | 0.000 | 0.075 | 54.084 | 0.000 | -34.252 | 0.000 | -6.521 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 63.949 | -490.085 | 0.000 | 0.000 | 112.890 | 171.560 | 403.414 | 190.673 | 0.000 | 2.886 | 157.250 | 0.000 | -434.582 | 0.000 | -177.955 | -0.031 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 36.854 | -458.397 | 0.000 | 0.000 | 53.171 | 110.514 | 259.975 | 360.459 | 0.000 | 1.779 | 26.860 | 0.000 | -270.913 | 0.000 | -120.302 | -0.008 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 36.929 | -723.704 | 0.000 | 0.000 | 108.835 | 170.974 | 403.420 | 694.709 | 0.000 | 2.632 | 0.031 | 0.000 | -413.188 | 0.000 | -188.635 | -91.972 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 27.970 | -511.490 | 0.000 | 0.000 | 72.203 | 110.210 | 259.973 | 369.798 | 0.000 | 1.711 | 83.592 | 0.000 | -289.408 | 0.000 | -124.561 | -0.018 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 18.708 | -46.734 | 0.000 | 0.000 | 11.457 | 17.156 | 40.341 | 19.218 | 0.000 | 0.325 | 1.012 | 0.000 | -40.731 | 0.000 | -20.752 | -0.000 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 10.605 | -44.211 | 0.000 | 0.000 | 7.313 | 11.051 | 25.998 | 36.266 | 0.000 | 0.206 | 0.000 | 0.000 | -25.530 | 0.000 | -14.066 | -7.632 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 12.188 | -67.840 | 0.000 | 0.000 | 11.089 | 17.097 | 40.342 | 69.932 | 0.000 | 0.304 | 0.001 | 0.000 | -38.773 | 0.000 | -21.904 | -22.435 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 8.105 | -49.799 | 0.000 | 0.000 | 7.335 | 11.021 | 25.997 | 37.107 | 0.000 | 0.204 | 2.042 | 0.000 | -27.394 | 0.000 | -14.620 | -0.001 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -134.973 | 0.000 | 0.000 | 0.000 | 2.524 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -21.432 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 3.715 | -1163.218 | 0.000 | 0.000 | 0.000 | 25.238 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -404.541 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.871 | -107.531 | 0.000 | 0.000 | 0.000 | 2.524 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -49.744 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.686 | -7154.304 | 0.000 | 0.000 | 0.000 | 54.633 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -395.872 |
GROUNDFLOOR_PLENUM | 1.524 | -55.056 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.209 | 71.949 | 0.000 | 0.000 | 0.000 | -18.626 | 0.000 |
MIDFLOOR_PLENUM | 81.155 | -335.887 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.840 | 561.029 | 0.000 | 0.000 | 0.000 | -310.136 | -0.012 |
TOPFLOOR_PLENUM | 30.850 | -53.878 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.287 | 55.268 | 0.000 | 0.000 | 0.000 | -32.528 | -0.005 |
Total Facility | 113.529 | -444.821 | 243.532 | -17516.239 | 0.000 | 0.000 | 1530.586 | 3042.726 | 15213.288 | 1937.462 | 0.000 | 14.819 | 1138.809 | 0.000 | -1697.034 | 0.000 | -1074.512 | -2502.190 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 25-DEC-15:23 | 0.00 | 0.00 | 0.00 | -114195.43 | 0.00 | 0.00 | 342.10 | 932.91 | 13457.54 | 0.00 | 0.00 | 0.00 | 99462.88 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 06-SEP-03:02 | 0.00 | 0.00 | 0.00 | -93840.16 | 0.00 | 0.00 | 0.00 | 955.16 | 8057.15 | 0.00 | 0.00 | 0.00 | 84827.85 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 16-JUN-04:02 | 0.00 | 0.00 | 0.00 | -832350.16 | 0.00 | 0.00 | 0.00 | 19103.16 | 80571.20 | 0.00 | 0.00 | 0.00 | 732675.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 20-JUN-03:02 | 0.00 | 0.00 | 0.00 | -88944.87 | 0.00 | 0.00 | 0.00 | 955.16 | 8057.12 | 0.00 | 0.00 | 0.00 | 79932.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 08-JUL-05:02 | 0.00 | 0.00 | 0.00 | -12240.08 | 0.00 | 0.00 | 107.40 | 170.70 | 1011.70 | 546.02 | 0.00 | 0.67 | 10403.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 29-MAY-08:22 | 0.00 | 0.00 | 0.00 | -17644.32 | 0.00 | 0.00 | 23.09 | 49.49 | 488.98 | 13011.58 | 0.00 | 0.00 | 4117.61 | 0.00 | -0.00 | 0.00 | -46.43 | 0.00 |
PERIMETER_BOT_ZN_1 | 22-OCT-12:32 | 0.00 | 0.00 | 0.00 | -17136.33 | 0.00 | 0.00 | 38.72 | 76.80 | 758.78 | 15506.20 | 0.00 | 0.00 | 807.39 | 0.00 | -0.00 | 0.00 | -51.56 | 0.00 |
PERIMETER_BOT_ZN_4 | 13-AUG-16:41 | 0.00 | 0.00 | 0.00 | -23161.10 | 0.00 | 0.00 | 20.11 | 49.49 | 488.98 | 8144.57 | 0.00 | 14.78 | 14443.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 10-JUL-03:02 | 0.00 | 0.00 | 0.00 | -121210.23 | 0.00 | 0.00 | 0.00 | 1199.30 | 10116.97 | 0.00 | 0.00 | 292.39 | 111039.87 | 0.00 | -1438.29 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 02-JUL-08:32 | 0.00 | 0.00 | 0.00 | -186579.38 | 0.00 | 0.00 | 226.72 | 494.89 | 4889.82 | 130480.52 | 0.00 | 0.00 | 51587.75 | 0.00 | -0.00 | 0.00 | -1100.32 | 0.00 |
PERIMETER_MID_ZN_1 | 04-SEP-12:42 | 0.00 | 0.00 | 0.00 | -163647.48 | 0.00 | 0.00 | 378.88 | 767.96 | 7587.84 | 139215.14 | 0.00 | 0.00 | 17039.70 | 0.00 | -0.00 | 0.00 | -1342.05 | 0.00 |
PERIMETER_MID_ZN_4 | 04-JUL-16:21 | 0.00 | 0.00 | 0.00 | -192658.69 | 0.00 | 0.00 | 224.63 | 494.89 | 4889.79 | 115896.79 | 0.00 | 0.00 | 72790.32 | 0.00 | -0.00 | 0.00 | -1637.74 | 0.00 |
PERIMETER_TOP_ZN_3 | 09-JUL-16:12 | 0.00 | 0.00 | 0.00 | -13565.44 | 0.00 | 0.00 | 44.12 | 76.79 | 758.77 | 3073.27 | 0.00 | 8.48 | 9604.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 09-JUL-09:32 | 0.00 | 0.00 | 0.00 | -18451.66 | 0.00 | 0.00 | 23.10 | 49.49 | 488.98 | 8712.43 | 0.00 | 70.57 | 9107.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 04-SEP-12:51 | 0.00 | 0.00 | 0.00 | -17915.27 | 0.00 | 0.00 | 37.22 | 76.80 | 758.78 | 13471.54 | 0.00 | 0.00 | 3716.84 | 0.00 | -0.00 | 0.00 | -145.92 | 0.00 |
PERIMETER_TOP_ZN_4 | 04-JUL-16:21 | 0.00 | 0.00 | 0.00 | -20794.33 | 0.00 | 0.00 | 21.39 | 49.49 | 488.98 | 11520.51 | 0.00 | 0.00 | 8942.18 | 0.00 | -0.00 | 0.00 | -228.22 | 0.00 |
DATACENTER_BOT_ZN_6 | 23-APR-17:50 | 0.00 | 0.00 | 0.00 | -7488.15 | 0.00 | 0.00 | 0.00 | 13.85 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -320.12 |
DATACENTER_MID_ZN_6 | 12-APR-17:20 | 0.00 | 0.00 | 0.00 | -70879.50 | 0.00 | 0.00 | 0.00 | 729.08 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7793.80 |
DATACENTER_TOP_ZN_6 | 12-APR-17:20 | 0.00 | 0.00 | 0.00 | -7182.47 | 0.00 | 0.00 | 0.00 | 72.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -684.86 |
DATACENTER_BASEMENT_ZN_6 | 18-FEB-00:31 | 0.00 | 0.00 | 0.00 | -410313.43 | 0.00 | 0.00 | 0.00 | 299.88 | 189816.26 | 0.00 | 0.00 | 0.00 | 220197.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 15-AUG-05:01 | 0.00 | -9035.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9040.65 | 0.00 | -0.00 | 0.00 | -5.61 | 0.00 |
MIDFLOOR_PLENUM | 25-JUL-05:01 | 0.00 | -90991.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91220.37 | 0.00 | -0.00 | 0.00 | -228.80 | 0.00 |
TOPFLOOR_PLENUM | 19-JUN-13:50 | 0.00 | -18178.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.92 | 17916.51 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 15-AUG-03:01 | 0.00 | 78102.77 | 0.00 | -1901558.20 | 0.00 | 0.00 | 0.00 | 17724.82 | 623236.89 | 0.00 | 0.00 | 1.53 | 1198299.55 | 0.00 | -12863.02 | 0.00 | -2944.34 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 14-JAN-05:49 | 0.00 | 0.00 | 135567.78 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.57 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -150088.89 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 453507.34 | -0.00 | 0.00 | 0.00 | 0.00 | 9551.58 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -543630.12 |
CORE_TOP | 02-JAN-04:01 | 0.00 | 0.00 | 78014.31 | -0.00 | 0.00 | 0.00 | 0.00 | 955.16 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -87026.58 |
PERIMETER_BOT_ZN_3 | 06-FEB-05:01 | 0.00 | 0.00 | 9443.37 | -0.00 | 0.00 | 0.00 | 0.00 | 239.86 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5596.86 | 0.00 | -2189.42 | -2908.65 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 7886.18 | -0.00 | 0.00 | 0.00 | 0.00 | 154.57 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3594.10 | 0.00 | -1439.52 | -3659.11 |
PERIMETER_BOT_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 12032.84 | -0.00 | 0.00 | 0.00 | 0.00 | 239.86 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5203.54 | 0.00 | -2115.29 | -5965.59 |
PERIMETER_BOT_ZN_4 | 02-JAN-06:01 | 0.00 | 0.00 | 4995.08 | -0.00 | 0.00 | 0.00 | 94.15 | 135.58 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3566.80 | 0.00 | -151.64 | -2158.36 |
PERIMETER_MID_ZN_3 | 02-JAN-01:22 | 0.00 | 0.00 | 123875.52 | -0.00 | 0.00 | 0.00 | 0.00 | 1199.30 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43784.44 | 0.00 | -31511.96 | -59895.39 |
PERIMETER_MID_ZN_2 | 02-JAN-01:22 | 0.00 | 0.00 | 150306.69 | -0.00 | 0.00 | 0.00 | 0.00 | 772.87 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28375.49 | 0.00 | -21425.13 | -107798.71 |
PERIMETER_MID_ZN_1 | 02-JAN-01:22 | 0.00 | 0.00 | 138187.48 | -0.00 | 0.00 | 0.00 | 0.00 | 1199.32 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -42919.53 | 0.00 | -31858.20 | -74726.20 |
PERIMETER_MID_ZN_4 | 02-JAN-01:22 | 0.00 | 0.00 | 147603.54 | -0.00 | 0.00 | 0.00 | 0.00 | 772.87 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -29556.75 | 0.00 | -21589.77 | -103749.60 |
PERIMETER_TOP_ZN_3 | 02-JAN-01:22 | 0.00 | 0.00 | 14092.66 | -0.00 | 0.00 | 0.00 | 0.00 | 119.93 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4292.91 | 0.00 | -3824.68 | -7106.69 |
PERIMETER_TOP_ZN_2 | 02-JAN-01:22 | 0.00 | 0.00 | 16098.85 | -0.00 | 0.00 | 0.00 | 0.00 | 77.29 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2783.03 | 0.00 | -2603.09 | -11442.00 |
PERIMETER_TOP_ZN_1 | 02-JAN-01:22 | 0.00 | 0.00 | 15915.01 | -0.00 | 0.00 | 0.00 | 0.00 | 119.93 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4206.83 | 0.00 | -3871.39 | -8968.44 |
PERIMETER_TOP_ZN_4 | 02-JAN-01:22 | 0.00 | 0.00 | 17254.15 | -0.00 | 0.00 | 0.00 | 0.00 | 77.29 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2897.05 | 0.00 | -2623.59 | -12462.76 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-JAN-23:40 | 0.00 | 0.00 | 5199.02 | 0.00 | 0.00 | 0.00 | 0.00 | 121.51 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24806.59 |
DATACENTER_TOP_ZN_6 | 16-JAN-17:40 | 0.00 | 0.00 | 548.04 | 0.00 | 0.00 | 0.00 | 0.00 | 12.15 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2508.79 |
DATACENTER_BASEMENT_ZN_6 | 13-JAN-21:51 | 0.00 | 0.00 | 61166.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1052.16 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -157127.25 |
GROUNDFLOOR_PLENUM | 26-DEC-04:01 | 13050.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -918.66 | -12132.08 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 151031.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -6537.47 | -144493.99 |
TOPFLOOR_PLENUM | 06-FEB-05:10 | 26288.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7875.54 | -18413.27 |
Total Facility | 02-JAN-04:01 | -150703.94 | 190311.72 | 1136046.43 | -190311.72 | 0.00 | 0.00 | 0.00 | 17724.82 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -177135.50 | 0.00 | -78014.92 | -1016279.59 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.2543 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.2543 | 0.2284 | 1.0000 | 1.2001 | 0.2284 | ||
VAV_BOT WITH REHEAT | 9.4669 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.8996 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 88.6114 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 82.6209 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.2559 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 8.4803 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.1850 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.1850 | 0.0160 | 1.0000 | 0.3384 | 0.0160 | ||
AIRLOOP DATACENTER BOT | 0.4589 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4589 | 0.0341 | 1.0000 | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3726 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3726 | 0.0357 | 1.0000 | 0.1563 | 0.0357 | ||
AIRLOOP DATACENTER TOP | 0.4454 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4454 | 0.0351 | 1.0000 | 0.0156 | 0.0351 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
CAV_BAS | 5.2543 | 0.0000 | 149.6021 | 1.0000 | 1.2001 | 5.2543 | 1.0000 | 1.0000 | 1.2001 | 0.2284 | ||
VAV_BOT WITH REHEAT | 4.7335 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.7915 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 44.3057 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 27.0938 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.6280 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.7445 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
AIRLOOP DATACENTER BASEMENT | 21.1850 | 0.0000 | 0.0000 | 1.0000 | 0.3384 | 21.1850 | 1.0000 | 1.0000 | 0.3384 | 0.0160 | ||
AIRLOOP DATACENTER BOT | 0.4589 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4589 | 1.0000 | 1.0000 | 0.0156 | 0.0341 | ||
AIRLOOP DATACENTER MID | 4.3726 | 0.0000 | 0.0000 | 1.0000 | 0.1563 | 4.3726 | 1.0000 | 1.0000 | 0.1563 | 0.0357 | ||
AIRLOOP DATACENTER TOP | 0.4454 | 0.0000 | 0.0000 | 1.0000 | 0.0156 | 0.4454 | 1.0000 | 1.0000 | 0.0156 | 0.0351 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2001 | 1.0000 | 1.2001 | 1.000 | 1.2001 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 0.0000 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 0.0000 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 0.0000 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2001 | 1.2001 | 1.2001 |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
AIRLOOP DATACENTER BASEMENT | 0.00 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 | |
AIRLOOP DATACENTER BOT | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 | |
AIRLOOP DATACENTER MID | 0.00 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 | |
AIRLOOP DATACENTER TOP | 0.00 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.2543 | 5.2543 | 5.2543 | 1.2001 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5344 | 5.5344 | 1.8872 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 51.9491 | 51.9491 | 18.4419 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.3092 | 5.3092 | 1.8582 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8387 | 0.8387 | 0.2373 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9587 | 0.9587 | 0.1917 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9441 | 0.9441 | 0.2370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1911 | 1.1911 | 0.2382 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.8083 | 7.8083 | 2.3191 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 9.9258 | 9.9258 | 1.9852 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.7820 | 8.7820 | 2.3184 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.1463 | 10.1463 | 2.0293 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8639 | 0.8639 | 0.2333 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0074 | 1.0074 | 0.2015 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9867 | 0.9867 | 0.2338 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0888 | 1.0888 | 0.2178 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4589 | 0.4589 | 0.4589 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3726 | 4.3726 | 4.3726 | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4454 | 0.4454 | 0.4454 | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.1850 | 21.1850 | 21.1850 | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.2543 | 5.2543 | 5.2543 | 5.2543 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 9.4669 | 8.8996 | 9.4669 | 2.7915 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 88.6114 | 82.6209 | 88.6114 | 27.0938 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.2559 | 8.4803 | 9.2559 | 2.7445 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.1850 | 21.1850 | 21.1850 | 21.1850 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4589 | 0.4589 | 0.4589 | 0.4589 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3726 | 4.3726 | 4.3726 | 4.3726 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4454 | 0.4454 | 0.4454 | 0.4454 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | 5.2543 | 5.2543 | 5.2543 | 1.2001 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7672 | 2.7672 | 1.8872 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 25.9745 | 25.9745 | 18.4419 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6546 | 2.6546 | 1.8582 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4193 | 0.4193 | 0.2373 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4793 | 0.4793 | 0.1917 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4720 | 0.4720 | 0.2370 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5956 | 0.5956 | 0.2382 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.9041 | 3.9041 | 2.3191 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9629 | 4.9629 | 1.9852 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.3910 | 4.3910 | 2.3184 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.0731 | 5.0731 | 2.0293 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4320 | 0.4320 | 0.2333 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5037 | 0.5037 | 0.2015 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4933 | 0.4933 | 0.2338 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5444 | 0.5444 | 0.2178 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.4589 | 0.4589 | 0.4589 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 4.3726 | 4.3726 | 4.3726 | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.4454 | 0.4454 | 0.4454 | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 | |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 21.1850 | 21.1850 | 21.1850 | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
CAV_BAS | 5.2543 | 5.2543 | 5.2543 | 5.2543 | 1.2001 | 1.0000 |
VAV_BOT WITH REHEAT | 4.7335 | 2.7915 | 2.7915 | 2.7915 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 44.3057 | 27.0938 | 27.0938 | 27.0938 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.6280 | 2.7445 | 2.7445 | 2.7445 | 0.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.1850 | 21.1850 | 21.1850 | 21.1850 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4589 | 0.4589 | 0.4589 | 0.4589 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.3726 | 4.3726 | 4.3726 | 4.3726 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4454 | 0.4454 | 0.4454 | 0.4454 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:59:48
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 44.83 |
Number of hours cooling loads not met | 174.83 |
Number of hours not met | 219.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Boiler | 0.00 | 0.00 | 707.28 | 1881428.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 985.74 | 262224.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Other | 2477.78 | 167172.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 3042.73 | 279851.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 438.74 | 36729.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.86 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.90 | 3737.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1895.08 | 122221.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2048.00 | 192923.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 478.16 | 55529.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 190.21 | 40303.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Other | 941.97 | 49248.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 25.40 | 41323.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 49.79 | 5613.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 557.21 | 81935.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.29 | 27852.63 |
Natural Gas | 0.00 | 1264.49 |
Additional | 0.00 | 0.00 |
Total | 15213.29 | 29117.12 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 65.69 |
Space Heating | 0.00 |
Space Cooling | 74.77 |
Fans (All) | 44.21 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 601.30 |
Subtotal | 601.30 |
Natural Gas [MJ/m2] | |
Space Heating | 15.27 |
Service Water Heating | 12.03 |
Miscellaneous (All) | 27.30 |
Subtotal | 27.30 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 10.45 |
Space Heating | 2.43 |
Space Cooling | 11.90 |
Fans (All) | 7.03 |
Service Water Heating | 1.91 |
Receptacle Equipment | 52.25 |
Miscellaneous | 14.03 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2597. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2154. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | BASEMENT DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.252727E+12 |
February | 0.000 | 0.177227E+12 |
March | 0.000 | 0.604177E+11 |
April | 0.000 | 0.125196E+11 |
May | 0.000 | 0.196331E+10 |
June | 0.000 | 0.240060E+10 |
July | 0.000 | 0.206238E+10 |
August | 0.000 | 0.312668E+10 |
September | 0.000 | 0.243274E+10 |
October | 0.000 | 0.499114E+10 |
November | 0.000 | 0.597982E+11 |
December | 0.000 | 0.127617E+12 |
Annual Sum or Average | 0.707284E+12 | |
Minimum of Months | 0.000 | 0.196331E+10 |
Maximum of Months | 0.000 | 0.252727E+12 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.466590E+11 | 106813.71 | 26-JAN-05:50 | -1.1 | -3.2 | 0.564638E+10 | 7499.18 | 03-JAN-10:00 | 12.00 | 11.46 |
February | 0.437720E+11 | 112881.08 | 21-FEB-04:01 | 1.78 | 1.01 | 0.511555E+10 | 7499.13 | 28-FEB-10:20 | 7.03 | 6.58 |
March | 0.550910E+11 | 107333.99 | 27-MAR-03:01 | 8.22 | 7.71 | 0.613019E+10 | 7499.10 | 16-MAR-13:30 | 0.00 | -0.0 |
April | 0.524593E+11 | 107364.97 | 21-APR-03:53 | 5.60 | 5.02 | 0.544738E+10 | 7499.14 | 07-APR-13:00 | 26.10 | 15.93 |
May | 0.550252E+11 | 108303.57 | 01-MAY-02:31 | 7.93 | 5.39 | 0.589951E+10 | 7499.52 | 25-MAY-09:20 | 16.87 | 13.21 |
June | 0.580055E+11 | 106823.57 | 05-JUN-02:20 | 16.50 | 13.05 | 0.588077E+10 | 7499.23 | 23-JUN-09:00 | 30.00 | 18.37 |
July | 0.585404E+11 | 99709.39 | 16-JUL-24:00 | 24.40 | 18.02 | 0.547218E+10 | 7499.16 | 12-JUL-09:20 | 27.40 | 18.55 |
August | 0.653768E+11 | 99935.21 | 23-AUG-03:50 | 18.58 | 14.13 | 0.613740E+10 | 7499.15 | 08-AUG-13:09 | 26.60 | 16.88 |
September | 0.597703E+11 | 108855.37 | 11-SEP-02:32 | 13.17 | 9.14 | 0.545238E+10 | 7499.25 | 19-SEP-09:20 | 18.87 | 14.30 |
October | 0.632912E+11 | 112615.67 | 09-OCT-09:53 | 11.70 | 6.58 | 0.567197E+10 | 7499.50 | 16-OCT-09:20 | 17.07 | 14.17 |
November | 0.591687E+11 | 112163.09 | 12-NOV-17:52 | 8.90 | 6.66 | 0.561473E+10 | 7499.12 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.555295E+11 | 114206.86 | 25-DEC-15:23 | 9.70 | 7.73 | 0.546883E+10 | 7499.07 | 22-DEC-10:09 | -2.0 | -4.7 |
Annual Sum or Average | 0.672689E+12 | 0.679373E+11 | ||||||||
Minimum of Months | 0.437720E+11 | 99709.39 | -1.1 | -3.2 | 0.511555E+10 | 7499.07 | -2.0 | -4.7 | ||
Maximum of Months | 0.653768E+11 | 114206.86 | 24.40 | 18.02 | 0.613740E+10 | 7499.52 | 30.00 | 18.55 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351414E+11 | 62312.86 | 24-JAN-05:01 | 10.18 | 10.18 | 0.504538E+10 | 6740.57 | 25-JAN-10:50 | 4.40 | 1.38 |
February | 0.351996E+11 | 67821.80 | 21-FEB-04:02 | 1.78 | 1.01 | 0.459252E+10 | 6734.80 | 09-FEB-10:30 | -5.2 | -7.3 |
March | 0.503388E+11 | 70801.50 | 27-MAR-03:02 | 8.22 | 7.71 | 0.550024E+10 | 6734.85 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.545304E+11 | 73338.70 | 08-APR-03:01 | 15.40 | 12.60 | 0.488217E+10 | 6734.80 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.532722E+11 | 82972.06 | 31-MAY-03:02 | 16.60 | 14.90 | 0.528157E+10 | 6735.05 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.612859E+11 | 86093.59 | 28-JUN-03:02 | 18.98 | 18.21 | 0.526503E+10 | 6734.80 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.691734E+11 | 82441.99 | 01-JUL-03:01 | 20.00 | 19.64 | 0.488576E+10 | 6734.46 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.772988E+11 | 80360.85 | 02-AUG-05:02 | 24.50 | 22.18 | 0.548852E+10 | 6734.77 | 30-AUG-13:50 | 28.62 | 15.48 |
September | 0.541362E+11 | 93847.16 | 06-SEP-03:02 | 21.60 | 19.31 | 0.487794E+10 | 6734.95 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.545264E+11 | 86557.12 | 06-OCT-03:02 | 19.40 | 17.99 | 0.507852E+10 | 6735.12 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.479310E+11 | 73073.18 | 06-NOV-04:01 | 5.00 | 2.82 | 0.503467E+10 | 6734.88 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.470098E+11 | 70844.37 | 26-DEC-04:02 | 5.60 | 4.99 | 0.490159E+10 | 6736.17 | 11-DEC-14:39 | 1.10 | -0.5 |
Annual Sum or Average | 0.639844E+12 | 0.608339E+11 | ||||||||
Minimum of Months | 0.351414E+11 | 62312.86 | 1.78 | 1.01 | 0.459252E+10 | 6734.46 | -5.2 | -7.3 | ||
Maximum of Months | 0.772988E+11 | 93847.16 | 24.50 | 22.18 | 0.550024E+10 | 6740.57 | 29.43 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230840E+11 | 55127.03 | 31-JAN-09:50 | -6.9 | -9.4 | 0.461259E+10 | 6735.01 | 20-JAN-14:09 | 7.30 | 3.68 |
February | 0.234331E+11 | 49914.03 | 24-FEB-06:03 | 4.60 | 4.47 | 0.433100E+10 | 6803.59 | 03-FEB-10:20 | -4.3 | -6.8 |
March | 0.321344E+11 | 55876.39 | 28-MAR-05:02 | 9.50 | 7.48 | 0.539966E+10 | 6818.34 | 30-MAR-09:09 | 2.98 | 1.99 |
April | 0.343372E+11 | 66877.41 | 10-APR-05:02 | 15.10 | 13.73 | 0.483243E+10 | 6747.36 | 21-APR-09:39 | 6.10 | 5.88 |
May | 0.436922E+11 | 71321.58 | 31-MAY-05:03 | 16.38 | 14.98 | 0.525383E+10 | 6734.98 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.487263E+11 | 83239.56 | 16-JUN-04:02 | 20.10 | 20.03 | 0.524345E+10 | 6734.72 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.503133E+11 | 78906.34 | 24-JUL-03:02 | 22.02 | 21.19 | 0.486484E+10 | 6734.47 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.540651E+11 | 79073.42 | 07-AUG-03:02 | 18.80 | 17.42 | 0.547439E+10 | 6734.80 | 30-AUG-13:00 | 28.90 | 15.44 |
September | 0.447203E+11 | 78432.39 | 13-SEP-05:02 | 21.70 | 18.83 | 0.485101E+10 | 6734.91 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.403780E+11 | 75166.09 | 06-OCT-05:02 | 19.40 | 18.22 | 0.504549E+10 | 6735.03 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.298375E+11 | 65322.07 | 10-NOV-06:01 | 14.60 | 14.60 | 0.492298E+10 | 6745.96 | 29-NOV-10:39 | 7.03 | 4.11 |
December | 0.269251E+11 | 53871.33 | 21-DEC-06:02 | -0.1 | -2.7 | 0.473016E+10 | 6748.69 | 14-DEC-14:30 | 5.30 | 1.19 |
Annual Sum or Average | 0.451646E+12 | 0.595618E+11 | ||||||||
Minimum of Months | 0.230840E+11 | 49914.03 | -6.9 | -9.4 | 0.433100E+10 | 6734.47 | -4.3 | -6.8 | ||
Maximum of Months | 0.540651E+11 | 83239.56 | 22.02 | 21.19 | 0.547439E+10 | 6818.34 | 28.90 | 16.94 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182226E+11 | 19470.84 | 20-JAN-16:55 | 5.60 | 3.18 | 0.416798E+10 | 6559.62 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.175161E+11 | 20252.41 | 24-FEB-17:00 | 6.70 | 1.40 | 0.382822E+10 | 6613.85 | 17-FEB-14:00 | 6.10 | 1.73 |
March | 0.259574E+11 | 33188.84 | 03-MAR-17:00 | 14.00 | 7.83 | 0.500081E+10 | 6734.57 | 07-MAR-14:30 | 10.00 | 5.03 |
April | 0.300575E+11 | 66135.99 | 10-APR-05:02 | 15.10 | 13.73 | 0.467535E+10 | 6734.68 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.421647E+11 | 72978.70 | 31-MAY-05:02 | 16.38 | 14.98 | 0.520971E+10 | 6734.96 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.515144E+11 | 88950.53 | 20-JUN-03:02 | 22.02 | 19.38 | 0.524194E+10 | 6745.18 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.550401E+11 | 82298.49 | 24-JUL-03:02 | 22.02 | 21.19 | 0.487416E+10 | 6734.44 | 05-JUL-09:09 | 24.08 | 21.68 |
August | 0.580108E+11 | 88305.38 | 28-AUG-03:02 | 20.50 | 17.38 | 0.547682E+10 | 6734.72 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.437407E+11 | 80314.63 | 13-SEP-05:02 | 21.70 | 18.83 | 0.482732E+10 | 6734.88 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.346564E+11 | 74172.67 | 06-OCT-05:01 | 19.40 | 18.22 | 0.493065E+10 | 6734.72 | 31-OCT-13:00 | 12.80 | 10.34 |
November | 0.225844E+11 | 32817.26 | 03-NOV-16:00 | 15.00 | 10.24 | 0.450554E+10 | 6734.74 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.194025E+11 | 18892.14 | 20-DEC-17:00 | 6.70 | 3.51 | 0.414383E+10 | 6578.32 | 20-DEC-14:00 | 8.30 | 4.99 |
Annual Sum or Average | 0.418867E+12 | 0.568823E+11 | ||||||||
Minimum of Months | 0.175161E+11 | 18892.14 | 5.60 | 1.40 | 0.382822E+10 | 6559.62 | 6.10 | 1.73 | ||
Maximum of Months | 0.580108E+11 | 88950.53 | 22.02 | 21.19 | 0.547682E+10 | 6745.18 | 29.43 | 21.68 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.248076E+10 | 2588.55 | 25-JAN-08:10 | 3.90 | 0.79 | 0.550600E+09 | 828.66 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.239713E+10 | 2503.83 | 24-FEB-14:10 | 9.22 | 3.10 | 0.505073E+09 | 845.59 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.401261E+10 | 5954.96 | 27-MAR-13:30 | 20.85 | 16.75 | 0.663690E+09 | 845.63 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.548287E+10 | 6849.92 | 07-APR-13:50 | 26.20 | 16.00 | 0.604258E+09 | 845.63 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.666771E+10 | 10856.09 | 31-MAY-05:02 | 16.38 | 14.98 | 0.660491E+09 | 845.66 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.919989E+10 | 11773.48 | 26-JUN-05:02 | 20.78 | 17.10 | 0.661395E+09 | 845.66 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.110276E+11 | 12241.22 | 08-JUL-05:02 | 25.10 | 22.68 | 0.614741E+09 | 845.60 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.118915E+11 | 11693.21 | 01-AUG-05:02 | 23.90 | 20.76 | 0.689683E+09 | 845.63 | 23-AUG-13:20 | 25.60 | 17.08 |
September | 0.708625E+10 | 12029.15 | 14-SEP-03:01 | 22.20 | 21.85 | 0.610695E+09 | 845.65 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.583611E+10 | 9287.80 | 25-OCT-05:01 | 18.05 | 17.39 | 0.631099E+09 | 845.67 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.377829E+10 | 4989.89 | 03-NOV-13:40 | 17.60 | 10.63 | 0.610813E+09 | 845.64 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.318860E+10 | 3787.58 | 26-DEC-13:30 | 9.45 | 5.01 | 0.576320E+09 | 845.61 | 18-DEC-14:00 | 6.10 | 2.60 |
Annual Sum or Average | 0.730493E+11 | 0.737886E+10 | ||||||||
Minimum of Months | 0.239713E+10 | 2503.83 | 3.90 | 0.79 | 0.505073E+09 | 828.66 | 6.10 | 2.25 | ||
Maximum of Months | 0.118915E+11 | 12241.22 | 26.20 | 22.68 | 0.689683E+09 | 845.67 | 29.43 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192730E+10 | 3206.35 | 19-JAN-09:30 | 6.10 | 3.62 | 0.354244E+09 | 544.95 | 20-JAN-10:09 | 4.60 | 1.16 |
February | 0.192139E+10 | 4666.86 | 22-FEB-09:25 | 0.30 | -3.1 | 0.327986E+09 | 544.95 | 22-FEB-10:39 | 1.67 | -2.2 |
March | 0.337892E+10 | 7351.69 | 29-MAR-08:40 | 5.20 | 2.68 | 0.424058E+09 | 544.95 | 01-MAR-10:00 | 13.90 | 7.41 |
April | 0.448940E+10 | 11342.00 | 23-APR-08:23 | 11.15 | 7.46 | 0.385063E+09 | 544.97 | 26-APR-09:50 | 16.38 | 12.55 |
May | 0.583138E+10 | 17643.82 | 29-MAY-08:22 | 25.00 | 16.72 | 0.424983E+09 | 545.00 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.710776E+10 | 16742.01 | 25-JUN-08:43 | 25.40 | 23.50 | 0.425373E+09 | 544.98 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.829966E+10 | 17047.89 | 02-JUL-09:22 | 25.85 | 21.73 | 0.395598E+09 | 544.94 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.936104E+10 | 12052.53 | 20-AUG-08:53 | 21.70 | 14.73 | 0.443774E+09 | 544.96 | 23-AUG-13:20 | 25.60 | 17.08 |
September | 0.585059E+10 | 17317.85 | 04-SEP-08:11 | 23.17 | 18.66 | 0.392942E+09 | 544.98 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.483950E+10 | 8202.09 | 03-OCT-08:40 | 18.33 | 16.57 | 0.405870E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.280583E+10 | 5027.73 | 02-NOV-08:50 | 10.82 | 5.70 | 0.388554E+09 | 544.96 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.237836E+10 | 3623.04 | 20-DEC-09:05 | 6.47 | 4.25 | 0.358292E+09 | 544.95 | 18-DEC-10:09 | 4.60 | 1.50 |
Annual Sum or Average | 0.581911E+11 | 0.472674E+10 | ||||||||
Minimum of Months | 0.192139E+10 | 3206.35 | 0.30 | -3.1 | 0.327986E+09 | 544.94 | 1.67 | -2.2 | ||
Maximum of Months | 0.936104E+10 | 17643.82 | 25.85 | 23.50 | 0.443774E+09 | 545.00 | 29.43 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359412E+10 | 10347.94 | 17-JAN-13:30 | 10.55 | 5.36 | 0.573501E+09 | 879.18 | 19-JAN-14:09 | 9.32 | 3.66 |
February | 0.379830E+10 | 10367.60 | 22-FEB-13:20 | 4.27 | -0.9 | 0.533354E+09 | 891.06 | 22-FEB-14:09 | 4.90 | -0.5 |
March | 0.595387E+10 | 11816.55 | 01-MAR-13:20 | 13.90 | 6.50 | 0.663692E+09 | 913.68 | 29-MAR-13:20 | 7.80 | 5.34 |
April | 0.629888E+10 | 11837.83 | 07-APR-12:30 | 26.15 | 15.88 | 0.599339E+09 | 845.66 | 10-APR-13:09 | 20.10 | 10.08 |
May | 0.695204E+10 | 11200.91 | 30-MAY-03:02 | 18.22 | 15.07 | 0.658859E+09 | 847.55 | 30-MAY-13:00 | 29.40 | 16.91 |
June | 0.948404E+10 | 12265.83 | 26-JUN-05:02 | 20.78 | 17.10 | 0.661249E+09 | 845.69 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.116270E+11 | 13764.37 | 08-JUL-05:02 | 25.10 | 22.68 | 0.615060E+09 | 845.62 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.138155E+11 | 16390.66 | 13-AUG-12:43 | 31.02 | 19.47 | 0.690970E+09 | 915.85 | 30-AUG-13:00 | 28.90 | 15.44 |
September | 0.961127E+10 | 16988.08 | 04-SEP-12:51 | 26.10 | 18.29 | 0.614253E+09 | 933.80 | 28-SEP-13:09 | 22.98 | 13.53 |
October | 0.989773E+10 | 17136.93 | 22-OCT-12:32 | 21.83 | 16.68 | 0.641877E+09 | 966.41 | 30-OCT-13:20 | 15.77 | 9.68 |
November | 0.576711E+10 | 12910.41 | 02-NOV-13:20 | 15.77 | 8.35 | 0.617780E+09 | 960.13 | 02-NOV-13:09 | 15.68 | 8.27 |
December | 0.489948E+10 | 13720.95 | 17-DEC-11:33 | 11.67 | 4.43 | 0.581623E+09 | 908.21 | 21-DEC-14:09 | 3.30 | -1.3 |
Annual Sum or Average | 0.916993E+11 | 0.745156E+10 | ||||||||
Minimum of Months | 0.359412E+10 | 10347.94 | 4.27 | -0.9 | 0.533354E+09 | 845.62 | 3.30 | -1.3 | ||
Maximum of Months | 0.138155E+11 | 17136.93 | 31.02 | 22.68 | 0.690970E+09 | 966.41 | 29.43 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.287727E+10 | 5597.01 | 20-JAN-15:50 | 7.30 | 3.82 | 0.367843E+09 | 544.94 | 20-JAN-14:30 | 7.50 | 3.79 |
February | 0.319134E+10 | 7854.89 | 24-FEB-15:30 | 8.05 | 2.02 | 0.348972E+09 | 544.95 | 23-FEB-10:20 | 5.60 | 3.17 |
March | 0.627771E+10 | 16997.89 | 26-MAR-16:33 | 10.97 | 9.74 | 0.442970E+09 | 544.96 | 27-MAR-09:09 | 11.20 | 11.20 |
April | 0.855219E+10 | 20601.44 | 16-APR-15:42 | 21.20 | 13.82 | 0.395803E+09 | 544.97 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.749013E+10 | 18194.42 | 21-MAY-15:43 | 19.27 | 12.81 | 0.427527E+09 | 544.99 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.106740E+11 | 21380.49 | 18-JUN-17:52 | 23.30 | 21.43 | 0.427532E+09 | 544.99 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.129813E+11 | 21457.67 | 04-JUL-14:32 | 27.40 | 18.56 | 0.397660E+09 | 544.94 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.160181E+11 | 23163.04 | 13-AUG-16:41 | 29.50 | 20.69 | 0.446038E+09 | 544.97 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.774960E+10 | 22167.83 | 10-SEP-16:22 | 23.05 | 12.76 | 0.395145E+09 | 544.98 | 01-SEP-13:00 | 31.10 | 17.31 |
October | 0.749359E+10 | 17461.39 | 06-OCT-03:01 | 19.40 | 17.99 | 0.410830E+09 | 544.99 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.505473E+10 | 13857.33 | 04-NOV-03:01 | 10.10 | 9.12 | 0.404783E+09 | 544.97 | 09-NOV-14:00 | 13.90 | 12.65 |
December | 0.480833E+10 | 11810.85 | 25-DEC-14:31 | 10.00 | 8.45 | 0.394329E+09 | 545.06 | 11-DEC-14:39 | 1.10 | -0.5 |
Annual Sum or Average | 0.931682E+11 | 0.485943E+10 | ||||||||
Minimum of Months | 0.287727E+10 | 5597.01 | 7.30 | 2.02 | 0.348972E+09 | 544.94 | 1.10 | -0.5 | ||
Maximum of Months | 0.160181E+11 | 23163.04 | 29.50 | 21.43 | 0.446038E+09 | 545.06 | 31.10 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.717219E+09 | 1954.93 | 20-JAN-13:20 | 6.47 | 3.05 | 0.473593E+09 | 705.65 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.734936E+09 | 2522.15 | 22-FEB-17:20 | 3.13 | -0.4 | 0.433828E+09 | 727.98 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.219758E+10 | 3138.43 | 27-MAR-16:00 | 22.20 | 16.33 | 0.565736E+09 | 841.84 | 28-MAR-13:00 | 13.30 | 8.40 |
April | 0.313347E+10 | 5183.15 | 07-APR-15:20 | 25.60 | 15.99 | 0.555626E+09 | 845.62 | 06-APR-13:09 | 18.90 | 14.06 |
May | 0.518500E+10 | 9705.60 | 31-MAY-05:02 | 16.38 | 14.98 | 0.647693E+09 | 845.65 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.728622E+10 | 11178.68 | 24-JUN-05:02 | 21.78 | 21.25 | 0.658982E+09 | 845.63 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.832052E+10 | 12126.14 | 10-JUL-03:02 | 26.10 | 21.75 | 0.614453E+09 | 845.60 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.856411E+10 | 11955.50 | 05-AUG-05:02 | 26.20 | 23.65 | 0.688992E+09 | 845.64 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.569475E+10 | 11164.09 | 02-SEP-05:02 | 22.12 | 16.29 | 0.602901E+09 | 845.64 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.403490E+10 | 5402.38 | 05-OCT-14:00 | 23.30 | 18.85 | 0.602513E+09 | 845.60 | 26-OCT-13:20 | 14.07 | 6.22 |
November | 0.203301E+10 | 2907.42 | 03-NOV-14:00 | 17.80 | 10.65 | 0.522332E+09 | 835.58 | 03-NOV-13:00 | 17.80 | 10.65 |
December | 0.110762E+10 | 2400.36 | 29-DEC-10:50 | 3.22 | 0.77 | 0.463728E+09 | 727.89 | 20-DEC-14:30 | 9.15 | 5.46 |
Annual Sum or Average | 0.490094E+11 | 0.683038E+10 | ||||||||
Minimum of Months | 0.717219E+09 | 1954.93 | 3.13 | -0.4 | 0.433828E+09 | 705.65 | 7.80 | 2.25 | ||
Maximum of Months | 0.856411E+10 | 12126.14 | 26.20 | 23.65 | 0.688992E+09 | 845.65 | 26.20 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.663658E+09 | 2026.49 | 27-JAN-09:40 | 4.03 | 1.32 | 0.225008E+09 | 471.78 | 27-JAN-09:39 | 4.03 | 1.32 |
February | 0.835909E+09 | 2229.68 | 22-FEB-17:20 | 3.13 | -0.4 | 0.208548E+09 | 498.80 | 22-FEB-09:50 | 0.50 | -3.0 |
March | 0.220615E+10 | 5645.11 | 29-MAR-09:00 | 5.60 | 2.97 | 0.279622E+09 | 525.77 | 22-MAR-08:50 | -1.3 | -4.9 |
April | 0.320341E+10 | 8834.28 | 28-APR-08:30 | 15.25 | 8.68 | 0.269509E+09 | 522.10 | 04-APR-08:39 | 8.67 | 4.31 |
May | 0.521994E+10 | 18163.79 | 29-MAY-08:52 | 26.10 | 16.70 | 0.305945E+09 | 521.24 | 30-MAY-08:00 | 26.10 | 16.89 |
June | 0.636610E+10 | 14512.90 | 25-JUN-09:43 | 26.02 | 23.32 | 0.311398E+09 | 521.24 | 22-JUN-14:20 | 30.20 | 17.78 |
July | 0.723830E+10 | 18657.94 | 02-JUL-08:32 | 25.20 | 21.53 | 0.291791E+09 | 521.20 | 11-JUL-14:50 | 28.40 | 17.61 |
August | 0.813753E+10 | 17158.02 | 13-AUG-08:13 | 26.67 | 19.13 | 0.326390E+09 | 521.23 | 23-AUG-12:30 | 25.85 | 16.60 |
September | 0.525876E+10 | 18080.89 | 04-SEP-08:42 | 23.72 | 18.56 | 0.285127E+09 | 521.22 | 19-SEP-10:09 | 20.00 | 15.37 |
October | 0.387757E+10 | 7380.65 | 05-OCT-08:40 | 18.53 | 16.65 | 0.289841E+09 | 521.22 | 16-OCT-08:00 | 16.70 | 14.03 |
November | 0.180855E+10 | 3257.84 | 03-NOV-09:00 | 12.80 | 8.07 | 0.249428E+09 | 521.19 | 03-NOV-10:39 | 14.43 | 8.86 |
December | 0.102448E+10 | 2766.33 | 21-DEC-09:30 | 0.30 | -2.5 | 0.221975E+09 | 491.18 | 20-DEC-09:39 | 7.57 | 4.72 |
Annual Sum or Average | 0.458404E+11 | 0.326458E+10 | ||||||||
Minimum of Months | 0.663658E+09 | 2026.49 | 0.30 | -2.5 | 0.208548E+09 | 471.78 | -1.3 | -4.9 | ||
Maximum of Months | 0.813753E+10 | 18657.94 | 26.67 | 23.32 | 0.326390E+09 | 525.77 | 30.20 | 17.78 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241814E+10 | 9472.28 | 17-JAN-14:00 | 11.10 | 5.13 | 0.534594E+09 | 877.68 | 19-JAN-14:09 | 9.32 | 3.66 |
February | 0.273994E+10 | 9906.75 | 22-FEB-13:20 | 4.27 | -0.9 | 0.501340E+09 | 911.41 | 22-FEB-14:09 | 4.90 | -0.5 |
March | 0.448609E+10 | 11197.88 | 01-MAR-13:40 | 13.90 | 6.18 | 0.626212E+09 | 929.99 | 01-MAR-14:09 | 13.62 | 5.83 |
April | 0.434869E+10 | 11062.19 | 07-APR-12:30 | 26.15 | 15.88 | 0.573324E+09 | 845.65 | 10-APR-13:09 | 20.10 | 10.08 |
May | 0.580543E+10 | 10848.71 | 31-MAY-05:02 | 16.38 | 14.98 | 0.649709E+09 | 845.68 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.774221E+10 | 12497.18 | 24-JUN-05:02 | 21.78 | 21.25 | 0.659197E+09 | 845.65 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.902928E+10 | 13759.64 | 10-JUL-03:02 | 26.10 | 21.75 | 0.614924E+09 | 845.62 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.107925E+11 | 15350.13 | 13-AUG-12:53 | 31.10 | 19.61 | 0.691747E+09 | 957.49 | 30-AUG-13:39 | 28.33 | 15.51 |
September | 0.872512E+10 | 16364.39 | 04-SEP-12:42 | 26.10 | 18.21 | 0.614160E+09 | 986.62 | 28-SEP-13:30 | 23.35 | 13.51 |
October | 0.876817E+10 | 15982.29 | 22-OCT-12:23 | 21.65 | 16.56 | 0.640458E+09 | 1004.66 | 30-OCT-13:39 | 15.93 | 9.65 |
November | 0.439455E+10 | 12499.35 | 02-NOV-13:30 | 15.85 | 8.44 | 0.589948E+09 | 994.87 | 02-NOV-13:20 | 15.77 | 8.35 |
December | 0.312147E+10 | 12484.17 | 17-DEC-12:43 | 12.20 | 4.85 | 0.540604E+09 | 908.35 | 21-DEC-14:09 | 3.30 | -1.3 |
Annual Sum or Average | 0.723716E+11 | 0.723622E+10 | ||||||||
Minimum of Months | 0.241814E+10 | 9472.28 | 4.27 | -0.9 | 0.501340E+09 | 845.62 | 3.30 | -1.3 | ||
Maximum of Months | 0.107925E+11 | 16364.39 | 31.10 | 21.75 | 0.691747E+09 | 1004.66 | 28.33 | 16.94 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.913957E+09 | 2662.46 | 20-JAN-16:00 | 7.20 | 3.79 | 0.312687E+09 | 521.18 | 20-JAN-16:40 | 6.13 | 3.40 |
February | 0.104331E+10 | 4037.02 | 22-FEB-16:30 | 3.85 | -0.4 | 0.289055E+09 | 538.65 | 24-FEB-14:00 | 8.30 | 2.25 |
March | 0.267977E+10 | 7810.27 | 29-MAR-16:00 | 7.20 | 4.87 | 0.378297E+09 | 544.94 | 28-MAR-13:39 | 13.50 | 8.49 |
April | 0.364867E+10 | 12481.04 | 09-APR-16:23 | 16.65 | 13.96 | 0.363811E+09 | 544.95 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.529679E+10 | 12506.51 | 21-MAY-15:23 | 20.00 | 13.21 | 0.416425E+09 | 544.98 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.716072E+10 | 17885.68 | 18-JUN-16:12 | 25.40 | 22.05 | 0.425226E+09 | 544.96 | 22-JUN-09:09 | 25.68 | 16.94 |
July | 0.786305E+10 | 19267.66 | 04-JUL-16:21 | 25.55 | 18.10 | 0.396559E+09 | 544.94 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.934298E+10 | 17950.74 | 13-AUG-16:12 | 29.80 | 20.55 | 0.445389E+09 | 544.97 | 08-AUG-13:50 | 26.20 | 17.18 |
September | 0.558163E+10 | 17580.90 | 10-SEP-16:12 | 23.13 | 12.79 | 0.388324E+09 | 544.96 | 11-SEP-13:09 | 20.60 | 11.99 |
October | 0.436691E+10 | 9976.13 | 04-OCT-15:30 | 23.35 | 19.11 | 0.391081E+09 | 544.94 | 19-OCT-13:00 | 15.60 | 10.52 |
November | 0.196656E+10 | 5509.29 | 03-NOV-15:30 | 16.10 | 10.63 | 0.341447E+09 | 544.95 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.128551E+10 | 2431.32 | 08-DEC-15:40 | 6.30 | 2.03 | 0.308189E+09 | 521.30 | 18-DEC-14:00 | 6.10 | 2.60 |
Annual Sum or Average | 0.511499E+11 | 0.445649E+10 | ||||||||
Minimum of Months | 0.913957E+09 | 2431.32 | 3.85 | -0.4 | 0.289055E+09 | 521.18 | 6.10 | 2.25 | ||
Maximum of Months | 0.934298E+10 | 19267.66 | 29.80 | 22.05 | 0.445389E+09 | 544.98 | 26.60 | 17.18 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.341046E+09 | 1761.53 | 20-JAN-16:10 | 6.93 | 3.70 | 0.465425E+09 | 672.13 | 20-JAN-14:00 | 7.80 | 3.96 |
February | 0.334675E+09 | 1774.95 | 17-FEB-16:10 | 6.02 | 1.70 | 0.423384E+09 | 677.06 | 17-FEB-14:00 | 6.10 | 1.73 |
March | 0.147598E+10 | 3036.30 | 27-MAR-16:00 | 22.20 | 16.33 | 0.537829E+09 | 827.68 | 28-MAR-13:00 | 13.30 | 8.40 |
April | 0.268671E+10 | 6027.80 | 07-APR-15:20 | 25.60 | 15.99 | 0.531365E+09 | 845.63 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.511293E+10 | 9542.30 | 30-MAY-05:03 | 18.17 | 14.30 | 0.633626E+09 | 845.66 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.768321E+10 | 11937.35 | 24-JUN-05:02 | 21.78 | 21.25 | 0.657622E+09 | 847.23 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.902509E+10 | 13566.40 | 09-JUL-16:12 | 27.03 | 24.29 | 0.614507E+09 | 845.60 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.915466E+10 | 12385.19 | 01-AUG-05:02 | 23.90 | 20.76 | 0.688314E+09 | 845.64 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.564555E+10 | 12288.33 | 02-SEP-05:02 | 22.12 | 16.29 | 0.595622E+09 | 845.63 | 11-SEP-13:09 | 20.60 | 11.99 |
October | 0.356364E+10 | 5817.71 | 04-OCT-14:00 | 24.40 | 18.94 | 0.576035E+09 | 845.59 | 16-OCT-13:20 | 19.07 | 15.96 |
November | 0.135303E+10 | 2811.78 | 03-NOV-14:00 | 17.80 | 10.65 | 0.489299E+09 | 804.10 | 03-NOV-13:00 | 17.80 | 10.65 |
December | 0.358736E+09 | 1738.81 | 20-DEC-14:20 | 9.43 | 5.61 | 0.449477E+09 | 674.33 | 20-DEC-14:30 | 9.15 | 5.46 |
Annual Sum or Average | 0.467353E+11 | 0.666250E+10 | ||||||||
Minimum of Months | 0.334675E+09 | 1738.81 | 6.02 | 1.70 | 0.423384E+09 | 672.13 | 6.10 | 1.73 | ||
Maximum of Months | 0.915466E+10 | 13566.40 | 27.03 | 24.29 | 0.688314E+09 | 847.23 | 29.43 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.362465E+09 | 1587.67 | 19-JAN-09:35 | 6.67 | 3.81 | 0.301650E+09 | 445.80 | 19-JAN-10:09 | 7.80 | 4.24 |
February | 0.461176E+09 | 1650.80 | 17-FEB-09:40 | 3.87 | 0.10 | 0.275725E+09 | 460.61 | 17-FEB-10:09 | 4.68 | 0.59 |
March | 0.166048E+10 | 4161.90 | 29-MAR-09:20 | 5.97 | 3.11 | 0.366499E+09 | 544.95 | 29-MAR-09:00 | 6.70 | 3.38 |
April | 0.284278E+10 | 8212.37 | 28-APR-08:40 | 15.53 | 8.73 | 0.359120E+09 | 544.96 | 26-APR-09:00 | 16.10 | 12.58 |
May | 0.518059E+10 | 18406.01 | 29-MAY-08:22 | 25.00 | 16.72 | 0.412249E+09 | 545.00 | 25-MAY-09:09 | 16.78 | 13.44 |
June | 0.673011E+10 | 15759.88 | 25-JUN-09:43 | 26.02 | 23.32 | 0.423747E+09 | 546.15 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.782443E+10 | 18451.23 | 09-JUL-09:32 | 29.43 | 25.36 | 0.396077E+09 | 544.94 | 11-JUL-09:30 | 24.45 | 16.70 |
August | 0.864411E+10 | 17462.82 | 13-AUG-08:13 | 26.67 | 19.13 | 0.444407E+09 | 544.96 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.526015E+10 | 17957.29 | 04-SEP-08:51 | 23.90 | 18.52 | 0.385917E+09 | 544.98 | 19-SEP-09:09 | 18.58 | 14.05 |
October | 0.348296E+10 | 6743.47 | 05-OCT-08:50 | 18.72 | 16.70 | 0.387058E+09 | 544.98 | 16-OCT-09:09 | 16.88 | 14.10 |
November | 0.129604E+10 | 2484.25 | 03-NOV-14:00 | 17.80 | 10.65 | 0.320748E+09 | 531.13 | 03-NOV-09:39 | 13.13 | 8.28 |
December | 0.466494E+09 | 1621.09 | 20-DEC-09:25 | 7.20 | 4.57 | 0.290833E+09 | 447.76 | 20-DEC-10:09 | 8.40 | 5.02 |
Annual Sum or Average | 0.442118E+11 | 0.436403E+10 | ||||||||
Minimum of Months | 0.362465E+09 | 1587.67 | 3.87 | 0.10 | 0.275725E+09 | 445.80 | 4.68 | 0.59 | ||
Maximum of Months | 0.864411E+10 | 18451.23 | 29.43 | 25.36 | 0.444407E+09 | 546.15 | 29.43 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.164684E+10 | 9923.15 | 19-JAN-13:40 | 9.40 | 3.84 | 0.517271E+09 | 845.64 | 30-JAN-14:39 | 2.80 | -0.8 |
February | 0.194455E+10 | 10096.17 | 02-FEB-14:15 | 5.40 | -0.8 | 0.476822E+09 | 849.26 | 02-FEB-14:20 | 5.40 | -0.8 |
March | 0.355455E+10 | 11881.10 | 01-MAR-13:40 | 13.90 | 6.18 | 0.596050E+09 | 883.70 | 01-MAR-14:09 | 13.62 | 5.83 |
April | 0.382006E+10 | 11783.63 | 07-APR-12:40 | 26.33 | 16.04 | 0.551533E+09 | 845.67 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.572122E+10 | 11010.30 | 30-MAY-05:03 | 18.17 | 14.30 | 0.636450E+09 | 845.69 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.814055E+10 | 13507.92 | 24-JUN-05:02 | 21.78 | 21.25 | 0.657683E+09 | 847.39 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.974852E+10 | 17120.22 | 30-JUL-14:22 | 26.40 | 23.20 | 0.614871E+09 | 845.62 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.114146E+11 | 17451.34 | 13-AUG-12:53 | 31.10 | 19.61 | 0.690430E+09 | 921.46 | 30-AUG-13:39 | 28.33 | 15.51 |
September | 0.865089E+10 | 17915.46 | 04-SEP-12:51 | 26.10 | 18.29 | 0.606414E+09 | 954.71 | 28-SEP-13:30 | 23.35 | 13.51 |
October | 0.795425E+10 | 17555.08 | 22-OCT-12:32 | 21.83 | 16.68 | 0.618147E+09 | 944.94 | 04-OCT-13:30 | 24.70 | 18.74 |
November | 0.328674E+10 | 13087.42 | 02-NOV-13:30 | 15.85 | 8.44 | 0.555759E+09 | 927.84 | 02-NOV-13:30 | 15.85 | 8.44 |
December | 0.195857E+10 | 9693.49 | 21-DEC-13:30 | 3.05 | -1.4 | 0.509743E+09 | 845.64 | 14-DEC-14:09 | 5.10 | 1.44 |
Annual Sum or Average | 0.678413E+11 | 0.703117E+10 | ||||||||
Minimum of Months | 0.164684E+10 | 9693.49 | 3.05 | -1.4 | 0.476822E+09 | 845.62 | 2.80 | -0.8 | ||
Maximum of Months | 0.114146E+11 | 17915.46 | 31.10 | 23.20 | 0.690430E+09 | 954.71 | 29.43 | 18.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.597510E+09 | 2214.67 | 20-JAN-16:10 | 6.93 | 3.70 | 0.306324E+09 | 517.91 | 20-JAN-16:19 | 6.67 | 3.60 |
February | 0.685640E+09 | 3367.67 | 22-FEB-16:30 | 3.85 | -0.4 | 0.281938E+09 | 521.19 | 22-FEB-16:00 | 3.30 | -0.4 |
March | 0.220891E+10 | 7567.78 | 29-MAR-16:00 | 7.20 | 4.87 | 0.360724E+09 | 544.93 | 02-MAR-14:00 | 12.80 | 10.91 |
April | 0.339334E+10 | 12585.71 | 09-APR-16:23 | 16.65 | 13.96 | 0.348031E+09 | 544.96 | 07-APR-13:09 | 26.60 | 16.30 |
May | 0.537068E+10 | 14238.86 | 21-MAY-15:32 | 19.63 | 13.01 | 0.405650E+09 | 544.98 | 15-MAY-13:00 | 17.80 | 11.34 |
June | 0.748651E+10 | 19244.91 | 18-JUN-16:12 | 25.40 | 22.05 | 0.423168E+09 | 546.15 | 22-JUN-13:39 | 29.43 | 17.53 |
July | 0.840169E+10 | 20796.72 | 04-JUL-16:21 | 25.55 | 18.10 | 0.396047E+09 | 544.94 | 11-JUL-09:39 | 24.63 | 16.82 |
August | 0.972811E+10 | 19387.22 | 20-AUG-15:42 | 25.97 | 16.58 | 0.444553E+09 | 544.96 | 23-AUG-13:09 | 25.60 | 17.05 |
September | 0.563109E+10 | 19008.05 | 04-SEP-16:51 | 24.40 | 18.65 | 0.381986E+09 | 544.96 | 11-SEP-13:09 | 20.60 | 11.99 |
October | 0.407541E+10 | 11480.24 | 15-OCT-16:20 | 19.03 | 12.03 | 0.374924E+09 | 544.93 | 12-OCT-13:09 | 20.10 | 16.59 |
November | 0.152640E+10 | 5102.85 | 03-NOV-15:40 | 15.73 | 10.51 | 0.321667E+09 | 542.25 | 08-NOV-14:00 | 13.30 | 11.09 |
December | 0.694310E+09 | 2124.23 | 08-DEC-15:50 | 6.20 | 1.94 | 0.296617E+09 | 501.96 | 08-DEC-15:00 | 6.10 | 1.86 |
Annual Sum or Average | 0.497996E+11 | 0.434163E+10 | ||||||||
Minimum of Months | 0.597510E+09 | 2124.23 | 3.85 | -0.4 | 0.281938E+09 | 501.96 | 3.30 | -0.4 | ||
Maximum of Months | 0.972811E+10 | 20796.72 | 25.97 | 22.05 | 0.444553E+09 | 546.15 | 29.43 | 17.53 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.884467E+09 | 3981.97 | 14-JAN-06:01 | -7.8 | -8.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.109075E+10 | 3849.55 | 21-FEB-06:09 | 2.30 | 1.56 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.297009E+10 | 4891.47 | 27-MAR-05:04 | 7.88 | 7.88 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.436926E+10 | 6504.36 | 10-APR-05:13 | 15.20 | 13.75 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.514514E+10 | 7843.53 | 30-MAY-13:50 | 29.50 | 17.08 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.686923E+10 | 8173.55 | 27-JUN-05:01 | 21.20 | 21.12 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.775029E+10 | 8624.47 | 13-JUL-05:01 | 21.97 | 21.02 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.888811E+10 | 9035.14 | 15-AUG-05:01 | 24.40 | 22.15 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.601104E+10 | 8716.79 | 05-SEP-05:13 | 20.60 | 18.00 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.541229E+10 | 7605.42 | 23-OCT-05:13 | 13.13 | 11.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.326157E+10 | 6516.73 | 13-NOV-06:15 | 5.77 | 4.70 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.240413E+10 | 3934.40 | 26-DEC-06:13 | 6.30 | 5.39 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.550564E+11 | 0.00 | ||||||||
Minimum of Months | 0.884467E+09 | 3849.55 | -7.8 | -8.5 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.888811E+10 | 9035.14 | 29.50 | 22.15 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218990E+09 | 4394.05 | 14-JAN-04:01 | -6.8 | -7.4 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.329150E+09 | 6433.38 | 13-FEB-04:11 | -8.9 | -10.8 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.824522E+09 | 3741.85 | 17-MAR-04:01 | -1.6 | -2.3 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.183103E+10 | 3412.38 | 10-APR-05:10 | 15.10 | 13.73 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.338783E+10 | 5550.75 | 31-MAY-05:04 | 16.38 | 14.98 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.522719E+10 | 6131.94 | 26-JUN-05:01 | 20.78 | 17.10 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.605126E+10 | 9099.58 | 25-JUL-05:01 | 23.90 | 23.41 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.680430E+10 | 6664.64 | 07-AUG-05:03 | 19.40 | 16.74 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.450442E+10 | 5600.78 | 07-SEP-05:10 | 22.20 | 21.37 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.300856E+10 | 3825.00 | 05-OCT-15:40 | 21.87 | 19.17 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.956441E+09 | 5308.64 | 24-NOV-05:01 | -4.0 | -5.9 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.445467E+09 | 4321.01 | 22-DEC-06:02 | -4.1 | -6.4 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.335892E+11 | 0.00 | ||||||||
Minimum of Months | 0.218990E+09 | 3412.38 | -8.9 | -10.8 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.680430E+10 | 9099.58 | 23.90 | 23.41 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 708319.59 | 308.68 | 19-JAN-13:00 | 9.40 | 4.16 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 44681493.48 | 1357.46 | 17-FEB-13:10 | 6.70 | 1.65 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.964787E+09 | 5972.90 | 03-MAR-14:30 | 15.00 | 8.49 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.268640E+10 | 11908.94 | 07-APR-13:20 | 26.50 | 16.23 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.602714E+10 | 17437.29 | 30-MAY-13:10 | 29.90 | 17.80 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.968060E+10 | 18178.94 | 19-JUN-13:50 | 34.50 | 23.72 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.116345E+11 | 16990.18 | 07-JUL-14:00 | 32.80 | 23.70 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.124532E+11 | 17113.88 | 30-AUG-13:25 | 28.05 | 15.53 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.651122E+10 | 16592.13 | 01-SEP-14:50 | 30.68 | 17.42 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.348154E+10 | 10242.72 | 04-OCT-14:20 | 24.23 | 19.00 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.391720E+09 | 4189.78 | 04-NOV-13:00 | 17.80 | 12.72 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 2220793.77 | 437.87 | 20-DEC-12:40 | 9.23 | 5.44 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.538788E+11 | 0.00 | ||||||||
Minimum of Months | 708319.59 | 308.68 | 6.70 | 1.65 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.124532E+11 | 18178.94 | 34.50 | 23.72 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.275615E+10 | 1818.27 | 20-JAN-16:30 | 6.40 | 3.50 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.748061E+10 | 3882.72 | 14-FEB-17:00 | 0.00 | -3.8 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.140924E+11 | 5918.36 | 26-MAR-17:30 | 10.30 | 9.37 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.185459E+11 | 7488.15 | 23-APR-17:50 | 12.38 | 8.82 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.424716E+10 | 2072.26 | 01-MAY-00:05 | 10.33 | 9.91 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.918675E+10 | 4016.46 | 18-JUN-18:08 | 23.22 | 21.39 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.145311E+11 | 5932.40 | 04-JUL-18:05 | 23.72 | 18.51 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.178905E+11 | 7203.10 | 08-AUG-04:53 | 15.00 | 12.46 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.424152E+10 | 4138.73 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.937683E+10 | 4078.79 | 15-OCT-16:33 | 18.67 | 11.87 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.136308E+11 | 5704.12 | 06-NOV-16:10 | 13.03 | 7.65 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.189928E+11 | 7374.39 | 18-DEC-15:50 | 5.68 | 2.50 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.134973E+12 | 0.00 | ||||||||
Minimum of Months | 0.275615E+10 | 1818.27 | 0.00 | -3.8 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.189928E+11 | 7488.15 | 23.72 | 21.39 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.691352E+09 | 1533.17 | 20-JAN-16:40 | 6.13 | 3.40 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.515730E+10 | 3492.99 | 22-FEB-17:00 | 3.30 | -0.4 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.119114E+11 | 5521.77 | 29-MAR-17:20 | 5.73 | 4.14 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.168289E+11 | 7087.95 | 12-APR-17:20 | 12.03 | 3.26 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.348937E+10 | 1874.21 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.853175E+10 | 3834.06 | 18-JUN-17:52 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.137941E+11 | 5647.11 | 12-JUL-18:20 | 25.40 | 21.22 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.170480E+11 | 6859.14 | 08-AUG-04:53 | 15.00 | 12.46 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.355937E+10 | 3891.24 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.813573E+10 | 3747.20 | 04-OCT-16:30 | 22.25 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.112966E+11 | 5344.94 | 03-NOV-16:00 | 15.00 | 10.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.158780E+11 | 6960.77 | 21-DEC-16:10 | 2.62 | -2.0 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.116322E+12 | 0.00 | ||||||||
Minimum of Months | 0.691352E+09 | 1533.17 | 2.62 | -2.0 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.170480E+11 | 7087.95 | 25.40 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.254048E+09 | 1439.60 | 20-JAN-16:40 | 6.13 | 3.40 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.350310E+10 | 3374.88 | 02-FEB-17:00 | 2.80 | -2.7 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.105793E+11 | 5518.56 | 29-MAR-17:10 | 5.92 | 4.23 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.160203E+11 | 7182.47 | 12-APR-17:20 | 12.03 | 3.26 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.316999E+10 | 1968.83 | 30-MAY-18:00 | 22.80 | 16.84 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.853073E+10 | 4030.89 | 18-JUN-17:52 | 23.30 | 21.43 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.139031E+11 | 5804.19 | 04-JUL-17:58 | 23.90 | 18.52 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.172979E+11 | 6897.72 | 20-AUG-02:37 | 15.77 | 13.16 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.332779E+10 | 3467.29 | 01-SEP-00:03 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.732892E+10 | 3800.25 | 04-OCT-16:30 | 22.25 | 18.94 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.972188E+10 | 5320.66 | 03-NOV-16:00 | 15.00 | 10.24 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.138940E+11 | 6803.45 | 08-DEC-16:10 | 5.92 | 1.75 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.107531E+12 | 0.00 | ||||||||
Minimum of Months | 0.254048E+09 | 1439.60 | 2.80 | -2.7 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.172979E+11 | 7182.47 | 23.90 | 21.43 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236224E+12 | 352319.46 | 14-JAN-11:01 | -7.1 | -7.7 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.4 |
February | 0.433362E+12 | 410457.24 | 18-FEB-00:31 | 0.97 | -0.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.0 |
March | 0.726883E+12 | 408294.64 | 18-MAR-17:22 | 2.20 | 0.92 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.34 |
April | 0.941973E+12 | 388119.32 | 01-APR-11:52 | 4.40 | 3.92 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
May | 0.238410E+12 | 357428.02 | 02-MAY-04:51 | 8.30 | 5.26 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
June | 0.468080E+12 | 182023.73 | 20-JUN-16:00 | 25.60 | 17.02 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.58 |
July | 0.729879E+12 | 274164.08 | 06-JUL-16:00 | 28.30 | 24.26 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.28 |
August | 0.976558E+12 | 368526.43 | 16-AUG-21:13 | 26.50 | 25.09 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
September | 0.234274E+12 | 105179.54 | 01-SEP-00:08 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
October | 0.486480E+12 | 352731.47 | 28-OCT-17:35 | 8.67 | 2.85 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
November | 0.707114E+12 | 408063.95 | 21-NOV-22:22 | -0.3 | -2.1 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
December | 0.975066E+12 | 390185.30 | 05-DEC-04:54 | 6.10 | 4.76 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.85 |
Annual Sum or Average | 0.715430E+13 | 0.00 | ||||||||
Minimum of Months | 0.234274E+12 | 105179.54 | -7.1 | -7.7 | 0.00 | 0.00 | -9.6 | -11.4 | ||
Maximum of Months | 0.976558E+12 | 410457.24 | 28.30 | 25.09 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.289707E+09 | 135572.34 | 14-JAN-05:49 | -7.7 |
February | 0.302757E+09 | 134422.35 | 08-FEB-05:28 | -6.7 |
March | 0.238593E+09 | 122322.27 | 14-MAR-04:00 | -1.7 |
April | 0.327901E+09 | 119424.41 | 15-APR-03:20 | 6.30 |
May | 0.721913E+09 | 122598.17 | 29-MAY-09:30 | 26.40 |
June | 0.832316E+09 | 129142.16 | 24-JUN-03:50 | 22.20 |
July | 0.110373E+10 | 128957.05 | 25-JUL-03:50 | 23.40 |
August | 0.114262E+10 | 129529.33 | 04-AUG-03:50 | 23.90 |
September | 0.112760E+10 | 130463.77 | 08-SEP-03:50 | 21.78 |
October | 0.127417E+10 | 124307.74 | 06-OCT-03:47 | 19.40 |
November | 0.124724E+10 | 124956.14 | 22-NOV-04:47 | -2.1 |
December | 0.366728E+09 | 123859.73 | 02-DEC-04:50 | 1.10 |
Annual Sum or Average | 0.897527E+10 | |||
Minimum of Months | 0.238593E+09 | 119424.41 | -7.7 | |
Maximum of Months | 0.127417E+10 | 135572.34 | 26.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.611002E+09 | 45350.79 | 02-JAN-04:01 | -11.8 |
February | 16688895.79 | 34099.56 | 06-FEB-06:01 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.627691E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 0.611002E+09 | 45350.79 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.323178E+10 | 78014.40 | 02-JAN-04:01 | -11.8 |
February | 0.211272E+10 | 75747.83 | 06-FEB-04:01 | -13.3 |
March | 0.327016E+09 | 68303.12 | 20-MAR-04:01 | -0.8 |
April | 47685397.38 | 65300.16 | 03-APR-04:01 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.705425E+09 | 70324.44 | 24-NOV-05:11 | -4.1 |
December | 0.823172E+09 | 71011.25 | 26-DEC-05:01 | 5.68 |
Annual Sum or Average | 0.724780E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.323178E+10 | 78014.40 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 36338612.35 | 9174.56 | 02-JAN-05:01 | -12.1 |
February | 45623733.44 | 9443.18 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 81962345.79 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 45623733.44 | 9443.18 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42411275.73 | 7509.10 | 02-JAN-05:01 | -12.1 |
February | 35971222.19 | 7885.90 | 06-FEB-05:01 | -13.2 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 49030.69 | 817.18 | 22-NOV-06:01 | -2.2 |
December | 32472.61 | 432.97 | 07-DEC-06:01 | 0.10 |
Annual Sum or Average | 78464001.21 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 42411275.73 | 7885.90 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166015E+09 | 11954.62 | 02-JAN-05:01 | -12.1 |
February | 0.115821E+09 | 12032.58 | 06-FEB-05:01 | -13.2 |
March | 744291.63 | 10471.56 | 13-MAR-05:01 | -0.6 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 1187349.93 | 9297.83 | 22-NOV-06:01 | -2.2 |
December | 1205246.52 | 8212.93 | 11-DEC-06:01 | 1.70 |
Annual Sum or Average | 0.284973E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.2 | |
Maximum of Months | 0.166015E+09 | 12032.58 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 5109781.29 | 4994.55 | 02-JAN-06:01 | -11.7 |
February | 2160957.87 | 4903.16 | 06-FEB-06:01 | -12.9 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 7270739.17 | |||
Minimum of Months | 0.00 | 0.00 | -12.9 | |
Maximum of Months | 5109781.29 | 4994.55 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.284247E+10 | 12387.83 | 02-JAN-01:22 | -11.4 |
February | 0.196603E+10 | 11897.17 | 06-FEB-01:11 | -13.3 |
March | 0.322332E+09 | 10492.22 | 13-MAR-04:01 | -0.1 |
April | 28106471.00 | 9627.01 | 03-APR-04:01 | 2.80 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 419645.53 | 2797.64 | 28-OCT-05:03 | 3.90 |
November | 0.363605E+09 | 10763.13 | 24-NOV-04:01 | -3.4 |
December | 0.871892E+09 | 11689.04 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.639486E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.284247E+10 | 12387.83 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173157E+10 | 15030.98 | 02-JAN-01:22 | -11.4 |
February | 0.101681E+10 | 14424.61 | 06-FEB-01:11 | -13.3 |
March | 0.179833E+09 | 12340.88 | 13-MAR-04:01 | -0.1 |
April | 18350181.20 | 11165.16 | 21-APR-05:01 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 89919.19 | 599.46 | 28-OCT-05:03 | 3.90 |
November | 0.207980E+09 | 12853.47 | 24-NOV-04:01 | -3.4 |
December | 0.530700E+09 | 12330.48 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.368534E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.173157E+10 | 15030.98 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.183491E+10 | 13819.12 | 02-JAN-01:22 | -11.4 |
February | 0.990648E+09 | 13139.74 | 06-FEB-01:11 | -13.3 |
March | 0.185910E+09 | 11471.89 | 13-MAR-04:01 | -0.1 |
April | 17683709.26 | 10540.99 | 21-APR-05:01 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.178539E+09 | 11494.08 | 24-NOV-05:01 | -4.0 |
December | 0.485134E+09 | 11541.29 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.369282E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.183491E+10 | 13819.12 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138358E+10 | 14760.61 | 02-JAN-01:22 | -11.4 |
February | 0.849191E+09 | 14133.03 | 06-FEB-01:11 | -13.3 |
March | 99819000.86 | 11817.73 | 13-MAR-04:01 | -0.1 |
April | 4159163.46 | 10675.92 | 21-APR-05:01 | 5.60 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.136930E+09 | 12126.77 | 24-NOV-05:01 | -4.0 |
December | 0.323287E+09 | 11889.30 | 07-DEC-05:01 | 0.00 |
Annual Sum or Average | 0.279697E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.138358E+10 | 14760.61 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.602598E+10 | 14092.91 | 02-JAN-01:22 | -11.4 |
February | 0.522783E+10 | 13760.66 | 05-FEB-20:02 | -10.1 |
March | 0.154034E+10 | 12649.51 | 13-MAR-03:01 | 0.50 |
April | 0.379272E+09 | 12232.93 | 03-APR-03:01 | 3.22 |
May | 6037892.85 | 10288.70 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.102825E+09 | 10607.68 | 28-OCT-04:03 | 4.32 |
