Program Version:EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:40
Tabular Output Report in Format: HTML
Building: OfficeMedium
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2020-06-03 19:40:53
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2485.97 | 498.97 | 498.97 |
Net Site Energy | 2485.97 | 498.97 | 498.97 |
Total Source Energy | 7147.36 | 1434.58 | 1434.58 |
Net Source Energy | 7147.36 | 1434.58 | 1434.58 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 0.300 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil #1 | 1.050 |
Fuel Oil #2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 4982.19 |
Net Conditioned Building Area | 4982.19 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 285.23 | 261.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 122.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 225.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 816.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 33.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 91.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 86.76 | 0.00 | 0.00 | 0.00 | 271.06 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 2137.58 | 348.40 | 0.00 | 0.00 | 0.00 | 271.06 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Additional Fuel [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 285.23 | 261.64 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 122.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 562.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 225.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 641.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 164.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 10.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 33.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 91.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 86.76 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.06 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 158.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 100.20 | 69.93 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 170.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.04 | 69.93 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Additional Fuel Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 158.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 100.20 | 69.93 | 0.00 | 0.00 | 0.00 | 0.05 |
Other | 170.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 429.04 | 69.93 | 0.00 | 0.00 | 0.00 | 0.05 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 2137.576 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 2137.576 | 100.00 |
Total On-Site and Utility Electric Sources | 2137.576 | 100.00 |
Total Electricity End Uses | 2137.576 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 271.06 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 271.06 | 100.00 |
Total Water End Uses | 271.06 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 461.33 |
Time Setpoint Not Met During Occupied Cooling | 12.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1836.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Meter |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
| Meter |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Meter |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
| Meter |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Meter |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Meter |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Meter |ZoneCoolingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneHeatingSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ZoneElectricSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |SpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | FIRSTFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |ComfortReportSimple55Monthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |OccupantComfortDataSummaryMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |DXReportMonthly
| PACU_VAV_BOT_COOLC DXCOIL | PACU_VAV_MID_COOLC DXCOIL | PACU_VAV_TOP_COOLC DXCOIL |WindowReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |WindowEnergyZoneSummaryMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SHWSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| CORE_BOTTOM VAV BOX REHEAT COIL | CORE_MID VAV BOX REHEAT COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | PACU_VAV_BOT_HEATC | PACU_VAV_MID_HEATC | PACU_VAV_TOP_HEATC | PACU_VAV_BOT_COOLC DXCOIL | PACU_VAV_MID_COOLC DXCOIL | PACU_VAV_TOP_COOLC DXCOIL |PlantLoopDemandReportMonthly
| SHWSYS1 |FanReportMonthly
| PACU_VAV_BOT FAN | PACU_VAV_MID FAN | PACU_VAV_TOP FAN |PumpReportMonthly
| SHWSYS1 PUMP |CondLoopDemandReportMonthly
| SHWSYS1 |ZoneTemperatureOscillationReportMonthly
| CORE_BOTTOM | TOPFLOOR_PLENUM | MIDFLOOR_PLENUM | FIRSTFLOOR_PLENUM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |AirLoopSystemEnergyAndWaterUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentLoadsMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |AirLoopSystemComponentEnergyUseMonthly
| PACU_VAV_BOT | PACU_VAV_MID | PACU_VAV_TOP |MechanicalVentilationLoadsMonthly
| CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
GeneralValue | |
Program Version and Build | EnergyPlus, Version 9.1.0-Unknown, YMD=2020.06.03 19:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Above Ground Wall Area [m2] | 1977.67 | 593.30 | 395.53 | 593.30 | 395.53 |
Window Opening Area [m2] | 652.62 | 195.79 | 130.53 | 195.79 | 130.53 |
Gross Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Above Ground Window-Wall Ratio [%] | 33.00 | 33.00 | 33.00 | 33.00 | 33.00 |
Total | |
Gross Roof Area [m2] | 1660.73 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
CORE_BOTTOM | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.7639 | 18.58 | 41.0466 |
TOPFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
FIRSTFLOOR_PLENUM | 1660.73 | Yes | No | 2024.76 | 1.00 | 202.84 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
CORE_MID | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.7639 | 18.58 | 8.0700 |
CORE_TOP | 983.54 | Yes | Yes | 2698.04 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.7639 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.7639 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.7639 | 18.58 | 8.0695 |
PERIMETER_TOP_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.7639 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.7639 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.7639 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.7639 | 18.58 | 8.0695 |
PERIMETER_BOT_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.7639 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.7639 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_3 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.7639 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 131.26 | Yes | Yes | 360.08 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.7639 | 18.58 | 8.0695 |
PERIMETER_MID_ZN_1 | 207.34 | Yes | Yes | 568.77 | 1.00 | 136.92 | 0.00 | 65.26 | 65.26 | 10.7639 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 131.25 | Yes | Yes | 360.05 | 1.00 | 91.28 | 0.00 | 43.51 | 43.51 | 10.7639 | 18.58 | 8.0700 |
Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.7639 | 18.58 | 14.5799 | |||
Conditioned Total | 4982.19 | 13667.13 | 1369.16 | 0.00 | 652.62 | 652.62 | 10.7639 | 18.58 | 14.5799 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 4982.19 | 6074.28 | 608.51 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
End UsesElectricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 02-JAN-08:09 | 07-JAN-07:00 | - | - | - | 02-JAN-12:09 |
Heating | 138016.81 | 115742.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 49183.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 58665.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 2305.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 4418.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 2003.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 252595.59 | 117746.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Propane [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 138016.81 | 115742.66 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 49183.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 22155.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 323.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 2305.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 4418.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 0.00 | 2003.43 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Additional Fuel [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 903.31 | 283.62 | 0.00 | 0.00 | 0.00 |
Cooling | 388.65 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1782.13 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 714.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 2585.05 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 107.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 288.62 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.46 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 94.05 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6769.70 | 377.66 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 181.31 | 56.93 | 0.00 | 0.00 | 0.00 |
Cooling | 78.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 357.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 143.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 518.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 57.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.88 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1358.78 | 75.80 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Additional Fuel [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 181.31 | 56.93 | 0.00 | 0.00 | 0.00 |
Cooling | 78.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 357.70 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 143.40 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 518.86 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 21.48 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 57.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.09 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 18.88 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1358.78 | 75.80 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
AirTerminal:SingleDuct:VAV:ReheatDesign Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Flow Fraction during Reheat [] | |
CORE_BOTTOM VAV BOX COMPONENT | 3.86 | 0.193929 | 0.300000 | 1.16 | 0.001179 | 0.300000 |
CORE_MID VAV BOX COMPONENT | 2.33 | 0.321329 | 0.317000 | 0.739358 | 0.000752 | 0.317000 |
CORE_TOP VAV BOX COMPONENT | 2.46 | 0.305118 | 0.300000 | 0.736883 | 0.000749 | 0.300000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.654711 | 0.241315 | 0.300000 | 0.196413 | 0.000947 | 0.300000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 0.812239 | 0.123143 | 0.300000 | 0.243672 | 0.001856 | 0.300000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.13 | 0.139378 | 0.300000 | 0.340065 | 0.001640 | 0.300000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 0.904831 | 0.110535 | 0.300000 | 0.271449 | 0.002068 | 0.300000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.514205 | 0.307254 | 0.300000 | 0.154262 | 0.000744 | 0.300000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 0.686046 | 0.145795 | 0.300000 | 0.205814 | 0.001568 | 0.300000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 0.910082 | 0.173602 | 0.300000 | 0.273025 | 0.001317 | 0.300000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 0.762689 | 0.131135 | 0.300000 | 0.228807 | 0.001743 | 0.300000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 0.569552 | 0.277397 | 0.317000 | 0.180548 | 0.000871 | 0.317000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 0.832535 | 0.120141 | 0.317000 | 0.263914 | 0.002011 | 0.317000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 1.06 | 0.149224 | 0.317000 | 0.335626 | 0.001619 | 0.317000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 0.854057 | 0.117106 | 0.317000 | 0.270736 | 0.002063 | 0.317000 |
Design Size Nominal Capacity [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 38169.69 |
CORE_MID VAV BOX REHEAT COIL | 24341.55 |
CORE_TOP VAV BOX REHEAT COIL | 34805.20 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 14737.08 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 9685.20 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 14723.85 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 9598.04 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 11513.72 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 7650.27 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 11491.21 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 7566.52 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 11521.68 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 8688.71 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 11533.01 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 8913.32 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PACU_VAV_BOT | 2.02 | 2.02 | 6.74 | 2.02 | 5.86 | 5.86 | 0.300000 | 0.344795 | 5.86 |
PACU_VAV_MID | 1.79 | 1.79 | 5.65 | 1.79 | 4.55 | 4.55 | 0.300000 | 0.393072 | 4.55 |
PACU_VAV_TOP | 1.79 | 1.79 | 5.96 | 2.54 | 5.22 | 5.22 | 0.300000 | 0.486094 | 5.22 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PACU_VAV_BOT_OA_CONTROLLER | 5.86 | 1.83 |
PACU_VAV_MID_OA_CONTROLLER | 4.55 | 1.79 |
PACU_VAV_TOP_OA_CONTROLLER | 5.22 | 1.74 |
Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
PACU_VAV_BOT_COOLC DXCOIL | 5.86 | 107139.90 | 0.800002 | 1.95 | 35709.73 | 0.800002 |
PACU_VAV_MID_COOLC DXCOIL | 4.55 | 85939.70 | 0.796525 | 1.52 | 28643.70 | 0.796525 |
PACU_VAV_TOP_COOLC DXCOIL | 5.22 | 96532.00 | 0.800147 | 1.74 | 32174.11 | 0.800147 |
Design Size Nominal Capacity [W] | |
PACU_VAV_BOT_HEATC | 35660.64 |
PACU_VAV_MID_HEATC | 27704.30 |
PACU_VAV_TOP_HEATC | 31757.89 |
Design Size Maximum Flow Rate [m3/s] | |
PACU_VAV_BOT FAN | 5.86 |
PACU_VAV_MID FAN | 4.55 |
PACU_VAV_TOP FAN | 5.22 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
SHWSYS1 | 0.000054 | 0.006435 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
SHWSYS1 PUMP | 0.000054 | 6.85 |
Use Side Design Flow Rate [m3/s] | |
SHWSYS1 WATER HEATER | 0.000054 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
VersionVersion ID | |
1 | 9.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeMedium | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 18 | 167 | 24 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 1.37 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 0.00 | 2.74 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
2 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 11.28 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 10.67 | 11.89 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 10 | 0 | 0 | No |
3 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 7.32 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 6.71 | 7.92 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
4 | FIRSTFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 3.35 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 33.27 | 2.74 | 3.96 | 1.22 | 2024.76 | TARP | TARP | 1660.73 | 202.84 | 202.84 | 0.00 | 14 | 0 | 0 | No |
5 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 5.33 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 3.96 | 6.71 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
6 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 16.64 | 9.30 | 1 | 1 | 1 | 4.57 | 45.34 | 4.57 | 28.70 | 7.92 | 10.67 | 2.74 | 2698.04 | TARP | TARP | 983.54 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
7 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
8 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 9.30 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
9 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 9.30 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 7.92 | 10.67 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
10 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 9.30 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 7.92 | 10.67 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
11 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
12 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 1.37 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
13 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 1.37 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 67.75 | 65.26 | 6 | 5 | 0 | Yes |
14 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 0.00 | 2.74 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 45.82 | 43.51 | 6 | 3 | 0 | Yes |
15 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 31.11 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 28.70 | 33.27 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
16 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 47.82 | 16.64 | 5.33 | 1 | 1 | 1 | 45.34 | 49.91 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.08 | TARP | TARP | 131.26 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
17 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 24.96 | 2.16 | 5.33 | 1 | 1 | 1 | 0.00 | 49.91 | 0.00 | 4.57 | 3.96 | 6.71 | 2.74 | 568.77 | TARP | TARP | 207.34 | 136.92 | 71.65 | 65.26 | 6 | 1 | 0 | Yes |
18 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.09 | 16.64 | 5.33 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 33.27 | 3.96 | 6.71 | 2.74 | 360.05 | TARP | TARP | 131.25 | 91.28 | 47.77 | 43.51 | 6 | 1 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | CORE_BOTTOM | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.764 | 41.047 | 0.000 | 0.000 | 0.000 | 0.000 | 51.811 | No |
2 | TOPFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
3 | MIDFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
4 | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
5 | CORE_MID | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
6 | CORE_TOP | 983.54 | 52.9 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
7 | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
8 | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.764 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.833 | No |
9 | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
10 | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
11 | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
12 | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.764 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.833 | No |
13 | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
14 | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
15 | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
16 | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 18.579 | 5.382E-002 | 10.764 | 8.069 | 0.000 | 0.000 | 0.000 | 0.000 | 18.833 | No |
17 | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
18 | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 18.579 | 5.382E-002 | 10.764 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 18.834 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | |
1 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
2 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
3 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 983.54 | 52.9 | 52.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
4 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
5 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
6 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
7 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
8 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
9 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
10 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
11 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
12 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
13 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
14 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 11.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
15 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 7.1 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | CORE_BOTTOM_LIGHTS | BLDG_LIGHT_SCH | CORE_BOTTOM | 983.54 | 52.9 | 10586.700 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10586.700 |
2 | CORE_MID_LIGHTS | BLDG_LIGHT_SCH | CORE_MID | 983.54 | 52.9 | 10586.700 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10586.700 |
3 | CORE_TOP_LIGHTS | BLDG_LIGHT_SCH | CORE_TOP | 983.54 | 52.9 | 10586.700 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 10586.700 |
4 | PERIMETER_TOP_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 2231.769 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2231.769 |
5 | PERIMETER_TOP_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1412.894 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1412.894 |
6 | PERIMETER_TOP_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 2231.769 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2231.769 |
7 | PERIMETER_TOP_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1412.802 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1412.802 |
8 | PERIMETER_BOT_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 2231.769 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2231.769 |
9 | PERIMETER_BOT_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1412.894 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1412.894 |
10 | PERIMETER_BOT_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 2231.769 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2231.769 |
11 | PERIMETER_BOT_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1412.802 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1412.802 |
12 | PERIMETER_MID_ZN_3_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 2231.769 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2231.769 |
13 | PERIMETER_MID_ZN_2_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1412.894 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1412.894 |
14 | PERIMETER_MID_ZN_1_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 2231.769 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2231.769 |
15 | PERIMETER_MID_ZN_4_LIGHTS | BLDG_LIGHT_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1412.802 | 10.764 | 199.980 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1412.802 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
2 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
3 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 983.54 | 52.9 | 7937.156 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 7937.156 |
4 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
5 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
6 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
7 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
8 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
9 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
10 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
11 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
12 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 1673.214 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.214 |
13 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 1059.217 | 8.069 | 149.921 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.217 |
14 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 1673.203 | 8.070 | 149.929 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1673.203 |
15 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 1059.210 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1059.210 |
16 | CORE_BOTTOM_ELEVATORS_EQUIP | BLDG_ELEVATORS | CORE_BOTTOM | 983.54 | 52.9 | 32109.890 | 32.647 | 606.549 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 22155.824 |
17 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | CORE_BOTTOM | 983.54 | 52.9 | 323.800 | 0.329 | 6.117 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 323.800 | 323.800 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.975 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
7 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
8 | NONRES_EXT_WALL | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
9 | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 30 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 31 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 32 | 2 | 7 | 0.167 | 0.3192 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 33 | 2 | 7 | 0.167 | 0.3371 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | CORE_BOT_ZN_5_FLOOR_FFACTOR | 34 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2516 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
9 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
10 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
11 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
12 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
13 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
15 | NONRES_EXTERIOR_WALL_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
16 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
17 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
19 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
20 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
21 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.056 |
22 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
23 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.890 |
24 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
25 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
26 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.9747885 | 3.9747885 | 3.9747885 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
23 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
24 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
25 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
26 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
27 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
28 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
29 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
30 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
31 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
32 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
33 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
34 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
35 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
36 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
37 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
38 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
39 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
40 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
41 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
42 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
43 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
44 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
45 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
46 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
47 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
48 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
49 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
50 | 7 | -0.13059908E-08 | -0.16504735E-15 | 0.90649122E-14 | -0.12541312E-15 |
51 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
52 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
53 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
54 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
55 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
56 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
57 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
58 | 7 | -0.12346633E-08 | -0.14425327E-15 | 0.91357699E-14 | -0.10087110E-15 |
59 | 6 | 0.94177090E-05 | 0.64929528E-08 | 0.31789869E-02 | -0.26668006E-04 |
60 | 5 | -0.68205191E-03 | 0.38502154E-05 | -0.22310594 | 0.19506899E-02 |
61 | 4 | 0.15716902E-01 | 0.17535208E-03 | 4.8192406 | -0.45165923E-01 |
62 | 3 | -0.13809356 | 0.13952366E-02 | -37.963195 | 0.39801023 |
63 | 2 | 0.49043520 | 0.23220647E-02 | 116.37063 | -1.4164235 |
64 | 1 | -0.70792287 | 0.70803996E-03 | -143.84059 | 2.0479434 |
65 | 0 | 0.34515858 | 0.17069463E-04 | 60.838472 | |
66 | 7 | -0.13059908E-08 | -0.16504702E-15 | 0.90649122E-14 | -0.12541312E-15 |
67 | 6 | 0.89164571E-05 | 0.61445766E-08 | 0.31804070E-02 | -0.26679919E-04 |
68 | 5 | -0.64531733E-03 | 0.36428408E-05 | -0.22318667 | 0.19514025E-02 |
69 | 4 | 0.14868215E-01 | 0.16589759E-03 | 4.8205855 | -0.45178851E-01 |
70 | 3 | -0.13063200 | 0.13198961E-02 | -37.970795 | 0.39809422 |
71 | 2 | 0.46393162 | 0.21965806E-02 | 116.38542 | -1.4166214 |
72 | 1 | -0.66966470 | 0.66967549E-03 | -143.84930 | 2.0480865 |
73 | 0 | 0.32650513 | 0.16166393E-04 | 60.838472 | |
74 | 7 | -0.12345751E-08 | -0.14398051E-15 | 0.92894684E-14 | -0.10085648E-15 |
75 | 6 | 0.94183649E-05 | 0.64934092E-08 | 0.31789851E-02 | -0.26667991E-04 |
76 | 5 | -0.68209995E-03 | 0.38504865E-05 | -0.22310583 | 0.19506890E-02 |
77 | 4 | 0.15718012E-01 | 0.17536444E-03 | 4.8192388 | -0.45165906E-01 |
78 | 3 | -0.13810332 | 0.13953351E-02 | -37.963185 | 0.39801012 |
79 | 2 | 0.49046985 | 0.23222288E-02 | 116.37061 | -1.4164232 |
80 | 1 | -0.70797289 | 0.70809005E-03 | -143.84058 | 2.0479432 |
81 | 0 | 0.34518296 | 0.17070678E-04 | 60.838472 | |
82 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
83 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
84 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
85 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
86 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
87 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
88 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
89 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
90 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.51_SHGC_0.4 | 29 | 1 | VerySmooth | 2.899 | 0.395 | 0.315 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER | SpectralAverage | 1.82741E-002 | 0.31435 | 0.46434 | 0.46434 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.10459 | 1.00000 | No |
Calculation Method | Value {days} | Allowable Number Figures in Shadow Overlap {} | Polygon Clipping Algorithm | Sky Diffuse Modeling Algorithm | External Shading Calculation Method | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | AverageOverDaysInFrequency | 30 | 15000 | SutherlandHodgman | SimpleSkyDiffuseModeling | InternalCalculation | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | 0.3785 | 29307.1 | 0.963 | 0.2202 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
2 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
3 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
4 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
5 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
6 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
7 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
9 | PERIMETER_TOP_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
11 | PERIMETER_TOP_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
12 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
13 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
14 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
15 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
16 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
17 | BUILDING_ROOF | 0 | 1660.73 | 183.01 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
18 | PERIMETER_MID_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
19 | PERIMETER_MID_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
21 | PERIMETER_MID_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
22 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
23 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
24 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
25 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
26 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
31 | iz-CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
33 | PERIMETER_BOT_PLENUM_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
35 | PERIMETER_BOT_PLENUM_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
36 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
37 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
38 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
39 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
40 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
41 | iz-PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
42 | iz-PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
43 | iz-PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
44 | iz-PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
45 | iz-CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 166.37 | 39.93 | 0.00 | 0 | No | No |
46 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
47 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
48 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
49 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
50 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
51 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
52 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
53 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
54 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
55 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
56 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
57 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
58 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
59 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 30.31 | -999.00 | 0 | No | No |
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
65 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
66 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
68 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
72 | iz-CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
73 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
74 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
81 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
82 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
84 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
88 | iz-CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
89 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
90 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
101 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
102 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
104 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
110 | iz-CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
111 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
112 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
123 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
124 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
126 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
132 | iz-CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
133 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
134 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
136 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 593.30 | 143.75 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
138 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
140 | iz-CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
141 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
142 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
144 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 395.53 | 143.75 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
148 | iz-CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
149 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
150 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 3 | No | No |
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 593.30 | 123.60 | 11.89 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 2 | No | No |
154 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
157 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
158 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 49.91 | 7.61 | 0.48 | 0 | No | No |
160 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 3 | No | No |
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 395.53 | 90.32 | 11.89 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 2 | No | No |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
164 | iz-CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
165 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
166 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 33.27 | 6.94 | 0.48 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 207.34 | 11.2 | 0.140 | 6.763E-004 | 1.024E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 131.26 | 7.1 | 9.348E-002 | 7.122E-004 | 1.024E-003 | 0.935 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 207.34 | 11.2 | 0.140 | 6.763E-004 | 1.024E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 131.25 | 7.1 | 9.348E-002 | 7.122E-004 | 1.024E-003 | 0.935 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 207.34 | 11.2 | 0.144 | 6.956E-004 | 1.024E-003 | 0.913 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 131.26 | 7.1 | 9.548E-002 | 7.274E-004 | 1.024E-003 | 0.955 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 0.144 | 6.956E-004 | 1.024E-003 | 0.913 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_BOT_ZN_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | PERIMETER_BOT_ZN_1 | 207.34 | 11.2 | 1.043 | 5.030E-003 | 7.407E-003 | 6.602 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 131.25 | 7.1 | 9.548E-002 | 7.274E-004 | 1.024E-003 | 0.955 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 207.34 | 11.2 | 0.140 | 6.763E-004 | 1.024E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 131.26 | 7.1 | 9.348E-002 | 7.122E-004 | 1.024E-003 | 0.935 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 207.34 | 11.2 | 0.140 | 6.763E-004 | 1.024E-003 | 0.888 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 131.25 | 7.1 | 9.348E-002 | 7.122E-004 | 1.024E-003 | 0.935 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | FIRSTFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | FIRSTFLOOR_PLENUM | 1660.73 | 0.0 | 0.208 | 1.251E-004 | 1.024E-003 | 0.369 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 1660.73 | 0.0 | 0.208 | 1.251E-004 | 1.024E-003 | 0.369 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 1660.73 | 0.0 | 0.208 | 1.251E-004 | 1.115E-004 | 0.369 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | CORE_BOTTOM | Mixing/Well-Stirred |
2 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
3 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
4 | FIRSTFLOOR_PLENUM | Mixing/Well-Stirred |
5 | CORE_MID | Mixing/Well-Stirred |
6 | CORE_TOP | Mixing/Well-Stirred |
7 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
8 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
9 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
10 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
11 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
12 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
13 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
14 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
15 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
16 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
17 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
18 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | CORE_BOTTOM | Cooling | 52836.33770 | 52836.33770 | 3.86459 | 3.86459 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 983.53657 | 52.93867 | 0.49961 | 0.00000 |
2 | CORE_BOTTOM | Heating | 8201.51075 | 8201.51075 | 0.35000 | 0.49961 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.49961 | 0.00000 |
3 | CORE_MID | Cooling | 31934.30634 | 31934.30634 | 2.33236 | 2.33236 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 983.53657 | 52.93867 | 0.49961 | 0.00000 |
4 | CORE_MID | Heating | 13409.06757 | 13409.06757 | 0.57515 | 0.57515 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.49961 | 0.00000 |
5 | CORE_TOP | Cooling | 33324.77043 | 33324.77043 | 2.45628 | 2.45628 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.79438E-003 | 983.53657 | 52.93867 | 0.49961 | 0.00000 |
6 | CORE_TOP | Heating | 24522.42913 | 24522.42913 | 1.05718 | 1.05718 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 983.53657 | 52.93867 | 0.49961 | 0.00000 |
7 | PERIMETER_TOP_ZN_3 | Cooling | 8882.70095 | 8882.70095 | 0.65471 | 0.65471 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 29.29600 | 8.79438E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
8 | PERIMETER_TOP_ZN_3 | Heating | 10353.77048 | 10353.77048 | 0.44763 | 0.44763 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
9 | PERIMETER_TOP_ZN_2 | Cooling | 11020.01747 | 11020.01747 | 0.81224 | 0.81224 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 23.02133 | 8.79438E-003 | 131.26219 | 7.06516 | 6.66770E-002 | 0.00000 |
10 | PERIMETER_TOP_ZN_2 | Heating | 6803.74586 | 6803.74586 | 0.29418 | 0.29418 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 6.66770E-002 | 0.00000 |
11 | PERIMETER_TOP_ZN_1 | Cooling | 15379.36596 | 15379.36596 | 1.13355 | 1.13355 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
12 | PERIMETER_TOP_ZN_1 | Heating | 10344.52194 | 10344.52194 | 0.44723 | 0.44723 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
13 | PERIMETER_TOP_ZN_4 | Cooling | 12276.27344 | 12276.27344 | 0.90483 | 0.90483 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 131.25358 | 7.06470 | 6.66726E-002 | 0.00000 |
14 | PERIMETER_TOP_ZN_4 | Heating | 6742.70167 | 6742.70167 | 0.29153 | 0.29153 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 6.66726E-002 | 0.00000 |
15 | PERIMETER_BOT_ZN_3 | Cooling | 6976.38137 | 6976.38137 | 0.51421 | 0.51421 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 29.40000 | 8.79438E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
16 | PERIMETER_BOT_ZN_3 | Heating | 8095.29012 | 8095.29012 | 0.34972 | 0.34972 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
17 | PERIMETER_BOT_ZN_2 | Cooling | 9374.39452 | 9374.39452 | 0.68605 | 0.68605 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 21.70400 | 8.79438E-003 | 131.26219 | 7.06516 | 6.66770E-002 | 0.00000 |
18 | PERIMETER_BOT_ZN_2 | Heating | 5377.90799 | 5377.90799 | 0.23237 | 0.23237 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 6.66770E-002 | 0.00000 |
19 | PERIMETER_BOT_ZN_1 | Cooling | 12347.44728 | 12347.44728 | 0.91008 | 0.91008 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 29.05333 | 8.79438E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
20 | PERIMETER_BOT_ZN_1 | Heating | 8079.54766 | 8079.54766 | 0.34904 | 0.34904 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
21 | PERIMETER_BOT_ZN_4 | Cooling | 10347.73703 | 10347.73703 | 0.76269 | 0.76269 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 26.90400 | 8.79438E-003 | 131.25358 | 7.06470 | 6.66726E-002 | 0.00000 |
22 | PERIMETER_BOT_ZN_4 | Heating | 5319.26629 | 5319.26629 | 0.22983 | 0.22983 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 6.66726E-002 | 0.00000 |
23 | PERIMETER_MID_ZN_3 | Cooling | 7727.29441 | 7727.29441 | 0.56955 | 0.56955 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 29.40000 | 8.79438E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
24 | PERIMETER_MID_ZN_3 | Heating | 8101.39818 | 8101.39818 | 0.34996 | 0.34996 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
25 | PERIMETER_MID_ZN_2 | Cooling | 11295.53710 | 11295.53710 | 0.83253 | 0.83253 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 22.36267 | 8.79438E-003 | 131.26219 | 7.06516 | 6.66770E-002 | 0.00000 |
26 | PERIMETER_MID_ZN_2 | Heating | 5385.61899 | 5385.61899 | 0.23269 | 0.23269 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.26219 | 7.06516 | 6.66770E-002 | 0.00000 |
27 | PERIMETER_MID_ZN_1 | Cooling | 14364.58693 | 14364.58693 | 1.05876 | 1.05876 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 28.96667 | 8.79438E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
28 | PERIMETER_MID_ZN_1 | Heating | 8109.34635 | 8109.34635 | 0.35031 | 0.35031 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 207.33814 | 11.15994 | 0.10532 | 0.00000 |
29 | PERIMETER_MID_ZN_4 | Cooling | 11587.38797 | 11587.38797 | 0.85406 | 0.85406 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 27.77067 | 8.79438E-003 | 131.25358 | 7.06470 | 6.66726E-002 | 0.00000 |
30 | PERIMETER_MID_ZN_4 | Heating | 5327.20140 | 5327.20140 | 0.23016 | 0.23016 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -4.20000 | 2.69032E-003 | 131.25358 | 7.06470 | 6.66726E-002 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PACU_VAV_BOT | Cooling | Sensible | 89929.55 | 5.86228 | 5.86228 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | PACU_VAV_BOT | Heating | Sensible | 33671.05 | 1.66056 | 1.66056 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
3 | PACU_VAV_MID | Cooling | Sensible | 72311.12 | 4.55433 | 4.55433 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | PACU_VAV_MID | Heating | Sensible | 35246.56 | 1.73826 | 1.73826 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 |
5 | PACU_VAV_TOP | Cooling | Sensible | 80876.65 | 5.22071 | 5.22071 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | PACU_VAV_TOP | Heating | Sensible | 35353.86 | 2.53775 | 2.53775 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 16:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.86459 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19393 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.15938 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.17878E-003 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
7 | Coil:Heating:Electric | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 38169.68684 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33236 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.32133 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73936 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.51734E-004 |
13 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31700 |
14 | Coil:Heating:Electric | CORE_MID VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 24341.54808 |
15 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.45628 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30512 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.73688 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.49218E-004 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
21 | Coil:Heating:Electric | CORE_TOP VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 34805.19742 |
22 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65471 |
23 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24131 |
24 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
25 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19641 |
26 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.47310E-004 |
27 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
28 | Coil:Heating:Electric | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14737.07529 |
29 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.81224 |
30 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12314 |
31 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
32 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24367 |
33 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85637E-003 |
34 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
35 | Coil:Heating:Electric | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9685.19927 |
36 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.13355 |
37 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13938 |
38 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
39 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34006 |
40 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64015E-003 |
41 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
42 | Coil:Heating:Electric | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 14723.85371 |
43 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90483 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11053 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27145 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06813E-003 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
49 | Coil:Heating:Electric | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 9598.03682 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.51421 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30725 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15426 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 7.44010E-004 |
55 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
56 | Coil:Heating:Electric | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11513.71651 |
57 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68605 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14579 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20581 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.56796E-003 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
63 | Coil:Heating:Electric | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7650.26518 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.91008 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17360 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27302 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31681E-003 |
69 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
70 | Coil:Heating:Electric | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11491.21277 |
71 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76269 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13114 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22881 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.74324E-003 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
77 | Coil:Heating:Electric | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 7566.52213 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56955 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27740 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18055 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 8.70789E-004 |
83 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31700 |
84 | Coil:Heating:Electric | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11521.67526 |
85 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.83253 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12014 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26391 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01058E-003 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31700 |
91 | Coil:Heating:Electric | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8688.71098 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05876 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14922 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33563 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61874E-003 |
97 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31700 |
98 | Coil:Heating:Electric | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 11533.00881 |
99 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.85406 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11711 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31700 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27074 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.06269E-003 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31700 |
105 | Coil:Heating:Electric | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Nominal Capacity [W] | 8913.32449 |
106 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.02128 |
107 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.02128 |
108 | AirLoopHVAC | PACU_VAV_BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.73762 |
109 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.02128 |
110 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.86228 |
111 | AirLoopHVAC | PACU_VAV_BOT | Adjusted Main Design Air Flow Rate [m3/s] | 5.86228 |
112 | AirLoopHVAC | PACU_VAV_BOT | User Heating Air Flow Ratio [] | 0.30000 |
113 | AirLoopHVAC | PACU_VAV_BOT | Calculated Heating Air Flow Ratio [] | 0.34479 |
114 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.79018 |
115 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.79018 |
116 | AirLoopHVAC | PACU_VAV_MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.64726 |
117 | AirLoopHVAC | PACU_VAV_MID | Adjusted Heating Design Air Flow Rate [m3/s] | 1.79018 |
118 | AirLoopHVAC | PACU_VAV_MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.55433 |
119 | AirLoopHVAC | PACU_VAV_MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.55433 |
120 | AirLoopHVAC | PACU_VAV_MID | User Heating Air Flow Ratio [] | 0.30000 |
121 | AirLoopHVAC | PACU_VAV_MID | Calculated Heating Air Flow Ratio [] | 0.39307 |
122 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.78848 |
123 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.78848 |
124 | AirLoopHVAC | PACU_VAV_TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.96161 |
125 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 2.53775 |
126 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.22071 |
127 | AirLoopHVAC | PACU_VAV_TOP | Adjusted Main Design Air Flow Rate [m3/s] | 5.22071 |
128 | AirLoopHVAC | PACU_VAV_TOP | User Heating Air Flow Ratio [] | 0.30000 |
129 | AirLoopHVAC | PACU_VAV_TOP | Calculated Heating Air Flow Ratio [] | 0.48609 |
130 | AirLoopHVAC | PACU_VAV_BOT | Design Supply Air Flow Rate [m3/s] | 5.86228 |
131 | AirLoopHVAC | PACU_VAV_MID | Design Supply Air Flow Rate [m3/s] | 4.55433 |
132 | AirLoopHVAC | PACU_VAV_TOP | Design Supply Air Flow Rate [m3/s] | 5.22071 |
133 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.86228 |
134 | Controller:OutdoorAir | PACU_VAV_BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.82930 |
135 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.86228 |
136 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 107139.89874 |
137 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80000 |
138 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.95390 |
139 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 35709.72825 |
140 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80000 |
141 | Coil:Heating:Fuel | PACU_VAV_BOT_HEATC | Design Size Nominal Capacity [W] | 35660.64151 |
142 | Fan:VariableVolume | PACU_VAV_BOT FAN | Design Size Maximum Flow Rate [m3/s] | 5.86228 |
143 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.55433 |
144 | Controller:OutdoorAir | PACU_VAV_MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.79028 |
145 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 4.55433 |
146 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 85939.69953 |
147 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size High Speed Rated Sensible Heat Ratio | 0.79652 |
148 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.51796 |
149 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 28643.70185 |
150 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.79652 |
151 | Coil:Heating:Fuel | PACU_VAV_MID_HEATC | Design Size Nominal Capacity [W] | 27704.30277 |
152 | Fan:VariableVolume | PACU_VAV_MID FAN | Design Size Maximum Flow Rate [m3/s] | 4.55433 |
153 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.22071 |
154 | Controller:OutdoorAir | PACU_VAV_TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.74445 |
155 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 5.22071 |
156 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 96531.99670 |
157 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80015 |
158 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 1.74006 |
159 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 32174.11450 |
160 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80015 |
161 | Coil:Heating:Fuel | PACU_VAV_TOP_HEATC | Design Size Nominal Capacity [W] | 31757.89361 |
162 | Fan:VariableVolume | PACU_VAV_TOP FAN | Design Size Maximum Flow Rate [m3/s] | 5.22071 |
163 | PlantLoop | SHWSYS1 | Maximum Loop Flow Rate [m3/s] | 5.36267E-005 |
164 | PlantLoop | SHWSYS1 | Plant Loop Volume [m3] | 6.43520E-003 |
165 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Flow Rate [m3/s] | 5.36267E-005 |
166 | Pump:ConstantSpeed | SHWSYS1 PUMP | Design Power Consumption [W] | 6.85023 |
167 | WaterHeater:Mixed | SHWSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 5.36267E-005 |
DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
1 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_BOT_COOLC DXCOIL | N/A | N/A | 105768.03 | 360895.50 | 10.58 | 2.72 | 3.03 | 3.19 | 3.37 | 9.29 | 10.33 | 10.87 | 11.49 | 6.6830 | 5.3268 | 3.5817 | 1.4214 |
2 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_MID_COOLC DXCOIL | N/A | N/A | 84953.70 | 289874.07 | 10.64 | 2.74 | 3.05 | 3.20 | 3.39 | 9.33 | 10.39 | 10.93 | 11.56 | 5.1919 | 4.1608 | 2.8045 | 1.0972 |
3 | Coil:Cooling:DX:TwoSpeed | PACU_VAV_TOP_COOLC DXCOIL | N/A | N/A | 95343.25 | 325324.66 | 10.61 | 2.73 | 3.03 | 3.19 | 3.38 | 9.30 | 10.35 | 10.89 | 11.52 | 5.9516 | 4.7531 | 3.1990 | 1.2607 |
Zone Name | # Surfaces | |
1 | CORE_BOTTOM | 7 |
2 | TOPFLOOR_PLENUM | 10 |
3 | MIDFLOOR_PLENUM | 14 |
4 | FIRSTFLOOR_PLENUM | 14 |
5 | CORE_MID | 7 |
6 | CORE_TOP | 7 |
7 | PERIMETER_TOP_ZN_3 | 8 |
8 | PERIMETER_TOP_ZN_2 | 8 |
9 | PERIMETER_TOP_ZN_1 | 8 |
10 | PERIMETER_TOP_ZN_4 | 8 |
11 | PERIMETER_BOT_ZN_3 | 12 |
12 | PERIMETER_BOT_ZN_2 | 10 |
13 | PERIMETER_BOT_ZN_1 | 12 |
14 | PERIMETER_BOT_ZN_4 | 10 |
15 | PERIMETER_MID_ZN_3 | 8 |
16 | PERIMETER_MID_ZN_2 | 8 |
17 | PERIMETER_MID_ZN_1 | 8 |
18 | PERIMETER_MID_ZN_4 | 8 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | CORE_BOT_ZN_5_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
8 | PERIMETER_TOP_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
9 | PERIMETER_TOP_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
10 | PERIMETER_TOP_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
11 | PERIMETER_TOP_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 225.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
13 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 135.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 45.00 | 180.00 | 6.47 | 40.76 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
15 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 315.00 | 180.00 | 6.47 | 24.13 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 180.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 1660.73 | 1660.73 | 1660.73 | 0.00 | 0.00 | 49.91 | 33.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | PERIMETER_MID_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
19 | PERIMETER_MID_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | PERIMETER_MID_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | PERIMETER_MID_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
23 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
26 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
27 | iz-PERIMETER_TOP_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
28 | iz-PERIMETER_TOP_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
29 | iz-PERIMETER_TOP_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
30 | iz-PERIMETER_TOP_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
31 | iz-CORE_TOP_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | PERIMETER_BOT_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 0.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | PERIMETER_BOT_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 90.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 60.85 | 60.85 | 60.85 | 180.00 | 90.00 | 49.91 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | PERIMETER_BOT_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 40.57 | 40.57 | 40.57 | 270.00 | 90.00 | 33.27 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
36 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
37 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
38 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
39 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
40 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
41 | iz-PERIMETER_MID_ZN_1_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
42 | iz-PERIMETER_MID_ZN_2_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
43 | iz-PERIMETER_MID_ZN_3_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
44 | iz-PERIMETER_MID_ZN_4_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
45 | iz-CORE_MID_ZN_5_FLOOR | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
46 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
48 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
49 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
51 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 180.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
52 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
53 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
56 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | iz-CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 983.54 | 983.54 | 983.54 | 0.00 | 180.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 983.54 | 983.54 | 983.54 | 0.00 | 0.00 | 40.76 | 24.13 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1967.08 | 1967.08 | 1967.08 | 0.00 | 90.00 | 1967.08 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
62 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
63 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | iz-CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
66 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 225.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
67 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
68 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
69 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
71 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
72 | iz-CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
73 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
74 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 315.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
75 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
76 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | PERIMETER_TOP_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
79 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | iz-CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
82 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 45.00 | 0.00 | 6.47 | 49.91 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
83 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
84 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