November | 0.177114E+10 | 13081.23 | 23-NOV-23:13 | -3.0 |
December | 0.365468E+10 | 13777.10 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.187081E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.4 | |
Maximum of Months | 0.602598E+10 | 14092.91 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.361579E+10 | 16099.25 | 02-JAN-01:22 | -11.4 |
February | 0.283771E+10 | 15656.70 | 05-FEB-20:02 | -10.1 |
March | 0.789611E+09 | 14577.35 | 13-MAR-03:01 | 0.50 |
April | 0.215682E+09 | 13930.94 | 03-APR-03:01 | 3.22 |
May | 3027887.81 | 11795.88 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 47025936.80 | 12044.06 | 18-OCT-05:01 | 6.02 |
November | 0.979316E+09 | 14642.09 | 22-NOV-04:01 | -1.8 |
December | 0.211720E+10 | 15757.14 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.106054E+11 | |||
Minimum of Months | 0.00 | 0.00 | -11.4 | |
Maximum of Months | 0.361579E+10 | 16099.25 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.419634E+10 | 15915.38 | 02-JAN-01:22 | -11.4 |
February | 0.318434E+10 | 15404.48 | 06-FEB-01:22 | -13.3 |
March | 0.106217E+10 | 14377.22 | 13-MAR-03:01 | 0.50 |
April | 0.311454E+09 | 13615.78 | 03-APR-03:01 | 3.22 |
May | 6085470.93 | 11696.56 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 27233966.84 | 11787.32 | 27-OCT-05:01 | 6.02 |
November | 0.104756E+10 | 14412.19 | 24-NOV-04:01 | -3.4 |
December | 0.235300E+10 | 15494.85 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.121882E+11 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.419634E+10 | 15915.38 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.298609E+10 | 17254.55 | 02-JAN-01:22 | -11.4 |
February | 0.229516E+10 | 16654.65 | 06-FEB-04:01 | -13.3 |
March | 0.539560E+09 | 15611.97 | 13-MAR-03:01 | 0.50 |
April | 0.113808E+09 | 13938.27 | 03-APR-04:01 | 2.80 |
May | 193468.28 | 1599.01 | 01-MAY-05:02 | 6.28 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 19925891.73 | 12583.69 | 27-OCT-05:01 | 6.02 |
November | 0.707667E+09 | 15690.30 | 24-NOV-04:01 | -3.4 |
December | 0.144278E+10 | 16621.10 | 31-DEC-21:12 | -6.9 |
Annual Sum or Average | 0.810519E+10 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.298609E+10 | 17254.55 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469820E+09 | 12309.40 | 03-JAN-06:01 | 4.27 |
February | 0.296083E+09 | 11012.68 | 27-FEB-05:01 | -0.8 |
March | 84256599.46 | 12293.44 | 13-MAR-03:01 | 0.50 |
April | 0.126466E+09 | 12507.63 | 24-APR-03:01 | 7.88 |
May | 56321785.62 | 9826.87 | 01-MAY-03:02 | 7.45 |
June | 61439902.01 | 8867.29 | 06-JUN-03:01 | 17.20 |
July | 74399633.43 | 8016.36 | 01-JUL-03:01 | 20.00 |
August | 41967657.89 | 4930.75 | 13-AUG-15:21 | 30.30 |
September | 47502878.32 | 8915.43 | 14-SEP-03:01 | 22.20 |
October | 76079057.12 | 10478.86 | 23-OCT-03:01 | 14.13 |
November | 79655472.12 | 12259.74 | 27-NOV-04:01 | 6.60 |
December | 0.110171E+09 | 13049.80 | 26-DEC-04:01 | 5.60 |
Annual Sum or Average | 0.152416E+10 | |||
Minimum of Months | 41967657.89 | 4930.75 | -0.8 | |
Maximum of Months | 0.469820E+09 | 13049.80 | 30.30 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347602E+10 | 15103.15 | 02-JAN-06:12 | -11.7 |
February | 0.184305E+10 | 9776.31 | 09-FEB-10:55 | -4.4 |
March | 0.795728E+09 | 8203.07 | 28-MAR-05:01 | 9.50 |
April | 0.176254E+09 | 8069.22 | 18-APR-05:01 | 7.12 |
May | 40955783.98 | 8106.01 | 03-MAY-04:11 | 11.70 |
June | 30851854.57 | 7413.38 | 12-JUN-03:01 | 18.90 |
July | 30242337.98 | 7588.48 | 07-JUL-03:01 | 26.10 |
August | 24626021.92 | 7549.60 | 17-AUG-03:01 | 25.50 |
September | 33105106.30 | 7372.13 | 25-SEP-04:01 | 14.40 |
October | 45300420.34 | 7538.18 | 18-OCT-05:01 | 6.02 |
November | 0.559870E+09 | 8018.70 | 01-NOV-05:01 | 6.10 |
December | 0.105920E+10 | 6509.52 | 20-DEC-06:01 | 3.53 |
Annual Sum or Average | 0.811521E+10 | |||
Minimum of Months | 24626021.92 | 6509.52 | -11.7 | |
Maximum of Months | 0.347602E+10 | 15103.15 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.869721E+10 | 24617.28 | 02-JAN-05:09 | -12.1 |
February | 0.718882E+10 | 26288.83 | 06-FEB-05:10 | -13.2 |
March | 0.300593E+10 | 16267.00 | 13-MAR-05:02 | -0.6 |
April | 0.123006E+10 | 16166.92 | 11-APR-05:01 | 6.10 |
May | 0.215057E+09 | 16146.73 | 15-MAY-05:01 | 8.07 |
June | 59777862.52 | 13607.44 | 03-JUN-05:02 | 13.48 |
July | 33741207.53 | 9277.99 | 01-JUL-05:01 | 20.10 |
August | 48301830.77 | 12498.49 | 26-AUG-05:01 | 16.38 |
September | 0.133688E+09 | 15010.76 | 29-SEP-05:01 | 11.78 |
October | 0.699385E+09 | 17271.86 | 17-OCT-05:01 | 10.10 |
November | 0.346098E+10 | 18797.78 | 24-NOV-06:03 | -4.4 |
December | 0.607697E+10 | 16938.94 | 11-DEC-06:13 | 1.70 |
Annual Sum or Average | 0.308499E+11 | |||
Minimum of Months | 33741207.53 | 9277.99 | -13.2 | |
Maximum of Months | 0.869721E+10 | 26288.83 | 20.10 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -9.6 | |
Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371476E+09 | 519.90 | 02-JAN-23:40 | -4.1 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.371476E+09 | |||
Minimum of Months | 0.00 | 0.00 | -4.1 | |
Maximum of Months | 0.371476E+09 | 519.90 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.827035E+09 | 548.04 | 16-JAN-17:40 | 4.07 |
February | 43977804.69 | 508.29 | 06-FEB-00:17 | -13.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.33 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.871013E+09 | |||
Minimum of Months | 0.00 | 0.00 | -13.3 | |
Maximum of Months | 0.827035E+09 | 548.04 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573907E+09 | 61159.65 | 13-JAN-21:51 | -3.0 |
February | 58286483.08 | 37394.72 | 22-FEB-01:01 | 2.70 |
March | 338795.56 | 3531.79 | 18-MAR-17:21 | 2.20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.27 |
May | 48840803.21 | 42187.41 | 16-MAY-03:07 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 23.90 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 23.43 |
October | 3911528.99 | 29746.35 | 28-OCT-17:51 | 8.30 |
November | 439266.58 | 4905.23 | 21-NOV-22:21 | -0.3 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 |
Annual Sum or Average | 0.685724E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 0.573907E+09 | 61159.65 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.161705E+11 | 16792.34 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.146671E+11 | 16792.34 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.174151E+11 | 16792.34 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.155689E+11 | 16792.34 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.167928E+11 | 16792.34 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.167065E+11 | 16792.34 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.156551E+11 | 16792.34 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.174151E+11 | 16792.34 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.155689E+11 | 16792.34 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.161705E+11 | 16792.34 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.159772E+11 | 16792.34 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.156551E+11 | 16792.34 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.193763E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.146671E+11 | 16792.34 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.174151E+11 | 16792.34 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.145222E+11 | 15080.70 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.131721E+11 | 15080.70 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.156400E+11 | 15080.70 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.139820E+11 | 15080.70 | 03-APR-07:10 | 0.261233E+11 | 18128.59 | 03-APR-07:10 |
May | 0.150811E+11 | 15080.70 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.150037E+11 | 15080.70 | 01-JUN-07:10 | 0.270334E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.140594E+11 | 15080.70 | 03-JUL-07:10 | 0.266454E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.156400E+11 | 15080.70 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.139820E+11 | 15080.70 | 01-SEP-07:10 | 0.261233E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.145222E+11 | 15080.70 | 02-OCT-07:10 | 0.270551E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.143487E+11 | 15080.70 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.140594E+11 | 15080.70 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.174013E+12 | 0.321278E+12 | ||||
Minimum of Months | 0.131721E+11 | 15080.70 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.156400E+11 | 15080.70 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.145222E+11 | 15080.70 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.131721E+11 | 15080.70 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.156400E+11 | 15080.70 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.139820E+11 | 15080.70 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.150811E+11 | 15080.70 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.150037E+11 | 15080.70 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.140594E+11 | 15080.70 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.156400E+11 | 15080.70 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.139820E+11 | 15080.70 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.145222E+11 | 15080.70 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.143487E+11 | 15080.70 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.140594E+11 | 15080.70 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.174013E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.131721E+11 | 15080.70 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.156400E+11 | 15080.70 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.145222E+11 | 15080.70 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.131721E+11 | 15080.70 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.156400E+11 | 15080.70 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.139820E+11 | 15080.70 | 03-APR-07:10 | 0.261232E+11 | 18128.52 | 03-APR-07:10 |
May | 0.150811E+11 | 15080.70 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.150037E+11 | 15080.70 | 01-JUN-07:10 | 0.270332E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.140594E+11 | 15080.70 | 03-JUL-07:10 | 0.266453E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.156400E+11 | 15080.70 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.139820E+11 | 15080.70 | 01-SEP-07:10 | 0.261232E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.145222E+11 | 15080.70 | 02-OCT-07:10 | 0.270550E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.143487E+11 | 15080.70 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.140594E+11 | 15080.70 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.174013E+12 | 0.321277E+12 | ||||
Minimum of Months | 0.131721E+11 | 15080.70 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.156400E+11 | 15080.70 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.150030E+10 | 1893.53 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.132254E+10 | 1789.80 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.153368E+10 | 1587.51 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.135044E+10 | 1382.30 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.144349E+10 | 1382.30 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.142769E+10 | 1382.30 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.134242E+10 | 1382.30 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.150147E+10 | 1382.30 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.135970E+10 | 1488.53 | 27-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.143478E+10 | 1660.51 | 31-OCT-15:00 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.146660E+10 | 1893.53 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.146445E+10 | 1893.53 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.171476E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.132254E+10 | 1382.30 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.153368E+10 | 1893.53 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.963881E+09 | 1220.26 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.851241E+09 | 1161.20 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.988589E+09 | 1084.37 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.871191E+09 | 890.81 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.932132E+09 | 890.81 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.922128E+09 | 890.81 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.866859E+09 | 890.81 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.969135E+09 | 890.81 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.876691E+09 | 890.81 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.924330E+09 | 1076.38 | 31-OCT-15:00 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.944575E+09 | 1220.26 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.938561E+09 | 1220.26 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.110493E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.851241E+09 | 890.81 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.988589E+09 | 1220.26 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.148389E+10 | 1893.57 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.131272E+10 | 1782.47 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.153051E+10 | 1518.59 | 02-MAR-16:00 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.135141E+10 | 1382.33 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.144612E+10 | 1382.33 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.143082E+10 | 1382.33 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.134505E+10 | 1382.33 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.150331E+10 | 1382.33 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.135892E+10 | 1459.99 | 27-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.142918E+10 | 1627.93 | 31-OCT-15:00 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.145755E+10 | 1893.57 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.144320E+10 | 1893.57 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.170927E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.131272E+10 | 1382.33 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.153051E+10 | 1893.57 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.958871E+09 | 1220.26 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.847463E+09 | 1144.71 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.985797E+09 | 1013.95 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.870513E+09 | 924.47 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.930314E+09 | 890.81 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.920468E+09 | 890.81 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.865556E+09 | 890.81 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.967568E+09 | 906.01 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.875847E+09 | 990.16 | 27-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.921773E+09 | 1054.77 | 06-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.940124E+09 | 1220.26 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.934753E+09 | 1220.26 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.110190E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.847463E+09 | 890.81 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.985797E+09 | 1220.26 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.150196E+10 | 1893.53 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.132365E+10 | 1792.91 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.153413E+10 | 1596.50 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.135074E+10 | 1382.30 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.144369E+10 | 1382.30 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.142796E+10 | 1382.30 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.134269E+10 | 1382.30 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.150164E+10 | 1382.30 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.136015E+10 | 1500.19 | 27-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.143540E+10 | 1667.37 | 31-OCT-15:00 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.146755E+10 | 1893.53 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.146645E+10 | 1893.53 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.171560E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.132365E+10 | 1382.30 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.153413E+10 | 1893.53 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.964216E+09 | 1220.26 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.851490E+09 | 1161.68 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.988721E+09 | 1085.38 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.871287E+09 | 890.81 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.932201E+09 | 890.81 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.922217E+09 | 890.81 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.866943E+09 | 890.81 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.969222E+09 | 890.81 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.876815E+09 | 890.81 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.924530E+09 | 1077.51 | 31-OCT-15:00 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.944780E+09 | 1220.26 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.938933E+09 | 1220.26 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.110514E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.851490E+09 | 890.81 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.988721E+09 | 1220.26 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.148483E+10 | 1893.57 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.131330E+10 | 1785.89 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.153001E+10 | 1510.81 | 16-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.135173E+10 | 1382.33 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.144637E+10 | 1382.33 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.143118E+10 | 1382.33 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.134540E+10 | 1382.33 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.150355E+10 | 1382.33 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.135929E+10 | 1472.70 | 27-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.142953E+10 | 1636.38 | 31-OCT-15:00 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.145804E+10 | 1893.57 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.144413E+10 | 1893.57 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.170974E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.131330E+10 | 1382.33 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.153001E+10 | 1893.57 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.959207E+09 | 1220.26 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.847696E+09 | 1145.52 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.985933E+09 | 1015.50 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.870624E+09 | 926.28 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.930380E+09 | 890.81 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.920537E+09 | 890.81 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.865630E+09 | 890.81 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.967666E+09 | 908.29 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.875991E+09 | 991.86 | 27-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.921897E+09 | 1056.01 | 06-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.940309E+09 | 1220.26 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.935171E+09 | 1220.26 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.110210E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.847696E+09 | 890.81 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.985933E+09 | 1220.26 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.150194E+10 | 1893.53 | 02-JAN-16:40 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.132365E+10 | 1792.84 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.153412E+10 | 1596.41 | 02-MAR-16:00 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.135074E+10 | 1382.30 | 03-APR-07:10 | 0.328017E+10 | 2276.32 | 03-APR-07:10 |
May | 0.144369E+10 | 1382.30 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.142796E+10 | 1382.30 | 01-JUN-07:10 | 0.339445E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.134269E+10 | 1382.30 | 03-JUL-07:10 | 0.334573E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.150164E+10 | 1382.30 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.136015E+10 | 1499.85 | 27-SEP-07:10 | 0.328017E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.143540E+10 | 1667.15 | 31-OCT-15:00 | 0.339718E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.146754E+10 | 1893.53 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.146645E+10 | 1893.53 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.171560E+11 | 0.403414E+11 | ||||
Minimum of Months | 0.132365E+10 | 1382.30 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.153412E+10 | 1893.53 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.964211E+09 | 1220.26 | 02-JAN-16:40 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.851491E+09 | 1161.63 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.988721E+09 | 1085.31 | 02-MAR-16:00 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.871285E+09 | 890.81 | 03-APR-07:10 | 0.211387E+10 | 1466.95 | 03-APR-07:10 |
May | 0.932200E+09 | 890.81 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.922215E+09 | 890.81 | 01-JUN-07:10 | 0.218751E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.866941E+09 | 890.81 | 03-JUL-07:10 | 0.215612E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.969225E+09 | 890.81 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.876815E+09 | 890.81 | 01-SEP-07:10 | 0.211387E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.924536E+09 | 1077.37 | 31-OCT-15:00 | 0.218927E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.944777E+09 | 1220.26 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.938935E+09 | 1220.26 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.110514E+11 | 0.259975E+11 | ||||
Minimum of Months | 0.851491E+09 | 890.81 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.988721E+09 | 1220.26 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.148483E+10 | 1893.57 | 02-JAN-16:40 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.131330E+10 | 1785.79 | 15-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.153001E+10 | 1510.53 | 16-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.135172E+10 | 1382.33 | 03-APR-07:10 | 0.328022E+10 | 2276.35 | 03-APR-07:10 |
May | 0.144637E+10 | 1382.33 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.143117E+10 | 1382.33 | 01-JUN-07:10 | 0.339450E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.134539E+10 | 1382.33 | 03-JUL-07:10 | 0.334578E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.150355E+10 | 1382.33 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.135929E+10 | 1472.36 | 27-SEP-07:10 | 0.328022E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.142953E+10 | 1636.19 | 31-OCT-15:00 | 0.339723E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.145804E+10 | 1893.57 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.144413E+10 | 1893.57 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.170973E+11 | 0.403420E+11 | ||||
Minimum of Months | 0.131330E+10 | 1382.33 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.153001E+10 | 1893.57 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.959205E+09 | 1220.26 | 02-JAN-16:40 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.847699E+09 | 1145.47 | 15-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.985934E+09 | 1015.32 | 16-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.870624E+09 | 926.11 | 14-APR-07:10 | 0.211386E+10 | 1466.94 | 03-APR-07:10 |
May | 0.930381E+09 | 890.81 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.920536E+09 | 890.81 | 01-JUN-07:10 | 0.218750E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.865628E+09 | 890.81 | 03-JUL-07:10 | 0.215610E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.967669E+09 | 908.00 | 16-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.875991E+09 | 991.65 | 27-SEP-07:10 | 0.211386E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.921897E+09 | 1055.85 | 06-OCT-07:10 | 0.218926E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.940310E+09 | 1220.26 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.935176E+09 | 1220.26 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.110210E+11 | 0.259973E+11 | ||||
Minimum of Months | 0.847699E+09 | 890.81 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.985934E+09 | 1220.26 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.455938E+10 | 4734.72 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.413549E+10 | 4734.72 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.491032E+10 | 4734.72 | 01-MAR-08:09 | 0.762606E+12 | 284724.39 | 01-MAR-00:10 |
April | 0.438976E+10 | 4734.72 | 03-APR-07:10 | 0.984007E+12 | 379632.52 | 01-APR-00:10 |
May | 0.473485E+10 | 4734.72 | 01-MAY-07:10 | 0.254202E+12 | 94908.13 | 01-MAY-00:10 |
June | 0.471053E+10 | 4734.72 | 01-JUN-07:10 | 0.492004E+12 | 189816.26 | 01-JUN-00:10 |
July | 0.441408E+10 | 4734.72 | 03-JUL-07:10 | 0.762606E+12 | 284724.39 | 01-JUL-00:10 |
August | 0.491032E+10 | 4734.72 | 01-AUG-07:10 | 0.101681E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.438976E+10 | 4734.72 | 01-SEP-07:10 | 0.246002E+12 | 94908.13 | 01-SEP-00:10 |
October | 0.455938E+10 | 4734.72 | 02-OCT-07:10 | 0.508404E+12 | 189816.26 | 01-OCT-00:10 |
November | 0.450489E+10 | 4734.72 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.441408E+10 | 4734.72 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.546329E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.413549E+10 | 4734.72 | 0.246002E+12 | 94908.13 | ||
Maximum of Months | 0.491032E+10 | 4734.72 | 0.101681E+13 | 379632.52 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.210625E+09 | 218.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.191042E+09 | 218.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.226836E+09 | 218.72 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.202789E+09 | 218.72 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.218730E+09 | 218.72 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.217607E+09 | 218.72 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.203912E+09 | 218.72 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.226836E+09 | 218.72 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.202789E+09 | 218.72 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.210625E+09 | 218.72 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.208107E+09 | 218.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.203912E+09 | 218.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.252381E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.191042E+09 | 218.72 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.226836E+09 | 218.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.210625E+09 | 218.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.191042E+09 | 218.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.226836E+09 | 218.72 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.202789E+09 | 218.72 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.218730E+09 | 218.72 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.217607E+09 | 218.72 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.203912E+09 | 218.72 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.226836E+09 | 218.72 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.202789E+09 | 218.72 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.210625E+09 | 218.72 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.208107E+09 | 218.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.203912E+09 | 218.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.252381E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.191042E+09 | 218.72 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.226836E+09 | 218.72 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.210625E+09 | 218.72 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.191042E+09 | 218.72 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.226836E+09 | 218.72 | 01-MAR-08:09 | 0.156574E+11 | 5845.82 | 01-MAR-00:10 |
April | 0.202789E+09 | 218.72 | 03-APR-07:10 | 0.202031E+11 | 7794.42 | 01-APR-00:10 |
May | 0.218730E+09 | 218.72 | 01-MAY-07:10 | 0.521915E+10 | 1948.61 | 01-MAY-00:10 |
June | 0.217607E+09 | 218.72 | 01-JUN-07:10 | 0.101016E+11 | 3897.21 | 01-JUN-00:10 |
July | 0.203912E+09 | 218.72 | 03-JUL-07:10 | 0.156574E+11 | 5845.82 | 01-JUL-00:10 |
August | 0.226836E+09 | 218.72 | 01-AUG-07:10 | 0.208766E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.202789E+09 | 218.72 | 01-SEP-07:10 | 0.505079E+10 | 1948.61 | 01-SEP-00:10 |
October | 0.210625E+09 | 218.72 | 02-OCT-07:10 | 0.104383E+11 | 3897.21 | 01-OCT-00:10 |
November | 0.208107E+09 | 218.72 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.203912E+09 | 218.72 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.252381E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.191042E+09 | 218.72 | 0.505079E+10 | 1948.61 | ||
Maximum of Months | 0.226836E+09 | 218.72 | 0.208766E+11 | 7794.42 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.161705E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.146671E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.174151E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.155689E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.167928E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.167065E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.156551E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.174151E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.155689E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.161705E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.159772E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.156551E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.193763E+12 | 0.424397E+12 | ||||||
Minimum of Months | 0.121482E+11 | 0.146671E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.174151E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.145222E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.131721E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.156400E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.139820E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.150811E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.150037E+11 | 0.270334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.140594E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.156400E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.139820E+11 | 0.261233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.145222E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.143487E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.140594E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.174013E+12 | 0.321278E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.131721E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.156400E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.145222E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.131721E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.156400E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.139820E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.150811E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.150037E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.140594E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.156400E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.139820E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.145222E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.143487E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.140594E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.174013E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.131721E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.156400E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.145222E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.131721E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.156400E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.139820E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.150811E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.150037E+11 | 0.270332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.140594E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.156400E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.139820E+11 | 0.261232E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.145222E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.143487E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.140594E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.174013E+12 | 0.321277E+12 | ||||||
Minimum of Months | 0.109099E+11 | 0.131721E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.156400E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.150030E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158888E+10 |
February | 0.136985E+10 | 0.132254E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138162E+10 |
March | 0.163685E+10 | 0.153368E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115262E+10 |
April | 0.145243E+10 | 0.135044E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522878.90 | 0.767015E+09 |
May | 0.157338E+10 | 0.144349E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3304272.55 | 0.426665E+09 |
June | 0.156900E+10 | 0.142769E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19626428.01 | 0.205976E+09 |
July | 0.145680E+10 | 0.134242E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 49240503.96 | 52197428.71 |
August | 0.163685E+10 | 0.150147E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57371970.84 | 71693398.70 |
September | 0.145243E+10 | 0.135970E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6441337.17 | 0.231685E+09 |
October | 0.150991E+10 | 0.143478E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99050.39 | 0.597561E+09 |
November | 0.149516E+10 | 0.146660E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116673E+10 |
December | 0.145680E+10 | 0.146445E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140153E+10 |
Annual Sum or Average | 0.181194E+11 | 0.171476E+11 | 0.403414E+11 | 0.136606E+09 | 0.904418E+10 | ||||
Minimum of Months | 0.136985E+10 | 0.132254E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52197428.71 |
Maximum of Months | 0.163685E+10 | 0.153368E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57371970.84 | 0.158888E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.963881E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104011E+10 |
February | 0.882782E+09 | 0.851241E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.909542E+09 |
March | 0.105485E+10 | 0.988589E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747219E+09 |
April | 0.936002E+09 | 0.871191E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 346614.42 | 0.494683E+09 |
May | 0.101394E+10 | 0.932132E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1574315.08 | 0.281778E+09 |
June | 0.101113E+10 | 0.922128E+09 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13325608.21 | 0.129596E+09 |
July | 0.938820E+09 | 0.866859E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34842580.94 | 27536302.28 |
August | 0.105485E+10 | 0.969135E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40714494.71 | 40178178.63 |
September | 0.936002E+09 | 0.876691E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4154224.90 | 0.152880E+09 |
October | 0.973041E+09 | 0.924330E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65409.36 | 0.390303E+09 |
November | 0.963541E+09 | 0.944575E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754538E+09 |
December | 0.938820E+09 | 0.938561E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.899813E+09 |
Annual Sum or Average | 0.116768E+11 | 0.110493E+11 | 0.259975E+11 | 95023247.62 | 0.586818E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.851241E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27536302.28 |
Maximum of Months | 0.105485E+10 | 0.988589E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40714494.71 | 0.104011E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.148389E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155891E+10 |
February | 0.136988E+10 | 0.131272E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138853E+10 |
March | 0.163688E+10 | 0.153051E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114018E+10 |
April | 0.145246E+10 | 0.135141E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522865.19 | 0.753417E+09 |
May | 0.157341E+10 | 0.144612E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2753577.40 | 0.421726E+09 |
June | 0.156904E+10 | 0.143082E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18678171.80 | 0.205040E+09 |
July | 0.145684E+10 | 0.134505E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46134784.46 | 54493372.70 |
August | 0.163688E+10 | 0.150331E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53992278.33 | 76550079.68 |
September | 0.145246E+10 | 0.135892E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5863120.78 | 0.241374E+09 |
October | 0.150994E+10 | 0.142918E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44278.94 | 0.620797E+09 |
November | 0.149520E+10 | 0.145755E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115220E+10 |
December | 0.145684E+10 | 0.144320E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137914E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170927E+11 | 0.403420E+11 | 0.127989E+09 | 0.899236E+10 | ||||
Minimum of Months | 0.136988E+10 | 0.131272E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54493372.70 |
Maximum of Months | 0.163688E+10 | 0.153051E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53992278.33 | 0.155891E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.958871E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108910E+10 |
February | 0.882782E+09 | 0.847463E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.965775E+09 |
March | 0.105485E+10 | 0.985797E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.829030E+09 |
April | 0.936002E+09 | 0.870513E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 345308.08 | 0.570146E+09 |
May | 0.101394E+10 | 0.930314E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1905537.33 | 0.307588E+09 |
June | 0.101113E+10 | 0.920468E+09 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11069382.44 | 0.163872E+09 |
July | 0.938820E+09 | 0.865556E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26253628.95 | 57220754.18 |
August | 0.105485E+10 | 0.967568E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31030949.40 | 71642329.49 |
September | 0.936002E+09 | 0.875847E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4085094.31 | 0.174237E+09 |
October | 0.973041E+09 | 0.921773E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 65437.96 | 0.437162E+09 |
November | 0.963541E+09 | 0.940124E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839097E+09 |
December | 0.938820E+09 | 0.934753E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101643E+10 |
Annual Sum or Average | 0.116768E+11 | 0.110190E+11 | 0.259973E+11 | 74755338.48 | 0.652130E+10 | ||||
Minimum of Months | 0.882782E+09 | 0.847463E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57220754.18 |
Maximum of Months | 0.105485E+10 | 0.985797E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31030949.40 | 0.108910E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.150196E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309725E+10 |
February | 0.136985E+10 | 0.132365E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274812E+10 |
March | 0.163685E+10 | 0.153413E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225216E+10 |
April | 0.145243E+10 | 0.135074E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1185654.92 | 0.150963E+10 |
May | 0.157338E+10 | 0.144369E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8957543.37 | 0.882251E+09 |
June | 0.156900E+10 | 0.142796E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41964061.20 | 0.445969E+09 |
July | 0.145680E+10 | 0.134269E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103786E+09 | 0.147877E+09 |
August | 0.163685E+10 | 0.150164E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116656E+09 | 0.196123E+09 |
September | 0.145243E+10 | 0.136015E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15886044.29 | 0.467540E+09 |
October | 0.150991E+10 | 0.143540E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 172963.01 | 0.117809E+10 |
November | 0.149516E+10 | 0.146755E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221310E+10 |
December | 0.145680E+10 | 0.146645E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265742E+10 |
Annual Sum or Average | 0.181194E+11 | 0.171560E+11 | 0.403414E+11 | 0.288608E+09 | 0.177955E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.132365E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147877E+09 |
Maximum of Months | 0.163685E+10 | 0.153413E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116656E+09 | 0.309725E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.964216E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206563E+10 |
February | 0.649041E+09 | 0.851490E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185360E+10 |
March | 0.773965E+09 | 0.988721E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152139E+10 |
April | 0.688021E+09 | 0.871287E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 744895.84 | 0.103818E+10 |
May | 0.744847E+09 | 0.932201E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3257374.84 | 0.604780E+09 |
June | 0.742030E+09 | 0.922217E+09 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26293869.77 | 0.303171E+09 |
July | 0.690839E+09 | 0.866943E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64187429.01 | 0.101650E+09 |
August | 0.773965E+09 | 0.969222E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74408943.37 | 0.136615E+09 |
September | 0.688021E+09 | 0.876815E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8940922.11 | 0.327200E+09 |
October | 0.715730E+09 | 0.924530E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115212.03 | 0.809890E+09 |
November | 0.708685E+09 | 0.944780E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148951E+10 |
December | 0.690839E+09 | 0.938933E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177861E+10 |
Annual Sum or Average | 0.858171E+10 | 0.110514E+11 | 0.259975E+11 | 0.177949E+09 | 0.120302E+11 | ||||
Minimum of Months | 0.649041E+09 | 0.851490E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101650E+09 |
Maximum of Months | 0.773965E+09 | 0.988721E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74408943.37 | 0.206563E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.148483E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320809E+10 |
February | 0.136988E+10 | 0.131330E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292526E+10 |
March | 0.163688E+10 | 0.153001E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237730E+10 |
April | 0.145246E+10 | 0.135173E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1102489.48 | 0.157116E+10 |
May | 0.157341E+10 | 0.144637E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6656656.73 | 0.901372E+09 |
June | 0.156904E+10 | 0.143118E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39348000.55 | 0.453136E+09 |
July | 0.145684E+10 | 0.134540E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 96107823.56 | 0.155603E+09 |
August | 0.163688E+10 | 0.150355E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107863E+09 | 0.213260E+09 |
September | 0.145246E+10 | 0.135929E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12100065.99 | 0.525310E+09 |
October | 0.150994E+10 | 0.142953E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67378.82 | 0.133766E+10 |
November | 0.149520E+10 | 0.145804E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236715E+10 |
December | 0.145684E+10 | 0.144413E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282817E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170974E+11 | 0.403420E+11 | 0.263245E+09 | 0.188635E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.131330E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155603E+09 |
Maximum of Months | 0.163688E+10 | 0.153001E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107863E+09 | 0.320809E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.959207E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211083E+10 |
February | 0.882782E+09 | 0.847696E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188451E+10 |
March | 0.105485E+10 | 0.985933E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158227E+10 |
April | 0.936002E+09 | 0.870624E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 769478.63 | 0.107621E+10 |
May | 0.101394E+10 | 0.930380E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4967845.32 | 0.632526E+09 |
June | 0.101113E+10 | 0.920537E+09 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24769878.59 | 0.338549E+09 |
July | 0.938820E+09 | 0.865630E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61241804.17 | 0.131848E+09 |
August | 0.105485E+10 | 0.967666E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69967896.85 | 0.166677E+09 |
September | 0.936002E+09 | 0.875991E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9298466.29 | 0.345123E+09 |
October | 0.973041E+09 | 0.921897E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 115354.42 | 0.846940E+09 |
November | 0.963541E+09 | 0.940309E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151497E+10 |
December | 0.938820E+09 | 0.935171E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182562E+10 |
Annual Sum or Average | 0.116768E+11 | 0.110210E+11 | 0.259973E+11 | 0.171131E+09 | 0.124561E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.847696E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131848E+09 |
Maximum of Months | 0.105485E+10 | 0.985933E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69967896.85 | 0.211083E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.150194E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367879E+10 |
February | 0.136985E+10 | 0.132365E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326195E+10 |
March | 0.163685E+10 | 0.153412E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260180E+10 |
April | 0.145243E+10 | 0.135074E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1367967.82 | 0.173379E+10 |
May | 0.157338E+10 | 0.144369E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9298577.67 | 0.104994E+10 |
June | 0.156900E+10 | 0.142796E+10 | 0.339445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47303488.69 | 0.555749E+09 |
July | 0.145680E+10 | 0.134269E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114251E+09 | 0.196072E+09 |
August | 0.163685E+10 | 0.150164E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135345E+09 | 0.249584E+09 |
September | 0.145243E+10 | 0.136015E+10 | 0.328017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17644288.96 | 0.555295E+09 |
October | 0.150991E+10 | 0.143540E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 160792.25 | 0.133810E+10 |
November | 0.149516E+10 | 0.146754E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248218E+10 |
December | 0.145680E+10 | 0.146645E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304917E+10 |
Annual Sum or Average | 0.181194E+11 | 0.171560E+11 | 0.403414E+11 | 0.325371E+09 | 0.207524E+11 | ||||
Minimum of Months | 0.136985E+10 | 0.132365E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196072E+09 |
Maximum of Months | 0.163685E+10 | 0.153412E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135345E+09 | 0.367879E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.964211E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245925E+10 |
February | 0.882782E+09 | 0.851491E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219505E+10 |
March | 0.105485E+10 | 0.988721E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176036E+10 |
April | 0.936002E+09 | 0.871285E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 851105.55 | 0.120146E+10 |
May | 0.101394E+10 | 0.932200E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3545124.77 | 0.724431E+09 |
June | 0.101113E+10 | 0.922215E+09 | 0.218751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30365963.88 | 0.378102E+09 |
July | 0.938820E+09 | 0.866941E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73087913.53 | 0.134212E+09 |
August | 0.105485E+10 | 0.969225E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87290998.34 | 0.173919E+09 |
September | 0.936002E+09 | 0.876815E+09 | 0.211387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10420104.35 | 0.392244E+09 |
October | 0.973041E+09 | 0.924536E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107170.30 | 0.930031E+09 |
November | 0.963541E+09 | 0.944777E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167449E+10 |
December | 0.938820E+09 | 0.938935E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204260E+10 |
Annual Sum or Average | 0.116768E+11 | 0.110514E+11 | 0.259975E+11 | 0.205668E+09 | 0.140662E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.851491E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134212E+09 |
Maximum of Months | 0.105485E+10 | 0.988721E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87290998.34 | 0.245925E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.148483E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377739E+10 |
February | 0.136988E+10 | 0.131330E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341152E+10 |
March | 0.163688E+10 | 0.153001E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274491E+10 |
April | 0.145246E+10 | 0.135172E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1281790.83 | 0.180846E+10 |
May | 0.157341E+10 | 0.144637E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7173675.80 | 0.107381E+10 |
June | 0.156904E+10 | 0.143117E+10 | 0.339450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45022781.38 | 0.564322E+09 |
July | 0.145684E+10 | 0.134539E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108654E+09 | 0.205947E+09 |
August | 0.163688E+10 | 0.150355E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127384E+09 | 0.270226E+09 |
September | 0.145246E+10 | 0.135929E+10 | 0.328022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14685946.07 | 0.626752E+09 |
October | 0.150994E+10 | 0.142953E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70822.86 | 0.154845E+10 |
November | 0.149520E+10 | 0.145804E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265341E+10 |
December | 0.145684E+10 | 0.144413E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321899E+10 |
Annual Sum or Average | 0.181198E+11 | 0.170973E+11 | 0.403420E+11 | 0.304273E+09 | 0.219042E+11 | ||||
Minimum of Months | 0.136988E+10 | 0.131330E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205947E+09 |
Maximum of Months | 0.163688E+10 | 0.153001E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127384E+09 | 0.377739E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.959205E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250442E+10 |
February | 0.882782E+09 | 0.847699E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224017E+10 |
March | 0.105485E+10 | 0.985934E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184634E+10 |
April | 0.936002E+09 | 0.870624E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 915553.38 | 0.125339E+10 |
May | 0.101394E+10 | 0.930381E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5779118.89 | 0.754217E+09 |
June | 0.101113E+10 | 0.920536E+09 | 0.218750E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29755046.92 | 0.416517E+09 |
July | 0.938820E+09 | 0.865628E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72571726.90 | 0.166607E+09 |
August | 0.105485E+10 | 0.967669E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83995131.05 | 0.207232E+09 |
September | 0.936002E+09 | 0.875991E+09 | 0.211386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11158456.61 | 0.411546E+09 |
October | 0.973041E+09 | 0.921897E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107367.37 | 0.980672E+09 |
November | 0.963541E+09 | 0.940310E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172496E+10 |
December | 0.938820E+09 | 0.935176E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211415E+10 |
Annual Sum or Average | 0.116768E+11 | 0.110210E+11 | 0.259973E+11 | 0.204282E+09 | 0.146202E+11 | ||||
Minimum of Months | 0.882782E+09 | 0.847699E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166607E+09 |
Maximum of Months | 0.105485E+10 | 0.985934E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83995131.05 | 0.250442E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.455938E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.413549E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.491032E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.438976E+10 | 0.984007E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.473485E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.471053E+10 | 0.492004E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.441408E+10 | 0.762606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.491032E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.438976E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.455938E+10 | 0.508404E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.450489E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.441408E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.546329E+11 | 0.749486E+13 | |||||||
Minimum of Months | 0.00 | 0.413549E+10 | 0.246002E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.491032E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.210625E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.191042E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.226836E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.202789E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.218730E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.217607E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.203912E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.226836E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.202789E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.210625E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.208107E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.203912E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252381E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.191042E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.226836E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.210625E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.191042E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.226836E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.202789E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.218730E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.217607E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.203912E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.226836E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.202789E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.210625E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.208107E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.203912E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252381E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.191042E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.226836E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 0.210625E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.191042E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.226836E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.202789E+09 | 0.202031E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.218730E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.217607E+09 | 0.101016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.203912E+09 | 0.156574E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.226836E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.202789E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.210625E+09 | 0.104383E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.208107E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.203912E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.252381E+10 | 0.153881E+12 | |||||||
Minimum of Months | 0.00 | 0.191042E+09 | 0.505079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.226836E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328808E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286270E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235031E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612322.05 | 0.156344E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5284342.74 | 0.866300E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30082074.75 | 0.425192E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78007760.82 | 0.121370E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86921352.38 | 0.169941E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8085289.25 | 0.475156E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6820.00 | 0.123431E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238475E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288416E+10 |
Annual Sum or Average | 0.209000E+09 | 0.186257E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121370E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86921352.38 | 0.328808E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529276E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479309E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394475E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1284209.88 | 0.262855E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12568424.60 | 0.149190E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56353173.47 | 0.734391E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144105E+09 | 0.219843E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154281E+09 | 0.317509E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15410635.20 | 0.805031E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20870.94 | 0.210135E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394943E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473500E+10 |
Annual Sum or Average | 0.384023E+09 | 0.310136E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219843E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154281E+09 | 0.529276E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552236E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496551E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.415756E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176783.58 | 0.280882E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4178387.89 | 0.170063E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38239671.72 | 0.891008E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101273E+09 | 0.296538E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132072E+09 | 0.378698E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10936695.81 | 0.898624E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221476E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396248E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473089E+10 |
Annual Sum or Average | 0.286877E+09 | 0.325279E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296538E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132072E+09 | 0.552236E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 16792.34 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 16792.34 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 16792.34 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 16792.34 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 16792.34 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 16792.34 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 16792.34 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 16792.34 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 16792.34 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 16792.34 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 16792.34 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 16792.34 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 17832.21 | 16792.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 16792.34 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 15080.70 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 15080.70 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 15080.70 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 15080.70 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 15080.70 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 15080.70 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 15080.70 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 15080.70 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 15080.70 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 15080.70 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 15080.70 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 15080.70 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 15080.70 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 15080.70 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 15080.70 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 15080.70 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 15080.70 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 15080.70 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 15080.70 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 15080.70 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 15080.70 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 15080.70 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 15080.70 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 15080.70 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 15080.70 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 15080.70 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 15080.70 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 15080.70 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 15080.70 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 15080.70 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 15080.70 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 15080.70 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 15080.70 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 15080.70 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 15080.70 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 15080.70 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 15080.70 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 15080.70 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 16014.58 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1893.53 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2658.51 | 31-JAN-00:51 |
February | 2010.79 | 01-FEB-10:09 | 1789.80 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2645.44 | 06-FEB-00:53 |
March | 2010.79 | 01-MAR-10:09 | 1587.51 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2059.00 | 12-MAR-10:00 |
April | 2010.79 | 03-APR-09:09 | 1382.30 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.65 | 07-APR-13:00 | 1608.51 | 11-APR-03:52 |
May | 2010.79 | 01-MAY-09:09 | 1382.30 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.26 | 29-MAY-12:00 | 950.91 | 03-MAY-04:00 |
June | 2010.79 | 01-JUN-09:09 | 1382.30 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.32 | 19-JUN-21:02 | 539.58 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1382.30 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 245.27 | 09-JUL-14:00 | 207.19 | 11-JUL-04:43 |
August | 2010.79 | 01-AUG-09:09 | 1382.30 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 307.22 | 12-AUG-18:53 | 339.34 | 20-AUG-06:00 |
September | 2010.79 | 01-SEP-09:09 | 1488.53 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 14-SEP-14:00 | 494.95 | 17-SEP-10:00 |
October | 2010.79 | 02-OCT-09:09 | 1660.51 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.06 | 25-OCT-11:00 | 1404.52 | 08-OCT-08:00 |
November | 2010.79 | 01-NOV-09:09 | 1893.53 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2205.19 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1893.53 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2856.38 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.19 | |||||
Maximum of Months | 2010.79 | 1893.53 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 307.22 | 2856.38 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1220.26 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1744.70 | 31-JAN-00:51 |
February | 1295.83 | 01-FEB-10:09 | 1161.20 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1814.81 | 05-FEB-08:40 |
March | 1295.83 | 01-MAR-10:09 | 1084.37 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1448.00 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 890.81 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 07-APR-13:00 | 1030.47 | 11-APR-03:52 |