85 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
86 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | iz-PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | iz-CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
90 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 135.00 | 0.00 | 6.47 | 33.27 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
91 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
92 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 67.75 | 136.92 | 67.75 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
93 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
94 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 21.75 | 21.75 | 21.75 | 0.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
96 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
97 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
98 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
100 | iz-CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
101 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
102 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
103 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
104 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 45.82 | 91.28 | 45.82 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 41.85 | 41.85 | 41.85 | 90.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
106 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 1.65 | 1.65 | 1.65 | 90.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
107 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
108 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
110 | iz-CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 0.337 | 0.312 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
112 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
113 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
114 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 67.75 | 136.92 | 67.75 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
116 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
117 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 21.75 | 21.75 | 21.75 | 180.00 | 90.00 | 15.82 | 1.37 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
118 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
119 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
120 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
121 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | iz-CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 0.319 | 0.296 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
124 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
125 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
126 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 45.82 | 91.28 | 45.82 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
127 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 41.85 | 41.85 | 41.85 | 270.00 | 90.00 | 30.84 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
128 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 1.65 | 1.65 | 1.65 | 270.00 | 90.00 | 1.22 | 1.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.975 | 3.975 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
130 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | iz-PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | iz-CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 0.337 | 0.312 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 71.65 | 136.92 | 71.65 | 0.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 65.26 | 65.26 | 65.26 | 0.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | iz-CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 180.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 0.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 180.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.68 | 414.68 | 414.68 | 0.00 | 90.00 | 414.68 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 47.77 | 91.28 | 47.77 | 90.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 43.51 | 43.51 | 43.51 | 90.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | iz-CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 270.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.26 | 131.26 | 131.26 | 90.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
150 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.26 | 131.26 | 131.26 | 270.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
151 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
152 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 71.65 | 136.92 | 71.65 | 180.00 | 90.00 | 49.91 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
153 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 65.26 | 65.26 | 65.26 | 180.00 | 90.00 | 49.91 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
154 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
155 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | iz-CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 111.82 | 111.82 | 111.82 | 0.00 | 90.00 | 40.76 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 207.34 | 207.34 | 207.34 | 180.00 | 180.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
158 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 207.34 | 207.34 | 207.34 | 0.00 | 0.00 | 40.76 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
159 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 414.67 | 414.67 | 414.67 | 0.00 | 90.00 | 414.67 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
160 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL | 0.514 | 0.477 | 47.77 | 91.28 | 47.77 | 270.00 | 90.00 | 33.27 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
161 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.51_SHGC_0.4 | N/A | 2.899 | No | 43.51 | 43.51 | 43.51 | 270.00 | 90.00 | 33.27 | 1.31 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
162 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | iz-PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | iz-PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.74 | 17.74 | 17.74 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | iz-CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.19 | 66.19 | 66.19 | 90.00 | 90.00 | 24.13 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 131.25 | 131.25 | 131.25 | 270.00 | 180.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 131.25 | 131.25 | 131.25 | 90.00 | 0.00 | 24.13 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
167 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 262.51 | 262.51 | 262.51 | 0.00 | 90.00 | 262.51 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1 |
2 | VETERANS DAY | Holiday | InputFile | 11/11 | 1 |
3 | CHRISTMAS | Holiday | InputFile | 12/25 | 1 |
4 | INDEPENDENCE DAY | Holiday | InputFile | 07/04 | 1 |
5 | MLK DAY | Holiday | InputFile | 01/16 | 1 |
6 | PRESIDENTS DAY | Holiday | InputFile | 02/20 | 1 |
7 | MEMORIAL DAY | Holiday | InputFile | 05/29 | 1 |
8 | LABOR DAY | Holiday | InputFile | 09/04 | 1 |
9 | COLUMBUS DAY | Holiday | InputFile | 10/09 | 1 |
10 | THANKSGIVING | Holiday | InputFile | 11/23 | 1 |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
NumberofWarmupDays | |
1 | 17 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 0.1734066760 | 0.1053712837 | Pass | Pass | 0.4657936420 | 0.5036904496 | Pass | Pass |
2 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1419857809 | 8.8528143197E-002 | Pass | Pass | 0.4946357668 | 0.4723214581 | Pass | Pass |
3 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 7.1591301940E-002 | 3.6151216717E-002 | Pass | Pass | 0.4828019975 | 0.4781282960 | Pass | Pass |
4 | FIRSTFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.0397601818E-002 | 3.6067068606E-002 | Pass | Pass | 0.5433255398 | 0.5743765957 | Pass | Pass |
5 | CORE_MID | RunPeriod: RUNPERIOD 1 | 6.4279384182E-002 | 5.1414699425E-002 | Pass | Pass | 0.9286072012 | 1.6720985452 | Pass | Pass |
6 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.1627842111E-002 | 2.5349532005E-002 | Pass | Pass | 1.2455754469 | 2.0783785015 | Pass | Pass |
7 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2822870480 | 0.2689963243 | Pass | Pass | 1.0317783524 | 1.2664013155 | Pass | Pass |
8 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.3015704994 | 0.3109410181 | Pass | Pass | 1.0259682540 | 1.2815364549 | Pass | Pass |
9 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2853102677 | 0.2974798145 | Pass | Pass | 1.0094716215 | 1.2312419822 | Pass | Pass |
10 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3017753908 | 0.3103999483 | Pass | Pass | 1.0529991952 | 1.3549873251 | Pass | Pass |
11 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2061219997 | 0.1914024853 | Pass | Pass | 1.0172397533 | 1.4382523772 | Pass | Pass |
12 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2236916141 | 0.2191601469 | Pass | Pass | 0.9228081330 | 1.1688231583 | Pass | Pass |
13 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2058850066 | 0.2040994533 | Pass | Pass | 0.9685623313 | 1.2713098002 | Pass | Pass |
14 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2249314237 | 0.2197804440 | Pass | Pass | 0.9100283007 | 1.1279636190 | Pass | Pass |
15 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2168560660 | 0.2049108466 | Pass | Pass | 0.8969665324 | 1.2932913928 | Pass | Pass |
16 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2335395880 | 0.2345312414 | Pass | Pass | 0.9916659651 | 1.3232453426 | Pass | Pass |
17 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2180742051 | 0.2217702569 | Pass | Pass | 0.9806155257 | 1.3158267419 | Pass | Pass |
18 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.2357621970 | 0.2352442992 | Pass | Pass | 0.9922853501 | 1.3209280886 | Pass | Pass |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_TOP_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_TOP_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_TOP_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.273 | 0.283 | 1660.73 | 1660.73 | 0.00 | 0.00 | |
PERIMETER_MID_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_MID_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_MID_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_MID_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_BOT_PLENUM_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 0.00 | 90.00 | N |
PERIMETER_BOT_PLENUM_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 90.00 | 90.00 | E |
PERIMETER_BOT_PLENUM_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 60.85 | 60.85 | 180.00 | 90.00 | S |
PERIMETER_BOT_PLENUM_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 40.57 | 40.57 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 136.92 | 67.75 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 91.28 | 45.82 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 136.92 | 67.75 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 91.28 | 45.82 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 136.92 | 71.65 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 91.28 | 47.77 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 136.92 | 71.65 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL | 0.30 | 0.477 | 0.514 | 91.28 | 47.77 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_3_FLOOR | PERIMETER_BOT_ZN_3_FLOOR_FFACTOR | 1.00 | 0.319 | 207.34 | 207.34 | 0.00 | 180.00 | ||
PERIMETER_BOT_ZN_2_FLOOR | PERIMETER_BOT_ZN_2_FLOOR_FFACTOR | 1.00 | 0.337 | 131.26 | 131.26 | 90.00 | 180.00 | ||
PERIMETER_BOT_ZN_1_FLOOR | PERIMETER_BOT_ZN_1_FLOOR_FFACTOR | 1.00 | 0.319 | 207.34 | 207.34 | 180.00 | 180.00 | ||
PERIMETER_BOT_ZN_4_FLOOR | PERIMETER_BOT_ZN_4_FLOOR_FFACTOR | 1.00 | 0.337 | 131.25 | 131.25 | 270.00 | 180.00 |
Construction | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.899 | 0.395 | 0.401 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.899 | 0.395 | 0.401 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.899 | 0.395 | 0.401 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.899 | 0.395 | 0.401 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.51_SHGC_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.51_SHGC_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.51_SHGC_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.51_SHGC_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.51_SHGC_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.51_SHGC_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.51_SHGC_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.51_SHGC_0.4 | 21.75 | 0.00 | 0.00 | 21.75 | 21.75 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.51_SHGC_0.4 | 41.85 | 0.00 | 0.00 | 41.85 | 41.85 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.51_SHGC_0.4 | 1.65 | 0.00 | 0.00 | 1.65 | 1.65 | 2.899 | 0.395 | 0.401 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.899 | 0.395 | 0.401 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.899 | 0.395 | 0.401 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | ||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 65.26 | 0.00 | 0.00 | 65.26 | 65.26 | 2.899 | 0.395 | 0.401 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | ||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.51_SHGC_0.4 | 43.51 | 0.00 | 0.00 | 43.51 | 43.51 | 2.899 | 0.395 | 0.401 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | ||
Total or Average | 652.62 | 2.899 | 0.395 | 0.401 | ||||||||||||
North Total or Average | 195.79 | 2.899 | 0.395 | 0.401 | ||||||||||||
Non-North Total or Average | 456.84 | 2.899 | 0.395 | 0.401 |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR | SWINGING DOOR_CON | 2.492 | 3.975 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Report: Shading Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Interior LightingZone | Lighting Power Density [W/m2] | Zone Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | 10.7639 | 983.54 | 10586.70 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 111.09 |
CORE_MID_LIGHTS | CORE_MID | 10.7639 | 983.54 | 10586.70 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 111.09 |
CORE_TOP_LIGHTS | CORE_TOP | 10.7639 | 983.54 | 10586.70 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 111.09 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | 10.7639 | 207.34 | 2231.77 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 23.42 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | 10.7639 | 131.26 | 1412.89 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 14.83 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | 10.7639 | 207.34 | 2231.77 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 23.42 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | 10.7639 | 131.25 | 1412.80 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 14.82 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | 10.7639 | 207.34 | 2231.77 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 23.42 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | 10.7639 | 131.26 | 1412.89 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 14.83 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | 10.7639 | 207.34 | 2231.77 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 23.42 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | 10.7639 | 131.25 | 1412.80 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 14.82 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | 10.7639 | 207.34 | 2231.77 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 23.42 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | 10.7639 | 131.26 | 1412.89 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 14.83 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | 10.7639 | 207.34 | 2231.77 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 23.42 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | 10.7639 | 131.25 | 1412.80 | LightsWired | BLDG_LIGHT_SCH | 57.39 | 168.00 | 55.90 | 0.0000 | Y | 14.82 |
Interior Lighting Total | 10.7639 | 4982.19 | 53627.80 | 562.72 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 14385.00 | AstronomicalClock | - | 83.55 | 83.55 | 225.60 | |
Exterior Lighting Total | 14385.00 | 225.60 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Central PlantType | Nominal Capacity [W] | Nominal Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 107139.90 | 85712.18 | 21427.72 | 0.80 | 3.23 | |||
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 85939.70 | 68453.09 | 17486.61 | 0.80 | 3.23 | |||
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | 96532.00 | 77239.79 | 19292.21 | 0.80 | 3.23 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER [Btu/W-h] | IEER [Btu/W-h] | |
PACU_VAV_BOT_COOLC DXCOIL | 105768.0 | 2.72 | 9.29 | N/A | 10.58 | |
PACU_VAV_MID_COOLC DXCOIL | 84953.7 | 2.74 | 9.33 | N/A | 10.64 | |
PACU_VAV_TOP_COOLC DXCOIL | 95343.2 | 2.73 | 9.30 | N/A | 10.61 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | ||||||||
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | 38169.69 | 1.00 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | 24341.55 | 1.00 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | 34805.20 | 1.00 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14737.08 | 1.00 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9685.20 | 1.00 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 14723.85 | 1.00 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 9598.04 | 1.00 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11513.72 | 1.00 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7650.27 | 1.00 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11491.21 | 1.00 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 7566.52 | 1.00 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11521.68 | 1.00 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8688.71 | 1.00 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | 11533.01 | 1.00 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | 8913.32 | 1.00 | |
PACU_VAV_BOT_HEATC | Coil:Heating:Fuel | 35660.64 | 0.80 | |
PACU_VAV_MID_HEATC | Coil:Heating:Fuel | 27704.30 | 0.80 | |
PACU_VAV_TOP_HEATC | Coil:Heating:Fuel | 31757.89 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electric Power [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PACU_VAV_BOT FAN | Fan:VariableVolume | 0.60 | 1573.68 | 5.86 | 15360.23 | 2620.18 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
PACU_VAV_MID FAN | Fan:VariableVolume | 0.59 | 1573.68 | 4.55 | 12116.76 | 2660.49 | 1.00 | 1.10 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
PACU_VAV_TOP FAN | Fan:VariableVolume | 0.59 | 1573.68 | 5.22 | 13889.64 | 2660.49 | 1.00 | 1.10 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electric Power [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
SHWSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000054 | 6.85 | 127739.32 | 0.30 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SHWSYS1 WATER HEATER | WaterHeater:Mixed | 0.38 | 29307.11 | 0.81 | 0.96 | 0.22 |
DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 105768.03 | 2.72 | 9.29 | 10.58 | 6.6830 | 3.03 | 10.33 | 5.3268 | 3.19 | 10.87 | 3.5817 | 3.37 | 11.49 | 1.4214 |
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 84953.70 | 2.74 | 9.33 | 10.64 | 5.1919 | 3.05 | 10.39 | 4.1608 | 3.20 | 10.93 | 2.8045 | 3.39 | 11.56 | 1.0972 |
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | None | 95343.25 | 2.73 | 9.30 | 10.61 | 5.9516 | 3.03 | 10.35 | 4.7531 | 3.19 | 10.89 | 3.1990 | 3.38 | 11.52 | 1.2607 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 52836.34 | 52836.34 | 53.72 | 3.865 | 3.865 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00873 | 21.70 | 0.00879 | 0.500 | 0.00 |
CORE_MID | 31934.31 | 31934.31 | 32.47 | 2.332 | 2.332 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00889 | 21.70 | 0.00879 | 0.500 | 0.00 |
CORE_TOP | 33324.77 | 33324.77 | 33.88 | 2.456 | 2.456 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00886 | 29.40 | 0.00879 | 0.500 | 0.00 |
PERIMETER_TOP_ZN_3 | 8882.70 | 8882.70 | 42.84 | 0.655 | 0.655 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 24.00 | 24.00 | 0.00878 | 29.30 | 0.00879 | 0.105 | 0.00 |
PERIMETER_TOP_ZN_2 | 11020.02 | 11020.02 | 83.95 | 0.812 | 0.812 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:40:00 | 24.00 | 24.00 | 0.00865 | 23.02 | 0.00879 | 0.067 | 0.00 |
PERIMETER_TOP_ZN_1 | 15379.37 | 15379.37 | 74.18 | 1.134 | 1.134 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00867 | 29.05 | 0.00879 | 0.105 | 0.00 |
PERIMETER_TOP_ZN_4 | 12276.27 | 12276.27 | 93.53 | 0.905 | 0.905 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00863 | 27.77 | 0.00879 | 0.067 | 0.00 |
PERIMETER_BOT_ZN_3 | 6976.38 | 6976.38 | 33.65 | 0.514 | 0.514 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00886 | 29.40 | 0.00879 | 0.105 | 0.00 |
PERIMETER_BOT_ZN_2 | 9374.39 | 9374.39 | 71.42 | 0.686 | 0.686 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00867 | 21.70 | 0.00879 | 0.067 | 0.00 |
PERIMETER_BOT_ZN_1 | 12347.45 | 12347.45 | 59.55 | 0.910 | 0.910 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00871 | 29.05 | 0.00879 | 0.105 | 0.00 |
PERIMETER_BOT_ZN_4 | 10347.74 | 10347.74 | 78.84 | 0.763 | 0.763 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 18:00:00 | 24.00 | 24.00 | 0.00865 | 26.90 | 0.00879 | 0.067 | 0.00 |
PERIMETER_MID_ZN_3 | 7727.29 | 7727.29 | 37.27 | 0.570 | 0.570 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 24.00 | 24.00 | 0.00883 | 29.40 | 0.00879 | 0.105 | 0.00 |
PERIMETER_MID_ZN_2 | 11295.54 | 11295.54 | 86.05 | 0.833 | 0.833 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 08:20:00 | 24.00 | 24.00 | 0.00864 | 22.36 | 0.00879 | 0.067 | 0.00 |
PERIMETER_MID_ZN_1 | 14364.59 | 14364.59 | 69.28 | 1.059 | 1.059 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 24.00 | 24.00 | 0.00868 | 28.97 | 0.00879 | 0.105 | 0.00 |
PERIMETER_MID_ZN_4 | 11587.39 | 11587.39 | 88.28 | 0.854 | 0.854 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 27.77 | 0.00879 | 0.067 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
CORE_BOTTOM | 8201.51 | 8201.51 | 8.34 | 0.350 | 0.500 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.500 | 0.00 |
CORE_MID | 13409.07 | 13409.07 | 13.63 | 0.575 | 0.575 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.500 | 0.00 |
CORE_TOP | 24522.43 | 24522.43 | 24.93 | 1.057 | 1.057 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.500 | 0.00 |
PERIMETER_TOP_ZN_3 | 10353.77 | 10353.77 | 49.94 | 0.448 | 0.448 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.105 | 0.00 |
PERIMETER_TOP_ZN_2 | 6803.75 | 6803.75 | 51.83 | 0.294 | 0.294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.067 | 0.00 |
PERIMETER_TOP_ZN_1 | 10344.52 | 10344.52 | 49.89 | 0.447 | 0.447 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.105 | 0.00 |
PERIMETER_TOP_ZN_4 | 6742.70 | 6742.70 | 51.37 | 0.292 | 0.292 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.067 | 0.00 |
PERIMETER_BOT_ZN_3 | 8095.29 | 8095.29 | 39.04 | 0.350 | 0.350 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -4.20 | 0.00269 | 0.105 | 0.00 |
PERIMETER_BOT_ZN_2 | 5377.91 | 5377.91 | 40.97 | 0.232 | 0.232 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00778 | -4.20 | 0.00269 | 0.067 | 0.00 |
PERIMETER_BOT_ZN_1 | 8079.55 | 8079.55 | 38.97 | 0.349 | 0.349 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00775 | -4.20 | 0.00269 | 0.105 | 0.00 |
PERIMETER_BOT_ZN_4 | 5319.27 | 5319.27 | 40.53 | 0.230 | 0.230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.067 | 0.00 |
PERIMETER_MID_ZN_3 | 8101.40 | 8101.40 | 39.07 | 0.350 | 0.350 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.105 | 0.00 |
PERIMETER_MID_ZN_2 | 5385.62 | 5385.62 | 41.03 | 0.233 | 0.233 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.067 | 0.00 |
PERIMETER_MID_ZN_1 | 8109.35 | 8109.35 | 39.11 | 0.350 | 0.350 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -4.20 | 0.00269 | 0.105 | 0.00 |
PERIMETER_MID_ZN_4 | 5327.20 | 5327.20 | 40.59 | 0.230 | 0.230 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.20 | 0.00269 | 0.067 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PACU_VAV_BOT | 5.86 | 5.86 | 1.66 | 1.66 | 5.8623 | 2.0213 | 5.8623 | 0.3448 | 0.3000 |
PACU_VAV_MID | 4.55 | 4.55 | 1.74 | 1.74 | 4.5543 | 1.7902 | 4.5543 | 0.3931 | 0.3000 |
PACU_VAV_TOP | 5.22 | 5.22 | 2.54 | 2.54 | 5.2207 | 2.5378 | 5.2207 | 0.4861 | 0.3000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 38169.687 | 38169.687 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 38169.69 | 16448.28 | 0.499605 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 8201.51 | 0.00 | -999.00 | -999.00 |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 24341.548 | 24341.548 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24341.55 | 18935.29 | 0.575146 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 13409.07 | 0.00 | -999.00 | -999.00 |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 34805.197 | 34805.197 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34805.20 | 34805.20 | 1.057184 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 24522.43 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 14737.075 | 14737.075 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14737.08 | 14737.08 | 0.447628 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00778702 | 49.6422 | 10353.77 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 9685.199 | 9685.199 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9685.20 | 9685.20 | 0.294181 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00778825 | 49.6500 | 6803.75 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 14723.854 | 14723.854 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14723.85 | 14723.85 | 0.447227 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00778678 | 49.6407 | 10344.52 | 0.00 | -999.00 | -999.00 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 9598.037 | 9598.037 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9598.04 | 9598.04 | 0.291534 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00778562 | 49.6335 | 6742.70 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 11513.717 | 11513.717 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11513.72 | 11513.72 | 0.349721 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00774963 | 49.4072 | 8095.29 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 7650.265 | 7650.265 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7650.27 | 7650.27 | 0.232372 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777518 | 49.5678 | 5377.91 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 11491.213 | 11491.213 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11491.21 | 11491.21 | 0.349038 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00774767 | 49.3948 | 8079.55 | 0.00 | -999.00 | -999.00 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 7566.522 | 7566.522 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7566.52 | 7566.52 | 0.229828 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776765 | 49.5204 | 5319.27 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 11521.675 | 11521.675 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11521.68 | 11521.68 | 0.349963 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771274 | 49.1750 | 8101.40 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 8688.711 | 8688.711 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8688.71 | 7660.76 | 0.232690 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772872 | 49.2756 | 5385.62 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 11533.009 | 11533.009 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11533.01 | 11533.01 | 0.350307 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00771321 | 49.1779 | 8109.35 | 0.00 | -999.00 | -999.00 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 8913.324 | 8913.324 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8913.32 | 7577.35 | 0.230157 | 12.80 | 11.46 | 0.00800000 | 40.00 | 20.98 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772295 | 49.2392 | 5327.20 | 0.00 | -999.00 | -999.00 |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_BOT | 107139.899 | 85712.179 | 5.862282 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 105807.23 | 101088.42 | 5.862282 | 25.69 | 17.04 | 0.00876743 | 10.64 | 10.64 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 31.2046 | 24.00 | 0.00872189 | 46.2679 | 79372.00 | 0.00 | 110421.03 | 86700.45 |
PACU_VAV_BOT_HEATC | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_BOT | 35660.642 | 35660.642 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35660.64 | 35660.64 | 1.758684 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 104.0152 | 21.00 | 0.00783062 | 49.9160 | 35073.52 | 0.00 | -999.00 | -999.00 |
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_MID | 85939.700 | 68453.086 | 4.554333 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 84587.75 | 80304.52 | 4.554333 | 26.12 | 17.23 | 0.00881479 | 10.61 | 10.61 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 39.3094 | 24.00 | 0.00876755 | 46.5067 | 61732.18 | 0.00 | 88571.58 | 69243.68 |
PACU_VAV_MID_HEATC | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_MID | 27704.303 | 27704.303 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27704.30 | 27704.30 | 1.366300 | -4.20 | -4.20 | 0.00269032 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 131.0313 | 21.00 | 0.00781137 | 49.7949 | 40332.63 | 0.00 | -999.00 | -999.00 |
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | PACU_VAV_TOP | 96531.997 | 77239.786 | 5.220706 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 95233.28 | 90691.74 | 5.220706 | 25.81 | 17.10 | 0.00878924 | 10.61 | 10.61 | 0.00850000 | 29.40 | 0.00879438 | 18.30 | 33.4141 | 24.00 | 0.00875114 | 46.4208 | 70732.17 | 0.00 | 99488.27 | 78108.89 |
PACU_VAV_TOP_HEATC | Coil:Heating:Fuel | AirLoopHVAC | PACU_VAV_TOP | 31757.894 | 31757.894 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 16:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31757.89 | 31757.89 | 1.566212 | -4.17 | -4.17 | 0.00269580 | 12.80 | 11.46 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 111.3802 | 21.00 | 0.00787568 | 50.1991 | 40161.55 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [C] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [KGWATER/KGDRYAIR] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [KGWATER/KGDRYAIR] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | No | unknown | No | 38169.687 | 38169.687 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 38169.69 | 16448.28 | 1.0000 | 0.59302666 | 0.499605 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38169.69 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 8201.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | No | unknown | No | 24341.548 | 24341.548 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 24341.55 | 18935.29 | 1.0000 | 0.68269329 | 0.575146 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24341.55 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 13409.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | No | unknown | No | 34805.197 | 34805.197 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 34805.20 | 34805.20 | 1.0000 | 1.25486740 | 1.057184 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34805.20 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 24522.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 14737.075 | 14737.075 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14737.08 | 14737.08 | 1.0000 | 0.53133086 | 0.447628 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14737.08 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778702 | 21.00 | 0.00778702 | 49.6422 | 10353.77 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 9685.199 | 9685.199 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9685.20 | 9685.20 | 1.0000 | 0.34919040 | 0.294181 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9685.20 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778825 | 21.00 | 0.00778825 | 49.6500 | 6803.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 14723.854 | 14723.854 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 14723.85 | 14723.85 | 1.0000 | 0.53085417 | 0.447227 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14723.85 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778678 | 21.00 | 0.00778678 | 49.6407 | 10344.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 9598.037 | 9598.037 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 9598.04 | 9598.04 | 1.0000 | 0.34604784 | 0.291534 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9598.04 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00778562 | 21.00 | 0.00778562 | 49.6335 | 6742.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11513.717 | 11513.717 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11513.72 | 11513.72 | 1.0000 | 0.41511580 | 0.349721 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11513.72 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774963 | 21.00 | 0.00774963 | 49.4072 | 8095.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 7650.265 | 7650.265 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7650.27 | 7650.27 | 1.0000 | 0.27582284 | 0.232372 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7650.27 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00777518 | 21.00 | 0.00777518 | 49.5678 | 5377.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11491.213 | 11491.213 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11491.21 | 11491.21 | 1.0000 | 0.41430445 | 0.349038 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11491.21 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00774767 | 21.00 | 0.00774767 | 49.3948 | 8079.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 7566.522 | 7566.522 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 7566.52 | 7566.52 | 1.0000 | 0.27280357 | 0.229828 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 7566.52 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00776765 | 21.00 | 0.00776765 | 49.5204 | 5319.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | No | unknown | No | 11521.675 | 11521.675 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11521.68 | 11521.68 | 1.0000 | 0.41540275 | 0.349963 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11521.68 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771274 | 21.00 | 0.00771274 | 49.1750 | 8101.40 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | No | unknown | No | 8688.711 | 8688.711 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8688.71 | 7660.76 | 1.0000 | 0.27620130 | 0.232690 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8688.71 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772872 | 21.00 | 0.00772872 | 49.2756 | 5385.62 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | No | unknown | No | 11533.009 | 11533.009 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 11533.01 | 11533.01 | 1.0000 | 0.41581137 | 0.350307 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 11533.01 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00771321 | 21.00 | 0.00771321 | 49.1779 | 8109.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Electric | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | No | unknown | No | 8913.324 | 8913.324 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8913.32 | 7577.35 | 1.0000 | 0.27319380 | 0.230157 | 12.80 | 11.46 | 0.00800000 | 33059.8 | 40.00 | 20.98 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8913.32 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 20.95 | 0.00772295 | 21.00 | 0.00772295 | 49.2392 | 5327.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_BOT_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 107139.899 | 85712.179 | 5.862282 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1382 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.862282 | 6.95847428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 105807.23 | 101088.42 | 1.0126 | 6.95847428 | 5.862282 | 25.69 | 17.04 | 0.00876743 | 48157.5 | 10.64 | 10.64 | 0.00850000 | 32115.9 | -999.0 | -999.00 | -999.00 | -999.00 | 15360.232 | 90447.00 | 29.40 | 0.00879438 | 18.30 | 1.82930000 | 31.2046 | 24.00 | 0.00875517 | 24.00 | 0.00872189 | 46.2679 | 79372.00 | 0.00 | 110421.03 | 86700.45 | 6.68297791 | 26.67 | 19.44 | 0.01117891 | 55307.7 | 13.99 | 13.82 | 0.00978726 | 38785.0 | |
PACU_VAV_BOT_HEATC | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_BOT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35660.642 | 35660.642 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_BOT FAN | Fan:VariableVolume | 5.862282 | 6.95847428 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 35660.64 | 35660.64 | 1.0000 | 2.08754228 | 1.758684 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35660.64 | -4.20 | 0.00269032 | -4.20 | 1.82930000 | 104.0152 | 20.94 | 0.00783062 | 21.00 | 0.00783062 | 49.9160 | 35073.52 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_MID_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 85939.700 | 68453.086 | 4.554333 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2263 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.554333 | 5.40595093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 84587.75 | 80304.52 | 1.0160 | 5.40595093 | 4.554333 | 26.12 | 17.23 | 0.00881479 | 48723.7 | 10.61 | 10.61 | 0.00850000 | 32082.1 | -999.0 | -999.00 | -999.00 | -999.00 | 12116.758 | 72470.99 | 29.40 | 0.00879438 | 18.30 | 1.79028000 | 39.3094 | 24.00 | 0.00882803 | 24.00 | 0.00876755 | 46.5067 | 61732.18 | 0.00 | 88571.58 | 69243.68 | 5.19192128 | 26.67 | 19.44 | 0.01117891 | 55307.7 | 13.63 | 13.62 | 0.00971932 | 38248.2 | |
PACU_VAV_MID_HEATC | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_MID | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27704.303 | 27704.303 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_MID FAN | Fan:VariableVolume | 4.554333 | 5.40595093 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 27704.30 | 27704.30 | 1.0000 | 1.62178528 | 1.366300 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27704.30 | -4.20 | 0.00269032 | -4.20 | 1.79028000 | 131.0313 | 20.92 | 0.00781137 | 21.00 | 0.00781137 | 49.7949 | 40332.63 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PACU_VAV_TOP_COOLC DXCOIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 96531.997 | 77239.786 | 5.220706 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1788 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.220706 | 6.19692963 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:20:00 | 95233.28 | 90691.74 | 1.0136 | 6.19692963 | 5.220706 | 25.81 | 17.10 | 0.00878924 | 48334.0 | 10.61 | 10.61 | 0.00850000 | 32082.0 | -999.0 | -999.00 | -999.00 | -999.00 | 13889.637 | 81343.64 | 29.40 | 0.00879438 | 18.30 | 1.74445000 | 33.4141 | 24.00 | 0.00878666 | 24.00 | 0.00875114 | 46.4208 | 70732.17 | 0.00 | 99488.27 | 78108.89 | 5.95158395 | 26.67 | 19.44 | 0.01117891 | 55307.7 | 13.84 | 13.75 | 0.00977048 | 38591.4 | |
PACU_VAV_TOP_HEATC | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PACU_VAV_TOP | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31757.894 | 31757.894 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PACU_VAV_TOP FAN | Fan:VariableVolume | 5.220706 | 6.19692963 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 16:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31757.89 | 31757.89 | 1.0000 | 1.85907889 | 1.566212 | -4.17 | -4.17 | 0.00269580 | 2527.7 | 12.80 | 11.46 | 0.00800000 | 33059.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31757.89 | -4.20 | 0.00269032 | -4.20 | 1.74445000 | 111.3802 | 21.00 | 0.00784548 | 21.00 | 0.00787568 | 50.1991 | 40161.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PACU_VAV_BOT_OA_CONTROLLER | DifferentialDryBulb | 1.83 | 5.86 | - | |||
PACU_VAV_MID_OA_CONTROLLER | DifferentialDryBulb | 1.79 | 4.55 | - | |||
PACU_VAV_TOP_OA_CONTROLLER | DifferentialDryBulb | 1.74 | 5.22 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
CORE_BOTTOM | 1233.17 | 3192.83 | 34.67 |
CORE_MID | 876.00 | 4252.67 | 174.00 |
CORE_TOP | 1281.33 | 4558.33 | 652.33 |
PERIMETER_TOP_ZN_3 | 2129.17 | 4927.00 | 1565.67 |
PERIMETER_TOP_ZN_2 | 2215.83 | 4959.67 | 1499.83 |
PERIMETER_TOP_ZN_1 | 2026.17 | 4779.67 | 1256.50 |
PERIMETER_TOP_ZN_4 | 2130.17 | 5151.00 | 1571.00 |
PERIMETER_BOT_ZN_3 | 1541.17 | 5107.17 | 1206.00 |
PERIMETER_BOT_ZN_2 | 1731.50 | 4995.17 | 1147.83 |
PERIMETER_BOT_ZN_1 | 1696.33 | 5126.83 | 1181.67 |
PERIMETER_BOT_ZN_4 | 1690.17 | 5190.00 | 1212.33 |
PERIMETER_MID_ZN_3 | 1631.33 | 4767.33 | 1048.50 |
PERIMETER_MID_ZN_2 | 1458.50 | 4333.00 | 991.33 |
PERIMETER_MID_ZN_1 | 1606.33 | 4678.17 | 815.83 |
PERIMETER_MID_ZN_4 | 1621.17 | 5139.50 | 1077.17 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 3573.67 | 5638.33 | 1836.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
CORE_BOTTOM | 1.33 | 2.50 | 0.33 | 0.00 |
CORE_MID | 3.83 | 0.50 | 1.67 | 0.00 |
CORE_TOP | 17.50 | 0.00 | 6.33 | 0.00 |
PERIMETER_TOP_ZN_3 | 145.50 | 0.00 | 33.83 | 0.00 |
PERIMETER_TOP_ZN_2 | 67.33 | 1.83 | 5.50 | 1.83 |
PERIMETER_TOP_ZN_1 | 63.50 | 1.00 | 6.00 | 1.00 |
PERIMETER_TOP_ZN_4 | 62.17 | 6.67 | 5.50 | 3.33 |
PERIMETER_BOT_ZN_3 | 52.83 | 0.00 | 14.83 | 0.00 |
PERIMETER_BOT_ZN_2 | 22.00 | 0.17 | 1.50 | 0.17 |
PERIMETER_BOT_ZN_1 | 458.00 | 1.00 | 441.50 | 1.00 |
PERIMETER_BOT_ZN_4 | 18.33 | 2.00 | 0.83 | 0.50 |
PERIMETER_MID_ZN_3 | 47.17 | 0.00 | 10.33 | 0.00 |
PERIMETER_MID_ZN_2 | 23.17 | 2.00 | 0.33 | 2.00 |
PERIMETER_MID_ZN_1 | 20.33 | 1.00 | 0.50 | 1.00 |
PERIMETER_MID_ZN_4 | 22.00 | 5.33 | 0.33 | 2.50 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 576.00 | 21.67 | 461.33 | 12.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 1.366 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.828 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.822 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 1.021 | 0.141 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 1.949 | 0.149 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 1.772 | 0.141 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 2.188 | 0.149 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.749 | 0.077 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 1.558 | 0.081 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 1.315 | 1.356 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 1.728 | 0.081 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.953 | 0.118 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 1.998 | 0.132 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 1.764 | 0.118 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 2.192 | 0.124 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
CORE_BOTTOM | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 21.77 | 52.94 | 2698.04 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 2.91 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 2.55 | 7.07 | 360.08 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 4.59 | 11.16 | 568.77 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 2.91 | 7.06 | 360.05 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Surfaces by ClassTotal | Outdoors | |
Wall | 72 | 24 |
Floor | 30 | 4 |
Roof | 26 | 1 |
Internal Mass | 15 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 18 | 18 |
Door | 6 | 6 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 3 |
Conditioned Zones | 18 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 0 |
Defaulted Fields | 0 |
Fields with Defaults | 0 |
Autosized Fields | 0 |
Autosizable Fields | 0 |
Autocalculated Fields | 0 |
Autocalculatable Fields | 0 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 2137.58 | 15571.00 | 12-MAR-17:20 | 252595.59 | 02-JAN-08:10 |
Electricity:Building | 1378.96 | 15066.99 | 01-JAN-00:10 | 107848.05 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 412.64 | 3234.28 | 01-JAN-00:10 | 39332.32 | 02-JAN-08:10 |
InteriorLights:Electricity | 562.72 | 2681.39 | 01-JAN-00:10 | 49183.02 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 111.09 | 529.33 | 01-JAN-00:10 | 9709.25 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 562.72 | 2681.39 | 01-JAN-00:10 | 49183.02 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 237.68 | 2910.48 | 01-JAN-00:10 | 16852.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 111.09 | 529.33 | 01-JAN-00:10 | 9709.25 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 237.68 | 2910.48 | 01-JAN-00:10 | 16852.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 111.09 | 529.33 | 01-JAN-00:10 | 9709.25 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 50.11 | 613.55 | 01-JAN-00:10 | 3552.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 23.42 | 111.59 | 01-JAN-00:10 | 2046.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 31.72 | 388.41 | 01-JAN-00:10 | 2249.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 14.83 | 70.64 | 01-JAN-00:10 | 1295.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 50.11 | 613.55 | 01-JAN-00:10 | 3552.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 23.42 | 111.59 | 01-JAN-00:10 | 2046.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 31.72 | 388.40 | 01-JAN-00:10 | 2248.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 14.82 | 70.64 | 01-JAN-00:10 | 1295.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 50.11 | 613.55 | 01-JAN-00:10 | 3552.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 23.42 | 111.59 | 01-JAN-00:10 | 2046.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 31.72 | 388.41 | 01-JAN-00:10 | 2249.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 14.83 | 70.64 | 01-JAN-00:10 | 1295.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 50.11 | 613.55 | 01-JAN-00:10 | 3552.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 23.42 | 111.59 | 01-JAN-00:10 | 2046.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 31.72 | 388.40 | 01-JAN-00:10 | 2248.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 14.82 | 70.64 | 01-JAN-00:10 | 1295.71 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 50.11 | 613.55 | 01-JAN-00:10 | 3552.69 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 23.42 | 111.59 | 01-JAN-00:10 | 2046.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 31.72 | 388.41 | 01-JAN-00:10 | 2249.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 14.83 | 70.64 | 01-JAN-00:10 | 1295.79 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 50.11 | 613.55 | 01-JAN-00:10 | 3552.68 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 23.42 | 111.59 | 01-JAN-00:10 | 2046.80 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 31.72 | 388.40 | 01-JAN-00:10 | 2248.99 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 14.82 | 70.64 | 01-JAN-00:10 | 1295.71 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 816.24 | 12385.60 | 01-JAN-00:10 | 58665.02 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 301.56 | 2704.95 | 01-JAN-00:10 | 29623.06 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity | 641.28 | 12061.80 | 01-JAN-00:10 | 36185.40 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 126.60 | 2381.15 | 01-JAN-00:10 | 7143.44 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.89 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 16.89 | 317.77 | 01-JAN-00:10 | 953.30 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 26.69 | 501.96 | 01-JAN-00:10 | 1505.88 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 16.89 | 317.76 | 01-JAN-00:10 | 953.29 | 02-JAN-08:10 |
ElevatorLift:InteriorEquipment:Electricity | 164.75 | 0.00 | 01-JAN-00:10 | 22155.82 | 02-JAN-08:10 |
ElevatorLightsFan:InteriorEquipment:Electricity | 10.21 | 323.80 | 01-JAN-00:10 | 323.80 | 01-JAN-00:10 |
Electricity:HVAC | 532.87 | 504.01 | 01-JAN-00:40 | 188522.39 | 02-JAN-06:30 |
ExteriorEquipment:Electricity | 33.79 | 501.71 | 01-JAN-00:10 | 2424.90 | 04-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 33.79 | 501.71 | 01-JAN-00:10 | 2424.90 | 04-JAN-08:20 |
ElectricityPurchased:Facility | 2137.58 | 15571.00 | 12-MAR-17:20 | 252595.59 | 02-JAN-08:10 |
ElectricityPurchased:Plant | 2137.58 | 15571.00 | 12-MAR-17:20 | 252595.59 | 02-JAN-08:10 |
Cogeneration:ElectricityPurchased | 2137.58 | 15571.00 | 12-MAR-17:20 | 252595.59 | 02-JAN-08:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 2137.58 | 15571.00 | 12-MAR-17:20 | 252595.59 | 02-JAN-08:10 |
ElectricityNet:Plant | 2137.58 | 15571.00 | 12-MAR-17:20 | 252595.59 | 02-JAN-08:10 |
Cogeneration:ElectricityNet | 2137.58 | 15571.00 | 12-MAR-17:20 | 252595.59 | 02-JAN-08:10 |
Heating:Electricity | 285.23 | 0.00 | 01-JAN-00:40 | 183449.94 | 02-JAN-06:30 |
Fans:Electricity | 91.13 | 0.00 | 01-JAN-00:40 | 17329.37 | 10-AUG-16:00 |
General:Fans:Electricity | 91.13 | 0.00 | 01-JAN-00:40 | 17329.37 | 10-AUG-16:00 |
ExteriorLights:Electricity | 225.60 | 0.00 | 01-JAN-08:10 | 14385.00 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 225.60 | 0.00 | 01-JAN-08:10 | 14385.00 | 01-JAN-00:10 |
Cooling:Electricity | 122.72 | 0.00 | 01-JAN-00:10 | 68841.24 | 29-AUG-15:20 |
Electricity:Plant | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:20 |
Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:20 |
General:Pumps:Electricity | 0.15 | 0.00 | 01-JAN-00:10 | 6.85 | 02-JAN-06:20 |
WIRED_LTG_ELECTRICITY | 15.81 | 0.00 | 01-JAN-00:10 | 1382.04 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 651.50 | 12385.60 | 01-JAN-00:10 | 36509.20 | 02-JAN-08:10 |
Gas Annual Value [GJ] | Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Gas:Facility | 348.40 | 2003.43 | 02-JAN-06:00 | 117746.09 | 07-JAN-08:00 |
Gas:Plant | 86.76 | 2003.43 | 02-JAN-06:00 | 10244.85 | 13-FEB-12:10 |
WaterSystems:Gas | 86.76 | 2003.43 | 02-JAN-06:00 | 10244.85 | 13-FEB-12:10 |
Water Heater:WaterSystems:Gas | 86.76 | 2003.43 | 02-JAN-06:00 | 10244.85 | 13-FEB-12:10 |
Gas:HVAC | 261.64 | 0.00 | 01-JAN-00:10 | 115742.66 | 07-JAN-08:00 |
Heating:Gas | 261.64 | 0.00 | 01-JAN-00:10 | 115742.66 | 07-JAN-08:00 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
MainsWater:Facility | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterUse:WaterSystems:Water | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 271.06 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopHeatingDemand:Facility | 50.79 | 0.00 | 01-JAN-00:10 | 6142.72 | 14-FEB-12:40 |
PlantLoopHeatingDemand:Plant | 50.79 | 0.00 | 01-JAN-00:10 | 6142.72 | 14-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 50.79 | 0.00 | 01-JAN-00:10 | 6142.72 | 14-FEB-12:40 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
EnergyTransfer:Facility | 2238.92 | 0.00 | 01-JAN-00:40 | 413266.99 | 10-AUG-16:00 |
EnergyTransfer:Building | 1222.01 | 0.00 | 01-JAN-00:40 | 171809.16 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_BOTTOM | 312.42 | 0.00 | 01-JAN-00:40 | 32495.88 | 10-AUG-08:00 |
Heating:EnergyTransfer | 107.33 | 0.00 | 01-JAN-00:40 | 165446.69 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.31 | 0.00 | 01-JAN-00:10 | 30003.90 | 02-JAN-05:10 |
Cooling:EnergyTransfer | 1114.68 | 0.00 | 01-JAN-00:40 | 171809.16 | 10-AUG-16:00 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 312.11 | 0.00 | 01-JAN-00:40 | 32495.88 | 10-AUG-08:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 47.67 | 0.00 | 01-JAN-00:40 | 11322.88 | 10-AUG-14:50 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 20.10 | 0.00 | 01-JAN-00:40 | 9244.63 | 13-FEB-05:40 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 27.57 | 0.00 | 01-JAN-00:10 | 11322.88 | 10-AUG-14:50 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 22.81 | 0.00 | 01-JAN-00:40 | 7236.03 | 02-JAN-08:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 5.10 | 0.00 | 01-JAN-00:40 | 7236.03 | 02-JAN-08:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 17.70 | 0.00 | 01-JAN-00:10 | 3852.92 | 10-AUG-16:00 |
EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 26.34 | 0.00 | 01-JAN-00:40 | 7158.54 | 02-JAN-05:40 |
Heating:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 3.99 | 0.00 | 01-JAN-00:40 | 7158.54 | 02-JAN-05:40 |
Cooling:EnergyTransfer:Zone:FIRSTFLOOR_PLENUM | 22.35 | 0.00 | 01-JAN-00:10 | 4531.97 | 10-AUG-16:00 |
EnergyTransfer:Zone:CORE_MID | 167.09 | 0.00 | 01-JAN-00:40 | 20311.81 | 11-AUG-04:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.78 | 0.00 | 01-JAN-00:10 | 20112.13 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 166.31 | 0.00 | 01-JAN-00:40 | 20311.81 | 11-AUG-04:10 |
EnergyTransfer:Zone:CORE_TOP | 154.21 | 0.00 | 01-JAN-00:40 | 22080.72 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:CORE_TOP | 4.04 | 0.00 | 01-JAN-00:40 | 20333.09 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 150.16 | 0.00 | 01-JAN-00:10 | 22080.72 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 37.89 | 0.00 | 01-JAN-00:40 | 6802.46 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 8.72 | 0.00 | 01-JAN-00:40 | 5604.22 | 21-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 29.18 | 0.00 | 01-JAN-00:10 | 6802.46 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.15 | 0.00 | 01-JAN-00:40 | 8927.27 | 10-AUG-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 5.96 | 0.00 | 01-JAN-00:40 | 6518.48 | 21-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 31.20 | 0.00 | 01-JAN-00:10 | 8927.27 | 10-AUG-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 58.33 | 0.00 | 01-JAN-00:40 | 13687.43 | 04-OCT-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 7.85 | 0.00 | 01-JAN-00:40 | 9156.12 | 21-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 50.49 | 0.00 | 01-JAN-00:10 | 13687.43 | 04-OCT-13:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 38.88 | 0.00 | 01-JAN-00:40 | 10266.76 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 6.14 | 0.00 | 01-JAN-00:40 | 7120.43 | 21-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 32.75 | 0.00 | 01-JAN-00:10 | 10266.76 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 28.93 | 0.00 | 01-JAN-00:40 | 4832.99 | 09-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 4.15 | 0.00 | 01-JAN-00:40 | 4359.59 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 24.79 | 0.00 | 01-JAN-00:10 | 4832.99 | 09-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 31.44 | 0.00 | 01-JAN-00:40 | 6875.33 | 10-AUG-08:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 2.84 | 0.00 | 01-JAN-00:40 | 5494.15 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 28.60 | 0.00 | 01-JAN-00:10 | 6875.33 | 10-AUG-08:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 55.33 | 0.00 | 01-JAN-00:40 | 13042.94 | 10-AUG-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 22.18 | 0.00 | 01-JAN-00:40 | 9053.73 | 26-DEC-07:50 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 33.14 | 0.00 | 01-JAN-00:10 | 13042.94 | 10-AUG-17:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 32.78 | 0.00 | 01-JAN-00:40 | 8179.65 | 10-AUG-17:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 2.83 | 0.00 | 01-JAN-00:40 | 6033.02 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 29.95 | 0.00 | 01-JAN-00:10 | 8179.65 | 10-AUG-17:40 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 35.07 | 0.00 | 01-JAN-00:40 | 5984.38 | 24-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 3.67 | 0.00 | 01-JAN-00:40 | 5062.62 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 31.41 | 0.00 | 01-JAN-00:10 | 5984.38 | 24-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 37.82 | 0.00 | 01-JAN-00:40 | 9155.60 | 10-AUG-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 2.70 | 0.00 | 01-JAN-00:40 | 6840.83 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 35.12 | 0.00 | 01-JAN-00:10 | 9155.60 | 10-AUG-08:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 58.89 | 0.00 | 01-JAN-00:40 | 13727.45 | 04-OCT-12:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 3.33 | 0.00 | 01-JAN-00:40 | 8919.58 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 55.56 | 0.00 | 01-JAN-00:10 | 13727.45 | 04-OCT-12:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 38.94 | 0.00 | 01-JAN-00:40 | 9807.60 | 10-AUG-16:40 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 2.65 | 0.00 | 01-JAN-00:40 | 6992.41 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 36.28 | 0.00 | 01-JAN-00:10 | 9807.60 | 10-AUG-16:40 |
EnergyTransfer:Plant | 50.79 | 0.00 | 01-JAN-00:10 | 6142.72 | 14-FEB-12:40 |
WaterSystems:EnergyTransfer | 50.79 | 0.00 | 01-JAN-00:10 | 6142.72 | 14-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 50.79 | 0.00 | 01-JAN-00:10 | 6142.72 | 14-FEB-12:40 |
EnergyTransfer:HVAC | 966.12 | 0.00 | 01-JAN-00:40 | 241906.46 | 29-AUG-15:10 |
HeatingCoils:EnergyTransfer | 494.54 | 0.00 | 01-JAN-00:40 | 210253.71 | 26-DEC-07:10 |
CoolingCoils:EnergyTransfer | 471.59 | 0.00 | 01-JAN-00:10 | 241906.46 | 29-AUG-15:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
CORE_BOTTOM | 0.000 | 0.000 | 0.313 | -312.111 | 0.000 | 0.000 | 33.287 | 111.087 | 301.557 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -134.132 |
CORE_MID | 0.000 | 0.000 | 0.777 | -166.311 | 0.000 | 0.000 | 34.672 | 111.087 | 126.597 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -106.822 |
CORE_TOP | 0.000 | 0.000 | 4.043 | -150.164 | 0.000 | 0.000 | 35.470 | 111.087 | 126.597 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -127.032 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 8.717 | -29.176 | 0.000 | 0.000 | 7.732 | 23.418 | 26.688 | 10.579 | 0.000 | 0.043 | 1.592 | 0.000 | -37.800 | 0.000 | -11.793 | -0.002 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 5.957 | -31.196 | 0.000 | 0.000 | 4.939 | 14.826 | 16.894 | 23.721 | 0.000 | 0.033 | 0.000 | 0.000 | -23.949 | 0.000 | -7.827 | -3.398 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 7.848 | -50.485 | 0.000 | 0.000 | 7.729 | 23.418 | 26.688 | 49.012 | 0.000 | 0.041 | 0.000 | 0.000 | -36.400 | 0.000 | -12.047 | -15.804 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 6.136 | -32.746 | 0.000 | 0.000 | 5.031 | 14.825 | 16.894 | 26.328 | 0.000 | 0.027 | 0.000 | 0.000 | -24.783 | 0.000 | -7.907 | -3.806 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 4.145 | -24.788 | 0.000 | 0.000 | 7.674 | 23.418 | 26.688 | 11.044 | 0.000 | 0.026 | 0.000 | 0.000 | -39.389 | 0.000 | -6.828 | -1.991 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 2.841 | -28.598 | 0.000 | 0.000 | 4.931 | 14.826 | 16.894 | 24.016 | 0.000 | 0.017 | 0.001 | 0.000 | -25.026 | 0.000 | -4.525 | -5.375 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 22.182 | -33.144 | 0.000 | 0.000 | 7.942 | 23.418 | 26.688 | 49.988 | 0.000 | 0.628 | 0.001 | 0.000 | -37.756 | 0.000 | -50.889 | -9.056 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 2.833 | -29.948 | 0.000 | 0.000 | 5.011 | 14.825 | 16.894 | 26.730 | 0.000 | 0.014 | 0.001 | 0.000 | -25.931 | 0.000 | -4.564 | -5.865 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 3.667 | -31.407 | 0.000 | 0.000 | 7.622 | 23.418 | 26.688 | 10.374 | 0.000 | 0.038 | 10.405 | 0.000 | -40.350 | 0.000 | -10.455 | -0.002 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 2.698 | -35.121 | 0.000 | 0.000 | 3.663 | 14.826 | 16.894 | 23.656 | 0.000 | 0.033 | 5.470 | 0.000 | -25.255 | 0.000 | -6.864 | -0.000 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 3.330 | -55.561 | 0.000 | 0.000 | 7.664 | 23.418 | 26.688 | 48.698 | 0.000 | 0.037 | 0.000 | 0.000 | -38.489 | 0.000 | -10.629 | -5.157 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 2.655 | -36.284 | 0.000 | 0.000 | 5.016 | 14.825 | 16.894 | 26.280 | 0.000 | 0.024 | 3.767 | 0.000 | -26.222 | 0.000 | -6.954 | -0.001 |
TOPFLOOR_PLENUM | 20.100 | -27.570 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.017 | 25.485 | 0.000 | 0.000 | 0.000 | -18.031 | -0.002 |
MIDFLOOR_PLENUM | 5.104 | -17.705 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.048 | 30.850 | 0.000 | 0.000 | 0.000 | -18.298 | -0.000 |
FIRSTFLOOR_PLENUM | 3.986 | -22.352 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.036 | 33.249 | 0.000 | 0.000 | 0.000 | -14.919 | -0.000 |
Total Facility | 29.190 | -67.627 | 78.142 | -1047.042 | 0.000 | 0.000 | 178.382 | 562.720 | 816.244 | 330.429 | 0.000 | 1.062 | 110.821 | 0.000 | -381.348 | 0.000 | -192.530 | -418.446 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 10-AUG-04:03 | 0.00 | 0.00 | 0.00 | -58350.94 | 0.00 | 0.00 | 0.00 | 1058.67 | 3498.66 | 0.00 | 0.00 | 0.00 | 53793.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 10-AUG-04:03 | 0.00 | 0.00 | 0.00 | -36768.82 | 0.00 | 0.00 | 0.00 | 1058.67 | 3174.86 | 0.00 | 0.00 | 0.00 | 32535.29 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 10-AUG-04:01 | 0.00 | 0.00 | 0.00 | -35108.11 | 0.00 | 0.00 | 0.00 | 1058.67 | 3174.86 | 0.00 | 0.00 | 0.00 | 30874.58 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 24-JUL-15:00 | 0.00 | 0.00 | 0.00 | -6802.43 | 0.00 | 0.00 | 737.23 | 2046.80 | 1505.89 | 3593.41 | 0.00 | 80.47 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1161.37 |
PERIMETER_TOP_ZN_2 | 10-AUG-08:30 | 0.00 | 0.00 | 0.00 | -8927.18 | 0.00 | 0.00 | 466.73 | 1295.79 | 953.30 | 12724.42 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -13.12 | -6499.93 |
PERIMETER_TOP_ZN_1 | 10-SEP-13:12 | 0.00 | 0.00 | 0.00 | -19407.41 | 0.00 | 0.00 | 25.41 | 113.71 | 501.96 | 14633.80 | 0.00 | 0.00 | 4422.87 | 0.00 | -0.00 | 0.00 | -290.35 | 0.00 |
PERIMETER_TOP_ZN_4 | 30-JUL-17:21 | 0.00 | 0.00 | 0.00 | -17198.55 | 0.00 | 0.00 | 0.00 | 70.64 | 317.76 | 13201.78 | 0.00 | 0.00 | 3716.20 | 0.00 | -0.00 | 0.00 | -107.83 | 0.00 |
PERIMETER_BOT_ZN_3 | 10-AUG-04:01 | 0.00 | 0.00 | 0.00 | -5517.84 | 0.00 | 0.00 | 0.00 | 223.18 | 669.29 | 0.00 | 0.00 | 0.00 | 6150.24 | 0.00 | -1356.10 | 0.00 | -168.76 | 0.00 |
PERIMETER_BOT_ZN_2 | 13-AUG-07:12 | 0.00 | 0.00 | 0.00 | -7425.01 | 0.00 | 0.00 | 18.30 | 71.99 | 317.77 | 12374.30 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -170.41 | -5186.93 |
PERIMETER_BOT_ZN_1 | 10-AUG-17:00 | 0.00 | 0.00 | 0.00 | -13042.28 | 0.00 | 0.00 | 223.03 | 1137.11 | 836.60 | 2083.55 | 0.00 | 8579.26 | 182.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 23-JUL-18:01 | 0.00 | 0.00 | 0.00 | -12026.44 | 0.00 | 0.00 | 0.00 | 70.64 | 317.76 | 11394.81 | 0.00 | 0.00 | 270.71 | 0.00 | -0.00 | 0.00 | -27.49 | 0.00 |
PERIMETER_MID_ZN_3 | 25-AUG-04:01 | 0.00 | 0.00 | 0.00 | -6917.93 | 0.00 | 0.00 | 0.00 | 223.18 | 669.29 | 0.00 | 0.00 | 0.00 | 7680.71 | 0.00 | -1352.49 | 0.00 | -302.75 | 0.00 |
PERIMETER_MID_ZN_2 | 10-SEP-08:32 | 0.00 | 0.00 | 0.00 | -11432.44 | 0.00 | 0.00 | 17.17 | 71.99 | 317.77 | 10623.03 | 0.00 | 0.00 | 548.58 | 0.00 | -0.00 | 0.00 | -146.08 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-14:02 | 0.00 | 0.00 | 0.00 | -17952.64 | 0.00 | 0.00 | 25.99 | 113.71 | 501.96 | 12437.87 | 0.00 | 0.00 | 5052.31 | 0.00 | -0.00 | 0.00 | -179.21 | 0.00 |
PERIMETER_MID_ZN_4 | 06-AUG-17:32 | 0.00 | 0.00 | 0.00 | -15212.41 | 0.00 | 0.00 | 0.00 | 70.64 | 317.76 | 11848.91 | 0.00 | 0.00 | 3143.11 | 0.00 | -0.00 | 0.00 | -168.02 | 0.00 |