May | 1295.83 | 01-MAY-09:09 | 890.81 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.16 | 29-MAY-12:00 | 618.05 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 890.81 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.06 | 19-JUN-21:02 | 349.18 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 890.81 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.51 | 09-JUL-14:00 | 125.28 | 02-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 890.81 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.97 | 12-AUG-18:53 | 218.96 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 890.81 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 14-SEP-14:00 | 319.00 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1076.38 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 25-OCT-11:00 | 1000.38 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1220.26 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1431.13 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1220.26 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1851.50 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.28 | |||||
Maximum of Months | 1295.83 | 1220.26 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 219.97 | 1851.50 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1893.57 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 2657.64 | 31-JAN-00:51 |
February | 2010.83 | 01-FEB-10:09 | 1782.47 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2573.41 | 06-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 1518.59 | 02-MAR-16:00 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2136.47 | 12-MAR-10:00 |
April | 2010.83 | 03-APR-09:09 | 1382.33 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.64 | 07-APR-13:00 | 1591.63 | 11-APR-03:52 |
May | 2010.83 | 01-MAY-09:09 | 1382.33 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 129.85 | 29-MAY-12:00 | 937.98 | 03-MAY-04:00 |
June | 2010.83 | 01-JUN-09:09 | 1382.33 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.93 | 19-JUN-21:02 | 538.91 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1382.33 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.60 | 09-JUL-14:00 | 209.88 | 11-JUL-04:43 |
August | 2010.83 | 01-AUG-09:09 | 1382.33 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.83 | 12-AUG-18:53 | 341.73 | 20-AUG-06:00 |
September | 2010.83 | 01-SEP-09:09 | 1459.99 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.92 | 14-SEP-14:00 | 489.37 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1627.93 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 | 25-OCT-11:00 | 1398.98 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 1893.57 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2170.93 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1893.57 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2771.45 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.88 | |||||
Maximum of Months | 2010.83 | 1893.57 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 299.83 | 2771.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1220.26 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1817.54 | 31-JAN-00:51 |
February | 1295.83 | 01-FEB-10:09 | 1144.71 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1823.94 | 05-FEB-07:52 |
March | 1295.83 | 01-MAR-10:09 | 1013.95 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1519.16 | 12-MAR-10:00 |
April | 1295.83 | 03-APR-09:09 | 924.47 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 07-APR-13:00 | 1184.17 | 11-APR-03:52 |
May | 1295.83 | 01-MAY-09:09 | 890.81 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.67 | 29-MAY-12:00 | 681.71 | 03-MAY-04:00 |
June | 1295.83 | 01-JUN-09:09 | 890.81 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.22 | 19-JUN-21:02 | 415.42 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 890.81 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.60 | 09-JUL-13:40 | 226.20 | 02-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 906.01 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 183.07 | 04-AUG-21:02 | 279.47 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 990.16 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.78 | 14-SEP-14:00 | 363.23 | 17-SEP-10:00 |
October | 1295.83 | 02-OCT-09:09 | 1054.77 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 25-OCT-11:00 | 1003.25 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1220.26 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1566.05 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1220.26 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2049.10 | 31-DEC-21:52 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.20 | |||||
Maximum of Months | 1295.83 | 1220.26 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 183.07 | 2049.10 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1893.53 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5191.67 | 31-JAN-00:51 |
February | 2010.79 | 01-FEB-10:09 | 1792.91 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5374.54 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1596.50 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4084.48 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1382.30 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 | 07-APR-13:00 | 3188.19 | 11-APR-03:52 |
May | 2010.79 | 01-MAY-09:09 | 1382.30 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.89 | 29-MAY-12:00 | 1916.60 | 03-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1382.30 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 459.74 | 19-JUN-21:02 | 1115.19 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1382.30 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 563.92 | 09-JUL-14:00 | 504.66 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1382.30 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 710.96 | 12-AUG-19:00 | 741.36 | 20-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 1500.19 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.44 | 14-SEP-14:00 | 986.05 | 23-SEP-03:51 |
October | 2010.79 | 02-OCT-09:09 | 1667.37 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 25-OCT-11:00 | 2637.80 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 1893.53 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4195.24 | 23-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1893.53 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5341.39 | 31-DEC-21:58 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.66 | |||||
Maximum of Months | 2010.79 | 1893.53 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 710.96 | 5374.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1220.26 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3467.73 | 31-JAN-00:51 |
February | 1239.33 | 01-FEB-08:09 | 1161.68 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3583.04 | 06-FEB-00:53 |
March | 1239.33 | 01-MAR-08:09 | 1085.38 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2726.86 | 21-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 890.81 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 07-APR-13:00 | 2125.74 | 11-APR-03:52 |
May | 1239.33 | 01-MAY-07:10 | 890.81 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 29-MAY-12:00 | 1287.22 | 03-MAY-03:55 |
June | 1239.33 | 01-JUN-07:10 | 890.81 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 305.37 | 19-JUN-21:02 | 746.53 | 02-JUN-22:00 |
July | 1239.33 | 03-JUL-07:10 | 890.81 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 328.68 | 09-JUL-14:00 | 345.31 | 11-JUL-05:00 |
August | 1239.33 | 01-AUG-07:10 | 890.81 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 492.29 | 12-AUG-19:00 | 520.65 | 20-AUG-06:00 |
September | 1239.33 | 01-SEP-07:10 | 890.81 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.29 | 14-SEP-14:00 | 656.15 | 10-SEP-08:10 |
October | 1239.33 | 02-OCT-07:10 | 1077.51 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 25-OCT-11:00 | 1942.90 | 08-OCT-08:00 |
November | 1239.33 | 01-NOV-07:10 | 1220.26 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2803.78 | 23-NOV-02:00 |
December | 1239.33 | 01-DEC-08:09 | 1220.26 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3573.04 | 31-DEC-21:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.31 | |||||
Maximum of Months | 1239.33 | 1220.26 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 492.29 | 3583.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1893.57 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5477.07 | 31-JAN-00:51 |
February | 2010.83 | 01-FEB-10:09 | 1785.89 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5374.57 | 06-FEB-00:53 |
March | 2010.83 | 01-MAR-10:09 | 1510.81 | 16-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4151.88 | 21-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1382.33 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.39 | 07-APR-13:00 | 3258.89 | 11-APR-03:52 |
May | 2010.83 | 01-MAY-09:09 | 1382.33 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 320.69 | 29-MAY-12:00 | 1956.36 | 03-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 1382.33 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.83 | 19-JUN-21:02 | 1123.81 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1382.33 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 500.31 | 09-JUL-14:00 | 509.92 | 11-JUL-05:00 |
August | 2010.83 | 01-AUG-09:09 | 1382.33 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 689.50 | 12-AUG-19:00 | 767.84 | 20-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 1472.70 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.63 | 14-SEP-14:00 | 1069.13 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1636.38 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.43 | 25-OCT-11:00 | 2806.75 | 08-OCT-08:00 |
November | 2010.83 | 01-NOV-09:09 | 1893.57 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4355.00 | 23-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1893.57 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5341.46 | 31-DEC-21:58 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.92 | |||||
Maximum of Months | 2010.83 | 1893.57 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 689.50 | 5477.07 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1220.26 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 3524.48 | 31-JAN-00:51 |
February | 1295.83 | 01-FEB-10:09 | 1145.52 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3583.08 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1015.50 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2792.52 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 926.28 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.26 | 07-APR-13:00 | 2226.96 | 11-APR-03:52 |
May | 1295.83 | 01-MAY-09:09 | 890.81 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 269.09 | 29-MAY-12:00 | 1354.27 | 03-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 890.81 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.40 | 19-JUN-21:02 | 830.85 | 03-JUN-19:00 |
July | 1295.83 | 03-JUL-09:09 | 890.81 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 346.02 | 09-JUL-14:00 | 454.45 | 02-JUL-17:40 |
August | 1295.83 | 01-AUG-09:09 | 908.29 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 427.56 | 12-AUG-19:00 | 562.42 | 20-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 991.86 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.30 | 14-SEP-14:00 | 709.48 | 30-SEP-24:00 |
October | 1295.83 | 02-OCT-09:09 | 1056.01 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 25-OCT-11:00 | 1834.79 | 17-OCT-24:00 |
November | 1295.83 | 01-NOV-09:09 | 1220.26 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2845.82 | 23-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1220.26 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3566.11 | 31-DEC-21:54 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.45 | |||||
Maximum of Months | 1295.83 | 1220.26 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 427.56 | 3583.08 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1893.53 | 02-JAN-16:40 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6147.41 | 01-JAN-21:00 |
February | 2010.79 | 01-FEB-10:09 | 1792.84 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6666.12 | 06-FEB-01:00 |
March | 2010.79 | 01-MAR-10:09 | 1596.41 | 02-MAR-16:00 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5058.54 | 21-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1382.30 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.96 | 07-APR-13:00 | 3651.65 | 11-APR-03:52 |
May | 2010.79 | 01-MAY-09:09 | 1382.30 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 446.67 | 29-MAY-12:00 | 2190.03 | 03-MAY-03:55 |
June | 2010.79 | 01-JUN-09:09 | 1382.30 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.16 | 19-JUN-21:02 | 1346.35 | 02-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1382.30 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 583.79 | 09-JUL-14:00 | 621.89 | 11-JUL-05:00 |
August | 2010.79 | 01-AUG-09:09 | 1382.30 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 841.58 | 12-AUG-19:00 | 875.44 | 20-AUG-05:53 |
September | 2010.79 | 01-SEP-09:09 | 1499.85 | 27-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 216.61 | 14-SEP-14:00 | 1148.03 | 23-SEP-03:51 |
October | 2010.79 | 02-OCT-09:09 | 1667.15 | 31-OCT-15:00 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 25-OCT-11:00 | 3006.72 | 17-OCT-24:00 |
November | 2010.79 | 01-NOV-09:09 | 1893.53 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4952.11 | 22-NOV-22:02 |
December | 2010.79 | 01-DEC-10:09 | 1893.53 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6663.19 | 31-DEC-22:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 621.89 | |||||
Maximum of Months | 2010.79 | 1893.53 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 841.58 | 6666.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1220.26 | 02-JAN-16:40 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4326.08 | 14-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1161.63 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4465.65 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1085.31 | 02-MAR-16:00 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3376.79 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 890.81 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.64 | 07-APR-13:00 | 2435.58 | 11-APR-03:52 |
May | 1295.83 | 01-MAY-09:09 | 890.81 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.22 | 29-MAY-11:50 | 1475.46 | 03-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 890.81 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.92 | 19-JUN-21:02 | 902.12 | 02-JUN-22:00 |
July | 1295.83 | 03-JUL-09:09 | 890.81 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 378.41 | 09-JUL-13:40 | 425.14 | 11-JUL-05:00 |
August | 1295.83 | 01-AUG-09:09 | 890.81 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 585.96 | 12-AUG-19:00 | 614.28 | 20-AUG-06:00 |
September | 1295.83 | 01-SEP-09:09 | 890.81 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.41 | 14-SEP-14:00 | 767.66 | 10-SEP-08:20 |
October | 1295.83 | 02-OCT-09:09 | 1077.37 | 31-OCT-15:00 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 25-OCT-11:00 | 2041.46 | 08-OCT-08:00 |
November | 1295.83 | 01-NOV-09:09 | 1220.26 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3302.33 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1220.26 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4442.40 | 31-DEC-21:58 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425.14 | |||||
Maximum of Months | 1295.83 | 1220.26 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 585.96 | 4465.65 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1893.57 | 02-JAN-16:40 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 6217.58 | 14-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 1785.79 | 15-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6698.29 | 06-FEB-01:00 |
March | 2010.83 | 01-MAR-10:09 | 1510.53 | 16-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5087.14 | 21-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1382.33 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.95 | 07-APR-13:00 | 3735.67 | 11-APR-03:52 |
May | 2010.83 | 01-MAY-09:09 | 1382.33 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.92 | 29-MAY-12:00 | 2239.84 | 03-MAY-03:55 |
June | 2010.83 | 01-JUN-09:09 | 1382.33 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.09 | 19-JUN-21:02 | 1356.50 | 02-JUN-22:00 |
July | 2010.83 | 03-JUL-09:09 | 1382.33 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.68 | 09-JUL-14:00 | 628.08 | 11-JUL-05:00 |
August | 2010.83 | 01-AUG-09:09 | 1382.33 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 816.41 | 12-AUG-19:00 | 907.52 | 20-AUG-05:53 |
September | 2010.83 | 01-SEP-09:09 | 1472.36 | 27-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.88 | 14-SEP-14:00 | 1232.07 | 30-SEP-24:00 |
October | 2010.83 | 02-OCT-09:09 | 1636.19 | 31-OCT-15:00 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.82 | 25-OCT-11:00 | 3231.68 | 17-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1893.57 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4968.47 | 22-NOV-22:02 |
December | 2010.83 | 01-DEC-10:09 | 1893.57 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6663.71 | 31-DEC-21:58 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 2010.83 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 628.08 | |||||
Maximum of Months | 2010.83 | 1893.57 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 816.41 | 6698.29 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1220.26 | 02-JAN-16:40 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 4326.08 | 14-JAN-06:00 |
February | 1295.83 | 01-FEB-10:09 | 1145.47 | 15-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4465.55 | 06-FEB-01:00 |
March | 1295.83 | 01-MAR-10:09 | 1015.32 | 16-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3401.85 | 21-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 926.11 | 14-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.64 | 07-APR-13:00 | 2564.13 | 11-APR-03:52 |
May | 1295.83 | 01-MAY-09:09 | 890.81 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 321.10 | 29-MAY-11:50 | 1561.13 | 03-MAY-03:55 |
June | 1295.83 | 01-JUN-09:09 | 890.81 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 360.38 | 19-JUN-21:02 | 1025.58 | 03-JUN-17:40 |
July | 1295.83 | 03-JUL-09:09 | 890.81 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 388.50 | 09-JUL-13:40 | 620.17 | 02-JUL-18:00 |
August | 1295.83 | 01-AUG-09:09 | 908.00 | 16-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 518.16 | 12-AUG-19:00 | 662.17 | 20-AUG-05:53 |
September | 1295.83 | 01-SEP-09:09 | 991.65 | 27-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.41 | 14-SEP-14:00 | 828.26 | 10-SEP-20:00 |
October | 1295.83 | 02-OCT-09:09 | 1055.85 | 06-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.55 | 25-OCT-11:00 | 2121.80 | 17-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1220.26 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3308.54 | 22-NOV-22:02 |
December | 1295.83 | 01-DEC-10:09 | 1220.26 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4442.44 | 31-DEC-21:56 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1295.83 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.17 | |||||
Maximum of Months | 1295.83 | 1220.26 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 518.16 | 4465.55 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 4734.72 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 4734.72 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 4734.72 | 01-MAR-08:09 | 284724.39 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 4734.72 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 4734.72 | 01-MAY-07:10 | 94908.13 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 4734.72 | 01-JUN-07:10 | 189816.26 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 4734.72 | 03-JUL-07:10 | 284724.39 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 4734.72 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 4734.72 | 01-SEP-07:10 | 94908.13 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 4734.72 | 02-OCT-07:10 | 189816.26 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 4734.72 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 4734.72 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 4734.72 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 4734.72 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 218.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 218.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 218.72 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 218.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 218.72 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 218.72 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 218.72 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 218.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 218.72 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 218.72 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 218.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 218.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 218.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 218.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 218.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 218.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 218.72 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 218.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 218.72 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 218.72 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 218.72 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 218.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 218.72 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 218.72 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 218.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 218.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 218.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 218.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.00 | 218.72 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 218.72 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 218.72 | 01-MAR-08:09 | 5845.82 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 218.72 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 218.72 | 01-MAY-07:10 | 1948.61 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 218.72 | 01-JUN-07:10 | 3897.21 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 218.72 | 03-JUL-07:10 | 5845.82 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 218.72 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 218.72 | 01-SEP-07:10 | 1948.61 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 218.72 | 02-OCT-07:10 | 3897.21 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 218.72 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 218.72 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 218.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 218.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 5599.18 | 31-JAN-00:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5585.25 | 06-FEB-00:53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4157.96 | 12-MAR-10:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.44 | 07-APR-13:00 | 3358.21 | 11-APR-03:54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.14 | 29-MAY-12:00 | 1976.84 | 03-MAY-04:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.18 | 19-JUN-21:02 | 1073.41 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 490.71 | 09-JUL-14:00 | 441.44 | 11-JUL-04:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.65 | 12-AUG-18:53 | 695.68 | 20-AUG-06:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.75 | 14-SEP-14:00 | 972.18 | 23-SEP-03:51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 25-OCT-11:00 | 2901.25 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4641.62 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5989.02 | 31-DEC-21:52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 441.44 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 565.65 | 5989.02 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9448.48 | 31-JAN-00:51 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9337.66 | 05-FEB-07:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6867.67 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.61 | 07-APR-13:00 | 5745.94 | 11-APR-03:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 601.03 | 29-MAY-12:00 | 3406.01 | 03-MAY-03:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623.24 | 19-JUN-21:02 | 1875.23 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 919.11 | 09-JUL-14:00 | 801.26 | 11-JUL-05:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.08 | 12-AUG-19:00 | 1244.17 | 20-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241.87 | 14-SEP-14:00 | 1687.53 | 23-SEP-03:51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 | 25-OCT-11:00 | 4908.55 | 08-OCT-08:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7790.08 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9576.60 | 31-DEC-21:52 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 801.26 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1031.08 | 9576.60 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 9589.56 | 31-JAN-01:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 9194.58 | 06-FEB-01:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 7706.33 | 21-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 | 08-APR-10:00 | 5879.74 | 11-APR-03:52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.98 | 29-MAY-12:00 | 3542.57 | 03-MAY-03:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 694.75 | 19-JUN-21:02 | 1957.89 | 02-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656.71 | 07-JUL-22:00 | 879.03 | 11-JUL-04:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.77 | 12-AUG-19:00 | 1279.95 | 20-AUG-05:53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.69 | 14-SEP-14:00 | 1780.36 | 23-SEP-03:51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4858.35 | 17-OCT-24:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 7598.26 | 23-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 9328.29 | 31-DEC-22:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.03 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1131.77 | 9589.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 106813.71 | 26-JAN-05:50 | 0.00 | 6381.40 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 112881.08 | 21-FEB-04:01 | 0.00 | 8508.54 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 107333.99 | 27-MAR-03:01 | 0.00 | 9572.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 107364.97 | 21-APR-03:53 | 0.00 | 3190.70 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 108303.57 | 01-MAY-02:31 | 0.00 | 9572.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 106823.57 | 05-JUN-02:20 | 0.00 | 3190.70 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 99709.39 | 16-JUL-24:00 | 0.00 | 3190.70 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 99935.21 | 23-AUG-03:50 | 0.00 | 3190.70 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 108855.37 | 11-SEP-02:32 | 0.00 | 5317.84 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 112615.67 | 09-OCT-09:53 | 2692.84 | 2798.72 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 112163.09 | 12-NOV-17:52 | 4488.06 | 4664.54 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 114206.86 | 25-DEC-15:23 | 2692.84 | 2798.72 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 99709.39 | 0.00 | 2798.72 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 114206.86 | 4488.06 | 9572.10 | 121117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 62312.86 | 24-JAN-05:01 | 0.00 | 19103.16 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67821.80 | 21-FEB-04:02 | 0.00 | 7641.26 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 70801.50 | 27-MAR-03:02 | 0.00 | 8596.42 | 72514.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73338.70 | 08-APR-03:01 | 0.00 | 9551.58 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 82972.06 | 31-MAY-03:02 | 0.00 | 9551.58 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 86093.59 | 28-JUN-03:02 | 0.00 | 9551.58 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82441.99 | 01-JUL-03:01 | 0.00 | 9551.58 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 80360.85 | 02-AUG-05:02 | 16122.38 | 16756.34 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 93847.16 | 06-SEP-03:02 | 0.00 | 9551.58 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86557.12 | 06-OCT-03:02 | 0.00 | 9551.58 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 73073.18 | 06-NOV-04:01 | 0.00 | 9551.58 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 70844.37 | 26-DEC-04:02 | 0.00 | 7641.26 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 62312.86 | 0.00 | 7641.26 | 60428.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93847.16 | 16122.38 | 19103.16 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 55127.03 | 31-JAN-09:50 | 45948.79 | 45242.11 | 54385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 49914.03 | 24-FEB-06:03 | 6448.95 | 6702.53 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55876.39 | 28-MAR-05:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66877.41 | 10-APR-05:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 71321.58 | 31-MAY-05:03 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 83239.56 | 16-JUN-04:02 | 0.00 | 19103.16 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78906.34 | 24-JUL-03:02 | 0.00 | 3820.63 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79073.42 | 07-AUG-03:02 | 0.00 | 4775.79 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78432.39 | 13-SEP-05:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 75166.09 | 06-OCT-05:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 65322.07 | 10-NOV-06:01 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 53871.33 | 21-DEC-06:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 49914.03 | 0.00 | 3820.63 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83239.56 | 45948.79 | 45242.11 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 19470.84 | 20-JAN-16:55 | 30632.53 | 30161.41 | 36257.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 20252.41 | 24-FEB-17:00 | 15316.26 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 33188.84 | 03-MAR-17:00 | 15316.26 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 66135.99 | 10-APR-05:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72978.70 | 31-MAY-05:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 88950.53 | 20-JUN-03:02 | 0.00 | 9551.58 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 82298.49 | 24-JUL-03:02 | 0.00 | 3820.63 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 88305.38 | 28-AUG-03:02 | 0.00 | 9551.58 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 80314.63 | 13-SEP-05:02 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74172.67 | 06-OCT-05:01 | 16122.38 | 16756.34 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32817.26 | 03-NOV-16:00 | 15316.26 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 18892.14 | 20-DEC-17:00 | 15316.26 | 15080.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 18892.14 | 0.00 | 3820.63 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 88950.53 | 30632.53 | 30161.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2588.55 | 25-JAN-08:10 | 3846.22 | 3177.62 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 276.05 |
February | 2503.83 | 24-FEB-14:10 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.45 |
March | 5954.96 | 27-MAR-13:30 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.49 |
April | 6849.92 | 07-APR-13:50 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 0.00 |
May | 10856.09 | 31-MAY-05:02 | 2024.33 | 1535.89 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11773.48 | 26-JUN-05:02 | 2024.33 | 1535.89 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 |
July | 12241.22 | 08-JUL-05:02 | 2024.33 | 1707.03 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 0.00 |
August | 11693.21 | 01-AUG-05:02 | 2024.33 | 2043.28 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
September | 12029.15 | 14-SEP-03:01 | 0.00 | 1199.30 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.37 |
October | 9287.80 | 25-OCT-05:01 | 2024.33 | 2103.93 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.13 |
November | 4989.89 | 03-NOV-13:40 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.57 |
December | 3787.58 | 26-DEC-13:30 | 1923.11 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2503.83 | 0.00 | 1199.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12241.22 | 3846.22 | 3177.62 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 28.36 | 277.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3206.35 | 19-JAN-09:30 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.26 |
February | 4666.86 | 22-FEB-09:25 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.52 |
March | 7351.69 | 29-MAR-08:40 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.38 |
April | 11342.00 | 23-APR-08:23 | 195.68 | 148.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.01 |
May | 17643.82 | 29-MAY-08:22 | 326.14 | 247.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.43 |
June | 16742.01 | 25-JUN-08:43 | 260.91 | 197.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.14 |
July | 17047.89 | 02-JUL-09:22 | 326.14 | 247.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.29 |
August | 12052.53 | 20-AUG-08:53 | 260.91 | 197.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.05 |
September | 17317.85 | 04-SEP-08:11 | 652.28 | 494.89 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
October | 8202.09 | 03-OCT-08:40 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.09 |
November | 5027.73 | 02-NOV-08:50 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.77 |
December | 3623.04 | 20-DEC-09:05 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.78 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3206.35 | 195.68 | 148.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 | |
Maximum of Months | 17643.82 | 2478.65 | 1781.61 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10347.94 | 17-JAN-13:30 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.31 |
February | 10367.60 | 22-FEB-13:20 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.93 |
March | 11816.55 | 01-MAR-13:20 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.85 |
April | 11837.83 | 07-APR-12:30 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 24.44 | 0.00 |
May | 11200.91 | 30-MAY-03:02 | 0.00 | 599.66 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.22 |
June | 12265.83 | 26-JUN-05:02 | 2024.37 | 1728.52 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.79 |
July | 13764.37 | 08-JUL-05:02 | 2024.37 | 1784.21 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 | 0.00 |
August | 16390.66 | 13-AUG-12:43 | 404.87 | 307.18 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 119.98 | 0.00 |
September | 16988.08 | 04-SEP-12:51 | 1012.19 | 767.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.52 |
October | 17136.93 | 22-OCT-12:32 | 404.87 | 307.18 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 |
November | 12910.41 | 02-NOV-13:20 | 2010.83 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.59 |
December | 13720.95 | 17-DEC-11:33 | 303.66 | 230.39 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.90 |
Annual Sum or Average | |||||||||||
Minimum of Months | 10347.94 | 0.00 | 230.39 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17136.93 | 2024.37 | 1784.21 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 119.98 | 467.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5597.01 | 20-JAN-15:50 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.65 |
February | 7854.89 | 24-FEB-15:30 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.24 |
March | 16997.89 | 26-MAR-16:33 | 260.91 | 197.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.71 |
April | 20601.44 | 16-APR-15:42 | 326.14 | 247.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.47 |
May | 18194.42 | 21-MAY-15:43 | 260.91 | 197.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.26 |
June | 21380.49 | 18-JUN-17:52 | 0.00 | 282.10 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.17 |
July | 21457.67 | 04-JUL-14:32 | 326.14 | 247.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.16 |
August | 23163.04 | 13-AUG-16:41 | 456.59 | 346.42 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 0.00 |
September | 22167.83 | 10-SEP-16:22 | 391.37 | 296.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.54 |
October | 17461.39 | 06-OCT-03:01 | 0.00 | 772.87 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.08 |
November | 13857.33 | 04-NOV-03:01 | 0.00 | 772.87 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.33 |
December | 11810.85 | 25-DEC-14:31 | 652.28 | 494.89 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.34 |
Annual Sum or Average | |||||||||||
Minimum of Months | 5597.01 | 0.00 | 197.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23163.04 | 1239.33 | 890.81 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 14.78 | 469.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1954.93 | 20-JAN-13:20 | 1923.11 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.61 |
February | 2522.15 | 22-FEB-17:20 | 1214.60 | 1982.49 | 2529.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.14 |
March | 3138.43 | 27-MAR-16:00 | 1923.11 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.02 |
April | 5183.15 | 07-APR-15:20 | 1923.11 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 | 0.00 |
May | 9705.60 | 31-MAY-05:02 | 2024.33 | 1535.89 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 11178.68 | 24-JUN-05:02 | 2024.33 | 1812.09 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.43 |
July | 12126.14 | 10-JUL-03:02 | 0.00 | 599.65 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 29.24 | 0.00 |
August | 11955.50 | 05-AUG-05:02 | 2024.33 | 2064.82 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 19.45 | 0.00 |
September | 11164.09 | 02-SEP-05:02 | 2024.33 | 2103.93 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.38 |
October | 5402.38 | 05-OCT-14:00 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.58 |
November | 2907.42 | 03-NOV-14:00 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.64 |
December | 2400.36 | 29-DEC-10:50 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.79 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1954.93 | 0.00 | 599.65 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12126.14 | 2024.33 | 2103.93 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 41.40 | 391.14 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2026.49 | 27-JAN-09:40 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.98 |
February | 2229.68 | 22-FEB-17:20 | 782.73 | 1284.74 | 1629.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.01 |
March | 5645.11 | 29-MAR-09:00 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 229.12 |
April | 8834.28 | 28-APR-08:30 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.87 |
May | 18163.79 | 29-MAY-08:52 | 326.14 | 247.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.76 |
June | 14512.90 | 25-JUN-09:43 | 260.91 | 197.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.94 |
July | 18657.94 | 02-JUL-08:32 | 391.37 | 296.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.03 |
August | 17158.02 | 13-AUG-08:13 | 260.91 | 197.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 |
September | 18080.89 | 04-SEP-08:42 | 326.14 | 247.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 |
October | 7380.65 | 05-OCT-08:40 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.30 |
November | 3257.84 | 03-NOV-09:00 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.86 |
December | 2766.33 | 21-DEC-09:30 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.49 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2026.49 | 260.91 | 197.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.82 | |
Maximum of Months | 18657.94 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9472.28 | 17-JAN-14:00 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.96 |
February | 9906.75 | 22-FEB-13:20 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 463.12 |
March | 11197.88 | 01-MAR-13:40 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.92 |
April | 11062.19 | 07-APR-12:30 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
May | 10848.71 | 31-MAY-05:02 | 2024.37 | 1554.13 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12497.18 | 24-JUN-05:02 | 2024.37 | 1854.01 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.54 |
July | 13759.64 | 10-JUL-03:02 | 0.00 | 599.66 | 5058.56 | 0.00 | 0.00 | 0.00 | 0.00 | 18.68 | 0.00 |
August | 15350.13 | 13-AUG-12:53 | 404.87 | 307.18 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 259.18 | 0.00 |
September | 16364.39 | 04-SEP-12:42 | 506.09 | 383.98 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.20 |
October | 15982.29 | 22-OCT-12:23 | 404.87 | 307.18 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.56 |
November | 12499.35 | 02-NOV-13:30 | 2010.83 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.35 |
December | 12484.17 | 17-DEC-12:43 | 404.87 | 307.18 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 955.73 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9472.28 | 0.00 | 307.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16364.39 | 2024.37 | 1854.01 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 259.18 | 955.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2662.46 | 20-JAN-16:00 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.17 |
February | 4037.02 | 22-FEB-16:30 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.55 |
March | 7810.27 | 29-MAR-16:00 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.75 |
April | 12481.04 | 09-APR-16:23 | 260.91 | 197.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.19 |
May | 12506.51 | 21-MAY-15:23 | 260.91 | 197.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.94 |
June | 17885.68 | 18-JUN-16:12 | 326.14 | 247.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.58 |
July | 19267.66 | 04-JUL-16:21 | 456.59 | 346.42 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.77 |
August | 17950.74 | 13-AUG-16:12 | 391.37 | 296.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 0.00 |
September | 17580.90 | 10-SEP-16:12 | 391.37 | 296.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.57 |
October | 9976.13 | 04-OCT-15:30 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.37 |
November | 5509.29 | 03-NOV-15:30 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.16 |
December | 2431.32 | 08-DEC-15:40 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.29 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2431.32 | 260.91 | 197.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19267.66 | 1239.33 | 890.81 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 108.60 | 481.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1761.53 | 20-JAN-16:10 | 1923.11 | 1617.09 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.65 |
February | 1774.95 | 17-FEB-16:10 | 1923.11 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 360.27 |
March | 3036.30 | 27-MAR-16:00 | 1923.11 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.72 |
April | 6027.80 | 07-APR-15:20 | 1923.11 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 0.00 |
May | 9542.30 | 30-MAY-05:03 | 809.73 | 614.35 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.39 |
June | 11937.35 | 24-JUN-05:02 | 2024.33 | 1811.90 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.73 |
July | 13566.40 | 09-JUL-16:12 | 506.08 | 383.97 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 0.00 |
August | 12385.19 | 01-AUG-05:02 | 2024.33 | 2045.14 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 |
September | 12288.33 | 02-SEP-05:02 | 2024.33 | 2103.93 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.35 |
October | 5817.71 | 04-OCT-14:00 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 3.91 | 0.00 |
November | 2811.78 | 03-NOV-14:00 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.92 |
December | 1738.81 | 20-DEC-14:20 | 2010.79 | 1382.30 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339.31 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1738.81 | 506.08 | 383.97 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13566.40 | 2024.33 | 2103.93 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 47.65 | 360.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1587.67 | 19-JAN-09:35 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.57 |
February | 1650.80 | 17-FEB-09:40 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.73 |
March | 4161.90 | 29-MAR-09:20 | 1295.83 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.05 |
April | 8212.37 | 28-APR-08:40 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.39 |
May | 18406.01 | 29-MAY-08:22 | 326.14 | 247.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.06 |
June | 15759.88 | 25-JUN-09:43 | 260.91 | 197.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 |
July | 18451.23 | 09-JUL-09:32 | 326.14 | 247.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 70.57 | 0.00 |
August | 17462.82 | 13-AUG-08:13 | 260.91 | 197.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.60 |
September | 17957.29 | 04-SEP-08:51 | 652.28 | 494.89 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.72 |
October | 6743.47 | 05-OCT-08:50 | 1239.33 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.68 |
November | 2484.25 | 03-NOV-14:00 | 1295.83 | 890.81 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.65 |
December | 1621.09 | 20-DEC-09:25 | 2478.65 | 1781.61 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1587.67 | 260.91 | 197.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18451.23 | 2478.65 | 1781.61 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 70.57 | 352.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9923.15 | 19-JAN-13:40 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.15 |
February | 10096.17 | 02-FEB-14:15 | 4021.67 | 2764.66 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 605.77 |
March | 11881.10 | 01-MAR-13:40 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 269.89 |
April | 11783.63 | 07-APR-12:40 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 67.37 | 0.00 |
May | 11010.30 | 30-MAY-05:03 | 809.75 | 619.04 | 4046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.49 |
June | 13507.92 | 24-JUN-05:02 | 2024.37 | 1853.80 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.08 |
July | 17120.22 | 30-JUL-14:22 | 506.09 | 383.98 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.39 |
August | 17451.34 | 13-AUG-12:53 | 404.87 | 307.18 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 286.82 | 0.00 |
September | 17915.46 | 04-SEP-12:51 | 1012.19 | 767.96 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.92 |
October | 17555.08 | 22-OCT-12:32 | 404.87 | 307.18 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.75 |
November | 13087.42 | 02-NOV-13:30 | 2010.83 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 323.36 |
December | 9693.49 | 21-DEC-13:30 | 1923.15 | 1382.33 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 613.96 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9693.49 | 404.87 | 307.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17915.46 | 4021.67 | 2764.66 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 286.82 | 690.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2214.67 | 20-JAN-16:10 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.23 |
February | 3367.67 | 22-FEB-16:30 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 347.72 |
March | 7567.78 | 29-MAR-16:00 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.06 |
April | 12585.71 | 09-APR-16:23 | 260.91 | 197.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.84 |
May | 14238.86 | 21-MAY-15:32 | 260.91 | 197.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 642.96 |
June | 19244.91 | 18-JUN-16:12 | 326.14 | 247.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.01 |
July | 20796.72 | 04-JUL-16:21 | 456.59 | 346.42 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.22 |
August | 19387.22 | 20-AUG-15:42 | 326.14 | 247.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.57 |
September | 19008.05 | 04-SEP-16:51 | 652.28 | 494.89 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.66 |
October | 11480.24 | 15-OCT-16:20 | 652.28 | 494.89 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.52 |
November | 5102.85 | 03-NOV-15:40 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.70 |
December | 2124.23 | 08-DEC-15:50 | 1239.33 | 890.81 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2124.23 | 260.91 | 197.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.57 | |
Maximum of Months | 20796.72 | 1239.33 | 890.81 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 747.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3981.97 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1177.99 |
February | 3849.55 | 21-FEB-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.79 |
March | 4891.47 | 27-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6504.36 | 10-APR-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.25 |
May | 7843.53 | 30-MAY-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.94 | 0.00 |
June | 8173.55 | 27-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.79 |
July | 8624.47 | 13-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 |
August | 9035.14 | 15-AUG-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
September | 8716.79 | 05-SEP-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.59 |
October | 7605.42 | 23-OCT-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.59 |
November | 6516.73 | 13-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.34 |
December | 3934.40 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3849.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.94 | 1177.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4394.05 | 14-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7750.54 |
February | 6433.38 | 13-FEB-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4440.73 |
March | 3741.85 | 17-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4101.75 |
April | 3412.38 | 10-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.39 |
May | 5550.75 | 31-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6131.94 | 26-JUN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.73 |
July | 9099.58 | 25-JUL-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.88 |
August | 6664.64 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.50 |
September | 5600.78 | 07-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.78 |
October | 3825.00 | 05-OCT-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.91 |
November | 5308.64 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2641.93 |
December | 4321.01 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 483.15 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3412.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9099.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7750.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 308.68 | 19-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1047.24 |
February | 1357.46 | 17-FEB-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.75 |
March | 5972.90 | 03-MAR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 710.56 |
April | 11908.94 | 07-APR-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 | 0.00 |
May | 17437.29 | 30-MAY-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.87 | 0.00 |
June | 18178.94 | 19-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.92 | 0.00 |
July | 16990.18 | 07-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.42 | 0.00 |
August | 17113.88 | 30-AUG-13:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.77 | 0.00 |
September | 16592.13 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.64 | 0.00 |
October | 10242.72 | 04-OCT-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.84 |
November | 4189.78 | 04-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.36 |
December | 437.87 | 20-DEC-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 354.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 308.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18178.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.92 | 1047.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1818.27 | 20-JAN-16:30 | 0.00 | 218.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3882.72 | 14-FEB-17:00 | 0.00 | 218.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5918.36 | 26-MAR-17:30 | 0.00 | 13.85 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7488.15 | 23-APR-17:50 | 0.00 | 27.71 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2072.26 | 01-MAY-00:05 | 0.00 | 27.71 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4016.46 | 18-JUN-18:08 | 0.00 | 69.27 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5932.40 | 04-JUL-18:05 | 0.00 | 27.71 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7203.10 | 08-AUG-04:53 | 0.00 | 83.12 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4138.73 | 01-SEP-00:03 | 0.00 | 55.41 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4078.79 | 15-OCT-16:33 | 0.00 | 36.45 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5704.12 | 06-NOV-16:10 | 0.00 | 218.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7374.39 | 18-DEC-15:50 | 0.00 | 218.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1818.27 | 0.00 | 13.85 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7488.15 | 0.00 | 218.72 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1533.17 | 20-JAN-16:40 | 0.00 | 218.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3492.99 | 22-FEB-17:00 | 0.00 | 218.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5521.77 | 29-MAR-17:20 | 0.00 | 72.91 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7087.95 | 12-APR-17:20 | 0.00 | 72.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1874.21 | 30-MAY-18:00 | 0.00 | 72.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3834.06 | 18-JUN-17:52 | 0.00 | 69.27 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5647.11 | 12-JUL-18:20 | 0.00 | 72.91 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6859.14 | 08-AUG-04:53 | 0.00 | 83.12 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3891.24 | 01-SEP-00:03 | 0.00 | 55.41 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3747.20 | 04-OCT-16:30 | 0.00 | 121.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5344.94 | 03-NOV-16:00 | 0.00 | 218.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6960.77 | 21-DEC-16:10 | 0.00 | 218.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1533.17 | 0.00 | 55.41 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7087.95 | 0.00 | 218.72 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1439.60 | 20-JAN-16:40 | 0.00 | 218.72 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3374.88 | 02-FEB-17:00 | 0.00 | 218.72 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5518.56 | 29-MAR-17:10 | 0.00 | 72.91 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7182.47 | 12-APR-17:20 | 0.00 | 72.91 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1968.83 | 30-MAY-18:00 | 0.00 | 72.91 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4030.89 | 18-JUN-17:52 | 0.00 | 69.27 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5804.19 | 04-JUL-17:58 | 0.00 | 69.27 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6897.72 | 20-AUG-02:37 | 0.00 | 41.56 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3467.29 | 01-SEP-00:03 | 0.00 | 55.41 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3800.25 | 04-OCT-16:30 | 0.00 | 121.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5320.66 | 03-NOV-16:00 | 0.00 | 218.72 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6803.45 | 08-DEC-16:10 | 0.00 | 218.72 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1439.60 | 0.00 | 41.56 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7182.47 | 0.00 | 218.72 | 29229.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 352319.46 | 14-JAN-11:01 | 0.00 | 15782.41 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 410457.24 | 18-FEB-00:31 | 0.00 | 2998.80 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 408294.64 | 18-MAR-17:22 | 0.00 | 2630.40 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 388119.32 | 01-APR-11:52 | 0.00 | 3945.60 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 357428.02 | 02-MAY-04:51 | 0.00 | 5997.61 | 949081.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 182023.73 | 20-JUN-16:00 | 0.00 | 4734.72 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 274164.08 | 06-JUL-16:00 | 0.00 | 4734.72 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 368526.43 | 16-AUG-21:13 | 0.00 | 3156.48 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 105179.54 | 01-SEP-00:08 | 0.00 | 1199.52 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 352731.47 | 28-OCT-17:35 | 0.00 | 2630.40 | 1898162.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 408063.95 | 21-NOV-22:22 | 0.00 | 5260.80 | 2847243.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 390185.30 | 05-DEC-04:54 | 0.00 | 2998.80 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 105179.54 | 0.00 | 1199.52 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 410457.24 | 0.00 | 15782.41 | 3796325.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.156209E+13 | 1033850.94 | 04-JAN-08:30 | 0.305086E+12 | 1887124.39 | 02-JAN-07:10 |
February | 0.176678E+13 | 1118484.78 | 02-FEB-08:00 | 0.225235E+12 | 1036437.34 | 13-FEB-07:10 |
March | 0.239992E+13 | 1387707.95 | 27-MAR-15:00 | 0.115468E+12 | 460454.47 | 13-MAR-06:10 |
April | 0.272891E+13 | 1585456.00 | 07-APR-15:39 | 0.601997E+11 | 293028.81 | 03-APR-05:10 |
May | 0.176400E+13 | 1318012.51 | 31-MAY-15:30 | 0.495365E+11 | 178015.04 | 01-MAY-05:10 |
June | 0.234668E+13 | 1537290.18 | 01-JUN-15:39 | 0.462350E+11 | 209678.40 | 23-JUN-03:00 |
July | 0.290414E+13 | 1677038.69 | 13-JUL-15:09 | 0.420973E+11 | 156992.12 | 15-JUL-03:00 |
August | 0.335598E+13 | 1850033.16 | 02-AUG-15:09 | 0.458939E+11 | 226835.71 | 26-AUG-03:49 |
September | 0.183727E+13 | 1395763.18 | 01-SEP-14:09 | 0.426814E+11 | 169869.94 | 04-SEP-00:20 |
October | 0.214110E+13 | 1478041.53 | 04-OCT-15:20 | 0.491317E+11 | 179099.46 | 07-OCT-03:49 |
November | 0.231782E+13 | 1360127.14 | 10-NOV-08:30 | 0.106167E+12 | 612582.79 | 24-NOV-07:10 |
December | 0.272793E+13 | 1447413.61 | 15-DEC-16:30 | 0.176759E+12 | 617883.87 | 07-DEC-05:10 |
Annual Sum or Average | 0.278526E+14 | 0.126449E+13 | ||||
Minimum of Months | 0.156209E+13 | 1033850.94 | 0.420973E+11 | 156992.12 | ||
Maximum of Months | 0.335598E+13 | 1850033.16 | 0.305086E+12 | 1887124.39 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.256443E+12 | 0.477370E+11 | 0.811612E+12 | 0.166493E+12 | 0.159763E+12 | 0.132097E+11 | 0.00 | 0.862541E+11 | 0.986583E+10 | 0.465304E+10 | 0.606004E+10 | 0.00 | 0.00 |
February | 0.231191E+12 | 0.392621E+11 | 0.102011E+13 | 0.150388E+12 | 0.145470E+12 | 0.148080E+11 | 0.00 | 0.140420E+12 | 0.138330E+11 | 0.536295E+10 | 0.594174E+10 | 0.00 | 0.00 |
March | 0.273193E+12 | 0.381727E+11 | 0.146224E+13 | 0.166684E+12 | 0.167459E+12 | 0.162728E+11 | 0.00 | 0.222677E+12 | 0.451178E+11 | 0.377615E+10 | 0.432826E+10 | 0.00 | 0.00 |
April | 0.243507E+12 | 0.316381E+11 | 0.170426E+13 | 0.161103E+12 | 0.164299E+12 | 0.247935E+11 | 0.00 | 0.301906E+12 | 0.939592E+11 | 0.189198E+10 | 0.154471E+10 | 0.00 | 0.00 |
May | 0.262157E+12 | 0.286868E+11 | 0.820095E+12 | 0.166588E+12 | 0.174804E+12 | 0.463029E+11 | 0.00 | 0.177528E+12 | 0.866043E+11 | 0.731967E+09 | 0.502929E+09 | 0.00 | 0.00 |
June | 0.260494E+12 | 0.257743E+11 | 0.110647E+13 | 0.161283E+12 | 0.179029E+12 | 0.687005E+11 | 0.00 | 0.375456E+12 | 0.164146E+12 | 67512988.08 | 0.526167E+10 | 0.00 | 0.00 |
July | 0.244276E+12 | 0.272751E+11 | 0.143833E+13 | 0.166407E+12 | 0.187340E+12 | 0.826121E+11 | 0.00 | 0.553408E+12 | 0.197499E+12 | 0.00 | 0.699610E+10 | 0.00 | 0.00 |
August | 0.272032E+12 | 0.306012E+11 | 0.177907E+13 | 0.166683E+12 | 0.199354E+12 | 0.858878E+11 | 0.00 | 0.631127E+12 | 0.185077E+12 | 50624276.71 | 0.609296E+10 | 0.00 | 0.00 |
September | 0.243842E+12 | 0.346131E+11 | 0.784429E+12 | 0.161103E+12 | 0.173496E+12 | 0.575618E+11 | 0.00 | 0.244831E+12 | 0.134236E+12 | 0.111337E+09 | 0.304732E+10 | 0.00 | 0.00 |
October | 0.254059E+12 | 0.412800E+11 | 0.112844E+13 | 0.166492E+12 | 0.175932E+12 | 0.382301E+11 | 0.00 | 0.236095E+12 | 0.976951E+11 | 0.128383E+10 | 0.159205E+10 | 0.00 | 0.00 |
November | 0.252890E+12 | 0.447945E+11 | 0.140306E+13 | 0.161177E+12 | 0.159898E+12 | 0.164959E+11 | 0.00 | 0.217777E+12 | 0.561510E+11 | 0.264929E+10 | 0.292421E+10 | 0.00 | 0.00 |
December | 0.248642E+12 | 0.489050E+11 | 0.175516E+13 | 0.166409E+12 | 0.161159E+12 | 0.132871E+11 | 0.00 | 0.276042E+12 | 0.480010E+11 | 0.482566E+10 | 0.550060E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.304273E+13 | 0.438740E+12 | 0.152133E+14 | 0.196081E+13 | 0.204800E+13 | 0.478162E+12 | 0.00 | 0.346352E+13 | 0.113219E+13 | 0.254043E+11 | 0.497926E+11 | ||
Minimum of Months | 0.231191E+12 | 0.257743E+11 | 0.784429E+12 | 0.150388E+12 | 0.145470E+12 | 0.132097E+11 | 0.00 | 0.862541E+11 | 0.986583E+10 | 0.00 | 0.502929E+09 | 0.00 | 0.00 |
Maximum of Months | 0.273193E+12 | 0.489050E+11 | 0.177907E+13 | 0.166684E+12 | 0.199354E+12 | 0.858878E+11 | 0.00 | 0.631127E+12 | 0.197499E+12 | 0.536295E+10 | 0.699610E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.252727E+12 | 0.00 | 0.523589E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.177227E+12 | 0.00 | 0.480075E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.604177E+11 | 0.00 | 0.550504E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125196E+11 | 0.00 | 0.476801E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.196331E+10 | 0.00 | 0.475732E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.240060E+10 | 0.00 | 0.438344E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.206238E+10 | 0.00 | 0.400350E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.312668E+10 | 0.00 | 0.427672E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.243274E+10 | 0.00 | 0.402487E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.499114E+10 | 0.00 | 0.441405E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.597982E+11 | 0.00 | 0.463687E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.127617E+12 | 0.00 | 0.491415E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.707284E+12 | 0.557206E+12 | |||||
Minimum of Months | 0.00 | 0.00 | 0.196331E+10 | 0.00 | 0.400350E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.252727E+12 | 0.00 | 0.550504E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 279851.83 | 02-JAN-16:40 | 36729.40 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 126332.05 | 03-JAN-08:20 | 96195.41 | 02-JAN-06:19 | 31091.94 | 02-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 275662.73 | 15-FEB-16:00 | 36729.40 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 126326.37 | 28-FEB-08:20 | 145251.41 | 03-FEB-10:50 | 30284.12 | 06-FEB-04:10 | 0.00 | 01-FEB-00:10 |
March | 265892.64 | 02-MAR-16:00 | 36729.40 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 126326.98 | 16-MAR-07:19 | 123530.53 | 29-MAR-15:20 | 31075.95 | 27-MAR-12:00 | 0.00 | 01-MAR-00:10 |
April | 260098.78 | 14-APR-07:10 | 36729.40 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 126324.19 | 14-APR-07:19 | 118693.03 | 28-APR-14:00 | 48999.88 | 07-APR-16:49 | 0.00 | 01-APR-00:10 |
May | 259675.04 | 01-MAY-07:10 | 36729.40 | 01-MAY-18:49 | 439129.89 | 01-MAY-07:10 | 126323.94 | 01-MAY-07:19 | 151017.20 | 30-MAY-14:09 | 51363.22 | 30-MAY-11:09 | 0.00 | 01-MAY-00:10 |
June | 259675.04 | 01-JUN-07:10 | 36729.40 | 01-JUN-19:19 | 557421.28 | 01-JUN-07:10 | 126323.94 | 01-JUN-07:19 | 170980.44 | 01-JUN-15:39 | 55297.33 | 01-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 259675.04 | 03-JUL-07:10 | 36729.40 | 01-JUL-19:30 | 675712.68 | 03-JUL-07:10 | 126323.94 | 03-JUL-07:19 | 148406.00 | 11-JUL-15:39 | 51858.77 | 24-JUL-07:00 | 0.00 | 01-JUL-00:10 |
August | 259882.32 | 16-AUG-07:10 | 36729.40 | 01-AUG-19:10 | 794004.08 | 01-AUG-07:10 | 126324.06 | 16-AUG-07:19 | 167038.40 | 30-AUG-13:30 | 54492.15 | 24-AUG-16:00 | 0.00 | 01-AUG-00:10 |
September | 263359.91 | 27-SEP-07:10 | 36729.40 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 126326.05 | 27-SEP-07:19 | 192923.61 | 01-SEP-14:09 | 55529.08 | 01-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 270170.19 | 31-OCT-15:00 | 36729.40 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 126329.22 | 06-OCT-07:19 | 118318.25 | 04-OCT-15:20 | 52545.45 | 05-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 279851.83 | 06-NOV-16:49 | 36729.40 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 126330.12 | 30-NOV-08:20 | 103871.20 | 01-NOV-14:00 | 30471.77 | 04-NOV-12:30 | 0.00 | 01-NOV-00:10 |
December | 279851.83 | 01-DEC-16:30 | 36729.40 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 126330.38 | 11-DEC-08:20 | 101406.15 | 21-DEC-13:09 | 30108.40 | 30-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 259675.04 | 36729.40 | 439129.89 | 126323.94 | 96195.41 | 30108.40 | 0.00 | |||||||