TOPFLOOR_PLENUM | 10-AUG-14:50 | 0.00 | -11322.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.42 | 11261.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 10-AUG-04:12 | 0.00 | -4286.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4757.79 | 0.00 | -0.00 | 0.00 | -471.34 | 0.00 |
FIRSTFLOOR_PLENUM | 10-AUG-04:12 | 0.00 | -4664.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5036.77 | 0.00 | -0.00 | 0.00 | -372.71 | 0.00 |
Total Facility | 10-AUG-04:01 | 0.00 | 12342.78 | 0.00 | -187798.57 | 0.00 | 0.00 | 0.00 | 5362.78 | 16406.20 | 0.00 | 0.00 | 0.00 | 171215.02 | 0.00 | -13776.97 | 0.00 | -3751.23 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
CORE_BOTTOM | 02-JAN-05:01 | 0.00 | 0.00 | 33283.80 | -0.00 | 0.00 | 0.00 | 0.00 | 1058.67 | 3498.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -37841.13 |
CORE_MID | 02-JAN-05:01 | 0.00 | 0.00 | 21524.35 | -0.00 | 0.00 | 0.00 | 0.00 | 1058.67 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25757.89 |
CORE_TOP | 02-JAN-05:01 | 0.00 | 0.00 | 21473.67 | -0.00 | 0.00 | 0.00 | 0.00 | 1058.67 | 3174.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25707.20 |
PERIMETER_TOP_ZN_3 | 20-FEB-05:53 | 0.00 | 0.00 | 5934.67 | -0.00 | 0.00 | 0.00 | 0.00 | 111.59 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2363.85 | 0.00 | -1409.14 | -2775.23 |
PERIMETER_TOP_ZN_2 | 21-FEB-05:11 | 0.00 | 0.00 | 7303.35 | -0.00 | 0.00 | 0.00 | 0.00 | 141.29 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1402.55 | 0.00 | -434.90 | -6030.88 |
PERIMETER_TOP_ZN_1 | 21-FEB-05:11 | 0.00 | 0.00 | 10129.06 | -0.00 | 0.00 | 0.00 | 0.00 | 223.18 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2074.02 | 0.00 | -659.91 | -8287.59 |
PERIMETER_TOP_ZN_4 | 21-FEB-05:11 | 0.00 | 0.00 | 8089.97 | -0.00 | 0.00 | 0.00 | 0.00 | 141.28 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1370.55 | 0.00 | -439.47 | -6844.92 |
PERIMETER_BOT_ZN_3 | 01-JAN-22:03 | 0.00 | 0.00 | 4597.59 | -0.00 | 0.00 | 0.00 | 0.00 | 111.59 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1432.12 | 0.00 | -648.97 | -3130.05 |
PERIMETER_BOT_ZN_2 | 02-JAN-05:01 | 0.00 | 0.00 | 5961.29 | -0.00 | 0.00 | 0.00 | 0.00 | 141.29 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -949.73 | 0.00 | -335.18 | -5241.36 |
PERIMETER_BOT_ZN_1 | 06-JAN-07:10 | 0.00 | 0.00 | 9054.93 | -0.00 | 0.00 | 0.00 | 189.80 | 682.27 | 669.28 | 0.00 | 0.00 | 0.00 | 12866.52 | 0.00 | -3519.50 | 0.00 | -19943.28 | 0.00 |
PERIMETER_BOT_ZN_4 | 02-JAN-05:01 | 0.00 | 0.00 | 6614.66 | -0.00 | 0.00 | 0.00 | 0.00 | 141.28 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -949.60 | 0.00 | -336.73 | -5893.29 |
PERIMETER_MID_ZN_3 | 01-JAN-22:03 | 0.00 | 0.00 | 5391.08 | -0.00 | 0.00 | 0.00 | 0.00 | 111.59 | 501.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1450.01 | 0.00 | -985.51 | -3569.11 |
PERIMETER_MID_ZN_2 | 17-JAN-05:01 | 0.00 | 0.00 | 7677.16 | -0.00 | 0.00 | 0.00 | 0.00 | 141.29 | 423.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1443.67 | 0.00 | -305.57 | -6492.89 |
PERIMETER_MID_ZN_1 | 02-JAN-05:01 | 0.00 | 0.00 | 9716.05 | -0.00 | 0.00 | 0.00 | 0.00 | 223.18 | 669.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1456.95 | 0.00 | -773.68 | -8377.88 |
PERIMETER_MID_ZN_4 | 17-JAN-05:01 | 0.00 | 0.00 | 7870.56 | -0.00 | 0.00 | 0.00 | 0.00 | 141.28 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1398.64 | 0.00 | -305.91 | -6730.98 |
TOPFLOOR_PLENUM | 09-JAN-06:10 | 9850.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -371.62 | -9478.57 |
MIDFLOOR_PLENUM | 02-JAN-05:30 | 7676.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1386.51 | -6289.49 |
FIRSTFLOOR_PLENUM | 02-JAN-05:30 | 8724.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1121.20 | -7603.68 |
Total Facility | 02-JAN-06:01 | 15849.93 | 0.00 | 153250.35 | 0.00 | 0.00 | 0.00 | 2604.09 | 5464.78 | 16406.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -15709.53 | 0.00 | -5271.50 | -172594.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 6.7376 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 5.8623 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 5.6473 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 4.5543 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 5.9616 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 5.2207 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PACU_VAV_BOT | 2.0213 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 2.0213 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_MID | 1.7902 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 1.7902 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | ||
PACU_VAV_TOP | 1.7885 | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 1.7885 | 0.0000 | 1.0000 | 0.0000 | 0.0000 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
CORE_BOTTOM | PACU_VAV_BOT | 0.000000 | 52.9387 | 0.000508 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | PACU_VAV_MID | 0.000000 | 52.9387 | 0.000508 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | PACU_VAV_TOP | 0.000000 | 52.9387 | 0.000508 | 983.54 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000508 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | 0.000000 | 7.0652 | 0.000508 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | 0.000000 | 11.1599 | 0.000508 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | 0.000000 | 7.0647 | 0.000508 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000508 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | 0.000000 | 7.0652 | 0.000508 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | 0.000000 | 11.1599 | 0.000508 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | 0.000000 | 7.0647 | 0.000508 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000508 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | 0.000000 | 7.0652 | 0.000508 | 131.26 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | 0.000000 | 11.1599 | 0.000508 | 207.34 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | 0.000000 | 7.0647 | 0.000508 | 131.25 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PACU_VAV_BOT | 0.00 | 0.000508 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_MID | 0.00 | 0.000508 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 | |
PACU_VAV_TOP | 0.00 | 0.000508 | 1660.7286 | 0.0000 | 0.0000 | 0.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.8646 | 3.8646 | 1.1594 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3324 | 2.3324 | 0.7394 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4563 | 2.4563 | 0.7369 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6547 | 0.6547 | 0.1964 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8122 | 0.8122 | 0.2437 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1335 | 1.1335 | 0.3401 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9048 | 0.9048 | 0.2714 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5142 | 0.5142 | 0.1543 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6860 | 0.6860 | 0.2058 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9101 | 0.9101 | 0.2730 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7627 | 0.7627 | 0.2288 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5696 | 0.5696 | 0.1805 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8325 | 0.8325 | 0.2639 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0588 | 1.0588 | 0.3356 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8541 | 0.8541 | 0.2707 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 6.7376 | 5.8623 | 6.7376 | 2.0213 | 0.0000 | 1.0000 |
PACU_VAV_MID | 5.6473 | 4.5543 | 5.6473 | 1.7902 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 5.9616 | 5.2207 | 5.9616 | 1.7885 | 0.0000 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
CORE_BOTTOM | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1594 | 1.1594 | 1.1594 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7394 | 0.7394 | 0.7394 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7369 | 0.7369 | 0.7369 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1964 | 0.1964 | 0.1964 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2437 | 0.2437 | 0.2437 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3401 | 0.3401 | 0.3401 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | PACU_VAV_TOP | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2714 | 0.2714 | 0.2714 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1543 | 0.1543 | 0.1543 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2058 | 0.2058 | 0.2058 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2730 | 0.2730 | 0.2730 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | PACU_VAV_BOT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2288 | 0.2288 | 0.2288 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.1805 | 0.1805 | 0.1805 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2639 | 0.2639 | 0.2639 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3356 | 0.3356 | 0.3356 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | PACU_VAV_MID | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2707 | 0.2707 | 0.2707 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PACU_VAV_BOT | 2.0213 | 2.0213 | 2.0213 | 2.0213 | 0.0000 | 1.0000 |
PACU_VAV_MID | 1.7902 | 1.7902 | 1.7902 | 1.7902 | 0.0000 | 1.0000 |
PACU_VAV_TOP | 1.7885 | 1.7885 | 1.7885 | 1.7885 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2020-06-03 19:40:53
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 4982.19 |
Principal Heating Source | Electricity |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
CORE_BOTTOM | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_MID | 983.54 | 983.54 | 0.00 | 113.98 |
CORE_TOP | 983.54 | 983.54 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 131.26 | 131.26 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 131.26 | 131.26 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 207.34 | 207.34 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 131.25 | 131.25 | 0.00 | 113.98 |
TOPFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
FIRSTFLOOR_PLENUM | 1660.73 | 1660.73 | 0.00 | 0.00 |
Totals | 4982.19 | 4982.19 | 0.00 |
Data | |
Number of hours heating loads not met | 461.33 |
Number of hours cooling loads not met | 12.33 |
Number of hours not met | 473.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electric Energy Use [GJ] | Electric Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Additional Fuel Use [GJ] | Additional Fuel Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- Not Subdivided | 285.23 | 183449.94 | 261.64 | 115742.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- Not Subdivided | 122.72 | 68841.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 562.72 | 49183.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 225.60 | 14385.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 641.28 | 36185.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLift | 164.75 | 22155.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- ElevatorLightsFan | 10.21 | 323.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 33.79 | 2424.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 91.13 | 17329.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 0.15 | 6.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 86.76 | 10244.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 816.24 | 2137.58 |
Natural Gas | 0.00 | 348.40 |
Additional | 0.00 | 0.00 |
Total | 816.24 | 2485.97 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 112.95 |
Space Heating | 57.25 |
Space Cooling | 24.63 |
Fans (All) | 18.29 |
Service Water Heating | 0.00 |
Receptacle Equipment | 163.83 |
Miscellaneous (All) | 429.04 |
Subtotal | 429.04 |
Natural Gas [MJ/m2] | |
Space Heating | 52.51 |
Service Water Heating | 17.41 |
Miscellaneous (All) | 69.93 |
Subtotal | 69.93 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 22.64 |
Space Heating | 22.00 |
Space Cooling | 4.94 |
Fans (All) | 3.67 |
Service Water Heating | 3.49 |
Receptacle Equipment | 32.83 |
Miscellaneous | 10.44 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
BLDG_LIGHT_SCH | 2992. | 8760. |
BLDG_EQUIP_SCH | 4487. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2545. | 5992. |
BLDG_ELEVATORS | 1470. | 4212. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 1470. | 4212. |
BLDG_SWH_SCH | 1441. | 5992. |
WORK_EFF_SCH | 0. | 0. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_TOP_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_BOT_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_3 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_2 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_1 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT LATENT FRACT SCHED | 438. | 8760. |
PERIMETER_MID_ZN_4 SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_DOOR_OPENING_SCH | 1154. | 3380. |
PERIMETER_MID_ZN_2_MDP_SCH | 2490. | 8760. |
PERIMETER_MID_ZN_2_OA_MULT | 7824. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_SCH_NO_OPTIMUM | CORE_BOTTOM DUALSPSCHED | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_NO_OPTIMUM | CORE_BOTTOM DUALSPSCHED | July | 24.00 | 365 | 26.70 | 365 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2006
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICEMEDIUM
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB [] | HEATING:GAS [J] | |
January | 0.000 | 0.667527E+11 |
February | 0.000 | 0.471912E+11 |
March | 0.000 | 0.280521E+11 |
April | 0.000 | 0.144720E+11 |
May | 0.000 | 0.471859E+10 |
June | 0.000 | 0.486130E+09 |
July | 0.000 | 379501.172 |
August | 0.000 | 0.212769E+08 |
September | 0.000 | 0.774920E+09 |
October | 0.000 | 0.767676E+10 |
November | 0.000 | 0.339172E+11 |
December | 0.000 | 0.575742E+11 |
Annual Sum or Average | 0.261638E+12 | |
Minimum of Months | 0.000 | 379501.172 |
Maximum of Months | 0.000 | 0.667527E+11 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.191772E+11 | 20108.35 | 13-JAN-08:30 | 2.80 | 1.90 | 0.182062E+10 | 2606.61 | 27-JAN-14:09 | 9.72 | 8.08 |
February | 0.193684E+11 | 30429.57 | 10-FEB-05:01 | 2.30 | 1.32 | 0.172392E+10 | 2606.61 | 10-FEB-14:09 | 6.20 | 4.16 |
March | 0.252434E+11 | 48169.24 | 02-MAR-05:01 | 1.02 | 0.09 | 0.210709E+10 | 2606.71 | 13-MAR-13:09 | 11.20 | 7.80 |
April | 0.245733E+11 | 53021.17 | 28-APR-04:02 | 11.60 | 10.10 | 0.188083E+10 | 2608.55 | 20-APR-09:00 | 10.00 | 7.48 |
May | 0.289051E+11 | 53256.28 | 08-MAY-04:02 | 8.98 | 8.71 | 0.205092E+10 | 2606.68 | 26-MAY-13:09 | 12.48 | 11.47 |
June | 0.307687E+11 | 55973.64 | 12-JUN-04:01 | 14.90 | 13.65 | 0.205231E+10 | 2606.69 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.310691E+11 | 57131.29 | 10-JUL-04:01 | 13.30 | 12.00 | 0.191097E+10 | 2606.61 | 21-JUL-13:09 | 21.60 | 14.89 |
August | 0.346897E+11 | 58356.30 | 10-AUG-04:03 | 17.90 | 14.45 | 0.214628E+10 | 2606.95 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.294017E+11 | 56966.81 | 05-SEP-04:01 | 11.52 | 9.75 | 0.190017E+10 | 2606.61 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.258676E+11 | 52843.88 | 05-OCT-04:02 | 9.22 | 5.87 | 0.196149E+10 | 2606.64 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.222082E+11 | 48951.99 | 06-NOV-05:02 | 10.68 | 8.05 | 0.192240E+10 | 2608.04 | 15-NOV-14:20 | 9.63 | 6.73 |
December | 0.208399E+11 | 23196.42 | 07-DEC-05:01 | 3.40 | 2.75 | 0.182974E+10 | 2606.76 | 13-DEC-14:09 | 7.10 | 5.11 |
Annual Sum or Average | 0.312112E+12 | 0.233067E+11 | ||||||||
Minimum of Months | 0.191772E+11 | 20108.35 | 1.02 | 0.09 | 0.172392E+10 | 2606.61 | 6.20 | 4.16 | ||
Maximum of Months | 0.346897E+11 | 58356.30 | 17.90 | 14.45 | 0.214628E+10 | 2608.55 | 23.80 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 13304215.83 | 671.50 | 20-JAN-14:30 | 6.95 | 4.82 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.253477E+09 | 2876.60 | 27-FEB-14:30 | 19.15 | 11.78 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.108264E+10 | 4367.02 | 14-MAR-13:50 | 15.40 | 10.32 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.228177E+10 | 9240.84 | 27-APR-14:30 | 26.65 | 17.04 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.372002E+10 | 9494.45 | 15-MAY-14:40 | 23.30 | 12.89 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.452306E+10 | 9859.34 | 28-JUN-14:50 | 25.92 | 15.54 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.564050E+10 | 10843.88 | 24-JUL-14:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.558151E+10 | 11322.88 | 10-AUG-14:50 | 30.07 | 18.93 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.315983E+10 | 8478.32 | 14-SEP-14:30 | 23.90 | 17.02 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.112013E+10 | 5618.89 | 04-OCT-13:30 | 20.85 | 11.29 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.180551E+09 | 3369.49 | 04-NOV-14:00 | 21.10 | 15.93 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 14055315.78 | 746.12 | 05-DEC-13:40 | 10.60 | 6.31 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.275708E+11 | 0.00 | ||||||||
Minimum of Months | 13304215.83 | 671.50 | 6.95 | 4.82 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.564050E+10 | 11322.88 | 30.07 | 18.93 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 65532670.42 | 2001.88 | 07-JAN-17:50 | 1.78 | 0.86 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.272957E+09 | 2196.39 | 04-FEB-17:10 | 7.20 | 5.92 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.721041E+09 | 2153.85 | 04-MAR-17:10 | 6.60 | 4.44 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.121575E+10 | 3373.52 | 28-APR-04:10 | 11.60 | 10.10 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.206250E+10 | 3587.24 | 05-MAY-05:02 | 12.98 | 10.75 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.270476E+10 | 3687.75 | 22-JUN-04:10 | 11.60 | 10.67 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.315077E+10 | 3783.21 | 25-JUL-04:10 | 13.90 | 12.98 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.353229E+10 | 4286.59 | 10-AUG-04:12 | 17.80 | 14.42 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.244046E+10 | 3794.56 | 14-SEP-04:10 | 13.72 | 12.77 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.109628E+10 | 2689.19 | 05-OCT-04:10 | 9.22 | 5.87 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.333083E+09 | 1932.65 | 18-NOV-17:40 | 11.70 | 9.50 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.109256E+09 | 2179.46 | 09-DEC-17:14 | 5.93 | 4.31 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.177047E+11 | 0.00 | ||||||||
Minimum of Months | 65532670.42 | 1932.65 | 1.78 | 0.86 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.353229E+10 | 4286.59 | 17.80 | 14.42 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.200231E+09 | 2031.64 | 07-JAN-17:50 | 1.78 | 0.86 | 0.00 | 0.00 | 01-JAN-00:10 | 5.92 | 4.99 |
February | 0.463804E+09 | 2168.18 | 04-FEB-17:10 | 7.20 | 5.92 | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 | 6.66 |
March | 0.107297E+10 | 2240.08 | 04-MAR-17:10 | 6.60 | 4.44 | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 | 4.69 |
April | 0.165433E+10 | 3812.40 | 27-APR-04:10 | 10.73 | 8.44 | 0.00 | 0.00 | 01-APR-00:10 | 7.93 | 7.13 |
May | 0.258717E+10 | 4013.94 | 05-MAY-04:10 | 13.22 | 10.57 | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 | 9.30 |
June | 0.316736E+10 | 4329.51 | 22-JUN-04:08 | 11.60 | 10.67 | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 | 10.28 |
July | 0.356117E+10 | 4293.15 | 08-JUL-04:10 | 13.30 | 11.12 | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 | 12.21 |
August | 0.404972E+10 | 4664.22 | 10-AUG-04:12 | 17.80 | 14.42 | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 | 13.74 |
September | 0.300238E+10 | 4391.26 | 14-SEP-04:07 | 13.72 | 12.77 | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 | 13.40 |
October | 0.163717E+10 | 3487.31 | 05-OCT-04:10 | 9.22 | 5.87 | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 | 12.41 |
November | 0.622019E+09 | 2294.66 | 04-NOV-04:15 | 13.13 | 11.87 | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 | 8.03 |
December | 0.334369E+09 | 2082.08 | 30-DEC-17:10 | 5.60 | 4.80 | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 | 3.48 |
Annual Sum or Average | 0.223527E+11 | 0.00 | ||||||||
Minimum of Months | 0.200231E+09 | 2031.64 | 1.78 | 0.86 | 0.00 | 0.00 | 4.40 | 3.48 | ||
Maximum of Months | 0.404972E+10 | 4664.22 | 17.80 | 14.42 | 0.00 | 0.00 | 17.17 | 13.74 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.939866E+10 | 9217.99 | 06-JAN-08:20 | -2.6 | -2.6 | 0.159853E+10 | 2350.86 | 12-JAN-14:00 | 7.20 | 5.88 |
February | 0.989983E+10 | 9729.60 | 28-FEB-17:00 | 14.40 | 10.81 | 0.151559E+10 | 2489.34 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.131572E+11 | 10472.98 | 02-MAR-17:00 | 12.80 | 8.56 | 0.191923E+10 | 2561.92 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.129408E+11 | 32766.56 | 28-APR-04:02 | 11.60 | 10.10 | 0.178033E+10 | 2606.61 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.153393E+11 | 32815.86 | 05-MAY-04:02 | 13.22 | 10.57 | 0.201544E+10 | 2607.96 | 09-MAY-09:09 | 11.78 | 9.90 |
June | 0.170741E+11 | 34290.34 | 29-JUN-04:01 | 13.22 | 11.72 | 0.203767E+10 | 2606.65 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.180069E+11 | 35105.64 | 25-JUL-04:01 | 13.90 | 12.98 | 0.190116E+10 | 2606.62 | 06-JUL-13:09 | 20.60 | 14.59 |
August | 0.200408E+11 | 36771.74 | 10-AUG-04:03 | 17.90 | 14.45 | 0.213683E+10 | 2606.80 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.158390E+11 | 34406.97 | 15-SEP-04:01 | 11.70 | 11.34 | 0.187565E+10 | 2606.60 | 11-SEP-09:39 | 18.17 | 13.90 |
October | 0.130699E+11 | 31416.74 | 05-OCT-04:02 | 9.22 | 5.87 | 0.184965E+10 | 2606.62 | 05-OCT-09:39 | 13.17 | 8.61 |
November | 0.111975E+11 | 9765.24 | 03-NOV-16:00 | 13.30 | 12.93 | 0.170302E+10 | 2499.19 | 03-NOV-13:00 | 13.30 | 12.64 |
December | 0.103476E+11 | 9433.19 | 06-DEC-16:10 | 2.93 | 2.59 | 0.158927E+10 | 2439.11 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.166312E+12 | 0.219224E+11 | ||||||||
Minimum of Months | 0.939866E+10 | 9217.99 | -2.6 | -2.6 | 0.151559E+10 | 2350.86 | 5.00 | 4.36 | ||
Maximum of Months | 0.200408E+11 | 36771.74 | 17.90 | 14.45 | 0.213683E+10 | 2607.96 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.697610E+10 | 8683.65 | 11-JAN-16:50 | 12.57 | 9.48 | 0.152369E+10 | 2252.71 | 20-JAN-14:00 | 7.20 | 4.93 |
February | 0.786566E+10 | 9474.04 | 28-FEB-17:00 | 14.40 | 10.81 | 0.143594E+10 | 2432.04 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.112187E+11 | 9907.99 | 02-MAR-17:00 | 12.80 | 8.56 | 0.181692E+10 | 2529.98 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.120921E+11 | 18426.44 | 27-APR-15:50 | 27.20 | 16.95 | 0.171557E+10 | 2606.62 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.151305E+11 | 31955.08 | 05-MAY-04:02 | 13.22 | 10.57 | 0.196462E+10 | 2606.64 | 26-MAY-13:09 | 12.48 | 11.47 |
June | 0.168590E+11 | 34134.89 | 12-JUN-04:01 | 14.90 | 13.65 | 0.201387E+10 | 2606.66 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.181332E+11 | 34225.64 | 25-JUL-04:01 | 13.90 | 12.98 | 0.188992E+10 | 2606.61 | 06-JUL-13:09 | 20.60 | 14.59 |
August | 0.197625E+11 | 35108.85 | 10-AUG-04:01 | 17.90 | 14.45 | 0.211994E+10 | 2606.78 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.146771E+11 | 32713.00 | 14-SEP-04:01 | 13.72 | 12.77 | 0.182318E+10 | 2606.58 | 11-SEP-09:39 | 18.17 | 13.90 |
October | 0.115776E+11 | 15329.70 | 04-OCT-16:00 | 21.10 | 11.38 | 0.174158E+10 | 2606.52 | 03-OCT-13:09 | 18.30 | 10.43 |
November | 0.865933E+10 | 9375.50 | 02-NOV-15:40 | 13.30 | 10.98 | 0.158807E+10 | 2398.53 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.721315E+10 | 8838.37 | 06-DEC-15:50 | 3.58 | 3.15 | 0.149109E+10 | 2297.54 | 06-DEC-14:00 | 5.00 | 4.36 |
Annual Sum or Average | 0.150165E+12 | 0.211244E+11 | ||||||||
Minimum of Months | 0.697610E+10 | 8683.65 | 3.58 | 3.15 | 0.143594E+10 | 2252.71 | 5.00 | 4.36 | ||
Maximum of Months | 0.197625E+11 | 35108.85 | 27.20 | 16.95 | 0.211994E+10 | 2606.78 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.369307E+09 | 2023.38 | 11-JAN-16:00 | 14.40 | 10.48 | 0.305327E+09 | 420.05 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.756029E+09 | 2325.64 | 27-FEB-16:20 | 19.23 | 12.32 | 0.281578E+09 | 477.22 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.169654E+10 | 2440.31 | 10-MAR-14:50 | 16.20 | 11.58 | 0.349553E+09 | 503.17 | 10-MAR-14:00 | 16.10 | 11.49 |
April | 0.237193E+10 | 5155.59 | 27-APR-15:40 | 27.20 | 17.01 | 0.335038E+09 | 549.49 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.345527E+10 | 5052.83 | 15-MAY-15:20 | 23.50 | 12.67 | 0.392974E+09 | 549.49 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.411750E+10 | 5796.22 | 21-JUN-15:40 | 24.80 | 15.83 | 0.409631E+09 | 549.50 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.464997E+10 | 6802.46 | 24-JUL-15:00 | 30.60 | 18.76 | 0.388712E+09 | 549.49 | 21-JUL-13:39 | 21.30 | 15.01 |
August | 0.503542E+10 | 6513.14 | 09-AUG-15:30 | 28.70 | 18.81 | 0.435455E+09 | 549.53 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.337368E+10 | 4941.11 | 14-SEP-15:50 | 24.32 | 17.01 | 0.362759E+09 | 549.48 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.198197E+10 | 3028.62 | 04-OCT-15:30 | 21.40 | 11.43 | 0.334009E+09 | 547.11 | 04-OCT-13:00 | 21.10 | 11.38 |
November | 0.946503E+09 | 2253.67 | 02-NOV-14:40 | 13.67 | 11.25 | 0.307854E+09 | 461.64 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.422399E+09 | 1909.56 | 29-DEC-15:00 | 10.60 | 8.76 | 0.295163E+09 | 406.68 | 26-DEC-10:00 | 0.10 | 0.04 |
Annual Sum or Average | 0.291765E+11 | 0.419805E+10 | ||||||||
Minimum of Months | 0.369307E+09 | 1909.56 | 10.60 | 8.76 | 0.281578E+09 | 406.68 | 0.10 | 0.04 | ||
Maximum of Months | 0.503542E+10 | 6802.46 | 30.60 | 18.81 | 0.435455E+09 | 549.53 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304277E+09 | 2291.05 | 28-JAN-17:02 | 6.70 | 5.64 | 0.193702E+09 | 257.46 | 02-JAN-10:00 | 8.30 | 5.92 |
February | 0.760241E+09 | 2584.06 | 27-FEB-15:50 | 19.50 | 12.37 | 0.176601E+09 | 270.85 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.183422E+10 | 3145.83 | 14-MAR-09:35 | 9.27 | 7.13 | 0.217028E+09 | 332.01 | 14-MAR-09:50 | 9.63 | 7.44 |
April | 0.276139E+10 | 6410.37 | 27-APR-09:00 | 17.80 | 12.19 | 0.212320E+09 | 347.88 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.375163E+10 | 6423.27 | 15-MAY-08:50 | 16.83 | 11.55 | 0.240038E+09 | 347.88 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.455331E+10 | 7111.88 | 28-JUN-09:00 | 18.90 | 13.38 | 0.253932E+09 | 347.88 | 28-JUN-09:00 | 21.10 | 14.50 |
July | 0.490700E+10 | 8575.32 | 31-JUL-08:30 | 21.65 | 16.75 | 0.241596E+09 | 347.87 | 18-JUL-09:09 | 17.07 | 11.94 |
August | 0.544381E+10 | 8927.27 | 10-AUG-08:30 | 21.75 | 16.97 | 0.269788E+09 | 347.93 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.366693E+10 | 6381.02 | 14-SEP-09:10 | 17.38 | 15.51 | 0.222266E+09 | 347.87 | 11-SEP-09:00 | 18.90 | 14.29 |
October | 0.206337E+10 | 4369.88 | 04-OCT-09:00 | 15.60 | 10.48 | 0.207139E+09 | 347.87 | 03-OCT-09:09 | 13.17 | 8.47 |
November | 0.785202E+09 | 2505.85 | 02-NOV-14:10 | 14.22 | 11.34 | 0.192895E+09 | 265.57 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.365044E+09 | 2286.85 | 23-DEC-17:02 | 5.60 | 5.27 | 0.187131E+09 | 257.45 | 26-DEC-10:00 | 0.10 | 0.04 |
Annual Sum or Average | 0.311964E+11 | 0.261444E+10 | ||||||||
Minimum of Months | 0.304277E+09 | 2286.85 | 5.60 | 5.27 | 0.176601E+09 | 257.45 | 0.10 | 0.04 | ||
Maximum of Months | 0.544381E+10 | 8927.27 | 21.75 | 16.97 | 0.269788E+09 | 347.93 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122995E+10 | 8248.30 | 20-JAN-13:04 | 6.70 | 4.71 | 0.312509E+09 | 549.48 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.198069E+10 | 8966.40 | 27-FEB-14:30 | 19.15 | 11.78 | 0.299563E+09 | 549.49 | 27-FEB-14:50 | 19.72 | 12.03 |
March | 0.354271E+10 | 10141.17 | 01-MAR-13:25 | 11.15 | 5.97 | 0.367795E+09 | 549.50 | 02-MAR-14:00 | 13.30 | 8.56 |
April | 0.416583E+10 | 11583.07 | 27-APR-13:10 | 26.10 | 16.35 | 0.340074E+09 | 549.51 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.525111E+10 | 8534.08 | 15-MAY-13:00 | 22.80 | 13.79 | 0.377067E+09 | 549.50 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.583054E+10 | 7770.82 | 11-JUN-12:31 | 21.70 | 15.38 | 0.387217E+09 | 549.50 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.664589E+10 | 12224.85 | 30-JUL-12:42 | 26.10 | 17.64 | 0.372086E+09 | 549.49 | 20-JUL-13:00 | 26.70 | 16.71 |
August | 0.785042E+10 | 13550.72 | 29-AUG-12:30 | 28.65 | 19.73 | 0.418848E+09 | 549.48 | 15-AUG-13:00 | 25.50 | 16.37 |
September | 0.642369E+10 | 19405.51 | 10-SEP-13:12 | 21.13 | 14.28 | 0.355629E+09 | 549.50 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.422421E+10 | 13687.43 | 04-OCT-13:00 | 20.60 | 11.19 | 0.347783E+09 | 549.49 | 25-OCT-13:09 | 13.40 | 10.30 |
November | 0.187971E+10 | 8683.09 | 04-NOV-13:30 | 20.85 | 15.99 | 0.315094E+09 | 549.48 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.146076E+10 | 7958.91 | 05-DEC-12:30 | 10.30 | 6.12 | 0.307834E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.504855E+11 | 0.420150E+10 | ||||||||
Minimum of Months | 0.122995E+10 | 7770.82 | 6.70 | 4.71 | 0.299563E+09 | 549.48 | 6.78 | 4.75 | ||
Maximum of Months | 0.785042E+10 | 19405.51 | 28.65 | 19.73 | 0.418848E+09 | 549.51 | 26.70 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.328958E+09 | 2759.31 | 05-JAN-15:50 | 6.20 | 4.70 | 0.193746E+09 | 257.45 | 09-JAN-10:00 | 4.40 | 1.06 |
February | 0.753989E+09 | 3559.52 | 27-FEB-15:40 | 19.60 | 12.33 | 0.178017E+09 | 328.03 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.172887E+10 | 5336.35 | 14-MAR-16:00 | 17.20 | 10.93 | 0.216381E+09 | 338.68 | 02-MAR-16:00 | 12.80 | 8.56 |
April | 0.267471E+10 | 8364.71 | 26-APR-16:00 | 24.40 | 14.46 | 0.200478E+09 | 346.65 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.407235E+10 | 16222.64 | 07-MAY-17:12 | 21.50 | 16.08 | 0.226545E+09 | 347.57 | 15-MAY-13:00 | 23.30 | 13.48 |
June | 0.468744E+10 | 15243.26 | 18-JUN-17:22 | 16.95 | 12.24 | 0.234170E+09 | 347.79 | 21-JUN-13:00 | 23.30 | 15.01 |
July | 0.556233E+10 | 17200.77 | 30-JUL-17:21 | 26.70 | 17.75 | 0.226819E+09 | 347.84 | 20-JUL-13:00 | 26.70 | 16.71 |
August | 0.578135E+10 | 15369.66 | 06-AUG-18:22 | 22.80 | 15.11 | 0.252284E+09 | 347.83 | 09-AUG-13:50 | 28.32 | 18.13 |
September | 0.397367E+10 | 15548.74 | 10-SEP-16:32 | 22.20 | 14.26 | 0.210404E+09 | 346.91 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.202985E+10 | 6727.17 | 04-OCT-16:00 | 21.10 | 11.38 | 0.202684E+09 | 338.68 | 03-OCT-15:00 | 18.30 | 10.42 |
November | 0.756840E+09 | 3214.88 | 04-NOV-15:40 | 20.37 | 15.92 | 0.193223E+09 | 278.91 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.395694E+09 | 2875.53 | 05-DEC-15:30 | 8.05 | 5.81 | 0.187244E+09 | 266.98 | 05-DEC-15:39 | 7.40 | 5.39 |
Annual Sum or Average | 0.327460E+11 | 0.252200E+10 | ||||||||
Minimum of Months | 0.328958E+09 | 2759.31 | 6.20 | 4.70 | 0.178017E+09 | 257.45 | 4.40 | 1.06 | ||
Maximum of Months | 0.578135E+10 | 17200.77 | 26.70 | 17.75 | 0.252284E+09 | 347.84 | 28.32 | 18.13 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.430851E+09 | 1619.20 | 11-JAN-16:00 | 14.40 | 10.48 | 0.306505E+09 | 427.74 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.698626E+09 | 1779.84 | 28-FEB-15:00 | 13.90 | 10.80 | 0.282793E+09 | 466.74 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.144403E+10 | 1847.65 | 10-MAR-14:40 | 16.30 | 11.67 | 0.349445E+09 | 484.86 | 10-MAR-14:50 | 16.20 | 11.58 |
April | 0.184598E+10 | 2659.60 | 27-APR-16:00 | 27.20 | 16.88 | 0.329698E+09 | 549.49 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.264326E+10 | 3162.39 | 05-MAY-15:40 | 24.80 | 17.24 | 0.390322E+09 | 549.48 | 04-MAY-13:09 | 22.48 | 15.27 |
June | 0.309182E+10 | 3848.24 | 21-JUN-16:00 | 25.00 | 16.15 | 0.412069E+09 | 549.49 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.347887E+10 | 4584.95 | 24-JUL-15:20 | 30.03 | 18.70 | 0.393677E+09 | 549.48 | 21-JUL-13:09 | 21.60 | 14.89 |
August | 0.396349E+10 | 5518.16 | 10-AUG-04:01 | 17.90 | 14.45 | 0.443440E+09 | 549.52 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.292112E+10 | 3744.93 | 14-SEP-15:50 | 24.32 | 17.01 | 0.377057E+09 | 549.48 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.218359E+10 | 2206.98 | 04-OCT-16:00 | 21.10 | 11.38 | 0.352763E+09 | 543.75 | 04-OCT-13:00 | 21.10 | 11.38 |
November | 0.139913E+10 | 1856.45 | 02-NOV-14:10 | 14.22 | 11.34 | 0.320694E+09 | 486.09 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.687673E+09 | 1616.65 | 29-DEC-14:10 | 11.02 | 8.99 | 0.297919E+09 | 425.11 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.247884E+11 | 0.425638E+10 | ||||||||
Minimum of Months | 0.430851E+09 | 1616.65 | 11.02 | 8.99 | 0.282793E+09 | 425.11 | 10.60 | 8.76 | ||
Maximum of Months | 0.396349E+10 | 5518.16 | 30.03 | 18.70 | 0.443440E+09 | 549.52 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.345370E+09 | 2038.15 | 11-JAN-05:04 | 10.00 | 7.32 | 0.194261E+09 | 257.48 | 02-JAN-10:00 | 8.30 | 5.92 |
February | 0.699730E+09 | 2111.21 | 27-FEB-15:40 | 19.60 | 12.33 | 0.176983E+09 | 264.52 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.162015E+10 | 2431.12 | 14-MAR-08:40 | 7.07 | 5.44 | 0.215864E+09 | 303.73 | 14-MAR-09:39 | 9.27 | 7.13 |
April | 0.235049E+10 | 4187.41 | 27-APR-09:10 | 17.98 | 12.32 | 0.208672E+09 | 347.87 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.312915E+10 | 4549.26 | 15-MAY-09:00 | 17.20 | 11.69 | 0.235411E+09 | 347.88 | 15-MAY-09:00 | 18.90 | 13.24 |
June | 0.383152E+10 | 5208.03 | 28-JUN-09:10 | 19.27 | 13.57 | 0.253580E+09 | 347.88 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.413857E+10 | 6447.90 | 24-JUL-09:00 | 23.90 | 16.62 | 0.241971E+09 | 347.87 | 19-JUL-09:00 | 18.30 | 13.51 |
August | 0.479559E+10 | 7425.01 | 13-AUG-07:12 | 18.43 | 14.55 | 0.273698E+09 | 347.92 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.353738E+10 | 5157.92 | 14-SEP-09:10 | 17.38 | 15.51 | 0.226459E+09 | 347.87 | 11-SEP-09:39 | 18.17 | 13.90 |
October | 0.237122E+10 | 3502.99 | 04-OCT-08:20 | 14.47 | 9.99 | 0.212621E+09 | 347.87 | 04-OCT-09:09 | 15.87 | 10.56 |
November | 0.121611E+10 | 2210.92 | 02-NOV-14:00 | 14.40 | 11.36 | 0.194600E+09 | 276.70 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.563005E+09 | 1953.29 | 23-DEC-17:02 | 5.60 | 5.27 | 0.187955E+09 | 257.45 | 26-DEC-10:00 | 0.10 | 0.04 |
Annual Sum or Average | 0.285983E+11 | 0.262208E+10 | ||||||||
Minimum of Months | 0.345370E+09 | 1953.29 | 5.60 | 5.27 | 0.176983E+09 | 257.45 | 0.10 | 0.04 | ||
Maximum of Months | 0.479559E+10 | 7425.01 | 23.90 | 16.62 | 0.273698E+09 | 347.92 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.311768E+09 | 3188.22 | 20-JAN-13:50 | 6.70 | 4.71 | 0.292225E+09 | 471.03 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.824839E+09 | 4432.30 | 27-FEB-14:55 | 20.00 | 12.15 | 0.276365E+09 | 549.50 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.161030E+10 | 3658.12 | 01-MAR-15:00 | 13.30 | 7.36 | 0.339810E+09 | 546.44 | 01-MAR-14:00 | 13.30 | 7.36 |
April | 0.230187E+10 | 8040.61 | 27-APR-16:10 | 27.02 | 16.87 | 0.312589E+09 | 549.51 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.315578E+10 | 4625.60 | 15-MAY-13:10 | 22.88 | 13.74 | 0.347010E+09 | 549.50 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.394779E+10 | 6490.93 | 28-JUN-17:00 | 26.70 | 16.72 | 0.361254E+09 | 549.49 | 28-JUN-13:50 | 24.90 | 15.64 |
July | 0.490241E+10 | 10836.24 | 31-JUL-16:10 | 28.80 | 19.09 | 0.361768E+09 | 549.50 | 21-JUL-13:20 | 21.50 | 14.93 |
August | 0.643196E+10 | 13042.94 | 10-AUG-17:00 | 31.80 | 18.67 | 0.416728E+09 | 549.55 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.489929E+10 | 11318.33 | 14-SEP-04:01 | 13.72 | 12.77 | 0.351673E+09 | 549.49 | 29-SEP-13:39 | 20.03 | 13.21 |
October | 0.311606E+10 | 10542.44 | 04-OCT-13:30 | 20.85 | 11.29 | 0.338778E+09 | 549.49 | 03-OCT-13:09 | 18.30 | 10.43 |
November | 0.102858E+10 | 6081.44 | 04-NOV-13:30 | 20.85 | 15.99 | 0.301730E+09 | 508.29 | 15-NOV-14:09 | 9.82 | 6.79 |
December | 0.613775E+09 | 3877.58 | 02-DEC-13:10 | 12.20 | 5.88 | 0.288524E+09 | 515.09 | 05-DEC-11:00 | 10.00 | 6.06 |
Annual Sum or Average | 0.331444E+11 | 0.398846E+10 | ||||||||
Minimum of Months | 0.311768E+09 | 3188.22 | 6.70 | 4.71 | 0.276365E+09 | 471.03 | 6.78 | 4.75 | ||
Maximum of Months | 0.643196E+10 | 13042.94 | 31.80 | 19.09 | 0.416728E+09 | 549.55 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.350413E+09 | 2315.16 | 05-JAN-15:50 | 6.20 | 4.70 | 0.194300E+09 | 257.46 | 02-JAN-10:00 | 8.30 | 5.92 |
February | 0.694466E+09 | 2790.75 | 27-FEB-15:50 | 19.50 | 12.37 | 0.177842E+09 | 305.13 | 27-FEB-15:00 | 19.40 | 12.41 |
March | 0.152730E+10 | 3025.02 | 02-MAR-16:50 | 12.88 | 8.53 | 0.214588E+09 | 331.60 | 02-MAR-16:00 | 12.80 | 8.56 |
April | 0.224785E+10 | 5324.27 | 26-APR-17:00 | 24.40 | 13.92 | 0.197296E+09 | 338.67 | 27-APR-15:20 | 27.20 | 17.14 |
May | 0.340770E+10 | 6806.95 | 07-MAY-16:32 | 21.87 | 16.21 | 0.225201E+09 | 338.68 | 08-MAY-15:00 | 18.90 | 14.80 |
June | 0.397967E+10 | 6131.85 | 22-JUN-18:10 | 23.80 | 16.21 | 0.234437E+09 | 341.98 | 21-JUN-13:00 | 23.30 | 15.01 |
July | 0.468847E+10 | 12026.36 | 23-JUL-18:01 | 25.82 | 15.87 | 0.232395E+09 | 347.83 | 24-JUL-13:50 | 29.22 | 18.14 |
August | 0.503748E+10 | 8778.12 | 09-AUG-04:01 | 14.93 | 12.08 | 0.260272E+09 | 347.84 | 09-AUG-13:39 | 28.13 | 17.99 |
September | 0.383804E+10 | 9608.41 | 10-SEP-16:32 | 22.20 | 14.26 | 0.217115E+09 | 339.62 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.242410E+10 | 5504.00 | 04-OCT-16:00 | 21.10 | 11.38 | 0.205644E+09 | 338.68 | 03-OCT-15:00 | 18.30 | 10.42 |
November | 0.118923E+10 | 2703.52 | 04-NOV-15:50 | 20.18 | 15.91 | 0.194384E+09 | 280.52 | 10-NOV-15:50 | 9.08 | 6.53 |
December | 0.563746E+09 | 2477.76 | 05-DEC-15:40 | 7.40 | 5.39 | 0.188164E+09 | 272.48 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.299485E+11 | 0.254164E+10 | ||||||||
Minimum of Months | 0.350413E+09 | 2315.16 | 6.20 | 4.70 | 0.177842E+09 | 257.46 | 6.75 | 4.97 | ||
Maximum of Months | 0.503748E+10 | 12026.36 | 25.82 | 16.21 | 0.260272E+09 | 347.84 | 29.22 | 18.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.675788E+09 | 1960.91 | 11-JAN-16:00 | 14.40 | 10.48 | 0.307527E+09 | 440.50 | 11-JAN-14:00 | 14.40 | 10.48 |
February | 0.108020E+10 | 2210.43 | 28-FEB-15:00 | 13.90 | 10.80 | 0.286737E+09 | 494.35 | 28-FEB-14:00 | 13.90 | 10.80 |
March | 0.212797E+10 | 2293.13 | 10-MAR-14:50 | 16.20 | 11.58 | 0.361625E+09 | 514.22 | 10-MAR-14:00 | 16.10 | 11.49 |
April | 0.254054E+10 | 4589.75 | 27-APR-16:00 | 27.20 | 16.88 | 0.345925E+09 | 549.49 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.347535E+10 | 4717.87 | 05-MAY-15:40 | 24.80 | 17.24 | 0.405239E+09 | 549.48 | 31-MAY-13:09 | 20.60 | 15.46 |
June | 0.399976E+10 | 5223.77 | 21-JUN-15:50 | 24.90 | 15.99 | 0.419002E+09 | 549.50 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.443120E+10 | 5984.38 | 24-JUL-15:00 | 30.60 | 18.76 | 0.395233E+09 | 549.49 | 28-JUL-13:39 | 21.10 | 15.46 |
August | 0.489545E+10 | 6918.66 | 25-AUG-04:01 | 18.07 | 15.52 | 0.443627E+09 | 549.54 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.348955E+10 | 4612.17 | 14-SEP-15:50 | 24.32 | 17.01 | 0.377359E+09 | 549.48 | 12-SEP-09:00 | 20.60 | 15.49 |
October | 0.240745E+10 | 3014.17 | 04-OCT-15:30 | 21.40 | 11.43 | 0.351306E+09 | 549.47 | 05-OCT-13:00 | 16.10 | 10.64 |
November | 0.144831E+10 | 2165.39 | 02-NOV-14:40 | 13.67 | 11.25 | 0.317117E+09 | 483.48 | 02-NOV-13:00 | 14.40 | 11.36 |
December | 0.835462E+09 | 1892.67 | 29-DEC-15:00 | 10.60 | 8.76 | 0.297936E+09 | 427.26 | 29-DEC-14:00 | 10.60 | 8.76 |
Annual Sum or Average | 0.314070E+11 | 0.430863E+10 | ||||||||
Minimum of Months | 0.675788E+09 | 1892.67 | 10.60 | 8.76 | 0.286737E+09 | 427.26 | 10.60 | 8.76 | ||
Maximum of Months | 0.489545E+10 | 6918.66 | 30.60 | 18.76 | 0.443627E+09 | 549.54 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.462838E+09 | 2488.72 | 28-JAN-17:02 | 6.70 | 5.64 | 0.143071E+09 | 250.67 | 02-JAN-11:00 | 8.90 | 5.76 |
February | 0.984349E+09 | 2852.69 | 08-FEB-09:50 | 1.93 | 0.91 | 0.130641E+09 | 272.83 | 08-FEB-09:00 | 2.20 | 1.26 |
March | 0.225247E+10 | 3471.89 | 14-MAR-09:00 | 7.80 | 5.89 | 0.160026E+09 | 326.50 | 14-MAR-08:00 | 7.80 | 5.89 |
April | 0.311479E+10 | 6750.11 | 27-APR-08:50 | 17.52 | 12.19 | 0.155047E+09 | 338.72 | 27-APR-10:20 | 19.63 | 13.25 |
May | 0.411250E+10 | 6712.18 | 15-MAY-08:40 | 16.47 | 11.41 | 0.173661E+09 | 338.73 | 15-MAY-10:09 | 19.18 | 13.23 |
June | 0.484658E+10 | 7245.56 | 28-JUN-08:40 | 18.53 | 13.25 | 0.183546E+09 | 338.72 | 27-JUN-10:20 | 20.37 | 14.38 |
July | 0.513260E+10 | 8745.91 | 31-JUL-08:00 | 21.10 | 16.62 | 0.175127E+09 | 338.74 | 24-JUL-07:49 | 21.23 | 16.01 |
August | 0.569455E+10 | 9155.60 | 10-AUG-08:20 | 21.50 | 16.91 | 0.196468E+09 | 338.78 | 09-AUG-10:09 | 23.92 | 15.99 |
September | 0.416233E+10 | 11432.78 | 10-SEP-08:32 | 15.53 | 13.26 | 0.162447E+09 | 338.73 | 15-SEP-10:09 | 18.80 | 15.33 |
October | 0.257666E+10 | 5191.61 | 04-OCT-08:50 | 15.32 | 10.36 | 0.153140E+09 | 338.71 | 04-OCT-10:09 | 17.48 | 10.95 |
November | 0.116603E+10 | 2789.09 | 15-NOV-09:20 | 6.87 | 5.34 | 0.142961E+09 | 266.48 | 15-NOV-09:30 | 6.95 | 5.42 |
December | 0.615630E+09 | 2487.13 | 23-DEC-17:02 | 5.60 | 5.27 | 0.138500E+09 | 250.66 | 26-DEC-08:09 | -1.1 | -1.2 |
Annual Sum or Average | 0.351213E+11 | 0.191463E+10 | ||||||||
Minimum of Months | 0.462838E+09 | 2487.13 | 1.93 | 0.91 | 0.130641E+09 | 250.66 | -1.1 | -1.2 | ||
Maximum of Months | 0.569455E+10 | 11432.78 | 21.50 | 16.91 | 0.196468E+09 | 338.78 | 23.92 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.162985E+10 | 9011.97 | 20-JAN-13:04 | 6.70 | 4.71 | 0.316054E+09 | 549.48 | 20-JAN-14:09 | 6.78 | 4.75 |
February | 0.247685E+10 | 9205.91 | 27-FEB-14:10 | 18.58 | 11.53 | 0.304101E+09 | 549.49 | 27-FEB-14:00 | 20.00 | 12.15 |
March | 0.421500E+10 | 10650.33 | 01-MAR-13:25 | 11.15 | 5.97 | 0.373707E+09 | 549.51 | 21-MAR-13:09 | 11.78 | 7.55 |
April | 0.457457E+10 | 10959.98 | 27-APR-13:00 | 26.10 | 16.26 | 0.344777E+09 | 549.50 | 27-APR-13:00 | 26.10 | 16.81 |
May | 0.555681E+10 | 7792.97 | 15-MAY-12:50 | 22.70 | 13.63 | 0.382650E+09 | 549.50 | 15-MAY-13:09 | 22.88 | 13.74 |
June | 0.599348E+10 | 6658.29 | 21-JUN-13:30 | 22.50 | 15.03 | 0.391668E+09 | 549.50 | 09-JUN-13:09 | 21.78 | 13.49 |
July | 0.664674E+10 | 9935.33 | 31-JUL-13:00 | 27.20 | 18.23 | 0.376120E+09 | 549.50 | 28-JUL-13:39 | 21.10 | 15.46 |
August | 0.790716E+10 | 13023.66 | 29-AUG-12:30 | 28.65 | 19.73 | 0.424892E+09 | 549.52 | 09-AUG-09:00 | 23.80 | 15.90 |
September | 0.692557E+10 | 17952.79 | 10-SEP-14:02 | 22.30 | 14.57 | 0.363200E+09 | 549.50 | 07-SEP-13:09 | 17.98 | 13.78 |
October | 0.501260E+10 | 13727.45 | 04-OCT-12:50 | 20.60 | 11.25 | 0.355144E+09 | 549.50 | 05-OCT-09:00 | 13.90 | 9.27 |
November | 0.259567E+10 | 8975.70 | 04-NOV-13:20 | 20.77 | 16.00 | 0.321330E+09 | 549.48 | 15-NOV-14:00 | 8.90 | 6.48 |
December | 0.202683E+10 | 9016.93 | 05-DEC-12:30 | 10.30 | 6.12 | 0.312655E+09 | 549.50 | 05-DEC-14:00 | 10.00 | 7.00 |
Annual Sum or Average | 0.555611E+11 | 0.426630E+10 | ||||||||
Minimum of Months | 0.162985E+10 | 6658.29 | 6.70 | 4.71 | 0.304101E+09 | 549.48 | 6.78 | 4.75 | ||
Maximum of Months | 0.790716E+10 | 17952.79 | 28.65 | 19.73 | 0.424892E+09 | 549.52 | 26.10 | 16.81 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum}[W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.544371E+09 | 2846.29 | 05-JAN-15:50 | 6.20 | 4.70 | 0.194283E+09 | 265.19 | 05-JAN-15:00 | 6.10 | 4.61 |
February | 0.102807E+10 | 3558.43 | 27-FEB-15:40 | 19.60 | 12.33 | 0.178954E+09 | 328.63 | 27-FEB-15:50 | 19.50 | 12.37 |
March | 0.218872E+10 | 5132.89 | 14-MAR-16:00 | 17.20 | 10.93 | 0.217362E+09 | 338.68 | 02-MAR-16:00 | 12.80 | 8.56 |
April | 0.298544E+10 | 7955.91 | 26-APR-16:00 | 24.40 | 14.46 | 0.201270E+09 | 338.68 | 26-APR-15:09 | 24.90 | 14.67 |
May | 0.431907E+10 | 9740.15 | 14-MAY-17:12 | 22.60 | 11.81 | 0.227987E+09 | 340.92 | 15-MAY-13:00 | 23.30 | 13.48 |
June | 0.485061E+10 | 9272.54 | 25-JUN-16:22 | 21.70 | 13.21 | 0.235128E+09 | 345.08 | 21-JUN-13:00 | 23.30 | 15.01 |
July | 0.561345E+10 | 14818.78 | 23-JUL-17:12 | 26.50 | 15.67 | 0.227645E+09 | 347.83 | 24-JUL-13:00 | 29.40 | 18.10 |
August | 0.589908E+10 | 15211.88 | 06-AUG-17:32 | 23.67 | 15.19 | 0.254217E+09 | 347.83 | 09-AUG-13:00 | 28.50 | 18.26 |
September | 0.437726E+10 | 8388.14 | 11-SEP-16:00 | 23.30 | 16.13 | 0.213196E+09 | 341.31 | 12-SEP-13:00 | 24.40 | 16.53 |
October | 0.258255E+10 | 6694.24 | 04-OCT-16:00 | 21.10 | 11.38 | 0.204616E+09 | 338.68 | 03-OCT-15:00 | 18.30 | 10.42 |
November | 0.120527E+10 | 3237.97 | 04-NOV-15:40 | 20.37 | 15.92 | 0.194146E+09 | 286.98 | 10-NOV-14:00 | 10.00 | 6.83 |
December | 0.690530E+09 | 2974.20 | 05-DEC-15:40 | 7.40 | 5.39 | 0.188071E+09 | 276.05 | 05-DEC-15:50 | 6.75 | 4.97 |
Annual Sum or Average | 0.362844E+11 | 0.253688E+10 | ||||||||
Minimum of Months | 0.544371E+09 | 2846.29 | 6.20 | 4.70 | 0.178954E+09 | 265.19 | 6.10 | 4.61 | ||
Maximum of Months | 0.589908E+10 | 15211.88 | 26.50 | 16.13 | 0.254217E+09 | 347.83 | 29.40 | 18.26 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.312278E+09 | 33283.80 | 02-JAN-05:01 | 6.10 |
February | 251857.61 | 2597.27 | 21-FEB-05:44 | 1.70 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 9.22 |
December | 49715.48 | 828.59 | 26-DEC-05:06 | -0.6 |
Annual Sum or Average | 0.312580E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.312278E+09 | 33283.80 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.484354E+10 | 9850.19 | 09-JAN-06:10 | -1.5 |
February | 0.310185E+10 | 9634.22 | 13-FEB-06:00 | 2.20 |
March | 0.198758E+10 | 8407.32 | 06-MAR-05:10 | 6.70 |
April | 0.111429E+10 | 7321.33 | 11-APR-04:09 | 5.10 |
May | 0.481489E+09 | 8757.47 | 05-MAY-04:02 | 13.22 |
June | 0.183621E+09 | 9555.24 | 22-JUN-04:02 | 11.60 |
July | 90544715.87 | 9730.57 | 07-JUL-04:02 | 12.02 |
August | 0.121030E+09 | 9665.30 | 11-AUG-04:01 | 12.62 |
September | 0.344230E+09 | 9316.00 | 15-SEP-04:01 | 11.70 |
October | 0.127953E+10 | 7144.67 | 16-OCT-04:07 | 7.20 |
November | 0.246974E+10 | 9195.18 | 13-NOV-05:10 | 1.20 |
December | 0.408196E+10 | 9514.96 | 11-DEC-05:10 | 3.72 |
Annual Sum or Average | 0.200994E+11 | |||
Minimum of Months | 90544715.87 | 7144.67 | -1.5 | |
Maximum of Months | 0.484354E+10 | 9850.19 | 13.22 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184696E+10 | 7676.01 | 02-JAN-05:30 | 6.10 |
February | 0.902529E+09 | 6666.62 | 21-FEB-05:12 | 1.70 |
March | 0.327603E+09 | 4170.46 | 06-MAR-05:08 | 6.70 |
April | 85874639.64 | 3480.47 | 02-APR-12:52 | 18.90 |
May | 12594863.93 | 3301.19 | 29-MAY-16:10 | 16.20 |
June | 10362322.41 | 2987.16 | 25-JUN-14:58 | 21.70 |
July | 13501440.24 | 3051.21 | 17-JUL-04:02 | 14.32 |
August | 12181314.35 | 3094.24 | 06-AUG-12:12 | 20.23 |
September | 13138114.17 | 3188.33 | 03-SEP-15:11 | 18.17 |
October | 0.130291E+09 | 3770.47 | 08-OCT-11:52 | 17.80 |
November | 0.593004E+09 | 4262.07 | 27-NOV-05:06 | 12.12 |
December | 0.115568E+10 | 6401.60 | 26-DEC-05:10 | -0.6 |
Annual Sum or Average | 0.510371E+10 | |||
Minimum of Months | 10362322.41 | 2987.16 | -0.6 | |
Maximum of Months | 0.184696E+10 | 7676.01 | 21.70 |
Report: ZoneHeatingSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.153468E+10 | 8724.88 | 02-JAN-05:30 | 6.10 |
February | 0.670402E+09 | 4461.69 | 21-FEB-08:50 | 2.02 |
March | 0.255212E+09 | 6470.06 | 02-MAR-05:01 | 1.02 |
April | 90122860.38 | 7979.04 | 08-APR-04:01 | 6.70 |
May | 26919686.79 | 7604.17 | 18-MAY-04:01 | 6.52 |
June | 20012186.91 | 7273.32 | 14-JUN-04:02 | 10.00 |
July | 17801949.01 | 6874.55 | 17-JUL-04:02 | 14.32 |
August | 17137970.75 | 6094.40 | 28-AUG-04:01 | 15.55 |
September | 20818182.69 | 6979.44 | 25-SEP-04:02 | 13.30 |
October | 93559750.97 | 8660.36 | 28-OCT-04:01 | 7.88 |
November | 0.411048E+09 | 8618.14 | 06-NOV-05:02 | 10.68 |
December | 0.828655E+09 | 4246.88 | 26-DEC-08:40 | -1.1 |
Annual Sum or Average | 0.398637E+10 | |||
Minimum of Months | 17137970.75 | 4246.88 | -1.1 | |
Maximum of Months | 0.153468E+10 | 8724.88 | 15.55 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.553482E+09 | 21524.35 | 02-JAN-05:01 | 6.10 |
February | 96175141.40 | 18640.38 | 21-FEB-05:01 | 1.70 |
March | 4315492.65 | 16984.34 | 06-MAR-05:01 | 6.70 |
April | 0.00 | 0.00 | 01-APR-00:10 | 7.93 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
November | 7032179.28 | 17070.00 | 27-NOV-05:01 | 12.12 |
December | 0.116213E+09 | 18608.60 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.777219E+09 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.553482E+09 | 21524.35 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.161279E+10 | 21473.67 | 02-JAN-05:01 | 6.10 |
February | 0.739408E+09 | 20959.97 | 21-FEB-05:11 | 1.70 |
March | 0.192548E+09 | 18975.87 | 06-MAR-05:01 | 6.70 |
April | 13408326.94 | 17111.27 | 17-APR-04:01 | 6.10 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 51067497.50 | 17429.08 | 16-OCT-04:01 | 7.20 |
November | 0.437509E+09 | 18993.54 | 13-NOV-05:01 | 1.20 |
December | 0.996023E+09 | 21119.70 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.404276E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.161279E+10 | 21473.67 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.258765E+10 | 5931.92 | 16-JAN-08:43 | -0.7 |
February | 0.157541E+10 | 5934.66 | 20-FEB-05:53 | -0.6 |
March | 0.770228E+09 | 5663.62 | 06-MAR-05:01 | 6.70 |
April | 0.385295E+09 | 5291.08 | 11-APR-04:01 | 5.10 |
May | 64788264.16 | 4875.51 | 18-MAY-04:01 | 6.52 |
June | 7533545.63 | 4593.03 | 14-JUN-04:02 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 12431129.33 | 4587.47 | 27-SEP-04:03 | 7.20 |
October | 0.360181E+09 | 5262.81 | 30-OCT-04:01 | 7.20 |
November | 0.100756E+10 | 5690.47 | 13-NOV-05:01 | 1.20 |
December | 0.194585E+10 | 5872.29 | 26-DEC-04:13 | -0.9 |
Annual Sum or Average | 0.871693E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.9 | |
Maximum of Months | 0.258765E+10 | 5934.66 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179126E+10 | 7158.46 | 16-JAN-08:43 | -0.7 |
February | 0.103607E+10 | 7303.44 | 21-FEB-05:11 | 1.70 |
March | 0.506954E+09 | 7006.73 | 06-MAR-05:01 | 6.70 |
April | 0.242825E+09 | 6560.63 | 11-APR-04:01 | 5.10 |
May | 52325231.14 | 6038.16 | 18-MAY-04:01 | 6.52 |
June | 8224342.79 | 5683.32 | 14-JUN-04:02 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 19600.18 | 112.00 | 18-AUG-05:08 | 11.50 |
September | 10413585.52 | 5622.80 | 27-SEP-04:03 | 7.20 |
October | 0.256606E+09 | 6466.51 | 30-OCT-04:01 | 7.20 |
November | 0.706128E+09 | 7033.43 | 13-NOV-05:01 | 1.20 |
December | 0.134619E+10 | 7033.76 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.595702E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.7 | |
Maximum of Months | 0.179126E+10 | 7303.44 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.228800E+10 | 10038.63 | 01-JAN-22:03 | 6.10 |
February | 0.128489E+10 | 10129.17 | 21-FEB-05:11 | 1.70 |
March | 0.731245E+09 | 9747.04 | 06-MAR-05:01 | 6.70 |
April | 0.387118E+09 | 9106.95 | 11-APR-04:01 | 5.10 |
May | 77304638.69 | 8416.36 | 18-MAY-04:01 | 6.52 |
June | 10815336.63 | 7898.88 | 14-JUN-04:02 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 21888.67 | 145.92 | 19-AUG-05:08 | 12.18 |
September | 14141570.66 | 7824.88 | 27-SEP-04:03 | 7.20 |
October | 0.329310E+09 | 8844.16 | 16-OCT-04:01 | 7.20 |
November | 0.942246E+09 | 9649.58 | 13-NOV-05:01 | 1.20 |
December | 0.178303E+10 | 9831.66 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.784813E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.228800E+10 | 10129.17 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.182253E+10 | 7833.29 | 02-JAN-05:01 | 6.10 |
February | 0.106981E+10 | 8090.08 | 21-FEB-05:11 | 1.70 |
March | 0.544655E+09 | 7787.04 | 06-MAR-05:01 | 6.70 |
April | 0.273712E+09 | 7258.54 | 11-APR-04:01 | 5.10 |
May | 55681319.19 | 6715.37 | 18-MAY-04:01 | 6.52 |
June | 6820061.72 | 6254.42 | 14-JUN-04:02 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 52651.21 | 189.00 | 21-AUG-05:08 | 11.20 |
September | 9707567.56 | 4710.85 | 27-SEP-04:03 | 7.20 |
October | 0.258191E+09 | 7141.66 | 30-OCT-04:01 | 7.20 |
November | 0.720934E+09 | 7744.03 | 13-NOV-05:01 | 1.20 |
December | 0.137389E+10 | 7818.13 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.613598E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.182253E+10 | 8090.08 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.163812E+10 | 4597.60 | 01-JAN-22:03 | 6.10 |
February | 0.852533E+09 | 4400.04 | 21-FEB-05:01 | 1.70 |
March | 0.382725E+09 | 4047.57 | 06-MAR-05:01 | 6.70 |
April | 0.159577E+09 | 3846.74 | 11-APR-04:01 | 5.10 |
May | 4629186.75 | 3547.35 | 18-MAY-04:01 | 6.52 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 12.83 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 35127694.43 | 3715.65 | 30-OCT-04:01 | 7.20 |
November | 0.241613E+09 | 3880.45 | 13-NOV-05:01 | 1.20 |
December | 0.831122E+09 | 4245.21 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.414545E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.163812E+10 | 4597.60 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115033E+10 | 5961.29 | 02-JAN-05:01 | 6.10 |
February | 0.536288E+09 | 5787.28 | 21-FEB-05:01 | 1.70 |
March | 0.234456E+09 | 5382.27 | 06-MAR-05:01 | 6.70 |
April | 92011840.92 | 5113.79 | 11-APR-04:01 | 5.10 |
May | 8184403.41 | 4754.85 | 18-MAY-04:01 | 6.52 |
June | 399820.79 | 745.23 | 15-JUN-04:04 | 8.40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 291150.64 | 585.91 | 27-SEP-04:05 | 7.20 |
October | 29704103.78 | 4898.62 | 31-OCT-04:01 | 7.38 |
November | 0.182645E+09 | 5148.90 | 13-NOV-05:01 | 1.20 |
December | 0.606513E+09 | 5650.66 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.284082E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.115033E+10 | 5961.29 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.469188E+10 | 9055.23 | 06-JAN-07:10 | -2.3 |
February | 0.300375E+10 | 8784.45 | 09-FEB-07:10 | -0.7 |
March | 0.250728E+10 | 8733.91 | 01-MAR-07:10 | -0.1 |
April | 0.164385E+10 | 8330.44 | 19-APR-06:10 | 2.48 |
May | 0.110777E+10 | 7911.37 | 18-MAY-06:10 | 5.68 |
June | 0.678788E+09 | 7029.60 | 15-JUN-06:10 | 9.60 |
July | 0.335020E+09 | 6491.46 | 03-JUL-06:15 | 12.07 |
August | 0.258869E+09 | 6583.14 | 18-AUG-06:10 | 11.63 |
September | 0.586935E+09 | 7216.52 | 28-SEP-06:10 | 8.40 |
October | 0.120962E+10 | 7666.36 | 16-OCT-06:10 | 6.60 |
November | 0.250275E+10 | 8457.42 | 24-NOV-07:10 | 1.20 |
December | 0.365582E+10 | 9053.73 | 26-DEC-07:50 | -1.2 |
Annual Sum or Average | 0.221823E+11 | |||
Minimum of Months | 0.258869E+09 | 6491.46 | -2.3 | |
Maximum of Months | 0.469188E+10 | 9055.23 | 12.07 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115157E+10 | 6614.66 | 02-JAN-05:01 | 6.10 |
February | 0.534145E+09 | 6394.26 | 21-FEB-05:01 | 1.70 |
March | 0.242922E+09 | 5988.46 | 06-MAR-05:01 | 6.70 |
April | 0.100147E+09 | 5633.48 | 18-APR-04:01 | 2.88 |
May | 6684026.47 | 5275.12 | 18-MAY-04:01 | 6.52 |
June | 492163.95 | 612.11 | 09-JUN-04:08 | 11.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 260310.47 | 560.74 | 28-SEP-04:53 | 8.30 |
October | 27383655.86 | 5399.28 | 31-OCT-04:01 | 7.38 |
November | 0.177954E+09 | 5663.49 | 27-NOV-05:01 | 12.12 |
December | 0.591695E+09 | 6268.13 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.283325E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.115157E+10 | 6614.66 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.136341E+10 | 5391.10 | 01-JAN-22:03 | 6.10 |
February | 0.635860E+09 | 5246.50 | 21-FEB-05:01 | 1.70 |
March | 0.274450E+09 | 4790.56 | 06-MAR-05:01 | 6.70 |
April | 98563242.26 | 4531.63 | 11-APR-04:01 | 5.10 |
May | 3546316.43 | 4175.41 | 18-MAY-04:01 | 6.52 |
June | 15954.69 | 132.96 | 14-JUN-04:06 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
October | 74039792.36 | 4477.60 | 30-OCT-04:01 | 7.20 |
November | 0.365747E+09 | 4714.44 | 13-NOV-05:01 | 1.20 |
December | 0.851017E+09 | 5160.17 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.366665E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.136341E+10 | 5391.10 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.997053E+09 | 7677.13 | 17-JAN-05:01 | 1.60 |
February | 0.450125E+09 | 7607.07 | 21-FEB-05:01 | 1.70 |
March | 0.194407E+09 | 6977.99 | 06-MAR-05:01 | 6.70 |
April | 74034354.06 | 6623.56 | 11-APR-04:01 | 5.10 |
May | 4145206.58 | 6100.89 | 18-MAY-04:01 | 6.52 |
June | 184638.55 | 506.84 | 06-JUN-04:06 | 11.10 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 14086.37 | 117.39 | 19-AUG-04:08 | 12.95 |
September | 420356.43 | 808.17 | 30-SEP-04:06 | 11.10 |
October | 60581688.67 | 6476.23 | 30-OCT-04:01 | 7.20 |
November | 0.277617E+09 | 6862.14 | 13-NOV-05:01 | 1.20 |
December | 0.639796E+09 | 7503.01 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.269838E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.997053E+09 | 7677.13 | 15.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.122601E+10 | 9716.05 | 02-JAN-05:01 | 6.10 |
February | 0.542516E+09 | 9537.78 | 21-FEB-05:01 | 1.70 |
March | 0.252102E+09 | 8852.69 | 06-MAR-05:01 | 6.70 |
April | 99315806.05 | 8382.25 | 11-APR-04:01 | 5.10 |
May | 5286983.99 | 7755.20 | 18-MAY-04:01 | 6.52 |
June | 133648.60 | 825.62 | 14-JUN-04:04 | 10.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 33408.10 | 106.13 | 27-SEP-05:07 | 7.38 |
October | 67368699.04 | 8085.32 | 31-OCT-04:01 | 7.38 |
November | 0.341086E+09 | 8604.35 | 27-NOV-05:01 | 12.12 |
December | 0.795911E+09 | 9467.53 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.332976E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.122601E+10 | 9716.05 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.979031E+09 | 7870.54 | 17-JAN-05:01 | 1.60 |
February | 0.443492E+09 | 7763.67 | 21-FEB-05:01 | 1.70 |
March | 0.201763E+09 | 7153.85 | 06-MAR-05:01 | 6.70 |
April | 75717009.46 | 6756.77 | 11-APR-04:01 | 5.10 |
May | 4607612.70 | 6260.69 | 18-MAY-04:01 | 6.52 |
June | 193338.57 | 611.90 | 13-JUN-04:06 | 11.70 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 15.43 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 17.17 |
September | 414295.66 | 713.38 | 27-SEP-05:07 | 7.38 |
October | 58659877.46 | 6593.82 | 30-OCT-04:01 | 7.20 |
November | 0.272537E+09 | 6962.77 | 13-NOV-05:01 | 1.20 |
December | 0.618421E+09 | 7683.77 | 26-DEC-05:01 | -0.6 |
Annual Sum or Average | 0.265484E+10 | |||
Minimum of Months | 0.00 | 0.00 | -0.6 | |
Maximum of Months | 0.979031E+09 | 7870.54 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.926863E+10 | 9709.25 | 02-JAN-08:09 | 0.252135E+11 | 29623.06 | 02-JAN-08:09 |
February | 0.840739E+10 | 9709.25 | 01-FEB-08:09 | 0.228812E+11 | 29623.06 | 01-FEB-08:09 |
March | 0.999136E+10 | 9709.25 | 01-MAR-08:09 | 0.268447E+11 | 29623.06 | 01-MAR-08:09 |
April | 0.892327E+10 | 9709.25 | 03-APR-07:10 | 0.243745E+11 | 29623.06 | 03-APR-07:10 |
May | 0.962999E+10 | 9709.25 | 01-MAY-07:10 | 0.260291E+11 | 29623.06 | 01-MAY-07:10 |
June | 0.958383E+10 | 9709.25 | 01-JUN-07:10 | 0.257954E+11 | 29623.06 | 01-JUN-07:10 |
July | 0.896944E+10 | 9709.25 | 03-JUL-07:10 | 0.246082E+11 | 29623.06 | 03-JUL-07:10 |
August | 0.999136E+10 | 9709.25 | 01-AUG-07:10 | 0.268447E+11 | 29623.06 | 01-AUG-07:10 |
September | 0.892327E+10 | 9709.25 | 01-SEP-07:10 | 0.243745E+11 | 29623.06 | 01-SEP-07:10 |
October | 0.926863E+10 | 9709.25 | 02-OCT-07:10 | 0.252135E+11 | 29623.06 | 02-OCT-07:10 |
November | 0.916028E+10 | 9709.25 | 01-NOV-07:10 | 0.247695E+11 | 29623.06 | 01-NOV-07:10 |
December | 0.896944E+10 | 9709.25 | 01-DEC-08:09 | 0.246082E+11 | 29623.06 | 01-DEC-08:09 |
Annual Sum or Average | 0.111087E+12 | 0.301557E+12 | ||||
Minimum of Months | 0.840739E+10 | 9709.25 | 0.228812E+11 | 29623.06 | ||
Maximum of Months | 0.999136E+10 | 9709.25 | 0.268447E+11 | 29623.06 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.926863E+10 | 9709.25 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.840739E+10 | 9709.25 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.999136E+10 | 9709.25 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.892327E+10 | 9709.25 | 03-APR-07:10 | 0.102937E+11 | 7143.44 | 03-APR-07:10 |
May | 0.962999E+10 | 9709.25 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.958383E+10 | 9709.25 | 01-JUN-07:10 | 0.106523E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.896944E+10 | 9709.25 | 03-JUL-07:10 | 0.104994E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.999136E+10 | 9709.25 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.892327E+10 | 9709.25 | 01-SEP-07:10 | 0.102937E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.926863E+10 | 9709.25 | 02-OCT-07:10 | 0.106609E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.916028E+10 | 9709.25 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.896944E+10 | 9709.25 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.111087E+12 | 0.126597E+12 | ||||
Minimum of Months | 0.840739E+10 | 9709.25 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.999136E+10 | 9709.25 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.926863E+10 | 9709.25 | 02-JAN-08:09 | 0.106609E+11 | 7143.44 | 02-JAN-08:09 |
February | 0.840739E+10 | 9709.25 | 01-FEB-08:09 | 0.964936E+10 | 7143.44 | 01-FEB-08:09 |
March | 0.999136E+10 | 9709.25 | 01-MAR-08:09 | 0.110552E+11 | 7143.44 | 01-MAR-08:09 |
April | 0.892327E+10 | 9709.25 | 03-APR-07:10 | 0.102937E+11 | 7143.44 | 03-APR-07:10 |
May | 0.962999E+10 | 9709.25 | 01-MAY-07:10 | 0.108580E+11 | 7143.44 | 01-MAY-07:10 |
June | 0.958383E+10 | 9709.25 | 01-JUN-07:10 | 0.106523E+11 | 7143.44 | 01-JUN-07:10 |
July | 0.896944E+10 | 9709.25 | 03-JUL-07:10 | 0.104994E+11 | 7143.44 | 03-JUL-07:10 |
August | 0.999136E+10 | 9709.25 | 01-AUG-07:10 | 0.110552E+11 | 7143.44 | 01-AUG-07:10 |
September | 0.892327E+10 | 9709.25 | 01-SEP-07:10 | 0.102937E+11 | 7143.44 | 01-SEP-07:10 |
October | 0.926863E+10 | 9709.25 | 02-OCT-07:10 | 0.106609E+11 | 7143.44 | 02-OCT-07:10 |
November | 0.916028E+10 | 9709.25 | 01-NOV-07:10 | 0.104194E+11 | 7143.44 | 01-NOV-07:10 |
December | 0.896944E+10 | 9709.25 | 01-DEC-08:09 | 0.104994E+11 | 7143.44 | 01-DEC-08:09 |
Annual Sum or Average | 0.111087E+12 | 0.126597E+12 | ||||
Minimum of Months | 0.840739E+10 | 9709.25 | 0.964936E+10 | 7143.44 | ||
Maximum of Months | 0.999136E+10 | 9709.25 | 0.110552E+11 | 7143.44 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195391E+10 | 2046.80 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.177235E+10 | 2046.80 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.210627E+10 | 2046.80 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.188110E+10 | 2046.80 | 03-APR-07:10 | 0.216999E+10 | 1505.89 | 03-APR-07:10 |
May | 0.203009E+10 | 2046.80 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.202035E+10 | 2046.80 | 01-JUN-07:10 | 0.224559E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.189084E+10 | 2046.80 | 03-JUL-07:10 | 0.221336E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.210627E+10 | 2046.80 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.188110E+10 | 2046.80 | 01-SEP-07:10 | 0.216999E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.195391E+10 | 2046.80 | 02-OCT-07:10 | 0.224739E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.193107E+10 | 2046.80 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.189084E+10 | 2046.80 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.234181E+11 | 0.266877E+11 | ||||
Minimum of Months | 0.177235E+10 | 2046.80 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.210627E+10 | 2046.80 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123699E+10 | 1295.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.112205E+10 | 1295.79 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.133344E+10 | 1295.79 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.119089E+10 | 1295.79 | 03-APR-07:10 | 0.137370E+10 | 953.30 | 03-APR-07:10 |
May | 0.128521E+10 | 1295.79 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.127905E+10 | 1295.79 | 01-JUN-07:10 | 0.142155E+10 | 953.30 | 01-JUN-07:10 |
July | 0.119706E+10 | 1295.79 | 03-JUL-07:10 | 0.140115E+10 | 953.30 | 03-JUL-07:10 |
August | 0.133344E+10 | 1295.79 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.119089E+10 | 1295.79 | 01-SEP-07:10 | 0.137370E+10 | 953.30 | 01-SEP-07:10 |
October | 0.123699E+10 | 1295.79 | 02-OCT-07:10 | 0.142270E+10 | 953.30 | 02-OCT-07:10 |
November | 0.122253E+10 | 1295.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.119706E+10 | 1295.79 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.148256E+11 | 0.168945E+11 | ||||
Minimum of Months | 0.112205E+10 | 1295.79 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.133344E+10 | 1295.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195391E+10 | 2046.80 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.177235E+10 | 2046.80 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.210627E+10 | 2046.80 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.188110E+10 | 2046.80 | 03-APR-07:10 | 0.216998E+10 | 1505.88 | 03-APR-07:10 |
May | 0.203009E+10 | 2046.80 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.202035E+10 | 2046.80 | 01-JUN-07:10 | 0.224557E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.189084E+10 | 2046.80 | 03-JUL-07:10 | 0.221335E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.210627E+10 | 2046.80 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.188110E+10 | 2046.80 | 01-SEP-07:10 | 0.216998E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.195391E+10 | 2046.80 | 02-OCT-07:10 | 0.224738E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.193107E+10 | 2046.80 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.189084E+10 | 2046.80 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.234181E+11 | 0.266876E+11 | ||||
Minimum of Months | 0.177235E+10 | 2046.80 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.210627E+10 | 2046.80 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123690E+10 | 1295.71 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.112197E+10 | 1295.71 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.133335E+10 | 1295.71 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.119082E+10 | 1295.71 | 03-APR-07:10 | 0.137369E+10 | 953.29 | 03-APR-07:10 |
May | 0.128513E+10 | 1295.71 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.127897E+10 | 1295.71 | 01-JUN-07:10 | 0.142154E+10 | 953.29 | 01-JUN-07:10 |
July | 0.119698E+10 | 1295.71 | 03-JUL-07:10 | 0.140114E+10 | 953.29 | 03-JUL-07:10 |
August | 0.133335E+10 | 1295.71 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.119082E+10 | 1295.71 | 01-SEP-07:10 | 0.137369E+10 | 953.29 | 01-SEP-07:10 |
October | 0.123690E+10 | 1295.71 | 02-OCT-07:10 | 0.142269E+10 | 953.29 | 02-OCT-07:10 |
November | 0.122245E+10 | 1295.71 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.119698E+10 | 1295.71 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.148246E+11 | 0.168944E+11 | ||||
Minimum of Months | 0.112197E+10 | 1295.71 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.133335E+10 | 1295.71 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195391E+10 | 2046.80 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.177235E+10 | 2046.80 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.210627E+10 | 2046.80 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.188110E+10 | 2046.80 | 03-APR-07:10 | 0.216999E+10 | 1505.89 | 03-APR-07:10 |
May | 0.203009E+10 | 2046.80 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.202035E+10 | 2046.80 | 01-JUN-07:10 | 0.224559E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.189084E+10 | 2046.80 | 03-JUL-07:10 | 0.221336E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.210627E+10 | 2046.80 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.188110E+10 | 2046.80 | 01-SEP-07:10 | 0.216999E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.195391E+10 | 2046.80 | 02-OCT-07:10 | 0.224739E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.193107E+10 | 2046.80 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.189084E+10 | 2046.80 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.234181E+11 | 0.266877E+11 | ||||
Minimum of Months | 0.177235E+10 | 2046.80 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.210627E+10 | 2046.80 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123699E+10 | 1295.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.112205E+10 | 1295.79 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.133344E+10 | 1295.79 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.119089E+10 | 1295.79 | 03-APR-07:10 | 0.137370E+10 | 953.30 | 03-APR-07:10 |
May | 0.128521E+10 | 1295.79 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.127905E+10 | 1295.79 | 01-JUN-07:10 | 0.142155E+10 | 953.30 | 01-JUN-07:10 |
July | 0.119706E+10 | 1295.79 | 03-JUL-07:10 | 0.140115E+10 | 953.30 | 03-JUL-07:10 |
August | 0.133344E+10 | 1295.79 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.119089E+10 | 1295.79 | 01-SEP-07:10 | 0.137370E+10 | 953.30 | 01-SEP-07:10 |
October | 0.123699E+10 | 1295.79 | 02-OCT-07:10 | 0.142270E+10 | 953.30 | 02-OCT-07:10 |
November | 0.122253E+10 | 1295.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.119706E+10 | 1295.79 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.148256E+11 | 0.168945E+11 | ||||
Minimum of Months | 0.112205E+10 | 1295.79 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.133344E+10 | 1295.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195391E+10 | 2046.80 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.177235E+10 | 2046.80 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.210627E+10 | 2046.80 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.188110E+10 | 2046.80 | 03-APR-07:10 | 0.216998E+10 | 1505.88 | 03-APR-07:10 |
May | 0.203009E+10 | 2046.80 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.202035E+10 | 2046.80 | 01-JUN-07:10 | 0.224557E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.189084E+10 | 2046.80 | 03-JUL-07:10 | 0.221335E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.210627E+10 | 2046.80 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.188110E+10 | 2046.80 | 01-SEP-07:10 | 0.216998E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.195391E+10 | 2046.80 | 02-OCT-07:10 | 0.224738E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.193107E+10 | 2046.80 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.189084E+10 | 2046.80 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.234181E+11 | 0.266876E+11 | ||||
Minimum of Months | 0.177235E+10 | 2046.80 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.210627E+10 | 2046.80 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123690E+10 | 1295.71 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.112197E+10 | 1295.71 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.133335E+10 | 1295.71 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.119082E+10 | 1295.71 | 03-APR-07:10 | 0.137369E+10 | 953.29 | 03-APR-07:10 |
May | 0.128513E+10 | 1295.71 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.127897E+10 | 1295.71 | 01-JUN-07:10 | 0.142154E+10 | 953.29 | 01-JUN-07:10 |
July | 0.119698E+10 | 1295.71 | 03-JUL-07:10 | 0.140114E+10 | 953.29 | 03-JUL-07:10 |
August | 0.133335E+10 | 1295.71 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.119082E+10 | 1295.71 | 01-SEP-07:10 | 0.137369E+10 | 953.29 | 01-SEP-07:10 |
October | 0.123690E+10 | 1295.71 | 02-OCT-07:10 | 0.142269E+10 | 953.29 | 02-OCT-07:10 |
November | 0.122245E+10 | 1295.71 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.119698E+10 | 1295.71 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.148246E+11 | 0.168944E+11 | ||||
Minimum of Months | 0.112197E+10 | 1295.71 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.133335E+10 | 1295.71 | 0.147531E+10 | 953.29 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195391E+10 | 2046.80 | 02-JAN-08:09 | 0.224739E+10 | 1505.89 | 02-JAN-08:09 |
February | 0.177235E+10 | 2046.80 | 01-FEB-08:09 | 0.203416E+10 | 1505.89 | 01-FEB-08:09 |
March | 0.210627E+10 | 2046.80 | 01-MAR-08:09 | 0.233052E+10 | 1505.89 | 01-MAR-08:09 |
April | 0.188110E+10 | 2046.80 | 03-APR-07:10 | 0.216999E+10 | 1505.89 | 03-APR-07:10 |
May | 0.203009E+10 | 2046.80 | 01-MAY-07:10 | 0.228896E+10 | 1505.89 | 01-MAY-07:10 |
June | 0.202035E+10 | 2046.80 | 01-JUN-07:10 | 0.224559E+10 | 1505.89 | 01-JUN-07:10 |
July | 0.189084E+10 | 2046.80 | 03-JUL-07:10 | 0.221336E+10 | 1505.89 | 03-JUL-07:10 |
August | 0.210627E+10 | 2046.80 | 01-AUG-07:10 | 0.233052E+10 | 1505.89 | 01-AUG-07:10 |
September | 0.188110E+10 | 2046.80 | 01-SEP-07:10 | 0.216999E+10 | 1505.89 | 01-SEP-07:10 |
October | 0.195391E+10 | 2046.80 | 02-OCT-07:10 | 0.224739E+10 | 1505.89 | 02-OCT-07:10 |
November | 0.193107E+10 | 2046.80 | 01-NOV-07:10 | 0.219649E+10 | 1505.89 | 01-NOV-07:10 |
December | 0.189084E+10 | 2046.80 | 01-DEC-08:09 | 0.221336E+10 | 1505.89 | 01-DEC-08:09 |
Annual Sum or Average | 0.234181E+11 | 0.266877E+11 | ||||
Minimum of Months | 0.177235E+10 | 2046.80 | 0.203416E+10 | 1505.89 | ||
Maximum of Months | 0.210627E+10 | 2046.80 | 0.233052E+10 | 1505.89 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123699E+10 | 1295.79 | 02-JAN-08:09 | 0.142270E+10 | 953.30 | 02-JAN-08:09 |
February | 0.112205E+10 | 1295.79 | 01-FEB-08:09 | 0.128771E+10 | 953.30 | 01-FEB-08:09 |
March | 0.133344E+10 | 1295.79 | 01-MAR-08:09 | 0.147532E+10 | 953.30 | 01-MAR-08:09 |
April | 0.119089E+10 | 1295.79 | 03-APR-07:10 | 0.137370E+10 | 953.30 | 03-APR-07:10 |
May | 0.128521E+10 | 1295.79 | 01-MAY-07:10 | 0.144901E+10 | 953.30 | 01-MAY-07:10 |
June | 0.127905E+10 | 1295.79 | 01-JUN-07:10 | 0.142155E+10 | 953.30 | 01-JUN-07:10 |
July | 0.119706E+10 | 1295.79 | 03-JUL-07:10 | 0.140115E+10 | 953.30 | 03-JUL-07:10 |
August | 0.133344E+10 | 1295.79 | 01-AUG-07:10 | 0.147532E+10 | 953.30 | 01-AUG-07:10 |
September | 0.119089E+10 | 1295.79 | 01-SEP-07:10 | 0.137370E+10 | 953.30 | 01-SEP-07:10 |
October | 0.123699E+10 | 1295.79 | 02-OCT-07:10 | 0.142270E+10 | 953.30 | 02-OCT-07:10 |
November | 0.122253E+10 | 1295.79 | 01-NOV-07:10 | 0.139048E+10 | 953.30 | 01-NOV-07:10 |
December | 0.119706E+10 | 1295.79 | 01-DEC-08:09 | 0.140115E+10 | 953.30 | 01-DEC-08:09 |
Annual Sum or Average | 0.148256E+11 | 0.168945E+11 | ||||
Minimum of Months | 0.112205E+10 | 1295.79 | 0.128771E+10 | 953.30 | ||
Maximum of Months | 0.133344E+10 | 1295.79 | 0.147532E+10 | 953.30 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.195391E+10 | 2046.80 | 02-JAN-08:09 | 0.224738E+10 | 1505.88 | 02-JAN-08:09 |
February | 0.177235E+10 | 2046.80 | 01-FEB-08:09 | 0.203415E+10 | 1505.88 | 01-FEB-08:09 |
March | 0.210627E+10 | 2046.80 | 01-MAR-08:09 | 0.233050E+10 | 1505.88 | 01-MAR-08:09 |
April | 0.188110E+10 | 2046.80 | 03-APR-07:10 | 0.216998E+10 | 1505.88 | 03-APR-07:10 |
May | 0.203009E+10 | 2046.80 | 01-MAY-07:10 | 0.228894E+10 | 1505.88 | 01-MAY-07:10 |
June | 0.202035E+10 | 2046.80 | 01-JUN-07:10 | 0.224557E+10 | 1505.88 | 01-JUN-07:10 |
July | 0.189084E+10 | 2046.80 | 03-JUL-07:10 | 0.221335E+10 | 1505.88 | 03-JUL-07:10 |
August | 0.210627E+10 | 2046.80 | 01-AUG-07:10 | 0.233050E+10 | 1505.88 | 01-AUG-07:10 |
September | 0.188110E+10 | 2046.80 | 01-SEP-07:10 | 0.216998E+10 | 1505.88 | 01-SEP-07:10 |
October | 0.195391E+10 | 2046.80 | 02-OCT-07:10 | 0.224738E+10 | 1505.88 | 02-OCT-07:10 |
November | 0.193107E+10 | 2046.80 | 01-NOV-07:10 | 0.219648E+10 | 1505.88 | 01-NOV-07:10 |
December | 0.189084E+10 | 2046.80 | 01-DEC-08:09 | 0.221335E+10 | 1505.88 | 01-DEC-08:09 |
Annual Sum or Average | 0.234181E+11 | 0.266876E+11 | ||||
Minimum of Months | 0.177235E+10 | 2046.80 | 0.203415E+10 | 1505.88 | ||
Maximum of Months | 0.210627E+10 | 2046.80 | 0.233050E+10 | 1505.88 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE LIGHTS ELECTRIC ENERGY [J] | ZONE LIGHTS ELECTRIC ENERGY {Maximum}[W] | ZONE LIGHTS ELECTRIC ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT ELECTRIC ENERGY {TIMESTAMP} | |
January | 0.123690E+10 | 1295.71 | 02-JAN-08:09 | 0.142269E+10 | 953.29 | 02-JAN-08:09 |
February | 0.112197E+10 | 1295.71 | 01-FEB-08:09 | 0.128770E+10 | 953.29 | 01-FEB-08:09 |
March | 0.133335E+10 | 1295.71 | 01-MAR-08:09 | 0.147531E+10 | 953.29 | 01-MAR-08:09 |
April | 0.119082E+10 | 1295.71 | 03-APR-07:10 | 0.137369E+10 | 953.29 | 03-APR-07:10 |
May | 0.128513E+10 | 1295.71 | 01-MAY-07:10 | 0.144900E+10 | 953.29 | 01-MAY-07:10 |
June | 0.127897E+10 | 1295.71 | 01-JUN-07:10 | 0.142154E+10 | 953.29 | 01-JUN-07:10 |
July | 0.119698E+10 | 1295.71 | 03-JUL-07:10 | 0.140114E+10 | 953.29 | 03-JUL-07:10 |
August | 0.133335E+10 | 1295.71 | 01-AUG-07:10 | 0.147531E+10 | 953.29 | 01-AUG-07:10 |
September | 0.119082E+10 | 1295.71 | 01-SEP-07:10 | 0.137369E+10 | 953.29 | 01-SEP-07:10 |
October | 0.123690E+10 | 1295.71 | 02-OCT-07:10 | 0.142269E+10 | 953.29 | 02-OCT-07:10 |
November | 0.122245E+10 | 1295.71 | 01-NOV-07:10 | 0.139047E+10 | 953.29 | 01-NOV-07:10 |
December | 0.119698E+10 | 1295.71 | 01-DEC-08:09 | 0.140114E+10 | 953.29 | 01-DEC-08:09 |
Annual Sum or Average | 0.148246E+11 | 0.168944E+11 | ||||
Minimum of Months | 0.112197E+10 | 1295.71 | 0.128770E+10 | 953.29 | ||
Maximum of Months | 0.133335E+10 | 1295.71 | 0.147531E+10 | 953.29 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.926863E+10 | 0.252135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.840739E+10 | 0.228812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.999136E+10 | 0.268447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.892327E+10 | 0.243745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.962999E+10 | 0.260291E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.958383E+10 | 0.257954E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.896944E+10 | 0.246082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.999136E+10 | 0.268447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.892327E+10 | 0.243745E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.926863E+10 | 0.252135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.916028E+10 | 0.247695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.896944E+10 | 0.246082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111087E+12 | 0.301557E+12 | ||||||
Minimum of Months | 0.427861E+10 | 0.840739E+10 | 0.228812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.999136E+10 | 0.268447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.926863E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.840739E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.999136E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.892327E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.962999E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.958383E+10 | 0.106523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.896944E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.999136E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.892327E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.926863E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.916028E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.896944E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111087E+12 | 0.126597E+12 | ||||||
Minimum of Months | 0.427861E+10 | 0.840739E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.999136E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.471610E+10 | 0.926863E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.427861E+10 | 0.840739E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.511242E+10 | 0.999136E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.453654E+10 | 0.892327E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.491426E+10 | 0.962999E+10 | 0.108580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.490054E+10 | 0.958383E+10 | 0.106523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.455026E+10 | 0.896944E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.511242E+10 | 0.999136E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.453654E+10 | 0.892327E+10 | 0.102937E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.471610E+10 | 0.926863E+10 | 0.106609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.467005E+10 | 0.916028E+10 | 0.104194E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.455026E+10 | 0.896944E+10 | 0.104994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.565941E+11 | 0.111087E+12 | 0.126597E+12 | ||||||
Minimum of Months | 0.427861E+10 | 0.840739E+10 | 0.964936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.511242E+10 | 0.999136E+10 | 0.110552E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.195391E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143759E+10 |
February | 0.901968E+09 | 0.177235E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127650E+10 |
March | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122720E+10 |
April | 0.956342E+09 | 0.188110E+10 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3375527.99 | 0.117075E+10 |
May | 0.103597E+10 | 0.203009E+10 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83794.48 | 0.951259E+09 |
June | 0.103308E+10 | 0.202035E+10 | 0.224559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 840739.89 | 0.799815E+09 |
July | 0.959235E+09 | 0.189084E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16077113.40 | 0.668600E+09 |
August | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22140153.45 | 0.536224E+09 |
September | 0.956342E+09 | 0.188110E+10 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98540.46 | 0.436780E+09 |
October | 0.994195E+09 | 0.195391E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.966886E+09 |
November | 0.984487E+09 | 0.193107E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110833E+10 |
December | 0.959235E+09 | 0.189084E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121268E+10 |
Annual Sum or Average | 0.119305E+11 | 0.234181E+11 | 0.266877E+11 | 42615869.67 | 0.117926E+11 | ||||
Minimum of Months | 0.901968E+09 | 0.177235E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436780E+09 |
Maximum of Months | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22140153.45 | 0.143759E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.123699E+10 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959169E+09 |
February | 0.571020E+09 | 0.112205E+10 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855604E+09 |
March | 0.682301E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815681E+09 |
April | 0.605444E+09 | 0.119089E+10 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2538143.86 | 0.780800E+09 |
May | 0.655854E+09 | 0.128521E+10 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 203489.71 | 0.626538E+09 |
June | 0.654023E+09 | 0.127905E+10 | 0.142155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 832239.15 | 0.528591E+09 |
July | 0.607275E+09 | 0.119706E+10 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12637890.82 | 0.438029E+09 |
August | 0.682301E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16552513.44 | 0.349245E+09 |
September | 0.605444E+09 | 0.119089E+10 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 150797.47 | 0.286989E+09 |
October | 0.629407E+09 | 0.123699E+10 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.641929E+09 |
November | 0.623262E+09 | 0.122253E+10 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.01 | 0.736623E+09 |
December | 0.607275E+09 | 0.119706E+10 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807979E+09 |
Annual Sum or Average | 0.755301E+10 | 0.148256E+11 | 0.168945E+11 | 32915671.45 | 0.782718E+10 | ||||
Minimum of Months | 0.571020E+09 | 0.112205E+10 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286989E+09 |
Maximum of Months | 0.682301E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16552513.44 | 0.959169E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.195391E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146647E+10 |
February | 0.901968E+09 | 0.177235E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134414E+10 |
March | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126945E+10 |
April | 0.956342E+09 | 0.188110E+10 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2392494.10 | 0.119903E+10 |
May | 0.103597E+10 | 0.203009E+10 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 130523.41 | 0.949119E+09 |
June | 0.103308E+10 | 0.202035E+10 | 0.224557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1069554.92 | 0.780890E+09 |
July | 0.959235E+09 | 0.189084E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16163523.67 | 0.655896E+09 |
August | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21533495.93 | 0.528093E+09 |
September | 0.956342E+09 | 0.188110E+10 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77634.11 | 0.451197E+09 |
October | 0.994195E+09 | 0.195391E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101710E+10 |
November | 0.984487E+09 | 0.193107E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113739E+10 |
December | 0.959235E+09 | 0.189084E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124856E+10 |
Annual Sum or Average | 0.119305E+11 | 0.234181E+11 | 0.266876E+11 | 41367226.15 | 0.120473E+11 | ||||
Minimum of Months | 0.901968E+09 | 0.177235E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451197E+09 |
Maximum of Months | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21533495.93 | 0.146647E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.123690E+10 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.961684E+09 |
February | 0.570983E+09 | 0.112197E+10 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861271E+09 |
March | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823911E+09 |
April | 0.605404E+09 | 0.119082E+10 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1289845.12 | 0.787998E+09 |
May | 0.655811E+09 | 0.128513E+10 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 294471.71 | 0.642943E+09 |
June | 0.653980E+09 | 0.127897E+10 | 0.142154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 711799.33 | 0.526219E+09 |
July | 0.607235E+09 | 0.119698E+10 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8733408.68 | 0.454422E+09 |
August | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16322282.88 | 0.354791E+09 |
September | 0.605404E+09 | 0.119082E+10 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78706.96 | 0.295022E+09 |
October | 0.629366E+09 | 0.123690E+10 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.648828E+09 |
November | 0.623221E+09 | 0.122245E+10 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.739779E+09 |
December | 0.607235E+09 | 0.119698E+10 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809837E+09 |
Annual Sum or Average | 0.755252E+10 | 0.148246E+11 | 0.168944E+11 | 27430514.68 | 0.790670E+10 | ||||
Minimum of Months | 0.570983E+09 | 0.112197E+10 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295022E+09 |
Maximum of Months | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16322282.88 | 0.961684E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.195391E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838247E+09 |
February | 0.901968E+09 | 0.177235E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.743832E+09 |
March | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.705055E+09 |
April | 0.956342E+09 | 0.188110E+10 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2601849.12 | 0.654737E+09 |
May | 0.103597E+10 | 0.203009E+10 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 237391.77 | 0.524239E+09 |
June | 0.103308E+10 | 0.202035E+10 | 0.224559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 544281.70 | 0.440469E+09 |
July | 0.959235E+09 | 0.189084E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10186417.26 | 0.371854E+09 |
August | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12727128.91 | 0.306663E+09 |
September | 0.956342E+09 | 0.188110E+10 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67608.50 | 0.255076E+09 |
October | 0.994195E+09 | 0.195391E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582984E+09 |
November | 0.984487E+09 | 0.193107E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674954E+09 |
December | 0.959235E+09 | 0.189084E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.730010E+09 |
Annual Sum or Average | 0.119305E+11 | 0.234181E+11 | 0.266877E+11 | 26364677.26 | 0.682812E+10 | ||||
Minimum of Months | 0.901968E+09 | 0.177235E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255076E+09 |
Maximum of Months | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12727128.91 | 0.838247E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629407E+09 | 0.123699E+10 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554226E+09 |
February | 0.571020E+09 | 0.112205E+10 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496847E+09 |
March | 0.682301E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468064E+09 |
April | 0.605444E+09 | 0.119089E+10 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1680987.51 | 0.439609E+09 |
May | 0.655854E+09 | 0.128521E+10 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204991.35 | 0.348520E+09 |
June | 0.654023E+09 | 0.127905E+10 | 0.142155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 479243.18 | 0.296351E+09 |
July | 0.607275E+09 | 0.119706E+10 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5976660.05 | 0.244680E+09 |
August | 0.682301E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8190620.16 | 0.203793E+09 |
September | 0.605444E+09 | 0.119089E+10 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77118.02 | 0.166636E+09 |
October | 0.629407E+09 | 0.123699E+10 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382752E+09 |
November | 0.623262E+09 | 0.122253E+10 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 662.30 | 0.441963E+09 |
December | 0.607275E+09 | 0.119706E+10 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481540E+09 |
Annual Sum or Average | 0.755301E+10 | 0.148256E+11 | 0.168945E+11 | 16610282.57 | 0.452498E+10 | ||||
Minimum of Months | 0.571020E+09 | 0.112205E+10 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166636E+09 |
Maximum of Months | 0.682301E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8190620.16 | 0.554226E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.195391E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643033E+10 |
February | 0.901968E+09 | 0.177235E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558822E+10 |
March | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582029E+10 |
April | 0.956342E+09 | 0.188110E+10 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24663038.15 | 0.434585E+10 |
May | 0.103597E+10 | 0.203009E+10 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4199455.05 | 0.366718E+10 |
June | 0.103308E+10 | 0.202035E+10 | 0.224557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28055078.33 | 0.273188E+10 |
July | 0.959235E+09 | 0.189084E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157640E+09 | 0.179640E+10 |
August | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408133E+09 | 0.171799E+10 |
September | 0.956342E+09 | 0.188110E+10 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5506283.19 | 0.265073E+10 |
October | 0.994195E+09 | 0.195391E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439382E+10 |
November | 0.984487E+09 | 0.193107E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558935E+10 |
December | 0.959235E+09 | 0.189084E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615741E+10 |
Annual Sum or Average | 0.119305E+11 | 0.234181E+11 | 0.266876E+11 | 0.628197E+09 | 0.508894E+11 | ||||
Minimum of Months | 0.901968E+09 | 0.177235E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171799E+10 |
Maximum of Months | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.408133E+09 | 0.643033E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.123690E+10 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555611E+09 |
February | 0.570983E+09 | 0.112197E+10 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497974E+09 |
March | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.471590E+09 |
April | 0.605404E+09 | 0.119082E+10 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1026146.29 | 0.440560E+09 |
May | 0.655811E+09 | 0.128513E+10 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 264690.95 | 0.358168E+09 |
June | 0.653980E+09 | 0.127897E+10 | 0.142154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 466850.20 | 0.290371E+09 |
July | 0.607235E+09 | 0.119698E+10 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4120228.81 | 0.259508E+09 |
August | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8464414.09 | 0.207187E+09 |
September | 0.605404E+09 | 0.119082E+10 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54589.39 | 0.171918E+09 |
October | 0.629366E+09 | 0.123690E+10 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385427E+09 |
November | 0.623221E+09 | 0.122245E+10 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443574E+09 |
December | 0.607235E+09 | 0.119698E+10 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482481E+09 |
Annual Sum or Average | 0.755252E+10 | 0.148246E+11 | 0.168944E+11 | 14396919.74 | 0.456437E+10 | ||||
Minimum of Months | 0.570983E+09 | 0.112197E+10 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171918E+09 |
Maximum of Months | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8464414.09 | 0.555611E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.195391E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126588E+10 |
February | 0.901968E+09 | 0.177235E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113086E+10 |
March | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109434E+10 |
April | 0.956342E+09 | 0.188110E+10 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2988596.03 | 0.103364E+10 |
May | 0.103597E+10 | 0.203009E+10 | 0.228896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98661.65 | 0.831298E+09 |
June | 0.103308E+10 | 0.202035E+10 | 0.224559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 734021.08 | 0.693640E+09 |
July | 0.959235E+09 | 0.189084E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14906235.23 | 0.581034E+09 |
August | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18988498.02 | 0.472340E+09 |
September | 0.956342E+09 | 0.188110E+10 | 0.216999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 88438.91 | 0.389218E+09 |
October | 0.994195E+09 | 0.195391E+10 | 0.224739E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.873635E+09 |
November | 0.984487E+09 | 0.193107E+10 | 0.219649E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.999887E+09 |
December | 0.959235E+09 | 0.189084E+10 | 0.221336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108939E+10 |
Annual Sum or Average | 0.119305E+11 | 0.234181E+11 | 0.266877E+11 | 37804450.93 | 0.104552E+11 | ||||
Minimum of Months | 0.901968E+09 | 0.177235E+10 | 0.203416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389218E+09 |
Maximum of Months | 0.107774E+10 | 0.210627E+10 | 0.233052E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18988498.02 | 0.126588E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.465148E+09 | 0.123699E+10 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841024E+09 |
February | 0.421807E+09 | 0.112205E+10 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757002E+09 |
March | 0.502994E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721530E+09 |
April | 0.447140E+09 | 0.119089E+10 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2434603.51 | 0.682135E+09 |
May | 0.484071E+09 | 0.128521E+10 | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546911.97 | 0.538634E+09 |
June | 0.482240E+09 | 0.127905E+10 | 0.142155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1055484.52 | 0.449070E+09 |
July | 0.448971E+09 | 0.119706E+10 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12690031.27 | 0.372595E+09 |
August | 0.502994E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15658363.93 | 0.299595E+09 |
September | 0.447140E+09 | 0.119089E+10 | 0.137370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259908.37 | 0.249157E+09 |
October | 0.465148E+09 | 0.123699E+10 | 0.142270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.571977E+09 |
November | 0.460569E+09 | 0.122253E+10 | 0.139048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 755.84 | 0.659285E+09 |
December | 0.448971E+09 | 0.119706E+10 | 0.140115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.722098E+09 |
Annual Sum or Average | 0.557719E+10 | 0.148256E+11 | 0.168945E+11 | 32646059.40 | 0.686410E+10 | ||||
Minimum of Months | 0.421807E+09 | 0.112205E+10 | 0.128771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249157E+09 |
Maximum of Months | 0.502994E+09 | 0.133344E+10 | 0.147532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15658363.93 | 0.841024E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.994195E+09 | 0.195391E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129368E+10 |
February | 0.901968E+09 | 0.177235E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119554E+10 |
March | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112432E+10 |
April | 0.956342E+09 | 0.188110E+10 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2189674.44 | 0.105175E+10 |
May | 0.103597E+10 | 0.203009E+10 | 0.228894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 183273.62 | 0.823487E+09 |
June | 0.103308E+10 | 0.202035E+10 | 0.224557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1088849.85 | 0.672032E+09 |
July | 0.959235E+09 | 0.189084E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15013214.50 | 0.566434E+09 |
August | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18666885.15 | 0.461338E+09 |
September | 0.956342E+09 | 0.188110E+10 | 0.216998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 69089.76 | 0.396197E+09 |
October | 0.994195E+09 | 0.195391E+10 | 0.224738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.908253E+09 |
November | 0.984487E+09 | 0.193107E+10 | 0.219648E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101854E+10 |
December | 0.959235E+09 | 0.189084E+10 | 0.221335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111705E+10 |
Annual Sum or Average | 0.119305E+11 | 0.234181E+11 | 0.266876E+11 | 37210987.31 | 0.106286E+11 | ||||
Minimum of Months | 0.901968E+09 | 0.177235E+10 | 0.203415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396197E+09 |
Maximum of Months | 0.107774E+10 | 0.210627E+10 | 0.233050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18666885.15 | 0.129368E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.629366E+09 | 0.123690E+10 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842866E+09 |
February | 0.570983E+09 | 0.112197E+10 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760265E+09 |
March | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728953E+09 |
April | 0.605404E+09 | 0.119082E+10 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1144157.49 | 0.689928E+09 |
May | 0.655811E+09 | 0.128513E+10 | 0.144900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 311621.41 | 0.557172E+09 |
June | 0.653980E+09 | 0.127897E+10 | 0.142154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 667505.44 | 0.452099E+09 |
July | 0.607235E+09 | 0.119698E+10 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7382176.27 | 0.391451E+09 |
August | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14147230.26 | 0.308764E+09 |
September | 0.605404E+09 | 0.119082E+10 | 0.137369E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76382.41 | 0.258312E+09 |
October | 0.629366E+09 | 0.123690E+10 | 0.142269E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578791E+09 |
November | 0.623221E+09 | 0.122245E+10 | 0.139047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.662002E+09 |
December | 0.607235E+09 | 0.119698E+10 | 0.140114E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723666E+09 |
Annual Sum or Average | 0.755252E+10 | 0.148246E+11 | 0.168944E+11 | 23729073.28 | 0.695427E+10 | ||||
Minimum of Months | 0.570983E+09 | 0.112197E+10 | 0.128770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258312E+09 |
Maximum of Months | 0.682256E+09 | 0.133335E+10 | 0.147531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14147230.26 | 0.842866E+09 |
Report: SpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178500E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163293E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157046E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3365989.24 | 0.146435E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24558.99 | 0.116227E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356397.79 | 0.961582E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14268794.33 | 0.808163E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17896056.88 | 0.671618E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1710.15 | 0.558906E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127633E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145082E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157624E+10 |
Annual Sum or Average | 35913507.38 | 0.149187E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.558906E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17896056.88 | 0.178500E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217657E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197978E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192599E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4730616.60 | 0.181650E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31527.73 | 0.146010E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457407.29 | 0.121631E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19231302.10 | 0.101957E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23774023.43 | 0.838897E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2579.62 | 0.690389E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153805E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173719E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189847E+10 |
Annual Sum or Average | 48227456.77 | 0.182978E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690389E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23774023.43 | 0.217657E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211494E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192900E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186533E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1925374.55 | 0.181701E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151213E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15571.12 | 0.127579E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3213641.75 | 0.107081E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11631691.29 | 0.837030E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680744E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147904E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165002E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179913E+10 |
Annual Sum or Average | 16786278.70 | 0.180310E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.680744E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11631691.29 | 0.211494E+10 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9709.25 | 02-JAN-08:09 | 29623.06 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9709.25 | 01-FEB-08:09 | 29623.06 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9709.25 | 01-MAR-08:09 | 29623.06 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9709.25 | 03-APR-07:10 | 29623.06 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9709.25 | 01-MAY-07:10 | 29623.06 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9709.25 | 01-JUN-07:10 | 29623.06 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9709.25 | 03-JUL-07:10 | 29623.06 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9709.25 | 01-AUG-07:10 | 29623.06 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9709.25 | 01-SEP-07:10 | 29623.06 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9709.25 | 02-OCT-07:10 | 29623.06 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9709.25 | 01-NOV-07:10 | 29623.06 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9709.25 | 01-DEC-08:09 | 29623.06 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 6198.29 | 9709.25 | 29623.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9709.25 | 29623.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9709.25 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9709.25 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9709.25 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9709.25 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9709.25 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9709.25 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9709.25 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9709.25 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9709.25 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9709.25 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9709.25 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9709.25 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 6198.29 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 6198.29 | 02-JAN-10:09 | 9709.25 | 02-JAN-08:09 | 7143.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 6198.29 | 01-FEB-10:09 | 9709.25 | 01-FEB-08:09 | 7143.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6198.29 | 01-MAR-10:09 | 9709.25 | 01-MAR-08:09 | 7143.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6198.29 | 03-APR-09:09 | 9709.25 | 03-APR-07:10 | 7143.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 6198.29 | 01-MAY-09:09 | 9709.25 | 01-MAY-07:10 | 7143.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6198.29 | 01-JUN-09:09 | 9709.25 | 01-JUN-07:10 | 7143.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6198.29 | 03-JUL-09:09 | 9709.25 | 03-JUL-07:10 | 7143.44 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6198.29 | 01-AUG-09:09 | 9709.25 | 01-AUG-07:10 | 7143.44 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6198.29 | 01-SEP-09:09 | 9709.25 | 01-SEP-07:10 | 7143.44 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6198.29 | 02-OCT-09:09 | 9709.25 | 02-OCT-07:10 | 7143.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6198.29 | 01-NOV-09:09 | 9709.25 | 01-NOV-07:10 | 7143.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6198.29 | 01-DEC-10:09 | 9709.25 | 01-DEC-08:09 | 7143.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||||||
Minimum of Months | 6198.29 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 6198.29 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2046.80 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2428.64 | 12-JAN-22:03 |
February | 1306.65 | 01-FEB-10:09 | 2046.80 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2287.33 | 16-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 2046.80 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2300.18 | 29-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 2046.80 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 489.26 | 01-APR-17:02 | 2272.61 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2046.80 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.99 | 05-MAY-16:00 | 1786.79 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2046.80 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.08 | 28-JUN-15:00 | 2015.30 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2046.80 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.30 | 23-JUL-16:00 | 1007.00 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2046.80 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 272.92 | 13-AUG-15:00 | 1524.55 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2046.80 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 14-SEP-17:00 | 978.73 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2046.80 | 02-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2097.92 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2046.80 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2273.06 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 2046.80 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1890.56 | 22-DEC-22:02 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 978.73 | |||||
Maximum of Months | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 489.26 | 2428.64 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1295.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1696.45 | 28-JAN-05:20 |
February | 827.22 | 01-FEB-10:09 | 1295.79 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1523.10 | 16-FEB-22:02 |
March | 827.22 | 01-MAR-10:09 | 1295.79 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1569.74 | 29-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 1295.79 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 381.20 | 01-APR-17:02 | 1511.89 | 10-APR-21:03 |
May | 827.22 | 01-MAY-09:09 | 1295.79 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 06-MAY-15:00 | 1191.19 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 1295.79 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.38 | 28-JUN-15:00 | 1310.16 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 1295.79 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.03 | 23-JUL-15:40 | 654.06 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 1295.79 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.61 | 13-AUG-15:00 | 1008.71 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 1295.79 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.19 | 14-SEP-17:00 | 634.58 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 1295.79 | 02-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1396.48 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 1295.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 | 04-NOV-15:00 | 1512.32 | 29-NOV-22:03 |
December | 827.22 | 01-DEC-10:09 | 1295.79 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1312.87 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.58 | |||||
Maximum of Months | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 381.20 | 1696.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2046.80 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2544.15 | 28-JAN-05:20 |
February | 1306.65 | 01-FEB-10:09 | 2046.80 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2287.24 | 16-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 2046.80 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2354.63 | 29-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 2046.80 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 429.98 | 01-APR-17:02 | 2272.82 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2046.80 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 | 06-MAY-15:00 | 1786.80 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2046.80 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.08 | 28-JUN-15:00 | 1975.10 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2046.80 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 523.10 | 23-JUL-15:40 | 1001.87 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2046.80 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.87 | 13-AUG-17:40 | 1532.20 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2046.80 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.93 | 14-SEP-17:00 | 966.99 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2046.80 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2097.22 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2046.80 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2272.06 | 29-NOV-22:03 |
December | 1306.65 | 01-DEC-10:09 | 2046.80 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1969.31 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 966.99 | |||||
Maximum of Months | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 523.10 | 2544.15 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1295.71 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1706.21 | 28-JAN-05:10 |
February | 827.17 | 01-FEB-10:09 | 1295.71 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1522.73 | 16-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 1295.71 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1569.74 | 29-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 1295.71 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 140.07 | 01-APR-17:02 | 1515.15 | 10-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 1295.71 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.72 | 06-MAY-13:00 | 1191.19 | 18-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 1295.71 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.39 | 28-JUN-15:00 | 1292.98 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1295.71 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 303.03 | 23-JUL-13:30 | 671.76 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 1295.71 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.52 | 13-AUG-13:00 | 1035.51 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 1295.71 | 01-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 | 14-SEP-17:00 | 634.78 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 1295.71 | 02-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1395.79 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1295.71 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1512.24 | 29-NOV-22:03 |
December | 827.17 | 01-DEC-10:09 | 1295.71 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1312.91 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.17 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.78 | |||||
Maximum of Months | 827.17 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 303.03 | 1706.21 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2046.80 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1386.79 | 28-JAN-05:20 |
February | 1306.65 | 01-FEB-10:09 | 2046.80 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1267.50 | 16-FEB-04:00 |
March | 1306.65 | 01-MAR-10:09 | 2046.80 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1283.62 | 29-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 2046.80 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 318.54 | 01-APR-17:02 | 1248.55 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2046.80 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.16 | 14-MAY-15:40 | 973.86 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2046.80 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.34 | 28-JUN-16:00 | 1227.27 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2046.80 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.54 | 23-JUL-15:50 | 612.31 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2046.80 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.98 | 13-AUG-14:52 | 900.20 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2046.80 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.88 | 14-SEP-17:00 | 596.48 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2046.80 | 02-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1159.40 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2046.80 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1341.72 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 2046.80 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1069.68 | 22-DEC-23:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 596.48 | |||||
Maximum of Months | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 318.54 | 1386.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.22 | 02-JAN-10:09 | 1295.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 923.47 | 28-JAN-05:08 |
February | 827.22 | 01-FEB-10:09 | 1295.79 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 831.40 | 16-FEB-04:00 |
March | 827.22 | 01-MAR-10:09 | 1295.79 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 849.82 | 29-MAR-05:00 |
April | 827.22 | 03-APR-09:09 | 1295.79 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 228.40 | 01-APR-17:02 | 833.90 | 07-APR-24:00 |
May | 827.22 | 01-MAY-09:09 | 1295.79 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.06 | 06-MAY-15:00 | 644.73 | 18-MAY-05:00 |
June | 827.22 | 01-JUN-09:09 | 1295.79 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 28-JUN-15:00 | 814.62 | 13-JUN-03:00 |
July | 827.22 | 03-JUL-09:09 | 1295.79 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.81 | 23-JUL-16:10 | 392.21 | 02-JUL-04:00 |
August | 827.22 | 01-AUG-09:09 | 1295.79 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.69 | 13-AUG-17:40 | 616.63 | 11-AUG-04:00 |
September | 827.22 | 01-SEP-09:09 | 1295.79 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.57 | 14-SEP-17:00 | 378.48 | 18-SEP-23:00 |
October | 827.22 | 02-OCT-09:09 | 1295.79 | 02-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 766.10 | 31-OCT-21:03 |
November | 827.22 | 01-NOV-09:09 | 1295.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 | 04-NOV-15:00 | 880.19 | 29-NOV-23:00 |
December | 827.22 | 01-DEC-10:09 | 1295.79 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 710.54 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 378.48 | |||||
Maximum of Months | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 228.40 | 923.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2046.80 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 29391.30 | 06-JAN-07:01 |
February | 1306.65 | 01-FEB-10:09 | 2046.80 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 27993.23 | 09-FEB-07:01 |
March | 1306.65 | 01-MAR-10:09 | 2046.80 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 27372.87 | 01-MAR-07:01 |
April | 1306.65 | 03-APR-09:09 | 2046.80 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3692.45 | 27-APR-16:10 | 23873.87 | 19-APR-06:01 |
May | 1306.65 | 01-MAY-09:09 | 2046.80 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 872.88 | 05-MAY-16:10 | 19408.16 | 18-MAY-06:01 |
June | 1306.65 | 01-JUN-09:09 | 2046.80 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3320.43 | 28-JUN-17:00 | 14121.05 | 15-JUN-06:02 |
July | 1306.65 | 03-JUL-09:09 | 2046.80 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5883.94 | 31-JUL-16:10 | 11274.25 | 03-JUL-06:05 |
August | 1306.65 | 01-AUG-09:09 | 2046.80 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8579.26 | 10-AUG-17:00 | 12540.64 | 01-AUG-06:05 |
September | 1306.65 | 01-SEP-09:09 | 2046.80 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.10 | 14-SEP-17:00 | 15757.67 | 27-SEP-06:01 |
October | 1306.65 | 02-OCT-09:09 | 2046.80 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 18585.46 | 24-OCT-06:01 |
November | 1306.65 | 01-NOV-09:09 | 2046.80 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 25692.94 | 24-NOV-07:01 |
December | 1306.65 | 01-DEC-10:09 | 2046.80 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 27569.44 | 26-DEC-07:01 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11274.25 | |||||
Maximum of Months | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 8579.26 | 29391.30 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1295.71 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 923.47 | 28-JAN-05:08 |
February | 827.17 | 01-FEB-10:09 | 1295.71 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 830.95 | 16-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 1295.71 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 849.82 | 29-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 1295.71 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.92 | 01-APR-17:02 | 827.76 | 10-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 1295.71 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 | 06-MAY-13:00 | 644.73 | 18-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 1295.71 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.96 | 10-JUN-17:03 | 775.14 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1295.71 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 119.54 | 23-JUL-15:02 | 407.11 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 1295.71 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 | 13-AUG-14:32 | 637.39 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 1295.71 | 01-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 | 14-SEP-17:00 | 376.79 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 1295.71 | 02-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 766.11 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1295.71 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 878.17 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 1295.71 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 710.54 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.17 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.79 | |||||
Maximum of Months | 827.17 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 131.92 | 923.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2046.80 | 02-JAN-08:09 | 1505.89 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2085.52 | 28-JAN-05:20 |
February | 1306.65 | 01-FEB-10:09 | 2046.80 | 01-FEB-08:09 | 1505.89 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1912.72 | 16-FEB-22:02 |
March | 1306.65 | 01-MAR-10:09 | 2046.80 | 01-MAR-08:09 | 1505.89 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1957.00 | 29-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 2046.80 | 03-APR-07:10 | 1505.89 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.06 | 01-APR-17:02 | 1904.40 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2046.80 | 01-MAY-07:10 | 1505.89 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.41 | 14-MAY-16:00 | 1484.91 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2046.80 | 01-JUN-07:10 | 1505.89 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | 28-JUN-15:00 | 1840.42 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2046.80 | 03-JUL-07:10 | 1505.89 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.75 | 23-JUL-16:00 | 917.56 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2046.80 | 01-AUG-07:10 | 1505.89 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.41 | 13-AUG-15:00 | 1355.08 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2046.80 | 01-SEP-07:10 | 1505.89 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 14-SEP-17:00 | 892.28 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2046.80 | 02-OCT-07:10 | 1505.89 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1759.54 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2046.80 | 01-NOV-07:10 | 1505.89 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1963.09 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 2046.80 | 01-DEC-08:09 | 1505.89 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1623.72 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 892.28 | |||||
Maximum of Months | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 424.06 | 2085.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 805.43 | 02-JAN-08:09 | 1295.79 | 02-JAN-08:09 | 953.30 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1417.91 | 28-JAN-05:08 |
February | 805.43 | 01-FEB-08:09 | 1295.79 | 01-FEB-08:09 | 953.30 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1273.73 | 16-FEB-22:02 |
March | 805.43 | 01-MAR-08:09 | 1295.79 | 01-MAR-08:09 | 953.30 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1304.66 | 29-MAR-05:00 |
April | 805.43 | 03-APR-07:10 | 1295.79 | 03-APR-07:10 | 953.30 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.14 | 01-APR-17:02 | 1266.36 | 10-APR-21:03 |
May | 805.43 | 01-MAY-07:10 | 1295.79 | 01-MAY-07:10 | 953.30 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.72 | 14-MAY-16:00 | 989.92 | 18-MAY-05:00 |
June | 805.43 | 01-JUN-07:10 | 1295.79 | 01-JUN-07:10 | 953.30 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.57 | 28-JUN-16:20 | 1190.68 | 13-JUN-03:00 |
July | 805.43 | 03-JUL-07:10 | 1295.79 | 03-JUL-07:10 | 953.30 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.31 | 23-JUL-16:00 | 593.70 | 02-JUL-04:00 |
August | 805.43 | 01-AUG-07:10 | 1295.79 | 01-AUG-07:10 | 953.30 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.28 | 13-AUG-18:00 | 893.14 | 11-AUG-04:00 |
September | 805.43 | 01-SEP-07:10 | 1295.79 | 01-SEP-07:10 | 953.30 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 | 10-SEP-14:50 | 569.69 | 18-SEP-23:00 |
October | 805.43 | 02-OCT-07:10 | 1295.79 | 02-OCT-07:10 | 953.30 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1170.42 | 31-OCT-21:03 |
November | 805.43 | 01-NOV-07:10 | 1295.79 | 01-NOV-07:10 | 953.30 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 04-NOV-15:00 | 1293.66 | 29-NOV-23:00 |
December | 805.43 | 01-DEC-08:09 | 1295.79 | 01-DEC-08:09 | 953.30 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1091.03 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 569.69 | |||||
Maximum of Months | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 367.31 | 1417.91 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1306.65 | 02-JAN-10:09 | 2046.80 | 02-JAN-08:09 | 1505.88 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2126.88 | 28-JAN-05:09 |
February | 1306.65 | 01-FEB-10:09 | 2046.80 | 01-FEB-08:09 | 1505.88 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2018.74 | 19-FEB-12:00 |
March | 1306.65 | 01-MAR-10:09 | 2046.80 | 01-MAR-08:09 | 1505.88 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1957.00 | 29-MAR-05:00 |
April | 1306.65 | 03-APR-09:09 | 2046.80 | 03-APR-07:10 | 1505.88 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.36 | 01-APR-17:02 | 1903.76 | 10-APR-21:03 |
May | 1306.65 | 01-MAY-09:09 | 2046.80 | 01-MAY-07:10 | 1505.88 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.75 | 14-MAY-16:40 | 1484.90 | 18-MAY-05:00 |
June | 1306.65 | 01-JUN-09:09 | 2046.80 | 01-JUN-07:10 | 1505.88 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | 28-JUN-15:00 | 1803.69 | 13-JUN-03:00 |
July | 1306.65 | 03-JUL-09:09 | 2046.80 | 03-JUL-07:10 | 1505.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 510.62 | 23-JUL-16:00 | 910.63 | 02-JUL-04:00 |