Maximum of Months | 279851.83 | 36729.40 | 794004.08 | 126332.05 | 192923.61 | 55529.08 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum}[W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum}[W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum}[W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 96051.55 | 04-JAN-21:10 | 15234.89 | 18-JAN-02:30 | 38706.79 | 04-JAN-08:30 | 5613.05 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 103064.41 | 10-FEB-20:10 | 17729.01 | 11-FEB-18:19 | 41323.61 | 06-FEB-19:00 | 5613.05 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 194262.97 | 27-MAR-15:00 | 53792.65 | 27-MAR-13:09 | 20800.75 | 04-MAR-18:40 | 5613.05 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 251202.05 | 07-APR-16:49 | 53238.40 | 08-APR-09:00 | 9509.47 | 01-APR-16:19 | 5613.05 | 01-APR-06:10 | 0.00 | 0.00 |
May | 278704.10 | 30-MAY-13:20 | 89551.59 | 30-MAY-10:20 | 13077.25 | 02-MAY-03:30 | 5613.05 | 19-MAY-17:49 | 0.00 | 0.00 |
June | 341860.81 | 19-JUN-11:00 | 89551.59 | 01-JUN-09:50 | 1989.00 | 02-JUN-19:00 | 5613.05 | 01-JUN-09:39 | 0.00 | 0.00 |
July | 383698.61 | 07-JUL-10:50 | 89551.59 | 01-JUL-07:00 | 0.00 | 01-JUL-00:10 | 5613.05 | 01-JUL-06:10 | 0.00 | 0.00 |
August | 429397.02 | 02-AUG-14:00 | 89551.59 | 01-AUG-05:49 | 4137.29 | 30-AUG-14:50 | 5613.05 | 01-AUG-06:10 | 0.00 | 0.00 |
September | 314706.58 | 01-SEP-14:09 | 89551.59 | 01-SEP-05:49 | 2675.04 | 28-SEP-17:00 | 5613.05 | 01-SEP-06:10 | 0.00 | 0.00 |
October | 306159.90 | 04-OCT-14:00 | 89551.59 | 03-OCT-12:20 | 40328.30 | 28-OCT-17:30 | 5613.05 | 03-OCT-11:39 | 0.00 | 0.00 |
November | 152212.14 | 03-NOV-13:00 | 51004.41 | 10-NOV-09:00 | 19255.66 | 22-NOV-22:30 | 5613.05 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 113400.69 | 15-DEC-15:39 | 42986.35 | 17-DEC-14:00 | 10977.59 | 30-DEC-17:30 | 5613.05 | 01-DEC-07:10 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||
Minimum of Months | 96051.55 | 15234.89 | 0.00 | 5613.05 | 0.00 | 0.00 | ||||
Maximum of Months | 429397.02 | 89551.59 | 41323.61 | 5613.05 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1033850.94 | 04-JAN-08:30 | 259675.04 | 439129.89 | 0.00 | 126324.29 | 71799.51 | 16756.49 | 0.00 | 70239.62 | 5606.27 |
February | 1118484.78 | 02-FEB-08:00 | 259675.04 | 557421.28 | 0.00 | 126323.94 | 72818.03 | 30049.56 | 0.00 | 59552.15 | 6399.33 |
March | 1387707.95 | 27-MAR-15:00 | 259675.04 | 675712.68 | 0.00 | 89544.55 | 84815.98 | 30951.08 | 0.00 | 194262.97 | 52745.65 |
April | 1585456.00 | 07-APR-15:39 | 259675.04 | 794004.08 | 0.00 | 89544.55 | 109071.37 | 33812.61 | 0.00 | 246225.89 | 53122.48 |
May | 1318012.51 | 31-MAY-15:30 | 259675.04 | 439129.89 | 0.00 | 89544.55 | 118123.02 | 51035.43 | 0.00 | 265339.95 | 89551.59 |
June | 1537290.18 | 01-JUN-15:39 | 259675.04 | 557421.28 | 0.00 | 89544.55 | 170980.44 | 53816.60 | 0.00 | 316300.68 | 89551.59 |
July | 1677038.69 | 13-JUL-15:09 | 259675.04 | 675712.68 | 0.00 | 89544.55 | 127614.96 | 50730.71 | 0.00 | 378596.12 | 89551.59 |
August | 1850033.16 | 02-AUG-15:09 | 259675.04 | 794004.08 | 0.00 | 89544.55 | 132378.49 | 51160.23 | 0.00 | 428106.14 | 89551.59 |
September | 1395763.18 | 01-SEP-14:09 | 259675.04 | 439129.89 | 0.00 | 40505.36 | 192923.61 | 55529.08 | 0.00 | 314706.58 | 89551.59 |
October | 1478041.53 | 04-OCT-15:20 | 259675.04 | 557421.28 | 0.00 | 89544.55 | 118318.25 | 52162.97 | 0.00 | 305754.80 | 89551.59 |
November | 1360127.14 | 10-NOV-08:30 | 259675.04 | 675712.68 | 0.00 | 126323.94 | 78998.11 | 30210.92 | 0.00 | 138575.54 | 50630.92 |
December | 1447413.61 | 15-DEC-16:30 | 279851.83 | 794004.08 | 36729.40 | 89553.82 | 80004.91 | 30045.61 | 0.00 | 111624.47 | 19321.36 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1033850.94 | 259675.04 | 439129.89 | 0.00 | 40505.36 | 71799.51 | 16756.49 | 0.00 | 59552.15 | 5606.27 | |
Maximum of Months | 1850033.16 | 279851.83 | 794004.08 | 36729.40 | 126324.29 | 192923.61 | 55529.08 | 0.00 | 428106.14 | 89551.59 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 1881428.52 | 02-JAN-07:10 | 0.00 | 81935.08 | 25-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 1030741.47 | 13-FEB-07:10 | 0.00 | 81806.18 | 28-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 454758.60 | 13-MAR-06:10 | 0.00 | 79768.87 | 10-MAR-13:39 | 0.00 |
April | 0.00 | 0.00 | 287332.94 | 03-APR-05:10 | 0.00 | 77282.14 | 04-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 172319.17 | 01-MAY-05:10 | 0.00 | 74766.58 | 01-MAY-11:20 | 0.00 |
June | 0.00 | 0.00 | 203982.53 | 23-JUN-03:00 | 0.00 | 70379.55 | 07-JUN-11:39 | 0.00 |
July | 0.00 | 0.00 | 151296.25 | 15-JUL-03:00 | 0.00 | 67254.81 | 05-JUL-11:50 | 0.00 |
August | 0.00 | 0.00 | 221139.84 | 26-AUG-03:49 | 0.00 | 66278.68 | 31-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 164174.07 | 04-SEP-00:20 | 0.00 | 68545.30 | 27-SEP-11:39 | 0.00 |
October | 0.00 | 0.00 | 173403.59 | 07-OCT-03:49 | 0.00 | 72564.56 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 606886.92 | 24-NOV-07:10 | 0.00 | 78028.82 | 22-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 612188.00 | 07-DEC-05:10 | 0.00 | 79756.82 | 11-DEC-12:50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 151296.25 | 0.00 | 66278.68 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1881428.52 | 0.00 | 81935.08 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.86 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.38 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 26.12 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.25 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.86 | 1.00 | 27.94 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.61 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 | 26.83 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 26.78 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 26.83 | 0.50 | 27.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.83 | 0.83 | 27.77 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.85 | 1.67 | 28.36 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.45 | 0.83 | 27.35 |
Annual Sum or Average | 0.00 | 0.00 | 87.00 | 26.69 | 4.83 | 27.94 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.86 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 26.86 | 1.67 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.57 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.16 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.61 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 1.67 | 25.65 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 26.16 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.33 | 19.57 | 1.50 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.33 | 19.57 | 1.50 | 19.99 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.57 | 1.50 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 18.74 | 0.50 | 19.88 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1.67 | 18.90 | 0.17 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.17 | 19.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 18.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 19.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 5.67 | 18.79 | 0.67 | 19.96 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 19.44 | 0.50 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.43 | 1.17 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.80 | 2.33 | 27.80 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.63 | 1.00 | 27.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.76 | 2.33 | 27.76 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.53 | 0.67 | 27.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.90 | 2.17 | 27.90 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.17 | 19.42 | 0.00 | 9.83 | 27.72 | 9.83 | 27.72 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.42 | 0.00 | 0.00 | 2.33 | 27.90 | 2.33 | 27.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.17 | 19.09 | 0.00 | 0.00 | 2.00 | 25.05 | 2.00 | 25.05 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 24.72 | 6.67 | 24.72 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 26.57 | 1.50 | 26.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.00 | 25.79 | 9.00 | 25.79 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 25.25 | 24.83 | 25.25 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 24.98 | 10.67 | 24.98 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 25.31 | 9.33 | 25.31 |
Annual Sum or Average | 0.33 | 19.15 | 0.00 | 64.00 | 25.26 | 64.00 | 25.26 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 19.22 | 0.00 | 0.00 | 24.83 | 26.57 | 24.83 | 26.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.50 | 1.17 | 27.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 27.27 | 3.50 | 28.01 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 2.17 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 27.23 | 3.50 | 27.95 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.08 | 6.50 | 27.98 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 26.96 | 5.33 | 28.01 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.65 | 2.17 | 28.12 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.59 | 2.00 | 27.59 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
Annual Sum or Average | 0.00 | 0.00 | 75.50 | 27.15 | 26.67 | 27.92 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.33 | 27.69 | 6.50 | 28.12 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.50 | 17.16 | 7.00 | 17.37 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13.00 | 17.93 | 3.00 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.67 | 19.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 19.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.00 | 17.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 37.33 | 17.56 | 10.00 | 18.12 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.50 | 19.18 | 7.00 | 19.85 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.50 | 16.27 | 2.83 | 15.05 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5.83 | 17.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 19.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.72 | 2.17 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.73 | 1.00 | 27.73 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.85 | 3.00 | 27.85 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.60 | 1.83 | 27.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.74 | 2.33 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2.17 | 17.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 21.83 | 16.82 | 2.83 | 15.05 | 10.33 | 27.74 | 10.33 | 27.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 19.14 | 2.83 | 15.05 | 3.00 | 27.85 | 3.00 | 27.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 14.17 | 17.25 | 3.83 | 18.22 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6.00 | 17.73 | 0.67 | 19.83 | 4.33 | 24.73 | 4.33 | 24.73 |
March | 0.50 | 19.30 | 0.00 | 0.00 | 7.50 | 24.79 | 7.50 | 24.79 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 25.36 | 4.67 | 25.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 25.38 | 21.83 | 25.38 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 41.83 | 25.14 | 41.83 | 25.14 |
November | 0.33 | 19.00 | 0.00 | 0.00 | 9.67 | 25.13 | 9.67 | 25.13 |
December | 0.83 | 19.25 | 0.00 | 0.00 | 2.33 | 25.35 | 2.33 | 25.35 |
Annual Sum or Average | 21.83 | 17.53 | 4.50 | 18.46 | 92.17 | 25.16 | 92.17 | 25.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 14.17 | 19.30 | 3.83 | 19.83 | 41.83 | 25.38 | 41.83 | 25.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 11.67 | 16.22 | 3.00 | 15.07 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.83 | 17.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.33 | 19.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.80 | 0.50 | 27.88 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.44 | 1.33 | 27.44 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.86 | 2.17 | 27.93 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.84 | 3.17 | 27.97 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.57 | 1.67 | 28.05 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.86 | 1.67 | 27.87 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 19.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.33 | 16.76 | 3.00 | 15.07 | 15.00 | 27.76 | 10.50 | 27.89 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 11.67 | 19.28 | 3.00 | 15.07 | 5.00 | 27.86 | 3.17 | 28.05 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.33 | 16.83 | 17.17 | 17.62 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 45.33 | 16.87 | 17.83 | 17.50 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7.50 | 18.71 | 1.17 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1.00 | 19.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11.00 | 17.80 | 2.50 | 19.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 19.67 | 17.60 | 5.50 | 17.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 137.83 | 17.15 | 44.17 | 17.64 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 53.33 | 19.08 | 17.83 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.50 | 15.80 | 7.33 | 15.20 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23.83 | 16.05 | 5.00 | 15.19 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.00 | 18.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 18.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.73 | 2.00 | 27.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.66 | 1.00 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.81 | 4.50 | 27.81 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.63 | 2.83 | 27.63 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.77 | 1.67 | 27.77 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.17 | 17.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 14.67 | 16.59 | 2.83 | 14.75 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 81.83 | 16.26 | 15.17 | 15.11 | 12.00 | 27.74 | 12.00 | 27.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.50 | 18.95 | 7.33 | 15.20 | 4.50 | 27.81 | 4.50 | 27.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.33 | 16.77 | 7.83 | 17.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 24.67 | 17.00 | 6.33 | 18.12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4.00 | 18.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 19.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.44 | 2.00 | 27.44 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 26.42 | 3.17 | 26.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 | 25.73 | 11.83 | 25.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 15.33 | 25.06 | 15.33 | 25.06 |
November | 5.00 | 18.60 | 0.67 | 20.30 | 2.50 | 24.87 | 2.50 | 24.87 |
December | 11.50 | 17.63 | 1.33 | 17.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78.17 | 17.20 | 16.17 | 17.92 | 35.00 | 25.54 | 34.83 | 25.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 32.33 | 19.00 | 7.83 | 20.30 | 15.33 | 27.44 | 15.33 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.17 | 15.89 | 4.50 | 14.76 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16.67 | 16.26 | 3.67 | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.50 | 18.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 19.29 | 0.00 | 0.00 | 0.67 | 27.81 | 0.50 | 27.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.47 | 1.50 | 27.47 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.98 | 2.17 | 28.09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.97 | 3.83 | 28.06 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.88 | 2.33 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.90 | 1.83 | 27.93 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.33 | 18.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.00 | 17.37 | 1.50 | 14.92 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 54.33 | 16.59 | 9.67 | 14.85 | 17.00 | 27.89 | 12.17 | 27.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.17 | 19.29 | 4.50 | 14.93 | 5.83 | 27.98 | 3.83 | 28.09 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 120.00 | 28.21 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 735.17 | 29.20 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.61 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 858.17 | 29.05 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 735.17 | 29.20 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 77.00 | 28.15 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 731.83 | 29.14 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 808.83 | 29.05 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 731.83 | 29.14 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 57.50 | 28.16 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 691.33 | 29.07 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 748.83 | 29.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 691.33 | 29.07 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 28.58 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.65 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 28.28 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.60 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.78 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 131.17 | 28.07 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 29.50 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.94 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.80 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 139.67 | 28.08 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 131.17 | 29.50 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 240.17 | 23.91 | 62.17 | 25.54 | 0.00 | 0.00 |
February | 270.00 | 23.93 | 51.83 | 26.24 | 0.00 | 0.00 |
March | 115.00 | 24.01 | 98.00 | 25.59 | 0.00 | 0.00 |
April | 39.33 | 24.01 | 148.33 | 25.41 | 0.00 | 0.00 |
May | 31.83 | 24.07 | 277.83 | 24.82 | 25.50 | 24.07 |
June | 152.00 | 24.78 | 438.17 | 24.49 | 152.00 | 24.78 |
July | 238.83 | 25.18 | 497.00 | 24.58 | 238.83 | 25.18 |
August | 114.67 | 25.09 | 476.00 | 24.50 | 114.67 | 25.09 |
September | 61.67 | 25.12 | 391.33 | 24.66 | 61.67 | 25.12 |
October | 52.00 | 24.39 | 341.50 | 24.84 | 22.33 | 24.88 |
November | 42.67 | 24.13 | 144.83 | 25.81 | 1.67 | 26.84 |
December | 146.00 | 24.02 | 90.83 | 26.42 | 0.00 | 0.00 |
Annual Sum or Average | 1504.17 | 24.39 | 3017.83 | 24.85 | 616.67 | 25.01 |
Minimum of Months | 31.83 | 23.91 | 51.83 | 24.49 | 0.00 | 0.00 |
Maximum of Months | 270.00 | 25.18 | 497.00 | 26.42 | 238.83 | 26.84 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 309.50 | 23.87 | 44.17 | 24.64 | 0.00 | 0.00 |
February | 265.33 | 23.91 | 18.00 | 25.80 | 0.00 | 0.00 |
March | 102.00 | 23.98 | 98.83 | 25.24 | 0.00 | 0.00 |
April | 26.83 | 23.98 | 162.50 | 24.82 | 0.00 | 0.00 |
May | 25.00 | 23.68 | 263.00 | 24.44 | 0.00 | 0.00 |
June | 1.00 | 23.59 | 416.17 | 24.24 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 470.50 | 24.15 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 471.50 | 24.11 | 0.00 | 0.00 |
September | 9.83 | 23.71 | 371.17 | 24.37 | 0.00 | 0.00 |
October | 41.67 | 24.01 | 312.17 | 24.52 | 0.00 | 0.00 |
November | 51.50 | 23.98 | 136.17 | 25.49 | 0.00 | 0.00 |
December | 137.83 | 23.99 | 71.33 | 25.95 | 0.00 | 0.00 |
Annual Sum or Average | 970.50 | 23.92 | 2835.50 | 24.46 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 18.00 | 24.11 | 0.00 | 0.00 |
Maximum of Months | 309.50 | 24.01 | 471.50 | 25.95 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.17 | 22.52 | 49.67 | 19.84 | 49.67 | 19.84 |
February | 452.00 | 23.07 | 6.50 | 21.04 | 6.50 | 21.04 |
March | 414.83 | 23.56 | 8.83 | 23.99 | 0.00 | 0.00 |
April | 248.33 | 23.58 | 49.67 | 24.66 | 0.00 | 0.00 |
May | 119.33 | 23.50 | 156.50 | 24.29 | 0.00 | 0.00 |
June | 41.33 | 23.27 | 295.00 | 24.29 | 0.00 | 0.00 |
July | 34.67 | 23.15 | 299.83 | 24.27 | 0.00 | 0.00 |
August | 26.33 | 23.31 | 314.83 | 24.29 | 0.00 | 0.00 |
September | 63.83 | 23.35 | 236.50 | 24.32 | 0.00 | 0.00 |
October | 128.50 | 23.68 | 177.00 | 24.32 | 0.00 | 0.00 |
November | 316.33 | 23.41 | 49.17 | 24.66 | 0.00 | 0.00 |
December | 487.33 | 23.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2829.00 | 23.23 | 1643.50 | 24.17 | 56.17 | 19.97 |
Minimum of Months | 26.33 | 22.52 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 496.17 | 23.68 | 314.83 | 24.66 | 49.67 | 21.04 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.21 | 165.00 | 19.66 | 165.00 | 19.66 |
February | 454.00 | 21.49 | 144.67 | 20.24 | 144.67 | 20.24 |
March | 487.17 | 22.52 | 26.67 | 20.64 | 26.67 | 20.64 |
April | 347.50 | 22.89 | 43.33 | 23.63 | 8.33 | 20.62 |
May | 183.83 | 23.35 | 134.33 | 24.16 | 0.00 | 0.00 |
June | 40.33 | 23.41 | 321.83 | 24.27 | 0.00 | 0.00 |
July | 8.50 | 23.28 | 361.83 | 24.29 | 0.00 | 0.00 |
August | 8.17 | 23.45 | 358.83 | 24.28 | 0.00 | 0.00 |
September | 111.83 | 23.22 | 226.83 | 24.19 | 0.00 | 0.00 |
October | 288.83 | 23.09 | 124.50 | 24.09 | 0.00 | 0.00 |
November | 459.00 | 22.32 | 70.83 | 20.68 | 65.33 | 20.40 |
December | 497.00 | 21.59 | 127.33 | 20.11 | 127.33 | 20.11 |
Annual Sum or Average | 3388.17 | 22.19 | 2106.00 | 23.18 | 537.33 | 20.08 |
Minimum of Months | 8.17 | 21.21 | 26.67 | 19.66 | 0.00 | 0.00 |
Maximum of Months | 502.00 | 23.45 | 361.83 | 24.29 | 165.00 | 20.64 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 501.83 | 21.98 | 81.17 | 20.68 | 81.17 | 20.68 |
February | 454.00 | 22.18 | 62.33 | 20.77 | 62.33 | 20.77 |
March | 452.17 | 23.16 | 11.33 | 24.09 | 0.00 | 0.00 |
April | 265.17 | 23.48 | 66.67 | 24.27 | 0.00 | 0.00 |
May | 98.33 | 23.65 | 185.17 | 24.29 | 0.00 | 0.00 |
June | 3.50 | 23.83 | 427.50 | 24.26 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 496.67 | 24.29 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 468.83 | 24.20 | 0.00 | 0.00 |
September | 60.50 | 23.76 | 316.67 | 24.30 | 3.67 | 26.03 |
October | 184.33 | 23.55 | 176.67 | 24.20 | 0.00 | 0.00 |
November | 378.17 | 23.19 | 19.67 | 24.28 | 0.00 | 0.00 |
December | 490.83 | 22.89 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2888.83 | 22.84 | 2312.67 | 24.04 | 147.17 | 20.85 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 501.83 | 23.83 | 496.67 | 24.30 | 81.17 | 26.03 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.83 | 21.86 | 85.33 | 20.67 | 85.33 | 20.67 |
February | 446.83 | 22.14 | 50.00 | 20.83 | 49.50 | 20.78 |
March | 421.17 | 22.81 | 11.33 | 24.71 | 0.00 | 0.00 |
April | 277.50 | 23.09 | 89.67 | 24.45 | 2.00 | 26.53 |
May | 118.50 | 23.57 | 233.17 | 24.49 | 7.33 | 26.83 |
June | 16.17 | 24.08 | 388.00 | 24.29 | 3.50 | 26.58 |
July | 11.33 | 26.73 | 451.50 | 24.29 | 11.33 | 26.73 |
August | 9.50 | 24.54 | 436.67 | 24.16 | 3.50 | 26.52 |
September | 84.00 | 23.81 | 317.83 | 24.43 | 13.67 | 26.55 |
October | 195.00 | 23.33 | 183.67 | 24.28 | 1.33 | 26.45 |
November | 380.67 | 22.85 | 15.00 | 24.34 | 1.67 | 20.86 |
December | 491.17 | 22.41 | 5.67 | 20.74 | 5.67 | 20.74 |
Annual Sum or Average | 2952.67 | 22.63 | 2267.83 | 24.09 | 184.83 | 22.08 |
Minimum of Months | 9.50 | 21.86 | 5.67 | 20.67 | 0.00 | 0.00 |
Maximum of Months | 500.83 | 26.73 | 451.50 | 24.71 | 85.33 | 26.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 444.83 | 21.89 | 102.00 | 20.81 | 92.17 | 20.35 |
February | 381.83 | 22.31 | 70.17 | 21.76 | 55.67 | 20.72 |
March | 372.67 | 22.91 | 40.67 | 24.35 | 1.17 | 21.00 |
April | 259.83 | 23.20 | 85.83 | 24.37 | 0.00 | 0.00 |
May | 117.50 | 23.50 | 180.50 | 24.33 | 0.00 | 0.00 |
June | 8.33 | 23.73 | 421.17 | 24.27 | 0.00 | 0.00 |
July | 2.67 | 26.30 | 495.83 | 24.33 | 2.67 | 26.30 |
August | 5.00 | 26.64 | 486.67 | 24.26 | 5.00 | 26.64 |
September | 53.33 | 24.41 | 376.33 | 24.44 | 15.17 | 26.63 |
October | 118.00 | 23.82 | 294.00 | 24.55 | 9.17 | 26.85 |
November | 301.67 | 22.96 | 76.50 | 24.37 | 4.17 | 20.80 |
December | 400.00 | 22.59 | 32.83 | 24.53 | 8.50 | 21.35 |
Annual Sum or Average | 2465.67 | 22.74 | 2662.50 | 24.15 | 193.67 | 21.56 |
Minimum of Months | 2.67 | 21.89 | 32.83 | 20.81 | 0.00 | 0.00 |
Maximum of Months | 444.83 | 26.64 | 495.83 | 24.55 | 92.17 | 26.85 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.83 | 22.40 | 19.67 | 21.06 | 18.33 | 20.72 |
February | 382.50 | 22.93 | 12.50 | 24.64 | 4.00 | 21.00 |
March | 140.50 | 23.76 | 120.67 | 24.77 | 2.50 | 26.72 |
April | 24.50 | 25.58 | 270.33 | 24.81 | 14.17 | 26.84 |
May | 19.00 | 24.91 | 349.17 | 24.49 | 8.17 | 26.65 |
June | 23.50 | 26.75 | 479.67 | 24.49 | 23.50 | 26.75 |
July | 45.83 | 26.58 | 497.00 | 24.57 | 45.83 | 26.58 |
August | 38.00 | 26.62 | 514.00 | 24.47 | 38.00 | 26.62 |
September | 17.50 | 26.15 | 410.83 | 24.47 | 13.33 | 26.92 |
October | 40.17 | 24.11 | 327.50 | 24.53 | 4.00 | 26.66 |
November | 136.67 | 23.63 | 125.50 | 25.00 | 0.67 | 26.63 |
December | 215.33 | 23.74 | 40.33 | 25.91 | 0.00 | 0.00 |
Annual Sum or Average | 1558.33 | 23.40 | 3167.17 | 24.56 | 172.50 | 25.91 |
Minimum of Months | 17.50 | 22.40 | 12.50 | 21.06 | 0.00 | 0.00 |
Maximum of Months | 474.83 | 26.75 | 514.00 | 25.91 | 45.83 | 26.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 332.67 | 19.88 | 332.67 | 19.88 |
February | 454.00 | 20.53 | 318.00 | 20.17 | 318.00 | 20.17 |
March | 511.83 | 21.47 | 101.67 | 20.30 | 101.67 | 20.30 |
April | 418.83 | 22.30 | 32.83 | 21.88 | 20.33 | 20.36 |
May | 270.00 | 23.18 | 97.17 | 24.12 | 0.00 | 0.00 |
June | 59.00 | 24.06 | 353.33 | 24.21 | 19.67 | 25.27 |
July | 34.00 | 25.53 | 473.17 | 24.31 | 34.00 | 25.53 |
August | 31.17 | 24.83 | 414.50 | 24.28 | 18.17 | 25.77 |
September | 158.33 | 23.24 | 208.17 | 24.12 | 7.67 | 24.53 |
October | 366.67 | 22.62 | 84.67 | 23.67 | 7.67 | 20.51 |
November | 487.00 | 21.51 | 113.33 | 20.07 | 113.33 | 20.07 |
December | 497.00 | 20.67 | 284.17 | 20.21 | 284.17 | 20.21 |
Annual Sum or Average | 3789.83 | 21.61 | 2813.67 | 22.50 | 1257.33 | 20.44 |
Minimum of Months | 31.17 | 20.33 | 32.83 | 19.88 | 0.00 | 0.00 |
Maximum of Months | 511.83 | 25.53 | 473.17 | 24.31 | 332.67 | 25.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.24 | 280.00 | 19.72 | 280.00 | 19.72 |
February | 385.00 | 20.64 | 225.17 | 20.06 | 225.17 | 20.06 |
March | 423.33 | 21.61 | 74.17 | 20.23 | 73.50 | 20.18 |
April | 305.83 | 22.26 | 57.83 | 24.41 | 5.17 | 20.32 |
May | 203.00 | 23.08 | 130.50 | 24.77 | 6.50 | 26.83 |
June | 58.67 | 24.08 | 291.83 | 24.41 | 18.00 | 26.03 |
July | 49.33 | 26.14 | 375.00 | 24.53 | 47.33 | 26.26 |
August | 35.50 | 25.52 | 364.67 | 24.42 | 26.17 | 26.26 |
September | 141.33 | 23.30 | 206.33 | 24.50 | 16.50 | 25.80 |
October | 280.83 | 22.66 | 86.50 | 24.10 | 2.17 | 20.27 |
November | 413.17 | 21.51 | 93.33 | 20.03 | 93.33 | 20.03 |
December | 422.00 | 20.69 | 225.00 | 20.14 | 225.00 | 20.14 |
Annual Sum or Average | 3145.00 | 21.66 | 2410.33 | 22.80 | 1018.83 | 20.68 |
Minimum of Months | 35.50 | 20.24 | 57.83 | 19.72 | 2.17 | 19.72 |
Maximum of Months | 427.00 | 26.14 | 375.00 | 24.77 | 280.00 | 26.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 463.67 | 20.94 | 201.17 | 19.73 | 196.67 | 19.62 |
February | 398.67 | 21.47 | 163.00 | 20.71 | 147.83 | 20.20 |
March | 414.67 | 21.99 | 81.67 | 21.99 | 51.17 | 20.51 |
April | 346.17 | 22.45 | 64.00 | 23.73 | 10.33 | 20.13 |
May | 224.50 | 23.17 | 120.17 | 24.28 | 0.00 | 0.00 |
June | 51.00 | 24.24 | 362.67 | 24.25 | 19.67 | 25.51 |
July | 36.67 | 25.73 | 479.33 | 24.37 | 36.67 | 25.73 |
August | 27.67 | 25.83 | 463.83 | 24.36 | 24.67 | 26.11 |
September | 86.00 | 23.81 | 335.17 | 24.42 | 19.50 | 26.06 |
October | 174.67 | 23.32 | 255.00 | 24.63 | 11.33 | 26.60 |
November | 372.17 | 22.12 | 90.67 | 22.08 | 48.83 | 20.06 |
December | 431.67 | 21.55 | 148.00 | 20.87 | 132.00 | 20.26 |
Annual Sum or Average | 3027.50 | 22.10 | 2764.67 | 23.48 | 698.67 | 20.98 |
Minimum of Months | 27.67 | 20.94 | 64.00 | 19.73 | 0.00 | 0.00 |
Maximum of Months | 463.67 | 25.83 | 479.33 | 24.63 | 196.67 | 26.60 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.59 | 270.50 | 19.90 | 270.50 | 19.90 |
February | 449.83 | 20.89 | 226.33 | 20.18 | 226.33 | 20.18 |
March | 458.50 | 21.81 | 65.17 | 21.13 | 54.50 | 20.52 |
April | 345.17 | 22.45 | 71.00 | 24.07 | 10.50 | 21.88 |
May | 192.83 | 23.14 | 182.17 | 24.37 | 2.67 | 26.46 |
June | 41.50 | 25.00 | 412.50 | 24.36 | 23.50 | 26.36 |
July | 44.17 | 26.40 | 477.50 | 24.47 | 44.17 | 26.40 |
August | 27.83 | 26.62 | 487.33 | 24.42 | 27.83 | 26.62 |
September | 118.00 | 23.36 | 276.83 | 24.30 | 14.17 | 25.88 |
October | 259.50 | 22.75 | 155.83 | 24.09 | 3.17 | 20.54 |
November | 468.67 | 21.63 | 82.00 | 20.18 | 81.33 | 20.15 |
December | 497.00 | 21.00 | 185.33 | 20.26 | 185.33 | 20.26 |
Annual Sum or Average | 3405.00 | 21.77 | 2892.50 | 23.16 | 944.00 | 20.89 |
Minimum of Months | 27.83 | 20.59 | 65.17 | 19.90 | 2.67 | 19.90 |
Maximum of Months | 502.00 | 26.62 | 487.33 | 24.47 | 270.50 | 26.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.97 | 402.00 | 19.69 | 402.00 | 19.69 |
February | 454.00 | 20.10 | 386.67 | 19.91 | 386.67 | 19.91 |
March | 514.00 | 20.91 | 224.33 | 20.06 | 224.33 | 20.06 |
April | 423.50 | 21.71 | 90.17 | 20.73 | 74.83 | 20.02 |
May | 296.17 | 22.80 | 95.00 | 24.16 | 0.33 | 20.99 |
June | 75.00 | 23.80 | 348.67 | 24.22 | 21.17 | 25.21 |
July | 41.83 | 25.56 | 467.00 | 24.36 | 41.83 | 25.56 |
August | 47.17 | 24.30 | 415.00 | 24.29 | 19.17 | 25.72 |
September | 196.00 | 22.92 | 195.50 | 24.10 | 9.00 | 23.89 |
October | 403.50 | 22.01 | 122.50 | 22.02 | 62.00 | 20.10 |
November | 489.00 | 20.74 | 219.00 | 19.74 | 219.00 | 19.74 |
December | 497.00 | 20.09 | 422.00 | 19.92 | 422.00 | 19.92 |
Annual Sum or Average | 3939.17 | 21.16 | 3387.83 | 21.94 | 1882.33 | 20.14 |
Minimum of Months | 41.83 | 19.97 | 90.17 | 19.69 | 0.33 | 19.69 |
Maximum of Months | 514.00 | 25.56 | 467.00 | 24.36 | 422.00 | 25.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.02 | 379.50 | 19.66 | 379.50 | 19.66 |
February | 454.00 | 20.25 | 354.00 | 19.97 | 354.00 | 19.97 |
March | 507.33 | 21.20 | 148.50 | 19.72 | 148.50 | 19.72 |
April | 366.83 | 21.88 | 113.50 | 22.35 | 53.67 | 20.17 |
May | 239.17 | 22.77 | 176.50 | 24.54 | 8.33 | 26.67 |
June | 72.83 | 23.82 | 364.67 | 24.31 | 19.00 | 25.82 |
July | 62.83 | 25.89 | 456.33 | 24.46 | 56.67 | 26.19 |
August | 44.83 | 25.25 | 449.83 | 24.34 | 29.00 | 26.33 |
September | 170.00 | 23.00 | 250.50 | 24.35 | 16.83 | 25.33 |
October | 344.83 | 22.20 | 132.33 | 23.29 | 27.33 | 20.23 |
November | 489.00 | 20.88 | 186.67 | 19.67 | 186.67 | 19.67 |
December | 497.00 | 20.17 | 372.00 | 19.86 | 372.00 | 19.86 |
Annual Sum or Average | 3750.67 | 21.27 | 3384.33 | 22.32 | 1651.50 | 20.31 |
Minimum of Months | 44.83 | 20.02 | 113.50 | 19.66 | 8.33 | 19.66 |
Maximum of Months | 507.33 | 25.89 | 456.33 | 24.54 | 379.50 | 26.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 483.50 | 20.53 | 275.50 | 19.44 | 275.50 | 19.44 |
February | 426.50 | 20.90 | 239.67 | 19.85 | 239.67 | 19.85 |
March | 438.50 | 21.37 | 160.67 | 20.42 | 142.00 | 19.94 |
April | 367.33 | 21.86 | 114.17 | 21.99 | 62.67 | 20.08 |
May | 255.83 | 22.77 | 115.33 | 24.30 | 0.50 | 22.74 |
June | 71.83 | 23.87 | 356.00 | 24.26 | 21.67 | 25.41 |
July | 50.17 | 25.76 | 473.50 | 24.40 | 48.83 | 25.83 |
August | 39.33 | 25.38 | 452.17 | 24.36 | 28.67 | 26.17 |
September | 130.83 | 23.41 | 305.67 | 24.36 | 22.33 | 25.79 |
October | 220.67 | 22.56 | 226.67 | 24.09 | 26.00 | 21.89 |
November | 412.83 | 21.35 | 150.67 | 20.32 | 130.17 | 19.72 |
December | 460.00 | 20.84 | 252.67 | 19.86 | 249.50 | 19.77 |
Annual Sum or Average | 3357.33 | 21.60 | 3122.67 | 22.70 | 1247.50 | 20.38 |
Minimum of Months | 39.33 | 20.53 | 114.17 | 19.44 | 0.50 | 19.44 |
Maximum of Months | 483.50 | 25.76 | 473.50 | 24.40 | 275.50 | 26.17 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 333.00 | 19.66 | 333.00 | 19.66 |
February | 453.17 | 20.48 | 306.33 | 19.97 | 306.33 | 19.97 |
March | 468.67 | 21.25 | 148.67 | 20.36 | 141.00 | 20.15 |
April | 369.17 | 21.89 | 100.67 | 22.63 | 44.67 | 20.43 |
May | 248.33 | 22.78 | 163.33 | 24.39 | 4.67 | 26.47 |
June | 64.83 | 24.24 | 391.00 | 24.35 | 24.67 | 26.22 |
July | 53.50 | 26.02 | 465.67 | 24.47 | 48.67 | 26.30 |
August | 38.33 | 25.80 | 472.83 | 24.42 | 29.50 | 26.58 |
September | 171.17 | 23.00 | 238.67 | 24.27 | 15.17 | 25.51 |
October | 325.83 | 22.20 | 140.83 | 23.27 | 30.83 | 20.28 |
November | 478.83 | 20.96 | 170.50 | 19.83 | 170.50 | 19.83 |
December | 497.00 | 20.44 | 329.00 | 20.01 | 329.00 | 20.01 |
Annual Sum or Average | 3670.83 | 21.37 | 3260.50 | 22.53 | 1478.00 | 20.45 |
Minimum of Months | 38.33 | 20.20 | 100.67 | 19.66 | 4.67 | 19.66 |
Maximum of Months | 502.00 | 26.02 | 472.83 | 24.47 | 333.00 | 26.58 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.33735 | 21.56606 | 0.30391 | 7.41746 |
February | 454.00000 | 24.36311 | 17.44144 | 0.28447 | 7.17452 |
March | 514.00000 | 24.36523 | 24.97924 | 0.35152 | 7.98590 |
April | 485.00000 | 24.46072 | 31.20565 | 0.41877 | 9.22899 |
May | 508.00000 | 24.45573 | 40.72610 | -0.3755 | 8.81186 |
June | 496.00000 | 24.42941 | 56.21925 | -0.2596 | 7.36652 |
July | 497.00000 | 24.57325 | 62.25564 | -0.1683 | 6.94096 |
August | 514.00000 | 24.45852 | 56.49363 | -0.2326 | 7.28383 |
September | 485.00000 | 24.53174 | 49.86923 | -0.2626 | 7.74806 |
October | 502.00000 | 24.58819 | 40.75350 | 0.53160 | 11.77997 |
November | 489.00000 | 24.56875 | 27.11632 | 0.42496 | 9.47341 |
December | 497.00000 | 24.52475 | 19.68644 | 0.35396 | 8.18728 |
Annual Sum or Average | 5943.00000 | 24.47157 | 37.51639 | 0.11206 | 8.28846 |
Minimum of Months | 454.00000 | 24.33735 | 17.44144 | -0.3755 | 6.94096 |
Maximum of Months | 514.00000 | 24.58819 | 62.25564 | 0.53160 | 11.77997 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.04224 | 25.68728 | 0.25270 | 6.64108 |
February | 454.00000 | 24.19651 | 20.02199 | 0.25990 | 6.66776 |
March | 514.00000 | 24.29651 | 26.48369 | 0.35479 | 7.95944 |
April | 485.00000 | 24.30103 | 32.58694 | 0.41392 | 8.92441 |
May | 508.00000 | 24.21764 | 40.79031 | -0.4233 | 9.24717 |
June | 496.00000 | 24.18626 | 47.10255 | -0.3679 | 8.16434 |
July | 497.00000 | 24.12621 | 49.02877 | -0.3644 | 7.92201 |
August | 514.00000 | 24.10609 | 47.48960 | -0.3684 | 7.93084 |
September | 485.00000 | 24.25579 | 45.33215 | -0.3680 | 8.37442 |
October | 502.00000 | 24.35619 | 38.41447 | 0.46938 | 10.05836 |
November | 489.00000 | 24.46006 | 29.16027 | 0.41174 | 9.15030 |
December | 497.00000 | 24.37748 | 21.66686 | 0.33599 | 7.70229 |
Annual Sum or Average | 5943.00000 | 24.24305 | 35.43017 | 0.04804 | 8.23737 |
Minimum of Months | 454.00000 | 24.04224 | 20.02199 | -0.4233 | 6.64108 |
Maximum of Months | 514.00000 | 24.46006 | 49.02877 | 0.46938 | 10.05836 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.52477 | 27.56628 | -0.1439 | 7.90536 |
February | 454.00000 | 23.06700 | 23.02791 | -0.0335 | 5.80618 |
March | 514.00000 | 23.65671 | 29.20910 | 0.17171 | 6.04377 |
April | 485.00000 | 23.89044 | 34.67863 | 0.28094 | 7.02501 |
May | 508.00000 | 23.97188 | 41.74553 | -0.5326 | 11.45051 |
June | 496.00000 | 24.02343 | 47.98353 | -0.4501 | 9.72136 |
July | 497.00000 | 23.99241 | 50.02696 | -0.4410 | 9.51674 |
August | 514.00000 | 24.05219 | 48.26830 | -0.4273 | 9.26398 |
September | 485.00000 | 24.00160 | 46.36970 | -0.4775 | 10.30485 |
October | 502.00000 | 24.02396 | 39.86654 | 0.36473 | 8.18953 |
November | 489.00000 | 23.71123 | 32.35071 | 0.20427 | 6.64257 |
December | 497.00000 | 23.30194 | 25.55887 | 0.04741 | 5.53134 |
Annual Sum or Average | 5943.00000 | 23.68893 | 37.32627 | -0.1212 | 8.13639 |
Minimum of Months | 454.00000 | 22.52477 | 23.02791 | -0.5326 | 5.53134 |
Maximum of Months | 514.00000 | 24.05219 | 50.02696 | 0.36473 | 11.45051 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.19510 | 29.82732 | -0.4747 | 13.15299 |
February | 454.00000 | 21.47767 | 24.64204 | -0.4329 | 11.11770 |
March | 514.00000 | 22.57963 | 31.74652 | -0.0961 | 6.67245 |
April | 485.00000 | 23.23143 | 36.47158 | 0.11825 | 6.76739 |
May | 508.00000 | 23.80715 | 42.52542 | -0.5864 | 12.95573 |
June | 496.00000 | 24.05337 | 47.73733 | -0.4272 | 9.31520 |
July | 497.00000 | 24.10719 | 49.34349 | -0.3846 | 8.50122 |
August | 514.00000 | 24.11052 | 47.77650 | -0.3924 | 8.67554 |
September | 485.00000 | 23.86074 | 46.81654 | -0.5229 | 11.45110 |
October | 502.00000 | 23.47259 | 41.47886 | 0.22527 | 7.30287 |
November | 489.00000 | 22.40761 | 35.32291 | -0.1233 | 7.52470 |
December | 497.00000 | 21.57709 | 28.59130 | -0.3814 | 9.95471 |
Annual Sum or Average | 5943.00000 | 23.00175 | 38.62357 | -0.2894 | 9.43886 |
Minimum of Months | 454.00000 | 21.19510 | 24.64204 | -0.5864 | 6.67245 |
Maximum of Months | 514.00000 | 24.11052 | 49.34349 | 0.22527 | 13.15299 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.97459 | 25.40888 | -0.2629 | 7.83713 |
February | 454.00000 | 22.17781 | 20.28582 | -0.2436 | 7.46672 |
March | 514.00000 | 23.26027 | 27.35827 | 0.07395 | 5.89566 |
April | 485.00000 | 23.75990 | 32.84390 | 0.25281 | 6.89737 |
May | 508.00000 | 24.03884 | 40.36875 | -0.5034 | 10.80835 |
June | 496.00000 | 24.21856 | 46.89444 | -0.3466 | 7.87388 |
July | 497.00000 | 24.28293 | 48.86742 | -0.2856 | 7.10320 |
August | 514.00000 | 24.17580 | 46.92662 | -0.3306 | 7.53177 |
September | 485.00000 | 24.12947 | 45.42591 | -0.4243 | 9.34449 |
October | 502.00000 | 23.87472 | 38.59474 | 0.32721 | 7.90771 |
November | 489.00000 | 23.39342 | 29.88355 | 0.12184 | 6.27035 |
December | 497.00000 | 22.89579 | 22.66867 | -0.0539 | 5.74946 |
Annual Sum or Average | 5943.00000 | 23.52430 | 35.57401 | -0.1397 | 7.55895 |
Minimum of Months | 454.00000 | 21.97459 | 20.28582 | -0.5034 | 5.74946 |
Maximum of Months | 514.00000 | 24.28293 | 48.86742 | 0.32721 | 10.80835 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.86410 | 25.27141 | -0.2813 | 7.95462 |
February | 454.00000 | 22.18079 | 19.99065 | -0.2330 | 7.41134 |
March | 514.00000 | 23.03722 | 27.32059 | 0.04300 | 6.15409 |
April | 485.00000 | 23.54467 | 32.99902 | 0.22789 | 7.31435 |
May | 508.00000 | 24.06279 | 40.07970 | -0.4468 | 10.75005 |
June | 496.00000 | 24.14933 | 46.85445 | -0.3351 | 8.12196 |
July | 497.00000 | 24.23126 | 48.73845 | -0.2717 | 7.47426 |
August | 514.00000 | 24.09183 | 46.86288 | -0.3125 | 7.67553 |
September | 485.00000 | 24.12703 | 45.14069 | -0.3831 | 9.57234 |
October | 502.00000 | 23.79916 | 38.48943 | 0.33559 | 8.29506 |
November | 489.00000 | 23.12523 | 30.08977 | 0.07118 | 6.32235 |
December | 497.00000 | 22.43173 | 22.88262 | -0.1511 | 6.35524 |
Annual Sum or Average | 5943.00000 | 23.39557 | 35.50759 | -0.1449 | 7.78647 |
Minimum of Months | 454.00000 | 21.86410 | 19.99065 | -0.4468 | 6.15409 |
Maximum of Months | 514.00000 | 24.23126 | 48.73845 | 0.33559 | 10.75005 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.14875 | 25.03224 | -0.2123 | 8.67101 |
February | 454.00000 | 22.64367 | 19.52181 | -0.1193 | 7.82086 |
March | 514.00000 | 23.24033 | 26.93885 | 0.09511 | 6.60869 |
April | 485.00000 | 23.63266 | 32.91192 | 0.23442 | 7.21026 |
May | 508.00000 | 23.99418 | 40.46623 | -0.5130 | 11.28849 |
June | 496.00000 | 24.21663 | 46.86299 | -0.3420 | 7.90910 |
July | 497.00000 | 24.32283 | 48.66831 | -0.2611 | 7.05213 |
August | 514.00000 | 24.24482 | 46.51927 | -0.2719 | 7.07279 |
September | 485.00000 | 24.28132 | 44.72564 | -0.3222 | 8.47912 |
October | 502.00000 | 24.22690 | 37.30007 | 0.46537 | 10.80781 |
November | 489.00000 | 23.45177 | 29.37316 | 0.16322 | 7.24646 |
December | 497.00000 | 22.94932 | 22.23605 | -0.0182 | 7.01720 |
Annual Sum or Average | 5943.00000 | 23.61923 | 35.16225 | -0.0925 | 8.10434 |
Minimum of Months | 454.00000 | 22.14875 | 19.52181 | -0.5130 | 6.60869 |
Maximum of Months | 514.00000 | 24.32283 | 48.66831 | 0.46537 | 11.28849 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.48898 | 24.00410 | -0.1176 | 6.65970 |
February | 454.00000 | 23.15158 | 18.47641 | 0.01776 | 6.28639 |
March | 514.00000 | 24.14900 | 24.98851 | 0.35277 | 8.20298 |
April | 485.00000 | 24.45475 | 30.71300 | 0.51501 | 11.46759 |
May | 508.00000 | 24.31293 | 39.21567 | -0.3182 | 8.15927 |
June | 496.00000 | 24.45702 | 45.42234 | -0.1375 | 6.68004 |
July | 497.00000 | 24.56236 | 47.12395 | -0.0470 | 6.59617 |
August | 514.00000 | 24.45757 | 45.32282 | -0.0331 | 6.23829 |
September | 485.00000 | 24.37075 | 44.12877 | -0.2494 | 7.52425 |
October | 502.00000 | 24.37652 | 36.86013 | 0.51987 | 11.42477 |
November | 489.00000 | 24.18939 | 27.66331 | 0.35822 | 8.45363 |
December | 497.00000 | 24.13829 | 20.10014 | 0.28506 | 7.17299 |
Annual Sum or Average | 5943.00000 | 24.09826 | 33.78246 | 0.09537 | 7.90873 |
Minimum of Months | 454.00000 | 22.48898 | 18.47641 | -0.3182 | 6.23829 |
Maximum of Months | 514.00000 | 24.56236 | 47.12395 | 0.51987 | 11.46759 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.33487 | 28.06502 | -0.7064 | 18.04196 |
February | 454.00000 | 20.53201 | 22.36166 | -0.6773 | 16.63347 |
March | 514.00000 | 21.47690 | 30.53553 | -0.3568 | 9.11981 |
April | 485.00000 | 22.52669 | 35.79595 | -0.0530 | 6.86787 |
May | 508.00000 | 23.57233 | 41.96986 | -0.6771 | 15.71103 |
June | 496.00000 | 24.07662 | 49.21888 | -0.4093 | 9.13003 |
July | 497.00000 | 24.28242 | 52.18752 | -0.2996 | 7.56588 |
August | 514.00000 | 24.18119 | 49.10860 | -0.3581 | 8.29279 |
September | 485.00000 | 23.75139 | 47.38134 | -0.5657 | 12.67004 |
October | 502.00000 | 22.97146 | 41.15428 | 0.10357 | 6.96259 |
November | 489.00000 | 21.51601 | 33.72838 | -0.3312 | 9.44722 |
December | 497.00000 | 20.66912 | 26.39985 | -0.6014 | 13.78809 |
Annual Sum or Average | 5943.00000 | 22.50604 | 38.27405 | -0.4096 | 11.15130 |
Minimum of Months | 454.00000 | 20.33487 | 22.36166 | -0.7064 | 6.86787 |
Maximum of Months | 514.00000 | 24.28242 | 52.18752 | 0.10357 | 18.04196 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.23722 | 27.04190 | -0.7194 | 18.58603 |
February | 385.00000 | 20.63904 | 21.14471 | -0.6339 | 15.49742 |
March | 433.00000 | 21.65747 | 29.30064 | -0.2965 | 8.70591 |
April | 410.00000 | 22.79066 | 34.33287 | 0.03155 | 7.55499 |
May | 430.00000 | 23.72112 | 40.83675 | -0.5774 | 14.78755 |
June | 418.00000 | 24.14152 | 48.48845 | -0.3490 | 9.05545 |
July | 422.00000 | 24.41517 | 51.21116 | -0.2160 | 7.82702 |
August | 433.00000 | 24.29236 | 48.13100 | -0.2636 | 7.76710 |
September | 410.00000 | 23.88098 | 46.35794 | -0.4815 | 12.16803 |
October | 427.00000 | 23.13605 | 39.54385 | 0.16297 | 7.27788 |
November | 417.00000 | 21.51572 | 32.75928 | -0.3184 | 9.27873 |
December | 422.00000 | 20.68187 | 25.35367 | -0.5905 | 13.54800 |
Annual Sum or Average | 5034.00000 | 22.60475 | 37.14400 | -0.3528 | 10.97794 |
Minimum of Months | 385.00000 | 20.23722 | 21.14471 | -0.7194 | 7.27788 |
Maximum of Months | 433.00000 | 24.41517 | 51.21116 | 0.16297 | 18.58603 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.18605 | 26.85534 | -0.4598 | 14.12374 |
February | 454.00000 | 21.84133 | 20.84745 | -0.3188 | 11.16825 |
March | 514.00000 | 22.39873 | 28.73771 | -0.1061 | 7.85819 |
April | 485.00000 | 22.93152 | 34.65726 | 0.05982 | 7.27002 |
May | 508.00000 | 23.68859 | 41.56097 | -0.6262 | 14.48679 |
June | 496.00000 | 24.11090 | 49.01664 | -0.3888 | 8.90749 |
July | 497.00000 | 24.33754 | 51.82641 | -0.2675 | 7.43017 |
August | 514.00000 | 24.30435 | 48.34499 | -0.2749 | 7.46405 |
September | 485.00000 | 24.15627 | 45.79246 | -0.3701 | 9.71313 |
October | 502.00000 | 24.00762 | 38.06105 | 0.40938 | 10.55101 |
November | 489.00000 | 22.59796 | 31.53088 | -0.0384 | 8.11672 |
December | 497.00000 | 21.93757 | 24.65324 | -0.2664 | 10.00513 |
Annual Sum or Average | 5943.00000 | 23.13446 | 36.94188 | -0.2207 | 9.75625 |
Minimum of Months | 454.00000 | 21.18605 | 20.84745 | -0.6262 | 7.27002 |
Maximum of Months | 514.00000 | 24.33754 | 51.82641 | 0.40938 | 14.48679 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.58578 | 27.33942 | -0.6219 | 15.70116 |
February | 454.00000 | 20.91935 | 21.55267 | -0.5570 | 13.86083 |
March | 514.00000 | 22.04348 | 29.06322 | -0.1918 | 7.78397 |
April | 485.00000 | 22.93686 | 34.37042 | 0.08139 | 7.46833 |
May | 508.00000 | 23.77789 | 41.06112 | -0.5470 | 13.14066 |
June | 496.00000 | 24.23634 | 47.99142 | -0.2832 | 8.03714 |
July | 497.00000 | 24.42220 | 50.71642 | -0.1834 | 7.26327 |
August | 514.00000 | 24.38173 | 47.60812 | -0.1845 | 6.95730 |
September | 485.00000 | 23.91070 | 46.29205 | -0.4519 | 10.96502 |
October | 502.00000 | 23.35659 | 39.58846 | 0.23254 | 7.88167 |
November | 489.00000 | 21.72523 | 32.84526 | -0.2625 | 8.54128 |
December | 497.00000 | 20.99406 | 25.53392 | -0.5037 | 11.54616 |
Annual Sum or Average | 5943.00000 | 22.78916 | 37.10813 | -0.2877 | 9.89996 |
Minimum of Months | 454.00000 | 20.58578 | 21.55267 | -0.6219 | 6.95730 |
Maximum of Months | 514.00000 | 24.42220 | 50.71642 | 0.23254 | 15.70116 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.97916 | 28.85145 | -0.8349 | 22.84485 |
February | 454.00000 | 20.10144 | 23.29808 | -0.8315 | 22.21116 |
March | 514.00000 | 20.91254 | 31.91925 | -0.5181 | 12.87965 |
April | 485.00000 | 21.99468 | 36.96593 | -0.1892 | 8.77794 |
May | 508.00000 | 23.31166 | 42.74779 | -0.7585 | 19.24033 |
June | 496.00000 | 24.03983 | 49.40209 | -0.4072 | 9.38355 |
July | 497.00000 | 24.31197 | 52.24676 | -0.2689 | 7.46871 |
August | 514.00000 | 24.17711 | 49.08600 | -0.3430 | 8.31522 |
September | 485.00000 | 23.56018 | 48.05711 | -0.6245 | 14.89290 |
October | 502.00000 | 22.36925 | 42.48047 | -0.0437 | 8.26953 |
November | 489.00000 | 20.73654 | 35.66019 | -0.5457 | 14.26643 |
December | 497.00000 | 20.09983 | 28.11595 | -0.7905 | 20.58865 |
Annual Sum or Average | 5943.00000 | 22.14943 | 39.18160 | -0.5109 | 14.03785 |
Minimum of Months | 454.00000 | 19.97916 | 23.29808 | -0.8349 | 7.46871 |
Maximum of Months | 514.00000 | 24.31197 | 52.24676 | -0.0437 | 22.84485 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.03458 | 28.44836 | -0.8057 | 21.91763 |
February | 454.00000 | 20.25996 | 22.80852 | -0.7652 | 19.83498 |
March | 514.00000 | 21.23470 | 31.11586 | -0.4159 | 11.47796 |
April | 485.00000 | 22.42507 | 35.58912 | -0.0608 | 8.51132 |
May | 508.00000 | 23.53285 | 41.75210 | -0.6252 | 16.80677 |
June | 496.00000 | 24.09069 | 48.64502 | -0.3384 | 8.87939 |
July | 497.00000 | 24.36741 | 51.10399 | -0.1958 | 7.58799 |
August | 514.00000 | 24.24529 | 48.06646 | -0.2437 | 7.51375 |
September | 485.00000 | 23.73174 | 46.99262 | -0.5151 | 13.22588 |
October | 502.00000 | 22.75091 | 41.06592 | 0.07359 | 8.03186 |
November | 489.00000 | 20.88268 | 35.01693 | -0.4927 | 13.21139 |
December | 497.00000 | 20.17894 | 27.65711 | -0.7550 | 19.33611 |
Annual Sum or Average | 5943.00000 | 22.32777 | 38.29861 | -0.4261 | 12.97790 |
Minimum of Months | 454.00000 | 20.03458 | 22.80852 | -0.8057 | 7.51375 |
Maximum of Months | 514.00000 | 24.36741 | 51.10399 | 0.07359 | 21.91763 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.66026 | 27.90634 | -0.6202 | 18.57787 |
February | 454.00000 | 21.08742 | 22.05821 | -0.5340 | 15.99708 |
March | 514.00000 | 21.75199 | 30.31011 | -0.2812 | 10.67316 |
April | 485.00000 | 22.40062 | 35.90703 | -0.0752 | 8.70276 |
May | 508.00000 | 23.42936 | 42.35950 | -0.7072 | 17.97743 |
June | 496.00000 | 24.06801 | 49.23028 | -0.3888 | 9.24308 |
July | 497.00000 | 24.35473 | 51.92171 | -0.2407 | 7.43865 |
August | 514.00000 | 24.28065 | 48.39427 | -0.2660 | 7.59887 |
September | 485.00000 | 23.96129 | 46.49037 | -0.4306 | 11.45934 |
October | 502.00000 | 23.49576 | 39.21642 | 0.27973 | 9.90067 |
November | 489.00000 | 21.76522 | 33.57767 | -0.2608 | 10.98614 |
December | 497.00000 | 21.09981 | 26.69238 | -0.5042 | 15.14663 |
Annual Sum or Average | 5943.00000 | 22.70911 | 37.95295 | -0.3348 | 11.95416 |
Minimum of Months | 454.00000 | 20.66026 | 22.05821 | -0.7072 | 7.43865 |
Maximum of Months | 514.00000 | 24.35473 | 51.92171 | 0.27973 | 18.57787 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.20971 | 28.08508 | -0.7459 | 20.00849 |
February | 454.00000 | 20.48379 | 22.46847 | -0.6972 | 18.21137 |
March | 514.00000 | 21.48387 | 30.39037 | -0.3415 | 10.29162 |
April | 485.00000 | 22.41249 | 35.50332 | -0.0473 | 8.54408 |
May | 508.00000 | 23.47001 | 41.90384 | -0.6390 | 16.71215 |
June | 496.00000 | 24.14748 | 48.28279 | -0.2972 | 8.57296 |
July | 497.00000 | 24.39062 | 50.87429 | -0.1728 | 7.40344 |
August | 514.00000 | 24.33785 | 47.69931 | -0.1842 | 7.16387 |
September | 485.00000 | 23.67535 | 47.02076 | -0.5217 | 13.27431 |
October | 502.00000 | 22.81468 | 40.75336 | 0.10189 | 8.20664 |
November | 489.00000 | 21.02516 | 34.56757 | -0.4493 | 12.03296 |
December | 497.00000 | 20.44290 | 27.10641 | -0.6735 | 16.57069 |
Annual Sum or Average | 5943.00000 | 22.42408 | 37.99684 | -0.3867 | 12.20380 |
Minimum of Months | 454.00000 | 20.20971 | 22.46847 | -0.7459 | 7.16387 |
Maximum of Months | 514.00000 | 24.39062 | 50.87429 | 0.10189 | 20.00849 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.433178E+09 | 2835.74 | 31-JAN-10:00 | 43.84 | 0.131491E+10 | 0.00 | 0.174808E+10 | 0.18 | 3.04 | 07-JAN-13:20 | 0.00 | 0.00 |
February | 0.700358E+09 | 4514.70 | 09-FEB-10:55 | 69.91 | 0.212592E+10 | 0.00 | 0.282628E+10 | 0.32 | 3.04 | 18-FEB-06:30 | 0.00 | 0.00 |
March | 0.402224E+10 | 90350.01 | 27-MAR-13:10 | 76.31 | 0.186064E+11 | 0.00 | 0.226286E+11 | 0.34 | 7.18 | 27-MAR-13:00 | 0.00 | 0.00 |
April | 0.224203E+11 | 101136.97 | 07-APR-11:40 | 166.12 | 0.120364E+12 | 0.00 | 0.142784E+12 | 0.98 | 7.19 | 07-APR-11:40 | 0.00 | 0.00 |
May | 0.746650E+11 | 111438.89 | 30-MAY-13:20 | 375.59 | 0.422444E+12 | 0.00 | 0.497109E+12 | 2.51 | 7.38 | 18-MAY-13:30 | 0.00 | 0.00 |
June | 0.146596E+12 | 168228.80 | 24-JUN-05:02 | 524.16 | 0.959167E+12 | 0.00 | 0.110576E+13 | 4.40 | 7.75 | 29-JUN-05:04 | 0.00 | 0.00 |
July | 0.178056E+12 | 178741.46 | 22-JUL-05:02 | 617.86 | 0.113239E+13 | 0.00 | 0.131045E+13 | 4.78 | 7.73 | 01-JUL-05:02 | 0.00 | 0.00 |
August | 0.178759E+12 | 157954.54 | 17-AUG-05:02 | 657.82 | 0.113787E+13 | 0.00 | 0.131663E+13 | 4.99 | 7.67 | 24-AUG-05:02 | 0.00 | 0.00 |
September | 0.117202E+12 | 182110.39 | 14-SEP-05:03 | 446.49 | 0.741445E+12 | 0.00 | 0.858647E+12 | 3.63 | 7.69 | 13-SEP-05:02 | 0.00 | 0.00 |
October | 0.623979E+11 | 123826.96 | 06-OCT-05:03 | 282.13 | 0.383399E+12 | 0.00 | 0.445797E+12 | 2.06 | 7.67 | 06-OCT-05:03 | 0.00 | 0.00 |
November | 0.586699E+10 | 58332.72 | 03-NOV-14:00 | 81.67 | 0.219052E+11 | 0.00 | 0.277721E+11 | 0.37 | 5.99 | 10-NOV-10:00 | 0.00 | 0.00 |
December | 0.547315E+09 | 19208.87 | 25-DEC-15:23 | 45.44 | 0.166162E+10 | 0.00 | 0.220893E+10 | 0.19 | 3.04 | 21-DEC-08:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.791666E+12 | 3387.34 | 0.494270E+13 | 0.573436E+13 | 2.07 | |||||||
Minimum of Months | 0.433178E+09 | 2835.74 | 43.84 | 0.131491E+10 | 0.00 | 0.174808E+10 | 0.18 | 3.04 | 0.00 | 0.00 | ||
Maximum of Months | 0.178759E+12 | 182110.39 | 657.82 | 0.113787E+13 | 0.00 | 0.131663E+13 | 4.99 | 7.75 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCHILLER ELECTRIC ENERGY [J] | CHILLER ELECTRIC POWER {Maximum}[W] | CHILLER ELECTRIC POWER {TIMESTAMP} | CHILLER ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum}[W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.336734E+10 | 111438.89 | 30-MAY-13:20 | 9.00 | 0.236019E+11 | 0.00 | 0.269693E+11 | 0.08 | 7.13 | 31-MAY-15:40 | 0.00 | 0.00 |
June | 0.374590E+11 | 168228.80 | 24-JUN-05:02 | 97.67 | 0.260169E+12 | 0.00 | 0.297628E+12 | 0.94 | 7.75 | 29-JUN-05:04 | 0.00 | 0.00 |
July | 0.636902E+11 | 178741.46 | 22-JUL-05:02 | 160.08 | 0.427512E+12 | 0.00 | 0.491202E+12 | 1.45 | 7.73 | 01-JUL-05:02 | 0.00 | 0.00 |
August | 0.608981E+11 | 157954.54 | 17-AUG-05:02 | 152.86 | 0.407772E+12 | 0.00 | 0.468670E+12 | 1.38 | 7.67 | 24-AUG-05:02 | 0.00 | 0.00 |
September | 0.220702E+11 | 182110.39 | 14-SEP-05:03 | 57.10 | 0.152937E+12 | 0.00 | 0.175007E+12 | 0.55 | 7.69 | 13-SEP-05:02 | 0.00 | 0.00 |
October | 0.659310E+10 | 123826.96 | 06-OCT-05:03 | 17.40 | 0.469144E+11 | 0.00 | 0.535075E+11 | 0.17 | 7.67 | 06-OCT-05:03 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.194078E+12 | 494.11 | 0.131891E+13 | 0.151298E+13 | 0.38 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.636902E+11 | 182110.39 | 160.08 | 0.427512E+12 | 0.00 | 0.491202E+12 | 1.45 | 7.75 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.986583E+10 | 744.00 | 17824.99 | 28-JAN-15:20 | 543813.88 | 28-JAN-23:00 | 21.54 | 18.33 | 13.84 |
February | 0.138330E+11 | 672.00 | 20787.26 | 24-FEB-00:55 | 581588.36 | 20-FEB-00:30 | 24.38 | 18.33 | 13.82 |
March | 0.450510E+11 | 744.00 | 49248.27 | 02-MAR-15:40 | 599396.26 | 04-MAR-18:40 | 27.37 | 18.40 | 13.84 |
April | 0.936076E+11 | 720.00 | 49248.27 | 05-APR-10:50 | 630149.46 | 07-APR-17:20 | 31.26 | 19.36 | 13.87 |
May | 0.818615E+11 | 744.00 | 49248.27 | 01-MAY-10:50 | 450001.44 | 01-MAY-02:50 | 23.24 | 19.62 | 13.87 |
June | 0.126840E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 379642.25 | 19-JUN-12:20 | 31.14 | 24.46 | 13.87 |
July | 0.131907E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 527782.60 | 07-JUL-12:20 | 38.98 | 29.11 | 13.87 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:03 | 659874.58 | 04-AUG-21:02 | 42.65 | 30.02 | 13.87 |
September | 0.113115E+12 | 720.00 | 49248.27 | 01-SEP-00:03 | 433897.76 | 01-SEP-00:03 | 25.77 | 22.02 | 13.87 |
October | 0.898724E+11 | 744.00 | 49248.27 | 02-OCT-08:20 | 583355.30 | 28-OCT-17:30 | 25.93 | 19.52 | 13.87 |
November | 0.561134E+11 | 720.00 | 49248.27 | 02-NOV-11:50 | 599583.10 | 14-NOV-22:13 | 27.37 | 18.40 | 13.86 |
December | 0.480010E+11 | 744.00 | 42991.68 | 17-DEC-15:00 | 614742.64 | 05-DEC-01:10 | 29.99 | 18.33 | 13.86 |
Annual Sum or Average | 0.941974E+12 | 8760.00 | 29.18 | 21.35 | 13.86 | ||||
Minimum of Months | 0.986583E+10 | 672.00 | 17824.99 | 379642.25 | 21.54 | 18.33 | 13.82 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 659874.58 | 42.65 | 30.02 | 13.87 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 215057.64 | 07-JAN-12:55 | 21.00 | 21.00 | 0.39 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 215135.52 | 09-FEB-10:30 | 21.01 | 21.00 | 0.57 |
March | 66873186.56 | 11.17 | 4544.38 | 27-MAR-13:10 | 751334.70 | 27-MAR-13:10 | 21.04 | 21.00 | 2.09 |
April | 0.351536E+09 | 91.07 | 3990.13 | 08-APR-10:00 | 810367.11 | 07-APR-15:40 | 21.26 | 21.01 | 9.76 |
May | 0.390852E+10 | 313.20 | 20151.66 | 18-MAY-09:00 | 897335.30 | 31-MAY-15:10 | 22.15 | 21.33 | 27.31 |
June | 0.258377E+11 | 507.38 | 20151.66 | 01-JUN-08:20 | 954409.50 | 01-JUN-14:10 | 24.52 | 22.67 | 39.47 |
July | 0.422846E+11 | 617.15 | 20151.66 | 01-JUL-03:01 | 966854.95 | 24-JUL-05:04 | 26.12 | 24.03 | 42.97 |
August | 0.345361E+11 | 634.08 | 20151.66 | 01-AUG-00:03 | 986996.19 | 30-AUG-13:50 | 25.30 | 23.18 | 46.89 |
September | 0.143894E+11 | 423.72 | 20151.66 | 01-SEP-02:33 | 1062868.07 | 01-SEP-14:10 | 23.77 | 22.34 | 33.81 |
October | 0.651451E+10 | 237.49 | 20151.66 | 03-OCT-09:00 | 938392.43 | 05-OCT-14:50 | 22.17 | 21.44 | 20.39 |
November | 37541659.40 | 26.17 | 1756.14 | 10-NOV-10:00 | 414713.65 | 03-NOV-14:00 | 21.12 | 21.07 | 3.26 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 215211.38 | 21-DEC-08:30 | 20.99 | 20.99 | 0.45 |
Annual Sum or Average | 0.127927E+12 | 2861.43 | 22.55 | 21.76 | 19.07 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 215057.64 | 20.99 | 20.99 | 0.39 | ||
Maximum of Months | 0.422846E+11 | 634.08 | 20151.66 | 1062868.07 | 26.12 | 24.03 | 46.89 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING TOWER FAN ELECTRIC ENERGY [J] | COOLING TOWER FAN ELECTRIC ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRIC POWER {Maximum}[W] | COOLING TOWER FAN ELECTRIC POWER {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum}[W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 21.00 | 21.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.01 | 21.01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.04 | 21.04 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.26 | 21.26 | 0.00 |
May | 0.834279E+09 | 11.50 | 20151.66 | 30-MAY-10:20 | 897335.30 | 31-MAY-15:10 | 22.15 | 22.09 | 0.82 |
June | 0.114683E+11 | 158.42 | 20151.66 | 01-JUN-09:50 | 954409.50 | 01-JUN-14:10 | 24.52 | 23.77 | 10.98 |
July | 0.233075E+11 | 321.28 | 20151.66 | 01-JUL-05:03 | 966854.95 | 24-JUL-05:04 | 26.12 | 24.68 | 20.24 |
August | 0.186342E+11 | 260.06 | 20151.66 | 01-AUG-05:01 | 986996.19 | 30-AUG-13:50 | 25.30 | 24.11 | 16.99 |
September | 0.673132E+10 | 92.80 | 20151.66 | 01-SEP-03:25 | 1062868.07 | 01-SEP-14:10 | 23.77 | 23.32 | 6.40 |
October | 0.130825E+10 | 18.03 | 20151.66 | 03-OCT-12:20 | 938392.43 | 05-OCT-14:50 | 22.17 | 22.08 | 1.38 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.12 | 21.12 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.99 | 20.99 | 0.00 |
Annual Sum or Average | 0.622839E+11 | 862.09 | 22.55 | 22.21 | 4.78 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.99 | 20.99 | 0.00 | ||
Maximum of Months | 0.233075E+11 | 321.28 | 20151.66 | 1062868.07 | 26.12 | 24.68 | 20.24 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum}[] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.188731E+12 | 0.00 | 504.72 | 1535039.18 | 02-JAN-07:10 | 0.00 | 74.05 | 78.33 | 2.29 | 0.00 | 0.04 | 0.90 | 02-JAN-07:10 |
February | 0.128257E+12 | 0.00 | 439.06 | 1238875.22 | 13-FEB-06:01 | 0.00 | 73.85 | 78.39 | 1.50 | 0.00 | 0.03 | 0.73 | 13-FEB-06:01 |
March | 0.413104E+11 | 0.00 | 322.43 | 794330.49 | 13-MAR-05:01 | 0.00 | 73.53 | 76.67 | 0.43 | 0.00 | 0.01 | 0.47 | 13-MAR-05:01 |
April | 0.820051E+10 | 0.00 | 130.97 | 827400.22 | 03-APR-05:01 | 0.00 | 68.95 | 71.19 | 0.06 | 0.00 | 0.00 | 0.48 | 03-APR-05:01 |
May | 0.144180E+10 | 0.00 | 12.64 | 257736.73 | 31-MAY-03:47 | 0.00 | 72.02 | 72.12 | 0.03 | 0.00 | 0.00 | 0.15 | 31-MAY-03:47 |
June | 0.181421E+10 | 0.00 | 11.25 | 331804.50 | 23-JUN-04:00 | 0.00 | 69.32 | 69.49 | 0.02 | 0.00 | 0.00 | 0.19 | 23-JUN-04:00 |
July | 0.159137E+10 | 0.00 | 5.94 | 257109.87 | 12-JUL-03:47 | 0.00 | 70.55 | 70.62 | 0.02 | 0.00 | 0.00 | 0.15 | 12-JUL-03:47 |
August | 0.233758E+10 | 0.00 | 18.01 | 362584.28 | 26-AUG-03:50 | 0.00 | 69.83 | 70.08 | 0.02 | 0.00 | 0.00 | 0.21 | 26-AUG-03:50 |
September | 0.187706E+10 | 0.00 | 5.67 | 317907.17 | 02-SEP-03:47 | 0.00 | 70.16 | 70.26 | 0.02 | 0.00 | 0.00 | 0.19 | 02-SEP-03:47 |
October | 0.342087E+10 | 0.00 | 50.34 | 276947.04 | 07-OCT-03:50 | 0.00 | 74.79 | 75.00 | 0.10 | 0.00 | 0.00 | 0.16 | 07-OCT-03:50 |
November | 0.410810E+11 | 0.00 | 269.10 | 781624.87 | 25-NOV-06:01 | 0.00 | 73.66 | 76.50 | 0.41 | 0.00 | 0.01 | 0.46 | 25-NOV-06:01 |
December | 0.884064E+11 | 0.00 | 438.09 | 1125406.94 | 30-DEC-05:01 | 0.00 | 59.65 | 71.49 | 0.37 | 0.00 | 0.02 | 0.66 | 30-DEC-05:01 |
Annual Sum or Average | 0.508470E+12 | 2208.23 | 70.84 | 73.32 | 0.43 | 0.00 | 0.01 | ||||||
Minimum of Months | 0.144180E+10 | 0.00 | 5.67 | 257109.87 | 0.00 | 59.65 | 69.49 | 0.02 | 0.00 | 0.00 | 0.15 | ||
Maximum of Months | 0.188731E+12 | 0.00 | 504.72 | 1535039.18 | 0.00 | 74.79 | 78.39 | 2.29 | 0.00 | 0.04 | 0.90 |
Report: BoilerReportMonthly
For: DUMMY BOILER
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum}[W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRIC POWER [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 21.54 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.38 | 24.38 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.37 | 27.37 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.26 | 31.26 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 23.24 | 23.24 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 31.14 | 31.14 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 38.98 | 38.98 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 42.65 | 42.65 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 25.77 | 25.77 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.93 | 25.93 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.37 | 27.37 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.99 | 29.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 29.18 | 29.18 | 0.00 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.54 | 21.54 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.65 | 42.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 9991177.59 | 0.00 | 0.69 | 4485778.53 | 0.00 | 0.00 | 0.00 | 0.00 | 36502.28 | 24-JAN-06:03 | 16007.70 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 |
February | 65643.28 | 0.00 | 0.35 | 65643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 73.64 | 07-FEB-16:10 | 73.64 | 07-FEB-16:10 | 0.00 | 0.00 | 0.00 |
March | 0.660943E+09 | 0.00 | 8.19 | 0.660640E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43095.73 | 27-MAR-16:00 | 43095.73 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.562517E+10 | 0.00 | 72.35 | 0.559146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 64989.48 | 07-APR-13:50 | 64989.48 | 07-APR-13:50 | 0.00 | 0.00 | 0.00 |
May | 0.170213E+11 | 0.00 | 192.14 | 0.160519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 104942.36 | 29-MAY-03:41 | 104942.36 | 29-MAY-03:41 | 0.00 | 0.00 | 0.00 |
June | 0.681252E+11 | 0.00 | 395.52 | 0.563868E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 169605.29 | 19-JUN-00:30 | 103869.14 | 12-JUN-03:01 | 0.00 | 0.00 | 0.00 |
July | 0.973037E+11 | 0.00 | 419.08 | 0.762391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174925.84 | 09-JUL-22:12 | 105397.77 | 31-JUL-03:00 | 0.00 | 0.00 | 0.00 |
August | 0.963353E+11 | 0.00 | 443.58 | 0.799270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 158740.93 | 13-AUG-20:31 | 109334.76 | 20-AUG-23:52 | 0.00 | 0.00 | 0.00 |
September | 0.519030E+11 | 0.00 | 347.32 | 0.449701E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 148693.55 | 01-SEP-03:01 | 102399.97 | 04-SEP-21:51 | 0.00 | 0.00 | 0.00 |
October | 0.204814E+11 | 0.00 | 190.24 | 0.168654E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109397.72 | 06-OCT-05:03 | 61563.60 | 04-OCT-13:00 | 0.00 | 0.00 | 0.00 |
November | 0.271865E+09 | 0.00 | 9.89 | 0.230239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 64451.20 | 10-NOV-06:02 | 25691.90 | 10-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 3652628.89 | 0.00 | 0.17 | 3536766.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8656.79 | 25-DEC-14:31 | 8656.79 | 25-DEC-14:31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.357742E+12 | 2079.51 | 0.296931E+12 | ||||||||||||
Minimum of Months | 65643.28 | 0.00 | 0.17 | 65643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 73.64 | 73.64 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.973037E+11 | 0.00 | 443.58 | 0.799270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 174925.84 | 109334.76 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 11945598.70 | 0.00 | 21.43 | 11945598.70 | 0.00 | 0.00 | 0.00 | 0.00 | 5733.61 | 19-JAN-08:10 | 5733.61 | 19-JAN-08:10 | 0.00 | 0.00 | 0.00 |
February | 15558758.05 | 0.00 | 34.18 | 15558758.05 | 0.00 | 0.00 | 0.00 | 0.00 | 2561.77 | 27-FEB-13:10 | 2561.77 | 27-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 0.193807E+10 | 0.00 | 45.64 | 0.164238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83926.22 | 27-MAR-13:00 | 66328.91 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.139456E+11 | 0.00 | 143.67 | 0.137788E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100163.14 | 07-APR-13:30 | 100163.14 | 07-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.429207E+11 | 0.00 | 359.27 | 0.361797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 143397.41 | 30-MAY-14:10 | 138214.51 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 |
June | 0.124127E+12 | 0.00 | 505.49 | 0.960090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 170016.15 | 26-JUN-05:02 | 144099.53 | 01-JUN-15:10 | 0.00 | 0.00 | 0.00 |
July | 0.162166E+12 | 0.00 | 587.41 | 0.128627E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 188843.08 | 21-JUL-05:02 | 152082.01 | 21-JUL-05:02 | 0.00 | 0.00 | 0.00 |
August | 0.166602E+12 | 0.00 | 634.82 | 0.142190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 179933.43 | 01-AUG-05:02 | 154495.52 | 22-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.853424E+11 | 0.00 | 427.51 | 0.695352E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 194060.38 | 14-SEP-03:01 | 154736.42 | 01-SEP-14:00 | 0.00 | 0.00 | 0.00 |
October | 0.462042E+11 | 0.00 | 271.51 | 0.332454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 162945.65 | 06-OCT-05:01 | 131504.31 | 06-OCT-05:01 | 0.00 | 0.00 | 0.00 |
November | 0.210546E+10 | 0.00 | 48.42 | 0.182456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44182.05 | 10-NOV-10:00 | 35502.44 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 7917315.97 | 0.00 | 7.03 | 7917315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.08 | 30-DEC-08:70 | 1616.08 | 30-DEC-08:70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.645387E+12 | 3086.38 | 0.523067E+12 | ||||||||||||
Minimum of Months | 7917315.97 | 0.00 | 7.03 | 7917315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1616.08 | 1616.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.166602E+12 | 0.00 | 634.82 | 0.142190E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 194060.38 | 154736.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 15165015.88 | 0.00 | 18.96 | 15165015.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4546.22 | 17-JAN-12:00 | 4546.22 | 17-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 78098848.18 | 0.00 | 36.42 | 78098848.18 | 0.00 | 0.00 | 0.00 | 0.00 | 81215.27 | 09-FEB-10:55 | 81215.27 | 09-FEB-10:55 | 0.00 | 0.00 | 0.00 |
March | 0.128099E+11 | 0.00 | 44.36 | 0.112068E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 506923.16 | 27-MAR-13:00 | 445717.02 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.932570E+11 | 0.00 | 114.89 | 0.929195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 828433.33 | 07-APR-13:30 | 828433.33 | 07-APR-13:30 | 0.00 | 0.00 | 0.00 |