August | 1306.65 | 01-AUG-09:09 | 2046.80 | 01-AUG-07:10 | 1505.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 251.87 | 13-AUG-18:00 | 1360.28 | 11-AUG-04:00 |
September | 1306.65 | 01-SEP-09:09 | 2046.80 | 01-SEP-07:10 | 1505.88 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.20 | 14-SEP-17:00 | 871.58 | 18-SEP-23:00 |
October | 1306.65 | 02-OCT-09:09 | 2046.80 | 02-OCT-07:10 | 1505.88 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1757.55 | 31-OCT-21:03 |
November | 1306.65 | 01-NOV-09:09 | 2046.80 | 01-NOV-07:10 | 1505.88 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1954.93 | 29-NOV-23:00 |
December | 1306.65 | 01-DEC-10:09 | 2046.80 | 01-DEC-08:09 | 1505.88 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1636.55 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 871.58 | |||||
Maximum of Months | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 510.62 | 2126.88 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum}[W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum}[W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum}[W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 827.17 | 02-JAN-10:09 | 1295.71 | 02-JAN-08:09 | 953.29 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 1417.91 | 28-JAN-05:08 |
February | 827.17 | 01-FEB-10:09 | 1295.71 | 01-FEB-08:09 | 953.29 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1273.45 | 16-FEB-22:02 |
March | 827.17 | 01-MAR-10:09 | 1295.71 | 01-MAR-08:09 | 953.29 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1304.66 | 29-MAR-05:00 |
April | 827.17 | 03-APR-09:09 | 1295.71 | 03-APR-07:10 | 953.29 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.21 | 01-APR-17:02 | 1269.20 | 10-APR-21:03 |
May | 827.17 | 01-MAY-09:09 | 1295.71 | 01-MAY-07:10 | 953.29 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 06-MAY-13:00 | 989.92 | 18-MAY-05:00 |
June | 827.17 | 01-JUN-09:09 | 1295.71 | 01-JUN-07:10 | 953.29 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.19 | 10-JUN-17:03 | 1180.48 | 13-JUN-03:00 |
July | 827.17 | 03-JUL-09:09 | 1295.71 | 03-JUL-07:10 | 953.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 299.72 | 23-JUL-13:50 | 609.41 | 02-JUL-04:00 |
August | 827.17 | 01-AUG-09:09 | 1295.71 | 01-AUG-07:10 | 953.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 182.04 | 13-AUG-12:00 | 918.85 | 11-AUG-04:00 |
September | 827.17 | 01-SEP-09:09 | 1295.71 | 01-SEP-07:10 | 953.29 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.80 | 14-SEP-17:00 | 571.33 | 18-SEP-23:00 |
October | 827.17 | 02-OCT-09:09 | 1295.71 | 02-OCT-07:10 | 953.29 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1169.92 | 31-OCT-21:03 |
November | 827.17 | 01-NOV-09:09 | 1295.71 | 01-NOV-07:10 | 953.29 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1290.80 | 29-NOV-23:00 |
December | 827.17 | 01-DEC-10:09 | 1295.71 | 01-DEC-08:09 | 953.29 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1091.03 | 20-DEC-06:00 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 827.17 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.33 | |||||
Maximum of Months | 827.17 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 299.72 | 1417.91 |
Report: PeakSpaceGainsMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3060.66 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2829.71 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2630.42 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.07 | 01-APR-17:02 | 2754.01 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 | 05-MAY-16:00 | 2062.86 | 18-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.50 | 28-JUN-16:30 | 2712.96 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 403.82 | 23-JUL-15:50 | 1337.65 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.23 | 13-AUG-14:52 | 1941.83 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.86 | 14-SEP-17:00 | 1270.59 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2430.78 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2883.89 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2341.17 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1270.59 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.07 | 3060.66 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3750.87 | 12-JAN-24:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3448.66 | 16-FEB-04:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3242.53 | 28-MAR-24:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.49 | 01-APR-17:02 | 3439.89 | 07-APR-24:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 | 05-MAY-16:00 | 2561.54 | 18-MAY-04:55 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 | 28-JUN-15:00 | 3400.95 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 532.97 | 23-JUL-16:00 | 1659.63 | 02-JUL-04:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 330.94 | 13-AUG-15:00 | 2454.78 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 14-SEP-17:00 | 1564.15 | 30-SEP-04:53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2996.63 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3512.80 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2879.08 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1564.15 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.49 | 3750.87 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum}[W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3545.07 | 12-JAN-22:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3288.92 | 16-FEB-22:02 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3145.56 | 29-MAR-05:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.10 | 01-APR-17:02 | 3369.56 | 10-APR-21:03 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 2452.10 | 18-MAY-05:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.48 | 28-JUN-17:00 | 2979.97 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.43 | 23-JUL-16:00 | 1764.62 | 04-JUL-15:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.55 | 08-AUG-17:00 | 2268.75 | 11-AUG-04:00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1461.77 | 18-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3086.84 | 31-OCT-21:03 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3360.85 | 29-NOV-23:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2880.33 | 22-DEC-23:00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.77 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.10 | 3545.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 20108.35 | 13-JAN-08:30 | 24140.03 | 38837.01 | 118492.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 30429.57 | 10-FEB-05:01 | 0.00 | 10586.70 | 34986.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 48169.24 | 02-MAR-05:01 | 0.00 | 8469.36 | 27989.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53021.17 | 28-APR-04:02 | 0.00 | 6352.02 | 20991.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53256.28 | 08-MAY-04:02 | 0.00 | 6352.02 | 20991.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 55973.64 | 12-JUN-04:01 | 0.00 | 7410.69 | 24490.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 57131.29 | 10-JUL-04:01 | 0.00 | 7410.69 | 24490.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 58356.30 | 10-AUG-04:03 | 0.00 | 7410.69 | 24490.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 56966.81 | 05-SEP-04:01 | 0.00 | 7410.69 | 24490.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 52843.88 | 05-OCT-04:02 | 0.00 | 6352.02 | 20991.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 48951.99 | 06-NOV-05:02 | 0.00 | 6352.02 | 20991.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 23196.42 | 07-DEC-05:01 | 0.00 | 9528.03 | 31487.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 20108.35 | 0.00 | 6352.02 | 20991.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 58356.30 | 24140.03 | 38837.01 | 118492.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 671.50 | 20-JAN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.70 |
February | 2876.60 | 27-FEB-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.36 |
March | 4367.02 | 14-MAR-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.61 |
April | 9240.84 | 27-APR-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 0.00 |
May | 9494.45 | 15-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.01 |
June | 9859.34 | 28-JUN-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
July | 10843.88 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 0.00 |
August | 11322.88 | 10-AUG-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.42 | 0.00 |
September | 8478.32 | 14-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.58 |
October | 5618.89 | 04-OCT-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.08 |
November | 3369.49 | 04-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 746.12 | 05-DEC-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.45 |
Annual Sum or Average | |||||||||||
Minimum of Months | 671.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11322.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.54 | 219.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2001.88 | 07-JAN-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.03 |
February | 2196.39 | 04-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.56 |
March | 2153.85 | 04-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 688.23 |
April | 3373.52 | 28-APR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.66 |
May | 3587.24 | 05-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3687.75 | 22-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.60 |
July | 3783.21 | 25-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1039.80 |
August | 4286.59 | 10-AUG-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 471.34 |
September | 3794.56 | 14-SEP-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2689.19 | 05-OCT-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 879.56 |
November | 1932.65 | 18-NOV-17:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.02 |
December | 2179.46 | 09-DEC-17:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.89 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1932.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4286.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1132.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2031.64 | 07-JAN-17:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.46 |
February | 2168.18 | 04-FEB-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.14 |
March | 2240.08 | 04-MAR-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 553.96 |
April | 3812.40 | 27-APR-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.50 |
May | 4013.94 | 05-MAY-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.17 |
June | 4329.51 | 22-JUN-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.08 |
July | 4293.15 | 08-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.88 |
August | 4664.22 | 10-AUG-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.71 |
September | 4391.26 | 14-SEP-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3487.31 | 05-OCT-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.66 |
November | 2294.66 | 04-NOV-04:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.87 |
December | 2082.08 | 30-DEC-17:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2031.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 4664.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 708.66 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 9217.99 | 06-JAN-08:20 | 60350.08 | 97092.53 | 71434.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9729.60 | 28-FEB-17:00 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 10472.98 | 02-MAR-17:00 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 32766.56 | 28-APR-04:02 | 0.00 | 6352.02 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 32815.86 | 05-MAY-04:02 | 0.00 | 6352.02 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34290.34 | 29-JUN-04:01 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 35105.64 | 25-JUL-04:01 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 36771.74 | 10-AUG-04:03 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34406.97 | 15-SEP-04:01 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31416.74 | 05-OCT-04:02 | 0.00 | 6352.02 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9765.24 | 03-NOV-16:00 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9433.19 | 06-DEC-16:10 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 9217.99 | 0.00 | 6352.02 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36771.74 | 60350.08 | 97092.53 | 71434.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 8683.65 | 11-JAN-16:50 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9474.04 | 28-FEB-17:00 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9907.99 | 02-MAR-17:00 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 18426.44 | 27-APR-15:50 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31955.08 | 05-MAY-04:02 | 0.00 | 6352.02 | 19049.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34134.89 | 12-JUN-04:01 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 34225.64 | 25-JUL-04:01 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 35108.85 | 10-AUG-04:01 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32713.00 | 14-SEP-04:01 | 0.00 | 7410.69 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 15329.70 | 04-OCT-16:00 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9375.50 | 02-NOV-15:40 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8838.37 | 06-DEC-15:50 | 6035.01 | 9709.25 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 8683.65 | 0.00 | 6352.02 | 7143.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35108.85 | 6035.01 | 9709.25 | 22224.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2023.38 | 11-JAN-16:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.02 |
February | 2325.64 | 27-FEB-16:20 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 |
March | 2440.31 | 10-MAR-14:50 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.34 |
April | 5155.59 | 27-APR-15:40 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 0.00 |
May | 5052.83 | 15-MAY-15:20 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.79 |
June | 5796.22 | 21-JUN-15:40 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 10.94 | 0.00 |
July | 6802.46 | 24-JUL-15:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 80.47 | 0.00 |
August | 6513.14 | 09-AUG-15:30 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 95.76 | 0.00 |
September | 4941.11 | 14-SEP-15:50 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.81 | 0.00 |
October | 3028.62 | 04-OCT-15:30 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.06 |
November | 2253.67 | 02-NOV-14:40 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.48 |
December | 1909.56 | 29-DEC-15:00 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1909.56 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6802.46 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 95.76 | 181.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2291.05 | 28-JAN-17:02 | 254.35 | 431.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.92 |
February | 2584.06 | 27-FEB-15:50 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 |
March | 3145.83 | 14-MAR-09:35 | 1654.44 | 2591.58 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.85 |
April | 6410.37 | 27-APR-09:00 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.93 |
May | 6423.27 | 15-MAY-08:50 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.71 |
June | 7111.88 | 28-JUN-09:00 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.00 |
July | 8575.32 | 31-JUL-08:30 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.96 |
August | 8927.27 | 10-AUG-08:30 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 |
September | 6381.02 | 14-SEP-09:10 | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.19 |
October | 4369.88 | 04-OCT-09:00 | 1610.86 | 2591.58 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.66 |
November | 2505.85 | 02-NOV-14:10 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.62 |
December | 2286.85 | 23-DEC-17:02 | 254.35 | 431.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.43 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2286.85 | 254.35 | 431.93 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.12 | |
Maximum of Months | 8927.27 | 1654.44 | 2591.58 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8248.30 | 20-JAN-13:04 | 6361.16 | 10233.98 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 |
February | 8966.40 | 27-FEB-14:30 | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.59 |
March | 10141.17 | 01-MAR-13:25 | 2544.47 | 4093.59 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.01 |
April | 11583.07 | 27-APR-13:10 | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 0.00 |
May | 8534.08 | 15-MAY-13:00 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 |
June | 7770.82 | 11-JUN-12:31 | 468.72 | 795.98 | 3513.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.56 |
July | 12224.85 | 30-JUL-12:42 | 334.80 | 568.55 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.36 |
August | 13550.72 | 29-AUG-12:30 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 56.94 | 0.00 |
September | 19405.51 | 10-SEP-13:12 | 334.80 | 568.55 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.35 |
October | 13687.43 | 04-OCT-13:00 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 |
November | 8683.09 | 04-NOV-13:30 | 137.54 | 341.13 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7958.91 | 05-DEC-12:30 | 687.71 | 2046.80 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 7770.82 | 137.54 | 341.13 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19405.51 | 6361.16 | 10233.98 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 56.94 | 290.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2759.31 | 05-JAN-15:50 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.78 |
February | 3559.52 | 27-FEB-15:40 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.36 |
March | 5336.35 | 14-MAR-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.93 |
April | 8364.71 | 26-APR-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 0.00 |
May | 16222.64 | 07-MAY-17:12 | 0.00 | 423.84 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.96 |
June | 15243.26 | 18-JUN-17:22 | 0.00 | 423.84 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 516.57 |
July | 17200.77 | 30-JUL-17:21 | 0.00 | 494.48 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.83 |
August | 15369.66 | 06-AUG-18:22 | 0.00 | 353.20 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.43 |
September | 15548.74 | 10-SEP-16:32 | 254.33 | 431.90 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.22 |
October | 6727.17 | 04-OCT-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.63 |
November | 3214.88 | 04-NOV-15:40 | 84.78 | 215.95 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.35 |
December | 2875.53 | 05-DEC-15:30 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.02 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2759.31 | 0.00 | 215.95 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17200.77 | 805.38 | 1295.71 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2.94 | 516.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1619.20 | 11-JAN-16:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.49 |
February | 1779.84 | 28-FEB-15:00 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1847.65 | 10-MAR-14:40 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.94 |
April | 2659.60 | 27-APR-16:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 28.74 | 0.00 |
May | 3162.39 | 05-MAY-15:40 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 0.00 |
June | 3848.24 | 21-JUN-16:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | 0.00 |
July | 4584.95 | 24-JUL-15:20 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 | 0.00 |
August | 5518.16 | 10-AUG-04:01 | 0.00 | 1562.24 | 4685.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.76 |
September | 3744.93 | 14-SEP-15:50 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1.84 | 0.00 |
October | 2206.98 | 04-OCT-16:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.55 |
November | 1856.45 | 02-NOV-14:10 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.35 |
December | 1616.65 | 29-DEC-14:10 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.32 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1616.65 | 0.00 | 1562.24 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5518.16 | 1306.65 | 2046.80 | 4685.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.18 | 168.76 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2038.15 | 11-JAN-05:04 | 0.00 | 989.03 | 2965.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.23 |
February | 2111.21 | 27-FEB-15:40 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
March | 2431.12 | 14-MAR-08:40 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.37 |
April | 4187.41 | 27-APR-09:10 | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.47 |
May | 4549.26 | 15-MAY-09:00 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.60 |
June | 5208.03 | 28-JUN-09:10 | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.44 |
July | 6447.90 | 24-JUL-09:00 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
August | 7425.01 | 13-AUG-07:12 | 211.95 | 359.94 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.41 |
September | 5157.92 | 14-SEP-09:10 | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
October | 3502.99 | 04-OCT-08:20 | 1610.86 | 2591.58 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.24 |
November | 2210.92 | 02-NOV-14:00 | 827.22 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.48 |
December | 1953.29 | 23-DEC-17:02 | 254.35 | 431.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.95 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1953.29 | 0.00 | 359.94 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 | |
Maximum of Months | 7425.01 | 1610.86 | 2591.58 | 2965.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3188.22 | 20-JAN-13:50 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3052.88 |
February | 4432.30 | 27-FEB-14:55 | 2613.31 | 4093.59 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 742.41 |
March | 3658.12 | 01-MAR-15:00 | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2014.57 |
April | 8040.61 | 27-APR-16:10 | 401.76 | 1137.11 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3692.45 | 0.00 |
May | 4625.60 | 15-MAY-13:10 | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 208.41 |
June | 6490.93 | 28-JUN-17:00 | 401.76 | 1137.11 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 3320.43 | 0.00 |
July | 10836.24 | 31-JUL-16:10 | 401.76 | 1137.11 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 5883.94 | 0.00 |
August | 13042.94 | 10-AUG-17:00 | 401.76 | 1137.11 | 836.60 | 0.00 | 0.00 | 0.00 | 0.00 | 8579.26 | 0.00 |
September | 11318.33 | 14-SEP-04:01 | 0.00 | 1562.24 | 4684.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 10542.44 | 04-OCT-13:30 | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 590.04 |
November | 6081.44 | 04-NOV-13:30 | 137.54 | 341.13 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3877.58 | 02-DEC-13:10 | 133.92 | 341.13 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.55 |
Annual Sum or Average | |||||||||||
Minimum of Months | 3188.22 | 0.00 | 341.13 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 13042.94 | 2613.31 | 4093.59 | 4684.97 | 0.00 | 0.00 | 0.00 | 0.00 | 8579.26 | 3052.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2315.16 | 05-JAN-15:50 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.59 |
February | 2790.75 | 27-FEB-15:50 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
March | 3025.02 | 02-MAR-16:50 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.92 |
April | 5324.27 | 26-APR-17:00 | 254.33 | 719.84 | 529.61 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 0.00 |
May | 6806.95 | 07-MAY-16:32 | 254.33 | 431.90 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.86 |
June | 6131.85 | 22-JUN-18:10 | 84.78 | 431.90 | 423.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
July | 12026.36 | 23-JUL-18:01 | 0.00 | 494.48 | 2224.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.49 |
August | 8778.12 | 09-AUG-04:01 | 0.00 | 988.96 | 2965.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.86 |
September | 9608.41 | 10-SEP-16:32 | 254.33 | 431.90 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.22 |
October | 5504.00 | 04-OCT-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.21 |
November | 2703.52 | 04-NOV-15:50 | 84.78 | 215.95 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
December | 2477.76 | 05-DEC-15:40 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.53 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2315.16 | 0.00 | 215.95 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12026.36 | 805.38 | 1295.71 | 2965.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.71 | 117.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1960.91 | 11-JAN-16:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.08 |
February | 2210.43 | 28-FEB-15:00 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2293.13 | 10-MAR-14:50 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.62 |
April | 4589.75 | 27-APR-16:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 43.39 | 0.00 |
May | 4717.87 | 05-MAY-15:40 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 7.23 | 0.00 |
June | 5223.77 | 21-JUN-15:50 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 11.36 | 0.00 |
July | 5984.38 | 24-JUL-15:00 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 67.25 | 0.00 |
August | 6918.66 | 25-AUG-04:01 | 0.00 | 1562.24 | 4685.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.75 |
September | 4612.17 | 14-SEP-15:50 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 2.57 | 0.00 |
October | 3014.17 | 04-OCT-15:30 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.21 |
November | 2165.39 | 02-NOV-14:40 | 1272.23 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.38 |
December | 1892.67 | 29-DEC-15:00 | 1306.65 | 2046.80 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.97 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1892.67 | 0.00 | 1562.24 | 1505.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6918.66 | 1306.65 | 2046.80 | 4685.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.25 | 302.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2488.72 | 28-JAN-17:02 | 254.35 | 431.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.83 |
February | 2852.69 | 08-FEB-09:50 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
March | 3471.89 | 14-MAR-09:00 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 |
April | 6750.11 | 27-APR-08:50 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.73 |
May | 6712.18 | 15-MAY-08:40 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.33 |
June | 7245.56 | 28-JUN-08:40 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.99 |
July | 8745.91 | 31-JUL-08:00 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.07 |
August | 9155.60 | 10-AUG-08:20 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 |
September | 11432.78 | 10-SEP-08:32 | 211.95 | 359.94 | 1588.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.08 |
October | 5191.61 | 04-OCT-08:50 | 1610.86 | 2591.58 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.01 |
November | 2789.09 | 15-NOV-09:20 | 805.43 | 1295.79 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.73 |
December | 2487.13 | 23-DEC-17:02 | 254.35 | 431.93 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.47 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2487.13 | 211.95 | 359.94 | 953.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 | |
Maximum of Months | 11432.78 | 1610.86 | 2591.58 | 1906.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9011.97 | 20-JAN-13:04 | 6361.16 | 10233.98 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 |
February | 9205.91 | 27-FEB-14:10 | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.70 |
March | 10650.33 | 01-MAR-13:25 | 2544.47 | 4093.59 | 3011.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.01 |
April | 10959.98 | 27-APR-13:00 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 0.00 |
May | 7792.97 | 15-MAY-12:50 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.03 |
June | 6658.29 | 21-JUN-13:30 | 1306.65 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.49 |
July | 9935.33 | 31-JUL-13:00 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 | 0.00 |
August | 13023.66 | 29-AUG-12:30 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 0.00 |
September | 17952.79 | 10-SEP-14:02 | 334.80 | 568.55 | 2509.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.21 |
October | 13727.45 | 04-OCT-12:50 | 1272.23 | 2046.80 | 1505.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.90 |
November | 8975.70 | 04-NOV-13:20 | 137.54 | 341.13 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9016.93 | 05-DEC-12:30 | 687.71 | 2046.80 | 1338.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.57 |
Annual Sum or Average | |||||||||||
Minimum of Months | 6658.29 | 137.54 | 341.13 | 585.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17952.79 | 6361.16 | 10233.98 | 7529.41 | 0.00 | 0.00 | 0.00 | 0.00 | 47.66 | 179.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum}[W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2846.29 | 05-JAN-15:50 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.76 |
February | 3558.43 | 27-FEB-15:40 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.40 |
March | 5132.89 | 14-MAR-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 |
April | 7955.91 | 26-APR-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 0.00 |
May | 9740.15 | 14-MAY-17:12 | 0.00 | 353.20 | 1588.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.21 |
June | 9272.54 | 25-JUN-16:22 | 254.33 | 431.90 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.52 |
July | 14818.78 | 23-JUL-17:12 | 0.00 | 423.84 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.68 |
August | 15211.88 | 06-AUG-17:32 | 0.00 | 423.84 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.02 |
September | 8388.14 | 11-SEP-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 |
October | 6694.24 | 04-OCT-16:00 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.35 |
November | 3237.97 | 04-NOV-15:40 | 84.78 | 215.95 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.72 |
December | 2974.20 | 05-DEC-15:40 | 805.38 | 1295.71 | 953.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.30 |
Annual Sum or Average | |||||||||||
Minimum of Months | 2846.29 | 0.00 | 215.95 | 370.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15211.88 | 805.38 | 1295.71 | 1906.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.62 | 236.21 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | GAS:FACILITY [J] | GAS:FACILITY {Maximum}[W] | GAS:FACILITY {TIMESTAMP} | |
January | 0.218597E+12 | 252595.59 | 02-JAN-08:09 | 0.744275E+11 | 117746.09 | 07-JAN-07:00 |
February | 0.178260E+12 | 204055.50 | 21-FEB-08:09 | 0.541564E+11 | 110059.72 | 18-FEB-07:10 |
March | 0.184654E+12 | 164861.05 | 06-MAR-05:10 | 0.359073E+11 | 97429.52 | 01-MAR-07:10 |
April | 0.159153E+12 | 155534.91 | 27-APR-15:09 | 0.216892E+11 | 76621.22 | 19-APR-06:10 |
May | 0.162120E+12 | 145857.05 | 05-MAY-15:00 | 0.121182E+11 | 50728.72 | 18-MAY-06:10 |
June | 0.162163E+12 | 157606.60 | 28-JUN-15:00 | 0.752606E+10 | 18990.00 | 15-JUN-06:10 |
July | 0.167415E+12 | 177643.15 | 31-JUL-15:00 | 0.691583E+10 | 9960.55 | 05-JUL-11:20 |
August | 0.189844E+12 | 188497.53 | 10-AUG-15:00 | 0.715966E+10 | 9931.22 | 31-AUG-11:50 |
September | 0.161708E+12 | 162045.47 | 14-SEP-12:00 | 0.754475E+10 | 28794.72 | 27-SEP-06:10 |
October | 0.168107E+12 | 146170.23 | 30-OCT-07:10 | 0.148433E+11 | 47587.39 | 16-OCT-06:00 |
November | 0.183861E+12 | 166601.96 | 13-NOV-08:09 | 0.410994E+11 | 91983.37 | 13-NOV-07:00 |
December | 0.201694E+12 | 210588.01 | 26-DEC-08:09 | 0.650080E+11 | 107901.03 | 26-DEC-07:10 |
Annual Sum or Average | 0.213758E+13 | 0.348396E+12 | ||||
Minimum of Months | 0.159153E+12 | 145857.05 | 0.691583E+10 | 9931.22 | ||
Maximum of Months | 0.218597E+12 | 252595.59 | 0.744275E+11 | 117746.09 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.469510E+11 | 0.245293E+11 | 0.685557E+11 | 0.283919E+10 | 0.703187E+10 | 12379738.55 | 0.686005E+11 | 77152427.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425883E+11 | 0.202224E+11 | 0.621111E+11 | 0.256962E+10 | 0.613940E+10 | 11196018.53 | 0.437458E+11 | 0.872454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.506121E+11 | 0.197391E+11 | 0.717900E+11 | 0.297811E+10 | 0.719476E+10 | 12675668.56 | 0.309252E+11 | 0.140189E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.452016E+11 | 0.164421E+11 | 0.662239E+11 | 0.273380E+10 | 0.682244E+10 | 11960504.38 | 0.167296E+11 | 0.498782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.487815E+11 | 0.146037E+11 | 0.701729E+11 | 0.290865E+10 | 0.768907E+10 | 12527703.56 | 0.739161E+10 | 0.105601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.485477E+11 | 0.128516E+11 | 0.691028E+11 | 0.286510E+10 | 0.835644E+10 | 12231773.55 | 0.296452E+10 | 0.174628E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.454354E+11 | 0.138700E+11 | 0.672940E+11 | 0.277735E+10 | 0.911752E+10 | 12256434.38 | 0.977332E+09 | 0.279312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.506121E+11 | 0.159242E+11 | 0.717900E+11 | 0.297811E+10 | 0.106433E+11 | 12675668.56 | 0.109268E+10 | 0.367911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452016E+11 | 0.179438E+11 | 0.662239E+11 | 0.273380E+10 | 0.819540E+10 | 11960504.38 | 0.399894E+10 | 0.173981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.469510E+11 | 0.212927E+11 | 0.685557E+11 | 0.283919E+10 | 0.701564E+10 | 12379738.55 | 0.173894E+11 | 0.405076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.464022E+11 | 0.230189E+11 | 0.671301E+11 | 0.278802E+10 | 0.637675E+10 | 12059147.71 | 0.369548E+11 | 0.117797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.454354E+11 | 0.251594E+11 | 0.672940E+11 | 0.277735E+10 | 0.655084E+10 | 12256434.38 | 0.544561E+11 | 8600178.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.562720E+12 | 0.225597E+12 | 0.816244E+12 | 0.337883E+11 | 0.911335E+11 | 0.146559E+09 | 0.285226E+12 | 0.122720E+12 | |||||
Minimum of Months | 0.425883E+11 | 0.128516E+11 | 0.621111E+11 | 0.256962E+10 | 0.613940E+10 | 11196018.53 | 0.977332E+09 | 8600178.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.506121E+11 | 0.251594E+11 | 0.717900E+11 | 0.297811E+10 | 0.106433E+11 | 12675668.56 | 0.686005E+11 | 0.367911E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS [J] | COOLING:GAS [] | WATERSYSTEMS:GAS [J] | COGENERATION:GAS [] | HUMIDIFIER:GAS [] | |
January | 0.00 | 0.00 | 0.667527E+11 | 0.00 | 0.767476E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.471912E+11 | 0.00 | 0.696514E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.280521E+11 | 0.00 | 0.785515E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.144720E+11 | 0.00 | 0.721721E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.471859E+10 | 0.00 | 0.739957E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.486130E+09 | 0.00 | 0.703993E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 379501.17 | 0.00 | 0.691545E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 21276874.05 | 0.00 | 0.713839E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.774920E+09 | 0.00 | 0.676983E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.767676E+10 | 0.00 | 0.716652E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.339172E+11 | 0.00 | 0.718222E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.575742E+11 | 0.00 | 0.743383E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.261638E+12 | 0.867580E+11 | |||||
Minimum of Months | 0.00 | 0.00 | 379501.17 | 0.00 | 0.676983E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.667527E+11 | 0.00 | 0.785515E+10 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum}[W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum}[W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum}[W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum}[W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum}[W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum}[W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 49183.02 | 02-JAN-08:09 | 14385.00 | 01-JAN-00:10 | 58665.02 | 02-JAN-08:09 | 2424.90 | 04-JAN-08:20 | 5263.32 | 20-JAN-13:09 | 6.85 | 02-JAN-06:19 | 183449.94 | 02-JAN-06:30 |
February | 49183.02 | 01-FEB-08:09 | 14385.00 | 01-FEB-00:10 | 58665.02 | 01-FEB-08:09 | 2424.90 | 06-FEB-08:20 | 5457.82 | 08-FEB-13:39 | 6.85 | 02-FEB-07:19 | 149848.18 | 21-FEB-05:19 |
March | 49183.02 | 01-MAR-08:09 | 14385.00 | 01-MAR-00:10 | 58665.02 | 01-MAR-08:09 | 2424.90 | 02-MAR-08:20 | 6045.32 | 01-MAR-13:39 | 6.85 | 01-MAR-13:09 | 123637.94 | 06-MAR-05:10 |
April | 49183.02 | 03-APR-07:10 | 14385.00 | 01-APR-00:10 | 58665.02 | 03-APR-07:10 | 2424.90 | 03-APR-12:09 | 10596.93 | 27-APR-15:09 | 6.85 | 01-APR-17:10 | 89800.14 | 11-APR-04:10 |
May | 49183.02 | 01-MAY-07:10 | 14385.00 | 01-MAY-00:10 | 58665.02 | 01-MAY-07:10 | 2424.90 | 01-MAY-07:19 | 10510.33 | 15-MAY-15:00 | 6.85 | 02-MAY-06:10 | 55659.78 | 18-MAY-04:10 |
June | 49183.02 | 01-JUN-07:10 | 14385.00 | 01-JUN-00:10 | 58665.02 | 01-JUN-07:10 | 2424.90 | 01-JUN-07:19 | 12569.99 | 28-JUN-15:00 | 6.85 | 01-JUN-07:10 | 31643.38 | 14-JUN-04:10 |
July | 49183.02 | 03-JUL-07:10 | 14385.00 | 01-JUL-00:10 | 58665.02 | 03-JUL-07:10 | 2424.90 | 03-JUL-07:19 | 13942.49 | 31-JUL-15:00 | 6.85 | 04-JUL-16:49 | 13489.81 | 03-JUL-06:10 |
August | 49183.02 | 01-AUG-07:10 | 14385.00 | 01-AUG-00:10 | 58665.02 | 01-AUG-07:10 | 2424.90 | 01-AUG-07:19 | 17329.37 | 10-AUG-15:00 | 6.85 | 01-AUG-11:09 | 17563.38 | 18-AUG-06:10 |
September | 49183.02 | 01-SEP-07:10 | 14385.00 | 01-SEP-00:10 | 58665.02 | 01-SEP-07:10 | 2424.90 | 01-SEP-07:19 | 13440.08 | 14-SEP-15:09 | 6.85 | 02-SEP-17:10 | 31828.53 | 28-SEP-06:10 |
October | 49183.02 | 02-OCT-07:10 | 14385.00 | 01-OCT-00:10 | 58665.02 | 02-OCT-07:10 | 2424.90 | 02-OCT-12:09 | 10172.56 | 04-OCT-15:09 | 6.85 | 02-OCT-06:10 | 77083.74 | 30-OCT-04:10 |
November | 49183.02 | 01-NOV-07:10 | 14385.00 | 01-NOV-00:10 | 58665.02 | 01-NOV-07:10 | 2424.90 | 13-NOV-08:20 | 5590.82 | 06-NOV-05:10 | 6.85 | 02-NOV-11:09 | 114678.98 | 27-NOV-05:10 |
December | 49183.02 | 01-DEC-08:09 | 14385.00 | 01-DEC-00:10 | 58665.02 | 01-DEC-08:09 | 2424.90 | 04-DEC-08:20 | 5371.79 | 05-DEC-12:30 | 6.85 | 02-DEC-17:10 | 148180.36 | 26-DEC-05:19 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 49183.02 | 14385.00 | 58665.02 | 2424.90 | 5263.32 | 6.85 | 13489.81 | |||||||
Maximum of Months | 49183.02 | 14385.00 | 58665.02 | 2424.90 | 17329.37 | 6.85 | 183449.94 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum}[W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 6106.07 | 11-JAN-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15842.42 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15143.02 | 18-MAR-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 42043.46 | 27-APR-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 35004.79 | 05-MAY-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42142.09 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 60806.14 | 31-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 68841.24 | 29-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 46180.04 | 14-SEP-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 25193.61 | 04-OCT-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21988.83 | 04-NOV-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 2847.89 | 14-DEC-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | |||||||
Minimum of Months | 2847.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 68841.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportELECTRICITY:FACILITY {Maximum}[W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 252595.59 | 02-JAN-08:09 | 49183.02 | 58665.02 | 0.00 | 2305.06 | 4418.83 | 6.85 | 138016.81 | 0.00 | 0.00 |
February | 204055.50 | 21-FEB-08:09 | 49183.02 | 58665.02 | 0.00 | 2305.06 | 4418.83 | 6.85 | 89476.71 | 0.00 | 0.00 |
March | 164861.05 | 06-MAR-05:10 | 5362.78 | 16406.20 | 14385.00 | 650.29 | 4418.83 | 0.00 | 123637.94 | 0.00 | 0.00 |
April | 155534.91 | 27-APR-15:09 | 49183.02 | 51279.75 | 0.00 | 2424.90 | 10596.93 | 6.85 | 0.00 | 42043.46 | 0.00 |
May | 145857.05 | 05-MAY-15:00 | 49183.02 | 51279.75 | 0.00 | 2424.90 | 7957.73 | 6.85 | 0.00 | 35004.79 | 0.00 |
June | 157606.60 | 28-JUN-15:00 | 49183.02 | 51279.75 | 0.00 | 2424.90 | 12569.99 | 6.85 | 0.00 | 42142.09 | 0.00 |
July | 177643.15 | 31-JUL-15:00 | 49183.02 | 51279.75 | 0.00 | 2424.90 | 13942.49 | 6.85 | 0.00 | 60806.14 | 0.00 |
August | 188497.53 | 10-AUG-15:00 | 49183.02 | 51279.75 | 0.00 | 2424.90 | 17329.37 | 6.85 | 0.00 | 68273.64 | 0.00 |
September | 162045.47 | 14-SEP-12:00 | 49183.02 | 51921.95 | 0.00 | 2424.90 | 12328.70 | 6.85 | 0.00 | 46180.04 | 0.00 |
October | 146170.23 | 30-OCT-07:10 | 49183.02 | 58665.02 | 0.00 | 2305.06 | 4418.83 | 6.85 | 31591.44 | 0.00 | 0.00 |
November | 166601.96 | 13-NOV-08:09 | 49183.02 | 58665.02 | 0.00 | 2305.06 | 4418.83 | 6.85 | 52023.17 | 0.00 | 0.00 |
December | 210588.01 | 26-DEC-08:09 | 49183.02 | 58665.02 | 0.00 | 2305.06 | 4418.83 | 6.85 | 96009.22 | 0.00 | 0.00 |
Annual Sum or Average | |||||||||||
Minimum of Months | 145857.05 | 5362.78 | 16406.20 | 0.00 | 650.29 | 4418.83 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 252595.59 | 49183.02 | 58665.02 | 14385.00 | 2424.90 | 17329.37 | 6.85 | 138016.81 | 68273.64 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportINTERIOREQUIPMENT:GAS [] | EXTERIOREQUIPMENT:GAS [] | HEATING:GAS {Maximum}[W] | HEATING:GAS {TIMESTAMP} | COOLING:GAS [] | WATERSYSTEMS:GAS {Maximum}[W] | WATERSYSTEMS:GAS {TIMESTAMP} | COGENERATION:GAS [] | |
January | 0.00 | 0.00 | 115742.66 | 07-JAN-07:00 | 0.00 | 10237.95 | 31-JAN-12:09 | 0.00 |
February | 0.00 | 0.00 | 108056.29 | 18-FEB-07:10 | 0.00 | 10244.85 | 13-FEB-12:09 | 0.00 |
March | 0.00 | 0.00 | 95426.09 | 01-MAR-07:10 | 0.00 | 10233.11 | 01-MAR-12:09 | 0.00 |
April | 0.00 | 0.00 | 74617.79 | 19-APR-06:10 | 0.00 | 10178.45 | 03-APR-11:20 | 0.00 |
May | 0.00 | 0.00 | 48725.29 | 18-MAY-06:10 | 0.00 | 10103.75 | 03-MAY-11:09 | 0.00 |
June | 0.00 | 0.00 | 16986.57 | 15-JUN-06:10 | 0.00 | 10028.40 | 02-JUN-11:20 | 0.00 |
July | 0.00 | 0.00 | 632.50 | 03-JUL-06:10 | 0.00 | 9960.55 | 05-JUL-11:20 | 0.00 |
August | 0.00 | 0.00 | 3750.76 | 01-AUG-06:10 | 0.00 | 9931.22 | 31-AUG-11:50 | 0.00 |
September | 0.00 | 0.00 | 26791.29 | 27-SEP-06:10 | 0.00 | 9967.37 | 29-SEP-11:30 | 0.00 |
October | 0.00 | 0.00 | 45583.96 | 16-OCT-06:00 | 0.00 | 10043.61 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 89979.94 | 13-NOV-07:00 | 0.00 | 10132.11 | 29-NOV-12:09 | 0.00 |
December | 0.00 | 0.00 | 105897.60 | 26-DEC-07:10 | 0.00 | 10198.08 | 27-DEC-12:09 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 0.00 | 0.00 | 632.50 | 0.00 | 9931.22 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 115742.66 | 0.00 | 10244.85 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 19.43 | 0.33 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.63 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.61 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.61 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1.33 | 19.43 | 0.33 | 20.13 | 2.50 | 24.61 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.43 | 0.33 | 20.13 | 1.83 | 24.63 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.17 | 19.20 | 1.67 | 19.71 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.33 | 20.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3.83 | 19.39 | 1.67 | 19.71 | 0.50 | 24.56 | 0.00 | |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.17 | 20.36 | 1.67 | 19.71 | 0.50 | 24.56 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.50 | 19.17 | 4.17 | 19.68 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.17 | 19.24 | 1.00 | 20.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.50 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.17 | 19.52 | 1.17 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 17.50 | 19.35 | 6.33 | 19.80 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.50 | 20.14 | 4.17 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 44.67 | 18.13 | 14.67 | 18.78 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 29.17 | 18.34 | 8.67 | 18.45 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 13.67 | 19.72 | 0.83 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5.83 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4.33 | 20.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16.67 | 19.63 | 2.83 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 30.67 | 19.07 | 6.83 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.50 | 18.83 | 33.83 | 18.97 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 44.67 | 20.30 | 14.67 | 20.07 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.17 | 17.28 | 3.67 | 16.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12.67 | 17.82 | 1.33 | 16.14 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6.00 | 19.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3.50 | 20.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.50 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.57 | 1.17 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.67 | 0.67 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.67 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.33 | 19.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 12.50 | 18.74 | 0.50 | 18.54 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 67.33 | 18.41 | 5.50 | 16.91 | 1.83 | 27.60 | 1.83 | 27.60 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.17 | 20.25 | 3.67 | 18.54 | 1.17 | 27.67 | 1.17 | 27.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 23.00 | 17.74 | 3.83 | 17.97 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10.83 | 18.47 | 1.33 | 16.14 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5.67 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 2.67 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.22 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.17 | 27.41 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.72 | 0.67 | 27.72 |
October | 2.50 | 20.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.83 | 19.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.67 | 19.38 | 0.83 | 20.21 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 63.50 | 18.81 | 6.00 | 17.87 | 1.00 | 27.59 | 1.00 | 27.59 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 23.00 | 20.24 | 3.83 | 20.21 | 0.67 | 27.72 | 0.67 | 27.72 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.50 | 17.21 | 3.00 | 16.35 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12.17 | 17.69 | 2.17 | 15.26 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5.33 | 19.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3.17 | 20.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.33 | 20.17 | 0.00 | 0.00 | 1.67 | 28.04 | 0.83 | 28.12 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.39 | 0.17 | 27.29 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 28.38 | 1.33 | 28.29 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 28.00 | 0.67 | 27.98 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.54 | 0.33 | 27.53 |
October | 2.17 | 20.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6.00 | 19.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11.50 | 18.63 | 0.33 | 15.02 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.17 | 18.33 | 5.50 | 15.84 | 6.67 | 28.09 | 3.33 | 28.06 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.50 | 20.17 | 3.00 | 16.35 | 2.83 | 28.38 | 1.33 | 28.29 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 19.47 | 10.00 | 19.46 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 12.17 | 19.76 | 2.83 | 19.77 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 3.67 | 20.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1.00 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.33 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 9.17 | 19.97 | 2.00 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 52.83 | 19.71 | 14.83 | 19.59 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 25.50 | 20.34 | 10.00 | 20.01 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.17 | 19.71 | 1.50 | 19.82 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4.17 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.50 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.17 | 20.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.17 | 20.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.00 | 19.97 | 1.50 | 19.82 | 0.17 | 27.28 | 0.17 | 27.28 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 9.17 | 20.31 | 1.50 | 19.82 | 0.17 | 27.28 | 0.17 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 92.33 | 17.78 | 84.17 | 17.59 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 63.50 | 18.00 | 60.67 | 17.91 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 55.33 | 18.45 | 54.33 | 18.42 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 34.00 | 18.56 | 33.50 | 18.54 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24.50 | 19.25 | 24.50 | 19.25 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 12.00 | 19.82 | 12.00 | 19.82 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.33 | 20.34 | 0.33 | 20.34 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 2.17 | 20.27 | 2.17 | 20.27 | 1.00 | 24.59 | 1.00 | 24.59 |
September | 9.17 | 19.76 | 9.17 | 19.76 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 29.83 | 19.23 | 29.83 | 19.23 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 60.83 | 18.43 | 60.17 | 18.41 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 74.00 | 17.74 | 70.67 | 17.63 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 458.00 | 18.31 | 441.50 | 18.25 | 1.00 | 24.59 | 1.00 | 24.59 |
Minimum of Months | 0.33 | 17.74 | 0.33 | 17.59 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 92.33 | 20.34 | 84.17 | 20.34 | 1.00 | 24.59 | 1.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 7.00 | 19.68 | 0.83 | 19.88 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.83 | 20.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.17 | 20.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.50 | 20.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.76 | 0.33 | 27.41 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.17 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1.00 | 20.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 3.83 | 20.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 18.33 | 19.99 | 0.83 | 19.88 | 2.00 | 27.68 | 0.50 | 27.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.00 | 20.32 | 0.83 | 19.88 | 1.50 | 27.76 | 0.33 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 20.00 | 19.29 | 6.00 | 19.43 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 9.33 | 19.73 | 2.17 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.33 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.83 | 20.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 3.83 | 20.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 10.50 | 19.85 | 2.17 | 19.96 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.17 | 19.63 | 10.33 | 19.66 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.00 | 20.39 | 6.00 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 18.54 | 0.33 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.83 | 19.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.50 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.68 | 1.33 | 27.68 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.80 | 0.67 | 27.80 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.67 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.33 | 20.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 23.17 | 19.51 | 0.33 | 20.03 | 2.00 | 27.72 | 2.00 | 27.72 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 20.38 | 0.33 | 20.03 | 1.33 | 27.80 | 1.33 | 27.80 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.83 | 18.97 | 0.50 | 19.64 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.17 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 1.33 | 20.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.17 | 27.28 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.67 | 27.64 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
November | 2.17 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.17 | 20.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 20.33 | 19.62 | 0.50 | 19.64 | 1.00 | 27.52 | 1.00 | 27.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.83 | 20.33 | 0.50 | 19.64 | 0.67 | 27.64 | 0.67 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.67 | 18.53 | 0.33 | 20.10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3.67 | 20.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2.00 | 20.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.67 | 20.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.81 | 0.83 | 27.72 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 28.27 | 1.00 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.91 | 0.50 | 27.88 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.67 | 0.17 | 27.67 |
October | 0.50 | 20.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.17 | 20.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 4.33 | 20.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22.00 | 19.49 | 0.33 | 20.10 | 5.33 | 28.02 | 2.50 | 27.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 8.67 | 20.38 | 0.33 | 20.10 | 2.50 | 28.27 | 1.00 | 28.22 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 494.00 | 22.41 | 34.17 | 19.13 | 34.17 | 19.13 |
February | 418.83 | 22.93 | 0.50 | 21.00 | 0.50 | 21.00 |
March | 396.00 | 23.22 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 294.50 | 23.26 | 36.17 | 24.64 | 0.00 | 0.00 |
May | 178.50 | 23.15 | 80.00 | 24.49 | 0.00 | 0.00 |
June | 125.50 | 23.17 | 169.17 | 24.63 | 0.00 | 0.00 |
July | 70.17 | 23.21 | 277.50 | 24.56 | 0.00 | 0.00 |
August | 55.83 | 23.20 | 345.00 | 24.35 | 0.00 | 0.00 |
September | 102.33 | 23.10 | 238.17 | 24.56 | 0.00 | 0.00 |
October | 232.00 | 23.16 | 43.67 | 24.97 | 0.00 | 0.00 |
November | 353.83 | 23.17 | 8.83 | 24.43 | 0.00 | 0.00 |
December | 471.33 | 22.93 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3192.83 | 23.00 | 1233.17 | 24.37 | 34.67 | 19.16 |
Minimum of Months | 55.83 | 22.41 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 494.00 | 23.26 | 345.00 | 24.97 | 34.17 | 21.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.30 | 107.00 | 20.03 | 107.00 | 20.03 |
February | 454.00 | 21.81 | 40.83 | 20.36 | 40.83 | 20.36 |
March | 513.50 | 22.47 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 411.67 | 22.78 | 12.50 | 24.22 | 0.00 | 0.00 |
May | 307.00 | 23.14 | 29.33 | 24.45 | 0.00 | 0.00 |
June | 188.00 | 23.20 | 77.50 | 24.40 | 0.00 | 0.00 |
July | 141.83 | 23.26 | 205.50 | 24.36 | 0.00 | 0.00 |
August | 110.67 | 23.16 | 256.83 | 24.24 | 0.00 | 0.00 |
September | 210.50 | 23.14 | 120.33 | 24.34 | 0.00 | 0.00 |
October | 428.50 | 22.79 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 488.00 | 22.20 | 0.17 | 20.65 | 0.17 | 20.65 |
December | 497.00 | 21.68 | 26.00 | 20.43 | 26.00 | 20.43 |
Annual Sum or Average | 4252.67 | 22.36 | 876.00 | 23.50 | 174.00 | 20.17 |
Minimum of Months | 110.67 | 21.30 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 513.50 | 23.26 | 256.83 | 24.45 | 107.00 | 20.65 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.69 | 216.67 | 19.78 | 216.67 | 19.78 |
February | 454.00 | 21.14 | 134.33 | 20.02 | 134.33 | 20.02 |
March | 514.00 | 21.83 | 43.50 | 20.39 | 43.50 | 20.39 |
April | 431.33 | 22.33 | 15.50 | 23.08 | 4.17 | 20.59 |
May | 346.17 | 22.79 | 31.00 | 24.19 | 0.00 | 0.00 |
June | 228.33 | 23.09 | 86.00 | 24.34 | 0.00 | 0.00 |
July | 155.83 | 23.15 | 194.50 | 24.27 | 0.00 | 0.00 |
August | 166.00 | 23.08 | 228.50 | 24.16 | 0.00 | 0.00 |
September | 300.50 | 22.87 | 77.67 | 24.15 | 0.00 | 0.00 |
October | 474.17 | 22.14 | 11.17 | 20.51 | 11.17 | 20.51 |
November | 489.00 | 21.42 | 74.83 | 20.23 | 74.83 | 20.23 |
December | 497.00 | 20.96 | 167.67 | 20.11 | 167.67 | 20.11 |
Annual Sum or Average | 4558.33 | 21.87 | 1281.33 | 22.08 | 652.33 | 20.02 |
Minimum of Months | 155.83 | 20.69 | 11.17 | 19.78 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 23.15 | 228.50 | 24.34 | 216.67 | 20.59 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.01 | 379.67 | 19.69 | 379.67 | 19.69 |
February | 454.00 | 20.30 | 265.33 | 19.72 | 265.33 | 19.72 |
March | 514.00 | 20.91 | 178.67 | 20.12 | 178.67 | 20.12 |
April | 460.50 | 21.56 | 76.17 | 20.73 | 66.33 | 20.25 |
May | 391.67 | 22.06 | 50.17 | 23.05 | 13.67 | 20.18 |
June | 295.17 | 22.52 | 78.50 | 24.19 | 0.00 | 0.00 |
July | 221.17 | 22.68 | 180.83 | 24.13 | 0.00 | 0.00 |
August | 229.00 | 22.55 | 201.33 | 24.08 | 0.00 | 0.00 |
September | 375.83 | 22.19 | 56.50 | 24.06 | 0.00 | 0.00 |
October | 497.67 | 21.26 | 76.00 | 19.91 | 76.00 | 19.91 |
November | 489.00 | 20.52 | 222.17 | 19.84 | 222.17 | 19.84 |
December | 497.00 | 20.17 | 363.83 | 19.86 | 363.83 | 19.86 |
Annual Sum or Average | 4927.00 | 21.19 | 2129.17 | 20.97 | 1565.67 | 19.84 |
Minimum of Months | 221.17 | 20.01 | 50.17 | 19.69 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 22.68 | 379.67 | 24.19 | 379.67 | 20.25 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.05 | 375.50 | 19.73 | 375.50 | 19.73 |
February | 454.00 | 20.33 | 256.00 | 19.81 | 256.00 | 19.81 |
March | 513.50 | 20.81 | 150.17 | 19.99 | 150.17 | 19.99 |
April | 444.33 | 21.45 | 68.83 | 21.10 | 51.50 | 20.15 |
May | 403.83 | 21.75 | 80.00 | 23.63 | 13.50 | 20.15 |
June | 296.17 | 22.09 | 145.67 | 24.34 | 0.17 | 25.67 |
July | 241.67 | 22.25 | 207.67 | 24.24 | 4.83 | 26.20 |
August | 256.00 | 22.18 | 201.00 | 24.14 | 3.83 | 26.32 |
September | 367.50 | 21.78 | 85.50 | 24.24 | 0.33 | 25.58 |
October | 494.67 | 21.15 | 69.50 | 20.01 | 68.00 | 19.93 |
November | 489.00 | 20.49 | 223.00 | 19.88 | 223.00 | 19.88 |
December | 497.00 | 20.18 | 353.00 | 19.85 | 353.00 | 19.85 |
Annual Sum or Average | 4959.67 | 21.05 | 2215.83 | 21.28 | 1499.83 | 19.89 |
Minimum of Months | 241.67 | 20.05 | 68.83 | 19.73 | 0.17 | 19.73 |
Maximum of Months | 513.50 | 22.25 | 375.50 | 24.34 | 375.50 | 26.32 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 497.83 | 20.25 | 320.67 | 19.73 | 319.17 | 19.71 |
February | 424.83 | 20.68 | 211.17 | 20.14 | 201.83 | 19.96 |
March | 466.83 | 21.03 | 154.17 | 20.55 | 134.33 | 20.04 |
April | 403.33 | 21.41 | 101.67 | 21.88 | 60.83 | 20.27 |
May | 396.00 | 21.70 | 73.00 | 23.52 | 15.83 | 20.48 |
June | 356.17 | 22.06 | 81.50 | 24.39 | 0.50 | 25.99 |
July | 277.33 | 22.20 | 165.33 | 24.25 | 0.67 | 25.68 |
August | 271.67 | 22.08 | 188.50 | 24.17 | 1.50 | 26.06 |
September | 323.50 | 21.82 | 130.33 | 24.25 | 2.33 | 26.36 |
October | 415.50 | 21.23 | 112.33 | 22.46 | 47.50 | 19.96 |
November | 464.83 | 20.70 | 192.67 | 20.26 | 178.67 | 19.93 |
December | 481.83 | 20.43 | 294.83 | 19.86 | 293.33 | 19.84 |
Annual Sum or Average | 4779.67 | 21.19 | 2026.17 | 21.56 | 1256.50 | 19.92 |
Minimum of Months | 271.67 | 20.25 | 73.00 | 19.73 | 0.50 | 19.71 |
Maximum of Months | 497.83 | 22.20 | 320.67 | 24.39 | 319.17 | 26.36 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.06 | 386.00 | 19.78 | 386.00 | 19.78 |
February | 453.00 | 20.37 | 261.83 | 19.85 | 261.83 | 19.85 |
March | 504.33 | 20.79 | 173.17 | 20.20 | 168.33 | 20.09 |
April | 438.00 | 21.20 | 98.83 | 21.51 | 68.50 | 20.23 |
May | 422.83 | 21.59 | 77.50 | 23.74 | 18.00 | 21.63 |
June | 368.67 | 21.85 | 81.17 | 24.35 | 1.50 | 25.87 |
July | 286.33 | 22.12 | 163.50 | 24.31 | 7.00 | 26.62 |
August | 319.67 | 21.93 | 146.50 | 24.19 | 3.83 | 26.36 |
September | 388.83 | 21.66 | 77.83 | 24.34 | 2.17 | 26.08 |
October | 481.33 | 21.02 | 79.50 | 20.48 | 69.50 | 19.94 |
November | 489.00 | 20.53 | 222.67 | 19.91 | 222.67 | 19.91 |
December | 497.00 | 20.20 | 361.67 | 19.89 | 361.67 | 19.89 |
Annual Sum or Average | 5151.00 | 21.01 | 2130.17 | 21.10 | 1571.00 | 19.98 |
Minimum of Months | 286.33 | 20.06 | 77.50 | 19.78 | 1.50 | 19.78 |
Maximum of Months | 504.33 | 22.12 | 386.00 | 24.35 | 386.00 | 26.62 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 357.67 | 20.01 | 357.67 | 20.01 |
February | 454.00 | 20.57 | 244.00 | 20.11 | 244.00 | 20.11 |
March | 514.00 | 21.04 | 151.67 | 20.47 | 151.67 | 20.47 |
April | 477.00 | 21.56 | 46.33 | 20.56 | 46.33 | 20.56 |
May | 475.83 | 22.31 | 4.00 | 24.00 | 0.00 | 0.00 |
June | 373.33 | 22.86 | 21.33 | 24.16 | 0.00 | 0.00 |
July | 246.50 | 23.09 | 101.83 | 24.07 | 0.00 | 0.00 |
August | 212.00 | 22.98 | 168.67 | 24.07 | 0.00 | 0.00 |
September | 366.67 | 22.71 | 39.33 | 24.01 | 0.00 | 0.00 |
October | 499.83 | 21.85 | 8.17 | 20.42 | 8.17 | 20.42 |
November | 489.00 | 21.10 | 113.67 | 20.32 | 113.67 | 20.32 |
December | 497.00 | 20.59 | 284.50 | 20.26 | 284.50 | 20.26 |
Annual Sum or Average | 5107.17 | 21.57 | 1541.17 | 21.04 | 1206.00 | 20.20 |
Minimum of Months | 212.00 | 20.30 | 4.00 | 20.01 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 23.09 | 357.67 | 24.16 | 357.67 | 20.56 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.32 | 358.00 | 20.05 | 358.00 | 20.05 |
February | 454.00 | 20.59 | 237.33 | 20.24 | 237.33 | 20.24 |
March | 514.00 | 20.94 | 112.17 | 20.36 | 112.17 | 20.36 |
April | 468.00 | 21.56 | 37.67 | 21.28 | 28.83 | 20.45 |
May | 446.67 | 21.87 | 31.50 | 24.78 | 0.00 | 0.00 |
June | 313.00 | 22.30 | 94.67 | 24.45 | 0.00 | 0.00 |
July | 239.83 | 22.43 | 149.83 | 24.32 | 0.00 | 0.00 |
August | 222.83 | 22.45 | 214.50 | 24.24 | 0.83 | 25.75 |
September | 357.50 | 22.09 | 84.17 | 24.28 | 0.00 | 0.00 |
October | 491.33 | 21.54 | 11.17 | 20.52 | 10.17 | 20.17 |
November | 489.00 | 20.90 | 114.50 | 20.31 | 114.50 | 20.31 |
December | 497.00 | 20.57 | 286.00 | 20.26 | 286.00 | 20.26 |
Annual Sum or Average | 4995.17 | 21.31 | 1731.50 | 21.60 | 1147.83 | 20.21 |
Minimum of Months | 222.83 | 20.32 | 11.17 | 20.05 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 22.45 | 358.00 | 24.78 | 358.00 | 25.75 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.94 | 353.50 | 19.48 | 353.50 | 19.48 |
February | 451.33 | 20.51 | 200.50 | 19.63 | 200.50 | 19.63 |
March | 505.00 | 20.86 | 121.50 | 19.61 | 121.50 | 19.61 |
April | 458.83 | 21.21 | 68.50 | 20.51 | 54.50 | 19.52 |
May | 477.83 | 21.51 | 28.83 | 22.06 | 13.50 | 18.96 |
June | 441.33 | 21.88 | 23.83 | 24.01 | 3.00 | 19.50 |
July | 338.17 | 22.33 | 86.83 | 24.31 | 0.00 | 0.00 |