May | 0.361363E+12 | 0.00 | 346.76 | 0.303000E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1149044.34 | 30-MAY-14:00 | 1149044.34 | 30-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.103239E+13 | 0.00 | 442.75 | 0.762962E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1930605.95 | 27-JUN-05:02 | 1340807.35 | 27-JUN-05:02 | 0.00 | 0.00 | 0.00 |
July | 0.128928E+13 | 0.00 | 463.60 | 0.947341E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2433318.92 | 22-JUL-03:01 | 1352246.09 | 14-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.126669E+13 | 0.00 | 481.80 | 0.102451E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 1934611.53 | 04-AUG-03:01 | 1500452.70 | 22-AUG-03:01 | 0.00 | 0.00 | 0.00 |
September | 0.738767E+12 | 0.00 | 404.23 | 0.587418E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2049511.97 | 14-SEP-05:01 | 1371028.50 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 |
October | 0.367620E+12 | 0.00 | 257.14 | 0.257420E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1403321.62 | 06-OCT-05:01 | 785241.91 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.154418E+11 | 0.00 | 51.60 | 0.134901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 276439.69 | 10-NOV-10:00 | 261566.66 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.260653E+09 | 0.00 | 20.38 | 0.260653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22915.69 | 15-DEC-14:30 | 22915.69 | 15-DEC-14:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.517797E+13 | 2682.89 | 0.400062E+13 | ||||||||||||
Minimum of Months | 15165015.88 | 0.00 | 18.96 | 15165015.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4546.22 | 4546.22 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.128928E+13 | 0.00 | 481.80 | 0.102451E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 2433318.92 | 1500452.70 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRIC POWER [] | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 12566054.31 | 0.00 | 28.43 | 12566054.31 | 0.00 | 0.00 | 0.00 | 0.00 | 2377.12 | 15-JAN-10:10 | 2377.12 | 15-JAN-10:10 | 0.00 | 0.00 | 0.00 |
February | 12883271.12 | 0.00 | 38.41 | 12883271.12 | 0.00 | 0.00 | 0.00 | 0.00 | 698.04 | 17-FEB-10:50 | 698.04 | 17-FEB-10:50 | 0.00 | 0.00 | 0.00 |
March | 0.119854E+10 | 0.00 | 59.41 | 0.105803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45176.94 | 27-MAR-13:00 | 39036.96 | 27-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.963708E+10 | 0.00 | 126.03 | 0.960656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91703.53 | 07-APR-15:30 | 91703.53 | 07-APR-15:30 | 0.00 | 0.00 | 0.00 |
May | 0.381543E+11 | 0.00 | 344.57 | 0.322685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 139655.48 | 30-MAY-13:10 | 139655.48 | 30-MAY-13:10 | 0.00 | 0.00 | 0.00 |
June | 0.112564E+12 | 0.00 | 441.96 | 0.844476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 204435.51 | 27-JUN-05:02 | 152826.70 | 01-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.144799E+12 | 0.00 | 466.14 | 0.107966E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 266333.21 | 22-JUL-03:01 | 140717.28 | 07-JUL-03:01 | 0.00 | 0.00 | 0.00 |
August | 0.140127E+12 | 0.00 | 479.06 | 0.114339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 207769.07 | 04-AUG-03:01 | 158713.45 | 30-AUG-13:30 | 0.00 | 0.00 | 0.00 |
September | 0.766327E+11 | 0.00 | 395.31 | 0.608874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 215930.87 | 14-SEP-05:01 | 161432.74 | 01-SEP-14:50 | 0.00 | 0.00 | 0.00 |
October | 0.359163E+11 | 0.00 | 249.02 | 0.250364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130107.74 | 06-OCT-05:03 | 91212.85 | 04-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.137721E+10 | 0.00 | 69.58 | 0.120567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23828.86 | 03-NOV-14:00 | 23828.86 | 03-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 16455256.51 | 0.00 | 35.67 | 16455256.51 | 0.00 | 0.00 | 0.00 | 0.00 | 511.53 | 15-DEC-10:30 | 511.53 | 15-DEC-10:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.560447E+12 | 2733.58 | 0.436858E+12 | ||||||||||||
Minimum of Months | 12566054.31 | 0.00 | 28.43 | 12566054.31 | 0.00 | 0.00 | 0.00 | 0.00 | 511.53 | 511.53 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.144799E+12 | 0.00 | 479.06 | 0.114339E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 266333.21 | 161432.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.308694E+12 | 0.795951E+11 | 728.39 | 0.308651E+12 | 42468935.83 | 0.00 | 1.00 | 02-JAN-22:04 | 0.01 | 30-JAN-22:21 | 437072.77 | 28-JAN-23:00 | 437072.77 | 28-JAN-23:00 | 6936.86 | 19-JAN-07:35 | 91465.82 | 28-JAN-23:00 | 0.00 |
February | 0.491139E+12 | 0.119086E+12 | 662.61 | 0.490999E+12 | 0.140291E+09 | 0.00 | 1.00 | 01-FEB-03:32 | 0.01 | 09-FEB-22:18 | 444821.84 | 20-FEB-00:30 | 444821.84 | 20-FEB-00:30 | 40617.72 | 09-FEB-23:50 | 91598.71 | 20-FEB-00:30 | 0.00 |
March | 0.779411E+12 | 0.178366E+12 | 743.78 | 0.779324E+12 | 86779346.82 | 0.00 | 1.00 | 01-MAR-22:10 | 0.01 | 17-MAR-20:57 | 433784.90 | 11-MAR-19:20 | 433784.90 | 11-MAR-19:20 | 22932.72 | 25-MAR-17:40 | 91409.43 | 11-MAR-19:20 | 0.00 |
April | 0.986260E+12 | 0.225072E+12 | 720.00 | 0.986244E+12 | 15774979.35 | 0.00 | 1.00 | 01-APR-11:52 | 0.78 | 01-APR-17:40 | 424575.28 | 17-APR-21:25 | 424575.28 | 17-APR-21:25 | 1512.12 | 27-APR-19:00 | 124822.31 | 07-APR-13:00 | 0.00 |
May | 0.316065E+12 | 0.824479E+11 | 742.91 | 0.314714E+12 | 0.135100E+10 | 0.00 | 1.00 | 01-MAY-01:39 | 0.05 | 01-MAY-04:11 | 422919.96 | 16-MAY-03:06 | 422919.96 | 16-MAY-03:06 | 5357.07 | 31-MAY-17:00 | 91223.10 | 16-MAY-03:06 | 0.00 |
June | 0.540252E+12 | 0.153271E+12 | 720.00 | 0.534717E+12 | 0.553530E+10 | 0.00 | 0.63 | 19-JUN-12:00 | 0.52 | 01-JUN-06:10 | 218655.93 | 15-JUN-12:50 | 211391.87 | 19-JUN-12:00 | 10581.70 | 15-JUN-13:50 | 91303.16 | 19-JUN-12:00 | 0.00 |
July | 0.798901E+12 | 0.247186E+12 | 744.00 | 0.790257E+12 | 0.864486E+10 | 0.00 | 0.84 | 07-JUL-12:00 | 0.74 | 01-JUL-00:10 | 308308.42 | 20-JUL-15:00 | 298798.99 | 10-JUL-15:00 | 11404.39 | 20-JUL-15:00 | 118351.69 | 07-JUL-12:00 | 0.00 |
August | 0.103167E+13 | 0.315737E+12 | 744.00 | 0.102598E+13 | 0.569606E+10 | 0.00 | 1.00 | 01-AUG-08:40 | 0.92 | 08-AUG-05:00 | 396747.48 | 18-AUG-19:00 | 388177.92 | 03-AUG-21:02 | 11940.54 | 16-AUG-20:00 | 143546.98 | 24-AUG-16:00 | 0.00 |
September | 0.312940E+12 | 0.869351E+11 | 720.00 | 0.309529E+12 | 0.341060E+10 | 0.00 | 0.38 | 01-SEP-00:03 | 0.31 | 23-SEP-06:20 | 135983.44 | 01-SEP-00:10 | 134618.73 | 01-SEP-00:10 | 8813.90 | 22-SEP-17:50 | 47618.13 | 01-SEP-14:00 | 0.00 |
October | 0.554924E+12 | 0.135907E+12 | 743.76 | 0.552607E+12 | 0.231672E+10 | 0.00 | 1.00 | 28-OCT-17:25 | 0.18 | 28-OCT-19:01 | 437558.66 | 28-OCT-17:30 | 437558.66 | 28-OCT-17:30 | 6598.64 | 04-OCT-18:00 | 91474.15 | 28-OCT-17:30 | 0.00 |
November | 0.759254E+12 | 0.173513E+12 | 719.73 | 0.759156E+12 | 97733038.55 | 0.00 | 1.00 | 07-NOV-22:17 | 0.01 | 18-NOV-14:58 | 431369.76 | 25-NOV-13:04 | 431369.76 | 25-NOV-13:04 | 11857.57 | 14-NOV-22:50 | 91368.01 | 25-NOV-13:04 | 0.00 |
December | 0.101762E+13 | 0.224930E+12 | 744.00 | 0.101762E+13 | 0.00 | 0.00 | 1.00 | 01-DEC-22:08 | 0.75 | 05-DEC-05:32 | 421116.32 | 15-DEC-22:33 | 421116.32 | 15-DEC-22:33 | 0.00 | 01-DEC-00:10 | 91192.17 | 15-DEC-22:33 | 0.00 |
Annual Sum or Average | 0.789714E+13 | 0.202205E+13 | 8733.20 | 0.786980E+13 | 0.273376E+11 | ||||||||||||||
Minimum of Months | 0.308694E+12 | 0.795951E+11 | 662.61 | 0.308651E+12 | 0.00 | 0.00 | 0.38 | 0.01 | 135983.44 | 134618.73 | 0.00 | 47618.13 | 0.00 | ||||||
Maximum of Months | 0.103167E+13 | 0.315737E+12 | 744.00 | 0.102598E+13 | 0.864486E+10 | 0.00 | 1.00 | 0.92 | 444821.84 | 444821.84 | 40617.72 | 143546.98 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.401996E+10 | 0.116718E+10 | 744.00 | 0.401996E+10 | 0.00 | 0.00 | 0.34 | 20-JAN-16:30 | 0.14 | 01-JAN-00:30 | 2268.54 | 20-JAN-16:30 | 2268.54 | 20-JAN-16:30 | 0.00 | 01-JAN-00:01 | 637.28 | 20-JAN-16:30 | 0.00 |
February | 0.848562E+10 | 0.229002E+10 | 672.00 | 0.848562E+10 | 0.00 | 0.00 | 0.61 | 22-FEB-16:50 | 0.43 | 06-FEB-06:12 | 4276.53 | 14-FEB-17:00 | 4276.53 | 14-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1127.38 | 22-FEB-16:50 | 0.00 |
March | 0.150462E+11 | 0.385301E+10 | 744.00 | 0.150462E+11 | 0.00 | 0.00 | 0.89 | 27-MAR-17:00 | 0.73 | 01-MAR-00:10 | 6256.50 | 26-MAR-17:30 | 6256.50 | 26-MAR-17:30 | 0.00 | 01-MAR-00:10 | 1967.17 | 27-MAR-17:00 | 0.00 |
April | 0.193196E+11 | 0.491187E+10 | 720.00 | 0.193196E+11 | 0.00 | 0.00 | 1.00 | 02-APR-13:50 | 0.96 | 01-APR-07:00 | 7724.78 | 23-APR-18:03 | 7724.78 | 23-APR-18:03 | 0.00 | 01-APR-00:10 | 2553.25 | 07-APR-13:00 | 0.00 |
May | 0.547023E+10 | 0.163121E+10 | 744.00 | 0.547023E+10 | 0.00 | 0.00 | 0.39 | 30-MAY-16:00 | 0.27 | 04-MAY-21:17 | 2570.48 | 01-MAY-00:05 | 2570.48 | 01-MAY-00:05 | 0.00 | 01-MAY-00:05 | 956.02 | 30-MAY-13:00 | 0.00 |
June | 0.102315E+11 | 0.337661E+10 | 720.00 | 0.102315E+11 | 0.00 | 0.00 | 0.70 | 19-JUN-12:00 | 0.54 | 03-JUN-07:00 | 4406.62 | 18-JUN-18:10 | 4406.62 | 18-JUN-18:10 | 0.00 | 01-JUN-00:10 | 2079.10 | 19-JUN-12:00 | 0.00 |
July | 0.154729E+11 | 0.562514E+10 | 744.00 | 0.154729E+11 | 0.00 | 0.00 | 0.97 | 10-JUL-15:00 | 0.81 | 02-JUL-03:00 | 6270.16 | 04-JUL-18:05 | 6270.16 | 04-JUL-18:05 | 0.00 | 01-JUL-00:10 | 2755.94 | 07-JUL-12:00 | 0.00 |
August | 0.186047E+11 | 0.658010E+10 | 744.00 | 0.186047E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-00:03 | 1.00 | 01-AUG-00:03 | 7507.36 | 08-AUG-04:57 | 7507.36 | 08-AUG-04:57 | 0.00 | 01-AUG-00:03 | 2933.94 | 24-AUG-16:00 | 0.00 |
September | 0.542169E+10 | 0.175514E+10 | 720.00 | 0.542169E+10 | 0.00 | 0.00 | 0.78 | 01-SEP-00:03 | 0.27 | 23-SEP-17:20 | 5298.93 | 01-SEP-00:03 | 5298.93 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 1817.87 | 01-SEP-00:03 | 0.00 |
October | 0.104596E+11 | 0.291572E+10 | 744.00 | 0.104596E+11 | 0.00 | 0.00 | 0.66 | 04-OCT-16:20 | 0.52 | 28-OCT-07:00 | 4467.24 | 15-OCT-16:33 | 4467.24 | 15-OCT-16:33 | 0.00 | 01-OCT-00:10 | 1472.96 | 02-OCT-16:40 | 0.00 |
November | 0.145540E+11 | 0.373139E+10 | 720.00 | 0.145540E+11 | 0.00 | 0.00 | 0.83 | 03-NOV-15:50 | 0.72 | 25-NOV-18:15 | 6048.12 | 06-NOV-16:10 | 6048.12 | 06-NOV-16:10 | 0.00 | 01-NOV-00:10 | 1649.94 | 03-NOV-14:00 | 0.00 |
December | 0.198116E+11 | 0.487880E+10 | 744.00 | 0.198116E+11 | 0.00 | 0.00 | 1.00 | 01-DEC-15:20 | 0.95 | 30-DEC-18:20 | 7641.69 | 21-DEC-16:20 | 7641.69 | 21-DEC-16:20 | 0.00 | 01-DEC-00:10 | 1858.38 | 21-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.146898E+12 | 0.427162E+11 | 8760.00 | 0.146898E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.401996E+10 | 0.116718E+10 | 672.00 | 0.401996E+10 | 0.00 | 0.00 | 0.34 | 0.14 | 2268.54 | 2268.54 | 0.00 | 637.28 | 0.00 | ||||||
Maximum of Months | 0.198116E+11 | 0.658010E+10 | 744.00 | 0.198116E+11 | 0.00 | 0.00 | 1.00 | 1.00 | 7724.78 | 7724.78 | 0.00 | 2933.94 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.158508E+11 | 0.482718E+10 | 548.90 | 0.158508E+11 | 0.00 | 0.00 | 0.31 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 19676.26 | 20-JAN-16:40 | 19676.26 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 5572.50 | 20-JAN-16:40 | 0.00 |
February | 0.616872E+11 | 0.170615E+11 | 672.00 | 0.616872E+11 | 0.00 | 0.00 | 0.58 | 22-FEB-17:00 | 0.18 | 06-FEB-04:01 | 38738.45 | 22-FEB-17:00 | 38738.45 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 10293.41 | 22-FEB-17:00 | 0.00 |
March | 0.128616E+12 | 0.333869E+11 | 744.00 | 0.128616E+12 | 0.00 | 0.00 | 0.87 | 27-MAR-17:00 | 0.60 | 13-MAR-04:18 | 58471.48 | 29-MAR-17:20 | 58471.48 | 29-MAR-17:20 | 0.00 | 01-MAR-00:10 | 18366.42 | 27-MAR-17:00 | 0.00 |
April | 0.175946E+12 | 0.451372E+11 | 720.00 | 0.175946E+12 | 0.00 | 0.00 | 1.00 | 03-APR-16:40 | 0.86 | 02-APR-06:50 | 73305.39 | 12-APR-18:00 | 73305.39 | 12-APR-18:00 | 0.00 | 01-APR-00:10 | 24350.44 | 07-APR-13:00 | 0.00 |
May | 0.466988E+11 | 0.140811E+11 | 744.00 | 0.466988E+11 | 0.00 | 0.00 | 0.38 | 30-MAY-17:50 | 0.22 | 04-MAY-07:00 | 22993.36 | 30-MAY-18:00 | 22993.36 | 30-MAY-18:00 | 0.00 | 01-MAY-00:05 | 8921.46 | 30-MAY-16:00 | 0.00 |
June | 0.953321E+11 | 0.315770E+11 | 720.00 | 0.953321E+11 | 0.00 | 0.00 | 0.70 | 19-JUN-12:00 | 0.51 | 03-JUN-07:00 | 42055.87 | 18-JUN-17:52 | 42055.87 | 18-JUN-17:52 | 0.00 | 01-JUN-00:10 | 19721.63 | 19-JUN-12:00 | 0.00 |
July | 0.146928E+12 | 0.534497E+11 | 744.00 | 0.146928E+12 | 0.00 | 0.00 | 0.96 | 10-JUL-15:00 | 0.80 | 01-JUL-00:10 | 59690.59 | 12-JUL-18:20 | 59690.59 | 12-JUL-18:20 | 0.00 | 01-JUL-00:10 | 26324.18 | 07-JUL-12:00 | 0.00 |
August | 0.177318E+12 | 0.627638E+11 | 744.00 | 0.177318E+12 | 0.00 | 0.00 | 1.00 | 01-AUG-00:03 | 1.00 | 01-AUG-00:03 | 71528.11 | 08-AUG-04:57 | 71528.11 | 08-AUG-04:57 | 0.00 | 01-AUG-00:03 | 27985.32 | 24-AUG-16:00 | 0.00 |
September | 0.469698E+11 | 0.153814E+11 | 720.00 | 0.469698E+11 | 0.00 | 0.00 | 0.77 | 01-SEP-00:03 | 0.22 | 23-SEP-17:17 | 50072.99 | 01-SEP-00:03 | 50072.99 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 17199.57 | 01-SEP-00:03 | 0.00 |
October | 0.918918E+11 | 0.258776E+11 | 744.00 | 0.918918E+11 | 0.00 | 0.00 | 0.65 | 04-OCT-16:20 | 0.45 | 08-OCT-07:20 | 41211.06 | 04-OCT-16:30 | 41211.06 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 13837.05 | 02-OCT-16:40 | 0.00 |
November | 0.122224E+12 | 0.318296E+11 | 720.00 | 0.122224E+12 | 0.00 | 0.00 | 0.82 | 03-NOV-16:00 | 0.57 | 24-NOV-05:19 | 56751.57 | 03-NOV-16:00 | 56751.57 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 15443.53 | 03-NOV-14:00 | 0.00 |
December | 0.167197E+12 | 0.419062E+11 | 744.00 | 0.167197E+12 | 0.00 | 0.00 | 1.00 | 08-DEC-15:50 | 0.72 | 31-DEC-23:58 | 72442.57 | 21-DEC-16:20 | 72442.57 | 21-DEC-16:20 | 0.00 | 01-DEC-00:10 | 17719.34 | 21-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.127666E+13 | 0.377279E+12 | 8564.90 | 0.127666E+13 | 0.00 | ||||||||||||||
Minimum of Months | 0.158508E+11 | 0.482718E+10 | 548.90 | 0.158508E+11 | 0.00 | 0.00 | 0.31 | 0.00 | 19676.26 | 19676.26 | 0.00 | 5572.50 | 0.00 | ||||||
Maximum of Months | 0.177318E+12 | 0.627638E+11 | 744.00 | 0.177318E+12 | 0.00 | 0.00 | 1.00 | 1.00 | 73305.39 | 73305.39 | 0.00 | 27985.32 | 0.00 |
Report: DXReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 0.740167E+09 | 0.231448E+09 | 332.25 | 0.740167E+09 | 0.00 | 0.00 | 0.30 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 1885.44 | 20-JAN-16:40 | 1885.44 | 20-JAN-16:40 | 0.00 | 01-JAN-00:01 | 536.72 | 20-JAN-16:40 | 0.00 |
February | 0.453780E+10 | 0.128255E+10 | 651.39 | 0.453780E+10 | 0.00 | 0.00 | 0.56 | 02-FEB-17:00 | 0.00 | 05-FEB-06:33 | 3767.79 | 02-FEB-17:00 | 3767.79 | 02-FEB-17:00 | 0.00 | 01-FEB-00:10 | 1007.86 | 02-FEB-17:00 | 0.00 |
March | 0.115896E+11 | 0.304948E+10 | 744.00 | 0.115896E+11 | 0.00 | 0.00 | 0.86 | 27-MAR-17:10 | 0.41 | 13-MAR-03:13 | 5852.85 | 29-MAR-17:10 | 5852.85 | 29-MAR-17:10 | 0.00 | 01-MAR-00:10 | 1831.57 | 27-MAR-17:00 | 0.00 |
April | 0.168333E+11 | 0.436430E+10 | 720.00 | 0.168333E+11 | 0.00 | 0.00 | 1.00 | 03-APR-17:20 | 0.70 | 02-APR-07:10 | 7437.16 | 12-APR-17:50 | 7437.16 | 12-APR-17:50 | 0.00 | 01-APR-00:10 | 2479.57 | 07-APR-13:00 | 0.00 |
May | 0.438288E+10 | 0.133569E+10 | 744.00 | 0.438288E+10 | 0.00 | 0.00 | 0.39 | 30-MAY-16:00 | 0.11 | 01-MAY-06:00 | 2400.20 | 30-MAY-18:00 | 2400.20 | 30-MAY-18:00 | 0.00 | 01-MAY-00:05 | 939.38 | 30-MAY-16:00 | 0.00 |
June | 0.955510E+10 | 0.317553E+10 | 720.00 | 0.955510E+10 | 0.00 | 0.00 | 0.71 | 19-JUN-12:00 | 0.47 | 03-JUN-07:00 | 4405.87 | 18-JUN-17:52 | 4405.87 | 18-JUN-17:52 | 0.00 | 01-JUN-00:10 | 2031.95 | 19-JUN-12:00 | 0.00 |
July | 0.148225E+11 | 0.540153E+10 | 744.00 | 0.148225E+11 | 0.00 | 0.00 | 0.97 | 10-JUL-15:00 | 0.78 | 01-JUL-00:10 | 6130.67 | 04-JUL-17:56 | 6130.67 | 04-JUL-17:56 | 0.00 | 01-JUL-00:10 | 2676.62 | 07-JUL-12:00 | 0.00 |
August | 0.180063E+11 | 0.638936E+10 | 744.00 | 0.180063E+11 | 0.00 | 0.00 | 1.00 | 01-AUG-00:03 | 0.97 | 08-AUG-05:01 | 7200.48 | 20-AUG-02:33 | 7200.48 | 20-AUG-02:33 | 0.00 | 01-AUG-00:03 | 2849.83 | 24-AUG-16:00 | 0.00 |
September | 0.449459E+10 | 0.148723E+10 | 720.00 | 0.449459E+10 | 0.00 | 0.00 | 0.69 | 01-SEP-00:03 | 0.13 | 24-SEP-06:40 | 4487.51 | 01-SEP-00:03 | 4487.51 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 | 1572.25 | 01-SEP-00:03 | 0.00 |
October | 0.842808E+10 | 0.240377E+10 | 744.00 | 0.842808E+10 | 0.00 | 0.00 | 0.65 | 04-OCT-16:20 | 0.30 | 29-OCT-07:25 | 4181.53 | 04-OCT-16:30 | 4181.53 | 04-OCT-16:30 | 0.00 | 01-OCT-00:10 | 1402.06 | 04-OCT-16:10 | 0.00 |
November | 0.107137E+11 | 0.283565E+10 | 720.00 | 0.107137E+11 | 0.00 | 0.00 | 0.80 | 03-NOV-16:00 | 0.34 | 24-NOV-04:02 | 5660.36 | 03-NOV-16:00 | 5660.36 | 03-NOV-16:00 | 0.00 | 01-NOV-00:10 | 1539.12 | 03-NOV-15:00 | 0.00 |
December | 0.148137E+11 | 0.377997E+10 | 744.00 | 0.148137E+11 | 0.00 | 0.00 | 0.97 | 08-DEC-16:10 | 0.53 | 31-DEC-24:00 | 7102.60 | 08-DEC-16:10 | 7102.60 | 08-DEC-16:10 | 0.00 | 01-DEC-00:10 | 1750.93 | 08-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.118918E+12 | 0.357365E+11 | 8327.63 | 0.118918E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.740167E+09 | 0.231448E+09 | 332.25 | 0.740167E+09 | 0.00 | 0.00 | 0.30 | 0.00 | 1885.44 | 1885.44 | 0.00 | 536.72 | 0.00 | ||||||
Maximum of Months | 0.180063E+11 | 0.638936E+10 | 744.00 | 0.180063E+11 | 0.00 | 0.00 | 1.00 | 0.97 | 7437.16 | 7437.16 | 0.00 | 2849.83 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.14 | 0.00 | 87.14 | 0.10 | 603.61 | 0.00 | 0.00 | 744.00 |
February | 119.24 | 0.00 | 119.24 | 1.38 | 624.14 | 0.00 | 0.00 | 672.00 |
March | 165.36 | 0.00 | 165.36 | 23.71 | 429.82 | 0.00 | 0.00 | 744.00 |
April | 198.61 | 0.56 | 198.06 | 75.90 | 302.45 | 0.00 | 0.00 | 720.00 |
May | 263.48 | 8.75 | 254.73 | 177.07 | 170.42 | 0.00 | 0.00 | 744.00 |
June | 279.41 | 14.98 | 264.43 | 269.45 | 86.79 | 0.00 | 0.00 | 720.00 |
July | 270.03 | 9.74 | 260.29 | 317.25 | 43.73 | 0.00 | 0.00 | 744.00 |
August | 239.24 | 2.83 | 236.41 | 282.40 | 61.42 | 0.00 | 0.00 | 744.00 |
September | 180.36 | 0.03 | 180.33 | 152.40 | 138.62 | 0.00 | 0.00 | 720.00 |
October | 156.09 | 0.00 | 156.09 | 75.65 | 266.64 | 0.00 | 0.00 | 744.00 |
November | 109.48 | 0.00 | 109.48 | 10.62 | 446.76 | 0.00 | 0.00 | 720.00 |
December | 76.01 | 0.00 | 76.01 | 0.10 | 587.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 179.05 | 3.09 | 175.96 | 116.31 | 311.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 76.01 | 0.00 | 76.01 | 0.10 | 43.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.41 | 14.98 | 264.43 | 317.25 | 624.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.14 | 0.00 | 87.14 | 0.10 | 603.61 | 0.00 | 0.00 | 744.00 |
February | 119.24 | 0.00 | 119.24 | 1.38 | 624.14 | 0.00 | 0.00 | 672.00 |
March | 165.36 | 0.00 | 165.36 | 23.71 | 429.82 | 0.00 | 0.00 | 744.00 |
April | 198.61 | 0.56 | 198.05 | 75.90 | 302.45 | 0.00 | 0.00 | 720.00 |
May | 263.48 | 8.75 | 254.72 | 177.06 | 170.42 | 0.00 | 0.00 | 744.00 |
June | 279.41 | 14.98 | 264.43 | 269.45 | 86.79 | 0.00 | 0.00 | 720.00 |
July | 270.03 | 9.74 | 260.29 | 317.25 | 43.73 | 0.00 | 0.00 | 744.00 |
August | 239.24 | 2.83 | 236.41 | 282.40 | 61.42 | 0.00 | 0.00 | 744.00 |
September | 180.36 | 0.03 | 180.33 | 152.40 | 138.62 | 0.00 | 0.00 | 720.00 |
October | 156.09 | 0.00 | 156.09 | 75.65 | 266.64 | 0.00 | 0.00 | 744.00 |
November | 109.48 | 0.00 | 109.48 | 10.62 | 446.76 | 0.00 | 0.00 | 720.00 |
December | 76.01 | 0.00 | 76.01 | 0.10 | 587.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 179.05 | 3.09 | 175.96 | 116.31 | 311.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 76.01 | 0.00 | 76.01 | 0.10 | 43.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.41 | 14.98 | 264.43 | 317.25 | 624.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.14 | 0.00 | 87.14 | 0.10 | 603.61 | 0.00 | 0.00 | 744.00 |
February | 119.24 | 0.00 | 119.24 | 1.38 | 624.14 | 0.00 | 0.00 | 672.00 |
March | 165.36 | 0.00 | 165.36 | 23.71 | 429.82 | 0.00 | 0.00 | 744.00 |
April | 198.61 | 0.56 | 198.06 | 75.90 | 302.45 | 0.00 | 0.00 | 720.00 |
May | 263.48 | 8.75 | 254.73 | 177.06 | 170.42 | 0.00 | 0.00 | 744.00 |
June | 279.41 | 14.98 | 264.43 | 269.45 | 86.79 | 0.00 | 0.00 | 720.00 |
July | 270.03 | 9.74 | 260.29 | 317.25 | 43.73 | 0.00 | 0.00 | 744.00 |
August | 239.24 | 2.83 | 236.41 | 282.40 | 61.42 | 0.00 | 0.00 | 744.00 |
September | 180.36 | 0.03 | 180.33 | 152.40 | 138.62 | 0.00 | 0.00 | 720.00 |
October | 156.09 | 0.00 | 156.09 | 75.65 | 266.64 | 0.00 | 0.00 | 744.00 |
November | 109.48 | 0.00 | 109.48 | 10.62 | 446.76 | 0.00 | 0.00 | 720.00 |
December | 76.01 | 0.00 | 76.01 | 0.10 | 587.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 179.05 | 3.09 | 175.96 | 116.31 | 311.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 76.01 | 0.00 | 76.01 | 0.10 | 43.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.41 | 14.98 | 264.43 | 317.25 | 624.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.14 | 0.00 | 87.14 | 0.10 | 603.61 | 0.00 | 0.00 | 744.00 |
February | 119.24 | 0.00 | 119.24 | 1.38 | 624.14 | 0.00 | 0.00 | 672.00 |
March | 165.36 | 0.00 | 165.36 | 23.71 | 429.82 | 0.00 | 0.00 | 744.00 |
April | 198.61 | 0.56 | 198.05 | 75.90 | 302.45 | 0.00 | 0.00 | 720.00 |
May | 263.48 | 8.75 | 254.72 | 177.06 | 170.42 | 0.00 | 0.00 | 744.00 |
June | 279.41 | 14.98 | 264.43 | 269.45 | 86.79 | 0.00 | 0.00 | 720.00 |
July | 270.03 | 9.74 | 260.29 | 317.25 | 43.73 | 0.00 | 0.00 | 744.00 |
August | 239.24 | 2.83 | 236.41 | 282.40 | 61.42 | 0.00 | 0.00 | 744.00 |
September | 180.36 | 0.03 | 180.33 | 152.40 | 138.62 | 0.00 | 0.00 | 720.00 |
October | 156.09 | 0.00 | 156.09 | 75.65 | 266.64 | 0.00 | 0.00 | 744.00 |
November | 109.48 | 0.00 | 109.48 | 10.62 | 446.76 | 0.00 | 0.00 | 720.00 |
December | 76.01 | 0.00 | 76.01 | 0.10 | 587.92 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 179.05 | 3.09 | 175.96 | 116.31 | 311.74 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 76.01 | 0.00 | 76.01 | 0.10 | 43.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.41 | 14.98 | 264.43 | 317.25 | 624.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 87.13 | 0.00 | 87.13 | 0.10 | 603.59 | 0.00 | 0.00 | 744.00 |
February | 119.24 | 0.00 | 119.24 | 1.38 | 624.12 | 0.00 | 0.00 | 672.00 |
March | 165.35 | 0.00 | 165.35 | 23.71 | 429.80 | 0.00 | 0.00 | 744.00 |
April | 198.60 | 0.56 | 198.05 | 75.90 | 302.43 | 0.00 | 0.00 | 720.00 |
May | 263.47 | 8.75 | 254.72 | 177.06 | 170.41 | 0.00 | 0.00 | 744.00 |
June | 279.40 | 14.98 | 264.42 | 269.44 | 86.78 | 0.00 | 0.00 | 720.00 |
July | 270.02 | 9.74 | 260.28 | 317.24 | 43.73 | 0.00 | 0.00 | 744.00 |
August | 239.23 | 2.83 | 236.40 | 282.38 | 61.42 | 0.00 | 0.00 | 744.00 |
September | 180.35 | 0.03 | 180.32 | 152.39 | 138.61 | 0.00 | 0.00 | 720.00 |
October | 156.08 | 0.00 | 156.08 | 75.65 | 266.63 | 0.00 | 0.00 | 744.00 |
November | 109.48 | 0.00 | 109.48 | 10.62 | 446.74 | 0.00 | 0.00 | 720.00 |
December | 76.00 | 0.00 | 76.00 | 0.10 | 587.90 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 179.04 | 3.09 | 175.95 | 116.31 | 311.73 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 76.00 | 0.00 | 76.00 | 0.10 | 43.73 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 279.40 | 14.98 | 264.42 | 317.24 | 624.12 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.27 | 81.11 | 121.16 | 76.29 | 610.29 | 0.00 | 0.00 | 744.00 |
February | 313.64 | 146.32 | 167.33 | 151.37 | 606.76 | 0.00 | 0.00 | 672.00 |
March | 400.11 | 170.17 | 229.94 | 267.18 | 437.91 | 0.00 | 0.00 | 744.00 |
April | 480.18 | 210.35 | 269.83 | 390.52 | 304.90 | 0.00 | 0.00 | 720.00 |
May | 582.28 | 232.68 | 349.60 | 564.84 | 185.11 | 0.00 | 0.00 | 744.00 |
June | 539.64 | 195.31 | 344.33 | 597.01 | 93.82 | 0.00 | 0.00 | 720.00 |
July | 542.01 | 195.57 | 346.44 | 666.40 | 43.78 | 0.00 | 0.00 | 744.00 |
August | 610.36 | 275.20 | 335.16 | 751.73 | 60.64 | 0.00 | 0.00 | 744.00 |
September | 455.26 | 204.28 | 250.98 | 477.20 | 143.67 | 0.00 | 0.00 | 720.00 |
October | 412.70 | 187.06 | 225.65 | 361.47 | 274.67 | 0.00 | 0.00 | 744.00 |
November | 255.24 | 98.02 | 157.21 | 134.57 | 441.78 | 0.00 | 0.00 | 720.00 |
December | 198.86 | 93.39 | 105.47 | 81.80 | 574.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 416.71 | 174.32 | 242.39 | 378.30 | 313.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 198.86 | 81.11 | 105.47 | 76.29 | 43.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 610.36 | 275.20 | 349.60 | 751.73 | 610.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.27 | 81.11 | 121.16 | 76.29 | 610.29 | 0.00 | 0.00 | 744.00 |
February | 313.64 | 146.32 | 167.33 | 151.37 | 606.76 | 0.00 | 0.00 | 672.00 |
March | 400.11 | 170.17 | 229.94 | 267.18 | 437.91 | 0.00 | 0.00 | 744.00 |
April | 480.18 | 210.35 | 269.83 | 390.52 | 304.90 | 0.00 | 0.00 | 720.00 |
May | 582.28 | 232.68 | 349.60 | 564.84 | 185.11 | 0.00 | 0.00 | 744.00 |
June | 539.64 | 195.31 | 344.33 | 597.01 | 93.82 | 0.00 | 0.00 | 720.00 |
July | 542.01 | 195.57 | 346.44 | 666.40 | 43.78 | 0.00 | 0.00 | 744.00 |
August | 610.36 | 275.20 | 335.16 | 751.73 | 60.64 | 0.00 | 0.00 | 744.00 |
September | 455.26 | 204.28 | 250.98 | 477.20 | 143.67 | 0.00 | 0.00 | 720.00 |
October | 412.70 | 187.06 | 225.65 | 361.47 | 274.67 | 0.00 | 0.00 | 744.00 |
November | 255.24 | 98.02 | 157.21 | 134.57 | 441.78 | 0.00 | 0.00 | 720.00 |
December | 198.86 | 93.39 | 105.47 | 81.80 | 574.21 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 416.71 | 174.32 | 242.39 | 378.30 | 313.15 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 198.86 | 81.11 | 105.47 | 76.29 | 43.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 610.36 | 275.20 | 349.60 | 751.73 | 610.29 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 202.26 | 81.10 | 121.16 | 76.29 | 610.28 | 0.00 | 0.00 | 744.00 |
February | 313.64 | 146.31 | 167.32 | 151.37 | 606.75 | 0.00 | 0.00 | 672.00 |
March | 400.10 | 170.16 | 229.94 | 267.17 | 437.90 | 0.00 | 0.00 | 744.00 |
April | 480.17 | 210.34 | 269.83 | 390.51 | 304.90 | 0.00 | 0.00 | 720.00 |
May | 582.27 | 232.68 | 349.59 | 564.83 | 185.10 | 0.00 | 0.00 | 744.00 |
June | 539.63 | 195.31 | 344.32 | 597.00 | 93.82 | 0.00 | 0.00 | 720.00 |
July | 542.00 | 195.56 | 346.44 | 666.39 | 43.78 | 0.00 | 0.00 | 744.00 |
August | 610.35 | 275.20 | 335.15 | 751.71 | 60.64 | 0.00 | 0.00 | 744.00 |
September | 455.25 | 204.27 | 250.98 | 477.19 | 143.67 | 0.00 | 0.00 | 720.00 |
October | 412.70 | 187.05 | 225.64 | 361.46 | 274.67 | 0.00 | 0.00 | 744.00 |
November | 255.23 | 98.02 | 157.21 | 134.56 | 441.77 | 0.00 | 0.00 | 720.00 |
December | 198.86 | 93.39 | 105.47 | 81.80 | 574.20 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 416.70 | 174.31 | 242.38 | 378.29 | 313.14 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 198.86 | 81.10 | 105.47 | 76.29 | 43.78 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 610.35 | 275.20 | 349.59 | 751.71 | 610.28 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.79 | 295.18 | 155.60 | 392.62 | 501.38 | 0.00 | 0.00 | 744.00 |
February | 594.81 | 393.80 | 201.01 | 507.02 | 512.39 | 0.00 | 0.00 | 672.00 |
March | 536.58 | 297.89 | 238.69 | 431.65 | 391.89 | 0.00 | 0.00 | 744.00 |
April | 416.17 | 164.53 | 251.64 | 283.05 | 291.63 | 0.00 | 0.00 | 720.00 |
May | 364.71 | 76.03 | 288.68 | 265.24 | 177.06 | 0.00 | 0.00 | 744.00 |
June | 342.25 | 52.25 | 289.99 | 318.20 | 92.24 | 0.00 | 0.00 | 720.00 |
July | 358.76 | 62.26 | 296.49 | 386.43 | 45.47 | 0.00 | 0.00 | 744.00 |
August | 479.09 | 177.66 | 301.44 | 497.80 | 64.88 | 0.00 | 0.00 | 744.00 |
September | 519.97 | 268.99 | 250.99 | 529.13 | 138.21 | 0.00 | 0.00 | 720.00 |
October | 712.56 | 446.95 | 265.61 | 744.10 | 254.51 | 0.00 | 0.00 | 744.00 |
November | 493.93 | 296.65 | 197.28 | 459.97 | 381.32 | 0.00 | 0.00 | 720.00 |
December | 488.51 | 346.79 | 141.72 | 454.72 | 474.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.30 | 239.14 | 240.17 | 439.06 | 275.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 342.25 | 52.25 | 141.72 | 265.24 | 45.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 712.56 | 446.95 | 301.44 | 744.10 | 512.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.78 | 295.18 | 155.60 | 392.62 | 501.38 | 0.00 | 0.00 | 744.00 |
February | 594.81 | 393.80 | 201.01 | 507.02 | 512.39 | 0.00 | 0.00 | 672.00 |
March | 536.58 | 297.89 | 238.69 | 431.65 | 391.89 | 0.00 | 0.00 | 744.00 |
April | 416.17 | 164.53 | 251.64 | 283.04 | 291.63 | 0.00 | 0.00 | 720.00 |
May | 364.71 | 76.03 | 288.68 | 265.24 | 177.06 | 0.00 | 0.00 | 744.00 |
June | 342.24 | 52.25 | 289.99 | 318.20 | 92.24 | 0.00 | 0.00 | 720.00 |
July | 358.76 | 62.26 | 296.49 | 386.42 | 45.47 | 0.00 | 0.00 | 744.00 |
August | 479.09 | 177.66 | 301.43 | 497.80 | 64.88 | 0.00 | 0.00 | 744.00 |
September | 519.97 | 268.98 | 250.99 | 529.12 | 138.21 | 0.00 | 0.00 | 720.00 |
October | 712.56 | 446.95 | 265.61 | 744.10 | 254.51 | 0.00 | 0.00 | 744.00 |
November | 493.93 | 296.65 | 197.27 | 459.96 | 381.32 | 0.00 | 0.00 | 720.00 |
December | 488.51 | 346.79 | 141.72 | 454.72 | 474.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.30 | 239.13 | 240.16 | 439.06 | 275.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 342.24 | 52.25 | 141.72 | 265.24 | 45.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 712.56 | 446.95 | 301.43 | 744.10 | 512.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.79 | 295.18 | 155.60 | 392.62 | 501.38 | 0.00 | 0.00 | 744.00 |
February | 594.81 | 393.80 | 201.01 | 507.02 | 512.39 | 0.00 | 0.00 | 672.00 |
March | 536.58 | 297.89 | 238.69 | 431.65 | 391.89 | 0.00 | 0.00 | 744.00 |
April | 416.17 | 164.53 | 251.64 | 283.05 | 291.63 | 0.00 | 0.00 | 720.00 |
May | 364.71 | 76.03 | 288.68 | 265.24 | 177.06 | 0.00 | 0.00 | 744.00 |
June | 342.25 | 52.25 | 289.99 | 318.20 | 92.24 | 0.00 | 0.00 | 720.00 |
July | 358.76 | 62.26 | 296.49 | 386.43 | 45.47 | 0.00 | 0.00 | 744.00 |
August | 479.09 | 177.66 | 301.44 | 497.80 | 64.88 | 0.00 | 0.00 | 744.00 |
September | 519.97 | 268.99 | 250.99 | 529.13 | 138.21 | 0.00 | 0.00 | 720.00 |
October | 712.56 | 446.95 | 265.61 | 744.10 | 254.51 | 0.00 | 0.00 | 744.00 |
November | 493.93 | 296.65 | 197.28 | 459.97 | 381.32 | 0.00 | 0.00 | 720.00 |
December | 488.51 | 346.79 | 141.72 | 454.72 | 474.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.30 | 239.14 | 240.17 | 439.06 | 275.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 342.25 | 52.25 | 141.72 | 265.24 | 45.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 712.56 | 446.95 | 301.44 | 744.10 | 512.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.78 | 295.18 | 155.60 | 392.62 | 501.38 | 0.00 | 0.00 | 744.00 |
February | 594.81 | 393.80 | 201.01 | 507.02 | 512.39 | 0.00 | 0.00 | 672.00 |
March | 536.58 | 297.89 | 238.69 | 431.65 | 391.89 | 0.00 | 0.00 | 744.00 |
April | 416.17 | 164.53 | 251.64 | 283.04 | 291.63 | 0.00 | 0.00 | 720.00 |
May | 364.71 | 76.03 | 288.68 | 265.24 | 177.06 | 0.00 | 0.00 | 744.00 |
June | 342.24 | 52.25 | 289.99 | 318.20 | 92.24 | 0.00 | 0.00 | 720.00 |
July | 358.76 | 62.26 | 296.49 | 386.42 | 45.47 | 0.00 | 0.00 | 744.00 |
August | 479.09 | 177.66 | 301.43 | 497.80 | 64.88 | 0.00 | 0.00 | 744.00 |
September | 519.97 | 268.98 | 250.99 | 529.12 | 138.21 | 0.00 | 0.00 | 720.00 |
October | 712.56 | 446.95 | 265.61 | 744.10 | 254.51 | 0.00 | 0.00 | 744.00 |
November | 493.93 | 296.65 | 197.27 | 459.96 | 381.32 | 0.00 | 0.00 | 720.00 |
December | 488.51 | 346.79 | 141.72 | 454.72 | 474.72 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.30 | 239.13 | 240.16 | 439.06 | 275.77 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 342.24 | 52.25 | 141.72 | 265.24 | 45.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 712.56 | 446.95 | 301.43 | 744.10 | 512.39 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 450.77 | 295.17 | 155.60 | 392.60 | 501.36 | 0.00 | 0.00 | 744.00 |
February | 594.78 | 393.78 | 201.00 | 507.00 | 512.37 | 0.00 | 0.00 | 672.00 |
March | 536.56 | 297.88 | 238.68 | 431.63 | 391.87 | 0.00 | 0.00 | 744.00 |
April | 416.15 | 164.52 | 251.63 | 283.03 | 291.62 | 0.00 | 0.00 | 720.00 |
May | 364.69 | 76.02 | 288.67 | 265.23 | 177.05 | 0.00 | 0.00 | 744.00 |
June | 342.23 | 52.25 | 289.98 | 318.18 | 92.24 | 0.00 | 0.00 | 720.00 |
July | 358.74 | 62.26 | 296.48 | 386.41 | 45.47 | 0.00 | 0.00 | 744.00 |
August | 479.07 | 177.65 | 301.42 | 497.78 | 64.87 | 0.00 | 0.00 | 744.00 |
September | 519.95 | 268.97 | 250.98 | 529.10 | 138.20 | 0.00 | 0.00 | 720.00 |
October | 712.53 | 446.93 | 265.60 | 744.07 | 254.50 | 0.00 | 0.00 | 744.00 |
November | 493.91 | 296.64 | 197.27 | 459.95 | 381.30 | 0.00 | 0.00 | 720.00 |
December | 488.49 | 346.77 | 141.71 | 454.70 | 474.70 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 479.28 | 239.13 | 240.16 | 439.04 | 275.76 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 342.23 | 52.25 | 141.71 | 265.23 | 45.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 712.53 | 446.93 | 301.42 | 744.07 | 512.37 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.68 | 81.80 | 117.88 | 78.96 | 654.78 | 0.00 | 0.00 | 744.00 |
February | 294.43 | 129.32 | 165.12 | 136.35 | 679.93 | 0.00 | 0.00 | 672.00 |
March | 434.80 | 200.75 | 234.05 | 297.38 | 489.88 | 0.00 | 0.00 | 744.00 |
April | 475.19 | 203.33 | 271.86 | 377.47 | 369.06 | 0.00 | 0.00 | 720.00 |
May | 553.48 | 210.15 | 343.32 | 527.91 | 210.53 | 0.00 | 0.00 | 744.00 |
June | 605.76 | 244.28 | 361.48 | 670.61 | 120.07 | 0.00 | 0.00 | 720.00 |
July | 567.34 | 213.61 | 353.73 | 679.96 | 70.16 | 0.00 | 0.00 | 744.00 |
August | 627.68 | 290.57 | 337.11 | 756.33 | 96.63 | 0.00 | 0.00 | 744.00 |
September | 445.64 | 194.76 | 250.88 | 467.38 | 169.67 | 0.00 | 0.00 | 720.00 |
October | 441.79 | 214.83 | 226.96 | 395.95 | 316.70 | 0.00 | 0.00 | 744.00 |
November | 207.46 | 59.96 | 147.50 | 81.25 | 516.21 | 0.00 | 0.00 | 720.00 |
December | 184.56 | 79.87 | 104.68 | 68.16 | 672.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 420.70 | 177.34 | 243.35 | 379.90 | 362.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 184.56 | 59.96 | 104.68 | 68.16 | 70.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 627.68 | 290.57 | 361.48 | 756.33 | 679.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.68 | 81.80 | 117.88 | 78.96 | 654.78 | 0.00 | 0.00 | 744.00 |
February | 294.43 | 129.32 | 165.12 | 136.35 | 679.93 | 0.00 | 0.00 | 672.00 |
March | 434.80 | 200.75 | 234.05 | 297.38 | 489.88 | 0.00 | 0.00 | 744.00 |
April | 475.19 | 203.33 | 271.86 | 377.47 | 369.06 | 0.00 | 0.00 | 720.00 |
May | 553.48 | 210.15 | 343.32 | 527.91 | 210.53 | 0.00 | 0.00 | 744.00 |
June | 605.76 | 244.28 | 361.48 | 670.61 | 120.07 | 0.00 | 0.00 | 720.00 |
July | 567.34 | 213.61 | 353.73 | 679.96 | 70.16 | 0.00 | 0.00 | 744.00 |
August | 627.68 | 290.57 | 337.11 | 756.33 | 96.63 | 0.00 | 0.00 | 744.00 |
September | 445.64 | 194.76 | 250.88 | 467.38 | 169.67 | 0.00 | 0.00 | 720.00 |
October | 441.79 | 214.83 | 226.96 | 395.95 | 316.70 | 0.00 | 0.00 | 744.00 |
November | 207.46 | 59.96 | 147.50 | 81.25 | 516.21 | 0.00 | 0.00 | 720.00 |
December | 184.56 | 79.87 | 104.68 | 68.16 | 672.80 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 420.70 | 177.34 | 243.35 | 379.90 | 362.04 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 184.56 | 59.96 | 104.68 | 68.16 | 70.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 627.68 | 290.57 | 361.48 | 756.33 | 679.93 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 199.68 | 81.80 | 117.88 | 78.95 | 654.76 | 0.00 | 0.00 | 744.00 |
February | 294.43 | 129.31 | 165.11 | 136.35 | 679.92 | 0.00 | 0.00 | 672.00 |
March | 434.79 | 200.75 | 234.04 | 297.37 | 489.87 | 0.00 | 0.00 | 744.00 |
April | 475.18 | 203.33 | 271.86 | 377.46 | 369.06 | 0.00 | 0.00 | 720.00 |
May | 553.47 | 210.15 | 343.32 | 527.90 | 210.53 | 0.00 | 0.00 | 744.00 |
June | 605.75 | 244.27 | 361.47 | 670.60 | 120.07 | 0.00 | 0.00 | 720.00 |
July | 567.33 | 213.61 | 353.72 | 679.95 | 70.16 | 0.00 | 0.00 | 744.00 |
August | 627.67 | 290.56 | 337.10 | 756.31 | 96.63 | 0.00 | 0.00 | 744.00 |
September | 445.63 | 194.75 | 250.87 | 467.37 | 169.67 | 0.00 | 0.00 | 720.00 |
October | 441.78 | 214.83 | 226.95 | 395.94 | 316.70 | 0.00 | 0.00 | 744.00 |
November | 207.46 | 59.96 | 147.50 | 81.25 | 516.20 | 0.00 | 0.00 | 720.00 |
December | 184.55 | 79.87 | 104.68 | 68.16 | 672.79 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 420.69 | 177.34 | 243.35 | 379.89 | 362.03 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 184.55 | 59.96 | 104.68 | 68.16 | 70.16 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 627.67 | 290.56 | 361.47 | 756.31 | 679.92 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 435.69 | 0.00 | 435.69 | 3.71 | 2653.22 | 0.00 | 0.00 | 744.00 |
February | 596.22 | 0.00 | 596.22 | 18.01 | 2791.32 | 0.00 | 0.00 | 672.00 |
March | 826.81 | 0.00 | 826.81 | 159.97 | 1878.39 | 0.00 | 0.00 | 744.00 |
April | 993.07 | 2.78 | 990.29 | 429.46 | 1331.51 | 0.00 | 0.00 | 720.00 |
May | 1317.40 | 43.76 | 1273.64 | 914.65 | 791.77 | 0.00 | 0.00 | 744.00 |
June | 1397.07 | 74.91 | 1322.16 | 1366.67 | 409.84 | 0.00 | 0.00 | 720.00 |
July | 1350.15 | 48.69 | 1301.47 | 1601.23 | 217.18 | 0.00 | 0.00 | 744.00 |
August | 1196.20 | 14.14 | 1182.06 | 1432.37 | 303.87 | 0.00 | 0.00 | 744.00 |
September | 901.80 | 0.16 | 901.64 | 786.92 | 633.27 | 0.00 | 0.00 | 720.00 |
October | 780.45 | 0.00 | 780.45 | 415.57 | 1194.95 | 0.00 | 0.00 | 744.00 |
November | 547.41 | 0.00 | 547.41 | 75.14 | 1911.76 | 0.00 | 0.00 | 720.00 |
December | 380.04 | 0.00 | 380.04 | 2.72 | 2516.75 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 895.24 | 15.45 | 879.79 | 604.62 | 1378.05 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 380.04 | 0.00 | 380.04 | 2.72 | 217.18 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1397.07 | 74.91 | 1322.16 | 1601.23 | 2791.32 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 606.80 | 243.31 | 363.48 | 246.39 | 1629.02 | 0.00 | 0.00 | 744.00 |
February | 940.92 | 438.94 | 501.98 | 478.48 | 1656.88 | 0.00 | 0.00 | 672.00 |
March | 1200.31 | 510.49 | 689.81 | 822.04 | 1194.24 | 0.00 | 0.00 | 744.00 |
April | 1440.53 | 631.04 | 809.49 | 1184.01 | 848.84 | 0.00 | 0.00 | 720.00 |
May | 1746.81 | 698.03 | 1048.78 | 1695.58 | 528.78 | 0.00 | 0.00 | 744.00 |
June | 1618.92 | 585.93 | 1032.98 | 1783.75 | 278.82 | 0.00 | 0.00 | 720.00 |
July | 1626.01 | 586.69 | 1039.32 | 1986.00 | 147.34 | 0.00 | 0.00 | 744.00 |
August | 1831.06 | 825.61 | 1005.46 | 2240.76 | 202.38 | 0.00 | 0.00 | 744.00 |
September | 1365.76 | 612.82 | 752.93 | 1433.87 | 407.32 | 0.00 | 0.00 | 720.00 |
October | 1238.10 | 561.17 | 676.93 | 1096.93 | 767.52 | 0.00 | 0.00 | 744.00 |
November | 765.70 | 294.07 | 471.63 | 428.50 | 1173.76 | 0.00 | 0.00 | 720.00 |
December | 596.57 | 280.16 | 316.41 | 263.82 | 1527.55 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1250.11 | 522.95 | 727.16 | 1143.01 | 859.06 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 596.57 | 243.31 | 316.41 | 246.39 | 147.34 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1831.06 | 825.61 | 1048.78 | 2240.76 | 1656.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2253.97 | 1475.94 | 778.04 | 1976.73 | 2356.31 | 0.00 | 0.00 | 744.00 |
February | 2974.11 | 1969.05 | 1005.06 | 2538.42 | 2453.14 | 0.00 | 0.00 | 672.00 |
March | 2682.97 | 1489.50 | 1193.47 | 2164.63 | 1849.52 | 0.00 | 0.00 | 744.00 |
April | 2080.88 | 822.66 | 1258.22 | 1436.22 | 1367.76 | 0.00 | 0.00 | 720.00 |
May | 1823.57 | 380.15 | 1443.42 | 1338.15 | 851.19 | 0.00 | 0.00 | 744.00 |
June | 1711.25 | 261.26 | 1449.99 | 1602.64 | 445.04 | 0.00 | 0.00 | 720.00 |
July | 1793.82 | 311.33 | 1482.49 | 1945.04 | 229.28 | 0.00 | 0.00 | 744.00 |
August | 2395.51 | 888.31 | 1507.20 | 2500.82 | 329.68 | 0.00 | 0.00 | 744.00 |
September | 2599.92 | 1344.96 | 1254.96 | 2641.88 | 669.60 | 0.00 | 0.00 | 720.00 |
October | 3562.87 | 2234.81 | 1328.06 | 3703.20 | 1238.28 | 0.00 | 0.00 | 744.00 |
November | 2469.69 | 1483.29 | 986.40 | 2308.03 | 1790.77 | 0.00 | 0.00 | 720.00 |
December | 2442.59 | 1733.99 | 708.61 | 2285.05 | 2221.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2396.55 | 1195.71 | 1200.85 | 2202.91 | 1310.21 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1711.25 | 261.26 | 708.61 | 1338.15 | 229.28 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3562.87 | 2234.81 | 1507.20 | 3703.20 | 2453.14 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.05 | 245.41 | 353.64 | 255.60 | 1704.68 | 0.00 | 0.00 | 744.00 |
February | 883.29 | 387.94 | 495.34 | 439.53 | 1767.47 | 0.00 | 0.00 | 672.00 |
March | 1304.37 | 602.24 | 702.13 | 937.93 | 1227.46 | 0.00 | 0.00 | 744.00 |
April | 1425.56 | 609.99 | 815.57 | 1187.57 | 913.72 | 0.00 | 0.00 | 720.00 |
May | 1660.41 | 630.45 | 1029.96 | 1607.37 | 572.96 | 0.00 | 0.00 | 744.00 |
June | 1817.25 | 732.83 | 1084.42 | 2035.60 | 317.62 | 0.00 | 0.00 | 720.00 |
July | 1702.00 | 640.83 | 1061.17 | 2073.47 | 178.08 | 0.00 | 0.00 | 744.00 |
August | 1883.01 | 871.70 | 1011.31 | 2306.41 | 248.78 | 0.00 | 0.00 | 744.00 |
September | 1336.90 | 584.27 | 752.63 | 1425.26 | 449.95 | 0.00 | 0.00 | 720.00 |
October | 1325.35 | 644.49 | 680.86 | 1223.61 | 824.25 | 0.00 | 0.00 | 744.00 |
November | 622.39 | 179.88 | 442.51 | 281.30 | 1248.42 | 0.00 | 0.00 | 720.00 |
December | 553.66 | 239.61 | 314.05 | 234.55 | 1617.40 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1262.08 | 532.02 | 730.06 | 1172.62 | 917.71 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 553.66 | 179.88 | 314.05 | 234.55 | 178.08 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1883.01 | 871.70 | 1084.42 | 2306.41 | 1767.47 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 435.69 | 0.00 | 435.69 | 5.96 | 2518.31 | 0.00 | 0.00 | 744.00 |
February | 596.22 | 0.00 | 596.22 | 27.23 | 2632.57 | 0.00 | 0.00 | 672.00 |
March | 826.81 | 0.00 | 826.81 | 179.15 | 1743.97 | 0.00 | 0.00 | 744.00 |
April | 993.07 | 2.78 | 990.29 | 452.51 | 1238.81 | 0.00 | 0.00 | 720.00 |
May | 1317.40 | 43.76 | 1273.64 | 920.30 | 759.91 | 0.00 | 0.00 | 744.00 |
June | 1397.07 | 74.91 | 1322.16 | 1352.91 | 407.76 | 0.00 | 0.00 | 720.00 |
July | 1350.15 | 48.69 | 1301.47 | 1577.81 | 225.20 | 0.00 | 0.00 | 744.00 |
August | 1196.20 | 14.14 | 1182.06 | 1415.78 | 306.91 | 0.00 | 0.00 | 744.00 |
September | 901.80 | 0.16 | 901.64 | 788.71 | 607.65 | 0.00 | 0.00 | 720.00 |
October | 780.45 | 0.00 | 780.45 | 441.81 | 1103.58 | 0.00 | 0.00 | 744.00 |
November | 547.41 | 0.00 | 547.41 | 95.20 | 1732.10 | 0.00 | 0.00 | 720.00 |
December | 380.04 | 0.00 | 380.04 | 7.09 | 2313.95 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 895.24 | 15.45 | 879.79 | 609.39 | 1291.58 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 380.04 | 0.00 | 380.04 | 5.96 | 225.20 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1397.07 | 74.91 | 1322.16 | 1577.81 | 2632.57 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 606.80 | 243.31 | 363.48 | 253.85 | 1548.91 | 0.00 | 0.00 | 744.00 |
February | 940.92 | 438.94 | 501.98 | 496.56 | 1563.49 | 0.00 | 0.00 | 672.00 |
March | 1200.31 | 510.49 | 689.81 | 840.99 | 1114.82 | 0.00 | 0.00 | 744.00 |
April | 1440.53 | 631.04 | 809.49 | 1201.09 | 798.71 | 0.00 | 0.00 | 720.00 |
May | 1746.81 | 698.03 | 1048.78 | 1697.30 | 512.04 | 0.00 | 0.00 | 744.00 |
June | 1618.92 | 585.93 | 1032.98 | 1774.10 | 278.72 | 0.00 | 0.00 | 720.00 |
July | 1626.01 | 586.69 | 1039.32 | 1971.42 | 152.88 | 0.00 | 0.00 | 744.00 |
August | 1831.06 | 825.61 | 1005.46 | 2229.27 | 205.07 | 0.00 | 0.00 | 744.00 |
September | 1365.76 | 612.82 | 752.93 | 1434.18 | 393.95 | 0.00 | 0.00 | 720.00 |
October | 1238.10 | 561.17 | 676.93 | 1114.92 | 717.22 | 0.00 | 0.00 | 744.00 |
November | 765.70 | 294.07 | 471.63 | 453.04 | 1071.81 | 0.00 | 0.00 | 720.00 |
December | 596.57 | 280.16 | 316.41 | 278.40 | 1407.45 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1250.11 | 522.95 | 727.16 | 1149.99 | 809.54 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 596.57 | 243.31 | 316.41 | 253.85 | 152.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1831.06 | 825.61 | 1048.78 | 2229.27 | 1563.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2253.97 | 1475.94 | 778.04 | 1997.43 | 2225.25 | 0.00 | 0.00 | 744.00 |
February | 2974.11 | 1969.05 | 1005.06 | 2575.93 | 2294.49 | 0.00 | 0.00 | 672.00 |
March | 2682.97 | 1489.50 | 1193.47 | 2189.12 | 1717.70 | 0.00 | 0.00 | 744.00 |
April | 2080.88 | 822.66 | 1258.22 | 1461.70 | 1279.48 | 0.00 | 0.00 | 720.00 |
May | 1823.57 | 380.15 | 1443.42 | 1344.06 | 819.56 | 0.00 | 0.00 | 744.00 |
June | 1711.25 | 261.26 | 1449.99 | 1590.44 | 443.53 | 0.00 | 0.00 | 720.00 |
July | 1793.82 | 311.33 | 1482.49 | 1924.79 | 237.60 | 0.00 | 0.00 | 744.00 |
August | 2395.51 | 888.31 | 1507.20 | 2487.90 | 332.23 | 0.00 | 0.00 | 744.00 |
September | 2599.92 | 1344.96 | 1254.96 | 2644.18 | 645.70 | 0.00 | 0.00 | 720.00 |
October | 3562.87 | 2234.81 | 1328.06 | 3726.69 | 1159.76 | 0.00 | 0.00 | 744.00 |
November | 2469.69 | 1483.29 | 986.40 | 2349.83 | 1634.37 | 0.00 | 0.00 | 720.00 |
December | 2442.59 | 1733.99 | 708.61 | 2326.20 | 2037.77 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 2396.55 | 1195.71 | 1200.85 | 2217.51 | 1229.49 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1711.25 | 261.26 | 708.61 | 1344.06 | 237.60 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 3562.87 | 2234.81 | 1507.20 | 3726.69 | 2294.49 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 599.05 | 245.41 | 353.64 | 260.60 | 1625.24 | 0.00 | 0.00 | 744.00 |
February | 883.29 | 387.94 | 495.34 | 448.02 | 1681.67 | 0.00 | 0.00 | 672.00 |
March | 1304.37 | 602.24 | 702.13 | 950.00 | 1152.11 | 0.00 | 0.00 | 744.00 |
April | 1425.56 | 609.99 | 815.57 | 1199.77 | 859.29 | 0.00 | 0.00 | 720.00 |
May | 1660.41 | 630.45 | 1029.96 | 1609.94 | 551.17 | 0.00 | 0.00 | 744.00 |
June | 1817.25 | 732.83 | 1084.42 | 2026.76 | 313.68 | 0.00 | 0.00 | 720.00 |
July | 1702.00 | 640.83 | 1061.17 | 2060.89 | 180.24 | 0.00 | 0.00 | 744.00 |
August | 1883.01 | 871.70 | 1011.31 | 2296.95 | 247.71 | 0.00 | 0.00 | 744.00 |
September | 1336.90 | 584.27 | 752.63 | 1426.28 | 433.26 | 0.00 | 0.00 | 720.00 |
October | 1325.35 | 644.49 | 680.86 | 1237.17 | 772.83 | 0.00 | 0.00 | 744.00 |
November | 622.39 | 179.88 | 442.51 | 296.66 | 1151.99 | 0.00 | 0.00 | 720.00 |
December | 553.66 | 239.61 | 314.05 | 244.19 | 1510.13 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1262.08 | 532.02 | 730.06 | 1176.66 | 868.65 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 553.66 | 179.88 | 314.05 | 244.19 | 180.24 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1883.01 | 871.70 | 1084.42 | 2296.95 | 1681.67 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233390E+09 | 0.00 | 0.233390E+09 | 266670.46 | 0.161672E+10 |
February | 0.288476E+09 | 0.00 | 0.288476E+09 | 3329594.56 | 0.150993E+10 |
March | 0.442906E+09 | 0.00 | 0.442906E+09 | 63514946.37 | 0.115122E+10 |
April | 0.514807E+09 | 1441450.84 | 0.513365E+09 | 0.196738E+09 | 0.783940E+09 |
May | 0.705707E+09 | 23441905.69 | 0.682265E+09 | 0.474254E+09 | 0.456456E+09 |
June | 0.724239E+09 | 38831416.63 | 0.685408E+09 | 0.698422E+09 | 0.224957E+09 |
July | 0.723250E+09 | 26081137.13 | 0.697169E+09 | 0.849734E+09 | 0.117126E+09 |
August | 0.640779E+09 | 7571924.77 | 0.633207E+09 | 0.756376E+09 | 0.164502E+09 |
September | 0.467495E+09 | 84246.64 | 0.467411E+09 | 0.395016E+09 | 0.359295E+09 |
October | 0.418073E+09 | 0.00 | 0.418073E+09 | 0.202634E+09 | 0.714180E+09 |
November | 0.283778E+09 | 0.00 | 0.283778E+09 | 27522562.40 | 0.115799E+10 |
December | 0.203578E+09 | 0.00 | 0.203578E+09 | 279405.61 | 0.157469E+10 |
Annual Sum or Average | 0.564648E+10 | 97452081.70 | 0.554903E+10 | 0.366809E+10 | 0.983101E+10 |
Minimum of Months | 0.203578E+09 | 0.00 | 0.203578E+09 | 266670.46 | 0.117126E+09 |
Maximum of Months | 0.724239E+09 | 38831416.63 | 0.697169E+09 | 0.849734E+09 | 0.161672E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233386E+09 | 0.00 | 0.233386E+09 | 266608.51 | 0.161672E+10 |
February | 0.288472E+09 | 0.00 | 0.288472E+09 | 3329185.95 | 0.150993E+10 |
March | 0.442900E+09 | 0.00 | 0.442900E+09 | 63512025.37 | 0.115122E+10 |
April | 0.514800E+09 | 1441419.15 | 0.513358E+09 | 0.196733E+09 | 0.783940E+09 |
May | 0.705697E+09 | 23441390.34 | 0.682255E+09 | 0.474244E+09 | 0.456456E+09 |
June | 0.724229E+09 | 38830562.96 | 0.685398E+09 | 0.698412E+09 | 0.224956E+09 |
July | 0.723240E+09 | 26080563.77 | 0.697159E+09 | 0.849723E+09 | 0.117125E+09 |
August | 0.640771E+09 | 7571758.31 | 0.633199E+09 | 0.756368E+09 | 0.164501E+09 |
September | 0.467489E+09 | 84244.79 | 0.467405E+09 | 0.395010E+09 | 0.359294E+09 |
October | 0.418067E+09 | 0.00 | 0.418067E+09 | 0.202629E+09 | 0.714179E+09 |
November | 0.283774E+09 | 0.00 | 0.283774E+09 | 27521172.64 | 0.115799E+10 |
December | 0.203575E+09 | 0.00 | 0.203575E+09 | 279345.63 | 0.157469E+10 |
Annual Sum or Average | 0.564640E+10 | 97449939.33 | 0.554895E+10 | 0.366803E+10 | 0.983101E+10 |
Minimum of Months | 0.203575E+09 | 0.00 | 0.203575E+09 | 266608.51 | 0.117125E+09 |
Maximum of Months | 0.724229E+09 | 38830562.96 | 0.697159E+09 | 0.849723E+09 | 0.161672E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233388E+09 | 0.00 | 0.233388E+09 | 266629.16 | 0.161672E+10 |
February | 0.288474E+09 | 0.00 | 0.288474E+09 | 3329322.15 | 0.150993E+10 |
March | 0.442902E+09 | 0.00 | 0.442902E+09 | 63512999.03 | 0.115122E+10 |
April | 0.514802E+09 | 1441429.72 | 0.513361E+09 | 0.196735E+09 | 0.783940E+09 |
May | 0.705700E+09 | 23441562.13 | 0.682259E+09 | 0.474247E+09 | 0.456456E+09 |
June | 0.724232E+09 | 38830847.52 | 0.685401E+09 | 0.698415E+09 | 0.224956E+09 |
July | 0.723243E+09 | 26080754.89 | 0.697163E+09 | 0.849727E+09 | 0.117125E+09 |
August | 0.640773E+09 | 7571813.79 | 0.633202E+09 | 0.756371E+09 | 0.164502E+09 |
September | 0.467491E+09 | 84245.41 | 0.467407E+09 | 0.395012E+09 | 0.359294E+09 |
October | 0.418069E+09 | 0.00 | 0.418069E+09 | 0.202631E+09 | 0.714179E+09 |
November | 0.283775E+09 | 0.00 | 0.283775E+09 | 27521635.89 | 0.115799E+10 |
December | 0.203576E+09 | 0.00 | 0.203576E+09 | 279365.62 | 0.157469E+10 |
Annual Sum or Average | 0.564643E+10 | 97450653.45 | 0.554898E+10 | 0.366805E+10 | 0.983101E+10 |
Minimum of Months | 0.203576E+09 | 0.00 | 0.203576E+09 | 266629.16 | 0.117125E+09 |
Maximum of Months | 0.724232E+09 | 38830847.52 | 0.697163E+09 | 0.849727E+09 | 0.161672E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233386E+09 | 0.00 | 0.233386E+09 | 266608.51 | 0.161672E+10 |
February | 0.288472E+09 | 0.00 | 0.288472E+09 | 3329185.95 | 0.150993E+10 |
March | 0.442900E+09 | 0.00 | 0.442900E+09 | 63512025.37 | 0.115122E+10 |
April | 0.514800E+09 | 1441419.15 | 0.513358E+09 | 0.196733E+09 | 0.783940E+09 |
May | 0.705697E+09 | 23441390.34 | 0.682255E+09 | 0.474244E+09 | 0.456456E+09 |
June | 0.724229E+09 | 38830562.96 | 0.685398E+09 | 0.698412E+09 | 0.224956E+09 |
July | 0.723240E+09 | 26080563.77 | 0.697159E+09 | 0.849723E+09 | 0.117125E+09 |
August | 0.640771E+09 | 7571758.31 | 0.633199E+09 | 0.756368E+09 | 0.164501E+09 |
September | 0.467489E+09 | 84244.79 | 0.467405E+09 | 0.395010E+09 | 0.359294E+09 |
October | 0.418067E+09 | 0.00 | 0.418067E+09 | 0.202629E+09 | 0.714179E+09 |
November | 0.283774E+09 | 0.00 | 0.283774E+09 | 27521172.64 | 0.115799E+10 |
December | 0.203575E+09 | 0.00 | 0.203575E+09 | 279345.63 | 0.157469E+10 |
Annual Sum or Average | 0.564640E+10 | 97449939.33 | 0.554895E+10 | 0.366803E+10 | 0.983101E+10 |
Minimum of Months | 0.203575E+09 | 0.00 | 0.203575E+09 | 266608.51 | 0.117125E+09 |
Maximum of Months | 0.724229E+09 | 38830562.96 | 0.697159E+09 | 0.849723E+09 | 0.161672E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.233378E+09 | 0.00 | 0.233378E+09 | 266608.09 | 0.161666E+10 |
February | 0.288461E+09 | 0.00 | 0.288461E+09 | 3329119.87 | 0.150987E+10 |
March | 0.442883E+09 | 0.00 | 0.442883E+09 | 63509952.37 | 0.115118E+10 |
April | 0.514780E+09 | 1441366.34 | 0.513339E+09 | 0.196726E+09 | 0.783909E+09 |
May | 0.705670E+09 | 23440531.44 | 0.682230E+09 | 0.474226E+09 | 0.456437E+09 |
June | 0.724201E+09 | 38829140.19 | 0.685372E+09 | 0.698385E+09 | 0.224947E+09 |
July | 0.723212E+09 | 26079608.16 | 0.697133E+09 | 0.849691E+09 | 0.117120E+09 |
August | 0.640746E+09 | 7571480.88 | 0.633175E+09 | 0.756339E+09 | 0.164495E+09 |
September | 0.467471E+09 | 84241.71 | 0.467387E+09 | 0.394995E+09 | 0.359280E+09 |
October | 0.418051E+09 | 0.00 | 0.418051E+09 | 0.202622E+09 | 0.714150E+09 |
November | 0.283763E+09 | 0.00 | 0.283763E+09 | 27520295.04 | 0.115794E+10 |
December | 0.203567E+09 | 0.00 | 0.203567E+09 | 279344.37 | 0.157463E+10 |
Annual Sum or Average | 0.564618E+10 | 97446368.71 | 0.554874E+10 | 0.366789E+10 | 0.983061E+10 |
Minimum of Months | 0.203567E+09 | 0.00 | 0.203567E+09 | 266608.09 | 0.117120E+09 |
Maximum of Months | 0.724201E+09 | 38829140.19 | 0.697133E+09 | 0.849691E+09 | 0.161666E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541754E+09 | 0.217233E+09 | 0.324521E+09 | 0.204330E+09 | 0.163461E+10 |
February | 0.758768E+09 | 0.353969E+09 | 0.404799E+09 | 0.366196E+09 | 0.146788E+10 |
March | 0.107164E+10 | 0.455773E+09 | 0.615871E+09 | 0.715610E+09 | 0.117289E+10 |
April | 0.124463E+10 | 0.545223E+09 | 0.699411E+09 | 0.101222E+10 | 0.790307E+09 |
May | 0.155957E+10 | 0.623209E+09 | 0.936360E+09 | 0.151287E+10 | 0.495785E+09 |
June | 0.139876E+10 | 0.506251E+09 | 0.892507E+09 | 0.154746E+10 | 0.243173E+09 |
July | 0.145172E+10 | 0.523802E+09 | 0.927917E+09 | 0.178488E+10 | 0.117268E+09 |
August | 0.163479E+10 | 0.737109E+09 | 0.897682E+09 | 0.201343E+10 | 0.162422E+09 |
September | 0.118003E+10 | 0.529485E+09 | 0.650542E+09 | 0.123690E+10 | 0.372390E+09 |
October | 0.110538E+10 | 0.501016E+09 | 0.604368E+09 | 0.968157E+09 | 0.735683E+09 |
November | 0.661569E+09 | 0.254078E+09 | 0.407491E+09 | 0.348794E+09 | 0.114510E+10 |
December | 0.532624E+09 | 0.250130E+09 | 0.282493E+09 | 0.219085E+09 | 0.153797E+10 |
Annual Sum or Average | 0.131412E+11 | 0.549728E+10 | 0.764396E+10 | 0.119299E+11 | 0.987548E+10 |
Minimum of Months | 0.532624E+09 | 0.217233E+09 | 0.282493E+09 | 0.204330E+09 | 0.117268E+09 |
Maximum of Months | 0.163479E+10 | 0.737109E+09 | 0.936360E+09 | 0.201343E+10 | 0.163461E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541754E+09 | 0.217233E+09 | 0.324521E+09 | 0.204330E+09 | 0.163461E+10 |
February | 0.758768E+09 | 0.353969E+09 | 0.404799E+09 | 0.366196E+09 | 0.146788E+10 |
March | 0.107164E+10 | 0.455773E+09 | 0.615871E+09 | 0.715610E+09 | 0.117289E+10 |
April | 0.124463E+10 | 0.545223E+09 | 0.699411E+09 | 0.101222E+10 | 0.790307E+09 |
May | 0.155957E+10 | 0.623209E+09 | 0.936360E+09 | 0.151287E+10 | 0.495785E+09 |
June | 0.139876E+10 | 0.506251E+09 | 0.892507E+09 | 0.154746E+10 | 0.243173E+09 |
July | 0.145172E+10 | 0.523802E+09 | 0.927917E+09 | 0.178488E+10 | 0.117268E+09 |
August | 0.163479E+10 | 0.737109E+09 | 0.897682E+09 | 0.201343E+10 | 0.162422E+09 |
September | 0.118003E+10 | 0.529485E+09 | 0.650542E+09 | 0.123690E+10 | 0.372390E+09 |
October | 0.110538E+10 | 0.501016E+09 | 0.604368E+09 | 0.968157E+09 | 0.735683E+09 |
November | 0.661569E+09 | 0.254078E+09 | 0.407491E+09 | 0.348794E+09 | 0.114510E+10 |
December | 0.532624E+09 | 0.250130E+09 | 0.282493E+09 | 0.219085E+09 | 0.153797E+10 |
Annual Sum or Average | 0.131412E+11 | 0.549728E+10 | 0.764396E+10 | 0.119299E+11 | 0.987548E+10 |
Minimum of Months | 0.532624E+09 | 0.217233E+09 | 0.282493E+09 | 0.204330E+09 | 0.117268E+09 |
Maximum of Months | 0.163479E+10 | 0.737109E+09 | 0.936360E+09 | 0.201343E+10 | 0.163461E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.541745E+09 | 0.217229E+09 | 0.324515E+09 | 0.204326E+09 | 0.163458E+10 |
February | 0.758754E+09 | 0.353962E+09 | 0.404792E+09 | 0.366189E+09 | 0.146785E+10 |
March | 0.107162E+10 | 0.455765E+09 | 0.615860E+09 | 0.715597E+09 | 0.117287E+10 |
April | 0.124461E+10 | 0.545214E+09 | 0.699398E+09 | 0.101220E+10 | 0.790292E+09 |
May | 0.155954E+10 | 0.623197E+09 | 0.936343E+09 | 0.151284E+10 | 0.495776E+09 |
June | 0.139873E+10 | 0.506241E+09 | 0.892490E+09 | 0.154743E+10 | 0.243169E+09 |
July | 0.145169E+10 | 0.523792E+09 | 0.927900E+09 | 0.178485E+10 | 0.117266E+09 |
August | 0.163476E+10 | 0.737095E+09 | 0.897666E+09 | 0.201339E+10 | 0.162419E+09 |
September | 0.118000E+10 | 0.529475E+09 | 0.650530E+09 | 0.123687E+10 | 0.372383E+09 |
October | 0.110536E+10 | 0.501007E+09 | 0.604357E+09 | 0.968139E+09 | 0.735670E+09 |
November | 0.661557E+09 | 0.254073E+09 | 0.407484E+09 | 0.348787E+09 | 0.114508E+10 |
December | 0.532614E+09 | 0.250126E+09 | 0.282488E+09 | 0.219081E+09 | 0.153794E+10 |
Annual Sum or Average | 0.131410E+11 | 0.549718E+10 | 0.764382E+10 | 0.119297E+11 | 0.987530E+10 |
Minimum of Months | 0.532614E+09 | 0.217229E+09 | 0.282488E+09 | 0.204326E+09 | 0.117266E+09 |
Maximum of Months | 0.163476E+10 | 0.737095E+09 | 0.936343E+09 | 0.201339E+10 | 0.163458E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120739E+10 | 0.790613E+09 | 0.416772E+09 | 0.105160E+10 | 0.134289E+10 |
February | 0.143897E+10 | 0.952685E+09 | 0.486282E+09 | 0.122659E+10 | 0.123959E+10 |
March | 0.143719E+10 | 0.797879E+09 | 0.639310E+09 | 0.115614E+10 | 0.104964E+10 |
April | 0.107871E+10 | 0.426460E+09 | 0.652255E+09 | 0.733658E+09 | 0.755905E+09 |
May | 0.976839E+09 | 0.203634E+09 | 0.773205E+09 | 0.710431E+09 | 0.474226E+09 |
June | 0.887102E+09 | 0.135436E+09 | 0.751666E+09 | 0.824769E+09 | 0.239096E+09 |
July | 0.960901E+09 | 0.166770E+09 | 0.794132E+09 | 0.103501E+10 | 0.121783E+09 |
August | 0.128321E+10 | 0.475840E+09 | 0.807367E+09 | 0.133331E+10 | 0.173764E+09 |
September | 0.134777E+10 | 0.697211E+09 | 0.650564E+09 | 0.137149E+10 | 0.358233E+09 |
October | 0.190853E+10 | 0.119712E+10 | 0.711407E+09 | 0.199301E+10 | 0.681684E+09 |
November | 0.128026E+10 | 0.768923E+09 | 0.511339E+09 | 0.119223E+10 | 0.988378E+09 |
December | 0.130842E+10 | 0.928842E+09 | 0.379580E+09 | 0.121793E+10 | 0.127148E+10 |
Annual Sum or Average | 0.151153E+11 | 0.754141E+10 | 0.757388E+10 | 0.138462E+11 | 0.869666E+10 |
Minimum of Months | 0.887102E+09 | 0.135436E+09 | 0.379580E+09 | 0.710431E+09 | 0.121783E+09 |
Maximum of Months | 0.190853E+10 | 0.119712E+10 | 0.807367E+09 | 0.199301E+10 | 0.134289E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120738E+10 | 0.790607E+09 | 0.416770E+09 | 0.105159E+10 | 0.134289E+10 |
February | 0.143896E+10 | 0.952678E+09 | 0.486279E+09 | 0.122657E+10 | 0.123959E+10 |
March | 0.143718E+10 | 0.797873E+09 | 0.639307E+09 | 0.115613E+10 | 0.104964E+10 |
April | 0.107871E+10 | 0.426457E+09 | 0.652251E+09 | 0.733652E+09 | 0.755905E+09 |
May | 0.976833E+09 | 0.203632E+09 | 0.773201E+09 | 0.710426E+09 | 0.474225E+09 |
June | 0.887097E+09 | 0.135435E+09 | 0.751663E+09 | 0.824765E+09 | 0.239095E+09 |
July | 0.960896E+09 | 0.166768E+09 | 0.794128E+09 | 0.103500E+10 | 0.121782E+09 |
August | 0.128320E+10 | 0.475836E+09 | 0.807363E+09 | 0.133330E+10 | 0.173763E+09 |
September | 0.134777E+10 | 0.697206E+09 | 0.650560E+09 | 0.137149E+10 | 0.358232E+09 |
October | 0.190851E+10 | 0.119711E+10 | 0.711403E+09 | 0.199299E+10 | 0.681683E+09 |
November | 0.128025E+10 | 0.768917E+09 | 0.511336E+09 | 0.119222E+10 | 0.988378E+09 |
December | 0.130841E+10 | 0.928836E+09 | 0.379578E+09 | 0.121792E+10 | 0.127148E+10 |
Annual Sum or Average | 0.151152E+11 | 0.754135E+10 | 0.757384E+10 | 0.138460E+11 | 0.869666E+10 |
Minimum of Months | 0.887097E+09 | 0.135435E+09 | 0.379578E+09 | 0.710426E+09 | 0.121782E+09 |
Maximum of Months | 0.190851E+10 | 0.119711E+10 | 0.807363E+09 | 0.199299E+10 | 0.134289E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120739E+10 | 0.790613E+09 | 0.416772E+09 | 0.105160E+10 | 0.134289E+10 |
February | 0.143897E+10 | 0.952685E+09 | 0.486282E+09 | 0.122659E+10 | 0.123959E+10 |
March | 0.143719E+10 | 0.797879E+09 | 0.639310E+09 | 0.115614E+10 | 0.104964E+10 |
April | 0.107871E+10 | 0.426460E+09 | 0.652255E+09 | 0.733658E+09 | 0.755905E+09 |
May | 0.976839E+09 | 0.203634E+09 | 0.773205E+09 | 0.710431E+09 | 0.474226E+09 |
June | 0.887102E+09 | 0.135436E+09 | 0.751666E+09 | 0.824769E+09 | 0.239096E+09 |
July | 0.960901E+09 | 0.166770E+09 | 0.794132E+09 | 0.103501E+10 | 0.121783E+09 |
August | 0.128321E+10 | 0.475840E+09 | 0.807367E+09 | 0.133331E+10 | 0.173764E+09 |
September | 0.134777E+10 | 0.697211E+09 | 0.650564E+09 | 0.137149E+10 | 0.358233E+09 |
October | 0.190853E+10 | 0.119712E+10 | 0.711407E+09 | 0.199301E+10 | 0.681684E+09 |
November | 0.128026E+10 | 0.768923E+09 | 0.511339E+09 | 0.119223E+10 | 0.988378E+09 |
December | 0.130842E+10 | 0.928842E+09 | 0.379580E+09 | 0.121793E+10 | 0.127148E+10 |
Annual Sum or Average | 0.151153E+11 | 0.754141E+10 | 0.757388E+10 | 0.138462E+11 | 0.869666E+10 |
Minimum of Months | 0.887102E+09 | 0.135436E+09 | 0.379580E+09 | 0.710431E+09 | 0.121783E+09 |
Maximum of Months | 0.190853E+10 | 0.119712E+10 | 0.807367E+09 | 0.199301E+10 | 0.134289E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120738E+10 | 0.790607E+09 | 0.416770E+09 | 0.105159E+10 | 0.134289E+10 |
February | 0.143896E+10 | 0.952678E+09 | 0.486279E+09 | 0.122657E+10 | 0.123959E+10 |
March | 0.143718E+10 | 0.797873E+09 | 0.639307E+09 | 0.115613E+10 | 0.104964E+10 |
April | 0.107871E+10 | 0.426457E+09 | 0.652251E+09 | 0.733652E+09 | 0.755905E+09 |
May | 0.976833E+09 | 0.203632E+09 | 0.773201E+09 | 0.710426E+09 | 0.474225E+09 |
June | 0.887097E+09 | 0.135435E+09 | 0.751663E+09 | 0.824765E+09 | 0.239095E+09 |
July | 0.960896E+09 | 0.166768E+09 | 0.794128E+09 | 0.103500E+10 | 0.121782E+09 |
August | 0.128320E+10 | 0.475836E+09 | 0.807363E+09 | 0.133330E+10 | 0.173763E+09 |
September | 0.134777E+10 | 0.697206E+09 | 0.650560E+09 | 0.137149E+10 | 0.358232E+09 |
October | 0.190851E+10 | 0.119711E+10 | 0.711403E+09 | 0.199299E+10 | 0.681683E+09 |
November | 0.128025E+10 | 0.768917E+09 | 0.511336E+09 | 0.119222E+10 | 0.988378E+09 |
December | 0.130841E+10 | 0.928836E+09 | 0.379578E+09 | 0.121792E+10 | 0.127148E+10 |
Annual Sum or Average | 0.151152E+11 | 0.754135E+10 | 0.757384E+10 | 0.138460E+11 | 0.869666E+10 |
Minimum of Months | 0.887097E+09 | 0.135435E+09 | 0.379578E+09 | 0.710426E+09 | 0.121782E+09 |
Maximum of Months | 0.190851E+10 | 0.119711E+10 | 0.807363E+09 | 0.199299E+10 | 0.134289E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.120733E+10 | 0.790578E+09 | 0.416754E+09 | 0.105155E+10 | 0.134283E+10 |
February | 0.143890E+10 | 0.952643E+09 | 0.486261E+09 | 0.122653E+10 | 0.123954E+10 |
March | 0.143713E+10 | 0.797844E+09 | 0.639283E+09 | 0.115609E+10 | 0.104959E+10 |
April | 0.107867E+10 | 0.426441E+09 | 0.652227E+09 | 0.733626E+09 | 0.755875E+09 |
May | 0.976797E+09 | 0.203625E+09 | 0.773172E+09 | 0.710400E+09 | 0.474206E+09 |
June | 0.887064E+09 | 0.135430E+09 | 0.751634E+09 | 0.824734E+09 | 0.239086E+09 |
July | 0.960860E+09 | 0.166762E+09 | 0.794098E+09 | 0.103496E+10 | 0.121777E+09 |
August | 0.128315E+10 | 0.475819E+09 | 0.807332E+09 | 0.133325E+10 | 0.173756E+09 |
September | 0.134772E+10 | 0.697180E+09 | 0.650536E+09 | 0.137143E+10 | 0.358218E+09 |
October | 0.190844E+10 | 0.119707E+10 | 0.711376E+09 | 0.199292E+10 | 0.681656E+09 |
November | 0.128021E+10 | 0.768889E+09 | 0.511317E+09 | 0.119218E+10 | 0.988338E+09 |
December | 0.130837E+10 | 0.928802E+09 | 0.379564E+09 | 0.121787E+10 | 0.127143E+10 |
Annual Sum or Average | 0.151146E+11 | 0.754108E+10 | 0.757355E+10 | 0.138455E+11 | 0.869631E+10 |
Minimum of Months | 0.887064E+09 | 0.135430E+09 | 0.379564E+09 | 0.710400E+09 | 0.121777E+09 |
Maximum of Months | 0.190844E+10 | 0.119707E+10 | 0.807332E+09 | 0.199292E+10 | 0.134283E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.534833E+09 | 0.219103E+09 | 0.315731E+09 | 0.211474E+09 | 0.175375E+10 |
February | 0.712291E+09 | 0.312842E+09 | 0.399449E+09 | 0.329856E+09 | 0.164489E+10 |
March | 0.116456E+10 | 0.537688E+09 | 0.626868E+09 | 0.796495E+09 | 0.131210E+10 |
April | 0.123170E+10 | 0.527035E+09 | 0.704664E+09 | 0.978396E+09 | 0.956609E+09 |
May | 0.148243E+10 | 0.562874E+09 | 0.919555E+09 | 0.141395E+10 | 0.563897E+09 |
June | 0.157012E+10 | 0.633170E+09 | 0.936953E+09 | 0.173823E+10 | 0.311230E+09 |
July | 0.151956E+10 | 0.572138E+09 | 0.947423E+09 | 0.182120E+10 | 0.187928E+09 |
August | 0.168117E+10 | 0.778259E+09 | 0.902911E+09 | 0.202575E+10 | 0.258809E+09 |
September | 0.115509E+10 | 0.504814E+09 | 0.650275E+09 | 0.121146E+10 | 0.439783E+09 |
October | 0.118328E+10 | 0.575405E+09 | 0.607879E+09 | 0.106051E+10 | 0.848255E+09 |
November | 0.537747E+09 | 0.155419E+09 | 0.382329E+09 | 0.210610E+09 | 0.133800E+10 |
December | 0.494314E+09 | 0.213926E+09 | 0.280387E+09 | 0.182553E+09 | 0.180202E+10 |
Annual Sum or Average | 0.132671E+11 | 0.559267E+10 | 0.767442E+10 | 0.119805E+11 | 0.114173E+11 |
Minimum of Months | 0.494314E+09 | 0.155419E+09 | 0.280387E+09 | 0.182553E+09 | 0.187928E+09 |
Maximum of Months | 0.168117E+10 | 0.778259E+09 | 0.947423E+09 | 0.202575E+10 | 0.180202E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.534833E+09 | 0.219103E+09 | 0.315731E+09 | 0.211474E+09 | 0.175375E+10 |
February | 0.712291E+09 | 0.312842E+09 | 0.399449E+09 | 0.329856E+09 | 0.164489E+10 |
March | 0.116456E+10 | 0.537688E+09 | 0.626868E+09 | 0.796495E+09 | 0.131210E+10 |
April | 0.123170E+10 | 0.527035E+09 | 0.704664E+09 | 0.978396E+09 | 0.956609E+09 |
May | 0.148243E+10 | 0.562874E+09 | 0.919555E+09 | 0.141395E+10 | 0.563897E+09 |
June | 0.157012E+10 | 0.633170E+09 | 0.936953E+09 | 0.173823E+10 | 0.311230E+09 |
July | 0.151956E+10 | 0.572138E+09 | 0.947423E+09 | 0.182120E+10 | 0.187928E+09 |
August | 0.168117E+10 | 0.778259E+09 | 0.902911E+09 | 0.202575E+10 | 0.258809E+09 |
September | 0.115509E+10 | 0.504814E+09 | 0.650275E+09 | 0.121146E+10 | 0.439783E+09 |
October | 0.118328E+10 | 0.575405E+09 | 0.607879E+09 | 0.106051E+10 | 0.848255E+09 |
November | 0.537747E+09 | 0.155419E+09 | 0.382329E+09 | 0.210610E+09 | 0.133800E+10 |
December | 0.494314E+09 | 0.213926E+09 | 0.280387E+09 | 0.182553E+09 | 0.180202E+10 |
Annual Sum or Average | 0.132671E+11 | 0.559267E+10 | 0.767442E+10 | 0.119805E+11 | 0.114173E+11 |
Minimum of Months | 0.494314E+09 | 0.155419E+09 | 0.280387E+09 | 0.182553E+09 | 0.187928E+09 |
Maximum of Months | 0.168117E+10 | 0.778259E+09 | 0.947423E+09 | 0.202575E+10 | 0.180202E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.534824E+09 | 0.219099E+09 | 0.315725E+09 | 0.211470E+09 | 0.175372E+10 |
February | 0.712278E+09 | 0.312836E+09 | 0.399441E+09 | 0.329850E+09 | 0.164486E+10 |
March | 0.116453E+10 | 0.537678E+09 | 0.626856E+09 | 0.796480E+09 | 0.131208E+10 |
April | 0.123168E+10 | 0.527025E+09 | 0.704651E+09 | 0.978378E+09 | 0.956592E+09 |
May | 0.148240E+10 | 0.562864E+09 | 0.919539E+09 | 0.141392E+10 | 0.563886E+09 |
June | 0.157009E+10 | 0.633159E+09 | 0.936936E+09 | 0.173820E+10 | 0.311224E+09 |
July | 0.151953E+10 | 0.572127E+09 | 0.947406E+09 | 0.182117E+10 | 0.187924E+09 |
August | 0.168114E+10 | 0.778245E+09 | 0.902895E+09 | 0.202571E+10 | 0.258804E+09 |
September | 0.115507E+10 | 0.504805E+09 | 0.650263E+09 | 0.121144E+10 | 0.439775E+09 |
October | 0.118326E+10 | 0.575394E+09 | 0.607868E+09 | 0.106049E+10 | 0.848239E+09 |
November | 0.537737E+09 | 0.155416E+09 | 0.382322E+09 | 0.210607E+09 | 0.133798E+10 |
December | 0.494305E+09 | 0.213922E+09 | 0.280382E+09 | 0.182549E+09 | 0.180199E+10 |
Annual Sum or Average | 0.132669E+11 | 0.559257E+10 | 0.767428E+10 | 0.119803E+11 | 0.114171E+11 |
Minimum of Months | 0.494305E+09 | 0.155416E+09 | 0.280382E+09 | 0.182549E+09 | 0.187924E+09 |
Maximum of Months | 0.168114E+10 | 0.778245E+09 | 0.947406E+09 | 0.202571E+10 | 0.180199E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116695E+10 | 0.00 | 0.116695E+10 | 9939828.32 | 0.710638E+10 |
February | 0.144238E+10 | 0.00 | 0.144238E+10 | 43569260.95 | 0.675276E+10 |
March | 0.221453E+10 | 0.00 | 0.221453E+10 | 0.428472E+09 | 0.503107E+10 |
April | 0.257403E+10 | 7207300.14 | 0.256683E+10 | 0.111315E+10 | 0.345128E+10 |
May | 0.352854E+10 | 0.117210E+09 | 0.341133E+10 | 0.244980E+10 | 0.212067E+10 |
June | 0.362120E+10 | 0.194158E+09 | 0.342704E+10 | 0.354240E+10 | 0.106231E+10 |
July | 0.361625E+10 | 0.130407E+09 | 0.348584E+10 | 0.428873E+10 | 0.581696E+09 |
August | 0.320389E+10 | 37859865.11 | 0.316603E+10 | 0.383645E+10 | 0.813874E+09 |
September | 0.233748E+10 | 421235.91 | 0.233705E+10 | 0.203971E+10 | 0.164145E+10 |
October | 0.209036E+10 | 0.00 | 0.209036E+10 | 0.111305E+10 | 0.320054E+10 |
November | 0.141889E+10 | 0.00 | 0.141889E+10 | 0.194753E+09 | 0.495528E+10 |
December | 0.101789E+10 | 0.00 | 0.101789E+10 | 7287364.88 | 0.674088E+10 |
Annual Sum or Average | 0.282324E+11 | 0.487264E+09 | 0.277451E+11 | 0.190673E+11 | 0.434582E+11 |
Minimum of Months | 0.101789E+10 | 0.00 | 0.101789E+10 | 7287364.88 | 0.581696E+09 |
Maximum of Months | 0.362120E+10 | 0.194158E+09 | 0.348584E+10 | 0.428873E+10 | 0.710638E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162525E+10 | 0.651693E+09 | 0.973554E+09 | 0.659919E+09 | 0.436316E+10 |
February | 0.227628E+10 | 0.106189E+10 | 0.121438E+10 | 0.115755E+10 | 0.400832E+10 |
March | 0.321490E+10 | 0.136731E+10 | 0.184759E+10 | 0.220174E+10 | 0.319866E+10 |
April | 0.373386E+10 | 0.163565E+10 | 0.209821E+10 | 0.306896E+10 | 0.220021E+10 |
May | 0.467866E+10 | 0.186961E+10 | 0.280905E+10 | 0.454145E+10 | 0.141629E+10 |
June | 0.419623E+10 | 0.151874E+10 | 0.267749E+10 | 0.462348E+10 | 0.722703E+09 |
July | 0.435511E+10 | 0.157139E+10 | 0.278372E+10 | 0.531932E+10 | 0.394631E+09 |
August | 0.490432E+10 | 0.221130E+10 | 0.269302E+10 | 0.600165E+10 | 0.542047E+09 |
September | 0.354004E+10 | 0.158844E+10 | 0.195161E+10 | 0.371659E+10 | 0.105577E+10 |
October | 0.331612E+10 | 0.150303E+10 | 0.181309E+10 | 0.293801E+10 | 0.205571E+10 |
November | 0.198469E+10 | 0.762225E+09 | 0.122246E+10 | 0.111067E+10 | 0.304239E+10 |
December | 0.159785E+10 | 0.750383E+09 | 0.847472E+09 | 0.706610E+09 | 0.409139E+10 |
Annual Sum or Average | 0.394233E+11 | 0.164917E+11 | 0.229317E+11 | 0.360459E+11 | 0.270913E+11 |
Minimum of Months | 0.159785E+10 | 0.651693E+09 | 0.847472E+09 | 0.659919E+09 | 0.394631E+09 |
Maximum of Months | 0.490432E+10 | 0.221130E+10 | 0.280905E+10 | 0.600165E+10 | 0.436316E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603704E+10 | 0.395315E+10 | 0.208389E+10 | 0.529446E+10 | 0.631113E+10 |
February | 0.719497E+10 | 0.476352E+10 | 0.243144E+10 | 0.614095E+10 | 0.593464E+10 |
March | 0.718607E+10 | 0.398948E+10 | 0.319659E+10 | 0.579774E+10 | 0.495375E+10 |
April | 0.539365E+10 | 0.213234E+10 | 0.326131E+10 | 0.372269E+10 | 0.354525E+10 |
May | 0.488426E+10 | 0.101819E+10 | 0.386607E+10 | 0.358409E+10 | 0.227982E+10 |
June | 0.443556E+10 | 0.677192E+09 | 0.375837E+10 | 0.415403E+10 | 0.115355E+10 |
July | 0.480457E+10 | 0.833865E+09 | 0.397070E+10 | 0.520961E+10 | 0.614102E+09 |
August | 0.641613E+10 | 0.237925E+10 | 0.403688E+10 | 0.669821E+10 | 0.883028E+09 |
September | 0.673898E+10 | 0.348613E+10 | 0.325286E+10 | 0.684776E+10 | 0.173561E+10 |
October | 0.954280E+10 | 0.598572E+10 | 0.355708E+10 | 0.991866E+10 | 0.331662E+10 |
November | 0.640143E+10 | 0.384470E+10 | 0.255674E+10 | 0.598241E+10 | 0.464168E+10 |
December | 0.654224E+10 | 0.464431E+10 | 0.189793E+10 | 0.612027E+10 | 0.594959E+10 |
Annual Sum or Average | 0.755777E+11 | 0.377078E+11 | 0.378699E+11 | 0.694709E+11 | 0.413188E+11 |
Minimum of Months | 0.443556E+10 | 0.677192E+09 | 0.189793E+10 | 0.358409E+10 | 0.614102E+09 |
Maximum of Months | 0.954280E+10 | 0.598572E+10 | 0.403688E+10 | 0.991866E+10 | 0.631113E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160448E+10 | 0.657301E+09 | 0.947183E+09 | 0.684609E+09 | 0.456582E+10 |
February | 0.213685E+10 | 0.938516E+09 | 0.119833E+10 | 0.106332E+10 | 0.427586E+10 |
March | 0.349363E+10 | 0.161305E+10 | 0.188058E+10 | 0.251216E+10 | 0.328762E+10 |
April | 0.369506E+10 | 0.158109E+10 | 0.211397E+10 | 0.307818E+10 | 0.236838E+10 |
May | 0.444724E+10 | 0.168861E+10 | 0.275864E+10 | 0.430519E+10 | 0.153463E+10 |
June | 0.471032E+10 | 0.189949E+10 | 0.281083E+10 | 0.527628E+10 | 0.823279E+09 |
July | 0.455864E+10 | 0.171640E+10 | 0.284224E+10 | 0.555359E+10 | 0.476959E+09 |
August | 0.504346E+10 | 0.233475E+10 | 0.270871E+10 | 0.617749E+10 | 0.666330E+09 |
September | 0.346523E+10 | 0.151443E+10 | 0.195080E+10 | 0.369429E+10 | 0.116628E+10 |
October | 0.354982E+10 | 0.172620E+10 | 0.182362E+10 | 0.327731E+10 | 0.220768E+10 |
November | 0.161323E+10 | 0.466251E+09 | 0.114697E+10 | 0.729138E+09 | 0.323591E+10 |
December | 0.148293E+10 | 0.641773E+09 | 0.841154E+09 | 0.628224E+09 | 0.433203E+10 |
Annual Sum or Average | 0.398009E+11 | 0.167778E+11 | 0.230230E+11 | 0.369798E+11 | 0.289408E+11 |
Minimum of Months | 0.148293E+10 | 0.466251E+09 | 0.841154E+09 | 0.628224E+09 | 0.476959E+09 |
Maximum of Months | 0.504346E+10 | 0.233475E+10 | 0.284224E+10 | 0.617749E+10 | 0.456582E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.116695E+10 | 0.00 | 0.116695E+10 | 15958924.85 | 0.674505E+10 |
February | 0.144238E+10 | 0.00 | 0.144238E+10 | 65882586.32 | 0.636871E+10 |
March | 0.221453E+10 | 0.00 | 0.221453E+10 | 0.479840E+09 | 0.467105E+10 |
April | 0.257403E+10 | 7207300.14 | 0.256683E+10 | 0.117291E+10 | 0.321100E+10 |
May | 0.352854E+10 | 0.117210E+09 | 0.341133E+10 | 0.246493E+10 | 0.203535E+10 |
June | 0.362120E+10 | 0.194158E+09 | 0.342704E+10 | 0.350674E+10 | 0.105690E+10 |
July | 0.361625E+10 | 0.130407E+09 | 0.348584E+10 | 0.422600E+10 | 0.603182E+09 |
August | 0.320389E+10 | 37859865.11 | 0.316603E+10 | 0.379203E+10 | 0.822033E+09 |
September | 0.233748E+10 | 421235.91 | 0.233705E+10 | 0.204435E+10 | 0.157503E+10 |
October | 0.209036E+10 | 0.00 | 0.209036E+10 | 0.118334E+10 | 0.295582E+10 |
November | 0.141889E+10 | 0.00 | 0.141889E+10 | 0.246755E+09 | 0.448960E+10 |
December | 0.101789E+10 | 0.00 | 0.101789E+10 | 18994535.89 | 0.619767E+10 |
Annual Sum or Average | 0.282324E+11 | 0.487264E+09 | 0.277451E+11 | 0.192177E+11 | 0.407314E+11 |
Minimum of Months | 0.101789E+10 | 0.00 | 0.101789E+10 | 15958924.85 | 0.603182E+09 |
Maximum of Months | 0.362120E+10 | 0.194158E+09 | 0.348584E+10 | 0.422600E+10 | 0.674505E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.162525E+10 | 0.651693E+09 | 0.973554E+09 | 0.679906E+09 | 0.414860E+10 |
February | 0.227628E+10 | 0.106189E+10 | 0.121438E+10 | 0.120129E+10 | 0.378241E+10 |
March | 0.321490E+10 | 0.136731E+10 | 0.184759E+10 | 0.225251E+10 | 0.298593E+10 |
April | 0.373386E+10 | 0.163565E+10 | 0.209821E+10 | 0.311324E+10 | 0.207025E+10 |
May | 0.467866E+10 | 0.186961E+10 | 0.280905E+10 | 0.454604E+10 | 0.137144E+10 |
June | 0.419623E+10 | 0.151874E+10 | 0.267749E+10 | 0.459846E+10 | 0.722453E+09 |
July | 0.435511E+10 | 0.157139E+10 | 0.278372E+10 | 0.528026E+10 | 0.409486E+09 |
August | 0.490432E+10 | 0.221130E+10 | 0.269302E+10 | 0.597087E+10 | 0.549253E+09 |
September | 0.354004E+10 | 0.158844E+10 | 0.195161E+10 | 0.371741E+10 | 0.102113E+10 |
October | 0.331612E+10 | 0.150303E+10 | 0.181309E+10 | 0.298620E+10 | 0.192101E+10 |
November | 0.198469E+10 | 0.762225E+09 | 0.122246E+10 | 0.117429E+10 | 0.277812E+10 |
December | 0.159785E+10 | 0.750383E+09 | 0.847472E+09 | 0.745672E+09 | 0.376972E+10 |
Annual Sum or Average | 0.394233E+11 | 0.164917E+11 | 0.229317E+11 | 0.362661E+11 | 0.255298E+11 |
Minimum of Months | 0.159785E+10 | 0.651693E+09 | 0.847472E+09 | 0.679906E+09 | 0.409486E+09 |
Maximum of Months | 0.490432E+10 | 0.221130E+10 | 0.280905E+10 | 0.597087E+10 | 0.414860E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.603704E+10 | 0.395315E+10 | 0.208389E+10 | 0.534991E+10 | 0.596010E+10 |
February | 0.719497E+10 | 0.476352E+10 | 0.243144E+10 | 0.623168E+10 | 0.555082E+10 |
March | 0.718607E+10 | 0.398948E+10 | 0.319659E+10 | 0.586334E+10 | 0.460070E+10 |
April | 0.539365E+10 | 0.213234E+10 | 0.326131E+10 | 0.378873E+10 | 0.331642E+10 |
May | 0.488426E+10 | 0.101819E+10 | 0.386607E+10 | 0.359993E+10 | 0.219510E+10 |
June | 0.443556E+10 | 0.677192E+09 | 0.375837E+10 | 0.412241E+10 | 0.114962E+10 |
July | 0.480457E+10 | 0.833865E+09 | 0.397070E+10 | 0.515536E+10 | 0.636382E+09 |
August | 0.641613E+10 | 0.237925E+10 | 0.403688E+10 | 0.666359E+10 | 0.889842E+09 |
September | 0.673898E+10 | 0.348613E+10 | 0.325286E+10 | 0.685373E+10 | 0.167366E+10 |
October | 0.954280E+10 | 0.598572E+10 | 0.355708E+10 | 0.998158E+10 | 0.310631E+10 |
November | 0.640143E+10 | 0.384470E+10 | 0.255674E+10 | 0.609075E+10 | 0.423629E+10 |
December | 0.654224E+10 | 0.464431E+10 | 0.189793E+10 | 0.623050E+10 | 0.545797E+10 |
Annual Sum or Average | 0.755777E+11 | 0.377078E+11 | 0.378699E+11 | 0.699315E+11 | 0.387732E+11 |
Minimum of Months | 0.443556E+10 | 0.677192E+09 | 0.189793E+10 | 0.359993E+10 | 0.636382E+09 |
Maximum of Months | 0.954280E+10 | 0.598572E+10 | 0.403688E+10 | 0.998158E+10 | 0.596010E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.160448E+10 | 0.657301E+09 | 0.947183E+09 | 0.697998E+09 | 0.435303E+10 |
February | 0.213685E+10 | 0.938516E+09 | 0.119833E+10 | 0.108384E+10 | 0.406830E+10 |
March | 0.349363E+10 | 0.161305E+10 | 0.188058E+10 | 0.254447E+10 | 0.308582E+10 |
April | 0.369506E+10 | 0.158109E+10 | 0.211397E+10 | 0.310981E+10 | 0.222728E+10 |
May | 0.444724E+10 | 0.168861E+10 | 0.275864E+10 | 0.431205E+10 | 0.147624E+10 |
June | 0.471032E+10 | 0.189949E+10 | 0.281083E+10 | 0.525337E+10 | 0.813071E+09 |
July | 0.455864E+10 | 0.171640E+10 | 0.284224E+10 | 0.551989E+10 | 0.482748E+09 |
August | 0.504346E+10 | 0.233475E+10 | 0.270871E+10 | 0.615215E+10 | 0.663459E+09 |
September | 0.346523E+10 | 0.151443E+10 | 0.195080E+10 | 0.369692E+10 | 0.112302E+10 |
October | 0.354982E+10 | 0.172620E+10 | 0.182362E+10 | 0.331362E+10 | 0.206995E+10 |
November | 0.161323E+10 | 0.466251E+09 | 0.114697E+10 | 0.768934E+09 | 0.298596E+10 |
December | 0.148293E+10 | 0.641773E+09 | 0.841154E+09 | 0.654032E+09 | 0.404474E+10 |
Annual Sum or Average | 0.398009E+11 | 0.167778E+11 | 0.230230E+11 | 0.371071E+11 | 0.273936E+11 |
Minimum of Months | 0.148293E+10 | 0.466251E+09 | 0.841154E+09 | 0.654032E+09 | 0.482748E+09 |
Maximum of Months | 0.504346E+10 | 0.233475E+10 | 0.284224E+10 | 0.615215E+10 | 0.435303E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.50 | 3018.05 | 435.68 | 0.00 | 435.68 | 0.00 | 0.00 |
February | 6.88 | 3120.69 | 596.21 | 0.00 | 596.21 | 0.00 | 0.00 |
March | 118.56 | 2149.07 | 826.80 | 0.00 | 826.80 | 0.00 | 0.00 |
April | 379.50 | 1512.22 | 993.05 | 2.78 | 990.27 | 0.00 | 0.00 |
May | 885.31 | 852.10 | 1317.38 | 43.76 | 1273.62 | 0.00 | 0.00 |
June | 1347.24 | 433.94 | 1397.04 | 74.90 | 1322.14 | 0.00 | 0.00 |
July | 1586.24 | 218.65 | 1350.13 | 48.69 | 1301.44 | 0.00 | 0.00 |
August | 1411.97 | 307.09 | 1196.18 | 14.13 | 1182.04 | 0.00 | 0.00 |
September | 761.98 | 693.08 | 901.79 | 0.16 | 901.63 | 0.00 | 0.00 |
October | 378.27 | 1333.21 | 780.44 | 0.00 | 780.44 | 0.00 | 0.00 |
November | 53.09 | 2233.76 | 547.40 | 0.00 | 547.40 | 0.00 | 0.00 |
December | 0.52 | 2939.59 | 380.03 | 0.00 | 380.03 | 0.00 | 0.00 |
Annual Sum or Average | 581.56 | 1558.68 | 895.23 | 15.45 | 879.78 | 0.00 | 0.00 |
Minimum of Months | 0.50 | 218.65 | 380.03 | 0.00 | 380.03 | 0.00 | 0.00 |
Maximum of Months | 1586.24 | 3120.69 | 1397.04 | 74.90 | 1322.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 228.86 | 1830.87 | 606.80 | 243.32 | 363.48 | 0.00 | 0.00 |
February | 454.11 | 1820.27 | 940.93 | 438.95 | 501.98 | 0.00 | 0.00 |
March | 801.53 | 1313.71 | 1200.31 | 510.50 | 689.82 | 0.00 | 0.00 |
April | 1171.54 | 914.70 | 1440.54 | 631.04 | 809.50 | 0.00 | 0.00 |
May | 1694.51 | 555.31 | 1746.82 | 698.03 | 1048.78 | 0.00 | 0.00 |
June | 1791.03 | 281.45 | 1618.92 | 585.93 | 1032.99 | 0.00 | 0.00 |
July | 1999.18 | 131.35 | 1626.02 | 586.69 | 1039.33 | 0.00 | 0.00 |
August | 2255.17 | 181.92 | 1831.07 | 825.61 | 1005.46 | 0.00 | 0.00 |
September | 1431.59 | 431.00 | 1365.76 | 612.83 | 752.94 | 0.00 | 0.00 |
October | 1084.40 | 824.01 | 1238.10 | 561.17 | 676.93 | 0.00 | 0.00 |
November | 403.69 | 1325.34 | 765.70 | 294.07 | 471.63 | 0.00 | 0.00 |
December | 245.39 | 1722.62 | 596.57 | 280.16 | 316.41 | 0.00 | 0.00 |
Annual Sum or Average | 1134.88 | 939.44 | 1250.11 | 522.95 | 727.16 | 0.00 | 0.00 |
Minimum of Months | 228.86 | 131.35 | 596.57 | 243.32 | 316.41 | 0.00 | 0.00 |
Maximum of Months | 2255.17 | 1830.87 | 1831.07 | 825.61 | 1048.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1963.08 | 2506.86 | 2253.90 | 1475.89 | 778.02 | 0.00 | 0.00 |
February | 2535.07 | 2561.95 | 2974.02 | 1968.99 | 1005.04 | 0.00 | 0.00 |
March | 2158.24 | 1959.43 | 2682.89 | 1489.45 | 1193.44 | 0.00 | 0.00 |
April | 1415.22 | 1458.14 | 2080.83 | 822.64 | 1258.19 | 0.00 | 0.00 |
May | 1326.21 | 885.27 | 1823.53 | 380.14 | 1443.39 | 0.00 | 0.00 |
June | 1590.97 | 461.21 | 1711.21 | 261.25 | 1449.96 | 0.00 | 0.00 |
July | 1932.11 | 227.34 | 1793.78 | 311.32 | 1482.46 | 0.00 | 0.00 |
August | 2488.97 | 324.38 | 2395.45 | 888.28 | 1507.17 | 0.00 | 0.00 |
September | 2645.60 | 691.03 | 2599.84 | 1344.91 | 1254.93 | 0.00 | 0.00 |
October | 3720.48 | 1272.55 | 3562.77 | 2234.74 | 1328.03 | 0.00 | 0.00 |
November | 2299.80 | 1906.58 | 2469.61 | 1483.24 | 986.37 | 0.00 | 0.00 |
December | 2273.58 | 2373.56 | 2442.52 | 1733.93 | 708.59 | 0.00 | 0.00 |
Annual Sum or Average | 2195.27 | 1378.84 | 2396.49 | 1195.67 | 1200.82 | 0.00 | 0.00 |
Minimum of Months | 1326.21 | 227.34 | 1711.21 | 261.25 | 708.59 | 0.00 | 0.00 |
Maximum of Months | 3720.48 | 2561.95 | 3562.77 | 2234.74 | 1507.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 236.86 | 1964.32 | 599.05 | 245.41 | 353.64 | 0.00 | 0.00 |
February | 409.05 | 2039.78 | 883.29 | 387.95 | 495.35 | 0.00 | 0.00 |
March | 892.13 | 1469.64 | 1304.38 | 602.25 | 702.13 | 0.00 | 0.00 |
April | 1132.40 | 1107.18 | 1425.57 | 609.99 | 815.58 | 0.00 | 0.00 |
May | 1583.71 | 631.60 | 1660.42 | 630.46 | 1029.96 | 0.00 | 0.00 |
June | 2011.83 | 360.22 | 1817.26 | 732.83 | 1084.43 | 0.00 | 0.00 |
July | 2039.86 | 210.49 | 1702.01 | 640.83 | 1061.18 | 0.00 | 0.00 |
August | 2268.97 | 289.88 | 1883.02 | 871.70 | 1011.32 | 0.00 | 0.00 |
September | 1402.14 | 509.01 | 1336.90 | 584.27 | 752.63 | 0.00 | 0.00 |
October | 1187.84 | 950.10 | 1325.36 | 644.49 | 680.86 | 0.00 | 0.00 |
November | 243.76 | 1548.61 | 622.39 | 179.88 | 442.51 | 0.00 | 0.00 |
December | 204.47 | 2018.38 | 553.66 | 239.61 | 314.05 | 0.00 | 0.00 |
Annual Sum or Average | 1139.69 | 1086.11 | 1262.08 | 532.02 | 730.06 | 0.00 | 0.00 |
Minimum of Months | 204.47 | 210.49 | 553.66 | 179.88 | 314.05 | 0.00 | 0.00 |
Maximum of Months | 2268.97 | 2039.78 | 1883.02 | 871.70 | 1084.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 3.71 | 2653.22 | 435.69 | 0.00 | 435.69 | 0.00 | 0.00 |
February | 18.01 | 2791.32 | 596.22 | 0.00 | 596.22 | 0.00 | 0.00 |
March | 159.97 | 1878.39 | 826.81 | 0.00 | 826.81 | 0.00 | 0.00 |
April | 429.46 | 1331.51 | 993.07 | 2.78 | 990.29 | 0.00 | 0.00 |
May | 914.65 | 791.77 | 1317.40 | 43.76 | 1273.64 | 0.00 | 0.00 |
June | 1366.67 | 409.84 | 1397.07 | 74.91 | 1322.16 | 0.00 | 0.00 |
July | 1601.23 | 217.18 | 1350.15 | 48.69 | 1301.47 | 0.00 | 0.00 |
August | 1432.37 | 303.87 | 1196.20 | 14.14 | 1182.06 | 0.00 | 0.00 |
September | 786.92 | 633.27 | 901.80 | 0.16 | 901.64 | 0.00 | 0.00 |
October | 415.57 | 1194.95 | 780.45 | 0.00 | 780.45 | 0.00 | 0.00 |
November | 75.14 | 1911.76 | 547.41 | 0.00 | 547.41 | 0.00 | 0.00 |
December | 2.72 | 2516.75 | 380.04 | 0.00 | 380.04 | 0.00 | 0.00 |
Annual Sum or Average | 604.62 | 1378.05 | 895.24 | 15.45 | 879.79 | 0.00 | 0.00 |
Minimum of Months | 2.72 | 217.18 | 380.04 | 0.00 | 380.04 | 0.00 | 0.00 |
Maximum of Months | 1601.23 | 2791.32 | 1397.07 | 74.91 | 1322.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.39 | 1629.02 | 606.80 | 243.31 | 363.48 | 0.00 | 0.00 |
February | 478.48 | 1656.88 | 940.92 | 438.94 | 501.98 | 0.00 | 0.00 |
March | 822.04 | 1194.24 | 1200.31 | 510.49 | 689.81 | 0.00 | 0.00 |
April | 1184.01 | 848.84 | 1440.53 | 631.04 | 809.49 | 0.00 | 0.00 |
May | 1695.58 | 528.78 | 1746.81 | 698.03 | 1048.78 | 0.00 | 0.00 |
June | 1783.75 | 278.82 | 1618.92 | 585.93 | 1032.98 | 0.00 | 0.00 |
July | 1986.00 | 147.34 | 1626.01 | 586.69 | 1039.32 | 0.00 | 0.00 |
August | 2240.76 | 202.38 | 1831.06 | 825.61 | 1005.46 | 0.00 | 0.00 |
September | 1433.87 | 407.32 | 1365.76 | 612.82 | 752.93 | 0.00 | 0.00 |
October | 1096.93 | 767.52 | 1238.10 | 561.17 | 676.93 | 0.00 | 0.00 |
November | 428.50 | 1173.76 | 765.70 | 294.07 | 471.63 | 0.00 | 0.00 |
December | 263.82 | 1527.55 | 596.57 | 280.16 | 316.41 | 0.00 | 0.00 |
Annual Sum or Average | 1143.01 | 859.06 | 1250.11 | 522.95 | 727.16 | 0.00 | 0.00 |
Minimum of Months | 246.39 | 147.34 | 596.57 | 243.31 | 316.41 | 0.00 | 0.00 |
Maximum of Months | 2240.76 | 1656.88 | 1831.06 | 825.61 | 1048.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1976.73 | 2356.31 | 2253.97 | 1475.94 | 778.04 | 0.00 | 0.00 |
February | 2538.42 | 2453.14 | 2974.11 | 1969.05 | 1005.06 | 0.00 | 0.00 |
March | 2164.63 | 1849.52 | 2682.97 | 1489.50 | 1193.47 | 0.00 | 0.00 |
April | 1436.22 | 1367.76 | 2080.88 | 822.66 | 1258.22 | 0.00 | 0.00 |
May | 1338.15 | 851.19 | 1823.57 | 380.15 | 1443.42 | 0.00 | 0.00 |
June | 1602.64 | 445.04 | 1711.25 | 261.26 | 1449.99 | 0.00 | 0.00 |
July | 1945.04 | 229.28 | 1793.82 | 311.33 | 1482.49 | 0.00 | 0.00 |
August | 2500.82 | 329.68 | 2395.51 | 888.31 | 1507.20 | 0.00 | 0.00 |
September | 2641.88 | 669.60 | 2599.92 | 1344.96 | 1254.96 | 0.00 | 0.00 |
October | 3703.20 | 1238.28 | 3562.87 | 2234.81 | 1328.06 | 0.00 | 0.00 |
November | 2308.03 | 1790.77 | 2469.69 | 1483.29 | 986.40 | 0.00 | 0.00 |
December | 2285.05 | 2221.32 | 2442.59 | 1733.99 | 708.61 | 0.00 | 0.00 |
Annual Sum or Average | 2202.91 | 1310.21 | 2396.55 | 1195.71 | 1200.85 | 0.00 | 0.00 |
Minimum of Months | 1338.15 | 229.28 | 1711.25 | 261.26 | 708.61 | 0.00 | 0.00 |
Maximum of Months | 3703.20 | 2453.14 | 3562.87 | 2234.81 | 1507.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.60 | 1704.68 | 599.05 | 245.41 | 353.64 | 0.00 | 0.00 |
February | 439.53 | 1767.47 | 883.29 | 387.94 | 495.34 | 0.00 | 0.00 |
March | 937.93 | 1227.46 | 1304.37 | 602.24 | 702.13 | 0.00 | 0.00 |
April | 1187.57 | 913.72 | 1425.56 | 609.99 | 815.57 | 0.00 | 0.00 |
May | 1607.37 | 572.96 | 1660.41 | 630.45 | 1029.96 | 0.00 | 0.00 |
June | 2035.60 | 317.62 | 1817.25 | 732.83 | 1084.42 | 0.00 | 0.00 |
July | 2073.47 | 178.08 | 1702.00 | 640.83 | 1061.17 | 0.00 | 0.00 |
August | 2306.41 | 248.78 | 1883.01 | 871.70 | 1011.31 | 0.00 | 0.00 |
September | 1425.26 | 449.95 | 1336.90 | 584.27 | 752.63 | 0.00 | 0.00 |
October | 1223.61 | 824.25 | 1325.35 | 644.49 | 680.86 | 0.00 | 0.00 |
November | 281.30 | 1248.42 | 622.39 | 179.88 | 442.51 | 0.00 | 0.00 |
December | 234.55 | 1617.40 | 553.66 | 239.61 | 314.05 | 0.00 | 0.00 |
Annual Sum or Average | 1172.62 | 917.71 | 1262.08 | 532.02 | 730.06 | 0.00 | 0.00 |
Minimum of Months | 234.55 | 178.08 | 553.66 | 179.88 | 314.05 | 0.00 | 0.00 |
Maximum of Months | 2306.41 | 1767.47 | 1883.01 | 871.70 | 1084.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5.96 | 2518.31 | 435.69 | 0.00 | 435.69 | 0.00 | 0.00 |
February | 27.23 | 2632.57 | 596.22 | 0.00 | 596.22 | 0.00 | 0.00 |
March | 179.15 | 1743.97 | 826.81 | 0.00 | 826.81 | 0.00 | 0.00 |
April | 452.51 | 1238.81 | 993.07 | 2.78 | 990.29 | 0.00 | 0.00 |
May | 920.30 | 759.91 | 1317.40 | 43.76 | 1273.64 | 0.00 | 0.00 |
June | 1352.91 | 407.76 | 1397.07 | 74.91 | 1322.16 | 0.00 | 0.00 |
July | 1577.81 | 225.20 | 1350.15 | 48.69 | 1301.47 | 0.00 | 0.00 |
August | 1415.78 | 306.91 | 1196.20 | 14.14 | 1182.06 | 0.00 | 0.00 |
September | 788.71 | 607.65 | 901.80 | 0.16 | 901.64 | 0.00 | 0.00 |
October | 441.81 | 1103.58 | 780.45 | 0.00 | 780.45 | 0.00 | 0.00 |
November | 95.20 | 1732.10 | 547.41 | 0.00 | 547.41 | 0.00 | 0.00 |
December | 7.09 | 2313.95 | 380.04 | 0.00 | 380.04 | 0.00 | 0.00 |
Annual Sum or Average | 609.39 | 1291.58 | 895.24 | 15.45 | 879.79 | 0.00 | 0.00 |
Minimum of Months | 5.96 | 225.20 | 380.04 | 0.00 | 380.04 | 0.00 | 0.00 |
Maximum of Months | 1577.81 | 2632.57 | 1397.07 | 74.91 | 1322.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 253.85 | 1548.91 | 606.80 | 243.31 | 363.48 | 0.00 | 0.00 |
February | 496.56 | 1563.49 | 940.92 | 438.94 | 501.98 | 0.00 | 0.00 |
March | 840.99 | 1114.82 | 1200.31 | 510.49 | 689.81 | 0.00 | 0.00 |
April | 1201.09 | 798.71 | 1440.53 | 631.04 | 809.49 | 0.00 | 0.00 |
May | 1697.30 | 512.04 | 1746.81 | 698.03 | 1048.78 | 0.00 | 0.00 |
June | 1774.10 | 278.72 | 1618.92 | 585.93 | 1032.98 | 0.00 | 0.00 |
July | 1971.42 | 152.88 | 1626.01 | 586.69 | 1039.32 | 0.00 | 0.00 |
August | 2229.27 | 205.07 | 1831.06 | 825.61 | 1005.46 | 0.00 | 0.00 |
September | 1434.18 | 393.95 | 1365.76 | 612.82 | 752.93 | 0.00 | 0.00 |
October | 1114.92 | 717.22 | 1238.10 | 561.17 | 676.93 | 0.00 | 0.00 |
November | 453.04 | 1071.81 | 765.70 | 294.07 | 471.63 | 0.00 | 0.00 |
December | 278.40 | 1407.45 | 596.57 | 280.16 | 316.41 | 0.00 | 0.00 |
Annual Sum or Average | 1149.99 | 809.54 | 1250.11 | 522.95 | 727.16 | 0.00 | 0.00 |
Minimum of Months | 253.85 | 152.88 | 596.57 | 243.31 | 316.41 | 0.00 | 0.00 |
Maximum of Months | 2229.27 | 1563.49 | 1831.06 | 825.61 | 1048.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1997.43 | 2225.25 | 2253.97 | 1475.94 | 778.04 | 0.00 | 0.00 |
February | 2575.93 | 2294.49 | 2974.11 | 1969.05 | 1005.06 | 0.00 | 0.00 |
March | 2189.12 | 1717.70 | 2682.97 | 1489.50 | 1193.47 | 0.00 | 0.00 |
April | 1461.70 | 1279.48 | 2080.88 | 822.66 | 1258.22 | 0.00 | 0.00 |
May | 1344.06 | 819.56 | 1823.57 | 380.15 | 1443.42 | 0.00 | 0.00 |
June | 1590.44 | 443.53 | 1711.25 | 261.26 | 1449.99 | 0.00 | 0.00 |
July | 1924.79 | 237.60 | 1793.82 | 311.33 | 1482.49 | 0.00 | 0.00 |
August | 2487.90 | 332.23 | 2395.51 | 888.31 | 1507.20 | 0.00 | 0.00 |
September | 2644.18 | 645.70 | 2599.92 | 1344.96 | 1254.96 | 0.00 | 0.00 |
October | 3726.69 | 1159.76 | 3562.87 | 2234.81 | 1328.06 | 0.00 | 0.00 |
November | 2349.83 | 1634.37 | 2469.69 | 1483.29 | 986.40 | 0.00 | 0.00 |
December | 2326.20 | 2037.77 | 2442.59 | 1733.99 | 708.61 | 0.00 | 0.00 |
Annual Sum or Average | 2217.51 | 1229.49 | 2396.55 | 1195.71 | 1200.85 | 0.00 | 0.00 |
Minimum of Months | 1344.06 | 237.60 | 1711.25 | 261.26 | 708.61 | 0.00 | 0.00 |
Maximum of Months | 3726.69 | 2294.49 | 3562.87 | 2234.81 | 1507.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 260.60 | 1625.24 | 599.05 | 245.41 | 353.64 | 0.00 | 0.00 |
February | 448.02 | 1681.67 | 883.29 | 387.94 | 495.34 | 0.00 | 0.00 |
March | 950.00 | 1152.11 | 1304.37 | 602.24 | 702.13 | 0.00 | 0.00 |
April | 1199.77 | 859.29 | 1425.56 | 609.99 | 815.57 | 0.00 | 0.00 |
May | 1609.94 | 551.17 | 1660.41 | 630.45 | 1029.96 | 0.00 | 0.00 |
June | 2026.76 | 313.68 | 1817.25 | 732.83 | 1084.42 | 0.00 | 0.00 |
July | 2060.89 | 180.24 | 1702.00 | 640.83 | 1061.17 | 0.00 | 0.00 |
August | 2296.95 | 247.71 | 1883.01 | 871.70 | 1011.31 | 0.00 | 0.00 |
September | 1426.28 | 433.26 | 1336.90 | 584.27 | 752.63 | 0.00 | 0.00 |
October | 1237.17 | 772.83 | 1325.35 | 644.49 | 680.86 | 0.00 | 0.00 |
November | 296.66 | 1151.99 | 622.39 | 179.88 | 442.51 | 0.00 | 0.00 |
December | 244.19 | 1510.13 | 553.66 | 239.61 | 314.05 | 0.00 | 0.00 |
Annual Sum or Average | 1176.66 | 868.65 | 1262.08 | 532.02 | 730.06 | 0.00 | 0.00 |
Minimum of Months | 244.19 | 180.24 | 553.66 | 179.88 | 314.05 | 0.00 | 0.00 |
Maximum of Months | 2296.95 | 1681.67 | 1883.01 | 871.70 | 1084.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1333124.72 | 0.808354E+10 | 0.116693E+10 | 0.00 | 0.116693E+10 | 0.00 | 0.00 |
February | 16646408.48 | 0.754958E+10 | 0.144236E+10 | 0.00 | 0.144236E+10 | 0.00 | 0.00 |
March | 0.317562E+09 | 0.575607E+10 | 0.221449E+10 | 0.00 | 0.221449E+10 | 0.00 | 0.00 |
April | 0.983665E+09 | 0.391967E+10 | 0.257399E+10 | 7207085.21 | 0.256678E+10 | 0.00 | 0.00 |
May | 0.237121E+10 | 0.228226E+10 | 0.352847E+10 | 0.117207E+09 | 0.341126E+10 | 0.00 | 0.00 |
June | 0.349205E+10 | 0.112477E+10 | 0.362113E+10 | 0.194153E+09 | 0.342698E+10 | 0.00 | 0.00 |
July | 0.424860E+10 | 0.585622E+09 | 0.361619E+10 | 0.130403E+09 | 0.348578E+10 | 0.00 | 0.00 |
August | 0.378182E+10 | 0.822501E+09 | 0.320384E+10 | 37858736.05 | 0.316598E+10 | 0.00 | 0.00 |
September | 0.197504E+10 | 0.179646E+10 | 0.233744E+10 | 421223.35 | 0.233701E+10 | 0.00 | 0.00 |
October | 0.101315E+10 | 0.357087E+10 | 0.209033E+10 | 0.00 | 0.209033E+10 | 0.00 | 0.00 |
November | 0.137607E+09 | 0.578991E+10 | 0.141886E+10 | 0.00 | 0.141886E+10 | 0.00 | 0.00 |
December | 1396806.87 | 0.787339E+10 | 0.101787E+10 | 0.00 | 0.101787E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.183401E+11 | 0.491546E+11 | 0.282319E+11 | 0.487249E+09 | 0.277446E+11 | 0.00 | 0.00 |
Minimum of Months | 1333124.72 | 0.585622E+09 | 0.101787E+10 | 0.00 | 0.101787E+10 | 0.00 | 0.00 |
Maximum of Months | 0.424860E+10 | 0.808354E+10 | 0.362113E+10 | 0.194153E+09 | 0.348578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.612986E+09 | 0.490381E+10 | 0.162525E+10 | 0.651696E+09 | 0.973558E+09 | 0.00 | 0.00 |
February | 0.109858E+10 | 0.440360E+10 | 0.227629E+10 | 0.106190E+10 | 0.121439E+10 | 0.00 | 0.00 |
March | 0.214682E+10 | 0.351865E+10 | 0.321491E+10 | 0.136731E+10 | 0.184760E+10 | 0.00 | 0.00 |
April | 0.303664E+10 | 0.237091E+10 | 0.373388E+10 | 0.163566E+10 | 0.209822E+10 | 0.00 | 0.00 |
May | 0.453858E+10 | 0.148735E+10 | 0.467868E+10 | 0.186961E+10 | 0.280906E+10 | 0.00 | 0.00 |
June | 0.464236E+10 | 0.729516E+09 | 0.419625E+10 | 0.151874E+10 | 0.267750E+10 | 0.00 | 0.00 |
July | 0.535461E+10 | 0.351803E+09 | 0.435513E+10 | 0.157140E+10 | 0.278373E+10 | 0.00 | 0.00 |
August | 0.604025E+10 | 0.487263E+09 | 0.490434E+10 | 0.221131E+10 | 0.269303E+10 | 0.00 | 0.00 |
September | 0.371067E+10 | 0.111716E+10 | 0.354006E+10 | 0.158844E+10 | 0.195161E+10 | 0.00 | 0.00 |
October | 0.290445E+10 | 0.220704E+10 | 0.331613E+10 | 0.150304E+10 | 0.181309E+10 | 0.00 | 0.00 |
November | 0.104637E+10 | 0.343528E+10 | 0.198470E+10 | 0.762229E+09 | 0.122247E+10 | 0.00 | 0.00 |
December | 0.657252E+09 | 0.461388E+10 | 0.159786E+10 | 0.750386E+09 | 0.847475E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.357896E+11 | 0.296262E+11 | 0.394235E+11 | 0.164917E+11 | 0.229317E+11 | 0.00 | 0.00 |
Minimum of Months | 0.612986E+09 | 0.351803E+09 | 0.159786E+10 | 0.651696E+09 | 0.847475E+09 | 0.00 | 0.00 |
Maximum of Months | 0.604025E+10 | 0.490381E+10 | 0.490434E+10 | 0.221131E+10 | 0.280906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.525792E+10 | 0.671439E+10 | 0.603686E+10 | 0.395302E+10 | 0.208384E+10 | 0.00 | 0.00 |
February | 0.613285E+10 | 0.619788E+10 | 0.719475E+10 | 0.476337E+10 | 0.243138E+10 | 0.00 | 0.00 |
March | 0.578062E+10 | 0.524814E+10 | 0.718586E+10 | 0.398935E+10 | 0.319652E+10 | 0.00 | 0.00 |
April | 0.366825E+10 | 0.377950E+10 | 0.539351E+10 | 0.213227E+10 | 0.326124E+10 | 0.00 | 0.00 |
May | 0.355211E+10 | 0.237111E+10 | 0.488414E+10 | 0.101816E+10 | 0.386598E+10 | 0.00 | 0.00 |
June | 0.412380E+10 | 0.119547E+10 | 0.443546E+10 | 0.677170E+09 | 0.375829E+10 | 0.00 | 0.00 |
July | 0.517497E+10 | 0.608907E+09 | 0.480445E+10 | 0.833838E+09 | 0.397062E+10 | 0.00 | 0.00 |
August | 0.666646E+10 | 0.868810E+09 | 0.641596E+10 | 0.237917E+10 | 0.403679E+10 | 0.00 | 0.00 |
September | 0.685739E+10 | 0.179115E+10 | 0.673880E+10 | 0.348601E+10 | 0.325278E+10 | 0.00 | 0.00 |
October | 0.996493E+10 | 0.340839E+10 | 0.954252E+10 | 0.598552E+10 | 0.355699E+10 | 0.00 | 0.00 |
November | 0.596109E+10 | 0.494185E+10 | 0.640124E+10 | 0.384457E+10 | 0.255667E+10 | 0.00 | 0.00 |
December | 0.608956E+10 | 0.635736E+10 | 0.654204E+10 | 0.464416E+10 | 0.189788E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.692299E+11 | 0.434829E+11 | 0.755756E+11 | 0.377066E+11 | 0.378690E+11 | 0.00 | 0.00 |
Minimum of Months | 0.355211E+10 | 0.608907E+09 | 0.443546E+10 | 0.677170E+09 | 0.189788E+10 | 0.00 | 0.00 |
Maximum of Months | 0.996493E+10 | 0.671439E+10 | 0.954252E+10 | 0.598552E+10 | 0.403679E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.634418E+09 | 0.526122E+10 | 0.160449E+10 | 0.657304E+09 | 0.947187E+09 | 0.00 | 0.00 |
February | 0.989563E+09 | 0.493464E+10 | 0.213686E+10 | 0.938520E+09 | 0.119834E+10 | 0.00 | 0.00 |
March | 0.238947E+10 | 0.393629E+10 | 0.349365E+10 | 0.161305E+10 | 0.188059E+10 | 0.00 | 0.00 |
April | 0.293517E+10 | 0.286981E+10 | 0.369507E+10 | 0.158110E+10 | 0.211398E+10 | 0.00 | 0.00 |
May | 0.424181E+10 | 0.169168E+10 | 0.444726E+10 | 0.168861E+10 | 0.275865E+10 | 0.00 | 0.00 |
June | 0.521466E+10 | 0.933683E+09 | 0.471034E+10 | 0.189950E+10 | 0.281084E+10 | 0.00 | 0.00 |
July | 0.546357E+10 | 0.563780E+09 | 0.455865E+10 | 0.171640E+10 | 0.284225E+10 | 0.00 | 0.00 |
August | 0.607720E+10 | 0.776421E+09 | 0.504348E+10 | 0.233476E+10 | 0.270872E+10 | 0.00 | 0.00 |
September | 0.363435E+10 | 0.131934E+10 | 0.346525E+10 | 0.151443E+10 | 0.195081E+10 | 0.00 | 0.00 |
October | 0.318152E+10 | 0.254475E+10 | 0.354983E+10 | 0.172620E+10 | 0.182363E+10 | 0.00 | 0.00 |
November | 0.631828E+09 | 0.401399E+10 | 0.161323E+10 | 0.466253E+09 | 0.114698E+10 | 0.00 | 0.00 |
December | 0.547655E+09 | 0.540603E+10 | 0.148293E+10 | 0.641775E+09 | 0.841157E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.359412E+11 | 0.342516E+11 | 0.398010E+11 | 0.167779E+11 | 0.230231E+11 | 0.00 | 0.00 |
Minimum of Months | 0.547655E+09 | 0.563780E+09 | 0.148293E+10 | 0.466253E+09 | 0.841157E+09 | 0.00 | 0.00 |
Maximum of Months | 0.607720E+10 | 0.540603E+10 | 0.504348E+10 | 0.233476E+10 | 0.284225E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 9939828.32 | 0.710638E+10 | 0.116695E+10 | 0.00 | 0.116695E+10 | 0.00 | 0.00 |
February | 43569260.95 | 0.675276E+10 | 0.144238E+10 | 0.00 | 0.144238E+10 | 0.00 | 0.00 |
March | 0.428472E+09 | 0.503107E+10 | 0.221453E+10 | 0.00 | 0.221453E+10 | 0.00 | 0.00 |
April | 0.111315E+10 | 0.345128E+10 | 0.257403E+10 | 7207300.14 | 0.256683E+10 | 0.00 | 0.00 |
May | 0.244980E+10 | 0.212067E+10 | 0.352854E+10 | 0.117210E+09 | 0.341133E+10 | 0.00 | 0.00 |
June | 0.354240E+10 | 0.106231E+10 | 0.362120E+10 | 0.194158E+09 | 0.342704E+10 | 0.00 | 0.00 |
July | 0.428873E+10 | 0.581696E+09 | 0.361625E+10 | 0.130407E+09 | 0.348584E+10 | 0.00 | 0.00 |
August | 0.383645E+10 | 0.813874E+09 | 0.320389E+10 | 37859865.11 | 0.316603E+10 | 0.00 | 0.00 |
September | 0.203971E+10 | 0.164145E+10 | 0.233748E+10 | 421235.91 | 0.233705E+10 | 0.00 | 0.00 |
October | 0.111305E+10 | 0.320054E+10 | 0.209036E+10 | 0.00 | 0.209036E+10 | 0.00 | 0.00 |
November | 0.194753E+09 | 0.495528E+10 | 0.141889E+10 | 0.00 | 0.141889E+10 | 0.00 | 0.00 |
December | 7287364.88 | 0.674088E+10 | 0.101789E+10 | 0.00 | 0.101789E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.190673E+11 | 0.434582E+11 | 0.282324E+11 | 0.487264E+09 | 0.277451E+11 | 0.00 | 0.00 |
Minimum of Months | 7287364.88 | 0.581696E+09 | 0.101789E+10 | 0.00 | 0.101789E+10 | 0.00 | 0.00 |
Maximum of Months | 0.428873E+10 | 0.710638E+10 | 0.362120E+10 | 0.194158E+09 | 0.348584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.659919E+09 | 0.436316E+10 | 0.162525E+10 | 0.651693E+09 | 0.973554E+09 | 0.00 | 0.00 |
February | 0.115755E+10 | 0.400832E+10 | 0.227628E+10 | 0.106189E+10 | 0.121438E+10 | 0.00 | 0.00 |
March | 0.220174E+10 | 0.319866E+10 | 0.321490E+10 | 0.136731E+10 | 0.184759E+10 | 0.00 | 0.00 |
April | 0.306896E+10 | 0.220021E+10 | 0.373386E+10 | 0.163565E+10 | 0.209821E+10 | 0.00 | 0.00 |
May | 0.454145E+10 | 0.141629E+10 | 0.467866E+10 | 0.186961E+10 | 0.280905E+10 | 0.00 | 0.00 |
June | 0.462348E+10 | 0.722703E+09 | 0.419623E+10 | 0.151874E+10 | 0.267749E+10 | 0.00 | 0.00 |
July | 0.531932E+10 | 0.394631E+09 | 0.435511E+10 | 0.157139E+10 | 0.278372E+10 | 0.00 | 0.00 |
August | 0.600165E+10 | 0.542047E+09 | 0.490432E+10 | 0.221130E+10 | 0.269302E+10 | 0.00 | 0.00 |
September | 0.371659E+10 | 0.105577E+10 | 0.354004E+10 | 0.158844E+10 | 0.195161E+10 | 0.00 | 0.00 |
October | 0.293801E+10 | 0.205571E+10 | 0.331612E+10 | 0.150303E+10 | 0.181309E+10 | 0.00 | 0.00 |
November | 0.111067E+10 | 0.304239E+10 | 0.198469E+10 | 0.762225E+09 | 0.122246E+10 | 0.00 | 0.00 |
December | 0.706610E+09 | 0.409139E+10 | 0.159785E+10 | 0.750383E+09 | 0.847472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.360459E+11 | 0.270913E+11 | 0.394233E+11 | 0.164917E+11 | 0.229317E+11 | 0.00 | 0.00 |
Minimum of Months | 0.659919E+09 | 0.394631E+09 | 0.159785E+10 | 0.651693E+09 | 0.847472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.600165E+10 | 0.436316E+10 | 0.490432E+10 | 0.221130E+10 | 0.280905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.529446E+10 | 0.631113E+10 | 0.603704E+10 | 0.395315E+10 | 0.208389E+10 | 0.00 | 0.00 |
February | 0.614095E+10 | 0.593464E+10 | 0.719497E+10 | 0.476352E+10 | 0.243144E+10 | 0.00 | 0.00 |
March | 0.579774E+10 | 0.495375E+10 | 0.718607E+10 | 0.398948E+10 | 0.319659E+10 | 0.00 | 0.00 |
April | 0.372269E+10 | 0.354525E+10 | 0.539365E+10 | 0.213234E+10 | 0.326131E+10 | 0.00 | 0.00 |
May | 0.358409E+10 | 0.227982E+10 | 0.488426E+10 | 0.101819E+10 | 0.386607E+10 | 0.00 | 0.00 |
June | 0.415403E+10 | 0.115355E+10 | 0.443556E+10 | 0.677192E+09 | 0.375837E+10 | 0.00 | 0.00 |
July | 0.520961E+10 | 0.614102E+09 | 0.480457E+10 | 0.833865E+09 | 0.397070E+10 | 0.00 | 0.00 |
August | 0.669821E+10 | 0.883028E+09 | 0.641613E+10 | 0.237925E+10 | 0.403688E+10 | 0.00 | 0.00 |
September | 0.684776E+10 | 0.173561E+10 | 0.673898E+10 | 0.348613E+10 | 0.325286E+10 | 0.00 | 0.00 |
October | 0.991866E+10 | 0.331662E+10 | 0.954280E+10 | 0.598572E+10 | 0.355708E+10 | 0.00 | 0.00 |
November | 0.598241E+10 | 0.464168E+10 | 0.640143E+10 | 0.384470E+10 | 0.255674E+10 | 0.00 | 0.00 |
December | 0.612027E+10 | 0.594959E+10 | 0.654224E+10 | 0.464431E+10 | 0.189793E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.694709E+11 | 0.413188E+11 | 0.755777E+11 | 0.377078E+11 | 0.378699E+11 | 0.00 | 0.00 |
Minimum of Months | 0.358409E+10 | 0.614102E+09 | 0.443556E+10 | 0.677192E+09 | 0.189793E+10 | 0.00 | 0.00 |
Maximum of Months | 0.991866E+10 | 0.631113E+10 | 0.954280E+10 | 0.598572E+10 | 0.403688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.684609E+09 | 0.456582E+10 | 0.160448E+10 | 0.657301E+09 | 0.947183E+09 | 0.00 | 0.00 |
February | 0.106332E+10 | 0.427586E+10 | 0.213685E+10 | 0.938516E+09 | 0.119833E+10 | 0.00 | 0.00 |
March | 0.251216E+10 | 0.328762E+10 | 0.349363E+10 | 0.161305E+10 | 0.188058E+10 | 0.00 | 0.00 |
April | 0.307818E+10 | 0.236838E+10 | 0.369506E+10 | 0.158109E+10 | 0.211397E+10 | 0.00 | 0.00 |
May | 0.430519E+10 | 0.153463E+10 | 0.444724E+10 | 0.168861E+10 | 0.275864E+10 | 0.00 | 0.00 |
June | 0.527628E+10 | 0.823279E+09 | 0.471032E+10 | 0.189949E+10 | 0.281083E+10 | 0.00 | 0.00 |
July | 0.555359E+10 | 0.476959E+09 | 0.455864E+10 | 0.171640E+10 | 0.284224E+10 | 0.00 | 0.00 |
August | 0.617749E+10 | 0.666330E+09 | 0.504346E+10 | 0.233475E+10 | 0.270871E+10 | 0.00 | 0.00 |
September | 0.369429E+10 | 0.116628E+10 | 0.346523E+10 | 0.151443E+10 | 0.195080E+10 | 0.00 | 0.00 |
October | 0.327731E+10 | 0.220768E+10 | 0.354982E+10 | 0.172620E+10 | 0.182362E+10 | 0.00 | 0.00 |
November | 0.729138E+09 | 0.323591E+10 | 0.161323E+10 | 0.466251E+09 | 0.114697E+10 | 0.00 | 0.00 |
December | 0.628224E+09 | 0.433203E+10 | 0.148293E+10 | 0.641773E+09 | 0.841154E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.369798E+11 | 0.289408E+11 | 0.398009E+11 | 0.167778E+11 | 0.230230E+11 | 0.00 | 0.00 |
Minimum of Months | 0.628224E+09 | 0.476959E+09 | 0.148293E+10 | 0.466251E+09 | 0.841154E+09 | 0.00 | 0.00 |
Maximum of Months | 0.617749E+10 | 0.456582E+10 | 0.504346E+10 | 0.233475E+10 | 0.284224E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 15958924.85 | 0.674505E+10 | 0.116695E+10 | 0.00 | 0.116695E+10 | 0.00 | 0.00 |
February | 65882586.32 | 0.636871E+10 | 0.144238E+10 | 0.00 | 0.144238E+10 | 0.00 | 0.00 |
March | 0.479840E+09 | 0.467105E+10 | 0.221453E+10 | 0.00 | 0.221453E+10 | 0.00 | 0.00 |
April | 0.117291E+10 | 0.321100E+10 | 0.257403E+10 | 7207300.14 | 0.256683E+10 | 0.00 | 0.00 |
May | 0.246493E+10 | 0.203535E+10 | 0.352854E+10 | 0.117210E+09 | 0.341133E+10 | 0.00 | 0.00 |
June | 0.350674E+10 | 0.105690E+10 | 0.362120E+10 | 0.194158E+09 | 0.342704E+10 | 0.00 | 0.00 |
July | 0.422600E+10 | 0.603182E+09 | 0.361625E+10 | 0.130407E+09 | 0.348584E+10 | 0.00 | 0.00 |
August | 0.379203E+10 | 0.822033E+09 | 0.320389E+10 | 37859865.11 | 0.316603E+10 | 0.00 | 0.00 |
September | 0.204435E+10 | 0.157503E+10 | 0.233748E+10 | 421235.91 | 0.233705E+10 | 0.00 | 0.00 |
October | 0.118334E+10 | 0.295582E+10 | 0.209036E+10 | 0.00 | 0.209036E+10 | 0.00 | 0.00 |
November | 0.246755E+09 | 0.448960E+10 | 0.141889E+10 | 0.00 | 0.141889E+10 | 0.00 | 0.00 |
December | 18994535.89 | 0.619767E+10 | 0.101789E+10 | 0.00 | 0.101789E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.192177E+11 | 0.407314E+11 | 0.282324E+11 | 0.487264E+09 | 0.277451E+11 | 0.00 | 0.00 |
Minimum of Months | 15958924.85 | 0.603182E+09 | 0.101789E+10 | 0.00 | 0.101789E+10 | 0.00 | 0.00 |
Maximum of Months | 0.422600E+10 | 0.674505E+10 | 0.362120E+10 | 0.194158E+09 | 0.348584E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.679906E+09 | 0.414860E+10 | 0.162525E+10 | 0.651693E+09 | 0.973554E+09 | 0.00 | 0.00 |
February | 0.120129E+10 | 0.378241E+10 | 0.227628E+10 | 0.106189E+10 | 0.121438E+10 | 0.00 | 0.00 |
March | 0.225251E+10 | 0.298593E+10 | 0.321490E+10 | 0.136731E+10 | 0.184759E+10 | 0.00 | 0.00 |
April | 0.311324E+10 | 0.207025E+10 | 0.373386E+10 | 0.163565E+10 | 0.209821E+10 | 0.00 | 0.00 |
May | 0.454604E+10 | 0.137144E+10 | 0.467866E+10 | 0.186961E+10 | 0.280905E+10 | 0.00 | 0.00 |
June | 0.459846E+10 | 0.722453E+09 | 0.419623E+10 | 0.151874E+10 | 0.267749E+10 | 0.00 | 0.00 |
July | 0.528026E+10 | 0.409486E+09 | 0.435511E+10 | 0.157139E+10 | 0.278372E+10 | 0.00 | 0.00 |
August | 0.597087E+10 | 0.549253E+09 | 0.490432E+10 | 0.221130E+10 | 0.269302E+10 | 0.00 | 0.00 |
September | 0.371741E+10 | 0.102113E+10 | 0.354004E+10 | 0.158844E+10 | 0.195161E+10 | 0.00 | 0.00 |
October | 0.298620E+10 | 0.192101E+10 | 0.331612E+10 | 0.150303E+10 | 0.181309E+10 | 0.00 | 0.00 |
November | 0.117429E+10 | 0.277812E+10 | 0.198469E+10 | 0.762225E+09 | 0.122246E+10 | 0.00 | 0.00 |
December | 0.745672E+09 | 0.376972E+10 | 0.159785E+10 | 0.750383E+09 | 0.847472E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.362661E+11 | 0.255298E+11 | 0.394233E+11 | 0.164917E+11 | 0.229317E+11 | 0.00 | 0.00 |
Minimum of Months | 0.679906E+09 | 0.409486E+09 | 0.159785E+10 | 0.651693E+09 | 0.847472E+09 | 0.00 | 0.00 |
Maximum of Months | 0.597087E+10 | 0.414860E+10 | 0.490432E+10 | 0.221130E+10 | 0.280905E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.534991E+10 | 0.596010E+10 | 0.603704E+10 | 0.395315E+10 | 0.208389E+10 | 0.00 | 0.00 |
February | 0.623168E+10 | 0.555082E+10 | 0.719497E+10 | 0.476352E+10 | 0.243144E+10 | 0.00 | 0.00 |
March | 0.586334E+10 | 0.460070E+10 | 0.718607E+10 | 0.398948E+10 | 0.319659E+10 | 0.00 | 0.00 |
April | 0.378873E+10 | 0.331642E+10 | 0.539365E+10 | 0.213234E+10 | 0.326131E+10 | 0.00 | 0.00 |
May | 0.359993E+10 | 0.219510E+10 | 0.488426E+10 | 0.101819E+10 | 0.386607E+10 | 0.00 | 0.00 |
June | 0.412241E+10 | 0.114962E+10 | 0.443556E+10 | 0.677192E+09 | 0.375837E+10 | 0.00 | 0.00 |
July | 0.515536E+10 | 0.636382E+09 | 0.480457E+10 | 0.833865E+09 | 0.397070E+10 | 0.00 | 0.00 |
August | 0.666359E+10 | 0.889842E+09 | 0.641613E+10 | 0.237925E+10 | 0.403688E+10 | 0.00 | 0.00 |
September | 0.685373E+10 | 0.167366E+10 | 0.673898E+10 | 0.348613E+10 | 0.325286E+10 | 0.00 | 0.00 |
October | 0.998158E+10 | 0.310631E+10 | 0.954280E+10 | 0.598572E+10 | 0.355708E+10 | 0.00 | 0.00 |
November | 0.609075E+10 | 0.423629E+10 | 0.640143E+10 | 0.384470E+10 | 0.255674E+10 | 0.00 | 0.00 |
December | 0.623050E+10 | 0.545797E+10 | 0.654224E+10 | 0.464431E+10 | 0.189793E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.699315E+11 | 0.387732E+11 | 0.755777E+11 | 0.377078E+11 | 0.378699E+11 | 0.00 | 0.00 |
Minimum of Months | 0.359993E+10 | 0.636382E+09 | 0.443556E+10 | 0.677192E+09 | 0.189793E+10 | 0.00 | 0.00 |
Maximum of Months | 0.998158E+10 | 0.596010E+10 | 0.954280E+10 | 0.598572E+10 | 0.403688E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.697998E+09 | 0.435303E+10 | 0.160448E+10 | 0.657301E+09 | 0.947183E+09 | 0.00 | 0.00 |
February | 0.108384E+10 | 0.406830E+10 | 0.213685E+10 | 0.938516E+09 | 0.119833E+10 | 0.00 | 0.00 |
March | 0.254447E+10 | 0.308582E+10 | 0.349363E+10 | 0.161305E+10 | 0.188058E+10 | 0.00 | 0.00 |
April | 0.310981E+10 | 0.222728E+10 | 0.369506E+10 | 0.158109E+10 | 0.211397E+10 | 0.00 | 0.00 |
May | 0.431205E+10 | 0.147624E+10 | 0.444724E+10 | 0.168861E+10 | 0.275864E+10 | 0.00 | 0.00 |
June | 0.525337E+10 | 0.813071E+09 | 0.471032E+10 | 0.189949E+10 | 0.281083E+10 | 0.00 | 0.00 |
July | 0.551989E+10 | 0.482748E+09 | 0.455864E+10 | 0.171640E+10 | 0.284224E+10 | 0.00 | 0.00 |
August | 0.615215E+10 | 0.663459E+09 | 0.504346E+10 | 0.233475E+10 | 0.270871E+10 | 0.00 | 0.00 |
September | 0.369692E+10 | 0.112302E+10 | 0.346523E+10 | 0.151443E+10 | 0.195080E+10 | 0.00 | 0.00 |
October | 0.331362E+10 | 0.206995E+10 | 0.354982E+10 | 0.172620E+10 | 0.182362E+10 | 0.00 | 0.00 |
November | 0.768934E+09 | 0.298596E+10 | 0.161323E+10 | 0.466251E+09 | 0.114697E+10 | 0.00 | 0.00 |
December | 0.654032E+09 | 0.404474E+10 | 0.148293E+10 | 0.641773E+09 | 0.841154E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.371071E+11 | 0.273936E+11 | 0.398009E+11 | 0.167778E+11 | 0.230230E+11 | 0.00 | 0.00 |
Minimum of Months | 0.654032E+09 | 0.482748E+09 | 0.148293E+10 | 0.466251E+09 | 0.841154E+09 | 0.00 | 0.00 |
Maximum of Months | 0.615215E+10 | 0.435303E+10 | 0.504346E+10 | 0.233475E+10 | 0.284224E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 1.17 | -0.6 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
February | -0.2 | -2.5 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
March | 5.59 | 3.46 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
April | 10.94 | 7.99 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
May | 16.05 | 12.30 | 9.14 | 4.42 | 7.76 | 109.28 | 173.60 | 0.03 |
June | 21.71 | 18.07 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
July | 25.05 | 21.75 | 20.26 | 4.06 | 17.38 | 114.46 | 172.96 | 0.02 |
August | 24.79 | 19.83 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
September | 19.96 | 15.95 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
October | 14.02 | 11.02 | 7.95 | 4.86 | 2.63 | 61.34 | 179.75 | 0.00 |
November | 7.31 | 5.00 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
December | 3.33 | 0.97 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
Annual Sum or Average | 12.55 | 9.51 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
Minimum of Months | -0.2 | -2.5 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
Maximum of Months | 25.05 | 21.75 | 20.26 | 5.65 | 17.38 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
February | 10.00 | 20-FEB-11:00 | 4.34 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
March | 22.20 | 27-MAR-15:00 | 16.33 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
April | 26.70 | 07-APR-12:00 | 16.37 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
May | 30.00 | 30-MAY-12:00 | 17.98 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
June | 36.70 | 19-JUN-11:00 | 24.26 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
July | 33.90 | 07-JUL-11:00 | 23.29 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
August | 33.90 | 24-AUG-14:00 | 20.20 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
September | 31.10 | 01-SEP-13:00 | 17.31 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
October | 25.00 | 04-OCT-12:00 | 18.52 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
November | 17.80 | 04-NOV-12:20 | 12.56 | 8.50 | 3.60 | 6.14 | 182.50 | 595.67 |
December | 12.20 | 17-DEC-12:20 | 4.63 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 4.34 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
Maximum of Months | 36.70 | 24.26 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -12.2 | 02-JAN-04:00 | -13.4 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
February | -13.9 | 06-FEB-02:00 | -15.2 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
March | -5.0 | 23-MAR-03:00 | -7.4 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
April | 2.20 | 01-APR-03:00 | 0.56 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
June | 13.30 | 03-JUN-02:00 | 9.34 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
August | 15.00 | 08-AUG-04:00 | 12.46 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
November | -4.4 | 24-NOV-05:00 | -6.1 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
December | -8.3 | 31-DEC-23:00 | -10.4 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -13.9 | -15.2 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
March | 16.98 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
April | 17.69 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 20.42 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
June | 24.95 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 26.09 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
August | 25.83 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
September | 23.56 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 19.75 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
Maximum of Months | 26.09 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
April | 15.60 | 09-APR-10:00 | 21.70 | 17.69 | 4.10 | 14.84 | 244.50 | 281.50 |
May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
June | 22.80 | 15-JUN-11:00 | 31.10 | 24.95 | 5.20 | 22.47 | 380.00 | 460.00 |
July | 24.40 | 09-JUL-07:00 | 27.20 | 25.16 | 2.10 | 15.39 | 195.00 | 504.00 |
August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
September | 22.20 | 07-SEP-13:00 | 27.20 | 23.56 | 6.20 | 15.02 | 148.00 | 730.50 |
October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.296414E+11 | -.390876E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.121238E+10 | 65.01 | 0.00 | 0.00 |
February | 0.273628E+11 | -.358737E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.108645E+10 | 64.75 | 0.00 | 0.00 |
March | 0.318631E+11 | -.412294E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.118017E+10 | 64.01 | 0.00 | 0.00 |
April | 0.262100E+11 | -.354865E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.116279E+10 | 64.84 | 0.00 | 0.00 |
May | 0.256454E+11 | -.352802E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122329E+10 | 65.55 | 0.00 | 0.00 |
June | 0.230348E+11 | -.324557E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.117879E+10 | 65.37 | 0.00 | 0.00 |
July | 0.193480E+11 | -.292634E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.125671E+10 | 66.83 | 0.00 | 0.00 |
August | 0.217264E+11 | -.315629E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.122178E+10 | 65.54 | 0.00 | 0.00 |
September | 0.200032E+11 | -.295512E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.120103E+10 | 66.26 | 0.00 | 0.00 |
October | 0.227363E+11 | -.324952E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.124217E+10 | 66.35 | 0.00 | 0.00 |
November | 0.250508E+11 | -.343583E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -.118660E+10 | 65.78 | 0.00 | 0.00 |
December | 0.269619E+11 | -.365451E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.120943E+10 | 65.18 | 0.00 | 0.00 |
Annual Sum or Average | 0.299584E+12 | -.413189E+12 | 8760.00 | -.143616E+11 | 65.46 | |||||
Minimum of Months | 0.193480E+11 | -.412294E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -.125671E+10 | 64.01 | 0.00 | 0.00 |
Maximum of Months | 0.318631E+11 | -.292634E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -.108645E+10 | 66.83 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.74 | 0.73 | 01-JAN-07:49 | 5390.26 | 32.83 | 169.00 | 225.83 | 2811.40 | 33.15 | 181.67 | 185.33 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 7971.99 | 36.13 | 202.83 | 249.67 | 1659.05 | 27.06 | 177.33 | 224.50 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-06:00 | 2850.39 | 22.61 | 90.17 | 309.50 | 1205.17 | 21.11 | 146.83 | 254.83 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 1621.71 | 17.42 | 0.00 | 328.00 | 937.45 | 20.40 | 105.50 | 278.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1428.99 | 17.29 | 0.00 | 380.17 | 788.85 | 20.21 | 150.67 | 318.33 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:19 | 1360.40 | 17.22 | 0.00 | 368.33 | 763.84 | 20.21 | 128.50 | 318.17 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 1504.28 | 17.53 | 0.00 | 375.33 | 824.63 | 20.52 | 170.83 | 323.00 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:00 | 1654.81 | 17.53 | 0.00 | 360.50 | 940.51 | 20.48 | 180.83 | 320.17 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 3131.93 | 19.93 | 29.50 | 312.33 | 1110.60 | 20.80 | 143.83 | 272.33 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 8728.76 | 35.01 | 278.50 | 299.17 | 1559.08 | 22.88 | 239.50 | 276.17 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:00 | 5433.40 | 33.81 | 217.00 | 248.67 | 1802.59 | 28.48 | 213.17 | 222.50 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-07:40 | 5038.16 | 33.61 | 178.83 | 230.17 | 4614.18 | 37.62 | 197.67 | 198.00 |
Annual Sum or Average | 3472.67 | 0.74 | 3496.15 | 23.74 | 1165.83 | 3687.67 | 1418.65 | 23.44 | 2036.33 | 3191.33 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1360.40 | 17.22 | 0.00 | 225.83 | 763.84 | 20.21 | 105.50 | 185.33 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 8728.76 | 36.13 | 278.50 | 380.17 | 4614.18 | 37.62 | 239.50 | 323.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:49 | 1611.02 | 19.10 | 60.33 | 201.83 | 855.52 | 18.44 | 40.00 | 136.17 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 2177.91 | 19.26 | 61.33 | 229.33 | 1336.73 | 20.58 | 58.50 | 177.33 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-06:49 | 2296.65 | 17.21 | 56.67 | 300.67 | 1318.35 | 17.09 | 38.50 | 227.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-05:00 | 3196.58 | 15.74 | 38.83 | 326.00 | 1184.20 | 14.47 | 0.00 | 273.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 2515.19 | 13.32 | 0.00 | 382.67 | 1385.48 | 14.53 | 0.00 | 323.50 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 2311.87 | 13.29 | 0.00 | 372.67 | 1261.58 | 14.56 | 0.00 | 333.50 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:00 | 2317.92 | 13.71 | 1.83 | 381.83 | 1266.52 | 14.87 | 0.00 | 334.50 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 3189.38 | 15.96 | 57.67 | 359.67 | 1286.75 | 14.74 | 0.00 | 327.00 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-05:49 | 2637.29 | 17.48 | 61.33 | 307.50 | 1157.18 | 15.13 | 5.50 | 260.33 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2377.13 | 18.82 | 74.17 | 279.83 | 1281.63 | 18.67 | 50.17 | 239.83 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-06:49 | 1507.73 | 17.76 | 52.00 | 230.33 | 829.77 | 18.76 | 46.17 | 174.33 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-07:40 | 1488.50 | 18.80 | 64.17 | 196.83 | 896.88 | 20.19 | 59.00 | 123.50 |
Annual Sum or Average | 3472.67 | 0.74 | 2376.00 | 16.31 | 528.33 | 3569.17 | 1199.28 | 16.44 | 297.83 | 2930.17 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1488.50 | 13.29 | 0.00 | 196.83 | 829.77 | 14.47 | 0.00 | 123.50 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 3196.58 | 19.26 | 74.17 | 382.67 | 1385.48 | 20.58 | 59.00 | 334.50 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.76 | 0.73 | 01-JAN-08:30 | 496.42 | 0.00 | 0.00 | 175.33 | 303.68 | 0.00 | 0.00 | 71.67 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:30 | 534.36 | 0.00 | 0.00 | 208.00 | 348.66 | 0.00 | 0.00 | 117.67 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-07:10 | 714.21 | 0.00 | 0.00 | 296.33 | 445.29 | 0.00 | 0.00 | 198.00 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 803.87 | 0.00 | 0.00 | 332.50 | 502.92 | 0.00 | 0.00 | 256.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1046.38 | 0.00 | 0.00 | 393.83 | 597.24 | 0.00 | 0.00 | 332.00 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 1174.41 | 0.00 | 0.00 | 390.83 | 646.83 | 0.00 | 0.00 | 351.33 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:00 | 1162.36 | 0.00 | 0.00 | 395.67 | 645.46 | 0.00 | 0.00 | 347.83 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:49 | 950.19 | 0.00 | 0.00 | 371.50 | 571.96 | 0.00 | 0.00 | 329.33 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 735.56 | 0.00 | 0.00 | 304.33 | 465.41 | 0.00 | 0.00 | 228.00 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 662.24 | 0.00 | 0.00 | 275.50 | 430.53 | 0.00 | 0.00 | 206.67 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-07:19 | 556.09 | 0.00 | 0.00 | 213.50 | 332.25 | 0.00 | 0.00 | 107.67 |
December | 211.17 | 0.77 | 0.73 | 01-DEC-08:20 | 398.09 | 0.00 | 0.00 | 155.00 | 252.26 | 0.00 | 0.00 | 34.67 |
Annual Sum or Average | 3472.67 | 0.74 | 820.02 | 0.00 | 0.00 | 3512.33 | 488.20 | 0.00 | 0.00 | 2580.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 398.09 | 0.00 | 0.00 | 155.00 | 252.26 | 0.00 | 0.00 | 34.67 | |
Maximum of Months | 389.17 | 0.77 | 0.73 | 1174.41 | 0.00 | 0.00 | 395.67 | 646.83 | 0.00 | 0.00 | 351.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-08:30 | 1542.58 | 18.95 | 57.17 | 204.83 | 900.98 | 20.25 | 52.17 | 138.00 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:39 | 1785.56 | 18.74 | 56.17 | 228.83 | 909.21 | 18.23 | 36.17 | 173.67 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-07:19 | 2475.51 | 18.29 | 69.67 | 304.50 | 1456.11 | 18.00 | 47.50 | 237.33 |
April | 261.17 | 0.74 | 0.73 | 01-APR-07:19 | 3006.24 | 15.52 | 36.00 | 324.50 | 1153.64 | 14.43 | 0.00 | 275.67 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:00 | 2774.73 | 13.38 | 0.00 | 382.83 | 1204.25 | 14.70 | 1.83 | 325.33 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:40 | 2612.12 | 13.49 | 0.00 | 377.83 | 1429.30 | 16.88 | 43.00 | 323.17 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:40 | 2457.38 | 13.82 | 3.50 | 381.83 | 1327.71 | 14.92 | 0.00 | 330.17 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:00 | 3250.88 | 15.81 | 54.33 | 360.17 | 1383.80 | 14.74 | 0.00 | 327.67 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:30 | 2506.38 | 16.28 | 45.67 | 307.50 | 1352.15 | 15.25 | 5.50 | 261.00 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2663.69 | 19.57 | 83.50 | 292.67 | 1138.72 | 19.16 | 53.17 | 256.00 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-07:19 | 1349.32 | 18.82 | 67.83 | 233.33 | 700.02 | 18.25 | 43.50 | 170.17 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-08:30 | 1269.78 | 19.04 | 67.33 | 198.50 | 677.01 | 18.15 | 43.67 | 125.67 |
Annual Sum or Average | 3472.67 | 0.74 | 2417.46 | 16.42 | 541.17 | 3597.33 | 1179.88 | 16.62 | 326.50 | 2943.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1269.78 | 13.38 | 0.00 | 198.50 | 677.01 | 14.43 | 0.00 | 125.67 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 3250.88 | 19.57 | 83.50 | 382.83 | 1456.11 | 20.25 | 53.17 | 330.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:00 | 5345.48 | 31.71 | 169.00 | 224.33 | 2851.56 | 31.28 | 143.83 | 186.17 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 7938.45 | 35.56 | 202.33 | 248.50 | 1709.74 | 23.22 | 79.83 | 225.50 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-06:00 | 2862.68 | 18.07 | 89.67 | 311.50 | 1250.08 | 16.80 | 4.33 | 258.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 1601.17 | 11.53 | 0.00 | 325.83 | 971.66 | 16.44 | 0.00 | 279.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1401.88 | 11.59 | 0.00 | 378.83 | 813.22 | 16.31 | 0.00 | 324.83 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:30 | 1334.88 | 11.55 | 0.00 | 366.17 | 787.09 | 16.37 | 0.00 | 321.00 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 1473.63 | 11.74 | 0.00 | 373.50 | 849.04 | 16.55 | 0.00 | 324.67 |
August | 389.17 | 0.75 | 0.73 | 01-AUG-05:00 | 1629.09 | 11.91 | 0.00 | 358.50 | 972.29 | 16.70 | 0.00 | 322.00 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 3107.57 | 14.47 | 29.50 | 310.83 | 1152.52 | 16.57 | 0.00 | 274.00 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 8687.73 | 34.29 | 278.17 | 298.67 | 1683.61 | 18.61 | 19.33 | 277.33 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:00 | 5363.62 | 32.60 | 213.50 | 247.50 | 2222.99 | 27.43 | 136.67 | 224.00 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-07:40 | 4814.27 | 29.34 | 155.00 | 227.67 | 4650.53 | 36.81 | 195.67 | 199.17 |
Annual Sum or Average | 3472.67 | 0.74 | 3455.25 | 19.56 | 1137.17 | 3671.83 | 1487.10 | 19.96 | 579.67 | 3216.67 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1334.88 | 11.53 | 0.00 | 224.33 | 787.09 | 16.31 | 0.00 | 186.17 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 8687.73 | 35.56 | 278.17 | 378.83 | 4650.53 | 36.81 | 195.67 | 324.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:49 | 1605.07 | 17.13 | 60.33 | 201.33 | 874.28 | 16.39 | 40.00 | 138.67 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 2173.70 | 17.07 | 61.33 | 228.50 | 1361.52 | 18.79 | 58.50 | 181.33 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-06:49 | 2300.03 | 14.89 | 56.83 | 300.00 | 1347.68 | 15.04 | 38.50 | 231.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:10 | 3200.54 | 12.88 | 38.83 | 324.83 | 1218.96 | 11.90 | 0.00 | 276.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 2489.85 | 9.90 | 0.00 | 381.83 | 1417.94 | 12.16 | 0.00 | 328.17 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 2207.01 | 9.90 | 0.00 | 372.17 | 1293.92 | 12.24 | 0.00 | 336.00 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:00 | 2299.78 | 10.29 | 1.83 | 381.17 | 1299.51 | 12.48 | 0.00 | 337.83 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 3182.97 | 13.22 | 57.67 | 359.33 | 1320.74 | 12.28 | 0.00 | 330.50 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-05:49 | 2643.15 | 15.00 | 61.33 | 305.83 | 1190.39 | 12.58 | 5.50 | 263.50 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2370.29 | 16.57 | 74.17 | 279.00 | 1311.15 | 16.52 | 50.17 | 243.67 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-06:49 | 1500.76 | 15.28 | 52.00 | 229.17 | 850.10 | 16.59 | 46.17 | 177.50 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-07:40 | 1486.52 | 16.80 | 64.17 | 196.33 | 913.94 | 18.39 | 59.33 | 127.67 |
Annual Sum or Average | 3472.67 | 0.74 | 2359.28 | 13.59 | 528.50 | 3559.50 | 1228.64 | 14.18 | 298.17 | 2972.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1486.52 | 9.90 | 0.00 | 196.33 | 850.10 | 11.90 | 0.00 | 127.67 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 3200.54 | 17.13 | 74.17 | 381.83 | 1417.94 | 18.79 | 59.33 | 337.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.76 | 0.73 | 01-JAN-08:30 | 484.94 | 0.00 | 0.00 | 169.50 | 311.21 | 0.00 | 0.00 | 77.50 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:30 | 523.87 | 0.00 | 0.00 | 205.33 | 357.94 | 0.00 | 0.00 | 122.83 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-07:10 | 701.51 | 0.00 | 0.00 | 294.83 | 458.09 | 0.00 | 0.00 | 202.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 791.69 | 0.00 | 0.00 | 331.00 | 518.10 | 0.00 | 0.00 | 262.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1028.10 | 0.00 | 0.00 | 392.50 | 615.13 | 0.00 | 0.00 | 335.50 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 1156.35 | 0.00 | 0.00 | 388.50 | 673.71 | 0.00 | 0.00 | 357.83 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:00 | 1143.09 | 0.00 | 0.00 | 393.17 | 664.21 | 0.00 | 0.00 | 350.17 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:49 | 935.15 | 0.00 | 0.00 | 370.33 | 588.76 | 0.00 | 0.00 | 332.17 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 723.52 | 0.00 | 0.00 | 302.17 | 479.05 | 0.00 | 0.00 | 233.67 |
October | 305.50 | 0.75 | 0.73 | 01-OCT-14:39 | 648.88 | 0.00 | 0.00 | 273.50 | 441.78 | 0.00 | 0.00 | 211.50 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-07:19 | 543.62 | 0.00 | 0.00 | 210.00 | 340.71 | 0.00 | 0.00 | 113.67 |
December | 211.17 | 0.77 | 0.73 | 01-DEC-08:30 | 388.65 | 0.00 | 0.00 | 149.00 | 258.30 | 0.00 | 0.00 | 41.83 |
Annual Sum or Average | 3472.67 | 0.75 | 805.69 | 0.00 | 0.00 | 3479.83 | 502.92 | 0.00 | 0.00 | 2641.67 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 388.65 | 0.00 | 0.00 | 149.00 | 258.30 | 0.00 | 0.00 | 41.83 | |
Maximum of Months | 389.17 | 0.77 | 0.73 | 1156.35 | 0.00 | 0.00 | 393.17 | 673.71 | 0.00 | 0.00 | 357.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-08:30 | 1525.29 | 16.79 | 56.17 | 203.50 | 919.19 | 18.38 | 52.33 | 141.00 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:39 | 1565.53 | 14.04 | 37.00 | 227.67 | 934.18 | 16.05 | 36.17 | 178.00 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-07:19 | 2473.43 | 15.97 | 68.67 | 303.83 | 1486.84 | 15.95 | 47.67 | 239.33 |
April | 261.17 | 0.74 | 0.73 | 01-APR-07:19 | 2797.50 | 12.65 | 36.00 | 324.00 | 1187.54 | 11.88 | 0.00 | 278.67 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:00 | 2757.53 | 9.95 | 0.00 | 382.17 | 1236.08 | 12.32 | 1.83 | 330.50 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:40 | 2590.04 | 9.98 | 0.00 | 377.33 | 1466.00 | 14.89 | 43.00 | 326.33 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:49 | 2437.42 | 10.38 | 3.50 | 380.50 | 1361.77 | 12.50 | 0.00 | 333.83 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:00 | 3245.49 | 13.03 | 54.33 | 359.83 | 1418.57 | 12.27 | 0.00 | 329.50 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:30 | 2510.06 | 13.55 | 45.67 | 305.50 | 1383.57 | 12.72 | 5.50 | 264.50 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2660.35 | 17.35 | 83.50 | 291.67 | 1168.50 | 16.99 | 53.17 | 258.00 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-07:19 | 1328.60 | 16.33 | 64.83 | 232.67 | 717.15 | 16.06 | 43.50 | 173.33 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-08:30 | 1098.61 | 14.36 | 45.67 | 196.50 | 693.51 | 16.12 | 43.67 | 129.67 |
Annual Sum or Average | 3472.67 | 0.74 | 2368.30 | 13.33 | 495.33 | 3585.17 | 1209.46 | 14.36 | 326.83 | 2982.67 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1098.61 | 9.95 | 0.00 | 196.50 | 693.51 | 11.88 | 0.00 | 129.67 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 3245.49 | 17.35 | 83.50 | 382.17 | 1486.84 | 18.38 | 53.17 | 333.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:00 | 5344.11 | 31.70 | 169.00 | 224.00 | 2852.87 | 31.27 | 143.67 | 186.33 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 7937.54 | 35.54 | 202.33 | 248.50 | 1711.14 | 23.20 | 79.83 | 225.67 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-06:00 | 2863.17 | 18.04 | 89.67 | 311.50 | 1251.43 | 16.79 | 4.33 | 258.33 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 1601.83 | 11.49 | 0.00 | 325.83 | 972.67 | 16.42 | 0.00 | 279.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1402.58 | 11.55 | 0.00 | 378.83 | 814.16 | 16.30 | 0.00 | 325.00 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:30 | 1335.47 | 11.51 | 0.00 | 366.33 | 787.94 | 16.35 | 0.00 | 321.33 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:30 | 1474.39 | 11.70 | 0.00 | 373.50 | 850.03 | 16.53 | 0.00 | 325.17 |
August | 389.17 | 0.75 | 0.73 | 01-AUG-05:00 | 1629.80 | 11.87 | 0.00 | 358.50 | 973.32 | 16.68 | 0.00 | 322.33 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 3108.24 | 14.43 | 29.50 | 310.83 | 1153.74 | 16.56 | 0.00 | 274.00 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 8687.35 | 34.28 | 278.17 | 298.67 | 1685.26 | 18.60 | 19.33 | 277.33 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-06:00 | 5362.42 | 32.58 | 213.50 | 247.50 | 2224.53 | 27.42 | 136.67 | 224.00 |
December | 211.17 | 0.75 | 0.73 | 01-DEC-07:40 | 4784.15 | 28.93 | 152.00 | 227.50 | 4651.53 | 36.81 | 195.67 | 199.17 |