August | 268.17 | 22.22 | 179.50 | 24.25 | 0.17 | 25.82 |
September | 303.83 | 21.89 | 132.50 | 24.30 | 2.67 | 20.68 |
October | 418.17 | 21.40 | 71.50 | 23.27 | 17.83 | 18.99 |
November | 471.50 | 20.71 | 142.67 | 20.08 | 129.67 | 19.59 |
December | 490.67 | 20.29 | 286.67 | 19.69 | 284.83 | 19.65 |
Annual Sum or Average | 5126.83 | 21.12 | 1696.33 | 21.03 | 1181.67 | 19.56 |
Minimum of Months | 268.17 | 19.94 | 23.83 | 19.48 | 0.00 | 0.00 |
Maximum of Months | 505.00 | 22.33 | 353.50 | 24.31 | 353.50 | 25.82 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.33 | 371.17 | 20.09 | 371.17 | 20.09 |
February | 454.00 | 20.60 | 243.00 | 20.21 | 243.00 | 20.21 |
March | 512.00 | 20.94 | 133.83 | 20.46 | 133.83 | 20.46 |
April | 465.17 | 21.33 | 49.67 | 21.22 | 39.67 | 20.46 |
May | 452.00 | 21.74 | 33.00 | 24.63 | 0.33 | 25.92 |
June | 403.67 | 22.04 | 57.00 | 24.37 | 0.00 | 0.00 |
July | 265.33 | 22.42 | 155.33 | 24.38 | 1.50 | 25.89 |
August | 289.00 | 22.29 | 149.33 | 24.26 | 0.67 | 25.83 |
September | 374.67 | 22.00 | 69.00 | 24.43 | 0.67 | 26.67 |
October | 486.17 | 21.40 | 14.83 | 22.27 | 7.50 | 20.20 |
November | 489.00 | 20.92 | 119.50 | 20.36 | 119.50 | 20.36 |
December | 497.00 | 20.58 | 294.50 | 20.28 | 294.50 | 20.28 |
Annual Sum or Average | 5190.00 | 21.28 | 1690.17 | 21.41 | 1212.33 | 20.26 |
Minimum of Months | 265.33 | 20.33 | 14.83 | 20.09 | 0.00 | 0.00 |
Maximum of Months | 512.00 | 22.42 | 371.17 | 24.63 | 371.17 | 26.67 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 309.33 | 19.81 | 309.33 | 19.81 |
February | 454.00 | 20.62 | 201.67 | 19.89 | 201.67 | 19.89 |
March | 514.00 | 21.27 | 91.00 | 20.31 | 91.00 | 20.31 |
April | 457.67 | 21.90 | 36.67 | 21.43 | 26.67 | 20.47 |
May | 376.83 | 22.42 | 31.50 | 24.13 | 0.00 | 0.00 |
June | 271.50 | 22.84 | 74.33 | 24.17 | 0.00 | 0.00 |
July | 190.33 | 22.99 | 171.83 | 24.09 | 0.00 | 0.00 |
August | 190.17 | 22.87 | 230.83 | 24.10 | 0.00 | 0.00 |
September | 333.67 | 22.58 | 64.33 | 24.08 | 0.00 | 0.00 |
October | 491.17 | 21.73 | 23.17 | 20.22 | 23.17 | 20.22 |
November | 489.00 | 20.95 | 130.17 | 20.07 | 130.17 | 20.07 |
December | 497.00 | 20.51 | 266.50 | 20.05 | 266.50 | 20.05 |
Annual Sum or Average | 4767.33 | 21.50 | 1631.33 | 21.46 | 1048.50 | 19.99 |
Minimum of Months | 190.17 | 20.28 | 23.17 | 19.81 | 0.00 | 0.00 |
Maximum of Months | 514.00 | 22.99 | 309.33 | 24.17 | 309.33 | 20.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.14 | 288.33 | 19.74 | 288.33 | 19.74 |
February | 385.00 | 20.51 | 183.00 | 19.96 | 183.00 | 19.96 |
March | 432.50 | 20.96 | 79.67 | 20.18 | 79.67 | 20.18 |
April | 380.33 | 21.51 | 37.33 | 21.62 | 24.67 | 20.36 |
May | 360.33 | 21.74 | 37.50 | 24.74 | 0.00 | 0.00 |
June | 282.67 | 22.06 | 89.17 | 24.64 | 0.50 | 25.48 |
July | 241.83 | 22.26 | 128.33 | 24.40 | 5.00 | 26.42 |
August | 244.50 | 22.16 | 146.50 | 24.20 | 3.33 | 26.36 |
September | 323.17 | 21.83 | 59.17 | 24.34 | 0.67 | 25.63 |
October | 416.67 | 21.31 | 26.50 | 20.63 | 23.17 | 20.09 |
November | 417.00 | 20.74 | 129.17 | 20.06 | 129.17 | 20.06 |
December | 422.00 | 20.39 | 253.83 | 19.99 | 253.83 | 19.99 |
Annual Sum or Average | 4333.00 | 21.19 | 1458.50 | 21.40 | 991.33 | 20.01 |
Minimum of Months | 241.83 | 20.14 | 26.50 | 19.74 | 0.00 | 0.00 |
Maximum of Months | 432.50 | 22.26 | 288.33 | 24.74 | 288.33 | 26.42 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.33 | 20.53 | 255.00 | 19.90 | 253.00 | 19.86 |
February | 415.33 | 20.95 | 154.33 | 20.56 | 139.33 | 20.14 |
March | 455.83 | 21.27 | 88.50 | 21.22 | 65.83 | 20.26 |
April | 396.33 | 21.61 | 64.50 | 22.83 | 24.83 | 20.45 |
May | 398.00 | 21.93 | 49.67 | 24.48 | 1.17 | 27.10 |
June | 360.00 | 22.21 | 70.00 | 24.48 | 0.00 | 0.00 |
July | 271.83 | 22.34 | 158.67 | 24.26 | 0.00 | 0.00 |
August | 256.67 | 22.27 | 195.50 | 24.19 | 1.00 | 25.62 |
September | 303.83 | 22.04 | 139.00 | 24.25 | 2.67 | 26.44 |
October | 398.17 | 21.50 | 87.83 | 23.83 | 12.00 | 20.24 |
November | 459.00 | 21.02 | 120.83 | 20.95 | 100.00 | 20.16 |
December | 469.83 | 20.71 | 222.50 | 20.23 | 216.00 | 20.09 |
Annual Sum or Average | 4678.17 | 21.43 | 1606.33 | 22.16 | 815.83 | 20.10 |
Minimum of Months | 256.67 | 20.53 | 49.67 | 19.90 | 0.00 | 0.00 |
Maximum of Months | 493.33 | 22.34 | 255.00 | 24.48 | 253.00 | 27.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.28 | 319.50 | 19.87 | 319.50 | 19.87 |
February | 453.00 | 20.61 | 194.83 | 19.97 | 194.83 | 19.97 |
March | 503.50 | 20.99 | 98.67 | 20.48 | 94.00 | 20.30 |
April | 438.83 | 21.37 | 57.17 | 22.36 | 29.17 | 20.38 |
May | 426.33 | 21.75 | 61.33 | 24.55 | 3.00 | 26.30 |
June | 377.50 | 21.95 | 77.00 | 24.43 | 0.50 | 25.52 |
July | 281.17 | 22.19 | 157.50 | 24.35 | 6.33 | 26.52 |
August | 315.33 | 22.05 | 140.67 | 24.26 | 3.00 | 26.26 |
September | 377.33 | 21.79 | 78.00 | 24.35 | 1.50 | 25.75 |
October | 478.50 | 21.26 | 35.33 | 21.47 | 24.17 | 20.14 |
November | 489.00 | 20.82 | 131.00 | 20.10 | 131.00 | 20.10 |
December | 497.00 | 20.50 | 270.17 | 20.06 | 270.17 | 20.06 |
Annual Sum or Average | 5139.50 | 21.20 | 1621.17 | 21.52 | 1077.17 | 20.11 |
Minimum of Months | 281.17 | 20.28 | 35.33 | 19.87 | 0.50 | 19.87 |
Maximum of Months | 503.50 | 22.19 | 319.50 | 24.55 | 319.50 | 26.52 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.41611 | 28.98519 | -0.1517 | 7.77135 |
February | 454.00000 | 22.99182 | 29.70153 | 0.01467 | 5.94964 |
March | 514.00000 | 23.39536 | 29.21640 | 0.13116 | 5.95453 |
April | 485.00000 | 23.60248 | 32.68223 | 0.21523 | 6.53517 |
May | 508.00000 | 23.83957 | 36.20145 | -0.5956 | 13.19537 |
June | 496.00000 | 23.97888 | 37.86864 | -0.5130 | 11.17488 |
July | 497.00000 | 24.11596 | 41.16528 | -0.4381 | 9.68707 |
August | 514.00000 | 24.05395 | 43.76647 | -0.4220 | 9.33263 |
September | 485.00000 | 24.01196 | 41.93952 | -0.4761 | 10.55056 |
October | 502.00000 | 23.72771 | 35.98346 | 0.26992 | 7.01774 |
November | 489.00000 | 23.42844 | 34.47129 | 0.16188 | 6.23777 |
December | 497.00000 | 22.96484 | 29.48077 | 0.00463 | 5.76200 |
Annual Sum or Average | 5943.00000 | 23.54772 | 35.15804 | -0.1520 | 8.28603 |
Minimum of Months | 454.00000 | 22.41611 | 28.98519 | -0.5956 | 5.76200 |
Maximum of Months | 514.00000 | 24.11596 | 43.76647 | 0.26992 | 13.19537 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.29147 | 31.53459 | -0.4156 | 10.33837 |
February | 454.00000 | 21.79774 | 32.55335 | -0.2696 | 7.69265 |
March | 514.00000 | 22.45660 | 31.93193 | -0.0998 | 5.94471 |
April | 485.00000 | 22.97910 | 35.09172 | 0.05481 | 5.96679 |
May | 508.00000 | 23.51401 | 38.36127 | -0.7373 | 17.44569 |
June | 496.00000 | 23.79213 | 39.74960 | -0.6124 | 13.55748 |
July | 497.00000 | 23.92938 | 43.20632 | -0.5311 | 11.52843 |
August | 514.00000 | 23.89907 | 45.82447 | -0.5114 | 11.13151 |
September | 485.00000 | 23.70811 | 44.24602 | -0.6176 | 13.85073 |
October | 502.00000 | 22.96789 | 38.97404 | 0.07308 | 5.91652 |
November | 489.00000 | 22.19165 | 37.89790 | -0.1376 | 6.20946 |
December | 497.00000 | 21.66663 | 32.51081 | -0.3068 | 7.65625 |
Annual Sum or Average | 5943.00000 | 22.85772 | 37.68921 | -0.3439 | 9.79290 |
Minimum of Months | 454.00000 | 21.29147 | 31.53459 | -0.7373 | 5.91652 |
Maximum of Months | 514.00000 | 23.92938 | 45.82447 | 0.07308 | 17.44569 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.68579 | 32.31441 | -0.5858 | 14.68318 |
February | 454.00000 | 21.13125 | 33.30876 | -0.4501 | 11.40127 |
March | 514.00000 | 21.81604 | 33.04055 | -0.2623 | 7.58333 |
April | 485.00000 | 22.50586 | 35.89305 | -0.0600 | 6.54777 |
May | 508.00000 | 23.18122 | 38.68182 | -0.8461 | 22.03869 |
June | 496.00000 | 23.64943 | 39.55197 | -0.6581 | 15.31107 |
July | 497.00000 | 23.84174 | 42.70164 | -0.5578 | 12.47341 |
August | 514.00000 | 23.75635 | 45.44886 | -0.5613 | 12.64600 |
September | 485.00000 | 23.31867 | 44.82339 | -0.7556 | 18.58347 |
October | 502.00000 | 22.22561 | 40.47957 | -0.1105 | 6.44747 |
November | 489.00000 | 21.41358 | 39.54794 | -0.3412 | 8.53846 |
December | 497.00000 | 20.96339 | 33.43686 | -0.5049 | 11.61900 |
Annual Sum or Average | 5943.00000 | 22.38428 | 38.29778 | -0.4752 | 12.33543 |
Minimum of Months | 454.00000 | 20.68579 | 32.31441 | -0.8461 | 6.44747 |
Maximum of Months | 514.00000 | 23.84174 | 45.44886 | -0.0600 | 22.03869 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.02377 | 33.28352 | -0.7925 | 21.08808 |
February | 454.00000 | 20.31338 | 34.23174 | -0.6777 | 17.46969 |
March | 514.00000 | 20.91067 | 34.80342 | -0.4874 | 11.43971 |
April | 485.00000 | 21.67746 | 37.60482 | -0.2494 | 8.31708 |
May | 508.00000 | 22.49031 | 40.63353 | -1.0507 | 31.26706 |
June | 496.00000 | 23.12577 | 41.36493 | -0.8038 | 21.11511 |
July | 497.00000 | 23.42630 | 44.03321 | -0.6665 | 16.49460 |
August | 514.00000 | 23.33955 | 47.47140 | -0.6718 | 16.80121 |
September | 485.00000 | 22.58208 | 47.46371 | -0.9836 | 28.00630 |
October | 502.00000 | 21.28540 | 42.96303 | -0.3332 | 8.67810 |
November | 489.00000 | 20.53325 | 40.90486 | -0.5765 | 13.76879 |
December | 497.00000 | 20.17997 | 34.93382 | -0.7348 | 18.41849 |
Annual Sum or Average | 5943.00000 | 21.66894 | 40.00882 | -0.6693 | 17.74323 |
Minimum of Months | 454.00000 | 20.02377 | 33.28352 | -1.0507 | 8.31708 |
Maximum of Months | 514.00000 | 23.42630 | 47.47140 | -0.2494 | 31.26706 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.06501 | 32.33233 | -0.7843 | 20.71528 |
February | 454.00000 | 20.34496 | 33.35374 | -0.6589 | 16.43660 |
March | 514.00000 | 20.82004 | 34.05376 | -0.4815 | 11.14305 |
April | 485.00000 | 21.64594 | 36.83086 | -0.2099 | 8.08223 |
May | 508.00000 | 22.21409 | 40.44498 | -1.0667 | 32.63781 |
June | 496.00000 | 22.90086 | 41.05716 | -0.7833 | 21.93148 |
July | 497.00000 | 23.15648 | 44.10036 | -0.6620 | 18.08940 |
August | 514.00000 | 23.04516 | 47.44618 | -0.6658 | 18.18938 |
September | 485.00000 | 22.30662 | 47.24705 | -0.9964 | 29.86103 |
October | 502.00000 | 21.18961 | 42.25973 | -0.3286 | 8.61353 |
November | 489.00000 | 20.50777 | 40.10477 | -0.5792 | 13.66222 |
December | 497.00000 | 20.20472 | 34.02833 | -0.7281 | 18.17255 |
Annual Sum or Average | 5943.00000 | 21.54342 | 39.47639 | -0.6625 | 18.14331 |
Minimum of Months | 454.00000 | 20.06501 | 32.33233 | -1.0667 | 8.08223 |
Maximum of Months | 514.00000 | 23.15648 | 47.44618 | -0.2099 | 32.63781 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29954 | 31.76189 | -0.6978 | 18.43484 |
February | 454.00000 | 20.90437 | 32.23882 | -0.5020 | 13.87065 |
March | 514.00000 | 21.30576 | 33.01857 | -0.3547 | 10.63428 |
April | 485.00000 | 21.84828 | 36.24971 | -0.1699 | 8.66644 |
May | 508.00000 | 22.20832 | 40.30144 | -1.0883 | 33.75776 |
June | 496.00000 | 22.61158 | 41.69187 | -0.9175 | 26.18293 |
July | 497.00000 | 23.00457 | 44.34814 | -0.7430 | 20.41473 |
August | 514.00000 | 22.97962 | 47.49186 | -0.7079 | 19.77942 |
September | 485.00000 | 22.56336 | 46.28049 | -0.8941 | 27.31995 |
October | 502.00000 | 21.73785 | 40.75257 | -0.1801 | 8.85563 |
November | 489.00000 | 20.88146 | 39.05850 | -0.4722 | 12.32057 |
December | 497.00000 | 20.55458 | 33.19343 | -0.6152 | 16.14789 |
Annual Sum or Average | 5943.00000 | 21.74874 | 38.90935 | -0.6133 | 18.07424 |
Minimum of Months | 454.00000 | 20.29954 | 31.76189 | -1.0883 | 8.66644 |
Maximum of Months | 514.00000 | 23.00457 | 47.49186 | -0.1699 | 33.75776 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07768 | 32.13897 | -0.7826 | 20.64128 |
February | 454.00000 | 20.39387 | 33.09073 | -0.6524 | 16.52635 |
March | 514.00000 | 20.85455 | 33.79133 | -0.4822 | 11.53728 |
April | 485.00000 | 21.47409 | 37.05832 | -0.2573 | 8.87484 |
May | 508.00000 | 21.99713 | 40.77845 | -1.1245 | 35.96501 |
June | 496.00000 | 22.39769 | 42.15447 | -0.9422 | 27.87499 |
July | 497.00000 | 22.91006 | 44.55097 | -0.7153 | 21.06333 |
August | 514.00000 | 22.66145 | 48.42771 | -0.7790 | 22.63176 |
September | 485.00000 | 22.12685 | 47.56535 | -1.0407 | 32.16861 |
October | 502.00000 | 21.14101 | 42.20133 | -0.3433 | 8.93542 |
November | 489.00000 | 20.54298 | 39.85046 | -0.5748 | 13.60153 |
December | 497.00000 | 20.21662 | 33.83313 | -0.7268 | 18.18467 |
Annual Sum or Average | 5943.00000 | 21.40797 | 39.66228 | -0.7026 | 19.86758 |
Minimum of Months | 454.00000 | 20.07768 | 32.13897 | -1.1245 | 8.87484 |
Maximum of Months | 514.00000 | 22.91006 | 48.42771 | -0.2573 | 35.96501 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.31130 | 33.82371 | -0.7122 | 17.50951 |
February | 454.00000 | 20.57645 | 34.80765 | -0.6118 | 14.49507 |
March | 514.00000 | 21.03895 | 35.58507 | -0.4640 | 10.16807 |
April | 485.00000 | 21.59084 | 38.69102 | -0.2883 | 7.78260 |
May | 508.00000 | 22.40604 | 41.87807 | -1.1176 | 32.88141 |
June | 496.00000 | 23.13137 | 42.38447 | -0.8491 | 21.61483 |
July | 497.00000 | 23.53945 | 44.49732 | -0.6787 | 15.75161 |
August | 514.00000 | 23.57339 | 47.46285 | -0.6369 | 14.63926 |
September | 485.00000 | 23.01147 | 47.08373 | -0.8637 | 22.20221 |
October | 502.00000 | 21.85241 | 42.53257 | -0.1893 | 6.61196 |
November | 489.00000 | 21.10390 | 40.70601 | -0.4078 | 9.34845 |
December | 497.00000 | 20.59734 | 35.09709 | -0.6048 | 13.40491 |
Annual Sum or Average | 5943.00000 | 21.90510 | 40.41416 | -0.6194 | 15.55952 |
Minimum of Months | 454.00000 | 20.31130 | 33.82371 | -1.1176 | 6.61196 |
Maximum of Months | 514.00000 | 23.57339 | 47.46285 | -0.1893 | 32.88141 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.33207 | 32.48381 | -0.7124 | 17.38310 |
February | 454.00000 | 20.60375 | 33.52003 | -0.5962 | 13.61017 |
March | 514.00000 | 20.94695 | 34.36734 | -0.4583 | 9.88050 |
April | 485.00000 | 21.63083 | 37.30946 | -0.2305 | 7.41209 |
May | 508.00000 | 22.14060 | 41.14113 | -1.1265 | 34.07759 |
June | 496.00000 | 22.95664 | 41.41891 | -0.8080 | 21.55406 |
July | 497.00000 | 23.26085 | 44.16446 | -0.6740 | 17.32137 |
August | 514.00000 | 23.33140 | 46.91220 | -0.6081 | 15.50739 |
September | 485.00000 | 22.59892 | 46.77946 | -0.9102 | 25.56692 |
October | 502.00000 | 21.58820 | 41.78395 | -0.2164 | 6.93288 |
November | 489.00000 | 20.90067 | 39.87326 | -0.4475 | 9.75783 |
December | 497.00000 | 20.58183 | 33.83444 | -0.6109 | 13.53648 |
Annual Sum or Average | 5943.00000 | 21.74874 | 39.50333 | -0.6173 | 16.07606 |
Minimum of Months | 454.00000 | 20.33207 | 32.48381 | -1.1265 | 6.93288 |
Maximum of Months | 514.00000 | 23.33140 | 46.91220 | -0.2164 | 34.07759 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.95640 | 32.32689 | -0.7378 | 18.84887 |
February | 454.00000 | 20.52956 | 32.80462 | -0.5484 | 13.61631 |
March | 514.00000 | 20.90911 | 33.53148 | -0.4203 | 10.34877 |
April | 485.00000 | 21.36343 | 36.99891 | -0.2765 | 8.56873 |
May | 508.00000 | 21.66817 | 41.66952 | -1.2704 | 40.33092 |
June | 496.00000 | 22.11238 | 43.07399 | -1.0970 | 32.19766 |
July | 497.00000 | 22.85742 | 45.27233 | -0.8221 | 21.58633 |
August | 514.00000 | 23.08888 | 48.03202 | -0.6923 | 18.09836 |
September | 485.00000 | 22.72792 | 46.33721 | -0.8302 | 23.74783 |
October | 502.00000 | 21.87694 | 40.35250 | -0.1081 | 7.64686 |
November | 489.00000 | 20.85545 | 38.96990 | -0.4174 | 10.66517 |
December | 497.00000 | 20.35219 | 33.36479 | -0.6058 | 14.91543 |
Annual Sum or Average | 5943.00000 | 21.53268 | 39.43997 | -0.6538 | 18.44065 |
Minimum of Months | 454.00000 | 19.95640 | 32.32689 | -1.2704 | 7.64686 |
Maximum of Months | 514.00000 | 23.08888 | 48.03202 | -0.1081 | 40.33092 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.34068 | 32.26358 | -0.7114 | 17.34667 |
February | 454.00000 | 20.61101 | 33.27937 | -0.5965 | 13.88850 |
March | 514.00000 | 20.95470 | 34.10511 | -0.4633 | 10.16283 |
April | 485.00000 | 21.43614 | 37.52875 | -0.2824 | 8.02233 |
May | 508.00000 | 22.00036 | 41.24434 | -1.1586 | 35.69040 |
June | 496.00000 | 22.41277 | 42.55875 | -0.9785 | 27.87609 |
July | 497.00000 | 23.18677 | 44.11645 | -0.6739 | 17.61955 |
August | 514.00000 | 23.01313 | 47.70837 | -0.7028 | 18.47019 |
September | 485.00000 | 22.46591 | 46.97095 | -0.9389 | 26.72735 |
October | 502.00000 | 21.47415 | 41.83731 | -0.2418 | 7.14247 |
November | 489.00000 | 20.92347 | 39.62296 | -0.4452 | 9.74850 |
December | 497.00000 | 20.59071 | 33.61513 | -0.6100 | 13.56789 |
Annual Sum or Average | 5943.00000 | 21.62583 | 39.61155 | -0.6513 | 17.22940 |
Minimum of Months | 454.00000 | 20.34068 | 32.26358 | -1.1586 | 7.14247 |
Maximum of Months | 514.00000 | 23.18677 | 47.70837 | -0.2418 | 35.69040 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29009 | 33.00601 | -0.6913 | 17.25615 |
February | 454.00000 | 20.62768 | 33.87208 | -0.5684 | 13.93163 |
March | 514.00000 | 21.27328 | 34.34952 | -0.3778 | 8.97022 |
April | 485.00000 | 22.00759 | 37.16955 | -0.1617 | 7.08482 |
May | 508.00000 | 22.80922 | 40.32894 | -0.9458 | 26.18159 |
June | 496.00000 | 23.36998 | 41.27488 | -0.7313 | 17.82642 |
July | 497.00000 | 23.62595 | 44.12483 | -0.6102 | 14.02127 |
August | 514.00000 | 23.58245 | 47.40836 | -0.5971 | 13.85924 |
September | 485.00000 | 23.00938 | 46.79820 | -0.8388 | 21.68596 |
October | 502.00000 | 21.77578 | 42.10050 | -0.1987 | 6.94705 |
November | 489.00000 | 20.95451 | 40.17843 | -0.4420 | 10.16200 |
December | 497.00000 | 20.51993 | 34.39559 | -0.6118 | 13.94105 |
Annual Sum or Average | 5943.00000 | 21.99848 | 39.61983 | -0.5650 | 14.33145 |
Minimum of Months | 454.00000 | 20.29009 | 33.00601 | -0.9458 | 6.94705 |
Maximum of Months | 514.00000 | 23.62595 | 47.40836 | -0.1617 | 26.18159 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.16051 | 31.47668 | -0.7303 | 18.46498 |
February | 385.00000 | 20.51671 | 32.32251 | -0.5933 | 13.99412 |
March | 433.00000 | 20.95754 | 33.28677 | -0.4324 | 9.61392 |
April | 410.00000 | 21.66795 | 36.27348 | -0.1982 | 7.43340 |
May | 430.00000 | 22.13027 | 40.35171 | -1.0897 | 33.09763 |
June | 418.00000 | 22.73911 | 41.48992 | -0.8368 | 23.56436 |
July | 422.00000 | 22.99360 | 44.59439 | -0.7197 | 19.59079 |
August | 433.00000 | 22.92387 | 47.92083 | -0.7065 | 19.11331 |
September | 410.00000 | 22.28456 | 47.21358 | -0.9898 | 29.03139 |
October | 427.00000 | 21.36559 | 41.50328 | -0.2687 | 7.52278 |
November | 417.00000 | 20.74850 | 38.94911 | -0.4929 | 10.94188 |
December | 422.00000 | 20.40601 | 32.94891 | -0.6459 | 14.89041 |
Annual Sum or Average | 5034.00000 | 21.58115 | 39.06601 | -0.6427 | 17.29632 |
Minimum of Months | 385.00000 | 20.16051 | 31.47668 | -1.0897 | 7.43340 |
Maximum of Months | 433.00000 | 22.99360 | 47.92083 | -0.1982 | 33.09763 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.60275 | 31.24977 | -0.5926 | 15.01037 |
February | 454.00000 | 21.22914 | 31.71313 | -0.3935 | 11.26370 |
March | 514.00000 | 21.57414 | 32.51353 | -0.2651 | 8.77189 |
April | 485.00000 | 22.05429 | 35.87111 | -0.1067 | 7.69382 |
May | 508.00000 | 22.37294 | 40.17225 | -1.0245 | 30.33289 |
June | 496.00000 | 22.70961 | 41.85145 | -0.8841 | 24.22221 |
July | 497.00000 | 23.09826 | 44.65356 | -0.7150 | 18.69224 |
August | 514.00000 | 23.13111 | 47.64004 | -0.6574 | 17.40555 |
September | 485.00000 | 22.78941 | 45.99099 | -0.8034 | 23.20189 |
October | 502.00000 | 22.06209 | 40.06088 | -0.0785 | 7.87211 |
November | 489.00000 | 21.23400 | 38.31780 | -0.3532 | 9.67858 |
December | 497.00000 | 20.91578 | 32.42740 | -0.4923 | 12.47564 |
Annual Sum or Average | 5943.00000 | 21.98743 | 38.58493 | -0.5322 | 15.59598 |
Minimum of Months | 454.00000 | 20.60275 | 31.24977 | -1.0245 | 7.69382 |
Maximum of Months | 514.00000 | 23.13111 | 47.64004 | -0.0785 | 30.33289 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29183 | 31.72978 | -0.6943 | 17.24667 |
February | 454.00000 | 20.62496 | 32.67500 | -0.5614 | 13.50945 |
March | 514.00000 | 21.05270 | 33.39408 | -0.4053 | 9.46021 |
April | 485.00000 | 21.62404 | 36.78309 | -0.2042 | 7.79681 |
May | 508.00000 | 22.12274 | 40.73017 | -1.0706 | 32.88998 |
June | 496.00000 | 22.45734 | 42.39256 | -0.9182 | 26.34123 |
July | 497.00000 | 22.97089 | 44.93224 | -0.6954 | 19.66035 |
August | 514.00000 | 22.75641 | 48.73838 | -0.7428 | 20.71866 |
September | 485.00000 | 22.28854 | 47.45709 | -0.9666 | 28.56706 |
October | 502.00000 | 21.38291 | 41.68484 | -0.2565 | 7.51393 |
November | 489.00000 | 20.82701 | 39.21154 | -0.4684 | 10.46315 |
December | 497.00000 | 20.51000 | 33.15303 | -0.6163 | 14.11408 |
Annual Sum or Average | 5943.00000 | 21.58363 | 39.45173 | -0.6344 | 17.39648 |
Minimum of Months | 454.00000 | 20.29183 | 31.72978 | -1.0706 | 7.51393 |
Maximum of Months | 514.00000 | 22.97089 | 48.73838 | -0.2042 | 32.88998 |
Report: DXReportMonthly
For: PACU_VAV_BOT_COOLC DXCOIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 94095934.85 | 27975401.07 | 6.67 | 68298663.41 | 25797271.44 | 0.00 | 0.26 | 11-JAN-14:00 | 0.00 | 01-JAN-00:03 | 7747.39 | 11-JAN-14:00 | 5752.69 | 11-JAN-14:00 | 1994.71 | 11-JAN-14:00 | 2271.18 | 11-JAN-14:00 | 0.00 |
February | 0.111243E+10 | 0.318161E+09 | 38.78 | 0.815184E+09 | 0.297244E+09 | 0.00 | 0.62 | 27-FEB-16:10 | 0.00 | 01-FEB-00:10 | 20369.42 | 27-FEB-16:10 | 19625.78 | 27-FEB-14:55 | 3959.22 | 25-FEB-12:00 | 5449.83 | 27-FEB-16:10 | 0.00 |
March | 0.182161E+10 | 0.519643E+09 | 67.00 | 0.145296E+10 | 0.368656E+09 | 0.00 | 0.62 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 20490.39 | 18-MAR-16:00 | 20490.39 | 18-MAR-16:00 | 4783.03 | 09-MAR-14:00 | 5477.62 | 18-MAR-16:00 | 0.00 |
April | 0.682626E+10 | 0.183428E+10 | 138.03 | 0.617126E+10 | 0.655004E+09 | 0.00 | 1.00 | 26-APR-14:00 | 0.00 | 01-APR-00:10 | 54749.15 | 27-APR-16:00 | 54749.15 | 27-APR-16:00 | 10305.56 | 28-APR-13:00 | 14286.16 | 27-APR-16:00 | 0.00 |
May | 0.146092E+11 | 0.387083E+10 | 265.77 | 0.120946E+11 | 0.251453E+10 | 0.00 | 1.00 | 04-MAY-13:40 | 0.00 | 01-MAY-00:10 | 52749.58 | 05-MAY-16:00 | 46376.62 | 05-MAY-16:00 | 10999.52 | 05-MAY-17:00 | 13060.78 | 05-MAY-16:00 | 0.00 |
June | 0.246482E+11 | 0.646466E+10 | 362.53 | 0.211825E+11 | 0.346568E+10 | 0.00 | 1.00 | 09-JUN-15:10 | 0.00 | 01-JUN-00:10 | 57093.61 | 28-JUN-16:00 | 57093.61 | 28-JUN-16:00 | 16474.56 | 12-JUN-04:03 | 14480.84 | 28-JUN-16:00 | 0.00 |
July | 0.401045E+11 | 0.102582E+11 | 409.89 | 0.327261E+11 | 0.737834E+10 | 0.00 | 1.00 | 06-JUL-15:10 | 0.00 | 01-JUL-00:10 | 78221.43 | 31-JUL-16:10 | 69060.20 | 24-JUL-15:10 | 17190.96 | 11-JUL-15:20 | 21111.40 | 31-JUL-16:10 | 0.00 |
August | 0.532474E+11 | 0.136571E+11 | 436.89 | 0.428691E+11 | 0.103783E+11 | 0.00 | 1.00 | 04-AUG-12:35 | 0.00 | 01-AUG-00:10 | 84939.70 | 10-AUG-16:05 | 82294.58 | 10-AUG-17:00 | 30531.57 | 25-AUG-04:03 | 24543.28 | 10-AUG-16:05 | 0.00 |
September | 0.254376E+11 | 0.656793E+10 | 340.33 | 0.188627E+11 | 0.657483E+10 | 0.00 | 1.00 | 08-SEP-14:20 | 0.00 | 01-SEP-00:10 | 71391.56 | 14-SEP-13:00 | 56935.89 | 14-SEP-16:00 | 23013.79 | 14-SEP-12:40 | 17234.83 | 14-SEP-13:00 | 0.00 |
October | 0.552696E+10 | 0.153905E+10 | 162.10 | 0.468122E+10 | 0.845737E+09 | 0.00 | 1.00 | 04-OCT-14:50 | 0.00 | 01-OCT-00:10 | 39067.17 | 04-OCT-15:10 | 39067.17 | 04-OCT-15:10 | 5829.99 | 08-OCT-12:53 | 9380.17 | 04-OCT-15:10 | 0.00 |
November | 0.158660E+10 | 0.437681E+09 | 53.50 | 0.965428E+09 | 0.621173E+09 | 0.00 | 0.89 | 04-NOV-13:30 | 0.00 | 01-NOV-00:10 | 31812.70 | 04-NOV-13:30 | 23697.89 | 04-NOV-14:00 | 9970.60 | 04-NOV-16:00 | 7886.97 | 04-NOV-13:30 | 0.00 |
December | 9782727.80 | 2988829.16 | 1.33 | 8119695.39 | 1663032.42 | 0.00 | 0.12 | 14-DEC-12:00 | 0.00 | 01-DEC-00:10 | 3468.04 | 14-DEC-12:00 | 2906.42 | 14-DEC-12:00 | 561.62 | 14-DEC-12:00 | 1050.76 | 14-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.175025E+12 | 0.454986E+11 | 2282.81 | 0.141898E+12 | 0.331269E+11 | ||||||||||||||
Minimum of Months | 9782727.80 | 2988829.16 | 1.33 | 8119695.39 | 1663032.42 | 0.00 | 0.12 | 0.00 | 3468.04 | 2906.42 | 561.62 | 1050.76 | 0.00 | ||||||
Maximum of Months | 0.532474E+11 | 0.136571E+11 | 436.89 | 0.428691E+11 | 0.103783E+11 | 0.00 | 1.00 | 0.00 | 84939.70 | 82294.58 | 30531.57 | 24543.28 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_MID_COOLC DXCOIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 82745291.73 | 24530281.35 | 6.83 | 61908618.01 | 20836673.72 | 0.00 | 0.27 | 11-JAN-15:00 | 0.00 | 01-JAN-00:03 | 6469.10 | 11-JAN-15:00 | 4926.58 | 11-JAN-14:00 | 1542.66 | 11-JAN-15:00 | 1891.89 | 11-JAN-15:00 | 0.00 |
February | 0.959865E+09 | 0.272186E+09 | 38.67 | 0.735404E+09 | 0.224461E+09 | 0.00 | 0.73 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 20059.35 | 27-FEB-15:00 | 20059.35 | 27-FEB-15:00 | 3287.05 | 25-FEB-12:00 | 5199.98 | 27-FEB-15:00 | 0.00 |
March | 0.153677E+10 | 0.436598E+09 | 67.67 | 0.126396E+10 | 0.272809E+09 | 0.00 | 0.68 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 18503.82 | 18-MAR-14:00 | 18503.82 | 18-MAR-14:00 | 3663.87 | 09-MAR-14:00 | 4859.93 | 18-MAR-14:00 | 0.00 |
April | 0.573644E+10 | 0.153218E+10 | 140.06 | 0.528741E+10 | 0.449031E+09 | 0.00 | 1.00 | 01-APR-14:50 | 0.00 | 01-APR-00:10 | 49232.35 | 27-APR-15:00 | 49232.35 | 27-APR-15:00 | 7967.38 | 28-APR-13:00 | 12840.62 | 27-APR-15:00 | 0.00 |
May | 0.122278E+11 | 0.323032E+10 | 271.83 | 0.104031E+11 | 0.182470E+10 | 0.00 | 1.00 | 04-MAY-13:00 | 0.00 | 01-MAY-00:10 | 42776.90 | 05-MAY-16:00 | 40561.02 | 15-MAY-16:00 | 7692.65 | 06-MAY-17:00 | 10594.40 | 05-MAY-16:00 | 0.00 |
June | 0.202835E+11 | 0.531271E+10 | 366.86 | 0.178111E+11 | 0.247248E+10 | 0.00 | 1.00 | 09-JUN-14:30 | 0.00 | 01-JUN-00:10 | 50039.67 | 28-JUN-16:00 | 50039.67 | 28-JUN-16:00 | 10884.81 | 12-JUN-15:00 | 12688.81 | 28-JUN-16:00 | 0.00 |
July | 0.331874E+11 | 0.848258E+10 | 415.24 | 0.279048E+11 | 0.528258E+10 | 0.00 | 1.00 | 06-JUL-15:00 | 0.00 | 01-JUL-00:10 | 68752.20 | 31-JUL-16:00 | 61175.33 | 24-JUL-15:00 | 13836.93 | 31-JUL-10:20 | 18554.56 | 31-JUL-16:00 | 0.00 |
August | 0.436408E+11 | 0.111971E+11 | 440.86 | 0.360353E+11 | 0.760548E+10 | 0.00 | 1.00 | 04-AUG-12:50 | 0.00 | 01-AUG-00:10 | 75889.74 | 29-AUG-14:40 | 68959.72 | 10-AUG-16:00 | 22189.27 | 30-AUG-13:00 | 21287.93 | 29-AUG-14:50 | 0.00 |
September | 0.207004E+11 | 0.534122E+10 | 340.99 | 0.158495E+11 | 0.485093E+10 | 0.00 | 1.00 | 08-SEP-13:40 | 0.00 | 01-SEP-00:10 | 58852.22 | 14-SEP-13:00 | 46935.02 | 14-SEP-15:50 | 18562.36 | 14-SEP-12:50 | 14206.48 | 14-SEP-13:00 | 0.00 |
October | 0.452357E+10 | 0.125658E+10 | 161.74 | 0.389943E+10 | 0.624148E+09 | 0.00 | 1.00 | 04-OCT-13:20 | 0.00 | 01-OCT-00:10 | 33577.77 | 04-OCT-15:00 | 33577.77 | 04-OCT-15:00 | 4448.22 | 08-OCT-12:53 | 8061.17 | 04-OCT-15:00 | 0.00 |
November | 0.134612E+10 | 0.367095E+09 | 53.67 | 0.852388E+09 | 0.493729E+09 | 0.00 | 0.96 | 04-NOV-13:00 | 0.00 | 01-NOV-00:10 | 28187.07 | 04-NOV-13:00 | 22687.79 | 04-NOV-14:00 | 7692.67 | 04-NOV-16:00 | 6842.11 | 04-NOV-13:00 | 0.00 |
December | 9946435.13 | 3043232.73 | 3.00 | 8707120.15 | 1239314.98 | 0.00 | 0.13 | 14-DEC-12:00 | 0.00 | 01-DEC-00:10 | 2949.08 | 14-DEC-12:00 | 2548.89 | 14-DEC-12:00 | 400.19 | 14-DEC-12:00 | 892.07 | 14-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.144235E+12 | 0.374562E+11 | 2307.42 | 0.120113E+12 | 0.241224E+11 | ||||||||||||||
Minimum of Months | 9946435.13 | 3043232.73 | 3.00 | 8707120.15 | 1239314.98 | 0.00 | 0.13 | 0.00 | 2949.08 | 2548.89 | 400.19 | 892.07 | 0.00 | ||||||
Maximum of Months | 0.436408E+11 | 0.111971E+11 | 440.86 | 0.360353E+11 | 0.760548E+10 | 0.00 | 1.00 | 0.00 | 75889.74 | 68959.72 | 22189.27 | 21287.93 | 0.00 |
Report: DXReportMonthly
For: PACU_VAV_TOP_COOLC DXCOIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRIC ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRIC ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM}[] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum}[W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum}[W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRIC POWER {Maximum}[W] | COOLING COIL ELECTRIC POWER {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRIC POWER [] | |
January | 82813312.19 | 24646745.35 | 6.67 | 59864302.36 | 22949009.83 | 0.00 | 0.24 | 11-JAN-15:00 | 0.00 | 01-JAN-00:03 | 6609.15 | 11-JAN-15:00 | 4845.11 | 11-JAN-14:00 | 1764.14 | 11-JAN-15:00 | 1943.57 | 11-JAN-15:00 | 0.00 |
February | 0.986718E+09 | 0.282107E+09 | 38.67 | 0.730146E+09 | 0.256572E+09 | 0.00 | 0.66 | 27-FEB-14:55 | 0.00 | 01-FEB-00:10 | 19754.74 | 27-FEB-14:55 | 19754.74 | 27-FEB-14:55 | 3520.25 | 25-FEB-12:00 | 5229.07 | 27-FEB-14:55 | 0.00 |
March | 0.155689E+10 | 0.445653E+09 | 66.00 | 0.123620E+10 | 0.320690E+09 | 0.00 | 0.61 | 18-MAR-14:00 | 0.00 | 01-MAR-00:10 | 18196.22 | 18-MAR-14:00 | 18196.22 | 18-MAR-14:00 | 3891.46 | 09-MAR-13:50 | 4874.25 | 18-MAR-14:00 | 0.00 |
April | 0.603417E+10 | 0.162137E+10 | 138.50 | 0.544811E+10 | 0.586062E+09 | 0.00 | 1.00 | 26-APR-13:40 | 0.00 | 01-APR-00:10 | 58156.71 | 27-APR-15:00 | 57888.37 | 27-APR-15:00 | 8719.81 | 28-APR-13:00 | 15160.59 | 27-APR-15:00 | 0.00 |
May | 0.130418E+11 | 0.345898E+10 | 269.27 | 0.107931E+11 | 0.224869E+10 | 0.00 | 1.00 | 04-MAY-13:00 | 0.00 | 01-MAY-00:10 | 46506.32 | 15-MAY-16:00 | 46506.32 | 15-MAY-16:00 | 8861.11 | 06-MAY-17:00 | 11349.61 | 05-MAY-16:00 | 0.00 |
June | 0.216188E+11 | 0.568539E+10 | 359.76 | 0.185680E+11 | 0.305083E+10 | 0.00 | 1.00 | 09-JUN-14:10 | 0.00 | 01-JUN-00:10 | 59053.55 | 28-JUN-16:00 | 59053.55 | 28-JUN-16:00 | 11601.11 | 12-JUN-14:00 | 14972.44 | 28-JUN-16:00 | 0.00 |
July | 0.358153E+11 | 0.919038E+10 | 408.51 | 0.294605E+11 | 0.635484E+10 | 0.00 | 1.00 | 06-JUL-15:00 | 0.00 | 01-JUL-00:10 | 78645.72 | 31-JUL-16:00 | 71980.91 | 24-JUL-15:00 | 20525.93 | 27-JUL-16:00 | 21519.52 | 24-JUL-15:00 | 0.00 |
August | 0.462283E+11 | 0.119368E+11 | 434.03 | 0.374939E+11 | 0.873443E+10 | 0.00 | 1.00 | 04-AUG-13:10 | 0.00 | 01-AUG-00:10 | 84240.14 | 29-AUG-14:40 | 78240.78 | 10-AUG-16:00 | 22579.11 | 30-AUG-13:00 | 23646.70 | 29-AUG-15:00 | 0.00 |
September | 0.211309E+11 | 0.548898E+10 | 332.58 | 0.156958E+11 | 0.543508E+10 | 0.00 | 1.00 | 08-SEP-14:05 | 0.00 | 01-SEP-00:10 | 61042.60 | 14-SEP-13:00 | 49645.39 | 12-SEP-15:00 | 19265.79 | 14-SEP-12:50 | 14738.73 | 14-SEP-13:00 | 0.00 |
October | 0.446526E+10 | 0.125513E+10 | 159.42 | 0.370075E+10 | 0.764506E+09 | 0.00 | 1.00 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 33198.97 | 04-OCT-15:00 | 33198.97 | 04-OCT-15:00 | 5065.89 | 08-OCT-13:13 | 7973.27 | 04-OCT-15:00 | 0.00 |
November | 0.135706E+10 | 0.373195E+09 | 53.21 | 0.831637E+09 | 0.525424E+09 | 0.00 | 0.91 | 04-NOV-13:20 | 0.00 | 01-NOV-00:10 | 29548.76 | 04-NOV-13:20 | 22265.67 | 04-NOV-14:00 | 8861.13 | 04-NOV-16:00 | 7279.80 | 04-NOV-13:20 | 0.00 |
December | 8397926.64 | 2568116.33 | 1.33 | 6880390.14 | 1517536.49 | 0.00 | 0.11 | 14-DEC-12:00 | 0.00 | 01-DEC-00:10 | 2983.50 | 14-DEC-12:00 | 2469.93 | 14-DEC-12:00 | 513.57 | 14-DEC-12:00 | 905.06 | 14-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.152326E+12 | 0.397652E+11 | 2267.94 | 0.124025E+12 | 0.283016E+11 | ||||||||||||||
Minimum of Months | 8397926.64 | 2568116.33 | 1.33 | 6880390.14 | 1517536.49 | 0.00 | 0.11 | 0.00 | 2983.50 | 2469.93 | 513.57 | 905.06 | 0.00 | ||||||
Maximum of Months | 0.462283E+11 | 0.119368E+11 | 434.03 | 0.374939E+11 | 0.873443E+10 | 0.00 | 1.00 | 0.00 | 84240.14 | 78240.78 | 22579.11 | 23646.70 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 275.93 | 0.00 | 275.93 | 1.60 | 1927.89 | 0.00 | 0.00 | 744.00 |
February | 429.35 | 0.00 | 429.35 | 41.80 | 1718.71 | 0.00 | 0.00 | 672.00 |
March | 632.58 | 0.00 | 632.58 | 139.86 | 1376.54 | 0.00 | 0.00 | 744.00 |
April | 895.13 | 3.14 | 891.98 | 386.55 | 1087.63 | 0.00 | 0.00 | 720.00 |
May | 1151.76 | 34.14 | 1117.62 | 635.76 | 882.41 | 0.00 | 0.00 | 744.00 |
June | 1211.01 | 79.85 | 1131.16 | 720.71 | 681.14 | 0.00 | 0.00 | 720.00 |
July | 1150.96 | 90.10 | 1060.86 | 813.28 | 614.75 | 0.00 | 0.00 | 744.00 |
August | 931.73 | 25.09 | 906.65 | 726.57 | 605.76 | 0.00 | 0.00 | 744.00 |
September | 723.81 | 0.21 | 723.60 | 386.67 | 878.77 | 0.00 | 0.00 | 720.00 |
October | 495.94 | 0.00 | 495.94 | 130.37 | 1182.03 | 0.00 | 0.00 | 744.00 |
November | 312.39 | 0.00 | 312.39 | 18.44 | 1533.25 | 0.00 | 0.00 | 720.00 |
December | 234.47 | 0.00 | 234.47 | 1.03 | 1925.37 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 705.11 | 19.52 | 685.59 | 335.46 | 1198.64 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 234.47 | 0.00 | 234.47 | 1.03 | 605.76 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1211.01 | 90.10 | 1131.16 | 813.28 | 1927.89 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.60 | 74.96 | 220.64 | 51.95 | 1232.72 | 0.00 | 0.00 | 744.00 |
February | 542.38 | 192.51 | 349.87 | 234.28 | 1065.35 | 0.00 | 0.00 | 672.00 |
March | 809.81 | 293.17 | 516.64 | 492.28 | 859.37 | 0.00 | 0.00 | 744.00 |
April | 1255.38 | 521.67 | 733.72 | 1009.63 | 677.79 | 0.00 | 0.00 | 720.00 |
May | 1335.68 | 464.33 | 871.36 | 1122.90 | 568.99 | 0.00 | 0.00 | 744.00 |
June | 1599.55 | 695.87 | 903.68 | 1476.43 | 450.98 | 0.00 | 0.00 | 720.00 |
July | 1489.51 | 668.45 | 821.05 | 1449.51 | 395.23 | 0.00 | 0.00 | 744.00 |
August | 1464.14 | 732.42 | 731.72 | 1522.07 | 379.05 | 0.00 | 0.00 | 744.00 |
September | 1082.68 | 499.41 | 583.27 | 966.88 | 546.49 | 0.00 | 0.00 | 720.00 |
October | 705.61 | 299.82 | 405.79 | 486.37 | 744.04 | 0.00 | 0.00 | 744.00 |
November | 345.86 | 97.65 | 248.21 | 110.19 | 979.85 | 0.00 | 0.00 | 720.00 |
December | 283.69 | 91.34 | 192.35 | 71.56 | 1230.32 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 935.88 | 386.81 | 549.07 | 752.19 | 759.41 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 283.69 | 74.96 | 192.35 | 51.95 | 379.05 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1599.55 | 732.42 | 903.68 | 1522.07 | 1232.72 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1218.74 | 723.53 | 495.20 | 926.21 | 1706.87 | 0.00 | 0.00 | 744.00 |
February | 1874.89 | 1160.60 | 714.28 | 1614.31 | 1536.47 | 0.00 | 0.00 | 672.00 |
March | 2017.57 | 1076.32 | 941.25 | 1732.73 | 1345.88 | 0.00 | 0.00 | 744.00 |
April | 2129.50 | 924.72 | 1204.78 | 1745.65 | 1115.97 | 0.00 | 0.00 | 720.00 |
May | 1946.72 | 579.76 | 1366.97 | 1444.09 | 928.17 | 0.00 | 0.00 | 744.00 |
June | 1781.05 | 478.00 | 1303.05 | 1264.17 | 738.33 | 0.00 | 0.00 | 720.00 |
July | 1942.26 | 711.15 | 1231.11 | 1573.57 | 664.41 | 0.00 | 0.00 | 744.00 |
August | 2086.92 | 973.08 | 1113.84 | 1975.99 | 632.89 | 0.00 | 0.00 | 744.00 |
September | 2313.13 | 1277.71 | 1035.41 | 2241.66 | 879.60 | 0.00 | 0.00 | 720.00 |
October | 2095.19 | 1293.84 | 801.35 | 2007.41 | 1159.06 | 0.00 | 0.00 | 744.00 |
November | 1238.17 | 709.47 | 528.70 | 1012.15 | 1413.10 | 0.00 | 0.00 | 720.00 |
December | 1295.31 | 838.09 | 457.22 | 1119.43 | 1751.96 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1827.50 | 893.87 | 933.63 | 1554.17 | 1154.24 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1218.74 | 478.00 | 457.22 | 926.21 | 632.89 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2313.13 | 1293.84 | 1366.97 | 2241.66 | 1751.96 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 311.79 | 91.96 | 219.83 | 73.15 | 1235.34 | 0.00 | 0.00 | 744.00 |
February | 559.00 | 210.10 | 348.90 | 273.71 | 1081.79 | 0.00 | 0.00 | 672.00 |
March | 783.29 | 264.40 | 518.90 | 485.95 | 887.32 | 0.00 | 0.00 | 744.00 |
April | 1191.71 | 455.67 | 736.05 | 955.74 | 722.54 | 0.00 | 0.00 | 720.00 |
May | 1533.21 | 622.75 | 910.46 | 1385.94 | 605.04 | 0.00 | 0.00 | 744.00 |
June | 1474.49 | 572.36 | 902.13 | 1358.08 | 479.60 | 0.00 | 0.00 | 720.00 |
July | 1821.48 | 957.31 | 864.17 | 1913.71 | 440.60 | 0.00 | 0.00 | 744.00 |
August | 1507.00 | 769.49 | 737.51 | 1626.35 | 418.86 | 0.00 | 0.00 | 744.00 |
September | 1227.33 | 588.93 | 638.40 | 1178.43 | 581.99 | 0.00 | 0.00 | 720.00 |
October | 698.69 | 284.68 | 414.01 | 499.79 | 773.48 | 0.00 | 0.00 | 744.00 |
November | 347.96 | 98.15 | 249.81 | 124.67 | 982.58 | 0.00 | 0.00 | 720.00 |
December | 292.54 | 100.26 | 192.28 | 97.55 | 1237.64 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 981.60 | 419.60 | 562.01 | 834.87 | 785.86 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 292.54 | 91.96 | 192.28 | 73.15 | 418.86 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1821.48 | 957.31 | 910.46 | 1913.71 | 1237.64 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.97 | 0.00 | 91.97 | 0.31 | 666.39 | 0.00 | 0.00 | 744.00 |
February | 143.11 | 0.00 | 143.11 | 13.88 | 591.77 | 0.00 | 0.00 | 672.00 |
March | 210.85 | 0.00 | 210.85 | 50.96 | 468.71 | 0.00 | 0.00 | 744.00 |
April | 298.36 | 1.05 | 297.31 | 140.35 | 362.24 | 0.00 | 0.00 | 720.00 |
May | 383.90 | 11.38 | 372.52 | 227.49 | 293.56 | 0.00 | 0.00 | 744.00 |
June | 403.65 | 26.62 | 377.03 | 254.69 | 226.91 | 0.00 | 0.00 | 720.00 |
July | 383.64 | 30.03 | 353.60 | 281.70 | 206.87 | 0.00 | 0.00 | 744.00 |
August | 310.56 | 8.36 | 302.20 | 247.87 | 208.77 | 0.00 | 0.00 | 744.00 |
September | 241.26 | 0.07 | 241.19 | 130.15 | 310.38 | 0.00 | 0.00 | 720.00 |
October | 165.30 | 0.00 | 165.30 | 40.34 | 428.11 | 0.00 | 0.00 | 744.00 |
November | 104.13 | 0.00 | 104.13 | 5.03 | 558.37 | 0.00 | 0.00 | 720.00 |
December | 78.15 | 0.00 | 78.15 | 0.11 | 684.02 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 235.03 | 6.51 | 228.52 | 116.73 | 416.32 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 78.15 | 0.00 | 78.15 | 0.11 | 206.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 403.65 | 30.03 | 377.03 | 281.70 | 684.02 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.97 | 0.00 | 91.97 | 0.31 | 666.43 | 0.00 | 0.00 | 744.00 |
February | 143.11 | 0.00 | 143.11 | 13.88 | 591.80 | 0.00 | 0.00 | 672.00 |
March | 210.86 | 0.00 | 210.86 | 50.96 | 468.74 | 0.00 | 0.00 | 744.00 |
April | 298.37 | 1.05 | 297.33 | 140.35 | 362.26 | 0.00 | 0.00 | 720.00 |
May | 383.92 | 11.38 | 372.54 | 227.50 | 293.58 | 0.00 | 0.00 | 744.00 |
June | 403.67 | 26.62 | 377.05 | 254.70 | 226.92 | 0.00 | 0.00 | 720.00 |
July | 383.65 | 30.03 | 353.62 | 281.71 | 206.88 | 0.00 | 0.00 | 744.00 |
August | 310.58 | 8.36 | 302.21 | 247.88 | 208.79 | 0.00 | 0.00 | 744.00 |
September | 241.27 | 0.07 | 241.20 | 130.15 | 310.40 | 0.00 | 0.00 | 720.00 |
October | 165.31 | 0.00 | 165.31 | 40.34 | 428.14 | 0.00 | 0.00 | 744.00 |
November | 104.13 | 0.00 | 104.13 | 5.03 | 558.41 | 0.00 | 0.00 | 720.00 |
December | 78.15 | 0.00 | 78.15 | 0.11 | 684.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 235.04 | 6.51 | 228.53 | 116.74 | 416.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 78.15 | 0.00 | 78.15 | 0.11 | 206.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 403.67 | 30.03 | 377.05 | 281.71 | 684.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 91.97 | 0.00 | 91.97 | 0.31 | 666.43 | 0.00 | 0.00 | 744.00 |
February | 143.11 | 0.00 | 143.11 | 13.88 | 591.80 | 0.00 | 0.00 | 672.00 |
March | 210.86 | 0.00 | 210.86 | 50.96 | 468.74 | 0.00 | 0.00 | 744.00 |
April | 298.37 | 1.05 | 297.33 | 140.35 | 362.26 | 0.00 | 0.00 | 720.00 |
May | 383.92 | 11.38 | 372.54 | 227.50 | 293.58 | 0.00 | 0.00 | 744.00 |
June | 403.67 | 26.62 | 377.05 | 254.70 | 226.92 | 0.00 | 0.00 | 720.00 |
July | 383.65 | 30.03 | 353.62 | 281.71 | 206.88 | 0.00 | 0.00 | 744.00 |
August | 310.58 | 8.36 | 302.21 | 247.88 | 208.79 | 0.00 | 0.00 | 744.00 |
September | 241.27 | 0.07 | 241.20 | 130.15 | 310.40 | 0.00 | 0.00 | 720.00 |
October | 165.31 | 0.00 | 165.31 | 40.34 | 428.14 | 0.00 | 0.00 | 744.00 |
November | 104.13 | 0.00 | 104.13 | 5.03 | 558.41 | 0.00 | 0.00 | 720.00 |
December | 78.15 | 0.00 | 78.15 | 0.11 | 684.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 235.04 | 6.51 | 228.53 | 116.74 | 416.34 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 78.15 | 0.00 | 78.15 | 0.11 | 206.88 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 403.67 | 30.03 | 377.05 | 281.71 | 684.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 284.35 | 72.10 | 212.25 | 49.11 | 1224.43 | 0.00 | 0.00 | 744.00 |
February | 521.75 | 185.19 | 336.56 | 224.59 | 1059.39 | 0.00 | 0.00 | 672.00 |
March | 779.00 | 282.02 | 496.98 | 484.53 | 850.13 | 0.00 | 0.00 | 744.00 |
April | 1207.62 | 501.82 | 705.80 | 994.42 | 663.99 | 0.00 | 0.00 | 720.00 |
May | 1284.86 | 446.66 | 838.20 | 1108.33 | 553.87 | 0.00 | 0.00 | 744.00 |
June | 1538.68 | 669.38 | 869.30 | 1446.52 | 444.61 | 0.00 | 0.00 | 720.00 |
July | 1432.83 | 643.02 | 789.81 | 1414.60 | 388.88 | 0.00 | 0.00 | 744.00 |
August | 1408.43 | 704.55 | 703.88 | 1472.32 | 385.96 | 0.00 | 0.00 | 744.00 |
September | 1041.49 | 480.41 | 561.08 | 933.84 | 558.04 | 0.00 | 0.00 | 720.00 |
October | 678.76 | 288.41 | 390.35 | 462.22 | 774.00 | 0.00 | 0.00 | 744.00 |
November | 332.70 | 93.93 | 238.77 | 102.63 | 1019.10 | 0.00 | 0.00 | 720.00 |
December | 272.90 | 87.87 | 185.03 | 66.44 | 1255.06 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 900.27 | 372.09 | 528.18 | 732.59 | 763.39 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 272.90 | 72.10 | 185.03 | 49.11 | 385.96 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1538.68 | 704.55 | 869.30 | 1472.32 | 1255.06 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.24 | 2.85 | 8.39 | 1.94 | 48.41 | 0.00 | 0.00 | 744.00 |
February | 20.63 | 7.32 | 13.31 | 8.88 | 41.89 | 0.00 | 0.00 | 672.00 |
March | 30.80 | 11.15 | 19.65 | 19.16 | 33.61 | 0.00 | 0.00 | 744.00 |
April | 47.75 | 19.84 | 27.91 | 39.32 | 26.25 | 0.00 | 0.00 | 720.00 |
May | 50.80 | 17.66 | 33.14 | 43.82 | 21.90 | 0.00 | 0.00 | 744.00 |
June | 60.84 | 26.47 | 34.37 | 57.19 | 17.58 | 0.00 | 0.00 | 720.00 |
July | 56.65 | 25.42 | 31.23 | 55.93 | 15.38 | 0.00 | 0.00 | 744.00 |
August | 55.69 | 27.86 | 27.83 | 58.21 | 15.26 | 0.00 | 0.00 | 744.00 |
September | 41.18 | 18.99 | 22.18 | 36.92 | 22.06 | 0.00 | 0.00 | 720.00 |
October | 26.84 | 11.40 | 15.43 | 18.28 | 30.60 | 0.00 | 0.00 | 744.00 |
November | 13.15 | 3.71 | 9.44 | 4.06 | 40.29 | 0.00 | 0.00 | 720.00 |
December | 10.79 | 3.47 | 7.32 | 2.63 | 49.62 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 35.60 | 14.71 | 20.88 | 28.97 | 30.18 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 10.79 | 2.85 | 7.32 | 1.94 | 15.26 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 60.84 | 27.86 | 34.37 | 58.21 | 49.62 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 406.24 | 241.17 | 165.06 | 313.71 | 582.02 | 0.00 | 0.00 | 744.00 |
February | 624.95 | 386.86 | 238.09 | 547.29 | 530.44 | 0.00 | 0.00 | 672.00 |
March | 672.51 | 358.77 | 313.75 | 592.22 | 462.31 | 0.00 | 0.00 | 744.00 |
April | 709.82 | 308.23 | 401.59 | 600.35 | 374.26 | 0.00 | 0.00 | 720.00 |
May | 648.90 | 193.25 | 455.65 | 502.58 | 306.71 | 0.00 | 0.00 | 744.00 |
June | 593.68 | 159.33 | 434.35 | 442.92 | 241.30 | 0.00 | 0.00 | 720.00 |
July | 647.41 | 237.04 | 410.37 | 538.31 | 222.54 | 0.00 | 0.00 | 744.00 |
August | 695.63 | 324.35 | 371.28 | 666.08 | 221.47 | 0.00 | 0.00 | 744.00 |
September | 771.03 | 425.90 | 345.13 | 752.69 | 315.95 | 0.00 | 0.00 | 720.00 |
October | 698.39 | 431.27 | 267.11 | 672.69 | 422.89 | 0.00 | 0.00 | 744.00 |
November | 412.72 | 236.49 | 176.23 | 338.51 | 505.89 | 0.00 | 0.00 | 720.00 |
December | 431.76 | 279.36 | 152.40 | 375.74 | 610.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 609.16 | 297.95 | 311.21 | 528.38 | 399.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.24 | 159.33 | 152.40 | 313.71 | 221.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 771.03 | 431.27 | 455.65 | 752.69 | 610.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 406.24 | 241.17 | 165.06 | 313.71 | 582.02 | 0.00 | 0.00 | 744.00 |
February | 624.95 | 386.86 | 238.09 | 547.29 | 530.44 | 0.00 | 0.00 | 672.00 |
March | 672.51 | 358.77 | 313.75 | 592.22 | 462.31 | 0.00 | 0.00 | 744.00 |
April | 709.82 | 308.23 | 401.59 | 600.35 | 374.26 | 0.00 | 0.00 | 720.00 |
May | 648.90 | 193.25 | 455.65 | 502.58 | 306.71 | 0.00 | 0.00 | 744.00 |
June | 593.68 | 159.33 | 434.35 | 442.92 | 241.30 | 0.00 | 0.00 | 720.00 |
July | 647.41 | 237.04 | 410.37 | 538.31 | 222.54 | 0.00 | 0.00 | 744.00 |
August | 695.63 | 324.35 | 371.28 | 666.08 | 221.47 | 0.00 | 0.00 | 744.00 |
September | 771.03 | 425.90 | 345.13 | 752.69 | 315.95 | 0.00 | 0.00 | 720.00 |
October | 698.39 | 431.27 | 267.11 | 672.69 | 422.89 | 0.00 | 0.00 | 744.00 |
November | 412.72 | 236.49 | 176.23 | 338.51 | 505.89 | 0.00 | 0.00 | 720.00 |
December | 431.76 | 279.36 | 152.40 | 375.74 | 610.88 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 609.16 | 297.95 | 311.21 | 528.38 | 399.09 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.24 | 159.33 | 152.40 | 313.71 | 221.47 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 771.03 | 431.27 | 455.65 | 752.69 | 610.88 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 406.21 | 241.16 | 165.05 | 313.69 | 581.99 | 0.00 | 0.00 | 744.00 |
February | 624.91 | 386.84 | 238.08 | 547.26 | 530.40 | 0.00 | 0.00 | 672.00 |
March | 672.47 | 358.74 | 313.73 | 592.19 | 462.28 | 0.00 | 0.00 | 744.00 |
April | 709.78 | 308.21 | 401.56 | 600.31 | 374.24 | 0.00 | 0.00 | 720.00 |
May | 648.86 | 193.24 | 455.62 | 502.54 | 306.69 | 0.00 | 0.00 | 744.00 |
June | 593.64 | 159.32 | 434.32 | 442.90 | 241.29 | 0.00 | 0.00 | 720.00 |
July | 647.37 | 237.03 | 410.34 | 538.28 | 222.53 | 0.00 | 0.00 | 744.00 |
August | 695.58 | 324.33 | 371.25 | 666.04 | 221.46 | 0.00 | 0.00 | 744.00 |
September | 770.98 | 425.87 | 345.11 | 752.65 | 315.93 | 0.00 | 0.00 | 720.00 |
October | 698.34 | 431.24 | 267.10 | 672.65 | 422.87 | 0.00 | 0.00 | 744.00 |
November | 412.69 | 236.47 | 176.22 | 338.49 | 505.86 | 0.00 | 0.00 | 720.00 |
December | 431.73 | 279.34 | 152.39 | 375.72 | 610.84 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 609.12 | 297.93 | 311.19 | 528.35 | 399.07 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 406.21 | 159.32 | 152.39 | 313.69 | 221.46 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 770.98 | 431.24 | 455.62 | 752.65 | 610.84 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 299.93 | 88.46 | 211.47 | 71.19 | 1229.09 | 0.00 | 0.00 | 744.00 |
February | 537.73 | 202.11 | 335.62 | 266.89 | 1078.44 | 0.00 | 0.00 | 672.00 |
March | 753.49 | 254.34 | 499.15 | 482.44 | 879.36 | 0.00 | 0.00 | 744.00 |
April | 1146.37 | 438.33 | 708.04 | 948.16 | 704.90 | 0.00 | 0.00 | 720.00 |
May | 1474.88 | 599.06 | 875.82 | 1366.07 | 592.95 | 0.00 | 0.00 | 744.00 |
June | 1418.39 | 550.58 | 867.80 | 1338.06 | 466.97 | 0.00 | 0.00 | 720.00 |
July | 1752.18 | 920.89 | 831.29 | 1862.05 | 442.79 | 0.00 | 0.00 | 744.00 |
August | 1449.66 | 740.21 | 709.45 | 1575.12 | 426.66 | 0.00 | 0.00 | 744.00 |
September | 1180.63 | 566.52 | 614.11 | 1139.66 | 596.14 | 0.00 | 0.00 | 720.00 |
October | 672.10 | 273.85 | 398.26 | 479.85 | 802.45 | 0.00 | 0.00 | 744.00 |
November | 334.72 | 94.42 | 240.30 | 117.84 | 1023.48 | 0.00 | 0.00 | 720.00 |
December | 281.41 | 96.45 | 184.96 | 93.21 | 1264.34 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 944.26 | 403.63 | 540.62 | 815.38 | 790.98 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 281.41 | 88.46 | 184.96 | 71.19 | 426.66 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1752.18 | 920.89 | 875.82 | 1862.05 | 1264.34 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 11.86 | 3.50 | 8.36 | 2.81 | 48.60 | 0.00 | 0.00 | 744.00 |
February | 21.26 | 7.99 | 13.27 | 10.55 | 42.64 | 0.00 | 0.00 | 672.00 |
March | 29.79 | 10.06 | 19.74 | 19.08 | 34.77 | 0.00 | 0.00 | 744.00 |
April | 45.33 | 17.33 | 28.00 | 37.49 | 27.87 | 0.00 | 0.00 | 720.00 |
May | 58.32 | 23.69 | 34.63 | 54.01 | 23.44 | 0.00 | 0.00 | 744.00 |
June | 56.08 | 21.77 | 34.31 | 52.91 | 18.46 | 0.00 | 0.00 | 720.00 |
July | 69.28 | 36.41 | 32.87 | 73.62 | 17.51 | 0.00 | 0.00 | 744.00 |
August | 57.32 | 29.27 | 28.05 | 62.28 | 16.87 | 0.00 | 0.00 | 744.00 |
September | 46.68 | 22.40 | 24.28 | 45.06 | 23.57 | 0.00 | 0.00 | 720.00 |
October | 26.57 | 10.83 | 15.75 | 18.97 | 31.73 | 0.00 | 0.00 | 744.00 |
November | 13.23 | 3.73 | 9.50 | 4.66 | 40.47 | 0.00 | 0.00 | 720.00 |
December | 11.13 | 3.81 | 7.31 | 3.69 | 49.99 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 37.33 | 15.96 | 21.38 | 32.24 | 31.27 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 11.13 | 3.50 | 7.31 | 2.81 | 16.87 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 69.28 | 36.41 | 34.63 | 73.62 | 49.99 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 275.93 | 0.00 | 275.93 | 0.52 | 2038.21 | 0.00 | 0.00 | 744.00 |
February | 429.35 | 0.00 | 429.35 | 36.28 | 1830.91 | 0.00 | 0.00 | 672.00 |
March | 632.58 | 0.00 | 632.58 | 128.76 | 1473.79 | 0.00 | 0.00 | 744.00 |
April | 895.13 | 3.14 | 891.98 | 374.36 | 1154.75 | 0.00 | 0.00 | 720.00 |
May | 1151.76 | 34.14 | 1117.62 | 628.20 | 935.17 | 0.00 | 0.00 | 744.00 |
June | 1211.01 | 79.85 | 1131.16 | 716.35 | 715.38 | 0.00 | 0.00 | 720.00 |
July | 1150.96 | 90.10 | 1060.86 | 813.38 | 644.69 | 0.00 | 0.00 | 744.00 |
August | 931.73 | 25.09 | 906.65 | 722.59 | 642.32 | 0.00 | 0.00 | 744.00 |
September | 723.81 | 0.21 | 723.60 | 374.33 | 944.69 | 0.00 | 0.00 | 720.00 |
October | 495.94 | 0.00 | 495.94 | 114.70 | 1284.33 | 0.00 | 0.00 | 744.00 |
November | 312.39 | 0.00 | 312.39 | 14.73 | 1661.96 | 0.00 | 0.00 | 720.00 |
December | 234.47 | 0.00 | 234.47 | 0.34 | 2060.19 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 705.11 | 19.52 | 685.59 | 328.97 | 1279.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 234.47 | 0.00 | 234.47 | 0.34 | 642.32 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1211.01 | 90.10 | 1131.16 | 813.38 | 2060.19 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 295.60 | 74.96 | 220.64 | 48.52 | 1296.93 | 0.00 | 0.00 | 744.00 |
February | 542.38 | 192.51 | 349.87 | 225.09 | 1127.34 | 0.00 | 0.00 | 672.00 |
March | 809.81 | 293.17 | 516.64 | 484.29 | 911.16 | 0.00 | 0.00 | 744.00 |
April | 1255.38 | 521.67 | 733.72 | 1004.78 | 710.65 | 0.00 | 0.00 | 720.00 |
May | 1335.68 | 464.33 | 871.36 | 1124.26 | 591.43 | 0.00 | 0.00 | 744.00 |
June | 1599.55 | 695.87 | 903.68 | 1483.94 | 463.87 | 0.00 | 0.00 | 720.00 |
July | 1489.51 | 668.45 | 821.05 | 1458.04 | 404.73 | 0.00 | 0.00 | 744.00 |
August | 1464.14 | 732.42 | 731.72 | 1526.44 | 391.41 | 0.00 | 0.00 | 744.00 |
September | 1082.68 | 499.41 | 583.27 | 964.98 | 573.47 | 0.00 | 0.00 | 720.00 |
October | 705.61 | 299.82 | 405.79 | 475.85 | 795.46 | 0.00 | 0.00 | 744.00 |
November | 345.86 | 97.65 | 248.21 | 104.99 | 1052.56 | 0.00 | 0.00 | 720.00 |
December | 283.69 | 91.34 | 192.35 | 67.57 | 1309.41 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 935.88 | 386.81 | 549.07 | 750.13 | 800.82 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 283.69 | 74.96 | 192.35 | 48.52 | 391.41 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1599.55 | 732.42 | 903.68 | 1526.44 | 1309.41 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1218.74 | 723.53 | 495.20 | 911.06 | 1801.40 | 0.00 | 0.00 | 744.00 |
February | 1874.89 | 1160.60 | 714.28 | 1592.81 | 1629.17 | 0.00 | 0.00 | 672.00 |
March | 2017.57 | 1076.32 | 941.25 | 1720.62 | 1428.35 | 0.00 | 0.00 | 744.00 |
April | 2129.50 | 924.72 | 1204.78 | 1736.62 | 1173.21 | 0.00 | 0.00 | 720.00 |
May | 1946.72 | 579.76 | 1366.97 | 1439.97 | 970.83 | 0.00 | 0.00 | 744.00 |
June | 1781.05 | 478.00 | 1303.05 | 1265.89 | 766.08 | 0.00 | 0.00 | 720.00 |
July | 1942.26 | 711.15 | 1231.11 | 1576.31 | 688.04 | 0.00 | 0.00 | 744.00 |
August | 2086.92 | 973.08 | 1113.84 | 1973.71 | 661.55 | 0.00 | 0.00 | 744.00 |
September | 2313.13 | 1277.71 | 1035.41 | 2233.13 | 929.58 | 0.00 | 0.00 | 720.00 |
October | 2095.19 | 1293.84 | 801.35 | 1990.28 | 1241.38 | 0.00 | 0.00 | 744.00 |
November | 1238.17 | 709.47 | 528.70 | 993.96 | 1515.82 | 0.00 | 0.00 | 720.00 |
December | 1295.31 | 838.09 | 457.22 | 1102.61 | 1863.66 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 1827.50 | 893.87 | 933.63 | 1544.21 | 1220.46 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 1218.74 | 478.00 | 457.22 | 911.06 | 661.55 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 2313.13 | 1293.84 | 1366.97 | 2233.13 | 1863.66 | 0.00 | 0.00 | 744.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 311.79 | 91.96 | 219.83 | 70.90 | 1300.13 | 0.00 | 0.00 | 744.00 |
February | 559.00 | 210.10 | 348.90 | 267.40 | 1146.04 | 0.00 | 0.00 | 672.00 |
March | 783.29 | 264.40 | 518.90 | 481.60 | 943.37 | 0.00 | 0.00 | 744.00 |
April | 1191.71 | 455.67 | 736.05 | 953.01 | 760.84 | 0.00 | 0.00 | 720.00 |
May | 1533.21 | 622.75 | 910.46 | 1387.09 | 634.14 | 0.00 | 0.00 | 744.00 |
June | 1474.49 | 572.36 | 902.13 | 1363.13 | 498.54 | 0.00 | 0.00 | 720.00 |
July | 1821.48 | 957.31 | 864.17 | 1919.98 | 457.25 | 0.00 | 0.00 | 744.00 |
August | 1507.00 | 769.49 | 737.51 | 1628.33 | 437.71 | 0.00 | 0.00 | 744.00 |
September | 1227.33 | 588.93 | 638.40 | 1175.71 | 614.91 | 0.00 | 0.00 | 720.00 |
October | 698.69 | 284.68 | 414.01 | 492.20 | 829.17 | 0.00 | 0.00 | 744.00 |
November | 347.96 | 98.15 | 249.81 | 120.40 | 1056.12 | 0.00 | 0.00 | 720.00 |
December | 292.54 | 100.26 | 192.28 | 94.47 | 1317.24 | 0.00 | 0.00 | 744.00 |
Annual Sum or Average | 981.60 | 419.60 | 562.01 | 833.33 | 831.48 | 0.00 | 0.00 | 8760.00 |
Minimum of Months | 292.54 | 91.96 | 192.28 | 70.90 | 437.71 | 0.00 | 0.00 | 672.00 |
Maximum of Months | 1821.48 | 957.31 | 910.46 | 1919.98 | 1317.24 | 0.00 | 0.00 | 744.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.739038E+09 | 0.00 | 0.739038E+09 | 4273109.67 | 0.516366E+10 |
February | 0.103868E+10 | 0.00 | 0.103868E+10 | 0.101116E+09 | 0.415789E+10 |
March | 0.169429E+10 | 0.00 | 0.169429E+10 | 0.374606E+09 | 0.368692E+10 |
April | 0.232017E+10 | 8147302.51 | 0.231202E+10 | 0.100193E+10 | 0.281914E+10 |
May | 0.308488E+10 | 91433861.41 | 0.299344E+10 | 0.170283E+10 | 0.236345E+10 |
June | 0.313893E+10 | 0.206975E+09 | 0.293196E+10 | 0.186809E+10 | 0.176552E+10 |
July | 0.308274E+10 | 0.241320E+09 | 0.284142E+10 | 0.217828E+10 | 0.164654E+10 |
August | 0.249556E+10 | 67193834.73 | 0.242836E+10 | 0.194604E+10 | 0.162246E+10 |
September | 0.187612E+10 | 535316.02 | 0.187558E+10 | 0.100225E+10 | 0.227776E+10 |
October | 0.132831E+10 | 0.00 | 0.132831E+10 | 0.349180E+09 | 0.316596E+10 |
November | 0.809717E+09 | 0.00 | 0.809717E+09 | 47806370.96 | 0.397419E+10 |
December | 0.627991E+09 | 0.00 | 0.627991E+09 | 2751798.45 | 0.515690E+10 |
Annual Sum or Average | 0.222364E+11 | 0.615605E+09 | 0.216208E+11 | 0.105791E+11 | 0.378004E+11 |
Minimum of Months | 0.627991E+09 | 0.00 | 0.627991E+09 | 2751798.45 | 0.162246E+10 |
Maximum of Months | 0.313893E+10 | 0.241320E+09 | 0.299344E+10 | 0.217828E+10 | 0.516366E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791735E+09 | 0.200761E+09 | 0.590973E+09 | 0.139155E+09 | 0.330172E+10 |
February | 0.131213E+10 | 0.465727E+09 | 0.846408E+09 | 0.566763E+09 | 0.257730E+10 |
March | 0.216901E+10 | 0.785232E+09 | 0.138377E+10 | 0.131853E+10 | 0.230173E+10 |
April | 0.325395E+10 | 0.135216E+10 | 0.190179E+10 | 0.261696E+10 | 0.175684E+10 |
May | 0.357749E+10 | 0.124365E+10 | 0.233384E+10 | 0.300759E+10 | 0.152397E+10 |
June | 0.414603E+10 | 0.180368E+10 | 0.234234E+10 | 0.382690E+10 | 0.116895E+10 |
July | 0.398949E+10 | 0.179039E+10 | 0.219911E+10 | 0.388236E+10 | 0.105858E+10 |
August | 0.392156E+10 | 0.196171E+10 | 0.195984E+10 | 0.407670E+10 | 0.101524E+10 |
September | 0.280632E+10 | 0.129447E+10 | 0.151184E+10 | 0.250614E+10 | 0.141649E+10 |
October | 0.188990E+10 | 0.803028E+09 | 0.108687E+10 | 0.130269E+10 | 0.199284E+10 |
November | 0.896474E+09 | 0.253104E+09 | 0.643370E+09 | 0.285601E+09 | 0.253976E+10 |
December | 0.759844E+09 | 0.244648E+09 | 0.515195E+09 | 0.191679E+09 | 0.329529E+10 |
Annual Sum or Average | 0.295139E+11 | 0.121986E+11 | 0.173154E+11 | 0.237211E+11 | 0.239487E+11 |
Minimum of Months | 0.759844E+09 | 0.200761E+09 | 0.515195E+09 | 0.139155E+09 | 0.101524E+10 |
Maximum of Months | 0.414603E+10 | 0.196171E+10 | 0.234234E+10 | 0.407670E+10 | 0.330172E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326426E+10 | 0.193791E+10 | 0.132635E+10 | 0.248077E+10 | 0.457168E+10 |
February | 0.453573E+10 | 0.280773E+10 | 0.172799E+10 | 0.390533E+10 | 0.371703E+10 |
March | 0.540386E+10 | 0.288282E+10 | 0.252104E+10 | 0.464095E+10 | 0.360481E+10 |
April | 0.551966E+10 | 0.239686E+10 | 0.312280E+10 | 0.452473E+10 | 0.289261E+10 |
May | 0.521411E+10 | 0.155283E+10 | 0.366128E+10 | 0.386784E+10 | 0.248602E+10 |
June | 0.461648E+10 | 0.123897E+10 | 0.337751E+10 | 0.327672E+10 | 0.191376E+10 |
July | 0.520215E+10 | 0.190473E+10 | 0.329742E+10 | 0.421465E+10 | 0.177956E+10 |
August | 0.558959E+10 | 0.260629E+10 | 0.298330E+10 | 0.529249E+10 | 0.169512E+10 |
September | 0.599563E+10 | 0.331183E+10 | 0.268379E+10 | 0.581039E+10 | 0.227994E+10 |
October | 0.561177E+10 | 0.346542E+10 | 0.214634E+10 | 0.537665E+10 | 0.310442E+10 |
November | 0.320934E+10 | 0.183895E+10 | 0.137039E+10 | 0.262350E+10 | 0.366276E+10 |
December | 0.346935E+10 | 0.224475E+10 | 0.122461E+10 | 0.299828E+10 | 0.469246E+10 |
Annual Sum or Average | 0.576319E+11 | 0.281891E+11 | 0.294428E+11 | 0.490123E+11 | 0.364002E+11 |
Minimum of Months | 0.320934E+10 | 0.123897E+10 | 0.122461E+10 | 0.248077E+10 | 0.169512E+10 |
Maximum of Months | 0.599563E+10 | 0.346542E+10 | 0.366128E+10 | 0.581039E+10 | 0.469246E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.835102E+09 | 0.246298E+09 | 0.588805E+09 | 0.195914E+09 | 0.330874E+10 |
February | 0.135234E+10 | 0.508284E+09 | 0.844056E+09 | 0.662148E+09 | 0.261707E+10 |
March | 0.209797E+10 | 0.708158E+09 | 0.138981E+10 | 0.130158E+10 | 0.237659E+10 |
April | 0.308892E+10 | 0.118109E+10 | 0.190783E+10 | 0.247727E+10 | 0.187282E+10 |
May | 0.410656E+10 | 0.166798E+10 | 0.243857E+10 | 0.371211E+10 | 0.162053E+10 |
June | 0.382188E+10 | 0.148356E+10 | 0.233831E+10 | 0.352014E+10 | 0.124313E+10 |
July | 0.487866E+10 | 0.256407E+10 | 0.231459E+10 | 0.512567E+10 | 0.118011E+10 |
August | 0.403635E+10 | 0.206100E+10 | 0.197535E+10 | 0.435603E+10 | 0.112189E+10 |
September | 0.318123E+10 | 0.152650E+10 | 0.165473E+10 | 0.305448E+10 | 0.150851E+10 |
October | 0.187136E+10 | 0.762483E+09 | 0.110888E+10 | 0.133863E+10 | 0.207169E+10 |
November | 0.901921E+09 | 0.254416E+09 | 0.647504E+09 | 0.323148E+09 | 0.254685E+10 |
December | 0.783542E+09 | 0.268548E+09 | 0.514994E+09 | 0.261276E+09 | 0.331491E+10 |
Annual Sum or Average | 0.309558E+11 | 0.132324E+11 | 0.177234E+11 | 0.263284E+11 | 0.247828E+11 |
Minimum of Months | 0.783542E+09 | 0.246298E+09 | 0.514994E+09 | 0.195914E+09 | 0.112189E+10 |
Maximum of Months | 0.487866E+10 | 0.256407E+10 | 0.243857E+10 | 0.512567E+10 | 0.331491E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246334E+09 | 0.00 | 0.246334E+09 | 817386.49 | 0.178486E+10 |
February | 0.346209E+09 | 0.00 | 0.346209E+09 | 33571134.36 | 0.143160E+10 |
March | 0.564736E+09 | 0.00 | 0.564736E+09 | 0.136502E+09 | 0.125539E+10 |
April | 0.773352E+09 | 2715639.01 | 0.770636E+09 | 0.363778E+09 | 0.938920E+09 |
May | 0.102824E+10 | 30476511.83 | 0.997767E+09 | 0.609310E+09 | 0.786270E+09 |
June | 0.104626E+10 | 68988392.45 | 0.977273E+09 | 0.660164E+09 | 0.588153E+09 |
July | 0.102753E+10 | 80436176.76 | 0.947094E+09 | 0.754508E+09 | 0.554082E+09 |
August | 0.831813E+09 | 22396885.22 | 0.809416E+09 | 0.663892E+09 | 0.559178E+09 |
September | 0.625343E+09 | 178430.23 | 0.625165E+09 | 0.337344E+09 | 0.804503E+09 |
October | 0.442750E+09 | 0.00 | 0.442750E+09 | 0.108048E+09 | 0.114665E+10 |
November | 0.269893E+09 | 0.00 | 0.269893E+09 | 13028644.75 | 0.144729E+10 |
December | 0.209321E+09 | 0.00 | 0.209321E+09 | 306383.09 | 0.183207E+10 |
Annual Sum or Average | 0.741179E+10 | 0.205192E+09 | 0.720659E+10 | 0.368127E+10 | 0.131290E+11 |
Minimum of Months | 0.209321E+09 | 0.00 | 0.209321E+09 | 306383.09 | 0.554082E+09 |
Maximum of Months | 0.104626E+10 | 80436176.76 | 0.997767E+09 | 0.754508E+09 | 0.183207E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246343E+09 | 0.00 | 0.246343E+09 | 817173.69 | 0.178498E+10 |
February | 0.346222E+09 | 0.00 | 0.346222E+09 | 33570667.32 | 0.143169E+10 |
March | 0.564758E+09 | 0.00 | 0.564758E+09 | 0.136502E+09 | 0.125547E+10 |
April | 0.773382E+09 | 2715712.01 | 0.770666E+09 | 0.363786E+09 | 0.938980E+09 |
May | 0.102828E+10 | 30477331.05 | 0.997806E+09 | 0.609326E+09 | 0.786320E+09 |
June | 0.104630E+10 | 68990246.88 | 0.977312E+09 | 0.660183E+09 | 0.588189E+09 |
July | 0.102757E+10 | 80438338.90 | 0.947134E+09 | 0.754536E+09 | 0.554115E+09 |
August | 0.831847E+09 | 22397487.25 | 0.809449E+09 | 0.663918E+09 | 0.559211E+09 |
September | 0.625368E+09 | 178435.03 | 0.625190E+09 | 0.337354E+09 | 0.804551E+09 |
October | 0.442767E+09 | 0.00 | 0.442767E+09 | 0.108048E+09 | 0.114672E+10 |
November | 0.269903E+09 | 0.00 | 0.269903E+09 | 13028297.27 | 0.144739E+10 |
December | 0.209328E+09 | 0.00 | 0.209328E+09 | 306299.37 | 0.183219E+10 |
Annual Sum or Average | 0.741208E+10 | 0.205198E+09 | 0.720688E+10 | 0.368137E+10 | 0.131298E+11 |
Minimum of Months | 0.209328E+09 | 0.00 | 0.209328E+09 | 306299.37 | 0.554115E+09 |
Maximum of Months | 0.104630E+10 | 80438338.90 | 0.997806E+09 | 0.754536E+09 | 0.183219E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.246343E+09 | 0.00 | 0.246343E+09 | 817173.69 | 0.178498E+10 |
February | 0.346222E+09 | 0.00 | 0.346222E+09 | 33570667.32 | 0.143169E+10 |
March | 0.564758E+09 | 0.00 | 0.564758E+09 | 0.136502E+09 | 0.125547E+10 |
April | 0.773382E+09 | 2715712.01 | 0.770666E+09 | 0.363786E+09 | 0.938980E+09 |
May | 0.102828E+10 | 30477331.05 | 0.997806E+09 | 0.609326E+09 | 0.786320E+09 |
June | 0.104630E+10 | 68990246.88 | 0.977312E+09 | 0.660183E+09 | 0.588189E+09 |
July | 0.102757E+10 | 80438338.90 | 0.947134E+09 | 0.754536E+09 | 0.554115E+09 |
August | 0.831847E+09 | 22397487.25 | 0.809449E+09 | 0.663918E+09 | 0.559211E+09 |
September | 0.625368E+09 | 178435.03 | 0.625190E+09 | 0.337354E+09 | 0.804551E+09 |
October | 0.442767E+09 | 0.00 | 0.442767E+09 | 0.108048E+09 | 0.114672E+10 |
November | 0.269903E+09 | 0.00 | 0.269903E+09 | 13028297.27 | 0.144739E+10 |
December | 0.209328E+09 | 0.00 | 0.209328E+09 | 306299.37 | 0.183219E+10 |
Annual Sum or Average | 0.741208E+10 | 0.205198E+09 | 0.720688E+10 | 0.368137E+10 | 0.131298E+11 |
Minimum of Months | 0.209328E+09 | 0.00 | 0.209328E+09 | 306299.37 | 0.554115E+09 |
Maximum of Months | 0.104630E+10 | 80438338.90 | 0.997806E+09 | 0.754536E+09 | 0.183219E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.761609E+09 | 0.193122E+09 | 0.568487E+09 | 0.131529E+09 | 0.327952E+10 |
February | 0.126221E+10 | 0.448004E+09 | 0.814203E+09 | 0.543327E+09 | 0.256289E+10 |
March | 0.208648E+10 | 0.755351E+09 | 0.133112E+10 | 0.129776E+10 | 0.227700E+10 |
April | 0.313014E+10 | 0.130071E+10 | 0.182943E+10 | 0.257755E+10 | 0.172106E+10 |
May | 0.344136E+10 | 0.119632E+10 | 0.224504E+10 | 0.296855E+10 | 0.148347E+10 |
June | 0.398827E+10 | 0.173505E+10 | 0.225322E+10 | 0.374938E+10 | 0.115242E+10 |
July | 0.383770E+10 | 0.172226E+10 | 0.211544E+10 | 0.378886E+10 | 0.104157E+10 |
August | 0.377234E+10 | 0.188706E+10 | 0.188528E+10 | 0.394347E+10 | 0.103377E+10 |
September | 0.269954E+10 | 0.124521E+10 | 0.145432E+10 | 0.242050E+10 | 0.144645E+10 |
October | 0.181799E+10 | 0.772470E+09 | 0.104552E+10 | 0.123801E+10 | 0.207307E+10 |
November | 0.862363E+09 | 0.243472E+09 | 0.618890E+09 | 0.266013E+09 | 0.264152E+10 |
December | 0.730931E+09 | 0.235338E+09 | 0.495593E+09 | 0.177961E+09 | 0.336156E+10 |