Annual Sum or Average | 3472.67 | 0.74 | 3453.61 | 19.51 | 1134.17 | 3671.50 | 1488.26 | 19.95 | 579.50 | 3218.50 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1335.47 | 11.49 | 0.00 | 224.00 | 787.94 | 16.30 | 0.00 | 186.33 | |
Maximum of Months | 389.17 | 0.75 | 0.73 | 8687.35 | 35.54 | 278.17 | 378.83 | 4651.53 | 36.81 | 195.67 | 325.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-07:49 | 1604.63 | 17.13 | 60.33 | 201.17 | 874.83 | 16.38 | 40.00 | 138.67 |
February | 216.00 | 0.74 | 0.73 | 01-FEB-07:40 | 2173.13 | 17.06 | 61.33 | 228.50 | 1362.06 | 18.78 | 58.50 | 181.83 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-06:49 | 2299.39 | 14.88 | 56.83 | 300.00 | 1348.43 | 15.04 | 38.50 | 231.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:10 | 3200.27 | 12.87 | 38.83 | 324.83 | 1219.79 | 11.89 | 0.00 | 277.33 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 2489.86 | 9.89 | 0.00 | 382.00 | 1418.95 | 12.15 | 0.00 | 328.17 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 2207.00 | 9.89 | 0.00 | 372.00 | 1294.84 | 12.23 | 0.00 | 336.00 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:00 | 2299.93 | 10.28 | 1.83 | 381.17 | 1300.56 | 12.47 | 0.00 | 337.83 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:40 | 3182.85 | 13.21 | 57.67 | 359.33 | 1321.68 | 12.27 | 0.00 | 330.50 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-05:49 | 2642.78 | 14.99 | 61.33 | 305.83 | 1191.16 | 12.57 | 5.50 | 263.50 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2369.59 | 16.56 | 74.17 | 279.00 | 1311.86 | 16.52 | 50.17 | 243.67 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-06:49 | 1500.40 | 15.27 | 52.00 | 229.17 | 848.07 | 16.41 | 44.83 | 177.00 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-07:40 | 1486.09 | 16.79 | 64.17 | 196.33 | 834.35 | 16.08 | 42.67 | 125.33 |
Annual Sum or Average | 3472.67 | 0.74 | 2359.01 | 13.58 | 528.50 | 3559.33 | 1224.39 | 14.02 | 280.17 | 2971.00 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1486.09 | 9.89 | 0.00 | 196.33 | 834.35 | 11.89 | 0.00 | 125.33 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 3200.27 | 17.13 | 74.17 | 382.00 | 1418.95 | 18.78 | 58.50 | 337.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.76 | 0.73 | 01-JAN-08:30 | 484.83 | 0.00 | 0.00 | 169.50 | 311.47 | 0.00 | 0.00 | 77.83 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:30 | 523.63 | 0.00 | 0.00 | 205.33 | 358.17 | 0.00 | 0.00 | 123.17 |
March | 275.00 | 0.75 | 0.73 | 01-MAR-07:10 | 701.38 | 0.00 | 0.00 | 294.83 | 458.46 | 0.00 | 0.00 | 202.17 |
April | 261.17 | 0.74 | 0.73 | 01-APR-06:19 | 791.53 | 0.00 | 0.00 | 331.00 | 518.50 | 0.00 | 0.00 | 263.00 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:40 | 1028.17 | 0.00 | 0.00 | 392.50 | 615.74 | 0.00 | 0.00 | 336.00 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-04:00 | 1156.38 | 0.00 | 0.00 | 388.50 | 674.33 | 0.00 | 0.00 | 358.00 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-04:00 | 1143.16 | 0.00 | 0.00 | 393.17 | 664.86 | 0.00 | 0.00 | 350.17 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:49 | 935.01 | 0.00 | 0.00 | 370.33 | 589.24 | 0.00 | 0.00 | 332.17 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:10 | 723.34 | 0.00 | 0.00 | 302.17 | 479.41 | 0.00 | 0.00 | 234.17 |
October | 305.50 | 0.75 | 0.73 | 01-OCT-14:39 | 648.58 | 0.00 | 0.00 | 273.33 | 442.06 | 0.00 | 0.00 | 211.67 |
November | 240.83 | 0.75 | 0.73 | 01-NOV-07:19 | 543.55 | 0.00 | 0.00 | 210.00 | 341.03 | 0.00 | 0.00 | 113.83 |
December | 211.17 | 0.77 | 0.73 | 01-DEC-08:30 | 388.49 | 0.00 | 0.00 | 149.50 | 258.49 | 0.00 | 0.00 | 42.17 |
Annual Sum or Average | 3472.67 | 0.75 | 805.59 | 0.00 | 0.00 | 3480.17 | 503.35 | 0.00 | 0.00 | 2644.33 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 388.49 | 0.00 | 0.00 | 149.50 | 258.49 | 0.00 | 0.00 | 42.17 | |
Maximum of Months | 389.17 | 0.77 | 0.73 | 1156.38 | 0.00 | 0.00 | 393.17 | 674.33 | 0.00 | 0.00 | 358.00 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN}[] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 199.50 | 0.75 | 0.73 | 01-JAN-08:30 | 1524.87 | 16.78 | 56.17 | 203.50 | 843.70 | 16.15 | 36.83 | 138.50 |
February | 216.00 | 0.75 | 0.73 | 01-FEB-08:39 | 1565.02 | 14.03 | 37.00 | 227.67 | 934.75 | 16.05 | 36.17 | 178.17 |
March | 275.00 | 0.74 | 0.73 | 01-MAR-07:19 | 2472.79 | 15.96 | 68.67 | 303.83 | 1487.61 | 15.94 | 47.67 | 239.83 |
April | 261.17 | 0.74 | 0.73 | 01-APR-07:19 | 2797.16 | 12.63 | 36.00 | 324.00 | 1188.37 | 11.87 | 0.00 | 278.83 |
May | 372.00 | 0.74 | 0.73 | 01-MAY-05:00 | 2757.59 | 9.93 | 0.00 | 382.33 | 1237.06 | 12.31 | 1.83 | 330.50 |
June | 351.83 | 0.74 | 0.73 | 01-JUN-05:40 | 2590.02 | 9.96 | 0.00 | 377.33 | 1467.11 | 14.88 | 43.00 | 326.50 |
July | 365.17 | 0.74 | 0.73 | 01-JUL-05:49 | 2437.55 | 10.37 | 3.50 | 380.83 | 1362.86 | 12.50 | 0.00 | 334.17 |
August | 389.17 | 0.74 | 0.73 | 01-AUG-05:00 | 3245.37 | 13.01 | 54.33 | 359.67 | 1419.52 | 12.26 | 0.00 | 329.50 |
September | 285.33 | 0.74 | 0.73 | 01-SEP-06:30 | 2509.65 | 13.53 | 45.67 | 305.33 | 1384.37 | 12.71 | 5.50 | 264.83 |
October | 305.50 | 0.74 | 0.73 | 01-OCT-14:39 | 2659.60 | 17.34 | 83.50 | 291.67 | 1169.23 | 16.99 | 53.17 | 258.00 |
November | 240.83 | 0.74 | 0.73 | 01-NOV-07:19 | 1328.37 | 16.32 | 64.83 | 232.67 | 717.78 | 16.06 | 43.50 | 173.33 |
December | 211.17 | 0.76 | 0.73 | 01-DEC-08:30 | 1098.21 | 14.34 | 45.67 | 196.50 | 693.91 | 16.11 | 43.67 | 129.67 |
Annual Sum or Average | 3472.67 | 0.74 | 2368.03 | 13.31 | 495.33 | 3585.33 | 1205.92 | 14.23 | 311.33 | 2981.83 | ||
Minimum of Months | 199.50 | 0.74 | 0.73 | 1098.21 | 9.93 | 0.00 | 196.50 | 693.91 | 11.87 | 0.00 | 129.67 | |
Maximum of Months | 389.17 | 0.76 | 0.73 | 3245.37 | 17.34 | 83.50 | 382.33 | 1487.61 | 16.99 | 53.17 | 334.17 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAWATERHEATC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.303805E+10 | 496656.60 | 04-JAN-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281799E+10 | 446258.95 | 04-FEB-22:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.679681E+09 | 285738.39 | 11-MAR-19:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88367856.38 | 82911.92 | 17-APR-21:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110574E+09 | 425941.86 | 02-MAY-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.217679E+09 | 435280.21 | 28-OCT-17:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.510187E+09 | 287810.11 | 25-NOV-13:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.269921E+09 | 87436.66 | 23-DEC-17:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.773246E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.303805E+10 | 496656.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152223E+11 | 488828.98 | 02-JAN-06:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121145E+10 | 488232.43 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164337E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152223E+11 | 488828.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.678798E+10 | 79397.11 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.495379E+10 | 79287.06 | 21-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.944661E+09 | 79533.39 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.151968E+09 | 79073.31 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187403E+10 | 79480.57 | 27-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.302950E+10 | 79366.57 | 26-DEC-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177419E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.678798E+10 | 79533.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.206323E+09 | 11336.61 | 14-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162765E+09 | 11331.46 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.369088E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.206323E+09 | 11336.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.232111E+09 | 9952.95 | 02-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.165743E+09 | 9954.05 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3825514.06 | 809.16 | 17-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3146448.69 | 2000.93 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9377837.82 | 1636.73 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.414204E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.232111E+09 | 9954.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.422483E+09 | 13546.63 | 31-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.281405E+09 | 13643.84 | 13-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10405999.14 | 13203.28 | 13-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 11265585.15 | 11783.91 | 22-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12069947.79 | 10428.99 | 07-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.737630E+09 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.422483E+09 | 13643.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 52007464.41 | 8344.61 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 19875124.63 | 8339.88 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 71882589.04 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 52007464.41 | 8344.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.438493E+11 | 117913.08 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.328923E+11 | 116411.26 | 28-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.843152E+10 | 116267.59 | 17-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.120068E+10 | 116977.81 | 21-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 88037743.87 | 42203.69 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.851130E+10 | 117214.75 | 06-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.202626E+11 | 119484.86 | 21-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115236E+12 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.438493E+11 | 119484.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.300496E+11 | 142363.63 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196846E+11 | 142388.85 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.508009E+10 | 140880.43 | 23-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.121168E+10 | 137789.97 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74681402.32 | 18174.46 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.578730E+10 | 141242.15 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.146194E+11 | 140504.60 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.765074E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.300496E+11 | 142388.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270170E+11 | 132665.07 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.162893E+11 | 131167.93 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.446277E+10 | 130582.68 | 20-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.915818E+09 | 131695.81 | 21-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380605E+10 | 131408.61 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108702E+11 | 131203.29 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.633611E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270170E+11 | 132665.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.248385E+11 | 140691.19 | 02-JAN-04:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171203E+11 | 140714.84 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344391E+10 | 138442.85 | 22-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.551858E+09 | 136147.50 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 28690931.85 | 4299.78 | 28-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.477967E+10 | 139575.08 | 24-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.108361E+11 | 138844.69 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.615990E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.248385E+11 | 140714.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.805667E+10 | 13070.71 | 24-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.705629E+10 | 12949.09 | 16-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.273858E+10 | 12981.98 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.815553E+09 | 13077.71 | 11-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 28112049.92 | 12877.61 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.255487E+09 | 13101.39 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.285323E+10 | 13007.39 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.558119E+10 | 12965.58 | 26-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.273851E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.805667E+10 | 13101.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.527847E+10 | 15185.11 | 24-JAN-05:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.423340E+10 | 15041.59 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157164E+10 | 15071.30 | 06-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.557763E+09 | 15043.81 | 22-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17132596.24 | 15031.72 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143389E+09 | 15277.10 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.180201E+10 | 15131.25 | 27-NOV-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.359499E+10 | 15083.91 | 30-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171988E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.527847E+10 | 15277.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.561267E+10 | 14901.34 | 24-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.430546E+10 | 14761.59 | 28-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180633E+10 | 14799.81 | 06-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.687704E+09 | 14745.47 | 18-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 27626666.11 | 14697.14 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.101209E+09 | 14680.49 | 18-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167383E+10 | 14854.29 | 27-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.348550E+10 | 14806.62 | 26-DEC-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177003E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.561267E+10 | 14901.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.457796E+10 | 16257.99 | 04-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.366018E+10 | 16209.32 | 14-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.124780E+10 | 16174.25 | 17-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.398736E+09 | 15982.65 | 03-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12695206.40 | 3020.54 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111891E+09 | 15832.17 | 27-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150308E+10 | 16242.67 | 22-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.287563E+10 | 16183.74 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.143880E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.457796E+10 | 16257.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_HEATC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.404766E+09 | 229811.99 | 14-JAN-05:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.403778E+09 | 229885.94 | 06-FEB-04:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312754E+09 | 225162.51 | 14-MAR-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.454583E+09 | 222597.28 | 15-APR-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.111498E+10 | 220995.00 | 04-MAY-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.123037E+10 | 220643.00 | 05-JUN-02:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149619E+10 | 218839.73 | 11-JUL-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.163148E+10 | 220644.31 | 26-AUG-03:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.169259E+10 | 220649.76 | 25-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196304E+10 | 222780.11 | 09-OCT-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198948E+10 | 227763.00 | 24-NOV-03:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458614E+09 | 225471.10 | 12-DEC-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.131526E+11 | |||||||
Minimum of Months | 0.312754E+09 | 218839.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.198948E+10 | 229885.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.403580E+09 | 40970.92 | 02-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371658E+09 | 35117.97 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.291483E+09 | 25300.02 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 39253304.02 | 10420.35 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8184454.65 | 5149.21 | 30-MAY-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 29154048.32 | 9208.01 | 01-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 14376154.93 | 3138.96 | 11-JUL-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 59450589.19 | 9063.73 | 30-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15598408.76 | 6559.47 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 12444318.24 | 7097.31 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.147354E+09 | 24450.32 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345405E+09 | 25408.20 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173794E+10 | |||||||
Minimum of Months | 8184454.65 | 3138.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.403580E+09 | 40970.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117205E+11 | 632365.60 | 31-JAN-09:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121154E+11 | 401551.17 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.998161E+10 | 276922.51 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.123590E+10 | 130684.15 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.107156E+09 | 29975.67 | 30-MAY-11:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.508647E+09 | 95300.34 | 01-JUN-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 65299572.50 | 35423.56 | 11-JUL-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.771618E+09 | 72825.98 | 30-AUG-14:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 15904120.26 | 51533.12 | 01-SEP-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.224329E+09 | 97387.32 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.590435E+10 | 284495.50 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.122294E+11 | 279278.27 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548801E+11 | |||||||
Minimum of Months | 15904120.26 | 29975.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.122294E+11 | 632365.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_HEATC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138382E+10 | 44641.64 | 31-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.882535E+09 | 45991.05 | 13-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.288559E+09 | 32684.44 | 23-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.101814E+09 | 17237.89 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4986731.48 | 4302.85 | 30-MAY-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 30252340.40 | 7383.09 | 01-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8573419.79 | 3484.77 | 11-JUL-16:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 30166031.15 | 13071.43 | 30-AUG-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 11653501.93 | 4168.73 | 01-SEP-13:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 39526489.75 | 13943.50 | 28-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210898E+09 | 33742.96 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.379862E+09 | 33102.86 | 22-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337265E+10 | |||||||
Minimum of Months | 4986731.48 | 3484.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.138382E+10 | 45991.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP HEATING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: DATACENTER_EXTRAELECHEATC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP DX SUPP HEATING COIL AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9991177.59 | 4485778.53 | 36502.28 | 24-JAN-06:03 | 16007.70 | 0.00 |
February | 0.00 | 0.00 | 65643.28 | 65643.28 | 73.64 | 07-FEB-16:10 | 73.64 | 0.00 |
March | 0.00 | 0.00 | 0.660943E+09 | 0.660640E+09 | 43095.73 | 27-MAR-16:00 | 43095.73 | 0.01 |
April | 0.00 | 0.00 | 0.562517E+10 | 0.559146E+10 | 64989.48 | 07-APR-13:50 | 64989.48 | 0.05 |
May | 0.00 | 0.00 | 0.170213E+11 | 0.160519E+11 | 104942.36 | 29-MAY-03:41 | 104942.36 | 0.13 |
June | 0.00 | 0.00 | 0.681252E+11 | 0.563868E+11 | 169605.29 | 19-JUN-00:30 | 98484.85 | 0.52 |
July | 0.00 | 0.00 | 0.973037E+11 | 0.762391E+11 | 174925.84 | 09-JUL-22:12 | 89197.49 | 0.56 |
August | 0.00 | 0.00 | 0.963353E+11 | 0.799270E+11 | 158740.93 | 13-AUG-20:31 | 70835.62 | 0.57 |
September | 0.00 | 0.00 | 0.519030E+11 | 0.449701E+11 | 148693.55 | 01-SEP-03:01 | 88291.82 | 0.43 |
October | 0.00 | 0.00 | 0.204814E+11 | 0.168654E+11 | 109397.72 | 06-OCT-05:03 | 46911.86 | 0.22 |
November | 0.00 | 0.00 | 0.271865E+09 | 0.230239E+09 | 64451.20 | 10-NOV-06:02 | 25691.90 | 0.00 |
December | 0.00 | 0.00 | 3652628.89 | 3536766.88 | 8656.79 | 25-DEC-14:31 | 8656.79 | 0.00 |
Annual Sum or Average | 0.357742E+12 | 0.296931E+12 | 0.21 | |||||
Minimum of Months | 0.00 | 0.00 | 65643.28 | 65643.28 | 73.64 | 73.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.973037E+11 | 0.799270E+11 | 174925.84 | 104942.36 | 0.57 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11945598.70 | 11945598.70 | 5733.61 | 19-JAN-08:10 | 5733.61 | 0.00 |
February | 0.00 | 0.00 | 15558758.05 | 15558758.05 | 2561.77 | 27-FEB-13:10 | 2561.77 | 0.00 |
March | 0.00 | 0.00 | 0.193807E+10 | 0.164238E+10 | 83926.22 | 27-MAR-13:00 | 54958.73 | 0.02 |
April | 0.00 | 0.00 | 0.139456E+11 | 0.137788E+11 | 100163.14 | 07-APR-13:30 | 100163.14 | 0.11 |
May | 0.00 | 0.00 | 0.429207E+11 | 0.361797E+11 | 143397.41 | 30-MAY-14:10 | 138214.51 | 0.26 |
June | 0.00 | 0.00 | 0.124127E+12 | 0.960090E+11 | 170016.15 | 26-JUN-05:02 | 102911.78 | 0.64 |
July | 0.00 | 0.00 | 0.162166E+12 | 0.128627E+12 | 188843.08 | 21-JUL-05:02 | 152082.01 | 0.79 |
August | 0.00 | 0.00 | 0.166602E+12 | 0.142190E+12 | 179933.43 | 01-AUG-05:02 | 150446.86 | 0.82 |
September | 0.00 | 0.00 | 0.853424E+11 | 0.695352E+11 | 194060.38 | 14-SEP-03:01 | 142625.48 | 0.51 |
October | 0.00 | 0.00 | 0.462042E+11 | 0.332454E+11 | 162945.65 | 06-OCT-05:01 | 131504.31 | 0.30 |
November | 0.00 | 0.00 | 0.210546E+10 | 0.182456E+10 | 44182.05 | 10-NOV-10:00 | 18324.10 | 0.02 |
December | 0.00 | 0.00 | 7917315.97 | 7917315.97 | 1616.08 | 30-DEC-08:70 | 1616.08 | 0.00 |
Annual Sum or Average | 0.645387E+12 | 0.523067E+12 | 0.29 | |||||
Minimum of Months | 0.00 | 0.00 | 7917315.97 | 7917315.97 | 1616.08 | 1616.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.166602E+12 | 0.142190E+12 | 194060.38 | 152082.01 | 0.82 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 15165015.88 | 15165015.88 | 4546.22 | 17-JAN-12:00 | 4546.22 | 0.00 |
February | 0.00 | 0.00 | 78098848.18 | 78098848.18 | 81215.27 | 09-FEB-10:55 | 81215.27 | 0.00 |
March | 0.00 | 0.00 | 0.128099E+11 | 0.112068E+11 | 506923.16 | 27-MAR-13:00 | 339129.88 | 0.02 |
April | 0.00 | 0.00 | 0.932570E+11 | 0.929195E+11 | 828433.33 | 07-APR-13:30 | 828433.33 | 0.08 |
May | 0.00 | 0.00 | 0.361363E+12 | 0.303000E+12 | 1149044.34 | 30-MAY-14:00 | 1149044.34 | 0.25 |
June | 0.00 | 0.00 | 0.103239E+13 | 0.762962E+12 | 1930605.95 | 27-JUN-05:02 | 1340807.35 | 0.56 |
July | 0.00 | 0.00 | 0.128928E+13 | 0.947341E+12 | 2433318.92 | 22-JUL-03:01 | 1349214.30 | 0.62 |
August | 0.00 | 0.00 | 0.126669E+13 | 0.102451E+13 | 1934611.53 | 04-AUG-03:01 | 1355030.28 | 0.62 |
September | 0.00 | 0.00 | 0.738767E+12 | 0.587418E+12 | 2049511.97 | 14-SEP-05:01 | 1327102.65 | 0.48 |
October | 0.00 | 0.00 | 0.367620E+12 | 0.257420E+12 | 1403321.62 | 06-OCT-05:01 | 603188.50 | 0.29 |
November | 0.00 | 0.00 | 0.154418E+11 | 0.134901E+11 | 276439.69 | 10-NOV-10:00 | 115335.82 | 0.02 |
December | 0.00 | 0.00 | 0.260653E+09 | 0.260653E+09 | 22915.69 | 15-DEC-14:30 | 22915.69 | 0.00 |
Annual Sum or Average | 0.517797E+13 | 0.400062E+13 | 0.25 | |||||
Minimum of Months | 0.00 | 0.00 | 15165015.88 | 15165015.88 | 4546.22 | 4546.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.128928E+13 | 0.102451E+13 | 2433318.92 | 1355030.28 | 0.62 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT_COOLC
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 12566054.31 | 12566054.31 | 2377.12 | 15-JAN-10:10 | 2377.12 | 0.00 |
February | 0.00 | 0.00 | 12883271.12 | 12883271.12 | 698.04 | 17-FEB-10:50 | 698.04 | 0.00 |
March | 0.00 | 0.00 | 0.119854E+10 | 0.105803E+10 | 45176.94 | 27-MAR-13:00 | 30322.51 | 0.02 |
April | 0.00 | 0.00 | 0.963708E+10 | 0.960656E+10 | 91703.53 | 07-APR-15:30 | 91703.53 | 0.08 |
May | 0.00 | 0.00 | 0.381543E+11 | 0.322685E+11 | 139655.48 | 30-MAY-13:10 | 139655.48 | 0.25 |
June | 0.00 | 0.00 | 0.112564E+12 | 0.844476E+11 | 204435.51 | 27-JUN-05:02 | 133748.74 | 0.56 |
July | 0.00 | 0.00 | 0.144799E+12 | 0.107966E+12 | 266333.21 | 22-JUL-03:01 | 139746.25 | 0.63 |
August | 0.00 | 0.00 | 0.140127E+12 | 0.114339E+12 | 207769.07 | 04-AUG-03:01 | 138906.04 | 0.61 |
September | 0.00 | 0.00 | 0.766327E+11 | 0.608874E+11 | 215930.87 | 14-SEP-05:01 | 134659.24 | 0.47 |
October | 0.00 | 0.00 | 0.359163E+11 | 0.250364E+11 | 130107.74 | 06-OCT-05:03 | 55799.24 | 0.28 |
November | 0.00 | 0.00 | 0.137721E+10 | 0.120567E+10 | 23828.86 | 03-NOV-14:00 | 23828.86 | 0.02 |
December | 0.00 | 0.00 | 16455256.51 | 16455256.51 | 511.53 | 15-DEC-10:30 | 511.53 | 0.00 |
Annual Sum or Average | 0.560447E+12 | 0.436858E+12 | 0.25 | |||||
Minimum of Months | 0.00 | 0.00 | 12566054.31 | 12566054.31 | 511.53 | 511.53 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.144799E+12 | 0.114339E+12 | 266333.21 | 139746.25 | 0.63 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.308694E+12 | 0.308651E+12 | 437072.77 | 28-JAN-23:00 | 437072.77 | 0.00 |
February | 0.00 | 0.00 | 0.491139E+12 | 0.490999E+12 | 444821.84 | 20-FEB-00:30 | 444821.84 | 0.00 |
March | 0.00 | 0.00 | 0.779411E+12 | 0.779324E+12 | 433784.90 | 11-MAR-19:20 | 433784.90 | 0.00 |
April | 0.00 | 0.00 | 0.986260E+12 | 0.986244E+12 | 424575.28 | 17-APR-21:25 | 424575.28 | 0.00 |
May | 0.00 | 0.00 | 0.316065E+12 | 0.314714E+12 | 422919.96 | 16-MAY-03:06 | 422919.96 | 0.00 |
June | 0.00 | 0.00 | 0.540252E+12 | 0.534717E+12 | 218655.93 | 15-JUN-12:50 | 208387.84 | 0.00 |
July | 0.00 | 0.00 | 0.798901E+12 | 0.790257E+12 | 308308.42 | 20-JUL-15:00 | 296904.04 | 0.00 |
August | 0.00 | 0.00 | 0.103167E+13 | 0.102598E+13 | 396747.48 | 18-AUG-19:00 | 387903.35 | 0.00 |
September | 0.00 | 0.00 | 0.312940E+12 | 0.309529E+12 | 135983.44 | 01-SEP-00:10 | 134618.73 | 0.00 |
October | 0.00 | 0.00 | 0.554924E+12 | 0.552607E+12 | 437558.66 | 28-OCT-17:30 | 437558.66 | 0.00 |
November | 0.00 | 0.00 | 0.759254E+12 | 0.759156E+12 | 431369.76 | 25-NOV-13:04 | 431369.76 | 0.00 |
December | 0.00 | 0.00 | 0.101762E+13 | 0.101762E+13 | 421116.32 | 15-DEC-22:33 | 421116.32 | 0.00 |
Annual Sum or Average | 0.789714E+13 | 0.786980E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.308694E+12 | 0.308651E+12 | 135983.44 | 134618.73 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.103167E+13 | 0.102598E+13 | 444821.84 | 444821.84 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.401996E+10 | 0.401996E+10 | 2268.54 | 20-JAN-16:30 | 2268.54 | 0.00 |
February | 0.00 | 0.00 | 0.848562E+10 | 0.848562E+10 | 4276.53 | 14-FEB-17:00 | 4276.53 | 0.00 |
March | 0.00 | 0.00 | 0.150462E+11 | 0.150462E+11 | 6256.50 | 26-MAR-17:30 | 6256.50 | 0.00 |
April | 0.00 | 0.00 | 0.193196E+11 | 0.193196E+11 | 7724.78 | 23-APR-18:03 | 7724.78 | 0.00 |
May | 0.00 | 0.00 | 0.547023E+10 | 0.547023E+10 | 2570.48 | 01-MAY-00:05 | 2570.48 | 0.00 |
June | 0.00 | 0.00 | 0.102315E+11 | 0.102315E+11 | 4406.62 | 18-JUN-18:10 | 4406.62 | 0.00 |
July | 0.00 | 0.00 | 0.154729E+11 | 0.154729E+11 | 6270.16 | 04-JUL-18:05 | 6270.16 | 0.00 |
August | 0.00 | 0.00 | 0.186047E+11 | 0.186047E+11 | 7507.36 | 08-AUG-04:57 | 7507.36 | 0.00 |
September | 0.00 | 0.00 | 0.542169E+10 | 0.542169E+10 | 5298.93 | 01-SEP-00:03 | 5298.93 | 0.00 |
October | 0.00 | 0.00 | 0.104596E+11 | 0.104596E+11 | 4467.24 | 15-OCT-16:33 | 4467.24 | 0.00 |
November | 0.00 | 0.00 | 0.145540E+11 | 0.145540E+11 | 6048.12 | 06-NOV-16:10 | 6048.12 | 0.00 |
December | 0.00 | 0.00 | 0.198116E+11 | 0.198116E+11 | 7641.69 | 21-DEC-16:20 | 7641.69 | 0.00 |
Annual Sum or Average | 0.146898E+12 | 0.146898E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.401996E+10 | 0.401996E+10 | 2268.54 | 2268.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.198116E+11 | 0.198116E+11 | 7724.78 | 7724.78 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.158508E+11 | 0.158508E+11 | 19676.26 | 20-JAN-16:40 | 19676.26 | 0.00 |
February | 0.00 | 0.00 | 0.616872E+11 | 0.616872E+11 | 38738.45 | 22-FEB-17:00 | 38738.45 | 0.00 |
March | 0.00 | 0.00 | 0.128616E+12 | 0.128616E+12 | 58471.48 | 29-MAR-17:20 | 58471.48 | 0.00 |
April | 0.00 | 0.00 | 0.175946E+12 | 0.175946E+12 | 73305.39 | 12-APR-18:00 | 73305.39 | 0.00 |
May | 0.00 | 0.00 | 0.466988E+11 | 0.466988E+11 | 22993.36 | 30-MAY-18:00 | 22993.36 | 0.00 |
June | 0.00 | 0.00 | 0.953321E+11 | 0.953321E+11 | 42055.87 | 18-JUN-17:52 | 42055.87 | 0.00 |
July | 0.00 | 0.00 | 0.146928E+12 | 0.146928E+12 | 59690.59 | 12-JUL-18:20 | 59690.59 | 0.00 |
August | 0.00 | 0.00 | 0.177318E+12 | 0.177318E+12 | 71528.11 | 08-AUG-04:57 | 71528.11 | 0.00 |
September | 0.00 | 0.00 | 0.469698E+11 | 0.469698E+11 | 50072.99 | 01-SEP-00:03 | 50072.99 | 0.00 |
October | 0.00 | 0.00 | 0.918918E+11 | 0.918918E+11 | 41211.06 | 04-OCT-16:30 | 41211.06 | 0.00 |
November | 0.00 | 0.00 | 0.122224E+12 | 0.122224E+12 | 56751.57 | 03-NOV-16:00 | 56751.57 | 0.00 |
December | 0.00 | 0.00 | 0.167197E+12 | 0.167197E+12 | 72442.57 | 21-DEC-16:20 | 72442.57 | 0.00 |
Annual Sum or Average | 0.127666E+13 | 0.127666E+13 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.158508E+11 | 0.158508E+11 | 19676.26 | 19676.26 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.177318E+12 | 0.177318E+12 | 73305.39 | 73305.39 | 0.00 |
Report: CoilReportMonthly
For: HEAT PUMP COOLING MODE AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.740167E+09 | 0.740167E+09 | 1885.44 | 20-JAN-16:40 | 1885.44 | 0.00 |
February | 0.00 | 0.00 | 0.453780E+10 | 0.453780E+10 | 3767.79 | 02-FEB-17:00 | 3767.79 | 0.00 |
March | 0.00 | 0.00 | 0.115896E+11 | 0.115896E+11 | 5852.85 | 29-MAR-17:10 | 5852.85 | 0.00 |
April | 0.00 | 0.00 | 0.168333E+11 | 0.168333E+11 | 7437.16 | 12-APR-17:50 | 7437.16 | 0.00 |
May | 0.00 | 0.00 | 0.438288E+10 | 0.438288E+10 | 2400.20 | 30-MAY-18:00 | 2400.20 | 0.00 |
June | 0.00 | 0.00 | 0.955510E+10 | 0.955510E+10 | 4405.87 | 18-JUN-17:52 | 4405.87 | 0.00 |
July | 0.00 | 0.00 | 0.148225E+11 | 0.148225E+11 | 6130.67 | 04-JUL-17:56 | 6130.67 | 0.00 |
August | 0.00 | 0.00 | 0.180063E+11 | 0.180063E+11 | 7200.48 | 20-AUG-02:33 | 7200.48 | 0.00 |
September | 0.00 | 0.00 | 0.449459E+10 | 0.449459E+10 | 4487.51 | 01-SEP-00:03 | 4487.51 | 0.00 |
October | 0.00 | 0.00 | 0.842808E+10 | 0.842808E+10 | 4181.53 | 04-OCT-16:30 | 4181.53 | 0.00 |
November | 0.00 | 0.00 | 0.107137E+11 | 0.107137E+11 | 5660.36 | 03-NOV-16:00 | 5660.36 | 0.00 |
December | 0.00 | 0.00 | 0.148137E+11 | 0.148137E+11 | 7102.60 | 08-DEC-16:10 | 7102.60 | 0.00 |
Annual Sum or Average | 0.118918E+12 | 0.118918E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.740167E+09 | 0.740167E+09 | 1885.44 | 1885.44 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.180063E+11 | 0.180063E+11 | 7437.16 | 7437.16 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3902.95 | 34148.19 | 16-JAN-11:00 | 14033.90 | 57420.49 | 25-JAN-12:10 |
February | 3595.26 | 33934.50 | 20-FEB-11:00 | 14327.08 | 57338.52 | 24-FEB-12:30 |
March | 2782.74 | 33584.83 | 27-MAR-05:08 | 15101.62 | 60436.40 | 14-MAR-11:35 |
April | 3877.62 | 33961.17 | 17-APR-05:08 | 13255.16 | 51246.77 | 03-APR-11:40 |
May | 4696.00 | 37944.34 | 29-MAY-09:26 | 12775.26 | 48313.63 | 30-MAY-11:40 |
June | 4527.33 | 37760.78 | 18-JUN-23:00 | 12167.02 | 44852.15 | 01-JUN-11:20 |
July | 6434.02 | 38262.07 | 30-JUL-18:50 | 10321.34 | 41945.76 | 03-JUL-11:40 |
August | 4854.57 | 38270.08 | 13-AUG-19:45 | 11460.87 | 40985.95 | 31-AUG-11:50 |
September | 5737.83 | 38231.42 | 03-SEP-22:40 | 10920.89 | 42871.39 | 29-SEP-12:00 |
October | 5783.78 | 38041.82 | 09-OCT-08:53 | 11593.95 | 46107.71 | 31-OCT-11:40 |
November | 4971.64 | 37711.81 | 12-NOV-11:00 | 12747.92 | 52386.89 | 24-NOV-12:10 |
December | 4256.75 | 35207.36 | 25-DEC-11:00 | 13085.75 | 54262.68 | 11-DEC-12:50 |
Annual Sum or Average | 4625.03 | 12639.56 | ||||
Minimum of Months | 2782.74 | 33584.83 | 10321.34 | 40985.95 | ||
Maximum of Months | 6434.02 | 38270.08 | 15101.62 | 60436.40 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2.13 | 1518.27 | 19-JAN-12:50 | 70464.20 | 1535039.18 | 02-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 53016.39 | 1238875.22 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 15423.53 | 794330.49 | 13-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 3163.78 | 827400.22 | 03-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 538.31 | 257736.73 | 31-MAY-03:47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 699.93 | 331804.50 | 23-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 594.15 | 257109.87 | 12-JUL-03:47 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 872.75 | 362584.28 | 26-AUG-03:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 724.17 | 317907.17 | 02-SEP-03:47 |
October | 0.37 | 1076.90 | 18-OCT-21:00 | 1277.21 | 276947.04 | 07-OCT-03:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15849.16 | 781624.87 | 25-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 33007.16 | 1125406.94 | 30-DEC-05:01 |
Annual Sum or Average | 0.21 | 16123.47 | ||||
Minimum of Months | 0.00 | 0.00 | 538.31 | 257109.87 | ||
Maximum of Months | 2.13 | 1518.27 | 70464.20 | 1535039.18 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 977.53 | 17137.69 | 31-JAN-10:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1749.80 | 27270.27 | 09-FEB-10:55 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13832.45 | 1290889.74 | 27-MAR-13:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 92468.26 | 1453845.57 | 07-APR-11:40 | 0.36 | 2341.83 | 17-APR-00:50 |
May | 314148.19 | 1585530.51 | 30-MAY-13:20 | 10.26 | 93109.46 | 29-MAY-03:41 |
June | 737850.20 | 2497932.88 | 27-JUN-05:03 | 4.24 | 39739.09 | 16-JUN-00:12 |
July | 843419.16 | 2469120.53 | 22-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 847406.55 | 2214111.64 | 17-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 570192.32 | 2642401.76 | 14-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 285209.02 | 1899248.44 | 06-OCT-05:03 | 1.04 | 41930.17 | 01-OCT-20:01 |
November | 16827.66 | 693226.28 | 10-NOV-10:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1235.29 | 116058.49 | 25-DEC-15:23 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312499.24 | 1.34 | ||||
Minimum of Months | 977.53 | 17137.69 | 0.00 | 0.00 | ||
Maximum of Months | 847406.55 | 2642401.76 | 10.26 | 93109.46 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.07 | 16727.53 | 24-JAN-06:03 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 17.08 | 23233.41 | 09-FEB-10:55 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8297.63 | 908701.79 | 27-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 61885.42 | 1327775.72 | 07-APR-15:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 222145.09 | 1613989.63 | 31-MAY-16:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 642594.96 | 3442782.93 | 27-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 733193.31 | 3486804.32 | 22-JUL-05:01 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 722760.33 | 2914769.05 | 17-AUG-05:01 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 464271.30 | 3719511.51 | 14-SEP-05:01 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 237130.85 | 2622927.68 | 06-OCT-05:01 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10077.37 | 529309.17 | 04-NOV-12:30 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 167.68 | 99831.29 | 25-DEC-12:31 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 260273.94 | 0.00 | ||||
Minimum of Months | 3.07 | 16727.53 | 0.00 | 0.00 | ||
Maximum of Months | 733193.31 | 3719511.51 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 153354.29 | 543813.88 | 28-JAN-23:00 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 290342.11 | 581588.36 | 20-FEB-00:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 436471.13 | 844647.85 | 27-MAR-16:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 628956.81 | 1289826.95 | 07-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237492.43 | 850555.66 | 30-MAY-13:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 623749.79 | 1440567.27 | 19-JUN-12:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1012275.96 | 1514811.11 | 07-JUL-12:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1196401.09 | 1681009.76 | 24-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 360613.38 | 916379.90 | 01-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 368064.50 | 801186.71 | 04-OCT-13:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 437569.38 | 616252.03 | 03-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 565941.31 | 614742.64 | 05-DEC-01:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 528017.21 | 0.00 | ||||
Minimum of Months | 153354.29 | 543813.88 | 0.00 | 0.00 | ||
Maximum of Months | 1196401.09 | 1681009.76 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 42.25 | 20612.07 | 19-JAN-11:00 | 1857.52 | 135363.96 | 10-JAN-10:00 |
February | 48.61 | 20599.87 | 23-FEB-14:50 | 2878.95 | 135374.01 | 09-FEB-12:30 |
March | 8638.06 | 900596.67 | 27-MAR-13:10 | 2422.84 | 135751.25 | 17-MAR-09:00 |
April | 65877.60 | 1209484.05 | 07-APR-11:40 | 1604.81 | 101774.63 | 14-APR-08:70 |
May | 264931.20 | 3682115.59 | 31-MAY-15:10 | 536.08 | 71229.16 | 13-MAY-04:30 |
June | 1129432.14 | 6001957.88 | 19-JUN-08:70 | 118.90 | 75621.53 | 02-JUN-06:50 |
July | 1864922.42 | 6475160.13 | 20-JUL-15:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1647711.81 | 6810416.08 | 02-AUG-15:00 | 84.96 | 30271.88 | 26-AUG-02:30 |
September | 745238.05 | 5358407.33 | 07-SEP-14:10 | 229.04 | 59182.79 | 19-SEP-03:30 |
October | 280586.63 | 3737075.98 | 05-OCT-14:50 | 523.05 | 83477.49 | 18-OCT-15:20 |
November | 11821.79 | 497101.66 | 03-NOV-14:00 | 1931.45 | 130291.97 | 21-NOV-09:40 |
December | 50.38 | 22978.26 | 30-DEC-12:30 | 1892.17 | 128618.67 | 15-DEC-13:40 |
Annual Sum or Average | 505878.94 | 1161.51 | ||||
Minimum of Months | 42.25 | 20599.87 | 0.00 | 0.00 | ||
Maximum of Months | 1864922.42 | 6810416.08 | 2878.95 | 135751.25 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.130165E+11 | 0.76 | 8909.54 | 02-JAN-04:01 | 1.39 |
February | 0.120666E+11 | 0.78 | 8909.54 | 01-FEB-05:01 | 1.40 |
March | 0.143123E+11 | 0.83 | 8909.54 | 01-MAR-05:01 | 1.39 |
April | 0.132970E+11 | 0.80 | 8909.54 | 01-APR-04:01 | 1.39 |
May | 0.141084E+11 | 0.82 | 8909.54 | 01-MAY-01:31 | 1.39 |
June | 0.142522E+11 | 0.85 | 8909.54 | 01-JUN-03:01 | 1.38 |
July | 0.139149E+11 | 0.80 | 8909.54 | 01-JUL-03:01 | 1.38 |
August | 0.151489E+11 | 0.87 | 8909.54 | 01-AUG-03:01 | 1.38 |
September | 0.144749E+11 | 0.86 | 8909.54 | 01-SEP-03:01 | 1.38 |
October | 0.147533E+11 | 0.85 | 8909.54 | 01-OCT-20:01 | 1.38 |
November | 0.140352E+11 | 0.84 | 8909.54 | 01-NOV-03:01 | 1.39 |
December | 0.137728E+11 | 0.80 | 8909.54 | 01-DEC-04:01 | 1.39 |
Annual Sum or Average | 0.167153E+12 | 0.82 | |||
Minimum of Months | 0.120666E+11 | 0.76 | 8909.54 | 1.38 | |
Maximum of Months | 0.151489E+11 | 0.87 | 8909.54 | 1.40 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.365800E+10 | 0.31 | 11228.62 | 03-JAN-06:01 | 1.29 |
February | 0.384795E+10 | 0.34 | 11228.62 | 09-FEB-06:01 | 1.30 |
March | 0.620343E+10 | 0.42 | 12281.32 | 02-MAR-05:01 | 1.36 |
April | 0.664378E+10 | 0.46 | 13648.57 | 10-APR-05:01 | 1.44 |
May | 0.542968E+10 | 0.40 | 20316.08 | 31-MAY-05:01 | 1.86 |
June | 0.612899E+10 | 0.46 | 20316.08 | 20-JUN-05:02 | 1.86 |
July | 0.699927E+10 | 0.52 | 20316.08 | 03-JUL-05:01 | 1.86 |
August | 0.853269E+10 | 0.59 | 20316.08 | 15-AUG-05:01 | 1.86 |
September | 0.540610E+10 | 0.41 | 20316.08 | 02-SEP-03:01 | 1.86 |
October | 0.634214E+10 | 0.42 | 19842.03 | 23-OCT-05:01 | 1.83 |
November | 0.577410E+10 | 0.40 | 12281.32 | 02-NOV-05:01 | 1.36 |
December | 0.566719E+10 | 0.39 | 12043.63 | 21-DEC-06:01 | 1.35 |
Annual Sum or Average | 0.706333E+11 | 0.43 | |||
Minimum of Months | 0.365800E+10 | 0.31 | 11228.62 | 1.29 | |
Maximum of Months | 0.853269E+10 | 0.59 | 20316.08 | 1.86 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.296633E+11 | 0.32 | 82741.78 | 31-JAN-09:50 | 1.13 |
February | 0.272126E+11 | 0.32 | 88798.28 | 03-FEB-10:20 | 1.17 |
March | 0.339076E+11 | 0.33 | 116831.86 | 10-MAR-06:02 | 1.38 |
April | 0.348179E+11 | 0.33 | 121466.42 | 21-APR-05:01 | 1.41 |
May | 0.412819E+11 | 0.36 | 188608.21 | 30-MAY-05:03 | 1.86 |
June | 0.470274E+11 | 0.39 | 188608.21 | 13-JUN-05:01 | 1.86 |
July | 0.505771E+11 | 0.40 | 188608.21 | 01-JUL-05:01 | 1.86 |
August | 0.589787E+11 | 0.44 | 188608.21 | 02-AUG-03:01 | 1.86 |
September | 0.429210E+11 | 0.37 | 188608.21 | 01-SEP-05:03 | 1.86 |
October | 0.413717E+11 | 0.35 | 122059.29 | 06-OCT-05:01 | 1.41 |
November | 0.309059E+11 | 0.31 | 121466.42 | 06-NOV-06:01 | 1.42 |
December | 0.288116E+11 | 0.30 | 121466.42 | 21-DEC-06:01 | 1.42 |
Annual Sum or Average | 0.467477E+12 | 0.35 | |||
Minimum of Months | 0.272126E+11 | 0.30 | 82741.78 | 1.13 | |
Maximum of Months | 0.589787E+11 | 0.44 | 188608.21 | 1.86 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.351727E+10 | 0.38 | 4270.25 | 02-JAN-04:01 | 0.76 |
February | 0.307099E+10 | 0.37 | 4270.25 | 01-FEB-06:01 | 0.76 |
March | 0.312791E+10 | 0.33 | 5170.80 | 29-MAR-15:30 | 0.84 |
April | 0.317742E+10 | 0.31 | 8408.49 | 07-APR-05:02 | 1.11 |
May | 0.407618E+10 | 0.35 | 19358.87 | 30-MAY-05:03 | 1.86 |
June | 0.525793E+10 | 0.41 | 19358.87 | 20-JUN-03:01 | 1.86 |
July | 0.594102E+10 | 0.43 | 19358.87 | 01-JUL-05:01 | 1.86 |
August | 0.678573E+10 | 0.46 | 19358.87 | 01-AUG-05:01 | 1.86 |
September | 0.433186E+10 | 0.36 | 19358.87 | 02-SEP-05:01 | 1.86 |
October | 0.355714E+10 | 0.32 | 9019.20 | 17-OCT-05:01 | 1.16 |
November | 0.282032E+10 | 0.31 | 4270.25 | 06-NOV-06:01 | 0.76 |
December | 0.299946E+10 | 0.33 | 4270.25 | 02-DEC-06:01 | 0.76 |
Annual Sum or Average | 0.486632E+11 | 0.36 | |||
Minimum of Months | 0.282032E+10 | 0.31 | 4270.25 | 0.76 | |
Maximum of Months | 0.678573E+10 | 0.46 | 19358.87 | 1.86 |
Report: FanReportMonthly
For: DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.940767E+11 | 1.35 | 35124.23 | 01-JAN-00:01 | 1.35 |
February | 0.849725E+11 | 1.35 | 35124.23 | 01-FEB-00:10 | 1.35 |
March | 0.940767E+11 | 1.35 | 35124.23 | 01-MAR-00:10 | 1.35 |
April | 0.910420E+11 | 1.35 | 35124.23 | 01-APR-00:10 | 1.35 |
May | 0.940767E+11 | 1.35 | 35124.23 | 01-MAY-00:05 | 1.35 |
June | 0.910420E+11 | 1.35 | 35124.23 | 01-JUN-00:10 | 1.35 |
July | 0.940767E+11 | 1.35 | 35124.23 | 01-JUL-00:10 | 1.35 |
August | 0.940767E+11 | 1.35 | 35124.23 | 01-AUG-00:03 | 1.35 |
September | 0.910420E+11 | 1.35 | 35124.23 | 01-SEP-00:03 | 1.35 |
October | 0.940767E+11 | 1.35 | 35124.23 | 01-OCT-00:10 | 1.35 |
November | 0.910420E+11 | 1.35 | 35124.23 | 01-NOV-00:10 | 1.35 |
December | 0.940767E+11 | 1.35 | 35124.23 | 01-DEC-00:10 | 1.35 |
Annual Sum or Average | 0.110768E+13 | 1.35 | |||
Minimum of Months | 0.849725E+11 | 1.35 | 35124.23 | 1.35 | |
Maximum of Months | 0.940767E+11 | 1.35 | 35124.23 | 1.35 |
Report: FanReportMonthly
For: DATACENTER BOT SUPPLY FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.137684E+10 | 0.93 | 514.05 | 01-JAN-00:01 | 0.93 |
February | 0.124360E+10 | 0.93 | 514.05 | 01-FEB-00:10 | 0.93 |
March | 0.137684E+10 | 0.93 | 514.05 | 01-MAR-00:10 | 0.93 |
April | 0.133243E+10 | 0.93 | 514.05 | 01-APR-00:10 | 0.93 |
May | 0.137684E+10 | 0.93 | 514.05 | 01-MAY-00:05 | 0.93 |
June | 0.133243E+10 | 0.93 | 514.05 | 01-JUN-00:10 | 0.93 |
July | 0.137684E+10 | 0.93 | 514.05 | 01-JUL-00:10 | 0.93 |
August | 0.137684E+10 | 0.93 | 514.05 | 01-AUG-00:03 | 0.93 |
September | 0.133243E+10 | 0.93 | 514.05 | 01-SEP-00:03 | 0.93 |
October | 0.137684E+10 | 0.93 | 514.05 | 01-OCT-00:10 | 0.93 |
November | 0.133243E+10 | 0.93 | 514.05 | 01-NOV-00:10 | 0.93 |
December | 0.137684E+10 | 0.93 | 514.05 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.162112E+11 | 0.93 | |||
Minimum of Months | 0.124360E+10 | 0.93 | 514.05 | 0.93 | |
Maximum of Months | 0.137684E+10 | 0.93 | 514.05 | 0.93 |
Report: FanReportMonthly
For: DATACENTER MID SUPPLY FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.131181E+11 | 0.93 | 4897.74 | 01-JAN-00:01 | 0.93 |
February | 0.118486E+11 | 0.93 | 4897.74 | 01-FEB-00:10 | 0.93 |
March | 0.131181E+11 | 0.93 | 4897.74 | 01-MAR-00:10 | 0.93 |
April | 0.126949E+11 | 0.93 | 4897.74 | 01-APR-00:10 | 0.93 |
May | 0.131181E+11 | 0.93 | 4897.74 | 01-MAY-00:05 | 0.93 |
June | 0.126949E+11 | 0.93 | 4897.74 | 01-JUN-00:10 | 0.93 |
July | 0.131181E+11 | 0.93 | 4897.74 | 01-JUL-00:10 | 0.93 |
August | 0.131181E+11 | 0.93 | 4897.74 | 01-AUG-00:03 | 0.93 |
September | 0.126949E+11 | 0.93 | 4897.74 | 01-SEP-00:03 | 0.93 |
October | 0.131181E+11 | 0.93 | 4897.74 | 01-OCT-00:10 | 0.93 |
November | 0.126949E+11 | 0.93 | 4897.74 | 01-NOV-00:10 | 0.93 |
December | 0.131181E+11 | 0.93 | 4897.74 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.154455E+12 | 0.93 | |||
Minimum of Months | 0.118486E+11 | 0.93 | 4897.74 | 0.93 | |
Maximum of Months | 0.131181E+11 | 0.93 | 4897.74 | 0.93 |
Report: FanReportMonthly
For: DATACENTER TOP SUPPLY FAN
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.133612E+10 | 0.93 | 498.85 | 01-JAN-00:01 | 0.93 |
February | 0.120682E+10 | 0.93 | 498.85 | 01-FEB-00:10 | 0.93 |
March | 0.133612E+10 | 0.93 | 498.85 | 01-MAR-00:10 | 0.93 |
April | 0.129302E+10 | 0.93 | 498.85 | 01-APR-00:10 | 0.93 |
May | 0.133612E+10 | 0.93 | 498.85 | 01-MAY-00:05 | 0.93 |
June | 0.129302E+10 | 0.93 | 498.85 | 01-JUN-00:10 | 0.93 |
July | 0.133612E+10 | 0.93 | 498.85 | 01-JUL-00:10 | 0.93 |
August | 0.133612E+10 | 0.93 | 498.85 | 01-AUG-00:03 | 0.93 |
September | 0.129302E+10 | 0.93 | 498.85 | 01-SEP-00:03 | 0.93 |
October | 0.133612E+10 | 0.93 | 498.85 | 01-OCT-00:10 | 0.93 |
November | 0.129302E+10 | 0.93 | 498.85 | 01-NOV-00:10 | 0.93 |
December | 0.133612E+10 | 0.93 | 498.85 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.157318E+11 | 0.93 | |||
Minimum of Months | 0.120682E+10 | 0.93 | 498.85 | 0.93 | |
Maximum of Months | 0.133612E+10 | 0.93 | 498.85 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 84426430.88 | 75983787.79 | 1656.27 | 02-JAN-07:10 | 1490.64 | 1490.64 | 68.31 | 26.38 |
February | 38396816.58 | 34557134.92 | 1243.78 | 06-FEB-06:01 | 1119.40 | 1119.40 | 70.26 | 23.13 |
March | 9046155.26 | 8141539.73 | 366.47 | 13-MAR-05:01 | 329.83 | 329.83 | 66.43 | 12.86 |
April | 1119278.76 | 1007350.88 | 359.29 | 03-APR-05:01 | 323.36 | 323.36 | 65.12 | 12.74 |
May | 828510.28 | 745659.25 | 90.08 | 04-MAY-04:50 | 81.07 | 81.07 | 77.64 | 5.96 |
June | 556012.32 | 500411.08 | 89.45 | 19-JUN-03:00 | 80.50 | 80.50 | 70.79 | 5.96 |
July | 633451.33 | 570106.19 | 89.45 | 10-JUL-02:10 | 80.51 | 80.51 | 70.88 | 5.96 |
August | 750313.01 | 675281.71 | 89.46 | 05-AUG-03:50 | 80.51 | 80.51 | 70.88 | 5.96 |
September | 702490.53 | 632241.47 | 89.44 | 25-SEP-00:10 | 80.49 | 80.49 | 70.70 | 5.96 |
October | 2530377.62 | 2277339.85 | 137.90 | 19-OCT-03:50 | 124.11 | 124.11 | 78.22 | 7.60 |
November | 9055811.55 | 8150230.40 | 377.90 | 27-NOV-06:01 | 340.11 | 340.11 | 67.60 | 13.05 |
December | 8194726.49 | 7375253.84 | 369.33 | 26-DEC-06:01 | 332.40 | 332.40 | 62.69 | 12.94 |
Annual Sum or Average | 0.156240E+09 | 0.140616E+09 | ||||||
Minimum of Months | 556012.32 | 500411.08 | 89.44 | 80.49 | 80.49 | 62.69 | 5.96 | |
Maximum of Months | 84426430.88 | 75983787.79 | 1656.27 | 1490.64 | 1490.64 | 78.22 | 26.38 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 13755.39 | 12379.85 | 30.91 | 24-JAN-06:03 | 27.82 | 27.82 | 7.02 | 3.76 |
February | 18366.19 | 16529.58 | 13.23 | 09-FEB-10:55 | 11.91 | 11.91 | 7.39 | 2.00 |
March | 15627676.63 | 14064908.96 | 998.39 | 27-MAR-13:00 | 898.55 | 898.55 | 8.88 | 27.70 |
April | 0.153375E+09 | 0.138037E+09 | 4043.72 | 07-APR-14:00 | 3639.35 | 3639.35 | 7.17 | 52.48 |
May | 0.561796E+09 | 0.505616E+09 | 4054.98 | 22-MAY-15:20 | 3649.48 | 3649.48 | 8.67 | 52.54 |
June | 0.250455E+10 | 0.225409E+10 | 24817.65 | 27-JUN-05:02 | 22335.89 | 22335.89 | 8.21 | 111.04 |
July | 0.283725E+10 | 0.255353E+10 | 19799.91 | 22-JUL-05:01 | 17819.92 | 17819.92 | 8.18 | 101.54 |
August | 0.293697E+10 | 0.264327E+10 | 14321.52 | 24-AUG-05:02 | 12889.37 | 12889.37 | 8.19 | 89.16 |
September | 0.168767E+10 | 0.151890E+10 | 27174.32 | 14-SEP-05:02 | 24456.89 | 24456.89 | 8.13 | 115.07 |
October | 0.866462E+09 | 0.779816E+09 | 10807.90 | 06-OCT-05:02 | 9727.11 | 9727.11 | 8.43 | 79.49 |
November | 10352358.75 | 9317122.88 | 412.54 | 04-NOV-12:30 | 371.29 | 371.29 | 8.60 | 17.82 |
December | 132595.22 | 119335.70 | 43.84 | 25-DEC-14:31 | 39.46 | 39.46 | 8.42 | 4.78 |
Annual Sum or Average | 0.115742E+11 | 0.104168E+11 | ||||||
Minimum of Months | 13755.39 | 12379.85 | 13.23 | 11.91 | 11.91 | 7.02 | 2.00 | |
Maximum of Months | 0.293697E+10 | 0.264327E+10 | 27174.32 | 24456.89 | 24456.89 | 8.88 | 115.07 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967962.60 | 3590388.78 | 5.96 | 01-JAN-06:02 | 1.79 | 1.79 | 70.59 | 0.44 |
February | 10809772.67 | 3242931.80 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 59.40 | 0.44 |
March | 11967962.60 | 3590388.78 | 5.96 | 01-MAR-06:02 | 1.79 | 1.79 | 61.96 | 0.44 |
April | 11581899.29 | 3474569.79 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 62.72 | 0.44 |
May | 11967962.60 | 3590388.78 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 72.00 | 0.44 |
June | 11581899.29 | 3474569.79 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 63.56 | 0.44 |
July | 11967962.60 | 3590388.78 | 5.96 | 01-JUL-05:01 | 1.79 | 1.79 | 60.50 | 0.44 |
August | 11967962.60 | 3590388.78 | 5.96 | 01-AUG-05:01 | 1.79 | 1.79 | 60.72 | 0.44 |
September | 11581899.29 | 3474569.79 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 65.23 | 0.44 |
October | 11967962.60 | 3590388.78 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 72.21 | 0.44 |
November | 11581899.29 | 3474569.79 | 5.96 | 01-NOV-05:01 | 1.79 | 1.79 | 59.77 | 0.44 |
December | 11967962.60 | 3590388.78 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 63.61 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273932.42 | ||||||
Minimum of Months | 10809772.67 | 3242931.80 | 5.96 | 1.79 | 1.79 | 59.40 | 0.44 | |
Maximum of Months | 11967962.60 | 3590388.78 | 5.96 | 1.79 | 1.79 | 72.21 | 0.44 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.146942E+10 | 0.132248E+10 | 9310.01 | 02-JAN-07:20 | 8379.01 | 8379.01 | 8.40 | 116.60 |
February | 0.234312E+10 | 0.210881E+10 | 9310.01 | 01-FEB-11:30 | 8379.01 | 8379.01 | 8.40 | 116.60 |
March | 0.255757E+10 | 0.230181E+10 | 9310.01 | 01-MAR-07:05 | 8379.01 | 8379.01 | 8.40 | 116.60 |
April | 0.557222E+10 | 0.501500E+10 | 9310.01 | 01-APR-08:20 | 8379.01 | 8379.01 | 8.40 | 116.60 |
May | 0.125927E+11 | 0.113334E+11 | 9310.01 | 01-MAY-01:31 | 8379.01 | 8379.01 | 8.45 | 116.60 |
June | 0.175718E+11 | 0.158147E+11 | 9310.01 | 01-JUN-03:01 | 8379.01 | 8379.01 | 9.60 | 116.60 |
July | 0.207084E+11 | 0.186375E+11 | 9310.01 | 01-JUL-03:01 | 8379.01 | 8379.01 | 9.95 | 116.60 |
August | 0.220476E+11 | 0.198428E+11 | 9310.01 | 01-AUG-00:03 | 8379.01 | 8379.01 | 7.36 | 116.60 |
September | 0.149646E+11 | 0.134682E+11 | 9310.01 | 01-SEP-00:03 | 8379.01 | 8379.01 | 7.41 | 116.60 |
October | 0.945640E+10 | 0.851076E+10 | 9310.01 | 01-OCT-20:01 | 8379.01 | 8379.01 | 8.28 | 116.60 |
November | 0.273721E+10 | 0.246348E+10 | 9310.01 | 01-NOV-09:10 | 8379.01 | 8379.01 | 8.43 | 116.60 |
December | 0.152293E+10 | 0.137064E+10 | 9310.01 | 01-DEC-07:00 | 8379.01 | 8379.01 | 8.40 | 116.60 |
Annual Sum or Average | 0.113544E+12 | 0.102190E+12 | ||||||
Minimum of Months | 0.146942E+10 | 0.132248E+10 | 9310.01 | 8379.01 | 8379.01 | 7.36 | 116.60 | |
Maximum of Months | 0.220476E+11 | 0.198428E+11 | 9310.01 | 8379.01 | 8379.01 | 9.95 | 116.60 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.889766E+10 | 0.800789E+10 | 3322.00 | 01-JAN-00:01 | 2989.80 | 2989.80 | 21.36 | 13.87 |
February | 0.803659E+10 | 0.723293E+10 | 3322.00 | 01-FEB-00:10 | 2989.80 | 2989.80 | 23.88 | 13.87 |
March | 0.889766E+10 | 0.800789E+10 | 3322.00 | 01-MAR-00:10 | 2989.80 | 2989.80 | 26.77 | 13.87 |
April | 0.861064E+10 | 0.774957E+10 | 3322.00 | 01-APR-00:10 | 2989.80 | 2989.80 | 29.72 | 13.87 |
May | 0.889766E+10 | 0.800789E+10 | 3322.00 | 01-MAY-00:05 | 2989.80 | 2989.80 | 23.90 | 13.87 |
June | 0.861064E+10 | 0.774957E+10 | 3322.00 | 01-JUN-00:10 | 2989.80 | 2989.80 | 26.53 | 13.87 |
July | 0.889766E+10 | 0.800789E+10 | 3322.00 | 01-JUL-00:10 | 2989.80 | 2989.80 | 32.25 | 13.87 |
August | 0.889766E+10 | 0.800789E+10 | 3322.00 | 01-AUG-00:03 | 2989.80 | 2989.80 | 39.75 | 13.87 |
September | 0.861064E+10 | 0.774957E+10 | 3322.00 | 01-SEP-00:03 | 2989.80 | 2989.80 | 35.95 | 13.87 |
October | 0.889766E+10 | 0.800789E+10 | 3322.00 | 01-OCT-00:10 | 2989.80 | 2989.80 | 24.32 | 13.87 |
November | 0.861064E+10 | 0.774957E+10 | 3322.00 | 01-NOV-00:10 | 2989.80 | 2989.80 | 27.00 | 13.87 |
December | 0.889766E+10 | 0.800789E+10 | 3322.00 | 01-DEC-00:10 | 2989.80 | 2989.80 | 29.66 | 13.87 |
Annual Sum or Average | 0.104763E+12 | 0.942865E+11 | ||||||
Minimum of Months | 0.803659E+10 | 0.723293E+10 | 3322.00 | 2989.80 | 2989.80 | 21.36 | 13.87 | |
Maximum of Months | 0.889766E+10 | 0.800789E+10 | 3322.00 | 2989.80 | 2989.80 | 39.75 | 13.87 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.274619E+10 | 0.247157E+10 | 17401.67 | 19-JAN-11:00 | 15661.50 | 15661.50 | 21.17 | 68.34 |
February | 0.437909E+10 | 0.394118E+10 | 17401.66 | 23-FEB-14:50 | 15661.50 | 15661.50 | 21.17 | 68.34 |
March | 0.478092E+10 | 0.430283E+10 | 17440.27 | 27-MAR-13:10 | 15696.24 | 15696.24 | 24.25 | 68.34 |
April | 0.104446E+11 | 0.940015E+10 | 34854.78 | 07-APR-11:40 | 31369.30 | 31369.30 | 23.22 | 136.68 |
May | 0.242380E+11 | 0.218142E+11 | 34973.99 | 31-MAY-15:10 | 31476.59 | 31476.59 | 27.55 | 136.68 |
June | 0.400014E+11 | 0.360012E+11 | 35011.07 | 07-JUN-09:50 | 31509.96 | 31509.96 | 28.89 | 136.68 |
July | 0.501562E+11 | 0.451406E+11 | 35011.07 | 05-JUL-09:20 | 31509.96 | 31509.96 | 28.81 | 136.68 |
August | 0.519928E+11 | 0.467935E+11 | 35011.07 | 01-AUG-08:20 | 31509.96 | 31509.96 | 28.97 | 136.68 |
September | 0.322866E+11 | 0.290579E+11 | 35011.07 | 07-SEP-10:30 | 31509.96 | 31509.96 | 28.92 | 136.68 |
October | 0.189951E+11 | 0.170956E+11 | 34976.81 | 05-OCT-14:50 | 31479.13 | 31479.13 | 27.64 | 136.68 |
November | 0.511706E+10 | 0.460536E+10 | 17422.55 | 03-NOV-14:00 | 15680.30 | 15680.30 | 22.84 | 68.34 |
December | 0.284620E+10 | 0.256158E+10 | 17401.77 | 30-DEC-12:30 | 15661.59 | 15661.59 | 21.18 | 68.34 |
Annual Sum or Average | 0.247984E+12 | 0.223186E+12 | ||||||
Minimum of Months | 0.274619E+10 | 0.247157E+10 | 17401.66 | 15661.50 | 15661.50 | 21.17 | 68.34 | |
Maximum of Months | 0.519928E+11 | 0.467935E+11 | 35011.07 | 31509.96 | 31509.96 | 28.97 | 136.68 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3902.95 | 34148.19 | 16-JAN-11:00 | 78.49 | 80.49 | 14033.90 | 57420.49 | 25-JAN-12:10 |
February | 3595.26 | 33934.50 | 20-FEB-11:00 | 78.37 | 80.39 | 14327.08 | 57338.52 | 24-FEB-12:30 |
March | 2782.74 | 33584.83 | 27-MAR-05:08 | 78.18 | 81.56 | 15101.62 | 60436.40 | 14-MAR-11:35 |
April | 3877.62 | 33961.17 | 17-APR-05:08 | 78.38 | 81.63 | 13255.16 | 51246.77 | 03-APR-11:40 |
May | 4696.00 | 37944.34 | 29-MAY-09:26 | 80.53 | 82.22 | 12775.26 | 48313.63 | 30-MAY-11:40 |
June | 4527.33 | 37760.78 | 18-JUN-23:00 | 80.43 | 82.07 | 12167.02 | 44852.15 | 01-JUN-11:20 |
July | 6434.02 | 38262.07 | 30-JUL-18:50 | 80.70 | 82.22 | 10321.34 | 41945.76 | 03-JUL-11:40 |
August | 4854.57 | 38270.08 | 13-AUG-19:45 | 80.71 | 82.22 | 11460.87 | 40985.95 | 31-AUG-11:50 |
September | 5737.83 | 38231.42 | 03-SEP-22:40 | 80.69 | 82.22 | 10920.89 | 42871.39 | 29-SEP-12:00 |
October | 5783.78 | 38041.82 | 09-OCT-08:53 | 80.59 | 82.22 | 11593.95 | 46107.71 | 31-OCT-11:40 |
November | 4971.64 | 37711.81 | 12-NOV-11:00 | 80.41 | 82.20 | 12747.92 | 52386.89 | 24-NOV-12:10 |
December | 4256.75 | 35207.36 | 25-DEC-11:00 | 79.06 | 81.01 | 13085.75 | 54262.68 | 11-DEC-12:50 |
Annual Sum or Average | 4625.03 | 12639.56 | ||||||
Minimum of Months | 2782.74 | 33584.83 | 78.18 | 80.39 | 10321.34 | 40985.95 | ||
Maximum of Months | 6434.02 | 38270.08 | 80.71 | 82.22 | 15101.62 | 60436.40 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2.13 | 1518.27 | 19-JAN-12:50 | 79.70 | 79.70 | 70464.20 | 1535039.18 | 02-JAN-07:10 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 72.87 | 72.87 | 53016.39 | 1238875.22 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 71.06 | 71.06 | 15423.53 | 794330.49 | 13-MAR-05:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 78.07 | 78.07 | 3163.78 | 827400.22 | 03-APR-05:01 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 68.39 | 68.39 | 538.31 | 257736.73 | 31-MAY-03:47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 69.28 | 69.28 | 699.93 | 331804.50 | 23-JUN-04:00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 70.33 | 70.33 | 594.15 | 257109.87 | 12-JUL-03:47 |
August | 0.00 | 0.00 | 01-AUG-00:03 | 70.86 | 70.86 | 872.75 | 362584.28 | 26-AUG-03:50 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 62.97 | 62.97 | 724.17 | 317907.17 | 02-SEP-03:47 |
October | 0.37 | 1076.90 | 18-OCT-21:00 | 79.66 | 79.66 | 1277.21 | 276947.04 | 07-OCT-03:50 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 78.79 | 78.79 | 15849.16 | 781624.87 | 25-NOV-06:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 69.08 | 69.08 | 33007.16 | 1125406.94 | 30-DEC-05:01 |
Annual Sum or Average | 0.21 | 16123.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 62.97 | 62.97 | 538.31 | 257109.87 | ||
Maximum of Months | 2.13 | 1518.27 | 79.70 | 79.70 | 70464.20 | 1535039.18 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 977.53 | 17137.69 | 31-JAN-10:00 | 8.41 | 8.39 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 1749.80 | 27270.27 | 09-FEB-10:55 | 8.43 | 8.40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 13832.45 | 1290889.74 | 27-MAR-13:10 | 10.25 | 8.92 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 92468.26 | 1453845.57 | 07-APR-11:40 | 9.96 | 8.40 | 0.36 | 2341.83 | 17-APR-00:50 |
May | 314148.19 | 1585530.51 | 30-MAY-13:20 | 9.94 | 6.70 | 10.26 | 93109.46 | 29-MAY-03:41 |
June | 737850.20 | 2497932.88 | 27-JUN-05:03 | 12.64 | 7.53 | 4.24 | 39739.09 | 16-JUN-00:12 |
July | 843419.16 | 2469120.53 | 22-JUL-05:02 | 12.09 | 7.03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 847406.55 | 2214111.64 | 17-AUG-05:02 | 11.47 | 6.94 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 570192.32 | 2642401.76 | 14-SEP-05:03 | 12.79 | 7.38 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 285209.02 | 1899248.44 | 06-OCT-05:03 | 11.69 | 7.80 | 1.04 | 41930.17 | 01-OCT-20:01 |
November | 16827.66 | 693226.28 | 10-NOV-10:00 | 9.71 | 9.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 1235.29 | 116058.49 | 25-DEC-15:23 | 8.61 | 8.49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 312499.24 | 1.34 | ||||||
Minimum of Months | 977.53 | 17137.69 | 8.41 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 847406.55 | 2642401.76 | 12.79 | 9.00 | 10.26 | 93109.46 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 3.07 | 16727.53 | 24-JAN-06:03 | 7.76 | 8.38 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 17.08 | 23233.41 | 09-FEB-10:55 | 9.48 | 8.39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 8297.63 | 908701.79 | 27-MAR-13:00 | 14.54 | 8.87 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 61885.42 | 1327775.72 | 07-APR-15:40 | 12.96 | 8.07 | 0.00 | 0.00 | 01-APR-00:10 |
May | 222145.09 | 1613989.63 | 31-MAY-16:00 | 14.40 | 8.28 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 642594.96 | 3442782.93 | 27-JUN-05:02 | 14.11 | 8.06 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 733193.31 | 3486804.32 | 22-JUL-05:01 | 14.91 | 7.86 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 722760.33 | 2914769.05 | 17-AUG-05:01 | 14.80 | 7.66 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 464271.30 | 3719511.51 | 14-SEP-05:01 | 14.88 | 8.02 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 237130.85 | 2622927.68 | 06-OCT-05:01 | 14.75 | 8.24 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 10077.37 | 529309.17 | 04-NOV-12:30 | 13.79 | 8.58 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 167.68 | 99831.29 | 25-DEC-12:31 | 11.78 | 8.42 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 260273.94 | 0.00 | ||||||
Minimum of Months | 3.07 | 16727.53 | 7.76 | 7.66 | 0.00 | 0.00 | ||
Maximum of Months | 733193.31 | 3719511.51 | 14.91 | 8.87 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 153354.29 | 543813.88 | 28-JAN-23:00 | 29.53 | 18.33 | 0.00 | 0.00 | 01-JAN-00:01 |
February | 290342.11 | 581588.36 | 20-FEB-00:30 | 30.30 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 436471.13 | 844647.85 | 27-MAR-16:00 | 35.62 | 26.10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 628956.81 | 1289826.95 | 07-APR-13:00 | 44.52 | 31.93 | 0.00 | 0.00 | 01-APR-00:10 |
May | 237492.43 | 850555.66 | 30-MAY-13:00 | 35.74 | 31.67 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 623749.79 | 1440567.27 | 19-JUN-12:00 | 47.49 | 39.88 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1012275.96 | 1514811.11 | 07-JUL-12:00 | 48.95 | 38.34 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1196401.09 | 1681009.76 | 24-AUG-16:00 | 52.21 | 39.32 | 0.00 | 0.00 | 01-AUG-00:03 |
September | 360613.38 | 916379.90 | 01-SEP-14:00 | 37.07 | 32.84 | 0.00 | 0.00 | 01-SEP-00:03 |
October | 368064.50 | 801186.71 | 04-OCT-13:00 | 34.75 | 27.83 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 437569.38 | 616252.03 | 03-NOV-14:00 | 31.00 | 21.61 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 565941.31 | 614742.64 | 05-DEC-01:10 | 30.97 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 528017.21 | 0.00 | ||||||
Minimum of Months | 153354.29 | 543813.88 | 29.53 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1196401.09 | 1681009.76 | 52.21 | 39.88 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 42.25 | 20612.07 | 19-JAN-11:00 | 21.17 | 20.58 | 1857.52 | 135363.96 | 10-JAN-10:00 |
February | 48.61 | 20599.87 | 23-FEB-14:50 | 21.17 | 20.54 | 2878.95 | 135374.01 | 09-FEB-12:30 |
March | 8638.06 | 900596.67 | 27-MAR-13:10 | 24.25 | 21.62 | 2422.84 | 135751.25 | 17-MAR-09:00 |
April | 65877.60 | 1209484.05 | 07-APR-11:40 | 23.22 | 22.33 | 1604.81 | 101774.63 | 14-APR-08:70 |
May | 264931.20 | 3682115.59 | 31-MAY-15:10 | 27.55 | 24.40 | 536.08 | 71229.16 | 13-MAY-04:30 |
June | 1129432.14 | 6001957.88 | 19-JUN-08:70 | 31.61 | 28.49 | 118.90 | 75621.53 | 02-JUN-06:50 |
July | 1864922.42 | 6475160.13 | 20-JUL-15:00 | 32.43 | 29.19 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1647711.81 | 6810416.08 | 02-AUG-15:00 | 33.02 | 29.64 | 84.96 | 30271.88 | 26-AUG-02:30 |
September | 745238.05 | 5358407.33 | 07-SEP-14:10 | 30.48 | 27.44 | 229.04 | 59182.79 | 19-SEP-03:30 |
October | 280586.63 | 3737075.98 | 05-OCT-14:50 | 27.64 | 24.36 | 523.05 | 83477.49 | 18-OCT-15:20 |
November | 11821.79 | 497101.66 | 03-NOV-14:00 | 22.84 | 21.39 | 1931.45 | 130291.97 | 21-NOV-09:40 |
December | 50.38 | 22978.26 | 30-DEC-12:30 | 21.18 | 20.48 | 1892.17 | 128618.67 | 15-DEC-13:40 |
Annual Sum or Average | 505878.94 | 1161.51 | ||||||
Minimum of Months | 42.25 | 20599.87 | 21.17 | 20.48 | 0.00 | 0.00 | ||
Maximum of Months | 1864922.42 | 6810416.08 | 33.02 | 29.64 | 2878.95 | 135751.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.39 | 7.48 |
February | 0.33 | 7.48 |
March | 0.11 | 7.48 |
April | 0.50 | 7.48 |
May | 0.39 | 7.48 |
June | 0.79 | 6.30 |
July | 0.83 | 7.11 |
August | 0.46 | 7.48 |
September | 0.65 | 7.48 |
October | 1.31 | 7.48 |
November | 0.75 | 7.48 |
December | 0.97 | 7.48 |
Annual Sum or Average | 7.49 | 7.31 |
Minimum of Months | 0.11 | 6.30 |
Maximum of Months | 1.31 | 7.48 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.71 | 13.04 |
February | 1.53 | 11.91 |
March | 3.02 | 10.36 |
April | 7.57 | 3.23 |
May | 2.88 | 3.66 |
June | 11.39 | 2.49 |
July | 21.01 | 2.00 |
August | 12.92 | 2.03 |
September | 5.59 | 2.48 |
October | 3.41 | 5.45 |
November | 1.61 | 4.15 |
December | 1.70 | 9.84 |
Annual Sum or Average | 73.32 | 3.36 |
Minimum of Months | 0.71 | 2.00 |
Maximum of Months | 21.01 | 13.04 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.35 | 86.52 |
February | 0.64 | 53.08 |
March | 0.47 | 93.26 |
April | 0.84 | 9.37 |
May | 2.52 | 7.52 |
June | 5.72 | 7.06 |
July | 7.15 | 4.06 |
August | 7.29 | 3.61 |
September | 2.53 | 3.76 |
October | 2.02 | 6.98 |
November | 0.08 | 13.44 |
December | 0.31 | 8.55 |
Annual Sum or Average | 29.93 | 8.62 |
Minimum of Months | 0.08 | 3.61 |
Maximum of Months | 7.29 | 93.26 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.03 | 13.44 |
March | 0.39 | 5.76 |
April | 0.70 | 7.25 |
May | 1.39 | 7.26 |
June | 4.20 | 5.98 |
July | 6.63 | 3.32 |
August | 5.77 | 3.95 |
September | 1.85 | 4.78 |
October | 0.62 | 6.12 |
November | 0.33 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 21.92 | 4.58 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.63 | 13.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.08 | 16.03 |
March | 0.22 | 0.21 |
April | 2.50 | 0.27 |
May | 1.39 | 0.28 |
June | 7.82 | 0.32 |
July | 14.67 | 0.26 |
August | 10.44 | 0.27 |
September | 2.51 | 0.23 |
October | 1.70 | 0.55 |
November | 0.78 | 0.12 |
December | 0.00 | 0.00 |
Annual Sum or Average | 42.12 | 0.31 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 14.67 | 16.03 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.33 | 5.44 |
March | 0.83 | 2.90 |
April | 3.43 | 0.18 |
May | 2.59 | 0.31 |
June | 9.54 | 0.24 |
July | 15.80 | 0.19 |
August | 11.78 | 0.18 |
September | 4.49 | 0.18 |
October | 3.14 | 0.38 |
November | 0.94 | 0.11 |
December | 0.14 | 0.54 |
Annual Sum or Average | 53.03 | 0.29 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 15.80 | 5.44 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.17 | 8.43 |
March | 0.25 | 0.28 |
April | 2.61 | 0.32 |
May | 1.55 | 0.36 |
June | 8.42 | 0.32 |
July | 14.92 | 0.25 |
August | 10.42 | 0.27 |
September | 2.02 | 0.15 |
October | 1.76 | 0.49 |
November | 0.53 | 0.18 |
December | 0.00 | 0.00 |
Annual Sum or Average | 42.64 | 0.31 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 14.92 | 8.43 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.17 | 1.09 |
February | 0.76 | 1.81 |
March | 1.00 | 0.34 |
April | 8.06 | 0.18 |
May | 3.89 | 0.23 |
June | 13.96 | 0.19 |
July | 25.15 | 0.15 |
August | 19.85 | 0.16 |
September | 5.42 | 0.23 |
October | 4.37 | 0.32 |
November | 1.81 | 0.08 |
December | 0.94 | 0.42 |
Annual Sum or Average | 85.38 | 0.20 |
Minimum of Months | 0.17 | 0.08 |
Maximum of Months | 25.15 | 1.81 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.70 | 0.78 |
February | 0.20 | 0.47 |
March | 0.10 | 0.84 |
April | 0.08 | 0.84 |
May | 0.67 | 0.58 |
June | 2.28 | 0.37 |
July | 4.43 | 0.44 |
August | 3.42 | 0.28 |
September | 1.68 | 0.35 |
October | 0.50 | 0.47 |
November | 0.00 | 0.00 |
December | 0.14 | 0.84 |
Annual Sum or Average | 14.21 | 0.41 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.43 | 0.84 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.30 | 6.03 |
February | 0.26 | 6.85 |
March | 0.29 | 7.07 |
April | 0.17 | 0.44 |
May | 2.41 | 0.44 |
June | 4.92 | 0.30 |
July | 7.99 | 0.23 |
August | 5.89 | 0.17 |
September | 2.54 | 0.24 |
October | 1.85 | 0.43 |
November | 0.00 | 0.00 |
December | 0.14 | 0.54 |
Annual Sum or Average | 26.76 | 0.47 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 7.99 | 7.07 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.24 | 6.29 |
February | 0.25 | 11.47 |
March | 0.04 | 0.84 |
April | 0.12 | 0.60 |
May | 0.77 | 0.46 |
June | 2.39 | 0.45 |
July | 4.19 | 0.44 |
August | 3.20 | 0.34 |
September | 1.26 | 0.20 |
October | 0.74 | 0.49 |
November | 0.00 | 0.00 |
December | 0.04 | 0.84 |
Annual Sum or Average | 13.24 | 0.72 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 4.19 | 11.47 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.03 | 0.54 |
February | 0.00 | 0.00 |
March | 0.21 | 0.98 |
April | 0.17 | 0.61 |
May | 2.85 | 0.39 |
June | 3.47 | 0.28 |
July | 6.08 | 0.27 |
August | 4.98 | 0.22 |
September | 2.68 | 0.26 |
October | 1.53 | 0.42 |
November | 0.00 | 0.00 |
December | 0.08 | 0.54 |
Annual Sum or Average | 22.10 | 0.30 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 6.08 | 0.98 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.06 | 0.49 |
February | 1.06 | 0.77 |
March | 0.46 | 0.74 |
April | 0.00 | 0.00 |
May | 0.58 | 0.66 |
June | 2.09 | 0.52 |
July | 3.84 | 0.30 |
August | 3.41 | 0.41 |
September | 0.99 | 0.31 |
October | 0.15 | 0.84 |
November | 0.18 | 1.61 |
December | 0.65 | 1.06 |
Annual Sum or Average | 15.47 | 0.49 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 3.84 | 1.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.30 | 0.54 |
February | 0.37 | 0.56 |
March | 0.40 | 0.54 |
April | 0.23 | 0.41 |
May | 1.73 | 0.35 |
June | 4.60 | 0.31 |
July | 6.11 | 0.19 |
August | 5.57 | 0.19 |
September | 1.52 | 0.30 |
October | 0.71 | 0.61 |
November | 0.02 | 0.54 |
December | 0.49 | 0.54 |
Annual Sum or Average | 22.05 | 0.28 |
Minimum of Months | 0.02 | 0.19 |
Maximum of Months | 6.11 | 0.61 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.75 | 0.66 |
February | 0.41 | 0.56 |
March | 0.27 | 0.74 |
April | 0.11 | 0.84 |
May | 0.70 | 0.69 |
June | 2.09 | 0.50 |
July | 3.38 | 0.25 |
August | 2.92 | 0.26 |
September | 0.65 | 0.41 |
October | 0.26 | 0.84 |
November | 0.08 | 1.69 |
December | 0.36 | 0.84 |
Annual Sum or Average | 11.99 | 0.42 |
Minimum of Months | 0.08 | 0.25 |
Maximum of Months | 3.38 | 1.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.20 | 0.54 |
February | 0.21 | 0.50 |
March | 0.26 | 0.72 |
April | 0.36 | 0.63 |
May | 2.51 | 0.44 |
June | 4.28 | 0.44 |
July | 6.52 | 0.29 |
August | 5.87 | 0.29 |
September | 1.88 | 0.41 |
October | 0.68 | 0.61 |
November | 0.02 | 0.54 |
December | 0.32 | 0.54 |
Annual Sum or Average | 23.11 | 0.37 |
Minimum of Months | 0.02 | 0.29 |
Maximum of Months | 6.52 | 0.72 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.03 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.03 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.03 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 17.52 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 17.52 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 17.52 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 16.53 | 0.00 |
February | 0.62 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 17.15 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 16.53 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 9.32 | 0.00 |
February | 14.45 | 0.00 |
March | 1.32 | 0.00 |
April | 0.33 | 0.00 |
May | 0.66 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.15 | 0.00 |
November | 1.89 | 0.00 |
December | 1.23 | 0.00 |
Annual Sum or Average | 29.36 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 14.45 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.404766E+09 | 0.00 | 9991177.59 | 0.130165E+11 | 0.00 | 0.00 |
February | 0.403778E+09 | 0.00 | 65643.28 | 0.120666E+11 | 0.00 | 0.00 |
March | 0.312754E+09 | 0.00 | 0.660943E+09 | 0.143123E+11 | 0.00 | 0.00 |
April | 0.454583E+09 | 0.00 | 0.562517E+10 | 0.132970E+11 | 0.00 | 0.00 |
May | 0.111498E+10 | 0.00 | 0.170213E+11 | 0.141084E+11 | 0.00 | 0.00 |
June | 0.123037E+10 | 0.00 | 0.681252E+11 | 0.142522E+11 | 0.00 | 0.00 |
July | 0.149619E+10 | 0.00 | 0.973037E+11 | 0.139149E+11 | 0.00 | 0.00 |
August | 0.163148E+10 | 0.00 | 0.963353E+11 | 0.151489E+11 | 0.00 | 0.00 |
September | 0.169259E+10 | 0.00 | 0.519030E+11 | 0.144749E+11 | 0.00 | 0.00 |
October | 0.196304E+10 | 0.00 | 0.204814E+11 | 0.147533E+11 | 0.00 | 0.00 |
November | 0.198948E+10 | 0.00 | 0.271865E+09 | 0.140352E+11 | 0.00 | 0.00 |
December | 0.458614E+09 | 0.00 | 3652628.89 | 0.137728E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.131526E+11 | 0.00 | 0.357742E+12 | 0.167153E+12 | 0.00 | 0.00 |
Minimum of Months | 0.312754E+09 | 0.00 | 65643.28 | 0.120666E+11 | 0.00 | 0.00 |
Maximum of Months | 0.198948E+10 | 0.00 | 0.973037E+11 | 0.151489E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.131650E+10 | 0.00 | 11945598.70 | 0.365800E+10 | 0.00 | 0.00 |
February | 0.100145E+10 | 0.00 | 15558758.05 | 0.384795E+10 | 0.00 | 0.00 |
March | 0.305715E+09 | 0.00 | 0.193807E+10 | 0.620343E+10 | 0.00 | 0.00 |
April | 39253304.02 | 0.00 | 0.139456E+11 | 0.664378E+10 | 0.00 | 0.00 |
May | 8184454.65 | 0.00 | 0.429207E+11 | 0.542968E+10 | 0.00 | 0.00 |
June | 29154048.32 | 0.00 | 0.124127E+12 | 0.612899E+10 | 0.00 | 0.00 |
July | 14376154.93 | 0.00 | 0.162166E+12 | 0.699927E+10 | 0.00 | 0.00 |
August | 59450589.19 | 0.00 | 0.166602E+12 | 0.853269E+10 | 0.00 | 0.00 |
September | 15598408.76 | 0.00 | 0.853424E+11 | 0.540610E+10 | 0.00 | 0.00 |
October | 12444318.24 | 0.00 | 0.462042E+11 | 0.634214E+10 | 0.00 | 0.00 |
November | 0.161766E+09 | 0.00 | 0.210546E+10 | 0.577410E+10 | 0.00 | 0.00 |
December | 0.366853E+09 | 0.00 | 7917315.97 | 0.566719E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.333074E+10 | 0.00 | 0.645387E+12 | 0.706333E+11 | 0.00 | 0.00 |
Minimum of Months | 8184454.65 | 0.00 | 7917315.97 | 0.365800E+10 | 0.00 | 0.00 |
Maximum of Months | 0.131650E+10 | 0.00 | 0.166602E+12 | 0.853269E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.152697E+12 | 0.00 | 15165015.88 | 0.296633E+11 | 0.00 | 0.00 |
February | 0.993134E+11 | 0.00 | 78098848.18 | 0.272126E+11 | 0.00 | 0.00 |
March | 0.313999E+11 | 0.00 | 0.128099E+11 | 0.339076E+11 | 0.00 | 0.00 |
April | 0.511594E+10 | 0.00 | 0.932570E+11 | 0.348179E+11 | 0.00 | 0.00 |
May | 0.107156E+09 | 0.00 | 0.361363E+12 | 0.412819E+11 | 0.00 | 0.00 |
June | 0.508647E+09 | 0.00 | 0.103239E+13 | 0.470274E+11 | 0.00 | 0.00 |
July | 65299572.50 | 0.00 | 0.128928E+13 | 0.505771E+11 | 0.00 | 0.00 |
August | 0.771618E+09 | 0.00 | 0.126669E+13 | 0.589787E+11 | 0.00 | 0.00 |
September | 15904120.26 | 0.00 | 0.738767E+12 | 0.429210E+11 | 0.00 | 0.00 |
October | 0.415739E+09 | 0.00 | 0.367620E+12 | 0.413717E+11 | 0.00 | 0.00 |
November | 0.287887E+11 | 0.00 | 0.154418E+11 | 0.309059E+11 | 0.00 | 0.00 |
December | 0.688176E+11 | 0.00 | 0.260653E+09 | 0.288116E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.388017E+12 | 0.00 | 0.517797E+13 | 0.467477E+12 | 0.00 | 0.00 |
Minimum of Months | 15904120.26 | 0.00 | 15165015.88 | 0.272126E+11 | 0.00 | 0.00 |
Maximum of Months | 0.152697E+12 | 0.00 | 0.128928E+13 | 0.589787E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.316976E+11 | 0.00 | 12566054.31 | 0.351727E+10 | 0.00 | 0.00 |
February | 0.250917E+11 | 0.00 | 12883271.12 | 0.307099E+10 | 0.00 | 0.00 |
March | 0.859758E+10 | 0.00 | 0.119854E+10 | 0.312791E+10 | 0.00 | 0.00 |
April | 0.271354E+10 | 0.00 | 0.963708E+10 | 0.317742E+10 | 0.00 | 0.00 |
May | 90553250.14 | 0.00 | 0.381543E+11 | 0.407618E+10 | 0.00 | 0.00 |
June | 30252340.40 | 0.00 | 0.112564E+12 | 0.525793E+10 | 0.00 | 0.00 |
July | 8573419.79 | 0.00 | 0.144799E+12 | 0.594102E+10 | 0.00 | 0.00 |
August | 30166031.15 | 0.00 | 0.140127E+12 | 0.678573E+10 | 0.00 | 0.00 |
September | 11653501.93 | 0.00 | 0.766327E+11 | 0.433186E+10 | 0.00 | 0.00 |
October | 0.651503E+09 | 0.00 | 0.359163E+11 | 0.355714E+10 | 0.00 | 0.00 |
November | 0.991708E+10 | 0.00 | 0.137721E+10 | 0.282032E+10 | 0.00 | 0.00 |
December | 0.189467E+11 | 0.00 | 16455256.51 | 0.299946E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.977868E+11 | 0.00 | 0.560447E+12 | 0.486632E+11 | 0.00 | 0.00 |
Minimum of Months | 8573419.79 | 0.00 | 12566054.31 | 0.282032E+10 | 0.00 | 0.00 |
Maximum of Months | 0.316976E+11 | 0.00 | 0.144799E+12 | 0.678573E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.303805E+10 | 0.00 | 0.375843E+12 | 0.178325E+12 | 0.00 | 1.73 |
February | 0.281799E+10 | 0.00 | 0.598151E+12 | 0.209421E+12 | 0.00 | 2.00 |
March | 0.679681E+09 | 0.00 | 0.948981E+12 | 0.276219E+12 | 0.00 | 1.40 |
April | 88367856.38 | 0.00 | 0.120838E+13 | 0.318006E+12 | 0.00 | 0.70 |
May | 0.110574E+09 | 0.00 | 0.387501E+12 | 0.177257E+12 | 0.00 | 0.27 |
June | 0.00 | 0.00 | 0.680927E+12 | 0.244381E+12 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.103636E+13 | 0.341263E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.134629E+13 | 0.409865E+12 | 0.00 | 0.02 |
September | 0.00 | 0.00 | 0.388581E+12 | 0.178088E+12 | 0.00 | 0.04 |
October | 0.217679E+09 | 0.00 | 0.679139E+12 | 0.231267E+12 | 0.00 | 0.48 |
November | 0.510187E+09 | 0.00 | 0.924320E+12 | 0.267205E+12 | 0.00 | 0.99 |
December | 0.269921E+09 | 0.00 | 0.123939E+13 | 0.323832E+12 | 0.00 | 1.80 |
Annual Sum or Average | 0.773246E+10 | 0.00 | 0.981386E+13 | 0.315513E+13 | 0.00 | 9.45 |
Minimum of Months | 0.00 | 0.00 | 0.375843E+12 | 0.177257E+12 | 0.00 | 0.00 |
Maximum of Months | 0.303805E+10 | 0.00 | 0.134629E+13 | 0.409865E+12 | 0.00 | 2.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.500440E+10 | 0.254402E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.105668E+11 | 0.353362E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.187413E+11 | 0.522985E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.242245E+11 | 0.624429E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.688274E+10 | 0.300805E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.133609E+11 | 0.470903E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.209704E+11 | 0.700198E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.251848E+11 | 0.795694E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.694804E+10 | 0.308756E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.131427E+11 | 0.429256E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.181328E+11 | 0.506381E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.246738E+11 | 0.625564E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.187833E+12 | 0.589274E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.500440E+10 | 0.254402E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.251848E+11 | 0.795694E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.197319E+11 | 0.179453E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.768168E+11 | 0.289101E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.160208E+12 | 0.465050E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220737E+12 | 0.578321E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.587865E+11 | 0.271992E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124528E+12 | 0.442719E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.199133E+12 | 0.665679E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.240082E+12 | 0.758819E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.602470E+11 | 0.280764E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.115511E+12 | 0.389957E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.152286E+12 | 0.445245E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.208237E+12 | 0.550243E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.163630E+13 | 0.531734E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.197319E+11 | 0.179453E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.240082E+12 | 0.758819E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.921425E+09 | 0.156757E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.565076E+10 | 0.248937E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.144370E+11 | 0.438560E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.211292E+11 | 0.565732E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.552394E+10 | 0.267181E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.124874E+11 | 0.446855E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200922E+11 | 0.673765E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.243955E+11 | 0.772548E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.577355E+10 | 0.278025E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.106025E+11 | 0.373989E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.133496E+11 | 0.412867E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.184498E+11 | 0.511609E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.152813E+12 | 0.514682E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.921425E+09 | 0.156757E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.243955E+11 | 0.772548E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.130165E+11 | 9991177.59 | 0.404766E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120666E+11 | 65643.28 | 0.403778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143123E+11 | 0.660943E+09 | 0.312754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132970E+11 | 0.562517E+10 | 0.454583E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141084E+11 | 0.170213E+11 | 0.111498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142522E+11 | 0.681252E+11 | 0.123037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139149E+11 | 0.973037E+11 | 0.149619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151489E+11 | 0.963353E+11 | 0.163148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144749E+11 | 0.519030E+11 | 0.169259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147533E+11 | 0.204814E+11 | 0.196304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140352E+11 | 0.271865E+09 | 0.198948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137728E+11 | 3652628.89 | 0.458614E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167153E+12 | 0.357742E+12 | 0.131526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120666E+11 | 65643.28 | 0.312754E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151489E+11 | 0.973037E+11 | 0.198948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.365800E+10 | 11945598.70 | 0.131650E+10 | 0.159977E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384795E+10 | 15558758.05 | 0.100145E+10 | 0.148416E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.620343E+10 | 0.193807E+10 | 0.305715E+09 | 0.403707E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664378E+10 | 0.139456E+11 | 39253304.02 | 0.350677E+09 | 8568974.31 | 0.00 | 0.00 | 0.00 |
May | 0.542968E+10 | 0.429207E+11 | 8184454.65 | 0.00 | 0.321334E+09 | 0.00 | 0.00 | 0.00 |
June | 0.612899E+10 | 0.124127E+12 | 29154048.32 | 0.00 | 0.495218E+10 | 0.00 | 0.00 | 0.00 |
July | 0.699927E+10 | 0.162166E+12 | 14376154.93 | 0.00 | 0.195844E+11 | 0.00 | 0.00 | 0.00 |
August | 0.853269E+10 | 0.166602E+12 | 59450589.19 | 0.00 | 0.188384E+11 | 0.00 | 0.00 | 0.00 |
September | 0.540610E+10 | 0.853424E+11 | 15598408.76 | 0.00 | 0.257396E+10 | 0.00 | 0.00 | 0.00 |
October | 0.634214E+10 | 0.462042E+11 | 12444318.24 | 43605403.58 | 18620391.24 | 0.00 | 0.00 | 0.00 |
November | 0.577410E+10 | 0.210546E+10 | 0.161766E+09 | 0.225420E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.566719E+10 | 7917315.97 | 0.366853E+09 | 0.531250E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706333E+11 | 0.645387E+12 | 0.333074E+10 | 0.428373E+11 | 0.462975E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.365800E+10 | 7917315.97 | 8184454.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.853269E+10 | 0.166602E+12 | 0.131650E+10 | 0.159977E+11 | 0.195844E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.296633E+11 | 15165015.88 | 0.152697E+12 | 0.218168E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272126E+11 | 78098848.18 | 0.993134E+11 | 0.210251E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339076E+11 | 0.128099E+11 | 0.313999E+11 | 0.882613E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348179E+11 | 0.932570E+11 | 0.511594E+10 | 0.131326E+11 | 90701284.00 | 0.00 | 0.00 | 0.00 |
May | 0.412819E+11 | 0.361363E+12 | 0.107156E+09 | 34091819.45 | 0.329544E+10 | 0.00 | 0.00 | 0.00 |
June | 0.470274E+11 | 0.103239E+13 | 0.508647E+09 | 0.00 | 0.502094E+11 | 0.00 | 0.00 | 0.00 |
July | 0.505771E+11 | 0.128928E+13 | 65299572.50 | 0.00 | 0.195308E+12 | 0.00 | 0.00 | 0.00 |
August | 0.589787E+11 | 0.126669E+13 | 0.771618E+09 | 0.00 | 0.187985E+12 | 0.00 | 0.00 | 0.00 |
September | 0.429210E+11 | 0.738767E+12 | 15904120.26 | 0.00 | 0.267879E+11 | 0.00 | 0.00 | 0.00 |
October | 0.413717E+11 | 0.367620E+12 | 0.415739E+09 | 0.171760E+10 | 0.324393E+09 | 0.00 | 0.00 | 0.00 |
November | 0.309059E+11 | 0.154418E+11 | 0.287887E+11 | 0.533877E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288116E+11 | 0.260653E+09 | 0.688176E+11 | 0.134433E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467477E+12 | 0.517797E+13 | 0.388017E+12 | 0.719385E+12 | 0.464001E+12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272126E+11 | 15165015.88 | 15904120.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.589787E+11 | 0.128928E+13 | 0.152697E+12 | 0.218168E+12 | 0.195308E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.351727E+10 | 12566054.31 | 0.316976E+11 | 0.247284E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307099E+10 | 12883271.12 | 0.250917E+11 | 0.246104E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312791E+10 | 0.119854E+10 | 0.859758E+10 | 0.126753E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317742E+10 | 0.963708E+10 | 0.271354E+10 | 0.269433E+10 | 967578.97 | 0.00 | 0.00 | 0.00 |
May | 0.407618E+10 | 0.381543E+11 | 90553250.14 | 22451771.83 | 0.111898E+09 | 0.00 | 0.00 | 0.00 |
June | 0.525793E+10 | 0.112564E+12 | 30252340.40 | 0.00 | 0.399594E+10 | 0.00 | 0.00 | 0.00 |
July | 0.594102E+10 | 0.144799E+12 | 8573419.79 | 0.00 | 0.171869E+11 | 0.00 | 0.00 | 0.00 |
August | 0.678573E+10 | 0.140127E+12 | 30166031.15 | 0.00 | 0.172035E+11 | 0.00 | 0.00 | 0.00 |
September | 0.433186E+10 | 0.766327E+11 | 11653501.93 | 0.00 | 0.199113E+10 | 0.00 | 0.00 | 0.00 |
October | 0.355714E+10 | 0.359163E+11 | 0.651503E+09 | 0.494884E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282032E+10 | 0.137721E+10 | 0.991708E+10 | 0.830219E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299946E+10 | 16455256.51 | 0.189467E+11 | 0.192473E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486632E+11 | 0.560447E+12 | 0.977868E+11 | 0.927752E+11 | 0.404903E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.282032E+10 | 12566054.31 | 8573419.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.678573E+10 | 0.144799E+12 | 0.316976E+11 | 0.247284E+11 | 0.172035E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.940767E+11 | 0.320686E+12 | 0.303805E+10 | 0.00 | 0.00 | 0.463218E+10 | 0.00 | 0.00 |
February | 0.849725E+11 | 0.510182E+12 | 0.281799E+10 | 0.00 | 0.00 | 0.533892E+10 | 0.00 | 0.00 |
March | 0.940767E+11 | 0.809976E+12 | 0.679681E+09 | 0.00 | 0.00 | 0.375923E+10 | 0.00 | 0.00 |
April | 0.910420E+11 | 0.102518E+13 | 88367856.38 | 0.00 | 0.00 | 0.188350E+10 | 0.00 | 0.00 |
May | 0.940767E+11 | 0.328736E+12 | 0.110574E+09 | 0.00 | 0.00 | 0.728687E+09 | 0.00 | 0.00 |
June | 0.910420E+11 | 0.562760E+12 | 0.00 | 0.00 | 0.00 | 67210446.62 | 0.00 | 0.00 |
July | 0.940767E+11 | 0.832730E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.940767E+11 | 0.107609E+13 | 0.00 | 0.00 | 0.00 | 50397417.50 | 0.00 | 0.00 |
September | 0.910420E+11 | 0.325853E+12 | 0.00 | 0.00 | 0.00 | 0.110838E+09 | 0.00 | 0.00 |
October | 0.940767E+11 | 0.577350E+12 | 0.217679E+09 | 0.00 | 0.00 | 0.127807E+10 | 0.00 | 0.00 |
November | 0.910420E+11 | 0.789199E+12 | 0.510187E+09 | 0.00 | 0.00 | 0.263741E+10 | 0.00 | 0.00 |
December | 0.940767E+11 | 0.105736E+13 | 0.269921E+09 | 0.00 | 0.00 | 0.480404E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.110768E+13 | 0.821611E+13 | 0.773246E+10 | 0.00 | 0.00 | 0.252905E+11 | 0.00 | 0.00 |
Minimum of Months | 0.849725E+11 | 0.320686E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.940767E+11 | 0.107609E+13 | 0.303805E+10 | 0.00 | 0.00 | 0.533892E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.137684E+10 | 0.413299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124360E+10 | 0.872421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137684E+10 | 0.154693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133243E+10 | 0.198784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137684E+10 | 0.562403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133243E+10 | 0.105192E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137684E+10 | 0.159080E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137684E+10 | 0.192647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133243E+10 | 0.557413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137684E+10 | 0.107537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133243E+10 | 0.149632E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137684E+10 | 0.203695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162112E+11 | 0.151181E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.124360E+10 | 0.413299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137684E+10 | 0.203695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.131181E+11 | 0.162971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118486E+11 | 0.634216E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131181E+11 | 0.132232E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126949E+11 | 0.180983E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131181E+11 | 0.480118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126949E+11 | 0.980125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131181E+11 | 0.151059E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131181E+11 | 0.183573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126949E+11 | 0.482904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131181E+11 | 0.944754E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126949E+11 | 0.125661E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131181E+11 | 0.171898E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154455E+12 | 0.131392E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.118486E+11 | 0.162971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131181E+11 | 0.183573E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.133612E+10 | 0.761050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120682E+10 | 0.466540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133612E+10 | 0.119154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129302E+10 | 0.173133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133612E+10 | 0.450611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129302E+10 | 0.982375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133612E+10 | 0.152393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133612E+10 | 0.186307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129302E+10 | 0.462096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133612E+10 | 0.866505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129302E+10 | 0.110149E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133612E+10 | 0.152302E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157318E+11 | 0.122386E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120682E+10 | 0.761050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133612E+10 | 0.186307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.130165E+11 | 0.404766E+09 | 9991177.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120666E+11 | 0.403778E+09 | 65643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143123E+11 | 0.312754E+09 | 0.660943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132970E+11 | 0.454583E+09 | 0.562517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141084E+11 | 0.111498E+10 | 0.170213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142522E+11 | 0.123037E+10 | 0.681252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139149E+11 | 0.149619E+10 | 0.973037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151489E+11 | 0.163148E+10 | 0.963353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144749E+11 | 0.169259E+10 | 0.519030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147533E+11 | 0.196304E+10 | 0.204814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140352E+11 | 0.198948E+10 | 0.271865E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137728E+11 | 0.458614E+09 | 3652628.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167153E+12 | 0.131526E+11 | 0.357742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.120666E+11 | 0.312754E+09 | 65643.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151489E+11 | 0.198948E+10 | 0.973037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.365800E+10 | 0.131650E+10 | 11945598.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.384795E+10 | 0.100145E+10 | 15558758.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.620343E+10 | 0.305715E+09 | 0.193807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.664378E+10 | 39253304.02 | 0.139456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.542968E+10 | 8184454.65 | 0.429207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.612899E+10 | 29154048.32 | 0.124127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.699927E+10 | 14376154.93 | 0.162166E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.853269E+10 | 59450589.19 | 0.166602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.540610E+10 | 15598408.76 | 0.853424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.634214E+10 | 12444318.24 | 0.462042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.577410E+10 | 0.161766E+09 | 0.210546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.566719E+10 | 0.366853E+09 | 7917315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.706333E+11 | 0.333074E+10 | 0.645387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.365800E+10 | 8184454.65 | 7917315.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.853269E+10 | 0.131650E+10 | 0.166602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.296633E+11 | 0.152697E+12 | 15165015.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272126E+11 | 0.993134E+11 | 78098848.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.339076E+11 | 0.313999E+11 | 0.128099E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.348179E+11 | 0.511594E+10 | 0.932570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.412819E+11 | 0.107156E+09 | 0.361363E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.470274E+11 | 0.508647E+09 | 0.103239E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.505771E+11 | 65299572.50 | 0.128928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.589787E+11 | 0.771618E+09 | 0.126669E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.429210E+11 | 15904120.26 | 0.738767E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.413717E+11 | 0.415739E+09 | 0.367620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.309059E+11 | 0.287887E+11 | 0.154418E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.288116E+11 | 0.688176E+11 | 0.260653E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467477E+12 | 0.388017E+12 | 0.517797E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.272126E+11 | 15904120.26 | 15165015.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.589787E+11 | 0.152697E+12 | 0.128928E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.351727E+10 | 0.316976E+11 | 12566054.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.307099E+10 | 0.250917E+11 | 12883271.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312791E+10 | 0.859758E+10 | 0.119854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.317742E+10 | 0.271354E+10 | 0.963708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.407618E+10 | 90553250.14 | 0.381543E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.525793E+10 | 30252340.40 | 0.112564E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.594102E+10 | 8573419.79 | 0.144799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.678573E+10 | 30166031.15 | 0.140127E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.433186E+10 | 11653501.93 | 0.766327E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.355714E+10 | 0.651503E+09 | 0.359163E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282032E+10 | 0.991708E+10 | 0.137721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.299946E+10 | 0.189467E+11 | 16455256.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.486632E+11 | 0.977868E+11 | 0.560447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.282032E+10 | 8573419.79 | 12566054.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.678573E+10 | 0.316976E+11 | 0.144799E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.940767E+11 | 0.303805E+10 | 0.375843E+12 | 0.00 | 0.795951E+11 | 0.00 | 0.00 | 0.00 | 0.465304E+10 | 0.00 | 0.00 | 0.00 |
February | 0.849725E+11 | 0.281799E+10 | 0.598151E+12 | 0.00 | 0.119086E+12 | 0.00 | 0.00 | 0.00 | 0.536295E+10 | 0.00 | 0.00 | 0.00 |
March | 0.940767E+11 | 0.679681E+09 | 0.948981E+12 | 0.00 | 0.178366E+12 | 0.00 | 0.00 | 0.00 | 0.377615E+10 | 0.00 | 0.00 | 0.00 |
April | 0.910420E+11 | 88367856.38 | 0.120838E+13 | 0.00 | 0.225072E+12 | 0.00 | 0.00 | 0.00 | 0.189198E+10 | 0.00 | 0.00 | 0.00 |
May | 0.940767E+11 | 0.110574E+09 | 0.387501E+12 | 0.00 | 0.824479E+11 | 0.00 | 0.00 | 0.00 | 0.731967E+09 | 0.00 | 0.00 | 0.00 |
June | 0.910420E+11 | 0.00 | 0.680927E+12 | 0.00 | 0.153271E+12 | 0.00 | 0.00 | 0.00 | 67512988.08 | 0.00 | 0.00 | 0.00 |
July | 0.940767E+11 | 0.00 | 0.103636E+13 | 0.00 | 0.247186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.940767E+11 | 0.00 | 0.134629E+13 | 0.00 | 0.315737E+12 | 0.00 | 0.00 | 0.00 | 50624276.71 | 0.00 | 0.00 | 0.00 |
September | 0.910420E+11 | 0.00 | 0.388581E+12 | 0.00 | 0.869351E+11 | 0.00 | 0.00 | 0.00 | 0.111337E+09 | 0.00 | 0.00 | 0.00 |
October | 0.940767E+11 | 0.217679E+09 | 0.679139E+12 | 0.00 | 0.135907E+12 | 0.00 | 0.00 | 0.00 | 0.128383E+10 | 0.00 | 0.00 | 0.00 |
November | 0.910420E+11 | 0.510187E+09 | 0.924320E+12 | 0.00 | 0.173513E+12 | 0.00 | 0.00 | 0.00 | 0.264929E+10 | 0.00 | 0.00 | 0.00 |
December | 0.940767E+11 | 0.269921E+09 | 0.123939E+13 | 0.00 | 0.224930E+12 | 0.00 | 0.00 | 0.00 | 0.482566E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110768E+13 | 0.773246E+10 | 0.981386E+13 | 0.00 | 0.202205E+13 | 0.00 | 0.00 | 0.00 | 0.254043E+11 | 0.00 | 0.00 | |
Minimum of Months | 0.849725E+11 | 0.00 | 0.375843E+12 | 0.00 | 0.795951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.940767E+11 | 0.303805E+10 | 0.134629E+13 | 0.00 | 0.315737E+12 | 0.00 | 0.00 | 0.00 | 0.536295E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.137684E+10 | 0.00 | 0.500440E+10 | 0.00 | 0.116718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.124360E+10 | 0.00 | 0.105668E+11 | 0.00 | 0.229002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.137684E+10 | 0.00 | 0.187413E+11 | 0.00 | 0.385301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.133243E+10 | 0.00 | 0.242245E+11 | 0.00 | 0.491187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.137684E+10 | 0.00 | 0.688274E+10 | 0.00 | 0.163121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.133243E+10 | 0.00 | 0.133609E+11 | 0.00 | 0.337661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137684E+10 | 0.00 | 0.209704E+11 | 0.00 | 0.562514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.137684E+10 | 0.00 | 0.251848E+11 | 0.00 | 0.658010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.133243E+10 | 0.00 | 0.694804E+10 | 0.00 | 0.175514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137684E+10 | 0.00 | 0.131427E+11 | 0.00 | 0.291572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.133243E+10 | 0.00 | 0.181328E+11 | 0.00 | 0.373139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.137684E+10 | 0.00 | 0.246738E+11 | 0.00 | 0.487880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.162112E+11 | 0.00 | 0.187833E+12 | 0.00 | 0.427162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.124360E+10 | 0.00 | 0.500440E+10 | 0.00 | 0.116718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.137684E+10 | 0.00 | 0.251848E+11 | 0.00 | 0.658010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.131181E+11 | 0.00 | 0.197319E+11 | 0.00 | 0.482718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118486E+11 | 0.00 | 0.768168E+11 | 0.00 | 0.170615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131181E+11 | 0.00 | 0.160208E+12 | 0.00 | 0.333869E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126949E+11 | 0.00 | 0.220737E+12 | 0.00 | 0.451372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.131181E+11 | 0.00 | 0.587865E+11 | 0.00 | 0.140811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.126949E+11 | 0.00 | 0.124528E+12 | 0.00 | 0.315770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.131181E+11 | 0.00 | 0.199133E+12 | 0.00 | 0.534497E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.131181E+11 | 0.00 | 0.240082E+12 | 0.00 | 0.627638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126949E+11 | 0.00 | 0.602470E+11 | 0.00 | 0.153814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131181E+11 | 0.00 | 0.115511E+12 | 0.00 | 0.258776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126949E+11 | 0.00 | 0.152286E+12 | 0.00 | 0.318296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131181E+11 | 0.00 | 0.208237E+12 | 0.00 | 0.419062E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154455E+12 | 0.00 | 0.163630E+13 | 0.00 | 0.377279E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.118486E+11 | 0.00 | 0.197319E+11 | 0.00 | 0.482718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.131181E+11 | 0.00 | 0.240082E+12 | 0.00 | 0.627638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.133612E+10 | 0.00 | 0.921425E+09 | 0.00 | 0.231448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120682E+10 | 0.00 | 0.565076E+10 | 0.00 | 0.128255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.133612E+10 | 0.00 | 0.144370E+11 | 0.00 | 0.304948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129302E+10 | 0.00 | 0.211292E+11 | 0.00 | 0.436430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.133612E+10 | 0.00 | 0.552394E+10 | 0.00 | 0.133569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129302E+10 | 0.00 | 0.124874E+11 | 0.00 | 0.317553E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.133612E+10 | 0.00 | 0.200922E+11 | 0.00 | 0.540153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.133612E+10 | 0.00 | 0.243955E+11 | 0.00 | 0.638936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.129302E+10 | 0.00 | 0.577355E+10 | 0.00 | 0.148723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133612E+10 | 0.00 | 0.106025E+11 | 0.00 | 0.240377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.129302E+10 | 0.00 | 0.133496E+11 | 0.00 | 0.283565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.133612E+10 | 0.00 | 0.184498E+11 | 0.00 | 0.377997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.157318E+11 | 0.00 | 0.152813E+12 | 0.00 | 0.357365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.120682E+10 | 0.00 | 0.921425E+09 | 0.00 | 0.231448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.133612E+10 | 0.00 | 0.243955E+11 | 0.00 | 0.638936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.255878E+10 | 0.00 | 0.00 | 0.121526E+09 | 0.00 | 0.00 | 0.630906E+11 | 0.00 | 0.48 |
February | 0.215516E+10 | 0.00 | 0.00 | 0.115090E+09 | 0.00 | 0.00 | 0.587483E+11 | 0.00 | 0.46 |
March | 0.412612E+09 | 0.00 | 0.00 | 0.137470E+09 | 0.00 | 0.00 | 0.744790E+11 | 0.00 | 0.70 |
April | 0.374351E+09 | 16069041.67 | 0.00 | 0.125345E+09 | 0.00 | 0.00 | 0.653019E+11 | 0.00 | 0.93 |
May | 0.194334E+09 | 0.201577E+09 | 0.00 | 0.128949E+09 | 0.00 | 0.00 | 0.582800E+11 | 0.00 | 1.28 |
June | 60317719.58 | 0.618790E+10 | 0.00 | 80741453.90 | 35039926.46 | 0.00 | 0.165342E+11 | 0.00 | 0.96 |
July | 8274439.67 | 0.199268E+11 | 0.00 | 18027978.09 | 0.120457E+09 | 0.00 | 0.105182E+10 | 0.00 | 0.38 |
August | 29760797.36 | 0.166901E+11 | 0.00 | 72847120.36 | 0.146437E+09 | 0.00 | 0.751183E+10 | 0.00 | 0.74 |
September | 0.218276E+09 | 0.415865E+10 | 0.00 | 0.123150E+09 | 4534029.56 | 0.00 | 0.322889E+11 | 0.00 | 1.14 |
October | 0.381006E+09 | 0.157994E+09 | 0.00 | 0.176614E+09 | 0.00 | 0.00 | 0.635475E+11 | 0.00 | 1.25 |
November | 0.380873E+09 | 0.00 | 0.00 | 0.173562E+09 | 0.00 | 0.00 | 0.789907E+11 | 0.00 | 0.86 |
December | 0.642996E+09 | 0.00 | 0.00 | 0.149431E+09 | 0.00 | 0.00 | 0.741198E+11 | 0.00 | 0.58 |
Annual Sum or Average | 0.741674E+10 | 0.473391E+11 | 0.00 | 0.142275E+10 | 0.306467E+09 | 0.00 | 0.593945E+12 | 0.00 | 0.81 |
Minimum of Months | 8274439.67 | 0.00 | 0.00 | 18027978.09 | 0.00 | 0.00 | 0.105182E+10 | 0.00 | 0.38 |
Maximum of Months | 0.255878E+10 | 0.199268E+11 | 0.00 | 0.176614E+09 | 0.146437E+09 | 0.00 | 0.789907E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.603417E+10 | 0.00 | 0.00 | 58818378.51 | 0.00 | 0.00 | 0.366667E+11 | 0.00 | 0.37 |
February | 0.336280E+10 | 0.00 | 0.00 | 66500553.31 | 0.00 | 0.00 | 0.392390E+11 | 0.00 | 0.38 |
March | 0.227561E+10 | 0.00 | 0.00 | 0.108331E+09 | 0.00 | 0.00 | 0.590745E+11 | 0.00 | 0.57 |
April | 0.623867E+10 | 2686580.81 | 0.00 | 99495535.02 | 0.00 | 0.00 | 0.523749E+11 | 0.00 | 0.76 |
May | 0.319127E+10 | 0.262272E+09 | 0.00 | 90284563.96 | 0.00 | 0.00 | 0.359525E+11 | 0.00 | 0.78 |
June | 0.156369E+10 | 0.777148E+10 | 0.00 | 30501618.35 | 0.134160E+09 | 0.00 | 0.569384E+10 | 0.00 | 0.49 |
July | 0.116665E+09 | 0.129420E+11 | 0.00 | 2238239.15 | 0.234369E+09 | 0.00 | 0.200798E+09 | 0.00 | 0.27 |
August | 0.182095E+10 | 0.835804E+10 | 0.00 | 23440944.90 | 0.177604E+09 | 0.00 | 0.232222E+10 | 0.00 | 0.45 |
September | 0.227107E+10 | 0.476920E+10 | 0.00 | 58324466.58 | 69030973.63 | 0.00 | 0.164400E+11 | 0.00 | 0.60 |
October | 0.408191E+10 | 0.871780E+09 | 0.00 | 96355114.13 | 0.00 | 0.00 | 0.358929E+11 | 0.00 | 0.73 |
November | 0.226212E+10 | 0.00 | 0.00 | 0.106223E+09 | 0.00 | 0.00 | 0.566491E+11 | 0.00 | 0.62 |
December | 0.252701E+10 | 0.00 | 0.00 | 0.102855E+09 | 0.00 | 0.00 | 0.556275E+11 | 0.00 | 0.46 |
Annual Sum or Average | 0.357459E+11 | 0.349774E+11 | 0.00 | 0.843369E+09 | 0.615163E+09 | 0.00 | 0.396134E+12 | 0.00 | 0.54 |
Minimum of Months | 0.116665E+09 | 0.00 | 0.00 | 2238239.15 | 0.00 | 0.00 | 0.200798E+09 | 0.00 | 0.27 |
Maximum of Months | 0.623867E+10 | 0.129420E+11 | 0.00 | 0.108331E+09 | 0.234369E+09 | 0.00 | 0.590745E+11 | 0.00 | 0.78 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.192839E+12 | 0.00 | 0.00 | 80972415.42 | 0.00 | 0.483123E+10 | 0.785907E+11 | 0.00 | 0.30 |
February | 0.171764E+12 | 0.00 | 0.00 | 0.119237E+09 | 0.00 | 0.118205E+09 | 0.104564E+12 | 0.00 | 0.30 |
March | 0.132498E+12 | 0.00 | 0.00 | 0.358116E+09 | 0.00 | 0.00 | 0.250902E+12 | 0.00 | 0.39 |
April | 0.773942E+11 | 20191682.94 | 0.00 | 0.467591E+09 | 2497606.14 | 0.00 | 0.287446E+12 | 0.00 | 0.49 |
May | 0.386760E+11 | 0.251556E+10 | 0.00 | 0.590731E+09 | 0.00 | 0.00 | 0.274972E+12 | 0.00 | 0.65 |
June | 0.850239E+10 | 0.714916E+11 | 0.00 | 0.236505E+09 | 0.546134E+10 | 0.00 | 0.471165E+11 | 0.00 | 0.43 |
July | 0.527360E+09 | 0.119252E+12 | 0.00 | 23971782.84 | 0.102213E+11 | 0.00 | 0.191171E+10 | 0.00 | 0.27 |
August | 0.519685E+10 | 0.783454E+11 | 0.00 | 0.216982E+09 | 0.513423E+10 | 0.00 | 0.218678E+11 | 0.00 | 0.40 |
September | 0.233787E+11 | 0.428984E+11 | 0.00 | 0.392690E+09 | 0.461111E+10 | 0.00 | 0.124750E+12 | 0.00 | 0.52 |
October | 0.396942E+11 | 0.785758E+10 | 0.00 | 0.564219E+09 | 0.241350E+09 | 0.00 | 0.243297E+12 | 0.00 | 0.56 |
November | 0.999788E+11 | 0.00 | 0.00 | 0.395454E+09 | 0.00 | 0.00 | 0.257235E+12 | 0.00 | 0.41 |
December | 0.157644E+12 | 0.00 | 0.00 | 0.201886E+09 | 0.00 | 0.00 | 0.165604E+12 | 0.00 | 0.31 |
Annual Sum or Average | 0.948094E+12 | 0.322381E+12 | 0.00 | 0.364835E+10 | 0.256719E+11 | 0.494943E+10 | 0.185826E+13 | 0.00 | 0.42 |
Minimum of Months | 0.527360E+09 | 0.00 | 0.00 | 23971782.84 | 0.00 | 0.00 | 0.191171E+10 | 0.00 | 0.27 |
Maximum of Months | 0.192839E+12 | 0.119252E+12 | 0.00 | 0.590731E+09 | 0.102213E+11 | 0.483123E+10 | 0.287446E+12 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199933E+11 | 0.00 | 0.00 | 558167.86 | 0.00 | 0.147866E+10 | 0.805109E+09 | 0.00 | 0.29 |
February | 0.182403E+11 | 0.00 | 0.00 | 987876.20 | 0.00 | 0.971109E+09 | 0.151207E+10 | 0.00 | 0.29 |
March | 0.199482E+11 | 0.00 | 0.00 | 10126672.06 | 0.00 | 0.194292E+09 | 0.103955E+11 | 0.00 | 0.36 |
April | 0.120672E+11 | 67950.79 | 0.00 | 27429527.87 | 0.00 | 73824739.78 | 0.193308E+11 | 0.00 | 0.45 |
May | 0.838549E+10 | 0.300894E+09 | 0.00 | 46630362.68 | 435356.04 | 0.00 | 0.216223E+11 | 0.00 | 0.64 |
June | 0.143776E+10 | 0.737223E+10 | 0.00 | 23007520.05 | 0.346282E+09 | 0.00 | 0.456288E+10 | 0.00 | 0.45 |
July | 51769743.36 | 0.129476E+11 | 0.00 | 2645685.36 | 0.497753E+09 | 0.00 | 0.211242E+09 | 0.00 | 0.27 |
August | 0.468388E+09 | 0.820372E+10 | 0.00 | 24995602.90 | 0.264748E+09 | 0.00 | 0.232312E+10 | 0.00 | 0.42 |
September | 0.451861E+10 | 0.427543E+10 | 0.00 | 31834705.14 | 0.654392E+09 | 0.00 | 0.917553E+10 | 0.00 | 0.50 |
October | 0.906583E+10 | 0.638274E+09 | 0.00 | 30298850.07 | 92129492.14 | 0.00 | 0.134249E+11 | 0.00 | 0.49 |
November | 0.179203E+11 | 0.00 | 0.00 | 8035456.52 | 0.00 | 0.399901E+09 | 0.830766E+10 | 0.00 | 0.35 |
December | 0.208399E+11 | 0.00 | 0.00 | 791080.41 | 0.00 | 0.469693E+09 | 0.171584E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.132937E+12 | 0.337382E+11 | 0.00 | 0.207342E+09 | 0.185574E+10 | 0.358748E+10 | 0.933869E+11 | 0.00 | 0.40 |
Minimum of Months | 51769743.36 | 0.00 | 0.00 | 558167.86 | 0.00 | 0.00 | 0.211242E+09 | 0.00 | 0.27 |
Maximum of Months | 0.208399E+11 | 0.129476E+11 | 0.00 | 46630362.68 | 0.654392E+09 | 0.147866E+10 | 0.216223E+11 | 0.00 | 0.64 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.370661E+10 | 0.00 | 0.00 | 65005.90 | 0.00 | 0.128411E+09 | 0.191759E+09 | 0.00 | 0.28 |
February | 0.323401E+10 | 0.00 | 0.00 | 241279.11 | 0.00 | 0.101304E+09 | 0.426687E+09 | 0.00 | 0.27 |
March | 0.281151E+10 | 0.00 | 0.00 | 3036974.72 | 0.00 | 0.00 | 0.246242E+10 | 0.00 | 0.40 |
April | 0.208383E+10 | 395977.58 | 0.00 | 5799118.56 | 0.00 | 0.00 | 0.379182E+10 | 0.00 | 0.65 |
May | 0.954244E+09 | 43544818.83 | 0.00 | 7788602.02 | 0.00 | 0.00 | 0.366834E+10 | 0.00 | 0.77 |
June | 0.223586E+09 | 0.123661E+10 | 0.00 | 3442347.97 | 16871971.86 | 0.00 | 0.723117E+09 | 0.00 | 0.58 |
July | 14379453.68 | 0.218209E+10 | 0.00 | 353778.75 | 29474367.05 | 0.00 | 30400402.74 | 0.00 | 0.36 |
August | 0.236020E+09 | 0.142657E+10 | 0.00 | 2983071.33 | 22335509.81 | 0.00 | 0.301890E+09 | 0.00 | 0.56 |
September | 0.560952E+09 | 0.668544E+09 | 0.00 | 4690714.70 | 8681363.35 | 0.00 | 0.163264E+10 | 0.00 | 0.61 |
October | 0.138645E+10 | 0.113636E+09 | 0.00 | 5226762.62 | 0.00 | 0.00 | 0.264442E+10 | 0.00 | 0.62 |
November | 0.235032E+10 | 0.00 | 0.00 | 3172795.32 | 0.00 | 0.00 | 0.259695E+10 | 0.00 | 0.42 |
December | 0.335085E+10 | 0.00 | 0.00 | 949923.45 | 0.00 | 0.00 | 0.113946E+10 | 0.00 | 0.29 |
Annual Sum or Average | 0.209128E+11 | 0.567139E+10 | 0.00 | 37750374.45 | 77363212.07 | 0.229715E+09 | 0.196099E+11 | 0.00 | 0.49 |
Minimum of Months | 14379453.68 | 0.00 | 0.00 | 65005.90 | 0.00 | 0.00 | 30400402.74 | 0.00 | 0.27 |
Maximum of Months | 0.370661E+10 | 0.218209E+10 | 0.00 | 7788602.02 | 29474367.05 | 0.128411E+09 | 0.379182E+10 | 0.00 | 0.77 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.289050E+10 | 0.00 | 0.00 | 246075.07 | 0.00 | 0.156129E+09 | 0.221825E+09 | 0.00 | 0.35 |
February | 0.264713E+10 | 0.00 | 0.00 | 374339.83 | 0.00 | 76137123.81 | 0.356577E+09 | 0.00 | 0.35 |
March | 0.229968E+10 | 0.00 | 0.00 | 3137570.75 | 0.00 | 0.00 | 0.227434E+10 | 0.00 | 0.52 |
April | 0.203702E+10 | 277162.58 | 0.00 | 4861847.30 | 0.00 | 0.00 | 0.292470E+10 | 0.00 | 0.84 |
May | 0.877456E+09 | 36577600.78 | 0.00 | 7141409.39 | 179130.85 | 0.00 | 0.330356E+10 | 0.00 | 1.05 |
June | 0.183076E+09 | 0.867473E+09 | 0.00 | 3029071.88 | 28635797.49 | 0.00 | 0.754706E+09 | 0.00 | 0.73 |
July | 11891837.90 | 0.157327E+10 | 0.00 | 328495.75 | 26459797.84 | 0.00 | 36012064.14 | 0.00 | 0.42 |
August | 0.200945E+09 | 0.108010E+10 | 0.00 | 2386568.53 | 18043640.14 | 0.00 | 0.303155E+09 | 0.00 | 0.70 |
September | 0.535631E+09 | 0.491797E+09 | 0.00 | 4205780.84 | 30033706.83 | 0.00 | 0.142795E+10 | 0.00 | 0.79 |
October | 0.129618E+10 | 82061169.20 | 0.00 | 4426764.56 | 4375584.71 | 0.00 | 0.217791E+10 | 0.00 | 0.82 |
November | 0.203845E+10 | 0.00 | 0.00 | 2021620.56 | 0.00 | 133490.66 | 0.178483E+10 | 0.00 | 0.50 |
December | 0.307983E+10 | 0.00 | 0.00 | 574473.99 | 0.00 | 162515.15 | 0.517296E+09 | 0.00 | 0.36 |
Annual Sum or Average | 0.180978E+11 | 0.413156E+10 | 0.00 | 32734018.46 | 0.107728E+09 | 0.232562E+09 | 0.160829E+11 | 0.00 | 0.62 |
Minimum of Months | 11891837.90 | 0.00 | 0.00 | 246075.07 | 0.00 | 0.00 | 36012064.14 | 0.00 | 0.35 |
Maximum of Months | 0.307983E+10 | 0.157327E+10 | 0.00 | 7141409.39 | 30033706.83 | 0.156129E+09 | 0.330356E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264550E+10 | 0.00 | 0.00 | 3673122.68 | 0.00 | 0.330077E+09 | 0.244365E+10 | 0.00 | 0.36 |
February | 0.226252E+10 | 0.00 | 0.00 | 4382652.40 | 0.00 | 0.165414E+09 | 0.296330E+10 | 0.00 | 0.38 |
March | 0.245903E+10 | 0.00 | 0.00 | 7657725.12 | 0.00 | 621973.99 | 0.524989E+10 | 0.00 | 0.59 |
April | 0.222754E+10 | 671220.64 | 0.00 | 7071395.74 | 0.00 | 0.00 | 0.438137E+10 | 0.00 | 0.75 |
May | 0.118111E+10 | 46855342.43 | 0.00 | 7883913.48 | 0.00 | 0.00 | 0.355857E+10 | 0.00 | 0.80 |
June | 0.243191E+09 | 0.127916E+10 | 0.00 | 3353724.92 | 16845132.35 | 0.00 | 0.708928E+09 | 0.00 | 0.59 |
July | 14356579.21 | 0.230559E+10 | 0.00 | 365883.69 | 29427479.97 | 0.00 | 30146516.31 | 0.00 | 0.39 |
August | 0.234451E+09 | 0.166259E+10 | 0.00 | 3756978.05 | 22299979.05 | 0.00 | 0.350711E+09 | 0.00 | 0.65 |
September | 0.522244E+09 | 0.813579E+09 | 0.00 | 8487938.72 | 9344189.25 | 0.00 | 0.237821E+10 | 0.00 | 0.83 |
October | 0.934776E+09 | 0.205064E+09 | 0.00 | 12739765.90 | 0.00 | 0.00 | 0.554439E+10 | 0.00 | 1.02 |
November | 0.190654E+10 | 0.00 | 0.00 | 7930243.10 | 0.00 | 1329969.92 | 0.541094E+10 | 0.00 | 0.65 |
December | 0.267758E+10 | 0.00 | 0.00 | 6017098.47 | 0.00 | 926526.32 | 0.394997E+10 | 0.00 | 0.42 |
Annual Sum or Average | 0.173089E+11 | 0.631351E+10 | 0.00 | 73320442.26 | 77916780.63 | 0.498369E+09 | 0.369701E+11 | 0.00 | 0.62 |
Minimum of Months | 14356579.21 | 0.00 | 0.00 | 365883.69 | 0.00 | 0.00 | 30146516.31 | 0.00 | 0.36 |
Maximum of Months | 0.267758E+10 | 0.230559E+10 | 0.00 | 12739765.90 | 29427479.97 | 0.330077E+09 | 0.554439E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.313901E+10 | 0.00 | 0.00 | 881932.61 | 0.00 | 25769231.02 | 0.102907E+10 | 0.00 | 0.45 |
February | 0.224055E+10 | 0.00 | 0.00 | 2284356.49 | 0.00 | 9820474.50 | 0.202696E+10 | 0.00 | 0.48 |
March | 0.595889E+09 | 0.00 | 0.00 | 10414349.57 | 0.00 | 0.00 | 0.706289E+10 | 0.00 | 0.91 |
April | 0.562805E+09 | 467801.74 | 0.00 | 15902911.79 | 0.00 | 0.00 | 0.819394E+10 | 0.00 | 1.51 |
May | 0.437876E+09 | 53310771.68 | 0.00 | 10828044.88 | 0.00 | 0.00 | 0.473254E+10 | 0.00 | 1.33 |
June | 0.152701E+09 | 0.145611E+10 | 0.00 | 5293850.69 | 12164306.59 | 0.00 | 0.975995E+09 | 0.00 | 1.06 |
July | 7039748.84 | 0.262869E+10 | 0.00 | 480114.08 | 16891003.38 | 0.00 | 41171362.04 | 0.00 | 0.68 |
August | 0.149210E+09 | 0.200003E+10 | 0.00 | 6025526.90 | 15024047.42 | 0.00 | 0.536132E+09 | 0.00 | 1.19 |
September | 0.300404E+09 | 0.725178E+09 | 0.00 | 7018770.04 | 7603457.83 | 0.00 | 0.203913E+10 | 0.00 | 1.03 |
October | 0.558890E+09 | 0.153758E+09 | 0.00 | 10298931.47 | 0.00 | 0.00 | 0.440569E+10 | 0.00 | 1.21 |
November | 0.717557E+09 | 0.00 | 0.00 | 7777995.07 | 0.00 | 0.00 | 0.553513E+10 | 0.00 | 0.84 |
December | 0.632745E+09 | 0.00 | 0.00 | 7157976.27 | 0.00 | 0.00 | 0.540320E+10 | 0.00 | 0.60 |
Annual Sum or Average | 0.949468E+10 | 0.701755E+10 | 0.00 | 84364759.86 | 51682815.21 | 35589705.52 | 0.419818E+11 | 0.00 | 0.94 |
Minimum of Months | 7039748.84 | 0.00 | 0.00 | 480114.08 | 0.00 | 0.00 | 41171362.04 | 0.00 | 0.45 |
Maximum of Months | 0.313901E+10 | 0.262869E+10 | 0.00 | 15902911.79 | 16891003.38 | 25769231.02 | 0.819394E+10 | 0.00 | 1.51 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162845E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184640E+11 | 0.00 | 0.00 | 0.30 |
February | 0.167876E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170763E+11 | 0.00 | 0.00 | 0.30 |
March | 0.355817E+11 | 0.00 | 0.00 | 747182.47 | 0.00 | 0.539580E+10 | 0.943815E+09 | 0.00 | 0.34 |
April | 0.288217E+11 | 2803499.05 | 0.00 | 13242503.79 | 314071.49 | 0.744750E+09 | 0.848606E+10 | 0.00 | 0.42 |
May | 0.164577E+11 | 0.418129E+09 | 0.00 | 43186521.08 | 2419428.26 | 0.00 | 0.191134E+11 | 0.00 | 0.62 |
June | 0.239041E+10 | 0.115033E+11 | 0.00 | 24997914.41 | 0.214056E+09 | 0.00 | 0.469198E+10 | 0.00 | 0.50 |
July | 68519578.03 | 0.206477E+11 | 0.00 | 3163773.41 | 0.297990E+09 | 0.00 | 0.271572E+09 | 0.00 | 0.36 |
August | 0.109413E+10 | 0.137007E+11 | 0.00 | 21752705.16 | 0.177818E+09 | 0.00 | 0.237047E+10 | 0.00 | 0.49 |
September | 0.878481E+10 | 0.597573E+10 | 0.00 | 27116232.67 | 0.478556E+09 | 0.00 | 0.834023E+10 | 0.00 | 0.51 |
October | 0.210819E+11 | 0.837368E+09 | 0.00 | 16697695.91 | 0.164465E+09 | 3893937.65 | 0.773424E+10 | 0.00 | 0.47 |
November | 0.311465E+11 | 0.00 | 0.00 | 966719.65 | 0.00 | 0.527721E+10 | 0.163684E+10 | 0.00 | 0.34 |
December | 0.243379E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138417E+11 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.202837E+12 | 0.530857E+11 | 0.00 | 0.151871E+09 | 0.133562E+10 | 0.608036E+11 | 0.535886E+11 | 0.00 | 0.41 |
Minimum of Months | 68519578.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.355817E+11 | 0.206477E+11 | 0.00 | 43186521.08 | 0.478556E+09 | 0.184640E+11 | 0.191134E+11 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.159675E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135563E+11 | 0.00 | 0.00 | 0.39 |
February | 0.180010E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107848E+11 | 0.00 | 0.00 | 0.39 |
March | 0.270811E+11 | 0.00 | 0.00 | 7769776.50 | 0.00 | 0.305616E+10 | 0.686910E+10 | 0.00 | 0.47 |
April | 0.190622E+11 | 2912790.43 | 0.00 | 29301492.02 | 0.00 | 0.512218E+09 | 0.178290E+11 | 0.00 | 0.65 |
May | 0.133357E+11 | 0.402432E+09 | 0.00 | 54017596.94 | 2379506.81 | 0.00 | 0.235248E+11 | 0.00 | 0.96 |
June | 0.121942E+10 | 0.866395E+10 | 0.00 | 30220807.94 | 0.799420E+09 | 0.00 | 0.691363E+10 | 0.00 | 0.71 |
July | 59575949.59 | 0.172893E+11 | 0.00 | 3598095.36 | 0.439130E+09 | 0.00 | 0.394870E+09 | 0.00 | 0.49 |
August | 0.732376E+09 | 0.125237E+11 | 0.00 | 24940224.99 | 0.175213E+09 | 0.00 | 0.327803E+10 | 0.00 | 0.74 |
September | 0.657033E+10 | 0.459150E+10 | 0.00 | 32394381.33 | 0.859555E+09 | 0.00 | 0.104139E+11 | 0.00 | 0.74 |
October | 0.140085E+11 | 0.765800E+09 | 0.00 | 27103813.43 | 0.138372E+09 | 3333306.07 | 0.128405E+11 | 0.00 | 0.69 |
November | 0.256474E+11 | 0.00 | 0.00 | 2639893.59 | 0.00 | 0.375455E+10 | 0.327548E+10 | 0.00 | 0.46 |
December | 0.225826E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100985E+11 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.164268E+12 | 0.442396E+11 | 0.00 | 0.211986E+09 | 0.241407E+10 | 0.417658E+11 | 0.853393E+11 | 0.00 | 0.59 |
Minimum of Months | 59575949.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.270811E+11 | 0.172893E+11 | 0.00 | 54017596.94 | 0.859555E+09 | 0.135563E+11 | 0.235248E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.177568E+11 | 0.00 | 0.00 | 23550601.27 | 0.00 | 0.100250E+11 | 0.148590E+11 | 0.00 | 0.36 |
February | 0.177125E+11 | 0.00 | 0.00 | 31426867.68 | 0.00 | 0.786633E+10 | 0.190275E+11 | 0.00 | 0.38 |
March | 0.244194E+11 | 0.00 | 0.00 | 52688883.65 | 0.00 | 0.303156E+10 | 0.338979E+11 | 0.00 | 0.51 |
April | 0.217489E+11 | 6456550.17 | 0.00 | 42398860.52 | 0.00 | 0.549906E+09 | 0.247535E+11 | 0.00 | 0.55 |
May | 0.146614E+11 | 0.465216E+09 | 0.00 | 56554953.38 | 2418795.86 | 0.00 | 0.242715E+11 | 0.00 | 0.68 |
June | 0.238630E+10 | 0.121971E+11 | 0.00 | 27506966.29 | 0.211363E+09 | 0.00 | 0.503541E+10 | 0.00 | 0.53 |
July | 68501668.23 | 0.222902E+11 | 0.00 | 3335723.78 | 0.337642E+09 | 0.00 | 0.276872E+09 | 0.00 | 0.39 |
August | 0.885697E+09 | 0.168729E+11 | 0.00 | 32117972.59 | 0.170309E+09 | 0.00 | 0.318179E+10 | 0.00 | 0.62 |
September | 0.604066E+10 | 0.793777E+10 | 0.00 | 77415887.33 | 0.302890E+09 | 0.00 | 0.192291E+11 | 0.00 | 0.77 |
October | 0.918626E+10 | 0.214898E+10 | 0.00 | 0.114291E+09 | 28478397.50 | 0.00 | 0.454741E+11 | 0.00 | 0.92 |
November | 0.195440E+11 | 0.00 | 0.00 | 55520865.76 | 0.00 | 0.216581E+10 | 0.354877E+11 | 0.00 | 0.54 |
December | 0.200849E+11 | 0.00 | 0.00 | 33642450.57 | 0.00 | 0.750749E+10 | 0.225633E+11 | 0.00 | 0.37 |
Annual Sum or Average | 0.154495E+12 | 0.619186E+11 | 0.00 | 0.550451E+09 | 0.105310E+10 | 0.311461E+11 | 0.248058E+12 | 0.00 | 0.55 |
Minimum of Months | 68501668.23 | 0.00 | 0.00 | 3335723.78 | 0.00 | 0.00 | 0.276872E+09 | 0.00 | 0.36 |
Maximum of Months | 0.244194E+11 | 0.222902E+11 | 0.00 | 0.114291E+09 | 0.337642E+09 | 0.100250E+11 | 0.454741E+11 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.176953E+11 | 0.00 | 0.00 | 639339.93 | 0.00 | 0.116839E+11 | 0.725045E+09 | 0.00 | 0.40 |
February | 0.188120E+11 | 0.00 | 0.00 | 2146105.15 | 0.00 | 0.932431E+10 | 0.171162E+10 | 0.00 | 0.40 |
March | 0.278274E+11 | 0.00 | 0.00 | 14879868.07 | 0.00 | 0.227573E+10 | 0.108061E+11 | 0.00 | 0.52 |
April | 0.195447E+11 | 2787630.01 | 0.00 | 35264447.89 | 0.00 | 0.181562E+09 | 0.203834E+11 | 0.00 | 0.72 |
May | 0.114649E+11 | 0.500903E+09 | 0.00 | 54820594.88 | 0.00 | 0.00 | 0.242438E+11 | 0.00 | 0.96 |
June | 0.148592E+10 | 0.113958E+11 | 0.00 | 29391240.60 | 0.109488E+09 | 0.00 | 0.546039E+10 | 0.00 | 0.77 |
July | 60898932.99 | 0.194764E+11 | 0.00 | 2931299.17 | 0.217780E+09 | 0.00 | 0.217214E+09 | 0.00 | 0.53 |
August | 0.619569E+09 | 0.153763E+11 | 0.00 | 28371173.52 | 0.138810E+09 | 0.00 | 0.270595E+10 | 0.00 | 0.85 |
September | 0.644709E+10 | 0.586766E+10 | 0.00 | 35328518.08 | 0.274867E+09 | 0.00 | 0.998379E+10 | 0.00 | 0.78 |
October | 0.152831E+11 | 0.116853E+10 | 0.00 | 29613283.59 | 35043050.17 | 0.00 | 0.135759E+11 | 0.00 | 0.76 |
November | 0.270193E+11 | 0.00 | 0.00 | 4544015.32 | 0.00 | 0.272395E+10 | 0.423178E+10 | 0.00 | 0.48 |
December | 0.252734E+11 | 0.00 | 0.00 | 492728.45 | 0.00 | 0.747871E+10 | 0.616592E+09 | 0.00 | 0.39 |
Annual Sum or Average | 0.171534E+12 | 0.537883E+11 | 0.00 | 0.238423E+09 | 0.775989E+09 | 0.336682E+11 | 0.946616E+11 | 0.00 | 0.63 |
Minimum of Months | 60898932.99 | 0.00 | 0.00 | 492728.45 | 0.00 | 0.00 | 0.217214E+09 | 0.00 | 0.39 |
Maximum of Months | 0.278274E+11 | 0.194764E+11 | 0.00 | 54820594.88 | 0.274867E+09 | 0.116839E+11 | 0.242438E+11 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.818362E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211844E+10 | 0.00 | 0.00 | 0.30 |
February | 0.820147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190819E+10 | 0.00 | 0.00 | 0.30 |
March | 0.259791E+10 | 0.00 | 0.00 | 31737.20 | 0.00 | 0.107120E+10 | 73166394.71 | 0.00 | 0.35 |
April | 0.252007E+10 | 9199.81 | 0.00 | 1285408.05 | 0.00 | 0.378965E+09 | 0.725529E+09 | 0.00 | 0.42 |
May | 0.173747E+10 | 48709039.40 | 0.00 | 4052815.08 | 576149.05 | 14895466.88 | 0.183390E+10 | 0.00 | 0.62 |
June | 0.251334E+09 | 0.112715E+10 | 0.00 | 2717515.05 | 47114296.05 | 0.00 | 0.532580E+09 | 0.00 | 0.52 |
July | 6907411.93 | 0.214241E+10 | 0.00 | 320742.00 | 39910180.45 | 0.00 | 29867139.56 | 0.00 | 0.36 |
August | 0.104102E+09 | 0.135794E+10 | 0.00 | 2760019.27 | 39607513.01 | 0.00 | 0.271073E+09 | 0.00 | 0.51 |
September | 0.845771E+09 | 0.596534E+09 | 0.00 | 2521336.83 | 73497846.38 | 0.00 | 0.800740E+09 | 0.00 | 0.50 |
October | 0.195518E+10 | 65988737.33 | 0.00 | 1170062.70 | 24056155.48 | 0.110253E+09 | 0.490505E+09 | 0.00 | 0.45 |
November | 0.225172E+10 | 0.00 | 0.00 | 6967.55 | 0.00 | 0.102980E+10 | 24074929.21 | 0.00 | 0.35 |
December | 0.104670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191691E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.149557E+11 | 0.533875E+10 | 0.00 | 14866603.74 | 0.224762E+09 | 0.854866E+10 | 0.478144E+10 | 0.00 | 0.41 |
Minimum of Months | 6907411.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.259791E+10 | 0.214241E+10 | 0.00 | 4052815.08 | 73497846.38 | 0.211844E+10 | 0.183390E+10 | 0.00 | 0.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.918457E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154945E+10 | 0.00 | 0.00 | 0.39 |
February | 0.103772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124780E+10 | 0.00 | 0.00 | 0.39 |
March | 0.225392E+10 | 0.00 | 0.00 | 377682.83 | 0.00 | 0.585687E+09 | 0.406293E+09 | 0.00 | 0.47 |
April | 0.166813E+10 | 8528.79 | 0.00 | 2604054.06 | 0.00 | 0.283654E+09 | 0.154490E+10 | 0.00 | 0.64 |
May | 0.132799E+10 | 48389772.09 | 0.00 | 5470642.64 | 497663.37 | 4620740.69 | 0.234562E+10 | 0.00 | 0.97 |
June | 0.128954E+09 | 0.868635E+09 | 0.00 | 3212982.12 | 89965230.44 | 0.00 | 0.736376E+09 | 0.00 | 0.73 |
July | 5850272.38 | 0.176848E+10 | 0.00 | 383158.00 | 65502181.07 | 0.00 | 42705308.85 | 0.00 | 0.49 |
August | 62786879.02 | 0.124092E+10 | 0.00 | 3012207.34 | 34707181.47 | 0.00 | 0.361368E+09 | 0.00 | 0.77 |
September | 0.599192E+09 | 0.483581E+09 | 0.00 | 3147362.07 | 94685219.14 | 0.00 | 0.101838E+10 | 0.00 | 0.73 |
October | 0.126670E+10 | 64896305.10 | 0.00 | 2124167.80 | 19357487.83 | 67463357.17 | 0.962205E+09 | 0.00 | 0.65 |
November | 0.207260E+10 | 0.00 | 0.00 | 47708.81 | 0.00 | 0.662695E+09 | 99601023.40 | 0.00 | 0.46 |
December | 0.116157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136228E+10 | 0.00 | 0.00 | 0.39 |
Annual Sum or Average | 0.125039E+11 | 0.447491E+10 | 0.00 | 20379965.66 | 0.304715E+09 | 0.576365E+10 | 0.751746E+10 | 0.00 | 0.59 |
Minimum of Months | 5850272.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.39 |
Maximum of Months | 0.225392E+10 | 0.176848E+10 | 0.00 | 5470642.64 | 94685219.14 | 0.154945E+10 | 0.234562E+10 | 0.00 | 0.97 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.118758E+10 | 0.00 | 0.00 | 1410565.62 | 0.00 | 0.122859E+10 | 0.962829E+09 | 0.00 | 0.33 |
February | 0.118188E+10 | 0.00 | 0.00 | 1879797.20 | 0.00 | 0.943659E+09 | 0.127061E+10 | 0.00 | 0.35 |
March | 0.197241E+10 | 0.00 | 0.00 | 3830147.07 | 0.00 | 0.557894E+09 | 0.285834E+10 | 0.00 | 0.49 |
April | 0.191052E+10 | 19064.81 | 0.00 | 3812076.77 | 0.00 | 0.332141E+09 | 0.222153E+10 | 0.00 | 0.53 |
May | 0.155999E+10 | 53452457.20 | 0.00 | 5355991.74 | 577588.24 | 16639168.85 | 0.238012E+10 | 0.00 | 0.69 |
June | 0.241735E+09 | 0.118458E+10 | 0.00 | 2994561.10 | 50176781.48 | 0.00 | 0.590461E+09 | 0.00 | 0.55 |
July | 6773679.55 | 0.230049E+10 | 0.00 | 358932.22 | 40843163.37 | 0.00 | 30983297.09 | 0.00 | 0.39 |
August | 80598275.98 | 0.166116E+10 | 0.00 | 4014296.96 | 26869845.21 | 0.00 | 0.386017E+09 | 0.00 | 0.64 |
September | 0.588101E+09 | 0.807822E+09 | 0.00 | 7357594.12 | 42189188.84 | 0.00 | 0.196229E+10 | 0.00 | 0.76 |
October | 0.941523E+09 | 0.181054E+09 | 0.00 | 9059550.22 | 5583668.23 | 48379679.27 | 0.391638E+10 | 0.00 | 0.86 |
November | 0.165057E+10 | 0.00 | 0.00 | 3414617.74 | 0.00 | 0.530884E+09 | 0.237867E+10 | 0.00 | 0.48 |
December | 0.139458E+10 | 0.00 | 0.00 | 1613440.27 | 0.00 | 0.100745E+10 | 0.109330E+10 | 0.00 | 0.33 |
Annual Sum or Average | 0.127163E+11 | 0.618857E+10 | 0.00 | 45101571.03 | 0.166240E+09 | 0.466564E+10 | 0.200515E+11 | 0.00 | 0.54 |
Minimum of Months | 6773679.55 | 0.00 | 0.00 | 358932.22 | 0.00 | 0.00 | 30983297.09 | 0.00 | 0.33 |
Maximum of Months | 0.197241E+10 | 0.230049E+10 | 0.00 | 9059550.22 | 50176781.48 | 0.122859E+10 | 0.391638E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.120715E+10 | 0.00 | 0.00 | 25373.12 | 0.00 | 0.138512E+10 | 47229105.42 | 0.00 | 0.42 |
February | 0.121068E+10 | 0.00 | 0.00 | 150851.41 | 0.00 | 0.112542E+10 | 0.135471E+09 | 0.00 | 0.42 |
March | 0.238396E+10 | 0.00 | 0.00 | 1214124.62 | 0.00 | 0.449530E+09 | 0.970584E+09 | 0.00 | 0.55 |
April | 0.204100E+10 | 7544.97 | 0.00 | 3174654.27 | 0.00 | 0.171943E+09 | 0.181209E+10 | 0.00 | 0.74 |
May | 0.144279E+10 | 51820604.92 | 0.00 | 5130535.79 | 417136.06 | 523164.66 | 0.234296E+10 | 0.00 | 1.01 |
June | 0.200333E+09 | 0.110483E+10 | 0.00 | 3073113.47 | 33827424.52 | 0.00 | 0.590564E+09 | 0.00 | 0.79 |
July | 6142571.79 | 0.197892E+10 | 0.00 | 426615.29 | 46599256.19 | 0.00 | 23636374.85 | 0.00 | 0.52 |
August | 72096423.05 | 0.148869E+10 | 0.00 | 3240158.38 | 20711637.89 | 0.00 | 0.296415E+09 | 0.00 | 0.85 |
September | 0.718794E+09 | 0.571393E+09 | 0.00 | 3344893.17 | 71112686.94 | 0.00 | 0.954735E+09 | 0.00 | 0.79 |
October | 0.157464E+10 | 94353162.18 | 0.00 | 2441414.10 | 13458131.37 | 52148602.11 | 0.106857E+10 | 0.00 | 0.75 |
November | 0.227393E+10 | 0.00 | 0.00 | 242900.17 | 0.00 | 0.592408E+09 | 0.217006E+09 | 0.00 | 0.50 |
December | 0.154650E+10 | 0.00 | 0.00 | 2989.69 | 0.00 | 0.115708E+10 | 8341286.29 | 0.00 | 0.42 |
Annual Sum or Average | 0.146780E+11 | 0.529002E+10 | 0.00 | 22467623.48 | 0.186126E+09 | 0.493417E+10 | 0.846760E+10 | 0.00 | 0.65 |
Minimum of Months | 6142571.79 | 0.00 | 0.00 | 2989.69 | 0.00 | 0.00 | 8341286.29 | 0.00 | 0.42 |
Maximum of Months | 0.238396E+10 | 0.197892E+10 | 0.00 | 5130535.79 | 71112686.94 | 0.138512E+10 | 0.234296E+10 | 0.00 | 1.01 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2020-06-03 19:59:48
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.240657E+09 | 0.00 | 0.00 | 0.251972E+09 | 0.00 | 0.00 | 0.172341E+11 | 0.00 | 0.32 |
February | 0.139149E+09 | 0.00 | 0.00 | 0.482672E+09 | 0.00 | 0.00 | 0.171343E+11 | 0.00 | 0.32 |
March | 4933523.85 | 0.00 | 0.00 | 0.739155E+09 | 0.00 | 0.00 | 0.148969E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.815929E+09 | 0.00 | 0.00 | 0.902621E+10 | 0.00 | 0.32 |
May | 0.00 | 0.198801E+09 | 0.00 | 0.185758E+09 | 0.00 | 0.00 | 0.488665E+10 | 0.00 | 0.33 |
June | 0.00 | 0.359423E+10 | 0.00 | 0.109808E+09 | 0.00 | 0.00 | 0.767895E+09 | 0.00 | 0.34 |
July | 0.00 | 0.816430E+10 | 0.00 | 10259361.08 | 0.00 | 0.00 | 10882691.22 | 0.00 | 0.31 |
August | 0.00 | 0.607359E+10 | 0.00 | 0.172896E+09 | 0.00 | 0.00 | 0.309981E+09 | 0.00 | 0.35 |
September | 0.00 | 0.201592E+10 | 0.00 | 0.114333E+09 | 0.00 | 0.00 | 0.207985E+10 | 0.00 | 0.32 |
October | 0.00 | 0.359367E+09 | 0.00 | 0.315694E+09 | 0.00 | 0.00 | 0.537261E+10 | 0.00 | 0.32 |
November | 7930146.86 | 0.00 | 0.00 | 0.644080E+09 | 0.00 | 0.00 | 0.116490E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.860099E+09 | 0.00 | 0.00 | 0.160789E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.392670E+09 | 0.204062E+11 | 0.00 | 0.470266E+10 | 0.00 | 0.00 | 0.994473E+11 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 10259361.08 | 0.00 | 0.00 | 10882691.22 | 0.00 | 0.31 |
Maximum of Months | 0.240657E+09 | 0.816430E+10 | 0.00 | 0.860099E+09 | 0.00 | 0.00 | 0.172341E+11 | 0.00 | 0.35 |