Annual Sum or Average | 0.283909E+11 | 0.117344E+11 | 0.166566E+11 | 0.231029E+11 | 0.240743E+11 |
Minimum of Months | 0.730931E+09 | 0.193122E+09 | 0.495593E+09 | 0.131529E+09 | 0.103377E+10 |
Maximum of Months | 0.398827E+10 | 0.188706E+10 | 0.225322E+10 | 0.394347E+10 | 0.336156E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 30113325.66 | 7635852.50 | 22477473.16 | 5200557.93 | 0.129669E+09 |
February | 49906533.69 | 17713682.12 | 32192851.57 | 21482644.95 | 0.101334E+09 |
March | 82497353.64 | 29865891.83 | 52631461.81 | 51312249.07 | 90030579.38 |
April | 0.123763E+09 | 51428738.46 | 72334207.80 | 0.101914E+09 | 68049086.32 |
May | 0.136068E+09 | 47301527.41 | 88766936.69 | 0.117374E+09 | 58655154.98 |
June | 0.157693E+09 | 68602148.07 | 89090408.15 | 0.148247E+09 | 45565749.75 |
July | 0.151739E+09 | 68096432.61 | 83642611.63 | 0.149808E+09 | 41182588.90 |
August | 0.149155E+09 | 74612798.14 | 74542115.74 | 0.155921E+09 | 40874156.75 |
September | 0.106737E+09 | 49234624.78 | 57502564.61 | 95704442.84 | 57191207.21 |
October | 71881654.78 | 30542751.77 | 41338903.01 | 48949631.40 | 81967461.66 |
November | 34097045.60 | 9626680.45 | 24470365.15 | 10517923.12 | 0.104443E+09 |
December | 28900352.34 | 9305067.50 | 19595284.84 | 7036434.91 | 0.132913E+09 |
Annual Sum or Average | 0.112255E+10 | 0.463966E+09 | 0.658585E+09 | 0.913468E+09 | 0.951876E+09 |
Minimum of Months | 28900352.34 | 7635852.50 | 19595284.84 | 5200557.93 | 40874156.75 |
Maximum of Months | 0.157693E+09 | 74612798.14 | 89090408.15 | 0.155921E+09 | 0.132913E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108807E+10 | 0.645958E+09 | 0.442110E+09 | 0.840249E+09 | 0.155889E+10 |
February | 0.151188E+10 | 0.935892E+09 | 0.575989E+09 | 0.132402E+10 | 0.128324E+10 |
March | 0.180126E+10 | 0.960921E+09 | 0.840335E+09 | 0.158622E+10 | 0.123824E+10 |
April | 0.183986E+10 | 0.798938E+09 | 0.104092E+10 | 0.155610E+10 | 0.970090E+09 |
May | 0.173801E+10 | 0.517598E+09 | 0.122041E+10 | 0.134610E+10 | 0.821500E+09 |
June | 0.153881E+10 | 0.412983E+09 | 0.112583E+10 | 0.114806E+10 | 0.625455E+09 |
July | 0.173403E+10 | 0.634898E+09 | 0.109913E+10 | 0.144181E+10 | 0.596055E+09 |
August | 0.186317E+10 | 0.868746E+09 | 0.994425E+09 | 0.178404E+10 | 0.593196E+09 |
September | 0.199851E+10 | 0.110392E+10 | 0.894587E+09 | 0.195098E+10 | 0.818939E+09 |
October | 0.187056E+10 | 0.115512E+10 | 0.715439E+09 | 0.180173E+10 | 0.113268E+10 |
November | 0.106976E+10 | 0.612969E+09 | 0.456791E+09 | 0.877426E+09 | 0.131126E+10 |
December | 0.115643E+10 | 0.748234E+09 | 0.408196E+09 | 0.100639E+10 | 0.163618E+10 |
Annual Sum or Average | 0.192103E+11 | 0.939618E+10 | 0.981416E+10 | 0.166631E+11 | 0.125857E+11 |
Minimum of Months | 0.106976E+10 | 0.412983E+09 | 0.408196E+09 | 0.840249E+09 | 0.593196E+09 |
Maximum of Months | 0.199851E+10 | 0.115512E+10 | 0.122041E+10 | 0.195098E+10 | 0.163618E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108807E+10 | 0.645958E+09 | 0.442110E+09 | 0.840249E+09 | 0.155889E+10 |
February | 0.151188E+10 | 0.935892E+09 | 0.575989E+09 | 0.132402E+10 | 0.128324E+10 |
March | 0.180126E+10 | 0.960921E+09 | 0.840335E+09 | 0.158622E+10 | 0.123824E+10 |
April | 0.183986E+10 | 0.798938E+09 | 0.104092E+10 | 0.155610E+10 | 0.970090E+09 |
May | 0.173801E+10 | 0.517598E+09 | 0.122041E+10 | 0.134610E+10 | 0.821500E+09 |
June | 0.153881E+10 | 0.412983E+09 | 0.112583E+10 | 0.114806E+10 | 0.625455E+09 |
July | 0.173403E+10 | 0.634898E+09 | 0.109913E+10 | 0.144181E+10 | 0.596055E+09 |
August | 0.186317E+10 | 0.868746E+09 | 0.994425E+09 | 0.178404E+10 | 0.593196E+09 |
September | 0.199851E+10 | 0.110392E+10 | 0.894587E+09 | 0.195098E+10 | 0.818939E+09 |
October | 0.187056E+10 | 0.115512E+10 | 0.715439E+09 | 0.180173E+10 | 0.113268E+10 |
November | 0.106976E+10 | 0.612969E+09 | 0.456791E+09 | 0.877426E+09 | 0.131126E+10 |
December | 0.115643E+10 | 0.748234E+09 | 0.408196E+09 | 0.100639E+10 | 0.163618E+10 |
Annual Sum or Average | 0.192103E+11 | 0.939618E+10 | 0.981416E+10 | 0.166631E+11 | 0.125857E+11 |
Minimum of Months | 0.106976E+10 | 0.412983E+09 | 0.408196E+09 | 0.840249E+09 | 0.593196E+09 |
Maximum of Months | 0.199851E+10 | 0.115512E+10 | 0.122041E+10 | 0.195098E+10 | 0.163618E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.108800E+10 | 0.645917E+09 | 0.442082E+09 | 0.840196E+09 | 0.155879E+10 |
February | 0.151179E+10 | 0.935833E+09 | 0.575953E+09 | 0.132393E+10 | 0.128316E+10 |
March | 0.180114E+10 | 0.960860E+09 | 0.840282E+09 | 0.158611E+10 | 0.123817E+10 |
April | 0.183974E+10 | 0.798888E+09 | 0.104086E+10 | 0.155600E+10 | 0.970029E+09 |
May | 0.173790E+10 | 0.517565E+09 | 0.122034E+10 | 0.134601E+10 | 0.821448E+09 |
June | 0.153871E+10 | 0.412956E+09 | 0.112575E+10 | 0.114799E+10 | 0.625416E+09 |
July | 0.173392E+10 | 0.634858E+09 | 0.109906E+10 | 0.144172E+10 | 0.596018E+09 |
August | 0.186305E+10 | 0.868692E+09 | 0.994362E+09 | 0.178392E+10 | 0.593159E+09 |
September | 0.199838E+10 | 0.110385E+10 | 0.894530E+09 | 0.195086E+10 | 0.818888E+09 |
October | 0.187044E+10 | 0.115504E+10 | 0.715393E+09 | 0.180161E+10 | 0.113261E+10 |
November | 0.106969E+10 | 0.612931E+09 | 0.456762E+09 | 0.877371E+09 | 0.131118E+10 |
December | 0.115636E+10 | 0.748187E+09 | 0.408170E+09 | 0.100632E+10 | 0.163608E+10 |
Annual Sum or Average | 0.192091E+11 | 0.939558E+10 | 0.981354E+10 | 0.166621E+11 | 0.125849E+11 |
Minimum of Months | 0.106969E+10 | 0.412956E+09 | 0.408170E+09 | 0.840196E+09 | 0.593159E+09 |
Maximum of Months | 0.199838E+10 | 0.115504E+10 | 0.122034E+10 | 0.195086E+10 | 0.163608E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.803329E+09 | 0.236926E+09 | 0.566403E+09 | 0.190671E+09 | 0.329200E+10 |
February | 0.130089E+10 | 0.488943E+09 | 0.811943E+09 | 0.645672E+09 | 0.260895E+10 |
March | 0.201815E+10 | 0.681211E+09 | 0.133694E+10 | 0.129218E+10 | 0.235529E+10 |
April | 0.297139E+10 | 0.113615E+10 | 0.183524E+10 | 0.245763E+10 | 0.182709E+10 |
May | 0.395031E+10 | 0.160452E+10 | 0.234580E+10 | 0.365888E+10 | 0.158815E+10 |
June | 0.367646E+10 | 0.142711E+10 | 0.224935E+10 | 0.346825E+10 | 0.121039E+10 |
July | 0.469303E+10 | 0.246651E+10 | 0.222653E+10 | 0.498732E+10 | 0.118597E+10 |
August | 0.388278E+10 | 0.198258E+10 | 0.190020E+10 | 0.421881E+10 | 0.114276E+10 |
September | 0.306019E+10 | 0.146842E+10 | 0.159178E+10 | 0.295400E+10 | 0.154520E+10 |
October | 0.180016E+10 | 0.733470E+09 | 0.106669E+10 | 0.128522E+10 | 0.214929E+10 |
November | 0.867605E+09 | 0.244736E+09 | 0.622869E+09 | 0.305444E+09 | 0.265286E+10 |
December | 0.753729E+09 | 0.258329E+09 | 0.495400E+09 | 0.249656E+09 | 0.338641E+10 |
Annual Sum or Average | 0.297780E+11 | 0.127289E+11 | 0.170491E+11 | 0.257137E+11 | 0.249444E+11 |
Minimum of Months | 0.753729E+09 | 0.236926E+09 | 0.495400E+09 | 0.190671E+09 | 0.114276E+10 |
Maximum of Months | 0.469303E+10 | 0.246651E+10 | 0.234580E+10 | 0.498732E+10 | 0.338641E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 31762800.94 | 9367800.05 | 22395000.89 | 7538897.72 | 0.130163E+09 |
February | 51435711.62 | 19332299.68 | 32103411.93 | 25529186.59 | 0.103156E+09 |
March | 79795529.23 | 26934400.59 | 52861128.65 | 51091439.10 | 93126007.68 |
April | 0.117486E+09 | 44922194.71 | 72563749.75 | 97172135.46 | 72241515.65 |
May | 0.156191E+09 | 63440935.07 | 92750519.12 | 0.144668E+09 | 62794179.29 |
June | 0.145364E+09 | 56426615.90 | 88937062.27 | 0.137131E+09 | 47857600.16 |
July | 0.185558E+09 | 97523076.34 | 88034771.18 | 0.197193E+09 | 46892176.10 |
August | 0.153521E+09 | 78389074.51 | 75132142.86 | 0.166808E+09 | 45183689.34 |
September | 0.120997E+09 | 58059665.29 | 62937343.71 | 0.116798E+09 | 61095931.96 |
October | 71176441.02 | 29000631.34 | 42175809.69 | 50816203.19 | 84980880.68 |
November | 34304213.11 | 9676590.42 | 24627622.69 | 12076924.56 | 0.104892E+09 |
December | 29801698.87 | 10214076.81 | 19587622.06 | 9871103.13 | 0.133896E+09 |
Annual Sum or Average | 0.117739E+10 | 0.503287E+09 | 0.674106E+09 | 0.101669E+10 | 0.986278E+09 |
Minimum of Months | 29801698.87 | 9367800.05 | 19587622.06 | 7538897.72 | 45183689.34 |
Maximum of Months | 0.185558E+09 | 97523076.34 | 92750519.12 | 0.197193E+09 | 0.133896E+09 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.739038E+09 | 0.00 | 0.739038E+09 | 1400919.18 | 0.545913E+10 |
February | 0.103868E+10 | 0.00 | 0.103868E+10 | 87766052.48 | 0.442933E+10 |
March | 0.169429E+10 | 0.00 | 0.169429E+10 | 0.344877E+09 | 0.394740E+10 |
April | 0.232017E+10 | 8147302.51 | 0.231202E+10 | 0.970346E+09 | 0.299312E+10 |
May | 0.308488E+10 | 91433861.41 | 0.299344E+10 | 0.168258E+10 | 0.250476E+10 |
June | 0.313893E+10 | 0.206975E+09 | 0.293196E+10 | 0.185679E+10 | 0.185426E+10 |
July | 0.308274E+10 | 0.241320E+09 | 0.284142E+10 | 0.217856E+10 | 0.172674E+10 |
August | 0.249556E+10 | 67193834.73 | 0.242836E+10 | 0.193539E+10 | 0.172039E+10 |
September | 0.187612E+10 | 535316.02 | 0.187558E+10 | 0.970259E+09 | 0.244863E+10 |
October | 0.132831E+10 | 0.00 | 0.132831E+10 | 0.307215E+09 | 0.343994E+10 |
November | 0.809717E+09 | 0.00 | 0.809717E+09 | 38186169.93 | 0.430780E+10 |
December | 0.627991E+09 | 0.00 | 0.627991E+09 | 905988.62 | 0.551802E+10 |
Annual Sum or Average | 0.222364E+11 | 0.615605E+09 | 0.216208E+11 | 0.103743E+11 | 0.403495E+11 |
Minimum of Months | 0.627991E+09 | 0.00 | 0.627991E+09 | 905988.62 | 0.172039E+10 |
Maximum of Months | 0.313893E+10 | 0.241320E+09 | 0.299344E+10 | 0.217856E+10 | 0.551802E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.791735E+09 | 0.200761E+09 | 0.590973E+09 | 0.129966E+09 | 0.347371E+10 |
February | 0.131213E+10 | 0.465727E+09 | 0.846408E+09 | 0.544531E+09 | 0.272727E+10 |
March | 0.216901E+10 | 0.785232E+09 | 0.138377E+10 | 0.129711E+10 | 0.244044E+10 |
April | 0.325395E+10 | 0.135216E+10 | 0.190179E+10 | 0.260440E+10 | 0.184202E+10 |
May | 0.357749E+10 | 0.124365E+10 | 0.233384E+10 | 0.301121E+10 | 0.158408E+10 |
June | 0.414603E+10 | 0.180368E+10 | 0.234234E+10 | 0.384638E+10 | 0.120235E+10 |
July | 0.398949E+10 | 0.179039E+10 | 0.219911E+10 | 0.390521E+10 | 0.108403E+10 |
August | 0.392156E+10 | 0.196171E+10 | 0.195984E+10 | 0.408842E+10 | 0.104836E+10 |
September | 0.280632E+10 | 0.129447E+10 | 0.151184E+10 | 0.250123E+10 | 0.148644E+10 |
October | 0.188990E+10 | 0.803028E+09 | 0.108687E+10 | 0.127452E+10 | 0.213056E+10 |
November | 0.896474E+09 | 0.253104E+09 | 0.643370E+09 | 0.272127E+09 | 0.272825E+10 |
December | 0.759844E+09 | 0.244648E+09 | 0.515195E+09 | 0.180966E+09 | 0.350713E+10 |
Annual Sum or Average | 0.295139E+11 | 0.121986E+11 | 0.173154E+11 | 0.236561E+11 | 0.252546E+11 |
Minimum of Months | 0.759844E+09 | 0.200761E+09 | 0.515195E+09 | 0.129966E+09 | 0.104836E+10 |
Maximum of Months | 0.414603E+10 | 0.196171E+10 | 0.234234E+10 | 0.408842E+10 | 0.350713E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.326426E+10 | 0.193791E+10 | 0.132635E+10 | 0.244019E+10 | 0.482486E+10 |
February | 0.453573E+10 | 0.280773E+10 | 0.172799E+10 | 0.385332E+10 | 0.394128E+10 |
March | 0.540386E+10 | 0.288282E+10 | 0.252104E+10 | 0.460852E+10 | 0.382569E+10 |
April | 0.551966E+10 | 0.239686E+10 | 0.312280E+10 | 0.450133E+10 | 0.304097E+10 |
May | 0.521411E+10 | 0.155283E+10 | 0.366128E+10 | 0.385680E+10 | 0.260027E+10 |
June | 0.461648E+10 | 0.123897E+10 | 0.337751E+10 | 0.328119E+10 | 0.198569E+10 |
July | 0.520215E+10 | 0.190473E+10 | 0.329742E+10 | 0.422199E+10 | 0.184285E+10 |
August | 0.558959E+10 | 0.260629E+10 | 0.298330E+10 | 0.528637E+10 | 0.177190E+10 |
September | 0.599563E+10 | 0.331183E+10 | 0.268379E+10 | 0.578827E+10 | 0.240946E+10 |
October | 0.561177E+10 | 0.346542E+10 | 0.214634E+10 | 0.533076E+10 | 0.332492E+10 |
November | 0.320934E+10 | 0.183895E+10 | 0.137039E+10 | 0.257635E+10 | 0.392900E+10 |
December | 0.346935E+10 | 0.224475E+10 | 0.122461E+10 | 0.295322E+10 | 0.499162E+10 |
Annual Sum or Average | 0.576319E+11 | 0.281891E+11 | 0.294428E+11 | 0.486983E+11 | 0.384885E+11 |
Minimum of Months | 0.320934E+10 | 0.123897E+10 | 0.122461E+10 | 0.244019E+10 | 0.177190E+10 |
Maximum of Months | 0.599563E+10 | 0.346542E+10 | 0.366128E+10 | 0.578827E+10 | 0.499162E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.835102E+09 | 0.246298E+09 | 0.588805E+09 | 0.189909E+09 | 0.348227E+10 |
February | 0.135234E+10 | 0.508284E+09 | 0.844056E+09 | 0.646897E+09 | 0.277249E+10 |
March | 0.209797E+10 | 0.708158E+09 | 0.138981E+10 | 0.128992E+10 | 0.252673E+10 |
April | 0.308892E+10 | 0.118109E+10 | 0.190783E+10 | 0.247021E+10 | 0.197211E+10 |
May | 0.410656E+10 | 0.166798E+10 | 0.243857E+10 | 0.371519E+10 | 0.169847E+10 |
June | 0.382188E+10 | 0.148356E+10 | 0.233831E+10 | 0.353323E+10 | 0.129221E+10 |
July | 0.487866E+10 | 0.256407E+10 | 0.231459E+10 | 0.514247E+10 | 0.122470E+10 |
August | 0.403635E+10 | 0.206100E+10 | 0.197535E+10 | 0.436132E+10 | 0.117237E+10 |
September | 0.318123E+10 | 0.152650E+10 | 0.165473E+10 | 0.304743E+10 | 0.159385E+10 |
October | 0.187136E+10 | 0.762483E+09 | 0.110888E+10 | 0.131830E+10 | 0.222085E+10 |
November | 0.901921E+09 | 0.254416E+09 | 0.647504E+09 | 0.312073E+09 | 0.273746E+10 |
December | 0.783542E+09 | 0.268548E+09 | 0.514994E+09 | 0.253029E+09 | 0.352808E+10 |
Annual Sum or Average | 0.309558E+11 | 0.132324E+11 | 0.177234E+11 | 0.262800E+11 | 0.262216E+11 |
Minimum of Months | 0.783542E+09 | 0.246298E+09 | 0.514994E+09 | 0.189909E+09 | 0.117237E+10 |
Maximum of Months | 0.487866E+10 | 0.256407E+10 | 0.243857E+10 | 0.514247E+10 | 0.352808E+10 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1.60 | 1927.89 | 275.93 | 0.00 | 275.93 | 0.00 | 0.00 |
February | 41.80 | 1718.71 | 429.35 | 0.00 | 429.35 | 0.00 | 0.00 |
March | 139.86 | 1376.54 | 632.58 | 0.00 | 632.58 | 0.00 | 0.00 |
April | 386.55 | 1087.63 | 895.13 | 3.14 | 891.98 | 0.00 | 0.00 |
May | 635.76 | 882.41 | 1151.76 | 34.14 | 1117.62 | 0.00 | 0.00 |
June | 720.71 | 681.14 | 1211.01 | 79.85 | 1131.16 | 0.00 | 0.00 |
July | 813.28 | 614.75 | 1150.96 | 90.10 | 1060.86 | 0.00 | 0.00 |
August | 726.57 | 605.76 | 931.73 | 25.09 | 906.65 | 0.00 | 0.00 |
September | 386.67 | 878.77 | 723.81 | 0.21 | 723.60 | 0.00 | 0.00 |
October | 130.37 | 1182.03 | 495.94 | 0.00 | 495.94 | 0.00 | 0.00 |
November | 18.44 | 1533.25 | 312.39 | 0.00 | 312.39 | 0.00 | 0.00 |
December | 1.03 | 1925.37 | 234.47 | 0.00 | 234.47 | 0.00 | 0.00 |
Annual Sum or Average | 335.46 | 1198.64 | 705.11 | 19.52 | 685.59 | 0.00 | 0.00 |
Minimum of Months | 1.03 | 605.76 | 234.47 | 0.00 | 234.47 | 0.00 | 0.00 |
Maximum of Months | 813.28 | 1927.89 | 1211.01 | 90.10 | 1131.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 51.95 | 1232.72 | 295.60 | 74.96 | 220.64 | 0.00 | 0.00 |
February | 234.28 | 1065.35 | 542.38 | 192.51 | 349.87 | 0.00 | 0.00 |
March | 492.28 | 859.37 | 809.81 | 293.17 | 516.64 | 0.00 | 0.00 |
April | 1009.63 | 677.79 | 1255.38 | 521.67 | 733.72 | 0.00 | 0.00 |
May | 1122.90 | 568.99 | 1335.68 | 464.33 | 871.36 | 0.00 | 0.00 |
June | 1476.43 | 450.98 | 1599.55 | 695.87 | 903.68 | 0.00 | 0.00 |
July | 1449.51 | 395.23 | 1489.51 | 668.45 | 821.05 | 0.00 | 0.00 |
August | 1522.07 | 379.05 | 1464.14 | 732.42 | 731.72 | 0.00 | 0.00 |
September | 966.88 | 546.49 | 1082.68 | 499.41 | 583.27 | 0.00 | 0.00 |
October | 486.37 | 744.04 | 705.61 | 299.82 | 405.79 | 0.00 | 0.00 |
November | 110.19 | 979.85 | 345.86 | 97.65 | 248.21 | 0.00 | 0.00 |
December | 71.56 | 1230.32 | 283.69 | 91.34 | 192.35 | 0.00 | 0.00 |
Annual Sum or Average | 752.19 | 759.41 | 935.88 | 386.81 | 549.07 | 0.00 | 0.00 |
Minimum of Months | 51.95 | 379.05 | 283.69 | 74.96 | 192.35 | 0.00 | 0.00 |
Maximum of Months | 1522.07 | 1232.72 | 1599.55 | 732.42 | 903.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 926.21 | 1706.87 | 1218.74 | 723.53 | 495.20 | 0.00 | 0.00 |
February | 1614.31 | 1536.47 | 1874.89 | 1160.60 | 714.28 | 0.00 | 0.00 |
March | 1732.73 | 1345.88 | 2017.57 | 1076.32 | 941.25 | 0.00 | 0.00 |
April | 1745.65 | 1115.97 | 2129.50 | 924.72 | 1204.78 | 0.00 | 0.00 |
May | 1444.09 | 928.17 | 1946.72 | 579.76 | 1366.97 | 0.00 | 0.00 |
June | 1264.17 | 738.33 | 1781.05 | 478.00 | 1303.05 | 0.00 | 0.00 |
July | 1573.57 | 664.41 | 1942.26 | 711.15 | 1231.11 | 0.00 | 0.00 |
August | 1975.99 | 632.89 | 2086.92 | 973.08 | 1113.84 | 0.00 | 0.00 |
September | 2241.66 | 879.60 | 2313.13 | 1277.71 | 1035.41 | 0.00 | 0.00 |
October | 2007.41 | 1159.06 | 2095.19 | 1293.84 | 801.35 | 0.00 | 0.00 |
November | 1012.15 | 1413.10 | 1238.17 | 709.47 | 528.70 | 0.00 | 0.00 |
December | 1119.43 | 1751.96 | 1295.31 | 838.09 | 457.22 | 0.00 | 0.00 |
Annual Sum or Average | 1554.17 | 1154.24 | 1827.50 | 893.87 | 933.63 | 0.00 | 0.00 |
Minimum of Months | 926.21 | 632.89 | 1218.74 | 478.00 | 457.22 | 0.00 | 0.00 |
Maximum of Months | 2241.66 | 1751.96 | 2313.13 | 1293.84 | 1366.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 73.15 | 1235.34 | 311.79 | 91.96 | 219.83 | 0.00 | 0.00 |
February | 273.71 | 1081.79 | 559.00 | 210.10 | 348.90 | 0.00 | 0.00 |
March | 485.95 | 887.32 | 783.29 | 264.40 | 518.90 | 0.00 | 0.00 |
April | 955.74 | 722.54 | 1191.71 | 455.67 | 736.05 | 0.00 | 0.00 |
May | 1385.94 | 605.04 | 1533.21 | 622.75 | 910.46 | 0.00 | 0.00 |
June | 1358.08 | 479.60 | 1474.49 | 572.36 | 902.13 | 0.00 | 0.00 |
July | 1913.71 | 440.60 | 1821.48 | 957.31 | 864.17 | 0.00 | 0.00 |
August | 1626.35 | 418.86 | 1507.00 | 769.49 | 737.51 | 0.00 | 0.00 |
September | 1178.43 | 581.99 | 1227.33 | 588.93 | 638.40 | 0.00 | 0.00 |
October | 499.79 | 773.48 | 698.69 | 284.68 | 414.01 | 0.00 | 0.00 |
November | 124.67 | 982.58 | 347.96 | 98.15 | 249.81 | 0.00 | 0.00 |
December | 97.55 | 1237.64 | 292.54 | 100.26 | 192.28 | 0.00 | 0.00 |
Annual Sum or Average | 834.87 | 785.86 | 981.60 | 419.60 | 562.01 | 0.00 | 0.00 |
Minimum of Months | 73.15 | 418.86 | 292.54 | 91.96 | 192.28 | 0.00 | 0.00 |
Maximum of Months | 1913.71 | 1237.64 | 1821.48 | 957.31 | 910.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.92 | 1999.26 | 275.92 | 0.00 | 275.92 | 0.00 | 0.00 |
February | 41.63 | 1775.37 | 429.34 | 0.00 | 429.34 | 0.00 | 0.00 |
March | 152.89 | 1406.19 | 632.56 | 0.00 | 632.56 | 0.00 | 0.00 |
April | 421.05 | 1086.76 | 895.11 | 3.14 | 891.96 | 0.00 | 0.00 |
May | 682.48 | 880.72 | 1151.74 | 34.14 | 1117.60 | 0.00 | 0.00 |
June | 764.09 | 680.76 | 1210.98 | 79.85 | 1131.13 | 0.00 | 0.00 |
July | 845.12 | 620.64 | 1150.94 | 90.10 | 1060.84 | 0.00 | 0.00 |
August | 743.63 | 626.34 | 931.72 | 25.09 | 906.63 | 0.00 | 0.00 |
September | 390.45 | 931.17 | 723.80 | 0.21 | 723.59 | 0.00 | 0.00 |
October | 121.02 | 1284.38 | 495.92 | 0.00 | 495.92 | 0.00 | 0.00 |
November | 15.08 | 1675.18 | 312.38 | 0.00 | 312.38 | 0.00 | 0.00 |
December | 0.34 | 2052.14 | 234.46 | 0.00 | 234.46 | 0.00 | 0.00 |
Annual Sum or Average | 350.20 | 1249.00 | 705.10 | 19.52 | 685.58 | 0.00 | 0.00 |
Minimum of Months | 0.34 | 620.64 | 234.46 | 0.00 | 234.46 | 0.00 | 0.00 |
Maximum of Months | 845.12 | 2052.14 | 1210.98 | 90.10 | 1131.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 51.05 | 1272.85 | 295.60 | 74.95 | 220.64 | 0.00 | 0.00 |
February | 233.47 | 1101.28 | 542.38 | 192.51 | 349.87 | 0.00 | 0.00 |
March | 503.69 | 883.75 | 809.80 | 293.17 | 516.64 | 0.00 | 0.00 |
April | 1033.74 | 690.24 | 1255.36 | 521.66 | 733.71 | 0.00 | 0.00 |
May | 1152.15 | 575.76 | 1335.66 | 464.32 | 871.34 | 0.00 | 0.00 |
June | 1503.71 | 462.19 | 1599.52 | 695.85 | 903.67 | 0.00 | 0.00 |
July | 1470.53 | 404.25 | 1489.48 | 668.44 | 821.04 | 0.00 | 0.00 |
August | 1530.54 | 401.22 | 1464.12 | 732.41 | 731.71 | 0.00 | 0.00 |
September | 970.76 | 580.11 | 1082.67 | 499.40 | 583.27 | 0.00 | 0.00 |
October | 480.49 | 804.60 | 705.60 | 299.81 | 405.79 | 0.00 | 0.00 |
November | 106.69 | 1059.40 | 345.86 | 97.65 | 248.21 | 0.00 | 0.00 |
December | 69.07 | 1304.69 | 283.69 | 91.34 | 192.35 | 0.00 | 0.00 |
Annual Sum or Average | 761.55 | 793.57 | 935.87 | 386.81 | 549.06 | 0.00 | 0.00 |
Minimum of Months | 51.05 | 401.22 | 283.69 | 74.95 | 192.35 | 0.00 | 0.00 |
Maximum of Months | 1530.54 | 1304.69 | 1599.52 | 732.41 | 903.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 941.12 | 1746.03 | 1218.69 | 723.50 | 495.18 | 0.00 | 0.00 |
February | 1641.85 | 1591.28 | 1874.81 | 1160.56 | 714.26 | 0.00 | 0.00 |
March | 1776.64 | 1386.89 | 2017.49 | 1076.28 | 941.22 | 0.00 | 0.00 |
April | 1801.00 | 1122.77 | 2129.42 | 924.68 | 1204.74 | 0.00 | 0.00 |
May | 1507.69 | 920.12 | 1946.66 | 579.73 | 1366.92 | 0.00 | 0.00 |
June | 1328.74 | 723.89 | 1780.99 | 477.98 | 1303.01 | 0.00 | 0.00 |
July | 1614.90 | 667.61 | 1942.19 | 711.12 | 1231.08 | 0.00 | 0.00 |
August | 1998.21 | 664.41 | 2086.84 | 973.04 | 1113.80 | 0.00 | 0.00 |
September | 2258.03 | 947.83 | 2313.04 | 1277.66 | 1035.38 | 0.00 | 0.00 |
October | 2018.02 | 1268.66 | 2095.11 | 1293.79 | 801.33 | 0.00 | 0.00 |
November | 1015.52 | 1517.63 | 1238.12 | 709.44 | 528.68 | 0.00 | 0.00 |
December | 1127.20 | 1832.60 | 1295.26 | 838.06 | 457.20 | 0.00 | 0.00 |
Annual Sum or Average | 1585.12 | 1197.25 | 1827.43 | 893.83 | 933.60 | 0.00 | 0.00 |
Minimum of Months | 941.12 | 664.41 | 1218.69 | 477.98 | 457.20 | 0.00 | 0.00 |
Maximum of Months | 2258.03 | 1832.60 | 2313.04 | 1293.79 | 1366.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 74.00 | 1277.69 | 311.79 | 91.96 | 219.83 | 0.00 | 0.00 |
February | 277.45 | 1121.08 | 559.00 | 210.10 | 348.89 | 0.00 | 0.00 |
March | 501.52 | 914.13 | 783.28 | 264.39 | 518.89 | 0.00 | 0.00 |
April | 985.65 | 732.77 | 1191.70 | 455.66 | 736.04 | 0.00 | 0.00 |
May | 1420.08 | 616.39 | 1533.19 | 622.74 | 910.45 | 0.00 | 0.00 |
June | 1390.96 | 485.43 | 1474.47 | 572.35 | 902.12 | 0.00 | 0.00 |
July | 1935.67 | 460.30 | 1821.46 | 957.30 | 864.16 | 0.00 | 0.00 |
August | 1637.40 | 443.53 | 1506.98 | 769.48 | 737.51 | 0.00 | 0.00 |
September | 1184.72 | 619.71 | 1227.31 | 588.92 | 638.39 | 0.00 | 0.00 |
October | 498.82 | 834.18 | 698.68 | 284.67 | 414.00 | 0.00 | 0.00 |
November | 122.50 | 1063.95 | 347.96 | 98.15 | 249.81 | 0.00 | 0.00 |
December | 96.90 | 1314.33 | 292.54 | 100.26 | 192.27 | 0.00 | 0.00 |
Annual Sum or Average | 847.62 | 822.26 | 981.59 | 419.59 | 562.00 | 0.00 | 0.00 |
Minimum of Months | 74.00 | 443.53 | 292.54 | 91.96 | 192.27 | 0.00 | 0.00 |
Maximum of Months | 1935.67 | 1314.33 | 1821.46 | 957.30 | 910.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.52 | 2038.21 | 275.93 | 0.00 | 275.93 | 0.00 | 0.00 |
February | 36.28 | 1830.91 | 429.35 | 0.00 | 429.35 | 0.00 | 0.00 |
March | 128.76 | 1473.79 | 632.58 | 0.00 | 632.58 | 0.00 | 0.00 |
April | 374.36 | 1154.75 | 895.13 | 3.14 | 891.98 | 0.00 | 0.00 |
May | 628.20 | 935.17 | 1151.76 | 34.14 | 1117.62 | 0.00 | 0.00 |
June | 716.35 | 715.38 | 1211.01 | 79.85 | 1131.16 | 0.00 | 0.00 |
July | 813.38 | 644.69 | 1150.96 | 90.10 | 1060.86 | 0.00 | 0.00 |
August | 722.59 | 642.32 | 931.73 | 25.09 | 906.65 | 0.00 | 0.00 |
September | 374.33 | 944.69 | 723.81 | 0.21 | 723.60 | 0.00 | 0.00 |
October | 114.70 | 1284.33 | 495.94 | 0.00 | 495.94 | 0.00 | 0.00 |
November | 14.73 | 1661.96 | 312.39 | 0.00 | 312.39 | 0.00 | 0.00 |
December | 0.34 | 2060.19 | 234.47 | 0.00 | 234.47 | 0.00 | 0.00 |
Annual Sum or Average | 328.97 | 1279.48 | 705.11 | 19.52 | 685.59 | 0.00 | 0.00 |
Minimum of Months | 0.34 | 642.32 | 234.47 | 0.00 | 234.47 | 0.00 | 0.00 |
Maximum of Months | 813.38 | 2060.19 | 1211.01 | 90.10 | 1131.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 48.52 | 1296.93 | 295.60 | 74.96 | 220.64 | 0.00 | 0.00 |
February | 225.09 | 1127.34 | 542.38 | 192.51 | 349.87 | 0.00 | 0.00 |
March | 484.29 | 911.16 | 809.81 | 293.17 | 516.64 | 0.00 | 0.00 |
April | 1004.78 | 710.65 | 1255.38 | 521.67 | 733.72 | 0.00 | 0.00 |
May | 1124.26 | 591.43 | 1335.68 | 464.33 | 871.36 | 0.00 | 0.00 |
June | 1483.94 | 463.87 | 1599.55 | 695.87 | 903.68 | 0.00 | 0.00 |
July | 1458.04 | 404.73 | 1489.51 | 668.45 | 821.05 | 0.00 | 0.00 |
August | 1526.44 | 391.41 | 1464.14 | 732.42 | 731.72 | 0.00 | 0.00 |
September | 964.98 | 573.47 | 1082.68 | 499.41 | 583.27 | 0.00 | 0.00 |
October | 475.85 | 795.46 | 705.61 | 299.82 | 405.79 | 0.00 | 0.00 |
November | 104.99 | 1052.56 | 345.86 | 97.65 | 248.21 | 0.00 | 0.00 |
December | 67.57 | 1309.41 | 283.69 | 91.34 | 192.35 | 0.00 | 0.00 |
Annual Sum or Average | 750.13 | 800.82 | 935.88 | 386.81 | 549.07 | 0.00 | 0.00 |
Minimum of Months | 48.52 | 391.41 | 283.69 | 74.96 | 192.35 | 0.00 | 0.00 |
Maximum of Months | 1526.44 | 1309.41 | 1599.55 | 732.42 | 903.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 911.06 | 1801.40 | 1218.74 | 723.53 | 495.20 | 0.00 | 0.00 |
February | 1592.81 | 1629.17 | 1874.89 | 1160.60 | 714.28 | 0.00 | 0.00 |
March | 1720.62 | 1428.35 | 2017.57 | 1076.32 | 941.25 | 0.00 | 0.00 |
April | 1736.62 | 1173.21 | 2129.50 | 924.72 | 1204.78 | 0.00 | 0.00 |
May | 1439.97 | 970.83 | 1946.72 | 579.76 | 1366.97 | 0.00 | 0.00 |
June | 1265.89 | 766.08 | 1781.05 | 478.00 | 1303.05 | 0.00 | 0.00 |
July | 1576.31 | 688.04 | 1942.26 | 711.15 | 1231.11 | 0.00 | 0.00 |
August | 1973.71 | 661.55 | 2086.92 | 973.08 | 1113.84 | 0.00 | 0.00 |
September | 2233.13 | 929.58 | 2313.13 | 1277.71 | 1035.41 | 0.00 | 0.00 |
October | 1990.28 | 1241.38 | 2095.19 | 1293.84 | 801.35 | 0.00 | 0.00 |
November | 993.96 | 1515.82 | 1238.17 | 709.47 | 528.70 | 0.00 | 0.00 |
December | 1102.61 | 1863.66 | 1295.31 | 838.09 | 457.22 | 0.00 | 0.00 |
Annual Sum or Average | 1544.21 | 1220.46 | 1827.50 | 893.87 | 933.63 | 0.00 | 0.00 |
Minimum of Months | 911.06 | 661.55 | 1218.74 | 478.00 | 457.22 | 0.00 | 0.00 |
Maximum of Months | 2233.13 | 1863.66 | 2313.13 | 1293.84 | 1366.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 70.90 | 1300.13 | 311.79 | 91.96 | 219.83 | 0.00 | 0.00 |
February | 267.40 | 1146.04 | 559.00 | 210.10 | 348.90 | 0.00 | 0.00 |
March | 481.60 | 943.37 | 783.29 | 264.40 | 518.90 | 0.00 | 0.00 |
April | 953.01 | 760.84 | 1191.71 | 455.67 | 736.05 | 0.00 | 0.00 |
May | 1387.09 | 634.14 | 1533.21 | 622.75 | 910.46 | 0.00 | 0.00 |
June | 1363.13 | 498.54 | 1474.49 | 572.36 | 902.13 | 0.00 | 0.00 |
July | 1919.98 | 457.25 | 1821.48 | 957.31 | 864.17 | 0.00 | 0.00 |
August | 1628.33 | 437.71 | 1507.00 | 769.49 | 737.51 | 0.00 | 0.00 |
September | 1175.71 | 614.91 | 1227.33 | 588.93 | 638.40 | 0.00 | 0.00 |
October | 492.20 | 829.17 | 698.69 | 284.68 | 414.01 | 0.00 | 0.00 |
November | 120.40 | 1056.12 | 347.96 | 98.15 | 249.81 | 0.00 | 0.00 |
December | 94.47 | 1317.24 | 292.54 | 100.26 | 192.28 | 0.00 | 0.00 |
Annual Sum or Average | 833.33 | 831.48 | 981.60 | 419.60 | 562.01 | 0.00 | 0.00 |
Minimum of Months | 70.90 | 437.71 | 292.54 | 91.96 | 192.28 | 0.00 | 0.00 |
Maximum of Months | 1919.98 | 1317.24 | 1821.48 | 957.31 | 910.46 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 4273109.67 | 0.516366E+10 | 0.739038E+09 | 0.00 | 0.739038E+09 | 0.00 | 0.00 |
February | 0.101116E+09 | 0.415789E+10 | 0.103868E+10 | 0.00 | 0.103868E+10 | 0.00 | 0.00 |
March | 0.374606E+09 | 0.368692E+10 | 0.169429E+10 | 0.00 | 0.169429E+10 | 0.00 | 0.00 |
April | 0.100193E+10 | 0.281914E+10 | 0.232017E+10 | 8147302.51 | 0.231202E+10 | 0.00 | 0.00 |
May | 0.170283E+10 | 0.236345E+10 | 0.308488E+10 | 91433861.41 | 0.299344E+10 | 0.00 | 0.00 |
June | 0.186809E+10 | 0.176552E+10 | 0.313893E+10 | 0.206975E+09 | 0.293196E+10 | 0.00 | 0.00 |
July | 0.217828E+10 | 0.164654E+10 | 0.308274E+10 | 0.241320E+09 | 0.284142E+10 | 0.00 | 0.00 |
August | 0.194604E+10 | 0.162246E+10 | 0.249556E+10 | 67193834.73 | 0.242836E+10 | 0.00 | 0.00 |
September | 0.100225E+10 | 0.227776E+10 | 0.187612E+10 | 535316.02 | 0.187558E+10 | 0.00 | 0.00 |
October | 0.349180E+09 | 0.316596E+10 | 0.132831E+10 | 0.00 | 0.132831E+10 | 0.00 | 0.00 |
November | 47806370.96 | 0.397419E+10 | 0.809717E+09 | 0.00 | 0.809717E+09 | 0.00 | 0.00 |
December | 2751798.45 | 0.515690E+10 | 0.627991E+09 | 0.00 | 0.627991E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105791E+11 | 0.378004E+11 | 0.222364E+11 | 0.615605E+09 | 0.216208E+11 | 0.00 | 0.00 |
Minimum of Months | 2751798.45 | 0.162246E+10 | 0.627991E+09 | 0.00 | 0.627991E+09 | 0.00 | 0.00 |
Maximum of Months | 0.217828E+10 | 0.516366E+10 | 0.313893E+10 | 0.241320E+09 | 0.299344E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.139155E+09 | 0.330172E+10 | 0.791735E+09 | 0.200761E+09 | 0.590973E+09 | 0.00 | 0.00 |
February | 0.566763E+09 | 0.257730E+10 | 0.131213E+10 | 0.465727E+09 | 0.846408E+09 | 0.00 | 0.00 |
March | 0.131853E+10 | 0.230173E+10 | 0.216901E+10 | 0.785232E+09 | 0.138377E+10 | 0.00 | 0.00 |
April | 0.261696E+10 | 0.175684E+10 | 0.325395E+10 | 0.135216E+10 | 0.190179E+10 | 0.00 | 0.00 |
May | 0.300759E+10 | 0.152397E+10 | 0.357749E+10 | 0.124365E+10 | 0.233384E+10 | 0.00 | 0.00 |
June | 0.382690E+10 | 0.116895E+10 | 0.414603E+10 | 0.180368E+10 | 0.234234E+10 | 0.00 | 0.00 |
July | 0.388236E+10 | 0.105858E+10 | 0.398949E+10 | 0.179039E+10 | 0.219911E+10 | 0.00 | 0.00 |
August | 0.407670E+10 | 0.101524E+10 | 0.392156E+10 | 0.196171E+10 | 0.195984E+10 | 0.00 | 0.00 |
September | 0.250614E+10 | 0.141649E+10 | 0.280632E+10 | 0.129447E+10 | 0.151184E+10 | 0.00 | 0.00 |
October | 0.130269E+10 | 0.199284E+10 | 0.188990E+10 | 0.803028E+09 | 0.108687E+10 | 0.00 | 0.00 |
November | 0.285601E+09 | 0.253976E+10 | 0.896474E+09 | 0.253104E+09 | 0.643370E+09 | 0.00 | 0.00 |
December | 0.191679E+09 | 0.329529E+10 | 0.759844E+09 | 0.244648E+09 | 0.515195E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.237211E+11 | 0.239487E+11 | 0.295139E+11 | 0.121986E+11 | 0.173154E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139155E+09 | 0.101524E+10 | 0.759844E+09 | 0.200761E+09 | 0.515195E+09 | 0.00 | 0.00 |
Maximum of Months | 0.407670E+10 | 0.330172E+10 | 0.414603E+10 | 0.196171E+10 | 0.234234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.248077E+10 | 0.457168E+10 | 0.326426E+10 | 0.193791E+10 | 0.132635E+10 | 0.00 | 0.00 |
February | 0.390533E+10 | 0.371703E+10 | 0.453573E+10 | 0.280773E+10 | 0.172799E+10 | 0.00 | 0.00 |
March | 0.464095E+10 | 0.360481E+10 | 0.540386E+10 | 0.288282E+10 | 0.252104E+10 | 0.00 | 0.00 |
April | 0.452473E+10 | 0.289261E+10 | 0.551966E+10 | 0.239686E+10 | 0.312280E+10 | 0.00 | 0.00 |
May | 0.386784E+10 | 0.248602E+10 | 0.521411E+10 | 0.155283E+10 | 0.366128E+10 | 0.00 | 0.00 |
June | 0.327672E+10 | 0.191376E+10 | 0.461648E+10 | 0.123897E+10 | 0.337751E+10 | 0.00 | 0.00 |
July | 0.421465E+10 | 0.177956E+10 | 0.520215E+10 | 0.190473E+10 | 0.329742E+10 | 0.00 | 0.00 |
August | 0.529249E+10 | 0.169512E+10 | 0.558959E+10 | 0.260629E+10 | 0.298330E+10 | 0.00 | 0.00 |
September | 0.581039E+10 | 0.227994E+10 | 0.599563E+10 | 0.331183E+10 | 0.268379E+10 | 0.00 | 0.00 |
October | 0.537665E+10 | 0.310442E+10 | 0.561177E+10 | 0.346542E+10 | 0.214634E+10 | 0.00 | 0.00 |
November | 0.262350E+10 | 0.366276E+10 | 0.320934E+10 | 0.183895E+10 | 0.137039E+10 | 0.00 | 0.00 |
December | 0.299828E+10 | 0.469246E+10 | 0.346935E+10 | 0.224475E+10 | 0.122461E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.490123E+11 | 0.364002E+11 | 0.576319E+11 | 0.281891E+11 | 0.294428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.248077E+10 | 0.169512E+10 | 0.320934E+10 | 0.123897E+10 | 0.122461E+10 | 0.00 | 0.00 |
Maximum of Months | 0.581039E+10 | 0.469246E+10 | 0.599563E+10 | 0.346542E+10 | 0.366128E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.195914E+09 | 0.330874E+10 | 0.835102E+09 | 0.246298E+09 | 0.588805E+09 | 0.00 | 0.00 |
February | 0.662148E+09 | 0.261707E+10 | 0.135234E+10 | 0.508284E+09 | 0.844056E+09 | 0.00 | 0.00 |
March | 0.130158E+10 | 0.237659E+10 | 0.209797E+10 | 0.708158E+09 | 0.138981E+10 | 0.00 | 0.00 |
April | 0.247727E+10 | 0.187282E+10 | 0.308892E+10 | 0.118109E+10 | 0.190783E+10 | 0.00 | 0.00 |
May | 0.371211E+10 | 0.162053E+10 | 0.410656E+10 | 0.166798E+10 | 0.243857E+10 | 0.00 | 0.00 |
June | 0.352014E+10 | 0.124313E+10 | 0.382188E+10 | 0.148356E+10 | 0.233831E+10 | 0.00 | 0.00 |
July | 0.512567E+10 | 0.118011E+10 | 0.487866E+10 | 0.256407E+10 | 0.231459E+10 | 0.00 | 0.00 |
August | 0.435603E+10 | 0.112189E+10 | 0.403635E+10 | 0.206100E+10 | 0.197535E+10 | 0.00 | 0.00 |
September | 0.305448E+10 | 0.150851E+10 | 0.318123E+10 | 0.152650E+10 | 0.165473E+10 | 0.00 | 0.00 |
October | 0.133863E+10 | 0.207169E+10 | 0.187136E+10 | 0.762483E+09 | 0.110888E+10 | 0.00 | 0.00 |
November | 0.323148E+09 | 0.254685E+10 | 0.901921E+09 | 0.254416E+09 | 0.647504E+09 | 0.00 | 0.00 |
December | 0.261276E+09 | 0.331491E+10 | 0.783542E+09 | 0.268548E+09 | 0.514994E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.263284E+11 | 0.247828E+11 | 0.309558E+11 | 0.132324E+11 | 0.177234E+11 | 0.00 | 0.00 |
Minimum of Months | 0.195914E+09 | 0.112189E+10 | 0.783542E+09 | 0.246298E+09 | 0.514994E+09 | 0.00 | 0.00 |
Maximum of Months | 0.512567E+10 | 0.331491E+10 | 0.487866E+10 | 0.256407E+10 | 0.243857E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 2451733.87 | 0.535482E+10 | 0.739021E+09 | 0.00 | 0.739021E+09 | 0.00 | 0.00 |
February | 0.100712E+09 | 0.429498E+10 | 0.103865E+10 | 0.00 | 0.103865E+10 | 0.00 | 0.00 |
March | 0.409505E+09 | 0.376634E+10 | 0.169425E+10 | 0.00 | 0.169425E+10 | 0.00 | 0.00 |
April | 0.109135E+10 | 0.281688E+10 | 0.232012E+10 | 8147063.03 | 0.231197E+10 | 0.00 | 0.00 |
May | 0.182796E+10 | 0.235891E+10 | 0.308481E+10 | 91431173.92 | 0.299338E+10 | 0.00 | 0.00 |
June | 0.198053E+10 | 0.176453E+10 | 0.313887E+10 | 0.206969E+09 | 0.293190E+10 | 0.00 | 0.00 |
July | 0.226358E+10 | 0.166231E+10 | 0.308267E+10 | 0.241313E+09 | 0.284136E+10 | 0.00 | 0.00 |
August | 0.199173E+10 | 0.167760E+10 | 0.249551E+10 | 67191859.72 | 0.242831E+10 | 0.00 | 0.00 |
September | 0.101205E+10 | 0.241361E+10 | 0.187608E+10 | 535300.29 | 0.187554E+10 | 0.00 | 0.00 |
October | 0.324144E+09 | 0.344009E+10 | 0.132829E+10 | 0.00 | 0.132829E+10 | 0.00 | 0.00 |
November | 39085239.28 | 0.434206E+10 | 0.809698E+09 | 0.00 | 0.809698E+09 | 0.00 | 0.00 |
December | 918981.84 | 0.549645E+10 | 0.627977E+09 | 0.00 | 0.627977E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.110440E+11 | 0.393886E+11 | 0.222359E+11 | 0.615587E+09 | 0.216204E+11 | 0.00 | 0.00 |
Minimum of Months | 918981.84 | 0.166231E+10 | 0.627977E+09 | 0.00 | 0.627977E+09 | 0.00 | 0.00 |
Maximum of Months | 0.226358E+10 | 0.549645E+10 | 0.313887E+10 | 0.241313E+09 | 0.299338E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.136730E+09 | 0.340919E+10 | 0.791722E+09 | 0.200757E+09 | 0.590965E+09 | 0.00 | 0.00 |
February | 0.564809E+09 | 0.266422E+10 | 0.131211E+10 | 0.465718E+09 | 0.846396E+09 | 0.00 | 0.00 |
March | 0.134907E+10 | 0.236703E+10 | 0.216897E+10 | 0.785217E+09 | 0.138376E+10 | 0.00 | 0.00 |
April | 0.267946E+10 | 0.178911E+10 | 0.325390E+10 | 0.135213E+10 | 0.190177E+10 | 0.00 | 0.00 |
May | 0.308593E+10 | 0.154213E+10 | 0.357743E+10 | 0.124362E+10 | 0.233381E+10 | 0.00 | 0.00 |
June | 0.389762E+10 | 0.119799E+10 | 0.414596E+10 | 0.180365E+10 | 0.234231E+10 | 0.00 | 0.00 |
July | 0.393866E+10 | 0.108275E+10 | 0.398944E+10 | 0.179035E+10 | 0.219908E+10 | 0.00 | 0.00 |
August | 0.409939E+10 | 0.107464E+10 | 0.392149E+10 | 0.196168E+10 | 0.195982E+10 | 0.00 | 0.00 |
September | 0.251621E+10 | 0.150364E+10 | 0.280627E+10 | 0.129445E+10 | 0.151182E+10 | 0.00 | 0.00 |
October | 0.128696E+10 | 0.215504E+10 | 0.188987E+10 | 0.803012E+09 | 0.108686E+10 | 0.00 | 0.00 |
November | 0.276531E+09 | 0.274596E+10 | 0.896460E+09 | 0.253099E+09 | 0.643361E+09 | 0.00 | 0.00 |
December | 0.184998E+09 | 0.349448E+10 | 0.759831E+09 | 0.244643E+09 | 0.515188E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.240164E+11 | 0.250262E+11 | 0.295135E+11 | 0.121983E+11 | 0.173151E+11 | 0.00 | 0.00 |
Minimum of Months | 0.136730E+09 | 0.107464E+10 | 0.759831E+09 | 0.200757E+09 | 0.515188E+09 | 0.00 | 0.00 |
Maximum of Months | 0.409939E+10 | 0.349448E+10 | 0.414596E+10 | 0.196168E+10 | 0.234231E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252069E+10 | 0.467657E+10 | 0.326413E+10 | 0.193783E+10 | 0.132630E+10 | 0.00 | 0.00 |
February | 0.397196E+10 | 0.384963E+10 | 0.453555E+10 | 0.280762E+10 | 0.172793E+10 | 0.00 | 0.00 |
March | 0.475855E+10 | 0.371466E+10 | 0.540366E+10 | 0.288270E+10 | 0.252095E+10 | 0.00 | 0.00 |
April | 0.466820E+10 | 0.291021E+10 | 0.551946E+10 | 0.239676E+10 | 0.312270E+10 | 0.00 | 0.00 |
May | 0.403821E+10 | 0.246445E+10 | 0.521393E+10 | 0.155276E+10 | 0.366116E+10 | 0.00 | 0.00 |
June | 0.344410E+10 | 0.187633E+10 | 0.461633E+10 | 0.123892E+10 | 0.337741E+10 | 0.00 | 0.00 |
July | 0.432534E+10 | 0.178813E+10 | 0.520197E+10 | 0.190465E+10 | 0.329732E+10 | 0.00 | 0.00 |
August | 0.535200E+10 | 0.177955E+10 | 0.558940E+10 | 0.260618E+10 | 0.298321E+10 | 0.00 | 0.00 |
September | 0.585282E+10 | 0.245677E+10 | 0.599540E+10 | 0.331170E+10 | 0.268370E+10 | 0.00 | 0.00 |
October | 0.540507E+10 | 0.339797E+10 | 0.561155E+10 | 0.346528E+10 | 0.214627E+10 | 0.00 | 0.00 |
November | 0.263222E+10 | 0.393370E+10 | 0.320921E+10 | 0.183887E+10 | 0.137034E+10 | 0.00 | 0.00 |
December | 0.301910E+10 | 0.490844E+10 | 0.346922E+10 | 0.224465E+10 | 0.122456E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.499883E+11 | 0.377564E+11 | 0.576298E+11 | 0.281879E+11 | 0.294419E+11 | 0.00 | 0.00 |
Minimum of Months | 0.252069E+10 | 0.177955E+10 | 0.320921E+10 | 0.123892E+10 | 0.122456E+10 | 0.00 | 0.00 |
Maximum of Months | 0.585282E+10 | 0.490844E+10 | 0.599540E+10 | 0.346528E+10 | 0.366116E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.198209E+09 | 0.342217E+10 | 0.835091E+09 | 0.246294E+09 | 0.588798E+09 | 0.00 | 0.00 |
February | 0.671202E+09 | 0.271211E+10 | 0.135232E+10 | 0.508275E+09 | 0.844046E+09 | 0.00 | 0.00 |
March | 0.134327E+10 | 0.244841E+10 | 0.209794E+10 | 0.708146E+09 | 0.138980E+10 | 0.00 | 0.00 |
April | 0.255480E+10 | 0.189933E+10 | 0.308888E+10 | 0.118107E+10 | 0.190781E+10 | 0.00 | 0.00 |
May | 0.380354E+10 | 0.165095E+10 | 0.410651E+10 | 0.166796E+10 | 0.243855E+10 | 0.00 | 0.00 |
June | 0.360538E+10 | 0.125824E+10 | 0.382183E+10 | 0.148354E+10 | 0.233829E+10 | 0.00 | 0.00 |
July | 0.518451E+10 | 0.123286E+10 | 0.487859E+10 | 0.256403E+10 | 0.231456E+10 | 0.00 | 0.00 |
August | 0.438562E+10 | 0.118794E+10 | 0.403630E+10 | 0.206097E+10 | 0.197533E+10 | 0.00 | 0.00 |
September | 0.307080E+10 | 0.160630E+10 | 0.318119E+10 | 0.152648E+10 | 0.165472E+10 | 0.00 | 0.00 |
October | 0.133604E+10 | 0.223427E+10 | 0.187133E+10 | 0.762470E+09 | 0.110886E+10 | 0.00 | 0.00 |
November | 0.317521E+09 | 0.275776E+10 | 0.901909E+09 | 0.254412E+09 | 0.647497E+09 | 0.00 | 0.00 |
December | 0.259527E+09 | 0.352031E+10 | 0.783531E+09 | 0.268543E+09 | 0.514988E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.267304E+11 | 0.259307E+11 | 0.309554E+11 | 0.132322E+11 | 0.177232E+11 | 0.00 | 0.00 |
Minimum of Months | 0.198209E+09 | 0.118794E+10 | 0.783531E+09 | 0.246294E+09 | 0.514988E+09 | 0.00 | 0.00 |
Maximum of Months | 0.518451E+10 | 0.352031E+10 | 0.487859E+10 | 0.256403E+10 | 0.243855E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 1400919.18 | 0.545913E+10 | 0.739038E+09 | 0.00 | 0.739038E+09 | 0.00 | 0.00 |
February | 87766052.48 | 0.442933E+10 | 0.103868E+10 | 0.00 | 0.103868E+10 | 0.00 | 0.00 |
March | 0.344877E+09 | 0.394740E+10 | 0.169429E+10 | 0.00 | 0.169429E+10 | 0.00 | 0.00 |
April | 0.970346E+09 | 0.299312E+10 | 0.232017E+10 | 8147302.51 | 0.231202E+10 | 0.00 | 0.00 |
May | 0.168258E+10 | 0.250476E+10 | 0.308488E+10 | 91433861.41 | 0.299344E+10 | 0.00 | 0.00 |
June | 0.185679E+10 | 0.185426E+10 | 0.313893E+10 | 0.206975E+09 | 0.293196E+10 | 0.00 | 0.00 |
July | 0.217856E+10 | 0.172674E+10 | 0.308274E+10 | 0.241320E+09 | 0.284142E+10 | 0.00 | 0.00 |
August | 0.193539E+10 | 0.172039E+10 | 0.249556E+10 | 67193834.73 | 0.242836E+10 | 0.00 | 0.00 |
September | 0.970259E+09 | 0.244863E+10 | 0.187612E+10 | 535316.02 | 0.187558E+10 | 0.00 | 0.00 |
October | 0.307215E+09 | 0.343994E+10 | 0.132831E+10 | 0.00 | 0.132831E+10 | 0.00 | 0.00 |
November | 38186169.93 | 0.430780E+10 | 0.809717E+09 | 0.00 | 0.809717E+09 | 0.00 | 0.00 |
December | 905988.62 | 0.551802E+10 | 0.627991E+09 | 0.00 | 0.627991E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103743E+11 | 0.403495E+11 | 0.222364E+11 | 0.615605E+09 | 0.216208E+11 | 0.00 | 0.00 |
Minimum of Months | 905988.62 | 0.172039E+10 | 0.627991E+09 | 0.00 | 0.627991E+09 | 0.00 | 0.00 |
Maximum of Months | 0.217856E+10 | 0.551802E+10 | 0.313893E+10 | 0.241320E+09 | 0.299344E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.129966E+09 | 0.347371E+10 | 0.791735E+09 | 0.200761E+09 | 0.590973E+09 | 0.00 | 0.00 |
February | 0.544531E+09 | 0.272727E+10 | 0.131213E+10 | 0.465727E+09 | 0.846408E+09 | 0.00 | 0.00 |
March | 0.129711E+10 | 0.244044E+10 | 0.216901E+10 | 0.785232E+09 | 0.138377E+10 | 0.00 | 0.00 |
April | 0.260440E+10 | 0.184202E+10 | 0.325395E+10 | 0.135216E+10 | 0.190179E+10 | 0.00 | 0.00 |
May | 0.301121E+10 | 0.158408E+10 | 0.357749E+10 | 0.124365E+10 | 0.233384E+10 | 0.00 | 0.00 |
June | 0.384638E+10 | 0.120235E+10 | 0.414603E+10 | 0.180368E+10 | 0.234234E+10 | 0.00 | 0.00 |
July | 0.390521E+10 | 0.108403E+10 | 0.398949E+10 | 0.179039E+10 | 0.219911E+10 | 0.00 | 0.00 |
August | 0.408842E+10 | 0.104836E+10 | 0.392156E+10 | 0.196171E+10 | 0.195984E+10 | 0.00 | 0.00 |
September | 0.250123E+10 | 0.148644E+10 | 0.280632E+10 | 0.129447E+10 | 0.151184E+10 | 0.00 | 0.00 |
October | 0.127452E+10 | 0.213056E+10 | 0.188990E+10 | 0.803028E+09 | 0.108687E+10 | 0.00 | 0.00 |
November | 0.272127E+09 | 0.272825E+10 | 0.896474E+09 | 0.253104E+09 | 0.643370E+09 | 0.00 | 0.00 |
December | 0.180966E+09 | 0.350713E+10 | 0.759844E+09 | 0.244648E+09 | 0.515195E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.236561E+11 | 0.252546E+11 | 0.295139E+11 | 0.121986E+11 | 0.173154E+11 | 0.00 | 0.00 |
Minimum of Months | 0.129966E+09 | 0.104836E+10 | 0.759844E+09 | 0.200761E+09 | 0.515195E+09 | 0.00 | 0.00 |
Maximum of Months | 0.408842E+10 | 0.350713E+10 | 0.414603E+10 | 0.196171E+10 | 0.234234E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.244019E+10 | 0.482486E+10 | 0.326426E+10 | 0.193791E+10 | 0.132635E+10 | 0.00 | 0.00 |
February | 0.385332E+10 | 0.394128E+10 | 0.453573E+10 | 0.280773E+10 | 0.172799E+10 | 0.00 | 0.00 |
March | 0.460852E+10 | 0.382569E+10 | 0.540386E+10 | 0.288282E+10 | 0.252104E+10 | 0.00 | 0.00 |
April | 0.450133E+10 | 0.304097E+10 | 0.551966E+10 | 0.239686E+10 | 0.312280E+10 | 0.00 | 0.00 |
May | 0.385680E+10 | 0.260027E+10 | 0.521411E+10 | 0.155283E+10 | 0.366128E+10 | 0.00 | 0.00 |
June | 0.328119E+10 | 0.198569E+10 | 0.461648E+10 | 0.123897E+10 | 0.337751E+10 | 0.00 | 0.00 |
July | 0.422199E+10 | 0.184285E+10 | 0.520215E+10 | 0.190473E+10 | 0.329742E+10 | 0.00 | 0.00 |
August | 0.528637E+10 | 0.177190E+10 | 0.558959E+10 | 0.260629E+10 | 0.298330E+10 | 0.00 | 0.00 |
September | 0.578827E+10 | 0.240946E+10 | 0.599563E+10 | 0.331183E+10 | 0.268379E+10 | 0.00 | 0.00 |
October | 0.533076E+10 | 0.332492E+10 | 0.561177E+10 | 0.346542E+10 | 0.214634E+10 | 0.00 | 0.00 |
November | 0.257635E+10 | 0.392900E+10 | 0.320934E+10 | 0.183895E+10 | 0.137039E+10 | 0.00 | 0.00 |
December | 0.295322E+10 | 0.499162E+10 | 0.346935E+10 | 0.224475E+10 | 0.122461E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.486983E+11 | 0.384885E+11 | 0.576319E+11 | 0.281891E+11 | 0.294428E+11 | 0.00 | 0.00 |
Minimum of Months | 0.244019E+10 | 0.177190E+10 | 0.320934E+10 | 0.123897E+10 | 0.122461E+10 | 0.00 | 0.00 |
Maximum of Months | 0.578827E+10 | 0.499162E+10 | 0.599563E+10 | 0.346542E+10 | 0.366128E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.189909E+09 | 0.348227E+10 | 0.835102E+09 | 0.246298E+09 | 0.588805E+09 | 0.00 | 0.00 |
February | 0.646897E+09 | 0.277249E+10 | 0.135234E+10 | 0.508284E+09 | 0.844056E+09 | 0.00 | 0.00 |
March | 0.128992E+10 | 0.252673E+10 | 0.209797E+10 | 0.708158E+09 | 0.138981E+10 | 0.00 | 0.00 |
April | 0.247021E+10 | 0.197211E+10 | 0.308892E+10 | 0.118109E+10 | 0.190783E+10 | 0.00 | 0.00 |
May | 0.371519E+10 | 0.169847E+10 | 0.410656E+10 | 0.166798E+10 | 0.243857E+10 | 0.00 | 0.00 |
June | 0.353323E+10 | 0.129221E+10 | 0.382188E+10 | 0.148356E+10 | 0.233831E+10 | 0.00 | 0.00 |
July | 0.514247E+10 | 0.122470E+10 | 0.487866E+10 | 0.256407E+10 | 0.231459E+10 | 0.00 | 0.00 |
August | 0.436132E+10 | 0.117237E+10 | 0.403635E+10 | 0.206100E+10 | 0.197535E+10 | 0.00 | 0.00 |
September | 0.304743E+10 | 0.159385E+10 | 0.318123E+10 | 0.152650E+10 | 0.165473E+10 | 0.00 | 0.00 |
October | 0.131830E+10 | 0.222085E+10 | 0.187136E+10 | 0.762483E+09 | 0.110888E+10 | 0.00 | 0.00 |
November | 0.312073E+09 | 0.273746E+10 | 0.901921E+09 | 0.254416E+09 | 0.647504E+09 | 0.00 | 0.00 |
December | 0.253029E+09 | 0.352808E+10 | 0.783542E+09 | 0.268548E+09 | 0.514994E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.262800E+11 | 0.262216E+11 | 0.309558E+11 | 0.132324E+11 | 0.177234E+11 | 0.00 | 0.00 |
Minimum of Months | 0.189909E+09 | 0.117237E+10 | 0.783542E+09 | 0.246298E+09 | 0.514994E+09 | 0.00 | 0.00 |
Maximum of Months | 0.514247E+10 | 0.352808E+10 | 0.487866E+10 | 0.256407E+10 | 0.243857E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.11 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.09 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.03 | 5.25 | 4.23 | 1.21 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.01 | 7.49 | 3.85 | 3.74 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.79 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.40 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.56 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.54 | 10.74 | 2.23 | 5.46 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.18 | 7.19 | 4.02 | 2.09 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.12 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.11 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.56 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.48 | 7.20 | 8.40 | 3.88 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.15 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.40 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.20 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.35 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.72 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.76 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.67 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.67 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.47 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.93 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.42 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.42 | 0.00 | 0.00 | 3.88 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.76 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM}[C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -1.9 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.18 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.56 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.56 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.48 | 11-JAN-21:00 | 11.10 | 10.00 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 12.41 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.44 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.27 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.57 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.72 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.16 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.12 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.96 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.04 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.70 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.48 | 11.10 | 6.70 | 0.00 | 6.35 | 0.00 | 0.00 | |
Maximum of Months | 20.12 | 28.90 | 15.70 | 6.70 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum}[C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.48 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.34 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.09 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.76 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.92 | 2.10 | 6.88 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.00 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.09 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SHWSYS1 WATER HEATER
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.130507E+10 | -.452614E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -969690399.7 | 70.25 | 0.00 | 0.00 |
February | 0.122036E+10 | -.414211E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -861988980.3 | 70.22 | 0.00 | 0.00 |
March | 0.159011E+10 | -.484931E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -923592565.8 | 69.21 | 0.00 | 0.00 |
April | 0.109961E+10 | -.425329E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -911175179.0 | 70.40 | 0.00 | 0.00 |
May | 0.111644E+10 | -.438731E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -932061877.8 | 70.23 | 0.00 | 0.00 |
June | 0.102397E+10 | -.420154E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -895121831.2 | 70.10 | 0.00 | 0.00 |
July | 0.571845E+09 | -.384653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -949629273.2 | 71.50 | 0.00 | 0.00 |
August | 0.928329E+09 | -.421539E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -927408457.6 | 70.33 | 0.00 | 0.00 |
September | 0.675270E+09 | -.384759E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -912303695.9 | 71.05 | 0.00 | 0.00 |
October | 0.838318E+09 | -.410187E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -949670865.2 | 70.95 | 0.00 | 0.00 |
November | 0.104120E+10 | -.418902E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -918577747.2 | 70.50 | 0.00 | 0.00 |
December | 0.106611E+10 | -.430217E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -965345892.2 | 70.75 | 0.00 | 0.00 |
Annual Sum or Average | 0.124766E+11 | -.508623E+11 | 8760.00 | -.111166E+11 | 70.46 | |||||
Minimum of Months | 0.571845E+09 | -.484931E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -969690399.7 | 69.21 | 0.00 | 0.00 |
Maximum of Months | 0.159011E+10 | -.384653E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -861988980.3 | 71.50 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | ||||||||||
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.137938E+10 | 38013.98 | 03-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.122421E+09 | 14019.08 | 21-FEB-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4718335.41 | 2640.82 | 06-MAR-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9331214.84 | 5963.10 | 27-NOV-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115451E+09 | 12251.72 | 26-DEC-05:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163130E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.137938E+10 | 38013.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270674E+10 | 24246.07 | 03-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.908366E+09 | 24165.36 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174212E+09 | 24225.22 | 06-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 9903442.07 | 1716.76 | 17-APR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 31329709.88 | 5595.13 | 23-OCT-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.449528E+09 | 24299.21 | 27-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.120369E+10 | 24241.26 | 18-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.548377E+10 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270674E+10 | 24299.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.621726E+10 | 24164.00 | 03-JAN-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.352141E+10 | 24212.82 | 27-FEB-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167419E+10 | 24180.87 | 13-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.570705E+09 | 24188.11 | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 12785966.05 | 2176.14 | 18-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4054571.98 | 900.48 | 28-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.762528E+09 | 24201.82 | 23-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273153E+10 | 24223.60 | 27-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489401E+10 | 24180.83 | 16-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203885E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.621726E+10 | 24223.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.513907E+10 | 6569.50 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.346968E+10 | 6466.18 | 24-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221444E+10 | 6469.09 | 10-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.113073E+10 | 6455.65 | 15-APR-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.350864E+09 | 6441.95 | 24-MAY-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 60653790.83 | 6452.54 | 14-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 4355010.17 | 536.14 | 21-AUG-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153412E+09 | 6451.60 | 27-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.135835E+10 | 6470.12 | 26-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280116E+10 | 6462.80 | 27-NOV-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432654E+10 | 6454.55 | 16-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210093E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.513907E+10 | 6569.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.515617E+10 | 7996.32 | 12-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.356784E+10 | 8021.96 | 24-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.252107E+10 | 8025.53 | 10-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129796E+10 | 8008.79 | 15-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.598953E+09 | 7991.10 | 24-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182039E+09 | 8005.06 | 14-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 55053969.24 | 2073.91 | 15-JUL-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 69892968.16 | 2531.00 | 18-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.463030E+09 | 8003.76 | 27-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.182247E+10 | 8013.61 | 20-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.330874E+10 | 8016.14 | 27-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.448963E+10 | 8006.42 | 16-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235329E+11 | |||||||
Minimum of Months | 55053969.24 | 2073.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.515617E+10 | 8025.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.627268E+10 | 11159.71 | 12-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424321E+10 | 11195.33 | 24-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315606E+10 | 11200.27 | 10-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189612E+10 | 11177.09 | 15-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.888632E+09 | 11152.34 | 24-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.332138E+09 | 11171.74 | 14-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 92440895.55 | 3131.30 | 18-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.117488E+09 | 3507.24 | 19-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.526450E+09 | 11169.94 | 27-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210575E+10 | 11183.68 | 20-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.399476E+10 | 11187.35 | 07-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.538555E+10 | 11173.83 | 16-DEC-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.290113E+11 | |||||||
Minimum of Months | 92440895.55 | 3131.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.627268E+10 | 11200.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.558598E+10 | 8907.87 | 12-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.400152E+10 | 8936.43 | 24-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.312948E+10 | 8905.59 | 08-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.182245E+10 | 8921.76 | 15-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.859973E+09 | 8902.05 | 24-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.358285E+09 | 8917.61 | 14-JUN-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145116E+09 | 2246.80 | 17-JUL-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.191960E+09 | 2883.80 | 21-AUG-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.626922E+09 | 7381.37 | 27-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.227123E+10 | 8927.13 | 20-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.374671E+10 | 8929.88 | 07-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489022E+10 | 8919.16 | 16-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.276298E+11 | |||||||
Minimum of Months | 0.145116E+09 | 2246.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.558598E+10 | 8936.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.343559E+10 | 5063.57 | 12-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218780E+10 | 5082.92 | 10-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.139704E+10 | 5204.18 | 02-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.679652E+09 | 5217.59 | 08-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.120486E+09 | 4891.38 | 18-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1807430.70 | 986.08 | 15-JUN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 4360185.87 | 1043.70 | 28-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.294945E+09 | 5221.77 | 28-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.104814E+10 | 5119.76 | 17-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233417E+10 | 5067.93 | 16-DEC-05:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.115040E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.343559E+10 | 5221.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.379848E+10 | 6755.75 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253546E+10 | 6781.47 | 10-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183818E+10 | 6943.76 | 02-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.886603E+09 | 6794.07 | 01-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.390994E+09 | 6525.82 | 18-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 82198788.19 | 2997.68 | 15-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6432768.21 | 1766.50 | 13-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 13985001.84 | 1814.29 | 21-AUG-04:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143944E+09 | 2830.44 | 27-SEP-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.781529E+09 | 6776.55 | 30-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.181774E+10 | 6830.87 | 17-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.296305E+10 | 6761.83 | 16-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.152586E+11 | |||||||
Minimum of Months | 6432768.21 | 1766.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.379848E+10 | 6943.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.801968E+10 | 8967.54 | 27-JAN-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.558400E+10 | 8995.27 | 23-FEB-13:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507613E+10 | 9092.84 | 23-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.339061E+10 | 9234.61 | 08-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.232615E+10 | 9000.30 | 30-MAY-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.131223E+10 | 9004.41 | 06-JUN-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.579571E+09 | 8993.17 | 12-JUL-06:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.495558E+09 | 9006.95 | 04-AUG-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.106396E+10 | 9006.85 | 25-SEP-11:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.251332E+10 | 9011.11 | 06-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.513022E+10 | 9061.39 | 17-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.667868E+10 | 8976.61 | 28-DEC-17:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.421701E+11 | |||||||
Minimum of Months | 0.495558E+09 | 8967.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.801968E+10 | 9234.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.413142E+10 | 7510.47 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285007E+10 | 7539.04 | 10-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.229895E+10 | 7566.52 | 01-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128239E+10 | 7566.52 | 08-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.486684E+09 | 7254.84 | 18-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156704E+09 | 2879.83 | 09-JUN-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5129041.75 | 1590.12 | 18-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 27019705.35 | 1646.91 | 18-AUG-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148143E+09 | 2829.89 | 28-SEP-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103315E+10 | 7516.14 | 23-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.215773E+10 | 7566.52 | 17-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327581E+10 | 7517.30 | 16-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178532E+11 | |||||||
Minimum of Months | 5129041.75 | 1590.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.413142E+10 | 7566.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332105E+10 | 5925.11 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.195634E+10 | 5925.67 | 01-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.108146E+10 | 5923.53 | 08-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.456421E+09 | 5917.70 | 10-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 45633736.28 | 5913.44 | 18-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 2751902.86 | 1921.49 | 14-JUN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 9567582.29 | 980.44 | 28-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.476589E+09 | 5935.82 | 27-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.148288E+10 | 5938.48 | 27-NOV-05:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.257973E+10 | 6075.56 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.114124E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332105E+10 | 6075.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.439634E+10 | 8660.84 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292109E+10 | 8661.81 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.207026E+10 | 8658.52 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.995641E+09 | 8648.69 | 08-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424247E+09 | 8643.82 | 18-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147851E+09 | 3125.81 | 06-JUN-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 37197000.38 | 1918.25 | 17-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 55716432.21 | 2732.25 | 19-AUG-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.342382E+09 | 3429.15 | 30-SEP-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.136006E+10 | 8670.20 | 23-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.276547E+10 | 8681.22 | 27-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.376629E+10 | 8671.66 | 16-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.192825E+11 | |||||||
Minimum of Months | 37197000.38 | 1918.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.439634E+10 | 8681.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.464178E+10 | 11014.39 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.289340E+10 | 11015.17 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200784E+10 | 11011.22 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.108468E+10 | 10998.88 | 08-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.396258E+09 | 10992.57 | 18-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.128295E+09 | 4352.23 | 14-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5820903.82 | 1591.92 | 18-JUL-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 29474337.59 | 2099.21 | 05-AUG-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.182269E+09 | 3430.87 | 27-SEP-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.111315E+10 | 11025.97 | 23-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.268500E+10 | 11039.49 | 27-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.378238E+10 | 11027.70 | 16-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189504E+11 | |||||||
Minimum of Months | 5820903.82 | 1591.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.464178E+10 | 11039.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.439886E+10 | 8884.73 | 12-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.298324E+10 | 8885.73 | 01-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.228112E+10 | 8882.35 | 08-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122578E+10 | 8872.27 | 08-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.489947E+09 | 8867.27 | 18-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.199573E+09 | 3300.22 | 14-JUN-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 50570985.56 | 1925.66 | 13-JUL-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 87232326.03 | 2437.17 | 18-AUG-04:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.330446E+09 | 3393.22 | 27-SEP-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146498E+10 | 8894.34 | 23-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282582E+10 | 8905.68 | 27-NOV-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.377088E+10 | 8895.85 | 16-DEC-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201084E+11 | |||||||
Minimum of Months | 50570985.56 | 1925.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.439886E+10 | 8905.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT_HEATC
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.166006E+11 | 33131.93 | 07-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113489E+11 | 29212.70 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.552136E+10 | 24731.31 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.264849E+10 | 19077.52 | 19-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.659038E+09 | 11917.15 | 18-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34261499.10 | 3203.37 | 15-JUN-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 62748749.23 | 5888.55 | 27-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.104132E+10 | 11152.99 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.733428E+10 | 23344.93 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.136924E+11 | 28509.32 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.589433E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166006E+11 | 33131.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID_HEATC
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188056E+11 | 27704.30 | 06-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135299E+11 | 27704.30 | 09-FEB-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.877659E+10 | 26283.42 | 01-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.466770E+10 | 20719.81 | 19-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164132E+10 | 13874.35 | 18-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194078E+09 | 5442.42 | 15-JUN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 303600.94 | 506.00 | 03-JUL-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 10753334.40 | 1745.25 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.302035E+09 | 8042.71 | 27-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270733E+10 | 12972.76 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.102154E+11 | 24768.94 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.165950E+11 | 27704.30 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.774461E+11 | |||||||
Minimum of Months | 303600.94 | 506.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.188056E+11 | 27704.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP_HEATC
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum}[W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.179959E+11 | 31757.89 | 07-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128742E+11 | 29528.03 | 18-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.814375E+10 | 25348.12 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426142E+10 | 19913.97 | 19-APR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147451E+10 | 13200.09 | 18-MAY-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160564E+09 | 4945.73 | 15-JUN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 6268164.83 | 1255.59 | 01-AUG-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.255152E+09 | 7505.77 | 27-SEP-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.239276E+10 | 12341.42 | 16-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.958411E+10 | 23870.08 | 13-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157720E+11 | 28534.46 | 26-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.729207E+11 | |||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.179959E+11 | 31757.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_BOT_COOLC DXCOIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 94095934.85 | 68298663.41 | 7747.39 | 11-JAN-14:00 | 5752.69 | 0.00 |
February | 0.00 | 0.00 | 0.111243E+10 | 0.815184E+09 | 20369.42 | 27-FEB-16:10 | 18892.14 | 0.00 |
March | 0.00 | 0.00 | 0.182161E+10 | 0.145296E+10 | 20490.39 | 18-MAR-16:00 | 20490.39 | 0.00 |
April | 0.00 | 0.00 | 0.682626E+10 | 0.617126E+10 | 54749.15 | 27-APR-16:00 | 54749.15 | 0.00 |
May | 0.00 | 0.00 | 0.146092E+11 | 0.120946E+11 | 52749.58 | 05-MAY-16:00 | 46376.62 | 0.00 |
June | 0.00 | 0.00 | 0.246482E+11 | 0.211825E+11 | 57093.61 | 28-JUN-16:00 | 57093.61 | 0.00 |
July | 0.00 | 0.00 | 0.401045E+11 | 0.327261E+11 | 78221.43 | 31-JUL-16:10 | 67240.57 | 0.00 |
August | 0.00 | 0.00 | 0.532474E+11 | 0.428691E+11 | 84939.70 | 10-AUG-16:05 | 80905.66 | 0.00 |
September | 0.00 | 0.00 | 0.254376E+11 | 0.188627E+11 | 71391.56 | 14-SEP-13:00 | 48443.55 | 0.00 |
October | 0.00 | 0.00 | 0.552696E+10 | 0.468122E+10 | 39067.17 | 04-OCT-15:10 | 39067.17 | 0.00 |
November | 0.00 | 0.00 | 0.158660E+10 | 0.965428E+09 | 31812.70 | 04-NOV-13:30 | 23146.59 | 0.00 |
December | 0.00 | 0.00 | 9782727.80 | 8119695.39 | 3468.04 | 14-DEC-12:00 | 2906.42 | 0.00 |
Annual Sum or Average | 0.175025E+12 | 0.141898E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 9782727.80 | 8119695.39 | 3468.04 | 2906.42 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.532474E+11 | 0.428691E+11 | 84939.70 | 80905.66 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_MID_COOLC DXCOIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 82745291.73 | 61908618.01 | 6469.10 | 11-JAN-15:00 | 4926.44 | 0.00 |
February | 0.00 | 0.00 | 0.959865E+09 | 0.735404E+09 | 20059.35 | 27-FEB-15:00 | 20059.35 | 0.00 |
March | 0.00 | 0.00 | 0.153677E+10 | 0.126396E+10 | 18503.82 | 18-MAR-14:00 | 18503.82 | 0.00 |
April | 0.00 | 0.00 | 0.573644E+10 | 0.528741E+10 | 49232.35 | 27-APR-15:00 | 49232.35 | 0.00 |
May | 0.00 | 0.00 | 0.122278E+11 | 0.104031E+11 | 42776.90 | 05-MAY-16:00 | 38174.97 | 0.00 |
June | 0.00 | 0.00 | 0.202835E+11 | 0.178111E+11 | 50039.67 | 28-JUN-16:00 | 50039.67 | 0.00 |
July | 0.00 | 0.00 | 0.331874E+11 | 0.279048E+11 | 68752.20 | 31-JUL-16:00 | 58599.90 | 0.00 |
August | 0.00 | 0.00 | 0.436408E+11 | 0.360353E+11 | 75889.74 | 29-AUG-14:40 | 64260.11 | 0.00 |
September | 0.00 | 0.00 | 0.207004E+11 | 0.158495E+11 | 58852.22 | 14-SEP-13:00 | 40344.10 | 0.00 |
October | 0.00 | 0.00 | 0.452357E+10 | 0.389943E+10 | 33577.77 | 04-OCT-15:00 | 33577.77 | 0.00 |
November | 0.00 | 0.00 | 0.134612E+10 | 0.852388E+09 | 28187.07 | 04-NOV-13:00 | 21897.37 | 0.00 |
December | 0.00 | 0.00 | 9946435.13 | 8707120.15 | 2949.08 | 14-DEC-12:00 | 2548.89 | 0.00 |
Annual Sum or Average | 0.144235E+12 | 0.120113E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 9946435.13 | 8707120.15 | 2949.08 | 2548.89 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.436408E+11 | 0.360353E+11 | 75889.74 | 64260.11 | 0.00 |
Report: CoilReportMonthly
For: PACU_VAV_TOP_COOLC DXCOIL
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum}[W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 82813312.19 | 59864302.36 | 6609.15 | 11-JAN-15:00 | 4845.01 | 0.00 |
February | 0.00 | 0.00 | 0.986718E+09 | 0.730146E+09 | 19754.74 | 27-FEB-14:55 | 19754.74 | 0.00 |
March | 0.00 | 0.00 | 0.155689E+10 | 0.123620E+10 | 18196.22 | 18-MAR-14:00 | 18196.22 | 0.00 |
April | 0.00 | 0.00 | 0.603417E+10 | 0.544811E+10 | 58156.71 | 27-APR-15:00 | 57888.37 | 0.00 |
May | 0.00 | 0.00 | 0.130418E+11 | 0.107931E+11 | 46506.32 | 15-MAY-16:00 | 46506.32 | 0.00 |
June | 0.00 | 0.00 | 0.216188E+11 | 0.185680E+11 | 59053.55 | 28-JUN-16:00 | 59053.55 | 0.00 |
July | 0.00 | 0.00 | 0.358153E+11 | 0.294605E+11 | 78645.72 | 31-JUL-16:00 | 68027.38 | 0.00 |
August | 0.00 | 0.00 | 0.462283E+11 | 0.374939E+11 | 84240.14 | 29-AUG-14:40 | 72268.02 | 0.00 |
September | 0.00 | 0.00 | 0.211309E+11 | 0.156958E+11 | 61042.60 | 14-SEP-13:00 | 41780.16 | 0.00 |
October | 0.00 | 0.00 | 0.446526E+10 | 0.370075E+10 | 33198.97 | 04-OCT-15:00 | 33198.97 | 0.00 |
November | 0.00 | 0.00 | 0.135706E+10 | 0.831637E+09 | 29548.76 | 04-NOV-13:20 | 21868.11 | 0.00 |
December | 0.00 | 0.00 | 8397926.64 | 6880390.14 | 2983.50 | 14-DEC-12:00 | 2469.93 | 0.00 |
Annual Sum or Average | 0.152326E+12 | 0.124025E+12 | ||||||
Minimum of Months | 0.00 | 0.00 | 8397926.64 | 6880390.14 | 2983.50 | 2469.93 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.462283E+11 | 0.374939E+11 | 84240.14 | 72268.02 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 703.92 | 4573.73 | 01-JAN-10:00 | 1300.70 | 6379.88 | 25-JAN-12:06 |
February | 684.81 | 4567.42 | 26-FEB-07:20 | 1311.03 | 6403.34 | 13-FEB-12:07 |
March | 587.66 | 4574.57 | 26-MAR-06:20 | 1420.74 | 6373.43 | 01-MAR-12:08 |
April | 700.67 | 4590.54 | 30-APR-07:10 | 1223.92 | 6209.99 | 03-APR-11:15 |
May | 702.02 | 4605.91 | 29-MAY-07:40 | 1237.80 | 6016.28 | 01-MAY-11:50 |
June | 688.22 | 4618.45 | 25-JUN-06:30 | 1202.13 | 5791.26 | 02-JUN-11:15 |
July | 846.23 | 4627.81 | 30-JUL-06:35 | 1017.87 | 5603.00 | 06-JUL-11:10 |
August | 714.90 | 4628.63 | 13-AUG-06:10 | 1149.40 | 5513.92 | 31-AUG-11:15 |
September | 794.74 | 4626.50 | 03-SEP-06:40 | 1061.31 | 5654.15 | 29-SEP-11:10 |
October | 783.80 | 4617.94 | 01-OCT-07:20 | 1127.38 | 5847.46 | 31-OCT-11:10 |
November | 752.47 | 4601.04 | 05-NOV-06:30 | 1231.36 | 6089.03 | 29-NOV-12:06 |
December | 746.49 | 4586.31 | 03-DEC-08:70 | 1193.22 | 6271.73 | 27-DEC-12:09 |
Annual Sum or Average | 725.74 | 1205.84 | ||||
Minimum of Months | 587.66 | 4567.42 | 1017.87 | 5513.92 | ||
Maximum of Months | 846.23 | 4628.63 | 1420.74 | 6403.34 |
Report: FanReportMonthly
For: PACU_VAV_BOT FAN
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.239482E+10 | 0.37 | 1935.01 | 13-JAN-08:30 | 0.68 |
February | 0.212471E+10 | 0.35 | 3321.62 | 10-FEB-05:01 | 0.87 |
March | 0.263595E+10 | 0.38 | 8585.76 | 02-MAR-05:01 | 1.51 |
April | 0.254872E+10 | 0.37 | 8585.76 | 08-APR-04:01 | 1.51 |
May | 0.294345E+10 | 0.39 | 8585.76 | 01-MAY-04:02 | 1.50 |
June | 0.318092E+10 | 0.41 | 8585.76 | 01-JUN-04:02 | 1.50 |
July | 0.337198E+10 | 0.41 | 12085.91 | 24-JUL-04:02 | 1.86 |
August | 0.400585E+10 | 0.46 | 15354.09 | 09-AUG-04:01 | 2.17 |
September | 0.316198E+10 | 0.40 | 12641.69 | 14-SEP-04:01 | 1.91 |
October | 0.267838E+10 | 0.36 | 8585.76 | 02-OCT-04:02 | 1.50 |
November | 0.232907E+10 | 0.35 | 8585.76 | 06-NOV-05:02 | 1.51 |
December | 0.229570E+10 | 0.35 | 2266.99 | 07-DEC-05:01 | 0.73 |
Annual Sum or Average | 0.336715E+11 | 0.38 | |||
Minimum of Months | 0.212471E+10 | 0.35 | 1935.01 | 0.68 | |
Maximum of Months | 0.400585E+10 | 0.46 | 15354.09 | 2.17 |
Report: FanReportMonthly
For: PACU_VAV_MID FAN
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.226800E+10 | 0.39 | 1958.29 | 20-JAN-13:04 | 0.77 |
February | 0.197638E+10 | 0.38 | 1980.06 | 27-FEB-14:10 | 0.77 |
March | 0.233508E+10 | 0.40 | 2176.88 | 01-MAR-13:25 | 0.81 |
April | 0.217820E+10 | 0.38 | 5486.30 | 27-APR-04:02 | 1.34 |
May | 0.242610E+10 | 0.40 | 5486.30 | 04-MAY-04:02 | 1.34 |
June | 0.267247E+10 | 0.43 | 5486.30 | 01-JUN-04:02 | 1.34 |
July | 0.294817E+10 | 0.43 | 6706.78 | 24-JUL-04:02 | 1.51 |
August | 0.344217E+10 | 0.48 | 12111.91 | 10-AUG-04:01 | 2.19 |
September | 0.266324E+10 | 0.42 | 5993.55 | 14-SEP-04:01 | 1.41 |
October | 0.223645E+10 | 0.37 | 5486.30 | 04-OCT-04:02 | 1.35 |
November | 0.207567E+10 | 0.37 | 1945.83 | 04-NOV-13:20 | 0.76 |
December | 0.213128E+10 | 0.37 | 1959.37 | 05-DEC-12:30 | 0.77 |
Annual Sum or Average | 0.293532E+11 | 0.40 | |||
Minimum of Months | 0.197638E+10 | 0.37 | 1945.83 | 0.76 | |
Maximum of Months | 0.344217E+10 | 0.48 | 12111.91 | 2.19 |
Report: FanReportMonthly
For: PACU_VAV_TOP FAN
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportFAN ELECTRIC ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRIC POWER {Maximum}[W] | FAN ELECTRIC POWER {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.236905E+10 | 0.41 | 1697.22 | 20-JAN-13:04 | 0.68 |
February | 0.203831E+10 | 0.39 | 1763.63 | 27-FEB-14:20 | 0.69 |
March | 0.222374E+10 | 0.38 | 1885.63 | 01-MAR-13:25 | 0.71 |
April | 0.209552E+10 | 0.36 | 3895.55 | 27-APR-14:50 | 1.01 |
May | 0.231952E+10 | 0.38 | 4907.05 | 05-MAY-04:02 | 1.16 |
June | 0.250305E+10 | 0.39 | 4907.05 | 12-JUN-04:01 | 1.15 |
July | 0.279737E+10 | 0.40 | 4985.09 | 24-JUL-15:20 | 1.17 |
August | 0.319532E+10 | 0.44 | 5896.18 | 10-AUG-16:00 | 1.29 |
September | 0.237018E+10 | 0.37 | 4907.05 | 01-SEP-04:02 | 1.16 |
October | 0.210081E+10 | 0.35 | 3001.10 | 04-OCT-15:00 | 0.88 |
November | 0.197202E+10 | 0.35 | 1732.82 | 04-NOV-13:30 | 0.69 |
December | 0.212386E+10 | 0.37 | 1669.79 | 05-DEC-12:30 | 0.68 |
Annual Sum or Average | 0.281087E+11 | 0.38 | |||
Minimum of Months | 0.197202E+10 | 0.35 | 1669.79 | 0.68 | |
Maximum of Months | 0.319532E+10 | 0.44 | 5896.18 | 1.29 |
Report: PumpReportMonthly
For: SHWSYS1 PUMP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPUMP ELECTRIC ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRIC POWER {Maximum}[W] | PUMP ELECTRIC POWER {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 12379738.55 | 3713921.57 | 6.85 | 01-JAN-06:05 | 2.06 | 2.06 | 77.79 | 0.05 |
February | 11196018.53 | 3358805.56 | 6.85 | 01-FEB-06:10 | 2.06 | 2.06 | 74.31 | 0.05 |
March | 12675668.56 | 3802700.57 | 6.85 | 01-MAR-06:05 | 2.06 | 2.06 | 72.10 | 0.05 |
April | 11960504.38 | 3588151.31 | 6.85 | 01-APR-05:10 | 2.06 | 2.06 | 74.70 | 0.05 |
May | 12527703.56 | 3758311.07 | 6.85 | 01-MAY-05:03 | 2.06 | 2.06 | 77.02 | 0.05 |
June | 12231773.55 | 3669532.07 | 6.85 | 01-JUN-05:03 | 2.06 | 2.06 | 69.11 | 0.05 |
July | 12256434.38 | 3676930.32 | 6.85 | 01-JUL-05:03 | 2.06 | 2.06 | 68.97 | 0.05 |
August | 12675668.56 | 3802700.57 | 6.85 | 01-AUG-05:03 | 2.06 | 2.06 | 70.68 | 0.05 |
September | 11960504.38 | 3588151.31 | 6.85 | 01-SEP-05:03 | 2.06 | 2.06 | 68.60 | 0.05 |
October | 12379738.55 | 3713921.57 | 6.85 | 01-OCT-05:10 | 2.06 | 2.06 | 67.93 | 0.05 |
November | 12059147.71 | 3617744.31 | 6.85 | 01-NOV-05:03 | 2.06 | 2.06 | 67.98 | 0.05 |
December | 12256434.38 | 3676930.32 | 6.85 | 01-DEC-06:05 | 2.06 | 2.06 | 72.11 | 0.05 |
Annual Sum or Average | 0.146559E+09 | 43967800.53 | ||||||
Minimum of Months | 11196018.53 | 3358805.56 | 6.85 | 2.06 | 2.06 | 67.93 | 0.05 | |
Maximum of Months | 12675668.56 | 3802700.57 | 6.85 | 2.06 | 2.06 | 77.79 | 0.05 |
Report: CondLoopDemandReportMonthly
For: SHWSYS1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum}[W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 703.92 | 4573.73 | 01-JAN-10:00 | 80.31 | 82.22 | 1300.70 | 6379.88 | 25-JAN-12:06 |
February | 684.81 | 4567.42 | 26-FEB-07:20 | 80.28 | 82.22 | 1311.03 | 6403.34 | 13-FEB-12:07 |
March | 587.66 | 4574.57 | 26-MAR-06:20 | 80.31 | 82.22 | 1420.74 | 6373.43 | 01-MAR-12:08 |
April | 700.67 | 4590.54 | 30-APR-07:10 | 80.38 | 82.22 | 1223.92 | 6209.99 | 03-APR-11:15 |
May | 702.02 | 4605.91 | 29-MAY-07:40 | 80.45 | 82.22 | 1237.80 | 6016.28 | 01-MAY-11:50 |
June | 688.22 | 4618.45 | 25-JUN-06:30 | 80.51 | 82.22 | 1202.13 | 5791.26 | 02-JUN-11:15 |
July | 846.23 | 4627.81 | 30-JUL-06:35 | 80.55 | 82.22 | 1017.87 | 5603.00 | 06-JUL-11:10 |
August | 714.90 | 4628.63 | 13-AUG-06:10 | 80.55 | 82.22 | 1149.40 | 5513.92 | 31-AUG-11:15 |
September | 794.74 | 4626.50 | 03-SEP-06:40 | 80.54 | 82.22 | 1061.31 | 5654.15 | 29-SEP-11:10 |
October | 783.80 | 4617.94 | 01-OCT-07:20 | 80.50 | 82.22 | 1127.38 | 5847.46 | 31-OCT-11:10 |
November | 752.47 | 4601.04 | 05-NOV-06:30 | 80.43 | 82.22 | 1231.36 | 6089.03 | 29-NOV-12:06 |
December | 746.49 | 4586.31 | 03-DEC-08:70 | 80.36 | 82.22 | 1193.22 | 6271.73 | 27-DEC-12:09 |
Annual Sum or Average | 725.74 | 1205.84 | ||||||
Minimum of Months | 587.66 | 4567.42 | 80.28 | 82.22 | 1017.87 | 5513.92 | ||
Maximum of Months | 846.23 | 4628.63 | 80.55 | 82.22 | 1420.74 | 6403.34 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 2.35 | 5.76 |
February | 3.40 | 6.36 |
March | 4.34 | 2.97 |
April | 4.09 | 2.40 |
May | 2.91 | 1.71 |
June | 2.60 | 1.50 |
July | 3.04 | 1.82 |
August | 1.96 | 1.55 |
September | 2.34 | 1.08 |
October | 3.86 | 4.31 |
November | 4.46 | 6.14 |
December | 3.67 | 3.74 |
Annual Sum or Average | 39.02 | 3.48 |
Minimum of Months | 1.96 | 1.08 |
Maximum of Months | 4.46 | 6.36 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.97 | 0.00 |
February | 0.70 | 0.00 |
March | 0.32 | 0.00 |
April | 0.06 | 0.00 |
May | 0.31 | 0.00 |
June | 0.30 | 0.00 |
July | 0.04 | 0.00 |
August | 0.08 | 0.00 |
September | 0.00 | 0.00 |
October | 0.11 | 0.00 |
November | 0.61 | 0.00 |
December | 1.24 | 0.00 |
Annual Sum or Average | 4.74 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 1.24 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.10 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.10 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.10 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FIRSTFLOOR_PLENUM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.07 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.06 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.12 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.07 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.50 | 0.35 |
February | 0.61 | 0.73 |
March | 2.01 | 1.53 |
April | 2.22 | 1.73 |
May | 2.55 | 2.55 |
June | 2.34 | 2.55 |
July | 1.14 | 2.00 |
August | 1.62 | 2.68 |
September | 1.80 | 2.92 |
October | 2.02 | 2.82 |
November | 1.94 | 1.65 |
December | 0.91 | 0.16 |
Annual Sum or Average | 19.65 | 2.08 |
Minimum of Months | 0.50 | 0.16 |
Maximum of Months | 2.55 | 2.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.34 | 1.79 |
February | 0.17 | 1.28 |
March | 0.26 | 0.00 |
April | 0.71 | 1.67 |
May | 2.49 | 2.88 |
June | 2.87 | 3.75 |
July | 2.66 | 3.70 |
August | 2.15 | 4.25 |
September | 2.43 | 4.22 |
October | 0.89 | 0.62 |
November | 0.33 | 0.78 |
December | 0.18 | 1.65 |
Annual Sum or Average | 15.49 | 3.25 |
Minimum of Months | 0.17 | 0.00 |
Maximum of Months | 2.87 | 4.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.59 | 0.28 |
February | 3.06 | 0.22 |
March | 2.38 | 0.02 |
April | 1.13 | 0.14 |
May | 0.84 | 0.64 |
June | 1.33 | 0.85 |
July | 1.48 | 0.84 |
August | 1.41 | 0.88 |
September | 1.11 | 1.02 |
October | 1.06 | 0.12 |
November | 2.42 | 0.09 |
December | 3.85 | 0.18 |
Annual Sum or Average | 23.66 | 0.35 |
Minimum of Months | 0.84 | 0.02 |
Maximum of Months | 3.85 | 1.02 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.15 | 0.22 |
February | 0.74 | 0.30 |
March | 0.12 | 0.28 |
April | 0.76 | 0.35 |
May | 2.00 | 0.30 |
June | 3.04 | 0.41 |
July | 4.63 | 0.36 |
August | 3.33 | 0.26 |
September | 1.04 | 0.29 |
October | 0.57 | 0.35 |
November | 0.44 | 0.31 |
December | 0.91 | 0.26 |
Annual Sum or Average | 18.72 | 0.32 |
Minimum of Months | 0.12 | 0.22 |
Maximum of Months | 4.63 | 0.41 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.15 | 0.31 |
February | 0.72 | 0.43 |
March | 0.15 | 0.35 |
April | 0.59 | 0.56 |
May | 1.97 | 0.44 |
June | 3.01 | 0.51 |
July | 4.56 | 0.51 |
August | 3.92 | 0.40 |
September | 1.95 | 0.63 |
October | 0.40 | 0.56 |
November | 0.39 | 0.44 |
December | 0.93 | 0.27 |
Annual Sum or Average | 19.73 | 0.47 |
Minimum of Months | 0.15 | 0.27 |
Maximum of Months | 4.56 | 0.63 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.59 | 0.25 |
February | 0.59 | 0.32 |
March | 0.12 | 0.28 |
April | 0.64 | 0.35 |
May | 1.79 | 0.30 |
June | 2.76 | 0.33 |
July | 3.44 | 0.28 |
August | 3.17 | 0.29 |
September | 1.07 | 0.30 |
October | 0.48 | 0.35 |
November | 0.41 | 0.33 |
December | 0.64 | 0.32 |
Annual Sum or Average | 15.74 | 0.30 |
Minimum of Months | 0.12 | 0.25 |
Maximum of Months | 3.44 | 0.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.74 | 0.16 |
February | 1.18 | 0.18 |
March | 0.34 | 0.16 |
April | 0.06 | 0.56 |
May | 0.03 | 0.00 |
June | 0.09 | 0.21 |
July | 0.23 | 0.42 |
August | 0.06 | 0.56 |
September | 0.27 | 0.07 |
October | 0.10 | 0.24 |
November | 0.04 | 0.56 |
December | 0.51 | 0.23 |
Annual Sum or Average | 4.64 | 0.20 |
Minimum of Months | 0.03 | 0.00 |
Maximum of Months | 1.74 | 0.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.69 | 0.30 |
February | 0.38 | 0.35 |
March | 0.10 | 0.35 |
April | 0.53 | 0.33 |
May | 1.07 | 0.18 |
June | 2.82 | 0.15 |
July | 5.01 | 0.16 |
August | 3.23 | 0.12 |
September | 2.36 | 0.11 |
October | 0.35 | 0.25 |
November | 0.22 | 0.35 |
December | 0.36 | 0.33 |
Annual Sum or Average | 17.12 | 0.17 |
Minimum of Months | 0.10 | 0.11 |
Maximum of Months | 5.01 | 0.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 3.56 | 5.70 |
February | 3.04 | 4.68 |
March | 2.73 | 5.37 |
April | 1.73 | 5.25 |
May | 2.80 | 4.29 |
June | 3.98 | 4.06 |
July | 5.69 | 3.28 |
August | 5.22 | 3.25 |
September | 4.66 | 3.60 |
October | 2.76 | 5.08 |
November | 1.90 | 3.91 |
December | 2.31 | 4.95 |
Annual Sum or Average | 40.39 | 4.25 |
Minimum of Months | 1.73 | 3.25 |
Maximum of Months | 5.69 | 5.70 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.44 | 0.33 |
February | 0.38 | 0.35 |
March | 0.10 | 0.35 |
April | 0.62 | 0.24 |
May | 1.81 | 0.18 |
June | 3.03 | 0.15 |
July | 4.98 | 0.15 |
August | 3.64 | 0.14 |
September | 2.84 | 0.10 |
October | 0.33 | 0.29 |
November | 0.22 | 0.35 |
December | 0.25 | 0.35 |
Annual Sum or Average | 18.65 | 0.16 |
Minimum of Months | 0.10 | 0.10 |
Maximum of Months | 4.98 | 0.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 1.11 | 0.12 |
February | 0.36 | 0.24 |
March | 0.07 | 0.00 |
April | 0.07 | 0.25 |
May | 0.62 | 0.52 |
June | 0.69 | 0.43 |
July | 0.32 | 0.32 |
August | 0.52 | 0.42 |
September | 0.65 | 0.69 |
October | 0.15 | 0.61 |
November | 0.19 | 0.29 |
December | 0.79 | 0.17 |
Annual Sum or Average | 5.56 | 0.34 |
Minimum of Months | 0.07 | 0.00 |
Maximum of Months | 1.11 | 0.69 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.43 | 0.28 |
February | 0.30 | 0.35 |
March | 0.10 | 0.35 |
April | 0.60 | 0.35 |
May | 2.52 | 0.29 |
June | 3.37 | 0.27 |
July | 4.40 | 0.17 |
August | 3.82 | 0.10 |
September | 2.06 | 0.22 |
October | 0.59 | 0.25 |
November | 0.35 | 0.35 |
December | 0.33 | 0.35 |
Annual Sum or Average | 18.89 | 0.22 |
Minimum of Months | 0.10 | 0.10 |
Maximum of Months | 4.40 | 0.35 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.29 | 0.40 |
February | 0.21 | 0.56 |
March | 0.06 | 0.56 |
April | 0.63 | 0.39 |
May | 2.30 | 0.32 |
June | 3.86 | 0.36 |
July | 5.27 | 0.22 |
August | 4.70 | 0.21 |
September | 3.04 | 0.30 |
October | 0.62 | 0.41 |
November | 0.35 | 0.56 |
December | 0.23 | 0.49 |
Annual Sum or Average | 21.56 | 0.29 |
Minimum of Months | 0.06 | 0.21 |
Maximum of Months | 5.27 | 0.56 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.20 | 0.31 |
February | 0.30 | 0.35 |
March | 0.10 | 0.35 |
April | 0.52 | 0.32 |
May | 2.34 | 0.23 |
June | 3.08 | 0.23 |
July | 4.56 | 0.16 |
August | 3.94 | 0.11 |
September | 2.15 | 0.18 |
October | 0.49 | 0.23 |
November | 0.26 | 0.35 |
December | 0.25 | 0.35 |
Annual Sum or Average | 18.19 | 0.19 |
Minimum of Months | 0.10 | 0.11 |
Maximum of Months | 4.56 | 0.35 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_BOT
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.231873E+11 | 0.207508E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.157226E+11 | 0.141861E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.137706E+11 | 0.690170E+10 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.106223E+11 | 0.331062E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.101386E+11 | 0.823798E+09 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.111985E+11 | 42826873.87 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.142213E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.181995E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.110903E+11 | 78435936.54 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.884038E+10 | 0.130165E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.129299E+11 | 0.916785E+10 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176658E+11 | 0.171154E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.167587E+12 | 0.736792E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.884038E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.231873E+11 | 0.207508E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.217573E+11 | 0.235071E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139110E+11 | 0.169124E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.103866E+11 | 0.109707E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.748280E+10 | 0.583462E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.701250E+10 | 0.205165E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.846365E+10 | 0.242598E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.115243E+11 | 379501.17 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.148117E+11 | 13441668.01 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.886913E+10 | 0.377544E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.793913E+10 | 0.338417E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.126515E+11 | 0.127692E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.172373E+11 | 0.207437E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.142047E+12 | 0.968076E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.701250E+10 | 379501.17 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.217573E+11 | 0.235071E+11 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PACU_VAV_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRIC ENERGY [J] | AIR SYSTEM GAS ENERGY [J] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.307649E+11 | 0.224949E+11 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.211241E+11 | 0.160927E+11 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153646E+11 | 0.101797E+11 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.104348E+11 | 0.532677E+10 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.848971E+10 | 0.184314E+10 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.912155E+10 | 0.200705E+09 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.122804E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.155159E+11 | 7835206.04 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.963303E+10 | 0.318940E+09 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.116763E+11 | 0.299095E+10 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.189281E+11 | 0.119801E+11 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.261124E+11 | 0.197150E+11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.189446E+12 | 0.911508E+11 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.848971E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.307649E+11 | 0.224949E+11 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_BOT
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.239482E+10 | 94095934.85 | 0.373652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212471E+10 | 0.111243E+10 | 0.246286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263595E+10 | 0.182161E+10 | 0.161364E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.254872E+10 | 0.682626E+10 | 0.888776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294345E+10 | 0.146092E+11 | 0.398335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.318092E+10 | 0.246482E+11 | 0.158720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337198E+10 | 0.401045E+11 | 0.591132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400585E+10 | 0.532474E+11 | 0.536563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.316198E+10 | 0.254376E+11 | 0.142315E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267838E+10 | 0.552696E+10 | 0.566426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232907E+10 | 0.158660E+10 | 0.174974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229570E+10 | 9782727.80 | 0.290595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336715E+11 | 0.175025E+12 | 0.147361E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212471E+10 | 9782727.80 | 0.536563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400585E+10 | 0.532474E+11 | 0.373652E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.226800E+10 | 82745291.73 | 0.382704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197638E+10 | 0.959865E+09 | 0.251924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233508E+10 | 0.153677E+10 | 0.163915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217820E+10 | 0.573644E+10 | 0.844013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242610E+10 | 0.122278E+11 | 0.299741E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267247E+10 | 0.202835E+11 | 0.672549E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294817E+10 | 0.331874E+11 | 93892490.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344217E+10 | 0.436408E+11 | 0.183176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266324E+10 | 0.207004E+11 | 0.116670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223645E+10 | 0.452357E+10 | 0.715343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207567E+10 | 0.134612E+10 | 0.204241E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213128E+10 | 9946435.13 | 0.316980E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293532E+11 | 0.144235E+12 | 0.152684E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197638E+10 | 9946435.13 | 93892490.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344217E+10 | 0.436408E+11 | 0.382704E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PACU_VAV_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.236905E+10 | 82813312.19 | 0.463671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203831E+10 | 0.986718E+09 | 0.316778E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222374E+10 | 0.155689E+10 | 0.208390E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209552E+10 | 0.603417E+10 | 0.109794E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231952E+10 | 0.130418E+11 | 0.418572E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250305E+10 | 0.216188E+11 | 0.109368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.279737E+10 | 0.358153E+11 | 0.292611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319532E+10 | 0.462283E+11 | 0.389963E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237018E+10 | 0.211309E+11 | 0.202902E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210081E+10 | 0.446526E+10 | 0.107131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197202E+10 | 0.135706E+10 | 0.261670E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212386E+10 | 8397926.64 | 0.397580E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281087E+11 | 0.152326E+12 | 0.194492E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197202E+10 | 8397926.64 | 0.292611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319532E+10 | 0.462283E+11 | 0.463671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_BOT
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.239482E+10 | 0.00 | 0.00 | 0.00 | 27975401.07 | 0.207645E+11 | 0.207508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212471E+10 | 0.00 | 0.00 | 0.00 | 0.318161E+09 | 0.132798E+11 | 0.141861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.263595E+10 | 0.00 | 0.00 | 0.00 | 0.519643E+09 | 0.106150E+11 | 0.690170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.254872E+10 | 0.00 | 0.00 | 0.00 | 0.183428E+10 | 0.623926E+10 | 0.331062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.294345E+10 | 0.00 | 0.00 | 0.00 | 0.387083E+10 | 0.332431E+10 | 0.823798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.318092E+10 | 0.00 | 0.00 | 0.00 | 0.646466E+10 | 0.155294E+10 | 42826873.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.337198E+10 | 0.00 | 0.00 | 0.00 | 0.102582E+11 | 0.591132E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.400585E+10 | 0.00 | 0.00 | 0.00 | 0.136571E+11 | 0.536563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.316198E+10 | 0.00 | 0.00 | 0.00 | 0.656793E+10 | 0.136040E+10 | 78435936.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.267838E+10 | 0.00 | 0.00 | 0.00 | 0.153905E+10 | 0.462294E+10 | 0.130165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232907E+10 | 0.00 | 0.00 | 0.00 | 0.437681E+09 | 0.101632E+11 | 0.916785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.229570E+10 | 0.00 | 0.00 | 0.00 | 2988829.16 | 0.153672E+11 | 0.171154E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.336715E+11 | 0.00 | 0.00 | 0.00 | 0.454986E+11 | 0.884172E+11 | 0.736792E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.212471E+10 | 0.00 | 0.00 | 0.00 | 2988829.16 | 0.536563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.400585E+10 | 0.00 | 0.00 | 0.00 | 0.136571E+11 | 0.207645E+11 | 0.207508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.226800E+10 | 0.00 | 0.00 | 0.00 | 24530281.35 | 0.194648E+11 | 0.235071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197638E+10 | 0.00 | 0.00 | 0.00 | 0.272186E+09 | 0.116624E+11 | 0.169124E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233508E+10 | 0.00 | 0.00 | 0.00 | 0.436598E+09 | 0.761489E+10 | 0.109707E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.217820E+10 | 0.00 | 0.00 | 0.00 | 0.153218E+10 | 0.377243E+10 | 0.583462E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.242610E+10 | 0.00 | 0.00 | 0.00 | 0.323032E+10 | 0.135609E+10 | 0.205165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.267247E+10 | 0.00 | 0.00 | 0.00 | 0.531271E+10 | 0.478471E+09 | 0.242598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.294817E+10 | 0.00 | 0.00 | 0.00 | 0.848258E+10 | 93588889.75 | 379501.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.344217E+10 | 0.00 | 0.00 | 0.00 | 0.111971E+11 | 0.172423E+09 | 13441668.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.266324E+10 | 0.00 | 0.00 | 0.00 | 0.534122E+10 | 0.864665E+09 | 0.377544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.223645E+10 | 0.00 | 0.00 | 0.00 | 0.125658E+10 | 0.444610E+10 | 0.338417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.207567E+10 | 0.00 | 0.00 | 0.00 | 0.367095E+09 | 0.102087E+11 | 0.127692E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213128E+10 | 0.00 | 0.00 | 0.00 | 3043232.73 | 0.151030E+11 | 0.207437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.293532E+11 | 0.00 | 0.00 | 0.00 | 0.374562E+11 | 0.752375E+11 | 0.968076E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.197638E+10 | 0.00 | 0.00 | 0.00 | 3043232.73 | 93588889.75 | 379501.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.344217E+10 | 0.00 | 0.00 | 0.00 | 0.111971E+11 | 0.194648E+11 | 0.235071E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PACU_VAV_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportAIR SYSTEM FAN ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRIC ENERGY [J] | AIR SYSTEM HEATING COIL GAS ENERGY [J] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRIC ENERGY [J] | AIR SYSTEM HUMIDIFIER GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRIC ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRIC ENERGY [J] | |
January | 0.236905E+10 | 0.00 | 0.00 | 0.00 | 24646745.35 | 0.283712E+11 | 0.224949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203831E+10 | 0.00 | 0.00 | 0.00 | 0.282107E+09 | 0.188037E+11 | 0.160927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222374E+10 | 0.00 | 0.00 | 0.00 | 0.445653E+09 | 0.126952E+11 | 0.101797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.209552E+10 | 0.00 | 0.00 | 0.00 | 0.162137E+10 | 0.671796E+10 | 0.532677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.231952E+10 | 0.00 | 0.00 | 0.00 | 0.345898E+10 | 0.271121E+10 | 0.184314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.250305E+10 | 0.00 | 0.00 | 0.00 | 0.568539E+10 | 0.933116E+09 | 0.200705E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.279737E+10 | 0.00 | 0.00 | 0.00 | 0.919038E+10 | 0.292611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.319532E+10 | 0.00 | 0.00 | 0.00 | 0.119368E+11 | 0.383695E+09 | 7835206.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237018E+10 | 0.00 | 0.00 | 0.00 | 0.548898E+10 | 0.177387E+10 | 0.318940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.210081E+10 | 0.00 | 0.00 | 0.00 | 0.125513E+10 | 0.832033E+10 | 0.299095E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.197202E+10 | 0.00 | 0.00 | 0.00 | 0.373195E+09 | 0.165829E+11 | 0.119801E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212386E+10 | 0.00 | 0.00 | 0.00 | 2568116.33 | 0.239859E+11 | 0.197150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281087E+11 | 0.00 | 0.00 | 0.00 | 0.397652E+11 | 0.121572E+12 | 0.911508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | |
Minimum of Months | 0.197202E+10 | 0.00 | 0.00 | 0.00 | 2568116.33 | 0.292611E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.319532E+10 | 0.00 | 0.00 | 0.00 | 0.119368E+11 | 0.283712E+11 | 0.224949E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178589E+11 | 0.00 | 0.00 | 14175871.70 | 0.00 | 0.419799E+09 | 0.124059E+11 | 0.00 | 0.75 |
February | 0.131723E+11 | 0.00 | 0.00 | 20950894.43 | 0.00 | 1447786.16 | 0.135266E+11 | 0.00 | 0.78 |
March | 0.122018E+11 | 0.00 | 0.00 | 33726430.64 | 0.00 | 0.00 | 0.174176E+11 | 0.00 | 0.88 |
April | 0.923441E+10 | 22422776.08 | 0.00 | 31808947.41 | 29780949.59 | 0.00 | 0.155889E+11 | 0.00 | 0.90 |
May | 0.582581E+10 | 41885139.88 | 0.00 | 40898900.78 | 28973679.52 | 0.00 | 0.186475E+11 | 0.00 | 1.07 |
June | 0.326783E+10 | 22358887.17 | 0.00 | 47903922.50 | 6802642.97 | 0.00 | 0.173440E+11 | 0.00 | 1.20 |
July | 0.169710E+10 | 0.595639E+09 | 0.00 | 44827997.53 | 0.128399E+09 | 0.00 | 0.114895E+11 | 0.00 | 1.13 |
August | 0.156590E+10 | 0.162506E+10 | 0.00 | 44141571.08 | 45522337.40 | 0.00 | 0.980565E+10 | 0.00 | 1.19 |
September | 0.338497E+10 | 74914716.28 | 0.00 | 45491735.61 | 48373713.56 | 0.00 | 0.156968E+11 | 0.00 | 1.15 |
October | 0.797542E+10 | 0.00 | 0.00 | 38467802.29 | 0.00 | 0.00 | 0.182329E+11 | 0.00 | 0.95 |
November | 0.106645E+11 | 0.00 | 0.00 | 29777778.20 | 17649037.65 | 0.00 | 0.165757E+11 | 0.00 | 0.81 |
December | 0.153200E+11 | 0.00 | 0.00 | 23008943.07 | 0.00 | 645906.31 | 0.147348E+11 | 0.00 | 0.74 |
Annual Sum or Average | 0.102169E+12 | 0.238228E+10 | 0.00 | 0.415181E+09 | 0.305502E+09 | 0.421893E+09 | 0.181466E+12 | 0.00 | 0.97 |
Minimum of Months | 0.156590E+10 | 0.00 | 0.00 | 14175871.70 | 0.00 | 0.00 | 0.980565E+10 | 0.00 | 0.74 |
Maximum of Months | 0.178589E+11 | 0.162506E+10 | 0.00 | 47903922.50 | 0.128399E+09 | 0.419799E+09 | 0.186475E+11 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.194991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.913591E+09 | 0.00 | 0.00 | 0.52 |
February | 0.165767E+11 | 0.00 | 0.00 | 113653.58 | 0.00 | 0.132164E+09 | 0.512638E+09 | 0.00 | 0.52 |
March | 0.156730E+11 | 0.00 | 0.00 | 1197569.39 | 0.00 | 27754507.74 | 0.250308E+10 | 0.00 | 0.56 |
April | 0.103756E+11 | 12113962.59 | 0.00 | 5703200.21 | 24598209.43 | 0.00 | 0.424651E+10 | 0.00 | 0.54 |
May | 0.605193E+10 | 2650600.72 | 0.00 | 14435002.84 | 20913183.78 | 0.00 | 0.751305E+10 | 0.00 | 0.60 |
June | 0.397914E+10 | 10436725.67 | 0.00 | 22140746.59 | 4124560.39 | 0.00 | 0.770106E+10 | 0.00 | 0.68 |
July | 0.234465E+10 | 0.315681E+09 | 0.00 | 23476421.56 | 79108047.55 | 0.00 | 0.556050E+10 | 0.00 | 0.66 |
August | 0.204562E+10 | 0.960091E+09 | 0.00 | 23374305.55 | 43806136.27 | 0.00 | 0.469663E+10 | 0.00 | 0.71 |
September | 0.443939E+10 | 24892330.27 | 0.00 | 18387577.65 | 31273230.13 | 0.00 | 0.589771E+10 | 0.00 | 0.64 |
October | 0.967660E+10 | 0.00 | 0.00 | 6779204.79 | 0.00 | 0.00 | 0.465595E+10 | 0.00 | 0.54 |
November | 0.157742E+11 | 0.00 | 0.00 | 364845.57 | 5581425.13 | 32731958.98 | 0.964177E+09 | 0.00 | 0.52 |
December | 0.191689E+11 | 0.00 | 0.00 | 8158.30 | 0.00 | 0.242673E+09 | 0.152075E+09 | 0.00 | 0.51 |
Annual Sum or Average | 0.125605E+12 | 0.132587E+10 | 0.00 | 0.115981E+09 | 0.209405E+09 | 0.134891E+10 | 0.444034E+11 | 0.00 | 0.58 |
Minimum of Months | 0.204562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
Maximum of Months | 0.194991E+11 | 0.960091E+09 | 0.00 | 23476421.56 | 79108047.55 | 0.913591E+09 | 0.770106E+10 | 0.00 | 0.71 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256355E+10 | 0.00 | 0.00 | 0.51 |
February | 0.147654E+11 | 0.00 | 0.00 | 9363.77 | 0.00 | 0.125450E+10 | 59145932.23 | 0.00 | 0.51 |
March | 0.157297E+11 | 0.00 | 0.00 | 458335.88 | 0.00 | 0.290376E+09 | 0.966726E+09 | 0.00 | 0.54 |
April | 0.110094E+11 | 0.00 | 0.00 | 4877290.30 | 1306442.15 | 71755382.94 | 0.306669E+10 | 0.00 | 0.53 |
May | 0.691992E+10 | 1923578.97 | 0.00 | 12059119.41 | 9481973.84 | 0.00 | 0.664889E+10 | 0.00 | 0.60 |
June | 0.382904E+10 | 720733.71 | 0.00 | 19694627.60 | 2416198.38 | 0.00 | 0.776808E+10 | 0.00 | 0.68 |
July | 0.213921E+10 | 0.246213E+09 | 0.00 | 21351070.41 | 38458356.77 | 0.00 | 0.561367E+10 | 0.00 | 0.68 |
August | 0.203991E+10 | 0.742872E+09 | 0.00 | 18979378.95 | 58495278.59 | 0.00 | 0.385186E+10 | 0.00 | 0.70 |
September | 0.492159E+10 | 1459477.98 | 0.00 | 12663881.08 | 13550466.48 | 0.00 | 0.424990E+10 | 0.00 | 0.60 |
October | 0.112364E+11 | 0.00 | 0.00 | 2861494.54 | 0.00 | 0.126051E+09 | 0.182883E+10 | 0.00 | 0.53 |
November | 0.145090E+11 | 0.00 | 0.00 | 0.00 | 4692427.11 | 0.712650E+09 | 0.00 | 0.00 | 0.51 |
December | 0.159386E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186002E+10 | 0.00 | 0.00 | 0.49 |
Annual Sum or Average | 0.119399E+12 | 0.993189E+09 | 0.00 | 92954561.95 | 0.128401E+09 | 0.687892E+10 | 0.340538E+11 | 0.00 | 0.57 |
Minimum of Months | 0.203991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
Maximum of Months | 0.163604E+11 | 0.742872E+09 | 0.00 | 21351070.41 | 58495278.59 | 0.256355E+10 | 0.776808E+10 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.158353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346058E+10 | 0.00 | 0.00 | 0.64 |
February | 0.189892E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238689E+10 | 0.00 | 0.00 | 0.65 |
March | 0.341802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110988E+10 | 0.00 | 0.00 | 0.69 |
April | 0.284295E+10 | 0.00 | 0.00 | 579081.88 | 348227.35 | 0.562746E+09 | 0.328352E+09 | 0.00 | 0.66 |
May | 0.230628E+10 | 3040108.18 | 0.00 | 2123111.86 | 0.00 | 0.122218E+09 | 0.108249E+10 | 0.00 | 0.74 |
June | 0.143492E+10 | 223778.03 | 0.00 | 3850307.50 | 644028.80 | 11798039.07 | 0.148286E+10 | 0.00 | 0.82 |
July | 0.805709E+09 | 71953461.02 | 0.00 | 4487510.19 | 9805018.21 | 0.00 | 0.117502E+10 | 0.00 | 0.84 |
August | 0.769820E+09 | 0.212636E+09 | 0.00 | 3426570.59 | 17141484.60 | 0.00 | 0.713328E+09 | 0.00 | 0.86 |
September | 0.172226E+10 | 359755.87 | 0.00 | 1879507.14 | 3611827.04 | 44582038.93 | 0.579943E+09 | 0.00 | 0.73 |
October | 0.274604E+10 | 0.00 | 0.00 | 141831.68 | 0.00 | 0.629953E+09 | 0.107537E+09 | 0.00 | 0.65 |
November | 0.224156E+10 | 0.00 | 0.00 | 0.00 | 1250749.20 | 0.181572E+10 | 0.00 | 0.00 | 0.64 |
December | 0.169956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304460E+10 | 0.00 | 0.00 | 0.62 |
Annual Sum or Average | 0.234696E+11 | 0.288213E+09 | 0.00 | 16487920.83 | 32801335.20 | 0.131890E+11 | 0.546953E+10 | 0.00 | 0.71 |
Minimum of Months | 0.769820E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
Maximum of Months | 0.341802E+10 | 0.212636E+09 | 0.00 | 4487510.19 | 17141484.60 | 0.346058E+10 | 0.148286E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.398630E+10 | 0.00 | 0.00 | 1.26 |
February | 0.258557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273143E+10 | 0.00 | 0.00 | 1.27 |
March | 0.439496E+10 | 0.00 | 0.00 | 16224.48 | 0.00 | 0.119726E+10 | 25106557.43 | 0.00 | 1.34 |
April | 0.344430E+10 | 0.00 | 0.00 | 825540.92 | 432012.91 | 0.528481E+09 | 0.680970E+09 | 0.00 | 1.30 |
May | 0.298620E+10 | 3021870.78 | 0.00 | 1732586.20 | 749705.34 | 0.168610E+09 | 0.112627E+10 | 0.00 | 1.40 |
June | 0.185010E+10 | 180499.40 | 0.00 | 3684753.00 | 798985.92 | 28885984.10 | 0.166414E+10 | 0.00 | 1.52 |
July | 0.111446E+10 | 60350310.18 | 0.00 | 3972910.23 | 18864033.79 | 0.00 | 0.113945E+10 | 0.00 | 1.48 |
August | 0.104559E+10 | 0.180472E+09 | 0.00 | 3185159.05 | 31006833.92 | 740259.77 | 0.727452E+09 | 0.00 | 1.58 |
September | 0.218907E+10 | 293134.41 | 0.00 | 1957587.64 | 4480853.91 | 38176387.80 | 0.686246E+09 | 0.00 | 1.40 |
October | 0.338659E+10 | 0.00 | 0.00 | 258759.36 | 0.00 | 0.720585E+09 | 0.218113E+09 | 0.00 | 1.28 |
November | 0.287303E+10 | 0.00 | 0.00 | 0.00 | 1551686.83 | 0.216045E+10 | 0.00 | 0.00 | 1.26 |
December | 0.245042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343521E+10 | 0.00 | 0.00 | 1.22 |
Annual Sum or Average | 0.305918E+11 | 0.244318E+09 | 0.00 | 15633520.87 | 57884112.62 | 0.149961E+11 | 0.626775E+10 | 0.00 | 1.36 |
Minimum of Months | 0.104559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 |
Maximum of Months | 0.439496E+10 | 0.180472E+09 | 0.00 | 3972910.23 | 31006833.92 | 0.398630E+10 | 0.166414E+10 | 0.00 | 1.58 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.396469E+10 | 0.00 | 0.00 | 260163.55 | 0.00 | 0.460690E+10 | 0.192818E+09 | 0.00 | 1.11 |
February | 0.381639E+10 | 0.00 | 0.00 | 1375964.67 | 0.00 | 0.288580E+10 | 0.868598E+09 | 0.00 | 1.15 |
March | 0.501063E+10 | 0.00 | 0.00 | 2479364.57 | 0.00 | 0.156542E+10 | 0.158477E+10 | 0.00 | 1.24 |
April | 0.421667E+10 | 602911.48 | 0.00 | 2813857.90 | 0.00 | 0.902379E+09 | 0.150908E+10 | 0.00 | 1.19 |
May | 0.416349E+10 | 5129174.11 | 0.00 | 2730316.94 | 134387.52 | 0.266916E+09 | 0.156255E+10 | 0.00 | 1.24 |
June | 0.317882E+10 | 256627.07 | 0.00 | 3231586.77 | 1115054.16 | 41842617.51 | 0.150505E+10 | 0.00 | 1.29 |
July | 0.178698E+10 | 95979737.76 | 0.00 | 4587319.33 | 23213305.71 | 0.00 | 0.130838E+10 | 0.00 | 1.28 |
August | 0.159889E+10 | 0.324924E+09 | 0.00 | 4202317.20 | 43529096.57 | 520092.32 | 0.866696E+09 | 0.00 | 1.42 |
September | 0.277321E+10 | 11409714.99 | 0.00 | 6285173.53 | 0.00 | 78985887.68 | 0.161143E+10 | 0.00 | 1.43 |
October | 0.399167E+10 | 0.00 | 0.00 | 3976844.44 | 0.00 | 0.899963E+09 | 0.168504E+10 | 0.00 | 1.25 |
November | 0.410936E+10 | 3388346.73 | 0.00 | 509031.29 | 22503.79 | 0.264065E+10 | 0.318729E+09 | 0.00 | 1.13 |
December | 0.373944E+10 | 0.00 | 0.00 | 652634.41 | 0.00 | 0.400329E+10 | 0.509399E+09 | 0.00 | 1.08 |
Annual Sum or Average | 0.423502E+11 | 0.441690E+09 | 0.00 | 33104574.61 | 68014347.76 | 0.178927E+11 | 0.135225E+11 | 0.00 | 1.24 |
Minimum of Months | 0.159889E+10 | 0.00 | 0.00 | 260163.55 | 0.00 | 0.00 | 0.192818E+09 | 0.00 | 1.08 |
Maximum of Months | 0.501063E+10 | 0.324924E+09 | 0.00 | 6285173.53 | 43529096.57 | 0.460690E+10 | 0.168504E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.236905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460206E+10 | 0.00 | 0.00 | 1.40 |
February | 0.277420E+10 | 0.00 | 0.00 | 17414.45 | 0.00 | 0.313888E+10 | 10010946.76 | 0.00 | 1.42 |
March | 0.454456E+10 | 0.00 | 0.00 | 278708.70 | 0.00 | 0.153898E+10 | 0.185581E+09 | 0.00 | 1.50 |
April | 0.387276E+10 | 418103.23 | 0.00 | 1125263.86 | 63157.46 | 0.784191E+09 | 0.543601E+09 | 0.00 | 1.46 |
May | 0.369959E+10 | 995366.75 | 0.00 | 2359797.17 | 3206154.29 | 0.241242E+09 | 0.921760E+09 | 0.00 | 1.61 |
June | 0.277788E+10 | 426797.30 | 0.00 | 2610488.57 | 890067.19 | 29702490.46 | 0.102244E+10 | 0.00 | 1.70 |
July | 0.151371E+10 | 0.108050E+09 | 0.00 | 3974581.69 | 11482017.18 | 0.00 | 0.102600E+10 | 0.00 | 1.72 |
August | 0.141171E+10 | 0.242087E+09 | 0.00 | 2482865.45 | 38187902.89 | 1210588.88 | 0.527427E+09 | 0.00 | 1.73 |
September | 0.260610E+10 | 1671421.95 | 0.00 | 2248278.00 | 3689311.91 | 63828634.95 | 0.597984E+09 | 0.00 | 1.59 |
October | 0.370632E+10 | 0.00 | 0.00 | 453944.98 | 0.00 | 0.884656E+09 | 0.248506E+09 | 0.00 | 1.44 |
November | 0.309455E+10 | 0.00 | 0.00 | 0.00 | 1728573.06 | 0.251273E+10 | 0.00 | 0.00 | 1.40 |
December | 0.246600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409057E+10 | 0.00 | 0.00 | 1.36 |
Annual Sum or Average | 0.348364E+11 | 0.353649E+09 | 0.00 | 15551342.86 | 59247183.97 | 0.178881E+11 | 0.508331E+10 | 0.00 | 1.53 |
Minimum of Months | 0.141171E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
Maximum of Months | 0.454456E+10 | 0.242087E+09 | 0.00 | 3974581.69 | 38187902.89 | 0.460206E+10 | 0.102600E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.143273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261770E+10 | 0.00 | 0.00 | 0.47 |
February | 0.169139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175164E+10 | 0.00 | 0.00 | 0.48 |
March | 0.278073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.820248E+09 | 0.00 | 0.00 | 0.50 |
April | 0.247050E+10 | 2036541.09 | 0.00 | 50311.75 | 3962519.16 | 0.414819E+09 | 21681131.05 | 0.00 | 0.49 |
May | 0.228220E+10 | 1574079.00 | 0.00 | 501306.24 | 7424665.30 | 26411685.26 | 0.315548E+09 | 0.00 | 0.54 |
June | 0.140664E+10 | 2453125.20 | 0.00 | 1997989.15 | 1054817.33 | 0.00 | 0.740395E+09 | 0.00 | 0.61 |
July | 0.750103E+09 | 74881820.77 | 0.00 | 2807551.96 | 22455889.53 | 0.00 | 0.681737E+09 | 0.00 | 0.61 |
August | 0.712839E+09 | 0.226313E+09 | 0.00 | 2466263.87 | 5794572.03 | 0.00 | 0.518389E+09 | 0.00 | 0.65 |
September | 0.155578E+10 | 7140714.45 | 0.00 | 1373958.02 | 7749218.43 | 0.00 | 0.461763E+09 | 0.00 | 0.58 |
October | 0.274110E+10 | 0.00 | 0.00 | 129177.39 | 0.00 | 0.114794E+09 | 88756672.59 | 0.00 | 0.50 |
November | 0.259200E+10 | 0.00 | 0.00 | 0.00 | 2348301.54 | 0.759635E+09 | 0.00 | 0.00 | 0.47 |
December | 0.188523E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199727E+10 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.223012E+11 | 0.314399E+09 | 0.00 | 9326558.37 | 50789983.33 | 0.850252E+10 | 0.282827E+10 | 0.00 | 0.53 |
Minimum of Months | 0.712839E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.278073E+10 | 0.226313E+09 | 0.00 | 2807551.96 | 22455889.53 | 0.261770E+10 | 0.740395E+09 | 0.00 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.206060E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334344E+10 | 0.00 | 0.00 | 0.99 |
February | 0.244198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215166E+10 | 0.00 | 0.00 | 1.00 |
March | 0.385205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.952337E+09 | 0.00 | 0.00 | 1.06 |
April | 0.324449E+10 | 2554427.58 | 0.00 | 287002.03 | 5286743.34 | 0.427741E+09 | 0.216181E+09 | 0.00 | 1.04 |
May | 0.303512E+10 | 1687147.20 | 0.00 | 639219.54 | 10094209.04 | 57708340.78 | 0.421873E+09 | 0.00 | 1.14 |
June | 0.196997E+10 | 2880088.41 | 0.00 | 2307845.28 | 1407324.05 | 2926844.46 | 0.901283E+09 | 0.00 | 1.26 |
July | 0.112769E+10 | 86629749.51 | 0.00 | 2647364.71 | 27956087.32 | 0.00 | 0.720147E+09 | 0.00 | 1.20 |
August | 0.101339E+10 | 0.233878E+09 | 0.00 | 2536464.13 | 13826731.80 | 0.00 | 0.608987E+09 | 0.00 | 1.32 |
September | 0.218765E+10 | 6399040.07 | 0.00 | 1553284.98 | 11415015.13 | 2436946.22 | 0.538217E+09 | 0.00 | 1.22 |
October | 0.349603E+10 | 0.00 | 0.00 | 277964.50 | 0.00 | 0.196812E+09 | 0.239292E+09 | 0.00 | 1.05 |
November | 0.339948E+10 | 0.00 | 0.00 | 0.00 | 3133074.45 | 0.107223E+10 | 0.00 | 0.00 | 0.99 |
December | 0.263235E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254763E+10 | 0.00 | 0.00 | 0.95 |
Annual Sum or Average | 0.304608E+11 | 0.334029E+09 | 0.00 | 10249145.17 | 73119185.13 | 0.107549E+11 | 0.364598E+10 | 0.00 | 1.10 |
Minimum of Months | 0.101339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.95 |
Maximum of Months | 0.385205E+10 | 0.233878E+09 | 0.00 | 2647364.71 | 27956087.32 | 0.334344E+10 | 0.901283E+09 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.955798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621299E+10 | 0.00 | 0.00 | 0.83 |
February | 0.214148E+10 | 0.00 | 0.00 | 80221.14 | 0.00 | 0.393350E+10 | 20096302.20 | 0.00 | 0.84 |
March | 0.318797E+10 | 0.00 | 0.00 | 185729.05 | 0.00 | 0.302187E+10 | 0.163281E+09 | 0.00 | 0.89 |
April | 0.318977E+10 | 6618838.93 | 0.00 | 331181.32 | 6938224.84 | 0.185996E+10 | 97691861.51 | 0.00 | 0.88 |
May | 0.348266E+10 | 4359384.37 | 0.00 | 315802.80 | 11296118.09 | 0.108825E+10 | 69779681.90 | 0.00 | 0.95 |
June | 0.301160E+10 | 4329263.93 | 0.00 | 551227.37 | 1866901.39 | 0.553457E+09 | 0.133095E+09 | 0.00 | 1.02 |
July | 0.187895E+10 | 0.131212E+09 | 0.00 | 1106222.30 | 46249841.39 | 0.204997E+09 | 0.268696E+09 | 0.00 | 0.97 |
August | 0.157355E+10 | 0.461790E+09 | 0.00 | 1715011.01 | 19048446.98 | 0.172025E+09 | 0.319854E+09 | 0.00 | 1.11 |
September | 0.259359E+10 | 35840103.03 | 0.00 | 3036128.17 | 1375462.73 | 0.436755E+09 | 0.607949E+09 | 0.00 | 1.11 |
October | 0.353085E+10 | 0.00 | 0.00 | 1480815.17 | 0.00 | 0.113883E+10 | 0.690227E+09 | 0.00 | 0.93 |
November | 0.260267E+10 | 5929134.87 | 0.00 | 40218.32 | 46273.93 | 0.332160E+10 | 7977415.87 | 0.00 | 0.83 |
December | 0.151172E+10 | 0.00 | 0.00 | 75238.61 | 0.00 | 0.527959E+10 | 80898477.89 | 0.00 | 0.80 |
Annual Sum or Average | 0.296606E+11 | 0.650079E+09 | 0.00 | 8917795.27 | 86821269.35 | 0.272238E+11 | 0.245955E+10 | 0.00 | 0.93 |
Minimum of Months | 0.955798E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172025E+09 | 0.00 | 0.00 | 0.80 |
Maximum of Months | 0.353085E+10 | 0.461790E+09 | 0.00 | 3036128.17 | 46249841.39 | 0.621299E+10 | 0.690227E+09 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.223976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376799E+10 | 0.00 | 0.00 | 1.10 |
February | 0.269721E+10 | 0.00 | 0.00 | 824.78 | 0.00 | 0.240752E+10 | 2099516.68 | 0.00 | 1.11 |
March | 0.413115E+10 | 0.00 | 0.00 | 47334.37 | 0.00 | 0.113801E+10 | 71902491.41 | 0.00 | 1.18 |
April | 0.360023E+10 | 2204320.49 | 0.00 | 309866.46 | 6741077.15 | 0.564992E+09 | 0.150790E+09 | 0.00 | 1.16 |
May | 0.357069E+10 | 781686.61 | 0.00 | 851456.38 | 12315836.15 | 58690697.89 | 0.282624E+09 | 0.00 | 1.28 |
June | 0.270509E+10 | 5857831.79 | 0.00 | 1279607.62 | 1342521.46 | 5347215.07 | 0.415882E+09 | 0.00 | 1.39 |
July | 0.144386E+10 | 0.130497E+09 | 0.00 | 2172972.55 | 23401512.03 | 0.00 | 0.593389E+09 | 0.00 | 1.36 |
August | 0.131862E+10 | 0.277368E+09 | 0.00 | 1507607.40 | 27023820.90 | 0.00 | 0.418288E+09 | 0.00 | 1.40 |
September | 0.261507E+10 | 10902907.64 | 0.00 | 1373562.76 | 9601288.64 | 3301911.96 | 0.364543E+09 | 0.00 | 1.35 |
October | 0.402261E+10 | 0.00 | 0.00 | 305444.30 | 0.00 | 0.211556E+09 | 0.146761E+09 | 0.00 | 1.18 |
November | 0.380193E+10 | 0.00 | 0.00 | 0.00 | 3483089.13 | 0.116934E+10 | 0.00 | 0.00 | 1.10 |
December | 0.289144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286724E+10 | 0.00 | 0.00 | 1.06 |
Annual Sum or Average | 0.350377E+11 | 0.427612E+09 | 0.00 | 7848676.62 | 83909145.47 | 0.121940E+11 | 0.244628E+10 | 0.00 | 1.22 |
Minimum of Months | 0.131862E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 |
Maximum of Months | 0.413115E+10 | 0.277368E+09 | 0.00 | 2172972.55 | 27023820.90 | 0.376799E+10 | 0.593389E+09 | 0.00 | 1.40 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278658E+10 | 0.00 | 0.00 | 0.60 |
February | 0.264159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156387E+10 | 0.00 | 0.00 | 0.60 |
March | 0.383725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608166E+09 | 0.00 | 0.00 | 0.64 |
April | 0.298706E+10 | 3412788.10 | 0.00 | 532987.36 | 6006772.85 | 0.228773E+09 | 0.324153E+09 | 0.00 | 0.61 |
May | 0.218984E+10 | 5721687.84 | 0.00 | 2190122.34 | 47237.43 | 7361441.01 | 0.103381E+10 | 0.00 | 0.68 |
June | 0.130731E+10 | 3225581.16 | 0.00 | 3942147.97 | 1007199.22 | 270353.71 | 0.142102E+10 | 0.00 | 0.77 |
July | 0.791228E+09 | 0.100426E+09 | 0.00 | 4293348.24 | 15135753.85 | 0.00 | 0.106764E+10 | 0.00 | 0.78 |
August | 0.795946E+09 | 0.292887E+09 | 0.00 | 3510111.08 | 3624268.77 | 0.00 | 0.745386E+09 | 0.00 | 0.82 |
September | 0.165482E+10 | 6175969.66 | 0.00 | 2183926.16 | 7636783.08 | 0.00 | 0.736181E+09 | 0.00 | 0.70 |
October | 0.307719E+10 | 0.00 | 0.00 | 253132.18 | 0.00 | 0.181494E+09 | 0.179457E+09 | 0.00 | 0.61 |
November | 0.305531E+10 | 0.00 | 0.00 | 0.00 | 1362959.08 | 0.104020E+10 | 0.00 | 0.00 | 0.60 |
December | 0.251388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226348E+10 | 0.00 | 0.00 | 0.59 |
Annual Sum or Average | 0.270495E+11 | 0.411849E+09 | 0.00 | 16905775.33 | 34820974.27 | 0.868020E+10 | 0.550765E+10 | 0.00 | 0.67 |
Minimum of Months | 0.791228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.59 |
Maximum of Months | 0.383725E+10 | 0.292887E+09 | 0.00 | 4293348.24 | 15135753.85 | 0.278658E+10 | 0.142102E+10 | 0.00 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.321047E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407585E+10 | 0.00 | 0.00 | 1.39 |
February | 0.385239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229488E+10 | 0.00 | 0.00 | 1.39 |
March | 0.558921E+10 | 0.00 | 0.00 | 62441.46 | 0.00 | 0.786432E+09 | 0.122320E+09 | 0.00 | 1.48 |
April | 0.436607E+10 | 2916528.30 | 0.00 | 750731.46 | 8780326.19 | 0.296451E+09 | 0.546334E+09 | 0.00 | 1.41 |
May | 0.378473E+10 | 2071552.52 | 0.00 | 1365918.21 | 6313761.50 | 22460155.24 | 0.846363E+09 | 0.00 | 1.51 |
June | 0.243432E+10 | 2794958.77 | 0.00 | 3006097.03 | 2138335.94 | 3433483.38 | 0.141538E+10 | 0.00 | 1.64 |
July | 0.150544E+10 | 80501101.25 | 0.00 | 3201303.24 | 39859001.92 | 0.00 | 0.990806E+09 | 0.00 | 1.55 |
August | 0.144895E+10 | 0.245912E+09 | 0.00 | 2704640.59 | 28909396.00 | 422813.40 | 0.691419E+09 | 0.00 | 1.68 |
September | 0.280370E+10 | 5132451.69 | 0.00 | 1768906.65 | 11808010.45 | 3243153.00 | 0.678331E+09 | 0.00 | 1.55 |
October | 0.442722E+10 | 0.00 | 0.00 | 335334.06 | 0.00 | 0.330311E+09 | 0.273890E+09 | 0.00 | 1.40 |
November | 0.434418E+10 | 0.00 | 0.00 | 0.00 | 1992288.64 | 0.164238E+10 | 0.00 | 0.00 | 1.39 |
December | 0.369221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329105E+10 | 0.00 | 0.00 | 1.35 |
Annual Sum or Average | 0.414589E+11 | 0.339329E+09 | 0.00 | 13195372.70 | 99801120.64 | 0.127469E+11 | 0.556484E+10 | 0.00 | 1.48 |
Minimum of Months | 0.144895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.35 |
Maximum of Months | 0.558921E+10 | 0.245912E+09 | 0.00 | 3201303.24 | 39859001.92 | 0.407585E+10 | 0.141538E+10 | 0.00 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.501080E+10 | 0.00 | 0.00 | 334721.95 | 0.00 | 0.398897E+10 | 0.312271E+09 | 0.00 | 1.12 |
February | 0.497208E+10 | 0.00 | 0.00 | 1737720.52 | 0.00 | 0.198827E+10 | 0.108051E+10 | 0.00 | 1.16 |
March | 0.577564E+10 | 0.00 | 0.00 | 2908353.56 | 0.00 | 0.107881E+10 | 0.177597E+10 | 0.00 | 1.26 |
April | 0.482282E+10 | 16225847.16 | 0.00 | 2606040.69 | 2884665.43 | 0.447036E+09 | 0.144063E+10 | 0.00 | 1.18 |
May | 0.455583E+10 | 9329308.89 | 0.00 | 2460512.34 | 1340912.26 | 25272702.17 | 0.131553E+10 | 0.00 | 1.23 |
June | 0.344386E+10 | 4233348.67 | 0.00 | 2766441.02 | 2084711.72 | 1230721.37 | 0.125376E+10 | 0.00 | 1.28 |
July | 0.209697E+10 | 0.144447E+09 | 0.00 | 3870578.81 | 32903249.86 | 0.00 | 0.101102E+10 | 0.00 | 1.24 |
August | 0.190063E+10 | 0.476393E+09 | 0.00 | 3424806.73 | 20214046.51 | 0.00 | 0.772077E+09 | 0.00 | 1.39 |
September | 0.324444E+10 | 36429603.37 | 0.00 | 5971675.29 | 774423.66 | 1913411.95 | 0.148318E+10 | 0.00 | 1.45 |
October | 0.471118E+10 | 0.00 | 0.00 | 4564703.98 | 0.00 | 0.356573E+09 | 0.191877E+10 | 0.00 | 1.26 |
November | 0.569161E+10 | 4392231.85 | 0.00 | 736775.83 | 0.00 | 0.152715E+10 | 0.462812E+09 | 0.00 | 1.14 |
December | 0.503085E+10 | 0.00 | 0.00 | 1075741.23 | 0.00 | 0.318107E+10 | 0.763682E+09 | 0.00 | 1.10 |
Annual Sum or Average | 0.512567E+11 | 0.691450E+09 | 0.00 | 32458071.94 | 60202009.46 | 0.125963E+11 | 0.135902E+11 | 0.00 | 1.24 |
Minimum of Months | 0.190063E+10 | 0.00 | 0.00 | 334721.95 | 0.00 | 0.00 | 0.312271E+09 | 0.00 | 1.10 |
Maximum of Months | 0.577564E+10 | 0.476393E+09 | 0.00 | 5971675.29 | 32903249.86 | 0.398897E+10 | 0.191877E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2020-06-03 19:40:53
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.342016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405452E+10 | 0.00 | 0.00 | 1.43 |
February | 0.408848E+10 | 0.00 | 0.00 | 19815.36 | 0.00 | 0.218617E+10 | 31510804.23 | 0.00 | 1.43 |
March | 0.553192E+10 | 0.00 | 0.00 | 285455.87 | 0.00 | 0.952979E+09 | 0.191008E+09 | 0.00 | 1.52 |
April | 0.449388E+10 | 6876582.70 | 0.00 | 937702.97 | 5978325.14 | 0.389108E+09 | 0.443651E+09 | 0.00 | 1.46 |
May | 0.409258E+10 | 409816.46 | 0.00 | 1911343.48 | 8192267.90 | 25266411.92 | 0.700844E+09 | 0.00 | 1.60 |
June | 0.304418E+10 | 7027602.58 | 0.00 | 2171062.93 | 1510320.75 | 2123551.06 | 0.794518E+09 | 0.00 | 1.70 |
July | 0.178117E+10 | 0.158126E+09 | 0.00 | 2962825.05 | 15321117.76 | 0.00 | 0.787046E+09 | 0.00 | 1.68 |
August | 0.169030E+10 | 0.351397E+09 | 0.00 | 1921460.83 | 21908854.60 | 0.00 | 0.454199E+09 | 0.00 | 1.73 |
September | 0.303726E+10 | 11143473.42 | 0.00 | 1974311.14 | 7927371.82 | 3927486.96 | 0.518339E+09 | 0.00 | 1.63 |
October | 0.458353E+10 | 0.00 | 0.00 | 487145.66 | 0.00 | 0.349408E+09 | 0.241321E+09 | 0.00 | 1.44 |
November | 0.450214E+10 | 0.00 | 0.00 | 0.00 | 2043791.67 | 0.163919E+10 | 0.00 | 0.00 | 1.43 |
December | 0.388614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327764E+10 | 0.00 | 0.00 | 1.39 |
Annual Sum or Average | 0.441517E+11 | 0.534981E+09 | 0.00 | 12671123.30 | 62882049.63 | 0.128803E+11 | 0.416244E+10 | 0.00 | 1.54 |
Minimum of Months | 0.169030E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.39 |
Maximum of Months | 0.553192E+10 | 0.351397E+09 | 0.00 | 2962825.05 | 21908854.60 | 0.405452E+10 | 0.794518E+09 | 0.00 | 1.73 |